AC Fluke 437 II Power Quality Energy Analyzer User Datasheet

Embed Size (px)

Citation preview

  • 8/11/2019 AC Fluke 437 II Power Quality Energy Analyzer User Datasheet

    1/8

  • 8/11/2019 AC Fluke 437 II Power Quality Energy Analyzer User Datasheet

    2/8

    2 Fluke Corporation Fluke 430 Series II Three-Phase Energy and Power Quality Analyzers

    Unified Power Measurement

    Flukes patented Unified Power Measurement sys-tem (UPM) provides the most comprehensive viewof power available, measuring: Parameters of Classical Power (Steinmetz 1897)

    and IEEE 1459-2000 Power Detailed Loss Analysis Unbalance AnalysisThese UPM calculations are used to quantifythe fiscal cost of energy loss caused by powerquality issues. The calculations are computed,along with other facility-specific information,by an Energy Loss Calculator that ultimatelydetermines how much money a facility losesdue to wasted energy.

    Energy savingsTraditionally energy savings are achieved bymonitoring and targeting, or in other words, byfinding the major loads in a facility and optimiz-ing their operation. The cost of power qualitycould only be quantified in terms of downtimecaused by lost production and damage to electri-cal equipment. The Unified Power Measurement(UPM) method now goes beyond this to achieveenergy savings by discovering the energy wastecaused by power quality issues. Using theUnified Power Measurement, Flukes Energy LossCalculator (see screen shot below) will determinehow much money a facility is losing due to wasteenergy.

    Unbalance

    UPM gives a more comprehensive breakdown ofthe energy consumed in the plant. In addition tomeasuring reactive power (caused by poor powerfactor), UPM also measures the energy wastecaused by unbalance; the effect of unevenlyloading each phase in three-phase systems.Unbalance can often be corrected by reconnect-ing loads on different phases to ensure thecurrent drawn on each phase is as equal aspossible. Unbalance can also be corrected byinstalling an unbalance reactance device (orfilter), that will minimize the effects. Correctingunbalance should be basic good housekeepingin the facility as unbalance problems can causemotor failure or shorten equipment life expec-tancy. Unbalance also wastes energy. UsingUPM can minimize or eliminate that energywaste, thus saving money.

    HarmonicsUPM also provides details of the energy wastedin your facility due to the presence of harmonics.Harmonics may be present in your facility due tothe loads you operate or may be caused by loadsin adjacent facilities. The presence of harmonicsin your facility can lead to: overheating transformers and conductors nuisance tripping of circuit breakers early failures of electrical equipmentQuantifying the cost of wasted energy due to thepresence of harmonics simplifies the return-on-investment calculation needed to justify purchas-ing harmonic filters. By installing a harmonicfilter the ill effects of harmonics can be reducedand energy waste eliminated, resulting in loweroperational costs and more reliable operation.

    Useful kilowatts (power) available ____________

    Reactive (unusable) power ____________

    Kilowatts made unusable by unbalance issues ____________

    Kilowatts made unusable by harmonics ____________

    Neutral current ____________

    Total cost of wasted kilowatt hours ____________

    Energy Loss Calculator

    actoolsupply.com

    actoolsupply.com

  • 8/11/2019 AC Fluke 437 II Power Quality Energy Analyzer User Datasheet

    3/8

    3 Fluke Corporation Fluke 430 Series II Three-Phase Energy and Power Quality Analyzers

    Technical specifications

    Specifications are valid for models Fluke 434-II, Fluke 435-II, Fluke 437-II unless otherwise specified.Specificatons for Amp and Watt readings are based upon i430-Flexi-TF unless otherwise specified.

