  • User’sManual ADMAG TI Series

    AXG1A Magnetic Flowmeter Remote TransmitterBRAIN Communication Type

    IM 01E22C02-01EN

    IM 01E22C02-01EN

    3rd Edition

  • 1

    IM 01E22C02-01EN

    ADMAG TI SeriesAXG1A Magnetic Flowmeter Remote TransmitterBRAIN Communication Type

    IM 01E22C02-01EN 3rd Edition

    Contents1. Introduction ...................................................................................................5

    1.1 For Safe Use of Product ...................................................................................... 81.2 Warranty .............................................................................................................. 10

    2. Operation by Display unit ..........................................................................112.1 Basic Operating Procedures ............................................................................ 112.2 DisplayandBasicConfiguration ..................................................................... 12

    2.2.1 DisplayConfiguration .......................................................................... 122.2.2 Operation Level ................................................................................... 14

    2.3 Display Mode and Setting Mode ....................................................................... 142.4 Parameter Setting from Display Panel ............................................................ 17

    2.4.1 SettingExampleofSelectTypeParameter(Flowrateunit) ............... 172.4.2 SettingExampleofNumericTypeParameter(Flowratespan) ......... 182.4.3 SettingExampleofAlphanumericTypeParameter(TagNo.) ............ 19

    2.5 microSD Card Insertion/Removal .................................................................... 20

    3. OperationwithBRAINConfigurationTool ............................................. 213.1 ConnectingBRAINConfigurationTool ........................................................... 213.2 BT200 Operating Procedures ........................................................................... 23

    3.2.1 KeyLayoutandScreenDisplay .......................................................... 233.2.2 KeyDescriptions ................................................................................. 243.2.3 FunctionKeys ..................................................................................... 25

    3.3 Calling Up Menu Addresses ............................................................................. 263.4 Parameter Update and Upload/ Download Function ..................................... 273.5 ParameterConfiguration .................................................................................. 28

    3.5.1 SettingExampleofSelecttypeParameter(FlowRateUnit) .............. 283.5.2 SettingExampleofNumericTypeParameter(Flowratespan) ......... 293.5.3 SettingExampleofAlphanumerictypeParameter(TagNo.) ............. 29

    4. Functions ................................................................................................... 304.1 Basic Settings .................................................................................................... 32

    4.1.1 Overview ............................................................................................. 324.1.2 PVMappingofProcessValue ............................................................ 334.1.3 DisplayoftheProcessValue .............................................................. 334.1.4 UnitSetting .......................................................................................... 344.1.5 SpanSetting........................................................................................ 35

    3rd Edition: Mar. 2020AllRightsReserved,Copyright©2019,YokogawaElectricCorporation

  • 2

    IM 01E22C02-01EN

    4.1.6 DampingTimeConstantSetting ......................................................... 364.1.7 Low-cutFunctionSetting .................................................................... 374.1.8 MeterfactorSetting ............................................................................. 394.1.9 SensorTypeSetting ............................................................................ 404.1.10 Sensor’sNominalSizeSetting ........................................................... 414.1.11 DensitySetting .................................................................................... 414.1.12 TemperatureSetting ........................................................................... 424.1.13 SpanFlowVelocityDisplay ................................................................. 424.1.14 UserSpanFunction ............................................................................ 434.1.15 ZeroAdjustment .................................................................................. 45

    4.2 Totalization Function ......................................................................................... 474.2.1 TotalizedValueandUnitSetting ......................................................... 474.2.2 TotalizedValueDisplayandTotalizationFunction .............................. 474.2.3 TotalizationSwitchFunction ............................................................... 494.2.4 TotalizerOperationatAlarmOccurrence ............................................ 504.2.5 Start/StopSettingforTotalizationFunction......................................... 504.2.6 TotalizationDirectionSetting .............................................................. 514.2.7 TotalizedValueReset/PresetFunction ............................................... 52

    4.3 Pulse Output, Frequency Output, and Status Output .................................... 534.3.1 Pulse/StatusOutputModeSetting ..................................................... 534.3.2 PulseOutput/FrequencyOutputMapping .......................................... 544.3.3 AlarmOutputFunction ........................................................................ 544.3.4 PulseWidthSetting ............................................................................. 554.3.5 ActiveDirectionSetting ....................................................................... 564.3.6 ActivePulseSetting ............................................................................ 574.3.7 PulseRateSetting .............................................................................. 574.3.8 FrequencyOutputRangeSetting ....................................................... 594.3.9 StatusOutputFunctionSetting ........................................................... 604.3.10 PulseOptionSetting ........................................................................... 63

    4.4 Status Input......................................................................................................... 644.4.1 ActiveDirectionSettingforStatusInput ............................................. 644.4.2 StatusInputFunctionSetting .............................................................. 65

    4.5 Analog Input and Analog Output ..................................................................... 664.5.1 AnalogOutputSelect .......................................................................... 664.5.2 AnalogOutputHigh/LowLimitFunction ............................................. 674.5.3 AbsoluteRangeFunction ................................................................... 684.5.4 AlarmOutputFunction ........................................................................ 694.5.5 AnalogOutputPriority ......................................................................... 694.5.6 CurrentValueAdjustment ................................................................... 704.5.7 AnalogInputFunctionSetting ............................................................. 714.5.8 DisplayAnalogInput ........................................................................... 714.5.9 AnalogInputUnitSetting .................................................................... 71

  • 3

    IM 01E22C02-01EN

    4.5.10 AnalogInputRangeSetting ................................................................ 724.5.11 AnalogInputHigh/LowLimitFunction ................................................ 72

    4.6 Multi Range Function ........................................................................................ 734.6.1 MultiRangetype ................................................................................. 734.6.2 MultiRangeSetting ............................................................................. 734.6.3 MultiRangeOperation ........................................................................ 744.6.4 Forward/ReverseRange .................................................................... 764.6.5 CombinationofMultiRangeandForward/ReverseRange ............... 784.6.6 ExternalContactRange ...................................................................... 794.6.7 ExternalContactRange(withAnswer) ............................................... 804.6.8 CombinationofExternalContactRangeandForward/Reverse

    Range .................................................................................................. 814.7 Auxiliary Calculation Function ......................................................................... 83

    4.7.1 FluidFlowDirectionSetting ................................................................ 834.7.2 RateLimitFunctionSetting ................................................................. 834.7.3 PulsingFlowSupportFunctionSetting ............................................... 864.7.4 PowerFrequencySynchronizationSetting ........................................ 864.7.5 DensityCorrectionCalculation ........................................................... 874.7.6 CalorieCalculation .............................................................................. 894.7.7 LimitofAlarmOutputFunction............................................................ 90

    4.8 Alarm ................................................................................................................... 914.8.1 ErrorsandCountermeasures ............................................................. 914.8.2 OperationattheTimeofError ............................................................ 974.8.3 AlarmDisplaySetting ........................................................................ 1014.8.4 AlarmHistoryFunction...................................................................... 1024.8.5 AlarmMaskFunction ........................................................................ 1034.8.6 BurnoutDirectionDisplay ................................................................. 1094.8.7 AlarmTerminalActiveDirectionSetting ............................................ 109

    4.9 Display ............................................................................................................... 1104.9.1 LanguageSetting ...............................................................................1104.9.2 DisplayItemSetting ...........................................................................1114.9.3 Decimal-PointPositionSetting ..........................................................1124.9.4 DisplayLineCountandScrollSettings ..............................................1144.9.5 TrendGraphSetting ..........................................................................1164.9.6 OtherSettings ....................................................................................1184.9.7 microSDCardSetting ....................................................................... 120

    4.10 Device Information ........................................................................................... 1224.10.1 OrderInformation .............................................................................. 1224.10.2 DeviceRevision ................................................................................ 1234.10.3 MemoFunction ................................................................................. 1234.10.4 DateandTimeInformation ............................................................... 1244.10.5 DisplayOperationTime .................................................................... 124

  • 4

    IM 01E22C02-01EN

    4.10.6 ExplosionProtectionSetting ............................................................. 1254.11 Self-diagnostic Function ................................................................................. 126

    4.11.1 TypesofDiagnosisFunctions ........................................................... 1264.11.2 AlarmHigh/LowLimitFunction ......................................................... 1264.11.3 ElectrodeAdhesionDetection .......................................................... 1284.11.4 SensorEmptyCheck ........................................................................ 1294.11.5 WiringConnectionDiagnosis ........................................................... 1304.11.6 Verification(DeviceHealthDiagnosis)Function .............................. 1314.11.7 ElectrodeInsulationDeteriorationDiagnosis ................................... 1354.11.8 FlowNoiseDiagnosis ....................................................................... 1364.11.9 LowConductivityDiagnosis .............................................................. 1374.11.10 CoilInsulationDiagnosis................................................................... 1384.11.11 OtherSetting ..................................................................................... 138

    4.12 Test Mode .......................................................................................................... 1394.12.1 TestModeSetting ............................................................................. 1394.12.2 TestValueSetting ............................................................................. 1404.12.3 Test2Mode ....................................................................................... 1414.12.4 TestModeAutoReset ....................................................................... 141

    4.13 Event Management Function .......................................................................... 1424.13.1 BackupFunction ............................................................................... 1424.13.2 Restore/DuplicateParameter ........................................................... 1454.13.3 BackupandRestoreParameters ..................................................... 1494.13.4 DataLoggingFunction ...................................................................... 153

    4.14 Parameter Protection ...................................................................................... 1554.14.1 SoftwareWriteProtectionFunction .................................................. 1554.14.2 DisplayRestrictionFunction ............................................................. 156

    5. Parameter Lists........................................................................................ 1576. Parameter Menu Tree .............................................................................. 191

    6.1 Display Menu Tree ........................................................................................... 191

    Revision Information ......................................................................................... 208

  • 5

    IM 01E22C02-01EN

    1. IntroductionThismanualexplainsbasicoperationsofADMAGTISeriesAXG1AMagneticFlowmeterRemoteTransmitterwithBRAINCommunicationProtocol.Foritemswhicharenotcoveredinthismanual,readtheapplicableuser’smanualslistedin“Table1.1ManualandGeneralSpecificationsList”intheADMAGTISeriesInstallationManual.ThesedocumentscanbedownloadedfromtheYOKOGAWAwebsite.Toensurethecorrectuseoftheproduct,readthesemanualsthoroughlyandfullyunderstandhowtooperatetheproductbeforeoperatingit.Toconfirmthemodelnameandspecificationsoftheproduct,refertothegeneralspecifications.Websiteaddress:http://www.yokogawa.com/fld/doc/

    Precautions Related to the Protection, Safety, and Alteration of the Product

    Thefollowingsafetysymbolmarksareusedinthismanualandtheproduct.

    WARNING

    AWARNINGsigndenotesahazard.Itcallsattentiontoaprocedure,practice,condition,orthelike,which,ifnotcorrectlyperformedoradheredto,couldresultininjuryordeathofpersonnel.

    CAUTIONACAUTIONsigndenotesahazard.Itcallsattentiontoaprocedure,practice,condition,orthelike,which,ifnotcorrectlyperformedoradheredto,couldresultindamagetoordestructionofpartoralloftheproduct.

    IMPORTANTAnIMPORTANTsigndenotesthatattentionisrequiredtoavoiddamagetotheproductorsystemfailure.

    NOTEANOTEsigndenotesinformationnecessaryforanessentialunderstandingofoperationandfeatures.

  • 6

    IM 01E22C02-01EN

    Thefollowingsymbolsareusedintheproductandthemanualtoindicatetheaccompanyingsafetyprecautions:

    Protectivegroundingterminal

    Functionalgroundingterminal(Thisterminalshouldnotbeusedasaprotectivegroundingterminal.)

    Alternatingcurrent

    Directcurrent

    CautionThissymbolindicatesthattheoperatormustrefertoanexplanationintheuser’smanualinordertoavoidtheriskofinjuryordeathofpersonnelordamagetotheproduct.

    Fortheprotectionandsafeuseoftheproductandthesysteminwhichthisproductisincorporated,besuretofollowtheinstructionsandprecautionsonsafetythatarestatedinuser’smanualwheneveryouhandletheproduct.Takespecialnotethatifyouhandletheproductinamannerthatviolatestheseinstructions,theprotectionfunctionoftheproductmaybedamagedorimpaired.Insuchacase,YOKOGAWAdoesnotguaranteethequality,performance,function,orsafetyoftheproduct.

    Regarding This User’s Manual• Thismanualshouldbeprovidedtotheenduser.

    • Thecontentsofthismanualaresubjecttochangewithoutpriornotice.

