    PROGRAM CONTACT PERSON LIST

    Asbestos Management.....................................................Art Schweitzer

    AED..........................................................................George Berndt

    AWAIR........................................................................Art Schweitzer

    Bleacher Safety............................................................ Art Schweitzer

    Bloodborne Pathogens......................................................Judy Huisman

    Community Right-to-Know...............................................Art Schweitzer

    Compressed Gas Safety...................................................Art Schweitzer

    Confined Space Entry.....................................................Art Schweitzer

    Emergency Action Planning...............................................Art Schweitzer

    Employee Right-to-Know/Hazard Communication...................Art Schweitzer

    Facilities Safety Management............................................Art Schweitzer

    First Aid/CPR ................................................................Judy Huisman

    Hazardous Waste Management..........................................Art Schweitzer

    Hearing Conservation.....................................................Art Schweitzer

    Indoor Air Quality..........................................................Art Schweitzer

    Integrated Pest Management............................................Art Schweitzer

    Laboratory Standard/Chemical Hygiene Plan......................................Matt

    McDowell

    Lead Management.........................................................Art Schweitzer

    Lockout/Tagout ...........................................................Art Schweitzer

    Machine Guarding .........................................................Art Schweitzer

    Personal Protective Equipment.........................................Art Schweitzer

    Playground Safety.........................................................Art Schweitzer

    Radon Gas Safety..........................................................Art Schweitzer

    Respiratory Protection...................................................Art Schweitzer

    USTs/ASTs...................................................................Art Schweitzer

    Welding Cutting Brazing....................................................Darrel Mayer

    http://opt/scribd/conversion/tmp/scratch24327/ActivitiesCheclist08-09.doc#Checklist%20of%20E/OHS%20Activities%20for%20Asbestos%20Managementhttp://opt/scribd/conversion/tmp/scratch24327/ActivitiesCheclist08-09.doc#Checklist%20of%20E/OHS%20Activities%20for%20Asbestos%20Management
  • 8/3/2019 ActivitiesCheclist10-11_3

    2/68

  • 8/3/2019 ActivitiesCheclist10-11_3

    3/68

    Checklist of E/OHS Activities for Asbestos Management

    Program Contact Person: Art Schweitzer

    Is the Asbestos Management Plan in place? Yes No N/A

    Is the Plan current for all buildings? Yes No N/A

    Has the Plan (or Plans) been reviewed this school year? Yes No N/A

    The Plan is located at affected building: Yes.

    Training for Asbestos Awareness was conducted October 24, 2008 .

    New PT employees received training on 10-24-2007 .

    (date)

    Annual written notification has been prepared; Yes .

    (date)

    Notification appeared in the following publication(s):

    Name of publication DateFall News letter Fall, 2010

    Three-year re-inspection Surveillance was conducted: 6/29/2010 .

    6-month Periodic Surveillance was conducted: 6/29/2010(first date)

    02/15/2011(second date)

    All caution labels have been posted.Label locations: Boiler room

    Tunnels

    Hard lagging

    Are supplies of repair materials adequate to meet the requirements ofmaintenance and repair of ACM? Yes No N/A

  • 8/3/2019 ActivitiesCheclist10-11_3

    4/68

    Asbestos Maintenance Supplies on Hand

    Bags Respirators Wrap-n-cure

    Is documentation of Operations and Maintenance available?

    Location: District Office

    Status of the Asbestos repair and maintenance Work Order System: N/AEstablished, Pending

    Comments: Repairs to asbestos are limited to replacement of damagedfloor tile.

    **For information regarding the medical review and questionnaire, see theRespiratory Protection Program.**

    Note: click here this link to review 6 month periodics.

    The tunnels were cleaned and maintained during the summer of 2009. Thiswork was conducted as O&M activities. LC

    http://opt/scribd/conversion/tmp/AsbestosFolderhttp://opt/scribd/conversion/tmp/AsbestosFolder
  • 8/3/2019 ActivitiesCheclist10-11_3

    5/68

    Checklist of E/OHS Activities for Automatic External Defibrillator

    Program Contact Person: George Berndt

    School policy for use adopted in place? Yes No N/A

    Brand of AED? Heart Start FRx Model: IP55

    Name of Medical Director? The director is yet to be determined.

    Year device was placed into use? 2010

    Location(s) of devices:Building Name Location in Building

    Ellsworth Public School Gym entrance

    Have all software updates been installed? Yes No N/A

    Date of update installation: 12-2010

    Expiration date of pads? 12-2012

    Expiration date of batteries? 01-2016(date)

    Has staff been trained on operation of the device? Yes, all school staff.

    Most recent date of training:12-2010(date

    Provider of training: Mary Lubben,

    Location of operators manual:

    Are battery checks documented? Yes, a check list is available at each AEDstationNotes:

  • 8/3/2019 ActivitiesCheclist10-11_3

    6/68

    Checklist of E/OHS Activities for AWAIR

    Program Contact Person: George Berndt

    Is the AWAIR Plan in place? Yes No N/A

    Is the Plan current? Yes No N/A

    Has the Plan been reviewed this school year? Yes No N/A

    Is the Safety Committee organized? Yes No N/A

    How often are meetings held? Quarterly

    Are minutes of the meeting maintained? Yes

    Location: File in Mr. Berndts office

    Posted:

    How is the program communicated to employees? All Staff training duringfall orientation

    Who is the Contact Person for OSHA 300? Darcy Groen

    Is the OSHA 300A Log completed for the previous calendar year? Yes

    Have the Logs been maintained for five (5) years? Yes

    Location: Activities Manual

    Is the Log posted from February 1 until April 30? Yes

    The location/s of the posted log: Main School Office.

    Is information on injuries recorded on the Log with five (5) working days? YesNo N/A

  • 8/3/2019 ActivitiesCheclist10-11_3

    7/68

    Safety Committee Meeting Schedule

    Date Location Time

    Jan. 12, 2011 Principals office 3:00pm

    Oct. 6, 2010 Principals office 3:00pm

    April 15, 2010 Principals office 3:00pm

    Jan. 18, 2010 Principles office 3:00pm

    District Safety Committee Members

    Member Position BuildingGeorge Berndt Principal Ellsworth Public

    Judy Huisman Lead Secretary Ellsworth Public

    Art Schweitzer Custodian Ellsworth Public

    Mike Palm Staff Ellsworth Public

    Darin DeBoer Staff Ellsworth Public

    Molly Schilling Staff Ellsworth Public

    Darrel Mayer Staff Ellsworth Public

    Dianne Johnson Food Service Ellsworth Public

    Darcey Groen Secretary Ellsworth Public

  • 8/3/2019 ActivitiesCheclist10-11_3

    8/68

    Checklist of E/OHS Activities for Bleacher safety

    Program Contact Person: Art Schweitzer

    Is the BSM Plan in place? Yes No N/A

    Is the Plan current? Yes No N/A

    Has the Plan been reviewed this school year? Yes No N/A

    Has an annual survey of school bleachers been conducted? Yes No N/A

    Is the five-year recertification required by December 31, 2007 complete andsubmitted to the Minnesota Department of Labor and Industry? Yes No N/ANote: Prepared 10-8-07 and sent.

  • 8/3/2019 ActivitiesCheclist10-11_3

    9/68

    Inspection Check List

    Openings and gaps:

    Openings limited to four-inch gap between the railings and between the footboards

    and seat boards, starting at a height of 56 inches or more.

    Retractable bleachers:

    They may contain openings of 9 inches or less

    If exempt from standards must have a safety management plan in place and anamortization schedule to plan for their future replacement

    Approved netting:

    Netting may be provided to prevent persons from falling through the bleachersbetween the seat and footboards

    Chain link fencing may be used but must be secured tightly to the underside of thebleachers.

    Railings:

    Bleachers 55 inches and under are exempt from railing requirements

    Bleachers with guardrails over 30 inches above grade must not contain openingsgreater than four inches, unless safety nets are installed.State building inspectors shall determine whether the safety nets and guardrail climbability meet the requirements of the alternate design section of the State BuildingCode.

