38
ACS Annunciators

ACS Annunciators. EIA-485 specification Overview RPT-485 - May extend the length 4,000 feet

Embed Size (px)

Citation preview

Page 1: ACS Annunciators. EIA-485 specification Overview RPT-485 - May extend the length 4,000 feet

ACSAnnunciators

Page 2: ACS Annunciators. EIA-485 specification Overview RPT-485 - May extend the length 4,000 feet

EIA-485 specification

Overview

RPT-485- May extend the length 4,000 feet

Page 3: ACS Annunciators. EIA-485 specification Overview RPT-485 - May extend the length 4,000 feet

Control Button

CONTROL for:- SLC Relay - NAC Control Modules- Speaker Circuits - Software Zones

ACM-24AT and ACM-48A

ACM-24AT

- Visual Indication ONLY

ACM-48A

Page 4: ACS Annunciators. EIA-485 specification Overview RPT-485 - May extend the length 4,000 feet

Rear View

Page 5: ACS Annunciators. EIA-485 specification Overview RPT-485 - May extend the length 4,000 feet

Address Wheels

NFS-320 / NFS2-640MAP

NFS2-3030 / NCA-2MAP

Page 6: ACS Annunciators. EIA-485 specification Overview RPT-485 - May extend the length 4,000 feet

KeylockSwitch

Key Lock Connection

Page 7: ACS Annunciators. EIA-485 specification Overview RPT-485 - May extend the length 4,000 feet

Dip Switches

Page 8: ACS Annunciators. EIA-485 specification Overview RPT-485 - May extend the length 4,000 feet

Receive & Transmit LED’s

Page 9: ACS Annunciators. EIA-485 specification Overview RPT-485 - May extend the length 4,000 feet

End of Line Resistor

Page 10: ACS Annunciators. EIA-485 specification Overview RPT-485 - May extend the length 4,000 feet

24V

Power Connection

Page 11: ACS Annunciators. EIA-485 specification Overview RPT-485 - May extend the length 4,000 feet

ACS Connection

Page 12: ACS Annunciators. EIA-485 specification Overview RPT-485 - May extend the length 4,000 feet

EIA-485 Circuits Power Circuits

RETROFIT CONSIDERATIONS

Page 13: ACS Annunciators. EIA-485 specification Overview RPT-485 - May extend the length 4,000 feet

- A 64 point map exceeds physical points on an annunciator- So we add an expander

ACM-24ATAEM-24AT

Address Expansion

Note the differencein device population

Page 14: ACS Annunciators. EIA-485 specification Overview RPT-485 - May extend the length 4,000 feet

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

51

52

53

54

55

56

57

58

59

60

61

62

63

64

NOT

USED

ACM-24AT AEM-24AT AEM-24AT

Set AddressIntelligence

resides on board

Expansion annunciatorsconnect to communication bus

and receive information through host ACM

ACM-24AT with 64-Point Limit

Page 15: ACS Annunciators. EIA-485 specification Overview RPT-485 - May extend the length 4,000 feet

123456789101112131415161718192021222324

ACM-48ASet AddressIntelligence

resides on board

AEM-48AExpansion annunciators connect to

communication bus and receiveinformation through host ACM

252627282930313233343536373839404142434445464748

495051525354555657585960616263646566676869707172

737475767778798081828384858687888990919293949596

NOT

USED

NOT

USED

NOT

USED

ACM-48A with 64-Point Limit

Page 16: ACS Annunciators. EIA-485 specification Overview RPT-485 - May extend the length 4,000 feet

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

ACM-24AT AEM-24AT AEM-24AT

Set AddressIntelligence

resides on board

Expansion annunciatorsconnect to communication bus

and receive information through host ACM

ACM-24AT with 96-Point Limit

49

50

51

52

53

54

55

56

57

58

59

60

61

62

63

64

65

66

67

68

69

70

71

72

73

74

75

76

77

78

79

80

81

82

83

84

85

86

87

88

89

90

91

92

93

94

95

96

AEM-24AT

Page 17: ACS Annunciators. EIA-485 specification Overview RPT-485 - May extend the length 4,000 feet

123456789101112131415161718192021222324

ACM-48ASet AddressIntelligence

resides on board

AEM-48AExpansion annunciators connect to

communication bus and receiveinformation through host ACM

252627282930313233343536373839404142434445464748

495051525354555657585960616263646566676869707172

737475767778798081828384858687888990919293949596

ACM-48A with 96-Point Limit

Page 18: ACS Annunciators. EIA-485 specification Overview RPT-485 - May extend the length 4,000 feet

DOORS

Page 19: ACS Annunciators. EIA-485 specification Overview RPT-485 - May extend the length 4,000 feet

CABINETRY

Page 20: ACS Annunciators. EIA-485 specification Overview RPT-485 - May extend the length 4,000 feet

Address Wheel Relationship

NFS-320 / NFS2-640MAP

1 6

Page 21: ACS Annunciators. EIA-485 specification Overview RPT-485 - May extend the length 4,000 feet

MAP Assignment

Page 22: ACS Annunciators. EIA-485 specification Overview RPT-485 - May extend the length 4,000 feet

SETUP in the NFS-320 and NFS2-640

Pre-defined Maps:

