Power Circuit Breakers
4/1ABB LIMITED
Contents
Tmax Technical Data .................................................................... 4-2
Distribution & Generator Protection Tmax...................................... 4-10
Isomax Technical Data .................................................................. 4-16
Distribution & Generator Protection Isomax.................................... 4-20
Tmax Accessories.......................................................................... 4-30
Isomax Accessories ...................................................................... 4-34
Motor Protection Tmax.................................................................. 4-48
Motor Protection Isomax................................................................ 4-51
Current Limiting MCCB’s .............................................................. 4-58
Emax Technical Data .................................................................... 4-60
Emax Air Ciruit Breakers................................................................ 4-66
Emax Accessories.......................................................................... 4-83
ABB LIMITED 4/2
Tmax Electrical Specifications
1) MF up to R 12.5 A2) In the plug-in version, the maximum setting is derated by 10% at 40°C3) F-FC Cu-FC CuAI-EF-ES-R-FC Cu AI 240mm2
Description T1
B C NPerformance level Iu [A] 160 160 160
Poles No. 3/4 3/4 3/4 3/4
Rated service voltage Ue(AC) 50-60Hz [V] 690 690 690(DC) [V] 500 500 500
Rated impulse withstand voltage Uimp [kV] 8 8 8
Rated insulation voltage Ui [V] 800 800 800
Voltage test at industrial frequency for 1 min. [V] 3000 3000 3000
Rated ultimate short circuit breaking capacity Icu(AC) 50-60Hz 220/230 V [kA] 25 40 50(AC) 50-60Hz 380/415 V [kA] 16 25 36(AC) 50-60Hz 440 V [kA] 10 15 22(AC) 50-60Hz 500 V [kA] 8 10 15(AC) 50-60Hz 690 V [kA] 3 4 6(DC) 250 V 2 poles in series [kA] 16 25 36(DC) 250 V 3 poles in series [kA] 20 30 40(DC) 500 V 3 poles in series [kA] 16 25 36
Rated short circuit service breaking capacity Ics(AC) 50-60Hz 220/230 V [kA] 100% 75% 75%(AC) 50-60Hz 380/415 V [kA] 100% 75% 50% (19kA)(AC) 50-60Hz 440 V [kA] 100% 75% 50%(AC) 50-60Hz 500 V [kA] 100% 75% 50%(AC) 50-60Hz 690 V [kA] 100% 75% 50%
Rated short circuit making capacity Icm(AC) 50-60Hz 220/230 V [kA] 52.5 84 105(AC) 50-60Hz 380/415 V [kA] 32 52.5 75.6(AC) 50-60Hz 440 V [kA] 17 30 46.2(AC) 50-60Hz 500 V [kA] 13.6 17 30(AC) 50-60Hz 690 V [kA] 4.3 5.9 9.2
Breaking time [ms] 7 6 5
Utilisation category A A A
Isolation behavior
Reference Standards IEC 60947-2 IEC 60947-2 IEC 60947-2
Releases Thermomagnetic TMD (adj.)TMF (fixed) - - -
magnetic only MA - - -
microprocessor based PR221 DS-LS - - -
PR221 DS-I - - -
Versions F F F
Terminals F - P FC Cu-EF-FC CuAI 95mm 2
Fixing on DIN rail DIN EN 50022
Mechanical life [No. Operations] 25000 25000 25000[No. Hourly Operations] 240 240 240
Electrical life at 415 V [No. Operations] 8000 8000 8000[No. Hourly Operations] 120 120 120
Basic dimensions, fixed version 3 poles L [mm] 76 76 764 poles L [mm] 102 102 102
H [mm] 130 130 130P [mm] 70 70 70
Weight fixed version 3/4 Poles [kg] 0.9 / 1.2 0.9 / 1.2 0.9 / 1.2plug-in version 3/4 Poles [kg] - - -
ABB LIMITED 4/3
T2 T3
N S H L N S160 160 160 160 160 160
3/4 3/4 3/4 3/4 3/4 3/4
690 690 690 690 690 690500 500 500 500 500 500
8 8 8 8 8 8
800 800 800 800 800 800
3000 3000 3000 3000 3000 3000
65 85 100 120 50 8536 50 70 85 36 5030 45 55 75 25 4025 30 36 50 20 306 7 8 10 5 836 50 70 85 36 5040 55 85 100 40 5536 50 70 85 36 50
100% 100% 100% 100% 75% 50%100% 100% 100% 75%(70kA) 75% 50% (27kA)100% 100% 100% 75% 75% 50%100% 100% 100% 75% 75% 50%100% 100% 100% 75% 75% 50%
143 187 220 264 105 18775.6 105 154 187 75.6 10563 94.5 121 165 52.5 84
52.5 63 75.6 105 40 639.2 11.9 13.6 17 7.7 13.6
3 3 3 3 7 6
A A A A A A
IEC 60947-2 IEC 60947-2 IEC 60947-2 IEC 60947-2 IEC 60947-2 IEC 60947-2
- - - - - -1) 1) 1) 1)
- -
- -
F-P2) F-P2) F-P2) F-P2) F-P2) F-P2)
F-FC Cu-FC CuAI-EF-ES-R-FC CuAI 185mm2 3) 3)
DIN EN 50022 DIN EN 50022
25000 25000 25000 25000 25000 25000240 240 240 240 120 120
8000 8000 8000 8000 8000 8000120 120 120 120 120 120
90 90 90 90 105 105120 120 120 120 140 140130 130 130 130 150 15070 70 70 70 70 70
1.1 / 1.5 1.1 / 1.5 1.1 / 1.5 1.1 / 1.5 2.1 / 3 2.1 / 31.5 / 1.9 1.5 / 1.9 1.5 / 1.9 1.5 / 1.9 2.7 / 3.7 2.7 / 3.7
ABB LIMITED 4/4
Description S3 S4
Isomax Electrical Specifications
N H L NPerformance level Iu [A] 160-250 160-250 160-250 160-250
Poles No. 3/4 3/4 3/4 3/4
Rated service voltage Ue(AC) 50-60Hz [V] 690 690 690 690(DC) [V] 750 750 750 -
Rated impulse withstand voltage Uimp [kV] 8 8 8 8
Rated insulation voltage Ui [V] 800 800 800 800
Voltage test at industrial frequency for 1 min. [V] 3000 3000 3000 3000
Rated ultimate short circuit breaking capacity Icu (AC) 50-60Hz 220/230 V [kA] 65 100 170 65(AC) 50-60Hz 380/415 V [kA] 35 65 85 35(AC) 50-60Hz 440 V [kA] 30 50 65 30(AC) 50-60Hz 500 V [kA] 25 40 50 25(AC) 50-60Hz 690 V [kA] 14 18 50 18(DC) 250 V 2 poles in series [kA] 35 65 85 -(DC) 250 V 3 poles in series [kA] 35 50 65 -(DC) 750 V 3 poles in series [kA] 20 35 50 -
Rated short circuit service breaking capacity Ics [%Icu] 100% 75% 75% 100%
Rated short circuit making capacity (415 V) [kA] 74 143 187 74
Opening Time (415 V at Icu) [ms] 8 7 6 8
Rated short time withstand current for 1 s, Icw [kA] - - - -
Utilisation category (EN 60947-2) A A A A
Isolation behavior
IEC 60947-2, EN 60947-2
Releases Thermomagnetic T adjustable, M fixed 3 Ith - -
T adjustable, M fixed 5 Ith -
T adjustable, M fixed 10 Ith -
T adjustable, M adjustable - - - -
magnetic only M fixed -
microprocessor based PR211/P (I-LI) - - -
PR212/P (LSI-LSIG - - -
Versions F-P-W F-P-W
Terminals Fixed F-EF-ES-FCFC CuAI-RC-R
Plug-in EF-FC-RWithdrawable EF-FC-R
Fixing on DIN rail DIN EN 50023
Mechanical life [No. Operations] 25000 25000 25000 20000[No. Hourly Operations] 120 120 120 120
Electrical life at 415 V [No. Operations] 10000 (160A) -8000 (250A)[No. Hourly Operations] 120 120 120 120
Basic dimensions, fixed 3/4 poles L [mm] 105/140 105/140 105/140 105/140D [mm] 103.5 103.5 103.5 103.5 103.5H [mm] 170 170 170 254 254
Weight fixed version 3/4 Poles [kg] 2.6/3.5 2.6/3.5 2.6/3.5 4/5.3plug-in version 3/4 Poles [kg] 3.1/4.1 3.1/4.1 3.1/4.1 4.5/5.9withdrawable 3/4 Poles [kg] 3.5/4.5 3.5/4.5 3.5/4.5 4.9/6.3
ABB LIMITED 4/5
S4 S5 S6 S7H L N H L N S H L S H L
160-250 160-250 400-630 400-630 400-630 630-800 630-800 630-800 630-800 1250-1600 1250-1600 1250-1600
3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4
690 690 690 690 690 690 690 690 690 690 690 690- - 750 750 750 750 750 750 750 - - -
8 8 8 8 8 8 8 8 8 8 8 8
800 800 800 800 800 800 800 800 800 800 800 800
3000 3000 3000 3000 3000 3000 3000 3000 3000 3000 3000 3000
100 200 65 100 200 65 85 100 200 85 100 20065 100 35 65 100 35 50 65 100 50 65 10050 80 30 50 80 30 45 50 80 40 55 8040 65 25 40 65 25 35 40 65 35 45 7022 30 20 25 30 20 22 25 30 20 25 35- - 35 65 100 35 50 65 100 - - -- - 35 50 65 20 35 50 65 - - -- - 20 35 50 16 20 35 50 - - -
100% 75% 100% 100% 75% 100% 100% 100% 75% 100% 75% 50%
143 220 74 143 220 74 105 143 220 105 143 220
7 6 8 7 6 10 9 8 7 22 22 22
- - 5 (400A) 7.6 (630A) - 10 (800A) 15 (1250A) - 20 (1600A)
A A B (400A) - A (630A) B B B B B B B
- - - - - - - - - - - -
- - - - - - - - - - - -
- - - - - - - - - - - -
- - - - -
- - - - - - - - - - - -
F-P-W F-P(400)-W F-W F-W
F-EF-ES-FC F-EF(400A)-ES-FC F-EF-ES-FC-CuAI F-EF-ES-FC CuAI(1250A)FC CuAI-RC-R FC CuAI(400A)-RC-(400A)-R RC-R HR-VR
EF-FC-R EF-FC-R - -EF-FC-R EF(400A)-ES-FC(400A) EF-HR-VR EF-HR-VR
DIN EN 50023 DIN EN 50023
20000 20000 20000 20000 20000 20000 20000 20000 20000 10000 10000 10000120 120 120 120 120 120 120 120 120 120 120 120
10000(160A) - 8000(250A) 7000 (400A) - 5000 (800A) 7000 (630A) - 5000 (800A) 7000 (1250A) - 5000 (1600A)120 120 60 60 60 60 60 60 60 20 20 20
105/140 105/140 140/184 140/184 140/184 210/280 210/280 210/280 210/280 210/280 210/280 210/280103.5 103.5 103.5 103.5 103.5 103.5 103.5 103.5 138.5 138.5 138.5254 254 254 254 268 268 268 268 406 406 406
4/5.3 4/5.3 5/7 5/7 5/7 9.5/12 9.5/12 9.5/12 9.5/12 17/22 17/22 17/224.5/5.9 4.5/5.9 6.1/8.4 6.1/8.4 6.1/8.4 - - - - - - -4.9/6.3 4.9/6.3 6.4/8.7 6.4/8.7 6.4/8.7 12.1/15.1 12.1/15.1 12.1/15.1 12.1/15.1 21.8/29.2 21.8/29.2 21.8/29.2
ABB LIMITED 4/6
Tmax Construction CharacteristicsModularity of the series
1
2
3
7
1314
9
ABB LIMITED 4/7
Starting from the fixed version circuit-breaker, all the other ver-
sions used for various requirements are obtained by means of
mounting conversion kits.
The following are available:
Kit for converting a fixed circuit-breaker into the moving
part of a plug-in
Circuit-breaker fixed parts for plug-in circuit-breakers
Conversion kit for the connection terminals
Various accessories are also available:
Shunt opening releases
Undervoltage releases
Auxiliary contacts
Position contacts
Advanced contacts on rotary handle
Front and rear connection terminals
Bracket for rear fixing on DIN EN 50022 rail
Front interlocking plate
Solenoid operating mechanism
Rotary handle operating mechanism - direct on circuit-
breaker and transmitted on compartment door
Three-pole and four-pole residual current releases
4
5
6
1
2
3
7
12
13
14
8
9
10
11
4
5
6
12
8
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
ABB LIMITED 4/8
Tmax Electronic Releases
L
S
I
Protection functionsof the PR221DS-LS releaseProtection Function Trip threshold Trip Curves
A B C
CANNOT BEEXCLUDED
CAN BEEXCLUDED
CAN BEEXCLUDED
Against overload with inverselong delay trip and trip charac-teristic according to a definitetime curve (I2t = constant)
Against short-circuit with instan-taneous adjustable trip (can beselected as an alternative toprotection function S)
Against a short-circuit withinverse short delay and tripcharacteristic with definite time(I2t = constant)
i1 = 0.40 - 0.44 - 0.48 - 0.52 -0.56 - 0.60 - 0.64 - 0.680.72 - 0.76 - 0.80 - 0.840.88 - 0.92 - 0.96 - 1 x In
Release between 1.05...1.30 x I1(IEC 60947-2)
i1 = 1 - 1.5 - 2 - 2.5 - 3 - 3.5 - 4.5- 5.5 - 6.5 - 7 - 7.5 - 8 - 8.5 - 9 - 10 x In
Tolerence ± 10% up to 2 x In± 20% over 2 x In
at 6 x I1 at 6 x I1t1 = 3s t1 = 6s
(Tolerence ± 10% up to 2 x In;± 20% over 2 xIn)
at 8 x In at 8 x Int2 = 0.1s t2 = 0.25s
(Tolerence ± 20%)
I3 = 1 - 1.5 - 2 - 2.5 - 3 - 3.5 - 4.5- 5.5 - 6.5 - 7 - 7.5 - 8 - 8.5 -9 - 10 x In
Tolerence ± 20%
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
ABB LIMITED 4/9
Tmax Thermomagnetic Releases
Thermomagnetic releases
The Tmax T1, T2 and T3 circuit-breakers can be fitted with thermomagnetic releases and areused to protect alternating and direct current networks with an application range from 1A to250A. They allow protection against overloads with a thermal device (with adjustable threshold)made using the bimetal technique, and protection against short-circuit with a magnetic device(with fixed threshold).The four-pole circuit-breakers are always supplied with the neutral protected by the releaseand protection of the neutral at 100% of the phase setting for settings up to 100A. For highersettings, the version with protection of the neutral at 50% of the phase setting is available.
