AMS
TIGHT SHUT-OFF VALVE
V
T
ACV 2 - WAY
ACV 3 - WAY
CAP - PIPE
CHECK VALVE
COMBINATION BALANCING, FLOW MEASURING &
FLOAT & THERMOSTATIC TRAP
ISOLATION VALVE
GLOBE VALVE
LOCKSHIELD GATE VALVE
MANUAL AIR VENT
OS&Y GATE VALVE
PETCOCK FOR GAUGE CONNECTION
PIPE ANCHOR
PIPE GUIDE
PLUG VALVE
PRESSURE GAUGE
PRESSURE REDUCING VALVE
PRESSURE RELIEF VALVE
STRAINER
TAKE - OFF FROM BOTTOM OF PIPE
TAKE - OFF FROM TOP OF PIPE
THERMOMETER
THERMOMETER WELL
THERMOSTATIC TRAP
UNION
DESCRIPTIONSYMBOL
EXISTING SUPPLY PIPING TO REMAIN
EXISTING RETURN PIPING TO REMAIN
NEW SUPPLY PIPING
NEW RETURN PIPING
PIPE DOWN
PIPE UP
DIFFERENTIAL PRESSURE SENSORDPS
INVERTED BUCKET TRAP
PIPING LEGEND
REDUCER - CONCENTRIC
REDUCER - ECCENTRIC
10'-0" FL1.2 GPM
RADIATION I.D. ( TYPE A, 10'-0" FINNED LENGTH, BALANCED TO 1.2 GPM) WITH DAMPERA
10'-0" FL/D
1.2 GPM
A RADIATION I.D. ( TYPE A, 10'-0" FINNED LENGTH, BALANCED TO 1.2 GPM) WITHOUT DAMPER
BUTTERFLY VALVE
FD (3 HR) FIRE DAMPER (3 HOUR RATED)
FIRE DAMPER (1 1/2 HOUR RATED)
BD
V
ACOUSTICALLY LINED DUCT
BACKDRAFT DAMPER
DUCT SECTION - SUPPLY/OUTDOOR AIR
DUCT SECTION - RETURN AIR
DUCT TURNING VANES
FLEXIBLE DUCT
LOUVER
MOTORIZED DAMPER
PRESSURE RELIEF DAMPER
RETURN OR EXHAUST AIR
SMOKE DAMPER
STRAINER
SUPPLY OR OUTSIDE AIR
VOLUME DAMPER
SPIRAL DUCT DIAMETER
CB COUNTERBALANCED DAMPER
DESCRIPTIONSYMBOL
S
PRD
M
F
AIRFLOW MEASURING STATION
DUCT MOUNTED SMOKE DETECTORSD
EXISTING DUCTWORK TO REMAIN
NEW DUCTWORK
DUCT SECTION - EXHAUST AIR
STATIC PRESSURE SENSORSPS
Ø
FIRE AND SMOKE DAMPER (1 1/2 HOUR RATED)F/S
DUCTWORK LEGEND
S2 4
400
SUPPLY DIFFUSER ( TYPE 2 )
400 CFM EA
DIFFUSER DESCRIPTION
QUANTITY
( SEE REG., GRILLES & DIFF SCHEDULE )
S (SUPPLY) R (RETURN)
E (EXHAUST) T (TRANSFER)
H
HS
HUMIDISTAT
HUMIDITY SENSOR
TEMPERATURE SENSOR
THERMOSTAT
THERMOSTAT COOLING
THERMOSTAT HEATING
THERMOSTAT - NIGHT
THERMOSTAT - HEATING/COOLING
T
TS
TC
H
N
H/C
T
T
T
DESCRIPTIONSYMBOL
CONTROLS LEGEND
A
M10.1SECTION I.D. ( SECTION A SHOWN ON DWG. M10.1)
DESCRIPTIONSYMBOL
EXISTING EQUIPMENT TO REMAIN
NEW EQUIPMENT
COMPLETELY REMOVE EQUIPMENT, DUCTWORK, OR PIPING
GENERIC LEGEND
CONNECT NEW TO EXISTING
Graphic ScaleGraphic Scale
Graphic ScaleGraphic Scale
Graphic ScaleGraphic Scale
Key Plan
Harriman Project No.
PA / PE:
Drawn By:Harriman Associates
c
Proj North
Revision DescriptionRev Date
May 17, 2021
GORHAM, MAINE
20478
M00-1
DWS
ASG
LEGEND & GENERALNOTES
2021
UNIVERSITY OFSOUTHERN MAINEHILL GYMNASIUM
ATHLETIC TRAININGRENOVATIONS
ABBREV DESCRIPTION
IN INCHES
LAT LEAVING AIR TEMPERATURE
LPCRLOW PRESSURE CONDENSATERETURN (LESS THAN 15 PSI)
LPSLOW PRESSURE STEAM(LESS THAN15 PSI)
LRA LOCKED ROTOR AMPS
LSGV LOCK & SHIELD GATE VALVE
LWT LEAVING WATER TEMPERATURE
M MOTORIZED DAMPER
MAX MAXIMUM
MBH 1000 BRITISH THERMAL UNITS
MCA MINIMUM CIRCUIT AMPS
MIN MINIMUM
MOPDMAXIMUM OVERCURRENTPROTECTIVE DEVICE
MPCRMEDIUM PRESSURE CONDENSATERETURN(16-30 PSIG)
MPSMEDIUM PRESSURE STEAM (16-30PSIG)
NA NOT APPLICABLE
NC NOISE CRITERIA
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NTS NOT TO SCALE
OA OUTSIDE AIR
OC ON CENTER
OED OPEN END DUCT
OS&YOUTSIDE SCREW & YOKE GATEVALVE
PD PRESSURE DROP
PRD PRESSURE RELIEF DAMPER
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PSIG POUNDS PER SQUARE INCH GAUGE
RET RETURN
RL REFRIGERANT LIQUID
RLA RATED LOAD AMPERES
RPM REVOLUTIONS PER MINUTE
RS REFRIGERANT SUCTION
S SMOKE DAMPER
SP STATIC PRESSURE
SS STAINLESS STEEL
SUP SUPPLY
TEMP TEMPERATURE
TT THERMOSTATIC TRAP
TYP TYPICAL
V VOLUME DAMPER
VFD VARIABLE FREQUENCY DRIVE
W/ WITH
W/O WITHOUT
WC WATER COLUMN
WG WATER GAUGE
WMS WELDED WIRE MESH SCREEN
WPD WATER PRESSURE DROP
Z ZONE DAMPER
PREFIX OF X EXISTING
ABBREV DESCRIPTIONACV AUTOMATIC CONTROL VALVE
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
ALD ACOUSTICAL LINED DUCT
AMS AIRFLOW MEASURING STATION
APD AIR PRESSURE DROP
ATCAUTOMATIC TEMPERATURECONTROL
B BAROMETRIC DAMPER
BD BACKDRAFT DAMPER
BHP BRAKE HORSEPOWER
BPD BYPASS DAMPER
BTU BRITISH THERMAL UNITS
CBDCOUNTERBALANCED BACKDRAFTDAMPER
CFM CUBIC FEET PER MINUTE
CHWR CHILLED WATER RETURN
CHWS CHILLED WATER SUPPLY
CO CLEANOUT
CTE CONNECT TO EXISTING
CWR CONDENSER WATER RETURN
CWS CONDENSER WATER SUPPLY
DCW DOMESTIC COLD WATER
DEG.F DEGREES FAHRENHEIT
DHW DOMESTIC HOT WATER
DIA DIAMETER
DN DOWN
DTR DUAL TEMPERATURE RETURN
DTS DUAL TEMPERATURE SUPPLY
EAT ENTERING AIR TEMPERATURE
ESP EXTERNAL STATIC PRESSURE
EWT ENTERING WATER TEMPERATURE
EXG EXISTING
EXH EXHAUST
F&T FLOAT & THERMOSTATIC TRAP
F/SFIRE AND SMOKE COMBINATIONDAMPER
FC FLEXIBLE CONNECTION
FD FIRE DAMPER
FL FINNED LENGTH OF RADIATION
FM FLOW METER
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
FPF FINS PER FOOT
FPI FINS PER/INCH
FPM FEET PER MINUTE
FT FEET
FT-HD FEET OF HEAD
FT-WG FEET WATER GAUGE
FTR FIN TUBE RADIATOR
GAL GALLONS
GPM GALLONS PER MINUTE
HP HORSEPOWER
HPCRHIGH PRESSURE CONDENSATERETURN (OVER 30 PSIG)
HPSHIGH PRESSURE STEAM (OVER30PSIG)
HRR HEAT RECOVERY RETURN
HRS HEAT RECOVERY SUPPLY
HWR HOT WATER RETURN
HWS HOT WATER SUPPLY
GENERAL NOTES1 VISIT THE BUILDING SITE PRIOR TO BIDDING TO BECOME FAMILIAR WITH EXISTING CONDITIONS, AND TO TAKE
MEASUREMENTS AS NECESSARY FOR COMPLETION OF THE WORK ASSOCIATED WITH THE DESIGN INTENT OFTHE CONTRACT DOCUMENTS.
2 COORDINATE WORK OF MECHANICAL SUBCONTRACTOR WITH WORK OF OTHER TRADES.
3 DUCTWORK, PIPING AND EQUIPMENT ARE INDICATED DIAGRAMMATICALLY. FIELD-VERIFY LOCATIONS.
4 PRIOR TO FABRICATING DUCTWORK, COORDINATE WITH OTHER TRADES TO ENSURE THAT THE DUCTWORKCAN BE INSTALLED WITH THE INDICATED SIZES AND LOCATIONS.FIELD-VERIFY EXISTING DUCT SIZES ANDCONDITIONS.SUBMIT ANY DISCREPANCIES OR PROPOSED CHANGES.
