ABB Power T&D Company ABB
Distribution AutomationDistribution AutomationOverview, Activities, and RoadmapOverview, Activities, and Roadmap
David G. Hart & Jay ParkDavid G. Hart & Jay ParkSeptember 1, 1999September 1, 1999
ABB Power T&D Company ABB
Overview - AutomationOverview - Automation
• Automation is the ability to remotely monitor and control the network, collect information, and provide information in a useful manner to the end user
DPU2000RABB
DPU2000RABB
DPU2000RABB
ABB Power T&D Company ABB
Overview - Levels of AutomationOverview - Levels of Automation
DPU2000RABB
LEVEL 1Intelligent Equipment
C
PICKUPPHASEGROUND
REMOTE ENABLE
GROUND BLOCK
ALTERNATE PU
SEF ENABLE
RECLOSE BLOCK
PROG 1
PROG 2
STATUS
l
0
LEVEL 2Communications
LEVEL 3Real-Time Control
LEVEL 4Off-Line Analysis
ABB Power T&D Company ABB
Substation Automation Substation Automation
• ABB Distribution Substation Solution
DPU2000R
ABB
DPU2000R
TPU2000R
ABB
TPU2000R
MicroShield OC
Power RICH System
PCD2000
ABB Power T&D Company ABB
Substation Automation - Substation Automation - Power Power RICHRICH System System
• Provides graphical user interface for control, monitoring, and device settings
• Utilizes standard local area network - MODBUS, MODBUS PLUS, DNP 3.0 & 160 other protocols
• Allows integration of digital protection/ control/ metering/ load profile using the 2000 series
• Supports MODBUS & DNP 3.0 with PCD2000
ABB Power T&D Company ABB
Substation Automation - ApplicationsSubstation Automation - Applications
• Interface to SCADA• Control with Power RICH System• Monitoring with Power RICH System• Restoration of system following an outage• etc.
ABB Power T&D Company ABB
Automation - BenefitsAutomation - Benefits
• Provides remote, immediate, status of the substations in the region
• Power RICH System provides monitor & control of multiple vendors devices NOW & in the future
• Personnel safety via remote control• One point of contact, ABB contact list• Advanced problem analysis with advanced ABB
devices
ABB Power T&D Company ABB
Feeder Automation Feeder Automation
• ABB Feeder Solution
VR3S Recloser VS3S Switch
ABB Power T&D Company ABB
15-27kV Three Phase Automatic Recloser15-27kV Three Phase Automatic Recloser15-27kV Three Phase Automatic Recloser15-27kV Three Phase Automatic Recloser
RATINGS
15 kV 27 kV 38 kV
Max. Voltage 15.5 27 38 kV
Cont. Current 560/800 560/800 560/800A
Int. Current 12/16 12.5/16 12.5/16 kA
BIL 110 125 170 kV
ABB Power T&D Company ABB
Interrupting UnitInterrupting UnitInterrupting UnitInterrupting Unit
Mechanical trip - for manual operation
Encapsulated vacuum Interrupters - low maint-enance; 10,000 loadbreak operations
Integrated Sensors - protected from the environment, designedto not saturate during fault conditions forfault information
Large easy to view Open/Close Indicators
Heavy gauge cabinet -Available in mild orstainless steel Recloser cable
includes wires forfor 3 phase voltage transformer wiring
ABB Power T&D Company ABB
Mounting ArrangementsMounting ArrangementsMounting ArrangementsMounting Arrangements• Substation Mounted• Pole Mounted
ABB Power T&D Company ABB
PCD2000 -front panel PCD2000 -front panel PCD2000
C
PICKUP
PHASE
GROUND
REMOTE BLOCKED
GROUND BLOCKED
ALT SETTINGS 1
SEF BLOCKED
RECLOSE BLOCKED
PROG 1
PROG 2
G-NORMALR-FAIL
LOCKOUT
OPEN
CLOSE
CLEAR
ENTER
Fault indicating targets - highlyvisible, pickup,phase and groundtrip and lockoutlights
Push-buttoncontrols withindicating LED’s
Control status indication - usesself-checking diagnostics
HMI - Human machineinterface; password protected, easy to use
Opticalcommunicationsport; RS-232C
Open/Closepush-buttons andposition indicatinglight
LCD Display - backlitDisplays metering vals and post fault information
PCD2000 Recloser Control FeaturesPCD2000 Recloser Control FeaturesPCD2000 Recloser Control FeaturesPCD2000 Recloser Control Features
ABB Power T&D Company ABB
PCD2000 - Advanced Protective FunctionsPCD2000 - Advanced Protective FunctionsPCD2000 - Advanced Protective FunctionsPCD2000 - Advanced Protective Functions
