© ABB GroupDecember 2, 2016 | Slide 1

Substation Communication withIEC 61850 and ApplicationExamples

ABB Medium Voltage Products – Sanjay Sharma, 29.11.2016

Page 2: ABB Medium Voltage Products – Sanjay Sharma, 29.11.2016 ... · PDF fileSubstation Communication with IEC 61850 and Application Examples ABB Medium Voltage Products – Sanjay Sharma,

© ABB GroupDecember 2, 2016 | Slide 2

Substation communication using IEC 61850Contents

1. Introduction2. IEC 61850 Overview, IEC 61850 Edition 23. IEC 61850 Horizontal Communication4. Relion® Performance5. IEC 61850 in DA products6. Application Examples7. Ethernet Redundancy8. Conclusion

Page 3: ABB Medium Voltage Products – Sanjay Sharma, 29.11.2016 ... · PDF fileSubstation Communication with IEC 61850 and Application Examples ABB Medium Voltage Products – Sanjay Sharma,

© ABB GroupDecember 2, 2016 | Slide 3

Communication SolutionsContents

1. Introduction2. IEC 61850 Overview, IEC 61850 Edition 23. IEC 61850 Horizontal Communication4. Relion® Performance5. IEC 61850 in DA Products6. Application Examples7. Ethernet Redundancy8. Conclusion

Page 4: ABB Medium Voltage Products – Sanjay Sharma, 29.11.2016 ... · PDF fileSubstation Communication with IEC 61850 and Application Examples ABB Medium Voltage Products – Sanjay Sharma,

§© ABB Group§December 2, 2016 | Slide 4

IEC 61850 Overview

§ Interoperability§ The ability of IEDs from one or several

manufacturers to exchangeinformation and use the information forthe their own functions.

§ Free configuration§ The standard shall support different

philosophies and allow a freeallocation of functions e.g. it must workequally well for centralized (RTU like)or decentralized (SCS like) systems

§ Long term stability§ The standard shall be future proof, i.e.

it must be able to follow the progress incommunication technology and theevolving system requirements

Starting point and set goals

Page 5: ABB Medium Voltage Products – Sanjay Sharma, 29.11.2016 ... · PDF fileSubstation Communication with IEC 61850 and Application Examples ABB Medium Voltage Products – Sanjay Sharma,

§© ABB Group§December 2, 2016 | Slide 5

IEC 61850 OverviewCommunication Profiles

Client -ServerCommunication

SampledValues

IEC 61850 Data Model (Objects, Services)

Ethernet Link Layer with VLAN and Priority taggingEthernet Physical Layer, 100Mb/s

Real timeCommunication

IP

MMS

Mapping

GOOSE

TCP

Page 6: ABB Medium Voltage Products – Sanjay Sharma, 29.11.2016 ... · PDF fileSubstation Communication with IEC 61850 and Application Examples ABB Medium Voltage Products – Sanjay Sharma,

§© ABB Group§December 2, 2016 | Slide 6

§ Vertical communication usingIEC 61850 MMS profile toCOM600, MicroSCADA,RTU560 or 3rd party masters

§ Based on normal TCP/IP inEthernet

§ DA relays accepts five parallelIEC 61850 clients

§ At the same time also IEC61850 horizontalcommunication and otherprotocols can be used as well

MicroSCADA Pro

IntroductionMechanical designModule functionalityCommunicationToolsApplication examplesConclusions

IEC 61850 OverviewVertical Communication Profile

Grid Automationcontroller COM600

IEC 61850MMS

Page 7: ABB Medium Voltage Products – Sanjay Sharma, 29.11.2016 ... · PDF fileSubstation Communication with IEC 61850 and Application Examples ABB Medium Voltage Products – Sanjay Sharma,

§© ABB Group§December 2, 2016 | Slide 7

IEC 61850 Edition 2Standard continues…

Data model for waterand wind application

IEC 61850 Edition 2.1 / 3New extensions in work for

smart grid

IEC 61850 Edition 1From proprietary protocols towards a

global communication standardfor substation automation

IEC 61850 Edition 2A broad, encompassing standard for

Communication Networks and Systemsfor power utility automation

Page 8: ABB Medium Voltage Products – Sanjay Sharma, 29.11.2016 ... · PDF fileSubstation Communication with IEC 61850 and Application Examples ABB Medium Voltage Products – Sanjay Sharma,