5 REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR LOCATIONS OF CEILING DIFFUSERS ANDREGISTERS.PROVIDE VOLUME DAMPERS SO THAT EVERY REGISTER, GRILLE AND DIFFUSER (SUPPLY, RETURN,AND EXHAUST) CAN BE INDIVIDUALLY BALANCED.
6 VERIFY INSTALLATION OF EXISTING VOLUME DAMPERS AT EACH BRANCH IN EXISTING SUPPLY DUCT. PROVIDEADDITIONAL VOLUME DAMPERS WHERE REQUIRED.
7 DUCT ELBOWS SHALL BE LONG-RADIUS TYPE (THROAT RADIUS EQUAL TO OR GREATER THAN DUCT WIDTH INTHE PLANE OF THE TURN) WHEREVER SPACE ALLOWS. IF SPACE IS NOT ADEQUATE, PROVIDE MITEREDELBOWS WITH TURNING VANES.
8 PROVIDE 16 GAUGE SINGLE-THICKNESS TURNING VANES AT MITERED DUCT ELBOWS. VANE EDGES (LEADINGAND TRAILING) SHALL BE TANGENTIAL TO AIRFLOW.
9 FLEXIBLE DUCT LENGTHS SHALL NOT EXCEED 5'-0"
10 PAINT DUCTWORK VISIBLE THRU CEILING OPENINGS, DUCT OPENINGS, AND REGISTERS, GRILLES, ANDDIFFUSERS WITH BLACK PAINT IN ACCORDANCE WITH DIVISION 09 SECTION "PAINTING."
11 MOUNT THERMOSTATS AND TEMPERATURE AND HUMIDITY SENSORS AT 48 INCHES AFF TO TOP OF ITEM.PROVIDE ELECTRICAL WALL BOX ATTACHED TO FRAMING.
12 WHERE THERMOSTATS/TEMPERATURE SENSORS ARE LOCATED NEAR LIGHT SWITCHES, INSTALL SO THATLIGHT SWITCHES ARE NEARER TO THE DOOR JAMBS. THE INTENT IS TO LOCATE THERMOSTATS/ TEMPERATURESENSORS SO THEY WILL NOT INTERFERE WITH ACCESSIBILITY OF LIGHT SWITCHES.
13 PIPING INDICATED IN OUTSIDE WALLS SHALL BE RUN ON THE WARM SIDE OF BUILDING INSULATION AND VAPORBARRIER. BUILDING INSULATION BEHIND SUCH PIPING SHALL BE CONTINUOUS, WITHOUT JOINTS OR GAPS.
14 PIPING SHALL BE CONCEALED EXCEPT IN MECHANICAL ROOMS AND AS INDICATED. WHERE PIPES DROP INBLOCK WALLS, PROVIDE 1/2" THICK INSULATION MINIMUM.
15 SEAL DUCTWORK AND PIPING THRU MECHANICAL ROOM FLOORS AND PARTITIONS, AND THRU FIRE-RATEDASSEMBLIES, WITH FIRESTOP MATERIAL AS SPECIFIED.
16 PROVIDE ALL REQUIRED PENETRATIONS IN RATED ASSEMBLIES, INCLUDING BUT LIMITED TO WALLS ANDFLOORS WITH A UL APPROVED FIRESTOPPING ASSEMBLY INCLUDING LISTING LABEL OF PENETRATION AFTERPASSING THROUGH UTILITIES.
CONSTRUCTION DOCUMENTS
DEMOLITION NOTES1 DURING DEMOLITION PROPERLY CAP AND PROTECT ALL PIPING & DUCTWORK THAT WILL REMAIN IN
OPERATION
2 WHERE EXISTING INSULATION TO REMAIN IS DAMAGED BY THE REQUIREMENTS OF WORK, REPLACE ANYDAMAGED INSULATION IN KIND
3 MECHANICAL CONTRACTOR SHALL REFER TO THE SPECIFICATIONS FOR DISTRIBUTION OF RESPONSIBILITYAMONGST CONTRACTORS FOR SPECIFIC PORTIONS OF CUTTING AND PATCHING WORK. PLUMBINGCONTRACTOR SHALL COORDINATE ALL CUTTING AND PATCHING WORK WITH ALL OTHER CONTRACTORSINVOLVED AS DEFINED IN THE SPECIFICATIONS
4 LOCATION OF EXISTING PIPING & DUCTWORK AS SHOWN ON DRAWINGS IS APPROXIMATE
5 COMPLETELY REMOVE ALL EQUIPMENT AS INDICATED & OR MISCELLANEOUS ARTICLES IN THEIR ENTIRETYINCLUDING AUXILLARY EQUIPMENT, PIPING, WIRING & CONDUIT
6 INCLUDE ALL DEMOLITION OF SYSTEMS AND COMPONENTS WHERE SYSTEMS SHALL BE REPLACED BY NEWWORK. REFER TO THE DRAWINGS & SPECIFICATIONS FOR SCOPE OF NEW & RECONNECTED WORK. THEINTENT OF THIS REQUIREMENT IS TO HAVE THE CONTRACTOR DISCONNECT, DEMOLISH & REMOVE ALLEXPOSED & CONCEALED WORK WHERE BEING REPLACED OR CONNECTED TO THE PROPOSED LAYOUTS
7 COORDINATE ELECTRICAL POWER DISCONNECTION PRIOR TO DEMOLITION WITH ELECTRICAL CONTRACTOR
8 ALL PIPING & DUCTWORK TO REMAIN SHALL HAVE ENDS TERMINATED IN A NEAT MANNER READY FORCONNECTION OF NEW WORK. ALL EXPOSED ENDS OF PIPING SHALL BE CAPPED
9 EXISTING PIPING NOT TO BE REUSED, NOT SUPPLYING ANY EQUIPMENT AND NOT SPECIFICALLY NOTED ORSHOWN ON DRAWINGS TO BE ABANDONED, SHALL BE COMPLETELY REMOVED
10 CONTRACTOR SHALL CLEAN UP, REMOVE AND DISPOSE OF ALL DEBRIS AND DISCARDED ITEMS UPONCOMPLETION OF CONSTRUCTION TO BE READY FOR A NEW OCCUPANCY CONDITION
11 DEMOLISH & COMPLETLY REMOVE EXISTING CONDITIONS DESIGNATED BY A HEAVY DASHED LINE UNLESSNOTED OTHERWISE. REFER TO LEGEND AND DEMOLITION PLANS FOR SCOPE OF WORK
HA HB HC HD HE HF HG
H1
H2
H3
AH
A17
A18
A19
D001
D001
D002
EXISTING UNIT HEATER
EXISTING FINTUBE
EXISTING BASEBOARD
EXISTING BASEBOARD
Graphic ScaleGraphic Scale
Graphic ScaleGraphic Scale
Graphic Scale
0 4' 8' 12'
1/8" = 1'-0"
Key Plan
Harriman Project No.
PA / PE:
Drawn By:Harriman Associates
c
Proj North
Revision DescriptionRev Date
May 17, 2021
GORHAM, MAINE
20478
M05-1
DWS
ASG
FIRST FLOORDEMOLITION DUCTWORK
2021
UNIVERSITY OFSOUTHERN MAINEHILL GYMNASIUM
ATHLETIC TRAININGRENOVATIONS
CONSTRUCTION DOCUMENTS
DEMO KEY NOTESCODE DESCRIPTION
D001 COMPLETELY REMOVE EXISTING EXHAUST DUCTWORK AND EXHAUST FAN;EXISTING SOFFIT EXHAUST GRILLE AND WALL PENETRATION TO BE REUSED FORNEW DUCTWORK AS SHOWN ON M
D002 COMPLETELY REMOVE EXHAUST FAN AND ASSOCIATED CONTROLS
D003 COMPLETELY REMOVE FINTUBE, FLOOR MOUNTED CABINET UNIT HEATERS ANDALL ASSOCIATED CONTROLS; DEMO AND CAP PIPING ABOVE CEILING
D004 COMPLETELY REMOVE CEILING MOUNTED UNIT HEATER AND ASSOCIATEDCONTROLS; 1" HWS/R PIPING TO BE REUSED FOR FUTURE CONNECTION TO NEWFLOOR MOUNTED RADIANT PANELS AS SHOWN ON M20-1
HA HB HC HD HE HF HG
H1
H2
H3
AG
AH
A15
A16
A17
A18
A19
D003D003
D003
D004
Graphic ScaleGraphic Scale
Graphic ScaleGraphic Scale
Graphic Scale
0 4' 8' 12'
1/8" = 1'-0"
Key Plan
Harriman Project No.
