Size 1 and 2 Starter
Product DescriptionSetting the Standard in MotorControlCutler-Hammer® Advantage motor starters from Eaton’s electrical busi- ness have extended operating life in a physical space requirement one half the size of conventional motor starters.
Offering motor overcurrent protection accurate to 2% at maximum FLC, Advantage also maintains constant coil power regardless of varying con- trol circuit conditions, eliminating coil burnout, contact chatter and welding due to low voltage of fluttering control signals.
Advantage is designed with a full com- plement of features that make it the most versatile motor starter in the industry. Multifunction overload pro-
sensing monitoring, an energy- balanced contact closure system that increased life by decreasing electrical and mechanical wear and an intelli- gent coil controller optimizing the con- tact closing process based on varying control circuit conditions. Coordinat- ing these breakthroughs to provide enhanced motor control performance is concentrated in the SURE chip.
Advantage uses the right combination of brains and brawn in effecting a motor start. The power circuit of the contactor employs heavy-duty silver alloy contacts scientifically designed for long life. The addition of a uniquely developed application-specific micro- processor chip regulates power sup- plied to the operating coil. The regulated closing profile is tailored to existing control circuit conditions. This results in an energy balanced system which reduces armature/magnet crash and contact bounce, extending mechanical and electrical life.
Improved Protection and MotorUtilizationThe motor circuit monitoring and over- load protection functions of Advan- tage starters are provided by three current sensors closely monitored by the microprocessor. This sensor/ microprocessor combination yields a protection scheme closely paralleling
Instructional Leaflets
that of the motor heating damage boundary expressed in terms of cur- rent and time. Accurate to 2% of full scale, Advantage allows full utilization of motor capability without motor damage or nuisance tripping.
No Heaters, Small Size Advantage starters eliminate the need for costly heater elements andtheir associated installation expense.Standard overload protection func- tions include phase loss and unbal- ance protection, selectable trip class, automatic/manual reset and ground current protection.
Built-In Communications Capabilities Provide Two-Way ControlAdvantage also offers low cost commu- nication capability. ON/OFF commands, status and motor data can be linked to automated control systems without the addition of costly sensors, I/O modules and transducers, in a language compat- ible with many computer-based soft- ware systems in use today.
Protected by 22 patents and proven in many years of operating experience in harsh industrial applications, Advan- tage motor starters and contactors offer the user unprecedented value at a price competitive with traditional devices.
tection options provide application flexibility while reducing inventory. Communication capability extends benefits, allowing Advantage to be interactively linked to higher order control systems for monitoring, troubleshooting and control.
Technological advances incorporated in the Advantage design, such as pre- start diagnostics, increased accuracy and the ability to communicate with other systems, are benefits not real- ized in traditional motor starters.
BenefitsAdvantage BreakthroughsTo achieve the level of benefits envi- sioned for Advantage controls at a competitive price, it was discovered early in the development process that simply improving existing design con- cepts would fall short of the mark. A new approach involving a higher level of technology was required. The result was the incorporation of three techni- cal breakthroughs — new current
17401 Sizes 1, 2 Non-reversing Contactors and Starters17403 Sizes 3, 4 Non-reversing Contactors and Starters17405 Sizes 5, 6 Non-reversing Contactors and Starters17482 Sizes 1, 2 Reversing Contactors and Starters17484B Sizes 3, 4 Reversing Contactors and Starters17486 Sizes 5, 6 Reversing Contactors and Starters17456 Sizes 1, 2 Contactor Overload Combo17457 Sizes 3, 4 Contactor Overload Combo17604 Sizes 5, 6 Contactor Overload Combo17595 Sizes 1, 2 Reversing Contactors and Starters with status-only ACM17596 Sizes 3, 4 Reversing Contactors and Starters with status-only ACM17597 Sizes 5, 6 Reversing Contactors and Starters with status-only ACM17598 Sizes 1, 2 Two-Speed Two-Winding Starters with status-only ACM17599 Sizes 3, 4 Two-Speed Two-Winding Starters with status-only ACM17600 Sizes 5, 6 Two-Speed Two-Winding Starters with status-only ACM17601 Sizes 1, 2 Two-Speed One-Winding Starters with status-only ACM17602 Sizes 3, 4 Two-Speed One-Winding Starters with status-only ACM17603 Sizes 5, 6 Two-Speed One-Winding Starters with status-only ACM
NEMA Contactors & StartersAdvantageContactors — Non-reversing and Reversing
A-111March 2007
CA08102001K For more information visit: www.EatonElectrical.ca
ContentsDescription Page
Product Family OverviewProduct Description . . . . . . A-110Benefits . . . . . . . . . . . . . . . . A-110
Contactors — Non-reversing and Reversing
Product Description . . . . . . A-111Features . . . . . . . . . . . . . . . A-111Product Selection . . . . . . . . A-111
Technical Data . . . . . . . . . . . . . A-116Accessories and Field
Modification Kits . . . . . . . . . A-121Renewal Parts . . . . . . . . . . . . A-123Control Modules . . . . . . . . . . . A-124Dimensions . . . . . . . . . . . . . . . A-126Wiring Diagrams . . . . . . . . . . . A-132
Product SelectionWhen Ordering Specify■ Non-reversing Catalogue Number
as specified in table below.
Size 3 and 4 Starter
■ Reversing Catalogue Number as specified in table below.
Product DescriptionCatalogue Number W201 — Non- reversing Contactors
Catalogue Number W211 — HorizontalReversing Contactors (shown above)— long axis horizontal
Catalogue Number W251 — VerticalReversing Contactors (not illustrated)— long axis vertical
Features■ Small physical size■ Brownout protection■ Communications capability■ Long electrical life■ Higher contact force
A
Table A-209. Advantage Contactors — 3-Pole Non-reversing and Reversing — NEMA Sizes 1 – 6NEMA Size
MotorVoltage
Max. hp
Continuous Amperes (Enclosed)
CoilVoltage/Hz
Non-reversing Reversing (Horizontal) Reversing (Vertical)CatalogueNumber
Price CatalogueNumber
Price CatalogueNumber
Price
1 200230460575
7-1/27-1/2
1010
27 120/60110/50
W201K1CF W201K1CN
W211K1CF W211K1CN
W251K1CF W251K1CN
2 200230460575
10152525
45 120/60110/50
W201K2CF W201K2CN
W211K2CF W211K2CN
W251K2CF W251K2CN
3 200230460575
25305050
90 120/60110/50
W201K3CF W201K3CN
W211K3CF W211K3CN
W251K3CF W251K3CN
4 200230460575
4050
100100
135 120/60110/50
W201K4CF W201K4CN
W211K4CF W211K4CN
W251K4CF W251K4CN
5 200230460575
75100200200
270 120/60110/50
W201K5CF W201K5CN
W211K5CF W211K5CN
W251K5CF W251K5CN
6 200230460575
150200400400
540 120/60110/50
W201K6CF W201K6CN
W211K6CF W211K6CN
W251K6CF W251K6CN
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . MC7
Description Catalogue Number Suffix
Omit Class II Ground-CurrentProtection
Y7
Omit Phase-Loss Protection Y4Omit both Class II Ground-Current Protection and Phase-Loss Protection
Y4Y7
A
ContentsDescription Page
Product Family OverviewProduct Description . . . . . . . A-110Benefits. . . . . . . . . . . . . . . . . A-110
Starters — Non-reversing and Reversing
Product Description . . . . . . . A-112Features . . . . . . . . . . . . . . . . A-112Technical Data . . . . . . . . . . . A-112Options . . . . . . . . . . . . . . . . . A-112Product Selection . . . . . . . . A-113
Technical Data. . . . . . . . . . . . . . A-116Accessories and Field
Modification Kits . . . . . . . . . . A-121Renewal Parts . . . . . . . . . . . . . A-123Control Modules . . . . . . . . . . . . A-124Dimensions . . . . . . . . . . . . . . . . A-126Wiring Diagrams. . . . . . . . . . . . A-133
Size 5 and 6 Starter
Product DescriptionCatalogue Number W200 — Non- reversing Starters (shown above)
Catalogue Number W210 — Horizontal Reversing Starters — long axis horizontal.
Catalogue Number W250 — VerticalReversing Starters (not illustrated) — long axis vertical.
FeaturesStarter■ Small physical size■ Brownout protection■ Communications capability■ Minimized bounce times■ Higher contact force■ Common auxiliary contacts
Motor Protection■ Heaters not required — selectable
settings■ Overload protection — accuracy 2%■ Phase loss and phase unbalance
protection■ Ground current protection
OL Protection Settings■ Selectable automatic/manual reset■ Selectable trip class — 10, 20, 30 or
no protection (disables overload)■ Selectable trip current
Technical DataTable A-210. Motor FLA RangesNEMA Size
1.15 to 1.25Service Factor
1.0 ServiceFactor
1 G)
123456
.47 – 3.813.15 – 27.03.15 – 45.09.90 – 90.09.90 – 13538.3 – 27038.3 – 540
.51 – 4.143.43 – 27.03.43 – 45.010.8 – 90.010.8 – 13541.7 – 27041.7 – 540
G) For motor full load current (FLA) range of.47A – 3.81A with a 1.15 to 1.25 service factor and for motor hp range of 1/4 hp to2 hp at 460V.
OptionsTable A-211. Optional Features
NEMA Contactors & StartersAdvantageStarters — Non-reversing and Reversing
A-113March 2007
CA08102001K For more information visit: www.EatonElectrical.ca
Product SelectionWhen Ordering Specify■ Non-reversing Catalogue Number
as specified in table below.■ Reversing Catalogue Number as
specified in table below. A Table A-212. Advantage Starters — 3-Pole Non-reversing and Reversing — Wired for Separate Control — Heaters Not Required — NEMA Sizes 1 – 6NEMA Size
MotorVoltage
Max. hp
Continuous Amperes (Enclosed)
CoilVoltage/Hz
Non-reversing Reversing (Horizontal) Reversing (Vertical)CatalogueNumber
Price CatalogueNumber
Price CatalogueNumber
Price
1 G) 200230460575
1122
27 120/60110/50
W200MLCFC W200MLCNC
W210MLCFC W210MLCNC
W250MLCFC W250MLCNC
1 200230460575
7-1/27-1/2
1010
27 120/60110/50
W200M1CFC W200M1CNC
W210M1CFC W210M1CNC
W250M1CFC W250M1CNC
2 200230460575
10152525
45 120/60110/50
W200M2CFC W200M2CNC
W210M2CFC W210M2CNC
W250M2CFC W250M2CNC
3 200230460575
25305050
90 120/60110/50
W200M3CFC W200M3CNC
W210M3CFC W210M3CNC
W250M3CFC W250M3CNC
4 200230460575
4050
100100
135 120/60110/50
W200M4CFC W200M4CNC
W210M4CFC W210M4CNC
W250M4CFC W250M4CNC
5 200230460575
75100200200
270 120/60110/50
W200M5CFC W200M5CNC
W210M5CFC W210M5CNC
W250M5CFC W250M5CNC
6 200230460575
150200400400
540 120/60110/50
W200M6CFC W200M6CNC
W210M6CFC W210M6CNC
W250M6CFC W250M6CNC
G) For motor full load current (FLA) range of .47A – 3.81A with a 1.15 to 1.25 service factor and for motor hp range of 1/4 hp to 2 hp at 460V.