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
Icu (415V) Model Current (A) Thermomagnetic PR221DS/LSIth 1SDA0 R1
3 Pole 4 Pole 3 Pole 4 Pole
T2N160R1.6 1.6A 50940 50962 - -
T2N160R2 2A 50941 50963 - -
T2N160R2.5 2.5A 50942 50964 - -
T2N160R3.2 3.2A 50943 50965 - -
T2N160R4 4A 50944 50966 - -
T2N160R5 5A 50945 50967 - -
T2N160R6.3 6.3A 50946 50968 - -
T2N160R8 8A 50947 50969 - -
T2N160R10 10A 50948 50970 51123 51128
T2N160R12.5 12.5A 50949 50971 - -
36kA T2N160R16 16A 50950 50972 - -
T2N160R20 20A 50951 50973 - -
T2N160R25 25A 50952 50974 51124 51129
T2N160R32 32A 50953 50975 - -
T2N160R40 40A 50954 50976 - -
T2N160R50 50A 50955 50977 - -
T2N160R63 63A 50956 50978 51125 51130
T2N160R80 80A 50957 50979 - -
T2N160R100 100A 50958 50980 51126 51131
T2N160R125 125A 50959 51115 - -
T2N160R160 160A 50960 51116 51127 51613
ABB LIMITED 4/11
Distribution and Generator Protection MCCBs Tmax T2N (160A)
Fixed Pattern Circuit Breaker
Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1Supplied as standard with front bar terminals for busbar - for other terminals seeaccessories section pagexx
Ratings @ 415V
Icu Ics
T2N 36kA 100%
Protection types availableType Settings
L S
Electronic
PR221DS/LS 0.4 -1x In 1-10x In
Thermomagnetic Ith Im
Standard Distribution 70 - 100% 10x Ith
Plug-in Circuit breakers
To convert fixed pattern device to plug-in pattern:-
1). Select correct Fixed Pattern Device from part numbers above2). Select Conversion Kit from part numbers below3). Add Fixed portion (Base) from part numbers below Plug-in
1SDA0 R1
3 Pole 4 Pole
Conversion Kit 51411 51412
Fixed portion (Base)
Front Copper Cable Terminals** 51329 51330
Icu (415V) Model Current (A) Thermomagnetic PR221DS/LSIth 1SDA0 R1
3 Pole 4 Pole 3 Pole 4 Pole
50kA T2S160R1.6 1.6A 50984 51006 - -
T2S160R2 2A 50985 51007 - -
T2S160R2.5 2.5A 50986 51008 - -
T2S160R3.2 3.2A 50987 51009 - -
T2S160R4 4A 50988 51010 - -
T2S160R5 5A 50989 51011 - -
T2S160R6.3 6.3A 50990 51012 - -
T2S160R8 8A 50991 51013 - -
T2S160R10 10A 50992 51014 51133 51138
T2S160R12.5 12.5A 50993 51015 - -
T2S160R16 16A 50994 51016 - -
T2S160R20 20A 50995 51017 - -
T2S160R25 25A 50996 51018 51134 51139
T2S160R32 32A 50997 51019 - -
T2S160R40 40A 50998 51020 - -
T2S160R50 50A 50999 51021 - -
T2S160R63 63A 51000 51022 51135 51140
T2S160R80 80A 51001 51023 - -
T2S160R100 100A 51002 51024 51136 51141
T2S160R125 125A 51003 51117 - -
T2S160R160 160A 51004 51118 51137 51614
ABB LIMITED 4/12
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
Distribution and Generator Protection MCCBs Tmax T2S (160A)
Ratings @ 415V
Icu Ics
T2S 50kA 100%
Protection types availableType Settings
L S
Electronic
PR221DS/LS 0.4 -1x In 1-10x In
Thermomagnetic Ith Im
Standard Distribution 70 - 100% 10x Ith*
Plug-in Circuit breakers
To convert fixed pattern device to plug-in pattern:-
1). Select correct Fixed Pattern Device from part numbers above2). Select Conversion Kit from part numbers below3). Add Fixed portion (Base) from part numbers below
Fixed Pattern Circuit Breaker
Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1Supplied as standard with front bar terminals for busbar - for other terminals seeaccessories section pagexx
Plug-in
1SDA0 R1
3 Pole 4 Pole
Conversion Kit 51411 51412
Fixed portion (Base)
Front Copper Cable Terminals** 51329 51330
Icu (415V) Model Current (A) Thermomagnetic PR221DS/LSIth 1SDA0 R1
3 Pole 4 Pole 3 Pole 4 Pole
T2H160R1.6 1.6A 51028 51050 - -
T2H160R2 2A 51029 51051 - -
T2H160R2.5 2.5A 51030 51052 - -
T2H160R3.2 3.2A 51031 51053 - -
T2H160R4 4A 51032 51054 - -
T2H160R5 5A 51033 51055 - -
T2H160R6.3 6.3A 51034 51056 - -
T2H160R8 8A 51035 51057 - -
T2H160R10 10A 51036 51058 51143 51148
70kA T2H160R12.5 12.5A 51037 51059 - -
T2H160R16 16A 51038 51060 - -
T2H160R20 20A 51039 51061 - -
T2H160R25 25A 51040 51062 51144 51149
T2H160R32 32A 51041 51063 - -
T2H160R40 40A 51042 51064 - -
T2H160R50 50A 51043 51065 - -
T2H160R63 63A 51044 51066 51145 51150
T2H160R80 80A 51045 51067 - -
T2H160R100 100A 51046 51068 51146 51151
T2H160R125 125A 51047 51119 - -
T2H160R160 160A 51048 51120 51147 51615
ABB LIMITED 4/13
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
Distribution and Generator Protection MCCBs Tmax T2H (160A)
Ratings @ 415V
Icu Ics
T2H 70kA 100%
Protection types availableType Settings
L S
Electronic
PR221DS/LS 0.4 -1x In 1-10x In
Thermomagnetic Ith Im
Standard Distribution 70 - 100% 10x Ith
Plug-in Circuit breakers
To convert fixed pattern device to plug-in pattern:-
1). Select correct Fixed Pattern Device from part numbers above2). Select Conversion Kit from part numbers below3). Add Fixed portion (Base) from part numbers below
Plug-in
1SDA0 R1
3 Pole 4 Pole
Conversion Kit 51411 51412
Fixed portion (Base)
Front Copper Cable Terminals** 51329 51330
Fixed Pattern Circuit Breaker
Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1Supplied as standard with front bar terminals for busbar - for other terminals seeaccessories section pagexx
ABB LIMITED 4/10
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
Icu (415V) Model Current (A) ThermomagneticIth 1SDA0 R1
1 Pole 3 Pole 4 Pole
T1B160R16 16A 52616 50870 50881
T1B160R20 20A 52617 50871 50882
T1B160R25 25A 52618 50872 50883
T1B160R32 32A 52619 50873 50884
T1B160R40 40A 52620 50874 50885
16kA (25A for T1B160R50 50A 52621 50875 50886
1 pole) T1B160R63 63A 52622 50876 50887
T1B160R80 80A 52623 50877 50888
T1B160R100 100A 52624 50878 50889
T1B160R125 125A 52625 50879 50890
T1B160R160 160A 52626 50880 50936
T1C160R25 25A - 50894 50905
T1C160R32 32A - 50895 50906
T1C160R40 40A - 50896 50907
T1C160R50 50A - 50897 50908
25kA T1C160R63 63A - 50898 50909
T1C160R80 80A - 50899 50910
T1C160R100 100A - 50900 50911
T1C160R125 125A - 50901 50912
T1C160R160 160A - 50902 50937
T1N160R32 32A - 50917 50928
T1N160R40 40A - 50918 50929
T1N160R50 50A - 50919 50930
36kA T1N160R63 63A - 50920 50931
T1N160R80 80A - 50921 50932
T1N160R100 100A - 50922 50933
T1N160R125 125A - 50923 50934
T1N160R160 160A - 50924 50938
Distribution and Generator Protection MCCBs Tmax T1... (160A)
Ratings @ 415V (230V for 1 pole)
Icu Ics Icw(1sec)
T1B (1Pole) 25kA 75%
T1B (3 & 4 Pole) 16kA 100%
T1C 25kA 75%
T1N 36kA 50%
T1D - - 2kA
Protection types availableType Settings
Ith Im
Standard Distribution (1 pole) 100% 10x Ith*
Standard Distribution (3&4 pole)70-100% 10x Ith*
* Subject to a Minimum value of 500A
Fixed Pattern Circuit Breaker
Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1Supplied as standard with front cable terminals for copper cables - for other terminals seeaccessories section pagexx
ABB LIMITED 4/14
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
Icu (415V) Model Current (A) Thermomagetic PR221DS/LSIth 1SDA0 R1
3 Pole 4 Pole 3 Pole 4 Pole
T2L160R1.6 1.6A 51072 51094 - -
T2L160R2 2A 51073 51095 - -
T2L160R2.5 2.5A 51074 51096 - -
T2L160R3.2 3.2A 51075 51097 - -
T2L160R4 4A 51076 51098 - -
T2L160R5 5A 51077 51099 - -
T2L160R6.3 6.3A 51078 51100 - -
T2L160R8 8A 51079 51101 - -
T2L160R10 10A 51080 51102 51153 51158
85kA T2L160R12.5 12.5A 51081 51103 - -
T2L160R16 16A 51082 51104 - -
T2L160R20 20A 51083 51105 - -
T2L160R25 25A 51084 51106 51154 51159
T2L160R32 32A 51085 51107 - -
T2L160R40 40A 51086 51108 - -
T2L160R50 50A 51087 51109 - -
T2L160R63 63A 51088 51110 51155 51160
T2L160R80 80A 51089 51111 - -
T2L160R100 100A 51090 51112 51156 51161
T2L160R125 125A 51091 51121 - -
T2L160R160 160A 51092 51122 51157 51162
Distribution and Generator Protection MCCBs Tmax T2 (160A)
Ratings @ 415V
Icu Ics
T2L 85kA 75%
Protection types availableType Settings
L S
Electronic
PR221DS/LS 0.4 -1x In 1-10x In
Thermomagnetic Ith Im
Standard Distribution 70 - 100% 10x Ith
Plug-in Circuit breakers
To convert fixed pattern device to plug-in pattern:-
1). Select correct Fixed Pattern Device from part numbers above2). Select Conversion Kit from part numbers below3). Add Fixed portion (Base) from part numbers below
Fixed Pattern Circuit Breaker
Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1Supplied as standard with front bar terminals for busbar - for other terminals seeaccessories section pagexx
Plug-in
1SDA0 R1
3 Pole 4 Pole
Conversion Kit 51411 51412
Fixed portion (Base)
Front Copper Cable Terminals** 51329 51330
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
ABB LIMITED 4/15
lcw (1 sec) Model Current (A) 1SDA0 R1
Iu 3 Pole 4 Pole
3.6kA T3D250 250A 51327 51328
Distribution and Generator Protection MCCBs Tmax T3 (250A)
Ratings @ 415V
Icu Ics Icw(1sec)
T3N 36kA 75%
T3S 50kA 50%
T3D - - 3.6kA
Protection types availableType SettingsThermomagnetic Ith Im
Standard Distribution 70-100% 10x Ith*
Fixed Pattern Circuit Breaker Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1Supplied as standard with front bar terminals for busbar - for other terminals seeaccessories section pagexx
Fixed Pattern Switch DisconnectorOrdering example: place five digit code below into order reference eg 1SDA0 39676 R1Supplied as standard with front cable terminals for copper cables - for other terminals seeaccessories section pagexx
Plug-in Circuit breakers
To convert fixed pattern device to plug-in pattern:-
1). Select correct Fixed Pattern Device from part numbers above2). Select Conversion Kit from part numbers below3). Add Fixed portion (Base) from part numbers below
Plug-in
1SDA0 R1
3 Pole 4 Pole
Conversion Kit 51411 51412
Fixed portion (Base)
Front Copper Cable Terminals** 51329 51330
Icu (415V) Model Current (A) ThermomagneticIth 1SDA0 R1
3 Pole 4 Pole
T3N250R63 63A 51241 51252
T3N250R80 80A 51242 51253
T3N250R100 100A 51243 51254
36kA T3N250R125 125A 51244 51303
T3N250R160 160A 51245 51304
T3N250R200 200A 51246 51305
T3N250R250 250A 51247 51306
T3S250R63 63A 51263 51274
T3S250R80 80A 51264 51275
T3S250R100 100A 51265 51276
50kA T3S250R125 125A 51266 51307
T3S250R160 160A 51267 51308
T3S250R200 200A 51268 51309
T3S250R250 250A 51269 51310
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
ABB LIMITED 4/16
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Rotary handle
Locking device
Motor operator
Thermal Magnetic Release
Standard escutcheon
Data plate
DINescutcheon
UVR
Shunt trip
Aux contact
Rear stud terminal
Cable clamp aluminium
Cable clamp copper
Extended bar terminals
Conversion kit from fixed to moving
Position carriage switch
1
2
3
4
5
6
7
8
9
10
22
22
27
27
Isomax Construction CharacteristicsModularity of the series
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
ABB LIMITED 4/17
17
18
19
20
21
22
23
24
25
26
27
Fixed portion terminal shrouds
Rear cable connections
Rear bolt connections
Door closing racking device
Carriage locking device
Long terminal shrouds
Plug-in tulip contacts
Shunt trip + UVR female socket
Aux connections plug-in / drawout
Female sockets for fixed breaker
Short terminal shrouds
11
12
13
14
15
16
1718
19
20
21
23
24
25
26
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
LI1 (0.4 ... 1xIn)t1 = 3 ... 18s
SI2 (1 ... 10 OFF x In)t2 = 0.05 ... 0.5s
II3 (1.5 ... 12 OFF x In)
GI4 (0.2 ... 1 OFF x In)t4 = 0.01 ... 0.8s
In
S4 100160250
S5 320400
S6 630800
S7 100012501600
ABB LIMITED 4/18
L
I1 (0.4 ... 1xIn)t1 = 3 ... 18s
I
I3 (1.5 ... 12 x In)
PR211/P PR212/P
In
S4 100160250
S5 320400
S6 630800
S7 100012501600
Isomax Electronic Releases
L
S
I
CANNOT BEEXCLUDED
CAN BEEXCLUDED
CAN BEEXCLUDED
Against overload with inverse long time delay and trip characteristicaccording to a time dependent curve (I2t = constant)
Against short-circuit with adjustable instantaneous trip
GCAN BE
EXCLUDED
Against earth fault with short inverse time delay and trip characteris-tic according to a dependent time curve (I2t = constant)
Against short-circuit with inverse short time delay and tripcharacteristic with dependent time (I 2t = constant) independent
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
ABB LIMITED 4/19
Isomax Thermomagnetic Releases
The thermomagnetic releases which equip the SACES3 circuit-breakers have the thermal element withthreshold adjustable from 0.7 ÷ 1 x In. The regulated current value which is obtained by using the appropri-ate selector must be intended as the rated value at 40ºC. The magnetic element has fixed trip threshold,with trip values which may vary according to the phase setting.
The thermomagnetic releases which equip SACE S5 and S6 circuit-breakers have the thermal element withthreshold adjustable from 0.7 ÷ 1 x In. The regulated current value which is obtained by using the appro-proate selector must be intended as the rated value at 40ºC. The magnetic element can be adjusted from5 ÷ 10 x In. The table gives the maximum magnetic trip values (10 x In) for protection of the phases (L1 -L2 - L3) and of the neutral.