§ Technological leadership, Standard isready

§ Market needs and expectations

§ Support for both Edition 1 and Edition 2

Edition 2

§ Mature technology

§ More features to support user needs

§ Latest version (important life cycleperspective)

IEC 61850Edition 2

Today2004

ABB

Edition 1 certificates ì

PRP ìHSR ìEdition 2 certificates ì

tech

nolo

gica

llea

ders

hip

Page 9: ABB Medium Voltage Products – Sanjay Sharma, 29.11.2016 ... · PDF fileSubstation Communication with IEC 61850 and Application Examples ABB Medium Voltage Products – Sanjay Sharma,

© ABB GroupDecember 2, 2016 | Slide 9

Communication SolutionsContents

1. Introduction2. IEC 61850 Overview3. IEC 61850 Horizontal Communication4. Relion® Performance5. IEC 61850 in DA Products6. Application Examples7. Ethernet Redundancy8. Conclusion

Page 10: ABB Medium Voltage Products – Sanjay Sharma, 29.11.2016 ... · PDF fileSubstation Communication with IEC 61850 and Application Examples ABB Medium Voltage Products – Sanjay Sharma,

§© ABB Group§December 2, 2016 | Slide 10

§ Standardized horizontalcommunication in station bus§ Ethernet replaces hard-wiring

between IEDs§ GOOSE = Generic Object Oriented

Substation Event§ GOOSE is used to broadcast events

to peer IEDs in a substation§ Ethernet Multicast messages§ Can in principle transmit any kind of

process data between the IEDs§ Ethernet technology offers a fast and

reliable station bus for transfer of data§ Supervised communication

StationAutomation

SeriesCOM600

Station bus IEC 61850

Network controlcenter

IEC 61850 Horizontal CommunicationGOOSE Communication, General

Page 11: ABB Medium Voltage Products – Sanjay Sharma, 29.11.2016 ... · PDF fileSubstation Communication with IEC 61850 and Application Examples ABB Medium Voltage Products – Sanjay Sharma,

© ABB GroupDecember 2, 2016 | Slide 11

§ Conventional copper-wired inter-bay signals like:§ Time synchronization

§ Protection blocking

§ Control interlocking

GPS time source

DCS/NCC

IRIG-B

LocalSCS

Clock synch

Interlocking, shared voltage signals…

Monitoring, control, settingsStation bus (e.g. Modbus TCP)

External signals

External signals

Local SCS

Thirdpartyrelay

IEC 61850 Horizontal CommunicationTraditional Approach

Page 12: ABB Medium Voltage Products – Sanjay Sharma, 29.11.2016 ... · PDF fileSubstation Communication with IEC 61850 and Application Examples ABB Medium Voltage Products – Sanjay Sharma,

© ABB GroupDecember 2, 2016 | Slide 12

§ Inter-bay signals using IEC 61850 and GOOSE

§ SNTP based time synchronization utilising station communication andenabling +/-1 ms event time stamping accuracy

GPS time source

DCS/NCC

Monitoring, control, settingsInterlocking, shared external signalsTime synchronizationStation bus IEC 61850

External signals

Control system- SCS & GW

Thirdpartyrelay

IEC 61850 Horizontal CommunicationStation Bus with GOOSE

LocalHMI

Page 13: ABB Medium Voltage Products – Sanjay Sharma, 29.11.2016 ... · PDF fileSubstation Communication with IEC 61850 and Application Examples ABB Medium Voltage Products – Sanjay Sharma,

§© ABB Group§December 2, 2016 | Slide 13

§ Standardized Process Buscommunication in Ethernet§ Ethernet replaces hard-wiring

between IEDs§ SMV = Sampled Measured Values

§ SMV is used to broadcast stream ofraw measurement samples to peerIEDs in a substation

§ Ethernet Multicast messages withsample rate of 4kHz

§ Ethernet technology offers a fast andreliable station bus for transfer of data

§ Supervised communication

StationAutomation

SeriesCOM600

Process bus IEC 61850

Network controlcenter

IEC 61850SMV Horizontal Communication

Page 14: ABB Medium Voltage Products – Sanjay Sharma, 29.11.2016 ... · PDF fileSubstation Communication with IEC 61850 and Application Examples ABB Medium Voltage Products – Sanjay Sharma,

