ABB DOC User Manual

  • Upload
    kkn1234

  • View
    855

  • Download
    12

Embed Size (px)

DESCRIPTION

ABB Doc Electrical Installation Verification Software User Manual

Citation preview

Page 1: ABB DOC User Manual

Release 2.0.0.0059

Page 2: ABB DOC User Manual

Page 2 of 170

1. WARNINGS................................................................................. 5

2. INTRODUCTION ......................................................................... 6

2.1. Presentation of the Program ................................................................................. 7

3. STARTING TO WORK WITH DOC ................................................ 10

3.1. Profile Selection ................................................................................................... 11

3.2. Plant General Properties ..................................................................................... 12

3.3. Layout Selection .................................................................................................. 18

3.4. Main Window ....................................................................................................... 19

4. DRAWING THE SINGLE-LINE DIAGRAM ....................................... 21

4.1. General indications on the drawing .................................................................. 22

4.2. Drawing with Macro Objects .............................................................................. 22

4.3. Examples .............................................................................................................. 26

4.4. Drawing an MV-LV Single-line Diagram with Macro Objects ......................... 32

4.5. Drawing and Defining a Network – UPS Generator Group Changeover ....... 37

4.6. Modifying the Drawing ........................................................................................ 40

4.7. Labels .................................................................................................................... 41

Page 3: ABB DOC User Manual

DOC – User Manual - Page 3

5. CALCULATION AND DIMENSIONING .......................................... 46

5.1. Calculation and Dimensioning ........................................................................... 47

5.2. Error Messages ..................................................................................................... 50

5.3. Failed Selection of Single Objects ..................................................................... 52

5.4. Calculation and Dimensioning Results .............................................................. 54

5.5. Changing the Dimensioning Results. ................................................................. 55

6. VERIFICATION AND PROTECTIONS ............................................ 57

6.1. Verifications and Protections .............................................................................. 58

6.2. Printing Options for the Curves Module ............................................................. 70

7. DRAWING DIAGRAMS OF AUXILIARIES ....................................... 73

7.1. Drawing the Key Diagram of the Auxiliary Circuits .......................................... 74

8. SWITCHBOARD CONFIGURATOR ................................................ 79

8.1. General indications on switchboard configuration ......................................... 80

8.2. WIZARD - Switchboard configuration ................................................................. 80

8.3. Modifying Front Panel View ................................................................................ 87

8.4. Busbar distribution system .................................................................................. 92

Page 4: ABB DOC User Manual

Page 4 of 170

9. PRINTING THE DOCUMENTATION.............................................. 97

9.1. Project Documentation Manager ...................................................................... 98

9.2. Creating the Project Documentation ................................................................ 99

9.3. Print Preview ....................................................................................................... 109

9.4. Commands for Managing the Project Documentation ................................. 110

ANNEX A: LIST OF COMMANDS ...................................................... 112

File Menu ........................................................................................................................ 113

Edit Menu ........................................................................................................................ 114

Objects Menu ................................................................................................................ 115

MV Objects Menu .......................................................................................................... 117

Tools Menu ..................................................................................................................... 118

View Menu ..................................................................................................................... 123

Help Menu ...................................................................................................................... 124

MV Macros ..................................................................................................................... 124

LV Macros ....................................................................................................................... 128

Auxiliaries Macro ........................................................................................................... 132

Switchboard Toolbar Menu........................................................................................... 133

ANNEX B: LIST AND DESCRIPTION OF THE SINGLE OBJECTS AND OF THE

RELATIVE CONTROL PANELS .......................................................... 135

Windows of MV Single Objects..................................................................................... 136

Windows of LV Single Objects ...................................................................................... 142

Page 5: ABB DOC User Manual

DOC – User Manual - Page 5

1. Warnings

Notes ABB S.p.A - ABB SACE Division responsibility towards the user necessarily presumes that the program has

been used in a professionally correct manner and that the user has followed all the given precautions/instructions.

Even in the case of program defects which have been detected and verified, ABB S.p.A - ABB SACE Division shall

only be responsible for repairing the program in a reasonable length of time.

ABB S.p.A - ABB SACE Division declines all responsibility for either direct or indirect damages, however caused, to

the user or third parties by use or non-use or late availability of the program, magnetic support or documentation

supplied.

The user must:

- check the use of the program supplied by ABB S.p.A - ABB SACE Division and the reliability and accuracy of the

data entered, and also that the data entered fully corresponds with and is consistent with the printed results;

- take all necessary precautions to safeguard and preserve data and to allow him to reconstruct data using his own means

should the data be lost or destroyed due to an error in handling or entering data and/or an error in using the program, or

even an operational defect of the program and/or processor used;

- ensure that the program is only used by professionally and technically qualified personnel able to use it correctly.

The user must follow the instructions and notes given and take all the precautions recommended at all times.

ABB S.p.A - ABB SACE Division declines all responsibility if the user does not follow the instructions for operation

and use indicated.

ABB S.p.A - ABB SACE Division declines all responsibility for any damages due to destruction of data files or other

occurrences caused by not having followed the instructions and precautions indicated, by not having used the program

correctly or due to an operational defect of the computer used, whatever the cause of this operational defect may be.

ABB S.p.A - ABB SACE Division declines all responsibility for mistakes by the user concerning the use of DOC and

any mistakes and/or inaccuracies contained in the data and/or data combinations entered.

ABB S.p.A - ABB SACE Division reserves the right to modify and/or update the program and relevant instructions, at

any such time that it is deemed necessary or opportune, in the light of new provisions of law and technological,

management or operational developments.

Conditions of use:

- The program is protected by Copyright.

- No unauthorized copies of the program and relevant documentation are permitted.

- Changing, adapting, re-designing or creating applications based on the program itself, on the files or documentation

supplied is forbidden.

- ABB S.p.A - ABB SACE Division reserves the right to take legal action to protect its interests. The software is not for

sale and is distributed for promotional purposes only.

Page 6: ABB DOC User Manual

Page 6 of 170

2. INTRODUCTION

This chapter describes:

the list of DOC functionalities;

the applications which can be made with DOC.

Page 7: ABB DOC User Manual

DOC – User Manual - Page 7

2.1. Presentation of the Program

DOC is the ABB program for drawing and calculating single-line diagrams of low and

medium voltage electrical plants, for selection of the switching and protection devices and for

verifying coordination of the protections.

DOC is aimed at all professionals in the electrical sector looking for a precise but simple and

rapid tool, which helps them to do their work.

The main functionalities of the program are:

Drawing the single-line electric diagram.

Drawing the key diagram of the auxiliary circuits.

Calculation of line current and voltage drops.

Calculation of short-circuit currents.

Dimensioning low and medium voltage cables.

Dimensioning switching and protection devices.

Switchboard configuration

Calculation of overtemperatures in ANS switchboards.

Setting and coordination of protection devices.

Verifying cable protection.

Printing the single-line diagram and project documentation.

The program can calculate electric networks with the following characteristics:

Medium voltage: Vn ≤ 36kV 50/60Hz

State of the neutral: Insulated / Compensated

Low voltage: Vn ≤ 1kV 50/60Hz

Three-phase power supplies with and without neutral,

two-phase and single-phase

Distribution system : TT – TN-S – TN-C – IT

Unlimited number of levels and departures.

Several distribution systems in the same network

Three-phase networks with single-phase and two-phase loads

Plants with service generator.

Plants in cogeneration.

Plants with back-up transformers.

Island operation, without restrictions on the number of generators.

Colors of the Single-line Diagram

To help in reading this document, the images of the single-line diagram have – where

possible – been made with a white background and therefore with a configuration of colors

different from the one predefined in the program.

To use the program it is advisable to use the predefined colors (black background and green,

yellow or red symbols according to their state).

Further clarifications about color management are available later in this document.

Page 8: ABB DOC User Manual

Page 8 of 170

DOC: Drawing the Single-line Diagram

DOC: Cable Section Calculation; Short-circuit Calculations

Page 9: ABB DOC User Manual

DOC – User Manual - Page 9

DOC: Cable Protection and Selectivity Verification

DOC: Printing Project Documentation

Page 10: ABB DOC User Manual

Page 10 of 170

3. Starting to work with DOC

This chapter describes

operations preliminary to drawing the single-line diagram;

description of the work environment;

personalization of the work environment.

After reading this chapter, the user will be able to:

personalize the appearance of the program;

select the utility;

define the plant general properties;

select the layout.

Page 11: ABB DOC User Manual

DOC – User Manual - Page 11

3.1. Profile Selection

DOC can be used either in the Light or Professional Profile according to requirements,

combining calculation precision with rapidity of project execution in the best way.

The Light Profile, with simple and immediate use, is recommended for drawing diagrams and

doing calculations with a low level of complexity and with low voltage or schematized

supply by means of a MV/LV transformer.

On the other hand, the Professional Profile, which makes all the DOC functionalities

available, is recommended for drawing and calculation of complex diagrams with medium

voltage supply or with supply by means of generators.

On program start-up, the window for selection of the Profile to use DOC with is shown.

Window for Profile Selection

Deactivate / Reactivate the Window for Profile Selection.

Profile selection can be deactivated by choosing the “Do not ask again on start/up” option.

In this case DOC will start up with the last Profile selected.

Profile selection can be reactivated from the Tools – Options… menu.

Page 12: ABB DOC User Manual

Page 12 of 170

3.2. Plant General Properties

The plant general properties window allows you to define the type of plant to be made.

The window is available in simplified mode (Light Profile) and in advanced mode

(Professional Profile). In both cases it is possible to select the type of supply at the top,

whereas in the lower part the parameters common to the whole single-line diagram are

defined.

Plant General Properties – Light Profile and Professional Profile

LV Distribution

This is the supply suitable for representing civil, service sector plants or small-sized

industrial applications.

The parameters required to define the supply are the three-phase short-circuit current or the

three-phase fault impedance value or of the short-circuit apparent power.

Page 13: ABB DOC User Manual

DOC – User Manual - Page 13

“LV Supply”: representation in the single-line diagram

Trafo MV-LV

This is the supply suitable for representing medium-large power plants when it is not

necessary to coordinate the protections between the MV side and the LV side of the

transformer/s.

It is also useful for verifying the voltage drop from the transformer secondary to the last load

(without considering the voltage drop inside the transformer which would be counted by

DOC if the “Transformer with 2 windings” Single Object was used).

The parameters needed to define the supply are the number, the rated power and the rated

short-circuit voltage of the transformer/s.

MV Supply

This is the supply suitable for representing the medium voltage section in a large-sized plant

as well, selecting the MV side switching and protection devices and coordinating them with

the LV side of the plant.

The parameters needed to define the supply (normally communicated by the power utility

company) are:

The rated voltage.

The short-circuit current.

The ground fault current at the point of delivery.

The state (insulated / compensated) of the neutral.

The calculator-shaped button allows input of the short-circuit current value in an alternative

way, when the three-phase fault impedance or the apparent short-circuit power are known.

It is also possible to personalize the short-circuit power factor value (needed for calculation

of the short-circuit current peak value).

Finally, input of the ground fault current value in an alternative way is possible when the

capacity to ground or the Petersen coil parameters are known (only in the case of

compensated neutral).

Page 14: ABB DOC User Manual

Page 14 of 170

“MV supply”: Calculator for defining the MV short-circuit

Calculation of the Ground Fault according to the State of the Neutral

The formulae used by DOC for calculation of the ground fault are given below with special

attention to the parameters available for defining the MV short-circuit.

System with insulated neutral

Ce2V1,133Io f

System with compensated neutral

2222

23121,131,1IgiIgr3Io

Lpf

CefVRp

V

where:

- 3Io [A]: ground fault current taken from the Homopolar transformer

- 1,1V [V]: phase voltage corrected according to the c factor of the IEC 60909-0

Standard

- f [Hz]: frequency

- Ce [μF]: capacity to ground of the network on the supply side of the utility

- Igr [A]: real component of the ground fault current due to the resistance of the

Petersen coil (Rp)

- Rp [Ω]: resistance of the Petersen coil

- Igi [A]: imaginary component of the ground fault current equal to the vectorial sum

of the capacitive contribution of the network (Ce) and of the inductive

contribution of the Petersen coil (Lp)

- Lp [mH]: inductance of the Petersen coil

Page 15: ABB DOC User Manual

DOC – User Manual - Page 15

“MV Supply”: representation in the single-line diagram

Generator

This is the supply suitable for representing plants totally supplied in an island, such as ships

or off-shore platforms.

To define the supply it is sufficient to indicate the rated voltage value of the generator.

Subsequently it will be possible to define the generator with all its parameters or to select it

from the list of those available in DOC.

Selection of the “Generator” Supply

The “Generator” supply must not be used in the case of cogeneration or service generators

(Cf. Chapter 4.5)

In these cases it is advisable to use another of the supplies available and subsequently

represent the generator by means of the “Generator” Single Object.

“Generator”: representation in the single-line diagram

Page 16: ABB DOC User Manual

Page 16 of 170

Panel for “Setting LV section parameters”

The panel allows the preset value for the main parameters characterizing the LV section of

the plant to be defined.

Precise setting of the parameters means the drawing and data input stages can be speeded up.

Parts of the plant which must have different parameter values (for example, you select Phases

= LLLN, but you also have to represent single-phase loads) can be customized afterwards

during drawing (Cf. point 3 of Chapter 4.2)

Rated voltage: a list of the standardized voltages is available. In any case, it is possible

to manually digit a value between 0V and 1000V as you want

Distributed phases: all possible combinations in a three-phase system are available

(LLLN, LLL, LLN, LL, L1N, L2N, L3N)

Distribution system: TN-C, TN-S, TT and IT distribution systems are available. It is

advisable to set the distribution system of the supply. Indications are given below about

how to proceed in the case where there are plant sections present with a different

distribution system (for example, sections managed with the TN-S system in plants with

TN-C supply)

Rated frequency

Selection of the number of poles according to the distributed phases: It is possible to

indicate your own preferences to DOC regarding management of the neutral in LLLN

and LN circuits.

Selection of the reference Standard for miniature circuit-breakers: DOC is able to

select the modular protection devices according to the correct product Standard

according to the type of plant.

In particular, for industrial plants, the nameplate values declared according to the IEC

60947-2 product Standard are used, whereas for plants in the civil/service sector, the

nameplate values declared according to the IEC 60898 product Standard are used

Automatic optimization of the neutral: when active, DOC proposes the neutral of the

cables with sections equal to 50% of the phase section (only under the conditions

permitted by the Standard!). Otherwise the neutral conductor has a section the same as

that of the phases.

Panel for “Plant loads”

After calculation of the single-line diagram drawn, the plant load data are given in this panel

in terms of:

Active power

Reactive power

Current

Power factor

Page 17: ABB DOC User Manual

DOC – User Manual - Page 17

Advanced settings

Further advanced level settings are available which are already predefined with values that do

not normally need to be changed.

The advanced settings are always visible if you use the Professional Profile. When using the

Light Profile, you can access them by pressing the “Advanced settings” button.

The advanced settings provided are:

Selection of the Standards for the short-circuit calculations between:

o IEC 60909 (International Standard for 50-60Hz applications)

o IEC 61363 (Naval Applications)

o NFC 15-100 (French Standard)

o VDE 0102 (German Standard)

o Method of the symmetrical components.

Selection of the Standard for dimensioning low voltage cables among:

o CEI 64-8 (Italian Standard)

o IEC 60092 (Naval Applications)

o IEC 60364 (International Standard)

o UNE 20460 (Spanish Standard)

o VDE 0298-4 (German Standard)

o NFC 15-100 (French Standard)

Temperature: ambient temperature value (used for calculation of switchboard

overtemperatures) and the one inside switchboards (presumed or calculated by DOC;

used to consider any temperature derating in of the performance of the protection

device)

Protection of people: contains the parameters used by DOC to verify protection against

indirect contacts: Contact voltage; Tripping time; Resistance of the ground plate (cf.

Chapter 6.1.1 for a description of their use).

Automatic selection of the type of circuit-breaker: data to guide DOC in selecting

Miniature, Molded-case or Air circuit-breakers according to the current.

Page 18: ABB DOC User Manual

Page 18 of 170

3.3. Layout Selection

Once the general plant properties have been defined, DOC allows the layout to be used to be

defined among the following types:

“MV columns” (recommended for drawing diagrams of MV compartments)

“LV columns” (recommended for drawing LV plants)

“Free” (recommended for producing extremely customized and/or special diagrams on

A2, A1, A0 page formats)

To make selection easier, a preview is available of all the possible layouts.

Previews of the “MV columns”, “LV columns” and “Free” layouts

Changing the Layout during Diagram Drawing

During drawing of a diagram, it may be necessary to change the layout in relation to the one

selected previously (for example, “MV columns” on the first page and “LV columns” on the

following pages).

This is possible by using the “Change layout – page dimensions” command in the “View”

menu.

The “Change layout – page dimensions” icon is available in the “View” toolbar.

Page 19: ABB DOC User Manual

DOC – User Manual - Page 19

3.4. Main Window

(1) Menus and toolbars

In this area there are the commands used for managing files, the commands for drawing and

the program functionalities.

(2) Macro Objects

The Macro Object area contains all the macro-blocks, i.e. blocks consisting of several Single

Objects, which allow rapid diagram drawing.

The contents of this area are contextual to the type of diagram you are drawing (MV, LV or

of the auxiliaries).

(3) Drawing sheet

This is the area where the project to be made with DOC takes shape. It is the page, complete

with layout, just as it can be printed to document the project.

(4) Work flow

The “Work flow” toolbar has the aim of guiding the user during the main stages of carrying

out the project.

DOC work Area

The work flow, from which the name of the relative Toolbar comes, to be followed to work

best with DOC, is as follows:

Drawing the Medium Voltage network (Cf. Chapter 4.4).