S3
S5/6
ABB LIMITED 4/20
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
Icu (415V) Model Current (A) Standard Low Threshold GeneratorIth 1SDA0 R1
3 Pole 4 Pole 3 Pole 4 Pole 3 Pole 4 Pole
S3N160R32 32A 13346 13371 13359 13383 - -
S3N160R50 50A 13348 13373 13361 13385 - -
S3N160R80 80A 13350 13375 13363 13387 - -
35kA S3N160R100 100A 13352 13377 13365 13389 48539 48549
S3N160R125 125A 13354 13379 13367 13391 48540 48550
S3N160R160 160A 13356 13381 13369 13393 48541 48551
S3N250R200 200A 13491 13499 13495 13503 48545 48555
S3N250R250 250A 13493 13501 13497 13505 48546 48556
S3H160R32 32A 13395 13419 13407 13431 - -
S3H160R50 50A 13397 13421 13409 13433 - -
S3H160R80 80A 13399 13423 13411 13435 - -
65kA S3H160R100 100A 13401 13425 13413 13437 48542 48552
S3H160R125 125A 13403 13427 13415 13439 48543 48553
S3H160R160 160A 13405 13429 13417 13441 48544 48554
S3H250R200 200A 13507 13515 13511 13519 48547 48557
S3H250R250 250A 13509 13517 13513 13521 48548 48558
Distribution and Generator Protection MCCBs Isomax S3 (250A)
Ratings @ 415V
Icu Ics Icw (1sec)
S3N 35kA 100%
S3H 65kA 75%
S3L 85kA 75%
S3D - - 6.5kA
Fixed Pattern Circuit Breaker
Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1Supplied as standard with front bar terminals for busbar - for other terminals seeaccessories section pagexx
ABB LIMITED 4/21
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
Icu (415V) Model Current (A) Standard Low ThresholdIth 1SDA0 R1
3 Pole 4 Pole 3 Pole 4 Pole
S3L160R32 32A 13443 13467 13455 13479
S3L160R50 50A 13445 13469 13457 13481
S3L160R80 80A 13447 13471 13459 13483
85kA S3L160R100 100A 13449 13473 13461 13485
S3L160R125 125A 13451 13475 13463 13487
S3L160R160 160A 13453 13477 13465 13489
S3L250R200 200A 13523 13531 13527 13535
S3L250R250 250A 13525 13533 13529 13537
lcw (1 sec) Model Current (A) 1SDA0 R1
Iu 3 Pole 4 Pole
S3D100 100A 20906 20907
6.5kA S3D100 160A 20908 20909
S3D250 250A 20910 20911
Distribution and Generator Protection MCCBs Isomax S3 (250A)
Fixed Pattern Circuit Breaker Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1Supplied as standard with front bar terminals for busbar - for other terminals seeaccessories section pagexx
Plug-in / Withdrawable Circuit breakers / Disconnectors
To convert fixed pattern device to plug-in or withdrawable pattern:-
1). Select correct Fixed Pattern Device from part numbers above2). Select Conversion Kit from part numbers below3). Add Fixed portion (Base) from part numbers below
Protection types availableType Settings
Ith Im
Standard Distribution 70-100% 10xIth
Low Threshold Thermomagnetic 70-100% 5xIth
Generator Thermomagnetic 70-100% 3xIth
Fixed Pattern Switch Disconnector
Plug-in Withdrawable
1SDA0 R1 1SDA0 R1
3 Pole 4 Pole 3 Pole 4 Pole
Conversion Kit 13608 13609 13610 13611
Fixed portion (Base)
Front Copper Cable Terminals 13543 13550 13559 13568
Extended Front bar Terminals 13539 13548 13555 13564
Threaded Rear Terminals 13547 13554 13563 13572
ABB LIMITED 4/22
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
Icu (415V) Model Current (A) Protection PR211 PR212
In 1SDA0 R1 1SDA0 R1
3 Pole 4 Pole 3 Pole 4 Pole
LI 15550 15838 - -
35kA S4N160R100 100A LSI - - 15553 15841
LSIG - - 15558 15846
LI 15551 15839 - -
35kA S4N160R160 160A LSI - - 15554 15842
LSIG - - 15559 15847
LI 17319 17385 - -
35kA S4N250R250 250A LSI - - 17320 17386
LSIG - - 17323 17389
LI 16144 16426 - -
65kA S4H160R100 100A LSI - - 16146 16428
LSIG - - 16152 16434
LI 16145 16427 - -
65kA S4H160R100 160A LSI - - 16147 16429
LSIG - - 16153 16435
LI 17451 17517 - -
65kA S4H250R250 250A LSI - - 17452 17518
LSIG - - 17455 17521
Distribution and Generator Protection MCCBs Isomax S4 (250A)
Ratings @ 415V
Icu Ics
S4N 35kA 100%
S4H 65kA 100%
S4L 100kA 75%
Fixed Pattern Circuit Breaker Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1Supplied as standard with front bar terminals for busbar - for other terminals seeaccessories section pagexx
ABB LIMITED 4/23
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
Icu (415V) Model Current (A) Protection PR211 PR212
In 1SDA0 R1 1SDA0 R13 Pole 4 Pole 3 Pole 4 Pole
LI 16732 17014 - -
100kA S4L160R100 100A LSI - - 16734 17016
LSIG - - 16740 17022
LI 16733 17015 - -
100kA S4L160R160 160A LSI - - 16735 17017
LSIG - - 16741 17023
LI 17583 17649 - -
100kA S4L250R250 250A LSI - - 17584 17650
LSIG - - 17587 17653
Fixed Pattern Circuit Breaker Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1Supplied as standard with front bar terminals for busbar - for other terminals see accessories section pagexx
Distribution and Generator Protection MCCBs Isomax S4 (250A)
Plug-in Withdrawable
1SDA0 R1 1SDA0 R1
3 Pole 4 Pole 3 Pole 4 Pole
Conversion Kit 13608 13609 13610 13611
Fixed portion (Base)
Front Copper Cable Terminals 13616 13625 13634 13643
Extended Front bar Terminals 13612 13621 13630 13639
Threaded Rear Terminals 13620 13629 13638 13647
Plug-in / Withdrawable Circuit breakers / Disconnectors
To convert fixed pattern device to plug-in or withdrawable pattern:-
1). Select correct Fixed Pattern Device from part numbers above2). Select Conversion Kit from part numbers below3). Add Fixed portion (Base) from part numbers below
Protection types availableElectronic (ac only)
Type SettingsL S I G
PR211/LI 0.4-1x In - 1.5-12x In -
PR212/LSI 0.4-1x In 1-10x In 1.5-12x In
PR212/LSIG 0.4-1x In 1-10xIn 1.5-12x In 0.2-1x In
ABB LIMITED 4/24
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
Icu (415V) Model Current (A) Protection PR211 PR212Ith 1SDA0 R1
3 Pole 4 Pole 3 Pole 4 Pole 3 Pole 4 Pole
T/Mag 38438 38440 - - - -
35kA S5N400R320 320ALI - - 17716 17848 - -
LSI - - - - 17718 17850
LSIG - - - - 17724 17856
T/Mag 38439 38441 - - - -
35kA S5N400R400 400ALI - - 17717 17849 - -
LSI - - - - 17719 17851
LSIG - - - - 17725 17857
T/Mag 38678 38683 - - - -
35kA S5N630R500 500ALI - - - - - -
LSI - - - - - -
LSIG - - - - - -
T/Mag - - - - - -
35kA S5N630R630 630ALI - - 38675 38680 - -
LSI - - - - 38676 38681
LSIG - - - - 38677 38682
T/Mag 38522 38524 - - - -
65kA S5H400R320 320ALI - - 17992 18124 - -
LSI - - - - 17994 18126
LSIG - - - - 18000 18132
T/Mag 38523 38525 - - - -
65kA S5H400R400 400ALI - - 17993 18125 - -
LSI - - - - 17995 18127
LSIG - - - - 18001 18133
T/Mag 38708 38713 - - - -
65kA S5H630R500 500ALI - - - - - -
LSI - - - - - -
LSIG - - - - - -
T/Mag - - - - - -
65kA S5H630R630 630ALI - - 38705 38710 - -
LSI - - - - 38706 38711
LSIG - - - - 38707 38712
Distribution and Generator Protection MCCBs Isomax S5 (630A)
Ratings @ 415V
Icu Ics Icw (1sec)*
S5N 35kA 100% 5kA
S5H 65kA 100% 5kA
S5L 100kA 75% 5kA
*400A only
Fixed Pattern Circuit Breaker Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1Supplied as standard with front bar terminals for busbar - for other terminals seeaccessories section pagexx
Thermomagnetic
ABB LIMITED 4/25
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
Distribution and Generator Protection MCCBs Isomax S5 (630A)
Icu (415V) Model Current (A) Protection PR211 PR212Ith 1SDA0 R1
3 Pole 4 Pole 3 Pole 4 Pole 3 Pole 4 Pole
T/Mag 38606 38608 - - - -
100kA S5L400R320 320ALI - - 18256 18388 - -
LSI - - - - 18258 18390
LSIG - - - - 18264 18396
T/Mag 38607 38609 - - - -
100kA S5L400R400 400ALI - - 18257 18389 - -
LSI - - - - 18259 18391
LSIG - - - - 18265 18397
T/Mag 38740 38745 - - - -
100kA S5L630R500 500ALI - - - - - -
LSI - - - - - -
LSIG - - - - - -
T/Mag - - - - - -
100kA S5L630R630 630ALI - - 38737 38742 - -
LSI - - - - 38738 38743
LSIG - - - - 38739 38744
Protection types availableElectronic L S I G
Type Settings
PR211/LI 0.4-1x In - 1.5-12x In -
PR212/LSI 0.4-1x In 1-10x In 1.5-12x In -
PR212/LSIG 0.4-1x In 1-10x In 1.5-12x In 0.2-1x In
Thermomagnetic Ith Im
Standard Distribution 70-100% 5-10x Ith
Thermomagnetic
400A 400A 630A plug-in withdrawable withdrawable
1SDA0 R1
3 Pole 4 Pole 3 Pole 4 Pole 3 Pole 4 Pole
Conversion Kit 13716 13717 13718 13719 38778 38779
Fixed portion (Base)
Front Copper Cable Terminals (400A) 13724 13733 13742 13751 - -
Extended Front bar Terminals 13720 13729 13738 13747 - -
Spreaded Ext Front bar Terminals - - - - 38761 38762
Threaded Rear Terminals 13728 13737 13746 13755 38763 38970
Vertical Flat bar Terminals - - - - 38971 38972
Plug-in / Withdrawable Circuit breakers / Disconnectors
To convert fixed pattern device to plug-in or withdrawable pattern:-
1). Select correct Fixed Pattern Device from part numbers above2). Select Conversion Kit from part numbers below3). Add Fixed portion (Base) from part numbers below
Fixed Pattern Circuit Breaker Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1Supplied as standard with front bar terminals for busbar - for other terminals seeaccessories section pagexx
ABB LIMITED 4/26
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
Fixed Pattern Circuit Breaker Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1Supplied as standard with front bar terminals for busbar - for other terminals seeaccessories section pagexx
Distribution and Generator Protection MCCBs Isomax S6 (800A)
Icu (415V) Model Current (A) Thermomagnetic PR211 PR212Ith 1SDA0 R1
3 Pole 4 Pole 3 Pole 4 Pole 3 Pole 4 Pole
T/Mag 38787 38788 - - - -
35kA S6N630R630 630ALI - - 18519 18573 - -
LSI - - - - 18520 18574
LSIG - - - - 18523 18577
T/Mag 38871 38872 - - - -
35kA S6N800R800 800A LI - - 18951 19005 - -
LSI - - - - 18952 19006
LSIG - - - - 18955 19009
T/Mag 38799 38800 - - - -
50kA S6S630R630 630ALI - - 18627 18681 - -
LSI - - - - 18628 18682
LSIG - - - - 18631 18685
T/Mag 38883 38884 - - - -
50kA S6S800R800 800ALI - - 19059 19113 - -
LSI - - - - 19060 19114
LSIG - - - - 19063 19117
T/Mag 38823 38824 - - - -
65kA S6H630R630 630ALI - - 18735 18789 - -
LSI - - - - 18736 18790
LSIG - - - - 18739 18793
T/Mag 38907 38908 - - - -
65kA S6H800R800 800ALI - - 19167 19221 - -
LSI - - - - 19168 19222
LSIG - - - - 19171 19225
Ratings @ 415V
Icu Ics Icw (1sec)
S6D - - 15kA
S6N 35kA 100% 7.6kA (630A) 10kA (800A)
S6S 50kA 100% 7.6kA (630A) 10kA (800A)
S6H 65kA 100% 7.6kA (630A) 10kA (800A)
S6L100kA 75% 7.6kA (630A) 10kA (800A)
ABB LIMITED 4/27
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
lcw (1 sec) Model Current (A)
Iu 1SDA0 R1
3 Pole 4 Pole
S6D400 400A 20545 20581
15kA S6D630 630A 20674 20699
S6D800 800A 20724 20749
1SDA0 R1
Withdrawable 3 Pole 4 Pole
Conversion Kit 13962 13963
Fixed portion (Base)
Extended Front bar Terminals 13964 13973
Horizontal Flat bar Terminals 13968 13977
Vertical Flat bar Terminals 13972 13981
Fixed Pattern Circuit Breaker Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1Supplied as standard with front bar terminals for busbar - for other terminals see accessories section pagexx
Icu (415V) Model Current (A) Thermomagnetic PR211 PR212Ith 1SDA0 R1
3 Pole 4 Pole 3 Pole 4 Pole 3 Pole 4 Pole
T/Mag 38847 38848 - - - -
100kA S6L630R630 630ALI - - 18843 18897 - -
LSI - - - - 18844 18898
LSIG - - - - 18847 18901
T/Mag 38931 38932 - - - -
100kA S6L800R800 800ALI - - 19275 19329 - -
LSI - - - - 19276 19330
LSIG - - - - 19279 19333
Distribution and Generator Protection MCCBs Isomax S6 (800A)
Fixed Pattern Switch Disconnector
Withdrawable Circuit breakers
To convert fixed pattern device to withdrawable pattern:-1). Select correct Fixed Pattern Device from part numbers above2). Select Conversion Kit from part numbers below3). Add Suitable Fixed portion (Base) from part numbers belowSpecial Notes: a).Withdrawable devices must be fitted with a front plate accessory such as:
Motor operatorPadlock DeviceRotary Handle
c). Remember to use accessories suitable for withdrawable pattern devices
Protection types availableElectronic L S I G
Type Settings
PR211/LI 0.4-1x In - 1.5-12x In -
PR212/LSI 0.4-1x In 1-10x In 1.5-12x In -
PR212/LSIG 0.4-1x In 1-10x In 1.5-12x In 0.2-1x In
Thermomagnetic Ith Im
Standard Distribution 70-100% 5-10x Ith
ABB LIMITED 4/28
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
Fixed Pattern Circuit Breaker Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1Supplied as standard with front bar terminals for busbar - for other terminals see accessories section pagexx
Distribution and Generator Protection MCCBs Isomax S7 (1250A)
Icu (415V) Model Current (A) Protection PR211 PR212In 1SDA0 R1
3 Pole 4 Pole 3 Pole 4 Pole
LI 19384 19492 - -
50kA S7S1250R1000 1000A LSI - - 19386 19494
LSIG - - 19392 19500
LI 19385 19493 - -
50kA S7S1250R1250 1250A LSI - - 19387 19495
LSIG - - 19393 19501
LI 20031 20073 - -
50kA S7S1600R1600 1600A LSI - - 20032 20074
LSIG - - 20035 20077
LI 19600 19708 - -
65kA S7H1250R1000 1000A LSI - - 19602 19710
LSIG - - 19608 19716
LI 19601 19709 - -
65kA S7H1250R1250 1250A LSI - - 19603 19711
LSIG - - 19609 19717
LI 20115 20157 - -
65kA S7H1600R1600 1600A LSI - - 20116 20158
LSIG - - 20119 20161
Ratings @ 415V
Icu Ics Icw (1sec)
S7S 50kA 100% 15kA (1250A) 20kA (1600A)
S7H 65kA 75% 15kA (1250A) 20kA (1600A)
S7L 100ka 50% 15kA (1250A) 20kA (1600A)
S7D - - 25kA
ABB LIMITED 4/29
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
lcw (1 sec) Model Current (A)
Iu 1SDA0 R1
3 Pole 4 Pole
S7D1000 1000A 20774 20799
25kA S7D1250 1250A 20824 20849
S7D1600 1600A 20874 20890
Distribution and Generator Protection MCCBs Isomax S7 (1250A)
Icu (415V) Model Current (A) Protection PR211 PR212In 1SDA0 R1
3 Pole 4 Pole 3 Pole 4 Pole
LI 19816 19924 - -
100kA S7L1250R1000 1000A LSI - - 19818 19926
LSIG - - 19824 19932
LI 19817 19925 - -
100kA S7L1250R1250 1250A LSI - - 19819 19927
LSIG - - 19825 19933
LI 20199 20241 - -
100kA S7L1600R1600 1600A LSI - - 20200 20242
LSIG - - 20203 20245
Fixed Pattern Circuit Breaker Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1Supplied as standard with front bar terminals for busbar - for other terminals see accessories section pagexx
Fixed Pattern Switch Disconnector
Withdrawable Circuit breakers
To convert fixed pattern device to withdrawable pattern:-1). Select correct Fixed Pattern Device from part numbers above2). Select Conversion Kit from part numbers below3). Add Suitable Fixed portion (Base) from part numbers belowSpecial Notes: a).Withdrawable devices must be fitted with a front plate accessory such as:
Motor operatorPadlock DeviceRotary Handle
c). Remember to use accessories suitable for withdrawable pattern devices
Protection types availableElectronic L S I G
Type Settings
PR211/LI 0.4-1x In 1.5-12x In
PR212/LSI 0.4-1x In 1-10xIn 1.5-12x In
PR212/LSIG 0.4-1x In 1-10x In 1.5-12x In 0.2-1x In
1SDA0 R1
Withdrawable 3 Pole 4 Pole
Conversion Kit 23299 14087
Fixed portion (Base)
Extended Front bar Terminals 48951 14097
Horizontal Flat bar Terminals 14092 14101
Vertical Flat bar Terminals 14096 14105
ABB LIMITED 4/30
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
Accessories Tmax T1, T2 and T3
a) b) c)
1). Electrical Accessories
a). Shunt Opening Releases ( cabled version)
AC Voltage 1SDA0 R1 DC Voltage 1SDA0 R1
12V DC 53001
24…30 AC 51339 24…30V DC 51339
48…60V AC 51340 48…60V DC 51340
110…127V AC 51341 110…125V DC 51341
220…240V AC 51342 220…250V DC 51342
380…440V AC 51343
480…500V AC 51344
b). Undervoltage Release (UVR) (cabled Version)
AC Voltage 1SDA0 R1 DC Voltage 1SDA0 R1
24…30V AC 51351 24…30V DC 51351
48V AC 51352 48V DC 51352
60V AC 52335 60V DC 52335
110…127V AC 51353 110…127V DC 51353
220…240V AC 51354 220…250V DC 51354
380…440V AC 51355
480…500V AC 51356
c). Time lag device for UVR (UVD)
AC Voltage 1SDA0 R1 DC Voltage 1SDA0 R1
24V AC 51357 24V DC 51357
48V AC 51358 48V DC 51358
60V AC 51359 60V DC 51359
110…125V AC 51360 110…125V DC 51360
220…250V AC 51361 220…250V DC 51361
ABB LIMITED 4/31
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
1). Electrical Accessories cont....