    Input characteristicsVoltage inputsNumber of inputs 4 (3 phase + neutral) dc-coupledMaximum input voltage 1000 VrmsNominal voltage range Selectable 1 V to 1000 VMax. peak measurement voltage 6 kV (transient mode only)Input impedance 4 M//5 pFBandwidth > 10 kHz, up to 100 kHz for transient modeScaling 1:1, 10:1, 100:1, 1,000:1 10,000:1 and variableCurrent inputsNumber of inputs 4 (3 phase + neutral) dc- or ac-coupledType Clamp or current transformer with mV output or i430flex-TFRange 0.5 Arms to 600 Arms with included i430flex-TF (with sensitivity 10x)

    5 Arms to 6000 Arms with included i430flex-TF (with sensitivity 1x)0.1 mV/A to 1 V/A and custom for use with optional ac or dc clamps

    Input impedance 1 MBandwidth > 10 kHzScaling 1:1, 10:1, 100:1, 1,000:1 10,000:1 and variable

    430 Series II Power Quality and Energy Analyzer selection table

    Model Fluke 434-II Fluke 435-II Fluke 437-IIStandard compliance IEC 61000-4-30 Class S IEC 61000-4-30 Class A IEC 61000-4-30 Class AVolt Amp Hz

    Dips and swells

    Harmonics

    Power and energy

    Energy loss calculator

    Unbalance

    Monitor

    Inrush

    Event waveform capture

    Flicker

    Transients

    Mains signaling

    Power wave

    Power inverter efficiency

    400Hz

    C1740 Soft Case

    C437-II Hard Case with rollers

    SD card (Max 32 GB) 8 GB 8 GB 8 GBAll models include the following accessories TL430 test lead set, 4 x i430 thin flexi current probes, BP290 battery, BC430 power adapter with international power adapter set, USB cableA-B mini and PowerLog CD.

    actoolsupply.com

    actoolsupply.com

  • 8/11/2019 AC Fluke 437 II Power Quality Energy Analyzer User Datasheet

    4/8

    4 Fluke Corporation Fluke 430 Series II Three-Phase Energy and Power Quality Analyzers

    Measurement modesScope 4 voltage waveforms, 4 current waveforms, Vrms, Vfund. Arms, A fund, V @ cursor, A @ cursor, phase anglesVolts/amps/hertz Vrms phase to phase, Vrms phase to neutral, Vpeak, V Crest Factor, Arms Apeak, A Crest Factor, HzDips and swells Vrms, Arms, Pinst with programmable threshold levels for event detectionHarmonics dc, 1 to 50, up to 9th harmonicfor 400 Hz

    Harmonics Volts, THD, Harmonic Amps, K factor Amps, Harmonic Watts, THd Watts, K factor Watts, InterharmonicVolts, Interharmonic Amps, Vrms, Arms (relative to fundamental or to total rms)

    Power and energy Vrms, Arms, Wfull, Wfund., VAfull, VAfund., VAharmonics, VAunbalance, var, PF, DPF, CosQ, Efficiency factor,Wforward, Wreverse

    Energy loss calculator Wfund, VAharmonics, VAunbalance, var, A, Loss Active, Loss Reactive, Loss Harmonics, Loss Unbalance, LossNeutral, Loss Cost (based upon user defined cost / kWh)Inverter efficiency(requires optional dc current clamp)

    Wfull, Wfund, Wdc, Efficiency, Vdc, Adc, Vrms, Arms, Hz

    Unbalance Vneg%, Vzero%, Aneg%, Azero%, Vfund, Afund, V phase angles, A phase anglesInrush Inrush current, Inrush duration, Arms, VrmsMonitor Vrms, Arms, harmonic Volts, THD Volts, PLT, Vrms, Arms, Hz, dips, swells, interruptions, rapid voltage changes,

    unbalance and mains signalling.All parameters are measured simultaneously in accordance with EN50160Flagging is applied according to IEC61000-4-30 to indicate unreliable readings due to dips or swells

    Flicker (435-II and 437-II only) Pst(1min), Pst, Plt, Pinst, Vrms , Arms , HzTransients (435-II and 437-II only) Transient waveforms 4x Voltage 4x Amps, triggers: Vrms , Arms , PinstMains Signaling (435-II and 437-II only) Relative signaling voltage and absolute signaling voltage averaged over three seconds for up to two selectable

    signaling frequenciesPower Wave (435-II and 437-II only) Vrms, Arms W, Hz and scope waveforms for voltage amps and watts

    Logger Custom selection of up to 150 PQ parameters measured simultaneously on 4 phases

