Upload
others
View
5
Download
0
Embed Size (px)
Citation preview
Actuator controls
AUMATIC AC 01.1/ACExC 01.1
Profibus DP
Manual Device integration Fieldbus
Table of contents Page
1. Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.1. General notes regarding safety 41.2. Range of application 51.3. Warnings and symbols 5
2. General information about Profibus DP . . . . . . . . . . . . . . . . . . . . . . . . 6
2.1. Basic characteristics 62.2. Basic functions of Profibus DP 72.3. Transfer mode 72.4. Bus access 72.5. Communication 72.6. Functionality 72.7. Protection functions 72.8. Device types 7
3. Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.1. Introduction 83.2. Parameter setting 83.3. Configuring the Profibus DP interface of the AUMATIC 83.4. Communication start-up 93.5. AUMA user parameters (AUMA specific parameters) 103.5.1 Process representation input (user parameter 1) 103.5.2 Settable (user definable) signals (user parameters 2 to 8 and 11 to 34) 103.5.3 Alarm contacts/collective fault signal (user parameter 9) 123.5.4 Percent/per mil coding for transmission values (user parameter 10) 133.6. Profibus DP-V1 services (option) 14
4. Description of the data interface . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
4.1. Input data (process representation input) – signals 154.1.1 Process representation input arrangement 1 (default process representation) 154.1.2 Process representation input arrangement 2 164.1.3 Process representation input arrangement 3 174.1.4 Process representation input arrangement 4 184.1.5 Signal description within process representation input arrangement 1 (default process representation)
194.2. Output data (Process representation output) 284.2.1 Description of the output data 28
2
Actuator controls AC 01.1/ACExC 01.1AUMATIC Manual
Reference documents:. Operation instructions (Assembly, operation, commissioning) for actuator. Manual (Operation and setting) AUMATIC AC 01.1/ACExC 01.1 Profibus DP
Can be downloaded from the Internet (www.auma.com) or ordered directly from AUMA(addresses from page 46).
Read operation instructions first. Observe safety instructions.
Purpose of the document:This document is intended to support the system integrator in integrating the fieldbus interface into the DCS.
Page
5. Description of the Profibus DP board. . . . . . . . . . . . . . . . . . . . . . . . . 33
5.1. Displays (optical signals) 335.2. Connections: 345.2.1 Profibus DP bus connection 345.2.2 Customer inputs (option) 345.2.3 Redundant bus connection with component redundancy (option) 35
6. Corrective actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
6.1. Fault indications and warning indications 366.2. Diagnostics 366.3. Troubleshooting 366.3.1 Measuring the Profibus signals using an oscilloscope 39
7. Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
8. Appendix – Proposed external wiring diagram. . . . . . . . . . . . . . . . . . . . 41
8.1. Connecting external sensors, 2-wire technology 418.2. Connecting external sensors, 3-wire technology 428.3. Connecting external sensors, 4-wire technology 43
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Addresses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
3
Actuator controls AC 01.1/ACExC 01.1Manual AUMATIC
1. Safety instructions
1.1. General notes regarding safety
4
Actuator controls AC 01.1/ACExC 01.1AUMATIC Manual
Standards/directives AUMA products are designed and manufactured in compliance with recog-nised standards and directives. This is certified in a declaration of incorpora-tion and a declaration of conformity.The end user or the contractor must ensure that all requirements withrespect to assembly, electrical connection, and commissioning at the placeof installation are met. They include among others:. Standards and directives such as: EN 60079 “Electrical apparatus for
explosive gas atmospheres"Part 14: Electrical installations in hazardous areas (other than mines).Part 17: Inspection and maintenance of electrical installations in hazard-ous areas (other than mines).
. Applicable configuration directives for fieldbus applications.
Safety instructions/warnings
All personnel working with this device must be familiar with the safety andwarning instructions in this manual and observe the instructions given.Safety instructions and warning signs on the device must be observed toavoid personal injury or property damage.
Qualification of staff Assembly, electrical connection, commissioning, operation, and maintenancemust be carried out exclusively by suitably qualified personnel authorised by theend user or contractor of the plant.Prior to working on this product, the staff must have thoroughly read and under-stood these instructions and, furthermore, know and observe officially recog-nised rules regarding occupational health and safety.Work performed in potentially explosive atmospheres is subject to special regu-lations which have be observed. The end user or contractor of the plant areresponsible for respect and control of these regulations, standards, and laws.
Commissioning Prior to commissioning, it is important to check that all settings are in com-pliance with the requirements of the application. Incorrect settings mightpresent a danger to the application, e.g. cause damage to the valve or theinstallation.The manufacturer will not be held liable for any consequential damage. Suchrisk lies entirely with the user.
Safe operation Prerequisites for safe and smooth operation:
. Correct transport, proper storage, mounting and installation, as well ascareful commissioning.
. Exclusively operate the device if it is in perfect condition while observingthese instructions.
. Immediately inform about any faults and damage and allow for correctivemeasures.
. Observe recognised rules for occupational health and safety.
Protective measures The end user or the contractor are responsible for implementing requiredprotective measures on site, such as enclosures, barriers, or personalsafety equipment for the staff.
Maintenance Any device modification requires the consent of the manufacturer.
1.2. Range of application
AUMA actuator controls are exclusively designed for the operation of AUMAactuators.
Other applications require explicit (written) confirmation by the manufac-turer.
The following applications are not permitted, e.g.:
. motor activation
. pump activation
No liability can be assumed for inappropriate or unintended use.
Observance of these operation instructions is considered as part of thedevice’s designated use.
1.3. Warnings and symbols
The following references and symbols are used in these instructions:
Potentially hazardous situation. Failure to observe this warning may result inproperty damage.
Information The term Information preceding the text indicates important notes andinformation.
For assembly, operation, and commissioning, observe the additional safetyand warning instructions of the reference documents (page 2).
Symbol for CLOSED
Symbol for OPEN
� Via the menu to parameterDescribes the path within the menu to the parameter. By using the push but-tons of the local controls you may quickly find the desired parameter in thedisplay.
� Description of the parameter settings/indicationsDescribes the setting/viewing possibilities of a parameter.
� Step by stepProvides a detailed description of each step for setting/viewing the parame-ter.
5
Actuator controls AC 01.1/ACExC 01.1Manual AUMATIC
NOTICE
2. General information about Profibus DP
For the exchange of information among automation systems and betweenautomation systems and the connected distributed field devices, serialfieldbus systems are mainly used today as the communication system.Thousands of applications have proved impressively that cost savings of upto 40 % in wiring, commissioning, and maintenance are achieved by usingfieldbus technology. While in the past the fieldbus systems used were oftenmanufacturer specific and incompatible with other bus systems, the systemsemployed today are almost exclusively open and standardized. This meansthat the user does not depend on individual suppliers and can choose thebest product at the most competitive price.Profibus DP is the leading open fieldbus system in Europe, which is alsoused successfully throughout the world. The application range includesautomation in the areas of manufacturing, processing, and building. ProfibusDP is an international, open fieldbus which has been standardized in thefieldbus standards IEC 61158 and IEC 61784. This standardization ensuresthat the investments of manufacturers and users are protected to the bestpossible degree and the independence of the manufacturer is guaranteed.
2.1. Basic characteristics
Profibus DP defines the technical and functional features of a serial fieldbussystem allowing the interconnection of distributed, digital automationdevices. Profibus DP distinguishes between master and slave devices.Profibus DP is designed for fast data transmission on the field level. Here,central control devices, such as a PLC or PC, communicate via a fast serialconnection with peripheral field stations such as input/output devices,valves, and actuators.The interchange of data among these field devices is based on cyclic com-munication. The necessary communication functions are defined by theProfibus DP basic functions according to IEC 61158 and IEC 61784.
Master devices control the data traffic on the bus. A master is allowed tosend messages without an external request. Masters are also called ‘activedevices’ in the Profibus protocol.
Slave devices such as AUMA Profibus DP actuators are peripheral devices.Typical slave devices are input/output devices, valves, actuators, and mea-suring transmitters. They do not have bus access, i.e. they may onlyacknowledge received messages or, at the request of a master, transmitmessages to that master. Slaves are also called ‘passive stations’.
6
Actuator controls AC 01.1/ACExC 01.1AUMATIC Manual
2.2. Basic functions of Profibus DP
The master reads the input information cyclically from the slaves and writesthe output information cyclically to the slaves. In addition to thiscyclic data transfer of the process representation, Profibus DP also providespowerful functions for diagnostics and commissioning purposes. The datatraffic is monitored through the monitoring functions on the master and slaveside.
2.3. Transfer mode
. RS-485 twisted pair cable or fibre optic cable.
. AUMA actuators support baud rates up to 1.5 Mbits/s
2.4. Bus access
. Token-passing between the masters and polling between master andslave.
. Mono-master or multi-master systems are possible.
. Master and slave devices: max. 126 stations connected to one bus
2.5. Communication
. Peer-to-peer (process data exchange [DATA EX]) or Multicast (controlcommands to all slaves).
. Cyclic master-slave process data exchange (DATA EX) or acyclic mas-ter-master data transfer.
2.6. Functionality
. Cyclic process data exchange (DATA EX) between DP master and DPslaves.
. Dynamic activation or de-activation of individual DP-slaves.
. Checking the configuration of the DP slaves
. Synchronisation of inputs and/or outputs.
2.7. Protection functions
. All messages are transmitted with Hamming Distance HD=4.
. Watchdog timer at DP slaves.
. Access protection for the inputs/outputs of the DP slaves
. Process data exchange (DATA EX) monitoring with configurable timerinterval at the master.
. Adjustable failure behaviour.
2.8. Device types
. DP master class 2 (DPM2), e.g. programming/configuration tools.
. DP master class 1 (DPM1), e.g. central controllers such as PLC, PC.
. DP slave, e.g. AUMA Profibus DP devices. Devices with binary or ana-logue inputs/outputs, actuators, valves.
7
Actuator controls AC 01.1/ACExC 01.1Manual AUMATIC
3. Commissioning
3.1. Introduction
When commissioning a Profibus DP network, the stations on the Profibus DPmust be parameterized and configured with the programming software at thecontrols (Profibus configurator).The programming software first reads the GSD file (GeneralStationData) ofthe individual actuators. The GSD file contains information about the proper-ties of the device which is needed by the master. The GSD file can be down-loaded from our website: www.auma.com.
Information AUMATIC actuator controls up to the logic software version Z031.922/04-00have a reduced number of parameters. Therefore, a GSD file with reducedfunctions is available at www.auma.com (see Readme.txt inAUMATIC_GSD.zip).
Afterwards, the user can configure and program the device at the ProfibusDP for the programming software of the process control system.This information is then stored in the controls (DP master) and sent to theactuators (DP slaves) each time communication is started.The control is executed via the process representation input and outputbytes.If a configuration with consistent data is chosen, special functional elementsfor the control of the Profibus DP slaves must be used with some PLCs.
