AccuSine PCS Selection 060427

Embed Size (px)

Citation preview

  • 8/13/2019 AccuSine PCS Selection 060427

    1/2

    Job ID:

    Ref #:

    St:

    Postal Code:

    Contact:

    5.0%

    2,250.0 KVA

    6.360% Impedance

    51,062.8 SCA

    799.8 amps

    Enter if known. Program will calculate demand load based upon loads defined below if not provided.63.8

    400 V

    If no value is entered for voltage, 480V is assumed.

    15%

    20%

    50

  • 8/13/2019 AccuSine PCS Selection 060427

    2/2

    0.950

    1.000

    If no values are entered for PF, this program defaults to .95 for both entries.

    D.

    Qty HP # Qty HP # Qty HP # Qty HP # Qty KVA # Qty KVA # Qty KVA # Qty KVA # Qty KVA #

    1 1 1.01 6 1 56.25 6

    2 2 2.01 6 1 23.13 6

    3 2 2.95 6 1 27.5 6

    4 1 5.36 6

    5 1 10.1 6

    6 2 14.7 6

    7 1 40.2 6

    8 1 49.6 6

    9 4 60.3 6

    10

    1112

    y Enter Y for yes, N for no.

    (Program defaults to 'No'.)

    D.1 KVA

    Linear Loads:E. 112.25 KVA

    The following summary is the basis for the AccuSine PCS selection shown below.

    400 volts.

    790.8 amps.

    162.0 amps.

    0.950

    1.000

    18.45% TDD.

    5.00% TDD.

    300.1

    Total rms current: Amps

    Fundamental current: Amps

    Harmonic current: Amps

    TDD:

    Reactive current: Amps

    Equivalent kVAR correction: kVAR

    The electrical system voltage is

    All loads total

    The original displacement power factor is

    The objective displacement power factor is

    742.8

    The TDD of the electrical system before AccuSine PCS is

    185.6

    Electrical System Current Approximations

    The objective TDD is

    142.7

    18.45%

    267.9

    List the tot al KVA of installed UV equipment:

    AccuSine PCS Select ion Resul ts :

    4.92%

    0.0

    773.4

    All linear loads total

    The requi red rat ing o f the AccuSine PCS system is amperes of co rrec tion .

    System with

    Acc uSin e

    Operating

    743.7

    Nonlinear Loads:

    UPS

    36.5

    CapacitiveResistive

    790.8

    System

    without

    Acc uSin e

    Are VFD loads centrifugal pump or fan loads?

    Total Linear Loads Installed:

    CSI Diode Converter

    VFDs

    PWM

    Other SCR converters

    VVI

    DC Drives

    List all nonlinear loads applicable for each group to be evaluated.

    InductiveSCR Converter

    C1. Known or calculated PF of the loads in question:

    C2. Objective displacement power factor:

    # does not require an entry if all nonlinear loads are 6-pulse and do not have dedicated tuned filters (5th harmonic trap filters). If a dedicated tuned filter is

    present enter '5' per line item. If the input rectifier is 12-pulse enter '12' per line item. If the input rectifier is 18-pulse enter '18' per line item.

    Specify 6, 12, or 18 pulse or 5, if a 5th harmonic tuned filter is used:

    Enter full load KVA capacity of linear loads.

    Displacement power factor:

    AccuSine PCS Selection 060427.xls Page 2 of 2 6/13/2007