    • NopartofthismanualmaybereproducedinanyformwithoutYOKOGAWA’swrittenpermission.

    • YOKOGAWAmakesnowarrantyofanykindwithregardtothismanual,including,butnotlimitedto,impliedwarrantyofmerchantabilityandfitnessforaparticularpurpose.

    • Ifanyquestionsariseorerrorsarefound,orifanyinformationismissingfromthismanual,informthenearestYOKOGAWAsalesoffice.

    • Thespecificationscoveredbythismanualarelimitedtothoseforthestandardtypeunderthespecifiedmodelnumberbreak-downanddonotcovercustom-madeproducts.

    • Notethatchangesinthespecifications,construction,orcomponentpartsoftheproductmaynotimmediatelybereflectedinthismanualatthetimeofchange,providedthatpostponementofrevisionswillnotcausedifficultytotheuserfromafunctionalorperformancestandpoint.

    • Thismanualisintendedforthefollowingpersonnel:

    Engineersresponsiblefortheinstallationandwiringoftheproduct.

    Personnelresponsibleforthenormaldailyoperationoftheproduct(operator).

    • Toensurecorrectuse,readthismanualandtheapplicablemanualsthoroughlybeforestartingoperation.Readthegeneralspecificationsforspecificationsoftheproduct.

  • 7

    IM 01E22C02-01EN

    Trademarks• AllthebrandsornamesofYokogawaElectric’sproductsusedinthismanualareeither

    trademarksorregisteredtrademarksofYokogawaElectricCorporation.

    • Allothercompanyandproductnamesmentionedinthismanualaretradenames,trademarksorregisteredtrademarksoftheirrespectivecompanies.

    • Inthismanual,trademarksandregisteredtrademarksarenotmarkedwith“™”or“®”.

  • 8

    IM 01E22C02-01EN

    1.1 For Safe Use of ProductFortheprotectionandsafeuseoftheproductandthesysteminwhichthisproductisincorporated,besuretofollowtheinstructionsandprecautionsonsafetythatarestatedinuser’smanualwheneveryouhandletheproduct.Takespecialnotethatifyouhandletheproductinamannerthatviolatestheseinstructions,theprotectionfunctionoftheproductmaybedamagedorimpaired.Insuchacase,YOKOGAWAshallnotbeliableforanyindirectorconsequentiallossincurredbyeitherusingornotbeingabletousetheproduct.

    General

    WARNING

    • Donotopenthecoverinwetweatherorhumidenvironments.Whenthecoverisopen,thestatedenclosureprotectionisnotapplicable.

    • Whenopeningthecover,waitformorethan20minutesafterturningoffthepower.Onlyanexpertengineerorskilledpersonnelispermittedtoopenthecover.

    Operation

    WARNING

    Besuretoenablethewriteprotectfunctiontopreventparametersfrombeingoverwrittenafterfinishingparametersetting.Inrarecases,theIRswitchesmayrespondunexpectedlytowaterdropsorextraneoussubstancesstickingonthesurfaceofthedisplaypanelduetocharacteristicsoftheoperatingprinciples.Thepossibilityofmalfunctionarisesafterrainorcleaningneartheplacewheretheflowmeterisinstalled.Repeatedlyturningaflashlight,etc.onandoffinthedirectionoftheIRswitchmayalsobethecauseofmalfunction.Refertotheinstallationmanualforthehardwarewriteprotectfunction,andSection4.14forthesoftwarewriteprotectfunction.

    Maintenance

    WARNING

    • Ifdirt,dust,orothersubstancesadherestotheglassofthedisplay,wipethemcleanwithasoftdrycloth.

    • Maintenanceofthisproductshouldbeimplementedinamaintenanceserviceshopwherenecessitytoolsandenvironmentconditionareprovided.Therequiredenvironmentalconditionisthattheambienttemperatureshouldbe5to40°C(themaximumrelativehumidityis80%fortemperature5to31°C,anddecreasinglinearlyto50%relativehumidityat40°C).

  • 9

    IM 01E22C02-01EN

    microSD card

    IMPORTANT• DonotstoreorusethemicroSDcardinplaceswithstaticelectricity,nearelectricallycharged

    objects,orwhereelectricalnoiseispresent.DoingsocanresultinshockordamagetothemicroSDcard.

    • DonotdisassembleormodifythemicroSDcard.• Donotphysicallyshock,bend,orpinchthemicroSDcard.• Duringreading/writingofdata,donotturnoffthepower,applyvibrationorshock,orpullout

    thecard.Datacanbecorruptedorpermanentlylost.• UseonlythemicroSDcardsdesignatedbyYOKOGAWA.Theoperationofthedevicecannot

    beguaranteedwhenothercardsareused.• WheninsertingthemicroSDcardintotheproduct,makesuretoorientthemicroSDcard

    correctly(faceupordown)andinsertitsecurely.Ifnotinsertedcorrectly,themicroSDcardwillnotberecognizedbytheproduct.

    • DonottouchthemicroSDcardwithwethands.• DonotusethemicroSDcardifitisdustyordirty.• ThemicroSDcardcomesformatted.IfyouwouldliketoformatthemicroSDcard,usethe

    product’sFormatfunction.• YOKOGAWAprovidesnowarrantyfordamageto,orlossofdatarecordedonthemicroSD

    card,regardlessofthecauseofsuchdamageorloss.Werecommendregularlymakingbackupcopiesofyourdata.

  • 10

    IM 01E22C02-01EN

    1.2 Warranty• Thewarrantyshallcovertheperioddescribedinthequotationpresentedtothepurchaserat

    thetimeofpurchase.Problemsthatmayoccurduringthewarrantyperiodshallberepairedfreeofcharge.

    • Incaseofproblems,thecustomershouldcontacttheYOKOGAWArepresentativefromwhichtheproductwaspurchasedorthenearestYOKOGAWAoffice.

    • Ifaproblemariseswiththisproduct,pleaseinformYOKOGAWAofthenatureoftheproblemandthecircumstancesunderwhichtheproblemdeveloped,includingthemodelspecificationandserialnumber.Anydiagrams,dataandotherinformationyoucanincludeinyourcommunicationwillalsobehelpful.

    • ResponsiblepartforrepaircostsoftheproblemsshallbedeterminedbyYOKOGAWAbasedonourinvestigation.

    • Thepurchasershallbeartheresponsibilityforrepaircosts,evenduringthewarrantyperiod,ifthemalfunctionisdueto:

    - Improperand/orinadequatemaintenancebythepurchaser.

    - Failureordamageduetoimproperhandling,use,orstoragewhichdoesnotconformtodesignconditions.

    - UseoftheproductinquestioninalocationnotconformingtothestandardsspecifiedbyYOKOGAWA,orproblemsduetoimpropermaintenanceoftheinstallationlocation.

    - FailureordamageduetomodificationorrepairbyanypartyexceptYOKOGAWAoranapprovedrepresentativeofYOKOGAWA.

    - Malfunctionordamagefromimproperrelocationoftheproductinquestionafterdelivery.

    - Reasonofforcemajeuresuchasfires,earthquakes,storms/floods,thunder/lightning,orothernaturaldisasters,aswellasdisturbances,riots,warfare,orradioactivecontamination.

  • 11

    IM 01E22C02-01EN

    2. Operation by Display unit

    2.1 Basic Operating ProceduresTheparametersettingscanbechangedbyusingthreeIR(infra-red)switches;[SET],[SHIFT]and[▼]switchesonthedisplay.ThethreeIRswitchesenabletheusertosetparametersfromtheoutsideoftheglassofthedisplaycover.ThissectionprovidesdescriptionsofbasicparameterconfigurationonthedisplayandoperationproceduresoftheIRswitches.ThisproductcanbealsooperatedbyusingthededicatedhandheldterminalortheFieldMate(VersatileDeviceManagementWizard).Fordetailsaboutthesettingprocedure,refertoChapter4.

    WARNING

    Besuretoenablethewriteprotectfunctiontopreventparametersfrombeingoverwrittenafterfinishingparametersetting.Inrarecases,theIRswitchesmayrespondunexpectedlytowaterdropsorextraneoussubstancesstickingonthesurfaceofthedisplaypanelduetocharacteristicsoftheoperatingprinciples.Thepossibilityofmalfunctionarisesafterrainorcleaningneartheplacewheretheflowmeterisinstalled.Turningonandofftheflashlight,etc.towardstheIRswitchmayalsobethecauseofthemalfunction.RefertotheInstallationManualforthehardwarewriteprotectfunction,andSection4.14forthesoftwarewriteprotectfunction.

    IMPORTANT

    Operatethedisplayunderconditionswheredirectsunlight,etc.donotshinetotheIRswitchesdirectlywhentheparametersettingoperationiscarriedout.

    NOTE

    • Alwayskeepthedisplaycoverclosedandoperatethesettingswitchesfromtheoutsideoftheglasswindow.

    • Ifdirt,dust,orothersubstancesadherestotheglassofthedisplay,wipethemcleanwithasoftdrycloth.

    • Operationwithdirtyglovesmaycauseaswitchresponseerror.

    NOTE

    Thelanguageonthedisplayissetto“English”asdefaultatfactoryshipment.SelecttheadequatelanguagereferringtoSubsection4.9.1.Themenupassofthedisplayonthismanualissetto“English”.

  • 12

    IM 01E22C02-01EN

    2.2 DisplayandBasicConfigurationThedisplayoftheAXG1Aremotetransmitterhasthevariousfunctionsbelow.

    2.2.1 DisplayConfiguration

    22.000mA0.0%

    0.00000m/s00 : 00

    VEL

    FLP

    A01SET SFT INC

    Status icon and time

    Data display(Abbreviation: see Table 2.2.1)Switch On/Off status(On: inverted)IR switches

    F0201.ai

    microSD card(Optional code: /MC)

    (1) Basic operation of IR switchesThebasicoperationsofthedisplaypanelaredonebythethreeIRswitches;[SET],[SHIFT],and[▼].CombiningtwoIRswitchesprovidesadifferentfunction,andthefunctionoftheswitchisdisplayedonthedisplay.

    IR switch (Note 1) Function of switch (Note 2) Function

    [SET►] SET ▪Applyparameteranddata(Note3)▪Movetonextmenu

    [SHIFT] SFT▪Set/resetMultipleselectableoptions (Selecttypeparameter)▪Movecursorright (Numerictypeparameter)

    [▼] INC

    ▪Movecursordown (Selecttypeparameter)▪Incrementvalue (Numerictypeparameter)▪Changepositionofdecimalpoint (Numerictypeparameter)

    [SHIFT]+[▼](=[▲]) DEC▪Movecursorup (Selecttypeparameter)▪Decrementvalue (Numerictypeparameter)

    [SHIFT]+[SET►](=[ESC◄]) ESC

    ▪Cancel▪Backtopreviousmenu

    Note1:[A]+[B](=[C]):Thefunctionischangedtoswitch[C]whenswitch[B]ispressedwhilepressingswitch[A].Note2:[SET],[SFT],[INC],[DEC]and[ESC]indicatetheassignedfunctioninaccordancewithdisplaymodeatthattime.All

    functionscannotbeusedsimultaneously.Note3:“Apply”and“Enter”areexecutedbypressing[SET]twice.Iftheexecutiondoesnotworkproperly,releaseyourfinger

    fromthedisplayglasscompletelyafterinitiallypressing[SET],andthen,pressthatkeyagain.

  • 13

    IM 01E22C02-01EN

    (2) Status iconsIcon Description Icon Description

    WriteprotectionfunctionDisable

    WriteprotectionfunctionEnable

    DeviceBusy DeviceFaultmicroSDcardReady

    microSDcardAccessing

    microSDcardDisabletoaccess

    ParameterUploading

    ParameterDownloading

    TrendgraphfunctionRunning

    SystemAlarmOccurs BRAINcommunication

    ProcessAlarmOccurs

    SettingAlarmOccurs

    WarningOccurs

    InformationOccurs

    DisplayDampingValid

    Operation level:Operator

    Operation level:Maintenance

    Operation level:Specialist

    (3) Data indication partUptoeightprocessvaluescanbeselectedonthedisplay.Itispossibletodisplayuptofouritemsonthedisplayatthesametime,andtheremainingfouritemscanbedisplayedifscrolled.Table 2.2.1 Abbreviation table of process values to be indicated on the display

    Abbreviation DescriptionFLP*1 Flowrate%PRV*1 ProcessvalueVEL*1 FlowvelocityVFL*1 VolumetricflowrateMFL*1 MassflowrateFLB Flowratein%bargraphCAL*1 CalorieTL1*1 Totalizedvalue1TL2*1 Totalizedvalue2TL3*1 Totalizedvalue3TAG TagNo.COM CommunicationprotocolADH Adhesiondiagnosticlevel(AlarmatLevel4)AO1*1 Analogoutputvalue1AO2*1 Analogoutputvalue2FNL Flowlevelofflownoisediagnosis(AlarmatLevel4)TC1 Total1countTC2 Total2countTC3 Total3count

    *1: Atrendgraphcanbedisplayedonline.