3.2. Parameter setting
The parameter setting is partly determined in the Profibus standard, e.g. abit for switching bus monitoring on and off (watchdog).The AUMA Profibus DP control can additionally receive up to 37 bytes of‘user parameters’, which can be used to set AUMA specific parameters. TheAUMA specific parameters are divided into 34 parameters with 1 byte eachper parameter. The parameters can be changed via the programming soft-ware of the controls. New programming software supports the setting of theparameters via text and a menu selection. When using older software, thevalues of the parameters must be entered using hexadecimal numbers.The meaning of the individual AUMA specific parameters is explained insubclause 3.5.
3.3. Configuring the Profibus DP interface of the AUMATIC
During configuration, the number of input and output bytes reserved foreach device in the controls’ memory is selected. Additionally it is determinedif the data is processed consistently or non-consistently.
Information Only the number of bytes determined in the configuration is transferredbetween the DP master and the DP slave.
8
Actuator controls AC 01.1/ACExC 01.1AUMATIC Manual
9
The following configurations are possible with AUMA Profibus DP actuators:
The number of input bytes states how many of the maximum of 24 bytes theDP slave sends to the DP master.The number of output bytes states how many of the maximum of 12 bytesthe DP master sends to the DP slave.
If, for example, the configuration with 8 bytes input is selected, only the first8 bytes are sent from the DP slave to the DP master. In this case, the mas-ter does not have access to the bytes 9 to 12.This way, the DP master saves memory space since it only has to reserve 8input bytes for the actuator.The data of the AUMA actuators should be consistently processed by theDP master. This ensures that the value of a 2-byte variable (position trans-mitter, analogue customer input) does not change after the reading out thefirst byte and, thus, does not distort the value.If a master does not offer the possibility to use consistent configurations bymeans of the process control system, a non-consistent configuration can bechosen. The values for the position transmitter and the analogue customerinputs can then be transferred in 1 byte format (Parameter 10 = 0).
3.4. Communication start-up
When the DP master is switched on, it first sends a parameter and configu-ration telegram to each DP slave. If parameter and configuration are correct,the DP slave enters the ‘Data Exchange’ mode to exchange process databetween the controls and the slave. Then, the DP master can control the DPslave and read its current state via the process representation.If communication is interrupted (e.g. through the switching off of the slave orthe breaking of the Profibus cable), it is resumed automatically by the DPmaster when the cause of the fault is eliminated.
Number of input bytes Number of output bytes
1 12 12 24 44 66 16 26 46 68 48 612 412 616 820 820 1222 824 8
All these configurations (except 1 In, 1 Out) can be selected as consistent or non-consistent
Table 1
3.5. AUMA user parameters (AUMA specific parameters)
The AUMA specific parameters are set by means of the GSD file.
3.5.1 Process representation input (user parameter 1)
Designation in GSD file:ExtUserPrmData = 1 “Byte order pattern”
� Description of the parameter settings:
3.5.2 Settable (user definable) signals (user parameters 2 to 8 and 11 to 34)Within the process representation input, the users can configure the datacontents of 4 signal bytes out of a predefined set of signals themselves.
Designation in GSD file:. ExtUserPrmData = 2 “Configuration Bit 5.0"
to ExtUserPrmData = 8 ”Configuration Bit 5.6"(bit 5.7 is intended for collective fault signals, refer to page 12)
. ExtUserPrmData = 11 “Configuration Bit 6.0"to ExtUserPrmData = 18 ”Configuration Bit 6.7"
. ExtUserPrmData = 19 “Configuration Bit 7.0"to ExtUserPrmData = 26 ”Configuration Bit 7.7"
. ExtUserPrmData = 27 “Configuration Bit 8.0"to ExtUserPrmData = 34 ”Configuration Bit 8.7"
� Description of the parameter settings:
10
Actuator controls AC 01.1/ACExC 01.1AUMATIC Manual
Value in GSD file Text in GSD file Indication in display Description
Prm_Text_Ref = 0 Arrangement 1 0Process representation arrangement 1(page 15) is used.
Prm_Text_Ref = 1 Arrangement 2 1Process representation arrangement 2(page 16) is used.
Prm_Text_Ref = 2 Arrangement 3 2Process representation arrangement 3(page 17) is used.
Prm_Text_Ref = 3 Arrangement 4 3Process representation arrangement 4(page 18) is used.
Value in GSD file Text in GSD file Indication in display DescriptionPrm_Text_Ref = 0 Not used NOT USED No signals
Prm_Text_Ref = 1 Closed position CLOSED POSITIONSignals LSC (WSR) or LSC (WSR) and TSC(DSR) (depending on type of seating)
Prm_Text_Ref = 2 Open position OPEN POSITIONSignals LSO (WOEL) or LSO (WOEL) andTSO (DOEL) (depending on type of seating)
Prm_Text_Ref = 3 Running close RUNNING CLOSE Actuator runs logically CLOSE
Prm_Text_Ref = 4 Running open RUNNING OPEN Actuator runs logically OPEN
Prm_Text_Ref = 5 Actuator moving ACTUATOR MOVING
Actuator runs from LOCAL, REMOTE ormanual operation (without positioner onlylocal or remote operation is indicated).
Prm_Text_Ref = 6 LSC (WSR) LSC (WSR) Limit switch CLOSE operated
Prm_Text_Ref = 7 LSO (WOEL) LSO (WOEL) Limit switch OPEN operated
Prm_Text_Ref = 8 TSC (DSR) TSC (DSR) Torque switch CLOSE operated
Prm_Text_Ref = 9 TSO (DOEL) TSO (DOEL) Torque switch OPEN operated
11
Actuator controls AC 01.1/ACExC 01.1Manual AUMATIC
Prm_Text_Ref = 10 Thermal fault THERMO FAULTMotor protection has tripped (reset may benecessary)
Prm_Text_Ref = 11 Torque fault (close) TORQUE FAULT (CLOSE) Torque fault in direction CLOSE occurredPrm_Text_Ref = 12 Torque fault (open) TORQUE FAULT (OPEN) Torque fault in direction OPEN occurredPrm_Text_Ref = 13 Torque fault (general)
TORQUE FAULT (GEN.)Torque fault CLOSE or OPEN (combinedsignal)
Prm_Text_Ref = 14 Setpoint E1 lossSETPOINT E1 LOSS
Nominal value signal is by 0.3 mA lower thanthe lowest set value
Prm_Text_Ref = 15 Feedback E2 lossFEEDBACK E2 LOSS
Actual position signal is by 0.3 mA lower thanthe lowest set value
Prm_Text_Ref = 16 Speed E3 loss SPEED E3 LOSS not availablePrm_Text_Ref = 17 Torque E6 loss
TORQUE E6 LOSSTorque signal is by 0.3 mA lower than thelowest set value
Prm_Text_Ref = 18 Warning oper.timeWARNING OPER.TIME
The programmed max. operating time for anOPEN - CLOSE operation has beenexceeded
Prm_Text_Ref = 19 Warning starts/runWARNING STARTS/RUN
The max. number of starts/h or max. runningtime/h has been exceeded.
Prm_Text_Ref = 20 Local sw. position LOCAL SW. POSITION Selector switch in position LOCALPrm_Text_Ref = 21 Remote sw. position REMOTE SW. POSITION Selector switch in position REMOTEPrm_Text_Ref = 22 Off sw. position OFF SW. POSITION Selector switch in position OFFPrm_Text_Ref = 23 Remote mode REMOTE MODE Operation mode REMOTE activePrm_Text_Ref = 24 Off sw. position SETPOINT MODE Operation mode SETPOINT MODEPrm_Text_Ref = 25 Intermed. pos.1 INTERMED. POS.1 Signalling the intermediate positions 1 to 4.
Signal behaviour according to POS.1CONTROL to POS.4 CONTROL
parameters
Prm_Text_Ref = 26 Intermed. pos.2 INTERMED. POS.2
Prm_Text_Ref = 27 Intermed. pos.3 INTERMED. POS.3
Prm_Text_Ref = 28 Intermed. pos.4 INTERMED. POS.4
Prm_Text_Ref = 29 Stepping modeSTEPPING MODE
Programmed stepping range (START STEP
STOP STEP) parameters) has been enteredPrm_Text_Ref = 30 Closing blink
CLOSING BLINK
Signal is blinking for operation in directionCLOSE. Signal is active in end positionCLOSED.
Prm_Text_Ref = 31 Opening blinkOPENING BLINK
Signal is blinking for operation in directionOPEN. Signal is active in end position OPEN.
Prm_Text_Ref = 32 Fault indicationFAULT IND.
Collective fault signal, includes: internal fault,torque fault, phase failure, thermal fault andconfiguration fault
Prm_Text_Ref = 33 Warning indicationWARNING IND.
Collective fault signal, includes: Operatingtime warning, warning starts/run, internalfeedback, internal warnings and loss of signal
Prm_Text_Ref = 34 Not ready indication
NOT READY IND.