d). Solenoid operator (inc padlock device)
Voltage 1SDA0 R1 1SDA0 R1Front Fitting Side by Side
48…60V DC 51376 51379
110…250V AC 51377 51380
e). Auxiliary Contacts (cabled version)
ON/OFF Tripped Release Breaker Protection 1SDA0 R1(c/o) Position (c/o) Tripped (c/o) Type
1 1 Thermomagnetic 51370
1 1 1 Electronic 53704
3 1 Thermomagnetic 51371
f). Residual - current releases
RC221 and RC222 addon blocks
Breakers must be fitted with Front cable terminals for copper cables on lower terminals( Terminal kit supplied with RCD addon kit for T2 and T3)
1SDA0 R1 1SDA0 R1
Breaker Type RC221 RC222
3 Pole 4 Pole 3 Pole 4 Pole
T1 51398 51401 51400 51402
T2 51403 51405 51404 51406
T3 51407 51409 51408 51410
Accessories Tmax T1, T2 and T3
e)d)
ABB LIMITED 4/32
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
2). Mechanical Accessories
a). Direct Mounted Rotary Handles (RHD)
For Fixed/Plug-in devices - Grey/White 1SDA051381R1
For Fixed/Plug-in devices - Red/Yellow 1SDA051382R1
b). Door Mounted Rotary Handles (complete with transmission rod Lmax = 300mm) (RHE)
• Adjustable depth• Padlockable• Complete with Door Interlock ( defeatable)
For Fixed/Plug-in devices - Grey/White 1SDA051383R1
For Fixed/Plug-in devices - Red/Yellow 1SDA051384R1
500mm transmission rod 1SDA051386R1
Optional Keylock 1SDA051389R1
IP54 Gasket 1SDA051392R1
c). Padlock Lever lock (PLL)
Padlock in OPEN Position 1SDA051393R1
Padlock in OPEN/CLOSED 1SDA051394R1
d). Mechanical Interlock across Two/ Three circuit breakers (MIF)
Between 2 circuit breakers 1SDA051396R1
Between 3 Circuit Breakers 1SDA052165R1
Accessories Tmax T1, T2 and T3
ABB LIMITED 4/33
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
2). Mechanical Accessories Cont....
e). Terminals for fixed pattern MCCBs and Plug-in Bases
1SDA0 R1
Terminal Type T1 T2 T3
6 pieces 8 pieces 6 pieces 8 pieces 6 pieces 8 pieces
Extended Front (EF) 51440 51441 51464 51465 51488 51489
Spreaded Extended (ES) - - 51468 51469 51492 51493
Rear Terminals (R) - - 51472 51473 51496 51497
Copper Front Cable terminals (FC Cu): Std Std 51452 51453 51480 51481
Cu/Al Front Cable terminals (FC CuAl):
1x95mm2 External 51444 51445 - - - -
1x95mm2 Internal - - 51456 51457 - -
1x185mm2 External - - 51460 51461 - -
1x185mm2 Internal - - - - 51484 51485
140…240mm2 External - - - - 51942 51943
f). Terminal covers
1SDA0 R1
MCCB No of poles High Low
T13 poles 51415 51421
4 poles 51416 51422
T23 poles 51417 51423
4 poles 51418 51424
T33 poles 51419 51425
4 poles 51420 51426
g). Separating Partitions (PB)
Height Qty 1SDA0 R1
100mm 4 51427
100mm 6 51428
200mm 4 51429
200mm 6 51430
Accessories Tmax T1, T2 and T3
ABB LIMITED 4/34
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
Accessories Isomax S3, S4 and S5
1). Electrical Accessories
a). Shunt TripAC Voltage 1SDA0 R1 DC Voltage 1SDA0 R1
12V DC 23403
24V AC 13781 24V DC 13781
48V AC 13782 48V DC 13782
60V AC 23405 60…72V DC 23405
110…120V AC 13783 110…125V DC 13783
220…240V AC 13785 220…250V DC 13785
380…400V AC 13786
480V AC 37512
Wiring Connector: Fixed pattern devices 13865
Wiring Connector: Plug-in/Withdrawable devices 13866
b). Undervoltage Release (UVR)AC Voltage 1SDA0 R1 DC Voltage 1SDA0 R1
24V AC 13842 24V DC 13833
48V AC 13843 48V DC 13835
60V AC 23346 60V DC 13836
110…127V AC 13844 110…125V DC 13838
220…250V AC 13846 220…250V DC 13839
380…440V AC 13847
480V AC 37513
Wiring Connector: Fixed pattern devices 13865
Wiring Connector: Plug-in/Withdrawable devices 13866
c). UVR + Time Lag Device 1SDA0 R1
UVR + Delay: S3/S5 Input voltage 110…220V AC only 13840
UVR + Delay: S6/S7 Input voltage 110…220V AC only 14186
Wiring Connector: Fixed pattern devices 13865
Wiring Connector: Plug-in/Withdrawable devices 13866
a) b) c)
ABB LIMITED 4/35
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
Accessories Isomax S3, S4 and S5
d). Direct acting Motor operator (inc padlock device)AC Voltage 1SDA0 R1 DC Voltage 1SDA0 R1
110…127V AC 13875 24V DC 13873
220…240V AC 13876 48…60V DC 13874
380V AC 13877 110…125V DC 13875
440V AC 14545 220...250V DC 13876
e). Auxiliary ContactsON/OFF (c/o) Tripped position (c/o) Signal type 1SDA0 R1
1 1 Analogue (>24V) 13575
1 1 Digital (<24V) 25545
2 0 Analogue (>24V) 13856
2 0 Digital (<24V) 25544
Wiring connector when fitting motor & auxiliary contacts:
Fixed pattern devices 13857
Plug-in/Withdrawable devices 13858
Wiring connector when fitting auxiliary contacts only:
Fixed pattern devices 13863
Plug-in/Withdrawable devices 13864
d) e)
ABB LIMITED 4/36
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
1). Electrical Accessories cont....
f). Protection Release Trip SignalX3/X4 ConnectorPattern Protection Type 1SDA0 R1
PR211/LI 13702
Fixed pattern PR212/LSI 13704
PR212/LSIG 13704
PR211/LI 13703
Plug-in/Withdrawable PR212/LSI 13705
PR212/LSIG 13705
g). External Neutral Current TransformerMCCB Current Rating 1SDA0 R1
100A 37114
S4 160A 37115
250A 37117
320A 37118
S5 400A 37119
630A 37120
Connector for Neutral CTPattern Protection Type 1SDA0 R1
PR211/LI 13702
Fixed pattern PR212/LSI 13704
PR212/LSIG 13704
PR211/LI 13703
Plug-in/Withdrawable PR212/LSI 13705
PR212/LSIG 13705
h). Residual-current release RC211 and RC212Type Vertical Mount Side/side Mount
1SDA0 R1
RC211-S3 20289 20288
RC212-S3 20291 20290
RC211 and RC212 add on blocks for S3 breakerFitting by our workshop is recommended4 pole circuit breaker/switch disconnector required
Accessories Isomax S3, S4 and S5
ABB LIMITED 4/37
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
Accessories Isomax S3, S4 and S5
2). Mechanical Accessories
a). Direct Mounted Rotary Handles1SDA0 R1
For Fixed/Plug-in devices - Grey/White 13867
For Fixed/Plug-in devices - Red/Yellow 13870
For Withdrawable devices - Grey/White 13868
b). Door Mounted Rotary Handles ( complete with transmission rod Lmax = 300mm)
Adjustable depth, Padlockable, complete with Door Interlock ( defeatable) 1SDA0 R1
For Fixed/Plug-in devices - Grey/White 13869
For Fixed/Plug-in devices - Red/Yellow 13871
For Withdrawable devices - Grey/White 50714
500mm transmission rod 25427
Optional Keylock 13881
IP54 Gasket 13891
c). Front Flange
Padlockable 1SDA0 R1
Fixed/ Plug-in devices 13889
Withdrawable devices 13890
Optional Keylock 13881
d). Mechanical Interlock across two circuit breakers
MCCB Horizontal Vertical1SDA0 R1
S3 23330 23331
S4 13690 13691
S5 43453 43454
S3X 50524 -
S4X 50525 -
ABB LIMITED 4/38
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
Accessories Isomax S3, S4 and S5
2). Mechanical Accessories Cont....
e). Terminal for Fixed Pattern MCCBs
Terminal kits consist of 6 or 8 pieceskits of 3 or 4 pieces are available - consult technical catalogue for order references
Terminal Type Max 1SDA0 R1Current S3 S4 S5
6 pcs 8 pcs 6 pcs 8 pcs 6 pcs 8 pcs
Extended Front (EF)250A 13596 13597 13596 13597 - -
400A - - - - 13706 13707
Spreaded Extended (ES) 46515 46516 46515 46516 47549 47550
250A 13606 13607 13606 13607 - -
Threaded rear stud (R) 400A - - - - 13714 13715
630A - - - - 38968 38775
250A 13598 13599 13598 13599 - -
Copper Front Cable terminals (FC Cu) 400A - - - - 13708 13709
630A - - - - 38767 38768
Cu/Al Front Cable terminals (FC CuAl) :
1x95mm2
160A 13602 13603 13602 13602 - -
1x150mm2
250A 20293 20294 20293 20294 - -
2x120mm2
400A - - - - 23295 23296
1x240mm2
400A - - - - 13710 13711
Cu/Al Rear cable terminals (RC CuAl)
1x120mm2
250A 13604 13605 13604 13605 - -
1x240mm2
400A - - - - 13712 13713
ABB LIMITED 4/39
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
2). Mechanical Accessories Cont....
f). Terminals for Plug-in and Withdrawable Bases
Terminal kits consist of 6 or 8 pieces
Terminal Type Max Current 1SDA0 R1S3 S4 S5
6 pcs 8 pcs 6 pcs 8 pcs 6 pcs 8 pcs
250A 13650 13651 13650 13651 - -
Extended Front (EF) 400A - - - - 13759 13760
630A - - - - 38780 38781
250A 13654 13655 13654 13655 - -
Threaded rear stud (R) 400A - - - - 13763 13764
630A - - - - 38969 38782
Cu/Al Front Cable terminals (FC CuAl) :250A 13652 13653 13652 13653 - -
400A - - - - 13760 13762
Vertical Flat Bar terminals (VR) 630A - - - - 38763 38784
g). Terminal Covers
Types available
High: For fixed pattern devices
Low: For Fixed pattern devices and for Moving parts of Plug-in and Withdrawable devices
FP High: For Plug-in and Withdrawable Bases
1SDA0 R1
MCCB No of poles High Low FP High
S33 poles 13695 13693 13697
4 poles 13696 13694 13698
S43 poles 13695 13693 13697
4 poles 13696 13694 13698
S53 poles 13897 13895 13899
4 poles 13898 13896 13900
Accessories Isomax S3, S4 and S5
ABB LIMITED 4/40
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
Accessories Isomax S6 and S7
1). Electrical Accessories
a). Shunt Trip
AC Voltage 1SDA0 R1 DC Voltage 1SDA0 R1
12V DC 23404
24V AC 14136 24V DC 14136
48V AC 14137 48V DC 14137
60V AC 23406 60…72V DC 23406
110…120V AC 14138 110…125V DC 14138
220…240V AC 14140 220…250V DC 14140
380…400V AC 14141
480V AC 37512
Shunt trip Wiring Connector
Fixed pattern devicesS6 13865
S7 14209
Plug-in/WithdrawableS6 13866
S7 14210
b). Undervoltage Release (UVR)
AC Voltage 1SDA0 R1 DC Voltage 1SDA0 R1
24V AC 14188 24V DC 14179
48V AC 14189 48V DC 14181
60V AC 23347 60V DC 14182
110…127V AC 14190 110…125V DC 14184
220…250V AC 14192 220…250V DC 14185
380…440V AC 14193
480V AC 37515
UVR Wiring Connector
Fixed pattern devicesS6 13865
S7 14209
Plug-in/Withdrawable S6 13866
S7 14210
a) b)
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
ABB LIMITED 4/41
Distribution and Generator Protection MCCBs Accessories Isomax S6 and S7
1). Electrical Accessories cont...
c). UVR + Time Lag Device1SDA0 R1
UVR + Delay: Input voltage 110…220V AC only 14186
Wiring Connector:
Fixed pattern devicesS6 13865
S7 14209
Plug-in/Withdrawable S6 13866
S7 14210
d). Stored Energy Motor operator
AC Voltage 1SDA0 R1 DC Voltage 1SDA0 R1
S6 S7 S6 S7
24V DC 14029 14214
48V DC 14030 14215
60V DC 23348 23350
110…127V AC 14031 14216 110…125V DC 14031 14216
220…250V AC 14032 14217 220…250V DC 14032 14217
380V AC 14033 14218
Motor Op Wiring Connector
Fixed pattern devicesS6 13857
S7 14203
Plug-in/Withdrawable S6 13858
S7 14204
Optional Keylock
Lock against manual and electrical operation S6/S7 13885
c)
d)
ABB LIMITED 4/42
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
Distribution and Generator Protection MCCBs Accessories Isomax S6 and S7
1). Electrical Accessories cont....
e). Auxiliary Contacts
On/Off Tripped pos On/Off Tripped position Signal type(c/o) (c/o) (1no & 1nc) (no) 1SDA0 R1
1 1 Analogue (>24V) 23332
1 1 Digital (<24V) 25775
2 0 Analogue (>24V) 23366
2 0 Digital (<24V) 25774
1 1 Analogue (>24V) 48956
1 1 Digital (<24V) -
Wiring connector when fitting motor & and auxiliary contacts:
Fixed pattern devicesS6 13857
S7 14203
Plug-in/Withdrawable S6 13858
S7 14204
Wiring connector when fitting auxiliary contacts only:
Fixed pattern devices S6 13863
S7 14207
Plug-in/Withdrawable S6 13864
S7 14208
f). Protection Release Trip Signal
X3/X4 ConnectorPattern Protection Type
PR211/LI 13702
Fixed pattern PR212/LSI 13704
PR212/LSIG 13704
PR211/LI 13703
Plug-in/Withdrawable PR212/LSI 13705
PR212/LSIG 13705
e)
ABB LIMITED 4/43
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
1). Electrical Accessories Cont....
g). External Neutral Current Transformer
MCCB Current Rating 1SDA0 R1
S6630A 25777
800A 25778
1000A 25779
S7 1250A 25780
1600A 25781
X3/X4 ConnectorPattern Protection Type 1SDA0 R1
PR211/LI 13702
Fixed pattern PR212/LSI 13704
PR212/LSIG 13704
PR211/LI 13703
Plug-in/Withdrawable PR212/LSI 13705
PR212/LSIG 13705
2). Mechanical Accessories
a). Direct Mounted Rotary Handles
1SDA0 R1
TypeColour S6 S7
For Fixed/Plug-in devicesGrey/White 14026 14211
Red/Yellow 14027 14212
For Withdrawable devices - Grey/White Grey/White 46568 46570
b). Door Mounted Rotary Handles ( complete with transmission rod Lmax = 500mm)
Adjustable depth padlockable, complete with door interlock ( defeatable) 1SDA0 R1Type Colour S6 S7
For Fixed/Plug-in devices Grey/White 14028 14213
Red/Yellow 46569 46572
For Withdrawable devices - Grey/White Grey/White 50715 50716
Optional Keylock 13881
IP54 Gasket 13891
c). Front Flange1SDA0 R1
Padlockable S6 S7
Fixed/ Plug-in devices 14035 14227
Withdrawable devices 14036 14228
Optional Keylock 13881
Distribution and Generator Protection MCCBs Accessories Isomax S6 and S7
ABB LIMITED 4/44
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
Accessories Isomax S6 and S7
2). Mechanical Accessories Cont....
d). Mechanical Interlock across two circuit breakers
MCCB Horizontal Vertical1SDA0 R1
S6 14024 14025
S7 14205 14206
e). Terminals for fixed pattern MCCBs
Terminal kits consist of 6 or 8 pieceskits of 3 or 4 pieces are available - consult technical catalogue for order references
Terminal Type Max Current1SDA0 R1
S6 S7
6 pcs 8 pcs 6 pcs 8 pcs
630A 13920 13921 - -
Extended Front (EF) 800A 13954 13955 - -
1600A - - 14079 14080
Spreaded Extended (ES) 1600A - - 50690 50691
Threaded rear stud (R) 800A 13960 13961 - -
Cu/Al Front Cable terminals (FC CuAl)
2x240mm2 630A 13922 13923 - -
3x185mm2 800A 13956 13957 - -
4x240mm2 1250A - - 14081 14082
Cu/Al Rear cable terminals (RC CuAl)
2x150mm2 630A 13924 13925 - -
3x240mm2 800A 13958 13959 - -
Horizontal/Vertical Flat Bar terms (HR/VR)
1600A - - 14083 14084
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
ABB LIMITED 4/46
Three-phase asynchronous motor starting, switching and protection are essential operations for its correct use. The traditional systemused for this purpose has three different devices: a circuit-breaker for protection against short-circuit, a thermal relay for protectionagainst overload and lack of or unbalanced phase, and a counter for the motor operations. Everything must necessarily take into accountthe problems which arise on start-up.