    Periodic inspections:

    Bleacher footboards and guardrails must at a minimum be reinspected at least everyfive years and a structural inspection at least every ten years. The equipment has norust, rot, cracks, or splinters, especially where it comes in contact with the ground

    There are no broken or missing components on the equipment (e.g., handrails,guardrails, protective barriers, steps, or rungs on ladders) and there are no damagedfences, benches, or signs on the playground

  • 8/3/2019 ActivitiesCheclist10-11_3

    10/68

    Checklist of E/OHS Activities for Bloodborne Pathogens

    Program Contact Person: Judy Huisman

    Is the Bloodborne Pathogens Written Plan in place? Yes No

    Has the Plan been reviewed this school year? Yes No

    List job categories that may be at risk to exposure:Bus driversParas, Special EdCustodiansSchool NurseSecretaries

    What is this schools policy regarding Hepatitis B vaccinations for employeesconsidered at risk versus employees considered not at risk in the ExposureControl Plan?Custodians provide clean up fluid spills.

    Is training provided at this school on methods and techniques to reduceexposure incidents? All staff is trained during the fall faculty developmentdays. The employee sign in log is posted in the Activities Manual

    New Employees: within ten days of employment

    Have the employees identified as first aid responders been given at a minimum

    Red Cross First Aid Training? Yes No N/ANote: Not recently.

    Are Exposure Control Kits available to staff? Yes No N/A

    Location(s): Each classroom is supplied with a clean-up kit. Kits are alsolocated in the janitors closet and also in the School Main Office.

    Status of Declination forms: Judy will be working organizing acceptance/declination forms. New forms will be distributed and previous vaccinationinformation will be gathered and recorded.

    How is blood or bodily-fluid-containing materials handled at this facility?Custodial staff typically responds to blood spills that occur when on campus.

    Location of biohazard bags at school: Nurses office and the custodial office

    Approved disposal location for biohazardous waste:Worthington Regional Hospital

  • 8/3/2019 ActivitiesCheclist10-11_3

    11/68

    Hepatitis B Vaccination Consent Form

    I have been given a copy of and have read or have had explained to me the

    information about hepatitis B and hepatitis B vaccine. I have had a chance to

    ask questions which were answered to my satisfaction. I believe I understand

    the benefits and risks of the hepatitis B vaccine, and request that it be given to

    me or to the person named below for whom I am authorized to make this

    request.

    Please Print:

    Name_________________________________________Date of Birth_________________

    Social Security or Visa #__________________________Employee #__________________

    Department and Lab room #__________________________________________________

    Principal Investigator________________________________________________________

    Signature______________________________________Date________________________

    Note: I have previously participated in an HBV vaccination program.

    Employer at time of vaccination _____________________________Date ___________Record maintained where __________________________________

  • 8/3/2019 ActivitiesCheclist10-11_3

    12/68

    Checklist of E/OHS Activities for Compressed Gas Safety

    Program Contact Person(s) Darrel Meyer

    Department Contacts:

    Maintenance Art Schweitzer

    Metals Shop Darrel Meyer

    Technology Ed. Darrel Meyer

    Is the Compressed Gas Plan in place? Yes No N/A

    Is the Plan current? Yes No N/A

    Has the Plan been reviewed this school year? Yes No N/A

    Has the facility been surveyed for compressed gas inventories? Yes No N/A

    Has training been conducted for affected personnel? Yes No N/A

    Are records established and maintained to monitor gas inventory? Yes No N/A

  • 8/3/2019 ActivitiesCheclist10-11_3

    13/68

    COMPRESSED GAS FIELD REVIEW

    Compressed Gas Inventory

    Date:04-12-2011 Program Contact Person: Brian Parrie

    Department: Metals Shop Department Responsible Person: Darrel Meyer

    Location: Wood Shop

    Cylinders: O2 ___1_________

    Acetyl ____1________ NH4 ____________

    CO2 ____________

    Argon ____________ Argon/CO2_____1_______ Other ____________

    Compliance Check List

    1. Are cylinders in well-ventilated area? X

    2. Are cylinders stored separate from flammable by at least 20 feet? X

    3. During storage are oxygen cylinders separated from fuel gascylinders, unless on welding cart?

    X

    4. Are cylinders kept away from sources of heat (below 130 F)? X

    5. Are safety chains used at all times on both full and emptycylinders? (2/3rds from top of cylinder)

    X

    6. Are empty cylinders maintained separate from full cylinders? X

    7. Are cylinders kept away from sources of ignition such as electricity,excessive heat or oily rags?

    X

    8. Are carts designed specifically for gas cylinders available? X

    9. Are damaged cylinders, valves/hoses removed from service? X

    10. Are all cylinders properly labeled with the contents? X

  • 8/3/2019 ActivitiesCheclist10-11_3

    14/68

  • 8/3/2019 ActivitiesCheclist10-11_3

    15/68

  • 8/3/2019 ActivitiesCheclist10-11_3

    16/68

    Checklist of E/OHS Activities for Confined Space Entry

    Program Contact Person: Art Schweitzer

    Is the Confined Space Entry Plan in place? Yes No N/A

    Is the Plan current? Yes No N/A

    Has the Plan been reviewed this school year? Yes No N/A

    Have confined space areas been identified? Yes No N/A

    Have measurements to include CCI/ft been completed? Yes No N/A

    Are permit entry forms in place? Yes No N/A

    Location: Activity Manual

    Are confined space labels in the proper locations? Yes No N/A

    Is a list of employees eligible to enter confined spaces complete? Yes No N/A

    Has training for affected employees completed? Yes No

    Date of completion: 10-24-09

  • 8/3/2019 ActivitiesCheclist10-11_3

    17/68

    Confined Space Inventory

    Ellsworth Public School

    Building: Combined Elementary, Middle School, High School

    Building Contact: Art Schweitzer Program Contact: Brian Parrie

    Completed By:Brian Parrie Date:2-15-2011

    Room IdentificationName Given Space

    OpeningDimension

    DimensionOf ConfinedSpace

    PotentialHazards

    Permit/Non-Permit

    Labeled PhotoID #

    Boiler Room 24X18 4X4X8 LE,heat,O2deficient

    PermitRequired

    Yes

    Boiler #1

    Boiler Room 24X18 4X4X8 LE, A PermitRequired

    No

    Boiler #2Boiler Room 4X4 4X4X>200 LE, A Permit

    RequiredYes

    Tunnel accessBoiler Room 4X4 4X4X>200 LE, A Permit

    RequiredYes

    Water Tank #2

  • 8/3/2019 ActivitiesCheclist10-11_3

    18/68

    Checklist of E/OHS Activities for Community Right-to-Know

    Program Contact Person: George Berndt/ Art Schweitzer

    Is the Community Right-to-Know Plan in place? Yes No N/A

    Is the Plan current? Yes No N/A

    Has the Plan been reviewed this school year? Yes No N/A

    Are quantities of stored and used designated hazardous materials documentedand verified? Yes No N/A

    Where are the documents stored? Activities Manual

    Have the State Emergency Response Commission and local fire departmentbeen notified of hazardous materials on school grounds? Yes No N/A

    When were they notified? 2-16- 2011(date)

    Has training been provided? Yes No N/A

    Date: N/A

    Presenter: N/A

  • 8/3/2019 ActivitiesCheclist10-11_3

    19/68

    Inventory Form

    Client: Ellsworth Public School

    Contact Person: Art Schweitzer Date: 10-8-07

    HazardousMaterial Quantity Location

    Reported onTier Two

    InstallationDate(s)

    #2 Fuel Oil 5,000 galWest sidebetweenbldgs.

    yes 1975

    Note: a 6,000 gal tank was removed from service during the summer of 2006.The tank was approximately installed in 1975.The tank remains in place but has been pumped and filled with water. The tankhad never knowingly leaked product into the ground.The remaining tank has been reported on the Tier II form. Sent 2-14-2008

    The Tier Two can be managed on line see web site:http://minnesota.idsimaps.com/submit/T2_Menu.asp

    Login: dgroen25Password: igloo55

    http://minnesota.idsimaps.com/submit/T2_Menu.asphttp://minnesota.idsimaps.com/submit/T2_Menu.asp
  • 8/3/2019 ActivitiesCheclist10-11_3

    20/68

    Checklist of E/OHS Activities for Emergency Action Planning

    Program Contact Person: George Berndt/

    Is the Emergency Action Planning program in place and as outlined in theMinnesota Executive Order 93-27 and Model Crisis Management Plan? Yes No

    Is the Plan current? Yes No

    Has the Plan been reviewed this school year? Yes No

    Have the program and goals been approved by the School Board for the currentschool year? Yes No

    Are information maps posted to indicate travel routes in the event of fire,tornado shelter locations, and procedures during lockdown? YesNo

    Located where? Maps are located in each classroom.