    NOTE

    ThePRV(PVvalue)andFLP(flowrate%)operateinthesamewayasAnalogoutput1.IfthelowcutfunctionisenableforAnalogoutput1(G01:AO1LOWCUT/Lowcut),thePRVandFLPareaffectedbythelowcutfunction.Theirvalueafterlowcutaredisplayed.Ontheotherhand,theVEL(flowvelocity),VFL(volumeflow),MFL(massflow),andCAL(calorificvalue)arenotaffectedbythelowcutfunction.Theirvaluesaredisplayedastheyare.

  • 14

    IM 01E22C02-01EN

    2.2.2 Operation LevelWhensettingaparameterfromthedisplay,configurableparametersdifferdependingonthethreeoperationlevelsshowninTable2.2.2.Formaintenanceandspecialistlevels,thepasscodeneedstobeentered.Table 2.2.2 Parameter Setting from Display and Operation Level

    Operation Level Parameter DescriptionReading Writing

    Operator AllparametersPossibletosetadisplaylanguageonthedisplayandparametersrelatedtodisplayitems.

    Nopasscoderequired

    Maintenance AllparametersPossibletosetparametersallowedtosetwiththeoperatorlevelandparametersrelatedtozeroadjustment.

    PasscoderequiredDefaultvalue:0000

    Specialist Allparameters PossibletosetallwritableparametersPasscoderequiredDefaultvalue:0000

    Apasscodecanbeconfiguredonlyfromthedisplay.Thissettingcanbeconfiguredwiththefollowingparameters.Menu path

    Display Devicesetup►Detailedsetup►Accesscfg►(seebelow)

    Parameter Description

    ChgmainteChangeofpasscode(maintenancecode)withmaintenanceoperationlevelauthority.Tochangethelevel,maintenanceorspecialistoperationlevelauthorityisnecessary.

    Chgspecial Changeofpasscode(specialcode)withspecialistoperationlevelauthority.Tochangethelevel,specialistoperationlevelauthorityisnecessary.

    2.3 Display Mode and Setting ModeThedevicerunsinDisplayModewhenthepowerison.Tocheckorchangeparameters,SettingModemustbeactivated.ThefollowingprocedureexplainshowtochangetoSettingModefromSettingMode.ForthefunctionsoftheIRswitches,refertoSubsection2.2.1.

    [Procedure]1) Keeptouching[SET]switchforfewseconds.

    F0513.ai

    0.00000m/s0.00000l/min

    00 : 00PRV

    VEL

    FLBSET SFT INC

    2) Touch[SFT]+[INC]switches.

    F0514.ai

    Touch SFT + INC00 : 00

    SET SFT INC

    3) “No“isselected. Touch[INC]switchandselect“Yes”.

    F0515.ai

    Setting Mode

    No Yes▲

    00 : 00

    SET SFT INC

  • 15

    IM 01E22C02-01EN

    4) Touch[SET]switch.

    F0516.ai

    Setting Mode

    Yes No▲

    00 : 00

    SET SFT INC

    5) “Yes”isblinking. Touch[SET]switchagain.

    F0517.ai

    00 : 00

    SET SFT INC

    Setting Mode Yes

    6) ThescreenmovestothemenuofOperationLevel.

    F0518.ai

    Operation level Specialist Exit Operator

    00 : 00

    SET SFT INC

    7) Selectanappropreateoperationlevelbymovingthecursorwith[INC]or[DEC]switch. Passcodeisnotnecessaryfor“Operator”.For“Maintenance”and“Specialist”,passcode

    isnecessaryforeach.Forpasscodesetting,[SFT]isforpositionchange,and[INC]isfornumber,thentwice[SET]isforentrycompletion.

    Thedefaultpasscodeatthefactoryshipmentissetto“0000”.

    F0519.ai

    Pass code **** 0000 0000 9999

    00 : 00

    SET SFT INC

    8) WhentheOperationLevelisdetermined,thescreenmovesto“Devicesetup”astheSettingModewhereparameterscanbeconfigured.

    9) Aftercompletingparametersetting,push[ESC]switch.ThescreenreturnstotheDisplayMode.

    NOTE

    FollowtheprocedurebellowwhenIndsoftrev(K52:INDBREV/Indsoftrev)isR2.01.02orearlier.

    [Procedure]1) TurnonthepowerandwaitforseveralsecondstostartDisplayMode.

    F0212.ai

    0.00000m/s0.00000l/min

    00 : 00PRV

    VEL

    FLBSET SFT INC

    2) Pressandholdthe[SET]switchfortwoseconds.Thescreenwillswitchtothe“Operationlevel”menu.

    F0213.ai

    Operation level Maintenance Specialist Exit

    00 : 00

    SET SFT INC

  • 16

    IM 01E22C02-01EN

    NOTE

    3) Selectanappropriateoperationlevelbymovingthecursorwiththe[INC]or[DEC]switch. The“Operator”doesnotrequireapasscode,butfor“Maintenance”and“Specialist”,the

    passcodeisnecessary. Whensettingthepasscode,[SFT]isforpositionchange,[INC]isfornumberchange,and

    pressing[SET]twiceisforentrycompletion. Thedefaultpasscodeissetto“0000”whenshippedfromthefactory.

    F0214.ai

    Pass code **** 0000 0000 9999

    00 : 00

    SET SFT INC

    4) Whentheoperationlevelisdetermined,thescreenmovesto“Devicesetup”andswitchestoSettingMode.InSettingMode,parameterscanbeconfigured.

    5) Aftercompletingtheparametersettings,pressthe[ESC]switch.ThescreenwillreturntoDisplay Mode.

    IMPORTANT

    Menu pathDisplay Devicesetup►Easysetupwizard

    WhenparametersonthemenudescribedabovearesetintheWizardofEasysetup,besuretoexecute“Settingdownload”ineachmenuaftersettingtheparameters.If“Settingdownload”isnotexecuted,anychangedparameterswillnotbecorrectlyappliedtothedevice.

    NOTE

    Ifthereisnooperationfor10minutesinSettingMode,thescreengoesbacktoDisplayMode.

    Parameter formThefollowingthreeparameterformsareavailable.

    Type Example of display Description

    SelecttypeUnit m3 l(liter) cm3▲

    00 : 00

    SET SFT INC

    Selectstheadequatetypeofdatafromamongthepre-determinedalternatives.

    NumerictypeSpan +7200.00 +2200.00 +0.00001 +999999

    00 : 00

    SET SFT INC

    Specifiesthedatawithacombinationofnumberandadecimalpointforeachdigit.

    Alphanumerictype

    T0500_03.ai

    Tag No FT-1234 FT-1234

    00 : 00

    SET SFT INC

    Thedataisconfiguredwiththecombinationofalphanumericcharacters.(TagNo.,Specialunit,etc.)

    Thealphanumerictypedisplaysthefollowingalphanumericcharactersinorder.0123456789ABCDEFGHIJKLMNOPQRSTUVWXYZabcdefghijklmnopqrstuvwxyz!"#$%&'()*+,-./:;[email protected][\]^_`{|}~"space"

  • 17

    IM 01E22C02-01EN

    2.4 Parameter Setting from Display PanelThissectionexplainshowtospecifytheparametersfromthedisplaypanel.RefertoSection2.3,andsettheoperationlevelto“Specialist”.AlsoselectaparametertobespecifiedintheSettingMode.

    NOTE

    Theflowrateunit,spanflow,andtagNo.areexplainedasanexample.Ifaparticularparametersisspecifiedatthetimeofordering,thisproductisshippedwiththeparameterspecified.Ifaparameterisnotspecifiedatthetimeofordering,thatparameterneedstobesetbythecustomer.

    2.4.1 Setting Example of Select Type Parameter (Flow rate unit)

    ThefollowingistheprocedureofchangingtheflowrateunitfortheSelecttypeparameter.Thephysicalunitandtimeunitneedtobespecifiedindividuallyfortheflowrateunit.Whensettingthevolumetricflowrateunittol/min,set“l(liter)”tothephysicalunitand“/min”tothetimeunit.Thissettingcanbeconfiguredwiththefollowingparameters.Menu path

    Display Devicesetup►Detailedsetup►Provar►Volume►(seebelow)

    Parameter DescriptionUnit Specifiesthephysicalunitofthevolumetricflowrate.Timeunit Specifiesthetimeunitofthevolumetricflowrate.

    F0215.ai

    Volume Damp pls/ttl Unit Time unit

    00 : 00

    SET SFT INC

    Specifythephysicalunitforvolumetricflowrate.Movethecursorwith[INC]and[DEC]accordingtothemenupathdescribedabove,press[SET]todetermine,andselectthe“Unit”.

    F0216.ai

    Unit m3 l(liter) cm3▲

    00 : 00

    SET SFT INC

    Movethecursorwith[INC]and[DEC],press[SET]todetermine,andselectthe“l(liter)”.Whiletheselectedunitisblinking,press[SET]todeterminetheunit.Thescreenreturnstothesettingpageaftercompletingthesetting.

    F0217.ai

    Volume Unit Time unit Span

    00 : 00

    SET SFT INC

    Specifythetimeunitforvolumetricflowrate.Movethecursorwith[INC]and[DEC]accordingtothemenupathabove,press[SET]todetermine,andselectthe“Timeunit”.

    F0218.ai

    Time unit /s /min /h

    00 : 00

    SET SFT INC

    Movethecursorwith[INC]and[DEC],select“/min”,andthenpress[SET].Whiletheselectedunitisblinking,press[SET]todeterminetheunit.Thescreenreturnstothesettingpageaftercompletingthesetting.

    F0219.ai

    0.00000m/s0.00000l/min

    00 : 00PRV

    VEL

    FLBSET SFT INC

    Aftercompletingtheparametersetting,youcanreturnthescreentoDisplayModebypressing[ESC].

  • 18

    IM 01E22C02-01EN

    NOTE

    Besuretosettheflowrateunitfirstwhenchangingtheflowrateunitandflowspanvalueatthesametime.Whentheflowrateunitischanged,thespanflowrateisconvertedinconjunctionwiththechangedunit.

    2.4.2 Setting Example of Numeric Type Parameter (Flow rate span)

    Thefollowingistheprocedureofchangingtheflowratespanasnumerictypeparameter.Thissettingcanbeconfiguredwiththefollowingparameters.Menu path

    Display Devicesetup►Detailedsetup►Provar►Volume►Span

    NOTE

    Besuretosettheflowrateunitfirstwhenchangingtheflowrateunitandflowspanvalueatthesametime.Whentheflowrateunitischanged,thespanflowrateisconvertedinconjunctionwiththechangedunit.

    F0220.ai

    Volume Time unit /h Span +7200.00 Setting download

    00 : 00

    SET SFT INC

    Specifytheflowratespanunit.Movethecursorwith[INC]and[DEC]accordingtothemenupathabove,press[SET]todetermine,andselectthe“Span”.

    F0221.ai

    Span +7200.00 +2200.00 +0.00001 +999999

    00 : 00

    SET SFT INC

    Theswitch'sfunctionalityforsettingthespanflowrateisasbelow:Plus/minusandnumericchange:[INC]Movementofdigits:[SFT]Determinationofparameter:[SET]:Minimumvalue:Maximumvalue

    Press[SET]todeterminetheparameterwhilethesettingvalueoftheflowratespanisblinking.Thescreenreturnstothesettingpageaftercompletingthesetting.

  • 19

    IM 01E22C02-01EN

    2.4.3 Setting Example of Alphanumeric Type Parameter (Tag No.)

    ThefollowingistheprocedureofchangingtheTagNo.ofalphanumerictypeparameter.Thissettingcanbeconfiguredwiththefollowingparameters.Menu path

    Display Devicesetup►Detailedsetup►Deviceinfo►Orderinfo►TagNo

    F0222.ai

    Device info Date/Time Order info Ver/Num info

    00 : 00

    SET SFT INC

    SpecifytheTagNo..Movethecursorwith[INC]and[DEC]accordingtothemenupathabove,press[SET]todetermine,andselectthe“TagNo”.