In particular, these different factors must be taken into account when selecting these devices, such as:
- the motor power
- the starting diagram
- the type of motor: with cage rotor or with wound rotor
- the fault current at the point of motor installation in the network
ABB SACEproposes a wide range of circuit-breakers, which by implementing the protection against short-circuit exclusively, are suitablefor use inside protected starters of traditional type.
The new SACE T2 with fixed magnetic protection is an extremely compact circuit-breaker, which stands out for its exceptional perfor-mances in terms of breaking capacity and limitation of the specific let-through energy.
It can be used in a vast range of start-ups, from 0.37kW to 37kW and from 400V-50kA up to 690V-50kA. SACE S3 N/H/L 160/250 circuitbreakers and the S3X 125/200 current-limiting circuit-breaker are fitted with a magnetic only release adjustable from 4 to 12 time the ratedservice current. They cover coordinations from 37 to 132kW and allow optimal motor protection thanks to their great flexibility due to thewide setting range of the magnetic threshold.
Finally, SACES4 160/250, S5 400/630, S6 630/800, and S7 1250/1600, with different capacity levels, like the current-limiting S4X andS6X, can be fitted with the PR211/P (I) electronic microprocessor-based release. Above all, they are used for protection of high powermotors and, thanks to adjustment of the protection against short-circuit from 1.5 to 12 times, allow the optimumtrip value to be selectedfor any motor type.
SACE Isomax S circuit-breakers for motor protection (protection against short-circuit)
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
ABB LIMITED 4/47
ABB LIMITED 4/48
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
Icu (415V) Model Current (A) 1SDA0 R1
In MF MA PR221DS/I
3 Pole 3 Pole 3 Pole 4 Pole
T2N160R1 1A 53110 - - -
T2N160R1.6 1.6A 53111 - - -
T2N160R2 2A 53112 - - -
T2N160R2.5 2.5A 53113 - - -
T2N160R3.2 3.2A 53114 - - -
T2N160R4 4A 53115 - - -
T2N160R5 5A 53116 - - -
T2N160R6.5 6.5A 53117 - - -
T2N160R8.5 8.5A 53118 - - -
36kA T2N160R10 10A - - 51163 51169
T2N160R11 11A 53119 - -
T2N160R12.5 12.5A 53120 - - -
T2N160R20 20A - 51207 - -
T2N160R25 25A - - 51164 51170
T2N160R32 32A - 51208 - -
T2N160R52 52A - 51209 - -
T2N160R63 63A - - 51165 51171
T2N160R80 80A - 51210 - -
T2N160R100 100A - 51211 51166 51172
T2N160R160 160A - - 51168 51617
Motor Protection MCCBs Tmax T2N (160A)
Ratings @ 415V
Icu Ics
T2N 36kA 100%
T2S 50kA 100%
Fixed Pattern Circuit Breaker Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1Supplied as standard with front bar terminals for busbar - for other terminals seeaccessories section pagexx
for accessories see page x/xx
ABB LIMITED 4/49
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
Motor Protection MCCBs Tmax T2S (160A)
Icu (415V) Model Current (A) 1SDA0 R1
In MF MA PR221DS/I
3 Pole 3 Pole 3 Pole 4 Pole
T2S160R1 1A 53121 - - -
T2S160R1.6 1.6A 53122 - - -
T2S160R2 2A 53123 - - -
T2S160R2.5 2.5A 53124 - - -
T2S160R3.2 3.2A 53125 - - -
T2S160R4 4A 53126 - - -
T2S160R5 5A 53127 - - -
T2S160R6.5 6.5A 53128 - - -
50kA T2S160R8.5 8.5A 53129 - - -
T2S160R10 10A - - 51174 51179
T2S160R11 11A 53130 - - -
T2S160R12.5 12.5A 53131 - - -
T2S160R20 20A - 51216 - -
T2S160R25 25A - - 51175 51180
T2S160R32 32A - 51217 - -
T2S160R52 52A - 51218 - -
T2S160R63 63A - - 51176 51181
T2S160R80 80A - 51219 - -
T2S160R100 100A - 51220 51177 51182
T2S160R160 160A - - 51178 51618
Fixed Pattern Circuit Breaker Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1Supplied as standard with front bar terminals for busbar - for other terminals see accessories section pagexx
Protection types availableType Settings
Electronic L S
PR221DS/I 1 - 10x In
Magnetic Only Im
Fixed Magnetic (MF) 13x In
Adjustable Magnetic (MA) 6…12x In
for accessories see page x/xx
ABB LIMITED 4/50
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
Icu (415V) Model Current (A) 1SDA0 R1Ith MA 3 Pole
T3N250R100 100A 51315
36kAT3N250R125 125A 51316
T3N250R160 160A 51317
T3N250R200 200A 51318
T3S250R100 100A 51320
50kAT3S250R125 125A 51321
T3S250R160 160A 51322
T3S250R200 200A 51323
1SDA0 R1
Plug-in 3 Pole 4 Pole
Conversion Kit 51413 51414
Fixed portion (Base)
Front Copper Cable Terminals** 51331 51332
**for other terminals see accessories section pagexx
Motor Protection MCCBs Tmax T3 (250A)
Ratings @ 415V
Icu Ics
T3N 36kA 75%
T3S 50kA 50%
Protection types availableType Settings
Magnetic Only
Adjustable Magnetic (MA) 6…12x In
Fixed Pattern Circuit Breaker Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1Supplied as standard with front bar terminals for busbar - for other terminals seeaccessories section pagexx
Plug-in Circuit breakers
To convert fixed pattern device to plug-in pattern:-
1). Select correct Fixed Pattern Device from part numbers above2). Select Conversion Kit from part numbers below3). Add Fixed portion (Base) from part numbers below
ABB LIMITED 4/45
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
Accessories Isomax S6 and S7
2). Mechanical Accessories Cont....
f). Terminals for Plug-in and Withdrawable Bases
Terminal kits consist of 6 or 8 pieces
Terminal Type Max Current 1SDA0 R1
S6 S7
6 pieces 8 pieces 6 pieces 8 pieces
Extended Front (EF)800A 13984 13985 - -
1600A - - 14108 14109
Horizontal Flat Bar (HR)800A 13986 13987 - -
1600A - - 14110 14111
Vertical Flat Bar terminals (VR)800A 13988 13989 - -
1600A - - 14112 14113
g). Terminal Covers
Types availableHigh: For fixed pattern devicesLow: For Fixed pattern devices and for Moving parts of Plug-in and
Withdrawable devicesFP High: For Plug-in and Withdrawable Bases
1SDA0 R1
MCCB No of poles High Low FP High
S63 poles 14040 14038 -
4 poles 14041 14039 -
S73 poles - 23324 -
4 poles - 23325 -
ABB LIMITED 4/51
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
Icu (415V) Model Current (A) 1SDA0 R1
Im 3 Pole
S3N160RM3 12…36A 47782
S3N160RM5 20…60A 47783
S3N160RM10 40…120A 47784
S3N160RM25 100…300A 47785
S3N160RM50 200…600A 47786
35kA S3N160RM100 400…1200A 47787
S3N160RM125 500…1500A 47788
S3N160RM160 640…1600A 47789
S3N250RM160 640…1920A 48651
S3N250RM200 800…2400A 48654
S3H160RM50 200…600A 45185
S3H160RM100 400…1200A 45186
65kAS3H160RM125 500…1500A 45187
S3H160RM160 640…1600A 45188
S3H250RM160 640…1920A 48657
S3H250RM200 800…2400A 48658
S3L160RM50 200…600A 50544
S3L160RM100 400…1200A 50545
85kAS3L160RM125 500…1500A 50546
S3L160RM160 640…1600A 50547
S3L250RM160 640…1920A 50548
S3L250RM200 800…2400A 50549
Motor Protection MCCBs Isomax S3N, H, L (250A)
Fixed Pattern Circuit Breaker Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1Supplied as standard with front bar terminals for busbar - for other terminals &accessories section pagexx
Ratings @ 415V
Icu Ics
S3N 35kA 100%
S3H 65kA 75%
S3L 85kA 75%
All breakers are Magnetic Only with adjustable
settings AVAILABLE IN 3 POLE ONLY
ABB LIMITED 4/52
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
Motor Protection MCCBs Isomax S3X (250A)
Icu (415V) Model Current (A) 1SDA0 R1
Im 3 Pole
S3X125RM25 100…300A 45387
S3X125RM50 200…600A 45388
S3X125RM100 400…1200A 45389
200kA S3X125RM125 500…1500A 45390
S3X200RM125 500…1500A 46135
S3X200RM160 640…1920A 48659
S3X200RM200 800…2400A 48660
Fixed Pattern Circuit Breaker Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1Supplied as standard with front bar terminals for busbar - for other terminals & accessories section pagexx
Ratings @ 415V
Icu Ics
S3X 200kA 100%
Plug-in Withdrawable
1SDA0 R1
3 Pole 4 Pole 3 Pole 4 Pole
Conversion Kit 46519 46520 46521 46522
Fixed
Front Copper Cable Terminals 13543 13550 13559 13568
Extended Front bar Terminals 13539 13548 13555 13564
Threaded Rear Terminals 13547 13554 13563 13572
Plug-in and Withdrawable Circuit breakers
To convert fixed pattern device to plug-in or withdrawable pattern:-1). Select correct Fixed Pattern Device from part numbers above2). Select Conversion Kit from part numbers below3). Add Suitable Fixed portion (Base) from part numbers belowSpecial Notes: a).Withdrawable devices must be fitted with a front plate accessory such as:
Motor operatorPadlock DeviceRotary Handle
b). Remember to use accessories suitable for Plug-in or withdrawable pattern devices
All breakers are Magnetic Only with adjustable
settings AVAILABLE IN 3 POLE ONLY
ABB LIMITED 4/53
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
Icu (415V) Model Current (A) 1SDA0 R1Ith PR211/I PR212/LRIU
3 Pole 4 Pole 3 Pole Only
S4N160R100 100A 15548 15836 50139
35kAS4N160R160 160A 15549 15837 50140
S4N250R200 200A - - 50141
S4N250R250 250A 17318 17384 -
S4H160R100 100A 16142 16424 45049
65kAS4H160R160 160A 16143 16425 45050
S4H250R200 200A - - 48662
S4H250R250 250A 17450 17516 -
S4L160R100 100A 16730 17012 50550
100kAS4L160R160 160A 16731 17013 50551
S4L250R200 200A - - 50552
S4L250R250 250A 17582 17648 -
S4X250R100 100A - - 46590
200kA S4X250R160 160A - - 46591
S4X250R200 200A - - 48661
Motor Protection MCCBs Isomax S4N, H, L, X (250A)
Ratings @ 415V
Icu Ics
S4N 35kA 100%
S4H 65kA 100%
S4L 100kA 75%
S4X 200kA 100%
Fixed Pattern Circuit Breaker Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1Supplied as standard with front bar terminals for busbar - for other terminals & accessories section pagexx
Protection types availableElectronic (ac only)
Type SettingsL R I U
PR212/I - - 1.5 - 12x In -
PR212/LR 0.4 - 1x In 3 - 10x In 6 - 12x In ON/OFF
Plug-in and Withdrawable Circuit breakers
To convert fixed pattern device to plug-in or withdrawable pattern:-1). Select correct Fixed Pattern Device from part numbers above2). Select Conversion Kit from part numbers below3). Add Suitable Fixed portion (Base) from part numbers belowSpecial Notes: a).Withdrawable devices must be fitted with a front plate accessory such as:
Motor operator, Padlock Device, Rotary Handleb). Remember to use accessories suitable for Plug-in or withdrawable pattern devices
Plug-in Withdrawable
S4N/H/L S4X S4N/H/L S4X
3 Pole 4 Pole 3Pole 3 Pole 4 Pole 3Pole
Conversion Kit 13608 13609 46511 13610 13611 46521
Fixed portion (Base)
Front Copper Cable Terminals - 13543 13550 13634 13643 -
Extended Front bar Terminals - 13612 13621 13630 13639 -
Threaded Rear Terminals - 13547 13554 13638 13647 -
ABB LIMITED 4/54
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
Motor Protection MCCBs Isomax S5 (630A)
Icu (415V) Model Current (A) 1SDA0 R1Ith PR211/I PR212/LRIU
3 Pole 4 Pole 3 Pole Only
S5N400R320 320A 17714 17846 50142
35kA S5N400R400 400A 17715 17847 -
S5N630R630 630A 38674 38679 -
S5H400R320 320A 17990 18122 45051
65kA S5H400R400 400A 17991 18123 -
S5H630R630 630A 38704 38709 -
S5L400R320 320A 18254 18386 50553
100kA S5L400R400 400A 18255 18387 -
S5L630R630 630A 38736 38741 -
Ratings @ 415V
Icu Ics Icw (1sec)
S5N 35kA 100% 5kA
S5H 65kA 100% 5kA
S5L 100kA 75% 5kA
Protection types availableElectronic (ac only)
Type SettingsL R I U
PR211/I 0.4-1x In 1.5-12x In
PR212/LRIU 0.4-1x In 3-10x In 6-12x In ON/OFF
Fixed Pattern Circuit Breaker Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1Supplied as standard with front bar terminals for busbar - for other terminals & accessories section pagexx
Plug-in and Withdrawable Circuit breakers
To convert fixed pattern device to plug-in or withdrawable pattern:-1). Select correct Fixed Pattern Device from part numbers above2). Select Conversion Kit from part numbers below3). Add Suitable Fixed portion (Base) from part numbers belowSpecial Notes: a). Withdrawable devices must be fitted with a front plate accessory such as:
Motor operator, padlock device, rotary handleb). Remember to use accessories suitable for Plug-in or withdrawable pattern devices
400A 630A 1SDA0 R1 1SDA0 R1
Plug-in Withdrawable Withdrawable
3 Pole 4 Pole 3 Pole 4 Pole 3 Pole 4 Pole
Conversion Kit 13716 13717 13718 13719 38778 38779
Fixed portion (Base)
Front Copper Cable Terminals (400A) 13724 13733 13742 13751 - -
Extended Front bar Terminals 13720 13729 13738 13747 - -
Spreaded Ext Front bar Terminals - - - - 38761 38762
Threaded Rear Terminals 13728 13737 13746 13755 38763 38970
Vertical Flat bar Terminals - - - - 38971 38972
ABB LIMITED 4/55
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
1SDA0 R1
S6N/S/H/L S6X
3 Pole 4 Pole 3 Pole
Conversion Kit 13962 13963 47619
Fixed portion (Base)
Extended Front bar Terminals 13964 13973 13964
Horizontal Flat bar Terminals 13968 13977 13968
Vertical Flat bar Terminals 14096 14105 14096
Icu (415V) Model Current (A) 1SDA0 R1Ith PR211/I PR212/LRIU
3 Pole 4 Pole 3 Pole Only
S6N630R630 630A 18518 18572 -
35kA S6N800R630 630A - - 50143
S6N800R800 800A 18950 19004 -
50kAS6S630R630 630A 18626 18680 -
S6S800R800 250A 19058 19112 -
S6H630R630 630A 18734 18788 -
65kA S6H800R630 630A - - 45052
S6H800R800 800A 19166 19220 -
S6L630R630 630A 38736 38741 -
100kA S6L800R630 630A - - 50554
S6L800R800 800A 19274 19328 -
S6X400R320 320A 47595 47601 47780
200kAS6X400R400 400A 46534 46538 -
S6X630R400 400A - - 47781
S6X630R630 630A 46560 46564 48663
Motor Protection MCCBs Isomax S6 (800A)
Ratings @ 415V
Icu Ics
S6N 35kA 100%
S6S 50kA 100%
S6H 65kA 100%
S6L 100kA 75%
S6X 200kA 100%
Fixed Pattern Circuit Breaker Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1Supplied as standard with front bar terminals for busbar - for other terminals & accessories section pagexx
Protection types availableElectronic (ac only)
Type SettingsL R I U
PR211/I 1.5-12x In
PR212/LRIU 0.4-1x In 3-10x In 6-12x In ON/OFF
Withdrawable Circuit breakersTo convert fixed pattern device to withdrawable pattern:-1). Select correct Fixed Pattern Device from part numbers above2). Select Conversion Kit from part numbers below3). Add Suitable Fixed portion (Base) from part numbers belowSpecial Notes: a).Withdrawable devices must be fitted with a front plate accessory such as:
Motor operator, Padlock Device, Rotary Handlec). Remember to use accessories suitable for withdrawable pattern devices
ABB LIMITED 4/56
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
Motor Protection MCCBs Isomax S7 (1250A)
Icu (415V) Model Current (A) 1SDA0 R1Ith PR211/I PR212/LRIU
3 Pole 4 Pole 3 Pole Only
50kAS7S1250R1000 1000A 19382 19490 50144
S7S1250R1250 1250A 19383 19491 -
65kAS7H1250R1000 1000A 19598 19706 45053
S7H1250R1250 1250A 19599 19707 -
100kAS7L1250R1000 1000A 19814 19922 -
S7L1250R1250 1250A 19815 19923 -
Ratings @ 415V
Icu Ics
S7S 50kA 100%
S7H 65kA 100%
S7L 100kA 75%
Protection types availableElectronic (ac only)
Type SettingsL R I U
PR211/I 1.5-12x In
PR212/LRIU 0.4-1x In 3-10x In 6-12x In ON/OFF
Withdrawable
1SDA0 R1
3 Pole 4 Pole
Conversion Kit 23299 14087
Fixed portion (Base)
Extended Front bar Terminals 48951 14097
Horizontal Flat bar Terminals 14092 14105
Vertical Flat bar Terminals 14096 14101
Withdrawable Circuit breakersTo convert fixed pattern device to withdrawable pattern:-1). Select correct Fixed Pattern Device from part numbers above2). Select Conversion Kit from part numbers below3). Add Suitable Fixed portion (Base) from part numbers belowSpecial Notes: a).Withdrawable devices must be fitted with a front plate accessory such as:
Motor operator, Padlock Device, Rotary Handlec). Remember to use accessories suitable for withdrawable pattern devices
Fixed Pattern Circuit Breaker Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1Supplied as standard with front bar terminals for busbar - for other terminals &accessories section pagexx
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
ABB LIMITED 4/57
ApplicationsThese current-limiting circuit-breakers are suitable for installation in all types of civil, industrial and service sector installa-tions, as well as for electrical installations on board ships, in mines or on oil rigs, as well as, generally speaking, in any instal-lations where high power generators and transformers make it possible for very high short-circuit currents of up to 200kA at380/415 V~, 180 kA at 440 V~ and 75 kA at 690 V~ to occur.