PA / PE:
Drawn By:Harriman Associates
c
Proj North
Revision DescriptionRev Date
May 17, 2021
GORHAM, MAINE
20478
M06-1
DWS
ASG
FIRST FLOORDEMOLITION PIPING
2021
UNIVERSITY OFSOUTHERN MAINEHILL GYMNASIUM
ATHLETIC TRAININGRENOVATIONS
CONSTRUCTION DOCUMENTS
DEMO KEY NOTESCODE DESCRIPTION
D001 COMPLETELY REMOVE EXISTING EXHAUST DUCTWORK AND EXHAUST FAN;EXISTING SOFFIT EXHAUST GRILLE AND WALL PENETRATION TO BE REUSED FORNEW DUCTWORK AS SHOWN ON M
D002 COMPLETELY REMOVE EXHAUST FAN AND ASSOCIATED CONTROLS
D003 COMPLETELY REMOVE FINTUBE, FLOOR MOUNTED CABINET UNIT HEATERS ANDALL ASSOCIATED CONTROLS; DEMO AND CAP PIPING ABOVE CEILING
D004 COMPLETELY REMOVE CEILING MOUNTED UNIT HEATER AND ASSOCIATEDCONTROLS; 1" HWS/R PIPING TO BE REUSED FOR FUTURE CONNECTION TO NEWFLOOR MOUNTED RADIANT PANELS AS SHOWN ON M20-1
V
V
V
V
V
T
T
T
M
M
V
V
V
V
V
V
V
V
ERV-1
AHU-1
20"x10" SU
P
6"ø S
UP
6"ø S
UP
24"x10" SU
P
10"ø S
UP
24"x10" RET
6"ø R
ET
10"ø R
ET
12"ø R
ET
12"ø R
ET
24"x10" RET
12"ø S
UP
S2
100
1
R2
400
1S3
400
1
E1
70
1S1
S1
400
400
R1
1075
1
M003
M004
M006
M006
M006
M002
M005
M001
M007
BALANCE OA TO 25 CFM (TYP OF 3)
10"ø S
UP
10"ø S
UP
20"x10" SU
P
10'-0" M
IN36"x12" PLENUM SIZED TO MATCH LOUVER
DIMENSIONS
4"ø S
UP
6"ø S
UP
6"ø S
UP
IU-3
IU-2
IU-1
S2
100
1
Graphic ScaleGraphic Scale
Graphic ScaleGraphic Scale
Graphic Scale
0 4' 8' 12'
1/8" = 1'-0"
Key Plan
Harriman Project No.
PA / PE:
Drawn By:Harriman Associates
c
Proj North
Revision DescriptionRev Date
May 17, 2021
GORHAM, MAINE
20478
M10-1
DWS
ASG
FIRST FLOOR DUCTWORK
2021
UNIVERSITY OFSOUTHERN MAINEHILL GYMNASIUM
ATHLETIC TRAININGRENOVATIONS
CONSTRUCTION DOCUMENTS
KEY NOTESCODE DESCRIPTION
M001 AHU-1 TO BE SUPPORTED BY BEAM FLANGECLAMPS ON TOP BEAM FLANGE ; REFER TOMANUFACTURER'S DOCUMENTS FORINSTALLATION REQUIREMENTS AND CLEARANCES
M002 ERV-1 TO BE INSTALLED ON FLOOR MOUNTEDEQUIPMENT STAND; INSTALL MANUFACTUREROA/RA MOD AS NECESSARY; ALL OA DUCT TO BEDOUBLE WRAPPED WITH 1.5" FIBERGLASSINSULATION A MINIMUM 4' FROM EXTERIOR WALLPLENUM; ALL FA DUCT TO BE WRAPPED WITH 1.5"FIBERGLASS INSULATION; REFER TOMANUFACTURER'S DOCUMENTS FOR EQUIPMENTINSTALLATION AND CLEARANCE REQUIREMENTS
M003 RE-USE EXISTING 36"X12" EXHAUST REGISTER ANDWALL SLEEVE FOR NEW 12" ERV EXHAUST DUCT;DEMO EXISTING AUTOMATIC DAMPER ASNECESSARY
M004 INSTALL NEW WALL SLEEVE AND INTAKE LOUVER10' FROM EXHAUST OUTLET; INTAKE LOUVER TOBE INSTALLED IN SOFFIT; INTAKE LOUVER TO BE36x10 GREENHECK ESD-435 OR EQUIVALENT
M005 ERV-1 12" EA/FA DUCT TAKEOFFS TO BE A MINIMUM5' APART; FA DUCT TO BE INSULATED WITH 1.5"FIBERGLASS WRAP; BALANCE EA AND FA TO AHU-1TO 585 CFM
M006 NEW 4-WAY CEILING CASSETTES TO BECONNECTED WITH 4" SA FROM AHU-1; EACHCASSETTE TO BE CONTROLLED BY WALLMOUNTED THERMOSTAT AND PROVIDED WITH ANINTEGRALL RELAY TO ENERGIZE BASEBOARDZONE CONTROL VALVE AS NECESSARY DURINGDEFROST MODE
M007 INSTALL OU-1 ON CONCRETE PAD; REFER TOMANUFACTURER'S DOCUMENTS FORINSTALLATION REQUIREMENTS AND CLEARANCES
T
T
T
HA HB HC HD HE HF HG
H1
H2
H3
AH
A16
A17
A18
A19
A10' - 0" FL1.0 GPM
A10' - 0" FL1.0 GPM
A10' - 0" FL1.0 GPM
AHU-1
RL- 3/8"
RS- 5/8"
RL-
3/8"
RS-1 1/4"
RL-
3/8"
RS-3/4"
RL- 3/8"
RS- 5/8"
RS- 5/8"
RL- 3/8"
RL-
3/8"
RS-5/8"
RS-5/8"
RL-
3/8"
HWS- 1 1
/2"
HWR- 1 1
/2"
HW
R-1 1/4"H
WS-1 1/4"
HW
R-1"H
WS-1"
HW
R-1 1/4"
HW
S-1 1/4"
HWR- 3/4
"
HWR- 3/4
"
HW
R-1 1/4"
HW
S-1"
ERV-1
INSTALL NEW 1/2" RADIANT ZONE CONTROL VALVE; CONTROL VALVE TO BE INTERLOCKED WITH CEILING CASSETTE RELAY
(TYP OF 3)
M007
M001
M002
M006
M006
M006
HW
R-3/4"
HW
R-3/4"
HWR- 3/4
"
5/8" RS / 3/8 RLPIPING DOWN TO AHU-1
OU-1
Graphic ScaleGraphic Scale
Graphic ScaleGraphic Scale
Graphic Scale
0 4' 8' 12'
1/8" = 1'-0"
Key Plan
Harriman Project No.
PA / PE:
Drawn By:Harriman Associates
c
Proj North
Revision DescriptionRev Date
May 17, 2021
GORHAM, MAINE
20478
M20-1
DWS
ASG
FIRST FLOOR PIPING
2021
UNIVERSITY OFSOUTHERN MAINEHILL GYMNASIUM
ATHLETIC TRAININGRENOVATIONS
CONSTRUCTION DOCUMENTS
KEY NOTESCODE DESCRIPTION
M001 AHU-1 TO BE SUPPORTED BY BEAM FLANGECLAMPS ON TOP BEAM FLANGE ; REFER TOMANUFACTURER'S DOCUMENTS FORINSTALLATION REQUIREMENTS AND CLEARANCES
M002 ERV-1 TO BE INSTALLED ON FLOOR MOUNTEDEQUIPMENT STAND; INSTALL MANUFACTUREROA/RA MOD AS NECESSARY; ALL OA DUCT TO BEDOUBLE WRAPPED WITH 1.5" FIBERGLASSINSULATION A MINIMUM 4' FROM EXTERIOR WALLPLENUM; ALL FA DUCT TO BE WRAPPED WITH 1.5"FIBERGLASS INSULATION; REFER TOMANUFACTURER'S DOCUMENTS FOR EQUIPMENTINSTALLATION AND CLEARANCE REQUIREMENTS
M003 RE-USE EXISTING 36"X12" EXHAUST REGISTER ANDWALL SLEEVE FOR NEW 12" ERV EXHAUST DUCT;DEMO EXISTING AUTOMATIC DAMPER ASNECESSARY
M004 INSTALL NEW WALL SLEEVE AND INTAKE LOUVER10' FROM EXHAUST OUTLET; INTAKE LOUVER TOBE INSTALLED IN SOFFIT; INTAKE LOUVER TO BE36x10 GREENHECK ESD-435 OR EQUIVALENT
M005 ERV-1 12" EA/FA DUCT TAKEOFFS TO BE A MINIMUM5' APART; FA DUCT TO BE INSULATED WITH 1.5"FIBERGLASS WRAP; BALANCE EA AND FA TO AHU-1TO 585 CFM
M006 NEW 4-WAY CEILING CASSETTES TO BECONNECTED WITH 4" SA FROM AHU-1; EACHCASSETTE TO BE CONTROLLED BY WALLMOUNTED THERMOSTAT AND PROVIDED WITH ANINTEGRALL RELAY TO ENERGIZE BASEBOARDZONE CONTROL VALVE AS NECESSARY DURINGDEFROST MODE
M007 INSTALL OU-1 ON CONCRETE PAD; REFER TOMANUFACTURER'S DOCUMENTS FORINSTALLATION REQUIREMENTS AND CLEARANCES
NOTE
ORIENT CONDENSING UNIT ON STANDSUCH THAT CONDENSER FAN WILLBLOW AIR TOWARD THE NEARBY BUILDING WALL AS RECOMMENDED BY THE MANUFACTURER
METAL SLEEVE TYPICAL ATPENETRATIONS. VERIFY SIZE & NUMBER. PROVIDE WATER-TIGHT SEAL TO FLASHING. PROVIDETWO (2) PIECE FIELD FABRICATED FLASHING WITH STAINLESS STEELCLAMPING RING OVER METAL SLEEVE
INSULATE VAPOR, LIQUID, ANDCONDENSATE DRAIN PIPING.PIPING EXPOSED INDOORS AND OUTDOORS: PROVIDE FULL PVCJACKET AND FITTINGS, WITH SEAMS SEALED AND LAPPEDDOWNWARD TO DRAIN.
