Type RADSB Transformer differential relay abb 1MDB04301-YN Page 1 Issued Dec 2003 changed since Oct 2001 Data subject to change without notice Abstract Complete phase and ground protection Static measuring circuits with active filters for optimum utilization of harmonics in the current circuits Up to three kilometer of high voltage cable can be included in the differential zone Harmonic restrained operating time 30 ms at 3 times pick-up current Unrestrained operating time 10-20 ms at 2 times pick-up current with minimum impulse time of 3 ms Variable percentage restraint for external fault security and on-load tap-changer transformer protection Second harmonic restraint from all three phases for inrush security Fifth harmonic restraint from all three phases for overexcitation security Sensitivity can be set to 20, 25, 35 or 50 per cent of rated current 1 A or 5 A Unrestrained operation does not respond to dc offset and can be set 8, 13 or 20 times relay rated current Provided with separate auxiliary CTs for ratio and phase angle matching and containment of zero sequence current No restrictions on the type of main CT connections Long CT secondary leads are feasible with 1 A relay Built-in trip relay, indicator and test switch Application The RADSB is a protective relay intended for all types of auto-transformers and multiple winding transformers. By including additional input restraint modules, up to 6 transformer windings can be connected. The relay is also well suited for generator and step-up transformer overall protection, often including the auxiliary transformer in the protected zone. The non-linear percentage restraint characteristic provides the required restraint for external faults. This makes the relay suitable for use with multi- winding transformers, auto-transformers or in a system where one transformer winding is directly connected to two or more breakers. The characteristics are designed to provide excellent internal fault sensitivity; RADSB is virtually unaffected by load restraint. The RADSB relay also has an unrestrained instantaneous module which responds to the total differential current (less any dc component). This module will provide redundant operation for severe internal faults. The second and fifth harmonic restraint voltages for each phase are paralleled and the sum used for harmonic restraint for each phase. The polyphase harmonic restraint circuitry prevents the relay from operating on inrush currents yet has a minimum effect on relay sensitivity if an internal fault occurs during energization. The fifth harmonic is used to prevent operation of the relay due to possible overexcitation of the transformer. Overexcitation protection should be provided by a V/Hz relay (preferably type RATUB which has an inverse-time operating characteristic). Auxiliary CTs are used to balance the main CT ratios. In addition auxiliary CTs may be used to reduce the effective lead burden of long secondary leads. The differential zone of the relay can include up to three kilometre of high voltage cable since adequate filtering provides security against high current oscillations.

abb Type RADSB - Electro Services · 2018-02-03 · DC-DC converter type RXTUG 22H Transformer unit type RTQTB 060 and 061 Measuring unit type RXDSB 4 Tripping relay type RXMS 1 Indicator

  • Upload
    others

  • View
    17

  • Download
    1

Embed Size (px)

Citation preview

Page 1: abb Type RADSB - Electro Services · 2018-02-03 · DC-DC converter type RXTUG 22H Transformer unit type RTQTB 060 and 061 Measuring unit type RXDSB 4 Tripping relay type RXMS 1 Indicator

Type RADSBTransformer differentialrelay

abb1MDB04301-YN

Page 1Issued Dec 2003changed since Oct 2001Data subject to change without notice

Abstract • Complete phase and ground protection• Static measuring circuits with active filters for

optimum utilization of harmonics in the currentcircuits

• Up to three kilometer of high voltage cable canbe included in the differential zone

• Harmonic restrained operating time 30 ms at 3times pick-up current

• Unrestrained operating time 10-20 ms at 2 timespick-up current with minimum impulse time of3 ms

• Variable percentage restraint for external faultsecurity and on-load tap-changer transformerprotection

• Second harmonic restraint from all threephases for inrush security

• Fifth harmonic restraint from all threephases for overexcitation security

• Sensitivity can be set to 20, 25, 35 or 50 percent of rated current 1 A or 5 A

• Unrestrained operation does not respond todc offset and can be set 8, 13 or 20 timesrelay rated current

• Provided with separate auxiliary CTs for ratioand phase angle matching and containmentof zero sequence current

• No restrictions on the type of main CTconnections

• Long CT secondary leads are feasible with1 A relay

• Built-in trip relay, indicator and test switch

Application The RADSB is a protective relay intended for alltypes of auto-transformers and multiple windingtransformers. By including additional input restraintmodules, up to 6 transformer windings can beconnected. The relay is also well suited forgenerator and step-up transformer overallprotection, often including the auxiliary transformerin the protected zone.

The non-linear percentage restraint characteristicprovides the required restraint for external faults.This makes the relay suitable for use with multi-winding transformers, auto-transformers or in asystem where one transformer winding is directlyconnected to two or more breakers. Thecharacteristics are designed to provide excellentinternal fault sensitivity; RADSB is vir tuallyunaffected by load restraint.

The RADSB relay also has an unrestrainedinstantaneous module which responds to the totaldifferential current (less any dc component). Thismodule will provide redundant operation for severeinternal faults.

