FeaturesIncreased revenue with lower operating costs makes this intelligent switchgear the perfect choice.

From manual sectionalising and single phase protection, up to large scale DSA/SCADA controlled electricity distribution networks and substations, you have the solution for your every overhead medium-voltage need.

Light-weight SolutionsReduced purchasing, installation and operating costs, with intelligent solid-dielectric switchgear.

Offering excellent solid-dielectric insulation in a cost effective solution, U-Series Automatic Circuit Reclosers provide the latest technology in vacuum interrupters, encased in an hydrophobic epoxy resin moulding.

The switching mechanism and switchgear microelectronics are enclosed in a 316 stainless steel tank.

Manual or Automated LBSEasy installation with the choice of manual switching or complete automation.

RL-Series Load Break Switches/Sectionalisers provide a simple low cost solution for your electricity distribution network.

Contained in a hard wearing, SF6 gas-filled, 316 Stainless Steel enclosure is the latest in arc quenching technology Extremely short arcing times (within half a cycle) plus tulip-type contacts with arc-resistant (Cu-W) material ensure a long switching life and extended short circuit making capability.

Current and Voltage transformers molded into the I-side terminal allow easy monitoring for your overhead voltage network, and with optional voltage measurement on the X-side terminal, you have full automation capabilities for your electricity distribution network or substation.

A mechanical lockout and highly visible ON/OFF indicator provide instant visual indication of the switchgear state.

Manual operation is possible using a hookstick, and an innovative design means the switch will trip or close quickly, and safely no mater how fast or slow the switch arm is moved.

The RL-Series LBS is available in bare terminal or fully insulated bushing arrangement, and 15kV, 27kV or 38kVmodels. (rated continuous current - 630A)

N-Series ACR15kV, 27 � kV and 38 kV options316 grade stainless steel tank �Fully insulated bushing arrangement �Latest technology vacuum arc interruption �800A continuous current �850A emergency current (8 hours) �Exceptiona � l reliability and service

U-Series ACR15kV and 27 kV options �316 grade stainless steel tank �Latest technology in solid dielectric and �vacuum arc interruptionI � -terminal current & voltage measurementOptional � X-terminal voltage measurementMechanical lockout �630A continuous rated current �

W-Series ACR24 kV phase to ground �316 grade stainless steel tank �Latest technology in solid dielectric and �vacuum arc interruptionSingle phase applications �SWER (Single Wire Earth Return) �applications400A continuous rated current �

RL-Series Sectionaliser15kV, 27 kV and 38kV options �316 grade stainless steel tank �Bare terminal or fully insulated bushing �arrangementLatest technology in SF � 6 arc interruptionChoice of manual or automated operation �630A continuous rated current �

Advanced Monitoring & ControlThe N-Series, U-Series and W-Series automatic circuit reclosers and RL-Series sectionalisers are all compatible with the latest ADVC Controller Range and WSOS 5 Software.

Combining switchgear reliability and flexibility with powerful monitoring and analysis tools means you have your medium voltage electricity distribution challenges under control.

Single Phase SolutionsAutomated protection for single phase or SWER (Single Wire Earth Return) Applications.

Using the latest technology in solid-dielectric insulation and vacuum arc interruption, the W-Series Single Phase ACR provides automation and remote control on one phase.

Housed in a 316 Stainless Steel tank, and including features such as manual trip, highly visible external ON/OFF indicators, the W-Series is ideal for any single phase requirement.

Available as a 24 kV model with a rated continuous current of 400A.

What's in a Range?Substation Solutions �

Feeder Solutions �

SWER Applications �

Load Break Switches/ Sectionalisers �

Single and 3-Phase �

Loop Automation �

Automatic Circuit Reclosers & Sectionalisers

Increased revenue with reduced costs.

A comprehensive range of Medium Voltage Overhead Switchgear gives you complete control of your electricity distribution network with minimal maintenance. Make the Switch!

Low Maintenance up to 38kV

Reduce lost revenue and operating costs, and defer capital works by employing the latest Automatic Circuit Recloser technology.

N-Series Automatic Circuit Reclosers combine state-of-the-art vacuum arc interruption with integrated voltage and current measurement. These features are encased in a fully welded and sealed 316 stainless steel enclosure filled with insulating SF6 gas.

Intelligent Switching

Load and source side voltage measurement and current measurement built in to the N-Series Reclosers, means you can be sure your network is making the right switching decisions in just fractions of a second.

The result is an Automatic Circuit Recloser that provides quick response to faults on your overhead medium voltage distribution network or substation, while reducing maintenance and helping keep outages to a minimum.

The N-Series is available in 15kV, 27kV, & 38kV up to 800A continuous current.

All this ensures you have the latest protection technology in an highly reliable and low maintenance Automatic Circuit Recloser.

Available in 15kV and 27kV models, the U-Series has a rated continuous current of 630A.