Collective fault signal, includes: Clear state,selector switch not REMOTE, wrongcommand, Emergency operation is active,external operation bus
Prm_Text_Ref = 35 Setpoint reached SETPOINT REACHED Actuator is in nominal positionPrm_Text_Ref = 36 Loss of phase LOSS OF PHASE One phase is missingPrm_Text_Ref = 37 I/O analogue IN 2 loss
I/O ANALOG IN2 LOSSSignal loss of the parallel interface analogueinput 2
Prm_Text_Ref = 38 I/O analogue IN 1 lossI/O ANALOG IN1 LOSS
Signal loss of the parallel interface analogueinput 1
Prm_Text_Ref = 39 Selector not remote SELECTOR NOT REMOTE Selector switch not in position REMOTEPrm_Text_Ref = 40 Wrong command
WRONG COMMAND
Wrong command received (several operationcommand bits set or nominal value > 100 %or > 1000 ‰)
Prm_Text_Ref = 41 Internal faultINTERNAL FAULT
An internal fault has occurred, see diagnosticindication D2
Prm_Text_Ref = 42 PE fault PE FAULT not availablePrm_Text_Ref = 43 Internal feedback
INTERNAL FEEDBACK
Actuator has not yet been opened to full endposition OPEN or closed to full end positionCLOSED
Prm_Text_Ref = 44 Internal warningINTERNAL WARNING
An internal warning has occurred, seediagnostic indication D3
Prm_Text_Ref = 46 Local operationRUNNING LOCAL
The actuator is running through an operationcommand from the local controls
Prm_Text_Ref = 47 Remote operationRUNNING REMOTE
The actuator is running through an operationcommand from REMOTE
3.5.3 Alarm contacts/collective fault signal (user parameter 9)
Designation in GSD file:ExtUserPrmData = 9 “Configuration Fault Bit”
� Description of the parameter settings:
12
Actuator controls AC 01.1/ACExC 01.1AUMATIC Manual
Prm_Text_Ref = 48 Hand wheel operationRUNNING WITH HANDWHL
The actuator is running through turning thehandwheel
Prm_Text_Ref = 49 Proportional operation PROPOTIONAL RUNNING Not availablePrm_Text_Ref = 50 Operation pause PHYS.DRIVE BREAK Actuator is in pause time of stepping modePrm_Text_Ref = 51 Clear-state
CLEAR-STATUSThe Profibus DP interface has received aGlobal Control CLEAR telegram
Prm_Text_Ref = 52 Digital input 1 DIG.IN 1 BUS1 A + 24 DC signal is present at the digital input(1 to 4) of the Profibus interfacePrm_Text_Ref = 53 Digital input 2 DIG.IN 2 BUS1
Prm_Text_Ref = 54 Digital input 3 DIG.IN 3 BUS1
Prm_Text_Ref = 55 Digital input 4 DIG.IN 4 BUS1
Prm_Text_Ref = 56 Intermed. pos.5 INTERMED. POS.5 Signalling of the intermediate positions 5 to 8.Signal behaviour according to POS.5CONTROL to POS.8 CONTROL
parameters
Prm_Text_Ref = 57 Intermed. pos.6 INTERMED. POS.6
Prm_Text_Ref = 58 Intermed. pos.7 INTERMED. POS.7
Prm_Text_Ref = 59 Intermed. pos.8 INTERMED. POS.8
Prm_Text_Ref = 60 Emergency stop buttonEMCY STOP BUTTON
The EMERGENCY STOP button (option) hasbeen operated
Prm_Text_Ref = 61 Fault FO communication FIBER OPTIC LOSS Fault at the fibre optic module (option)Prm_Text_Ref = 62 Power for brake OK BRAKE SUPPLY FAIL Not availablePrm_Text_Ref = 63 Reset indication RESET INDICATION Not availablePrm_Text_Ref = 64 Digital input 1 DP2 DIG.IN 1 BUS2 Not availablePrm_Text_Ref = 65 Digital input 2 DP2 DIG.IN 2 BUS2
Prm_Text_Ref = 66 Digital input 3 DP2 DIG.IN 3 BUS2
Prm_Text_Ref = 67 Digital input 4 DP2 DIG.IN 4 BUS2
Prm_Text_Ref = 68 Local operation openRUNNING OPEN (LOCAL)
Actuator is running in direction OPEN (by anoperation command from the local controls orby turning the handwheel)
Prm_Text_Ref = 69 Local operation closeRUNNING CLOSE (LO-
CAL)
Actuator is running in direction CLOSE (by anoperation command from the local controls orby turning the handwheel)
Prm_Text_Ref = 70 Actuator in intermed.position INTERMED. POSITION
Actuator in intermediate position
Value in GSD file Text in GSD file Indication in display Signals (collective fault signal)Prm_Text_Ref = 0 Fault group 1
FAULT GROUP 1Fault ind.Not ready for operation Remote
Prm_Text_Ref = 1 Fault group 2FAULT GROUP 2
Fault without torque faultNot ready for operation Remote
Prm_Text_Ref = 2 Fault group 3 FAULT GROUP 3 Fault ind.Prm_Text_Ref = 3 Fault group 4 FAULT GROUP 4 Fault without torque faultPrm_Text_Ref = 4 Fault group 5
FAULT GROUP 5
Fault ind.Not ready for operation RemoteWarning
Prm_Text_Ref = 5 Fault group 6FAULT GROUP 6
Fault without thermal faultNot ready for operation Remote
Prm_Text_Ref = 6 Fault group 7FAULT GROUP 7
Fault without torque fault + without thermalfaultNot ready for operation Remote
Prm_Text_Ref = 7 Fault group 8 FAULT GROUP 8 Fault without thermal faultPrm_Text_Ref = 8 Fault group 9
FAULT GROUP 9Fault without torque fault + without thermalfault
Prm_Text_Ref = 9 Fault group 10FAULT GROUP 10
Fault without thermal faultNot ready for operation RemoteWarnings
3.5.4 Percent/per mil coding for transmission values (user parameter 10)This parameter is used to change over the coding of the analogue ProfibusDP transmission values between 0 and 100 %, or 0 and 1,000 ‰.
Designation in GSD file:ExtUserPrmData = 10 “Format of analogue indications”
� Description of the parameter settings:
13
Actuator controls AC 01.1/ACExC 01.1Manual AUMATIC
Value in GSD file Text in GSD file Indication in display DescriptionPrm_Text_Ref = 0 0 to 100 percent 0-100 PERCENT Coding of the analogue values in percentPrm_Text_Ref = 1 0 to 1000 per mil 0-1000 PER MIL Coding of the analogue values in per mil
3.6. Profibus DP-V1 services (option)
Apart from the cyclic DP-V0 process data exchange, the Profibus DP-V1services can establish an additional acyclic communication via the fieldbus.An AUMATIC with activated Profibus DP-V1 service grants access to thecontents of the electronic name plate, the operating data and the mostimportant operation parameters.Access to the data of all actuators connected by the Profibus DP network istherefore enabled, which may be important for preventive maintenance oruniform parameter setting.
Integration into the process con-trol system
Different options are available for simple integration of the AUMATIC opera-tion parameters into the DCS.
For further information refer to. Device integration with DTM (Device Type Manage) manual. Device integration with EDD (Electronic Device Description) for Simatic
PDM (Process Device Manager) manual
14
Actuator controls AC 01.1/ACExC 01.1AUMATIC Manual
4. Description of the data interface
4.1. Input data (process representation input) – signals
Via the process representation input, the master (controls) can read thestate of the slave (actuator).With AUMA user parameter 1 (page ), a selection can be made from 4 dif-ferent process representation arrangements.
4.1.1 Process representation input arrangement 1 (default process representation)Grey bits are collective signals. They contain the results of a disjunction(OR operation) of other information.
15
Actuator controls AC 01.1/ACExC 01.1Manual AUMATIC
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Logical signals Actuator signalsT
SC
(D
SR
)
TS
O(D
OE
L)
LSC
(W
SR
)
LSO
(WO
EL)
Loca
l sw
. pos
ition
Rem
ote
sw. p
ositi
on
Loss
ofph
ase
The
rmal
faut
(Fau
lt3)
(Not
read
yin
d.)
(Los
sof
phas
e)
(Tor
que
faul
t (O
PE
N))
(Tor
que
faul
t (C
LOS
E))
(Rem
ote
sw. p
ositi
on)
(Ope
npo
sitio
n)
(Clo
sed
posi
tion)
(Run
sfo
mLo
cal)
(Run
sfr
omR
EM
OT
E)
(Run
svi
aha
ndhw
eel)
(Act
uato
rm
ovin
g)
(--)
(Sta
rtst
eppi
ngm
ode)
Res
erve
d
(Ope
ratio
npa
use)
(--)
(--)
(--)
(--)
(--)
(--)
(--)
(--)
Configurable byte 1
DP1 Analogue inputhigh byte
Torquehigh byte
Torquelow byte
Byte1: Byte 2:
Options part 1(configurable byte 3)
Byte 7:
Byte 3: E2 (Actual position)
Physical operation(configurable byte 2)
Byte 6:Byte 5:
Byte 4: E2 (Actual position)
Options part 2(configurable byte 4)
Byte 8:
Byte16: Warning signalspart 2
Byte15: Warning signalspart 1
Byte14: Fault signalsByte13: Not ready ind.
Byte12: E6 (Torque)Byte 11: E6 (Torque)Byte 10: DP1 An1Byte 9: DP1 An1
Actual position high byte(positioner)
Actual position low byte(positioner)Fa
ulti
nd.
War
ning
ind.
Run
ning
CLO
SE
Run
ning
OP
EN
Not
read
yin
d.
Set
poin
t rea
ched
Clo
sed
posi
tion
Ope
npo
sitio
n
(DP
1di
g.in
put 4
)
(DP
1di
g.in
put 3
)
(DP
1di
g.in
put 2
)
(DP
1di
g.in
put 1
)
(Int
erm
ed. p
os. 4
)
(Int
erm
ed. p
os. 3
)
(Int
erm
ed. p
os. 2
)
(Int
erm
ed. p
os. 1
)
DP1 Analogue inputlow byte
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
--
Inte
rnal
faul
t
Torq
uefa
ult (
CLO
SE
D)
Torq
uefa
ult (
OP
EN
)
Loss
ofph
ase
The
rmal
faul
t
--
Con
fig. f
ault
Ext
erna
l ope
ratio
n
Cle
arst
ate
Em
erge
ncy
mod
e
Em
cyst
opac
tive
--
Act
uato
rlo
cked
Sel
ecto
rno
t rem
ote
Wro
ngco
mm
and
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Ana
log
In1
DP
1lo
ss
Ana
log
In2
DP
2lo
ss
-- --
Set
poin
t E1
loss
Fee
dbac
kE
2lo
ss
--
Torq
ueE
4lo
ss
Ope
ratio
ntim
e
Sta
rts/
run
Inte
rnal
feed
back
Inte
rnal
war
ning
I/O1
Anl
ogIn
2lo
ss
I/O1
Anl
ogIn
1lo
ss
--
P-F
eedb
ack
E4
loss
DP1 Analogue input 2high byte
Reserved forfuture extensions
Reserved forfuture extensions
Byte 20: ReservedByte 19: ReservedByte 18: DP1 An2Byte 17: DP1 An2
DP1 Analogue input 2low byte
Reserved forfuture extensions
Byte 22: ReservedByte 21: Reserved
Reserved forfuture extensions
Byte 24: ReservedByte 23: Additional data
Reserved forfuture extensions
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Inin
term
ed.p
ositi
on
-- -- –
Inte
rmed
. pos
. 8
Inte
rmed
. pos
. 7
Inte
rmed
. pos
. 6
Inte
rmed
. pos
. 5
4.1.2 Process representation input arrangement 2
Grey bits are collective signals. They contain the results of a disjunction(OR operation) of other information.
16
Actuator controls AC 01.1/ACExC 01.1AUMATIC Manual
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Logische Meldungen Antriebsmeldungen
DS
R
DO
EL
WS
R
WO
EL
Wah
lsch
alte
rO
rt
Wah
lsch
alte
rF
ern
Pha
sena
usfa
ll
The
rmof
ehle
r
(Stö
rung
3)
(Nic
htbe
reit
Fer
n)
(Pha
sena
usfa
ll)
(DO
EL-
Feh
ler)
(DS
R-F
ehle
r)
(Wah
lsch
alte
rF
ern)
(End
lage
AU
F)
(End
lage
ZU
)
(--)
(--)
(--)
(--)
(--)
(--)
(--)
(--)
DP1 Analoger EingangHigh-Byte
DrehmomentHigh-Byte
DrehmomentLow-Byte
Byte1: Byte 2: Byte 3: E2 (Istposition) Byte 4: E2 (Istposition)
Byte16: WarnungsmeldungenTeil 2
Byte15: WarnungsmeldungenTeil 1
Byte14: FehlermeldungenByte13: Nicht bereit Fern
Byte12: E6 (Drehmoment)Byte 11: E6 (Drehmoment)
Byte 10: DP1 An1Byte 9: DP1 An1
Istposition High-Byte(Stellungsgeber)
Istposition Low-Byte(Stellungsgeber)
Feh
lerm
eldu
ngen
War
nung
smel
dung
en
Faeh
rtZ
U
Faeh
rtA
UF
Nic
htbe
reit
Fer
n
Ist S
oll
End
lage
ZU
End
lage
AU
F
DP1 Analoger EingangLow-Byte
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
--
Inte
rne
Feh
ler
DS
R F
ehle
r
DO
EL
Feh
ler
Pha
sena
usfa
ll
The
rmo
Feh
ler
--
Kon
figur
atio
nsfe
hler
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
DP1 Analoger Eingang 2High-Byte
Byte 18: DP1 An2Byte 17: DP1 An2
DP1 Analoger Eingang 2Low-Byte
Konfigurierbares Byte 1Byte 6: Physikalische Fahrt(Konfigurierbares Byte 2)Byte 5:
Byte 7: Optionen Teil 1(Konfigurierbares Byte 3)
(DP
1di
g.E
inga
ng4)
(DP
1di
g.E
inga
ng3)
(DP
1di
g.E
inga
ng2)
(DP
1di
g.E
inga
ng1)
(Zw
isch
enst
ellu
ng4)
(Zw
isch
enst
ellu
ng3)
(Zw
isch
enst
ellu
ng2)
(Zw
isch
enst
ellu
ng1)
(Fae
hrt v
onO
rt)
(Fae
hrt v
onF
ern)
(Fae
hrt m
itH
andr
ad)
(Ant
rieb
fähr
t)
--
(Tak
tstr
ecke
betr
eten
)
(Pro
port
iona
lfahr
t)
(Fah
rpau
se)
Ext
erne
rB
etrie
b
Cle
arZ
usta
nd
NO
T-Fa
hrt a
ktiv
NO
T-A
US
aktiv
--
Ant
rieb
verr
iege
lt
Wah
lsch
alte
rn.