PROVIDE SUPPORTS AND PENETRATIONS ASREQUIRED FOR PIPING AND ELECTRICAL
DHP INDOOR UNIT(EVAPORATOR FAN-COIL)
COND., PITCHTO DRAIN
FLOOR
BUILDING EXTERIORWALL
CONCRETE PAD
GRADE
BI-FLOW LIQUID-LINESOLENOID VALVE WITHIN2 FEET OF UNIT, ARROWPOINTING TOWARD UNIT
16-INCH-HIGH SNOWSTAND, FASTEN TO PAD
AND TO UNIT
LIQUID-LINE MOISTURE-AND LIQUID INDICATINGSIGHT GLASS
GALVANIZED STEEL PIPE STAND,FASTENED TO CONCRETE PAD
CEILING
FILTER-DRIER FURNISHEDWITH HEAT PUMP
PROVIDE TEST VALVES
HEATING ACCURATER DEVICEFURNISHED WITH HEAT PUMP
COOLING ACCURATERDEVICE INSIDE UNIT
DHP OUTDOORCONDENSING UNIT
VAPOR LINE
LIQUID LINE
INVERTED TRAP INVAPOR LINE.
TOP SHALL BE ABOVE TOP OF
INDOOR UNIT
PENETRATE CEILINGCLOSE TO UNIT, WITHESCUTCHEONS
SPACE BETWEENUNIT AND WALL
FOR INTAKE DUCT
60" MAX
1"
NOTES:1. REINFORCEMENT MAY BE USED FOR ATTACHMENT IF IT QUALIFIES FOR BOTH DUTIES.2. ATTACH HANGERS TO TOP CHORD OF JOISTS.3. DO NOT EXCEED ALLOWABLE LOAD LIMITS.
STRAP OR ANGLE
ROD
SIZE BOLT(S) FOR LOAD
STRAP
24" DIA MAX36" DIA MAX
10" DIA MAX
BAND OF SAME SIZEAS HANGER STRAP
ROD
HANGERS MUST NOTDEFORM DUCT SHAPEBAND ONE HALF-ROUND MAY BEUSED IF DUCT SHAPE IS MAINTAINED
LOCKNUTS(TYPICAL)
ANGLES
SCREWS
UNLESS FOOT OF STRAPIS PLACED UNDER ABOTTOM REINFORCEMENT
SCREWS MAY BE OMITTEDIF HANGER LOOPS
HANGER STRAPS
HANGER
SECUREWIRE
LOAD RATEDFASTENERS
HANGER RODS,WIRES, ORSTRAPS
ALTERNATE ROD LOCATION(VERIFY UPPER TRAPEZELOAD CAPACITY)
TRAPEZE HANGERSSTRAP HANGERS
PLENUM(INSULATE AS
FOR DUCTWORK)
SURFACE MOUNTEDAIR DEVICE
DRAWBANDS ON BOTH INNERCORE AND OUTER VAPOR BARRIERFINISH WITH TAPE TO SEAL
PLENUM(INSULATE AS
FOR DUCTWORK)2 x INLET
DUCT HEIGHT
LAY-IN CEILING
ANGLES TOSUPPORT PLENUM ONCEILING GRID
MAINDUCT
LAY-IN AIRDEVICE
DRAWBANDS ON BOTH INNERCORE AND OUTER VAPOR BARRIERFINISH WITH TAPE TO SEAL
LAY-IN CEILING
STRAIGHT LENGTH OFFLEXIBLE DUCT 4'-0"LONG MAX.
SEE AIR DEVICEDETAILS BELOW FOR CONNECTION TO MAIN DUCT
LAY-IN AIRDEVICE
LAY-IN CEILING
MAINDUCT
SPIN FITTING FOR ROUND,45° TAP FOR RECTANGULAR
SURFACE MOUNTED CEILING AIR DEVICE
ROUND-NECK DIFFUSER CONNECTION
LAY-IN AIR DEVICE UNDER DUCT
2 x INLETDUCT HEIGHT
SPIN FITTING FOR ROUND,45° TAP FOR RECTANGULAR
STRAIGHT LENGTH OFFLEXIBLE DUCT 4'-0"LONG MAX.
SURFACE MOUNTEDAIR DEVICE
DRAWBANDS ON BOTH INNERCORE AND OUTER VAPOR BARRIERFINISH WITH TAPE TO SEAL
LAY-IN CEILING
ANGLES TOSUPPORT PLENUM ONCEILING GRID
MAINDUCT
SPIN FITTING FOR ROUND,45° TAP FOR RECTANGULAR
STRAIGHT LENGTH OFFLEXIBLE DUCT 4'-0"LONG MAX.
ANGLES TOSUPPORT PLENUM ONCEILING GRID
OR
OR
VOLUME DAMPERS:1) PROVIDE STAND-OFF BRACKETS ON INSULATED DUCTS.
2) INSULATE UNDER BRACKETS, SEAL VAPOR BARRIER TO BRACKETS
3) PROVIDE LOCKING, INDICATING QUADRANTS.
MAIN DUCT
CLOSE OPENINGS AT
CORNERS
BRANCH DUCT
45° ENTRY
BRANCH TAKE-OFF
STAND-OFF MOUNTING
BRACKET
OPPOSED BLADE BALANCING DAMPER
PROVIDE CONTINUOUS INSULATION BETWEEN
BRACKET AND DUCT WHILE LEAVING DAMPER HANDLE
EXPOSED.
1/4 OF DUCT WIDTH, MINIMUM OF 4".
HANG SURVEYOR'S TAPE FROM VOLUME DAMPER WHERE CONCEALED ABOVE CEILINGS SO THAT BALANCER CAN LOCATE DAMPER LOCATIONS. TAPE IS NOT REQUIRED WHERE DUCTS ARE EXPOSED.
DIRECTION OF AIR FLOW RETURN/EXHAUST)
DIRECTION OF AIR FLOW (SUPPLY)
PLAN VIEW
ISOMETRIC VIEW
.
CLOSE OPENINGAT CORNERS
MAIN DUCT
BRANCHDUCT
HANG SURVEYOR'S TAPE FROMVOLUME DAMPERS SO THAT BALANCER CAN LOCATE DAMPER LOCATIONS
DUCT TAKE-OFF FROMTOP OF DUCT
45° TAKE-OFF
DIRECTION OFFLOW (RETURN)
DIRECTION OFFLOW (SUPPLY)
VOLUME DAMPER
OPPOSED BLADEBALANCING DAMPER
BRANCHTAKE-OFF
PROVIDE CONTINUOUSINSULATION BETWEEN
BRACKET AND DUCT
INSULATED SUPPLY AND RETURN DUCTWORK SHALL BE INSTALLED WITHSTAND-OFF MOUNTING BRACKETS FOR VOLUME/BALANCING DAMPEROPERATORS. ALLOW CLEARANCE BETWEEN DUCT AND OPERATOR OF NOTLESS THAN INSULATION THICKNESS.
ISOMETRIC VIEW
PLAN VIEW
STAND-OFF MOUNTING BRACKET
1/2" PLUGGED TEEFOR DRAIN
PITCH UP
PITCH UP
COMBINATION BALANCING, FLOW MEASURING, & TIGHT SHUT-OFF VALVE
SHUT-OFF VALVE
UNION
STRAINER
ACV
V
V
AIR VENT
R =2WO
R =W
VANES, SINGLE THICKNESS, FULL 2-IN. RADIUS, 90° TURN, MINIMUM 16-GAUGE, FILLING ENTIRE CROSS SECTION
USE MITERED ONLY WHERE SPACE IS TOO TIGHT FORRADIUS, OR WHERE INDICATED ON DRAWINGS.
RADIUSES MITERED
W
W
I
1 1/2"
SHEET METAL DUCTWORK
WALL
OUTER EDGE OF DUCT OR OUTER LIMIT OF DUCT INSULATION
1" SPACE BETWEEN DUCT & SLEEVE
NON COMBUSTIBLE GLASS FIBER INSULATION USED FOR BACKING BETWEEN DUCT AND SLEEVE
20 GAUGE CLOSURE COLLARS SEE SPECIFICATION SECTION 233300 FOR
ATTACHMENT REQUIREMENTS FOR DIFFERENT WALL AND FLOOR PENETRATIONS
20 GAUGE GALVANIZED SHEET METAL DUCT SLEEVE SHALL BE FABRICATED WITH LONGITUDINAL PITTSBURGH LOCK. EXPOSED ENDS OF DUCT SHALL BE HEMMED
SLEEVE SHALL BE FLUSH WITH WALL OR FLOOR UNLESS OTHERWISE NOTED
Graphic ScaleGraphic Scale
Graphic ScaleGraphic Scale
Graphic ScaleGraphic Scale
Key Plan
Harriman Project No.