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . MC7
1 G) 200230460575
1122
1122
27 120/60110/50
W960MLCFCM3W960MLCNCM3
1 200230460575
7-1/27-1/2
1010
557-1/27-1/2
27 120/60110/50
W960M1CFCM3W960M1CNCM3
2 200230460575
10152525
7-1/2102020
45 120/60110/50
W960M2CFCM3W960M2CNCM3
3 200230460575
25305050
20254040
90 120/60110/50
W960M3CFCM3W960M3CNCM3
4 200230460575
4050
100100
30407575
135 120/60110/50
W960M4CFCM3W960M4CNCM3
5 200230460575
75100200200
6075
150150
270 120/60110/50
W960M5CFCM3W960M5CNCM3
6 200230460575
150200400400
100150300300
540 120/60110/50
W960M6CFCM3W960M6CNCM3
A
ContentsDescription Page
Product Family OverviewProduct Description . . . . . . . A-110Benefits. . . . . . . . . . . . . . . . . A-110
Starters — Non-reversingTwo-Speed
Product Selection . . . . . . . . A-114Technical Data. . . . . . . . . . . . . . A-116Accessories and Field
Modification Kits . . . . . . . . . . A-121Renewal Parts . . . . . . . . . . . . . A-123Control Modules . . . . . . . . . . . . A-124Dimensions . . . . . . . . . . . . . . . . A-126
Product SelectionWhen Ordering Specify■ Catalogue Number as shown in
table below.
Table A-213. Two-Speed Advantage Starters — Wired for Separate Control — Heaters Not Required — NEMA Sizes 1 – 6NEMA Size
MotorVoltage
Max. Horsepower Continuous Amperes (Enclosed)
Coil Voltage/ Hz
Open Type (Horizontal)Constant or Variable Torque
Constant hp
CatalogueNumber
Price
For Separate (2) Winding Type Motors — Wye Wye
G) For motor full load current (FLA) range of .47A – 3.81A with a 1.15 to 1.25 service factor and for motor hp range of 1/4 hp to 2 hp at 460V.
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . MC7
NEMA Size
MotorVoltage
Max. Horsepower Continuous Amperes
Coil Voltage/
Open Type (Horizontal)Constant or Variable Torque
Constant hp
CatalogueNumber
Price
NEMA Contactors & StartersAdvantageStarters — Non-reversing, Two-Speed
A-6March 2007
CA08102001K For more information visit: www.EatonElectrical.ca
Table A-213. Two-Speed Advantage Starters — Wired for Separate Control — Heaters Not Required — NEMA Sizes 1– 6 (Continued)
For Single Winding Type Motors Constant Horsepower A
1 G) 200230460575
— 1122
27 120/60110/50
W970MLCFCM3W970MLCNCM3
1 200230460575
— 557-1/27-1/2
27 120/60110/50
W970M1CFCM3W970M1CNCM3
2 200230460575
— 7-1/2102020
45 120/60110/50
W970M2CFCM3W970M2CNCM3
3 200230460575
— 20254040
90 120/60110/50
W970M3CFCM3W970M3CNCM3
4 200230460575
— 30407575
135 120/60110/50
W970M4CFCM3W970M4CNCM3
5 200230460575
— 6075
150150
270 120/60110/50
W970M5CFCM3W970M5CNCM3
6 200230460575
— 100150300300
540 120/60110/50
W970M6CFCM3W970M6CNCM3
For Single Winding Type Motors (Constant or Variable Torque)
1 G) 200230460575
1122
— 27 120/60110/50
W980MLCFCM3W980MLCNCM3
1 200230460575
7-1/27-1/2
1010
— 27 120/60110/50
W980M1CFCM3W980M1CNCM3
2 200230460575
10152525
— 45 120/60110/50
W980M2CFCM3W980M2CNCM3
3 200230460575
25305050
— 90 120/60110/50
W980M3CFCM3W980M3CNCM3
4 200230460575
4050
100100
— 135 120/60110/50
W980M4CFCM3W980M4CNCM3
5 200230460575
75100200200
— 270 120/60110/50
W980M5CFCM3W980M5CNCM3
6 200230460575
150150400400
— 540 120/60110/50
W980M6CFCM3W980M6CNCM3
G) For motor full load current (FLA) range of .47A – 3.81A with a 1.15 to 1.25 service factor and for motor hp range of 1/4 hp to 2 hp at 460V.
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . MC7
Maximum Voltage Rating 600V 600V 600V 600V 600V 600VAmpere Rating — Open
— Enclosed30A27A
50A45A
100A90A
150A135A
300A270A
600A540A
Maximum Horsepower — Squirrel Cage Motor200V, 60 Hz230V, 60 Hz380V, 50 Hz460 – 575V, 60 Hz
7-1/2 hp7-1/2 hp
10 hp10 hp
10 hp15 hp25 hp25 hp
25 hp30 hp50 hp50 hp
40 hp50 hp75 hp
100 hp
75 hp100 hp150 hp200 hp
150 hp200 hp300 hp400 hp
Resistive Heating, kW G) — Three-Phase, 3-Pole120V240V480V600V
5 kW10 kW20 kW25 kW
8.5 kW17 kW34 kW43 kW
17 kW34 kW68 kW86 kW
26 kW68 kW
105 kW130 kW
52 kW105 kW210 kW260 kW
105 kW210 kW415 kW515 kW
Capacitor Switching kVAR — Three-Phase240V480V600V
———
12 kVAR25 kVAR32 kVAR
27 kVAR53 kVAR67 kVAR
40 kVAR80 kVAR
100 kVAR
80 kVAR160 kVAR200 kVAR
160 kVAR320 kVAR400 kVAR
Transformer Switching, kVA 0 — Three-Phase, 3-Pole208V240V480V600V
3.6 kVA4.3 kVA8.5 kVA
11 kVA
6.3 kVA7.2 kVA
14 kVA18 kVA
12 kVA14 kVA28 kVA35 kVA
20 kVA23 kVA47 kVA59 kVA
41 kVA47 kVA94 kVA
117 kVA
81 kVA94 kVA
188 kVA234 kVA
NEMA Contactors & StartersAdvantageTechnical Data and Specifications
A-116March 2007
CA08102001K For more information visit: www.EatonElectrical.ca
Table A-214. Electrical Characteristics, Sizes 1 – 6Description Size 1 Size 2 Size 3 Size 4 Size 5 Size 6
A
G) Resistive loads having inrush currents not exceeding 1.5 times continuous rating.0 Transformers having inrush currents not more than 20 times peak of continuous current ratings.
Table A-215. 380V, 50 Hz Starters — Maximum Horsepower RatingsNEMA Size 1 2 3 4 5 6Maximum hp 10 25 50 75 150 300
Ground Current Sensing ProtectionEaton’s Cutler-Hammer Advantage starters with ground cur- rent sensing protection feature provide equipment protec- tion against ground currents between a factory-set low level and a lockout current. It is designed to open the circuit when it senses the low-level and arcing ground currents often occurring in motor branch circuits. This feature is standard with Cutler-Hammer Advantage starters. The ground current sensing protection feature can either be omitted from devices supplied by the factory, or omitted in the field by modifying the device with an Advantage Programming Module (WAPM).
Note: These devices are NOT Ground Fault Interrupters (GFIs) designed to protect people. Additionally, branch circuit short-circuit protective devices are to be used to clear faults that exceed the interrupting rating of the starter.
Table A-216. Ground Current SensingSize Trip Current Lockout Current Trip TimeIL 10 24 .4 sec.1 10 48 .4 sec.2 20 86 .4 sec.3 40 171 .4 sec.4 60 256 .4 sec.5 240 1045 .4 sec.6 240 1045 .4 sec.
The table above gives trip amperes and lockout amperes for each size of the starter. Lockout current is the sum of the phase current and ground current.
Phase UnbalanceIf the unbalance of any two phases is greater than 30% of the DIP switch selected trip rating of the starter, a phase unbal- ance is declared and a trip occurs. No time delay is required for reset. This feature is standard in the Cutler-Hammer Advantage starter. To customize your protection, phase unbalance can be omitted by disabling the protection using an Advantage Programming Module (WAPM).
Phase LossThe Advantage starter will trip on phase loss, after two seconds, if the current in any one phase is lower than the currents listed in the table below. No time delay is required for reset. Phase loss protection is standard on the Cutler- Hammer Advantage starter. The phase loss protection feature can either be omitted from devices supplied by the factory, or omitted in the field by modifying the device with an Advantage Programming Module (WAPM).
Table A-217. Phase Trip TimeSize 1 Size 2 Size 3 Size 4 Size 5 Size 6
Phase UnbalanceLevel
30% Unbalance
Phase UnbalanceTrip Delay
6 sec. 9 sec. 12 sec.
Phase Loss Trip after 2 sec. if Phase Current is below:
.15A 01.15A
1.15A 2.5A 2.5A 11A 11A
0 Size 1 Lower Current Range for motor hp range of 1/4 hp to 2 hp at460V.
AC CoilBurden — Inrush VA
Closed VAClosed Watts
Pick-Up Volts G)
Drop-Out Volts G)
250 VA25 VA5W78V60V
250 VA25 VA5W78V60V
500 VA50 VA10W78V60V
500 VA50 VA10W78V60V
2600 VA50 VA10W78V60V
2600 VA50 VA10W78V60V
Recommended VA rating for machine tool control power transformers
100 VA 100 VA 150 VA 150 VA 300 VA 300 VA
Horsepower Squirrel Cage AC200V 230V 460V 575V
1/41/23/4
11-1/2
1.152.33.24.16.0
12.02.83.65.2
.61.01.41.82.6
.5
.81.11.42.1
2357-1/2
10
7.811.017.525.332.2
6.89.6
15.22228
3.44.87.6
1114
2.73.96.19
111520253040
48.362.178.292
120
42546880
104
2127344052
1722273241
506075
100125
150177221286359
130154192248312
657796
124156
52627799
125150200
414552
360480
180240
144192
Table A-218. Operating Coil Characteristics at Rated Coil Volts, Sizes 1 – 6Description Size 1 Size 2 Size 3 Size 4 Size 5 Size 6
A
Note: The above represent typical production test values and should not be interpreted as a guarantee of actual performance.G) Values may vary based upon control power transformer capacities.