§© ABB Group§December 2, 2016 | Slide 14

IEC 61850 Communication

§ IEEE 1588 (Precision Time Protocol – PTP)version 2 with Power Profile timesynchronization method enabling 1 μs highaccuracy time synchronization

§ Required especially in process busapplications with sampled values usingprotocol IEC 61850-9-2LE

§ IED has a time-stamp resolution of < 4 μs

§ Grand Master Clock sends once per secondsynchronization message to network asmulticast message

§ Accurate usage of IEEE 1588 requireshardware level support from all devices innetwork

IEEE 1588 Time Synchronization

Page 15: ABB Medium Voltage Products – Sanjay Sharma, 29.11.2016 ... · PDF fileSubstation Communication with IEC 61850 and Application Examples ABB Medium Voltage Products – Sanjay Sharma,

§© ABB Group§December 2, 2016 | Slide 15

IEC 61850 Communication

§ Benefits

§ High accuracy (1 μs)

§ Reliable

§ Ethernet and HSR/PRP compliant

§ Reliability

§ Redundant clock masters

§ Backup clock masters (IED level)

§ Supervision

§ Ready for The most demanding applications

§ 1 μs = 1:1000000s

§ 1 μs < 0.05⁰

IEEE 1588 time synchronization

Page 16: ABB Medium Voltage Products – Sanjay Sharma, 29.11.2016 ... · PDF fileSubstation Communication with IEC 61850 and Application Examples ABB Medium Voltage Products – Sanjay Sharma,

§© ABB Group§December 2, 2016 | Slide 16

IEC 61850 CommunicationIEEE 1588 Example

Page 17: ABB Medium Voltage Products – Sanjay Sharma, 29.11.2016 ... · PDF fileSubstation Communication with IEC 61850 and Application Examples ABB Medium Voltage Products – Sanjay Sharma,

© ABB GroupDecember 2, 2016 | Slide 17

Communication SolutionsContents

1. Introduction2. IEC 61850 Overview3. IEC 61850 Horizontal Communication4. Relion® Performance5. IEC 61850 in DA Products6. Application Examples7. Ethernet Redundancy8. Conclusion

Page 18: ABB Medium Voltage Products – Sanjay Sharma, 29.11.2016 ... · PDF fileSubstation Communication with IEC 61850 and Application Examples ABB Medium Voltage Products – Sanjay Sharma,

§© ABB Group§December 2, 2016 | Slide 18

Relion® PerformanceGOOSE Performance Requirements

CommunicationProcessorF 1 Communication

Processor F 2

ta tb tc

Transfer time t = ta + tb + tc

Physical device PD1 Physical device PD2

§ GOOSE response time requirements from application toapplication according the standard (IEC 61850-5) are:

§ Type 1A (tripping)§ Class P2/3: <3ms

§ Class P1: <10ms (P1 = distribution S/S)

§ Type 1B (others)§ Class P2/3: <20ms

§ Class P1: <100ms

Page 19: ABB Medium Voltage Products – Sanjay Sharma, 29.11.2016 ... · PDF fileSubstation Communication with IEC 61850 and Application Examples ABB Medium Voltage Products – Sanjay Sharma,

§© ABB Group§December 2, 2016 | Slide 19

Relion® Performance615 and 630 performance testing with KEMA

§ Not only the relays are tested for IEC 61850 conformance,but also ABB switchgear solution was tested in Brnoswitchgear factory high-voltage lab

§ IEC 62271-3, High-voltage switchgear and controlgear – Part 3: Digital interfaces based on IEC 61850

§ Test arrangement above

Page 20: ABB Medium Voltage Products – Sanjay Sharma, 29.11.2016 ... · PDF fileSubstation Communication with IEC 61850 and Application Examples ABB Medium Voltage Products – Sanjay Sharma,

§© ABB Group§December 2, 2016 | Slide 20

Relion® PerformanceComparison between hardwired and GOOSE performance

§ GOOSE performance is fasterthan the overall hardwired one

§ Relion® IEDs fullfill standardrequirement for protectionapplications

§ GOOSE has higher errordetection§ Interruption of

communication link isdetected withinconfigurable setting

§ KEMA test report accordingIEC 62271-3, High-voltageswitchgear and control gear –Part 3: Digital interfaces basedon IEC 61850 available