Drawing the Low Voltage departures (Cf. Chapters 4.2 and 4.3).

Calculating and dimensioning the plant (Cf. Chapter 5).

Curve verification and drawing (cf. Chapter 6).

Functional drawing of the auxiliary circuit electric diagrams (Cf. Chapter 7).

Switchboard configuration (Cf. Chapter 9).

Page 20: ABB DOC User Manual

Page 20 of 170

Creating and printing the documentation (Cf. Chapter 9).

3.4.1. Personalizing the Main Window

The appearance of the main window of DOC can be customized by changing the colors of the

diagram and the presence and position of the toolbars.

This way you can work in a way closer to your own habits.

Colors

To change the colors, use the “Preferences…” command in the “Tools” menu.

The settings are on the “Colors” page.

The colors which define the state of the Single Objects can be changed, as well as the work

sheet background color.

Window for personalizing the colors

The profile of the colors preset in the program have the following meanings:

Color Meaning

Yellow Single Object to be dimensioned or checked

Green Single Object dimensioned correctly

Red Single Object with problems or errors

Brown Single Object not supplied in the present network configuration

Toolbars

The Toolbars can be enabled – disabled by the “Toolbars” command in the “View” menu.

It is also possible to move the Toolbars into your favorite position of the work environment

by dragging them with the mouse.

Visibility of the Macro Objects bars is a function of the active work flow button. Their

position can be customized in the same way as the other Toolbars.

Page 21: ABB DOC User Manual

DOC – User Manual - Page 21

4. Drawing the single-line diagram

This chapter describes:

drawing the single-line diagram of Low Voltage networks;

drawing the single-line diagram of Medium Voltage networks;

network data input;

managing several power supplies in the same project.

After reading this chapter, the user will be able to:

use the Single Objects and Macro Objects to draw the single-line diagram of Medium and Low Voltage networks;

draw all types of diagrams, even those consisting of several switchboards and shown over several pages;

define the characteristics of loads and lines;

configure networks supplied by a power supply and by back-up generators.

Page 22: ABB DOC User Manual

Page 22 of 170

4.1. General indications on the drawing Once the general properties of the plant and the layout have been defined, the utility symbol

is already present on the drawing sheet.

You can therefore proceed to draw the single-line diagram as described in this chapter.

It is possible to use two different types of objects with DOC:

Single Objects

Macro Objects

The Single Objects are the blocks which represent a single element of the electrical plant and

which allow a single-line diagram to be made (for example: “LV Circuit-breaker”, “LV

Cable”, “Generic load”, “Busbar”, “Motor”, …). By connecting the Single Objects with each

other, you can obtain infinite combinations for representing any type of plant.

The icons of the Single Objects are found in the Toolbars area.

On the other hand, the Macro Objects are a combination of several Single Objects already

ready to be drawn with a single click.

The Macro Objects thereby allow you to draw much more quickly, at the expense of the

variety of plants which can be shown.

Furthermore, with the Macro Objects it is only possible to draw purely radial networks,

whereas the Single Objects allow meshed type networks to be made which DOC is able to

manage during the calculations.

The best result is obtained by combining the Single Objects and the Macro Objects,

combining the need of each particular plant with the speed of making the diagram.

To draw a Single Object or a Macro Object, it is sufficient to click over the icon that

represents it. The Single Object or the Macro Object will be hooked up to the mouse pointer,

ready to be drawn with a click of the left button in the desired position in the diagram.

The Single Objects are only available with the Professional Profile.

The Medium Voltage Single Objects and the Medium Voltage Macro Objects are

available using the Professional Profile and starting a network with the “MV Supply”

4.2. Drawing with Macro Objects This chapter describes how to make a single-line diagram only using Macro Objects.

The Macro Objects are useful to make a single-line diagram rapidly, starting from the main

device and going on with the departures on the load side until the loads are reached.

The program automatically verifies congruence of the single-line diagram.

Page 23: ABB DOC User Manual

DOC – User Manual - Page 23

Low Voltage Macro Objects

“General” and “General Second level” Macro Objects

“Generic departure” and “Motor departure” Macro Objects

1) Start positioning the main circuit-breaker by selecting the “Main CB with Overload and Short

circuit protection” icon from the “General” Macro tools toolbar.

The program will see to stretching the connections so as to take up all the space available

both vertically and horizontally on the work sheet.

1) Main CB with Overload and Short circuit protection

2) From the “Generic departure” Macro select the type of feeder to be shown, for example, a

“Generic Load feeder, CB with Overload and Short circuit protection + RCB” departure.

Hook the Macro Object up to the barring on output from the main circuit-breaker.

3) The departure line is now connected to the barring and the program shows the dialog window

for fast definition of the feeder data.

This way it is possible to define the main data of the feeder while drawing:

Phases (single-phase, three-phase with and without neutral)

Distribution system

Description of the departure (to allow more flexibility, these are available on two lines)

Consumption of the generic load (rated current or rated active power and power factor)

Length and type of cable

Page 24: ABB DOC User Manual

Page 24 of 170

3) Feeder properties fast input window

To disable the panel for fast definition of the feeder, remove the checking off sign at the

“Always show” option.

Disabling these functions is useful for those who want to edit the data of a feeder in

detail.

The panel can be re-enabled from the “Toolbar” menu – “Preferences…”, on the

“Other” page.

Phases and Distribution system

The phases and distribution system properties must be consistent in the plant.

This does not mean they must necessarily be the same throughout plant, but that there are

rules which DOC helps you to follow (in fact, it is possible, for example, to manage sections

of plant with a TN-S or TT distribution system starting from a TN-C supply, or single-phase

lines derived from a three-phase system with neutral; but it is not possible, for example, to

derive a single-phase load from a three-phase distribution without neutral or to derive an IT

system from a TN system without using an insulation transformer which separates the two

parts of the plant).

DOC helps the user by only showing the properties compatible with the type of distribution

selected.

In the case of incongruence, DOC notifies the incorrect situation during the calculations and

indicates the Single Objects by changing their color (Cf. Chapter Error! Reference source

ot found.).

Page 25: ABB DOC User Manual

DOC – User Manual - Page 25

Modifying the phases and distribution system

Modifying the phases and distribution system can be done in two ways:

By selecting just one Single Object to be modified, applying the “Properties” command

(the same as a double click over the symbol of the Single Object) and modifying its

Phase and/or Distribution system properties (DOC will only show the values compatible

with the position the Single Object occupies in the plant).

By selecting several Single Objects to be modified and using the “Properties” command,

in the “Edit” menu. You can change the common properties with the “Common

properties” window.

4) Once the main data has been defined, DOC adapts the feeder line in height according to the

layout, occupying all the space available.

4) Final appearance of a feeder line

5) Repeat the procedure for every other feeder line.

Advice on Drawing in Columns

There are two important rules to follow to improve the result of a drawing in columns:

The Macro Objects must be inserted in the center of the column. DOC helps to do this

correctly thanks to the predefined (and unalterable) grid step, with the horizontal and

vertical lines which intersect in the cursor position and follow it in its movements and

with the same structure as the layout in columns.

Do not insert two Single Objects of the same type in the same column (for example, two

“Circuit-breaker” Single Objects): the layout would not be able to host the data of both!

Page 26: ABB DOC User Manual

Page 26 of 170

Coding the Single Objects

DOC automatically codes the Single Objects according to the type of layout:

In the layout in columns, the coding follows the rule: Page.Column.

Other Single Objects drawn in the same column will have the same numbering (Circuit-

breaker –QF1.1; Cable –WC1.1; Load –L1.1).

In the free layout, the Single Objects of the same type will have incremental coding. The

fifth circuit-breaker inserted from the start of the drawing will have the code “–QF5”;

and could be combined with the third cable “-WC3”.

4.3. Examples

4.3.1. Switchboard with Sub-levels

With the Macro Objects it is also possible to draw several levels in the same switchboard (for

example, several thermomagnetic devices subordinate to a single residual current device).

1) Starting from the switchboard already defined in chapter 4.2, add a “Main second level

residual current CB” Macro Object in the first free column from the “Main second level”

Macros. The special barring will be added directly on the load side of the main second level

device.

1) Main second level residual current circuit-breaker

2) Select the type of feeder to be shown from the “Generic feeders” Macros, for example a

“Generic Load feeder, CB with Overload and Short circuit protection”. Hook the Macro

Object up to the barring on the load side of the residual current device.

Page 27: ABB DOC User Manual

DOC – User Manual - Page 27

2) Feeders protected by thermomagnetic device

Page 28: ABB DOC User Manual

Page 28 of 170

4.3.2. Switchboard over Several Pages

When a switchboard requires more space than the 11 columns available in the layout, the

procedure described in this chapter can be followed to show it over several pages.

1) After having drawn the part of the switchboard which can be shown on the present page, add

the “Line departure” Macro Object from the “General” Macros to the barring.

1) Board with link to page

2) Add a new page to the project with the “Add Page” command, available in the “View” menu

(or click over the icon on the left)

The settings of the current page, are also kept for the new page.

Chapter 9.4 describes the settings available and how to change them should the new page

require this.

Page 29: ABB DOC User Manual

DOC – User Manual - Page 29

3) On the new page, add the “Line with arrival link” Macro Object from the “General”

Macros. The pointer of the mouse must be positioned so as to fall half-way down the first

column.

Once the barring has been added, DOC will ask which “Departure line link” to connect it to

among those available.

The “Departure line link” sign follows the Page.Column format.

In the case of an underlying image, the arrival line page link will be connected to link 1.11.

A description can be added to improve recognition of the links.

3

Dialog window to connect the “Link to page”

5) The line on the new page has been added. Now it is possible to continue drawing the board

on the new page!

Browsing through the Project Pages

When the project consists of several pages, it is possible to browse through these using the

“Next page” and “Previous page” commands in the “View” menu. The commands can also

be carried out using the F12 and F11 function keys or by clicking over the icons shown on

the left.

Page 30: ABB DOC User Manual

Page 30 of 170

4.3.3. Diagram with More than One Distribution Board

If the plant foresees several distribution boards, these can be drawn in a single diagram with

DOC.

A network consisting of dozens of boards and hundreds of circuit-breakers and cables,

can take up a lot of the processor resources and require long processing times.

Should the calculation times become long, it is advisable to divide the project into

several files.

This is possible by simulating a board with a single generic load of equal power, net of

the demand factor, and putting the board removed back into a new file.

Simulate the network on the supply side in the new file by setting the supply data,

copying the results of the calculation, voltage and short-circuit current of the original

project.

1) A sub-board which supplies some feeders can be derived from the main distribution board.

The line from the main distribution board to the sub-distribution board is drawn by means of

the “Feeder line to sub-board…” Macro Object in the “Main feeders” Macro toolbar.

The user can select the type of protection device to be used.

Feeder lines for sub-board

2) Add a new page as shown in the previous example.

3) On the new page, draw the “Arrival line link” Macro Object from the “General” Macros

toolbar. The pointer of the mouse must be centered half-way down the first column of the

layout.

The program will ask to connect the Macro Object to the relative “Departure line link”.

Page 31: ABB DOC User Manual

DOC – User Manual - Page 31

Arrival page

4) Draw the general device of the sub-board selecting it from the Macro Objects available in the

“General” Macros toolbar.

5) Complete the sub-board with its feeder lines.

Sub-board with main switch-disconnector

Page 32: ABB DOC User Manual

Page 32 of 170

4.4. Drawing an MV-LV Single-line Diagram with Macro Objects

Once the MV Supply in the “General plant properties” has been selected, select the

“Medium voltage” icon in the “Work flow” tools toolbar.

The Medium Voltage Macro Objects will now be visible and ready to be drawn.

“First column” and “Last column” Macro Objects

“MV feeders” Macro Objects

“MV bus-tie” Macro Objects

You can only draw the Medium Voltage Single Objects and Macro Objects with the

Professional Profile and only if an MV supply has been selected.

In the case of other supplies, these Macro Objects are not visible.

Medium Voltage Macro Objects

Each Medium Voltage Macro Object represents a typical compartment of the Unimix

secondary distribution board.

Page 33: ABB DOC User Manual

DOC – User Manual - Page 33

1) Select the compartment you want to use as arrival line from the utility company.

Arrival with typical P1A compartment

2) Draws the Medium Voltage diagram with the Macro Objects available, already preset to

make up a Unimix board, placing a typical compartment side by side with another.

MV switchgear with arrival line in “P1A” compartment, “M (Measurement)” compartment

and two “P1E” feeders compartments separated from the “ASR bus-tie” compartment

Page 34: ABB DOC User Manual

Page 34 of 170

3) Add the “Transformer” to get ready to draw the LV section of the plant.

4) Add a “Vertical departure line link” to the secondary winding of the “Transformer”.

5) MV switchgear with two transformers and two departure lines

5) Add a new page with the “Add Page” command, available in the “View” menu, or with the

icon shown on the left.

6) Change the layout of the new page with the “Change layout – page size” command,

available in the “View” menu, or with the icon shown on the left.

Select the layout with low voltage columns.

Page 35: ABB DOC User Manual

DOC – User Manual - Page 35

Changing the layout

7) In the “Work flow” area, select the “Low Voltage” icon to display the Low voltage Macro

Objects.

8) On the new page, draw the “Arrival line link” from the bar of the “General” Macro Objects.

The pointer of the mouse must be centered half-way down the first column of the layout. The

program will ask to connect the Line in from the page link to the appropriate link.

9) On the load side of the link, draw the “LV cable” Single Object and define its main

characteristics in the dialog window.

Page 36: ABB DOC User Manual

Page 36 of 170

9) LV cable connected to a transformer secondary

10) Draws the main device from the bar of the “General” Macro Objects.

Arrival line from the MV-LV transformer with cable and main circuit-breaker

11) Complete the main low voltage switchboard with its feeders (cf. Chapters 4.3.1, 4.3.2, 4.3.3

for further details on drawing low voltage electric diagrams).

Page 37: ABB DOC User Manual

DOC – User Manual - Page 37

4.5. Drawing and Defining a Network – UPS Generator Group Changeover

By selecting the Professional Profile, it is possible to define several power supplies in mutual

exclusion for the same plant.

1) Draw a network with “MV-LV Trafo” supply and where a “Generator” Single Object is also

present.

Example of diagram with two power supplies

Page 38: ABB DOC User Manual

Page 38 of 170

2) Use the “Network configurations” command in the “Tools” menu.

“Network configurations” window

3) Define the “TRAFO” configuration:

Double click over the “<default>” text to rename the existing configuration in

“TRAFO”;

Deselect the protection device which connects the “Generator” Single Object to the rest

of the network. In this way, in the TRAFO configuration, the generator will be

disconnected from the plant.

4) Define a new “GENSET” configuration:

Click over the “New” button;

Assign the “GENSET” name to the new configuration;

Deselect the protection device which connects the supply to the rest of the network. In

this way, in the GENSET configuration, the supply will be disconnected from the plant.

Network configurations: “GENSET” configuration

Page 39: ABB DOC User Manual

DOC – User Manual - Page 39

5) Once the mask for defining the configurations is closed, a part of the network will be of a

different color according to the configuration selected.

The color indicates that a part of network is “off”, or not supplied (to change the colors or to

know their meaning, Cf. Chapter Error! Reference source not found.).

The unsupplied part of the network will not be considered in the calculation of this

configuration.

Single-line diagram: “GENSET” configuration

Single-line diagram: “TRAFO” configuration

Page 40: ABB DOC User Manual

Page 40 of 170

4.6. Modifying the Drawing

This chapter describes the most useful commands for modifying the single-line diagram

drawing.

All the commands are available in the “Edit” menu.

Zoom In, Zoom Out and Pan with the mouse

The “Zoom In”, “Zoom Out” and “Pan” commands can be given using the mouse wheel:

this way the relative part of the diagram can be displayed rapidly with the right level of

detail.

The “Zoom In” and “Zoom Out” commands are, respectively, turning the mouse wheel

upwards and clinking downwards.

The “Pan” command is obtained by keeping the mouse wheel pressed and dragging the page.

Multiple selection by means of selection box

To select several Single Objects it is advisable to:

Disable any active command by pressing the “Esc” key.

Click over an empty point of the drawing.

Create a selection box which touches or completely includes the Single Objects to be

selected.

The selection will consist of all the Single Objects touched or completely included in the

selection box according to the first click and to the direction in which the Single Objects are

selected.

If the first click is on the right of the Single Objects to be selected, DOC will add all

the Single Objects touched by the selection box to the Multiple selection.

If the first click is on the left of the Single Objects to be selected, DOC will add all

the Single Objects completely included in the selection box to the Multiple selection.

Multiple selection by means of clicking over the Single Objects to be selected

A multiple selection can be created by clicking over each Single Object you want to add to

the selection list. Once all the Single Objects wanted have been selected, select the Command

you want to apply (for example, the “Properties” command)

Duplicate

The “Duplicate” command allows a Single Object or a Multiple selection of Single Objects

to be copied onto the same page of the drawing with just one command.

The predefined values of the original Single Objects will be copied into the duplicated Single

Objects.

Copy – paste

The “Copy” and “Paste” commands allow a Single Object or a Multiple selection of Single

Objects to be copied onto different pages of the drawing.

The predefined values of the original Single Objects will be indicated in the pasted Single

Objects.

Stretch

The “Stretch” command allows the length of “Busbars” and “Connections” to be modified.

Page 41: ABB DOC User Manual

DOC – User Manual - Page 41

Connections stretched using the “Stretch” command

Add a text

To add the text notes to the single-line diagram, use the “Text” command in the “Tools”

menu.

4.7. Labels The Labels are texts associated with each Single Object which allow the characteristics and

calculation results to be displayed, such as the Iz of a Cable, the Description of a Circuit-

breaker or the short-circuit current at a Busbar.