FE
RN
Fals
ches
Kom
man
do
Sig
Br.
DP
1A
nIn
1
Sig
Br.
DP
1A
nIN
2
-- --
Sig
Br.
Sol
lpos
. E1
Sig
Br.
Sol
lpos
. E2
Sig
Br.
LWL-
Mod
ul
Sig
Br.
Dre
hmom
ent E
6
Ste
llzei
twar
nung
ED
-War
nung
kein
eR
efer
enzf
ahrt
Inte
rne
War
nung
Sig
Br.
PAR
1A
nIn
2
Sig
Br.
PAR
1A
nIn
1
--
Sig
Br.
Pro
zess
istw
ert E
4
Für zukünftige Erweiterungenreserviert
Für zukünftige Erweiterungenreserviert
Byte 20: ReserviertByte 19: Reserviert
Für zukünftige Erweiterungenreserviert
Byte 22: ReserviertByte 21: Reserviert
Für zukünftige Erweiterungenreserviert
Byte 24: ReserviertByte 23: Zusatzdaten
Für zukünftige Erweiterungenreserviert
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
InZ
wis
chen
stel
lung
-- -- --
Zw
isch
enst
ellu
ng8
Zw
isch
enst
ellu
ng7
Zw
isch
enst
ellu
ng6
Zw
isch
enst
ellu
ng5
Byte 8: Optionen Teil 2(Konfigurierbares Byte 4)
4.1.3 Process representation input arrangement 3
Grey bits are collective signals. They contain the results of a disjunction(OR operation) of other information.
17
Actuator controls AC 01.1/ACExC 01.1Manual AUMATIC
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Logical signals Actuator signals
TS
C (
DS
R)
TS
O(D
OE
L)
LSC
(W
SR
)
LSO
(WO
EL)
Loca
l sw
. pos
ition
Rem
ote
sw. p
ositi
on
Loss
ofph
ase
The
rmal
faut
(Fau
lt3)
(Not
read
yin
d.)
(Los
sof
phas
e)
(Tor
que
faul
t (O
PE
N))
(Tor
que
faul
t (C
LOS
E))
(Rem
ote
sw. p
ositi
on)
(Ope
npo
sitio
n)
(Clo
sed
posi
tion)
(Run
sfo
mLo
cal)
(Run
sfr
omR
EM
OT
E)
(Run
svi
aha
ndhw
eel)
(Act
uato
rru
ns)
(--)
(Sta
rtst
eppi
ngm
ode)
(Pro
port
iona
l ope
ratio
n)
(Ope
ratio
npa
use)
(--)
(--)
(--)
(--)
(--)
(--)
(--)
(--)
Configurable byte 1Physical operation(configurable byte 2)
DP1 Analogue inputhigh byte
Torquehigh byte
Torquelow byte
Byte1: Byte 2:
Options part 1(configured byte 3)
Byte 7:
Byte 3: E2 (Actual position)Byte 6:
Byte 5: Byte 4: E2 (Actual position)
Options part 2(configured byte 4)
Byte 8:
Byte16: Warning signalspart 2
Byte15: Warning signalspart 1
Byte12: E6 (Torque)Byte 11: E6 (Torque)
Byte 10: DP1 An1Byte 9: DP1 An1
Actual position high-byte(positioner)
Actual position low-byte(positioner)
Faul
tind
.
War
ning
ind.
Run
ning
CLO
SE
Run
ning
OP
EN
Not
read
yin
d.
Set
poin
t rea
ched
Clo
sed
posi
tion
Ope
npo
sitio
n
(DP
1di
g.in
put 4
)
(DP
1di
g.in
put 3
)
(DP
1di
g.in
put 2
)
(DP
1di
g.in
put 1
)
(Int
erm
ed. p
os. 4
)
(Int
erm
ed. p
os. 3
)
(Int
erm
ed. p
os. 2
)
(Int
erm
ed. p
os. 1
)
DP1 Analogue inputlow byte
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Ana
log
In1
DP
1lo
ss
Ana
log
In2
DP
2lo
ss
-- --
Set
poin
t E1
loss
Fee
dbac
k.E
2lo
ss
Fib
erop
ticlo
ss
Torq
ueE
4lo
ss
Ope
ratio
ntim
e
Sta
rts/
run
Inte
rnal
feed
back
Inte
rnal
war
ning
I/O1
Anl
ogIn
2lo
ss
I/O1
Anl
ogIn
1lo
ss
--
P-F
eedb
ack
E4
loss
DP1 Analogue input 2high byte
Byte 18: DP1 An2Byte 17: DP1 An2
DP1 Analogue input 2low byte
Reserved forfuture extensions
Byte 22: ReservedByte 21: Reserved
Reserved forfuture extensions
Byte14: Fault signalsByte13: Not ready ind.
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
--
Inte
rnal
faul
t
Torq
uefa
ult (
CLO
SE
)
Torq
uefa
ult (
OP
EN
)
Loss
ofph
ase
The
rmal
faul
t
--
Con
fig. f
ault
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Ext
erna
l ope
ratio
n
Cle
arst
ate
Em
erge
ncy
mod
e
Em
cyst
opac
tive
--
Act
uato
rlo
cked
Sel
ecto
rno
t rem
ote
Wro
ngco
mm
and
Reserved forfuture extensions
Reserved forfuture extensions
Byte 20: ReservedByte 19: Reserved
Byte 24: ReservedByte 23: Additional data
Reserved forfuture extensions
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Inin
term
ed.p
ositi
on
-- -- --
Inte
rmed
. pos
. 8
Inte
rmed
. pos
. 7
Inte
rmed
. pos
. 6
Inte
rmed
.Pos
. 5
4.1.4 Process representation input arrangement 4
Grey bits are collective signals. They contain the results of a disjunction(OR operation) of other information.
18
Actuator controls AC 01.1/ACExC 01.1AUMATIC Manual
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Logical signals Actuator signals
TS
C (
DS
R)
TS
O(D
OE
L)
LSC
(W
SR
)
LSO
(WO
EL)
Loca
l sw
. pos
ition
Rem
ote
sw. p
ositi
on
Loss
ofph
ase
The
rmal
faut
(Fau
lt3)
(Not
read
yin
d.)
(Los
sof
phas
e)
(Tor
que
faul
t (O
PE
N))
(Tor
que
faul
t (C
LOS
E))
(Rem
ote
sw. p
ositi
on)
(Ope
npo
sitio
n)
(Clo
sed
posi
tion)
(Run
sfo
mLo
cal)
(Run
sfr
omR
EM
OT
E)
(Run
svi
aha
ndhw
eel)
(Act
uato
rm
ovin
g)
(--)
(Sta
rtst
eppi
ngm
ode)
(Pro
port
iona
l ope
ratio
n)
(Ope
ratio
npa
use)
(--)
(--)
(--)
(--)
(--)
(--)
(--)
(--)
Configured byte 1
Torquehigh byte
Torquelow byte
Byte1: Byte 2:
Options part 1(configured byte 3)
Byte 7:
Byte 3: E2 (Actual position)Physical operation(configured byte 2)
Byte 6:
Byte 5: Byte 4: E2 (Actual position)
Options part 2(configured byte 4)
Byte 8:
Byte12: E6 (Torque)Byte 11: E6 (Torque)
Actual position high-byte(positioner)
Actual position low-byte(positioner)
Faul
tind
.
War
ning
ind.
Run
ning
CLO
SE
Run
ning
OP
EN
Not
read
yin
d.
Set
poin
t rea
ched
Clo
sed
posi
tion
Ope
npo
sitio
n
(DP
1di
g.in
put 4
)
(DP
1di
g.in
put 3
)
(DP
1di
g.in
put 2
)
(DP
1di
g.in
put 1
)
(Int
erm
ed. p
os. 4
)
(Int
erm
ed. p
os. 3
)
(Int
erm
ed. p
os. 2
)
(Int
erm
ed. p
os. 1
)
DP1 Analogue input 1high byte
Byte 18: DP1 An1Byte 9: DP1 An1
DP1 Analogue input 1low byte
Byte16: Warning signalspart 2
Byte15: Warning signalspart 1
Byte14: Fault signalsByte13: Not ready ind.
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
--
Inte
rnal
faul
t
Torq
uefa
ult (
CLO
SE
)
Torq
uefa
ult (
OP
EN
)
Loss
ofph
ase
The
rmal
faul
t
--
Con
fig. f
ault
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Ana
log
In1
DP
1lo
ss
Ana
log
In2
DP
2lo
ss
-- --
Set
poin
t E1
loss
Fee
dbac
k.E
2lo
ss
Fib
erO
ptic
loss
Torq
ueE
6lo
ss
Ope
ratio
ntim
e
Sta
rts/
run
Inte
rnal
feed
back
Inte
rnal
war
ning
I/O1
Ana
log
In2
Loss
I/O1
Ana
log
In1
Loss
-
Cha
nnel
2ac
tive
P-F
eedb
ack
E4
loss
DP1 Analogue input 2high byte
Byte 18: DP1 An2Byte 17: DP1 An2
DP1 Analogue input 2low byte
Reserved forfuture extensions
Byte 22: ReservedByte 21: Reserved
Reserved forfuture extensions
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Ext
erna
l ope
ratio
n
Cle
arst
ate
Em
erge
ncy
mod
e
Em
cyst
opac
tive
--
Act
uato
rlo
cked
Sel
ecto
rno
t rem
ote
Wro
ngco
mm
and
Reserved forfuture extensions
Reserved forfuture extensions
Byte 20: ReservedByte 19: Reserved
Byte 24: ReservedByte 23: Additional data
Reserved forfuture extensions
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Inte
rmed
.pos
ition
-- -- --
Inte
rmed
. pos
. 8
Inte
rmed
. pos
. 7
Inte
rmed
. pos
. 6
Inte
rmed
.Pos
. 5
4.1.5 Signal description within process representation input arrangement 1 (default process representa-tion)
Byte 1: Logical signals
Bits 3, 6, and 7 are collective signals.Bits 5 and 4 of the logical signals(byte1) indicate a logical operation ofthe actuator, i.e. they are set when theactuator has received the commandto perform an electrical operation(also present when e.g. the actuatorhappens to be in a stepping pauseduring stepping mode or waits for theend of the dead time)
19
Actuator controls AC 01.1/ACExC 01.1Manual AUMATIC
Bit Designation Value Short description
0
Open positionFor limit seating inend position OPEN
1 Limit switch operated in direction OPEN
0 No signals
Open positionFor torque seating inend position OPEN
1 Torque switch and limit switch operatedin direction OPEN
0 No signals
1
Closed positionFor limit seating inend position CLOSED
1 Limit switch operated in direction CLOSE
0 No signals
Closed positionFor torque seating inend position CLOSED
1 Torque switch and limit switch operatedin direction CLOSE
0 No signals
2 Setpoint reached1
The setpoint is within max. error variable(outer dead band). Signal occurs only ifProfibus DP master has set the RemoteSETPOINT bit.