    F0223.ai

    Tag No FT-1234 FT-1234

    00 : 00

    SET SFT INC

    TheTagNo.canbesetwithuptoeightcharactersfromthedisplay.Theswitch'sfunctionalityforsettingtheTagNo.isasfollows:Numberandcharacterchange:[INC]Movementofdigits:[SFT]Determinationofparameter:[SET]Availablecharacters:ASCIIcharactersPress[SET]todeterminetheparameterwhilethevalueofTagNo.isblinking.Thescreenreturnstothesettingpageaftercompletingthesetting.

  • 20

    IM 01E22C02-01EN

    2.5 microSD Card Insertion/RemovalIftheoptionalcodeMCisselected,theparametersettingcanbestoredintothededicatedmicroSDcardinsertedintothedisplayunit.Thestoreddatacanberestoredtothedevice.Fordetailedonthefunctions,refertoChapter4.

    WARNING

    UseonlyamicroSDcarddesignatedbyYOKOGAWA.Theoperationofthedevicecannotbeguaranteedwhenothercardsareused.

    (1) Insertion of microSD CardCarefullyinsertthededicatedmicroSDcardintotheslotonthedisplayuntiltheslotholdsthecard.(seeFigure2.5).

    22.000mA0.0%

    0.00000m/s 00 : 00

    VEL

    FLP

    AO1SET SFT INC

    F0224.ai

    microSD card

    Figure 2.5 Insertion of microSD Card

    (2) Removal of microSD CardRemovethemicroSDfromtheslotshowninFigure2.5.WhenremovingthemicroSDcard,select“Execute”fromthefollowingparameters.Menu path

    Display Devicesetup►microSD►Unmount

    IMPORTANT

    IfthemicroSDcardisremovedwithoutexecuting“Unmount”onthesoftware,itmaycausethestoreddatatobeerasedortheproducttooperateabnormally.

  • 21

    IM 01E22C02-01EN

    3. OperationwithBRAINConfigurationTool

    ThischapterdescribestheconnectionmethodofthisproductandBRAINconfigurationtool(BRAINTERMINAL(BT200)orFieldMate(VersatileDeviceManagementWizard)),andtheoperationmethodusingBT200.Readtheuser’smanualofBT200(IM01C00A11-01E)fordetailsabouttheBT200.Readtheuser’smanualofFieldMate(IM01R01A01-01E)fordetailsabouttheFieldMate.

    NOTEInthismanual,theoperationwiththeconfigurationtoolisexplainedusingthescreenofBT200forwhichlanguageissettoEnglish.

    3.1 ConnectingBRAINConfigurationToolInBRAINcommunication,thecommunicationsignalissuperimposedontothe4to20mADCanalogsignaltobetransmitted.TheBRAINconfigurationtoolcanbeconnectedtoanyrelayterminalintheinstrumentroomortransmissionloopforcommunication,providedthereistheminimumloadresistanceof250ΩbetweenthisproductandtheconnectionterminaloftheBRAINsettingtool.TheBRAINconfigurationtoolmustbeconnectedinparallelwiththisproductforcommunication,buttheconnectionisnotaffectedbythepolarity.SeeFigure3.1foraconnectionexample.

    4 to 20 mA DCSignal Transmission Line DistributorTerminalBoard

    BT200F0301.ai

    Iout+Iout-

    USBFieldMate

    Modem

    USB

    PC/FieldMate

    Magnetic FlowmeterTerminal Box

    Relaying Terminals

    Control Room

    LoadResistance

    250 to 450 Ω

    Figure3.1 ConnectingtheBRAINConfigurationTool

    IMPORTANTCommunicationsignalissuperimposedonoutputsignalatcommunication.Itisrecommendedtosetalow-passfilter(approximately0.1s)tothereceiverinordertoreducetheoutputeffectfromcommunicationsignal.Beforeonlinecommunication,confirmthatcommunicationsignaldoesnotgiveeffectonthehigh-levelsystem.

    IMPORTANTRestrictionsexistwithregardtothedistanceoverwhichcommunicationispossible.Readthegeneralspecifications.

  • 22

    IM 01E22C02-01EN

    AfterconnectingtheBT200,checkthatitoperatesproperly.(1) WhentheBT200isturnedon,themessage“Pleasewait..”.isdisplayedontheBT200

    screenforseveralseconds.Then,presstheEnterkey.

    (2) Theinitialdatascreenisdisplayed.Pressthefunctionkey“F4”[OK]ortheEnterkey.

    F0302.ai

    PARAM01:MODEL 02:TAG NO 03:SELF CHECK GOOD

    OK

    Initial data screen

    [01:MODEL]:Productmodelname[02:TAGNO]:TagNo.(ifspecifiedatordering)[03:SELFCHECK]:AbnormalitycheckforthisproductGOODorERROR

    (3) Whenthemenuscreenisdisplayed,theparameterscanbedisplayedandchangedusingtheBT200.

    IfthereisaprobleminthewiringsystemwiththeBT200,“communicationerror”isdisplayed.

    F0303.ai

    MENUA:DISPLAYB:EASY SETUPC:BASIC SETUPD:TOTAL SETE:PULSE OUTF:STATUS I/OHOME SET ADJ ESC

    communication error

    ESC

    Menu screen Communication error (Faulty wiring)

  • 23

    IM 01E22C02-01EN

    3.2 BT200 Operating Procedures3.2.1 Key Layout and Screen Display

    Alphanumeric keys• Enter numbers• Enter alphabetic

    characters in combination with the shift keys.

    F0304.ai

    Power ON/OFF key

    Shift keys

    Screen Display(21 characters × 8 lines)

    Movement keys• Move the cursor• Change pages

    Function keysUsed to execute commands displayed at the bottom of the screen.(See Table 3.2.)

    Enter key• Enter selected

    items• Set up input

    data on the connected instrument.

    • Run BT200 functions.

    F0305.ai

    Menu(Max: 6 lines)

    Menu screen

    Screen title Function commands

    Parameter(Max: 3 items)

    Function commands

    Parameter screen

    MENUA:DISPLAYB:EASY SETUPC:BASIC SETUPD:TOTAL SETE:PULSE OUTF:STATUS I/OHOME SET ADJ ESC

    PARAMA10:FLOW RATE(%) 0.0%A20:FLOW RATE 0.00000m3/hA21:FLW RATE(mA) 0.000mADATA DIAG PRNT ESC

  • 24

    IM 01E22C02-01EN

    3.2.2 Key DescriptionsUsethealphanumerickeysinconjunctionwiththeshiftkeystoenternumbers,symbols,andalphabeticcharacters.

    F0306.ai

    (1) Entering Numbers, Spaces and HyphenSimplypressthealphanumerickeystoinputkeys.

    Entry Key-in sequence

    –4

    0.3

    1 –9F0307.ai

    (2) Entering Alphabetic CharactersPresseithertheleftorrightshiftkeyandthenanalphanumerickeytoenterthedesiredalphabeticcharacter.

    Theshiftkeymustbepressedeachtimeanalphabeticcharacterisentered.

    Entry

    F0308.ai

    (3) Entering Uppercase and LowercaseThecasetogglesbetweenuppercaseandlowercaseeachtime“F2”[CAPS]ispressed.

    Entering lowercase CODE caps CLR ESC

    Entering uppercase CODE CAPS CLR ESC

    Entry

    F0309.ai

  • 25

    IM 01E22C02-01EN

    (4) Entering SymbolsPressthefunctionkey“F1”[CODE]toselectthefollowingsymbols.Thefollowingsymbolswillappearinsequence,oneatatime,atthecursoreachtime“F1”[CODE]ispressed:/.−,+*)(’&%$#"!Toentercharactersnexttothesesymbols,pressthemovementkeytomovethecursor.

    Entry Key-in Sequence

    F0310.ai

    3.2.3 Function KeysThefunctionsofthefunctionkeysdependonfunctioncommandsdisplayedonthescreen.

    F0311.ai

    Function commands

    Function keys

    MENUA:DISPLAYB:EASY SETUPC:BASIC SETUPD:TOTAL SETE:PULSE OUTF:STATUS I/OHOME SET ADJ ESC

    Table 3.2 Function CommandCommand Meaning

    ADJ DisplaystheADJmenuCAPS/caps ChangesthecasemodeCODE Selectssymbol/signCLR ErasesinputdataordeletesalldataDATA UpdatesparameterdataDEL DeletesonecharacterDIAG Callstheself-checkpanelESC ReturnstothemostrecentdisplayHOME DisplaysthemenupanelNO Resetting ReturntosettingscreenOK ProceedstothenextpanelPRAM EnterstheparameternumbersetupmodeSET DisplaystheSETmenuSLOT ReturnstotheslotselectionpanelUTIL Callstheutilitypanel*COPY Printsoutparametersondisplay*FEED Paperfeed*LIST Listsallparametersinthemenu*PON/POFF Automaticprintoutmodeonoroffforsettingchangedata*PRNT Changestotheprintmode*GO Startsprinting*STOP Cancelsprinting

    *: AvailableonBT200-P00(withprinter).

  • 26

    IM 01E22C02-01EN

    3.3 Calling Up Menu AddressesCalling-upmenuonthescreenisasfollows.Pressmovementkeystomovethecursor.Byusingthemovementkeyleftandright,anitemcanbemovedbyonescreen.

    "HOME" menu screen "SET" menu screen

    Utility screen

    Function screen

    "ADJ" menu screen

    [UTIL]

    [SET]

    [ESC]

    [ADJ]

    The utility screen contains the following items.1. ID settings for BT2002. Security code settings3. Selecting language of messages4. Display contrast settings for BT2005. Adjusting printout tone (BT200-P00 only)

    F0312.ai

    Startupscreen

    Initial datascreen

    Menuscreen

    Parameterscreen

    Setupscreen

    MENUA:DISPLAYB:EASY SETUPC:BASIC SETUPD:TOTAL SETE:PULSE OUTF:STATUS I/OHOME SET ADJ ESC

    MENUB:EASY SETUPC:BASIC SETUPD:TOTAL SETE:PULSE OUTF:STATUS I/OG:ANALOG I/OHOME SET ADJ ESC

    MENUL:DIAGNOSISM:TESTN:EVENT MANAGEP:PROTECT

    HOME SET ADJ ESC

    PARAMA10:FLOW RATE(%) 0.0%A20:FLOW RATE 0.00000m3/hA21:FLW RATE(mA) 0.000mADATA DIAG PRNT ESC

    PARAMB10:LANGUAGE EnglishB20:VOL DMP A/F 0.0sB21:VOL DMP P/T 0.0sDATA DIAG PRNT ESC

    PARAML10:ADHESION CHK EnableL11:ADH LEVEL1 0.10MohmL12:ADH LEVEL2 0.50MohmDATA DIAG PRNT ESC

    SETL10:ADHESION CHK Enable

    ESC

    FUNC1.MENU2.UPLOAD TO HHT3.DOWNLOAD TO INST4.PRINT ALL DATA

    HOME SET ADJ

    UTILITY1.ID2.SECURITY CODE3.LANGUAGE SELECT4.LCD CONTRAST5.PRINTER ADJUST

    ESC

    PARAM01:MODEL 02:TAG NO

    03:SELF CHECK GOOD

    OK

    --WELCOME--BRAIN TERMINAL ID:

    check connectionpush ENTER key

    UTIL FEED

    SETB10:LANGUAGE English

    ESC

  • 27

    IM 01E22C02-01EN

    3.4 Parameter Update and Upload/ Download Function

    (1) Updating ParametersThedisplayoftheparametersisupdatedautomaticallyeverysevenseconds.Forthefollowingparameters,refertothefollowingtable.

    Item Name Item NameA10 FLOWRATE(%) I54 ALMRECORD3A20 FLOWRATE I55 ALMTIME3A21 FLWRATE(mA) I56 ALMRECORD4A30 TOTAL1 I57 ALMTIME4A31 TOTAL2 K02 OPERATETIMEA32 TOTAL3 K03 CURDATEA33 TOTAL1CNT K04 CURTIMEA34 TOTAL2CNT L16 ADHMEASVALA35 TOTAL3CNT L17 ADHSTATUSC40 VELOCITYCHK L25 FLNOISEVALF14 SI3STATE L26 FLNOISESTSG23 AIVALUE L31 CONDUCTIVITYH22 IEXPWRFREQ L40 VPEAKHOLDH23 MESPWRFREQ L41 IEXCOILRH37 MEASTEMP L42 ELECVOLAH38 CORRCTDENS L43 ELECVOLBH42 CALVALUE L44 EMPTYSTSI50 ALMRECORD1 N21 RESTORERSLTI51 ALMTIME1 P20 WRTPROTECTI52 ALMRECORD2 P23 SOFTSEALI53 ALMTIME2

    (2) Upload/Download FunctionTheuploadfunctionisusedforcopyingtheparametersofthisproducttoBT200.ThedownloadfunctionisusedforsettingthecopiedparametersintheBT200intootherproduct.Forthefollowingparameters,refertothefollowingtable.