The circuit-breakers can be positioned downstream of the power supply either to provide general protection (installations,multi-user systems and electrical lines) or for protecting electrical equipment (motors, generators, transformers and capaci-tors).They can also be fitted in systems where back-up protection is required that allows the use of circuit-breakers downstreamwhich have a lower breaking capacity than the prospective short-circuit current in the point of installation.The breaking capacities of the SACE current-limiting circuit-breakers are higher than the best values achieved by other unitsof this type.
Current Limiting MCCBs Tmax T2, Isomax S3X, S4X, S6X
ABB LIMITED 4/58
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
Icu (415V) Model Current (A) Standard Low Threshold PR221DS/LSIth 1SDA0 R1
3 Pole 4 Pole 3 Pole 4 Pole 3 Pole 4 Pole
T2L160R1.6 1.6A - - 51072 51094 - -
T2L160R2 2A - - 51073 51095 - -
T2L160R2.5 2.5A - - 51074 51096 - -
T2L160R3.2 3.2A - - 51075 51097 - -
T2L160R4 4A - - 51076 51098 - -
T2L160R5 5A - - 51077 51099 - -
T2L160R6.3 6.3A - - 51078 51100 - -
T2L160R8 8A - - 51079 51101 - -
T2L160R10 10A - - 51080 51102 51153 51158
T2L160R12.5 12.5A - - 51081 51103 - -
85kA T2L160R16 16A 51082 51104 - - - -
T2L160R20 20A 51083 51105 - - - -
T2L160R25 25A 51084 51106 - - 51154 51159
T2L160R32 32A 51085 51107 - - - -
T2L160R40 40A 51086 51108 - - - -
T2L160R50 50A 51087 51109 - - - -
T2L160R63 63A 51088 51110 - - 51155 51160
T2L160R80 80A 51089 51111 - - - -
T2L160R100 100A 51090 51112 - - 51156 51161
T2L160R125 125A 51091 51121 - - - -
T2L160R160 160A 51092 51122 - - 51157 51162
Current Limiting MCCBs Tmax T2 (160A)
Ratings @ 415V
Icu Ics
T2L 85kA 75%
Protection types availableType SettingsElectronic L S
PR221DS/LS 0.4 - 1x In 1 - 10x In
Thermomagnetic Ith Im
Standard Distribution 70-100% 10x Ith*
Low Threshold Thermomagnetic 70-100% 10x Ith
Plug-in Circuit breakers
To convert fixed pattern device to plug-in pattern:-
1). Select correct Fixed Pattern Device from part numbers above2). Select Conversion Kit from part numbers below3). Add Fixed portion (Base) from part numbers below
Plug-in
1SDA0 R1
3 Pole 4 Pole
Conversion Kit 51411 51412
Fixed portion (Base)
Front Copper Cable Terminals** 51329 51330
Fixed Pattern Circuit Breaker Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1Supplied as standard with front bar terminals for busbar - for other terminals & accessories section pagexx
ABB LIMITED 4/59
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
Icu (415V) Model Current (A) PR211 PR212
In/Ith Protection 1SDA0 R1
3 Pole 4 Pole 3 Pole 4 Pole 3 Pole 4 Pole
S3X125R32 32A T/Mag 45197 45207 - - - -
S3X125R50 50A T/Mag 45199 45209 - - - -
S3X125R80 80A T/Mag 45201 45211 - - - -
S3X S3X125R100 100A T/Mag 45203 45213 - - - -
S3X125R125 125A T/Mag 45205 45215 - - - -
S3X200R125 125A T/Mag 46039 46045 - - - -
S3X200R160 160A T/Mag 46041 46047 - - - -
S3X200R200 200A T/Mag 46043 46049 - - - -
LI - - 46584 46594 - -
S4X S4X250R100 100A LSI - - - - 46586 46596
LSIG - - - - 46588 46598
LI - - 46585 46595 - -
S4X S4X250R160 160A LSI - - - - 46587 46597
LSIG - - - - 46589 46599
LI - - 46525 46529 - -
S4X S4X250R250 250A LSI - - - - 46526 46530
LSIG - - - - 46527 46531
LI - - 47596 47602 - -
S6X S6X400R320 320A LSI - - - - 47597 47603
LSIG - - - - 47598 47604
LI - - 46535 46539 - -
S6X S6X400R400 400A LSI - - - - 46536 46540
LSIG - - - - 46537 46541
LI - - 46561 46565 - -
S6X S6X630R630 630A LSI - - - - 46562 46566
LSIG - - - - 46563 46567
Current Limiting MCCBs Isomax S3X, S4X, S6X
Fixed Pattern Circuit Breaker Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1Supplied as standard with front bar terminals for busbar - for other terminals & accessories section pagexx
Thermomagnetic
Ratings @ 415V
Icu Ics
S3X 200kA 100%
S4X 200kA 100%
S6X 200kA 100%
Protection types available
Type SettingsElectronic L S I G
PR211/LI 0.4-1x In 1.5-12x In
PR212/LSI 0.4-1x In 1-10x In 1.5 - 12x In
PR212/LSIG 0.4-1x In 1-10x In 1.5-12x In 0.2-1x In
Thermomagnetic Ith Im
Standard Distribution 70-100% 5-10x Ith
ABB LIMITED 4/60
Description
Emax Air Circuit Breaker Electrical Specifications
Voltages Rated Service Voltage Ue [V] 690(ac) 250(dc)Rated Insulation Voltage Ui [V] 1000Rated Impulse Voltage Uimp [kV] 12
Temperature Service °C -5...+70Storage °C -40...+70 N B N L
Performance LevelRated uninterrupted current @ 40°VC Iu [A] 800 1600 1250 1250
[A] 1250 2000 1600 1600[A] - - 2000 -[A] - - - -[A] - - - -
Capacity of neutral on 4 pole breakers % Iu 100% 100%
Rated ultimate short circuit breaking capacity Icu220/230/380/400/415 Vac [kA] 50 42 65 130440 Vac [kA] 50 42 65 110500/660/690 Vac [kA] 36 42 55 85250Vdc [kA] 36 40 55 -
Rated duty short circuit breaking capacity Ics220/230/380/400/415 Vac [kA] 50 42 65 130440 Vac [kA] 50 42 65 110500/660/690 Vac [kA] 36 42 55 65250 Vdc [kA] 36 42 55 -
Rated short time withstand current Icw1 sec [kA] 50 42 55 103 secs [kA] 36 42 42 -
Rated short circuit making capacity Icm220/230/380/400/415 Vac [kA] 105 88.2 143 286440 Vac [kA] 105 88.2 143 242500/600/690 Vac [kA] 75.6 88.2 121 187
Utilisation category (according to BS EN 60947-2) B B B A
Microprocessor-based releases for a.c. applications operating timeClosing time (max) [mS] 80 80 80 80Break time for I < Icw (max) [mS] 70 70 70 70Break time for I > Icw (max) [mS] 30 30 30 12
DimensionsFixed (H=418mm D=302mm W=3/4 pole) [mm] 296/386 296/386Drawout (H=461mm D=396.5mm W=3/4 pole) [mm] 324/414 324/414
WeightFixed 3/4 pole [kg] 45/54 50/61 50/61 52/63Drawout 3/4 pole [kg] 70/82 78/93 78/93 8095
Rated uninterrupted current @ 40°C Iu [A] 800/1250 1250 1600 2000Mechanical Life (with routine maintenance) [ops x 1000] 25 25(B-N) 10(L) 25(B-N) 20(L) 25Frequency [No. ops per Hr] 60 60 60 60Electrical Life [ops x 1000] 10 15(B-N) 4(L) 12(B-N) 3(L) 10Frequency [No. ops per Hr] 30 30 30 30
E1 E2
ABB LIMITED 4/61
E3 E4 E6
N S H/b H L S S/f H H H/f
2500 1250 1250 1250 2000 4000 3200 3200 5000 50003200 1600 1600 1600 2500 - 4000 4000 6300 6300
- 2000 2000 2000 - - - - - -- 2500 2500 2500 - - - - - -- 3200 3200 3200 - - - - - -
100% 50% 100% 50% 50% 100%
65 75 80 100 130 75 80 100 100 10065 75 80 100 110 75 80 100 100 10065 75 75 85 85 75 75 85 100 10065 75 75 75 - 75 75 100 100 100
65 75 80 85 130 75 80 100 100 10065 75 80 85 110 75 80 100 100 10065 75 75 85 65 75 75 85 100 10065 75 75 75 - 75 75 100 100 100
65 75 80 75 15 75 80 100 100 10065 65 - 65 - 75 - 75 85 -
143 165 176 220 286 165 176 220 220 220143 165 176 220 242 165 176 220 220 220143 165 165 187 187 165 165 187 220 220
B B B B A B B B B B
80 80 80 80 80 80 80 80 80 8070 70 70 70 70 70 70 70 70 7030 30 30 30 12 30 30 30 30 30
404/530 556/656 757* 556/656 782/908 1045*432/558 594/684 778* 594/684 810/936 1062*
66/80 66/80 66/80 66/80 72/83 97/117 132* 97/117 140/160 193*104/125 104/125 104/125 104/125 110/127 147/165 211* 147/165 210/240 295*
1250 1600 2000 2500 3200 3200 4000 - 3200 400020 20 20(N-S-H) 15(L) 20(N-S-H) 15(L) 20 15 12 - 12 1260 60 60 60 60 60 60 - 60 6012 10 9(N-S-H) 2(L) 8(N-S-H) 1.8(L) 6 7 5 - 5 420 20 20 20 20 10 10 - 10 10
E3 E4 E6
ABB LIMITED 4/62
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
Emax Air Circuit BreakersMicroprocessor-based overcurrent releases
General specificications of the microprocessor-based releases include:• operation without the need for an external power supply• microprocessor technology (8-bit for SACE PR111 and 16-bit for SACE PR112 and PR113)• high precision• sensitivity to the true r.m.s. value of the current• interchangeability among all types of releases• setting for neutral normally 50% of setting phases, with possibility of setting it to 100% (on requestonly for circuit -breakers E1, E2, E3 standard and £4/f, E6/f full size versions).
For the release PR113, it is also possible to select neutral protection at 150% and 200% of the ratedcurrent of the phases, if compatible with the setting of the current transformers.The main performance features of the releases are listed in the tables below.
SACE PR111
Protection
PR111/P
PR112/P
PR112/PDModbus
PR112/PDModbus
PR112/PDLON
PR112/PDLON
PR112/P
PR111/P PR111/P
L S I G L S I L I
SACE PR112
Protection L S I G L S I
Protection &Communication L S I G L S I L S I G L S I
PR113/P
PR113/PDModbus
SACE PR113Protection L S I G
Protection &Communication L S I G
D U OT UV OV RV RP M
D U OT UV OV RV RP M
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
ABB LIMITED 4/63
Protection Functions PR111 PR112 PR113
Inverse long time-delay trip overload protectionAdjustable-slope curve (IEC 60255-3)
Selective short-circuit protection with inverse or definiteshort time-delay trip
Instantaneous short-circuit protection with adjustabletrip current threshold
Earth fault protectionresidual (internal sensor)
source ground return (external sensor)
Directional short-circuit protection with adjustable delay
Protection against phase umbalance
Protection against over temperature
Undervoltage and overvoltage protection
Residual voltage protection / neutral displacement protection
Reverse power protection
Thermal memory for L and S functions
Measurements
Currents (phases, neutral, earth fault)
Voltage (phase-phase, phase-neutral, residual)
Power (active, reactive, apparent)
Power factor
Frequency and peak factor
Energy (active, reactive, apparent, counter)
Harmonics calculation (displays waveform and module of the harmonics)
Maintenance events and data
Events stored in chronological order
Counting number of operations and contact wear
Communication with centralized supervision and control system
Remote setting of parameters for protection functions, unit configuration and communication
Transmission of measurements, states and alarms from circuit-breaker to system
Transmission of maintenance events and data from circuit-breaker to system
Self-test
Alarm and tripping for release overtemperature
Alarm for microprocessor fault
User interface
Parameters set using DIP switches
Parameters set using keys and liquid crystal display
Alarm signals for L, S, I and G functions
Alarm signalling one of the following protections: undervoltage, overvoltage, residual voltage, reverse power
Imbalance phase and overtemperature signal
Complete management of pre-alarms and alarms for all protection and self monitoring functions
Password for use with “READ” or “EDIT” mode
Load control
Connection-disconnection of loads in relation to the current flowing through the circuit breaker
Zone selectivity
May be activated for protection functions S or G
May be activated for protection funcions S, G or D
Number of programmable contacts 1 2
Start-up function S, D, I and G
Emax Air Circuit BreakersMicroprocessor-based overcurrent releases
I
L
S
G
D
U
OT
UVOV
RV
RP
M
ABB LIMITED 4/64
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
E4S/f E6H/f
Rated uninterrupted current (at 40ºC) Iu [A] 4000 5000
[A] 6300
Number of poles 4 4
Rated service voltage Ue [V~] 690 690
Rated ultimate short-circuit breaking capacity Icu
220/230/380/400/415 V ~ [kA] 80 100
440 V ~ [kA] 80 100
500/660/690 V ~ [kA] 75 100
Rated service short-circuit breaking capacity Ics
220/230/380/400/415 V ~ [kA] 80 100
440 V ~ [kA] 80 100
500/660/690 V ~ [kA] 75 100
Rated short-time withstand current Icw
(1s) [kA] 80 100
(3s) [kA] 75 85
Rated short-circuit making capacity (peak value) Icm [kA] 176 220
Application category (in accordance with IEC 60947-2) B B
Isolation behavior (in accordance with IEC 60947-2)
Overall dimensions
Fixed: H= 418mm - D= 302mm L [mm] 746 1034
Withdrawable: H=461 - D= 396.5mm L [mm] 774 1062
Weights (circuit-breaker complete with releases and CT, not including accessories)
Fixed [kg] 120 165
Withdrawable (including fixed part) [kg] 170 250
Emax Air Circuit BreakersAutomatic circuit-breakers with full-size neutral conductor
The Emax range of automatic circuit-breakers with full size neutral conductor is used in special appli-
cations where the presence of triple-N harmonics on individual phases may lead to a very high current
on the neutral conductor.
Typical applications include installations with loads having high harmonics distortions (computers and
electronic devices in general), lighting systems with a large number of fluorescent lamps, systems with
inverters and rectifiers, UPS, systems for adjusting the speed of electric motors.
This range includes standard circuit-breakers with full-size neutral conductor in sizes E1, E2, E3.