PA / PE:
Drawn By:Harriman Associates
c
Proj North
Revision DescriptionRev Date
May 17, 2021
GORHAM, MAINE
20478
M50-1
DWS
ASG
DETAILS
2021
UNIVERSITY OFSOUTHERN MAINEHILL GYMNASIUM
ATHLETIC TRAININGRENOVATIONS
CONSTRUCTION DOCUMENTS
SCALE: 1/8" = 1'-0"1
DUCTLESS HEAT PUMP UNIT
SCALE: 1" = 10'-0"2
LOWER HANGER ATTACHMENT
SCALE: 1/8" = 1'-0"7
CEILING AIR DEVICE
SCALE: 1" = 10'-0"5
SIDE BRANCH TAKE-OFF
SCALE: 1" = 10'-0"4
TOP BRANCH TAKE-OFF
SCALE: 1/8" = 1'-0"3
HOT WATER RADIATIONSCALE: 1 1/2" = 1'-0"
6DUCT ELBOW
SCALE: 1/8" = 1'-0"8
DUCT SLEEVE
Graphic ScaleGraphic Scale
Graphic ScaleGraphic Scale
Graphic ScaleGraphic Scale
Key Plan
Harriman Project No.
PA / PE:
Drawn By:Harriman Associates
c
Proj North
Revision DescriptionRev Date
May 17, 2021
GORHAM, MAINE
20478
M60-1
DWS
ASG
SCHEDULES
2021
UNIVERSITY OFSOUTHERN MAINEHILL GYMNASIUM
ATHLETIC TRAININGRENOVATIONS
CONSTRUCTION DOCUMENTS
AIR HANDLER SCHEDULE
TAG MANUFACTURER MODEL SERVICE
TOTALCAPACITY(BTU/HR) Airflow
MIN.OUTDOOR
AIR(CFM)
WEIGHT(LBS)
FAN SECTION FILTERS
FAN MOTOR
DIMENSIONS (IN.) EFF'YTYPEE.S.P
(IN.WG) VOLTSAHU-1 Mitsubishi Electric TPVFYP048 SEE PLANS 48000 1400 585 172 FORWARD
CURVED.80 208 20x24x1 MERV 8
DUCTLESS AIR CONDITIONER SCHEDULE
TAG MANUFACTURER MODEL SERVICE
COOLINGCAPACITY
(MBH)
INDOOR UNIT PIPING SIZES ELECTRIC
NOTES
AIR FLOWHI/MED/LOW
(CFM)NOISE
(HI SPEED dB(A))HEIGHT
(IN)WIDTH
(IN)DEPTH
(IN)SUCTION
(IN)LIQUID
(IN)
MAXLENGTH
(FT) VOLTS PHASEMCA
(AMPS)MAX FUSE
(AMPS)IU-1 Mitsubishi Electric TPLFYP024 SEE PLANS 24000 812 32 dB 0' - 11 3/4" 2' - 9 3/32" 2' - 9 3/32" 5/8" 3/8" 100' - 0" 208 1 0.54 15
IU-2 Mitsubishi Electric TPLFYP024 SEE PLANS 24000 812 32 dB 0' - 11 3/4" 2' - 9 3/32" 2' - 9 3/32" 5/8" 3/8" 100' - 0" 208 1 0.54 15
IU-3 Mitsubishi Electric TPLFYP024 SEE PLANS 24000 812 32 dB 0' - 11 3/4" 2' - 9 3/32" 2' - 9 3/32" 5/8" 3/8" 100' - 0" 208 1 0.54 15
FINTUBE RADIATION SCHEDULE
TAG MANUFACTURER MODELPIPE SIZE
(IN.)CAPACITY
BTU/FT ROWS
ENCLOSUREDIMENSIONS
W x H (IN.) NOTESA STERLING PR2-03 3/4" 994 3 8-5/8"x 10'
ENERGY RECOVERY VENTILATOR SCHEDULE
TAG MFR MODEL
FA AIRFLOW(CFM)
EXT SP(IN) HP
EA AIRFLOW(CFM)
EXT SP(IN) HP
OUTDOOR AIR INDOOR AIR SUPPLY AIR ELECTRICAL FILTER
WEIGHT(LBS) NOTES
SUMMERDB
(DEG.F)
SUMMERWB
(DEG.F)
WINTERDB
(DEG.F)
WINTERWB
(DEG.F)
SUMMERDB
(DEG.F)
SUMMERWB(%)
WINTERDB
(DEG.F)
WINTERWB(%)
SUMMERDB
(DEG.F)
SUMMERWB
(DEG.F)
WINTERDB
(DEG.F)
WINTERWB
(DEG.F) VOLTS PHASE MCA EFF'Y QTYERV-1 RenewAire HE1XINH 585 1.0 0.5 655 1 0.5 87 °F 71 °F 0 °F -2 °F 75 °F 62.5 70 °F 54.4 78 °F 66 °F 54 °F 44 °F 208 V 1 10.8 MERV 13 2 275.00 lb/ft³
REGISTERS, GRILLES & DIFFUSERS SCHEDULE
TAG MANUFACTURER MODEL TYPENOMINAL FACE
SIZE (IN)NECK
SIZE (IN) MAX NC MAX SP DAMPER FINISH BORDERE1 PRICE INDUSTRIES 530 SERIES LOUVERED 8 x 8 6" 20 0.09 in-wg NONE BAKED ENAMEL
WHITESURFACE
MOUNT
R1 PRICE INDUSTRIES 530 SERIES LOUVERED 24 x 24 22 x 22 20 0.09 in-wg NONE BAKED ENAMELWHITE
TYPE 3 LAY IN
R2 PRICE INDUSTRIES 530 SERIES LOUVERED 12 x 12 12 x 12 20 0.09 in-wg NONE BAKED ENAMELWHITE
SURFACEMOUNT
S1 PRICE INDUSTRIES SCD CEILING DIFFUSER 24 x 24 10" 20 0.09 in-wg NONE BAKED ENAMELWHITE
TYPE 3 LAY IN
S2 PRICE INDUSTRIES SCD CEILING DIFFUSER 24 x 24 6" 20 0.09 in-wg NONE BAKED ENAMELWHITE
TYPE 3 LAY IN
S3 PRICE INDUSTRIES 520 SERIES LOUVEREDSUPPLY
12 x 12 10" 20 0.09 in-wg NONE BAKED ENAMELWHITE
SURFACEMOUNT
VRV SCHEDULE
TAG MANUFACTURER MODEL SERVICE
TOTALHEATING
CAPACITY(MBH)
TOTALCOOLINGCAPACITY
(MBH)DIMENSIONS(W x H x D) in
MOUNTINGTYPE
ELECTRICAL
NOTESMOPD PHASE VOLTSOU-1 Mitsubishi Electric TUHYE1203 SEE PLANS 135,000 120,000 48-7/8" x 71-5/8" x 29-3/16"
"PAD 60 3 208 V
REF:A1
--
NOTES
1.
2.
3.
5.
6.
7.
LIGHTING FIXTURE NOTES
4.
8. ALL LIGHT FIXTURES SHALL MEET UTILITY COMPANY INCENTIVE
REQUIREMENTS.INCENTIVE FORMS SHALL BE COMPLETED BY
ELECTRICAL CONTRACTOR. ALL INCENTIVES SHALL BE PAID
DIRECTLY TO OWNER.
THE ELECTRICAL CONTRACTOR SHALL FURNISH ALL
LIGHTING FIXTURES COMPLETE WITH MOUNTING
ACCESSORIES TO MEET JOB REQUIREMENTS.
ALL FIXTURES SHALL BE SUPPORTED FROM THE BUILDING
STRUCTURE, INDEPENDENT OF HUNG CEILINGS.
THE ELECTRICAL CONTRACTOR SHALL VERIFY FIXTURE
MOUNTING AND LOCATION AGAINST PLANS, ELEVATIONS,
AND DETAIL DRAWINGS. EXACT LOCATION OF ALL
FIXTURES SHALL BE CONFIRMED WITH THE ARCHITECT
PRIOR TO ROUGHING IN.
FIXTURE LETTERS SHOWN ON A CONTINUOUS ROW OF
FIXTURES SHALL BE TYPICAL FOR THAT ROW UNLESS
OTHERWISE NOTED.
9. OCCUPANCY SENSOR SHALL CONTROL THE LIGHTING CIRCUIT
SERVING THE ROOM AHEAD OF SWITCH CONTROLS. PROVIDE
POWER PACKS AS REQUIRED FOR A FULLY FUNCTIONING SYSTEM.
1.
2.
3.
4.
5.
6.
7.
8.
UNLESS OTHERWISE NOTED, WIRING SHALL BE 2#12 AWG
CONDUCTORS & #12 GND. HOMERUNS FED FROM 20A, SINGLE
POLE CIRCUITS IN EXCESS OF 100 FEET SHALL BE #10 AWG
UNLESS INDICATED OTHERWISE. INSULATION TYPE SHALL BE
THHN/TWHN, 75 DEG. C, AND 600V CLASS UNLESS SPECIFIED
OTHERWISE.
FLEXIBLE CONNECTIONS TO MOTORS SHALL BE
FLEXIBLE LIQUID TIGHT CONDUIT.
9.
10.
11.
12.
13.
14.
15.
16.
UNLESS OTHERWISE NOTED, ALL WIRING SHALL
BE 600V, COPPER WITH THHN-THWN INSULATION.
WHERE IT IS INDICATED THAT EXISTING WIRING
IS TO BE REUSED, THE ELECTRICAL SUBCONTRACTOR
SHALL VERIFY THAT THE INTEGRITY OF THE INSULATION
IS ADEQUATE FOR REUSE. ALL SUSPECT WIRING SHALL
BE REPLACED BY THE SUBCONTRACTOR.
GENERAL NOTES GENERAL NOTES (CON'T)
ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH
THE LATEST EDITION OF NFPA 70, NATIONAL ELECTRICAL
CODE (NEC), OSHA REGULATIONS, AS WELL AS APPLICABLE
REGULATIONS OF THE PERTINENT FEDERAL, STATE, COUNTY,
AND CITY AGENCIES. PROVIDE MATERIALS AND EQUIPMENT
THAT COMPLY WITH ANSI, IEEE, IES, AND NEMA STANDARDS.