The position of the Labels depends on the layout.

Layout in columns

The layout in columns shows all the data relative to a Single Object in the layout underlying

it.

The contents of each compartment of the layout is explained in the caption at the bottom on

the left.

It is not possible to modify the layout and results displayed.

Page 42: ABB DOC User Manual

Page 42 of 170

Layout: Caption (first column on the left); data of a dimensioned feeder (green color) and

data of an undimensioned feeder (blue color)

Free Layout

The free layout shows some calculation results in the labels placed beside each Single Object.

Labels in a free configuration diagram; Window for Label Management

Page 43: ABB DOC User Manual

DOC – User Manual - Page 43

Label Management

The Labels show the user the main data of each Single Object.

The Labels can be customized:

The list of data contained in the Label can be changed by the user with the “Label

Management” command in the “Edit” menu. There are two predefined Label

configurations: one for the free diagram, the other for the layouts in columns. Special

Label configurations can be saved to then be used again in other projects.

The fixed text part of the Labels can be changed by the user with the “Edit object

labels” command in the “Edit” menu.

Code of the circuit-breaker modified with the “Modify labels” command

Move the Labels

Using layouts A3, A2, A1 or A0, which allow free drawing of the single-line diagram, the

labels are shown beside the Single Objects.

When two or more labels are overlaid, it is possible to move them with the “Move labels”

command.

Modify the data shown on a Label

To modify the list of data shown on a Label, the “Label Management” command in the

“Edit” menu is used.

Page 44: ABB DOC User Manual

Page 44 of 170

Window for label management

The window for label management allows definition of which properties to display in the

diagram.

To modify the state of a property, first select the Single Object to be modified in the “Object”

menu, then you can enable or disable a property on the list of “Properties”. The selection

effects all the Single Objects in the single-line diagram.

Furthermore, it is possible to save a label configuration by means of the “Save

configuration…” button, to be able to use it again in another project.

The “Board configuration diagram” and “Free configuration diagram” options refer to the

two types of layout:

“Board configuration diagram” is the layout in columns, available in two variants: one

for LV plants and one for MV switchgear.

“Free configuration diagram” is the layout without columns, where the labels are

displayed beside each Single Object.

Example of using label management: Display\Hide the padlock

The padlock icon (Cf. Chapter 5.5) present in the Labels is used to make the Single Objects,

which have been locked by the user and that DOC cannot modify following a calculation,

recognizable.

The symbol is very useful during design, but cannot be used during the printing stage.

It can therefore be useful to know how to manage the Labels to show or hide the padlock icon

according to the task you are carrying out.

This situation can be managed with two label configurations:

With padlock

Without padlock

1) Launch the “Label Management” command from the “Edit” menu

2) Select the “Switchboard configuration diagram” or “Free configuration diagram” option

according to the layout being used

3) Activate the padlock for all the Single Objects. The padlock is managed by the “STATE”

properties.

Page 45: ABB DOC User Manual

DOC – User Manual - Page 45

Label management: STATE label of the LV circuit-breaker

4) Save the configuration with the “Save configuration…” button, assigning it whatever name

you like.

5) Disable the padlock for all the Single Objects.

6) Save the new configuration as described in point 4).

7) To display of the padlock, launch the “Label management” command from the “Edit” menu,

select the type of diagram used, switchboard or free, select the configuration where display of

the padlock is foreseen from the pull-down.

8) Once the two configurations described in point 4) and 7) have been created, you can rapidly

pass from one to the other by executing the “Label management” command and selecting the

desired configuration from the list at the top on the left.

Single-line diagram with the padlock visible and not visible

Page 46: ABB DOC User Manual

Page 46 of 170

5. Calculation and Dimensioning

This chapter describes:

the DOC calculation potential;

results of the calculation;

verification of existing plants.

After reading this chapter, the user will be able to:

understand what is calculated by the program;

understand how the calculations are done;

solve most of incorrect situations highlighted by the program;

read the calculation results;

customize the program choices.

Page 47: ABB DOC User Manual

DOC – User Manual - Page 47

5.1. Calculation and Dimensioning

When the single-line diagram drawing is completed and the data of the Single Objects have

been defined, it is possible to calculate the single-line diagram.

DOC is fitted with a powerful calculation engine able to automatically carry out long and

complex operations which would take a long time to carry out manually or using other less

powerful software.

In particular the DOC calculation engine is able to:

Verify correctness of the single-line diagram design

Calculate the load currents at all points of the diagram

Calculate the voltage drops

Balance single-phase - two-phase loads over the three phases

Calculate the power consumed by the supply and the power factor

Dimension the cables according to the calculated load currents and/or the voltage drops

Repeat steps 2 and 3 until all the cables have been correctly dimensioned

Calculate the maximum and minimum short-circuit currents at all points of the single-

line diagram

Select the protection devices according to the load currents, short-circuit currents,

protection of cables and people, and if required, coordinate the protection devices

(discrimination and/or back-up).

The calculation is done using the “Calculate” button of the “Work flow” toolbar. All the

calculation parameters are preset so as to satisfy the needs which are found in the most

common plants, therefore starting the calculation is immediate and does not require any

further decisions by the user.

Advanced Calculation Settings

Some parameters used in the calculation procedure can be modified by the user.

This operation is generally not indispensable because the parameters are preset so as to

satisfy the most common needs. Therefore, to view and modify these parameters it is

necessary to use the “Options…” command in the “Tools” menu, and to select the “Show

calculation settings before dimensioning” box on the “Calculation options” page,

Modification of the advanced calculation options is only recommended for expert users and

those with special requirements. In fact, they regard:

Definition of the instants at which to calculate the short-circuit currents;

Tolerance over the power supply voltage;

Reference temperature of the cables for calculation of the maximum short-circuit

currents;

Type of over-excitation of the generators present in the diagram;

Manual exclusion of the motor contributions in calculating the short-circuit currents.

Page 48: ABB DOC User Manual

Page 48 of 170

Minimum and Maximum short-circuit currents

DOC calculates the Minimum and Maximum short-circuit currents it all points of the

network.

Their difference is explained in the IEC 60909-0 Standard in chapters 2.4 and 2.5 (the

differences are also given in DOC during printing in the “Short-circuit Calculation

Hypotheses”; 9.2.3).

It is important to underline that, with regard to the end-of-line fault currents, DOC calculates:

The Minimum fault current in the cable, used for protection against indirect contacts

(Cf. Chapter 6.1).

The Maximum fault current in the switchboard on the load side of this line, used for

selection of the Breaking Capacity of the protection devices installed in the switchboard.

Two different short-circuit values are therefore available at the end of the line, defined as

follows:

Maximum short-circuit currents

To calculate the maximum short-circuit currents, the voltage factor cmax (equal to 1.05

or 1.1);

The motors are included if their contribution is higher than 5% of the maximum short-

circuit current calculated without this contribution;

The resistances of the lines (overhead and in cables) are taken at a temperature of 20°C.

Minimum short-circuit currents

To calculate the minimum short-circuit currents, the voltage factor cmin, equal to 0.95, is

applied;

The contribution of motors is excluded;

The resistances of the lines (overhead and in cables) are taken at a temperature of 80°C.

The values of the cable resistance at 20°C and at 80°C can be printed by enabling the “Table

of LV cables” of the project documentation (Cf. Chapter 9.2.4.).

Page 49: ABB DOC User Manual

DOC – User Manual - Page 49

During calculation, a window is visible which shows the state of progress of the process.

Calculation Window

During calculation, messages may appear, when significant or abnormal situations occur.

The meaning of the main messages is explained in chapter 5.2.

According to what is found by DOC, the Single Objects may change color in conformity with

the profile of the colors (Cf. chapter Error! Reference source not found..) on completion of

he calculation.

It may also occur that in some situations DOC is not able to select some switching and

protection devices.

The main cases which may occur are explained in chapter 5.3.

The results available on completion of calculation and the methods for displaying these are

described in chapter 4.7.

The main actions which can be taken on completion of the calculation to verify the results

and, where necessary, to modify the program selections are described in chapter 5.5.

Page 50: ABB DOC User Manual

Page 50 of 170

5.2. Error Messages

This chapter explains the most important and frequent error messages that can appear during

calculation.

The error messages which could appear during calculation are of two types:

Blocking messages: warn of a critical and incorrect situation which must be corrected

before being able to proceed with the calculation.

Warning messages: draw the user‟s attention to an anomalous or potentially incorrect

situation but do not block the calculation process.

Blocking messages

Phases – Distribution system not consistent in the highlighted Objects

DOC verifies the congruence of the single-line diagram (for example: a single-phase

cable cannot supply a three-phase load).

Solutions: verify the phase and distribution system properties in the Single Objects

indicated. In the case of any discrepancies, cancel and draw new the Single Objects or

modify the Phase and Distribution system properties after having carried out a Multiple

selection (Cf. Chapter 4.6) of the Single Objects involved.

Single-line diagram incorrect: it is necessary to add a power source between supply

and loads. Verify the Highlighted Objects

DOC needs at least one Single Object with impedance not nil (for example, a cable or a

busway) to be present between supply and loads.

Solution: verify that there is at least a cable or busway between the supply and the

loads.

Single-line diagram incorrect: it is necessary to add a power source between two

supplies. Verify the Highlighted Objects

DOC needs at least one Single Object with not nil impedance (for example, a cable or a

busway) to be present between two supplies which work in parallel.

Solution: verify that there is at least a cable or busway between the two power supplies.

Single-line diagram incorrect: some objects are short-circuited! Verify the

Highlighted Objects.

DOC verifies that there are no branches with nil impedance in parallel with Single

Objects or branches of the plant: the latter would, in fact, not be passed through by

current and this is indication of an error in the single-line diagram drawing.

Solution: verify the connections between the two short-circuited Single Objects.

Single-line diagram incorrect: connections missing. Verify the Highlighted Objects

A part of the single-line diagram is not connected to the supply.

Solution: connect the Highlighted Single Objects to the supply.

Single-line diagram incorrect: links not connected. Verify the Highlighted Objects

A link has not been connected to the relative arrival.

Solution: verify the link indicated and connect it to another link; should the link be

superfluous, cancel it.

Page 51: ABB DOC User Manual

DOC – User Manual - Page 51

Warning messages

Voltage drop higher than the limit set for the highlighted Objects

DOC verifies that there is a voltage drop percentage no higher than 4% (or than the

value entered by the user) on each load and signals the loads for which the threshold has

been exceeded.

Solution: verify the sizes of cables on the supply side of the load involved.

The transformer highlighted is not dimensioned correctly: increase the size!

DOC verifies that the transformers are able to supply the power required by the plant.

The message generally appears when the transformers have been locked with a padlock,

otherwise DOC would be able to select another power transformer suitable for the load

required automatically.

Solution: Increase the size of the transformer, verify that the power of the loads and the

demand coefficients have been entered correctly.

These objects are not protected against overload \ short-circuit \ indirect contacts

DOC verifies that all the cables and switching devices are protected against faults (the

warning can be disabled in the window which communicates the warning).

Solution: It is not always necessary to take measures (for example, in the case of

missing protection against overload in the emergency configurations): the user can

decide, under their own responsibility, to omit the protections when the Standards

and/or the characteristics of the plant allow this.

If necessary, add a protection device on the supply side of the unprotected object.

Attention: some supplies consume power instead of supplying it

DOC verifies if the flow of power goes from the supply to the loads. In the case of

several power supplies in parallel (generator and power supply) a generator may satisfy

the power required by the plant and also supply energy to the power supply.

Solutions: if you do not want the generator to supply energy to the power supply, verify

the size of the generator, the power of the loads and the demand coefficients.

If it is normal for the generator to supply power to the network in the plant, the message

is confirmation of this behavior.

Attention: some supplies have lower rated power than the one required by the

plant

DOC verifies that the generators and the UPS are able to supply the power required by

the plant, comparing their rating plate data with the requirements of the loads (the

supply is considered to be a generator with infinite power).

Solution: in this order, verify the rating plate data of generators and UPS, the demand

coefficients and the power consumed by the loads.

In the highlighted cables the following dimensioning criteria are not verified:

- The carrying capacity is insufficient

- The voltage drop exceeds the limit set

DOC verifies that the locked cables (Cf. Chapter 5.5) satisfy the carrying capacity and

voltage drop criteria.

Solutions: verify the cable data (length, insulation, method of installation) and the load

data; or trip unit the cable and let DOC re-calculate the section.

Page 52: ABB DOC User Manual

Page 52 of 170

5.3. Failed Selection of Single Objects

Sometimes DOC is not able to find a valid product, or shows the products locked by the user

with the padlock as invalid.

The most frequent cause of failed selection or verification of a product are listed below and

can guide the user to modify the selection criteria appropriately.

If the Single Object is locked with the padlock, unlock it and restart the calculation.

Verify that the appropriate protections against indirect contacts with the power sources

by means of residual current devices are present, when the distribution system is TT. It

may be impossible to ensure protection against indirect contacts with other protection

functions.

In the case where the fault current is high (over 15kA) and the section of cable to be

protected against short-circuit is less than 4 mm2, try to restart the calculation after

having selected a cable with a larger section and having locked it with the padlock.

Verify that you are do not find yourself in one of the cases specified below, for which no

suitable products exist:

o 1P, 1P+N and 2P products in circuits with current higher than 125A (the 1P,

1P+N and 2P devices are of modular type and have a maximum rated current of

125A. It is necessary to select 3P, 3P+N or 4P devices.

o Residual current protection with rated current higher than 2000A (the maximum

size of an RCQ external toroid is 2000A).

o Fuses with rated current higher than 630A (the maximum rated current of the

fuses managed by DOC is 630A).

o Fuses with breaking capacity higher than 100kA (the fuses have a breaking

capacity of 100kA. If DOC has calculated higher short-circuit currents, verify the

supply data, or select a circuit-breaker instead of a fuse).

o Circuit-breakers with breaking capacity higher than 200kA (The circuit-breakers

have a breaking capacity maximum of 200kA. If DOC has calculated higher

short-circuit currents, verify the supply data).

o Molded-case circuit-breakers with rated current higher than 160A to protect

residual current circuit-breakers (it is not possible to carry out protection of

residual current circuit-breakers with molded-case type circuit-breakers with

rated current higher than 160A).

o Molded-case circuit-breakers with current lower than or equal to 160A to protect

residual current circuit-breakers with short-circuit current higher than 6kA

(molded-case circuit-breakers with rated current up to 160A can only protect

residual current circuit-breakers up to 6kA).

o Miniature circuit-breakers in circuits with current higher than >125A or breaking

capacity >25kA. In this case, remove the limit on the type of product and allow

selection of a molded-case type of circuit-breaker.

Page 53: ABB DOC User Manual

DOC – User Manual - Page 53

If a fuse, or a switch-fuse, protects a cable, verify that the relation between Iz and Ib is at

least equal to 1.2 (Cf. Chapter 6.1.1: a cable with Iz of 30A can only be protected by a

fuse up to 0.9 x 30A = 27A.

If a circuit-breaker protects a cable, verify that between Ib and Iz there is space to be

able to select a size of product. For example,: if Ib is 26A and Iz is 30A it is not possible

to select a miniature circuit-breaker to protect these since the closest sizes are 25A,

lower than Ib, and 32A, higher than Iz.

Verify that there are not too many objects protected by the same protection device (the

window to display \ modify the list of the protections is described in Annex B).

For the circuit-breaker, verify that there are not too many simultaneous discrimination,

back-up and cable protection restrictions. In this case, slacken one or more of the

restrictions.

Help for Failed Selection of Single Objects

In the case where it is not possible to achieve selection of a product using the suggestions

given above, you can the send the project file and a description of the anomaly to assistance

service which is at your disposal.

The address is as follows: [email protected]

Page 54: ABB DOC User Manual

Page 54 of 170

5.4. Calculation and Dimensioning Results

Calculation results

DOC calculates the following, both in low and in medium voltage:

Maximum short-circuit currents at all points of the single-line diagram.

Minimum short-circuit currents at the end of the line.

Phase and of neutral currents (in unbalanced networks) at all points of the single-line

diagram.

Power factor on each line and at each busbar.

Active and reactive power required at the supply.

Dimensioning results

The program is able to select the following, both in low and in medium voltage:

The minimum sections of the cables which satisfy the following criteria:

o thermal according to the Standard selected

o voltage drop on the single line less than 4% (modifiable by the user)

The most economical protection apparatus (circuit-breakers, fuses) on the list of

technically correct ABB products.

The most economical switching apparatus (disconnectors, contactors) on the list of

technically correct ABB products.

Further results

Other results coming from a calculation:

Balancing unbalanced networks. The program applies an algorithm to “move” the

single-phase and two-phase loads from one phase to the other, so that the consumption

of current on the supply side is as balanced as possible.

Dimensioning for the rated current of a transformer or generator. The Single Objects

placed on the load side of a transformer or generator will be dimensioned according to

the rated current of the secondary winding of the transformer or according to the rated

power of the generator, instead of to the current required by the plant.

This option is useful for those who possess machines dimensioned taking future

enlargements of the plants into consideration. Cables and switching and protection

devices will not have to be changed, with obvious savings in execution times and costs.

Page 55: ABB DOC User Manual

DOC – User Manual - Page 55

5.5. Changing the Dimensioning Results.

This chapter will explain how to modify the selections made automatically by the program.

Locking and Unlocking Single Objects

During the stage of modifying the program selections after dimensioning, the most important

commands, are those which allow a Single Object to be Locked or Unlocked.

The “Lock objects” command modifies the calculation settings, so that at the next

dimensioning, the locked Single Object is only checked and not modified by DOC.

The locked Single Objects behave as follows:

Object Effect of the lock

Cable The section is not re-calculated.

Protection device The product is not changed with a more economical one.

Switching device The product is not changed with a more economical one.