    Item Name Item NameB10/J32 LANGUAGE B31/E14 P1RATEVALB20/C12 VOLDMPA/F B32/E17 F1AT0%B21/C13 VOLDMPP/T B33/E18 F1AT100%B22/C32 VOLFUNIT B40/J10 LINE1 SELB23/C35 TIMEUNIT B41/J11 LINE2 SELB24/C36 VOLFSPAN B42/J12 LINE3 SELB30/E13 P1RATEUNIT B50/C51 AUTOZEROEXE

  • 28

    IM 01E22C02-01EN

    3.5 ParameterConfigurationThissectiondescribesproceduresforsettingparametersusingtheBT200.

    IMPORTANTDonotturnofftheproductrightafterchangingparameterwiththeBT200.Ifthisproductisturnedoffbefore30secondsaftersettingtheparameters,thesettingswillnotbestoredcorrectly.Pleasekeeptheproductturnedonforover30secondsaftersettingtheparameters.

    IMPORTANTBesuretoenablethewriteprotectfunctiontopreventparametersfrombeingoverwrittenafterfinishingparametersetting.RefertotheInstallationManualforthehardwarewriteprotectfunction,andSection4.14forthesoftwarewriteprotectfunction.

    NOTEBeforeupdatinganysetting,refertoChapter5andchecktheparametercontentyouwanttochange.

    3.5.1 Setting Example of Select type Parameter (Flow Rate Unit)

    With[B22:VOLFUNIT]oftheselecttypeparameter,changetheflowrateunitfromm3tol(liter).

    (1) Movefrom[B:EASYSETUP]to[B22:VOLFUNIT].(2) Movetothesetupscreen,selecttheflowrateunit.Movethecursorto[l(liter)],andpress

    theEnterkey. Whentheselectedunitblinks,presstheEnterkeytodetermine.

    F0313.ai

    SETB22:VOL F UNIT m3

    ESC

    (3) Theflowrateunitisnowchangedto“l(liter)”.Pressthefunctionkey“F4”[OK],andthenthescreenisbacktotheparameterscreen.Pressthefunctionkey“F3”[NO],andthenthescreenisbacktothesetupscreen.

    F0314.ai

    SETB22:VOL F UNIT l(liter)

    FEED NO OK

  • 29

    IM 01E22C02-01EN

    3.5.2 Setting Example of Numeric Type Parameter (Flow rate span)

    With[B24:VOLFSPAN]ofthenumeric-typeparameter,changetheflowratespanfrom“100.000l/min”to“120.000l/min”.

    (1) Movefrom[B:EASYSETUP]to[B24:VOLFSPAN].(2) Movetothesetupscreen,andentertheflowspanvalue.Enterthevalue“120.000”,and

    presstheEnterkey.Whentheenteredvalueblinks,presstheEnterkeytodetermine.

    F0315.ai

    SETB24:VOL F SPAN 100.000l/min +120.000

    DEL CLR ESC

    (3) Theflowspanisnowchangedto“120.000l/min”.Pressthefunctionkey“F4”[OK],andthenthescreenisbacktotheparameterscreen.Pressthefunctionkey“F3”[NO],andthenthescreenisbacktothesetupscreen.

    F0316.ai

    SETB24:VOL F SPAN 120.000l/min

    FEED NO OK

    3.5.3 Setting Example of Alphanumeric type Parameter (Tag No.)

    With[K01:TAGNO]ofthealphanumerictypeparameter,changeTagNo.from“F-123”to“F-456”.

    (1) Moveto[K:DEVICEINFO]->[K01:TAGNO].(2) Movetothesetupscreen,andentertheTagNo.Enterthealphanumericcharacter“F-456”,

    andpresstheEnterkey.Whenenteredthealphanumericcharacterblinks,presstheEnterkeytodetermine.

    F0317.ai

    SETK01:TAG NO F-123 F-456

    CODE CAPS CLR ESC

    (3) TheTagNo.isnowchangedto“F-456”.Pressthefunctionkey“F4”[OK],andthenthescreenisbacktotheparameterscreen.Pressthefunctionkey“F3”[NO],andthenthescreenisbacktothesetupscreen.

    F0318.ai

    SETK01:TAG NO F-456

    FEED NO OK

  • 30

    IM 01E22C02-01EN

    4. FunctionsThischapterdescribesthefunctionsoftheproduct.Followingisanoverviewofeachfunction.

    Basic settingsThisproductcanmeasuretheprocessvaluesoftheflowvelocity,volumetricflowrate,massflowrate,calorie,andflownoiseatthesametime.Adampingtimeconstantcanbespecifiedforeachprocessvalue.Fordetailsabouthowtocheckmeasuredresultsandthesettingprocedure,refertoSection4.1.

    Totalization functionThisproducthasthreetotalizersfortotalizingselectedprocessvalues.Inadditiontothetotalizedvaluedisplayfunction,theproducthasatotalizationcounterfunctiontoscaletotalizedvalueswiththeconversionfactorandtocountaspecificflowrate.Theproductalsohasatotalizationswitchfunctionthatcomparesaspecifiedtargetvaluewithatotalizedvaluetooutputtheresultintheformofthestatusoutput,andatotalizationpresetfunctionthattotalizationstartsfromavaluesetinadvance.Fordetailsaboutthetotalizationfunctionandsettingprocedures,refertoSection4.2.

    Pulse output, Frequency output, and Status outputAmeasurementresultcanbeoutputaspulseoutput,frequencyoutput,orstatusoutput.Whenapulseoutputisused,thepulsewidthorpulseratecanbeselected.Whenafrequencyoutputisused,outputsat0%and100%forthespanoftheprocessvaluecanbespecified.Whenastatusoutputisused,theproductstatuscanbeoutputasastatusoutput.Forbothpulseoutputandfrequencyoutput,thelow-cutvaluescanbeset.Fordetailsabouteachoutputandthesettingprocedure,refertoSection4.3.

    Status inputSincethisproducthasastatusinputterminal,thetotalizerpresetfunctionandzeroadjustmentfunction,etc.canbeusedinresponsetothestatusinputfromtheoutside.Fordetailsaboutthesettingprocedureofthesefunctions,refertoSection4.4.

    Analog output/Analog inputUptotwoanalogoutputsareavailable.Thehigh/lowlimitfunction,forward/reverseflowratefunction(reverseflowrate:4to12mA,forwardflowrate:12to20mA),alarmoutputfunction,low-cutfunctionandotherfunctionsareavailable.Analoginputisusefulforinputtingfluidtemperatureviaanexternaltemperaturetransmitter.Fordetailsaboutsettingproceduresfortheanalogoutputandanaloginput,refertoSection4.5.

    Multi range functionThemultirangefunctionmakesitpossibletomeasureaflowratewhileswitchingmultipleranges.Arangecanbeswitchedinresponsetoaflowrate,flowdirection,andstatusinput.Fordetailsaboutthemultirangefunction,refertoSection4.6.

    Auxiliary calculation functionThisfunctionisusedtocalculatethetemperaturecorrectionfordensityorcaloriebyinputtingthetemperaturefromanexternaldeviceintheformofananaloginput.Theaccuracyofmassflowratemeasurementisimprovedbysettingthetemperaturecorrectionfordensity.Fordetailsabouttheauxiliarycalculationfunction,refertoSection4.7.

  • 31

    IM 01E22C02-01EN

    AlarmAdetectederrorcanbenotifiedasanalarmorwarning.ThisfunctioncanshowtheerrorstatusbasedinaccordancewithNAMURNE107tosuitparametersettings.Itisalsopossibletorecordalarmsthatoccurredinthepastinthehistoryandmaskunnecessarysothattheyarehiddenonthedisplay.Fordetailsaboutcontentsandsettingprocedures,refertoSection4.8.

    DisplayThisdisplaysupportsmultiplelanguagesforuseonthedisplay.Thisfunctioncanalsoshowthetimechangesoftheselectedparameterinatrendgraphonthedisplay.Fordetailsaboutdisplaysettings,refertoSection4.9.

    NOTEThelanguageonthedisplayissetto“English”asdefaultatfactoryshipment.Ifnecessary,refertoSubsection4.9.1toselecttheadequatelanguage.Themenupassofthedisplayonthismanualissetto“English”.

    Device informationWiththisfunction,theparametersspecifiedatthetimeoforder,modelcode,andsuffixcodeofthisproductcanbecheckedonthedisplay.Fordetailsabouthowtocheckthedeviceinformation,refertoSection4.10.

    Self-diagnostic functionTheself-diagnosticfunctioncanbeusedtodiagnosefailuresoftheproductortheprocessstate.Forexample,thisfunctionisusefulfordiagnosingthehealthoftheproductbyusingtheelectrodeadhesiondetectingfunction,sensoremptycheckfunction,orverificationfunction.Fordetailsaboutthevariousself-diagnosticfunctions,refertoSection4.11.

    Test modeWiththismode,theprocessvalueandthevalueoutputfromaconnectionterminalcanbearbitrarilyspecifiedtotestaresponsefromthedevice.Fordetailsaboutthetestmode,refertoSection4.12.

    Backup, Restore, and Duplicate of ParameterThebackupfunctioncanstoresettingsoftheparametersintothebuilt-inmemoryinthedisplay.IftheoptionalcodeMCisselected,settingparametersarestoredinthemicroSDcardsuppliedwiththisproductinadditiontothebuilt-inmemoryinthedisplay(displayboard).Thebackupdatacanbeusedtorestoresettingsoftheproductforwhichdataisbackeduporduplicatesettingstoanotherproduct.Fordetailsaboutthebackup,restore,andduplicatefunctions,refertoSection4.13.

    Software write protection functionAwriteprotectcanbechangedusingthehardwarewriteprotectionswitchandtheparametersettings(softwarewriteprotection).Fordetailsaboutthehardwarewriteprotectionswitch,refertotheInstallationManual.Fordetailsaboutthesoftwarewriteprotectionfunction,refertoSection4.14.

  • 32

    IM 01E22C02-01EN

    4.1 Basic Settings4.1.1 Overview

    Thisproductcanmeasureflowvelocity,volumetricflowrate,massflowrate,calorie,andflownoiseatthesametime.Ameasuredresultcanbeoutputasananalogoutput,frequencyoutput,pulseoutput,andstatusoutput.Refertothetablebelowforcodesandconnectionterminalsofcommunication/input-outputandinputandoutputforeachterminal.

    Communicationand I/O Code Connection Terminal

    BRAIN Iout1 +/- P/Sout1 +/- ALM +/- So11 +So12 +Si11 +Si12 + MIO +/-

    D0

    Iout1(Active)

    P/Sout1(Passive)

    AlarmOutput(Passive)

    Sout1,2(Passive)

    Sin1,2(No-

    voltage)

    -

    D2 Iin(Active)

    D3 P/Sout2(Passive)

    D4P/Sout2(Active,

    withoutinternalresistor)

    D5P/Sout2(Active,

    withinternalresistor)

    D6 Iout2(Active)

    Iout1:Analogoutput1(BRAINcommunicationsignalsuperimposed)Iout2:Analogoutput2Iin:AnaloginputP/Sout1:Pulse/Statusoutput1P/Sout2:Pulse/Statusoutput2Sout1,2:Statusoutput1,2Sin1,2:Statusinput1,2ThepositionofCommunicationandI/Ocode:AXG1A-□□□□□□□■■□□

    NOTEAvailablefunctionsvarydependingontheconnectionterminaltypespecifiedatthetimeoforder.Beforeusingeachfunctionofthisproduct,besuretochecktheterminaloftheproductwiththetableabove.

  • 33

    IM 01E22C02-01EN

    4.1.2 PV Mapping of Process ValueTheflowvelocity,volumetricflowrate,massflowrate,andflownoisecanbemappedtotheprimaryvariable(PV).Thissettingcanbeconfiguredwiththefollowingparameters.Menu path

    Display Devicesetup►Detailedsetup►Provar►PVflowselectBRAIN C:BASICSETUP►C30:PVFLOWSEL

    Selection DescriptionDisplay BRAINVelocity Velocity SpecifiestheflowvelocitytothePrimaryValue.