Under/Over Voltage control and alarming*– Very useful for detection of high side fuse operation/ single phasing condition– Also used for loop sectionalizing, voltage transfer– Allows time delayed load shedding
Under/Over Frequency control and alarming* (1phase or 3 phase)– Allows enhanced load shedding capability
Directional specific overcurrent protection*– Allows for closed loop schemes
Directional specific power flow control*– Allows for changing to alternate profile during backfeed condition
Directional specific overcurrent protection*– Allows for closed loop schemes
* Requires voltage inputs
ABB Power T&D Company ABB
PCD2000 MeteringPCD2000 MeteringAccuracy of Volts and Amps to ±1%Accuracy of Volts and Amps to ±1%PCD2000 MeteringPCD2000 MeteringAccuracy of Volts and Amps to ±1%Accuracy of Volts and Amps to ±1%
CurrentsMagnitude and Angle for Ia, Ib, Ic, & InPositive, Negative, and Zero Sequence
CurrentsMagnitude and Angle for Ia, Ib, Ic, & InPositive, Negative, and Zero Sequence
Voltages*Phase Magnitude and AnglePositive and Negative Sequence
Voltages*Phase Magnitude and AnglePositive and Negative Sequence
Watts*Kilowatts Per PhaseTotal Kilowatts for 3-Phase
Watts*Kilowatts Per PhaseTotal Kilowatts for 3-Phase
Vars*Kilovars Per PhaseTotal Kilovars for 3-Phase
Vars*Kilovars Per PhaseTotal Kilovars for 3-Phase
Watt-Hours*Kilowatt-Hours Per PhaseKilowatts for 3-Phase
Watt-Hours*Kilowatt-Hours Per PhaseKilowatts for 3-Phase
Var-Hours*Kilovar-Hours Per PhaseKilovars for 3-Phase
Var-Hours*Kilovar-Hours Per PhaseKilovars for 3-Phase
Power Factor*For Wye VTs
Power Factor*For Wye VTs
Frequency*Hertz
Frequency*Hertz
* Requires Voltage Inputs
ABB Power T&D Company ABB
PCD2000 - Data recordsPCD2000 - Data recordsPCD2000 - Data recordsPCD2000 - Data recordsLoad Profile
– Up to 160 days of data
– Records kW, kVAR & volts per phase
Operation/Fault Records • 128 recloser operations • Fault duty accumulator for interrupters• Operation and trip counters• Fault records
– Records detailed fault data for last 32 faults (including relay times, distance to fault)
– Basic fault data for last 128 faults
ABB Power T&D Company ABB
PCD2000 - Advanced Data recordsPCD2000 - Advanced Data recordsPCD2000 - Advanced Data recordsPCD2000 - Advanced Data records
Oscillographic capture– Valuable tool for analyzing post fault waveforms
– Records total of 64 cycles per phase currents and voltages 8 distinct events
Power Quality records per ANSI/IEEE 1159 Standard– Very powerful tool for pinpointing source of power quality problems
– Records voltage sags, swells, Total Harmonic Distortion, Total Demand Distortion
– Can use ANSI recommended voltage/duration thresholds or can be user specified
– Holds up to 256 records
ABB Power T&D Company ABB
PCD2000 Communication FeaturesPCD2000 Communication Features
• Open protocols, DNP3.0, Modbus ASCII & RTU included with each unit
• Doesn’t require additional hardware for protocols• RS232, RS485, programmable I/O and optical port are
all standard. Fiber port is optional• Fiber port is unsurpassed, fully regenerates signal,
preventing signal attenuation• Software for the PCD2000, WinPCD, has dial up
capability and an extensive control interface• Control Cabinet has plenty of room for a radio or
modem, and a 12 V DC power supply is optional
ABB Power T&D Company ABB
Soon to be released:Soon to be released:
• Single phase tripping– Very advantageous for residential loads– Reduces affected customers by 2/3 rds – Single or three phase lockout selection– Option to block ground tripping after single phase trip/lockout– Can change to three phase trip only based on KW demand
threshold
• Loop Scheme automatic reconfiguration (10/99)– Does not require communications between units or master– One control used for both main feeder and tie (or midpoint)
reclosers– Has separate user interface with per phase voltage indication
recloser status and override.
