HAND in HAND HIGHER and HIGHER Haier Air conditioner Cooperation – AIRCON For Europe

Abnormality Solution DB

  • Upload
    aisman8

  • View
    393

  • Download
    8

Embed Size (px)

DESCRIPTION

service manuals air conditioner

Citation preview

Page 1: Abnormality Solution DB

HAND in HAND

HIGHER and HIGHER

Haier Air conditioner

Cooperation – AIRCON For EuropeFor Europe

Page 2: Abnormality Solution DB

Cooperation – AIRCON For EuropeFor Europe

HSU-18H03/R2(DB) HFU-18H03/R2(DB)

HSU-22H03/R2(DB)

Page 3: Abnormality Solution DB

Cooperation – AIRCON For EuropeFor Europe

Malfunction Codes (1)

Content

Malfunction codes

Indoor Unit

Outdoor Unit

Auto

Recover

Twinklingtimes of outdoor

LED 2

Power Timer operateoperate Heat Cool

Room-temperature sensor malfunction ★ ■ ■ * *

Heat-exchange thermister anomaly ★ � � * *

Frost-removing temperature sensor fault � � ★ * * 10

Exhaust temperature sensor ★ � ■ * * 13

Outdoor ambient temp sensor fault � ★ ■ * * 12

Page 4: Abnormality Solution DB

Cooperation – AIRCON For EuropeFor Europe

Malfunction Codes (2)

Content

Malfunction codes

Indoor Unit

Outdoor Unit

Auto

Recover

Twinklingtimes of outdoor

LED 2

Power Timer operate

operate Heat Cool

Communication fault between the indoor and outdoor units ■ ■ ★ * * 15

Anomaly of compressor Running ★ ■ � * 18or19

Overheat protection for exhaust temperature ■ ★ ■ * 8

AC electricity protection ★ ★ ■ * 3

DC electricity protection ★ ★ � * 2

Page 5: Abnormality Solution DB

Cooperation – AIRCON For EuropeFor Europe

Malfunction Codes (3)

Content

Malfunction codes

Indoor Unit

Outdoor Unit

Auto

Recover

Twinklingtimes of outdoor

LED 2

Power Timer operate

operate Heat Cool

High work-intense protection ★ ★ ★ * 21

EEPROM error ★ � ★ * *Indoor fan motor

malfunction ■ � ★ *

Explanation :□ bright ★flashing ■turn-off * Represents there is this function Explanation :□ bright ★flashing ■turn-off * Represents there is this function

Page 6: Abnormality Solution DB

Cooperation – AIRCON For EuropeFor Europe

Countermeasures for Frequent Malfunctions (1)

Countermeasure Flow Chart:Countermeasure Flow Chart:

Check whether Terminal CN4forH(CN8forHS,CN12for HFU) on the indoor mainboard contact well.

Pull out the terminals on the indoor mainboard and reinsert them.

NONO

Pull the sensor out of the mainboard, and measure the value of resistance between its two jumpers as well as the temperature at the temperature sensing head. Check the specifications of the sensor to decide whether the sensor is damaged.

Replace with a new sensor

YESYES Sensor

damaged Sensor

damaged

Malfunction unsolved

Malfunction unsolved

Sensor all right

Sensor all right

Replace with a new mainboard.

Content

Malfunction codes

Indoor Unit

Outdoor Unit

Auto

Recover

Power Timer operate

operate Heat Cool

Room-temperature sensor malfunction ★ ■ ■ * *

Page 7: Abnormality Solution DB

Cooperation – AIRCON For EuropeFor Europe

Countermeasures for Frequent Malfunctions(2)

Countermeasure Flow Chart: Countermeasure Flow Chart:

Check whether Terminal CN4forH(CN8forHS,CN12for HFU) on the indoor mainboard contact well.

Pull out the terminals on the indoor main board and reinsert them.

NONO

Pull the sensor out of the mainboard, and measure the value of resistance between its two jumpers as well as the temperature at the temperature sensing head. Check the specifications of the sensor to decide whether the sensor is damaged.

Sensor damaged

YESYES Sensor

damaged Sensor

damaged

Malfunction unsolved

Malfunction unsolved

Replace with a new mainboard

Sensor all rightSensor all right

Content

Malfunction codes

Indoor Unit

Outdoor Unit

Auto

Recover

Power Timer operate

operate Heat Cool

Heat-exchange sensor malfunction ★ ⃞� ⃞� * *

Page 8: Abnormality Solution DB

Cooperation – AIRCON For EuropeFor Europe

Countermeasures for Frequent Malfunctions(3)

Countermeasure Flow Chart: Countermeasure Flow Chart:

Check whether Terminal CN21 on the outdoor mainboard contact well.

Pull out the terminals on the indoor mainboard and reinsert them.

NONO

Pull the sensor out of the mainboard, and measure the value of resistance between its two jumpers as well as the temperature at the temperature sensing head. Check the specifications of the sensor to decide whether the sensor is damaged.

Replace with a new sensor

YESYES Sensor

damaged Sensor

damaged

Malfunction unsolved

Malfunction unsolved

Sensor all right Sensor all right

Replace with a new mainboard.

With the malfunction, LED2 on the outdoor mainboard blinks 13 times at frequency of 1 Hz and interval of 2 seconds or so.

Content

Malfunction codes

Indoor Unit

Outdoor Unit

Auto

Recover

Power Timer operate

operate Heat Cool

Frost-removing temperature sensor fault

� � ★ * *

Page 9: Abnormality Solution DB

Cooperation – AIRCON For EuropeFor Europe

Countermeasures for Frequent Malfunctions (4)

Countermeasure Flow Chart:Countermeasure Flow Chart:

Check whether Terminal CN20 on the outdoor mainb

oard contact well.

Pull out the terminals on the indoor mainboard and reinsert them.

NONO

Pull the sensor out of the mainboard, and measure the value of resistance between its two jumpers as well as the temperature at the temperature sensing head. Check the specifications of the sensor to decide whether the sensor is damaged.