Models E4 and E6 are available in the “full size” version up to rated currents of 6300A. Models E4/f
and E6/f are available in fixed and withdrawable four-pole versions. These models may be fitted with
all accessories available of the Emax range; the exception, on the E6/f model, are the mechanical
interlocks made using flexible wires and 15 external auxiliary contacts, which are therefore incompati-
ble.
All the models may be fitted with all available version of electronic protection relays, in the standard
version.
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
ABB LIMITED 4/65
E1B/MS E1N/MS E2B/MS E2N/MS E3N/MS E3S/MS E4S/MS E4S/fMS E4H/MS E6H/MS E6H/fMS
Rated uninterrupted current (at 40ºC) Iu [A] 800 800 1600 1250 2500 1250 4000 4000 3200 5000 5000
[A] 1250 1250 2000 1600 3200 1600 - - 4000 6300 6300
[A] - - - 2000 - 2000 - - - - -
[A] - - - - - 2500 - - - - -
[A] - - - - - 3200 - - - - -
Rated service voltage Ue [V ~] 690 690 690 690 690 690 690 690 690 690 690
[V ~] 250 250 250 250 250 250 250 250 250 250 250
Rated insulation voltage Ui [V ~] 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Rated impulse withstand voltage Uimp [kV] 12 12 12 12 12 12 12 12 12 12 12
Rated short-time withstand current Icw (1s) [kA] 36 50 42 55 65 75 75 80 100 100 100
(3s) [kA] 36 36 42 42 65 65 75 75 75 85 85
Rated short-circuit making capacity (peak value) ICM
220/230/380/400/415/440 V ~ [kA] 75.6 105 88.2 121 143 165 165 176 220 220 220
500/660/690 V ~ [kA] 75.6 75.6 88.2 121 143 165 165 165 187 220 220
Emax Air Circuit BreakersSwitch-disconnectors
The switch-disconnectors are derived from the corresponding automatic circuit-breakers, of which
they maintain the overall dimensions and the possibility of mounting accessories.
This version differs from the automatic circuit-breakers only in the absence of overcurrent releases.
The circuit-breaker is available in both fixed and withdrawable versions, three-pole and four-pole. The
switch-disconnectors, identified by the label “/MS”, may be used according to the category of use AC-
23A (switching motor loads or other highly inductive loads) in accordance with the standard IEC
60947-3. The electrical specifications of the switch-disconnectors are listed below.
ABB LIMITED 4/66
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
Icu Model Current (A) Protection Non Automatic PR111 PR112(415V) Ith 1SDA0 R1
3 Pole 4 Pole 3 Pole 4 Pole 3 Pole 4 Pole
LI 53803 53804 - - - -
42kA E1N 08 800A LSI - - 53754 53761 53757 53763
LSIG - - 53755 53762 53758 53764
LI 53805 53806 - - - -
42kA E1N 12 1250A LSI - - 53767 53773 53769 53775
LSIG - - 53768 53774 53770 53776
Emax Air Circuit BreakersEmax E1 - Fixed Rear Horizontal Terminals
Ratings @ 415V
Icu Ics Icw (1sec)
E1N 50kA 50kA 50kA
With Rear Horizontal TerminalsOrdering example: place five digit code below into order reference eg 1SDA0 39676 R1For version with FULLY RATED NEUTRAL, add /FRN to order reference eg 1SDA0 39676R1/FRN
ABB LIMITED 4/67
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
Icu Model Current (A) Protection Non Automatic PR111 PR112(415V) Ith 1SDA0 R1
3 Pole 4 Pole 3 Pole 4 Pole 3 Pole 4 Pole
LI 53807 53808 - - - -
42kA E1N 08 800A LSI - - 53780 53786 53782 53788
LSIG - - 53781 53787 53783 53789
LI 53809 53810 - - - -
42kA E1N 12 1250A LSI - - 53792 53798 53794 53800
LSIG 53793 53799 53795 53801
Emax Air Circuit BreakersEmax E1 - Drawout
Ratings @ 415V
Icu Ics Icw (1sec)
E1N 50kA 50kA 50kA
Moving PortionsOrdering example: place five digit code below into order reference eg 1SDA0 39676 R1For version with FULLY RATED NEUTRAL, add /FRN to order reference eg 1SDA0 39676R1/FRN
Refer to sales office for breakers fitted with PR113 release
Fixed PortionsOrdering example: place five digit code below into order reference eg 1SDA0 39676 R1Front, Flat and mixed terminal versions available on request, refer to technical catalogue
Terminal type 1SDA0 R13 pole 4pole
Rear Horizontal 37821 37826
Rear Vertical 37872 37877
ABB LIMITED 4/68
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
Icu Model Current (A) Protection Non-Automatic PR111 PR112(415V) Ith 1SDA0 R1
3 Pole 4 Pole 3 Pole 4 Pole 3 Pole 4 Pole
MS n/a n/a - - - -
65kA E2N 12 800A LSI - - 39676 39791 39684 39799
LSIG - - 39680 39795 39688 39803
MS 37531 37559 - - - -
65kA E2N12 1250A LSI - - 39677 39792 39685 39800
LSIG - - 39681 39796 39689 39803
MS 37532 37560 - - - -
65kA E2N 16 1600A LSI 39906 39994 39912 40000
LSIG 39909 39997 39915 40003
MS 37533 37561 - - - -
65kA E2N 20 2000A LSI - - 40082 40170 40088 40176
LSIG - - 40085 40173 40091 40091
MS n/a n/a - - - -
130kA E2L 12 1250A LSI - - 43394 40341 43402 40349
LSIG - - 43398 40345 43406 40353
MS n/a n/a - - - -
130kA E2L 16 1600A LSI - - 40455 40543 40461 40549
LSIG - - 40458 40546 40464 40552
Emax Air Circuit BreakersEmax E2 - Fixed Rear Horizontal Terminals
Ratings @ 415V
Icu Ics Icw (1sec)
E2N 65kA 65kA 55kA
E2L 130kA 130kA 10kA
With Rear Horizontal TerminalsOrdering example: place five digit code below into order reference eg 1SDA0 39676 R1For version with FULLY RATED NEUTRAL, add /FRN to order reference eg 1SDA0 39676R1/FRN
ABB LIMITED 4/69
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
Icu Model Current (A) Protection Non-Automatic PR111 PR112(415V) Ith 1SDA0 R1
3 Pole 4 Pole 3 Pole 4 Pole 3 Pole 4 Pole
MS n/a n/a - - - -
65kA E2N 12 800A LSI - - 39762 39878 39770 39886
LSIG - - 39766 39882 39774 39890
MS 37648 37652 - - - -
65kA E2N 12 1250A LSI - - 39763 39879 39771 39887
LSIG - - 39767 39883 39775 39891
MS 37647 37651 - - - -
65kA E2N 16 1600A LSI - - 39972 40060 39978 40066
LSIG - - 39975 40064 39981 40069
MS 37649 37650 - - - -
65kA E2N 20 2000A LSI - - 40148 40214 40154 40220
LSIG - - 40151 40217 40157 40223
MS n/a n/a - - - -
130kA E2L 12 1250A LSI - - 40296 40428 40304 40436
LSIG - - 40300 40432 40308 40440
MS n/a n/a - - - -
130kA E2L 16 1600A LSI - - 40521 40609 40527 40615
LSIG - - 40524 40612 40530 40618
Emax Air Circuit BreakersEmax E2 - Drawout
Refer to sales office for breakers fitted with PR113 release
Fixed PortionsOrdering example: place five digit code below into order reference eg 1SDA0 39676 R1Front, Flat and mixed terminal versions available on request, refer to technical catalogue
Moving PortionsOrdering example: place five digit code below into order reference eg 1SDA0 39676 R1For version with FULLY RATED NEUTRAL, add /FRN to order reference eg 1SDA0 39676R1/FRN
Ratings @ 415V
Icu Ics Icw (1sec)
E2N 65kA 65kA 55kA
E2L 130kA 130kA 10kA
Terminal type 1SDA0 R13 pole 4pole
Rear Horizontal 37822 37827
Rear Vertical 37873 37886
ABB LIMITED 4/70
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
With Rear Horizontal TerminalsOrdering example: place five digit code below into order reference eg 1SDA0 39676 R1For version with FULLY RATED NEUTRAL, add /FRN to order reference eg 1SDA0 39676R1/FRN
Emax Air Circuit BreakersEmax E3N, S - Fixed Rear Horizontal Terminals
Icu Model Current (A) Protection Non-Automatic PR111 PR112(415V) Ith 1SDA0 R1
3 Pole 4 Pole 3 Pole 4 Pole 3 Pole 4 Pole
MS - - - - - -
65kA E3N 25 2500A LSI - - 40651 40711 40655 40715
LSIG - - 41653 41713 40657 40717
MS - -
65kA E3N 32 3200A LSI - - 40786 43375 40790 43379
LSIG - - 40788 43377 40792 43381
MS - - - - - -
75kA E3S 12 1250A LSI - - 40891 40951 40895 40955
LSIG - - 40893 40953 40897 40957
MS - - - - - -
75kA E3S 16 1600A LSI - - 41011 41071 41015 41075
LSIG - - 41013 41073 41017 41077
MS - - - - - -
75kA E3S 20 2000A LSI - - 41131 41191 41135 41195
LSIG - - 41133 41193 41137 41197
MS - - - - - -
75kA E3S 25 2500A LSI - - 41251 41311 41255 41315
LSIG - - 41253 41313 41257 41317
MS - - - - - -
75kA E3S 32 3200A LSI - - 41371 41431 41375 41435
LSIG - - 41373 41933 41377 41437
Ratings @ 415V
Icu Ics Icw (1sec)
E3N 65kA 65kA 65kA
E3S 75kA 75kA 75kA
ABB LIMITED 4/71
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
Icu Model Current (A) Protection Non-Automatic PR111 PR112(415V) Ith 1SDA0 R1
3 Pole 4 Pole 3 Pole 4 Pole 3 Pole 4 Pole
MS TBC TBC
80kA E3H/b 12 1250A LSI TBC TBC TBC TBC
LSIG TBC TBC TBC TBC
MS TBC TBC
80kA E3H/b 16 1600A LSI TBC TBC TBC TBC
LSIG TBC TBC TBC TBC
MS TBC TBC
80kA E3H/b 20 2000A LSI TBC TBC TBC TBC
LSIG TBC TBC TBC TBC
MS TBC TBC
80kA E3H/b 25 2500A LSI TBC TBC TBC TBC
LSIG TBC TBC TBC TBC
MS TBC TBC
80kA E3H/b 32 3200A LSI TBC TBC TBC TBC
LSIG TBC TBC TBC TBC
MS - -
100kA E3H 12 1250A LSI - - 41491 41551 41495 41555
LSIG - - 41493 41553 41497 41557
MS - -
100kA E3H 16 1600A LSI - - 41611 41671 41615 41675
LSIG - - 41613 41673 41617 41677
MS - -
100kA E3H 20 2000A LSI - - 41731 41791 41735 41795
LSIG - - 41733 41793 41737 41797
MS - -
100kA E3H 25 2500A LSI - - 41851 41911 41855 41915
LSIG - - 41853 41913 41857 41917
MS - -
100kA E3H 32 3200A LSI - - 41971 42031 41975 42035
LSIG - - 41973 42033 41977 42037
MS - -
130kA E3L 20 2000A LSI - - 42091 42151 42095 42155
LSIG - - 42093 42153 42097 42157
MS - -
130kA E3L 25 2500A LSI - - 42211 42271 42215 42275
LSI - - 42213 42273 42217 42277
Emax Air Circuit BreakersEmax E3H/b, H, L - Fixed Rear Horizontal Terminals
Ratings @ 415V
Icu Ics Icw (1sec)
E3H/b 80kA 80kA 80kA
E3H 100kA 85kA 75kA
E3L 130kA 130kA 15kA
With Rear Horizontal TerminalsOrdering example: place five digit code below into order reference eg 1SDA0 39676 R1For version with FULLY RATED NEUTRAL, add /FRN to order reference eg 1SDA0 39676R1/FRN
ABB LIMITED 4/72
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
Emax Air Circuit BreakersEmax E3N, S - Drawout
Moving PortionsOrdering example: place five digit code below into order reference eg 1SDA0 39676 R1For version with FULLY RATED NEUTRAL, add /FRN to order reference eg 1SDA0 39676R1/FRN
Ratings @ 415V
Icu Ics Icw (1sec)
E3N 65kA 65kA 65kA
E3S 75kA 75kA 75kA
Icu Model Current (A) Protection Non-Automatic PR111 PR112(415V) Ith 1SDA0 R1
3 Pole 4 Pole 3 Pole 4 Pole 3 Pole 4 Pole
MS 37656 37653 - - - -
65kA E3N 25 2500A LSI - - 40696 40756 40700 40760
LSIG - - 40698 40758 40702 40762
MS 37655 37654 - - - -
65kA E3N 32 3200A LSI - - 40831 40876 40835 40880
LSIG - - 40833 40878 40837 40882
MS 37657 37664 - - - -
75kA E3S 12 1250A LSI - - 40936 40996 40940 41000
LSIG - - 40938 40998 40942 41002
MS 37660 37665 - - - -
75kA E3S 16 1600A LSI - - 41056 41116 41060 41120
LSIG - - 41058 41118 41062 41122
MS 37658 37666 - - - -
75kA E3S 20 2000A LSI - - 41176 41236 41180 41240
LSIG - - 41178 41238 41182 41242
MS 37661 37662 - - - -
75kA E3S 25 2500A LSI - - 41296 41356 41300 41360
LSIG - - 41298 41358 41302 41362
MS 37659 37663 - - - -
75kA E3S 32 3200A LSI - - 41416 41476 41420 41480
LSIG - - 41418 41478 41422 41482
Refer to sales office for breakers fitted with PR113 release
Fixed PortionsOrdering example: place five digit code below into order reference eg 1SDA0 39676 R1Front, Flat and mixed terminal versions available on request, refer to technical catalogue
Terminal type 1SDA0 R13 pole 4pole
Rear Horizontal 37822 37827
Rear Vertical 37873 37886
ABB LIMITED 4/73
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
Emax Air Circuit BreakersEmax E3H/b, H, L Drawout
Ratings @ 415V
Icu Ics Icw (1sec)
E3H/b 80kA 80kA 80kA
E3H 100kA 85kA 75kA
E3L 130kA 130kA 15kA
Refer to sales office for breakersfitted with PR113 release
Fixed Portions - Refer to page ????