Advantage contactors will withstand 110% of their rated voltage continuously without injury to the operating coils and will close successfully at 65% of their rated voltage.
Table A-219. Mechanical Characteristics — Sizes 1 – 6Description Size 1 Size 2 Size 3 Size 4 Size 5 Size 6Dimensions in Inches (mm) HeightWidthDepth
6.50 (165.1)2.50 (63.5)4.96 (126.0)
6.50 (165.1)2.50 (63.5)4.96 (126.0)
8.00 (203.2)3.68 (93.5)6.54 (166.1)
8.00 (203.2)3.68 (93.5)6.54 (166.1)
10.08 (256.0)7.07 (179.6)7.64 (194.1)
10.08 (256.0)7.07 (179.6)7.64 (194.1)
Panel area, square inchesShipping weight, lbs.
16.252.00
16.252.00
29.446.00
29.446.00
71.2730.00
71.2730.00
Maximum cable size/phase copper — AWG/MCM 0Auxiliary Electrical Circuits Available Maximum wire size for auxiliary electrical circuit — AWGMaximum wire size for control circuit — AWG
8 AWG8
12
(2) 14
4 AWG8
12
(2) 14
250 MCM Q)
812
(2) 14
250 MCM Q)
812
(2) 14
(1) 500 MCM Q)
812
(2) 14
(2) 500 MCM Q)
812
(2) 14Mechanical interlock combinations available Vert. Horiz. Vert. Horiz. Vert. Horiz. Vert. Horiz. Vert. Horiz. Vert. Horiz.
0 Also referenced as “kcmil” (1990 NEC).
Motor FLA, Three-Phase ACTable A-220. Data from Table 430-150 of 1990 NEC Table A-221. Temperature Specifications, Sizes 1 – 6
Ambient Temperature
Storage
Operating
External (NEMA Enclosed)
Table A-222. DIP Switch Overload Protection SettingsReset Method Position 8
MANUAL (Non-automatic — wait 5 minutes)AUTOMATIC (Reset time is based on protection Class)
Overload Class Position 7
10 020 030 1None 1
Note: These current values are for motors running at usual speeds and with normal torque characteristics. Motors for special low speed or high torque may require higher current. In all cases, OL trip cur- rent setting should be selected on basis of information on motor nameplate or motor card data.
Column A Service Factor1.15 to 1.25Min. Max.
Column B Service Factor1.0Min. Max.
Trip RatingAmperes
DIP Switch Setting 0(Positions) (54321)
3.15 – 3.463.47 – 3.813.82 – 4.194.20 – 4.614.62 – 5.0
3.43 – 3.753.76 – 4.134.14 – 4.554.56 – 4.995.00 – 5.4
3.934.334.775.255.77
0000000001000100001100100
5.2 – 5.55.6 – 6.06.1 – 6.66.7 – 7.37.4 – 8.1
5.5 – 6.06.1 – 6.56.6 – 7.27.3 – 8.08.1 – 8.8
6.356.97.78.59.3
0010100110001110100001001
8.2 – 8.99.0 – 9.89.9 – 0.8
10.9 – 11.912.0 – 13.1
8.9 – 9.69.7 – 10.6
10.7 – 11.711.8 – 12.913.0 – 14.2
10.211.212.413.615.0
0101001011011000110101110
13.2 – 14.414.5 – 15.815.9 – 17.417.5 – 19.219.3 – 21.1
14.3 – 15.715.8 – 17.217.3 – 18.919.0 – 20.921.0 – 22.9
16.518.119.921.924.1
0111110000100011001010011
21.2 – 23.323.4 – 25.625.7 – 27.0
23.0 – 25.225.3 – 27.0— —
26.529.132.1
101001010110110.47 – .51
.52 – .56
.57 – .61
.62 – .68
.69 – .75
.51 – .56
.57 – .61
.62 – .67
.68 – .74
.75 – .82
.59
.65
.71
.78
.86
0000000001000100001100100
.76 – .82
.83 – .90
.91 – 1.001.01 – 1.091.10 – 1.21
.83 – .89
.90 – .98
.99 – 1.091.10 – 1.191.20 – 1.31
.951.041.141.261.38
0010100110001110100001001
1.22 – 1.331.34 – 1.461.47 – 1.611.62 – 1.771.78 – 1.95
1.32 – 1.441.45 – 1.591.60 – 1.751.76 – 1.931.94 – 2.12
1.521.671.842.022.23
0101001011011000110101110
1.96 – 2.142.15 – 2.362.37 – 2.602.61 – 2.852.86 – 3.14
2.13 – 2.332.34 – 2.562.57 – 2.822.83 – 3.103.11 – 3.42
2.452.692.963.263.58
0111110000100011001010011
3.15 – 3.463.47 – 3.81
3.43 – 3.763.77 – 4.14
3.944.34
1010010101
3.15 – 3.463.47 – 3.813.82 – 4.194.20 – 4.614.62 – 5.0
3.43 – 3.753.76 – 4.134.14 – 4.554.56 – 4.995.00 – 5.4
3.934.334.775.255.77
0000000001000100001100100
5.1 – 5.55.6 – 6.06.1 – 6.66.7 – 7.37.4 – 8.1
5.5 – 6.06.1 – 6.56.6 – 7.27.3 – 8.08.1 – 8.8
6.356.97.78.59.3
0010100110001110100001001
8.2 – 8.99.0 – 9.89.9 – 10.8
10.9 – 11.912.0 – 13.1
8.9 – 9.69.7 – 10.6
10.7 – 11.711.8 – 12.913.0 – 14.2
10.211.212.413.615.0
0101001011011000110101110
13.2 – 14.414.5 – 15.815.9 – 17.417.5 – 19.219.3 – 21.1
14.3 – 15.715.8 – 17.217.3 – 18.919.0 – 20.921.0 – 22.9
16.518.119.921.924.1
0111110000100011001010011
21.2 – 23.223.3 – 25.625.7 – 28.128.2 – 31.031.1 – 34.1
23.0 – 25.225.3 – 27.827.9 – 30.530.6 – 33.733.8 – 37.0
26.529.132.135.338.9
1010010101101101011111000
34.2 – 37.537.6 – 41.241.3 – 45.0
37.1 – 40.740.8 – 44.844.9 – 45.0
42.847.051.6
110011101011011
NEMA Contactors & StartersAdvantageTechnical Data and Specifications
A-118March 2007
CA08102001K For more information visit: www.EatonElectrical.ca
A
Overload Trip Current SettingsFull Voltage StartersTo select the overload current trip setting, find the starter size table. Locate the full load current from motor nameplate in column A or B. Change DIP switch positions 5 – 1 to correspond to the table.
Reduced Voltage StartersMultiply the full load current from motor nameplate by factor below for your type of reduced voltage starter. Find this adjusted full load current in starter Size table in Column A or B. Change DIP switch positions 5 – 1 to correspond to the table.
Table A-223. FactorCatalogue Number Multiplier
Factor
Table A-225. Size 1 — Upper Current Range
W600 Autotransformer W700 Part Winding W800, W890 Wye-Delta
1.0.5.575
Table A-224. Size 1 — Lower Current RangeColumn A Service Factor1.15 to 1.25Min. Max.
Column B Service Factor1.0Min. Max.
Trip RatingAmperes
DIP Switch Setting G)
(Positions) (54321)
0 All settings not shown are equivalent to 00000.
Table A-226. Size 2 — Current RangeColumn A Service Factor1.15 to 1.25Min. Max.
Column B Service Factor1.0Min. Max.
Trip RatingAmperes
G) All settings not shown are equivalent to 00000.
8 Auto/Man7 6 Class
ControlVoltage
5 4 3 2 1 OL Set 3 P E C1
0
Reset
Figure A-51. DIP Switch, Terminals and Reset0 All settings not shown are equivalent to 00000.
Column A Service Factor1.15 to 1.25Min. Max.
Column B Service Factor1.0Min. Max.
Trip RatingAmperes
DIP Switch Setting 0(Positions) (54321)Column A
Service Factor1.15 to 1.25Min. Max.
Column B Service Factor1.0Min. Max.
Trip RatingAmperes
DIP Switch Setting G)
(Positions) (54321)
38.3 – 41.942.0 – 46.146.2 – 51.051.1 – 55.956.0 – 61.7
41.7 – 45.645.7 – 50.150.2 – 55.555.6 – 60.860.9 – 67.1
47.952.557.763.970.0
0000000001000100001100100
61.8 – 67.567.6 – 74.975.0 – 82.382.4 – 90.390.4 – 99.9
67.2 – 73.473.5 – 81.481.5 – 89.589.6 – 98.298.3 – 108
77.384.593.7
103113
0010100110001110100001001
100 – 109110 – 120121 – 132133 – 145146 – 159
109 – 118119 – 130131 – 143144 – 157158 – 173
125137151166182
0101001011011000110101110
160 – 175176 – 193194 – 213214 – 233234 – 257
174 – 190191 – 209210 – 231232 – 254255 – 270
200220242267293
0111110000100011001010011
258 – 270 — — 322 10100
9.9 – 10.810.9 – 11.912.0 – 13.113.2 – 14.414.5 – 15.8
10.8 – 11.711.8 – 12.913.0 – 14.214.3 – 15.615.7 – 17.2
12.413.615.016.518.1
0000000001000100001100100
15.9 – 17.317.5 – 19.219.3 – 21.121.2 – 23.223.3 – 25.6
17.3 – 18.919.0 – 20.921.0 – 22.923.0 – 25.225.3 – 27.8
19.921.924.126.529.1
0010100110001110100001001
25.7 – 28.128.2 – 30.931.0 – 34.134.2 – 37.537.6 – 41.3
27.9 – 30.630.7 – 33.633.7 – 37.037.1 – 40.840.9 – 44.9
32.135.338.842.747.0
0101001011011000110101110
41.4 – 45.445.5 – 50.050.1 – 54.955.0 – 60.560.6 – 66.5
45.0 – 49.449.5 – 54.354.4 – 59.759.8 – 65.765.8 – 72.3
51.756.962.668.875.7
0111110000100011001010011
66.6 – 73.273.3 – 80.780.8 – 88.788.8 – 90.0
72.4 – 79.679.7 – 87.787.8 – 90.0— —
83.391.6
101.0111.0
10100101011011010111 Column A
Service Factor1.15 to 1.25Min. Max.
Column B Service Factor1.0Min. Max.