    Volume Volume SpecifiesthevolumetricflowratetothePrimaryValue.Mass Mass SpecifiesthemassflowratetothePrimaryValue.Diag Diag SpecifiestheflownoisetothePrimaryValue.

    Settingexample:IfthevolumetricflowrateissettoPV,andthevolumetricflowratespanissetto100m3/hforuse,settheparametersasfollows. C30:PVFLOWSEL=“Volume” C32:VOLFUNIT=“m3” C35:TIMEUNIT=“/h” C37:VOLFSPAN=“100”

    Settingexample:IfthemassflowrateissettoPV,withthemassflowratespanbeingsetto10,000kg/handthedensityto1000kg/m3foruse,settheparametersasfollows. H31:DENSITYUNIT=“kg/m3” H32:FIXEDDENS=“1000” C30:PVFLOWSEL=“Mass” C33:MASSFUNIT=“kg” C35:TIMEUNIT=“/h” C38:MASSFSPAN=“10000”

    4.1.3 Display of the Process ValueTheflowvelocity,volumetricflowrate,massflowrate,totalizedvalue,calorie,andflownoisecanbecheckedwiththefollowingparameters.

    Flow rate (PV)Menu path

    Display Devicesetup►Processvariables►(seebelow)BRAIN A:DISPLAY►(seebelow)

    Parameter DescriptionDisplay BRAIN

    Flowrate(%) FLOWRATE(%) DisplaysthepercentagetotherangefortheprocessvaluesettothePrimaryValue.Flowrate FLOWRATE DisplaystheprocessvaluesettothePrimaryValue.

  • 34

    IM 01E22C02-01EN

    Flowvelocity,Volumetricflowrate,Massflowrate,Totalizedvalue,Calorie

    Menu pathDisplay Devicesetup►Processvariables►(seebelow)BRAIN A:DISPLAY►(seebelow)

    Parameter DescriptionDisplay BRAINVelocity (*) Displaystheflowvelocity.Volume (*) Displaysthevolumetricflowrate.Mass (*) Displaysthemassflowrate.Totalizer►Totalizer1 TOTAL1 Displaysthetotalizedvalueoftotalizer1.Totalizer►Totalizer2 TOTAL2 Displaysthetotalizedvalueoftotalizer2.Totalizer►Totalizer3 TOTAL3 Displaysthetotalizedvalueoftotalizer3.Calorie (*) Displaysthecalorie.

    (*) OnlytheprocessvalueselectedwithC30:PVFLOWSELcanbecheckedfromBRAINcommunication.

    Flow noiseMenu path

    Display Devicesetup►Diag/Service►Diagnosis►Flownoise►Result►ValueBRAIN L:DIAGNOSIS►L25:FLNOISEVAL

    Thisparameterdisplaystheflownoise.

    4.1.4 Unit SettingUnitscanbespecifiedfortheflowvelocity,volumetricflowrate,massflowrate,andcalorie.Eachflowrateunitcanbespecifiedwiththephysicalunitandthetimeunit,individually.However,notethatthetimeunitiscommontoallflowrates.Also,theunitoftheflowvelocityisfixedto“cm/s”anditcannotbechanged.

    Example)Tosetthevolumetricflowrateunitto“m3/h”Thevolumetricunitcanbesetto“m3/h”andthetimeunitto“/h”.Atthistime,thetimeunitforthemassflowrateandcaloriearealsosetto“/h”.

    Thissettingcanbeconfiguredwiththefollowingparameters.

    Physical unitMenu path

    Display Devicesetup►Detailedsetup►Provar►(seebelow)BRAIN C:BASICSETUP►(seebelow)

    Parameter DescriptionDisplay BRAINVelocity►Unit C31:VELOFUNIT Specifiesthephysicalunitoftheflowvelocity.

    Volume►Unit C32:VOLFUNIT Specifiesthephysicalunitofthevolumetricflowrate.Mass►Unit C33:MASSFUNIT Specifiesthephysicalunitofthemassflowrate.Calorie►Unit C34:CALUNIT Specifiesthephysicalunitofthecalorie.

  • 35

    IM 01E22C02-01EN

    Time unitMenu path

    Display Devicesetup►Detailedsetup►Provar►(seebelow)BRAIN C:BASICSETUP►(seebelow)

    Parameter DescriptionDisplay BRAINVolume►Timeunit C35:TIMEUNIT Specifiesthetimeunitofthevolumetricflowrate.Mass►Timeunit C35:TIMEUNIT Specifiesthetimeunitofthemassflowrate.Calorie►Timeunit C35:TIMEUNIT Specifiesthetimeunitofthecalorie.

    4.1.5 Span SettingAspancanbespecifiedfortheflowvelocity,volumetricflowrate,massflowrate,calorie,andflownoise.However,theunitforthespanisthesameastheunitspecifiedinSubsection4.1.4.Iftheunitischanged,thespanvalueisconvertedtomatchthechangedunit.Thissettingcanbeconfiguredwiththefollowingparameters.

    Flowvelocity,Volumetricflowrate,Massflowrate,CalorieMenu path

    Display Devicesetup►Detailedsetup►Provar►(seebelow)BRAIN C:BASICSETUP►(seebelow)

    Parameter DescriptionDisplay BRAINVelocity►Span C36:VELOFSPAN Specifiesthespanoftheflowvelocity.Volume►Span C37:VOLFSPAN Specifiesthespanofvolumetricflowrate.Mass►Span C38:MASSFSPAN Specifiesthespanofthemassflowrate.Calorie►Span C39:CALFSPAN Specifiesthespanofthecalorie.

    Flow noiseMenu path

    Display Devicesetup►Diag/Service►Diagnosis►Flownoise►SpanBRAIN L:DISGNOSIS►L28:FLNOISESPN

    Thisparameterspecifiesthespanoftheflownoise.

    NOTEBesuretonotethefollowingpointswhenspecifyingtheflowratespan.• Foralinewithasignificantflowchange,settheflowratespantothemaximumflowrate.If

    theflowrateexceedstheflowratespan,theerroroftheflowrate%increases.• Foralinewithastableflowrate,settheflowratespantoapproximately1.5to2.0timesthe

    normalflowrate.• Settheflowrateforwhichtheflowvelocityiscomparabletotherangefrom0.3to10

    m/s.Theflowvelocitycanbecheckedusingthesizingdatadescribedinthegeneralspecifications.Whentheflowvelocityischeckedusingtheparameter,itdisplaysthevalueobtainedbyconvertingthespecifiedflowratespantotheflowvelocity.

  • 36

    IM 01E22C02-01EN

    NOTEBesuretosettheflowrateunitfirstwhenthespanvalueanditsflowrateunitarechangedatthesametime.

    4.1.6 Damping Time Constant SettingThedampingtimeconstant(63.2%response)canbespecifiedfortheflowvelocity,volumetricflowrate,massflowrate,calorie,andflownoise.Toreduceanoutputfluctuationorchangetheresponsespeed,changethedampingtimeconstant(defaultvalueis3.0seconds).Itispossibletomeasureapulsingflowofupto1Hzwithanoutputdampingof0.1secondsforapistonpump,etc.Thedampingtimeconstantcanbesetfortheoutputofeachprocessvalue.Thedampingtimeconstantisacommonsettingfortheanalogoutput,frequencyoutput,pulseoutput,andtotalizedvalue.However,thedampingsettingfortheflownoiseiscommontoalloutputs.Thissettingcanbeconfiguredwiththefollowingparameters.

    Analog output/Frequency outputMenu path

    Display Devicesetup►Detailedsetup►Provar►(seebelow)BRAIN C:BASICSETUP►(seebelow)

    Parameter DescriptionDisplay BRAIN

    Velocity►DampAO/F C10:VELODMPA/F Specifiesthedampingtimeconstantoftheflowvelocity.

    Volume►DampAO/F C12:VOLDMPA/F Specifiesthedampingtimeconstantofthevolumetricflowrate.

    Mass►DampAO/F C14:MASSDMPA/F Specifiesthedampingtimeconstantofthemassflowrate.Calorie►DampAO/F C16:CALDMPA/F Specifiesthedampingtimeconstantofthecalorie.

    Pulse output/TotalizerMenu path

    Display Devicesetup►Detailedsetup►Provar►(seebelow)BRAIN C:BASICSETUP►(seebelow)

    Parameter DescriptionDisplay BRAIN

    Velocity►Damppls/ttl C11:VELODMPP/T Specifiesthedampingtimeconstantoftheflowvelocity.

    Volume►Damppls/ttl C13:VOLDMPP/T Specifiesthedampingtimeconstantofthevolumetricflowrate.

    Mass►Damppls/ttl C15:MASSDMPP/T Specifiesthedampingtimeconstantofthemassflowrate.Calorie►Damppls/ttl C17:CALDMPP/T Specifiesthedampingtimeconstantofthecalorie.

  • 37

    IM 01E22C02-01EN

    Flow noiseMenu path

    Display Devicesetup►Diag/Service►Diagnosis►Flownoise►DampBRAIN L:DIAGNOSIS►L27:FLNOISEDMP

    Thisparameterspecifiesthedampingtimeconstantoftheflownoise.

    NOTETheoutputfluctuationincreasesifthedampingtimeconstantissettoalowervalue.Setthedampingtimeconstantto5secondsorlongerforcontrolprocessingapplication.

    4.1.7 Low-cut Function SettingAlow-cutvaluecanbespecifiedfortheanalogoutput,frequencyoutput,pulseoutput,andtotalizeroutputvalue.Ifthelow-cutfunctionisused,theflowratebelowsetvaluescanbestoppedfrombeingoutput.Thisfunctionhelpsreduceerroneousoutputwhentheflowis“0”.However,theunitofthelow-cutvalueisthesameastheunitspecifiedinSubsection4.1.4.Iftheunitischanged,thelow-cutvalueischangedtomatchthechangedunit.Thelow-cutvalueisnotsynchronizedwiththespanvalue.Ifthespanvalueischanged,besuretoresetthelow-cutvalue.Setthelow-cutvalueto“0”ifthelow-cutfunctionisnotused.Thissettingcanbeconfiguredwiththefollowingparameters.

    Analog outputMenu path

    Display Devicesetup►Detailedsetup►Analogout/in►(seebelow)BRAIN G:ANALOGI/O►(seebelow)

    Parameter DescriptionDisplay BRAIN

    AO1►Lowcut G01:AO1LOWCUTSpecifiesthelow-cutvalueofanalogoutput1.IfPVissetforthemeasurementscreenonthedisplay,aPVvaluewhichislow-cutwiththevaluesethereisdisplayed.

    AO2►Lowcut G11:AO2LOWCUT Specifiesthelow-cutvalueofanalogoutput2.

    Frequency output/Pulse outputMenu path

    Display Devicesetup►Detailedsetup►Pulse/Statusout►(seebelow)BRAIN E:PULSEOUT►(seebelow)

    Parameter DescriptionDisplay BRAIN

    PO1/SO1►Lowcut E15:P1LOWCUT Specifiesthelow-cutvaluesoffrequencyoutput1andpulseoutput1.

    PO2/SO2►Lowcut E37:P2LOWCUT Specifiesthelow-cutvaluesoffrequencyoutput2andpulseoutput2.

  • 38

    IM 01E22C02-01EN

    TotalizerMenu path

    Display Devicesetup►Detailedsetup►Totalizer►(seebelow)BRAIN D:TOTALSET►(seebelow)

    Parameter DescriptionDisplay BRAINTotalizer1►Lowcut D12:TOT1LOWCUT Specifiesthelow-cutvalueoftotalizer1.Totalizer2►Lowcut D22:TOT2LOWCUT Specifiesthelow-cutvalueoftotalizer2.Totalizer3►Lowcut D32:TOT3LOWCUT Specifiesthelow-cutvalueoftotalizer3.

    Theactualvalueforwhichthelow-cutiseffectivehas±0.5%ofthehysteresisfromthesetlow-cutvalue.Thehysteresiswidthonthenegativeside(goingintothelow-cutWhenflowrateisdecreasing)andthepositiveside(goingoutoflow-cut.Whenflowrateisincreasing)areasfollows:(1) Negativeside

    =Low-cutsetvalue–(Minimumspansetwithmultirange×0.5%)

    (2) Positiveside

    =Low-cutsetvalue+(Minimumspansetwithmultirange×0.5%)

    Example:Whensettingtospanofvolumetricflowrate=10.0m3/h, Low-cutvalue=1.0m3/h

    (1) Negativeside

    =1.0[m3/h]–(10.0[m3/h]×0.5[%])

    =0.95[m3/h]

    (2) Positiveside

    =1.0[m3/h]+(10.0[m3/h]×0.5[%])

    =1.05[m3/h]

    Inthiscase,whentheflowrateisdecreasing,theoutputflowratevaluebecomes0.0[m3/h]withthelow-cutfunctioniftheactualflowrategoesbelow0.95[m3/h].Ontheotherhand,whentheflowrateisincreasing,theflowratevalueisoutputiftheactualflowrategoesover1.05[m3/h].