    Are all drills timed and recorded? Yes No

    Responsible person: Art Schweitzer_________________________________

    Location of records: District Office__________________________________

    Forms provided: Yes No

    Does this school coordinate drills with local government authorities to assuresheltering in school, evacuating to their homes or use of congregate carecenters? Yes No N/A

    Has this school completed the Fire Marshall required Fire Safety and EmergencyEvacuation Plan? Yes No N/A

    Training provided for affected staff? Yes No N/A

  • 8/3/2019 ActivitiesCheclist10-11_3

    21/68

  • 8/3/2019 ActivitiesCheclist10-11_3

    22/68

    Checklist of E/OHS Activities for Employee Right-to-Know/HazardCommunication

    Program Contact Person: Art Schweitzer

    Is the Employee Right-to-Know/Hazard Communication Plan in place? Yes No

    Is the Plan current? Yes No

    Has the Plan been reviewed this school year? Yes No

    Has the program been approved by the School Board for the current schoolyear?Yes No

    Has the chemical inventory been completed for the following functional areas?

    Location of Chemical InventoryForm

    Art Instruction Yes No N/A

    Custodians Yes No N/A Custodial Room

    Food Service Yes No N/A Head cooks desk drawer

    Science Rooms Yes No N/A Chemistry Lab

    Shop (metals, wood, auto) Yes No N/A

    Are MSDS available and located with the chemical inventory? Yes No

    Do the MSDS concur with the chemical inventory? Yes No

    Has training been provided for the following staff?

    Art Instructors Yes No N/A Science Yes No N/A

    Custodians Yes No N/A Shop Yes No N/A

    Food Service Yes No N/A Transportation Yes No N/A

  • 8/3/2019 ActivitiesCheclist10-11_3

    23/68

    Contact List for Employee Right-to-Know Program

    Client: Ellsworth Public School

    DepartmentKey Contact for Department

    (person responsible for making MSDSs)

    ArtMrs. Steinmetz

    Biology/chemistryMolly Shilling

    Consumer Life ScienceJill Christensen

    Custodial/MaintenanceArt Schweitzer

    Food ServiceMargaret LarsonDianne Johnson

    PhotoN/A

    ShopWelding

    Darrel Meyer

    Completed by: Brian Parrie Date: 2-15-2011

  • 8/3/2019 ActivitiesCheclist10-11_3

    24/68

    Checklist of E/OHS Activities for Facilities Safety Managementand Fire Safety in Schools

    Program Contact Person: George Berndt

    Is the Facilities Safety Management program in place? Yes No

    Does this school use contracted services for the Management AssistantProgram? Yes No N/A

    If no, who is the designated person or persons?

    Fire and Life Safety in Schools

    Program Contact Person: George Berndt/ Art Schweitzer

    Is the Fire Marshal approved Emergency Evacuation Plan in place for eachdistrict building? Yes No

    Most recent date of sprinkler electronics inspection N/A

    Most recent date of alarm inspection: July, 2010

    Most recent inspection of fire extinguisher: June, 2010

    Most recent inspection of fume hood with fire suppressant: N/A

    Are emergency lights tested at least monthly? Yes No N/A

    Science safety Checklist completed? Yes No N/A

  • 8/3/2019 ActivitiesCheclist10-11_3

    25/68

    Facilities Safety Review

    Building: Ellsworth Public School

    Mock-OSHA ReviewArea

    Date ReviewCompleted Recommendations

    Art N/A

    Dark Room N/A

    Wood Shop 1/15/2010 See written report

    Kitchen 1/15/2010

    Metal Shop 1/15/2010

    Halls, Gym, etc. 1/15/2010

    Graphic Arts 1/15/2010 N/A

    Maintenance/Custodial

    1/15/2010

    Transportation 1/15/2010 N/A

    Grounds/Garage 1/15/2010

    Chemistry/Life

    Science

    1/15/2010

  • 8/3/2019 ActivitiesCheclist10-11_3

    26/68

    Checklist of E/OHS Activities for First Aid/CPR

    Program Contact Person(s): Judy Huisman

    Is the First Aid/CPR program in place? Yes No

    Is the Plan current? Yes No

    Has the Plan been reviewed this school year? Yes No

    Have the program and goals been approved by the School Board for the currentschool year? Yes No

    Has the District determined a provider in the event of a medical emergency?Yes No

    The local provider determined travel time was estimated to be within the 4-8minute limit. Therefore Ellsworth Rescue Squad

    will be the designated emergency response provider.

    The local provider determined travel time was estimated to be in excess of the4-8 minute limit. Therefore N/A will be thedesignated emergency response person located within the district.

    Has training been provided for affected staff? Yes No

    CPR training held 12-2010 for all staff. Training provided by Mary Lubbenfrom Fulda, certified CPR trainer.

  • 8/3/2019 ActivitiesCheclist10-11_3

    27/68

  • 8/3/2019 ActivitiesCheclist10-11_3

    28/68

    Checklist of E/OHS Activities for Hazardous Waste Management

    Program Contact Person(s)

    Primary Contact Person:_Art Schweitzer

    Secondary Contact Person: _George Berndt

    Is the Hazardous Waste Management program in place? Yes No

    Is the Plan current? Yes No

    Has the Plan been reviewed this school year? Yes No

    Have the program and goals been approved by the School Board for the currentschool year? Yes No

    Did this school generate ten gallons of waste per year? Yes No

    Note: In Greater Minnesota, schools generating ten gallons of waste per year orless do not need a license.

    Did this school generate 220 pounds or less per month hazardous waste (about drum or less liquid)? Yes No

    Note: Wastes that do not count include antifreeze, cathode ray tubes,fluorescent lamps, lead acid batteries, pcb ballasts, photo fixer reclaimed onsite, used oil and oil filters.

    Training for VSQGs do not have training requirements however MPCA stronglyrecommends persons handling wastes be given training on best handling andsafety risks associated.Has training been provided for affected persons? Yes No N/A

    Date Conducted: N/A

    Date Scheduled: N/A

    Has annual report and license application sent in? Yes No N/A

    Note: A Hazardous Waste License Application was sent in on Jan. 9, 2009. Theschool is declaring that it is a VSQG and will not be required to pay a license

    fee. The science lab was cleaned this summer and the U of M removed theunneeded chemicals. It was reported that about 20 kilograms was removed.1-9-2009 LC

  • 8/3/2019 ActivitiesCheclist10-11_3

    29/68

    Note: The school has continued to meet the VSQG criteria during the 2009-2010 school year. They are not required to report their waste generatingactivities. LC 4-5-2010

    Note: The school has continued to meet the VSQG criteria during the 2010-

    2011 school year. They are not required to report their waste generatingactivities. LC 10-26-2010

  • 8/3/2019 ActivitiesCheclist10-11_3

    30/68

    Checklist of E/OHS Activities for Hearing Conservation

    Program Contact Person: Art Schweitzer

    Is the Hearing Conservation Plan in place? Yes No

    Is the Plan current? Yes No

    Has the Plan been reviewed this school year? Yes No

    Has the program been approved by the School Board for the current schoolyear?Yes No

    Has the school been surveyed for noise hazards? Yes No

    Have sound level measurements been collected? Yes No

    Have the results been documented? Yes No

    Location: Activities Manual

    Has training been scheduled or completed for affected individuals this schoolyear?