Trip RatingAmperes
DIP Switch Setting ®(Positions) (54321)
38.3 – 41.942.0 – 46.146.2 – 51.051.1 – 55.956.0 – 61.7
41.7 – 45.645.7 – 50.150.2 – 55.555.6 – 60.860.9 – 67.1
47.952.557.763.970.0
0000000001000100001100100
61.8 – 67.567.6 – 74.975.0 – 82.382.4 – 90.390.4 – 99.9
67.2 – 73.473.5 – 81.481.5 – 89.589.6 – 98.298.3 – 108
77.384.593.7
103113
0010100110001110100001001
100 – 109110 – 120121 – 132133 – 145146 – 159
109 – 118119 – 130131 – 143144 – 157158 – 173
125137151166182
0101001011011000110101110
160 – 175176 – 193194 – 213214 – 233234 – 257
174 – 190191 – 209210 – 231232 – 254255 – 279
200220242267293
0111110000100011001010011
258 – 282283 – 311312 – 342343 – 376377 – 414
280 – 307308 – 338339 – 372373 – 409410 – 450
322354390429471
1010010101101101011111000
415 – 456457 – 501502 – 540
451 – 496497 – 540— —
519571628
110011101011011
9.9 – 10.810.9 – 11.912.0 – 13.113.2 – 14.414.5 – 15.8
10.8 – 11.711.8 – 12.913.0 – 14.214.3 – 15.615.7 – 17.2
12.413.615.016.518.1
0000000001000100001100100
15.9 – 17.417.5 – 19.219.3 – 21.121.2 – 23.223.3 – 25.6
17.3 – 18.919.0 – 20.921.0 – 22.923.0 – 25.225.3 – 27.8
19.921.924.126.529.1
0010100110001110100001001
25.7 – 28.128.2 – 30.931.0 – 34.134.2 – 37.537.6 – 41.3
27.9 – 30.630.7 – 33.633.7 – 37.037.1 – 40.840.9 – 44.9
32.135.338.842.747.0
0101001011011000110101110
41.4 – 45.445.5 – 50.050.1 – 54.955.0 – 60.560.6 – 66.5
45.0 – 49.449.5 – 54.354.4 – 59.759.8 – 65.765.8 – 72.3
51.756.962.668.875.7
0111110000100011001010011
66.6 – 73.273.3 – 80.780.8 – 88.788.8 – 97.597.6 – 106
72.4 – 79.679.7 – 87.787.8 – 96.496.5 – 105
106 – 116
83.391.6
101111122
1010010101101101011111000
107 – 117118 – 129130 – 133
117 – 127128 – 133— —
134147162
110011101011011
Overload Trip Current Settings (Continued)Table A-227. Size 3 Current Range
Table A-229. Size 5 Current Range
A
0 All settings not shown are equivalent to 00000.
Table A-230. Size 6 Current Range
G) All settings not shown are equivalent to 00000.
Table A-228. Size 4 Current RangeColumn A Service Factor1.15 to 1.25Min. Max.
Column B Service Factor1.0Min. Max.
Trip RatingAmperes
DIP Switch Setting 0(Positions) (54321)
® All settings not shown are equivalent to 00000.
0 All settings not shown are equivalent to 00000.
Short-Circuit Protective Device (SCPD)
Max. Rating (SCPD)
Circuit Breaker Interrupting Rating
Short-CircuitWithstand Rating
Typical Disconnect DeviceCurrent Voltage
Short-Circuit Protective Device (SCPD)
Max. Rating (SCPD)
Circuit Breaker Interrupting Rating
Short-CircuitWithstand Rating
Typical Disconnect DeviceCurrent Voltage
Class H Fuse 60A — 5,000A 600V 30A DS Sw.Class J, Ror T Fuse
60A — 100,000A50,000A
480V600V
30A DS Sw.
65,000A 600V 100A FD-K Molded Case Sw.
Magnetic Only G)
Type CB 0
3A — 100,000A25,000A
480V600V
HMCP HMCPS
7A — 100,000A25,000A
480V600V
HMCPS
15A — 100,000A25,000A
480V600V
HMCP
30A — 100,000A25,000A
480V600V
HMCP
Thermal Magnetic Type CB 0
50A 65,000A25,000A
65,000A25,000A
480V600V
HFD
100,000A35,000A
100,000A35,000A
480V600V
FDC
Magnetic Only Type CB plus CL ®
30A — 100,000A 600V HMCP plus CL
Thermal/Mag. Type CBplus CL ®
50A 150,000A 100,000A 600V HFD plus CL
Class H Fuse 600A — 10,000A 600V 400A KD-K Molded Case Sw.Class J, R
or T Fuse600A — 100,000A 600V
Magnetic Only G)
Type CB 0
250A — 100,000A25,000A
480V600V
HMCP
400A — 100,000A25,000A
480V600V
Thermal Magnetic Type CB 0
400A 65,000A50,000A35,000A
65,000A100,000A25,000A
480V600V600V
HFD KDC HKD
Class H Fuse 100A — 5,000A 600V 60A DS Sw.Class J, Ror T Fuse
100A — 100,000A50,000A
480V600V
60A DS Sw.
65,000A 600V 100A FD-K Molded Case Sw.
Magnetic Only G)
Type CB 0
50A — 100,000A25,000A
480V600V
HMCP
Thermal Magnetic Type CB 0
90A 65,000A25,000A
65,000A25,000A
480V600V
HFD
100,000A35,000A
100,000A35,000A
480V600V
FDC
Magnetic Only Type CB plus CL ®
50A — 100,000A 600V HMCP plus CL
Thermal/Mag. Type CBplus CL ®
90A 150,000A 100,000A 600V HFD plus CL
Class J, Ror T Fuse
600A — 100,000A65,000A
480V600V
600A LD-K Molded Case Sw.
Class L Fuse 800A — 100,000A65,000A
480V600V
600A LD-K Molded Case Sw.
Magnetic Only G)
Type CB 0
600A — 100,000A25,000A
480V600V
HMCP
800A — 65,000A25,000A
480V600V
Magnetic OnlyHMCP
Thermal Magnetic Type CB 0
600A 65,000A25,000A
65,000A35,000A
480V600V
HLD
800A 50,000A25,000A
65,000A25,000A
480V600V
Thermal Mag- neticHMC
Thermal/Mag. with CL ®
800A 200,000A 100,000A 600V NB Tri-Pac
Class H Fuse 350A — 5,000A 600V 100A DS Sw.Class R Fuse 200A — 100,000A
65,000A480V600V
100A FD-K Molded Case Sw.
Class Jor T Fuse
200A — 100,000A65,000A
480V600V
100A FD-K Molded Case Sw.
Magnetic Only G)
Type CB 0
200A — 100,000A25,000A
480V600V
HMCP
ThermalMagnetic
150A 65,000A25,000A
65,000A25,000A
480V600V
HFD
100,000A35,000A
100,000A35,000A
480V600V
FDC
Magnetic Only Type CB plus CL ®
100A — 100,000A 600V HMCP plus CL
Thermal/Mag. Type CBplus CL ®
150A 150,000A 100,000A 600V HFD plus CL
NEMA Contactors & StartersAdvantageTechnical Data and Specifications
A-120March 2007
CA08102001K For more information visit: www.EatonElectrical.ca
Short Circuit RatingsTable A-231. Short-Circuit Ratings
ASize 1 Size 4
Class H Fuse 500A — 10,000AClass J Fuse 400A — 100,000A
65,000AClass R orClass T Fuse
400A — 100,000A65,000A
Magnetic Only G) Type CB 0 150A — 100,000A50,000A
Thermal Magnetic Type CB 0 250A 100,000A35,000A
100,000A50,000A
65,000A25,000A
65,000A25,000A
Magnetic Only Type CB plus CL ® 150A — 100,000A
Size 5
Size 2
Size 6
Size 3G) Instantaneous adjustable trip.0 Circuit breaker.0 Inverse time circuit breaker.® Instantaneous adjustable trip with current limiting attachment.® Inverse time with built-in current limiting attachment.
Form C Contact RatingsMaximum Amperes —120V AC
CatalogueNumber
Price
Make Break
2880 VA 480 VA WBELLContinuous Current Rating: 5A
Voltage Color LegendPlate
CatalogueNumber
Price ReplacementPart
Price
120240480600
Red Red Red Green
RUN RUN RUN OFF
PLK1R PLK2R PLK4R PLK1G
99-3590-199-3590-399-3590-699-3590-8
DeviceNet™ CommunicationsModule
DeviceNet Module
The DeviceNet Communications mod- ule (Catalogue Number WPONIDNA) is designed to plug into the Advantage with the attached cable and plug. The module can be snapped onto the top or bottom of the Advantage unit. It can also be mounted separately using the mounting plate assembly (Catalogue
Type W Auxiliary Contact Modules■ Provides four separate contact sets
which wire vertically and are color coded; black designates NC and silver designated NO.
■ Up to two auxiliary contact modules can be mounted for a total of up to eight contact sets.
■ Provides circuit isolation (no polar- ity restrictions) and single break bifurcated contacts.
■ Common design fits all Sizes 1 – 6.
Table A-233. RatingsVoltage Make Break
NEMA A600 —120 – 600V AC
7200 VA 720 VA
NEMA Q300 —125 – 300V DC
69 VA 69 VA
Table A-234. Auxiliary Contact Modules
Bell Alarm Module
Bell Alarm Module
■ Simple snap-on mounting —see mounting examples in Figure A-52.
■ Isolated NO and NC contacts(1 each)
■ Plugs into Reset port■ Remote electrical Reset wired to
A
Number WPONIBASE). The module provides DeviceNet users with the ability to control and monitor the func-
Description CatalogueNumber
PriceCatalogue Number WBELL module
Table A-235. Ratings
tions of the Advantage system at 125,250 or 500 kbaud. A connector is pro- vided so that a HAND/OFF/AUTO hard contact may be used to selectively enable or disable the output of the control functions from the module without affecting its ability to monitor. A “Feedback” input is provided so that the state of an auxiliary contact may
2NO, 2NC3NO, 1NC4NO4NC1NO, 3NC1NO, 1NC and2 Tie Points
W22W31W40W04W13W11T
be read over the DeviceNet network.
Three bicolor LEDs indicate:
■ DeviceNet address■ Network status (including
connected, not connected, not powered)
■ Module status (including normal operation, minor fault, needs commissioning)
Table A-232. DeviceNet InterfaceDescription Catalogue
NumberPrice
DeviceNet InterfaceModule
WPONIDNA
Mounting PlateAssembly
WPONIBASE
Note: See Page A-136 for WPONI NetworkInterface.