Page 21: ABB Medium Voltage Products – Sanjay Sharma, 29.11.2016 ... · PDF fileSubstation Communication with IEC 61850 and Application Examples ABB Medium Voltage Products – Sanjay Sharma,

§© ABB Group§December 2, 2016 | Slide 21

Relion® Performance

Use case:§ UniGear with 10 bays

§ Load management system, aswell as control system interface

§ ~58% of the signals are between therelays or other automation§ Replaced by Ethernet

Utilizing GOOSE in Switchgear

Page 22: ABB Medium Voltage Products – Sanjay Sharma, 29.11.2016 ... · PDF fileSubstation Communication with IEC 61850 and Application Examples ABB Medium Voltage Products – Sanjay Sharma,

§© ABB Group§December 2, 2016 | Slide 22

Relion® PerformanceSolution benefits with GOOSE

§ Application changes can beeasily implemented viasoftware without being forceto modify wiring andrelevant drawings

Page 23: ABB Medium Voltage Products – Sanjay Sharma, 29.11.2016 ... · PDF fileSubstation Communication with IEC 61850 and Application Examples ABB Medium Voltage Products – Sanjay Sharma,

© ABB GroupDecember 2, 2016 | Slide 23

Substation communication using IEC 61850Contents

1. Introduction2. IEC 61850 Overview3. IEC 61850 Horizontal Communication4. Relion® Performance5. IEC 61850 in DA products6. Application Examples7. Ethernet Redundancy8. Conclusion

Page 24: ABB Medium Voltage Products – Sanjay Sharma, 29.11.2016 ... · PDF fileSubstation Communication with IEC 61850 and Application Examples ABB Medium Voltage Products – Sanjay Sharma,

© ABB GroupDecember 2, 2016 | Slide 24

IEC 61850 in DA ProductsAdvanced Usage of Ethernet

• WebHMI• Viewing of alarm & event list• Saving of event data• Parameter setting• Signal monitoring• Measurement viewing• Phasor Diagram viewing

• Fault Records• Upload, analysis

• Disturbance Recordings• Upload, analysis

• IED Tool Connectivity• Local, Remote

• Service Bus access• Settings export/import

Page 25: ABB Medium Voltage Products – Sanjay Sharma, 29.11.2016 ... · PDF fileSubstation Communication with IEC 61850 and Application Examples ABB Medium Voltage Products – Sanjay Sharma,

§© ABB Group§December 2, 2016 | Slide 25

IEC 61850 in DA Products

§ Native support for IEC 61850 communication

§ Native IEC 61850 enables fast “GOOSE”(Generic Object Oriented Substation Event)horizontal communication between IEDs

§ KEMA IEC 61850 conformance statementsavailable

§ In 615/620 Ethernet redundancy as option

§ 615 and 620 series also supports in parallelwith IEC 61850:

§ Modbus TCP/IP and RTU/ASCII

§ DNP3 TCP/IP and serial

§ IEC 60870-5-103

§ 630 series also supports:§ DNP3 TCP/IP

§ IEC 60870-5-103

Relion®

Page 26: ABB Medium Voltage Products – Sanjay Sharma, 29.11.2016 ... · PDF fileSubstation Communication with IEC 61850 and Application Examples ABB Medium Voltage Products – Sanjay Sharma,

§© ABB Group§December 2, 2016 | Slide 26

IEC 61850 in DA Products615, 620 and 630 series IEC 61850

§ IED core protocol for all functionalityand applications

§ Settings and parameterization are donefully according IEC 61850 services

§ COMTRADE disturbance recordingsover IEC 61850 or FTP

§ Fault records available in IEC 61850

§ Fast GOOSE messaging between IEDsfulfilling IEC 61850-5 requirement, datatransmission time <10 ms from IED toIED

§ SNTP for time synchronization with 1msaccuracy

§ Support of five parallel clients

Page 27: ABB Medium Voltage Products – Sanjay Sharma, 29.11.2016 ... · PDF fileSubstation Communication with IEC 61850 and Application Examples ABB Medium Voltage Products – Sanjay Sharma,

§© ABB Group§December 2, 2016 | Slide 27

IEC 61850 in DA ProductsCOM600

§ Powerful gateway between substationand IEDs

§ Takes full advantage of DA IEDs IEC61850 features improving engineeringefficiency