Replace with a new sensor

YESYESSensor damagedSensor damaged

Malfunction unsolved

Malfunction unsolved

Sensor all rightSensor all right

Replace with a new mainboard

With the malfunction, LED2 on the outdoor mainboard blinks 10 times at frequency of 1 Hz and interval of 2 seconds or so.

Content

Malfunction codes

Indoor Unit

Outdoor Unit

Auto

Recover

Power Timer operate

operate Heat Cool

Exhaust temperature sensor ★ � ■ * *

Page 10: Abnormality Solution DB

Cooperation – AIRCON For EuropeFor Europe

Countermeasures for Frequent Malfunctions (5)

Countermeasure Flow Chart:Countermeasure Flow Chart:

Check whether Terminal CN22 on the outdoor mainboard contact well.

Pull out the terminals on the indoor mainboard and reinsert them.

NONO

Pull the sensor out of the mainboard, and measure the resistance between its two jumpers as well as the temperature at the temperature sensing head. Check the specifications of the sensor to decide whether the sensor is damaged.

Replace with a new sensor

YESYES Sensor damagedSensor damaged

Malfunction unsolved

Malfunction unsolved Sensor all rightSensor all right

Replace with a new mainboard

With the malfunction, LED2 on the outdoor mainboard blinks 12 times at frequency of 1 Hz and interval of 2 seconds or so.

Content

Malfunction codes

Indoor Unit

Outdoor Unit

Auto

Recover

Power Timer operate

operate Heat Cool

Ambient temp sensor fault � ★ ■ * *

Page 11: Abnormality Solution DB

Cooperation – AIRCON For EuropeFor EuropeCountermeasures for Frequent Malfunctions ( 7-

1)

Countermeasure Flow Chart:Countermeasure Flow Chart:

Connect to the power supply, and turn on with the remote controller to check whether it starts up normally.

1. If starting up normally, the outdoor mainboard needs dewetting;

2. .If starting up normally, but malfunction occurs again after a while, the outdoor mainboard needs dedusting.

YESYES

Check whether the linking cable between the indoor and outdoor units is well connected and whether its core wires are well insulated.

Check the status of LED1 on the indoor mainboard.

NONO See next page.( TO BE CONTIUED )

NONO

1.Reconnect the linking cable;

2. Replace the linking cable with new one.

YESYES OFFOFF

onon

1. If LED1 keeps on, the indoor mainboard is damaged;

2. If LED1 blinks interruptedly, both the indoor and outdoor mainboards may be damaged. Judge as follow:

⑴ measure the voltage between Jumpers 3 and 4 of PC1 on the indoor mainboard with a multimeter. If the voltage is of a constant value of 0VDC or 5VDC, the indoor mainboard is damaged;

⑵ measure the voltage between Jumpers 3 and 4 of PC1 on the indoor mainboard with a multimeter. If the voltage varies between 0 and 3VDC, the outdoor mainboard is damaged.

Content

Malfunction codesIndoor Unit

Outdoor Unit

Auto

RecoverPower Timer operate operate Heat Cool

Communication fault between the indoor and outdoor units ■ ■ ★ * *

Page 12: Abnormality Solution DB

Cooperation – AIRCON For EuropeFor Europe

Countermeasures for Frequent Malfunctions ( 7-2)

Countermeasure Flow Chart ( CONTINUE ):Countermeasure Flow Chart ( CONTINUE ):

LED1 of indoor mainboard is OFF.

Trouble shooting process:

1. Test the outdoor power supply (230VAC and +310VDC) with a multimeter. If 230VAC is available but 310DC not, the SPDU ( IPDU, HT ) module is damaged, replace it with a new one. If both 230VAC and 310DC are available, go forward to step 2.

2. Measure the voltage across Jumpers 1 and 4 of Terminal CN3 on the outdoor mainboard with a multimeter. If +12DC is not available, the SPDU ( IPDU, HT ) module is damaged, replace it with a new one. If +12VDC is available, go forward to step 3.

3. Within two minutes after the machine is supplied with power and turn on, measure the AC voltage between positions 1 and 3 on the terminal of outdoor unit with a multimeter. If the value varies between 0 and 80 VAC, the outdoor mainboard is damaged, replace it with a new one. If the value is constant at about 30V, the indoor mainboard is damaged, replace it with a new one.

Content

Malfunction codes

Indoor Unit

Outdoor Unit

Auto

Recover

Power Timer operate operate

Heat Cool

Communication fault between the indoor and outdoor units ■ ■ ★ * *

Page 13: Abnormality Solution DB

Cooperation – AIRCON For EuropeFor Europe

Countermeasures for Frequent Malfunctions (7)

Countermeasure Flow Chart :Countermeasure Flow Chart :

Check the status of LED2 on the maindboard of outdoor unit and the running condition of outdoor unit within 3 minutes after startup.

Within 3 minutes after the machine is supplied with power and turned on with the remote controller, the outdoor unit stops shortly after startup, and the compressor will start up again 10 seconds after the machine stops. The above process repeats again and again.

1. The wiring of compressor is incorrect or the connection is poor;

2. The compressor is damaged

CASE1CASE1

At the stopped state, LED2 blinks ( 1Hz ) for several times, and after pause of 2 seconds or so, it blinks for the same times again.

LED2 blinking for 20 times indicates that the compressor might be damaged.

CASE2CASE2

LED2 blinking for 19 times indicates that Module SPDU might be damaged

Content

Malfunction codes

Indoor Unit

Outdoor Unit

Auto

RecoverPower Timer

operateoperate Heat Cool

Anomaly of compressor Running ★ ■ � *

Page 14: Abnormality Solution DB

Cooperation – AIRCON For EuropeFor Europe

Countermeasures for Frequent Malfunctions (8)

Countermeasure Flow Chart :Countermeasure Flow Chart :

Electrify the machine again and turn it on with the remote controller, then measure the temperature at the exhaust temperature sensor of the compressor on the outdoor unit.