    Yes No N/A

    Date:

    Presenter:

    Have regulatory changes occurred that may affect this program? No

  • 8/3/2019 ActivitiesCheclist10-11_3

    31/68

    Client: Ellsworth Public Schools

    Measuring Device: Center 325 Sound LevelMeter

    Calibration: Pre___________Post___________

    Reason for Testing: General Survey

    Affected Personnel: Band Custodial, Maintenance, Shop

    Location Equipment Results Recommendations

    Shop Chop Saw 99.5.dBA Provide Protection

    Shop Jet Router 84.9 dBA Provide Protection

    Shop Delta Band Saw 82.7 dBA

    Shop StationaryBelt/Disk Sander

    83.3 dBA

    Shop Radial Arm Saw 84.4 dBA Provide Protection

    Shop Joiner 86.3-87.7 dBA Provide Protection

    Shop Sander Planner 80.7 dBA

    Completed by Lee Carlson Date 3-13 -2009

    Note: No over limit exposures could be determined. However due to theexceptionally loud readings for short periods it is recommended that hearingprotection be provided to affected staff. LC

  • 8/3/2019 ActivitiesCheclist10-11_3

    32/68

    Checklist of E/OHS Activities for Indoor Air Quality

    Program Contact Person: George Berndt

    Is the IAQ Plan in place? Yes No

    Is the Plan current? Yes No

    Has the Plan been reviewed this school year? Yes No

    Has an IAQ Committee beenestablished? Yes No

    Have the program and goals been approved by the School Board for the currentschool year? Yes No

    Has the annual cursory walk-through been conducted? Yes No

    Havethedistrictskeybuilding systems been evaluated? Yes No

    When was the evaluation completed? 3-17-1999

    Who conducted the evaluation? Musser Environmental Inc.

    Wereoccupied areas of the district evaluated using the EPAs Tools for Schoolscheck list or equivalent?

    Teachers check list? An information fact sheet was provided all staff.# of forms distributed # of Forms returned:

    Building maintenance checklist? Yes

    Building ventilation checklist? Yes

    Training conducted Aug 29, 2007 (date)

    Training has been scheduled for ____N/A___________. (date)

    Has the District determined the mechanical ventilation rate of each occupiedspace? Yes No.

    Supportive technical services were conducted on: 2/26/2010. (date)

    Results of technical services are located? See IAQ Report

  • 8/3/2019 ActivitiesCheclist10-11_3

    33/68

    Checklist of E/OHS Activities for Integrated Pest Management

    Program Contact Person: Art Schweitzer

    Is the IPM Plan in place? Yes No

    Is the Plan current? Yes No

    Has the Plan been reviewed this school year? Yes No

    Has the annual monitoring been conducted to determine location and degree ofinfestation? Yes No

    A map of the problem area/areas has been developed. Yes No

    Has notice been given to parents regarding application activities? Yes No

    Location or publication used to notify parents: fall news letter.

    Note: the school has had cockroach infestations in the past. Plunkets nowprovides monthly services to control insects and mice. The staff reports goodsuccess.

  • 8/3/2019 ActivitiesCheclist10-11_3

    34/68

  • 8/3/2019 ActivitiesCheclist10-11_3

    35/68

    Checklist of E/OHS Activities for Laboratory Standard/ChemicalHygiene Plan

    Program Contact Person: Matt McDowell, CHO

    Is the Laboratory Standard/Chemical Hygiene Plan in place? Yes No N/A

    Is the Plan current? Yes No N/A

    Has the Plan been reviewed this school year? Yes No N/A

    Fume hood was tested on ____N/A___________.(date)

    The results indicate air velocity to be: satisfactory, unsatisfactory, N/A.

    Chemical inventory:

    Date of most recent survey: 2009-2010 school year

    Location of inventory listing: Science Room

    Are Material Safety Data Sheets (MSDSs) located with inventory? Yes No N/AThe MSDS are listed at the following website:http://www.flinnsci.com/search_MSDS.asp

    Are the MSDS readily accessible? Yes No N/A

    Has the Minnesota Dept of Ed Science Lab Checklist been completed? Yes NoN/A

    Is training for affected personnel complete? Yes No N/A

    Date(s) of instruction:

    Roster signed? Yes No N/A

    Lesson plan outline available with roster? Yes No N/A

    Status of Emergency Eye Wash/Deluge Shower:

    Is flushing conducted weekly? Yes No N/A

    Is descriptive signage properly posted? Yes No N/A

    Is flushing activity documented? Yes No N/A

    http://www.flinnsci.com/search_MSDS.asphttp://www.flinnsci.com/search_MSDS.asp
  • 8/3/2019 ActivitiesCheclist10-11_3

    36/68

    General Science Safety ConsiderationsFor All Rooms Where Science Laboratories Are Conducted

    And/or Demonstrations Are Given

    Client: Ellsworth Public School

    Room Number(s):

    Description: A school science laboratory is defined as a classroom wheredemonstrations and/or laboratory instructions are provided for individual or groupexperiments. They are places where science is taught. In addition, any conditionlisted under either the storage section or the chemical laboratory section thatmay apply to any area, for instance, must keep inventories of all biology reagentsand chemicals.

    ITEM CITATIONCONDITION

    EXISTS LACKING N/A

    1) Laboratories must be equipped with adequateventilation. For new labs (build after July 1990) anmanual shutoff control for the laboratory exhaustventilation system must be provided outside of the room,in a position adjacent to the access door to the room orin such other location as approved by the fire chief.

    UBC (97) 305.2.4,307.5.2, & 1202.2.3UFC (97) 8004.1.11 &8003.1.4.2

    2) At least one 2A-20BC, or larger, rated and approvedportable fire extinguisher must be provided for each3,000 of laboratory. Travel distance must not exceed 50from anywhere in the lab. At least one fire extinguishersuitable for class D fires must be provided in laboratorieswhere combustible metals are used and stored.

    UFC (97) 1002.1UFC Std. 10-1-3-2

    X

    3) At least one approved fire blanket must be provided in

    each laboratory.

    UFC (97) 1001.9 X

    4) Students must be under the direct supervision of afaculty member or an assistant at all times. In mostcases it is recommended that direct supervision meansdirect eye contact. It is recommended that no more thantwo students be assigned to a lab station, a place in theroom equipped with water, gas, and electricity, or aplace where students do labs.

    NFPA 45 (91) 1-4

    X

    5) Aisles serving work areas on two sides must be atleast 42 wide; those serving work areas on one sideonly must be 36.

    UFC (97) 1204.2.2 (2)X

    6) Minimum of two means of exit access must beprovided when:Existing: lab exceeds 1,000 sq. feetNew: lab exceeds 200 sq. feet (built after 7/90)

    NPFA 45 (91) 3-4.1UBC (97) 1007.3.8

    X

    7) Labs must be separated from each other and otherportions of the building by not less than a 1-houroccupancy separation.*Existing: labs located in buildings protected by automaticextinguishing systemsonly smoke separation requiredNew: (built after 7/72)*Recommend this be determined by a licensed designprofessional

    UFC (97) Appendix 1-A7.2 as amended

    UBC (97), 305.2.4

    8) Labs must be equipped with automatic detectionelectrically interconnected with the building fire alarmsystem. Exception: labs protected by a completeautomatic sprinkler system that is interconnected to thebuilding fire alarm require no additional detection.

    UFC (97) 1007.2.4.2 &1007.2.4.1.1 asamended

  • 8/3/2019 ActivitiesCheclist10-11_3

    37/68

    9) All electrical outlets must be properly grounded and allfixed electrical equipment and appliances must beplugged in to grounded outlets as required by theelectrical code.

    UFC (97) 850499NEC 250-112

    X

    ITEM CITATIONCONDITION

    EXISTS LACKING N/A

    10) Electrical receptacles, switches, and controls mustbe located so as not to be subject to liquid spills.