WHERE APPLICABLE, PROVIDE ONLY MATERIALS THAT ARE
U.L. LISTED AND LABELED.
THE ELECTRICAL SUBCONTRACTOR SHALL VISIT THE SITE
AND INSPECT EXISTING CONDITIONS, SERVICES, CONDUITS,
SPATIAL CONSIDERATIONS AND ALL OTHER PERTINENT
CONDITIONS TO FULLY FAMILIARIZE HIMSELF WITH
CONDITIONS TO BE ENCOUNTERED IN THE PERFORMANCE
OF THIS WORK. THE ELECTRICAL SUBCONTRACTOR SHALL
COORDINATE THIS WORK WITH THE GENERAL CONTRACTOR
DURING CONSTRUCTION. FAILURE TO DO SO WILL NOT
RELIEVE THE ELECTRICAL SUBCONTRACTOR OF THE
RESPONSIBILITY FOR FULL COMPLETION OF THE WORK
IN ACCORDANCE WITH APPLICABLE DRAWINGS AND
SPECIFICATIONS. VERIFY EXISTING SYSTEMS THAT WILL BE
UTILIZED FOR CONNECTION TO THE NEW SYSTEM. IF
DISCREPANCIES EXIST BETWEEN THE CONTRACT DRAWINGS
AND THE ACTUAL EXISTING CONDITIONS, THE ELECTRICAL
SUBCONTRACTOR SHALL NOTIFY THE ENGINEER/OWNER
PRIOR TO PROCEEDING WITH THE INSTALLATION.
ALL MOTOR SAFETY SWITCHES, DISCONNECTS AND MOTOR
STARTERS THAT ARE NOT PROVIDED BY OTHER DIVISIONS,
SHALL BE PROVIDED BY DIVISION 26, UNLESS SPECIFICALLY
NOTED OTHERWISE.
ALL PENETRATIONS THROUGH FIRE-RATED FLOORS, WALLS
AND PARTITIONS SHALL BE SEALED WITH UL APPROVED
FIRE SEALANT MATERIAL TO MAINTAIN THE RATING
OF THE SEPARATION.
WHERE MATERIAL IS CALLED OUT IN THE LEGEND BY
MANUFACTURER, TYPE OR CATALOG NUMBER, SUCH
DESIGNATIONS ARE TO ESTABLISH STANDARDS OR
DESIRED QUALITY. ACCEPTANCE OR REJECTION OF
THE PROPOSED SUBSTITUTIONS SHALL BE SUBJECT
TO THE APPROVAL OF THE OWNER.
REFER TO ARCHITECTURAL DRAWINGS FOR EXACT
LOCATION OF EQUIPMENT, DEVICES, AND FURNITURE
REQUIREMENTS, PRIOR TO ROUGHING IN FOR SAME.
ALL GENERAL NOTES, SYMBOLS, LISTS, ABBREVIATIONS
AND DETAILS ARE TO BE CONSIDERED APPLICABLE TO
ALL ELECTRICAL DRAWINGS FOR THIS PROJECT.
IN AREAS AFFECTED BY THIS RENOVATION, THE
ELECTRICAL SUBCONTRACTOR SHALL MAINTAIN
CONTINUITY OF EXISTING ELECTRICAL SERVICE.
PRIOR TO REMOVAL OF EQUIPMENT, THE OWNER WILL
INDICATE WHICH EXISTING DEVICES OR MATERIALS
SHALL BE SALVAGED AND TURNED OVER FOR STORAGE.
WHERE EXISTING EQUIPMENT AND DEVICES ARE TO BE
RELOCATED, ALL ASSOCIATED WIRING, CONDUIT AND
ACCESSORIES SHALL BE EXTENDED, RELOCATED OR
REPLACED WHERE REQUIRED.
17.NEW DEVICES SHALL BE RECESSED. SURFACE MOUNTED
DEVICES SHALL ONLY BE USED WHEN SPECIFICALLY
APPROVED BY OWNER AND ARCHITECT. WHEN SURFACE
MOUNTED DEVICES ARE APPROVED THEY SHALL BE
INSTALLED IN A FINISHED WIREMOLD TYPE BOX AND
WIREMOLD WIREMANAGEMENT SYSTEM. SURFACE
MOUNTED CONDUIT AND JUNCTION BOXES WITH
KNOCKOUT LOCATIONS WILL NOT BE ACCEPTED.ALL LIGHT FIXTURES ARE TO BE STANDARD COLOR
3500K UNLESS OTHERWISE NOTED.
ALL LED DRIVERS SHALL HAVE A MINIMUM 5 YEAR
MANUFACTURER'S WARRANTY.
NOT USED.
CONDUIT RUNS ARE SHOWN DIAGRAMATICALLY. INSTALL
CONDUIT WITH A MINIMUM OF BENDS RECTILINEAR TO
BUILDING LINES CONSIDERING THE BUILDINGS
CONSTRUCTION AND OBSTRUCTIONS, EXCEPT WHERE
OTHERWISE NOTED.
WHERE A DISCREPANCY OCCURS BETWEEN THE
DRAWINGS AND THE SPECIFICATIONS, THE MOST
STRINGENT SHALL PREVAIL. CONTACT THE
ENGINEER FOR CLARIFICAION WHEN SUCH A
SITUATION OCCURS.
FIRE ALARM RED
BLUE
SIGNAL (NURSE CALL, PA)
AUDIO VISUAL
480V
277V
120V
208V
PURPLE
WHITE
BROWN
ORANGE
BLACK
JUNCTION BOX IDENTIFICATION
COLOR CODE CHART
1.
a.
2.
b.
FIRE ALARM
SYSTEM NOTES
REFER TO ELECTRICAL DRAWINGS FOR QUANTITIES
AND LOCATIONS OF ALL FIRE ALARM DEVICES
ASSOCIATED WITH FIRE PROTECTION SYSTEMS.
c. MAKE ALL CONNECTIONS AS REQUIRED.
PROVIDE ALL REQUIRED PROGRAMMING.d.
MODIFY THE EXISTING NOTIFIER
MAIN FIRE ALARM CONTROL PANEL TO
ACCOMMODATE THE NEW DEVICES INDICATED.
PROVIDE NEW ZONES(IDENTIFY AS REQUIRED).
NEW CONTACTS, ADDITIONAL POWER SUPPLIES
AND ALL OTHER ACCESSORIES FOR A COMPLETE
AND OPERATIONAL SYSTEM.
PROVIDE NEW FIRE ALARM
SPEAKER/STROBES WHERE INDICATED.
PROVIDE NEW FIRE ALARM
STROBES WHERE INDICATED.
E L E C T R I C A L L E G E N D
CIRCUIT NUMBER(S)
PANEL DESIGNATION
WIRING CONCEALED IN WALL OR CEILING
GFI GFCI DUPLEX CONVENIENCE RECEPTACLE - MOUNTED C/L UP 48" UNLESS NOTED OTHERWISE
SAME AS ASSOCIATED RECEPTACLE
EXISTING PANELBOARD
PANELBOARD
AC/BATTERY POWERED EXIT SIGN WITH ARROWS AS INDICATED OR HATCH INDICATES FACE - CEILING MOUNTED
AC/BATTERY POWERED EXIT SIGN WITH ARROWS AS INDICATED OR HATCH INDICATES FACE - WALL MOUNTED
DIRECTLY ABOVE DOOR
EXISTING ITEMS SHOWN DASHED
DUPLEX CONVENIENCE RECEPTACLE WITH DUAL USB CHARGING PORTS - MOUNTED C/L UP 24" UNLESS NOTED OTHERWISE
DOUBLE DUPLEX CONVENIENCE RECEPTACLE WITH FOUR USB CHARGING PORTS - MOUNTED C/L UP 24" UNLESS NOTED OTHERWISE
THREE-WAY SWITCH - MOUNTED C/L UP 48" UNLESS NOTED OTHERWISE - SUBLETTER INDICATES SWITCH CONTROL
OC WATTSTOPPER DT-300 OCCUPANCY SENSOR AND POWER PACK - PROVIDE NUMBER OF POWER PACKS REQUIRED TO ALLOW FOR NUMBER OF
OCCUPANCY SENSORS AND SWITCHING SHOWN
DIMMER SWITCH - MOUNTED C/L UP 48" UNLESS NOTED OTHERWISE - LUTRON DIVA LED 0-10V DIMMING SWITCH MODEL DVSTV
VOICE AND DATA OUTLET - JUNCTION BOX WITH 1" CONDUIT TO 6" ABOVE DROP CEILING - MOUNT UP
REF:B1
--
LIGHT FIXTURE SCHEDULE
REF:B2
--
LEGEND
SINGLE POLE SWITCH - MOUNTED C/L UP 48" UNLESS NOTED OTHERWISE - SUBLETTER INDICATES SWITCH CONTROL
LAMPS, HANGERS, FITTINGS, ETC. FOR A COMPLETE AND PROPER INSTALLATION
ALL FIXTURES SHALL BE FURNISHED COMPLETE WITH ALL HARDWARE
LIGHTING FIXTURE SCHEDULE
TYPE MANUFACTURER CATALOG NO. MTG. VOLTNO. WATT
LAMPS
TYPEREMARKS/BALLAST INFORMATION
LEDUNVRA
3500K
LED
LEDUNVR3500K
LED
LITHONIA38
AE PROVIDE WITH INTEGRAL EMERGENCY BATTERY PACK.38
LEDUNVS
LED E PROVIDE WITH INTEGRAL EMERGENCY BATTERY PACK.LQM-S-W-3-R-MVOLT-ELN1
FIRE ALARM LIGHT UNIT - CANDLE POWER (CD) PER NFPA 72 OR AS NOTED - 15/75 WHERE NOT
OTHERWISE INDICATED ON PLANS - CEILING MOUNTED
OTHERWISE INDICATED ON PLANS - CEILING MOUNTED
S
FIRE ALARM SPEAKER/LIGHT UNIT - CANDLE POWER (CD) PER NFPA 72 OR AS NOTED - 15/75 WHERE NOT
EMERGENCY BATTERY UNIT WITH TWO HEADS
LP-1#3 HOMERUN TO PNLBRD
W
WIRELESS ACCESS POINT (WAP)
MANUAL MOTOR STARTER WITH OVERLOAD PROTECTION
J JUNCTION BOX
LED 2x4 FLAT PANEL WITH EMERGENCY BATTERY PACK
LED 2x4 FLAT PANEL
EPANL-2x4-4000-80CRI-35K-MIN10-MVOLT
LED EXIT SIGN WITH EMERGENCY BATTERY PACK - SINGLE OR DOUBLE FACE AND CHEVRONS AS INDICATED ON DRAWINGS
SAME AS ASSOCIATED RECEPTACLE
VOICE OUTLET - JUNCTION BOX WITH 1" CONDUIT TO 6" ABOVE DROP CEILING - MOUNT UP
LITHONIA
LITHONIA
CR
DC
REX
CARD READER- PROVIDE JUNCTION BOX AND 3/4" C TO DOOR CONTROLLER
DOOR POSITION SWITCH- PROVIDE JUNCTION BOX AND 3/4" C TO DOOR CONTROLLER
ELECTRIC STRIKE- PROVIDE JUNCTION BOX AND 3/4" C TO DOOR CONTROLLER
REQUEST TO EXIT PASSIVE INFRARED SENSOR- PROVIDE JUNCTION BOX AND 3/4" C TO DOOR CONTROLLER
1.