§ Easy to use local or Web HMI withsingle line diagram, even&alarm list andmuch more

§ Intelligent real-time applications inCOM600 with 61131 Logic Processor

§ Supports GOOSE e.g. with RIO600§ Cyber Security optimized

Page 28: ABB Medium Voltage Products – Sanjay Sharma, 29.11.2016 ... · PDF fileSubstation Communication with IEC 61850 and Application Examples ABB Medium Voltage Products – Sanjay Sharma,

© ABB GroupDecember 2, 2016 | Slide 28

Communication SolutionsContents

1. Introduction2. IEC 61850 Overview3. IEC 61850 Horizontal Communication4. Relion® Performance5. IEC 61850 in DA Products6. Application Examples7. Ethernet Redundancy8. Conclusion

Page 29: ABB Medium Voltage Products – Sanjay Sharma, 29.11.2016 ... · PDF fileSubstation Communication with IEC 61850 and Application Examples ABB Medium Voltage Products – Sanjay Sharma,

§© ABB Group§December 2, 2016 | Slide 29

Application Examples

§ RIO600 inputs are connected to EarthingSwitch open and closed statuses

§ In case there is change of status RIO600sends information to IED B

§ Due change in station interlocking schemeIED B sends notification to other IEDs in IEC61850 station bus

§ The use of RIO600 extends the available I/Ospace for Relion ® IEDs

ES statusin GOOSEmessage

Remote I/O RIO600

Station bus IEC 61850

INC

OUT OUT

Ok, thx forstatus update.Now I canclose my CBalso.

Page 30: ABB Medium Voltage Products – Sanjay Sharma, 29.11.2016 ... · PDF fileSubstation Communication with IEC 61850 and Application Examples ABB Medium Voltage Products – Sanjay Sharma,

§© ABB Group§December 2, 2016 | Slide 30

Binary GOOSE ApplicationBusbar Protection (O/C blocking)

Station bus IEC 61850

§ GOOSE can be used for Logic BusbarProtection (Overcurrent blockingprotection) for logic protectioncoordination

§ Fault on cable side on outgoing feederis seen by IED in the OUT feeder andby IED in incoming feeder, due to theset parameters for Overcurrentprotection function (I>>)

§ I>>> Start from outgoing feeder isshared via GOOSE to incoming feederwhere it blocks the I>> function

§ Fault is cleared out by Circuit Breakerin outgoing feeder faster than hardwired

INC

OUT

GOOSE msg. sentto upstream IED

I see fault in myfeeder.

Ok, thanks forinformation. Iwill block myO/C function.

I also see thefault on Busbar

I will take careof it. You donot need tooperate.

Page 31: ABB Medium Voltage Products – Sanjay Sharma, 29.11.2016 ... · PDF fileSubstation Communication with IEC 61850 and Application Examples ABB Medium Voltage Products – Sanjay Sharma,

§© ABB Group§December 2, 2016 | Slide 31

Application examplesArc protection using REF615

Three separate sensors§ Busbar compartment§ Circuit-breaker

compartment§ Cable compartment

Operating conditions§ Arc detected§ Arc and current detected

§ Current thresholdseparately adjustablefor phase currents andneutral current

X

1.

2.

3.

Page 32: ABB Medium Voltage Products – Sanjay Sharma, 29.11.2016 ... · PDF fileSubstation Communication with IEC 61850 and Application Examples ABB Medium Voltage Products – Sanjay Sharma,

§© ABB Group§December 2, 2016 | Slide 32

Binary GOOSE ApplicationARC Protection Intertripping

Station bus IEC 61850

§ GOOSE can be used for ARCprotection intertripping within theswitchgear

§ IED in OUT feeder detects the ARCe.g. on busbar side

§ The IED in INC have to eliminate thisfault

§ IED in INC will open the CB and faultis cleared

INC

OUT

GOOSE msg. sentto upstream IED

I see fault onBusbar side,who isinterested?

I am, I willopen my CBto eliminatethe fault.

Page 33: ABB Medium Voltage Products – Sanjay Sharma, 29.11.2016 ... · PDF fileSubstation Communication with IEC 61850 and Application Examples ABB Medium Voltage Products – Sanjay Sharma,

Application examplesLoss-of-mains protection using GOOSE and BST

X IED A

GOOSE messageX

G

X

REF615

RED615

RED615

BST message overprotectioncommunication(upto 20km optical link)

IED “B”

IED “C”Cab

leor

OH

L

Connection togrid is lost.Disconnectgenerator!