    F0401.ai0

    Output [m3/h]

    1

    Hysteresis1 %

    Input [m3/h]1

    (1)

    (2)

    1.050.95

  • 39

    IM 01E22C02-01EN

    NOTENotethatthetotalizationmightbecountedduetotheinfluenceoftheoutputfluctuationnear0%outputifasmalllow-cutvalueisset.Inparticular,ifthevalueoftheflowratespan,dampingtimeconstant,orconductivityislow,thetotalizationiseasilycountedwhentheflowrateis“0”.Insuchacase,increasetheflowratespan,dampingtimeconstant,orlow-cutvalue.

    NOTEWhenchangingtheoutputprocessvaluetobeoutput,itisnecessarytospecifythelow-cutvalueagain.

    4.1.8 Meter factor SettingWhenorderingonlyAXG1A,orwhenchangingtheremotesensortocombinewith,themeterfactoroftheremotesensormustbespecified.Thissettingcanbeconfiguredwiththefollowingparameters.WhenthecustomerordersAXG1Aandtheremotesensoratthesametimeasacombination,themeterfactoroftheremotesensortocombinewithissettoAXG1A.So,thecustomerisnotrequiredtosetthemeterfactor.Menu path

    Display Devicesetup►Detailedsetup►Sensor►(seebelow)BRAIN C:BASICSETUP►(seebelow)

    Parameter DescriptionDisplay BRAINLowMF C20:LOWMF Specifiesthemeterfactorofthelow-frequencyside.

    HighMF C21:HIGHMF Specifiesthemeterfactorofthehigh-frequencyside.

    NOTEThemeterfactorisdescribedintheMETERFACTORcolumnontheremotesensornameplate.

    Example:

    F0445.ai

  • 40

    IM 01E22C02-01EN

    4.1.9 Sensor Type SettingWhenonlyAXG1Aisordered,orwhentheremotesensortocombinewith,thetypeoftheremotesensormustbespecified.Thissettingcanbeconfiguredwiththefollowingparameters.WhenthecustomerordersAXG1Aandtheremotesensoratthesametimeasacombination,thetypeoftheremotesensortocombinewithissettoAXG1Aatthefactorybeforeshipment.So,thecustomerisnotrequiredtosetthesensortype.Menu path

    Display Devicesetup►Detailedsetup►Sensor►FlowsensorselBRAIN C:BASICSETUP►C24:FLOWSNSOR

    Fromthetablebelow,selectthesensortype.Selection DescriptionDisplay BRAIN

    ADMAGAXG ADMAGAXG ConfiguretousetheADMAGAXGSeriesremotesensor.

    ADMAGAXW ADMAGAXW ConfiguretousetheADMAGAXWSeriesremotesensor.

    ADMAGAXF ADMAGAXF ConfiguretousetheADMAGAXFSeriesremotesensor.ADMAG ADMAG ConfiguretousetheADMAGSeriesremotesensor.

    ADMAGAE ADMAGAE ConfiguretousetheADMAGAESeriesremotesensor.

    ADMAGSE ADMAGSE ConfiguretousetheADMAGSESeriesremotesensor.

    YEWMAG YEWMAG ConfiguretousetheYEWMAGSeriesremotesensor.Calibrator Calibrator ConfiguretousetheAM012(calibrator).Other1 Other1

    Configuretouseanotherremotesensor.Other2 Other2Other3 Other3

    IMPORTANTWhenchangingthecombinationofthesensors,themeterfactorneedstobere-adjustedbasedonactualflowcalibrationtosecuretheaccuracy.Whenusinganotherremotesensor,suchasothercompanies'products,contactaYokogawasalesofficeorrepresentative.

  • 41

    IM 01E22C02-01EN

    4.1.10 Sensor’s Nominal Size SettingWhenonlyAXG1Aisordered,orwhenchangingtheremotesensortocombine,thenominalsizeoftheremotesensormustbespecified.Thissettingcanbeconfiguredwiththefollowingparameters.WhenthecustomerordersAXG1Aandtheremotesensoratthesametimeasacombination,thenominalsizeoftheremotesensortocombinewithissettoAXG1Aatthefactorybeforeshipment.So,thecustomerisnotrequiredtosetthenominalsize.Menu path

    Display Devicesetup►Detailedsetup►Sensor►(seebelow)BRAIN C:BASICSETUP►(seebelow)

    Parameter DescriptionDisplay BRAINNominalsizeunit C26:SIZEUNIT Specifiestheunitofthenominalsize.Nominalsize C27:NOMINALSIZE Specifiesnominalsize.

    4.1.11 Density SettingThedensitymustbesetinordertomeasurethemassflowrate.Thedensitycanbeselectedfromthedensitycompensatedwithfixeddensityordensitycorrectedbytemperature.Fordetailsabouthowtomeasurethemassflowrateorcorrectthedensitybytemperature,refertoSubsection4.7.5.Ifdensityissetto“0”whilethemassflowrateismappedtoPV,asettingerrorwillresult.Thissettingcanbeconfiguredwiththefollowingparameters.Menu path

    Display Devicesetup►Detailedsetup►Provar►Density►(seebelow)BRAIN H:AUXCALC►(seebelow)

    Parameter DescriptionDisplay BRAIN

    Valueselect H30:DENSITYSELSelectsoneofthetemperature-baseddensitycorrectionsfromthefollowing.• Fixedvalue :Usesthefixeddensity• Correctionvalue:Usesthecorrecteddensity

    Unit H31:DENSITYUNIT Specifiestheunitofthedensity.Fixeddensity H32:FIXEDDENS Specifiesthevalueofthefixeddensity.

    Std density H33:STDDENSITYSpecifiesthereferencedensityvalueofthestandardconditionwhenusingthedensitycompensatedwithtemperature.

    Correctdensity H38:CORRCTDENS Displaysthecorrecteddensity.

  • 42

    IM 01E22C02-01EN

    4.1.12 Temperature SettingThetemperaturesettingisrequiredwhencalculatingthecaloriebasedonthisvalue’sdifferencefromthetemperaturethatisinputviatheanaloginputprocess.Fordetailsaboutthecaloriecalculation,refertoSubsection4.7.6.Thissettingcanbeconfiguredwiththefollowingparameters.Menu path

    Display Devicesetup►Detailedsetup►Provar►Temperature►(seebelow)BRAIN H:AUXCALC►(seebelow)

    Parameter DescriptionDisplay BRAIN

    Stdtemperature H34:STDTEMPSpecifiesthereferencestandardtemperatureforusingthetemperature-baseddensitycorrectionfunction.

    Meastemperature H37:MEASTEMP Displaysthetemperaturethatisinputfromanaloginput.

    Fixedtemperature H41:CALFIXTEMPSpecifiesthereferencetemperaturetouseforthecaloriecalculationwiththetemperaturedifferencefromthetemperaturewhichisinputfromanaloginput.

    4.1.13 Span Flow Velocity DisplayThespanofthePV-mappedprocessvalueinSubsection4.1.2canbedisplayedintheflowvelocityunit.Thisinformationcanbeviewedwiththefollowingparameters.Menu path

    Display Devicesetup►Detailedsetup►Provar►VelocitycheckBRAIN C:BASICSETUP►C40:VELOCITYCHK

  • 43

    IM 01E22C02-01EN

    4.1.14 User Span FunctionTheuserspanfunctioncandisplayaprocessvalueassignedtoanalogoutput1andanalogoutput2withthecustomer’sdesiredspecialunit.Ifthesameprocessvalueisassignedtobothanalogoutputs,thesettingforanalogoutput1takesprecedence.Thissettingcanbeconfiguredwiththefollowingparameters.

    Using user spanMenu path

    Display Devicesetup►Detailedsetup►UserSpan►(seebelow)BRAIN C:BASICSETUP►(seebelow)

    Parameter DescriptionDisplay BRAINUserspanAO1►Select C41:USRSPNSEL1

    Specifiestheuserspanfunctiontotheprocessvalueallocatedtoanalogoutput1.

    UserspanAO2►Select C44:USRSPNSEL2

    Specifiestheuserspanfunctiontotheprocessvalueallocatedtoanalogoutput2.

    From the table below, select the user span function.Selection DescriptionDisplay BRAIN

    No No Notusinguserspanfunction.Yes Yes Usinguserspanfunction.

    User unit settingMenu path

    Display Devicesetup►Detailedsetup►UserSpan►(seebelow)BRAIN C:BASICSETUP►(seebelow)

    Parameter DescriptionDisplay BRAIN

    UserspanAO1►Unit C42:USRUNIT1 Specifiesthedesiredunitofupto8characterstotheprocessvalueassignedtoanalogoutput1.

    UserspanAO2►Unit C45:USRUNIT2 Specifiesthedesiredunitofupto8characterstotheprocessvalueassignedtoanalogoutput2.

  • 44

    IM 01E22C02-01EN

    User span settingMenu path

    Display Devicesetup►Detailedsetup►UserSpan►(seebelow)BRAIN C:BASICSETUP►(seebelow)

    Parameter DescriptionDisplay BRAIN

    UserspanAO1►Span C43:USRSPAN1 Specifiesthedesiredspantotheprocessvalueassignedtoanalogoutput1.

    UserspanAO2►Span C46:USRSPAN2 Specifiesthedesiredspantotheprocessvalueassignedtoanalogoutput2.

    IMPORTANTTheoutputintheuserunitisdisplayedasfollows:Outputinuserunit=(Outputinaphysicalunitoftheprocessvalue/Spaninaphysicalunitoftheprocessvalue)×Userspan

    Example:Tosetthespansettingforanalogoutput1to100dl/s,settheparametersasfollowsdueto100dl=10L.Displays100dl/swhenoutputting100%. PV=“Volumeflow” Spanofvolumetricflowrate=“10l/s” Usinguserspanforanalogoutput1=“Yes” Userunitforanalogoutput1=“dl/s” Userspanforanalogoutput1=“100”

  • 45

    IM 01E22C02-01EN

    4.1.15 Zero AdjustmentThezeroadjustmentiscarriedouttosettheoutputforzeroflowvelocityto0%(4mA).Althoughtheadjustmenttozeroisperformedatthemanufacturingfactorypriortoshipment,thisproceduremustbecarriedoutonceagainfollowingtheinstallationofpipingtomatchthemagneticflowmetertoitsoperatingconditions.Thissubsectiondescribesthezeroadjustmentprocedureusingthedisplay.

    IMPORTANT• Thezeroadjustmentshouldbecarriedoutbeforetheactualoperation.Notethatsetting

    andupdatingotherparameterscannotbecarriedoutduringthezeroadjustment(forapproximately30seconds).

    • Thezeroadjustmentshouldbeexecutedonlyafterthesensorisfilledwithmeasuringfluidandthefluidvelocityisreducedtozerobyclosingthevalve.

    • Eachtimethemeasuringfluidischanged,besuretoperformthezeroadjustmentforthatchangedfluid.

    Execution of zero adjustmentZeroadjustmentusingthedisplaycanbeexecutedwiththefollowingparameters.Menu path

    Display Devicesetup►Diag/Service►Autozero►Execute►Execute

    F0402.ai

    Device setup Process variables Diag/Service Easy setup wizard

    00 : 00

    SET SFT INC

    Select“Diag/Service”inaccordancewiththemenupathabove.

    F0403.ai

    Diag/Service Verification Autozero AO/AI trim

    00 : 00

    SET SFT INC

    Select“Autozero”.

    F0404.ai

    Autozero Execute Result▲

    00 : 00

    SET SFT INC►

    Select“Execute”.

    F0405.ai

    Execute Not execute Execute Not execute▲

    00 : 00

    SET SFT INC

    Select“Execute”.

    F0406.ai

    Execute Execute

    00 : 00

    SET SFT INC

    When“Execute”blinks,touch[SET]toexecute.

    F0407.ai

    Autozero functionexecuting...

    00 : 00

    00 : 08SET SFT INC

    The time remaining until the end.

    Thezeroadjustmentstarts,andtheprogressisdisplayedwiththeremainingtimeandabargraph.Waitforthezeroadjustmenttocomplete.