    Sampling systemResolution 16 bit analog to digital converter on 8 channelsMaximum sampling speed 200 kS/s on each channel simultaneouslyRMS sampling 5000 samples on 10/12 cycles according to IEC61000-4-30PLL synchronization 4096 samples on 10/12 cycles according to IEC61000-4-7Nominal frequency 434-II and 435-II: 50 Hz and 60 Hz

    437-II: 50 Hz, 60 Hz and 400 Hz

    Display modesWaveform display Available in all modes via SCOPE key

    435-II and 437-II: Default display mode for Transients functionUpdate rate 5x per secondDisplays 4 cycles of waveform data on screen, up to 4 waveforms simultaneously

    Phasor diagram Available in all modes via Scope waveform displayDefault view for Unbalance mode

    Meter readings Available in all modes except Monitor and Transients, provides tabulated view of all available readingsFully customizable up to 150 readings for Logger mode

    Trend graph Available in all modes except TransientsSingle vertical cursor with min max and avg reading at cursor position

    Bar graph Available in Monitor and Harmonics modeEvent list Available in all modes

    Provides waveforms on 435II & 437II only.

    Input characteristics cont.

    actoolsupply.com

    actoolsupply.com

  • 8/11/2019 AC Fluke 437 II Power Quality Energy Analyzer User Datasheet

    5/8

    5 Fluke Corporation Fluke 430 Series II Three-Phase Energy and Power Quality Analyzers

    Product specificationsModel Measurement range Resolution Accuracy

    VoltVrms (ac+dc) 434-II 1 V to 1000 V phase to neutral 0.1 V 0.5 % of nominal voltage****

    435-II and 437-II 1 V to 1000 V phase to neutral 0.01 V 0.1 % of nominal voltage****Vpk 1 Vpk to 1400 Vpk 1 V 5 % of nominal voltageVoltage Crest Factor (CF) 1.0 > 2.8 0.01 5 %Vrms 434-II 1 V to 1000 V phase to neutral 0.1 V 1 % of nominal voltage

    434-II and 435-II 0.1 V 0.2 % of nominal voltageVfund 434-II 1 V to 1000 V phase to neutral 0.1 V 0.5 % of nominal voltage

    435-II and 437-II 0.1 V 0.1 % of nominal voltageAmps (accuracy excluding clamp accuracy)Amps (ac +dc) i430-Flex 1x 5 A to 6000 A 1 A 0.5 % 5 counts

    i430-Flex 10x 0.5 A to 600 A 0.1 A 0.5 % 5 counts1mV/A 1x 5 A to 2000 A 1A 0.5 % 5 counts1mV/A 10x 0.5 A A to 200 A (ac only) 0.1 A 0.5 % 5 counts

    Apk i430-Flex 8400 Apk 1 Arms 5 %1mV/A 5500 Apk 1 Arms 5 %

    A Crest Factor (CF) 1 to 10 0.01 5 %Amps i430-Flex 1x 5 A to 6000 A 1 A 1 % 10 counts

    i430-Flex 10x 0.5 A to 600 A 0.1 A 1 % 10 counts1mV/A 1x 5 A to 2000 A 1A 1 % 10 counts1mV/A 10x 0.5 A A to 200 A (ac only) 0.1 A 1 % 10 counts

    Afund i430-Flex 1x 5 A to 6000 A 1 A 0.5 % 5 countsi430-Flex 10x 0.5 A to 600 A 0.1 A 0.5 % 5 counts1mV/A 1x 5 A to 2000 A 1A 0.5 % 5 counts1mV/A 10x 0.5 A A to 200 A (ac only) 0.1 A 0.5 % 5 counts

    HzHz Fluke 434 @ 50 Hz nominal 42.50 Hz to 57.50 Hz 0.01 Hz 0.01 Hz

    Fluke 434 @ 60 Hz nominal 51.00 Hz to 69.00 Hz 0.01 Hz 0.01 HzFluke 435/7 @ 50 Hz nominal 42.500 Hz to 57.500 Hz 0.001 Hz 0.01 Hz

    Fluke 435/7 @ 60 Hz nominal 51.000 Hz to 69.000 Hz 0.001 Hz 0.01 HzFluke 437 @ 400 Hz nominal 340.0 Hz to 460.0 Hz 0.1 Hz 0.1 Hz