0 No signals
3 Not ready ind.1
Collective signal: contains the result of adisjunction (OR-operation) of all bits com-prised in the “Not ready ind.” byte(page 23).
0 No signal is active in “Not ready ind.”byte (page 23).
4 Running OPEN1
Operation command (OPEN orSETPOINT) from Profibus DP in directionOPEN is executed. For operation in step-ping mode, this signal is also active dur-ing an off-time, the dead time, and the re-versing prevention.
0 No operation is carried out via ProfibusDP
5 Running CLOSE1
Operation command (CLOSE orSETPOINT) from Profibus DP in directionCLOSE is executed. For operation instepping mode, this signal is also activeduring an off-time, the dead time, and thereversing prevention.
0 No operation is carried out via ProfibusDP
6 Warning ind.1
Collective signal: contains a disjunction(OR-operation) of all bits comprised inthe “Warning ind.” byte (page 25).
0 No warnings are active (all bits of thewarnings cancelled)
7 Fault ind.1
Collective signal: contains the result of adisjunction (OR-operation) of all bits com-prised in the “Fault ind.” byte (page 24)
0 No faults are active (all bits are cancelledin the fault byte)
Table 2
Byte 2: Actuator signals
Bytes 3 and 4:E2 (actual position) high byte
Byte 3 = high byte, byte 4 = low byte.If a position transmitter (potentiometer, RWG, or MWG) is installed in theactuator, bytes 3 and 4 are used to transmit the current actuator position.The value can be transmitted either in percent (value: 0 – 100) or in per mil(value 0 – 1000). The coding (percent or per mil) is selected via the AUMAuser parameter 10: “Format of analogue indication” (page 13).For the scale 0 – 100, only the low byte requires evaluation.
Byte 5: Configurable byte 1
The bits in the configurable byte 5 canbe assigned to different signals. Bit 7is only for fault signals, the other bitsfor other signals. The bit assignmentis defined via parameters in the GSDfile (default assignments are indi-cated in the table).
20
Actuator controls AC 01.1/ACExC 01.1AUMATIC Manual
Bit Designation Value Short description
0 Thermalfault
1 A thermal fault (motor protection) has oc-curred.
0 No thermal fault has occurred.
1 Loss of phase1 One phase is missing.
0 All phases are present.
2 Remote sw position1 Selector switch is in position REMOTE.
0 Selector switch is not in position RE-MOTE.
3 Local sw. position 1 Selector switch is in position LOCAL.
0 Selector switch is not in position LOCAL.
4 LSO (WOEL)1 Limit switch OPEN left operated.
0 Limit switch OPEN left not operated.
5 LSC (WSR)1 Limit switch CLOSE right operated.
0 Limit switch CLOSE right not operated.
6 TSO (DOEL)1 Torque switch OPEN left operated (stor-
ing).
0 Torque switch OPEN left not operated.
7 TSC (DSR)1 Torque switch CLOSE right operated
(storing).
0 Torque switch CLOSE right not operated.
Table 3
Bit Designation Value Short description
0
Closed positionLimit seating in endposition CLOSED
1 Limit switch operated in directionCLOSE.
0 No signals
Closed positionTorque seating in endposition CLOSED
1 Torque switch and limit switch operatedin direction CLOSE.
0 No signals
1
Open positionLimit seating in endposition OPEN
1 Limit switch operated in OPEN direction.
0 No signals
Open positionTorque seating in endposition OPEN
1 Torque switch and limit switch operatedin direction OPEN.
0 No signals
2 Remote sw. position1 Selector switch is in position REMOTE
0 No signals
3 Torque fault(CLOSE)
1 Torque fault in CLOSE direction (storing)
0 No signals
4 Torque fault (OPEN)1 Torque fault in OPEN direction (storing)
0 No signals
Table 4
Byte 6: Physical operation(configurable byte 2)
This is where the information aboutthe actual movement of the actuatoris stored.The bit assignment is defined viaparameters in the GSD file (defaultassignments are indicated in thetable).
Byte 7: Options part 1(configurable byte 3)
The additional freely available inputsand the possibly activated signals ofthe intermediate positions arelocated in the Options part 1. The bitassignment is defined via parame-ters in the GSD file (default assign-ments are indicated in the table).
21
Actuator controls AC 01.1/ACExC 01.1Manual AUMATIC
5 Loss of phase1 One phase is missing
0 No signals
6 Not ready ind.1
Collective signal: contains the result of adisjunction (OR-operation) of all bits com-prised in the “Not ready ind.” byte (page23).
0 No signals
7 Fault ind.1
Collective signal: contains the result of adisjunction (OR-operation) of all bits com-prised in the “Fault ind.” byte (page 24).
0 No signals
Bit Designation Value Short description
0 Operation pause1
Indicates the passing of operation pauses(reversing prevention time, dead time,pause times in stepping mode)
0 No signals
1 (reserved)1
0
2 Start stepping mode1
Indicates that the actuator has enteredthe set stepping range while in steppingmode
0 No signals
3 —1
0
4 Actuator moving1
Collective signal: contains the result of adisjunction (OR-operation) of bit 7, bit 6,and bit 5
0 No signals
5 Runs withhandwheel
1 Indicates a movement at the output drivewithout electrical operation command
0 No signals
6 Runs from REMOTE1
Indicates the movement of the outputdrive during electrical operation fromREMOTE
0 No signals
7 Runs from LOCAL1
Indicates the movement of the outputdrive during electrical operation fromLOCAL
0 No signals
Table 5
Bit Designation Value Short description
0 Intermed.pos. 11 Intermediate position 1 is signalled
0 No signals
1 Intermed.pos. 21 Intermediate position 2 is signalled
0 No signals
2 Intermed.pos. 31 Intermediate position 3 is signalled
0 No signals
3 Intermed.pos. 41 Intermediate position 4 is signalled
0 No signals
Table 6
Byte 8: Options part 2(configurable byte 4)
The contents of Options Part 2 (byte 8) are provided for future extensionsand may be defined within the GSD file via the AUMA user parameters 27 to34 (page 10).
Bytes 9 and 10:DP1 analogue input 1
Byte 9 = high byte, byte 10 = low byte.Bytes 9 and 10 transmit the value of the first additional free analogue cur-rent input of the Profibus DP interface. The start and end values can be setat the AUMATIC via the push-buttons and the display (For operation, pleaserefer to the respective operations instructions for the actuator.).If the measured values are 0.3 mA below the initial value, a signal loss isreported (refer to page 26, byte 16: Warning signals part 2).The value can be transmitted either in percent (value: 0 – 100) or in per mil(value 0 – 1000). The coding (percent or per mil) is selected via the AUMAuser parameter 10: “Format of analogue indication” (page 13).For the scale 0 – 100, only the low byte requires evaluation.
Bytes 11 and 12:Torque
Byte 11 = high byte, byte 12 = low byte.Bytes 11 and 12 transmit the current torque of the actuator (only if an MWGis installed in the actuator).The value transmitted is the current torque in percent or per mil of the nomi-nal actuator torque.The value can be transmitted either in percent (value: 0 – 100) or in per mil(value 0 – 1000). The coding (percent or per mil) is selected via the AUMAuser parameter 10: “Format of analogue indication” (page 13).For the scale 0 – 100, only the low byte requires evaluation.The torque zero point is at 500 or 50.100.0 % torque in direction OPEN corresponds to the value100 or 1000100.0 % torque in direction CLOSE corresponds to the value 0.
22
Actuator controls AC 01.1/ACExC 01.1AUMATIC Manual
4 DP1 dig. input 11 A 24 V signal is present at the digital in-
put 1.
0 No signals
5 DP1 dig. input 21 A 24 V signal is present at the digital in-
put 2.
0 No signals
6 DP1 dig. input 31 A 24 V signal is present at the digital in-
put 3.
0 No signals
7 DP1 dig. input 41 A 24 V signal is present at the digital in-
put 4.
0 No signals
Byte 13: Not ready ind.
The Not ready ind. data byte containsthe indication of causes why the actu-ator can not be operated fromRemote.
Bit 6 CLEAR state: Failure behaviourA failure operation can be initiated in case of bus communication loss.Conditions:. The failure behaviour is activated (FAILURE BEHAVIOUR M1510
parameter is selected).. The source for initiation (FAILURE SOURCE M1514 parameter) is set
to: BUSINTERFACE.Sources for initiation (failure sources) for a failure operation are:. The connection to the master is interrupted.. The master goes into Clear state and sends:
– either global control telegrams with the content Clear.– Or data telegrams of the length 0 (DP fail safe mode).
The failure operation can only be set off when the watchdog function is acti-vated in the master.
As soon as the cause for triggering the failure mode is eliminated (connec-tion restored, master in Operate state), the operation commands from themaster can be executed again at once.
23
Actuator controls AC 01.1/ACExC 01.1Manual AUMATIC
Bit Designation Value Short description
0 Wrong command1
Indicates the fact that several operationcommands were received simultaneouslyvia Profibus DP (e.g. Remote OPEN andRemote CLOSE simultaneously or Re-mote CLOSE/Remote OPEN and Re-mote SETPOINT simultaneously) or thatthe maximum value for a setpoint hasbeen exceeded (setpoint > 1,000).
0 Operation commands are o.k.
1 Selector not remote1 Selector switch position: REMOTE or
OFF
0 Selector switch position: REMOTE
2 Actuator locked1 Actuator locked (only set for special ap-
plications e.g. for by-pass function)
0 Actuator released
4 Emcy stopactive
1 The EMERGENCY STOP button (option)has been operated.
0The EMERGENCY STOP button has notbeen not operated(normal operation)
3 —1
0
5 Emergency mode1 Emergency mode is active.
0 Normal operation
6 Clearstate
1
Indicates that a Global Control Clear tele-gram was sent via the Profibus DP (thebit can only be deleted with a GlobalControl Operate telegram). In this statethe actuator cannot be operated fromREMOTE.