Transformer Pilot Light KitsTable A-236. Transformer Pilot Light Kits
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . MC7
NEMA Contactors & StartersAdvantageAccessories
A-122March 2007
CA08102001K For more information visit: www.EatonElectrical.ca
A
TopView
Sizes 1 & 2 Sizes 3 & 4 Sizes 5 & 6
1.61 (40.9)
1.68(42.7)
From C NO/NC ContactLocal LED Trip Indication (When Used) (All Sizes)
Control Wire Ring/Spade Terminal Block
2.25 (57.2)
FrontView
.29 (7.4)
1.47 (37.3)
2.14 (54.4)
For Removal of Bell Alarm Module .55 (14.0) (All Sizes)
Note: Plug Orientation (All Sizes)
1.02 (25.9) For Removal of Plug(All Sizes) .70 (17.8) Distance .70 .93
4.20 (106.7)
Optional Mounting Locations
Mounting — Bell Alarm Modules
to Be Addedto the Widthof Contactor
(17.8) (23.6)
Figure A-52. Approximate Dimensions in Inches (mm)
Mechanical Interlock Kits
Figure A-53. Approximate Dimensions in Inches (mm)
■ For use with all Sizes 1 – 6.■ Provisions for ring or spade type lugs or stripped
conductors.■ Bottom side pre-wired with color coded conductors.■ Side mounting on contactor identical to Type W auxiliary
contact module mounting or can be mounted on Type W auxiliary contacts.
■ Kit contains fuses for use with all size starters.
Table A-238. Control Wire Terminal Block
Installed Mechanical Interlock Kit
■ Prevents closing of one contactor of a reversing or multi- speed controller until the opposite contactor is completely open.
■ Lever type mechanism assures positive action.■ Electrical interlocking contacts included — two NC
contacts.
Note: These kits cannot be field installed on reversing starters.
Table A-237. Mechanical Interlock KitsOrientation NEMA Size Catalogue
NumberPrice
Horizontal 1 – 6 WM16HVertical 1, 2
3, 456
WM12V WM34V WM55V WM66V
Vertical 1 or 2 to 3 or 43 or 4 to 5 or 65, 6
WM23VR G)
WM45VR 0WMBBV 0
G) Used to interlock a Size 1 or 2 to a Size 3 or 4 — mounts on right only.0 Used to interlock a Size 3 or 4 to a Size 5 or 6 — mounts on right only.0 Interconnecting bus bars are furnished with the interlock.
Description CatalogueNumber
Control Wire Terminal Block WTBF16
Price
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . MC7
Reset with TripIndication2 ft. Cable6 ft. Cable
15 ft. Cable
WRSTL24WRSTL72WRSTL180
Reset Only2 ft. Cable6 ft. Cable
15 ft. Cable
WRST24WRST72WRST180
Conversion Kit Reset Only to Reset with Trip Indication
WRLTT
6 ft. Cable Only15 ft. Cable Only LED Replacement Bulb
WRC72WRC180WRLT
NEMA Size
Number of Poles
CatalogueNumber
Price
123456
333333
WCK13WCK23WCK33WCK43WCK53WCK63
CoilSize
Voltage and Hz
CatalogueNumber
Price
1 & 2
3 & 4
5 & 6
110/120V60 Hz110/120V60 Hz110/120V60 Hz
WCOIL12F
WCOIL34F
WCOIL56F
OL Selection DIP Switch Window Internal Trip Indicator ■ Mount remotely up to 6 ft. away■ Unit completely assembled includ-
ing legend plate■ Available also in reset-only form —
no trip indication provided
Table A-243. Remote Pushbuttons A
DIP Switch Window Internal Trip Indicator
■ Overload condition indication —indicated by blinking light
■ Trip condition — indicated by solid light
Table A-241. Trip Indicator
Description CatalogueNumber
Price
Description CatalogueNumber Price
Internal TripIndicator
WLED
Figure A-54. DIP Switch Window
■ Simple snap-in installation■ Allows clear visibility of DIP
switches■ Prevents unwanted tampering of
DIP switch settings■ Once in must be pried out from rear■ One window supplied with each
Competitive Baseplate Kit■ Allows for direct retrofit of competi-
tive non-reversing starters■ Eliminates the need for re-drilling
and tapping of mounting holes■ Simple selection of competitive
footprints
Table A-242. Baseplate Kit
Renewal PartsTable A-244. Replacement Contact Kits
starter Description CatalogueNumber
Price
Table A-239. DIP Switch WindowDescription Catalogue
Number PriceEach
Sizes 1 and 2Sizes 3 and 4
WBASE12WBASE34
Table A-245. Replacement Coils
DIP Switch Window, (Must order in packages of 10)
WDIPSW10
Remote Reset and TripIndicator Pushbutton
DIN Rail Adapter Kit■ Provides snap-on mounting on
35 mm DIN rail■ For use with Sizes 1 and 2 non-
reversing contactors and starters
Table A-240. DIN Rail Adapter KitDescription Catalogue
Number
DIN Rail Adapter Kit WDIN
PriceFWD/REV/OFF/AUTO Control
■ OL condition indication■ Trip indication — OL phase-loss/
unbalance and ground fault■ OL reset capability■ 10250T — for 30 mm mounting■ NEMA 4 oiltight rated
NEMA Contactors & StartersAdvantageAccessories
A-122March 2007
CA08102001K For more information visit: www.EatonElectrical.ca
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . MC7
AFull Voltage PushbuttonControl Module
Metering Module
Cutler-Hammer® Advantage Control Modules (ACMs) from Eaton’s electrical business provide a cost-effective alter- native to pushbuttons, selector switches, indicating lights, reset mech- anisms, bell alarms and panel meters when used with the Advantage prod- uct line. Typical input/output control functions provided by panel mounted devices are conveniently packaged in a series of modules depending on appli- cation and complexity.
Sixteen styles cover applications ranging from:
■ Full voltage non-reversing■ Full voltage reversing■ Full voltage multispeed■ Reduced voltage■ DeviceNet compatible
Modules exist for each application to
An additional Metering Module replaces conventional ammeters (three-phase), replaces reset mecha- nisms and displays trip cause and data, control voltage and status.
This Metering Module can be used independently or in conjunction with any of the ACMs. An extra plug con- nection is available on the rear of each ACM to accept the Metering Module input.
The ACM family has been designed to save:
■ Panel space (versus conventional pushbuttons, selector switches and indicating lights)
■ Mounting and assembly labor■ Wiring and installation time
Regardless of the configuration, instal- lation requires mounting only one 2.25 x 3.5 inch module, substantially reduc- ing space requirements. Fitting a stan- dard Greenlee punch and die set, Greenlee #60071, installation is accomplished with only two screws.
ACMs provide savings in wiring costs as well. Regardless of the complexity of the application, wiring is reduced to a single plug-in cable, see photo at left.
Communication is not restricted by use of the Advantage Control Mod- ules. An extra plug connection is available on the rear of the ACM or Metering Module to allow a WPONIDNA or WPONI Communica- tions module to be plugged in.
2.25 (57.2)
Full Voltage and Reduced VoltageControl ModulesStatus Only■ 4 LEDs indicate that the motor is
OFF, Running, Tripped or in Alarm mode (motor current is above the trip current setting)
■ Includes RESET button
START/STOP■ Motor START/STOP controlled by
START and STOP buttons■ Includes all features of Status Only
module
HOA Selector Switch withSTART/STOP■ In HAND mode, motor will start and
stop in response to START/STOP pushbuttons
■ In AUTO mode, motor will run in response to remote signal
■ Includes all features of Status Only module
ON/OFF/AUTO Selector Switch■ Motor will run in ON mode and not
in the OFF mode■ In AUTO mode the motor will run in
response to a remote signal■ Includes all features of Status Only
module
Reduced Voltage Control ModulesThe four reduced voltage pushbutton control modules provide control using two to four starters and/or contactors. The faceplates are identical to the full voltage modules, and the pushbuttons all perform the same functions. The module is programmed for the type of reduced voltage starter which sets the sequence of contact open and closing.
provide the functions of:
■ Status only❑ Indicating lights❑ Reset
■ Status, START/STOP and RESET■ Status, HOA and RESET■ Status, START/STOP/HOA and
Run
Off
RESResetOL Alarm OL Trip Trip
3.5 (88.9)
Run
Off
START
STOP
RESResetOL Alarm OL Trip Trip
Run
Off
HAND
OFF
AUTO
RESResetOL Alarm OL Trip Trip
START
STOP
Run
Off
ON
OFF
AUTO
RESResetOL Alarm OL Trip Trip
RESET Status Only START/STOP Control
HAND/OFF/AUTO Control with START/STOP Pushbutton
Control in HAND Mode
ON/OFF/AUTO Control
Figure A-55. Full Voltage and Reduced Voltage Control Modules
Full VoltageStatus Only with Reset START/STOP START/STOP/HOA ON/OFF/AUTOLOCAL/OFF/REMOTE with Lockable ACM G)
LOCAL/OFF/REMOTE with Network Health G)
WPBFV1WPBFV2WPBFV3WPBFV4WPBFV5 G)
WPBFV7 G)
ReversingStatus Only with Reset FWD/REV/STOP FWD/REV/STOP/HOA
WPBR1WPBR2WPBR3
2-SpeedStatus Only with Reset FAST/SLOW/STOP FAST/SLOW/STOP/HOA
WPB2S1WPB2S2WPB2S3
Reduced VoltageStatus Only with Reset START/STOP START/STOP/HOA ON/OFF/AUTO
WPBRV1WPBRV2WPBRV3WPBRV4
Metering Module10 ft. Interconnect Cable (3m)6 ft. Interconnect Cable (1.8m)3 ft. Interconnect Cable (.9m)1 ft. Interconnect Jumper (.3m)
WMETER 0WACM10WACM6WACM3WACM1
NEMA Contactors & StartersAdvantageAdvantage Control Modules
A-126March 2007
CA08102001K For more information visit: www.EatonElectrical.ca
Reversing and 2-SpeedPushbutton Modules
2.25 (57.2)
RESReset
Status Only■ 5 LEDs which indicate that the
motor is OFF, running forward
Metering ModuleThe Advantage Metering Module mon- itors status of a motor along with any of the pushbutton modules. It may be plugged into the pushbutton control module, and communicates to the starter through it, or plugged directly
A
3.5 (88.9)
Run Fwd Run Rev
Off
OL Alarm OL Trip Trip
RES
Reset
Status Only
(FAST), running reverse (SLOW),tripped or in alarm mode
■ Includes RESET button
FORWARD (FAST)/REVERSE (SLOW)/STOP■ Pushbuttons control whether motor
is running forward (FAST), running
into the starter when a pushbutton control module is not used.