Transformer The size is not re-calculated according to the loads.

Load The single-phase loads are not connected to a different phase in

order to minimize the unbalance.

The “Unlock objects” command resets the calculation settings, so that at the next

dimensioning, the unlocked Single Object is selected by DOC.

The unlocked Single Objects behave as follows:

Object Effect of the lock

Cable DOC re-calculates the section, optimizing it according to the

voltage drop and the carrying capacity

Protection device The most economical product among those technically suitable is

proposed.

Switching device The most economical product among those technically suitable is

proposed.

Transformer The size is re-calculated according to the loads.

Load If this is single-phase, it can be connected to a different phase to

minimize the unbalance.

Page 56: ABB DOC User Manual

Page 56 of 170

Changing a product

The automatic selections made by DOC cannot take into account every single requirement of

all the program users!

To change a product proposed by DOC, simply:

Enter the Single Object Properties window.

Click over the “Select >>>” button

Navigate the tree to find the desired product.

Lock the desired product with the padlock.

Entering the selection window, the list of products displayed considers the technical selection

filters of the product (for example, circuit-breakers with breaking capacity lower than the

short-circuit current will not be shown).

If the desired product is not on the list, remove the technical filters by selecting the “Free

selection” option at the top on the left.

“Select >>” button in a circuit-breaker window

At the next calculation, DOC will verify the locked product instead of selecting a new

product.

Changing cable sizes

DOC selects the cable sections according to the Standard, to the carrying capacity of the

cable and to the voltage drop.

Changing the cable sections, for example, to verify a cable already installed, is possible by

entering the cable Properties window.

In this window, select the most suitable sections for your situation and lock the selection with

the padlock.

Modifying the size of a cable changes the impedance of the cable itself and therefore the

voltage and short-circuit values on the load side of the cable.

New values of the short-circuit currents could invalidate the selections relative to the

protection devices already selected: it is therefore necessary to re-calculate the whole

single-line diagram !

Page 57: ABB DOC User Manual

DOC – User Manual - Page 57

6. Verification and Protections

This chapter describes:

verifications of the overload, short-circuit, indirect contacts and discrimination from a theoretical viewpoint;

the verifications carried out by the program.

After reading this chapter, the user will be able to:

understand the overload, short-circuit, indirect contacts and discrimination verifications;

use the curves module to carry out overload, short-circuit, indirect contacts and discrimination verifications.

Page 58: ABB DOC User Manual

Page 58 of 170

6.1. Verifications and Protections

This chapter describes how to verify cable protection and the discrimination criteria by means

of the module dedicated to drawing the curves.

6.1.1. Description of the Protections

DOC verifies the protections against the following in real time:

Overload (hereinafter OL).

Short-circuit (hereinafter SC).

Indirect contacts in TT systems (hereinafter NDT-TT).

Indirect contacts in TN systems (hereinafter NDT-TN).

The protection criteria are defined in the standard IEC 60364-4-43:

Overload (IEC 60364-4-43Standard Chapter 433):

- The set current of the protection device (In) must be between the service current

(Ib) and the carrying capacity of the power source (Iz).

IzInIb

- The threshold of guaranteed tripping of the protection device must be less than

1.45 times the carrying capacity of the power source.

IzI 45.12

where:

Ib = Service current.

Iz = Carrying capacity in permanent regime of the power source.

In = Current set of the protection device (for non-adjustable protection devices,

this coincides with the rated current).

I2 = Current which ensures effective operation of the protection device

within the prearranged time under defined conditions.

Current for Guaranteed Circuit-breaker Tripping and Fuse intervention

For construction characteristics, the I2 current for guaranteed tripping is:

- Always less than or equal to In45.1 for circuit-breakers

- Equal to In6.1 for fuses.

It follows that:

- A circuit-breaker is able to protect a cable against overload over the whole of its

carrying capacity, making the verification superfluous IzI 45.12

- In a fuse, the most strict condition is verification on I2. Replacing I2 with the value

In6.1 , you obtain:

IzIn 45.16.1 From which it follows that:

IzIn 906.0 In other words, protection of a cable against overload by means of a fuse does not allow

use of this cable up to its carrying capacity, but only up to about the 90% of its carrying

capacity.

Page 59: ABB DOC User Manual

DOC – User Manual - Page 59

Short-circuit (IEC 60364-4-43 Standard Chapter 434):

o The specific energy let-through by the protection device is lower than the specific

energy supported by the cable for all the current values from Ib to the maximum

short-circuit current.

With DOC, the verification is carried out graphically by comparing the curve of the

specific energy let through by the circuit-breaker (I2t) and the curve of the maximum

energy which can be supported by the cable (K2S

2) and verifying that there are no

intersections in the range of currents defined by the Standard.

Diagram of energy: comparison of the curves of a circuit-breaker (blue) with a completely

protected cable (black) and a partially protected cable (red)

Indirect contacts in TT systems (IEC 60364-4-43 Standard Chapter 413):

o The contact voltage is less than 50 [V] i.e.:

50 IaRa

where:

RA [Ω] = Sum of the resistances of the ground plate and protection conductors of

the exposed conductive parts.

IA [A] = Current which causes automatic operation of the protection device (if the

protection device is of the residual current type, IA is the rated Idn residual current).

Page 60: ABB DOC User Manual

Page 60 of 170

Modifying the RA Value

As described in the previous paragraph, RA is given by the sum of two resistances: the

ground plate and the protection conductors of the exposed conductive parts.

Ground plate: its value is defined in the “General plant properties” (cf. Chapter 3.2).

If necessary, it is possible to set a different value of the ground plate for each single

feeder in the “Protected Objects” window of the protection device (“LV circuit-

breaker”, “LV Fuse”, “Residual current circuit-breaker”) placed on the supply side of

the feeder itself.

Protection conductors of the exposed conductive parts: the value of the resistance of

the conductors is calculated by the program according to the type of cable and its

section. The values of the conductor resistances can be

o Consulted in the “LV cable” properties (Cf. Annex B);

o Printed in the “Table of LV cables” 9.2.4).

Indirect contacts in TN systems (IEC 60364-4-43 Standard Chapter 413)::

o The trip threshold of the protection device must be lower than the fault current at the

end of the Phase – Ground line, i.e.:

UoIaZs

where:

ZS [Ω] = Impedance of the fault ring which includes the source, the live conductor

as far as the fault point and the protection conductor between the fault point and the

source (in DOC, this type of fault is called “L-PE”, i.e. between phase and

protection conductor).

IA [A] = Current which causes automatic operation of the protection device within

the time defined in the following table (if the protection device is of residual current

type, IA is the rated residual current Idn).

Uo [V] Trip time [s]

120 0.8

230 0.4

400 0.2

>400 0.1

U0 [V] = Effective value of the rated voltage between phase and ground.

DOC calculates the value ZsUo , indicated as “Icc L-PE” (short-circuit fault

current between Phase and Protection conductor). The verification carried out is

therefore:

PEIccL Im

where:

IM [A] = is the current which causes protection device tripping within the scheduled

tripping time.

Page 61: ABB DOC User Manual

DOC – User Manual - Page 61

Indirect contacts in IT systems (IEC 60364-4-43 Standard Chapter 413):

o In IT systems the live part of the network is electrically insulated from the

exposed conductive parts, therefore the circuit of any possible ground fault

can only be re-closed in capacitive couplings between live conductors and

exposed conductive parts or groundings (as in the diagram below).

The value of these capacitive couplings cannot easily be calculated, making

it impossible to give a value to the impedance of the fault ring and therefore

to the current which passes through it.

Circuit of a ground fault in a IT system

Not knowing the value of the first ground fault, DOC is not able to verify

the protection against indirect contacts.

Remember that, in any case, the above-mentioned Standard foresees the use

of an insulation control device to indicate appearance of an initial fault

between a live part of the network and exposed conductive parts or ground.

The same Standard does not impose protection against indirect contacts in

IT systems by means of automatic interruption of the power supply.

The parameters used for verification of protection against indirect contacts can be modified in

the “General plant properties” window (Cf. Chapter 3.2).

Further Information about Protection against Indirect Contacts

For further information, we recommend consulting the “QT3 - Distribution systems and

protection against indirect contacts and ground faults” guide for more details on the subject.

Page 62: ABB DOC User Manual

Page 62 of 170

6.1.2. Protection devices

The protection devices are able to supply the types of protection listed in the table below.

Protection device OL SC

NDT-

TN

NDT-

TT

Thermomagnetic circuit-breaker X X X

Thermomagnetic circuit-breaker with residual

current X X X X

Magnetic only circuit-breaker X X

Magnetic only circuit-breaker with residual

current X X X

Residual current circuit-breaker X

Fuse X X X

Switch-fuse X X X

Thermomagnetic Manual motor starter X X X

Magnetic only Manual motor starter X X

Thermal trip unit X

DOC automatically assigns cable protection to the most suitable device on the supply side.

However, it is possible to modify the program selections by pressing the “Advanced Options

>>>” or “Protected Objects” buttons which are always present in the windows dedicated to

each protection device.

Removal of the protection restrictions of switching devices or power sources might leave

these objects unprotected in the case of a fault.

We recommend using this option very carefully.

Window for assigning the protections.

Page 63: ABB DOC User Manual

DOC – User Manual - Page 63

6.1.3. Verifying Protections

Curves Module Manual

This Chapter only contains basic indications about using the curves module.

For a detailed explanation on how to set the trip units and on the functionalities of the

application, please consult the “Curves Manual” user guide in the DOC “Help” menu.

Verification of the protections is carried out with the curves module, which is enabled by

clicking over the icon shown on the left and which is located in the “Work flow” tools

toolbar.

Once the command is given, DOC shows a new work environment where it is possible to

work on the curves of the devices present in the diagram and on all the settings available.

Main curves module window.

The “Relations”, i.e. the list of protections verified by DOC, are shown in the lower part of

the screen.

Page 64: ABB DOC User Manual

Page 64 of 170

The “Relations” window is divided into four columns:

Object on the supply side (protection device, a circuit-breaker or a fuse).

Object on the load side (object protected, typically a cable).

Verification calculation carried out by DOC (the calculation is done in real time as soon

as a curve is modified and in conformity with the criteria expressed previously).

Present state of the verification.

If a protection relation is satisfied, the text which describes it is black and the state is “OK”.

If a protection relation fails, the text which describes it is red and the state is “Failed”.

You can print the results of all the verifications made by DOC in the “Report of protections”

(Cf. Chapter 9.2.9).

Examples of satisfactory and failed verifications

Page 65: ABB DOC User Manual

DOC – User Manual - Page 65

6.1.4. Modifying Verifications

When a protection relation fails you can proceed according to the indications given below to

understand the reasons for this and to take the appropriate measures to make it satisfactory.

Verification of protection against overload

Verification of overload

Select the failed verification by ticking its box;

The curves module will show the Time-Current diagram (I-t);

The protection device and the cable the verification refers to will be shown;

Double click over the curve of the protection device;

Modify the setting of the thermal threshold (“L” threshold) until the current set between

“Ib” (load current) and “Iz” (carrying capacity of the cable) is made to fall;

The color of the message will change in real time from red to black, when the protection

relation has been verified.

Page 66: ABB DOC User Manual

Page 66 of 170

Verification of protection against short-circuit

Verification of short-circuit

Select the failed verification by ticking its box;

The curves module will show the diagram of the specific let-through energy (I-I2t);

The protection device and the cable the verification refers to will be shown;

There may be circuit-breakers of large size and fitted with a microprocessor trip unit: in

this case enable functions “S” and “I” of the microprocessor trip unit and modify the

setting until the circuit-breaker curve is completely under the cable curve;

The color of the message will change in real time from red to black, when the protection

relation has been verified.

Page 67: ABB DOC User Manual

DOC – User Manual - Page 67

Verification of protection against indirect contacts

Verification of indirect contacts

Select the failed verification by ticking its box;

The curves module will show the Phase-ground fault current – Time (I-t LPE) diagram

Select the circuit-breaker curve by clicking over it;

Click over the “min Ik” icon: the command makes a vertical straight line appear in the

diagram which represents the fault current at the end of the line. A positive verification

is obtained when the magnetic threshold of the circuit-breaker is on the left of the fault

current at the end of the line;

Lower the magnetic threshold of the thermomagnetic trip units, or enable thresholds “S”

or “I” of the microprocessor trip units and use sufficiently low setting values;

The color of the message will change in real time from red to black, when the protection

relation has been verified.

Page 68: ABB DOC User Manual

Page 68 of 170

Verification of discrimination

Verification of short-circuit

Discrimination is achieved when both the following conditions are satisfied:

The circuit-breakers have been selected by assigning them the discrimination restriction

in the single-line diagram (Cf. Annex B, “LV circuit-breaker” chapter).

The curve of the circuit-breaker on the supply side, in the Time-Current diagram, does

not intersect the one of the circuit-breaker on the load side.

When the program notifies failed discrimination verification, it is advisable to proceed as

described below:

Select the failed verification by ticking its box;

The curves module will show the Time-Current diagram (I-t)

Double click over the circuit-breaker on the supply side, by accessing the mask for

setting its trip unit.

If the trip unit is of thermomagnetic type (“Circuit-breaker with thermomagnetic trip

unit”), raise threshold “I” up to the maximum value allowed.

If the trip unit is of microprocessor type (“Circuit-breaker with microprocessor trip

unit”), disable function “I”;

o Once function “I” has been disabled, it is advisable to enable function “S”

(protection against delayed short-circuit);

o Raise threshold “S” both in time and in current until discrimination is obtained.

The color of the message will change in real time from red to black, when the protection

has been verified.

Page 69: ABB DOC User Manual

DOC – User Manual - Page 69

The hatched area appears in the diagram when a discrimination verification has been

selected. This area represents the maximum discrimination value which can be achieved by

the pair of circuit-breakers.

The maximum discrimination value is defined as:

The magnetic setting of the circuit-breaker on the supply side minus the tolerance, if:

o The circuit-breaker on the supply side is fitted with a microprocessor trip unit and

function “I” is enabled;

o The circuit-breaker is fitted with a thermomagnetic trip unit and the setting of the

magnetic threshold “I” is lower than the maximum value allowed.

The value of discrimination published in the ABB “Coordination Tables” if:

o The circuit-breaker on the supply side is fitted with a microprocessor trip unit and

function “I” is disabled;

o The circuit-breaker is fitted with a thermomagnetic trip unit and the setting of the

magnetic threshold “I” is equal to the maximum value allowed.

Further Information about Discrimination Verification.

The “QT1 - Discrimination in low voltage with ABB circuit-breakers” guide is available in

the “Help” menu. It is advisable to consult this for in-depth information on the subject.

Discrimination Studies between MV Apparatus and LV Apparatus

The “QT2 - MV/LV Substations: theory and short-circuit calculation examples” guide is

available in the “Help” menu. It is advisable to consult this for in-depth information on the

subject.

Impossibility of Verifying all the Relations.

It may not be possible to satisfy all the protection relations simultaneously, since a setting

made to satisfy one may not allow satisfaction of others.

This can occur, for example, if both protection against indirect contacts and discrimination

with circuit-breakers on the load side must be guaranteed using the same protection device:

the former requires a low magnetic setting, whereas the latter requires high values or

disablement of function “I”.

It is advisable to:

Replace the thermomagnetic trip units with microprocessor ones, provided with several

possibilities during the setting stage.

Use trip units fitted with function “G”, which allows you to have high magnetic settings

for verification of discrimination and low magnetic settings for protection against

indirect contacts.

Verification of Back-up

DOC is able to select circuit-breakers coordinated by means of back-up.

This relationship does not require any further verification: back-up is a function of the

construction characteristics of the circuit-breakers and does not depend on the trip unit

settings.

The back-up value is declared by the Manufacturer in the ““Coordination Tables”.

Page 70: ABB DOC User Manual

Page 70 of 170

6.2. Printing Options for the Curves Module

6.2.1. Printing the Diagram

The curves module allows you to print the diagrams using the “Print” command.

It is possible to print:

The diagram shown on screen;

The settings of the objects in the diagram;

The verification selected at present (in this case, the objects visible will only be those

involved in the relative verification).

Printing from the curves module.

Page 71: ABB DOC User Manual

DOC – User Manual - Page 71

6.2.2. Exporting the Data from the Diagram

The curves module is fitted with two commands to export the diagram (“Copy graph”) and

the setting values (“Copy values”).

Once copied, the graph or values are pasted into any application which supports MS

Windows copy-paste.

Using these commands, it is possible to create a customized document containing:

The diagram shown on screen;

The settings of the objects in the diagram;

The verification currently selected (in this case, the objects visible will only be those

involved in the relative verification).

Document created using copy-paste of values and graph

Page 72: ABB DOC User Manual

Page 72 of 170

6.2.3. Copying the Diagram onto the Single-line Diagram

From the curves module it is possible to add the diagram currently displayed onto the single-

line diagram, by means of the “Draw” icon.

To draw a diagram in the single-line diagram, follow the instructions below:

Select the page of the single-line diagram where you want to add the diagram, or create

a new one.

Launch the curves module.

Select the objects to be displayed in the diagram.

Select the “Draw” command.

DOC will temporarily show the single-line diagram.

Give an initial click to determine the vertex at the top on the left of the diagram.

Give a second click to determine the second vertex of the diagram. After the second

click, DOC will show the new curves module.

Diagram drawn in the single-line diagram

Page 73: ABB DOC User Manual

DOC – User Manual - Page 73

7. Drawing Diagrams of Auxiliaries

This chapter describes:

the functionalities of drawing not included in the power diagram.

After reading this chapter, the user will be able to:

add purely graphic symbols to the diagram;

draws simple key diagrams.

Page 74: ABB DOC User Manual

Page 74 of 170

7.1. Drawing the Key Diagram of the Auxiliary Circuits

This chapter describes how to use DOC to draw key diagrams.