0
7 Externaloperation
1
External operation (option). As soon asthe BUS/REMOTE input is connected to24 V DC (or 115 V AC), the AC will onlyreact to operation commands by the I/Ointerface or the additional bus inputs(OPEN - STOP - CLOSE or MODE and0/4 – 20 mA).
0 Normal operation
Table 7
NOTICE
Byte 14: Fault signals
The fault signals contain the causeswhy the actuator cannot be operated.
24
Actuator controls AC 01.1/ACExC 01.1AUMATIC Manual
Bit Designation Value Short description
0 Config. fault1
Indicates a faulty configuration, i.e. thecurrent setting of the AUMATIC is notvalid, the exact cause can be determinedfrom a diagnosis indication (D4) on thedisplay.
0 AUMATIC has been correctly configured
1 —1
0
2 Thermalfault
1
Motor protection tripped; remedy: cooldown, wait or perform a reset of the localcontrols using the Reset push button af-ter cooling-down. Check fuse F4.
0 No fault
3 Loss of phase1
One phase missing; remedy: connectphase. When externally supplied with 24V DC, the complete AC power supplymight be missing, check and connect ifnecessary.
0 No signals
4 Torque fault (OPEN)1
Torque fault OPEN occurred (only torqueor torque before limit, depending on thetype of seating); remedy: reset with coun-ter command, or with Reset push buttonof the local controls.
0 No fault
5 Torque fault(CLOSE)
1
Torque fault CLOSED occurred (onlytorque or torque before limit, dependingon the type of seating); remedy: resetwith counter command, or with Resetpush button of the local controls.
0 No fault
6 Internalfault
1
The internal diagnostics of the AUMATIChave detected a fault (the precise causecan be viewed on diagnosis page D2 andDQ of the display).
0 No fault
7 —1
0
Table 8
Byte 15:Warning signals part 1
The two data bytes 15 and 16 containwarning signals. The warning signalsserve only information purposes anddo not interrupt or cancel an opera-tion (as opposed to faults).
25
Actuator controls AC 01.1/ACExC 01.1Manual AUMATIC
Bit Designation Value Short description
0 P-FeedbackE4 loss
1Signal loss of the actual process valueE4 (only if PID controller is available andactive).
0 No loss of signal
1 —1
0
2 Anlog In1I/O1 loss
1Loss of signal of the analogue input 1 ofthe parallel interface (only for ProfibusDP in combination with parallel interface).
0 No loss of signal
3 Analog In2I/O1 loss
1Loss of signal of the analogue input 2 ofthe parallel interface (only for ProfibusDP in combination with parallel interface).
0 No loss of signal
4 Internalwarning
1
The internal diagnostics of the AUMATIChave detected a warning (the exact causecan be determined on the diagnosis pageD3 of the display).
0 No warning
5 Internal feedback1
Indicates that the position transmitter hasnot been adjusted to the limit end posi-tions yet.To adjust the actuator: Move the actuatormanually to the end positions OPEN orCLOSED using the push buttons on thelocal controls.
0 No reference operation
6 Starts/run1
Indicates an exceeding of the set limits ofthe starts/run monitoring, signal is de-leted automatically.
0 No warning
7Operation time
1
Indicates that the set operating time foran operation from one end position to theother has been exceeded, the next newoperation command deletes thisindication.
0 No warning
Table 9
Byte 16:Warning signals part 2
The warning signals part 2 containthe wire break signals of the differentinputs.
26
Actuator controls AC 01.1/ACExC 01.1AUMATIC Manual
Bit Designation Value Short description
0 Torque E6 loss1 A signal loss has occurred for the torque
measuring.
0 No warning
1 Fiber optic loss1)1 Presence of FO cable interruption
0 No loss of signal
2 Feedback E2 loss1 A signal loss has occurred for the actual
position.
0 No loss of signal
3 Setpoint E1 loss1 A signal loss has occurred for the nomi-
nal position.
0 No loss of signal
4 —1
0
5 —1
0
6 Analog In2 DP1 loss1 A signal loss has occurred in the ana-
logue input 2.
0 No loss of signal
7 Analog In1 DP1 loss1 A signal loss has occurred in the ana-
logue input 1.
0 No loss of signal1) Only for Profibus DP with FO loop topology
Table 10
Bytes 17 and 18:DP1 analogue input 2
Byte 17 = high byte, byte 18 = low byte.Bytes 17 and 18 transmit the value of the second additional free analoguecurrent input of the Profibus DP interface.The start and end values can be set at the AUMATIC via the push buttonsand the display. (For information about operation, refer to operation instruc-tions for the actuator).If the measuring values are 0.3 mA below the initial value a cable break isindicated.The value can be transmitted either in percent (value: 0 – 100) or in per mil(value 0 – 1000). The coding (percent or per mil) is selected via the AUMAuser parameter 10: “Format of analogue indication” (page 13).For the scale 0 – 100, only the low byte requires evaluation.
Bytes 19 to 22: Reserved The contents of bytes 19 to 22 are reserved for future extensions.
Byte 23: Additional data
Feedback signals of the intermediatepositions
Byte 24: Reserved The contents of byte 24 are reserved for future extensions.
27
Actuator controls AC 01.1/ACExC 01.1Manual AUMATIC
Bit Designation Value Short description
0 Intermed.pos. 51 Intermediate position 5 is signalled.
0 No signals
1 Intermed.pos. 61 Intermediate position 6 is signalled.
0 No signals
2 Intermed.pos. 71 Intermediate position 7 is signalled.
0 No signals
3 Intermed.pos.81 Intermediate position 8 is signalled.
0 No signals
4 (reserved)1
0
5 (reserved)1
0
6 (reserved)1
0
7 In intermed.position
1
Is set if the actuator does not execute anoperation command and is neither in endposition OPEN nor in end positionCLOSED
0 No signals
Table 11
4.2. Output data (Process representation output)
The master (controls) can control the slave (actuator) via the process repre-sentation output.
Information To be able to perform remote operations, the selector switch must be inposition REMOTE.
4.2.1 Description of the output data
Byte 1: Commands (high byte)
28
Actuator controls AC 01.1/ACExC 01.1AUMATIC Manual
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Rem
ote
OP
EN
Rem
ote
CLO
SE
D
Rem
ote
SE
TP
OIN
T
Byte 1: Commands Byte 4: E1 (Setpoint)Byte 3: E1 (Setpoint)Byte 2: E3 (reserved)
Res
et
Setpoint high byte Setpoint low byte
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Byte 5: Additional commands Byte 6: Operation commands for multiport valve function1)
Cha
nnel
2
Loca
l sw
. pos
ition
Off
sw. p
ositi
on
Rem
ote
sw. p
ositi
on
Cha
nnel
1
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Inte
rmed
. pos
. 8
Inte
rmed
. pos
. 7
Inte
rmed
. pos
. 6
Inte
rmed
. pos
. 5
Inte
rmed
. pos
. 4
Inte
rmed
. pos
. 3
Inte
rmed
. pos
. 2
Inte
rmed
. pos
. 1
LOC
AL-
OF
F/R
EM
OT
E
Bit Designation Value
Short description
0 Remote OPEN1 Operation command in direction OPEN
0 No operation
1 Remote CLOSED1 Operation command in direction CLOSE
0 No operation
2 Setpoint mode1 Run to setpoint (setpoint is provided via
bytes 3 and 4)
0 No operation
3 RESET1
Certain indications of the AUMATIC canbe reset (e.g. PTC tripping device andtorque faults). The function of this bit cor-responds to the Reset push button at thelocal controls.
0 No command
4 —1
0
5 —1
0
Table 12
Bits 0, 1, 2 = operation commandsBits 0 – 2 are used to transmit operation commands to the actuator.Only one command bit may be set to 1 at any one time. If several commandbits are set, no operation is performed and the Wrong command fault sig-nal is given.For operation commands via the Remote SETPOINT bit:. A position transmitter (potentiometer, RWG, MWG) is required in the
actuator for sending operation commands via the Remote SETPOINTbit.
. If the setpoint is 0 percent/per mil, the actuators runs to the end positionCLOSED; it runs to the end position OPEN for 100 percent/1000 per mil.
. If the setpoint exceeds the limit 100 or 1000, the actuator stops and sig-nals Wrong command
. To avoid placing too much strain on the mechanics, the reversing ofdirection is delayed. The standard setting in the factory for the reversingprevention time is 300 ms.
Bits 4, 5, 6, 7Bits 4 through 7 are not used and must be set to 0.
Byte 2: Reserved Not used
Bytes 3 and 4: Setpoint E1 Setpoint E1 is transmitted via bytes 3 and 4.
The value can be transmitted either in percent (value: 0 – 100) or in per mil(value 0 – 1000). The coding (percent or per mil) is selected via the AUMAuser parameter 10: “Format of analogue indication” (page 13).For the scale 0 – 100, only the low byte requires evaluation.
29
Actuator controls AC 01.1/ACExC 01.1Manual AUMATIC
6 —1
0
7 —1
0
Condition Value byte 3(High-Byte)
Value byte 4(Low-Byte)
AUMA user parameter:Format of analogue indica-tions = 0
0 Setpoint 0...100
AUMA user parameter:Format of analogue indica-tions = 1
Setpoint 0...1000 Setpoint 0...1000
Table 13
Byte 5: Additional commands
Bits 1, 2, 3: Local controls enable function (option)The selector switch functions on the local controls (LOCAL, OFF, andREMOTE) may be either enabled or disabled via the fieldbus.Precondition:ENABLE LOCAL MODE parameter is set to:. BUS, or. BUS, AUTO LOCAL, or. BUS, AUTO REMOTE, or. BUS, AUTO
The ENABLE LOCAL MODE parameter also determines the behaviour incase of bus failure.For further information, please refer to the AUMATIC AC 01.1 Profibus DPmanual (operation and setting).
Bits 4, 5: Redundant bus connection with component redundancy(option)In addition to the first fieldbus interface, the AUMATIC actuator controls canbe equipped with a second fieldbus interface. The 2nd interface may beused to increase the operational safety. If one of the interfaces fails, theother interface automatically takes over (component redundancy).If there is a communication to the master available via both fieldbus inter-faces, the operation commands of the interface which first established acommunication to the master will be executed.
Information Both fieldbus components must be identically programmed by the master(identical setting of the GSD file).
30
Actuator controls AC 01.1/ACExC 01.1AUMATIC Manual
Bit Designation Value Short description
0 Remote sw. posi-tion
1 Selector switch position REMOTE is re-leased.
0 Selector switch position REMOTE islocked.
1 Remote sw. posi-tion
1 Selector switch position OFF is released.
0 Selector switch position OFF is locked.
2 Local sw. position1 Selector switch position LOCAL is re-
leased.
0 Selector switch position LOCAL islocked.
3 —1
0
4 Channel 11 Change-over to Profibus DP communi-
cation channel 1
0 No change-over
5 Channel 21 Change-over to Profibus DP communi-
cation channel 2
0 No change-over
6 LOCAL-OFF/REMOTE
1 AUMATIC changes to REMOTE.
0 Selector switch positions LOCAL andOFF enabled.
7 —1
0
Table 14
Bits 4 and 5 (channels 1 and 2) are used to select a communication chan-nel:
Information . Only a transition between these bits causes a change-over. This means,the change-over is initiated by 0 � 1 transition.