  • 46

    IM 01E22C02-01EN

    F0408.ai

    Autozero Execute Result▲

    00 : 00

    SET SFT INC►

    Afterthezeroadjustmentisfinished,thedisplayreturnsto“Autozero”menu.

    ZeroadjustmentbyBRAINcommunicationcanbeexecutedwiththefollowingparameters.Menu path

    BRAIN C:BASICSETUP►C51:AUTOZEROEXE

    ConfirmationofzeroadjustmentresultThezeroadjustmentresultusingthedisplaycanbeconfirmedwiththefollowingparameters.Menu path

    Display Devicesetup►Diag/Service►Autozero►Result►Zerovalue

    F0409.ai

    Result Zero value ▲

    00 : 00

    SET SFT INC

    Fortheresultofthezeroadjustment,select“Result”andthen“Zerovalue”.

    F0410.ai

    Zero value – 00.018cm/s – 00.018cm/s – 99.999 + 99.999

    00 : 00

    SET SFT INC

    Theresultofzeroadjustmentisdisplayedasontheleftofthescreen.

    NOTEWhenthezeroadjustmentresultexceedsthedefinedvalue,thewarning[092:AZwarn]isdisplayed.

    ThezeroadjustmentresultusingBRAINcommunicationcanbeconfirmedwiththefollowingparameters.Menu path

    BRAIN C:BASICSETUP►C52:ZERO

  • 47

    IM 01E22C02-01EN

    4.2 Totalization Function4.2.1 Totalized Value and Unit Setting

    Thisfunctioncantotalizethevolumetricflowrate,massflowrate,andcalorie.Thisproducthasthreetotalizersandcantotalize3processvaluesatthesametime.Totalizer1totalizesthevaluesintheunitofthePV-mappedprocessvalueinSubsection4.1.2.Totalizers2and3totalizetheprocessvalueoftheselectedunit.Thissettingcanbedisplayedandconfiguredwiththefollowingparameters.Menu path

    Display Devicesetup►Detailedsetup►Totalizer►(seebelow)BRAIN D:TOTALSET►(seebelow)

    Parameter DescriptionDisplay BRAINTotalizer1►Unit D10:TOT1UNIT Displaystheunitoftotalizer1.Totalizer2►Unit D20:TOT2UNIT SpecifiestheunitofTotalizer2.Totalizer3►Unit D30:TOT3UNIT SpecifiestheunitofTotalizer3.

    NOTETheflowvelocityandflownoisecannotbetotalized.IfflowvelocityorflownoiseisselectedforthePrimaryValue,totalizer1totalizesthevolumetricflowrateandunitusing“m3”.

    4.2.2 Totalized Value Display and Totalization FunctionThetotalizationresultcanbedisplayedwithatotalizedvalueoratotalizedvaluewhichisscaledwiththeconversionfactor(totalizedcountvalue).Whenthetotalizedvalueisscaledwiththeconversionfactor,aspecificflowrateistotalizedin1-countincrements,whichcanbeusedasatotalizercounter.However,notethattheconversionfactorcannotbesetto“0”.Ifthetotalizedvalueonthedisplayexceeds±99999999,themaximumvalueofthedisplayeddigits,thedisplayedvalueisresetto0.Inaddition,ifthevaluesofA30-A35exceedthelimitofthedisplayeddigits,theyareresetto0inthesamewayasthevalueonthedisplay.Thetotalizedvaluecanbedisplayedandconfiguredwiththefollowingparameters.

    Displaying totalized valueMenu path

    Display Devicesetup►Processvariables►Totalizer►(seebelow)BRAIN A:DISPLAY►(seebelow)

    Parameter DescriptionDisplay BRAINTotalizer1 A30:TOTAL1 Displaysthetotalizedvalueoftotalizer1.Totalizer2 A31:TOTAL2 Displaysthetotalizedvalueoftotalizer2.Totalizer3 A32:TOTAL3 Displaysthetotalizedvalueoftotalizer3.

  • 48

    IM 01E22C02-01EN

    NOTEIfMainsoftrev(K50:MAINBREV/Mainsoftrev)isR2.01.02orearlier,orIndsoftrev(K52:INDBREV/Indsoftrev)isR2.01.01orearlier,thetotalizedvalueonthedisplayisheldattheupperlimitifitexceeds±99999999,themaximumvalueofthedisplayeddigits.Inaddition,ifthevaluesofA30-A35exceedthelimitofthedisplayeddigits,theyareheldattheupperlimitinthesamewayasthevalueonthedisplay.Fordetailsabouthowtocheckthedevicerevision(MainsoftrevandIndsoftrev),refertoSubsection4.10.2.

    Setting conversion factor for scalingMenu path

    Display Devicesetup►Detailedsetup►Totalizer►(seebelow)BRAIN D:TOTALSET►(seebelow)

    Parameter DescriptionDisplay BRAINTotalizer1►Convfactor D11:TOT1CONVFC Specifiestheconversionfactoroftotalizer1.Totalizer2►Convfactor D21:TOT2CONVFC Specifiestheconversionfactoroftotalizer2.Totalizer3►Convfactor D31:TOT3CONVFC Specifiestheconversionfactoroftotalizer3.

    Display of the totalized count value that is scaled with the conversion factor

    Menu pathDisplay Devicesetup►Processvariables►Totalizer►(seebelow)BRAIN A:DISPLAY►(seebelow)

    Parameter DescriptionDisplay BRAINTotalizer1count A33:TOTAL1CNT Displaysthescaledtotalizedvalueoftotalizer1.Totalizer2count A34:TOTAL2CNT Displaysthescaledtotalizedvalueoftotalizer2.Totalizer3count A35:TOTAL3CNT Displaysthescaledtotalizedvalueoftotalizer3.

    Example:Settheunitoftotalizer2to“m3”andtheconversionfactorto2.->Ifthetotalizedvalueoftotalizer2issetto“10.123m3”,thetotalizedvalueisscaledto“10.123÷2=5”.

    NOTEIfMainsoftrev(K50:MAINBREV/Mainsoftrev)isR2.01.02orearlier,orIndsoftrev(K52:INDBREV/Indsoftrev)isR2.01.01orearlier,thetotalizedvalueonthedisplayisheldattheupperlimitifitexceeds±99999999,themaximumvalueofthedisplayeddigits.Inaddition,ifthevaluesofA30-A35exceedthelimitofthedisplayeddigits,theyareheldattheupperlimitinthesamewayasthevalueonthedisplay.Fordetailsabouthowtocheckthedevicerevision(MainsoftrevandIndsoftrev),refertoSubsection4.10.2.

  • 49

    IM 01E22C02-01EN

    4.2.3 Totalization Switch FunctionWhenatargetvalue(threshold)tototalizeisspecified,itcanbeusedasatotalizationswitchfunction.Thetotalizationswitchfunctioncancomparethespecifiedtargetvaluewiththetotalizedvalueandoutputtheresultinstatusoutput.Thestatusoutputisactivewhilethetotalizedvalueexceedsthespecifiedtargetvalue.Evenifthetotalizedvalueexceedsthedisplayeddigitlimitandisresetto0underthatstate,thestatusoutputremainsactive.Fordetailsabouttheoutput,activedirection,andstatusoutputfunctionsettingforeachterminal,refertoSection4.3.Thissettingcanbeconfiguredwiththefollowingparameters.Menu path

    Display Devicesetup►Detailedsetup►Totalizer►(seebelow)BRAIN D:TOTALSET►(seebelow)

    Parameter DescriptionDisplay BRAINTotalizer1►Setpoint D18:TOT1SETPNT Specifiesthetargetvalueoftotalizer1.Totalizer2►Setpoint D28:TOT2SETPNT Specifiesthetargetvalueoftotalizer2.Totalizer3►Setpoint D38:TOT3SETPNT Specifiesthetargetvalueoftotalizer3.

    Example: Setting procedure to use the totalization switch function with the pulse/status output 1.

    Followthestepsbelowtosetthestatusoutputofpulse/statusoutput1to“Onactive”whenthetotalizedvalueoftotalizer1reachesthetargetvalue.(1) RefertoSubsection4.3.1tospecifytheoutputofpulse/statusoutput1to“Statusoutput”.

    (2) RefertoSubsection4.3.5tospecifytheactivedirectionofpulse/statusoutput1to“Onactive”.

    (3) RefertoSubsection4.3.9tospecifythestatusoutputfunctionto“Totallimit1”.

    (4) Refertothissubsectiontospecifythetargetvalueoftotalizer1.

  • 50

    IM 01E22C02-01EN

    4.2.4 Totalizer Operation at Alarm OccurrenceThetotalizeroperationcanbespecifiedtodealwithanalarmthataffectsthetotalizationfunction.Thissettingcanbeconfiguredwiththefollowingparameters.Menu path

    Display Devicesetup►Detailedsetup►Totalizer►(seebelow)BRAIN D:TOTALSET►(seebelow)

    Parameter DescriptionDisplay BRAIN

    Totalizer1►Failureopts D13:TOT1FOPTS Specifiesthetotalizer1operationtobeperformedwhenanalarmoccurs.

    Totalizer2►Failureopts D23:TOT2FOPTS Specifiesthetotalizer2operationtobeperformedwhenanalarmoccurs.

    Totalizer3►Failureopts D33:TOT3FOPTS Specifiestotalizer3operationtobeperformedwhenanalarmoccurs.

    Fromthetablebelow,selecttheoperationofthetotalizationfunction.Selection DescriptionDisplay BRAIN

    Measuredvalue Measuredvalue Continuesthetotalizationfunctionwhileanalarmisoccurring.

    Stop Stop Stopsthetotalizationfunctionwhileanalarmisoccurring.

    Last valid Last validContinuesthetotalizationfunctionwiththelastvalidvaluerightbeforethealarmoccurredwhileanalarmisoccurring.

    4.2.5 Start/Stop Setting for Totalization FunctionThestart/stopoperationofthetotalizationfunctioncanbeset.Thissettingcanbeconfiguredwiththefollowingparameters.Menu path

    Display Devicesetup►Detailedsetup►Totalizer►(seebelow)BRAIN D:TOTALSET►(seebelow)

    Parameter DescriptionDisplay BRAIN

    Totalizer1►Start/Stop D15:TOT1EXEC SpecifiesStart/Stoptothetotalizationfunctionoftotalizer1.

    Totalizer2►Start/Stop D25:TOT2EXEC SpecifiesStart/Stoptothetotalizationfunctionoftotalizer2.

    Totalizer3►Start/Stop D35:TOT3EXEC SpecifiesStart/Stoptothetotalizationfunctionoftotalizer3.

    NOTEThetotalizationfunctionissetto“Stop”atshipmentfromthemanufacturingfactory.Tostartthetotalizationfunction,besuretosetitto“Start”.

  • 51

    IM 01E22C02-01EN

    4.2.6 Totalization Direction SettingThetotalizationdirectioncanbespecifiedwhenusingthetotalizationfunction.Thissettingcanbeconfiguredwiththefollowingparameters.Menu path

    Display Devicesetup►Detailedsetup►Totalizer►(seebelow)BRAIN D:TOTALSET►(seebelow)

    Parameter DescriptionDisplay BRAINTotalizer1►Options D14:TOT1OPTS Specifiesthetotalizationdirectionoftotalizer1.Totalizer2►Options D24:TOT2OPTS Specifiesthetotalizationdirectionoftotalizer2.Totalizer3►Options D34:TOT3OPTS Specifiesthetotalizationdirectionoftotalizer3.

    Fromthetablebelow,selectthetotalizationdirection.Selection DescriptionDisplay BRAIN

    Balanced Balanced Totalizesthedifferentialflowratebetweentheforwardandreversedirections.Absolute Absolute Totalizestheabsolutevalueoftheflowrate.Only positive Only positive Totalizesonlytheflowrateintheforwarddirection.Onlynegative Onlynegative Totalizesonlytheflowrateinthereversedirection.

    Hold Hold Stopstotalizationprocessing(holdsthecurrenttotalizedvalue).

  • 52

    IM 01E22C02-01EN

    4.2.7 Totalized Value Reset/Preset FunctionThereset/presetfunctioncanbespecifiedforthetotalizedvalue.Iftheresetfunctionisused,thefunctionresetsthetotalizedvalueto“0”.Ifthepresetfunctionisused,itsetsthepresetvaluespecifiedinadvancetothetotalizedvalue.Thepresetfunctionisusedwhenstartingtocounttotalizationfromthespecifiedvalue.Thissettingcanbeconfiguredwiththefollowingparameters.

    Use of the reset/preset functionMenu path

    Display D