The second and fifth harmonic restraint voltagesfor each phase are paralleled and the sum usedfor harmonic restraint for each phase. Thepolyphase harmonic restraint circuitry preventsthe relay from operating on inrush currents yethas a minimum effect on relay sensitivity if aninternal fault occurs during energization. Thefifth harmonic is used to prevent operation ofthe relay due to possible overexcitation of thetransformer. Overexcitation protection should beprovided by a V/Hz relay (preferably type RATUBwhich has an inverse-time operatingcharacteristic).

Auxiliary CTs are used to balance the main CTratios. In addition auxiliary CTs may be used toreduce the effective lead burden of longsecondary leads. The differential zone of therelay can include up to three kilometre of highvoltage cable since adequate filtering providessecurity against high current oscillations.

Page 2: abb Type RADSB - Electro Services · 2018-02-03 · DC-DC converter type RXTUG 22H Transformer unit type RTQTB 060 and 061 Measuring unit type RXDSB 4 Tripping relay type RXMS 1 Indicator

Type RADSBTransformer differentialrelay

1MDB04301-YN

Page 2

Fig. 1 Application examples for the RADSBtransformer differential relay.

Applicatio n The RADSB relay is available with two, three, fiveor six through-fault restraint inputs and can be usedfor dual-winding or multi-winding transformerswhich have one or more circuit-breakers for eachwinding.

The relay comprises the following modules:

With or without test switch (Screw type termination)DC-DC converter type RXTUG 22HTransformer unit type RTQTB 060 and 061Measuring unit type RXDSB 4Tripping relay type RXMS 1Indicator type RXSGA 1

In RXSGA 1, LEDs indicate unrestrained operationand restrained operation and also the phase whichcaused the latter operation.

The RADSB relay can be connected directly to themain current transformers; however, when this isnot practical, auxiliary CTs are used for ratio andphase-angle matching purposes. Auxiliary CTs alsoprovide an additional point of insulation so that themain CTs can be grounded independent of the

ground at the relay location in addition to mainCT secondary grounding. In the case of longCT leads, auxiliary current transformers can beused to reduce the secondary CT lead burden tothe relay or the 1 A relay can be used.

When internal faults such as short circuits betweenphases, groundfaults or inter-turn short circuitsoccur, the differential relay rapidly disconnects thesupply to the transformer. On the other hand, theRADSB restraints for differential currents which arecaused by external faults, inrush currents orovervoltages. The operating values for restrainedand unrestrained operations are set with switcheson the measuring unit. The operating times of therelay are shown in fig. 2.

RADSB has static measuring circuits with activefilters to enable optimum utilization of theharmonics in the differential current whenrestraining to inrush currents and overvoltages. Therestraint limits in the case of external faults areshown in fig. 3.

Fig. 2 Operating times for restrained andunrestrained operation, with RXMS 1 as thetripping relay.

Fig. 3 The restraint of the relay for externalfaults is variable and is adapted to themagnitude of the through current

where Ix and Iy are the highestincoming and outgoingcurrents, respectively, of thetransformer.

Ix + Iy

2

RADSB3

restraintinput

RADSB5

restraintinput

RADSB2

restraintinput

Operating time in ms

Restrained operation

Unrestrained operating

1 1.5 2 3 5 10 15 20 30

5045403530

25

20

15

109876

Differential current in multiples of the set operating value

Operation

Non-operation

Through current in multiples of rated current

1 1.5 2 3 5 10 20

%

60

40

20

Differential current in per cent of the through current

Id/I1+I2

2

I1 + I2

2

0.5XIn

0.35XIn

0.25XIn

0.20XIn

Page 3: abb Type RADSB - Electro Services · 2018-02-03 · DC-DC converter type RXTUG 22H Transformer unit type RTQTB 060 and 061 Measuring unit type RXDSB 4 Tripping relay type RXMS 1 Indicator

Type RADSBTransformer differentialrelay

1MDB04301-YN

Page 3

Technical data Rated current In 1 or 5A

Rated frequency 50 or 60 Hz

Restrained operatingvalue Isr Settable 20, 25, 35, or

50% of In

Unrestrainedinstantaneousopreating value Isu Reconnectible : 8,

13 and 20 times In

Operating time: RXMS 1 RXME 18at Id = 3 x Isr 30 ms 50 msat Id = 2 x Isu 10-20 ms 40 ms

Overload capacity:withstands1 A version 10 A continuously

100 A for 1 s

5 A version 20 A continuously250 A for 1 s

Permitted ambienttemperature –25 to 550 C

Auxiliary voltage Un dc 24 – 36 V, 48 – 60 V(EL) or 110 – 250 V

+ 10% – 20%

Power consumptiontotal at rated current(approximately)In = 1 A 0.02 VA/phaseIn = 5 A 0.14 VA/phase

In diff. circuit 0.25 x In

In = 1 A 0.003 VA/phaseIn = 5 A 0.02 VA/phaseIn auxiliary voltage circuitbefore operation 10 Wat operation 14 WDielectric testscurrent circuits 50 Hz, 2.5 kV, 1 minremaining circuits 50 Hz, 2.0 kV, 1 minImpulse votlage test 1.2/50µs, 5.0 kV, 0.5 J

Power frequency test 50 Hz, 0.5 kV, 2 minFast transient test 4–8 kV, 2s1 MHz burst test 2.5 kV, 2s

Auxiliary CTs typeSLCE 12, tapsfrom 0.75 – 0.95 and4 – 4.8 in one per cent steps

To order Specify :• Type RADSB• Quantity• Ordering no. from table 1 for COMBIFLEX version & refer page 7 for screw type version.