My Breaker hasbeen opened.Disconnectall distributedgeneration!

§ IED A on the incoming feeder detects anopen circuit-breaker condition

§ The CB position information istransferred to Relay B as a GOOSEmessage

§ After receiving the GOOSE messageRelay B transfers the information toRelay C using BST, binary signaltransfer

§ Relay C will issue a command todisconnect the generator from network

§ Whole communication chain 28ms!

© ABB GroupDecember 2, 2016 | Slide 33

Page 34: ABB Medium Voltage Products – Sanjay Sharma, 29.11.2016 ... · PDF fileSubstation Communication with IEC 61850 and Application Examples ABB Medium Voltage Products – Sanjay Sharma,

© ABB GroupDecember 2, 2016 | Slide 34

Binary GOOSE applicationTap changer control with AVR (Master/Follower mode)

e.g.REU615 e.g.REU615/RET620

Master FollowerFollowerFollower

e.g.REU615 e.g.REU615

Station bus IEC 61850GOOSE msg. sentto Followers

My tap positionis changed.Adjust your tappositions also.

Affirmative. Affirmative. Affirmative.

KM2

Page 35: ABB Medium Voltage Products – Sanjay Sharma, 29.11.2016 ... · PDF fileSubstation Communication with IEC 61850 and Application Examples ABB Medium Voltage Products – Sanjay Sharma,

Slide 34

KM2 tento tiez zanimovat nejakKarol Majer; 22.5.2014

Page 36: ABB Medium Voltage Products – Sanjay Sharma, 29.11.2016 ... · PDF fileSubstation Communication with IEC 61850 and Application Examples ABB Medium Voltage Products – Sanjay Sharma,

© ABB GroupDecember 2, 2016 | Slide 35

Analog GOOSE applicationTap changer control with AVR (Minizing circulating current mode)

e.g.REU615 e.g.REU615/RET620e.g.REU615 e.g.REU615

Station bus IEC 61850Vector information is sharedover Analog GOOSE betweenregulators

Page 37: ABB Medium Voltage Products – Sanjay Sharma, 29.11.2016 ... · PDF fileSubstation Communication with IEC 61850 and Application Examples ABB Medium Voltage Products – Sanjay Sharma,

§© ABB Group§December 2, 2016 | Slide 36

Amb. Temp.measurement

OUT 2

Analog GOOSE applicationTemperature measurement in Motor substation

OUT 1 OUT 3

INC

Station bus IEC 61850

GOOSE msg. sentto other OUT feeders

I measure theambienttemperature inMotor room. Thevalue is 25,2Celsius.

Thanks,temperaturevalue received.

Thanks,temperaturevalue received.

Page 38: ABB Medium Voltage Products – Sanjay Sharma, 29.11.2016 ... · PDF fileSubstation Communication with IEC 61850 and Application Examples ABB Medium Voltage Products – Sanjay Sharma,

§© ABB Group§December 2, 2016 | Slide 37

IED

Binary and Analog GOOSE application“Active” Load-shedding with PML630

Station bus IEC 61850

G

Transformer Cable Transformer Cable

G

Bus Coupler

Generator Generator

M M

PML630

COM600

HMIExternalSystems

Gridconnection

Gridconnection

Priority 1 Priority 2 Priority 2 Priority 3Priority 3

I’m loosingpower, Ihave todisconnectmy CB

Ok, I see.We have toshed loadsto keep thenetworkstabilized.Priority 1CBs OPEN!