    NFPA 45 (91) 3-6.1 X

    11) Extension cords must not be used as a substitute forpermanent wiring.

    UFC (97) 8506.1 X12) The use of multi-plug adapters, octopusarrangements, cube adapters, strip plugs, or any otherdevice that does not comply with the electrical code isprohibited.

    UFC (97) 8507

    X

    13) A minimum of 30 of clearance must be maintainedin front of electrical control panels for access.

    UFC (97) 8509.2

    14) Written procedures for laboratory emergencies,including emergency evacuation, must be developed foreach lab.

    NFPA 45 (91) 4-6.3.1X

    15) Piping systems must comply with nationallyrecognized standards.

    NFPA 45 (91) 8-1.1

    16) Enough eye protection devices (goggles) must beprovided for every student in the room, visitors, and theteacher whenever potentially hazardous activities are

    taking place.

    MN Public Law, section126.20

    X

    17) Refrigerators, freezers, and other cooling equipmentused to store of cool flammable liquids must be ofexplosion-proof construction

    NFPA 45 (91) 9-2.2.2

    18) Each refrigerator, freezer, or cooler must beprominently labeled to indicate whether it is or is notsuitable for storing flammable liquids.

    NFPA 45 (97) 9-2.2.1

    19) Flammable liquids stored in refrigerated equipmentmust be in closed containers.

    NFPA 45 (91) 9-1.6.6

  • 8/3/2019 ActivitiesCheclist10-11_3

    38/68

    General Science Safety ConsiderationsFor All Laboratories And/or Rooms Where Chemical Demonstrations Are

    Conducted

    Client: Ellsworth Public School

    Room Number(s):

    Description: In addition to the provisions that are outlined for any sciencelaboratory area, the following provisions are specific for chemistry classes (butmay apply to any lab where similar activities are carried on).

    ITEM CITATIONCONDITION

    EXISTS LACKING N/A

    1) Proper eyewash facilities must be installed thatproduce 25 psi of water for 15 minutes. Squeeze bottlesdo not meet this specification. It is recommended that

    eyewash fountains should be located within 25 ofstudents in any area of the room. The device must beplumbed into a drinkable water supply. This rule appliesto any rooms where labs are conducted that arepotentially harmful to the eyes.

    ANSI Z-358.1-1981 X

    2) Emissions generated at workstations must beconfined to the area in which they are generated(laboratory hoods).

    UBC (97) 1202.2.3X

    3) In new labs (build after 7/90) a manual shutoff controlfor the laboratory exhaust ventilation system must beprovided outside of the room in a position adjacent to theaccess door to the room or in such other location asapproved by the fire chief.

    UBC (97) 1202.2.3UFC (97) 8003.1.4.2

    4) Chemicals stored in the open in the laboratory workarea must be kept to the minimum necessary for thework being done.

    NFPA 45 (91) 7-2.3.1X

    5) A complete inventory of chemicals on hand must bemaintained and must be available to the fire chief. Allmaterials must be dated upon receipt.

    UFC (97) 8001.6

    6) Persons responsible for each lab must be familiar withthe chemical nature of the materials present in the laband the appropriate mitigating actions to be taken incase of fire, leak, or spill.

    UFC (97) 8001.11.1.1

    X

    7) Incoming shipments of chemicals must be transportedan opened by school personnel familiar with the potentialhazards.

    NFPA 45 (91) 7-2.2.1X

    8) Neutralizing chemicals spill kits, dry sand, vermiculite,EM Absorbent, and other spill control methods must bereadily available while the lab is in use.

    UFC (97) 8001.11.1X

    9) Written maintenance procedures must be established,including regular inspection, testing, and maintenance oflab utilities, hood and exhaust systems, pressureequipment (autoclaves, steam sterilizers, etc.), and

    emergency equipment.

    NFPA 45 (91) 4-6.2

    10) Lab hoods and special local exhaust systems mustbe labeled to indicate intended use. Hoods in whichradioactive materials are handled must be identified withthe radiation hazard symbol.

    NFPA 45 (91) 6-13

    X

    11) Provide a properly marked, easily accessible maingas shutoff valve in the room.

    UFC (97) 8004.1.12 X

    12) Fume/exhaust hoods must be listed (e.g., UL or FM)and maintained in proper operating condition.

    UFC (97) 8001.4.4 &8001.4.7.1

    X

    13) Heat sources (e.g., gas burners, hot plates, heatingmantles, etc.) should never be left unattended.

    Recommendation X

  • 8/3/2019 ActivitiesCheclist10-11_3

    39/68

    ITEM CITATIONCONDITION

    EXISTS LACKING N/A

    14) It is recommended that due to the serious explosionhazard present, the following chemicals not be used inan instructional setting:

    Benzoyl Peroxide Percholoric AcidCarbon Disulfide Picric AcidEthyl Ether Potassium Metal

    Magnesium Powdered Metal

    Recommendation

    X

    15) Loose clothing (e.g., full cut blouses, neckties, etc.)and long hair should be properly restrained. Also, somelaboratory activities could be dangerous to personswearing contact lenses.

    Recommendation

    X

    Note: Potassium metal is handled by the instructor only.

  • 8/3/2019 ActivitiesCheclist10-11_3

    40/68

    General Science Safety ConsiderationsFor Chemical Storage Facilities

    Client: Ellsworth Public School

    Room Number(s):

    Description: Chemical Storage Facilities means any area or room wherechemicals are stored. Usually this refers to the chemistry storage area, butoccasionally there may be other facilities in the school, most likely located withina classroom, that store chemicals. These rules apply to all areas wherechemicals are stored.

    ITEM CITATIONCONDITION

    EXISTS LACKING N/A

    1) Quantities of flammable and combustible liquids shall

    not exceed the amounts necessary fro demonstration,treatment, laboratory work, maintenance purposes, oroperation of equipment. Not in any case will it exceedthe limits set forth in table 7902.5-A.

    UFC (97) 7902.5.7.2 #3

    X

    2) Quantities of flammable and combustible liquid inexcess of 10 gallons must be stored in a flammableliquids cabinet. Quantities not exceeding ten gallonsmust be stored in an approved location.

    UFC (97) 7902.5.8

    X

    3) The maximum quantity of flammable and combustibleliquids in storage and use in a lab must not exceed 120gallons.Exception: These quantities may be doubled in areasprotected by an automatic extinguishing system.Exception: These quantities may be doubled if stored inapproved storage cabinets.(Both exceptions may apply.)

    UFC (97) table 7902.5-A

    X

    4) Class I flammable liquids may be stored in glass

    containers of not more than one-gallon capacity only ifthe required liquid purity would be affected by storage ina metal container, or if the liquid would cause excessivecorrosion of a metal container. Otherwise, Class I-Aliquids are restricted to glass containers not exceedingone-pint capacity and Class 1-B liquids are restricted toglass containers not exceeding one-quart capacity.Class 1-C liquids are permitted to be stored in containersup to one-gallon capacity.

    UFC (97) 7902.1-A

    5) No container for Class I or II liquids in any lab mayexceed a capacity of one gallon. See table 7902.1-A forother limitations.

    UFC (97) 7902.1-A

    6) Materials that will react with water or other liquids toproduce a hazard must not be stored in the same roomwith flammable or combustible liquids.

    UFC (97) 7902.5.4X

    7) Stored gas cylinders shall have all protective devices

    on (caps, collars, and similar devices).

    UFC (97) 7401.7.1 X

    8) All gas cylinders must be secured in a place toprevent falling.

    UFC (97) 7401.6.4 X

    9) Material Safety Data Sheets (MSDS) must be readilyavailable on the premises for all hazardous chemicals.

    UFC (97) 8001.6 X

    10) All chemicals must be stored in approved containers(if possible, chemicals should be stored in the originalshipping package).

    UFC (97) 8001.4.2X

    11) Incompatible materials shall be segregated toprevent accidental contact with one another. (Storage ofmaterials which are incompatible shall no be allowed inthe same cabinet or exhausted enclosure.)