Icu Model Current (A) Protection Non-Automatic PR111 PR112(415V) Ith 1SDA0 R1
3 Pole 4 Pole 3 Pole 4 Pole 3 Pole 4 Pole
MS TBC TBC
80kA E3H/b 12 1250A LSI TBC TBC TBC TBC
LSIG TBC TBC TBC TBC
MS TBC TBC
80kA E3H/b 16 1600A LSI TBC TBC TBC TBC
LSIG TBC TBC TBC TBC
MS TBC TBC
80kA E3H/b 20 2000A LSI TBC TBC TBC TBC
LSIG TBC TBC TBC TBC
MS TBC TBC
80kA E3H/b 25 2500A LSI TBC TBC TBC TBC
LSIG TBC TBC TBC TBC
MS TBC TBC
80kA E3H/b 32 3200A LSI TBC TBC TBC TBC
LSIG TBC TBC TBC TBC
MS - - - - - -
100kA E3H 12 1250A LSI - - 41536 41596 41540 41600
LSIG - - 41568 41598 41542 41602
MS - - - - - -
100kA E3H 16 1600A LSI - - 41656 41716 41660 41720
LSIG - - 41658 41718 41662 41722
MS - - - - - -
100kA E3H 20 2000A LSI - - 41776 41836 41780 41840
LSIG - - 41778 41838 41782 41842
MS - - - - - -
100kA E3H 25 2500A LSI - - 41896 41956 41900 41960
LSIG - - 41898 41958 41902 41962
MS - - - - - -
100kA E3H 32 3200A LSI - - 42016 42076 42020 42080
LSIG - - 42018 42078 42022 42082
MS - - - - - -
130kA E3L 20 2000A LSI - - 42136 42196 42140 42200
LSIG - - 42138 42198 42142 42202
MS - - - - - -
130kA E3L 25 2500A LSI - - 42256 42316 42260 42320
LSI - - 42258 42318 42262 42322
Moving PortionsOrdering example: place five digit code below into order reference eg 1SDA0 39676 R1For version with FULLY RATED NEUTRAL, add /FRN to order reference eg 1SDA0 39676R1/FRN
ABB LIMITED 4/74
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
Emax Air Circuit BreakersEmax E4S, S/f, H - Fixed - Rear Horizontal Terminals
Ratings @ 415V
Icu Ics Icw (1sec)
E4S 75kA 75kA 75kA
E4S/f 80kA 80kA 80kA
E4H 100kA 100kA 100kA
With Rear Horizontal TerminalsOrdering example: place five digit code below into order reference eg 1SDA0 39676 R1For E4S 3 pole version for use with fully rated external neutral CT, add /FRN to order reference eg 1SDA039791R1/FRN. For E4S 4 pole fully rated neutral version use E4S/f part numbers
Icu Model Current (A) Protection Non-Automatic PR111 PR112(415V) Ith 1SDA0 R1
3 Pole 4 Pole 3 Pole 4 Pole 3 Pole 4 Pole
MS 37546 37574 - - - -
75kA E4S 4000A LSI - - 42332 42392 42336 42396
LSIG - - 42334 42394 42338 42398
MS n/a 48737 n/a - n/a -
80kA E4S/f 4000A LSI n/a - n/a 48675 n/a 48677
LSIG n/a - n/a 48676 n/a 48678
MS 37547 37575 - - - -
100kA E4H 32 3200A LSI - - 42452 43419 42456 42423
LSIG - - 42454 43421 42458 42425
MS 37548 37576 - - - -
100kA E4H 40 4000A LSI - - 42557 42617 42561 42621
LSIG - - 42559 42619 42563 42623
* Available in 4 pole ( fully rated neutral) version only
* Available with 50% rated neutral only
Refer to sales office for breakers fitted with PR113 release
ABB LIMITED 4/75
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
Refer to sales office for breakers fitted with PR113 release
Fixed PortionsOrdering example: place five digit code below into order reference eg 1SDA0 39676 R1Front, Flat and mixed terminal versions available on request, refer to technical catalogueFor E4S 4 pole fully rated neutral version use E4S/f part numbers
Emax Air Circuit BreakersEmax E4S, S/f, H Drawout
Icu Model Current (A) Protection Non-Automatic PR111 PR112(415V) Ith 1SDA0 R1
3 Pole 4 Pole 3 Pole 4 Pole 3 Pole 4 Pole
MS 37677 37678 - - - -
75kA E4S 4000A LSI - - 42377 42437 42381 42441
LSIG - - 42379 42439 42383 42443
MS n/a 48740 n/a - n/a -
80kA E4S/f 4000A LSI n/a - n/a 48696 n/a 48698
LSIG n/a - n/a 48697 n/a 48699
MS 37682 37679 - - - -
100kA E4H 32 3200A LSI - - 42497 42542 42501 42546
LSIG - - 42499 42544 42503 42548
MS 37681 37680 - - - -
100kA E4H 40 4000A LSI - - 42602 42662 42606 42666
LSIG - - 42604 42664 42608 42668
Ratings @ 415V
Icu Ics Icw (1sec)
E4S 75kA 75kA 75kA
E4S/f 80kA 80kA 80kA
E4H 100kA 100kA 100kA
* Note: Available in 4 pole ( fully rated neutral) version only
* Note: Available with 50% rated neutral only
Terminal type 1SDA0 R13 pole 4pole
Rear HorizontalE4S & E4H 37824 37829
E4S/f n/a 48702
Rear VerticalE4S & E4H 37875 37879
E4S/f n/a 48707
Moving PortionsOrdering example: place five digit code below into order reference eg 1SDA0 39676 R1For E4S 3 pole version for use with fully rated external neutral CT, add /FRN to order reference eg 1SDA039791R1/FRN. For E4S 4 pole fully rated neutral version use E4S/f part numbers
ABB LIMITED 4/76
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
Icu Model Current (A) Protection Non-Automatic PR111 PR112(415V) Ith 1SDA0 R1
3 Pole 4 Pole 3 Pole 4 Pole 3 Pole 4 Pole
MS 37549 37577 - - - -
100kA E6H 50 5000A LSI - - 42677 42737 42681 42741
LSIG - - 42679 42739 42683 42743
MS 37550 37578 - - - -
100kA E6H 63 6300A LSI - - 42797 42857 42801 42861
LSIG - - 42799 42859 42803 42863
MS n/a 50810 n/a - n/a -
100kA E6H/f 50 5000A LSI n/a - n/a 50768 n/a 50770
LSIG n/a - n/a 50769 n/a 50771
MS n/a 50813 n/a - n/a -
100kA E6H/f 63 6300A LSI n/a - n/a 50789 n/a 50791
LSIG n/a - n/a 50790 n/a 50792
MS - - - - - -
150kA E6V 32 3200A LSI - - 42923 42955 42925 42957
LSIG - - 42924 42956 42926 42958
MS - - - - - -
150kA E6V 40 4000A LSI - - 42996 43056 43000 43060
LSIG - - 42998 43058 43002 43062
MS - - - - - -
150kA E6V 50 5000A LSI - - 43101 43161 43105 43165
LSIG - - 43103 43163 43107 43167
MS - - - - - -
150kA E6V 63 6300A LSI - - 43221 43281 43225 43285
LSIG - - 43223 43283 43227 43287
Emax Air Circuit BreakersEmax E6H, H/f, V - Fixed Rear Horizontal Terminals
* Note: This breaker is available in 4 pole ( fully rated neutral) version only
* Note: This breaker is available with 50% rated neutral only
Ratings @ 415V
Icu Ics Icw (1sec)
E6H 100kA 100kA 100kA
E6H/f 100kA 100kA 100kA
E6V 150kA 125kA 100kA
With Rear Horizontal TerminalsOrdering example: place five digit code below into order reference eg 1SDA0 39676 R1For E6H 3 pole version for use with fully rated external neutral CT, add /FRN to orderreference eg 1SDA039791R1/FRN. For E6H 4 pole fully rated neutral version use E6H/f part numbers
* Note: Available in 4 pole ( fully rated neutral) version only
* Note: Available with 50% rated neutral only
ABB LIMITED 4/77
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
Icu Model Current (A) Protection Non-Automatic PR111 PR112(415V) Ith 1SDA0 R1
3 Pole 4 Pole 3 Pole 4 Pole 3 Pole 4 Pole
MS 37683 37686 - - - -
100kA E6H 50 5000A LSI - - 42722 42782 42726 42786
LSIG - - 42742 42784 42728 42788
MS 37684 37685 - - - -
100kA E6H 63 6300A LSI - - 42842 42902 42846 42906
LSIG - - 42844 42904 42848 42908
MS n/a 50812 n/a - n/a -
100kA E6H/f 50 5000A LSI n/a - n/a 50782 n/a 50784
LSIG n/a - n/a 50783 n/a 50785
MS n/a 50815 n/a - n/a -
100kA E6H/f 63 6300A LSI n/a - n/a 50804 n/a 50806
LSIG n/a - n/a 50805 n/a 50807
MS - - - - - -
150kA E6V 32 3200A LSI - - 42939 42971 42941 42973
LSIG - - 42940 42972 42942 42974
MS - - - - - -
150kA E6V 40 4000A LSI - - 43026 43086 43030 43090
LSIG - - 43028 43088 43032 43092
MS - - - - - -
150kA E6V 50 5000A LSI - - 43146 43206 43150 43210
LSIG - - 43148 43208 43152 43212
MS - - - - - -
150kA E6V 63 6300A LSI - - 43266 43311 43270 43315
LSIG - - 43268 43313 43272 43317
Emax Air Circuit BreakersEmax E6H, H/f, V Drawout
Ratings @ 415V
Icu Ics Icw (1sec)
E6H 100kA 100kA 100kA
E6H/f 100kA 100kA 100kA
E6V 150kA 125kA 100kA
1SDA0 R1Terminal type 3 pole 4pole
Rear HorizontalE6H & E6V 37825 37830
E6H/f n/a 50816
Rear VerticalE6H & E6V 37876 37880
E6H/f n/a 50821
Moving PortionsOrdering example: place five digit code below into order reference eg 1SDA0 39676 R1. For E6H 3 pole version for use with fully rated external neutral CT, add /FRN to order referenceeg:1SDA039791R1/FRN. For E6H 4 pole fully rated neutral version use E6H/f part numbers
Refer to sales office for breakers fitted with PR113 release
Fixed PortionsOrdering example: place five digit code below into order reference eg 1SDA0 39676 R1Front, Flat and mixed terminal versions available on request, refer to technical catalogueFor E6H 4 pole fully rated neutral version use E6H/f part numbers
* Note: Available in 4 pole ( fully rated neutral) version only
* Note: Available with 50% rated neutral only
ABB LIMITED 4/78
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
Emax Air Circuit BreakersEmax fixed part accessories
Electrical Accessories
1). Shunt opening/closing release
E 1/6 1SDA0 R1
24 V 38286
30 V 38287
48 V 38288
60 V 38289
110...120 V 38290
120...127 V 38291
220...240 V 38292
240...250 V 38293
380...400 V 38294
440 V 38295
the shunt opening release and closng release share the same construction and are therefore interchangable. Their function is determined bythe position in which they are mounted on the circuit-breaker.
2a). Undervoltage release
E1/6 1SDA0 R1
24 V 38306
30 V 38307
48 V 38308
60 V 38309
110...120 V 38310
120...127 V 38311
220...240 V 38312
240...250 V 38313
380...400 V 38314
440...480 V 38315
2b). Electronic time-delay device for undervoltage release
E1/6 1SDA0 R1
24...30 V 38316
48 V 38317
60 V 38318
110...115 V 38319
220...250 V 38320
3). Geared motor for automatic charging of closing springs
E1/6 1SDA0 R1
24...30 V 38321
48...60 V 38322
100...130 V 38323
220...250 V 38324
supplied as standard with limit contact and microswitch for signalling the closing springs are charged
ABB LIMITED 4/79
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
Emax Air Circuit BreakersEmax fixed part accessories
Electrical Accessories cont...
4). Signal for overload current releases tripped
E 1/6 1SDA0 R1
Mechanical 38337
Electrical 1) 38338
1) Requires mechanical signal as well.
5a). Electrical signalling of circuit-breaker open/closed
E1/6 1SDA0 R1
4 auxilliary contacts 2) 38326
10 auxilliary contacts 3) 4) 38327
15 additional auxilliary contacts 5) 43475
15 additional auxilliary contacts (special version for withdrawable) 5) 48827
2) Order for MS-CS-MT-MTP version only. Already included for automatic circuit-breaker.3) Not available with PR112 release.4) Order for MS-CS-MT-MTP version. Order as a loose kit only for automatic circuit-breaker5) Outside circuit-breaker. Order as alternative to various types of interlock and to accessory 8e.
For mounting on fixed circuit-breaker requires accessory 10.4 as well (interlock plate for fixed circuit-breaker)
5b). Electrical signalling of connected/isolated/isolated for test position
1SDA0 R1
E1/E6 - 5 auxilliary contacts 38361
E1/E2 - 10 auxilliary contacts 3 poles 38360
E1/E2 - 10 auxilliary contacts 4 poles 43467
E3 - 10 auxilliary contacts 3 poles 43468
E3 - 10 auxilliary contacts 4 poles 43469
E4/E6 - 10 auxilliary contacts 3/4 poles 43470
5c). Contact for signalling closing springs charged
E1/6 1SDA0 R1
- 38325
Order as alternative to geared motor
5d). Contact for signalling undervoltage release energised
E1/6 1SDA0 R1
1 normally open contact 38340
1 normally closed contact 38341
ABB LIMITED 4/80
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
Emax Air Circuit BreakersEmax fixed part accessories
Electrical Accessories cont...
6a). Current transformer for neutral conductor outside circuit-breaker
E2 1SDA0 R1
R250 38269
R400 38270
R800 38271
R1250 38272
R1600 38273
R2000 38274
E3 1SDA0 R1
R250 48952
R400 48953
R800 38277
R1250 38278
R1600 38279
R2000 38280
R2500 38281
R3200 38282
E4 1SDA0 R1
R2000 48957
R3200 38275
R4000 38276
E6 1SDA0 R1
R3200 48958
R4000 38283
R5000 38284
R6300 38285
6b). Homopolar toroid for the main power supply earthing conductor
1SDA0 R1
In 100A 48067
In 250A 48068
In 400A 48069
In 800A 48070
ABB LIMITED 4/81
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
Emax Air Circuit BreakersEmax fixed part accessories
Mechanical Accessories
7). Mechanical operation counter
E 1/6 1SDA0 R1
38345
1) Requires mechanical signal as well.
8a). Lock in open position
E1/6 - key lock 1SDA0 R1
for 1 circuit-breaker (different keys) 38350
for sets of circuit-breakers (same keys No. 3004222) 38346
for sets of circuit-breakers (same keys No. 0025431) 38347
for sets of circuit-breakers (same keys No. 0233424) 38348
for sets of circuit-breakers (same keys No. 0335452) 38349
padlock (as alternative to mechanical accessory 3a) 38351
castell lock (not supplied please order from Castell International Ref: PDS01388(s)) NONSTD161
8b). Circuit-breaker lock in connected/isolated/isolated for test position
E1/6 - key lock + padlock 1SDA0 R1
for 1 circuit-breaker (different keys) 38356
for sets of circuit-breakers (same keys No. 3004222) 38352
for sets of circuit-breakers (same keys No. 0025431) 38353
for sets of circuit-breakers (same keys No. 0233424) 38354
for sets of circuit-breakers (same keys No. 0335452) 38355
8c). Accessory for lock in isolated/isolated for test position
E1/6 1SDA0 R1
- 38357
Order in addition to mechanical accessory 2b
8d). Accessory for padlock device for shutters
E1/6 1SDA0 R1
- 38363
8e). Mechanical lock for compartment door
E1/6 1SDA0 R1
- 1) 2) 3) 45039
1) Order as an alternative to the various types of interlocks and electrical accessory 5a (15 auxilliary contacts)2) the use of accessory 10.2 is necessary for installation3) for fixed circuit-breaker, plate 10.4
ABB LIMITED 4/82
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
Emax Air Circuit BreakersEmax fixed part accessories
Mechanical Accessories
9a). Protection cover opening and closing pushbuttons
E 1/6 1SDA0 R1
- 38343
9b). IP54 protective cover for door
E1/6 - key lock 1SDA0 R1
- 38344
10a). Interlock cable set (order one per interlock set)
E1/6 Horizontal VerticalDescription 1SDA0 R1 1SDA0 R1
A type cable set 38329 38333
B type cable set 38330 38334
C type cable set 38331 38335
D type cable set 38332 38336
10b). Interlock mechanism (order one per breaker)
Type 1SDA0 R1
E1 38366
E2 38366
E3 38367
E4 - 3 poles 38368
E5 - 4 poles / E6 - 3 poles 43466
E6 - 4 poles 38369
10c). Interlock mechanism (order one per breaker)
Type 1SDA0 R1
A E2 - E6 fixed or moving part 38364
B E2 - E6 fixed or moving part 38364
C E2 - E6 fixed or moving part 38365
D E2 - E6 fixed or moving part 38364
10d). Interlock plate for fixed breaker (order one per breaker)
E1/6 1SDA0 R1
- 38363
Mechanical Interlock Ordering Example:C type horizontal interlock for 3 off E2N drawout pattern breakers1 off C type cable set (10a) 1SDA038331R12 off Interlock mechanism (10c) 1SDA038366R13 off Interlock mechanism (10b) 1SDA038365R1
3 off E2Nfixed pattern breakers3 off Interlock mechanism (10d) 1SDA038358R1
ABB LIMITED 4/83
www.abb.com/lowvoltage email [email protected] Telephone 02476 368549 Facsimile 02476 368401
Emax Air Circuit BreakersConversion kit for fixed circuit-breaker or fixed parts
Conversion Kits
Kit for converting fixed circuit-breaker with horizontal rear terminals to vertical rear terminals
Type 1SDA0 R13 terminals for 3 poles 4 terminals for 4 poles
E1 38052 38057
E2 38053 38058
E3 38054 38059
E4 38055 38060
E6 38056 38061
Each kit fits both upper and lower application.To convert a complete circuit-breaker, order 2 kits.
Kit for converting fixed circuit-breakerwith horizontal rear terminals to front terminals
Type 1SDA0 R13 terminals for 3 poles 4 terminals for 4 poles
E1 38062 38067
E2 38063 38068
E3 38064 38069
E4 38065 38070
E6 38066 38071
Each kit fits both upper and lower application.To convert a complete circuit-breaker, order 2 kits.
Kit for converting fixed partswith horizontal rear terminals to front terminals
Type 1SDA0 R13 terminals for 3 poles 4 terminals for 4 poles
E1 38062 38067
E2 45031 45035
E3 45032 45036
E4 45033 45037
E6 45034 45038
Each kit fits both upper and lower application.To convert a complete circuit-breaker, order 2 kits.