. If the bit for channel changing is set, the addition of the second bit doesnot have any effect.
. Transition from one channel to the other is supported, i.e. bits can bechanged simultaneously (e.g. channel A: 1 ��� and channel B: 0 � 1).
The change-over is only performed if the bits in the process representation areset accordingly and both fieldbus interfaces communicate with the master.
Bit 6: Enable function LOCAL-OFF/REMOTE of the local controls(option)The selector switch functions on the local controls LOCAL or OFF may beeither enabled or disabled via the fieldbus. Furthermore the REMOTE modeof the AUMATIC can be forced independently from the actual selector switchposition.Precondition:ENABLE LOCAL MODE parameter is set to:. BUS, AUTO LOCAL II
The ENABLE LOCAL MODE parameter also determines the behaviour incase of bus failure.For bit 6 = 1 (AUMATIC changes to REMOTE) the AC mode is alwaysREMOTE, independently from the actual selector switch position.For bit 6 = 0 (selector switch positions LOCAL and OFF are enabled), theAC mode depends on the actual selector switch position. Only the LOCALand OFF modes are possible.
Information Observe during commissioning and maintenance: Any control fromREMOTE via the system cannot be interrupted or blocked locally viathe selector switch position.For further information, please refer to the “Manual (operation and setting)AUMATIC AC 01.1 Profibus DP”.
31
Actuator controls AC 01.1/ACExC 01.1Manual AUMATIC
Bit 5Chan-nel 2
Bit4Chan-nel 1
Meaning
0 0 No channel selected, change-over does not take place. Thepreviously selected channel remains active.
0 0 � 1 Change-over to channel 1 (A) is started.
0 1 Channel 1 (A) remains selected
0 1 � 0 Channel 1 (A) remains selected.
0 0 Channel remains active.
0 � 1 0 Switch-over to channel 2 (B) is started.
1 0 Channel 2 (B) remains selected.
1 � 0 0 Channel 2 (B) remains selected.
0 0 Channel remains active.
0 � 1 0 � 1 No change-over.
1 0 � 1 No change-over.
0 � 1 1 No change-over.
1 1 Channel remains active.
0 � 1 1 � 0 Change-over to channel 2 (B) is started.
1 � 0 0 � 1 Change-over to channel 1 (A) is started.
Table 15
Byte 6: Operation commandsfor multiport valve func-
tion(option)
Bits 0 – 7 allow the direct selection of 8 intermediate positions via fieldbuscommands. Hereby the selected intermediate position is approacheddirectly, without stopping in another intermediate position.
In this case, the actuator continues running until the selected intermediateposition has been reached. Example: Operation from position 5 to 7 withoutstopping at position 6.For further information, please refer to the AUMATIC AC 01.1 Profibus DPmanual (operation and setting).
Bytes 7 to 16 The contents of bytes 7 to 16 are reserved for future extensions and shouldbe set to 0.
32
Actuator controls AC 01.1/ACExC 01.1AUMATIC Manual
Bit Designation Value Short description
0 Intermed. pos.11 Actuator is to approach intermediate po-
sition 1.
0 No command
1 Intermed. pos.21 Actuator is to approach intermediate po-
sition 2.
0 No command
2 Intermed. pos.31 Actuator is to approach intermediate po-
sition 3.
0 No command
3 Intermed. pos.41 Actuator is to approach intermediate po-
sition 4.
0 No command
4 Intermed. pos.51 Actuator is to approach intermediate po-
sition 5.
0 No command
5 Intermed. pos.61 Actuator is to approach intermediate po-
sition 6.
0 No command
6 Intermed. pos.71 Actuator is to approach intermediate po-
sition 7.
0 No command
7 Intermed. pos.81 Actuator is to approach intermediate po-
sition 8.
0 No command
Table 16
5. Description of the Profibus DP board
Profibus DP board:
5.1. Displays (optical signals)
V1: LED system OK (green) Shows the correct voltage supply to the Profibus DP board.
Is continuously illuminated: Voltage connected to Profibus DP board.Is blinking: Microcontroller defective.Is not illuminated: No voltage at the DP board.
V2: LED DATA EX (green) If the LED is illuminated, the Profibus DP interface has entered the ‘DataExchange’ state. Controlling the actuator by the DP master and reading theactuator state can be performed in this state only.
V3: LED CAN STATE (red) Is illuminated or blinking: Communication to logic is faultyIs not illuminated: Communication with logic is in order.
V4: LED STATE (green) Is illuminated ornot illuminated: Profibus DP board is not readyIs blinking: Program on the Profibus DP board is being
executed.
Regular single blinking of the LED during operation indicates correct func-tion of the Profibus DP board.
V16, V19, V22, V25 LEDs of the digital customer inputs (option); they are illuminated when+ 24 V are applied to the inputs.
33
Actuator controls AC 01.1/ACExC 01.1Manual AUMATIC
Figure 1
X2 Plug Profibus DP connection S1 DIP switch redundancyX4 Plug customer inputs V16 LED digital input 1V1 LED system OK (green) V19 LED digital input 2V2 LED DATA EX (green) V22 LED digital input 3V3 LED CAN STATE V25 LED digital input 4V4 LED STATE
5.2. Connections:
5.2.1 Profibus DP bus connectionThe bus signals and the galvanically isolated voltage supply for the bus ter-mination, as well as the bus termination resistors located on the Profibus DPboard are connected on the X2 plug.
5.2.2 Customer inputs (option)Plug X4 provides pins for 4 digital customer inputs and 2 analogue customerinputs.Table 18: Digital inputs (galvanically isolated)
These signals are freely available inputs, which the microcontroller transmitsinto the process representation input (OPTIONS part 1, bits 4 to 7). Theinputs are galvanically isolated and internally connected to 0 V via pull-downresistors. In an unconnected state, a logical zero is transmitted. To set aninput to logical one, + 24 V DC must be applied.Table 19: Analogue inputs
External 0/4 – 20mA sensors for transmitting the measured values via theProfibus DP can be connected to these inputs.
Information The measuring range of analogue inputs can be set viaCONFIGURATION(M40)>SETUP(M41) parameter.
34
Actuator controls AC 01.1/ACExC 01.1AUMATIC Manual
Pin Description1 Channel 1: B cable bus termination2 Channel 1: A cable bus termination3 Channel 1: Profibus B cable4 Channel 1: Profibus A cable8 Channel 2: Profibus A cable (redundant channel)7 Channel 2: Profibus A cable (redundant channel)9 Channel 2: Profibus termination B cable (redundant channel)10 Channel 2: Profibus termination A cable (redundant channel)
Table 17
Pin Description LED9 R1: digital input 1 V 1610 R2: digital input 2 V 1911 R3: digital input 3 V 2212 R4: digital input 4 V 258 0 V
Table 18
Pin Description3 AN1: Analogue signal (0 – 20 mA)4 GND (System ground)5 AN2: Analogue signal (0 – 20 mA)6 GND (System ground)
Table 19
Damage on the Profibus DP board in case of incorrect connection!� Observe proposed external wiring diagrams (see appendix).� The bounce time of the connected switches should not be more than 1
ms.� The inputs AN1 and AN2 do not have galvanic isolation via opto-isolator.
NOTICE
5.2.3 Redundant bus connection with component redundancy (option)
DIP switch S1 (figure 1).
35
Actuator controls AC 01.1/ACExC 01.1Manual AUMATIC
S1-1
Only one Profibus DP interfaceavailable
OFF
Two Profibus DP interfaces avail-able
1st Profibus DP interface: OFF
2nd Profibus DP interface: ONS1-2 Reserved OFF
Table 20
6. Corrective actions
6.1. Fault indications and warning indications
Faults interrupt or prevent the electrical operation of the actuator.Warnings have no influence on the electrical operation of the actuator. Theyonly serve information purposes.Fault and warning indications are shown on the display (status indications S).
6.2. Diagnostics
The information contained in the diagnostic indications is only provided forthe AUMA service and for enquiries in the factory.The diagnostic indications can be called up during trouble-shooting via thedisplay (group D).
6.3. Troubleshooting
36
Actuator controls AC 01.1/ACExC 01.1AUMATIC Manual
Change to the
diagnotic page
DE
DP1 BUS STATUS
DP1 BUS STATUS
DATA EX
indicates:or
LED (V2) is illuminated on Profibus DP board
No communicationbetween
slave and master
Profibus DPcommunication
correct
No baud ratefound
- Check master- Check wiring- Check bus connection
DP1 BUS STATUS
BAUD SEARCH
indicates:
yes no
yes
Incorrect configurationdata.Correct configurationin the master,configuration datanot yet sent:Send configurationdata
Fault in the internalDP status machine:switch actuator offand on
no
Parameter data in-correct. Correctparameters in themaster.Parameters not yetsent. Sendparameters.Possibly thewrong GSD filewas used.
2
1
3
DP1 BUS STATUS
WAIT PRM
indicates:no
yes
DP1 BUS STATUS
WAIT CFG
indicates:no
yes
DP1 BUS STATUS
DP FAULT
indicates:no
yes
Actuator cannot be controlledvia Profibus DP
37
Actuator controls AC 01.1/ACExC 01.1Manual AUMATIC
DP1 BUS STATUS
GC CLEAR
DATA WITH LENGTH 0
indicates:or
no yes
If necessary, switch offAutoclear-Funktionin the master. SendGC OPERATE telegram
yes no
2
Slave isin
Fail Safe state
Check all other programmedlaves at the Profibus.s
3
4
Profibus DPcommunication
correct
Operationvia local
controls possible?
Master doesnot give operation
command or incorrectoperation command
Check programmingof controls
Other faults:(torque, thermal,or internal faults)
logic board,motor controls andmotorProfibus DP board
38
Actuator controls AC 01.1/ACExC 01.1AUMATIC Manual
Profibus DP boarddefective
Check LED V1: SYSTEM OK on Profibus board
Voltage supplyof the Profibus DP
board is correct
Check Profibus DPboard
ExchangeProfibus DP board
Check connection oflogic and ProfibusDP board. If necessaryexchange boardCheck programming
Profibus DP board notsupplied with voltage
Check voltage supplyof the AUMATICCheck fusesCheck Profibus DPboard
V1 is continuously illuminated V1 is blinking V1 is not illuminated
LED V4: STATE blinking
LED V3: CAN STATEilluminated or blinking?
Program on theProfibus DP board
is executed
internal communicationfaulty or
incorrectly configured
yes
yes
no
no
Internal communicationcorrect
1
4
6.3.1 Measuring the Profibus signals using an oscilloscope
1. Open terminal compartment (refer to operation instructions on the actua-tor)
2. Check Profibus signal, channel 1, on the connection board, and pin 2(N/A) and pin 1 (P/B) on plug (X1) with a digital oscilloscope.The off-load voltage between pin 1 (+) and pin 2 (-) must be positive andin the range between 0.8 V and 1.4 V.