The key diagrams allows purely Graphic Objects to be drawn.

The purely Graphic Objects are not considered in the drawing of the single-line power

diagram and therefore do not affect the calculations.

7.1.1. Tools toolbars for the Key Diagrams.

The first step for drawing key diagrams is to enable the special tools toolbar with the

auxiliaries icon in the “Work flow”.

Tools toolbar of the auxiliaries

The toolbar is divided into three areas:

“Connection”

“Auxiliary Objects”

“Buttons”

Connection

The “Connection” area represents the line which must be traced to connect the objects

present with each other in the diagram of the auxiliaries.

Page 75: ABB DOC User Manual

DOC – User Manual - Page 75

Auxiliary Objects

The “Auxiliary Objects” are the symbols with which it is possible to draw the key diagram of

the auxiliary circuits. They include the contacts (NO and NC), the changeover contacts, and

the coils (normal and of contactor).

Buttons

The “Buttons” group together different symbols which are associated with different types of

buttons.

7.1.2. Drawing Key Diagrams

1) Select “Line” and trace the main lines of the diagram.

Main lines of a key diagram

Page 76: ABB DOC User Manual

Page 76 of 170

2) Add the contacts and the coils to be shown.

Diagram with contacts and coils

3) Close the diagram by adding the “Line”

Complete diagram

Page 77: ABB DOC User Manual

DOC – User Manual - Page 77

4) Finish the diagram by adding any “Pushbuttons”.

Diagram complete with pushbuttons

5) Insert any explicative texts, using the “Text” command in the “Tools” menu.

Diagram with texts

Page 78: ABB DOC User Manual

Page 78 of 170

Example of motor starting.

Page 79: ABB DOC User Manual

DOC – User Manual - Page 79

8. Switchboard configurator

This chapter describes:

The list of switchboard configurator functionalities

The procedure to drawing the front panel by wizard

How to modify the front panel configuration

Drawing Busbar distribution system

After reading this chapter, the user will be able to:

Use the configurator tools for design front panel.

Configure a front panel starting from a single-line diagram or a quotation of CAT.

Page 80: ABB DOC User Manual

Page 80 of 170

8.1. General indications on switchboard configuration

This chapter describes how to use DOC to draw and configure a front panel of ArTu and IS2

switchboard.

After calculating and verifying the single line diagram you can proceed to design and

configure the switchboard as described in this chapter.

Design and configure switchgear is carried out with the switchboard module, which is enable

by clicking over the “Switchboard configuration” and which is located in the “Work flow”

tools toolbar.

The switchboard configuration is only available with the Professional Profile.

8.2. WIZARD - Switchboard configuration

This chapter describes how to configure front panel using wizard procedure.

The Wizard is useful procedure to configure faster a front panel, starting from the single line

diagram in DOC or from selected materials from the CAT software estimation.

Starting from a single line diagram generate in DOC, the first step to configure a switchboard

is to enable the special tools toolbar by clicking over the icon shown on the left and which is

locate in the “Work flow”.

Single-line diagram

Page 81: ABB DOC User Manual

DOC – User Manual - Page 81

Starting from the bill of material selected by software CAT, the first step to configure a

switchboard, is to enable the special tools toolbar by clicking over the icon shown on the left

and which is locate in CAT ribbon bar.

The “switchboard toolbar” will now be visible and ready to be use.

Wizard

Tools for insert, editing and the device manager.

Tools for drawing busbar distribution system and OTC

Layer management

Page 82: ABB DOC User Manual

Page 82 of 170

Using “Wizard” command, the program shows the first of three step of Wizard procedure for

the fast setting of switchboard data.

Wizard - Step 1/3 Through the mask 1 / 3 can be defined the list of devices to be included in the front panel

configuration.

The checkbox allows you to decide whether the device is actually to be considered or not in

the configuration of the front panel.

Window 1/3- Wizard procedure

To not consider one or more devices in the front panel configuration, simply remove the

tick sign from its check box.

Modify sorting device. Modificare ordinamento dei dispositivi

Thanks to the commands “Move Up” and “Move Down” is possible define sorting of devices

within the switchgear front view.

Page 83: ABB DOC User Manual

DOC – User Manual - Page 83

Wizard - Step 2/3 Once the electrical devices have been defined, you can rapidly pass to the step 2 by executing

the “next” command.

The switchboard configuration wizard 2/3 window allows you to define the switchboard main

characteristic.

This way it is possible to define the main data of the electrical switchboard while drawing:

Switchboard attributes (segregation compartment of form, IP protection degree,

Installation position, definition of a rated short-time short-circuit withstand current Icw,

rated short-circuit peak current Ipk).

Suggested column (definition of series and column dimension)

Window 2/3- Wizard procedure

The “Datasheet” button allows you to display the declaration of conformity of selected column.

Datasheet in Wizard procedure window 2/3

Page 84: ABB DOC User Manual

Page 84 of 170

The “Change” button allows you to display the available columns for the suggested enclosure

series. Possibility to choose a column with cable container or a reduced frame.

Change column in Wizard procedure 2/3

Wizard - Step 3/3 In the third and final step of the Wizard procedure, the software shows the dialog window for

fast definition of preferred installation method.

During the last step of Wizard it is possible to define:

Preferred device installation method

Moulded case Kit and DIN rail Kit options

Blind panel options

Reserve definition

Window 3/3- Wizard procedure

Page 85: ABB DOC User Manual

DOC – User Manual - Page 85

The “Switchboard accessories” button allows you to define the accessories that complete the

switchboard configuration: Dividers, Support for terminal boxes, Reinforced lifting, etc.

Switchboard accessories in Wizard procedure 3/3

The “Filling-In Criteria” button allows you to define the filling sorting of electrical device.

Filling-In criteria in Wizard procedure3/3

The “Reserve positioning” allows you to define positioning of reserves for horizontal busbar

distribution system and also for global reserve.

Reserve positioning in Wizard procedure 3/3

The “Select Stamp” allows you to select the layout selection. Switchboard – A3 layout is set

default and it‟s recommended and for production of front panel view.

Page 86: ABB DOC User Manual

Page 86 of 170

Changing the Layout during configuration

During configuration of a switchboard it may be necessary to change the layout in relation to

the one selected previously.

This is possible by using the “Change layout – page dimension” command in the “View”

menu. The “Change Layout – page dimension” icon is available the “View” toolbar.

Wizard result Once the electrical devices (Step 1/3), the switchboard attributes (Step 2/3) and the preferred

installation method (Step 3/3), have been selected, is possible to launch the automatic

drawing of front panel by using the “Finish” command.

The wizard draw a

The Wizard will see to drawing the front panel view considering all the variables we

specified. Such as, reserved, method and criteria, for sorting devices.

The Wizard draws the switchboard taking into account every single attributes and options we

specified.

Wizard final result

Browsing through the Project Page

When the Front panel views consist of several pages, it is possible to browse through these

using the “Next Page” and “Previous Page” commands in the View menu.

The commands can also be carried out using the F12 and F11 function keys or by clicking

over the icons shown on the left.

Page 87: ABB DOC User Manual

DOC – User Manual - Page 87

8.3. Modifying Front Panel View

Once the Wizard steps you can customize the front panel through the “Switchboard tools”

command available.

This chapter describes the most useful commands for modifying the switchboard

configuration drawn.

All the commands are available in the “Switchboard” menu.

Graphics commands

All graphics commands available in switchboard configurator are based on CAD graphics

engine.

In the most cases, to launch a command you can proceed according to the indications given

below:

Once the command has been selected, select the object.

For example, to execute “erase” command: first of all launch “erase” command and than

select the object you want to delete, confirm the command with right mouse clicking or press

Enter on keyboard.

Page 88: ABB DOC User Manual

Page 88 of 170

8.3.1. Modifying switchboard dimensions

Once the Wizard procedure has finished, is possible to modify height, width and depth of

switchboard by clicking over the icons show on the left.

1) Disable any active command by pressing “Esc” Key.

2) Select “Modify Switchboard Depth” icon from the “switchboard toolbar”.

3) Click over the top of the switchboard to select.

The program shows the dialog window for definition of new depth.

Dialog window to modify switchboard depth

For modifying the height and width of switchboard, repeat the same procedure described

above, respectively using the “Modify Switchboard Height” and “Modify Switchboard

Width” icons.

8.3.2. Inserting New Column

The “Insert Column” command allows you to insert a new column in a configured

switchboard.

1) Disable any active command by pressing “Esc” Key.

2) Select “Insert column” icon from the “switchboard toolbar”.

3) In the dialog window select the column width and coverings.

4) The column will be hooked up to the mouse pointer, ready to be drawn with a click of the left

button in the available position.

The available positions are identified thank to the “X” sign appear.

5) Repeat the procedure for each inserting of column.

Page 89: ABB DOC User Manual

DOC – User Manual - Page 89

8.3.3. Inserting new KIT

The “Insert KIT” command allows you to insert in a column an installation kits, blind panels

end back plates.

1) Disable any active command by pressing “Esc” Key.

2) Select “Insert Kit” icon from the “switchboard toolbar”.

3) Select, by mouse left clicking, the destination column of a new Kit.

4) In the dialog window select one of available kits.

5) The new Kit will be hooked up to the mouse pointer, ready to be drawn with a click of the

left button in the available position.

The available positions are identified thank to the “X” sign appear.

6) Repeat the procedure for each inserting Kits.

8.3.4. Inserting new devices

The “device manager” command allows you to manage switchboard devices and insert new

ones. Procedure given below about how to insert a measurement device in a switchboard.

1) Disable any active command by pressing “Esc” Key.

2) Select “Device manger” icon from the “switchboard toolbar”.

The program shows the “Device manager” windows.

Dialog manager windows

3) Select “Select device” command and subsequetenly “Front panel products” to insert a

measurement device in a switchboard.

4) Select the product, adjust the quantity with “Add” button and confirm the selection by “OK”.

In this example we select three direct amperometer and one direct voltmeter with Dim.

96X96mm.

Page 90: ABB DOC User Manual

Page 90 of 170

5) The measurement devices are shown on the “Device manager” window.

Device manager window

6) Select the measurement devices you want to insert in the front panel view and launch the

“Insert” command.

7) The measurement device will be hooked up to the mouse pointer, ready to be drawn with a

click of the left button in the available position.

The available positions are identified thank to the “X” sign appear.

Front panel view with measurement devices

Page 91: ABB DOC User Manual

DOC – User Manual - Page 91

8.3.5. Moving KIT

The “Move Kit” command allows you to move a kit into the configured switchboard.

1) Disable any active command by pressing “Esc” Key.

2) Select “Move Kit” icon from the “switchboard toolbar”.

3) Click over the Kit to select.

4) Select the destination column by left mouse clicking; The Kit will be hooked up to the mouse

pointer, ready to be move with a click of the left button in the available position.

The available positions are identified thank to the “X” sign appear.

5) Repeat the procedure for each Kits.

8.3.6. Moving devices

The “Move Device” command allows you to move one or more devices into the configured

switchboard.

1) Disable any active command by pressing “Esc” Key.

2) Select “Move Device” icon from the “switchboard toolbar”.

3) Select the device by left mouse clicking. In Case of miniature circuit-breakers, a multiple

selection can be created by clicking over each single object you want to add to the selection

list.

Front panel view with miniature circuit-breakers selected

4) Once the miniature circuit-breakers have been defined, you can confirm with right mouse

clicking or press Enter on keyboard.

5) Select the destination kit by left mouse clicking; The devices will be hooked up to the mouse

pointer, ready to be move with a click of the left button in the available position.

The available positions are identified thank to the “X” sign appear.

Page 92: ABB DOC User Manual

Page 92 of 170

Front panel view with available position for miniature circuit- breakers

8.4. Busbar distribution system

Once configured the switchboard by Wizard procedure, DOC allows you to draw a busbar

distribution system into the distribution switchgear.

Busbar distribution system

During drawing Busbar distribution system, the program run the compatibility check, and

shows the only eligible Busbar taking into account the family, the size of the column and the

kit installed on it.

8.4.1. Inserting busbar distribution system.

The “Vertical Busbar system” command allows you to insert and draw a Busbar system into

a switchgear.

1) Disable any active command by pressing “Esc” Key.

2) Select “vertical busbar system” icon from the “switchboard toolbar”.

3) Select the switchboard by left mouse clicking. The Busbar will be showed the only eligible

Busbar taking into account the switchboard configuration.

Page 93: ABB DOC User Manual

DOC – User Manual - Page 93

Vertical Busbar system.

4) Once selected the Busbar position you can pass to the definition of its length.

The first click on the Busbar defines its starting point; the second click the end point, the

pointer will show the length of the Busbar that you are going to draw into the switchboard.

Vertical Busbar system: definition of its length.

Page 94: ABB DOC User Manual

Page 94 of 170

5) The program shows the dialog window “Busbar configuration manager” for definition of

characteristic of Busbar and Busbar holder.

Busbar configuration manager window.

Busbar calculation

Is possible set the Busbar calculation selecting the “Reuses leftover”.

Thanks to this option the program will configure the Busbar distribution system taking into

account of the Busbar leftover.

6) Once the main data of the Busbar has been defined the program will draw the vertical Busbar

into the switchboard.

Vertical Busbar system

For the design of horizontal Busbar systems and earth Busbar system, follow the same

procedure just described going to select icons respectively "Horizontal Busbar System" and

"Earth Busbar system”.

Page 95: ABB DOC User Manual

DOC – User Manual - Page 95

8.4.2. Modifying Busbar system dimension.

The “resize” command allows you to modify the Busbar length into the switchboard.

The procedure to resizing the Busbar follows the same procedure given above in the point 4)

of “Inserting busbar distribution system”.

Show/Hide Busbar system.

The “Show/Hide Busbar” allow you to show or hide the Busbar distribution system into the

front view of switchboard

8.4.3. Layer view.

During the switchboard configuration, could be necessary view the different layer of the front

panel.

This is possible thanks to the commands:

“Door layer”: allows to view the distribution switchgear including the view of the glass or

blind doors.

“Panel Layer”: allows to view the distribution switchgear from the panel layer.

“Plate layer”: allows to view the distribution switchgear from the plate layer.

1) Disable any active command by pressing “Esc” Key.

2) Select “Door layer” icon from the “switchboard toolbar”.

3) Click over the top of the switchboard to select.

The program will show the front panel view including the glass or blind doors.

The same procedure is for view Panel layer or Plate layer.

Door layer

Panel layer plate layer

Page 96: ABB DOC User Manual

Page 96 of 170

8.4.4. Overtemperature calculation

The “Overtemparature” command allows you to run the thermal calculation module.

The Overtemperature rise assessment module allows verification of the thermal behavior of

ABB boards and – if desired – to dimension the fans and air-conditioning units to be installed

in the board. It can also be used on sets of boards obtained by installing several units side by

side.

OTC Module Manual.

This Chapter only contains basic indications about using the OTC module.

For a detailed explanation on the functionalities of the application, please consult the “OTC

Help Manual” user guide in the DOC “Help” menu.

Page 97: ABB DOC User Manual

DOC – User Manual - Page 97

9. Printing the Documentation

This chapter describes:

creating the documentation;

the diagram and documentation printing functions;

the diagram and project data exportation functions.

After reading this chapter, the user will be able to:

use the “Project Documentation Manager”;

create the documentation relative to the single-line diagram;

fill in the layouts to personalize printing;

export the documentation in .xls format

export the diagram and documentation in .pdf. format

Page 98: ABB DOC User Manual

Page 98 of 170

Configuring the Printer

Before printing it is necessary to configure your own predefined printer. Use the “Set

printer…” command in the “File” menu.

9.1. Project Documentation Manager

Once the drawing, calculation and verification stages of the plant are completed, you can

proceed to print the project documentation.

The printing functions are available inside the “Project Documentation Manager” in the

“Work flow” toolbar.

With DOC, the project is not only made up of the single-line diagram, but also of other

sections which can be included and then printed as you like.

The Sections available are:

Header (Cf. Chapter 9.2.1 “Header”);

Calculation and Dimensioning Criteria (Cf. Chapter 9.2.2 “Calculation and

Dimensioning Criteria”);

Short-circuit calculation hypothesis (Cf. Chapter 9.2.3 “Short-circuit Calculation

Hypotheses”);

Single-line diagram;

Table of LV cables (Cf. Chapter 9.2.4 “Table of LV cables”);

List of MV products (Cf. Chapter 9.2.5 “List of MV devices” and “List of LV

devices”);

List of LV products (Cf. Chapter 9.2.5 “List of MV devices” and “List of LV devices”);

Report of MV circuit-breakers-trip units (Cf. Chapter 9.2.6 “Report of MV Circuit-

breakers and Trip units”);

Report of LV circuit-breakers (Cf. Chapter 9.2.7 “Report of LV Circuit-breakers”);

Short-circuit calculations (Cf. Chapter 9.2.8 “Short-circuit calculations”);

Report of protections (Cf. Chapter 9.2.9 “Report of protections”).

To add a Section to the project, simply click over the ticking off box on the left of each

Section.

One or more pages will be generated, whose preview will be visible immediately in the

central part of the “Project Documentation Manager”.

Page 99: ABB DOC User Manual

DOC – User Manual - Page 99

Project Documentation Manager; the list of the Sections available is visible on the left with

the relative ticking off box to include / exclude them from the documentation

9.2. Creating the Project Documentation

It is possible to add and remove sections from the project document using the Project

Navigator: select a specific section to add it to the document, and select it a second time to

remove it.

The sections added to the project document will be:

Displayed in the print Preview;

Added to the project file with the pages of the single-line diagram.

The program proposes three heading sections for the project and seven technical sections for

printing all the accumulated codes, calculations and verifications.