    UFC (97) 8001.11.8

    X

  • 8/3/2019 ActivitiesCheclist10-11_3

    41/68

    ITEM CITATIONCONDITION

    EXISTS LACKING N/A

    12) All shelving must be of substantial construction andproperly secured to prevent falling over. (Shelving abovework areas should be kept free of chemicals; storageabove eye level should be avoided.)

    UFC (97) 8001.11.9

    X

    13) Shelving must be equipped with a lip or guard toavoid products rolling off. UFC (97) 8001.11.9 X14) Defective containers must be removed and disposedof in a proper manner.

    UFC (97) 8001.4.7.3 X

    15) Disposal of chemical wastes must be in accordancewith applicable federal and state regulations and goodsafety practices.

    UFC (97) 8001.5.1X

    16) All storage cabinets and storage rooms must belocked or otherwise secured against unauthorized entry.

    UFC (97) 8001.11.2 X

    17) All containers must be properly labeled to identify thecontents.

    UFC (97) 8001.7 X

    18) Toxic and highly toxic compressed gas, Class IVliquid, solid oxidizers, unclassified detonable, Class Iorganic peroxides, Class III and IV unstable and reactivematerial shall not be allowed in the classroom.

    UFC (97) 8001.15.2.4

    X

    19) When transferring flammable liquids between metalcontainers, the containers must be properly bonded

    together. The practice of purchasing large containersand dispensing into smaller ones is discouraged.

    UFC (97) 8001.11.5

    X

    TABLE 7902.1-A: MAXIMUM SIZE OF CONTAINERS AND PORTABLE TANKS

    CONTAINER TYPE CLASS I-A CLASS I-B CLASS I-C CLASS II CLASS III

    1. Glass1 1 pt. 1 qt. 1 gal. 1 gal. 5 gal.

    2. Metal or listed approved plastic2 1 gal. 5 gal. 5 gal. 5 gal. 5 gal.

    3. Approved plastic 0 gal. 0 gal. 0 gal. 0 gal. 5 gal.

    4. Safety cans 2 gal. 5 gal. 5 gal. 5 gal. 5 gal.

    5. Metal drum 60 gal. 60 gal. 60 gal. 60 gal. 60 gal.

    6. Approved portable tanks 660 gal. 660 gal. 660 gal. 660 gal. 660 gal.

    7. Polyethylene3 Note 4 Note 4 Note 4 60 gal. 60 gal.

    TABLE 7902.5-A: EXEMPT AMOUNTS OF FLAMMABLE AND COMBUSTIBLE LIQUIDSMAXIMUM QUANTITIES STORED PER CONTROL AREA1,2,3

    TYPE OF LIQUID EXEMPT AMOUNT (gallons)

    FlammableClass I-AClass I-BClass I-CCombination I-A, I-B, I-C

    306090

    1204

    CombustibleClass IIClass III-AClass III-B

    120330

    13,2005

    1Control areas shall be separated from each other by not less than a one-hour fire-resistive occupancy separation. Thenumber of control areas within a building used for retail or wholesale sales shall not exceed two. The number of control

    areas in buildings with other uses shall not exceed four. See Sections 204 and 8001.10.2.2Quantities are allowed to be increased 100 percent when stored in approved storage cabinets. When Note 3 applies, theincrease for each Note is allowed.3Quantities are allowed to be increased 100 percent in buildings equipped with an approved automatic sprinkler system.When Note 2 applies, the increase for each Note is allowed.4Combinations shall not contain more than the exempt amounts of any individual class.5Quantities permitted in a building equipped with an approved automatic sprinkler system are not limited.

  • 8/3/2019 ActivitiesCheclist10-11_3

    42/68

    Carcinogen/Substances of Known High Chronic ToxicityStandard Operating Procedures

    Client: Ellsworth Public School

    Which carcinogens are present in district science laboratories?

    KNOWN CARCINOGENS SUSPECT CARCINOGENS OTHERS

    Asbestos Cadmium/Cadmium Compounds

    Arsenic Carbon Tetrachloride

    Benzene Chloroform

    Benzidine DDT

    Bis (Chloromethyl) Ether 2,4D

    Chloromethyl Methyl Ether Methylene Chloride

    Chromium/Chromium Compounds Formaldehyde (Gas)

    Mustard Gas Lead Acetate Vinyl Chloride Lead Phosphate

    Nickel/Nickel Compounds (Powder)

    Saccharin

    Urethane

    List total time (in hours) employee is exposed to carcinogens (checkedchemicals above) per academic year.

    N/A hours per academic year

    Are checked chemicals required, or could acceptable substitutes beimplemented?

    Will retain carcinogen in curriculum Will discontinue use ofchemicals

    If retained in curriculum, use table to log/document usage:

    CARCINOGENICCHEMICAL AMOUNTS

    USEDDATES USED

    NAME(S) OFUSER(S)

    NUMBER OFHOURS USED

  • 8/3/2019 ActivitiesCheclist10-11_3

    43/68

    Carcinogen/Substances of Known High Chronic ToxicityStorage Guidelines

    1. Store in a well-ventilated area. N/A

    2. Use secondary containers or trays with sufficient capacity > 100% primarycontainer.

    3. Label with the following information:

    WARNING!

    HIGH CHRONIC TOXICITY

    ORCANCER-SUSPECT AGENT

    4. Limited access should be provided for these chemicals.

    5. Areas should be posted.

    6. District Storage Location: N/A

    7. Guidelines (from above) that need to be implemented: 1 2 3 4 5

  • 8/3/2019 ActivitiesCheclist10-11_3

    44/68

    Carcinogen/Substances of Known High Chronic ToxicityHandling Guidelines

    1. Use a controlled area (an exhaust hood, glove box, designated area in a

    laboratory with localized ventilation).

    District Controlled Area: N/A, however, fume hoods are available should needarise.

    2. Controlled areas should possess the following signage, conspicuouslyposted:

    WARNING!

    TOXIC SUBSTANCE IN USE

    ORCANCER-SUSPECT AGENT:

    AUTHORIZED PERSONNEL ONLY

    3. Use of Personal Protective Equipment, like impermeable gloves, aprons, andface shields.

    4. Protect surfaces where carcinogens are handled by using chemically resistanttrays or pans that can be decontaminated.

    5. On leaving a controlled area, laboratory workers should remove anyprotective apparel that has been used and thoroughly wash hands, forearms,face, and neck. If disposable apparel or absorbent paper liners have beenused, these items should be placed in a closed and impervious container thatshould then be labeled in some manner such as the following: CAUTIONCONTENTS CONTAMINATED WITH SUBSTANCES OF HIGH CHRONICTOXICITY. Non-disposable protective apparel should be thoroughly washed,and containers of disposable apparel and paper liners should be incinerated.

    6. Wastes and other contaminated materials from an experiment involvingsubstances of high chronic toxicity should be collected together with the

    washings from flasks and such and either decontaminated chemically orplaced in closed, suitable labeled containers for incineration away from thecontrolled area. If chemical decontamination is to be used, a method shouldbe chosen that can reasonable by expected to convert essentially all of thetoxic materials into nontoxic materials. For example, residues and wastesfrom experiments in which B-propiolactone, bis (chloromethyl) ether, ormethyl chloromethyl ether have been used should be treated for 10 minuteswith concentrated aqueous ammonia.

  • 8/3/2019 ActivitiesCheclist10-11_3

    45/68

    In the event that chemical decontamination is not feasible, wastes andresidues should be placed in an impervious container that should be closedand labeled in some manner such as the following: CAUTIONCOMPOUNDS OF HIGH CHRONIC TOXICITY or CAUTIONCANCER-

    SUSPECT AGENT.

    7. Transfer of contaminated wastes from the controlled area to the incineratorshould be done under the supervision of authorized personnel and in such amanner as to prevent spill or loss. In general, liquid wastes containing suchcompounds should be placed in glass or polyethylene (usually preferable)bottles half-filled with vermiculite, and these should be transported in plasticor metal pails of sufficient capacity to contain the material in case ofaccidental breakage of the primary container.