    PowerWatts (VA, var) i430-Flex max 6000 MW 0.1 W to 1 MW 1 % 10 counts

    1 mV/A max 2000 MW 0.1 W to 1 MW 1 % 10 countsPower factor (Cos j/DPF) 0 to 1 0.001 0.1 % @ nominal load conditionsEnergykWh (kVAh, kvarh) i430-Flex 10x Depends on clamp scaling and V nominal 1 % 10 countsEnergy loss i430-Flex 10x Depends on clamp scaling and V nominal 1 % 10 counts

    Excluding line resistance accuracyHarmonicsHarmonic order (n) DC, 1 to 50 Grouping: Harmonic groups according to IEC 61000-4-7Inter-harmonic order (n) OFF, 1 to 50 Grouping: Harmonic and Interharmonic subgroups according to IEC 61000-4-7

    Volts %f 0.0 % to 100 % 0.1 % 0.1 % n x 0.1 %%r 0.0 % to 100 % 0.1 % 0.1 % n x 0.4 %Absolute 0.0 to 1000 V 0.1 V 5 % *THD 0.0 % to 100 % 0.1 % 2.5 %

    Amps %f 0.0 % to 100 % 0.1 % 0.1 % n x 0.1 %%r 0.0 % to 100 % 0.1 % 0.1 % n x 0.4 %Absolute 0.0 to 600 A 0.1 A 5 % 5 countsTHD 0.0 % to 100 % 0.1 % 2.5 %

    Watts %f or %r 0.0 % to 100 % 0.1 % n x 2 %Absolute Depends on clamp scaling and V nominal 5 % n x 2 % 10 countsTHD 0.0 % to 100 % 0.1 % 5 %

    Phase Angle -360 to +0 1 n x 1

    actoolsupply.com

    actoolsupply.com

  • 8/11/2019 AC Fluke 437 II Power Quality Energy Analyzer User Datasheet

    6/8

    6 Fluke Corporation Fluke 430 Series II Three-Phase Energy and Power Quality Analyzers

    FlickerPlt, Pst, Pst(1min) Pinst 0.00 to 20.00 0.01 5 %UnbalanceVolts % 0.0 % to 20.0 % 0.1 % 0.1 %Amps % 0.0 % to 20.0 % 0.1% 1 %Mains signalingThreshold levels Threshold, limits and signaling duration is

    programable for two signaling frequencies

    Signaling frequency 60 Hz to 3000 Hz 0.1 HzRelative V% 0 % to 100 % 0.10 % 0.4 %Absolute V3s (3 second avg.) 0.0 V to 1000 V 0.1 V 5 % of nominal voltage

    Trend recordingMethod Automatically records min, max and average values over t ime for all readings being displayed for the three phases and neutral

    simultaneouslySampling 5 readings/s continuous sampling per channel, 100/120** reading/s for 1/2 cycle values and Pinst

    Recording time 1 hr up to 1 year, user selectable (default setting 7 days)Averaging time Minimum of 1 secondMemory Data is stored on SDcard (8GB included 32GB max)Events 434-II: Tabulated in event list

    435-II & 437-II: Tabulated in event list, including 50/60** waveform cycles and 7.5s 1/2 cycle rms Voltage and Amps trend

    Measurement methodVrms, Arms 10/12 cycle contiguous non-overlapping intervals using 500/416 2 samples per cycle in accordance with IEC 61000-4-30Vpeak, Apeak Absolute highest sample value within 10/12 cycle interval with 40 s sample resolutionV Crest Factor Measures ratio between the Vpeak and VrmsA Crest Factor Measures ratio between the Apeak and ArmsHz Measured every 10 sec in accordance with IEC61000-4-30. Vrms, Arms Value is measured over 1 cycle, commencing at a

    fundamental zero crossing, and refreshed each half-cycle.This technique is independent for each channel in accordance with IEC 61000-4-30.