Section: “Single-line Diagram”

The “Single-line diagram” section is the only one which cannot be removed from the project

because it is the essence of the project itself.

It is, in any case, possible not to print it (Cf. Chapter 9.3.).

Page 100: ABB DOC User Manual

Page 100 of 170

9.2.1. “Header” Section

This is the first page of the project documentation and contains the user, customer and project

data.

To fill in the data, see chapter 9.4.

Heading

Page 101: ABB DOC User Manual

DOC – User Manual - Page 101

9.2.2. “Calculation and Dimensioning Criteria” Section

This describes the Standards and the main parameters used for the calculations and

verifications.

Printed together with the “Cable Verification” Section, it allows the positive outcome of the

verifications to be justified.

Calculation and Dimensioning Criteria

Page 102: ABB DOC User Manual

Page 102 of 170

9.2.3. “Short-circuit Calculation Hypotheses” Section

The short-circuit calculation hypotheses section takes up the general conditions and the

calculation hypotheses for the maximum and minimum short-circuit currents from the CEI

11-25 Standard (CEI EN 60909).

Short-circuit calculation hypotheses

Page 103: ABB DOC User Manual

DOC – User Manual - Page 103

9.2.4. “Table of LV cables” Section

This presents the main data of the cables present in the single-line diagram in a single table:

Sections;

Insulating material;

Conductor material;

Number of installations as defined in the selected Standard;

Carrying capacity;

Working temperature;

Dissipated power;

Voltage drop percentage;

Resistances and reactances.

Table of LV cables

Page 104: ABB DOC User Manual

Page 104 of 170

9.2.5. “List of MV devices” and “List of LV devices” Sections

The two Sections present the lists of MV and LV products present in the single-line diagram,

complete with ordering codes and description.

List of LV devices

Page 105: ABB DOC User Manual

DOC – User Manual - Page 105

9.2.6. “Report of MV Circuit-breakers and Trip units” Section

This presents the list of the “MV Circuit-breakers”, MV trip units with relative CT and HCT

and shows the setting of each individual trip unit grouped together by function.

Report of MV circuit-breakers and trip units

Page 106: ABB DOC User Manual

Page 106 of 170

9.2.7. “Report of LV Circuit-breakers” Section

This presents the list of “LV circuit-breakers” and the settings of the relative trip units

grouped together by function.

Report of LV circuit-breakers

Page 107: ABB DOC User Manual

DOC – User Manual - Page 107

9.2.8. “Short-circuit calculations” Section

The short-circuit and peak currents for three-phase, two-phase, phase-neutral and phase-PE

faults are indicated, for every Switchboard present in the single-line diagram,.

Short-circuit calculations

Printing a short-circuit result in any point of the diagram

Using the Professional Profile, it is possible to print the results of the short-circuit

calculations in any point of the diagram.

It is necessary to add a “Busbar” Single Object at the point where you want to verify the

short-circuit value: DOC interprets the “Busbar” Single Object as a new Switchboard which

will be added to the list of Switchboards in the “Short-circuit calculations” Section.

Page 108: ABB DOC User Manual

Page 108 of 170

9.2.9. “Report of protections” Section

This shows the state of the verifications of the protection relations for every “LV cable”

drawn in the single-line diagram.

The verification table consists of:

User data

Cable data

Protection device data (circuit-breaker or fuse)

State of the verification of protection against SC, CC, CI-TN, CI-TT

The state of the verifications can be:

“OK” if the verification is positive

“-“ in the case of failed or not assigned verification

Verification Table

The “OK”s are not shown

When DOC does not show the “OK”s in the table, it is necessary to verify the protection of

the cables by accessing the curves module at least once (Cf. Chapter 6).

Page 109: ABB DOC User Manual

DOC – User Manual - Page 109

9.3. Print Preview

The central part of the “Project Documentation Manager” shows the print Preview of all the

pages created, both of the single-line diagram and of the project document sections.

It is possible to create selection groups consisting of one or more pages in the print Preview

area.

The “Project Documentation Manager” commands, described in the following chapter, will

only have effect on the selected Pages.

Advice about Selection of Pages

Apart from the “Select all” and “Deselect all” commands, which allow all the Pages of the

project to be selected and deselected, it is possible to use the SHIFT and CTRL keys to select

several Pages, even those not adjacent to each other.

By keeping CTRL pressed and clicking over a Page, the latter will be added to the list of

Pages selected. If the page has already been selected, it will be deselected.

It is possible to add several pages to the selection using the SHIFT key:

Click over the first page you want to select;

Keep SHIFT pressed.

Click over the last page you want to select.

Page selected, with blue background – Page deselected, with white background

Page 110: ABB DOC User Manual

Page 110 of 170

9.4. Commands for Managing the Project Documentation

The Commands for managing the project documentation contain the modify, print and export

functionalities.

List and description of the commands

Renumber pages: Changes the single-line diagram page numbering.

Selection of the layout: like the “Change layout – page dimensions” command in the

“View” menu, this changes the layout of the Pages selected in the print preview.

Compile layout: allows the layout of each Page and the “Heading” Section to be

compiled. Having launched the command, simply double click in the “Present Value”

column and type the data in.

The command has effect on the selected Pages: it is therefore possible to select all the

Pages and compile them all at once.

Window for the compiling the layout

Insert empty page: Adds a page to the single-line diagram, in exactly the same way as

the “Add page” command in the “View” menu.

Delete current page: Removes all the selected pages of the single-line diagram. It is

therefore advisable to use this command extremely carefully. In the case where pages

are removed by mistake, abandon the “Project Navigator” by clicking over the

“Cancel” button: the cancelled pages will be restored.

Move Up – Move Down: Allow the selected pages to be moved up or down, in order.

Print selection: Allows the selected Pages to be printed with the predefined printer.

Create .pdf document: Generates a pdf file of the Pages selected. Works like a .pdf

virtual printer.

Export report in .xls: Exports the Sections into an .xls file. The file created will have as

many work sheets as there are Sections.

Page 111: ABB DOC User Manual

DOC – User Manual - Page 111

Example of exportation in .xls format

Page 112: ABB DOC User Manual

Page 112 of 170

ANNEX A: List of Commands

The following Annex includes the list and description of all the commands available in the DOC Menu and Tools

Toolbars.

Page 113: ABB DOC User Manual

DOC – User Manual - Page 113

Commands and Tools Toolbars

If the commands can be executed by means of the icon inserted in the Tools Toolbars, the

icon itself is given at the side of the description of the command.

File Menu

The “File” menu contains the commands for managing files and for printing.

New

Creates a new project.

Before creation of a new project, the program will ask you to save any modifications to the

present project. All new projects do not have an associated file. To associate a file to a

project, use the Save option of the File menu.

Open…

Opens a file saved previously.

Before opening an old file, the program will ask you to save any modifications to the present

file. The DOC project files have “*.ILE” extension.

Save

Saves the present project.

If the project does not have an associated file, the program will ask you for the name and

path for saving the file. The DOC files have *.ILE extension.

Save with name…

Saves this project with a file name and/or path different from the current one.

Export… \ Exports to ABB software

Save all the accumulated codes dimensioned by DOC in a file importable from CAT.

The file has *.DEF extension.

Export… \ Exports DWG-DXF

Exports the drawing in CAD *.DWG or *.DXF format.

Export macro

Exports the Single Objects selected in a single Macro Object. The Macro Object is saved in a

*.blk file.

Import macro

Imports a Macro Object previously saved in a *.blk file.

Set default properties

Definition of the program default characteristics. The settings, for Single Object or for

functionalities, allow you to customize the program calculations and results.

Printer Setup…

Configuration of the printer used and of the most common printing options.

Print

Launches the Project Navigator (described in chapter Error! Reference source not found.).

Exit

Closes the program.

It will be necessary to save the project, if this has not been saved previously or if it has been

modified since the last save.

Page 114: ABB DOC User Manual

Page 114 of 170

Edit Menu

The “Edit” menu contains the commands for interaction with the Single Objects present in

the single-line diagram.

Undo

Cancels the last command carried out.

Redo

Redoes the last command undone.

Cut

Cuts and Deletes the Single Objects selected and makes them available for the Paste

command.

Copy

Copies the Single Objects selected and makes them available for the Paste command.

Paste

Pastes the Single Objects previously Cut or Copied into the diagram. It is not available (of a

different color to the other commands) if no Single Object has previously been Cut or

Copied.

Duplicate

Allows copy-paste with a single command.

Move

Moves the Single Objects selected.

Rotate

Rotates the Single Objects selected by 90°.

Stretch

Modifies the length of Connections and Busbars.

Erase

Erases the Single Objects selected from the diagram. In the case of any errors, use the Undo

command.

Lock Objects

Locks the Single Objects selected, which will not be modified in the subsequent calculations

but only be verified.

Unlock Objects

Unlocks the Single Objects locked previously. An unlocked Single Object is redefined by the

program during the calculation stage.

Renumbering

Modifies the current numbering of the codes of the Single Objects. The new numbering will

be progressive in the following order: from left to right, from top to bottom, from the first to

the last page.

It only works for the Single Objects drawn in the “free” A3, A2, A1, A0 layouts. The

numbering in the layouts in columns follows different criteria.

Edit object labels

Modifies the label contents and formatting.

Move object labels

Moves the labels displayed in the single-line diagram.

Page 115: ABB DOC User Manual

DOC – User Manual - Page 115

Label management

Defines which labels are displayed.

Properties

Carried out on a Single Object, it opens its window with the relative properties.

Carried out on several Single Objects, it opens its window for managing multiple properties.

Objects Menu

The “Objects” menu contains the low voltage Single Objects and the Single Objects for

connections and page links.

This menu is only available in the DOC Professional profile.

UPS

Draws the “UPS” Single Object.

Generator

Draws the “Generator” Single Object.

Transformer

Draws the “Transformer with 2 windings” Single Object.

Transformer with 3-windings

Draws the “Transformer with 3 windings” Single Object.

Cable

Draws the “LV cable” Single Object.

Busway

Draws the “Busway” Single Object.

Impedance

Draws the “Generic impedance” Single Object.

Busbar

Draws the “Busbar” Single Object.

Multimeter

Draws the “Multimeter” Single Object.

CB with Overload and Short Circuit protection

Draws the “LV circuit-breaker” Single Object equipped with trip unit for protection against

overload and short-circuit.

CB with Overload and Short Circuit protection + RCB

Draws the “LV circuit-breaker” Single Object equipped with trip unit for protection against

overload, short-circuit and Residual Current Block.

CB with only Short Circuit protection

Draws the “LV circuit-breaker” Single Object equipped with trip unit only for protection

against short-circuit.

CB with only Short Circuit protection + RCB

Draws the “LV circuit-breaker” Single Object equipped with trip unit only for protection

against short-circuit and Residual Current Block.

Page 116: ABB DOC User Manual

Page 116 of 170

Residual current CB

Draws the “Residual current circuit-breaker” Single Object.

Fuse

Draws the “LV Fuse” Single Object.

Switch-fuse

Draws the “LV Switch-fuse” Single Object.

Disconnector

Draws the “LV Disconnector” Single Object.

Contactor

Draws the “LV Contactor” Single Object.

Overload Relay

Draws the “Thermal trip unit” Single Object.

Thermomagnetic Manual motor starter

Draws the “Manual motor starter” Single Object with trip unit for protection against

overload and short-circuit.

Magnetic only Manual motor starter

Draws the “Manual motor starter” Single Object with trip unit only for protection against

short-circuit.

Generic load

Draws the “Generic load” Single Object.

Motor

Draws the “Motor” Single Object.

Lighting load

Draws the “Lighting load” Single Object.

Capacitor bank

Draws the “Capacitor bank” Single Object.

Connection

Draws the “Connection” Single Object.

Dashed connection

Draws the “Dashed connection” Single Object.

Vertical Departure line link

Draws the “Vertical Departure line link” Single Object.

Vertical Arrival line link

Draws the “Vertical Arrival line link” Single Object.

Horizontal Departure line link

Draws the “Horizontal Departure line link” Single Object.

Horizontal Arrival line link

Draws the “Vertical Departure line link” Single Object.

Page 117: ABB DOC User Manual

DOC – User Manual - Page 117

MV Objects Menu

The MV Objects menu contains the Medium voltage Single Objects.

This menu is only available in the DOC Professional profile and only if the power supply

selection is the “MV Supply” type.

MV Cable

Draws the “MV Cable” Single Object.

MV circuit-breaker

Draws the “MV circuit-breaker” Single Object.

MV Disconnector

Draws the “MV Disconnector” Single Object.

MV Earth switch

Draws the “MV Earth switch” Single Object.

MV Disconnector+ fuse

Draws the “MV Disconnector” and “MV fuse” Single Objects.

MV Switch Disconnector

Draws the “MV Switch Disconnector” Single Object.

MV Switch Disconnector + Fuse

Draws the “MV Switch Disconnector” and “MV Fuse” Single Objects.

CT

Draws the purely Graphic “CT” Object.

HCT

Draws the purely Graphic “HCT” Object.

VT

Draws the purely Graphic “VT” Object.

Combisensor

Draws the purely Graphic “Combisensor” Object.

Resistive or Capacitive divider

Draws the purely Graphic “Voltage divider” Object.

Rogowski Coil

Draws the purely Graphic “Rogowski Coil” Object.

MV generic Load

Draws the “Generic load” Single Object predefined with a specific symbol for Medium

voltage.

Page 118: ABB DOC User Manual

Page 118 of 170

Tools Menu

The “Tools” menu contains the commands for managing the main functionalities of DOC in

terms of calculation, drawing curves and verification of switchboard overtemperatures.

Furthermore, it contains management of free texts added to the single-line diagram and the

Advanced Options.

Text

Adds a free text, defined by the user, not bound to any Single Object and which can be

positioned as desired in the single-line diagram.

Text management also includes the height and the style of the text itself.

Window for the inserting text into the single-line diagram

Page 119: ABB DOC User Manual

DOC – User Manual - Page 119

Text Style

Command for managing the text styles, the list and functions for creating/removing a text

style.

A text style contains the main information on the character used in writing the free text.

To define a text style, type in the name and click over “New”.

To use a text style, select the name of the style desired and select the “Present” option.

General plant properties

Opens the general plant properties window, described in chapter 3.2.

Calculate

Launches the calculations, as described in chapter 5.

Network configurations

Opens the window for defining the network configurations.

Curves

Displays the curves module, whose description is in chapter 6.

Page 120: ABB DOC User Manual

Page 120 of 170

Switchboards

Opens the window containing the definition of the switchboards in the single-line diagram,

with the option for calculation of the switchboard overtemperatures and the possibility of

adding a switchboard “Label” to the single-line diagram.

The switchboard numbering is given by the program in a progressive way and can be

customized by typing a new name for the switchboard in the Properties.

The “Calculate>>” button opens OTC, the program for calculating switchboard

overtemperatures, whose guide is available in the “Help” menu.

Window for managing the switchboards

Coordination Tables

Opens the latest version of the coordination tables in .pdf format.

Page 121: ABB DOC User Manual

DOC – User Manual - Page 121

Options…

Definition of the advanced customization options. The Options… are divided into the

following pages:

Circuit-breakers

Management of temperature derating of circuit-breakers and product filters.

Preferences: Circuit-breaker page

Cables

Modifies the resistance and reactance data of the individual cable and filter to the list of

sections used during calculation.

Preferences: Cable page

Page 122: ABB DOC User Manual

Page 122 of 170

Calculation options

Allows the window to be enabled/disabled to define the calculation options before

dimensioning, and contains management of the other advanced options for

dimensioning.

Preferences: Cable page

Colors

See chapter Colors

Others

Advanced Options for drawing. This allows selection of the DOC Light - DOC

Professional profile and the panel for fast definition of the feeder to be enabled

/disabled.

Preferences: Others page

Page 123: ABB DOC User Manual

DOC – User Manual - Page 123

View Menu

The “View” menu contains the options for drawing management and display.

Add page

Adds a page to the single-line diagram.

Delete page

Removes the present page from the single-line diagram. To cancel removal of a page, use the

“Cancel” command in the “Edit” menu.

Change layout – page dimensions

Modifies the layout and consequently the dimensions of the page for the current page only.

To modify several pages, enter the Project Navigator.

Previous page

Displays the previous page.

Next page

Displays the next page.

Insert Logo/Picture

Adds a logo from a graphic file in .jpg or .bmp format to all the pages of the single-line

diagram.

Toolbars

Enables/disables a specific toolbar.

Zoom

Displays the part of a drawing contained in the selection window.

Zoom in

Zooms in towards the central point of the drawing.

Zoom out

Zooms out in the central point of the drawing.

Zoom Previous

Restores the previous Zoom level

Zoom All

Zoom which allows all the Single Objects present on the current page to be displayed.

Pan

Drags the diagram to only display the desired part.

Regen

Cleans the screen of the “traces” left when passing from one page to another.

Page 124: ABB DOC User Manual

Page 124 of 170

Help Menu

The “Help” menu includes the guide for using the program and its warnings.

User guide …

Contains the guide to using DOC, Curves and OTC.

Technical guide …

Contains the versions in pdf format of the ABB Technical Application Notebooks of: “QT1 -

Low voltage discrimination with ABB circuit-breakers”; “QT2 - MV/LV Substations: theory

and examples of short-circuit calculation” and “QT3 - Distribution systems and protection

against indirect contacts and ground faults”, the”Electrical Installation Handbook” and the

specifications of the Unimix Medium Voltage switchboards for secondary distribution.

Warnings

Shows the warnings about using the program, such as in the chapter: 1 Warnings.

UTE Certification

Shows certification of the program for calculation and dimensioning issued by the French

UTE Standards body, relative to the NFC15-500 Standard.

Info

Shows the version of the program, to be communicated if you contact the Assistance service

office.