If the temperature exceeds 115 ℃shortly after the machine starts up, the cryogen may have been leaked during installation, or there may be leakage in the piping system, or there may be other causes to make the exhaust temperature too high.

CASE1CASE1

Malfunctions occur after running for some time even though the measured temperature is below 115 .℃

Pull out the exhaust sensor and measure its resistance at standard temperatures. If the results deviate much from those in the resistance-temperature table, the sensor is damaged and needs replacing.

CASE2CASE2

Pull out the exhaust sensor and measure its resistance at standard temperatures. If the results do not deviate or deviate a little from those in the resistance-temperature table, the outdoor mainboard is damaged and needs replacing.

CASE1CASE1

CASE2CASE2

Content

Malfunction codes

Indoor Unit

Outdoor Unit

Auto

Recover

Power Timer operate

operate Heat Cool

Overheat protection for exhaust temperature ■ ★ ■ *

Page 15: Abnormality Solution DB

Cooperation – AIRCON For EuropeFor Europe

Countermeasures for Frequent Malfunctions (9)

Countermeasure Flow Chart :Countermeasure Flow Chart :

Electrify the machine again and turn it on with the remote controller, then observe its operate

If malfunctions are reported before or upon the compressor being started up, Module SPDU is damaged and needs replacing.

CASE1CASE1

The compressor is started normally, but malfunctions are reported after it has run for some time.

If the power supply is in order, the system may have been over or under charged with gas, which can be judged through the pressure of the measuring system.

CASE2CASE2

Check the power supply. If the voltage is too low or too high, the machine is not damaged. It is the power supply that needs to be changed or improved.

CASE1CASE1

CASE2CASE2

With this malfunction, LED2 on the outdoor mainboard blinks 3 times at a frequency of 1Hz and an interval of about 2 seconds for 3 times.

Content

Malfunction codes

Indoor Unit

Outdoor Unit

Auto

RecoverPower Timer

operateoperate Heat Cool

AC electricity protection

★ ★ ■ *

Page 16: Abnormality Solution DB

Cooperation – AIRCON For EuropeFor Europe

Countermeasures for Frequent Malfunctions (10)

Countermeasure Flow Chart :Countermeasure Flow Chart :

Electrify the machine again and turn it on with the remote controller, then measure temperature on the module radiator and decide whether it is too high.

If the radiator temperature is too high, Module SPDU might be poorly radiated and need to be recoated with heat conducting paste and reinstalled.

YESYES

With a multimeter, test whether there is diode characteristic between the three terminals U/V/W and the two terminals P/N of Module SPDU.

Test with a multimeter whether the resistance values among Phases U, V and W of compressor are equal and between 1 and 3Ω.

NONO

If there is arc over or break, Module SPDU is damaged and needs replacing.

YESYES

NONO

YESYES

1. Module SPDU is damaged and needs replacing.

2.The shaft of compressor is seized and the compressor needs replacing.

NONO

If there is arc over or break, the compressor is damaged and needs replacing.

Content

Malfunction codes

Indoor Unit

Outdoor Unit

Auto

RecoverPower Timer

operateoperate Heat Cool

DC electricity protection

★ ★ � *

Page 17: Abnormality Solution DB

Cooperation – AIRCON For EuropeFor Europe

Countermeasures for Frequent Malfunctions (11)

Countermeasure Flow Chart :Countermeasure Flow Chart :

Electrify the machine again and turn it on with the remote controller, then observe its operation.

If the wind temperature is below 50 and t℃he malfunction is reported after the machine has run for some time, check whether the sensor or the temperature monitoring circuit of the indoor mainboard is in order. See countermeasures for sensor troubles.

CASE1CASE1

If both the sensor and the temperature monitoring circuit of the indoor mainboard are in order, shoot the trouble as follows:

1. Check whether the indoor unit blows poorly due to blocked filters or poor condition of the fan. If yes, clean the filters or reinstall the fan. If not, go forward to Case 2.

2. Measure the pressure of the system. If the pressure is too high, the system is over charged with gas, otherwise go forward to Case 3.

3. Find other causes to make the temperature of coil pipes on the indoor unit too high and take according measures.

CASE2CASE2

Content

Malfunction codes

Indoor Unit

Outdoor Unit

Auto

RecoverPower Timer

operateoperate Heat Cool

High work-intense protection ★ ★ ★ *

Page 18: Abnormality Solution DB

Cooperation – AIRCON For EuropeFor Europe

Countermeasures for Frequent Malfunctions (12)

Content

Malfunction codes

Indoor Unit

Outdoor Unit

Auto

RecoverPower Timer

operateoperate Heat Cool

EEPROM error ★ � ★ * *

Countermeasure Flow Chart :Countermeasure Flow Chart :

Check whether LED2 on the outdoor unit blinks once at an interval of 2 seconds.

The indoor mainboard is damaged. Replace it with a new one.

NONO

The outdoor mainboard is damaged. Replace it with a new one. If the malfunction still exists, it is possible that the indoor mainboard is also damaged, and needs replacing with a new one.

YESYES

Page 19: Abnormality Solution DB

Cooperation – AIRCON For EuropeFor Europe

Countermeasures for Frequent Malfunctions (13)

Countermeasure Flow Chart :Countermeasure Flow Chart :

Check whether Terminal CN9 for H,CON12 for HS CN8,CN13 for HFU on the indoor mainboard is well inserted.

Pull out and reinsert the terminals.

NONO

Electrify the machine again and turn it on in the Cool state with the remote controller. Measure the voltage between the middle wire and the black side wire of Terminal CN9(COM12 CN8 CN13) on the indoor mainboard

YESYES

Malfunction unsolved

Malfunction unsolved

YESYES

NONO

If there is variation of voltage, the indoor mainboard is damaged and needs replacing

If there is no variation of voltage, the motor of the indoor unit is damaged and needs replacing

Content

Malfunction codes

Indoor Unit

Outdoor Unit

Auto

Recover

Power Timer operate

operate Heat Cool

Indoor fan motor malfunction ■ � ★ *

Page 20: Abnormality Solution DB

Cooperation – AIRCON For EuropeFor Europe

Countermeasures for Other Frequent Malfunctions (14)

Countermeasure Flow Chart :Countermeasure Flow Chart :

With the machine electrified, the remote controller cannot start itWith the machine electrified, the remote controller cannot start it

Open the front cover of the indoor unit and press the emergency button once.