    8. Normal laboratory work should not be resumed in a space that has been used

    as a controlled area until it has been adequately decontaminated. Worksurfaces should be thoroughly washed and rinsed. If experiments haveinvolved the use of finely divided solid materials, dry sweeping should not bedone. In such cases, surfaces should be cleaned by wet mopping or by use ofa vacuum cleaner equipped with a high efficiency particulate air (HEPA) filter.All equipment (e.g., glassware, vacuum traps, and containers) that is knownor suspected to have been in contact with substances of high chronic toxicityshould be washed and rinsed before they are removed from the controlledarea.

    8. In the event of continued experimentation with a substance of high chronic

    toxicity (i.e., if a worker regularly uses toxicologically significant quantitiesof such a substance three times a week), a qualified physician should beconsulted to determine whether it is advisable to establish a regularschedule of medical surveillance or biological monitoring.

    Note: Chemical MSDS may be obtained at the following website:

    http://www.flinnsci.com/search_MSDS.asp

    http://www.flinnsci.com/search_MSDS.asphttp://www.flinnsci.com/search_MSDS.asp
  • 8/3/2019 ActivitiesCheclist10-11_3

    46/68

  • 8/3/2019 ActivitiesCheclist10-11_3

    47/68

    Checklist of E/OHS Activities for Lead-in-Water Management

    Program Contact Person: Art Schweitzer

    Is the Lead-in-Water Management Plan in place? Yes No

    Is the Plan current? Yes No

    Has the Plan been reviewed this school year? Yes No

    This school completed testing of water supply taps _5-1-1996_.(date)

    Is a map of all potable water taps available for review? Yes No N/A

    Checklist of E/OHS Activities for Lead-in-Paint Management

    Program Contact Person: Art Schweitzer

    Is the Lead-in-Paint Management Plan in place? Yes No

    Is the Plan current? Yes No

    Has the Plan been reviewed this school year? Yes No

    Testing for lead in paint on playground equipment: Note: All playground

    equipment has been replace with lead free.

    Date completed: N/A

    Yet to be tested: N/A

    Results of evaluation for paint condition in rooms K-1:Building constructed post-1978; facility not applicableBuilding constructed prior to 1978; paint determined to be in

    ____good__________ condition

  • 8/3/2019 ActivitiesCheclist10-11_3

    48/68

  • 8/3/2019 ActivitiesCheclist10-11_3

    49/68

    Checklist of E/OHS Activities for Lockout/Tagout

    Program Contact Person: Art Schweitzer

    Is the Lockout/Tagout Plan in place? Yes No N/A

    Is the Plan current? Yes No N/A

    Has the Plan been reviewed this school year? Yes No N/A

    Is LO/TO equipment available? Yes No N/A

    Is the equipment appropriate for application? Yes No N/A

    If available, where is the equipment located? __Boiler room_______________

    Is the equipment maintained in an orderly and readily usable condition? Yes NoN/A

    Have affected personnel been trained as to methods and technique of use? YesNo N/A

    Are written procedures available for affected staff? Yes No N/A

    If available, the procedures are located where? __Activities Manual________

    Has the annual audit of energy control procedures been completed? Yes No

    Date or dates of completion:

  • 8/3/2019 ActivitiesCheclist10-11_3

    50/68

  • 8/3/2019 ActivitiesCheclist10-11_3

    51/68

    Checklist of E/OHS Activities for Machine Guarding

    Program Contact Person: Darrel Mayer __

    Is the Machine Guarding Plan for each affected work area in place? Yes No

    Is the plan/plans current? Yes No

    Has the Plan been reviewed this school year? Yes No

    Has a survey of all district fixed equipment been conducted?Yes No

    When was the evaluation completed?_______________________

    Who conducted the evaluation? _______________________

    How are corrections documented? _______________________________

    Is all fixed equipment safeguarded to meet OSHA criteria? Yes No

    Has the alternative MDE best practices criteria used to safeguard equipment?Yes No

    Has equipment determined not in compliance scheduled for repair orreplacement? Yes No N/A

    If replaced, was best practices, bid specification criteria used forprocurement? Yes No

  • 8/3/2019 ActivitiesCheclist10-11_3

    52/68

    Identified Fixed Equipment Locations

    Location Building/Buildings Staff Affected # of itemAutomotive Shop

    Wood ShopCustodial/Maintenance

    Welding Shop

    Ag Shop

    Bus Garage

    Art

    Scene shop

    Science

    Contracted technical services to review and recommend? __________________.

    Name of person or contractor conducting survey? ___________________.(date)

    Results of technical services located where? ________________________

    Checklist for minimum requirements:

    Power outage protection provided for required equipment

    Emergency stops provided for required equipment

    Safe work practice placards at applicable fixed tool stations Proper guards provided and used

    Color coding as prescribed by OSHA standards

    Non-slip surfaces by each piece of equipment

    Fixed equipment secured to prevent walking or movement

    Has a log of employee accidents and near misses been established and used?

    Yes No

    Annual training for affected staff is provided? Yes No

    Training conducted ____________. (date)

    Training has been scheduled for ____________.(date)

  • 8/3/2019 ActivitiesCheclist10-11_3

    53/68

    Checklist of E/OHS Activities for Playground Safety

    Program Contact Person: Art Schweitzer

    Is the Playground Safety program in place? Yes No

    Is the Plan current? Yes No

    Has the Plan been reviewed this school year? Yes No

    Surfacing:

    X The equipment has adequate protective surfacing under and around itand the surfacing materials have not deteriorated

    X Loose-fill surfacing materials have no foreign objects or debris

    X Loose-fill surfacing materials are not compacted and do not havereduced depth in heavy use areas such as under swings or at slide exits

    General Hazards:

    X There are no sharp points, corners, or edges on the equipment

    X There are no missing or damaged protective caps or plugs

    X There are no hazardous protrusions and projections

    X There are no potential clothing entanglement hazards, such as open S-hooks or protruding bolts

    X There are no pinch, crush, and shearing points or exposed moving parts

    X There are no trip hazards, such as exposed footings on anchoringdevices and rocks, roots, or any other environmental obstacles in theplay area

    Deterioration of the Equipment:

    X The equipment has no rust, rot, cracks, or splinters, especially whereit comes in contact with the ground

  • 8/3/2019 ActivitiesCheclist10-11_3

    54/68

    X There are no broken or missing components on the equipment (e.g.,handrails, guardrails, protective barriers, steps, or rungs on ladders)and there are no damaged fences, benches, or signs on the playground

    X All equipment is securely anchored

    Security of Hardware:

    X There are no loose fastening devices or worn connections, such as S-hooks

    X Moving components, such as swing hangers or merry-go-round bearings,are not worn

    Drainage:

    X The entire play area has satisfactory drainage, especially in heavy useareas such as under swings and at slide exits

    Leaded Paint:

    X The leaded paint used on the playground equipment has notdeteriorated as noted by peeling, cracking, chipping, or chalking

    X There are no areas of visible leaded paint chips or accumulation oflead dust

    General Upkeep of Playgrounds:

    X The entire playground is free from miscellaneous debris or litter suchas tree branches, soda cans, bottles, glass, etc.

    X There are no missing or full trash receptacles

    Click here to view playground equipment.

    Note: Recommend replacing trip hazard wood retainers with plastic retainers.LC 4-7-2010

    http://opt/scribd/conversion/tmp/PlaygroundProgramhttp://opt/scribd/conversion/tmp/PlaygroundProgram
  • 8/3/2019 ActivitiesCheclist10-11_3

    55/68

  • 8/3/2019 ActivitiesCheclist10-11_3

    56/68

  • 8/3/2019 ActivitiesCheclist10-11_3

    57/68

    Checklist of E/OHS Activities for Personal Protective Equipment

    Program Contact Person: Art Schweitzer

    Is the Personal Protective Equipment Plan in place? Yes No N/A

    Is the Plan current? Yes No N/A

    Has the Plan been reviewed this school year? Yes No N/A

    Has a survey of potential workplace hazards been completed? Yes No N/A

    Date(s) activity was conducted:4/06/2010

    Have recommendations been completed for appropriate equipment? Yes No

    Has training been completed for the following departments?