The four digit display will show the current in each phase, control voltage or cause of trip. The STEP button may be pressed to step through these val- ues, and the five LEDs will indicate which value is being displayed. It is also equipped with a reset button and
Run Fwd Run Rev
Off
FWD
OL Alarm OL Trip Trip
REV
START/STOP Control
reverse (SLOW) or stopped■ Includes all features of Status Only
module
Trip Lockout LED.
STOP
Run Fwd Run Rev
Off
OFF
AUTO
RES
ResetOL Alarm OL Trip Trip
FWD
REV
STOP
HAND
FWD/REV/OFF/ AUTO Control
FWD/REV/OFF/AUTO■ In AUTO mode, motor is running
forward (FAST), running reverse (SLOW) or OFF in response to a remote signal
■ All features of FORWARD/REVERSE/ STOP module
Note: For 2-speed modules, FAST replacesFWD and SLOW replaces REV.
Table A-246. Control Modules/Accessories
Figure A-56. Reversing and 2-SpeedPushbutton Module
ACM Specifications■ Input supply requirements: 120V AC
(supplied by the Advantage motor controller)
■ Max. distance from Advantage motor controller: 6 ft. (1.83m)
■ Operating frequency: 50 or 60 Hz■ Operating temperature: -20° to 70°C■ Storage temperature: -20° to 85°C■ Humidity: 0 to 95%, non-condensing■ Remote input wire size: 18 – 14 AWG■ Maximum distance between remote
pushbuttons and ACM: 200 ft. (60.9m)
■ Cutout dimensions: 2.25 x 3.5 inches (57.2 x 88.9 mm) (see above). The cutout can be made using a Greenlee rectangular punch #600710
■ Enclosure type: NEMA 1 or 12, when properly installed
Description CatalogueNumber
Price
G) The WPBFV5 and WPBFV7 are DeviceNet® only. They can only be used when an active network is connected.
0 Harmonic distortion may cause the WMETER to display inaccurate current measurements.
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . MC7
C
NEMA Contactors & StartersAdvantageDimensions
A-126March 2007
CA08102001K For more information visit: www.EatonElectrical.ca
Non-reversing Contactors, NEMA Sizes 1 – 6
A 4 Circuit Aux. A Contact Block F G (When Used) I CL
Communications Connector (When
Used)4 Circuit Aux. Contact Block (When Used)
H D
4 Pt. ControlTerminal Block(Max. 2 of #14 B
per Point)
Slots for #10E Mounting Screws
(3 Holes)
Figure 1Sizes 1 and 2 Contactor
C
4 Circuit Aux. A Contact Block F G (When Used) I CL
Communications Connector (When
Used)
4 Circuit Aux. Contact Block
D(When Used)
H 4 Pt. Control B
Terminal Block(Max. 2 of #14
per Point)
4 Circuit Aux. Contact Block(When Used) A
I 4 Circuit Aux. Contact Block (When Used)
Slots for 1/4-20
E Mounting Screws C (3 Places)
Figure 2Sizes 3 and 4 Contactor
4 Pt. ControlTerminal Block
H (Max. 2 of #14per Point) B
Communication Connector
(When Used)
Slots for 5/16Mounting Bolts E (4 Slots)
Figure 3Sizes 5 and 6 Contactor
Figure A-57. Approximate Dimensions in Inches and Shipping Weights
Table A-247. Catalogue Number W201 Non-reversing ContactorsNEMA Size
Number of Poles
FigureNumber
Mounting Screws Dimensions in Inches (mm) Ship. Wt. Lbs. (kg)Number Size Wide
AHighB
DeepC
D E F G H I
1, 2 3 1 3 #10 2.50 (63.5)
6.50 (165.1)
4.84 (122.9)
5.12 (130.0)
1.88 (47.8)
1.25 (31.8)
.75 (19.1)
6.00 (152.4)
.52 (13.2)
2 (.9)
3, 4 3 2 3 1/4-20 3.68 (93.5)
8.00 (203.2)
6.49 (164.8)
6.45 (163.8)
2.80 (71.1)
1.84 (46.7)
.93 (23.6)
7.50 (190.5)
.52 (13.2)
6 (2.7)
5, 6 3 3 4 5/16 7.07 (179.6)
10.08 (256.0)
7.64 (194.1)
— 6.00 (152.4)
— — 9.20 (233.7)
.50 (12.7)
30 (13.6)
J
Horizontal Reversing, Open Contactors, NEMA Sizes 1 – 6
A F
IG
D J K
4 Circuit Aux. Cont. Blk.
(When Used)
HB
A 4 Circuit Aux. I F Cont. Blk.
G (When Used)
D J
A
H
B
Matches Bottom Mounting for A210 Size 1
Matches BottomMounting for E
C
4 Pt. ControlMatches Bottom
Mounting for A211E C
4 Pt. ControlA210 Size 2
Control Wire TB for Customer Connection
Terminal Block (Max. 2 of #14
per Point)Slots for #10
Mounting Screws(3 Holes)
Size 3 and 4 Control Wire TB for Customer Connection
Terminal Block(Max. 2 of #14
per Point)Slots for 1/4-20
Mounting Screws(3 Places)
Figure 1Sizes 1 and 2 Horizontal Reversing Contactor Figure 2
Sizes 3 and 4 Horizontal Reversing Contactor
AE
CControl Wire TB
for Customer I Connection
4 Circuit Aux.Cont. Blk.
(When Used) HK
D B4 Pt. ControlTerminal Block(Max. 2 of #14
per Point)
Holes for 5/16Mounting Bolts
(4 Places)G
Figure 3Sizes 5 and 6 Horizontal Reversing Contactor
Figure A-58. Approximate Dimensions in Inches and Shipping Weights
Note: For all Sizes 1 – 6, factory furnishes the control wiring between the forward and reverse contactors, and the control wire terminal block for customer connection.
Table A-248. Catalogue Number W211 Horizontal Reversing ContactorsNEMA Size
Number of Poles
FigureNumber
Mounting Screws Dimensions in Inches (mm) Ship. Wt. Lbs. (kg)Number Size Wide
AHighB
DeepC
D E F G H I J K
1, 2 3 x 3 1 3 #10 7.13 (181.1)
8.05 (204.5)
5.09 (129.3)
7.50 (190.5)
5.69 (144.5)
3.56 (90.4)
6.00 (152.4)
5.53 (140.5)
.33 (8.4)
6.75 (171.5)
6.00 (152.4)
6 (2.7)
3, 4 3 x 3 2 3 1/4-20 9.76 (247.9)
11.37 (288.8)
6.76 (171.7)
10.50 (266.7)
8.00 (203.2)
4.88 (124.0)
8.36 (212.3)
6.45 (163.8)
.45 (11.4)
9.25 (235.0)
— 16 (7.3)
5 3 x 3 3 4 5/16 22.24 (564.9)
18.24 (463.3)
8.91 (226.3)
14.00 (355.6)
20.00 (508.0)
— 15.15 (384.8)
10.08 (256.0)
.50 (12.7)
19.95 (506.7)
22.47 (570.7)
80 (36.3)
6 3 x 3 3 4 5/16 22.24 (564.9)
18.24 (463.3)
8.65 (219.7)
14.00 (355.6)
20.00 (508.0)
— 16.18 (411.0)
10.08 (256.0)
.50 (12.7)
19.76 (501.9)
22.28 (565.9)
80 (36.3)
I
NEMA Contactors & StartersAdvantageDimensions
A-128March 2007
CA08102001K For more information visit: www.EatonElectrical.ca
Vertical Reversing, Open Contactors, NEMA Sizes 1 – 6
A G
A F
A 4 Pt. ControlG Terminal BlockF (Max. 2 of #14
I per Point)4 Circuit Aux.
Cont. Blk. (When Used)
4 Circuit Aux. Cont. Blk.
(When Used)
D
Control Wire TB for Customer Connection
Slots for #10Mounting Screws
D H
4 Circuit Aux.Cont. Blk.
B (When Used)
Control Wire TB for Customer Connection
E CSlots for 1/4-20
H
B
4 Pt. Control Terminal Block (Max. 2 of #14
per Point)
(3 Holes) Control WireTerminal Blk.
Figure 1
Mounting Screws(3 Places)
C E
Figure 2Sizes 1 and 2 Vertical Reversing Contactor Sizes 3 and 4 Vertical Reversing Contactor
A G
4 Circuit Aux. Cont. Blk.
(When Used)
4 Pt. Control Terminal Block (Max. 2 of #14
per Point)
DH
B
Control Wire TB for Customer Connection
Holes for 5/16Mounting Bolts
(4 Places)E C
Figure 3Sizes 5 and 6 Vertical Reversing Contactor
Figure A-59. Approximate Dimensions in Inches and Shipping Weights
Note: For all Sizes 1 – 6, factory furnishes the control wiring between the forward and reverse contactors, and the control wire terminal block for customer connection.
Table A-249. Catalogue Number W251 Vertical Reversing ContactorsNEMA Size
Number of Poles
FigureNumber
Mounting Screws Dimensions in Inches (mm) Ship. Wt. Lbs. (kg)Number Size Wide
AHighB
DeepC
D E F G H I
1, 2 3 x 3 1 3 #10 4.27 (108.5)
18.50 (469.9)
5.09 (129.3)
18.00 (457.2)
1.88 (47.8)
1.80 (45.7)
3.73 (94.7)
12.65 (321.3)
.52 (13.2)
7 (3.2)
3, 4 3 x 3 2 3 1/4-20 5.42 (137.7)
25.13 (638.3)
6.76 (171.7)
24.25 (616.0)
2.88 (73.2)
2.31 (58.7)
4.62 (117.3)
16.94 (430.3)
.52 (13.2)
17 (7.7)
5 3 x 3 3 4 5/16 13.24 (336.3)
34.94 (887.5)
8.64 (219.5)
32.00 (812.8)
10.00 (254.0)
— 12.04 (305.8)
33.29 (845.6)
— 80 (36.3)
6 3 x 3 3 4 5/16 13.24 (336.3)
34.94 (887.5)
8.64 (219.5)
32.00 (812.8)
10.00 (254.0)
— 12.04 (305.8)
33.16 (842.3)
— 80 (36.3)
Non-reversing Starters, NEMA Sizes 1 – 6
AF G
I CL
4 Circuit Aux. Contact Block (When Used)
Communications Connector (When
Used)A 4 Circuit Aux.