Table 1, RADSB Selection:

No. of restraint Rated Freq. Aux. Modular size Ordering Circuit diagraminput current Voltage No.

2 1A 50 Hz 110 VDC / 220 VDC 4 S, 36 C IN 330-021-CA IN 7454-3344-CE

3 1A 50 Hz 110 VDC / 220 VDC 4 S, 42 C IN 330-041-CA 7454-356-CC

5 1A 50 Hz 110 VDC / 220 VDC 4 S, 60 C IN 330-051-CA 7454-359-CC

2 5A 50 Hz 110 VDC / 220 VDC 4 S, 36 C IN 330-021-CB IN 7454-3344-CE

3 5A 50 Hz 110 VDC / 220 VDC 4 S, 42 C IN 330-041-CB 7454-356-CC

5 5A 50 Hz 110 VDC / 220 VDC 4 S, 60 C IN 330-051-CB 7454-359-CC

Page 4: abb Type RADSB - Electro Services · 2018-02-03 · DC-DC converter type RXTUG 22H Transformer unit type RTQTB 060 and 061 Measuring unit type RXDSB 4 Tripping relay type RXMS 1 Indicator

Type RADSBTransformer differentialrelay

1MDB04301-YN

Page 4

IN7454-3344-CE – Circuit diagram for RADSB with 2 restraint inputs

7454-356-CC – Circuit diagram for RADSB with 3 restraint inputs

3Id/I>

3Id/I>

3Id/I>

3Id/I>

Page 5: abb Type RADSB - Electro Services · 2018-02-03 · DC-DC converter type RXTUG 22H Transformer unit type RTQTB 060 and 061 Measuring unit type RXDSB 4 Tripping relay type RXMS 1 Indicator

Type RADSBTransformer differentialrelay

1MDB04301-YN

Page 5

7454-359-CC – Circuit diagram for RADSB with 5 restraint inputs

Page 6: abb Type RADSB - Electro Services · 2018-02-03 · DC-DC converter type RXTUG 22H Transformer unit type RTQTB 060 and 061 Measuring unit type RXDSB 4 Tripping relay type RXMS 1 Indicator

ABB Ltd.,Automation Products5 & 6, II Phase, Peenya Ind. Estate, Bangalore-560 058Tel: 080-8395181, Tlx: 0845-5094 ABBP IN, Telefax: 080-8396121

abb

The following versions of mounting arrangement are available for mounting the relays

• 19’’ Rack mounting with equipment frame (apparatus frame+door) – IN5628-3003-A

• Flush mounting system (RHGX20) – IN5609-1200-D

Specify the mounting arrangement as per requirement during ordering

Panel cutout details for 19’’ rack mounting and flush mounting are as shown below

Type RADSBTransformer differentialrelay

1MDB04301-YN

Page 6

Three-phase harmonically restrained transformerdifferential relay having second harmonic restraintfor security against transformer inrush current andfifth harmonic restraint against over excitation.

The relay shall have a variable through-currentrestraint feature. For security reasons, the restraintshould be summed from all three phases. Aninstantaneous unrestrained function is to be

SampleSpecification

provided set at 8, 13 or 20 times rated current.Minimum operating current of restraint module tobe set at 25 to 50 per cent of rated current in threesteps. The protected differential zone shall be ableto include up to one kilometre of high voltage cable.

Auxiliary current transformers shall be used andsupplied separately for ratio and phase anglecorrection purposes.

Buyer’s Guide No.

DC-DC converter type

RXTUG 22 H 1MRK 513001-BENAuxiliary relay type RXMS 1 1MDB08307-YNAuxiliary relay data table 1MDB08301-YN

Indicator type RXSGA 1 B03-9150E

Referenc e

Test system COMBITEST B03-9510EDimensions 1MDB14315-YNFurther information :

User’s Guide 1MDU04007-EN

Mounting:

RHGX 20 Case19’’ rack

All dimensions in mm7

17519’’ rack101.6

36.5

465

446

RHGX 20Flush mounting

448

190

Page 7: abb Type RADSB - Electro Services · 2018-02-03 · DC-DC converter type RXTUG 22H Transformer unit type RTQTB 060 and 061 Measuring unit type RXDSB 4 Tripping relay type RXMS 1 Indicator

Type RADSB 1MDB04301-YNTransformer differentialRelay Page 7