    Art and Photo Yes No N/A

    Custodial Yes No N/A

    Grounds keeping/Garage Yes No N/A

    Kitchen Yes No N/A

    Maintenance Yes No N/A

    Science Laboratories Yes No N/A

    Technical Education Yes No N/A

    Transportation Yes No N/A

  • 8/3/2019 ActivitiesCheclist10-11_3

    58/68

    Physical Hazard Assessment

    Hazard(Heat, Noise,Radiation)

    Building Location Labeled

    Heat, chemical, bodyfluids, noise, asbestos

    K-12 Custodial N/A

    Noise, chemical, hotwater,

    K-12 Kitchen N/A

    Heat, chemical, bodyfluids, noise

    K-12 Science Room N/A

    Noise, impact,compressed gas, dust

    K-12 Wood Shop N/A

    Affected Employees

    Name Department

    Art SchweitzerCustodial/Maintenance

    Margaret L. Food Service

    Dianne J. Food Service

    Molly Shilling Education (science)

    Darrel Meyer Tech Ed

    Completed by Lee Carlson ________Date_4-06-10_____________

  • 8/3/2019 ActivitiesCheclist10-11_3

    59/68

    Personal Protective Equipment Assessment

    Location:

    Chemistry

    Location:

    Food Service

    Location:

    Custodian

    Location:

    Tech Shop,wood/metalEmployee:Molly Gort

    Employee:Margaret LDianne J.

    Employee:Art Schweitzer

    Employee:Darrel Meyer

    Hand

    Nitrile

    Latex X XVinyl XLeather X X XNeoprene X X

    Face

    Impact XSplash X X X XShieldRespirator X

    EarMuffs X X XPlugs X X X X

    BodyNeo Apron X XDenim X

    FootSteel Toes

    Metatarsal

    Head Hard Hat

    Hazard(s)

    Heat, chemical,body fluids,

    Noise, chemical,hot water, blood

    Heat, chemical,body fluids,

    noise, openflame, impact

    Heat, chemical,body fluids, noise,

    open flame,impact

    Comments onAvailability,Condition, &Storage

    Suggestadditionalhearing

    protection forfood service staff

    Suggest additionalhearing protection

    for students

    Completed by Brian Parrie Date 2/15/2011

  • 8/3/2019 ActivitiesCheclist10-11_3

    60/68

    Checklist of E/OHS Activities for Radon Gas Safety

    Program Contact Person: Art Schweitzer

    Is the Radon Gas Safety Plan in place? Yes No N/A

    Is the Plan current? Yes No N/AHas the Plan been reviewed this school year? Yes No N/A

    Testing was last conducted: No records on file.(date)

    Results of tests:

    Room Name & No. Level Tested Recommendation

    Has training is not requirement of this program. However if elevated levels aredetermine present training of affected persons is recommended.

    Date training complete: N/A

    Testing is / is not now in progress:

    Note: No records could be located that indicated testing for radon in the past.I recommend that areas below grade be tested.

  • 8/3/2019 ActivitiesCheclist10-11_3

    61/68

    Checklist of E/OHS Activities for Respiratory Protection

    Program Contact Person: Art Schweitzer

    Does this school provide respirators for voluntary use? Yes No N/A

    If the school allows employees to use respirators voluntarily the following ismandatory.

    1. Read and follow instructions provided by manufacturer.2. Choose respirators certified for use against contaminants of concern.3. Do not wear respirators in atmospheres containing contaminants not

    designed to protect from those contaminants.4. Keep track of respirators so that you do not mistakenly wear someone

    elses respirator.

    Is the Respiratory Protection program in place? Yes No N/A

    Is the Plan current? Yes No N/A

    Has the Plan been reviewed this school year? Yes No N/A

    Date of review: _Sept, 2010

    Are all employees in this program identified? Yes No N/A

    Employee IntendedUse

    Type ofRespirator

    Medical Exam/Questionnaire

    Date ofMedical

    Date ofFit Test

    Art Schweitzer Misc.voluntary

    Mask yes 1/2009 1/2009

    Fit testing was completed on N/A.(date)

    Type of testing protocol; Irritant Smoke (Stannic Chloride) orBitrex (Denatonium Benzoate)

    Condition and location of respirators:

    Condition: Good condition

    Location(s): In metal cabinet next to desk in boiler room.

  • 8/3/2019 ActivitiesCheclist10-11_3

    62/68

    Are the appropriate adequate accessories on hand? Yes No N/A

    Verified by Lee Carlson

    Respirator Equipment Inventory

    Cartridges

    RespiratorType

    RespiratorBrand Location

    ValveFlaps? Straps? Organic Particulate Combination

    PAPRPowerFlow

    PAPRPowerFlow

    mask AOS Boiler room

    yes yes yes

    mask

    mask

    Full face Wilson Boiler room

    yes yes yes

    Full face

  • 8/3/2019 ActivitiesCheclist10-11_3

    63/68

    The respirators were cleaned and checked 1-4-10. LCArt is no longer fit checked and having physicals completed as a requirement ofthe local fire department. Future use will be on a voluntary basis.1-4-10

  • 8/3/2019 ActivitiesCheclist10-11_3

    64/68

  • 8/3/2019 ActivitiesCheclist10-11_3

    65/68

    Checklist of E/OHS Activities for Underground and AbovegroundStorage Tanks

    Program Contact Person: Art Schweitzer

    Is the Underground and Aboveground Storage Tanks Plan in place? Yes No

    Is the Plan current? Yes No

    Has the Plan been reviewed this school year? Yes No

    Have forms for inventory tracking been provided? Yes No N/A

    Do existing records accurately reflect purchase use correlation? Yes No N/A

    Are all USTs registered with the Minnesota Pollution Control Agency? Yes NoN/A

    Are removals or additions of tanks anticipated in this facility? Yes No N/A

    Notes:

    Underground/Aboveground Storage Tank Status

    Tank No. Location Size Contents Registered Install date

    #1 West sidebetweenbuildings

    5,000 #2 fuel oil yes

    Regulated Tanks:Motor fuel tanks larger than 110 gallons

    Non-regulated Tanks:Heating oil tanks

    Requirements for All USTs: Tank must be registered with MPCA

    Requirements for Regulated Tanks:Annual tightness testing and inventorycontrol Tank must be updated, replaced, or removed by December 22, 1998

    Upgrades:--Overfill protection--Corrosion protection STPI approved

  • 8/3/2019 ActivitiesCheclist10-11_3

    66/68

    --Leak detection

    Tightness Testing Results on File:

    Dates of past testing:_____N/A_______________

    Records on file:_____N/A___________________

  • 8/3/2019 ActivitiesCheclist10-11_3

    67/68

    Checklist of E/OHS Activities for Welding and Brazing Safety

    Program Contact Person(s) Darrel Mayer

    Department Contact:

    Metals Shop/Ag. FFA Darrel Mayer

    Art (jewelry) N/A

    Custodial N/A

    Is the Welding and Brazing Plan in place? Yes No

    Is the Plan current? Yes No

    Has the Plan been reviewed this school year? Yes No

    Method or methods used to control airborne particulate matter? Externalnegative air and internal filters

    Has training been conducted for affected personnel? Yes No

    Type of welding equipment available

    Electric arch. Yes No N/A

    Wire feed/TIG MIG. Yes No N/A

    Electric spot weld Yes No N/A

    Personal Protective Equipment: availability and condition

    Gloves Yes No N/A

    Goggles Yes No N/A

    Welding mask Yes No N/A

    Apron Yes No N/A

    Steel toed shoes Yes No N/A

    Describe location of welding activities, example; out-of-doors, booth, floor, allof the above:

    Welding can conducted indoors or out. The air filter is adequate to handle asignificant particle load.