Contact BlockF G (When Used)I
Communications Connector (When
Used) A
D H
E OL Selection J DIP Switch
Push .02 (.5)in to Reset
(When Used)
Manual Reset(When Used)
Trip Ind./Reset Connector
(When Used)
4 Pt. Control Terminal Block (Max. 2 of #14
per Point) C
Slots for #10Mounting Screws
(4 Holes)
Figure 1Sizes 1 and 2 Starter
B H D
EOL Selection J DIP Switch
Push .02 (.5) in to Reset
(When Used)
Manual Reset(When Used)
BTrip Ind./Reset
Connector (When Used)
4 Pt. ControlTerminal Block(Max. 2 of #14 Cper Point)
Slots for 1/4-20Mounting Screws
(3 Places)
Figure 2Sizes 3 and 4 Starter
A4 Circuit Aux. I Contact Block(When Used)
4 Circuit Aux. Contact Block (When Used)
4 Pt. Control Terminal Block (Max. 2 of #14
Hper Point)
Communications BConnector
Manual Reset(When Used)
Push .02 (.5) into Reset
(When Used)
OL SelectionDIP Switch J
E
Slots for 5/16Trip Ind./Reset
Connector CMounting Bolts(4 Slots)
(When Used)
Figure 3Sizes 5 and 6 Starter
Figure A-60. Approximate Dimensions in Inches and Shipping Weights
Table A-250. Catalogue Number W200 Non-reversing StartersNEMA Size
Number of Poles
FigureNumber
Mounting Screws Dimensions in Inches (mm) Ship. Wt. Lbs. (kg)Number Size Wide
AHighB
DeepC
D E F G H I J
1, 2 3 1 3 #10 2.50 (63.5)
6.50 (165.1)
4.96 (126.0)
5.12 (130.0)
1.88 (47.8)
1.25 (31.8)
.75 (19.1)
6.00 (152.4)
.52 (13.2)
.29 (7.4)
2 (.9)
3, 4 3 2 3 1/4-20 3.68 (93.5)
8.00 (203.2)
6.54 (166.1)
6.45 (163.8)
2.80 (71.1)
1.84 (46.7)
.93 (23.6)
7.50 (190.5)
.52 (13.2)
.32 (8.1)
6 (2.7)
5, 6 3 3 4 5/16 7.07 (179.6)
10.08 (256.0)
7.64 (194.1)
— 6.00 (152.4)
— — 9.20 (233.7)
.50 (12.7)
.46 (11.7)
30 (13.6)
J
NEMA Contactors & StartersAdvantageDimensions
A-130March 2007
CA08102001K For more information visit: www.EatonElectrical.ca
Horizontal Reversing, Open Starters, NEMA Sizes 1 – 6
A I
D J K
4 Circuit Aux. Cont. Blk. A (When Used) I F
G4 Pt. Control Terminal Block
A (Max. 2 of #14 per Point)F
Communication ConnectorG (When Used)
ManualReset D J(WhenUsed) H
Push
4 Circuit Aux. Cont. Blk. (When Used)
4 Pt. Control Terminal Block (Max. 2 of #14
per Point)
ManualReset(When HUsed)
BPush
.02 (.5)
Matches Bottom
Mounting for A210 Size 1
.02 (.5) in to Reset (When Used)
C
B
Matches Bottom
in toReset(WhenUsed)
E CMatchesBottom
Mounting forE
OL SelectionMounting for A210
Size 3 and 4 OL SelectionDIP Switch
Trip Ind./ResetConnector
A210 Size 2
Control Wire Slots for #10
DIP Switch Trip Ind./ResetConnector Control Wire TB
for Customer(When Used)
Slots for 1/4-20 CommunicationTB for Customer
ConnectionMounting Screws
(3 Holes)
Figure 1
(When Used) Connection Mounting Screws(3 Places)
Figure 2
Connector(When Used)
Sizes 1 and 2 Horizontal Reversing Contactor Sizes 3 and 4 Horizontal Reversing Contactor
A 4 Circuit Aux. C Cont. Blk.
I (When Used)
4 Pt. ControlTerminal Block(Max. 2 of #14
per Point) HK
D Manual B Reset
(When Used)
Push .02 (.5) in to Reset
(When Used)
Holes for 5/16 G Mounting Bolts Trip Ind./Reset Communication(4 Places) OL Selection
DIP SwitchFigure 3
Connector(When Used)
Connector(When Used)
Sizes 5 and 6 Horizontal Reversing Contactor
Figure A-61. Approximate Dimensions in Inches and Shipping Weights
Note: For all Sizes 1 – 6, factory furnishes the control wiring between the forward and reverse contactors, and the control wire terminal block for customer connection.
Table A-251. Catalogue Number W210 Horizontal Reversing StartersNEMA Size
Number of Poles
FigureNumber
Mounting Screws Dimensions in Inches (mm) Ship. Wt. Lbs. (kg)Number Size Wide
AHighB
DeepC
D E F G H I J K
1, 2 3 x 3 1 3 #10 7.13 (181.1)
8.05 (204.5)
5.25 (133.4)
7.50 (190.5)
5.69 (144.5)
3.56 (90.4)
6.00 (152.4)
7.62 (192.5)
.33 (8.4)
6.75 (171.5)
6.00 (152.4)
7 (3.2)
3, 4 3 x 3 2 3 1/4-20 9.76 (247.9)
11.37 (288.8)
6.81 (173.0)
10.50 (266.7)
8.00 (203.2)
4.88 (124.0)
8.47 (215.1)
9.79 (248.7)
.45 (11.4)
9.25 (235.0)
— 18 (8.2)
5 3 x 3 3 4 5/16 22.24 (564.9)
18.24 (463.3)
8.91 (226.3)
14.00 (355.6)
20.00 (508.0)
— 15.28 (388.1)
16.82 (427.2)
.50 (12.7)
21.76 (552.7)
22.47 (570.7)
85 (38.6)
6 3 x 3 3 4 516 22.24 (564.9)
18.24 (463.3)
8.65 (219.7)
14.00 (355.6)
20.00 (508.0)
— 15.28 (388.1)
16.82 (427.2)
.50 (12.7)
21.57 (547.9)
22.28 (565.9)
85 (38.6)
Vertical Reversing, Open Starters, NEMA Sizes 1 – 6
I
4 Circuit Aux. Contact Block (When Used)
D
OL SelectionDIP Switch
A G
FCL
4 Pt. Control Terminal Block (Max. 2 of #14
per Point)
Communications Connector (When
Used)
Manual Reset(When Used)
Push .02 (.5) in to Reset
(When Used)
A G
FI
4 Circuit Aux. Contact Block (When Used)
H
B 4 Circuit Aux.Contact Block D(When Used)
4 Pt. Control Terminal Block (Max. 2 of #14
per Point)OL SelectionDIP Switch
Control Wire TBfor Customer
Communications Connector (When
Used)
Push .02 (.5)in to Reset
Manual Reset(When Used)
Trip Ind./Reset
A
H
B
Slots for #10Mounting Screws E (3 Holes)
Control Wire TB for Customer Connection
C
Trip Indication/
Connection Connector(When Used)
Slots for 1/4-20
Figure 1
Reset Connector(When Used) E Mounting Screws C (3 Places)
Figure 2Sizes 1 and 2 Vertical Reversing Starter Sizes 3 and 4 Vertical Reversing Starter
A G
4 Circuit Aux. Contact Block (When Used)
D
4 Pt. Control Terminal Block (Max. 2 of #14
per Point)
Communications H Connector(When Used) B
OL SelectionDIP Switch Manual Reset
Push .02 (.5)Control Wire TB
for Customer Connection
Holes for 5/16Mounting Bolts E (4 Places)
Figure 3
in to Reset
Trip Ind./ Reset C Connector(When Used)
Sizes 5 and 6 Vertical Reversing Starter
Figure A-62. Approximate Dimensions in Inches and Shipping Weights
Note: For all Sizes 1 – 6, factory furnishes the control wiring between the forward and reverse contactors, and the control wire terminal block for customer connection.
Table A-252. Catalogue Number W250 Vertical Reversing StartersNEMA Size
Number of Poles
FigureNumber
Mounting Screws Dimensions in Inches (mm) Ship. Wt. Lbs. (kg)Number Size Wide
AHighB
DeepC
D E F G H I
1, 2 3 x 3 1 3 #10 4.27 (108.5)
18.50 (469.9)
5.25 (133.4)
18.00 (457.2)
1.88 (47.8)
1.80 (45.7)
3.73 (94.7)
14.72 (373.9)
.52 (13.2)
7.5 (3.4)
3, 4 3 x 3 2 3 1/4-20 5.42 (137.7)
25.13 (638.3)
6.81 (173.0)
24.25 (616.0)
2.88 (73.2)
2.31 (58.7)
4.62 (117.3)
20.28 (515.1)
.52 (13.2)
19.0 (8.6)
5 3 x 3 3 4 5/16 13.24 (336.3)
34.94 (887.5)
8.64 (219.5)
32.00 (812.8)
10.00 (254.0)
— 12.04 (305.8)
34.78 (883.4)
— 85.0 (38.6)
6 3 x 3 3 4 516 13.24 (336.3)
34.94 (887.5)
8.64 (219.5)
32.00 (812.8)
10.00 (254.0)
— 12.04 (305.8)
34.59 (878.6)
— 85.0 (38.6)
Electrical
Interlocks
Mechancial
Interlocks
3 4 5 2 E
C
Stopped
Reverse
Forward
L1 L2 L3X
1 H1
Baseplate w
ith Com
ponents as Supplied
X2 H
2O
ptional E
mergency S
topM
echanicalInterlock
3 – Start
P – R
un Perm
itF3 P
E C
L1R3 P
E C
/Stop
E –
Pow
erC
–E
lectrical Interlocks
Rm
L2
F
Com
mon
L3
T1
FR
Fm
F R R
T1
T2T3
R R
G3 4 5
2 E C
T2 T3
Motor
NEMA Contactors & StartersAdvantageWiring Diagrams
Fm and R
m A
re Electrical C
ontactsO
perated by the Mechanical Interlock
= Accessible Term
inals
Conductors E
xternal to Baseplate
Are Installer C
onnections
A-132
Stop
Fwd R
ev
3 2 4 5
March 2007
CA08102001K For more information visit: www.EatonElectrical.ca
Non-reversing and Reversing Contactors, NEMA Sizes 1 – 6
A L3
L2
L1
M
H1 H2X1 X2
T3
T2Motor
T1L3
L2
L1
M
H1 H2X1 X2
T3
T2Motor
T1
OptionalStop
Stop1
Start
Start2 3 Off
Hand
3Jumper P M
No Connection When Optional Start/Stop Pushbutton Used
3Optional P M
Emergency Stop E C
Automatic E Remote C ControlDevice
OptionalEmergency Stop
Mb Optional
Ma
StoppedG
RunningR
Mb Optional
Ma
StoppedG
RunningR
Cat. No. W201 Non-reversing Contactor3-Wire Control with Internal Holding Circuit
Cat. No. W201 Non-reversing Contactor2-Wire Control with Maintained HOA Switch
Forward
Reverse
Stopped Optional
3 – StartP – Run Permit
/StopE – PowerC – Common
F
3 P E C Fm
L1 L2 L3X1 H1
X2 H2
Optional L1EmergencyStop L2
RL3
RmOptional(Dashed Area)
3 P E C F R
F
F R RR
T1T2
R R G T3
Baseplatewith Components
as Supplied
T1 T2
T3
Motor
Stop Fwd Rev
3 2 4 5 Fm and Rm Are Electrical ContactsOperated by the Mechanical Interlock
Cat. No. W251 Vertical Reversing Contactor3-Wire Control with Internal Holding Circuit
Cat. No. W211 Horizontal Reversing Contactor C3-Wire Control with Internal Holding Circuit
Figure A-63. Typical Wiring DiagramsG) Sizes 5 and 6 horizontal reversing contactors have their Forward and Reverse contactor arrangement reversed. Reverse contactor is on left and
Forward contactor is on right.