If the air conditioner is started normally, check whether the battery in the remote controller is powerless, whether the remote controller is damaged and whether the signal receiver works well

CASE1CASE1

If there is no response after the emergency button is pressed down, shoot the trouble as follows:

1. Check whether there is voltage of 230VAC between Positions 1 and 2 on the terminal of the indoor unit. If not, check the power supply and the damage of the power cables. If yes, go forward to Step 2.

2. Check the FUSE of the indoor mainboard. If burned out or broken, replace the fuse, or go forward to Step 3.

3. Check with a multimeter whether the voltage between the two ulterior positions on Terminal CN1-2 of the indoor mainboard is 10VAC ~ 14VAC. If no, the transformer needs replacing. If yes, the indoor mainboard might be damaged and needs replacing.

CASE2CASE2

If the remote controller resets itself frequently and the air conditioner cannot receive signals from the controller, the batteries in the remote controller need replacing.

Page 21: Abnormality Solution DB

E5

100UF/16V

C21

103

+5

+5

E2

4.7UF/16V

E1

4.7UF/16V1234

CN12

12345

CN4

C32

104

C13104E6

1UF/16V

R4310K

D101N4148

R3410K

R3310K

R25*20K

R26*3.3K

C27102 C26

102

C24

104

+5

C18102

R21 1K

R22 10K

12

CN10

R32

10K

+5

123

CN14R36 10K

R39

1K+5

+5v

12V

C25104

123

CN15R35 10K

R37

1K+5

123456789 10

11

12

13

14

15

16

IC32003

C34

10412V

1 2 3 4 5 6 7

CN16Á¬½ÓÏßC7-CZ14

RL2JQ1A-12V

Ï·ç»úÇý¶¯ÉÏ·ç»úÇý¶¯

Ï·ç»úÇý¶¯ÉÏ·ç»úÇý¶¯

P/G-OUT0'P/G-OUT1'

12V

RL2-DRIVE'

RL

2-D

RIV

E'

Àë×Ó¼¯³¾

123456789

10111213141516

IC2

2003

ZJ1

+5

R20100

R141k

BUZ

+5

R38

10K

Ò£¿Ø½ÓÊÕ

·äÃùÆ÷

ÊÒÍâͨѶ·¢ËÍÊÒÍâͨѶ½ÓÊÕ

Àë×Ó¼¯³¾

LED2LED1

¼¯ÖпØÖÆÊä³ö¼¯ÖпØÖƽÓÊÕ

Àë

×Ó

¼¯

³¾

DOWN

R445.1K

12

CN3

B 2B-PH-K°×

+5V

+5V

Ò£¿Ø½ÓÊÕCOMLED1LED2

µ½Ò£¿Ø½ÓÊÕ°å

PULSE UP

PULSE DOWN

´Å¿ª¹Ø

¶Ì·ÅÅÕë

¹¦ÄÜÑ¡Ôñ°å

Sensor

IC8

TLP 3526

123

CN8

C191.2UF

12V

R45

680

IC9

TLP 3526

123

CN13

C301.2UFC28

0.01uF/275V

12V

R55120/1W

R48

680

P/G-OUT1'

P/G-OUT0'