    Harmonics Calculated from 10/12-cycle gapless harmonic group measurements on Voltage and Amps according to IEC 61000-4-7Watt Full and fundamental real power display. Calculates average value of instantaneous power over 10/12 cycle period for each

    phase. Total Active Power PT = P1 + P2 + P3.VA Full and fundamental apparent power display. Calculates apparent power using Vrms x Arms value over 10/12 cycle period.var Fundamental reactive power display. Calculates reactive power on fundamental positive sequence components. Capacitive and

    inductive load is indicated with capacitor and inductor icons.VA Harmonics Total disturbance power due to harmonics. Calculated for each phase and for total system based upon total apparent power and

    fundamental real power.VA Unbalance Unbalance power for total sytem. Calculated using symmetrical components method for fundamental apparent power and total

    apparent power.Power factor Calculated total watt/VACos j Cosine of angle between fundamental voltage and currentDPF Calculated fundamental Watt/VAEnergy/energy cost Power values are accumulated over time for kWh values. Energy cost is calculated from user defined /kWh cost variable

    Unbalance The supply voltage unbalance is evaluated using the method of symmetrical components according to IEC61000-4-30Flicker According to IEC 61000-4-15 flickermeterfunctional and design specification.

    Includes 230 V 50 Hz lamp and 120 V 60 Hz lamp models.Transient capture Captures waveform triggered on signal envelope. Additionally triggers on dips, swells, interruptions and Amps levelInrush current The inrush current begins when the Arms half cycle rises above the inrush threshold, and ends when the Arms half cycle

    rms is equal to or below the inrush threshold minus a user-selected hysteresis value. The measurement is the square root ofthe mean of the squared Arms half cycle values measured during the inrush duration. Each half-cycle interval is contiguousand non-overlapping as recommended by IEC 61000-4-30. Markers indicate inrush duration. Cursors allow measurement ofpeak Arms half cycle.

    Mains signaling Measurements are based on: either the corresponding 10/12-cycle rms value interharmonic bin or the rms of the four nearest10/12-cycle rms value interharmonic bins per IEC 61000-4-30. Limit setup for Monitor mode follows EN50160 standard limits.

    Time synchronization Optional GPS430-II timesync module provides time uncertainty 20 ms or 16.7 ms for time tagging of events and timeaggregated measurements. When synchronization is not available, time tolerance is 1-s/24h

    Product specifications cont.

    actoolsupply.com

    actoolsupply.com

  • 8/11/2019 AC Fluke 437 II Power Quality Energy Analyzer User Datasheet

    7/8

    7 Fluke Corporation Fluke 430 Series II Three-Phase Energy and Power Quality Analyzers

    EnvironmentalOperating temperature 0 C ~ +40 C; +40 C ~ +50 C excl. batteryStorage temperature -20 C ~ +60 CHumidity +10 C ~ +30 C: 95 % RH non-condensing

    +30 C ~ +40 C: 75 % RH non-condensing+40 C ~ +50 C: 45 % RH non-condensing

    Maximum operating altitude Up to 2,000 m (6666 ft) for CAT IV 600 V, CAT III 1000 VUp to 3,000 m (10,000 ft) for CAT III 600 V, CAT II 1000 VMaximum storage altitude 12 km (40,000 ft)

    Electro-Magnetic-Compatibility(EMC)

    EN 61326 (2005-12) for emission and immunity

    Interfaces mini-USB-B, Isolated USB port for PC connectivitySD card slot accessible behind instrument battery

    Warranty Three years (parts and labor) on main instrument, one year on accessories

    Included accessoriesPower options BC430 Power Adapter

    International plug adapter setBP290 (Single capacity Li-ion battery) 28Wh (Up to 8 hours)

    Leads TL430 Test lead and Alligator clip setColor coding WC100 color coding clips and regional decalsFlexible current probes i430flex-TF, 24 inch (61cm) length, 4 clampsMemory, Software andPC connection

    8 GB SD cardPowerLog on CD (includes operator manuals in PDF format)USB cable A-Bmini

    Carrying case C1740 Soft Case for 434-II and 435-IIC437 Hard Case with rollers for 437-II

    * 5 % if 1 % of nominal voltage 0.05 % of nominal voltage if < 1% of nominal voltage** 50Hz/60Hz nominal frequency according to IEC 61000-4-30