Electrical
Interlocks
MechanicalInterlo
ck
3 4 98 5 2
E C
Tripped
Stopped
Reverse
Forw
ard
L1 L2 L3X
1 H1
Baseplate w
ith Com
ponents as Su
ppliedX
2 H2
Optional
Em
ergency S
top
MechanicalInterlo
ck3 – S
tartP
– Run P
ermit
F3 P E
C
R3 P E
C/S
topE
–L1
Pow
erC
–E
lectrical Interlocks
Rm
L2C
omm
on
L3F
FR
Fm
F R R
96 95 98 EC
Contacts
Reset
OLR
R R
G A
Show
nin E
nergizedS
tateReset
3 4 98 5 2E
CT1 T2 T3
WP
ON
I M
od.
(Option
al) Lighte
d Also
A
vailable(O
ptional)
May A
lso Be
Added
to
Forw
ard&
Reverse
Contactors
T2 T3
Mo
tor
T1
Fm and R
m A
re Electrical C
ontactsO
perated by the M
echanical Interlock
= Accessible Term
inals
Conductors E
xternal to Baseplate
Are Installer C
onnections
1S
top Fwd R
ev
3 2 4 5To
IMP
AC
C/IN
CO
M
Ne
twork
P
F
Non-reversing and Reversing Starters, NEMA Sizes 1 – 6
L3 T3
L2 T2
L1 T1 Motor L3
L2
T3
T2Motor A
M
H1 H2
X1 X2
(Current Sensors Are IntegralInside Starter Units)
L1
M
H1 H2
X1 X2
T1
(Current Sensors Are IntegralInside Starter Units)Optional
StartStop Trip Stop Start
TripInd./Reset To
Other
Stop1
Start2 3
Ind./Reset(When Used)
3P M
Stop 2 33
(When Used) IMPACC Network
E M Devices
No Connection When Optional Start/Stop Pushbutton Used
OptionalEmergency Stop
E C
Reset
OptionalEmergency Stop
CReset
PONI I1Mod. I2
Caution – UnplugIMPACC Plug To
Mb Optional
Ma
StoppedG
RunningR
Mb Optional
Ma
StoppedG
RunningR
DuringMaintenance
IMPACC Network PC
Cat. No. W200 Non-reversing Starter3-Wire Control with Internal Holding Circuit
Cat. No. W200 Non-reversing StarterInternal Holding Circuit, 3-Wire with IMPACC
Forward
Reverse
Stopped
98 TrippedOptional
3 – StartP – Run Permit
/StopE – PowerC – Common
FFm
3 P E C
L1 L2 L3X1 H1
X2 H2
EmergencyStop
Optional(Dashed Area)
L1
L2
RL3
Rm3 P E C
F
F R RR
R R G A
Contacts Shown in Energized
StateReset
96 95 98 E C
Reset
OLR
WPONI
T1 T2 T3
98
1Stop Fwd Rev
(Optional) Lighted Also
Available
Mod. (Optional)
May Also BeAdded toForward
& ReverseContactors
Baseplatewith
Componentsas Supplied
T1
To
T2 T3
Motor
3 2 4 5 IMPACC/INCOMNetwork
Cat. No. W250 Vertical Reversing Starter3-Wire Control with Internal Holding Circuit
Cat. No. W210 Horizontal Reversing Starter C3-Wire Control with Internal Holding Circuit
Figure A-64. Typical Wiring Diagrams
NEMA Contactors & StartersAdvantageWiring Diagrams
A-134March 2007
CA08102001K For more information visit: www.EatonElectrical.ca
G) Sizes 5 and 6 horizontal reversing contactors have their Forward and Reverse contactor arrangement reversed. Reverse contactor is on left andForward contactor is on right.
NEMA Contactors & StartersAdvantagePowerNet Communication Devices
A-134March 2007
CA08102001K For more information visit: www.EatonElectrical.ca
A
ContentsDescription Page
Central Monitoring Unit . . . . . A-134Product Operated Network
Interface (PONI) . . . . . . . . . . . A-136
Central Monitoring Unit
Central Monitoring Unit
Parameters Displayed■ Monitored values:
❑ Device description❑ 1A, 1B, 1C currents❑ Control voltage (excluding IQ500)❑ Present time, date❑ Resettable operation count❑ Run time, hours
■ Trip data — same as current values with cause of trip
■ Set points:❑ Device size❑ OL trip current setting (FLA
setting)❑ OL trip class❑ Ground fault protection —
ON/OFF❑ Phase loss/unbalance protection
— ON/OFF❑ Reset mode — AUTO/MANUAL❑ Frequency
Technical Data■ Device power requirement: 10 VA
maximum■ Frequency: 50/60 Hz■ Line characteristics: 120 or 240V AC
+20%, -20% (auto selected)■ Operating temperature: 0° to 70°C
(32° to 158°F)■ Storage temperature: -20° to 85°C
(-4° to 185°F)■ Humidity: 0 to 95%, R.H. non-
condensing■ Alarm contact ratings —
❑ 240V AC: 10A, resistive❑ 30V DC: 10A, resistive
Dimensions 5.38
(136.7)
(6 Holes)4.44
(112.8)
only) 9.38 (238.3)
Central Monitoring Unit from Eaton’s electrical business is a communications centre which transmits to and receives
(IQ500 only)❑ Phase unbalance % (IQ500 only)
4.44 (112.8)
.13 2.56 contactors or IQ500s equipped withPONI cards. The CMU can be mounted
Module set points — if LOAD CONTROL selected:
.25 (6.4)
(3.3) (65) 5.12
(130)
custom panel using the existing IQ cut- out dimensions.
The eight-digit alphanumeric display monitors active data, trip data or set points. The group of data being dis- played is indicated by one of three LEDs and is selected by the user. The two-digit alphanumeric display indi- cates the address of the device about which the data is being displayed. This address is also selected by the user.
Five LEDs are provided which indicate the present status of the selected starter. Two additional LEDs are also provided at the top of the panel, one which indicates that the CMU is OPERATIONAL, and another which indicates ALARM status. An ACKNOWLEDGE/RESET button permits the user to reset the CMU following a device trip.
The CMU can be interfaced into a larger PowerNet network with the addition of a PowerNet PONI Communications Module.
❑ Load shed delay time❑ Load resume level❑ Load resume delay time❑ Long acceleration time
If UNDERLOAD/JAM selected:
❑ Jam trip level❑ Jam trip delay time❑ Jam start delay time❑ Underload trip level❑ Underload trip delay time❑ Underload start delay time❑ Long acceleration time❑ Relay control
in Inches (mm)
2
Wiring Diagram
6Advantage CMU
J3 J51
A Alarm
Trip
2 2 Wire Connector3 (Supplied with CMU)45
J66 Communication
1. For Network Interconnection Use Twisted PairConductors. No. 18 AWG Shielded. 1
2. Refer to Starter Wiring Diagrams for ActualConnections.
3. A 150 Ohm (1/2 Watt) Carbon Composition120 or 7
240V AC 8Ground 9
6
4To IBM
Compatible Personal Computer
5
Module(Optional)
1
(Y) 1 23 (BL) 4View A
Resistor Unit Must Be Installed on the MostRemote Starter Terminals as Shown.
4. An Eaton‘s Cutler-Hammer CONI (Computer OperatedNetwork Interface) Card Must Be Inserted intothe Computer Frame. (See IL 17199)
5. Modular Telephone Connector. Type RJ11 is toBe Supplied by the Customer and Wired per ViewA Required at Computer.
6. Ground Shielding at Only One Place as Shown.7. Where Devices Are Daisy Chained, Tie Shielding
Together for Continuity.8. On Last Device in Network, Tie Back Shield and Tape.
7 7
8
3 R E S
OL Relay Contactor Starter
0 9 8 O 0 0F 0 0F PONI 2 1Communication
Module
IQ 500 3-Digit IncomAddress Register
Figure A-66. Typical Wiring Diagram
Product SelectionTable A-253. Central Monitoring UnitDescription Catalogue
NumberPrice
Advantage Central Monitoring Unit WCMU
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . C40
NEMA Contactors & StartersAdvantagePowerNet Communication Devices
A-136March 2007
CA08102001K For more information visit: www.EatonElectrical.ca
Product Operated NetworkInterface (PONI)
Communications Data■ ON/OFF reset■ Status (ON, OFF, TRIPPED, NO
Product SelectionTable A-254. WPONI Network Interface
A Product Description RESPONSE)■ 3-phase unbalance
Description CatalogueNumber
Price
To use the PowerNet Communications network with Advantage motor con-
■ % phase unbalance■ Control voltage
Advantage WPONITo panel mount a WPONI
WPONIWPONIBASE
trol, a PONI is required for each device.The WPONI operates at 9600 baud.
■ Overload protection settings■ Cause of trip■ Trip data
Note: See Page A-121 for WPONIDNA DeviceNet Interface Module.
Mounting Dimensions
Sizes 1 & 2 Sizes 3 & 4 Sizes 5 & 6
IMPACC Connection (2 Wire)
TopView
WPONI WPONI WPONI (All Sizes)
Address Switches (All Sizes)
Local LED Trip Indication (When Used) (All Sizes)
1.61 (40.9)
Front
1.68 (42.7)
1.47 (37.3)
2.14 (54.4)
For Removal of WPONI (All Sizes)
Note: Plug Orientation (All Sizes)
View .29
(7.4)
.55 (14.0) (All Sizes)
Optional Mounting Locations1.02 (25.9)
For Removalof Plug(All Sizes)
Figure A-67. Mounting Procedures — WPONI — Approximate Dimensions in Inches (mm)
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . MC7