Switchgear Solutions

Page 3: ADVC2 Launch Section G Switchgear Brochure

Switchgear Comparison TableN-SERIES U-SERIES RL-SERIES W-SERIES

15kV12.5 kA

27kV12.5kA

38kV12.5kA

38kV16kA

15kV12.5kA

27kV12.5kA

15kV12.5 / 16kA

27kV12.5 / 16kA

38kV 12.5 / 16kA

RATINGS

Rated Maximum Voltage 15.5kV 27kV 38kV 38kV 15.5kV 27kV 15.5kV 27kV 38kV 24kV

Rated Nominal Voltage (phase to ground) 21kV

Rated Continuous Current 800A 800A 800A 800A 630A 630A 630A 630A 630A 400A

Emergency Current (8 hours) 850A 850A 850A 850A

Fault Make Capacity (RMS) 12.5kA 12.5kA 12.5kA 16kA 12.5kA 12.5kA 12.5 / 16kA 12.5 / 16kA 12.5 / 16kA 6kA

Fault Make Capacity (Peak) 31.5kA 31.5kA 31.5kA 40kA 31.5kA 31.5kA 31.5 / 40kA 31.5 / 40kA 31.5 / 40kA 15kA

Power Operating Time (Close/Open) 0.1/0.05s 0.1/0.05s 0.1/0.05s 0.1/0.05s 0.1/0.05s 0.1/0.05s < 2s < 2s < 2s 0.1/0.05s

Mechanical Operations 10,000 10,000 10,000 10,000 10,000 10,000 3000 3000 3000 10,000

Rated full load operations 10,000 10,000 10,000 10,000 10,000 10,000 600 600 400 10,000

Short time current 12.5kA 12.5kA 12.5kA 16kA 12.5kA 12.5kA 12.5 / 16kA 12.5 / 16kA 12.5 / 16kA 6kABREAKING CAPACITY

Mainly Active (0.7pf) 800A 800A 800A 800A 630A 630A 630A 630A 630A 400A

Fault break capacity 12.5kA 12.5kA 12.5kA 16kA 12.5kA 12.5kA 6kA

Cable charging 25A 40A 40A 40A 25A 25A 25A 25A 25A 25A

Line Charging 5A

Transformer magnetising 22A 22A 22A 22A 22A 22A 22A 22A 22A 22A

Capacitor bank 250ALIGHTNING IMPULSE WITHSTAND LEVEL

Phase to Phase 125kV 150kV 170kV

Phase to Earth 110kV 150kV 170kV 170kV 110kV 125kV 125kV 150kV 170kV 125kV

Across Interrupter 110kV 150kV 170kV 170kV 110kV 125kV 145kV 170kV 200kV 125kV

On Loss of SF6 60kV 70kV 70kV 70kV 50kV 70kV 70kVPOWER FREQUENCY WITHSTAND VOLTAGE

Phase to Earth 50kV 60kV 70kV 70kV 50kV 60kV 40kV 60kV 70kV 60kV

Across Interrupter 50kV 60kV 70kV 70kV 50kV 60kV 50kV 60kV 80kV 60kVSERVICE CONDITIONS

Ambient Temperaturea (ºC) -40 to 50 -40 to 50 -40 to 50 -40 to 50 -40 to 50 -40 to 50 -30 to 50 -30 to 50 -30 to 50 -30 to 50

Ambient Temperaturea (ºF) -40 to 122 -40 to 122 -40 to 122 -40 to 122 -40 to 122 -40 to 122 -22 to 122 -22 to 122 -22 to 122 -22 to 122

Radiation (Max) 1.1kW/m2 1.1kW/m2 1.1kW/m2 1.1kW/m2 1.1kW/m2 1.1kW/m2 1.1kW/m2 1.1kW/m2 1.1kW/m2 1.1kW/m2

Humidity 0 to 100% 0 to 100% 0 to 100% 0 to 100% 0 to 100% 0 to 100% 0 to 100% 0 to 100% 0 to 100% 0 to 100%

Altitude meters (Max)b 3000 3000 3000 3000 3000 3000 3000 3000 3000 3000

Altitude feet (Max)b 9840 9840 9840 9840 9840 9840 9840 9840 9840 9840NET WEIGHTS

Circuit breaker with pole mount bracket (kg/lbs) 249 / 549 249 / 549 249 / 549 249 / 549 146 / 322 146 / 322 128 / 282 128 / 282 128 / 282 75 / 165

Control cubicle with control cable (kg / lbs) 41 / 90 41 / 90 41 / 90 41 / 90 41 / 90 41 / 90 41 / 90 41 / 90 41 / 90 41 / 90

Gross weight of crate (kg / lbs) 404 / 891 404 / 891 404 / 891 404 / 891 263 / 580 263 / 580 285 / 628 285 / 628 285 / 628 196 / 432

External VT (kg / lbs) (N series Only) 60 / 132 60 / 132 60 / 132 60 / 132 60 / 132 60 / 132 60 / 132 60 / 132 60 / 132 60 / 132CRATE DIMENSIONS

Width (mm / in) 1160 / 45.7 1160 / 45.7 1160 / 45.7 1160 / 45.7 960 / 37.8 960 / 37.8 1200 / 47.2 1200 / 47.2 1200 / 47.2 1150 / 45.3

Depth (mm / in) 730 / 28.7 730 / 28.7 730 / 28.7 730 / 28.7 1020 / 40.2 1020 / 40.2 1150 / 45.3 1150 / 45.3 1150 / 45.3 1150 / 45.3

Height (mm / in) 1640 64.6 1640 64.6 1640 64.6 1640 64.6 1160 / 45.7 1160 / 45.7 755 / 29.7 755 / 29.7 755 / 29.7 570 / 22.4Option when cubicle battery heater is fitted (-10a. ºC to 50ºC {-14ºF to 122ºF} without heater)For altitudes above 1000m (3280 feet), derate in accordance with ANSI C37.60b.

08/2008 AD

C-1

01?-

NI

Corporate office & factory80 Schneider Rd, Eagle Farm, Qld 4009 Tel: +61 7 3635 7500Fax: +61 7 3635 7560

e-mail: [email protected]://www.nulec.com.au

USA officeNu-Lec LLCc/- Square D services2979 Pacific DriveSuite ENorcross, GA 30071USA

e-mail: [email protected]://www.nulec.com

As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication.

Nu-Lec Industries

Locked Bag 10, Eagle Farm Business Centre, Qld 4009