Figure 2 shows the connection board (standard version).
39
Actuator controls AC 01.1/ACExC 01.1Manual AUMATIC
S1
X1
X3
P/B
X2
P/B
N/A
N/A
Figure 2
S1 Bus termination channel 1 X1 Channel 1, � from the previous deviceX2X3
Channel 1, � to the next deviceShielding clamp
7. Technical data
Settings/programming the Profibus DP interfaceSetting the baud rate Automatic baud rate recognitionSetting the Profibus DP interface The setting of the Profibus DP address is made via the display of the AUMATICConfigurable processrepresentation via GSD file
For an optimal adaptation to the process control system, 4 different process representations areavailable.Additionally, the contents of four signal bytes are freely programmable.
Commands and signals of the Profibus DP interfaceProcess representation output(command signals)
OPEN, STOP, CLOSE, nominal position value1), RESET
Process representation input(feedback)
End position OPEN, CLOSEDActual position value3)
Actual torque value6)
Selector switch in position LOCAL/REMOTERunning indication 3) (directional)Torque switch OPEN, CLOSEDLimit switch OPEN, CLOSEDManual operation by handwheel 3) or local controlsAnalogue (2) and digital (4) customer inputs
Process representation input(fault signals)
Motor protection trippedTorque switch tripped in mid-travelOne phase missingLoss of the analogue customer inputs
Behaviour on loss ofcommunication
The behaviour of the actuator is programmable:- stop in current position- move to end position OPEN or CLOSED- move to any intermediate position1)
General data Profibus DPCommunication protocol Profibus DP according to IEC 61158 and 61784Network topology Linear (bus) structure. When using repeaters, tree structures can also be implemented.
Coupling and uncoupling of devices during operation without affecting other devices ispossible.
Transmission medium Twisted, screened copper cable according to EN 50 170Profibus DP interface EIA-485 (RS485)Transmission speed/cable length
Device types DP master class 1, e.g. central controllers such as PLC, PC, ...DP master class 2, e.g. programming/configuration toolsDP slave, e.g. devices with digital and/or analogue inputs/outputs such as actuators,sensors
Number of devices 32 devices without repeater, with repeater expandable to 126Bus access Token-passing between the masters and polling for slaves.
Mono-master or multi-master systems are possible.Supported Profibus DP functions Cyclic data exchange, sync mode, freeze mode, fail-safe mode
1) Requires position transmitter in actuator
40
Actuator controls AC 01.1/ACExC 01.1AUMATIC Manual
Baud rate (kbit/s) Max. cable length(segment length) without
repeaterPossible cable length with
repeaters (total network cablelength)
9.6 – 93.75187.5
5001,500
1,200 m1,000 m
400 m200 m
approx. 10 kmapprox. 10 kmapprox. 4 kmapprox. 2 km
8. Appendix – Proposed external wiring diagram
8.1. Connecting external sensors, 2-wire technology
41
Actuator controls AC 01.1/ACExC 01.1Manual AUMATIC
8.2. Connecting external sensors, 3-wire technology
42
Actuator controls AC 01.1/ACExC 01.1AUMATIC Manual
8.3. Connecting external sensors, 4-wire technology
43
Actuator controls AC 01.1/ACExC 01.1Manual AUMATIC
Notes
44
Actuator controls AC 01.1/ACExC 01.1AUMATIC Manual
IndexAAlarm contact 12
BBasic functions 7Bus access 7Bus failure 30
CCollective fault signal 12Commissioning 8Communication 7Component redundancy 30,35Configuration 24Corrective actions 36
DDead band 19Dead time 19,21Device types 7Diagnostics 36
EEnable local controls 30Error variable 19
FFailure behaviour 23Failure operation 23Failure source 23Faults 24,36Functionality 7
HHandwheel 21
LLimit seating 19
MMeasuring the Profibus signals 39Motor protection 20,24
OOperating time 25
PParameter setting 8Pause time 21Percent/per mil change-over 13Phase loss 24Process representation 15,28Process representation input 10Protective functions 7
RRange of application 5Redundant bus connection 30,35Remote operation 28
SSafety instructions 4Selector switch 20,23Signals 19Signals via fieldbus 15Source for initiation 23Stepping mode 19,21
TTechnical data 40Transfer mode 7Troubleshooting 36Type of seating 24
WWarnings 19,36
45
Actuator controls AC 01.1/ACExC 01.1Manual AUMATIC
EuropeAUMA Riester GmbH & Co. KGPlant MüllheimDE-79373 MüllheimTel +49 7631 809 - 0Fax +49 7631 809 - [email protected]
Plant Ostfildern-NellingenDE-73747 OstfildernTel +49 711 34803 - 0Fax +49 711 34803 - [email protected]
Service-Center KölnDE-50858 KölnTel +49 2234 2037 - 9000Fax +49 2234 2037 - [email protected]
Service-Center MagdeburgDE-39167 NiederndodelebenTel +49 39204 759 - 0Fax +49 39204 759 - [email protected]
Service-Center BayernDE-85386 EchingTel +49 81 65 9017- 0Fax +49 81 65 9017- [email protected]
AUMA Armaturenantriebe GmbHAT-2512 TribuswinkelTel +43 2252 82540Fax +43 2252 [email protected]
AUMA (Schweiz) AGCH-8965 BerikonTel +41 566 400945Fax +41 566 [email protected]
AUMA Servopohony spol. s.r.o.CZ-250 01 Brandýs n.L.-St.BoleslavTel +420 326 396 993Fax +420 326 303 [email protected]
OY AUMATOR ABFI-02230 EspooTel +358 9 5840 22Fax +358 9 5840 [email protected]
AUMA France S.A.R.L.FR-95157 Taverny CedexTel +33 1 39327272Fax +33 1 [email protected]
AUMA ACTUATORS Ltd.GB- Clevedon North Somerset BS21 6QHTel +44 1275 871141Fax +44 1275 [email protected]
AUMA ITALIANA S.r.l. a socio unicoIT-20023 Cerro Maggiore (MI)Tel +39 0331 51351Fax +39 0331 [email protected]
AUMA BENELUX B.V.NL-2314 XT LeidenTel +31 71 581 40 40Fax +31 71 581 40 [email protected]
AUMA Polska Sp. z o.o.PL-41-310 Dabrowa GórniczaTel +48 32 261 56 68Fax +48 32 261 48 [email protected]
OOO Priwody AUMARU-141400 Moscow region for mail:124365 Moscow a/ya 11Tel +7 495 221 64 28Fax +7 495 221 64 [email protected]
ERICHS ARMATUR ABSE-20039 MalmöTel +46 40 311550Fax +46 40 [email protected]
GRØNBECH & SØNNER A/SDK-2450 København SVTel +45 33 26 63 00Fax +45 33 26 63 [email protected]
IBEROPLAN S.A.ES-28027 MadridTel +34 91 3717130Fax +34 91 [email protected]
D. G. Bellos & Co. O.E.GR-13671 Acharnai AthensTel +30 210 2409485Fax +30 210 [email protected]
SIGURD SØRUM A. S.NO-1300 SandvikaTel +47 67572600Fax +47 [email protected]
INDUSTRAPT-2710-297 SintraTel +351 2 1910 95 00Fax +351 2 1910 95 [email protected]
MEGA Endüstri Kontrol Sistemieri Tic. Ltd.Sti.TR-06810 AnkaraTel +90 312 217 32 88Fax +90 312 217 33 [email protected]
CTS Control Limited Liability CompanyUA-02099 KiyivTel +38 044 566-9971, -8427Fax +38 044 [email protected]
AfricaAUMA South Africa (Pty) Ltd.ZA-1560 SpringsTel +27 11 3632880Fax +27 11 [email protected]
A.T.E.C.EG- CairoTel +20 2 23599680 - 23590861Fax +20 2 [email protected]
AmericaAUMA ACTUATORS INC.US-PA 15317 CanonsburgTel +1 724-743-AUMA (2862)Fax +1 [email protected]
AUMA Automação do Brasil Ltda.BR-Sao PauloTel +55 11 [email protected]
AUMA Chile Representative OfficeCL-9500414 BuinTel +56 2 821 4108Fax +56 2 281 [email protected]
LOOP S. A.AR-C1140ABP Buenos AiresTel +54 11 4307 2141Fax +54 11 4307 [email protected]
TROY-ONTOR Inc.CA-L4N 5E9 Barrie OntarioTel +1 705 721-8246Fax +1 705 [email protected]
MAN Ferrostaal de Colombia Ltda.CO- Bogotá D.C.Tel +57 1 401 1300Fax +57 1 416 [email protected]
PROCONTIC Procesos y Control AutomáticoEC- QuitoTel +593 2 292 0431Fax +593 2 292 [email protected]
IESS de Mexico, S.A. de C.V.MX-C.P. 02900 Mexico D.F.Tel +52 55 55 56 1701Fax +52 55 55 56 [email protected]
Corsusa International S.A.C.PE- Miralflores - LimaTel +511444-1200 / 0044 / 2321Fax [email protected]
PASSCO Inc.PR-00936-4153 San JuanTel +18 09 78 77 20 87 85Fax +18 09 78 77 31 72 [email protected]
SuplibarcaVE- Maracaibo Estado, ZuliaTel +58 261 7 555 667Fax +58 261 7 532 [email protected]
AsiaAUMA Actuators (Tianjin) Co., Ltd.CN-300457 TianjinTel +86 22 6625 1310Fax +86 22 6625 [email protected]
AUMA (INDIA) PRIVATE LIMITEDIN-560 058 BangaloreTel +91 80 2839 4655Fax +91 80 2839 [email protected]
46
AUMA worldwide
AUMA JAPAN Co., Ltd.JP-210-0848 Kawasaki-ku, Kawasaki-shiKanagawaTel +91 80 2839 4655Fax +81 44 366 [email protected]
AUMA ACTUATORS (Singapore) Pte Ltd.SG-569551 SingaporeTel +65 6 4818750Fax +65 6 [email protected]
AUMA Actuators Middle East W.L.L.AE- 15268 Salmabad 704Tel +973 [email protected]
PERFECT CONTROLS Ltd.HK- Tsuen Wan, KowloonTel +852 2493 7726Fax +852 2416 [email protected]
DW Controls Co., Ltd.KR-153-803 Seoul KoreaTel +82 2 2113 1100Fax +82 2 2113 1088/[email protected]
Sunny Valves and Intertrade Corp. Ltd.TH-10120 Yannawa BangkokTel +66 2 2400656Fax +66 2 [email protected]/
Top Advance Enterprises Ltd.TW- Jhonghe City Taipei Hsien (235)Tel +886 2 2225 1718Fax +886 2 8228 [email protected]
AustraliaBARRON GJM Pty. Ltd.AU-NSW 1570 ArtarmonTel +61 294361088Fax +61 [email protected]
2009-01-22
47
Certificate Registration No.12 100/104 4269
AUMA Riester GmbH & Co. KGP.O.Box 1362D-79373 MüllheimTel +49 7631 809 - 0Fax+49 7631 809 - [email protected]
For detailed information on AUMA products refer to the Internet: www.auma.com
Y000.082/003/en/2.09