CBB61

CBB61 L

L

N

FAN DOWN

FAN UP

1

CN6220VN

1

CN7

1

CN2

µçÔ´ÒýÈëN¶Ë

L

R1910K

C9104

R23

10K

Q7C9013

R24

10K

+5

COM

ÉÏ´¹Ö±°Ú·ç²½½øµç»ú

Ï´¹Ö±°Ú·ç²½½øµç»ú

ÏÂÁ÷·ç»ú

ÉÏÁ÷·ç»ú

C1104

C2104

R1 5.1k

R25.1k

Ï·ç»ú·´À¡

ÉÏ·ç»ú·´À¡

ÊÒÍâͨѶ½ÓÊÕ

ÊÒÍâͨѶ·¢ËÍ

C3102

C4102

Ï·ç»ú·´À¡

ÉÏ·ç»ú·´À¡

Q89013

Q6

9013

¹¦ÄÜÑ¡Ôñ

´Å¿ª¹Ø

´Å¿ª¹Ø

Ó¦¼±/×Ô¼ì/Ëõʱ

Ó¦¼±¿ª¹Ø

ÊÒÎÂÄÚÅÌ

CX1

32.768KHZR16

330K

R1310M

30P

30P

OSC1OSC2

RST

RST

ÉÏBÉÏCÉÏD

·äÃ

ùÆ

÷

345

678 1

2

IC10

24C02

SDASCL

R8 10K

R7 10K

C14104

+5

SDASCL

C5102

R30

10K

R281K

R27

10K

R29

10K

Q22SC2412

Q3

2SC2412

Ô¶³ÌͨÐÅ

12

CN11

R31

10K

+12V

¼¯ÖÐ

R424.7K

R40

27

¼¯ÖпØÖÆÊä³ö

¼¯ÖпØÖÆÊäÈë

C8102

IC5TLP371

R9330K

R112.2K

C12103

D71N4007

D61N4007

LED1

GREEN

R12

2W/6.8K

1

CN1

Á¬½ÓÏßC2-CZ9

R10

330

R62.2K

+5

+5

IC6

P521

N

ÊÒÍâ»úͨѶ

1

2 4

56

1

2

3

4

Q12SC2412

R17

10kC11102

R4710k

R183k

R41

1K

+5

Q4

2SC2412

C17

103/50v

C29104/50v

1

CN5

220VL

FUSE1

T3.15A

C6474/275V

ZE1S14K350/550NR-14D

1

2

3

4

12VIC7

7805+5

T1TRAN1-3

E7

100U/16VE9

1000U/35VC10104

C20104

220V-L

220V-N

D1

D3 D4

D2

D94007

E8470U/25V

C22104

+5V

Q5

2SC2412

R15

10k

ÏÂAÏÂB

ÏÂA

ÏÂB

ÏÂC

ÏÂCÏÂD

ÏÂD

PTA4/ATD6PTA3/ATD5

PTA1/ATD3PTA2/ATD438

394041

34 PTC4/ATD9

PTA5/ATD7

ÏÞλ¿ª¹Ø

ÏÞλ¿ª¹Ø

PTA0/ATD2SDASCL

PTB0/SDA0PTB1/SCL0

1718

16212223

PTD3/KBI3PTD4/KBI4PTD5/KBI5PTD6/KBI6

PTC1/PWM125

2 PTC5/ATD10

OSC1OSC2

910

15 RST

26

272931

PTC2/PWM2

PTA7/T1CH1PTA6/T1CH0PTB5/T2CH1

PTB4/T2CH032

1920PTB2/SDA1/TxD

PTB3/SCL1/RxD

¹ýÁã¼ì²â

IRQ113

6

7

PTC3/ATD8

PTD0/KBI0

14 PTD2/KBI2

PTC0/PWM0/CD24

35

12

28

33

PTD1/KBI1

PTD7/KBI7

OPIN1/ATD0

R4

4K7

R3

10K

1234567

CN23

B7B-PH-K£¨ºì£©

VDD8

11 VSS

VDDA1

C7

104

34 VSSAM

VREFHVREFL

373642 VSSA

E3

100UF/16V

C15

104

+5

IC1

+5V

ÊÒÎÂ

Å̹Ü

30PTB6/IRQ2

MC68HC908SR12

»úÐÍÑ¡Ôñ/ÉÏA

+51

2

3

SW1

JSS1247

R46

4K7

CGMXFC5

R5810K

+5

C310.47uF

C16

102

R491K

1

CN9

6

4

C23

0.01uF/275V

R54120/1W

N6

4

C36

C39

12V

R50 22K

ÊÒÎÂÄÚÅÌ

LX1

Ò£¿Ø½ÓÊÕ

R7

10K

R9100

LED2LED3

R8100

R5220

Q29013

R35.1K

SW1

+5

+5

R151K

R162.2K

R174.3K

SW

3

SW

4

SW

2

¹¦ÄÜÑ¡Ôñ°åÔ Àíͼ

12

CN2

Ò£¿Ø½ÓÊÕ¼°ÏÔÊ¾Ô Àíͼ

FUNCTION

REMOTE

HEALTH

TIM

E

RU

N

R4

10K

R6220

Q19012

POWER

LED1

LED1LED2

Ó¦¼±¿ª¹Ø

Ò£¿Ø½ÓÊÕCOM

¾«Ãܵç×è

SW2:µ¥/Ë«»úÔËÐÐÑ¡ÔñSW3:A/BÂë½ÓÊÕÑ¡ÔñSW4:¹¦ÄÜ´ý¶¨£¬²»º¸£¬R16²»º¸

YE

LLO

W

GR

EE

N

1234567

CN1

GN

D

+5

V

IR

HS0038A2MPD1

E1

4.7U/50VR110K

+5

R2100

The figure on the right shows the electric diagram for the outdoor unit ofHFU-18/22H03/R2(DB)

Page 22: Abnormality Solution DB

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16 17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32P04/INT24