a.
b.
c.
PROVIDE NEW CARD READERS
WHERE INDICATED.
PROVIDE NEW DOOR CONTACTS
WHERE INDICATED.
PROVIDE NEW REQUEST TO EXIT
DEVICES WHERE INDICATED.
2.
3.
d.
e. PROVIDE NEW ELECTRIC STRIKES
WHERE INDICATED.
CARD ACCESS
SYSTEM NOTES
COORDINATE ALL CARD ACCESS WORK WITH USM
CAMPUS POLICE DEPARTMENT.
ACCESS CONTROL WORK SHALL BE DONE BY
USM SECURITY SYSTEM VENDOR. CONTACT
USM FOR CONTACT INFORMATION OF SECURITY
SYSTEM VENDOR.
PROVIDE CONNECTION TO FIRE
ALARM SYSTEM AS REQUIRED.
MODIFY THE EXISTING CARD ACCESS
SYSTEM PRESENTLY SERVING THE
BUILDING TO ACCOMMODATE THE NEW
DEVICES INDICATED. PROVIDE EXPANSION CARDS
ADDITIONAL POWER SUPPLIES, CABLES AND
ALL OTHER ACCESSORIES FOR A COMPLETE AND
OPERATIONAL SYSTEM.
EPANL-2x4-4000-80CRI-35K-MIN10-MVOLT-E10WCP
LEDUNVRBE
3500K
LED 20
EXTERIOR 20" WIDE MULLION MOUNTED LED LIGHT FIXTURE WITH PHOTOCELL AND REMOTE INVERTER/BATTERY
BLD-24IN-NODIM-2DRV-20W-2100LM-40K-MVOL-DP-SIL-LITHONIA
EMB20R-PC
LEDUNVRA1
3500K
LED
LEDUNVR3500K
LED
LITHONIA45
A1E PROVIDE WITH INTEGRAL EMERGENCY BATTERY PACK.45
LED 2x4 FLAT PANEL WITH EMERGENCY BATTERY PACK
LED 2x4 FLAT PANEL
EPANL-2x4-4800-80CRI-35K-MIN10-MVOLT
LITHONIA EPANL-2x4-4800-80CRI-35K-MIN10-MVOLT-E10WCP
Harriman Project No.
Drawing Scales
PA / PE:
Drawn By:Harriman Associates
c 2021
Proj NorthKey Plan
GORHAM, MAINE
20478
RENOVATIONS
ATHLETIC TRAINING
HILL GYMNASIUM
SOUTHERN MAINE
UNIVERSITY OF
MAY 17, 2021
CONSTRUCTION DOCUMENTS
Rev Date Revision Description
LEGENDS, NOTES
AND
SCHEDULES
JWT
APG
E00-1
H1
H2
H3
1FIRST FLOOR PART PLANSCALE: 1/8" = 1'-0"
GFI
GFI
GFI
UNIT HEATER
PLUGMOLD
C
GFI
OC
OC
OC
OC
W
OC
DEMOLITION NOTES:
LEGEND:
EXISTING EQUIPMENT TO BE DEMOLISHED IS INDICATED AS BOLD AND DASHED:
EXISTING EQUIPMENT TO REMAIN IS INDICATED BY LIGHT AND DASHED:
EXISTING EQUIPMENT TO BE BE MODIFIED IS INDICATED AS BOLD AND DASHED WITH TEXT ADJACENT:(XRE)
DOTTED INDICATES EXISTING EQUIPMENT
(REFER TO LEGEND FOR TYPE)
(EN)EXISTING IN NEW LOCATION
EXISTING
EQUIPMENT LEGEND
(XN)EXISTING TO BE REPLACED WITH NEW
(XRE)EXISTING TO BE RELOCATED
1. ELECTRICAL INDICATED IS AS GENERALLY FOUND (APRIL
2021). THE INTENT OF THE DEMOLITION PLAN(S) IS TO
DOCUMENT EXISTING CONDITIONS. HOWEVER, ALL ELECTRICAL
DEVICES MAY NOT NECESSARILY BE INDICATED ON THE
DRAWINGS. FIELD VERIFY AND ADJUST WORK TO SUIT ALL FOUND.
2. REFER TO FLOOR PLANS TO DETERMINE EXTENT OF WORK
IN EACH AREA, INCLUDING WHETHER DEVICES ARE TO REMAIN,
BE REMOVED, REPLACED, ETC... EXCEPT AS NOTED, GENERALLY
THE INTENT IS THAT IF EXISTING DEVICES ARE SHOWN ON THE
DEMOLITION PLANS AND NEW DEVICES ARE SHOWN ON THE FLOOR
PLANS THEN EXISTING DEVICES ARE TO BE REMOVED. IF EXISTING
DEVICES ARE SHOWN ON BOTH THEN DEVICES ARE TO REMAIN.
3. ALL EXISTING ITEMS INTENDED FOR REMOVAL SHALL BE REMOVED
WITH ALL ASSOCIATED HARDWARE INCLUDING, BUT NOT LIMITED TO:
CONDUIT, BOXES, WIRING, CABLES, HANGERS, ETC...
4. COORDINATE WITH MECHANICAL AND PLUMBING DRAWINGS FOR
MECHANICAL AND PLUMBING EQUIPMENT TO BE REMOVED. REMOVE
ALL ASSOCIATED CONDUIT, BOXES, WIRING, ETC...
5. CONDUIT IN GOOD CONDITION AND PROPERLY LOCATED MAY BE
REUSED WHERE APPLICABLE, UNLESS NOTED OTHERWISE.
6. IN AREAS NOT RENOVATED BY THIS CONTRACT VERIFY THAT
ELECTRICAL POWER, LIGHTING AND SYSTEMS ARE NOT AFFECTED
BY THE ALTERATIONS. PROVIDE ALL WORK AS REQUIRED TO
MAINTAIN POWER AND PROPER OPERATION OF SYSTEMS.
D01 EXISTING 20 POLE, SUB PANEL 1 PANELBANELBOARD TO BE DEMOLISHED AND REPLACED WITH NEW PANEL P IN ADJACENT MECHANICAL ROOM.
EXISTING 100A SUB PANEL 1 FEEDER TO BE EXTENDED TO NEW PANEL P. ALL EXISTING BRANCH CIRCUITS REMAINING AFTER DEMOLITION TO
BE EXTENDED TO NEW MATCHING BREAKERS IN NEW PANEL P.
D01
J
DOOR
SUB PANEL 1
(XRE)
(XRE)
(XRE)
(XRE)
(XRE)
(XRE)
(XRE)
(XRE)
(XRE)
(XRE)
Harriman Project No.
Drawing Scales
PA / PE:
Drawn By:Harriman Associates
c 2021
Proj NorthKey Plan
GORHAM, MAINE
20478
RENOVATIONS
ATHLETIC TRAINING
HILL GYMNASIUM
SOUTHERN MAINE
UNIVERSITY OF
MAY 17, 2021
CONSTRUCTION DOCUMENTS
Rev Date Revision Description
PART
PLAN
EXISTING CONDITIONS
JWT
APG
E05-1
1/8" = 1'-0"
0 4' 8' 12'
OFFICE
116
OFFICE
113
OFFICE
114
OFFICE
115
SUPPLY ROOM
112S
TOILET
112T
OFFICE
117
WET ROOM
112W
ATHLETIC TRAINING
112
MENS GA LOCKER
ROOM
120
CORRIDOR
111
MECHANICAL
129
H1
H2
H3
ICE
HEAT
1FIRST FLOOR PART PLANSCALE: 1/8" = 1'-0"
1FIRST FLOOR PART PLANSCALE: 1/8" = 1'-0"
(EN)
(EN)
(EN)
(EN)
L01
AE
CIRCUIT NEW FIXTURE TO LIGHTING CIRCUIT AND CONTROLS SERVING CORRIDOR 111. PROVIDE UNSWITCHED LEG OF LIGHTING CIRCUIT FOR
EMERGENCY BATTERY BACKUP.
