8/13/2019 AccuSine PCS Selection 060427
1/2
Job ID:
Ref #:
St:
Postal Code:
Contact:
5.0%
2,250.0 KVA
6.360% Impedance
51,062.8 SCA
799.8 amps
Enter if known. Program will calculate demand load based upon loads defined below if not provided.63.8
400 V
If no value is entered for voltage, 480V is assumed.
15%
20%
50
8/13/2019 AccuSine PCS Selection 060427
2/2
0.950
1.000
If no values are entered for PF, this program defaults to .95 for both entries.
D.
Qty HP # Qty HP # Qty HP # Qty HP # Qty KVA # Qty KVA # Qty KVA # Qty KVA # Qty KVA #
1 1 1.01 6 1 56.25 6
2 2 2.01 6 1 23.13 6
3 2 2.95 6 1 27.5 6
4 1 5.36 6
5 1 10.1 6
6 2 14.7 6
7 1 40.2 6
8 1 49.6 6
9 4 60.3 6
10
1112
y Enter Y for yes, N for no.
(Program defaults to 'No'.)
D.1 KVA
Linear Loads:E. 112.25 KVA
The following summary is the basis for the AccuSine PCS selection shown below.
400 volts.
790.8 amps.
162.0 amps.
0.950
1.000
18.45% TDD.
5.00% TDD.
300.1
Total rms current: Amps
Fundamental current: Amps
Harmonic current: Amps
TDD:
Reactive current: Amps
Equivalent kVAR correction: kVAR
The electrical system voltage is
All loads total
The original displacement power factor is
The objective displacement power factor is
742.8
The TDD of the electrical system before AccuSine PCS is
185.6
Electrical System Current Approximations
The objective TDD is
142.7
18.45%
267.9
List the tot al KVA of installed UV equipment:
AccuSine PCS Select ion Resul ts :
4.92%
0.0
773.4
All linear loads total
The requi red rat ing o f the AccuSine PCS system is amperes of co rrec tion .
System with
Acc uSin e
Operating
743.7
Nonlinear Loads:
UPS
36.5
CapacitiveResistive
790.8
System
without
Acc uSin e
Are VFD loads centrifugal pump or fan loads?
Total Linear Loads Installed:
CSI Diode Converter
VFDs
PWM
Other SCR converters
VVI
DC Drives
List all nonlinear loads applicable for each group to be evaluated.
InductiveSCR Converter
C1. Known or calculated PF of the loads in question:
C2. Objective displacement power factor:
# does not require an entry if all nonlinear loads are 6-pulse and do not have dedicated tuned filters (5th harmonic trap filters). If a dedicated tuned filter is
present enter '5' per line item. If the input rectifier is 12-pulse enter '12' per line item. If the input rectifier is 18-pulse enter '18' per line item.
Specify 6, 12, or 18 pulse or 5, if a 5th harmonic tuned filter is used:
Enter full load KVA capacity of linear loads.
Displacement power factor:
AccuSine PCS Selection 060427.xls Page 2 of 2 6/13/2007