P05/INT25

P06/INT26

P61

P07/INT27

P60

/RST

X0

X1

VSS

P37/BZ/PPG

P36/INT12

P35/INT11

P34/T0/INT10

P33/EC

C P32/UI/SI

P31/UO/SO

P30/UCK/SCK

P50/PWM

P70

P71

P72

P40/AN0

P41/AN1

P42/AN2

P43/AN3

P00/-INT20/AN4

P01/-INT21/AN5

P02/-INT22/AN6

P03/-INT23/AN7

VCC

FLZ

BUZ1

R2

1K

R1220

+12V

R410K

R5 10K

¸ºÀë×Ó

»»Ð·ç

ÊÒÍâͨѶÊä³ö

¹ýÁã¼ì²â

Ëõʱ/×Ô¼ì

Ó¦¼±¿ª¹Ø

R1210KCN10

TEST

+5V

SW1

+5V

+5V

C4 104

OSC1

8M

123

CN8R7 10K

R6

2.2K C6

102

+5V

PG·´À¡

Ò£¿Ø½ÓÊÕ

12345678 9

10111213141516

12345

CN6

+12V

ABCD

123

SW2R10 2.2K

+5VR9 2.2K

×Ô¶¯ÔËÐÐ

»úÐÍÑ¡Ôñ

C10 104

C7

102

12345

678

+5VC11 104

IC2

IC3

IC1+5V

TIMERRUN

GND

+5V

REC

1234

CN4+5V

R133.3K

R1420K

C12102

C13

102

ROOMPIPE

R1510K

·ç»úÊä³öÃæ°åÑ¡Ôñ

µ¼°åÑ¡Ôñ

ÊÒÍâͨѶÊäÈë

A

B

C

D

·äÃùÆ÷

TXO

TXI

FLZPGO

C1 102

C2103

C5103

C9103

R32 1K

E8

4.7U

R1910K

R1810KR20

1K

Q39013

R1710K

E4

470uF/16V

C15104

Vout3

GN

D2

Vin1

IC47805

FUSE1

T3.15A 250VACC20

1uF/275VAC

1

2

3

4

IN4007

ZE1S14K350

E3

1000uF/35V

C14

104

+5V+12VD5

IN4007

CN14AC-L

AC-N

D1D2

D3 D4

+5V

RL1

12345

CN9

FLZ

+12V

FLZ

FRED

FWHITE

C18103/275V

C19

1.2uF/450VAC

AC-L

C

PGO

AC-N

1

2 3

4

1

2

34

5

6

TLP421

TLP371

C17104

R28

330K

R272.2K

LED1

D7

IN4007

D6

IN4007

R29

2W6.8K

R262.2K

R25

10K

C16

102

+5V

ÊÒÍâÍ Ñ¶ÊäÈë

+5V

R30

330Q2

9013

ÊÒÍâÍ Ñ¶Êä³ö

R24120/1W

PGÇý¶¯

+12VIC5

TLP3526

R21

680

IC8

IC7

R31

1K

C21104

C22

104

123

SW3R39 2.2K

1234567

CN2-1

µçÔ´G

µçÔ´R

R34470

R36470

R37

100

R38

10K

R351K

C23

102

12

CN5

COM

220-N

123

CN1-1

123

CN1-2

CN11

CN12

E74.7U

+5

R11

2.2K

The figure on the right shows the electric diagram for the outdoor unit ofHSU-18/22H03/R2(DB)

Page 23: Abnormality Solution DB

1 2 3 4 5 6 7 8

A

B

C

D

87654321

D

C

B

A

R54

2W/ 78K

R1710k

C12102

C13104

C16102

12345CN3

13 2

XT18M

下摆步进电机

左摆步进 右摆步进

集中输入

集中输出

PG反馈

R1510k

R3810K

IC9

TLP521

R184.7k

R41 1K

R42 10K+5

C5 102

R30

33K

R28 1K

R27 10K

+5

R29 10K

N22SC2412

N12SC2412

远程通信

12CN9

123

CN7

+5

风机反馈C43103

+5VR50 51K

R14 1K

+5

IC10

TLP3526

+12V

R57680

PG输出

345

678 1

2

I C2

24C02

+5

E6 4.7UF/50V

E7 4.7UF/50V

1234

CN8

R44 1K

R45 1K

R35 3.3K 1%

R34 20K 1%

+5

PG输出

室温盘管

C2104

R3910K

C10102 C9

102

N4

2SC2412

SDASCL

1 2 3 4 5 6 7 89

10111213141516

I C42003

12345

CN4

1 2 3 4 5 6 7 89

10111213141516

I C52003

1 2 3 4 5 6 7 89

10111213141516

I C32003

BADCBA

C

CD

B

A

CD

BA

上摆步进电机

+12

+12

+12

+12

C4104

+5

C6

103/

50V

+5

C18104/ 50V

+5

( )白

R22 22K

C37104

R654.7k

C17

103/ 50v

负离子

RL3G5N- 1A

+12

负离子

R20 22KR19 4.7K

+5

H系列大分体灯板显示原理图

蜂鸣器

1234

CN6

( )网络 红

R36 1K

R37 10K +5V

R8 10K

+5VR7 10K

C14104

BUZ1

BEEP- PKM13EPY- 4002

N52SC2412

R11

10K

R49100

R9 4.7K

R11M

R78

10K

R41KP8

2SB1182

+12V

换新风

R31

10K

+12V

C41102

D2 RLS4148

R2 10K

R3 1K

C1102

应急开关

+5V

02 I RQ

07

08 PTF4/ TBCH0

PTF3/ TBCH3

过零检测

48

49

PTH1/ KBD3

PTH1/ KBD4

03 RST 复位脚

21 VSS GND

GNDAVSS/ VRE45

60 PTC0

PTF710

13 PTE0/ TXD 网络输出

56 VSSA GND

14 PTE1/ RXD 网络输入

PTE2/ TACH015

25 PTG2/ KBD2

PTE3/ TACH11617 PTE4/ SS181920

PTE5/ MI SOPTE6/ MOSIPTE7/ SPSCK

换新风负离子

PTC401

12345678910 CN5

26 PA0 A上摆27 PA1 B上摆28 PA2 C上摆29 PA3 D上摆30 PA4 A下摆31 PA5 B下摆32 PA6 C下摆33 PA7 D下摆38 PTB4 D左摆

( )单、冷暖

(大、小机型)

12

CN15

门开关

R33 10K

R32 1K

+5v

C21102

50 PTD4 门开关

34PTB0/ ATD0

35PTB1/ ATD1

/缩时 自检

394041424346

PTB5/ ATD5PTD6/ ATD6PTB7/ ATD7PTD0PTD1PTD2

C左摆B左摆A左摆D右摆C右摆B右摆

47PTD3A右摆

VDDAREF电源 44

0605PTF1/ TACH3

PTF2/ TBCH2EE数据EE时钟

57 CGMXFC

5455

VDDAVREFH

电源

59

58

OSC1

OSC2晶振

晶振

51

健康灯定时灯 PTD6/ TACLK

5253626364

PTD7PTC2/ MCLKPTC3PTC5PTF0/ TACH2 04遥控接收

制热灯除湿灯制冷灯运转灯

22

3637PTB3/ ATD3

PTB2/ ATD2

VDD电源

内盘管内环温

09 NC 空 61

23

24

PTC1

PTG1/ KBD1

PTG0/ KBD0

编制: 审核:

