Upload
scribdlostandfound
View
215
Download
0
Embed Size (px)
Citation preview
8/8/2019 Additional Work of l.p.o
1/13
Customer: GALFAR ENGG. CONTG. CO. LLC
Project: New Jetty at SBSNSB, Wudam
Voltamp ref: SO290249 + SO221048
Details of Variations w.r.t Design Changes Client: MODES
S.No
Panel
description
As per Rev.0 submission of drawingsAs per consultant comments received on
18.05.10
ADDITIONAL PRICE -
IN OMR
1 100A SL-FP-JO
a
Sheet steel enclosure of size
1000Hx800Wx250D in mm
Changed to GRP type enclosure of size
1000Hx800Wx300D in mm 110
a
Sheet steel enclosure of size
1000Hx800Wx250D in mm
Changed to GRP type enclosure of size
1000Hx800Wx300D in mm 110
a
Sheet steel enclosure of size
1000Hx800Wx250D in mmChanged to GRP type enclosure of size
1000Hx800Wx300D in mm 110
a
Sheet steel enclosure of size
700Hx500Wx200D in mm
Changed to GRP type enclosure of size
850Hx550Wx280D in mm 110
a
Sheet steel enclosure of size
700Hx500Wx200D in mm
Changed to GRP type enclosure of size
850Hx550Wx280D in mm 110
a
Sheet steel enclosure of size
700Hx500Wx200D in mm
8/8/2019 Additional Work of l.p.o
2/13
Changed to GRP type enclosure of size
850Hx550Wx280D in mm 110
a
Sheet steel enclosure of size
700Hx500Wx200D in mm
Changed to GRP type enclosure of size
850Hx550Wx280D in mm 110
a
Sheet steel enclosure of size
1800Hx1200Wx400D in mm
Changed to GRP type enclosure of size
1800Hx1200Wx400D in mm 150
b - 1 no. of digital KWH meter added 385
c - 3 x Current transformers for the digital KWH meter 30
d - Space heater + thermostat with switch 50
a
Sheet steel enclosure of size
1800Hx1200Wx400D in mm
Changed to GRP type enclosure of size
1800Hx1200Wx400D in mm 150
b - 1 no. of digital KWH meter added 385
c - 3 x Current transformers for the digital KWH meter 30
d - Space heater + thermostat with switch 50
STREET LIGHT FEEDER PILLARS, HIGH MAST CONTROL PANELS & 1600A TX-1 & 2 LVDBs - Volta
2100A SL-FP-BLDG
32A HIGH MAST CONTROL PANEL-JM1
32A HIGH MAST CONTROL PANEL-JM2
32A HIGH MAST CONTROL PANEL-JO1
32A HIGH MAST CONTROL PANEL-JO2
1600A TX-1 LVDB
1600A TX-2 LVDB
100A SL-FP-JM
C:\Documents and Settings\Ananthan\Desktop\MOD - Wudam Jetty Project
Customer: GALFAR ENGG. CONTG. CO. LLC
Project: New Jetty at SBSNSB, Wudam
Voltamp ref: SO290249 + SO221048
Details of Variations w.r.t Design Changes Client: MODES
S.No
Panel
description
As per Rev.0 submission of drawings
As per consultant comments received on
18.05.10
8/8/2019 Additional Work of l.p.o
3/13
ADDITIONAL PRICE -
IN OMR
a - 1 no. of digital KWH meter added 385
b - 3 x Current transformers for the digital KWH meter 30
c - Space heater + thermostat with switch 50
d -
4C x 300 Sq.mm cable mentioned in the commented
drawings for 63A/100A/125A outgoing feedersGalfar to check
and confirm.
a
433V at LV winding side offered as per
Technical specification & our compliance
statement
440V at LV winding side required as per consultant
MAS 350
a
RMU+Transformer+LV feeder pillar ismounted on a BASE SKID without any
enclosure
Details required by consultant for the enclosure
system of package substation
Not considered.
Please clarify
b - 1 no. of digital KWH meter added 385
c - 3 x Current transformers for the digital KWH meter 30
d - Space heater + thermostat with switch 50
a433V at LV winding side offered as per
Technical specification & our compliance
statement
440V at LV winding side required as per consultant
MAS 350
a
RMU+Transformer+LV feeder pillar is
mounted on a BASE SKID without any
enclosure
Details required by consultant for the enclosure
system of package substation
Not considered.
Please clarify
1. LV FEEDER PILLAR
2. TRANSFORMER
1MVA, 11kV, 50Hz PACKAGE SUBSTATION (includes Transformer + RMU + 1600A Feeder pillar
SO290249
1MVA, 11kV, 60Hz PACKAGE SUBSTATION (includes Transformer + RMU + 1600A Feeder pillar
SO290249
8/8/2019 Additional Work of l.p.o
4/13
2. TRANSFORMER
3. SKID
3. SKID
1. LV FEEDER PILLAR
C:\Documents and Settings\Ananthan\Desktop\MOD - Wudam Jetty Project
Please refer our appended e-mail & attachment for your LPO # 4401814 dt.19.04.2010 & LPO
8/8/2019 Additional Work of l.p.o
5/13
8/8/2019 Additional Work of l.p.o
6/13
: SO
8/8/2019 Additional Work of l.p.o
7/13
8/8/2019 Additional Work of l.p.o
8/13
110 dt.31.05.2010.
8/8/2019 Additional Work of l.p.o
9/13
L.P.O 4401814PACKAGE SUB STATION-50 Hz /60Hz
1 VOLTAGE RATIO,TAP CHANGE ,
MAS COMMENTS FOR PACAKAGE SUBSTATION1 PAINTS SHOULD BE EPOXY
2 THE POWER METER SHALL BE (PRI) METER
3 THE OUT GOING FEEDER SHALL BE AS PER SCOPE OF WORK
4 R.M.U SHALL BE LUCY OIL TYPE
2 VOLTAGE RATIO,TAP CHANGE ,/ MAS COMME
MAS COMMENTS FOR PACAKAGE SUBSTATION
1 PAINTS SHOULD BE EPOXY
2 THE POWER METER SHALL BE (PRI) METER3 THE OUT GOING FEEDER SHALL BE AS PER SCOPE OF WORK
4 R.M.U SHALL BE LUCY OIL TYPE
EXISTING TRANSFORMER DATA
KVA 1000
RATED VOLTS (H.V) 11000
NO LOAD(L.V) 457
RATED CURRENT(H.V) 52.49
RATED CURRENT(L.V) 1263
PHASES 3
INSULATION LEVEL H.V 75 KVp
INSULATION LEVEL L.V 3.0 KVp
INSULATION LIQUID RISE 50 DEG
INSULATION RESISTANCE 55 DEG
TYPE OF COOLING ONAN
RATED FREEQUENCY 60 Hz
IMPEDENCE VOLTS
.V.. .%.....
11000V 4.86%
H.V. VOLTS .V.SWITC
TAP SETTING
POSS'
11550 1
11275 2
11000 3
PACKAGE SUB STATION
50 Hz
PACKAGE SUB STATION
60 Hz
8/8/2019 Additional Work of l.p.o
10/13
8/8/2019 Additional Work of l.p.o
11/13
ORDER PLASED TO VOLTAMP +REVISED S.L.D ATTACHED
ORDER PLASED TO VOLTAMP +REVISED S.L.D ATTACHED
8/8/2019 Additional Work of l.p.o
12/13
8/8/2019 Additional Work of l.p.o
13/13
L.P.O 4403110FEEDER PILLARS AND L.V BOARDS