E
L01
CIRCUIT NEW EXIT SIGN TO UNSWITCHED LEG OF LIGHTING CIRCUIT SERVING CORRIDOR 111. L02
L02
(EN)
OC
OC
(EN)
CIRCUIT TO UNSWITCHED LEG OF LIGHTING CIRCUIT SERVING THE ROOM 120. L03
E OC
OC
OC
OC
OC
OC
OC
OC
OC
OC
E
L03
L03
CIRCUIT RELOCATED FIXTURE TO LIGHTING CIRCUIT AND CONTROLS SERVING CORRIDOR ROOM 120.L04
L04
L04
L04
A
A
A
A
A
A
A
A
A
A
AEBE
L01
A1
A1E
A1E
A1E
A1E
A1EA1
A1
A1
A1 A1
A1
A1
A1
A
P#21
PANEL P
21
21
21
21
21
21
21
21
21
21
21
21
21
21
21
21
21
21
21
21
21
2121
21
21
21
21
21
Harriman Project No.
Drawing Scales
PA / PE:
Drawn By:Harriman Associates
c 2021
Proj NorthKey Plan
GORHAM, MAINE
20478
RENOVATIONS
ATHLETIC TRAINING
HILL GYMNASIUM
SOUTHERN MAINE
UNIVERSITY OF
MAY 17, 2021
CONSTRUCTION DOCUMENTS
Rev Date Revision Description
PART
PLAN
LIGHTING
JWT
APG
E10-1
1/8" = 1'-0"
0 4' 8' 12'
OFFICE
116
OFFICE
113
OFFICE
114
OFFICE
115
SUPPLY ROOM
112S
TOILET
112T
OFFICE
117
WET ROOM
112W
ATHLETIC TRAINING
112
MENS GA LOCKER
ROOM
120
CORRIDOR
111
MECHANICAL
129
H1
H2
H3
ICE
HEAT
1FIRST FLOOR PART PLANSCALE: 1/8" = 1'-0"
C
GFI
J
DOOR
1FIRST FLOOR PART PLANSCALE: 1/8" = 1'-0"
(EN)
(EN)
CR
DC
J DOORRE
X
WP GFI
GFI
W(EN)
PANEL P
15cd
30cd
GFI
GFI
GFI
75cd
ICE
TUB
P#28
P#26
P#30
P#32
P#24
P#22
P#29
P#37
P#31
P#35
P#21
P#23
P#27
P#25
P01 CIRCUIT NEW DOOR CONTROLLER TO EXISTING CIRCUIT SERVING ADJACENT CARD ACESS CONTROLLED DOOR.
P01
P02 EXTEND EXISTING 100A CIRCUIT FROM EXISTING SUB PANEL 1 PANELBOARD BEING DEMOLISHED TO NEW PANEL P. PROVIDE SPLICE BOX
AND NEW WIRE AND CONDUIT AS REQUIRED. EXTEND EXISTING BRANCH CIRCUITS REMAINING FROM SUB PANEL A AFTER DEMOLITION TO
MATCHING SPARE BREAKERS IN NEW PANEL P. PROVIDE ALL WIRE, CONDUIT AND SPLICE BOXES AS REQUIRED TO EXTEND EXISTING BRANCH
CIRCUITS.
P02
(EN) 75cd
15cd
21
21
21
21
21
2323
23
23
25
25
25
25
27
27
33
3131
31
31
31
33
P#33
35
35
3535
3737
37
37
22
24
26
28
30
32
27
27
MOUNT RECEPTACLE AT 48" AFF.P03
P03
P03
P03
P03
P03
P03
GFI
GFI TUB
TUB
P03
P03
P03
P03
P03
29
29
GFI
P0322
22
27
39
P#39
HEAT BOX
AHU-1
ERV-1
IU-1
IU-3
IU-2
OU-1
WP
P#38,40
P#34,36
34,3638,40
J ATC
J ATC
P#41
41
41
3#4+1#10G IN 1"C.P04
P04
P04
P#42,44
42,44
42,44
42,44
P#46,48,50
46,48,50
Harriman Project No.
Drawing Scales
PA / PE:
Drawn By:Harriman Associates
c 2021
Proj NorthKey Plan
GORHAM, MAINE
20478
RENOVATIONS
ATHLETIC TRAINING
HILL GYMNASIUM
SOUTHERN MAINE
UNIVERSITY OF
MAY 17, 2021
CONSTRUCTION DOCUMENTS
Rev Date Revision Description
PART
PLAN
POWER
JWT
APG
E20-1
1/8" = 1'-0"
0 4' 8' 12'
ID ID
WATT LOADS
MOUNTING:
LOCATION:
LOAD DESCRIPTION
AM
P
PO
LE
CRKTDWG
NO. PO
LE
WATTSPH A PH B PH C
WATTS
PO
LE
CRKTDWG
NO. PO
LE
AM
P
LOAD DESCRIPTION
FEEDER:AIC RATING:MAIN BREAKER:VOLTAGE:
BUSES:PH & WIRES:
120/208
3P 4W
225
100A MAIN BRKR
10K AIC
SURFACE
MECHANICAL RM
SEE DRAWINGP
TUB 1 OF 1 - REMARKS:
RELOCATED EXISTING LOAD 20 1 1 400 800 --- --- 400 2 2 1 20 EXISTING RELOCATED LOAD
RELOCATED EXISTING LOAD 15 2 3 3 2496 --- 1648 --- 400 4 4 1 20 EXISTING RELOCATED LOAD
- - - 5 --- --- 1648 400 6 6 1 20 EXISTING RELOCATED LOAD
RELOCATED EXISTING LOAD 20 1 7 7 400 800 --- --- 400 8 8 1 20 EXISTING RELOCATED LOAD
RELOCATED EXISTING LOAD 20 1 9 9 400 --- 800 --- 400 10 10 1 20 EXISTING RELOCATED LOAD
RELOCATED EXISTING LOAD 20 2 11 11 3328 --- --- 2064 400 12 12 1 20 EXISTING RELOCATED LOAD
- - - 13 2064 --- --- 400 14 14 1 20 EXISTING RELOCATED LOAD
RELOCATED EXISTING LOAD 20 1 15 15 400 --- 2064 --- 3328 16 16 2 20 EXISTING RELOCATED LOAD
RELOCATED EXISTING LOAD 20 1 17 17 400 --- --- 2064 18 - - -
RELOCATED EXISTING LOAD 20 1 19 19 400 800 --- --- 400 20 20 1 20 EXISTING RELOCATED LOAD
OFFICE 113 RCPTS 20 1 21 1200 --- 1800 --- 600 22 1 20 RM 112W RCPT
OFFICE 114 RCPTS 20 1 23 23 1000 --- --- 2000 1000 24 24 1 20 RM 112W RCPT
OFFICE 114 RCPTS 20 1 25 25 1000 2000 --- --- 1000 26 26 1 20 RM 112W RCPT
ROOM 112 RCPTS 20 1 27 27 1000 --- 2000 --- 1000 28 28 1 20 RM 112W RCPT
ROOM 112 RCPTS 20 1 29 29 800 --- --- 1800 1000 30 30 1 20 RM 112W RCPT
ROOM 112 RCPTS 20 1 31 31 800 1800 --- --- 1000 32 32 1 20 RM 112W RCPT
ROOM 112/112T RCPTS 20 1 33 33 400 --- 986 --- 1171 34 2 15 ERV-1
OFFICE 116 RCPTS 20 1 35 35 1000 --- --- 1586 36 - - -
OFFICE 117 RCPTS 20 1 37 37 1000 2123 --- --- 2246 38 38 2 15 ERV-1
ROOM 112 HEAT BOX RCPT 20 1 39 1000 --- 2123 --- 40 - - -
ATC J-BOXES 20 1 41 200 --- --- 368 337 42 2 15 IU-1, IU-2, IU-3
SPARE 20 1 43 0 168 --- --- 44 - - -
SPARE 20 1 45 0 --- 4803 --- 14410 46 46 3 60 OU-1
SPARE 20 1 47 0 --- --- 4803 48 - - -
SPARE 30 3 49 0 4803 --- --- 50 - - -
- - - 51 --- 0 --- 0 52 1 20 SPARE
- - - 53 --- --- 0 0 54 1 20 SPARE
TOTAL AMPS: 133.1 15358 16223 16333 TOTAL WATTS: 47914
REMARKS:
04/28/2021
Harriman Project No.
Drawing Scales
PA / PE:
Drawn By:Harriman Associates
c 2021
Proj NorthKey Plan
GORHAM, MAINE
20478
RENOVATIONS
ATHLETIC TRAINING
HILL GYMNASIUM
SOUTHERN MAINE
UNIVERSITY OF
MAY 17, 2021
CONSTRUCTION DOCUMENTS
Rev Date Revision Description
PANEL
SCHEDULES
JWT
APG
E60-1