CON18 CON19、

1

CON14( )红

FLZ对接线

集中

C11

104

C19104

C20104

MC68HC908AB32

+12v

R12 1K R13

1K

N7S9013

N6S90131

23

CN12

+12v

R2522K

R694.7K

5v

11

12PTF5

PTF6

A紫外线控制C紫外线控制

紫外线控制

E11UF/ 16V

R4822K

C7

104/

50V

C3103

C42104/50V

C29104/ 50v

R53 1K

SW1

应急开关

220V

-L

220V

-N

R594.7K

1

CON15( )白

FLZ对接线

A12VC

R66 27

C44103/50V

C45103/50V

C47102/50VC46102/50VC25102/50VC27102/50VC26102/50V

C34102/50V

E12100u/ 16v

R63 330R67 330R70 330R71 330R72 330 64

63

62

53

52

51

E13100u/ 25v

1

CON21

250/AMP-63824-1

FUSE1

T3.15A

C40104/275V

LX1

开关电源

ZE1S14K350

1

2

3

4

C48104/ 50V

I C8 Q817C

L1 20UH12VI C7

7805

+5T1

TRAN1-3

C33 222/ 300VAC

E4220U/ 16V

E101000U/25V

E922U/ 35V

D6

UF4007

D8 UF302

R601.3 2W欧姆

R614.7K

R55560

D11 1N4007

C28104

R52 3.6 /3W欧R51

47K/ 2W

R58 27C30102

C31

472/ 1KV

C35104

D7

10V/ 0.5W

E822U/ 450V

220V-L

220V-N

E11470U/ 25V

C36104

I C14

STD2NBP60

AD

J1

FB2

CS

3

GN

D4

DR

V5

Vcc

6

NC

7

HV

8

I C6 NCP1200P60

R7515

R6239K

D9

D13 D14

D12

SC

D

R7610K

E14

100U

/25V

R56 330

R1610k

+5

R21 4.7K

SW3

I R

HEALTH

HEATDRYCOOLRUNTIME

123456789

CN5- 1

B9B- PH- K(红)

PTD5

123

CON12

C39 2U

F 45

0V

内风机

220V-N220V-L

R5120 1WC24

0.01UF 275V

N3

2SC2412

R231K

换新风

换新风

1

CON25( )白

DJR对接线

E15100U/25V

R734.7K

二氧化碳

一氧化碳

R47 22K

R77 22K

R26

4.7K5v

SW2

5v

4

515253626364

R10 10K

R40 10K+5V

R24

10K12

ZJ1

+5

/自检 缩时

R46

1K C15102

R6

10K+5V

D3 1N4007

1

CN14

R81

330K 1/ 4W

R82

330 1/4W

C22102

R85 2.2K 1/ 4W

R8710K 1/4W

+5

R8610K 1/4W

R80

2.2k 1/ 4WIC15

TLP521

1

N

C49103/ 50V

LED1

GREEN

+5

N62SC2412

I C16TLP371

+51

2 4

56

1

23

4

D41N4007

+5

通信收

通信发

通信收通信发负离子

R84 6.8K

+5V

D15

15V/ 0.5W

L2

125UH

R902

10KR901

10K

R43 22K

The figure on the right shows the electric diagram for the outdoor unit ofHSU-18/22HS03/R2(DB)

Page 24: Abnormality Solution DB

The figure on the right shows the electric diagram for the outdoor unit of DC products with LCD Series.

1 2 3 4 5 6 7 8

A

B

C

D

87654321

D

C

B

A

P331

P342

P353

P364

P375

P409

P4110

P4211

P4312

P4413

P4514

P4615

P4716

TEST20

RESET24

XIN18

XOUT19

VSS17

VAREF6

P2223

P2025

P00/INT026

P0127

P0228

P0329

P0430

P0531

P0632

P0733

P1534

P1435

P1336

P1237

P1138

P1039

P3040

P3141

VDD21

AVSS8

AVDD7

P2122

P3242

IC1

TMP86PM46N

ÍÂ Æø

±¸Ó à Π¶È

Ñ ¹» ú ¿ÇÌåΠ¶È

ÉÏÉý /ÏÂ ½µ

·§ /·ç» ú

» ·¾³

³ý ˪

Îü Æø

·ç» ú µ÷ËÙ

·çËÙ ·´À ¡

Ç¿Ö ÆÖ ÆÀä

Ç¿Ö ÆÖ ÆÈÈ

SERIA L

SS/TEST

±¸Ó Ã

±¸Ó Ã

TO ÊÒÄ Ú » ú

FRO MÊÒ ÄÚ » ú

±¸Ó Ã

FRO MÄ £ ¿é

TO Ä £ ¿é

Å ò Õ Í·§ D

Å ò Õ Í·§ C

Å ò Õ Í·§ B

Å ò Õ Í·§ A

ËÄ Í¨

¸ß /µÍ·ç

·ç» ú ¿ª¹Ø

Ñ õ °É

PTC

±¸Ó à ¼ÌµçÆ÷

SCL

SD A /ERR_ LED

C17

30P

C18

30P

X1

16.000MHz

R13 10K

1

2

3IC9

PST600D

+5V

1234567

GND8

COM9

10111213141516

CO

M

IC2

ULN2003

123456

CN2

XC25-06WS

A

+12V

BCD

CD1 25V/220U

1 2 3 4 CN3B4B-XH-A

+1

2V

RX

TX

GN

D

Q1

S9013

R1560

C1

1000P

R222K

+5V

R31K

C2

1000P

R11

10K

+12V

R1610K

+5V

IC5

TLP371

IC6

TLP521

C31000P

R12

10K

+5V

R36 390

C4

1000P

R25

330

D1

1N

40

07

R41K

R30 15K

R29 15K

R28 15K

D2 1N4007

R31

22K/2W

D3

1N4007

FU1 275V-25A

CD3

22uF/250V

R33

220K

R34

220K

R35

220K

D4

1N4007

C7275V-103

L1T10022

C13

275-474

C15275-472

C16275-472

ZE1S14K350

SA1RA-362M

1

CN6

KET6.3

1

CN7

KET6.3

220VAC-L

220VAC-N

L3

059

L2 T10022

C14

275-474

ZE2

S14K350

C12

275-474PTC1

PTC

1CN9

KET6.3

1CN5

KET6.3

RL1G4A-1A

RL2PCH-112D2H/G5S-1

RL3OJE-SS-112DM

RL4OJE-SS-112DM

123 CN14

B2P3-VHËÄÍ

C9275V-103

R53100/1W

123

CN15B2P3-VH

µ¥ËÙ·ç»ú(±¸ÓÃ)

12345

CN18

B3P5-VHC29

CBB61-1.5UF-500V

HLCOM

+15VB

1234567

GND8

COM910111213141516

CO

M

IC3

ULN2003

RL6OJE-SS-112DM

123 CN17

B2P3-VH

C11275V-103

R55100/1W

±¸ÓÃ

1 2 3

CN19B3B-XH-A(˦)