MV Macros

The Medium voltage Macro Objects are not available in a Menu, but only after having

selected “Medium voltage” in the “Work flow” Toolbar.

Each Medium voltage Macro Object represents a typical unit of the ABB Unimix secondary

distribution switchboard.

P1A dx Unit

Draws the “P1A dx” Macro Object. The “P1A”, “A”, “RAC” units and “Cable riser duct” can

only be installed as first (on the left, or sx) or last (on the right, or dx) column of the

switchboard.

Page 125: ABB DOC User Manual

DOC – User Manual - Page 125

A dx Unit

Draws the “A dx” Macro Object. The “P1A”, “A”, “RAC” units and “Cable riser duct” can

only be installed as first (on the left, or sx) or last (on the right, or dx) column of the

switchboard.

RAC dx Unit

Draws the “RAC dx” Macro Object. The “P1A”, “A”, “RAC” units and “Cable riser duct”

can only be installed as first (on the left, or sx) or last (on the right, or dx) column of the

switchboard.

CL Left lat. cable riser Unit

Draws the “Cable riser duct dx” Macro Object. The “P1A”, “A”, “RAC” units and “Cable

riser duct” can only be installed as first (on the left, or sx) or last (on the right, or dx) column

of the switchboard.

P1A sx Unit

Draws the “P1A sx” Macro Object. The “P1A”, “A”, “RAC” units and “Cable riser duct” can

only be installed as first (on the left, or sx) or last (on the right, or dx) column of the

switchboard.

A sx Unit

Draws the “A sx” Macro Object. The “P1A”, “A”, “RAC” units and “Cable riser duct” can

only be installed as first (on the left, or sx) or last (on the right, or dx) column of the

switchboard.

RAC sx Unit

Draws the “RAC sx” Macro Object. The “P1A”, “A”, “RAC” units and “Cable riser duct” can

only be installed as first (on the left, or sx) or last (on the right, or dx) column of the

switchboard.

CL Right lat. cable riser Unit

Draws the “Cable riser duct sx” Macro Object. The “P1A”, “A”, “RAC” units and “Cable

riser duct” can only be installed as first (on the left, or sx) or last (on the right, or dx) column

of the switchboard.

Page 126: ABB DOC User Manual

Page 126 of 170

P1E bus-tie + riser Unit

Draws the “P1E bus-tie + riser” Macro Object. The “P1E bus-tie”, “P1F bus-tie”, “P2 bus-

tie”, “P3 bus-tie” and “ASR bus-tie” units can only be followed by the “Riser” unit. The

program proposes a Macro Object with both the units, to speed up drawing.

P1F bus-tie + riser Unit

Draws the “P1F bus-tie + riser” Macro Object. The “P1E bus-tie”, “P1F bus-tie”, “P2 bus-

tie”, “P3 bus-tie” and “ASR bus-tie” units can only be followed by the “Riser” unit. The

program proposes a Macro Object with both the units, to speed up drawing.

P2 bus-tie + riser Unit

Draws the “P2 bus-tie + riser” Macro Object. The “P1E bus-tie”, “P1F bus-tie”, “P2 bus-

tie”, “P3 bus-tie” and “ASR bus-tie” units can only be followed by the “Riser” unit. The

program proposes a Macro Object with both the units, to speed up drawing.

P3 bus-tie + riser Unit

Draws the “P3 bus-tie + riser” Macro Object. The “P1E bus-tie”, “P1F bus-tie”, “P2 bus-

tie”, “P3 bus-tie” and “ASR bus-tie” units can only be followed by the “Riser” unit. The

program proposes a Macro Object with both the units, to speed up drawing.

ASR bus-tie + riser Unit

Draws the “ASR bus-tie + riser” Macro Object. The “P1E bus-tie”, “P1F bus-tie”, “P2 bus-

tie”, “P3 bus-tie” and “ASR bus-tie” units can only be followed by the “Riser” unit. The

program proposes a Macro Object with both the units, to speed up drawing.

Page 127: ABB DOC User Manual

DOC – User Manual - Page 127

P1E Unit

Draws the “P1E” Macro Object.

P1F Unit

Draws the “P1F” Macro Object.

P2 Unit

Draws the “P2” Macro Object.

P3 Unit

Draws the “P3” Macro Object.

ASR Unit

Draws the “ASR” Macro Object.

M Measurements Unit

Draws the “Measurements” Macro Object.

Trafo box Unit

Draws the “Trafo box” Macro Object.

Page 128: ABB DOC User Manual

Page 128 of 170

LV Macros

The Low voltage Macro Objects are not available in a Menu, but only after having selected

“Low voltage” in the “Work flow” Toolbar.

The Low voltage Macro Objects have been made to be able to create most types of low

voltage plants.

Further information about drawing with Macro Objects is available in chapter 4.2.

Main CB with Overload and Short circuit protection + RCB

Draws the “Main CB with Overload and Short circuit protection + RCB” Macro Object.

Main CB with Overload and Short circuit protection

Draws the “Main CB with Overload and Short circuit protection” Macro Object.

Main fuse

Draws the “Main fuse” Macro Object.

Main switch-fuse

Draws the “Main switch-fuse” Macro Object.

Main disconnector

Draws the “Main disconnector” Macro Object.

Line without main device

Draws the “Line without main device” Macro Object.

Line with arrival link

Draws the “Line with arrival link” Macro Object.

Departure line link

Draws the “Departure line link” Macro Object.

Arrival line link

Draws the “Arrival line link” Macro Object.

Page 129: ABB DOC User Manual

DOC – User Manual - Page 129

Main second level, CB with Overload and Short circuit protection + RCB

Draws the “Main second level, CB with Overload and Short circuit protection + RCB”

Macro Object.

Main second level, CB with Overload and Short circuit protection

Draws the “Main second level, CB with Overload and Short circuit protection” Macro

Object.

Main second level, Residual current CB

Draws the “Main second level, Residual current CB” Macro Object.

Main second level, Fuse

Draws the “Main second level, Fuse” Macro Object.

Main second level, Switch-Fuse

Draws the “Main second level, Switch-Fuse” Macro Object.

Main second level, Disconnector

Draws the “Main second level, Disconnector” Macro Object.

Feeder line to sub board, CB with Overload and Short circuit protection + RCB

Draws the “Feeder line to sub board, CB with Overload and Short circuit protection + RCB”

Macro Object.

Feeder line to sub board, CB with Overload and Short circuit protection

Draws the “Feeder line to sub board, CB with Overload and Short circuit protection” Macro

Object.

Feeder line to sub board, Switch-Fuse

Draws the “Feeder line to sub board, Switch-Fuse” Macro Object.

Feeder line to sub board, Fuse

Draws the “Feeder line to sub board, Fuse” Macro Object.

Generic Load feeder, CB with Overload and Short circuit protection + RCB

Draws the “Generic Load feeder, CB with Overload and Short circuit protection + RCB”

Macro Object.

Generic Load feeder, CB with Overload and Short circuit protection

Draws the “Generic Load feeder, CB with Overload and Short circuit protection” Macro

Object.

Page 130: ABB DOC User Manual

Page 130 of 170

Generic Load feeder, Switch-Fuse

Draws the “Generic Load feeder, Switch-Fuse” Macro Object.

Generic Load feeder, Switch-Fuse + Residual current CB

Draws the “Generic Load feeder, Switch-Fuse + Residual current CB” Macro Object.

Generic Load feeder, Fuse

Draws the “Generic Load feeder, Fuse” Macro Object.

Generic Load feeder, Fuse + Residual current CB

Draws the “Generic Load feeder, Fuse + Residual current CB” Macro Object.

Capacitor bank feeder, Circuit-breaker with Overload and Short circuit protection

Draws the “Capacitor bank feeder, Circuit-breaker with Overload and Short circuit

protection” Macro Object.

Circuit-breaker with Overload and Short circuit protection and Capacitor bank

Draws the “Circuit-breaker with Overload and Short circuit protection and Capacitor bank”

Macro Object.

Motor feeder DOL, Magnetic only Manual motor starter and overload relay

Draws the “Motor feeder DOL, Magnetic only Manual motor starter and overload relay”

Macro Object.

Motor feeder DOL, Thermomagnetic Manual motor starter

Draws the “Motor feeder DOL, Thermomagnetic Manual motor starter” Macro Object.

Motor feeder DOL, Switch-Fuse and overload relay

Draws the “Motor feeder DOL, Switch-Fuse and overload relay” Macro Object.

Motor feeder DOL, Magnetic Only Molded case CB and overload relay

Draws the “Motor feeder DOL, Magnetic Only Molded case CB and overload relay” Macro

Object.

Motor feeder DOL, Molded case Circuit-breaker with MP release

Draws the “Motor feeder DOL, Molded case Circuit-breaker with MP release” Macro

Object.

Motor feeder Star-Delta, Magnetic only Manual motor starter and overload relay

Draws the “Motor feeder Star-Delta, Magnetic only Manual motor starter and overload

relay” Macro Object.

Page 131: ABB DOC User Manual

DOC – User Manual - Page 131

Motor feeder Star-Delta, Thermomagnetic Manual motor starter

Draws the “Motor feeder Star-Delta, Thermomagnetic Manual motor starter” Macro Object.

Motor feeder Star-Delta, Switch-Fuse and overload relay

Draws the “Motor feeder Star-Delta, Switch-Fuse and overload relay” Macro Object.

Motor feeder Star-Delta, Magnetic Only Molded case CB and overload relay

Draws the “Motor feeder Star-Delta, Magnetic Only Molded case CB and overload relay”

Macro Object.

Motor feeder Star-Delta, Molded case Circuit-breaker with MP release

Draws the “Motor feeder Star-Delta, Molded case Circuit-breaker with MP release” Macro

Object.

Page 132: ABB DOC User Manual

Page 132 of 170

Auxiliaries Macro

The Auxiliaries Macro Objects are not available in a Menu, but only after having selected

“Auxiliaries” in the “Work flow” Toolbar.

Line

Draws the “Line” object.

NO contact

Draws the “NO contact” object.

NC contact

Draws the “NC contact” object.

Changeover contact

Draws the “Changeover contact” object.

Changeover contact without interruption

Draws the “Changeover contact without interruption” object.

Changeover contact with 3 positions

Draws the “Changeover contact with 3 positions” object.

Coil

Draws the “Coil” object.

Contactor coil

Draws the “Contactor coil” object.

Emergency stop

Draws the “Emergency stop” object.

Pushbutton with automatic return

Draws the “Pushbutton with automatic return” object.

Tie-rod with automatic return

Draws the “Tie-rod with automatic return” object.

Closing pushbutton with positive operation

Draws the “Closing pushbutton with positive operation” object.

Manual operating mechanism with locking device

Draws the “Manual operating mechanism with locking device” object.

Manual operating mechanism

Draws the “Manual operating mechanism” object.

Rotary operating mechanism without automatic return

Draws the “Rotary operating mechanism without automatic return” object.

Page 133: ABB DOC User Manual

DOC – User Manual - Page 133

Switchboard Toolbar Menu

The Switchboard toolbar Objects are not available in a Menu, but only after having selected

“Switchboard Configuration” in the “Work flow” Toolbar.

Wizard

Run the automatic procedure to configure a switchboard.

Insert column

Draw the “Column” object.

Insert Kit

Draw the “Kit” object.

Device manager

Open the device manager windows.

Move Kit

Move the object “Kit”.

Move device

Move the “Device” object.

Move column

Move the “Column” object.

Modifiy switchboard height

Modify the height of column.

Modifiy switchboard width

Modify the width of column.

Modifiy switchboard depth

Modify the depth of column.

Show/Hide labels

Show/Hide the object label.

Page 134: ABB DOC User Manual

Page 134 of 170

Complete with blind panels

Draw the “blind panels” object.

Switchboard accessories

Add a switchboard accessories in the switchboard quotation.

Vertical busbar system

Draw the “Vertical busbar system” object.

Horizontal busbar System

Draw the “Vertical busbar system” object.

Earth Busbar System

Draw the “Horizontal busbar system” object.

Resize

Resize the “busbar system” object.

Overtemperature

Run the OTC module. The program for calculating switchboard overtemperatures, whose

guide is available in the “Help” menu.

Door layer

Show the switchboard door layer.

Panel layer

Show the switchboard panel layer

Plate layer

Show the switchboard plate layer

Show/hide busbar

Show/Hide Busbar system

Add switchboard table

Draw a switchboard table with the technical characteristic

Switchboard graphic copy

Draw a graphic copy of switchboard.

Page 135: ABB DOC User Manual

DOC – User Manual - Page 135

ANNEX B: List and Description of the Single Objects

and of the relative Control Panels

The following Annex includes the list and description of all the Single Objects windows.

Page 136: ABB DOC User Manual

Page 136 of 170

Windows of MV Single Objects

This Annex contains the list and description of the windows of MV Single Objects, only

available with the Professional Profile and only in projects started with an “MV Supply”.

The windows of each Single Object can be displayed in two ways:

With a double click over the Single Object symbol in the single-line diagram.

Using the “Properties” command in the “Edit” menu.

MV circuit-breaker

In the “MV circuit-breaker” control panel it is possible to define:

Description of the User, on two lines.

Circuit-breaker family.

The trip unit which will be associated with the circuit-breaker.

The CT (only among those compatible with the trip unit selected).

The HCT (only among those compatible with the trip unit selected)

Main MV circuit-breaker window

Page 137: ABB DOC User Manual

DOC – User Manual - Page 137

MV Disconnector

In the control panel of the “MV Disconnector” it is possible to define:

Description of the User, on two lines.

The Symbol of the disconnector, upright or turned over

Main MV disconnector window

MV Earth disconnector

In the control panel of the “MV Earth disconnector” it is possible to define:

Description of the User, on two lines.

Main MV grounding switch window

Page 138: ABB DOC User Manual

Page 138 of 170

MV disconnector + Fuse

In the control panel of the “MV Disconnector + fuse” it is possible to define:

Description of the User, on two lines.

Main window of MV disconnector with fuse

MV Switch-Disconnector

In the control panel of the “MV Switch-Disconnector” it is possible to define:

Description of the User, on two lines.

Main MV switch-disconnector window

Page 139: ABB DOC User Manual

DOC – User Manual - Page 139

MV Switch-disconnector + fuse

In the control panel of the “MV Switch-disconnector + fuse” it is possible to define:

Description of the User, on two lines.

Main MV Switch-disconnector + fuse window

Page 140: ABB DOC User Manual

Page 140 of 170

MV cable

In the “MV cable” control panel it is possible to define:

Description of the User, on two lines.

Ambient temperature.

Maximum Cdt% on the branch of cable.

Length.

Type of cable (Single-core – Multi-core).

The maximum service temperature of the insulation (XLPE at 65°C – XPLE at 90°C).

The installation method (Overhead installation and relative details – Installation in the

ground and relative details).

Main MV cable window

The “Advanced Options >>>” button allows the data which can change the carrying

capacity of the cable to be defined as correction factors:

Installation details (adjacent circuits – depth of installation)

Screen data (Type and Section)

Minimum Iz/Ib ratio

Advanced Options for the MV cable

Page 141: ABB DOC User Manual

DOC – User Manual - Page 141

MV Load

In the “MV Load” control panel it is possible to define:

Description of the User, on two lines.

Consumption as a function of Load current and Power factor.

Consumption as a function of active Power consumed and Power factor.

Symbol with which the load will be displayed (a small ball - an arrow - a transformer).

Main MV Load window

Graphic symbols of the MV Load

Page 142: ABB DOC User Manual

Page 142 of 170

Windows of LV Single Objects

This Annex contains the list and description of the windows of LV Single Objects.

The windows of each Single Object can be displayed in two ways:

With a double click over the Single Object symbol in the single-line diagram.

Using the “Properties” command in the “Edit” menu.

UPS

On the “UPS” control panel it is possible to define:

Description.

Apparent rated Power, Rated Power factor of the UPS (from these two data, the program

finds how much active power Pn and reactive power Qn it is able to supply to the

network).

The relation between the short-circuit current and the rated current, with which the

program calculates the contribution to the UPS fault.

Main UPS window

Page 143: ABB DOC User Manual

DOC – User Manual - Page 143

Generator

The “Generator” window allows you to define:

Description of the type of generator (Model).

The type of PV or PQ source.

A “PV” generator will always keep the active Power and reference Voltage at its

terminals constant. Consequently the reactive Power supplied to the network will be a

function of the current required by the network.

A “PQ” generator will always keep the active Power and reactive Power constant.

Consequently the Voltage at the network terminals will be a function of the current

required by the network.

“< Browse database” allows you to search for a generator in the program database.

“>Add to database” allows the generator currently defined to be saved in the program

database. To be able to save a generator its Model must be written.

The following rating plate data:

Rated apparent Power and rated Power factor (from these two data the program will find

how much active power Pn and reactive power Qn it is able to supply to the network).

Loss participation factor: only for PV sources and with several generators in parallel,

this factor decides how much a generator will be loaded.

Armature resistance in [Ω] or in [ms] of the time constant Ta.

The Reactances: Subtransient (direct axis and quadrature), Transient, Synchronous,

Inverse Sequence and Homopolar.

The time constants: Subtransient and Transient.

Main Generator window

Page 144: ABB DOC User Manual

Page 144 of 170

The rating plate data defined in the generator are used in the network and short-circuit

calculations.

Data not defined, or defined incorrectly, can produce results far from realty.

When these data are not known, or availability of data is incomplete, it is advisable to

select the generator with the characteristics most similar to your own generator from

the DOC generator database, and if necessary modify the characteristics provided by

the program using the data in your possession.

Transformer

The window of the “Transformer” allows you to define:

Description of the type of transformer (Model).

“< Browse database” allows you to search for a transformer in the program database.

“>Add to database” allows the transformer currently defined to be saved in the program

database. To be able to save a transformer, its Model must be written.