    *** 400Hz measurements are not supported for Flicker, Mains Signaling and Monitor Mode.**** for nominal voltage 50 V to 500 V

    Wiring configurations1 + NEUTRAL Single phase with neutral1 SPLIT PHASE Split phase1 IT NO NEUTRAL Single phase system with two phase voltages without neutral3 WYE Three phase four wire system WYE3 DELTA Three phase three wire system Delta3 IT Three phase system without neutral WYE3 HIGH LEG Four wire three phase Delta system with center tapped high leg3 OPEN LEG Open delta three wire system with 2 transformer windings2-ELEMENT Three phase three wire system without current sensor on phase L2/B (2 watt meter method)2-ELEMENT Three phase four wire system without voltage sensor on phase L2/BINVERTER EFFICIENCY dc voltage and current input with ac output power (automatically displayed and selected in Inverter Efficiency mode)

    General specificationsCase Design Rugged, shock proof with integrated protective holster

    Drip and dust proof IP51 according to IEC60529 when used in tilt stand positionShock and vibration Shock 30 g, vibration: 3 g sinusoid, random 0.03 g 2 /Hz according to MIL-PRF-28800F Class 2

    Display Brightness: 200 cd/m 2 typ. using power adapter, 90 cd/m 2 typical using battery powerSize: 127 mm x 88 mm (153 mm/6.0 in diagonal) LCDResolution: 320 x 240 pixelsContrast and brightness: user-adjustable, temperature compensated

    Memory 8GB SD card (SDHC compliant, FAT32 formatted) standard, upto 32GB optionallyScreen save and multiple data memories for storing data including recordings (dependent on memory size)

    Real-time clock Time and date stamp for Trend mode, Transient display, System Monitor and event capture

    actoolsupply.com

    actoolsupply.com

  • 8/11/2019 AC Fluke 437 II Power Quality Energy Analyzer User Datasheet

    8/8

    Ordering informationFluke-434-II Three-Phase Energy AnalyzerFluke-435-II Three-Phase Power Quality and Energy AnalyzerFluke-437-II 400 Hz Three-Phase Power Quality and Energy AnalyzerOptional/replacement accessoriesI430-FLEXI-TF-4PK 6000 A Fluke 430 Thin Flexi 61 cm (24 in) 4 packC437-II Hard Case 430 Series II with rollerC1740 Softcase for 174X and 43X-II PQ Analyzeri5sPQ3 i5sPQ3, 5 A ac Current Clamps, 3-packi400s i400s AC Current ClampWC100 WC100 Color Localization SetGPS430-II GPS430 Time Synchronization ModuleBP291 Double capacity Li-ion battery (up to 16 hr)HH290 Hanging hook for use on cabinet doors

    Fluke. The Most Trusted Tools in the World.

    Flexible Current Probe i430 Flexi-TF specificationGeneral specificationsProbe and cable material Alcryn 2070NC, reinforced insulation, UL94 V0, Color: REDCouplings material Lati Latamid 6H-V0 NylonProbe cable length 610 mm (24 in)Probe cable diameter 12.4 mm (0.49 in)Probe cable bend radius 38.1 mm (1.5 in)Output cable length 2.5 meters RG58Output connector Safety BNC connectorOperating range -20 C to +90 CStorage temperature -40 C to +105COperating humidity 15 % to 85 % (non condensing)Degree of protection (Probe) IP41SpecificationsCurrent range 6000 A AC RMSVoltage output (@1000 ARMS, 50 Hz) 86.6 mVAccuracy 1 % of reading (@ 25 C, 50 Hz)Linearity (10 % to 100 % of range) 0.2 % of readingNoise (10 Hz 7 kHz) 1.0 mV ACRMSOutput impedance 82 minLoad impedance 50 MInternal Resistance per 100 mm probelength

    10.5 5 %

    Bandwidth (-3dB) 10 Hz to 7 kHzPhase error (45 Hz 65 Hz) 1Position sensitivity 2 % of reading max.Temperature coefficient 0.08 % max of reading per CWorking voltage(see safety standards section)

    1000 V AC RMS or DC (head)30 V max. (output)

    actoolsupply.com

    t l l