1 2 3

CN20B3B-XH-A(°×)

1 2 3

CN22B3B-XH-A(Ȯ)

1 2

CN21B2B-XH-A(ÂÌ)

TaTeTdTs

CD950V/4.7U

CD1050V/4.7U

CD1150V/4.7U

CD1250V/4.7U

+5V

R7 1KR6 1KR5 1K

R8 1KR9 1K

1 2 3

CN23B3B-XH-A(ºì)

±¸ÓÃ

CD1350V/4.7U

R15 10KR14 10K

+5V

CJ1 TJC8-02A

+5V

12

CN11B2B-XH-A

R40

2K

R412K

R392K

C23

103

+5V

R43

2K

R442K

R422K

C24

103

+5V

R38100K

R37100K

C22

103

R10

1K

+5V

R2110K

12

CN12B2B-XH-A

12

CN13B2B-XH-A

A01

A12

A23

GND4

SDA5

SCL6

WP7

VCC8

IC12

AT24C02

R23

10K

R24

10K

R22 10K

C21 104+5V

ALARMSL-342VR

R47 330

+5V

CD1

40

0V

/68

0U

CD2

40

0V

/68

0U

CD3

40

0V

/68

0U

1

CN3

KET6.3

1

CN4

KET6.3

CD2

25V/220U

C30 27

5-1

04

D5

RS1J

C8

27

5V

-10

3

D6RS1J

D8

41

48

C25

103

CD15

25

V-1

0U

F

CD1650V-1UF

R58 1

R59 1

Q22SC2712R60

5.1K

ZD1

12

V/0

.5W

R611.5K R62

27

CD8

25V-470UF

+15VB

D7

RS1J

CD17

25V-220UF

+15VA

9

10

6

7

1

34

5

T1

E22012

GND1

BUS+

DRAINVCC

Softst

FBIsenseGND

NC1

2 3 8

6

547IC10ICE2A265

C20

104

R5

61

MR

57

1M

R46 160K

R45 160K

+310V

0V

123456CN24B6P6-VH

BUS+

GND1

+3

10

V

0V

µç

Ô´

µ÷

ËÙ

ËÙ

¶È

·´À

¡

IC8

TLP521

IC7

TLP521

R64

330

ZD25.1V/0.5W

R63

330

GND1

+15VA

R65330

+5VR661K

ZD3

9V/0.5W

R671K

R682K CD14

50V/4.7UC26

103

R691K

7805

IC117805

CD1916V-100UF

+5V

CD1825V-220UF

+12V

SW1H=5

SW2H=5

SW3H=5

SW4H=5

CJ2 TJC8-02A

CJ3 TJC8-02A

C19

104

R4820K

R4947K

R5020K

R5120K

R5220K

J16

10MM

+12VJ7

10MM

1 5 V

1 5 V

1 5 V

SS

SERIAL

COOL

HEAT

¿ÇÌå±£»¤ ѹÁ¦¿ª¹Ø

UP

DOWN

FA

FAN

J4210MM

R7010K

1 2 3 4 5

RP2 10K*4+5V

R1

22

0K

R2

22

0K

µçÈݰ岿·Ö

CP1 1000PF*8

LED1SL-342VR

R17110K-2W

1 2 3 4 5 6

RP2 10K*5

1

CN10

KET6.3

1

CN10'

KET6.3

´óµØ

ÄÚ»úÍ Ñ¶

(ºÚ)

(°×)

(ºì)

»ðÏß³ö(»Ò)

ÁãÏß³ö

* J2310MM

SPDUÄ£¿éÍ Ñ¶

»·Î³ý˪ÍÂÆøÎüÆø

*R1810K

Ö±Á÷Íâ·ç»ú

PMV

Á½ËÙ·ç»ú

Page 25: Abnormality Solution DB

。The figure on the right shows the wiring diagram for the indoor unit of DC products HSU-22HS03/R2 ( DB ) .

C0N15

C0N14C0N21

CN17

CN16

CON12 CN7 CN8

Y/G

EMERGENCY SWI TCH

FAN MOTOR

CN3CN4

LOUVER MOTOR

LOUVER MOTOR

CN5-1

DI SPLAY RECEI VER BOARD

CN9

CN5LOUVER MOTOR

LOUVER MOTOR

TO OUTDOOR UNIT

NOTES:THE PARTS OF DOTTED ARE OPTI ONAL

Y/ G: YELLOW / GREEN

R: RED

B: BLACK

W: WHI TE

1 2 3

CN11

EMI FI LTER

Page 26: Abnormality Solution DB

。The figure on the right shows the wiring diagram for the indoor unit of DC products HSU-22H03/R2 ( DB) .

THE UNIT WITHOUT THE HEALTH FUNCTION HAS NOT

Page 27: Abnormality Solution DB

。The figure on the right shows the wiring diagram for the indoor unit of DC products HSU-18HS03/R2 ( DB ) .

Y/ G: YELLOW / GREEN

NOTES:THE PARTS OF DOTTED ARE OPTI ONAL

CN11

LOUVER MOTOR

LOUVER MOTOR

POWER SUPPLYTO OUTDOOR UNIT

1 32BR BL

BR: BLOWN

R: REDBL: BLUE

B: BLACK

W: WHI TE

C0N14C0N21

CON12

CN16

C0N15

CN17

CN3

CN7

CN5

CN5-1

DI SPLAY RECEI VER BOARD

CN4

CN8

CN9

LOUVER MOTOR

FAN MOTORY/G

EMERGENCY SWI TCH

LOUVER MOTOR

Page 28: Abnormality Solution DB

。The figure on the right shows the wiring diagram for the indoor unit of DC products HFU-18H03/R2 ( DB) .

Page 29: Abnormality Solution DB

The figure below shows the wiring diagram for the outdoor unit of DC products 22 Series

Page 30: Abnormality Solution DB

The figure below shows the wiring diagram for the outdoor unit of DC products 18 Series

Page 31: Abnormality Solution DB

THANKS!