Ok,understand. Iopen my CB

Page 39: ABB Medium Voltage Products – Sanjay Sharma, 29.11.2016 ... · PDF fileSubstation Communication with IEC 61850 and Application Examples ABB Medium Voltage Products – Sanjay Sharma,

§© ABB Group§December 2, 2016 | Slide 38

IEC 61850 9-2 Sampled ValuesProcess Bus Example

Raw phase measurements sent with 4kHz sampling rate

Page 40: ABB Medium Voltage Products – Sanjay Sharma, 29.11.2016 ... · PDF fileSubstation Communication with IEC 61850 and Application Examples ABB Medium Voltage Products – Sanjay Sharma,

© ABB GroupDecember 2, 2016 | Slide 39

Communication SolutionsContents

1. Introduction2. IEC 61850 Overview3. IEC 61850 Horizontal Communication4. Relion® Performance5. IEC 61850 in DA Products6. Application Examples7. Ethernet Redundancy8. Conclusion

Page 41: ABB Medium Voltage Products – Sanjay Sharma, 29.11.2016 ... · PDF fileSubstation Communication with IEC 61850 and Application Examples ABB Medium Voltage Products – Sanjay Sharma,

Redundancy solutions retained for IEC 61850

§ With “zero” switchover time (seamless)

§ PRP (Parallel Redundancy Protocol)IEC 62439-3 Clause 4

§ HSR (High-availability Seamless Redundancy)IEC 62439-3 Clause 5

§ PRP/HSR is a patent of ABB Corporate Research

§ ABB has assured the IEC to provide licenses throughout the worldfree of charge or under reasonable terms

Page 42: ABB Medium Voltage Products – Sanjay Sharma, 29.11.2016 ... · PDF fileSubstation Communication with IEC 61850 and Application Examples ABB Medium Voltage Products – Sanjay Sharma,

§© ABB Group§December 2, 2016 | Slide 41

HSR

Operationdescription:

1. Message fromIED is sent viaboth links (“A”and “B”) to theSCADA via HSRring

Normal operation

A B

A B A B A B A B A B

A BA B

Page 43: ABB Medium Voltage Products – Sanjay Sharma, 29.11.2016 ... · PDF fileSubstation Communication with IEC 61850 and Application Examples ABB Medium Voltage Products – Sanjay Sharma,

§© ABB Group§December 2, 2016 | Slide 42

HSR

Operationdescription:

1. Failurerecognized inHSR ring (“A”link)

2. Message isreceived bySCADA viahealthy part ofring (“B” link)

Operation under failure condition

Broken comm. link

A B

A B A B A B A B A B

A BA B

Page 44: ABB Medium Voltage Products – Sanjay Sharma, 29.11.2016 ... · PDF fileSubstation Communication with IEC 61850 and Application Examples ABB Medium Voltage Products – Sanjay Sharma,

§© ABB Group§December 2, 2016 | Slide 43

PRP

Operationdescription:

1. Message isreceived inCOM600 viaboth parallel links(LAN “A” andLAN “B”)

Normal operation

A B

LAN BLAN A

A B A B A B A B

A B

Page 45: ABB Medium Voltage Products – Sanjay Sharma, 29.11.2016 ... · PDF fileSubstation Communication with IEC 61850 and Application Examples ABB Medium Voltage Products – Sanjay Sharma,

§© ABB Group§December 2, 2016 | Slide 44

PRP

Operationdescription:

1. Failurerecognized inPRP network(LAN “A”)

2. Message isreceived inCOM600 viahealthy link (LAN“B”)

Operation under failure condition

Broken comm. link

LAN BLAN A

A BA B A B A B A B

A B

Page 46: ABB Medium Voltage Products – Sanjay Sharma, 29.11.2016 ... · PDF fileSubstation Communication with IEC 61850 and Application Examples ABB Medium Voltage Products – Sanjay Sharma,

© ABB GroupDecember 2, 2016 | Slide 45

Communication SolutionsContents

1. Introduction2. IEC 61850 Overview3. IEC 61850 Horizontal Communication4. Relion® Performance5. IEC 61850 in DA Products6. Application Examples7. Ethernet Redundancy8. Conclusion

Page 47: ABB Medium Voltage Products – Sanjay Sharma, 29.11.2016 ... · PDF fileSubstation Communication with IEC 61850 and Application Examples ABB Medium Voltage Products – Sanjay Sharma,

§© ABB Group§December 2, 2016 | Slide 46

§ IEC 61850 offers system integration and interoperability

§ Less wiring between IEDs means less equipmentand work

§ GOOSE and 9-2 has superior functionality comparing totraditional wiring (performance, link and data supervision)

§ Flexible utilization of available I/Os in the substationequipment

§ Substation automation and IED configuration is moreintelligent and flexible

§ Seamless Redundant Ethernet provides improvedavailability

§ Future proof communication standard choice

Communication SolutionsConclusions