ABB Power T&D Company ABB
SCD2000 -Front Panel SCD2000 -Front Panel SCD2000
C
Phase A
Phase B
Phase C
REMOTE BLOCKED
SECTIONALIZE BLOCKED
OPERATIONS COUNTER
SWITCH SELECT
LED TEST
BATTERY TEST
PROG 1
G-NORMALR-FAIL
Ground
OPEN
CLOSE
CLEAR
ENTER
Fault indicating targets - highlyvisible, pickup,phase and groundtrip and lockoutlights
Push-buttoncontrols withindicating LED’s
Control status indication - usesself-checking diagnostics
HMI - Human machineinterface; password protected, easy to use
Opticalcommunicationsport; RS-232C
Open/Closepush-buttons andposition indicatinglight
LCD Display - backlitDisplays metering vals and post fault information
SCD2000 Switch Control Features SCD2000 Switch Control Features
ABB Power T&D Company ABB
SCD2000 - Control FunctionsSCD2000 - Control FunctionsSCD2000 - Control FunctionsSCD2000 - Control Functions
Features:• Fault indication that utilizes currents or
currents and voltages• Phase imbalance• Switch failure alarm• Number of operations• Sectionalizing function• Automatic source transfer
ABB Power T&D Company ABB
Substation/Feeder IntegrationSubstation/Feeder Integration
Communications Gateway
Power RICH System
ABB Power T&D Company ABB
DCD2000 DCD2000
• DCD 2000 Communications Gateway Development - Located in substation to link substation and feeder devices– Provides multiple master/slave operation in one integrated box– Provides interface to multiple applications
Port for Power RICH System Port for existing SCADA RTU MODEM for off-line applications being developed such as PQ
– Provides interface to substation and field devices RS-232 with handshaking for feeder long distance radio RS-485 twisted pair to connect substation relays fiber optic to connect yard equipment
– Support standard protocols (MODBUS and DNP 3.0)
ABB Power T&D Company ABB
DCD2000 Communications GatewayDCD2000 Communications Gateway
RS-232 Leased Line
Modem/232
RS-485
Remote RFDial-Up
Fiber Optic
Substation
Feeder
Real TimeControl
Off-Line Applications
Gateway
DPU2000RABB
DPU2000RABB
DPU2000RABB
RS-232
Industrial PLC
Power RICH System
ABB Power T&D Company ABB
DCD2000 Communications GatewayDCD2000 Communications GatewaySCADA
Off-Line Applications
Feeder
DPU2000RABB
DPU2000RABB
DPU2000RABB
DPU2000RABB
DPU2000RABB
Substation
Radio
Twisted Pair
Fiber
PLCPower RICH System
ABB Power T&D Company ABB
Substation/Feeder Integration - ApplicationSubstation/Feeder Integration - Application• PLC monitors DPU2000 to determine breaker is open,
opens other side of fault, and restores power with tie switch
DPU2000RABB
DPU2000RABB
PLC
DCD2000 Gateway
ABB Power T&D Company ABB
Substation/Feeder Integration - ApplicationSubstation/Feeder Integration - Application• Power RICH System provides HMI and control• PQIS monitors key customers
DPU2000RABB
DPU2000RABB
DPU2000RABB
DPU2000RABB
DPU2000RABB
DPU2000RABB
Power RICH SystemPQIS
ABB Power T&D Company ABB
Off-Line ApplicationsOff-Line Applications
• Provide utility with new off-line applications that utilize intelligence in equipment
• Topics: PQ, load profile, fault location, etc.
ABB Power T&D Company ABB
Off-Line ApplicationsOff-Line Applications
• Power Quality - Provide industrial account representative with PQ data on key customers from reclosers/switches, relays and meters
Use IEEE definitions Easy to understand presentation Distributed PC users in different departments Local or corporate database (s) Scalable number of monitoring devices Data captured in relay/controller
ABB Power T&D Company ABB
DemonstrationDemonstration
DPU2000R
OC Relay
Power RICH System
C
REMOTE ENABLE
ALTERNATE PU
ABB PCD 2000
Gateway Modbusover RS-485
MDS Radio
PLCPhone
SimulatorOff-Line Application
Modbus over RS-232
C
PICKUPPHASEGROUND
REMOTE ENABLE
GROUND BLOCK
ALTERNATE PU
SEF ENABLE
RECLOSE BLOCK
PROG 1
PROG 2
STATUS
l
0
C
PICKUP
PHASEGROUND
REMOTE ENABLE
GROUND BLOCK
ALTERNATE PU
SEF ENABLE
RECLOSE BLOCK
PROG 1
PROG 2
STATUS
l
0
C
PICKUP
PHASE
GROUND
REMOTE ENABLE
GROUND BLOCK
ALTERNATE PU
SEF ENABLE
RECLOSE BLOCK
PROG 1
PROG 2
STATUS
l
0
PCD2000