ACS Group Annunciator DisplayA 8 System points & Zones 1 – 56B Zones 57 - 99, 9 F Zones, 8 R Zones, 4 NACsC Loop 1, Modules 1 – 64D Loop 2, Modules 1 – 64E Loop 1, Modules 65 – 128F Loop 2, Modules 65 – 128

G Loop 1, Modules 129 - 159 (1 unused point) Loop 2, Modules 129 - 159 (1 unused point)

H Loop 1, Detectors 1 – 64I Loop 2, Detectors 1 – 64J Loop 1, Detectors 65 – 128K Loop 2, Detectors 65 – 128

L Loop 1, Detectors 129 - 159 (1 unused point) Loop 2, Detectors 129 - 159 (1 unused point)

M For use with FireVoice NFV-25/50ZS N 8 System Points & Zones 1-56 O 8 System Points & Zones 1-56

MAP A 8 System points & Zones 1 – 56

Points 11 – 62 Zones 3 thru 54

SYSTEMPOINTS

Page 23: ACS Annunciators. EIA-485 specification Overview RPT-485 - May extend the length 4,000 feet

POINT TYPE RED LED YELLOW LED SWITCH FUNCTION*1 Input System Alarm System Trouble Acknowledge2 Output Not Used Signal Silenced Alarm Silence3 Output Not Used Program Mode System Reset4 Output Not Used Supervisory Drill5 Output NAC #1 Active NAC Trouble Control NAC #16 Input Security P/A Maint Alert Not Used7 Input Not Used Low Battery Not Used8 Input Not Used AC Fail Not Used

* Pressing the switch button when the Switch Function is "Not Used" causes the associated LED to stop blinking. This is a local acknowledgement at the annunciator only: no message is sent to the panel.

SYSTEM POINTS

Page 24: ACS Annunciators. EIA-485 specification Overview RPT-485 - May extend the length 4,000 feet

Pre-defined and USER MapsACS Group Annunciator Display

A 8 System points & Zones 1 – 56B Zones 57 - 99, 9 F Zones, 8 R Zones, 4 NACsC Loop 1, Modules 1 – 64D Loop 2, Modules 1 – 64E Loop 1, Modules 65 – 128F Loop 2, Modules 65 – 128

G Loop 1, Modules 129 - 159 (1 unused point) Loop 2, Modules 129 - 159 (1 unused point)

H Loop 1, Detectors 1 – 64I Loop 2, Detectors 1 – 64J Loop 1, Detectors 65 – 128K Loop 2, Detectors 65 – 128

L Loop 1, Detectors 129 - 159 (1 unused point) Loop 2, Detectors 129 - 159 (1 unused point)

M For use with FireVoice NFV-25/50ZS N 8 System Points & Zones 1-56 O 8 System Points & Zones 1-561 – 10 USER-DEFINED MAPS

Page 25: ACS Annunciators. EIA-485 specification Overview RPT-485 - May extend the length 4,000 feet

SETUP in the NFS-320 and NFS2-640

ACS Group Annunciator Display1 Programmable Annunciator #12 Programmable Annunciator #23 Programmable Annunciator #34 Programmable Annunciator #45 Programmable Annunciator #56 Programmable Annunciator #67 Programmable Annunciator #78 Programmable Annunciator #89 Programmable Annunciator #9

10 Programmable Annunciator #10

Page 26: ACS Annunciators. EIA-485 specification Overview RPT-485 - May extend the length 4,000 feet

User Defined Maps

Page 27: ACS Annunciators. EIA-485 specification Overview RPT-485 - May extend the length 4,000 feet

User Map Programming

Select User Map #1

Page 28: ACS Annunciators. EIA-485 specification Overview RPT-485 - May extend the length 4,000 feet

User Map Programming

Select a point TYPE

Page 29: ACS Annunciators. EIA-485 specification Overview RPT-485 - May extend the length 4,000 feet

User Map Programming

When you choose the point, installed points appear

Page 30: ACS Annunciators. EIA-485 specification Overview RPT-485 - May extend the length 4,000 feet

User Map Programming

Selecting the point will install it on the map

Page 31: ACS Annunciators. EIA-485 specification Overview RPT-485 - May extend the length 4,000 feet

User Map Programming

You must decide what to DO with the point

Page 32: ACS Annunciators. EIA-485 specification Overview RPT-485 - May extend the length 4,000 feet

User Map Programming

Monitor/Control or Enable/Disable

Page 33: ACS Annunciators. EIA-485 specification Overview RPT-485 - May extend the length 4,000 feet

User Map Programming

Select MODIFY to install the point

Page 34: ACS Annunciators. EIA-485 specification Overview RPT-485 - May extend the length 4,000 feet

Final ACS Addressing

When the User-Defined map is saved, it will appear in the list

Page 35: ACS Annunciators. EIA-485 specification Overview RPT-485 - May extend the length 4,000 feet

CLICKACS1

Final ACS Addressing

When it’s added, ACS 1 is highlighted providing a quick-link

Page 36: ACS Annunciators. EIA-485 specification Overview RPT-485 - May extend the length 4,000 feet

Final ACS Addressing

The quick-link brings you back to the User Map

Page 37: ACS Annunciators. EIA-485 specification Overview RPT-485 - May extend the length 4,000 feet

ACS Map in VeriFire Tools

NFS-320 / NFS2-640MAP

Page 38: ACS Annunciators. EIA-485 specification Overview RPT-485 - May extend the length 4,000 feet

Questions