The levels of voltage: MV/MV, MV/LV, LV/LV (the latter can be three-phase, two-

phase or single-phase).

Rated power.

Short-circuit impedance.

Loss in the copper, defined as a percentage of the rated power or as an absolute value in

[kW] (from which the resistive modulus of the transformer impedance is taken).

For the Primary and Secondary windings:

The type of winding, only for three-phase transformers (Star, Ground Star, Triangle).

The rated voltage of the relative side of the plant.

The no-load voltage, i.e. the voltage that the transformer would supply to the terminals

of the secondary winding if no load was connected.

Definition of the sockets and any set socket.

The number of phases.

The distribution system.

Main window of the Transformer

Page 145: ABB DOC User Manual

DOC – User Manual - Page 145

Transformer with 3 windings

The window of the “Transformer with 3 windings” allows you to define:

Description of the type of transformer (Model).

The levels of voltage: MV/MV, MV/LV, LV/LV (the latter can be three-phase, two-

phase or single-phase).

For the Primary, Secondary and Tertiary windings:

The type of winding, only for three-phase transformers (Star, Star a ground, Triangle).

The rated voltage of the relative side of plant.

The no-load voltage, i.e. the voltage that the transformer would supply to the terminals

of the secondary winding if no load was connected.

The definition of the of the sockets and any set socket.

The number of phases.

The distribution system.

Rated power.

Short-circuit impedance.

Loss in the copper, defined in a percentage of the rated power or as an absolute value in

[kW] (from which the resistive modulus of the transformer impedance is taken).

Main window of Transformer with 3 windings

Page 146: ABB DOC User Manual

Page 146 of 170

Impedance

The “Impedance” is used for a short-circuit calculation in which the resistance and reactance

characteristics of a cable or of a busway are already known. It is therefore possible to define:

Phase Resistance and Reactance.

Neutral Resistance and Reactance.

PE Resistance and Reactance.

Main Impedance window

Page 147: ABB DOC User Manual

DOC – User Manual - Page 147

LV cable

In the “LV cable” it is possible to define:

Description of the User, on two lines.

Ambient temperature, to which a relative correction factor will be associated.

The maximum Cdt% with which the single cable will be dimensioned.

The “Cable in double insulation (Class II)” option. A cable in class II will not be

verified for protection against indirect contacts.

Cable length.

Type of cable, defined as

PVC, EPR/XPLE

Conductor material made of Copper (Cu) or Aluminium (Al).

The installation method, where the multiple selections serve to direct you to one of the

methods defined in the reference Standard. Different Current Carrying Capacities,

available Sections, correction Factors correspond with each method.

The number and the section of the Phase, Neutral and PE conductors (or PEN, in TN-C

systems).

Main LV cable window e

The “Advanced Options >>>” button allows you to define the data which can change the

carrying capacity of the cable:

Installation details (adjacent circuits for several cables in the same duct or the

installation depth for cables in the ground).

Presence and Data of the PE, if different from the phase and Neutral conductors.

Temperature performances of the insulation, which different K2S

2 values correspond to

and working temperature.

The PE option laid in the same conduit as the phases determines the K2S

2 of the PE.

Installation symmetry considered for parallel cables.

Presence of third harmonics, which will correspond to any over-dimensioning of the

Neutral conductor.

The minimum Iz/Ib ratio to be taken into consideration in dimensioning the cable.

Page 148: ABB DOC User Manual

Page 148 of 170

LV cable Advanced Options

Busway

In the “Busway” it is possible to define:

Description of the User, on two lines.

Ambient temperature, which a relative correction factor will be associated to.

The maximum Cdt% with which the busway will be dimensioned.

The “Cable in double insulation (Class II)” option. A cable in class II will not be

verified for protection against indirect contacts.

Length of the cable.

The type of busway, defined as

Section of Neutral at 50% or 100%

The PE in the same housing as the phases or in a dedicated Housing

The type of busway selected.

Main Busway window

Page 149: ABB DOC User Manual

DOC – User Manual - Page 149

Busbar

The “Busbar” serves to display the values calculated by the program at a point of the

network, as well as to connect several departures to a single main circuit-breaker. The values

displayed on the Busbar page are:

Rated voltage.

Calculated voltage.

Phase shift between the distributed voltage and the calculated voltage.

Load current Ib.

Power factor.

Phases and Distribution system to the busbar, inherited from the branch which supplies

it.

The busbar also serves to set the Demand Factor (DF) of all loads connected to the busbar

considered.

Busbar Window

The “Corrections” button allows you to calculate:

The capacitive reactive Power needed to correct the power factor of all the loads

connected to the busbar under consideration to a new desired Power factor.

The Power factor which will be reached according to the installed capacitive reactive

Power.

Power factor correction Window

Page 150: ABB DOC User Manual

Page 150 of 170

The values displayed on the Short-circuit currents page are:

Short-circuit Ik and peak Ip current for Three-phase (LLL), Phase-Phase (LL), Phase-

Neutral (LN) and Phase-Ground (LPE) faults.

Short-circuit currents Window

It is also possible to display the “Details…” of the short-circuit calculations:

Short-circuit Ik and peak Ip current for Three-phase (LLL), Phase-Phase (LL), Phase-

Neutral (LN) and Phase-Ground (LPE) faults.

The details show all the components of the short-circuit defined in the selected calculation

Standard.

Window with Details of the Short-circuit currents

Page 151: ABB DOC User Manual

DOC – User Manual - Page 151

Multimeter

The “Multimeter” displays the values calculated by the program in any point of the network.

The values displayed on the Load-Flow page are:

Rated voltage.

Calculated voltage.

Phase shift between the distributed voltage and the calculated voltage.

Load current Ib.

Power factor.

Multimeter Load-Flow Window

The “Corrections” button allows calculation of:

The capacitive reactive Power needed to correct the power factor of all the loads

connected to the busbar under consideration to a new desired Power factor.

The Power factor which will be reached according to the installed capacitive reactive

Power.

Power factor correction Window

Page 152: ABB DOC User Manual

Page 152 of 170

The values displayed on the Short-circuit currents page are:

Short-circuit Ik and peak Ip current for Three-phase (LLL), Phase-Phase (LL), Phase-

Neutral (LN) and Phase-Ground (LPE) faults.

Short-circuit currents Window

Furthermore, it is possible to display the “Details…” of the short-circuit calculations:

Short-circuit current Ik and of peak Ip for faults Three-phase (LLL), Phase-Phase (LL),

Phase-Neutral (LN) and Phase-Ground (LPE).

The details show all the components of the short-circuit defined in the selected calculation

Standard.

Window with Details of the Short-circuit currents

Page 153: ABB DOC User Manual

DOC – User Manual - Page 153

LV circuit-breaker

The “LV circuit-breaker” window displays the data used by the program to dimension the

circuit-breaker itself. Some filters are also available to guide the program to select the circuit-

breaker most suitable for the user‟s requirements.

It is possible to define:

Description of the User, on two lines.

The values used for selection of the circuit-breaker are:

Load current Ib which passes through the circuit-breaker, used to determine the size Iu

of the circuit-breaker itself.

Carrying capacity of the cable Iz, used to select the circuit-breaker with a set current Ith

lower than Iz.

The Standard for use of the circuit-breaker (Industrial or IEC 60497-2; Civil or IEC

60898).

Maximum fault current Max Icc, used to select the Breaking capacity

Minimum fault current Min Icc, used to select the magnetic setting Im of the circuit-

breaker (if the circuit-breaker is not equipped with a residual current block).

The filters available are:

Type: Thermomagnetic circuit-breaker, Thermomagnetic with residual current circuit-

breaker, Magnetic only circuit-breaker, Magnetic only circuit-breaker with residual

current trip unit. This field is predefined according to the symbol drawn in the single-

line diagram.

Data of the residual current fitted with accessories:

Wave form of the leakage current detected (A, AC, B).

Tripping Characteristic (Instantaneous, Selective, Anti-disturbance).

Rated sensitivity IΔn.

Version: Fixed, Withdrawable, Plug-in.

The Poles (1P, 1P+N, 2P, 3P, 3P+N, 4P).

Family of the circuit-breaker: Molded-case Tmax, Modular System Pro M Compact, Air

Emax.

Trip unit: Thermomagnetic or Electronic.

Main LV circuit-breaker window

Page 154: ABB DOC User Manual

Page 154 of 170

The “Select >>” button allows selection of the desired circuit-breaker from a tree structure.

The filters set in the main window are:

Kept during selection of the product if “Apply filters” has been selected.

Not considered during selection of the product if “Free selection” has been selected.

LV circuit-breaker Selection Window

The “Advanced Options >>>” button allows you to define further criteria which come into

selection of the circuit-breaker:

Number of adjacent circuit-breakers, introduces derating of the carrying capacity of the

miniature circuit-breakers.

Breaking capacity, selected between Icu or Ics.

Definition of a minimum Icw short-circuit withstand.

The list of protected objects

The discrimination and back-up functionalities

LV circuit-breaker Advanced Options Window

Page 155: ABB DOC User Manual

DOC – User Manual - Page 155

The “Protected Objects” button, in the “Advanced Options >>>” of “LV circuit-breaker”

allows display and, if necessary, assignment of the protections of cables, busways, switch-

disconnectors, residual current circuit-breakers and contactors to the circuit-breaker.

The “Protection of people” data are taken from the General plant properties (chapter 3.2), and

can be modified. These data are used for selection of the magnetic and/or a possible residual

current block.

The protections against short-circuit of Residual current circuit-breakers, Switch-

disconnectors and Contactors are established according to the values and the rules defined in

the ABB coordination Tables.

Window of Objects Protected by a LV circuit-breaker

The “Discrimination and back-up” button in the “Advanced Options >>>” of “LV circuit-

breaker”, allows two or more circuit-breakers with discrimination and back-up restrictions to

be associated.

The discrimination and back-up values used for selection of the circuit-breakers are given in

the ABB “Coordination Tables”.

The fields displayed in the definition of discrimination are:

Level desired: short-circuit value up to which you want to verify discrimination. “Total”

means: up to calculated Icc.

Calculated Icc: short-circuit value of the circuit-breaker on the load side.

Max [kA]: value of discrimination between the circuit-breakers at present selected.

LV circuit-breaker Discrimination and Back-up Window

Page 156: ABB DOC User Manual

Page 156 of 170

Residual current circuit-breaker

The data used by the program to dimension the residual current circuit-breaker itself are

displayed in the “Residual current circuit-breaker” window. Some filters are also available to

guide the program to select the product most suitable for the user‟s requirements.

It is possible to define:

Description of the User, on two lines.

The values used for selection of the circuit-breaker are:

Load current Ib which passes through the residual current circuit-breaker, used to

determine the size of the circuit-breaker itself.

The filters available are:

Circuit-breaker Family: Modular System Pro M Compact, Modular System Pro M.

Residual current data:

Wave form of the leakage current detected (A, AC, B).

Tripping characteristic (Instantaneous, Selective, Anti-disturbance).

Rated sensitivity IΔn.

Poles (2P or 4P).

Main Residual current circuit-breaker window

The “Protected Objects” button allows display and, if necessary, assignment of the

protections against indirect contacts of cables and busways

The “Protection of people” data are taken from the General plant properties (chapter 3.2), and

can be modified. These data are used for selection of the residual current sensitivity.

Page 157: ABB DOC User Manual

DOC – User Manual - Page 157

Window of the Objects Protected by a Residual current circuit-breaker

LV Fuse

The data used by the program to dimension the fuse are displayed in the “LV Fuse” window.

Some filters are also available to guide the program to select the fuse most suitable for the

user‟s requirements.

It is possible to define:

Description of the User, on two lines.

The values used for selection of the fuse are:

Load current Ib which passes through the fuse, used to determine the rated current In of

the fuse itself.

Carrying capacity of the cable Iz, used to select the fuse with a rated current In lower

than the Iz.

The filters available are:

Family of the fuse-holder base: closed or open bases.

Fuse data:

Cartridge: gG for general use or aM for motor protection

Size of cartridge: 00, 0, 1, 2, 3

Poles of the fuse-holder base (1P, 2P, 3P).

Page 158: ABB DOC User Manual

Page 158 of 170

Main LV Fuse window

The “Protected Objects” button of the LV Fuse window allows display and, if necessary,

assignment of the cable protections, busways, switch-disconnectors, residual current circuit-

breakers and contactors to the circuit-breaker.

The “protection of people” data are taken from the General plant properties (chapter 3.2), and

can be modified.

Window of the Objects Protected by a LV Fuse

Page 159: ABB DOC User Manual

DOC – User Manual - Page 159

LV Switch-fuse

The data used by the program to dimension the switch-fuse are displayed in the window of

the “LV Switch-fuse”. Some filters are also available to guide the program to select the fuse

most suitable for the user‟s requirements.

It is possible to define:

Description of the User, on two lines.

The values used for selection of the fuse are:

Load current Ib which passes through the switch-fuse, used to determine the rated

current In of the fuse.

Carrying capacity of the cable Iz, used to select the switch-fuse with a rated current In

lower than Iz.

The filters available are:

Family of the switch-fuse: E930, OS, OESA.

Fuse data:

Cartridge: gG for general use or aM for motor protection

Size of the cartridge: 00, 0, 1, 2, 3

Poles of the switch-fuse (1P, 1P+N 2P, 3P, 3P+N, 4P).

Main LV Switch-fuse window

The “Protected Objects” button of the LV Switch-fuse window allows display and, if

necessary, assignment of the cable protections, busways, switch-disconnectors, residual

current circuit-breakers and contactors to the circuit-breaker.

The “protection of people” data are taken from the General plant properties (chapter 3.2), and

can be modified.

Page 160: ABB DOC User Manual

Page 160 of 170

Window of the Objects Protected by a LV Switch-fuse

Page 161: ABB DOC User Manual

DOC – User Manual - Page 161

LV Disconnector

In the “LV Disconnector” window it is possible to define:

Description of the User, on two lines.

Load current Ib which passes through the disconnector, used to determine the size Iu of

the disconnector itself.

The filters available are:

Disconnector family: Standard Disconnector, derived from Molded-case circuit-breaker

or E 200 Miniature switch, derived from Air Circuit-breaker.

Version: Fixed, Plug-in, Withdrawable

Poles of the disconnector (3P, 4P).

“Use Icw” and “Use Icm” serve to dimension the disconnector according to it‟s short-

circuit withstand (Icw) and closing under short-circuit (Icm) characteristics. When both

the boxes are disabled, the program dimensions the LV disconnector trying to protect it

with the first circuit-breaker on the supply side, using the data in the ABB coordination

Tables.

Main LV Disconnector window

Page 162: ABB DOC User Manual

Page 162 of 170

LV Contactor

In the “LV Contactor” window it is possible to define:

Description of the User, on two lines.

Load current Ib which passes through the contactor, used to determine the carrying

capacity Ie of the contactor itself.

The filters available are:

Contactor Family: Industrial Contactors of type A – AF, ESB range, EN range; E 259 -

Installation relays; E 250 - Latching relays (electro-magnetic); E 260 - Latching relays

(electronic).

Poles of the contactor.

The contactor service: AC-1 (resistive loads), AC-3 (inductive loads).

Main LV Contactor window

The “Advanced Options >>>” button allows you to define further criteria for selection of the

contactor according to the number and frequency of operations.

Derating will show the carrying capacity Ie of the contactor.

LV Contactor Advanced Options Window

Page 163: ABB DOC User Manual

DOC – User Manual - Page 163

Page 164: ABB DOC User Manual

Page 164 of 170

Generic load

In the “Generic load” control panel it is possible to define:

Description of the User, on two lines.

The utilization factor (UF). A 100A load with a UF of 50% will generate a current load

Ib of 50A.

Consumption as a function of Load current and Power Factor.

Consumption as a function of active Power consumed and Power Factor.

Symbol with which the load will be displayed (a ball - an arrow - a transformer).

Main Generic load window

Graphic symbols of the Generic load

Page 165: ABB DOC User Manual

DOC – User Manual - Page 165

Motor

In the “Motor” control panel it is possible to define:

Description of the User, on two lines.

The utilization factor (UF). A 100A motor with a UF of 50% will generate a load current

Ib of 50A.

Motor model.

Rated voltage

Rated apparent Power

Efficiency

Rated power factor

The rated current will be calculated from these data.

Furthermore a database of the motors is available:

“< Load from database…” allows you to load a motor from the DOC motor database

“> Add to database” allows you to save the motor currently defined in the DOC motor

database. To be able to save a motor, the Model field must be filled in.

The fields destined for coordination are only available if the motor is supplied from the

Single Objects which make up one of the ABB coordinations, as in the Motor Departure

Macro Objects (chapter 4.2).

These fields include:

Type of starting: Direct (DOL) or Star/Delta (YD).

Class of starting: normal (class 10) or heavy-duty (class 30).

Type of coordination: Type 1 or Type 2.

Main Motor window

Page 166: ABB DOC User Manual

Page 166 of 170

The “Advanced Options >>>” button allows you to define other parameters of the motor.

These parameters are:

The ratio between the starting current and the rated current Ilr/In

The number of poles

The Rotor and Stator resistances and the reactances, in „per unit‟ (p.u.).

Motor Advanced Options Window

Lighting load

The “Lighting load” considers both the load part and the cable part of a lighting plant. The

following are defined on the load side:

Type of lamps.

Rated power of each single lamp.

The Phases loaded by the lamps.

Number of lamps per phase.

The length of the initial branch of cable as far as the first lamp.

The distance between each lamp.

Window of the Lighting load, definition of the load

Page 167: ABB DOC User Manual

DOC – User Manual - Page 167

For the cable side, verify the “LV cable” Single Object described in this section.

The length of the cable will be the result of “Initial length + ((Number of lamps - 1) *

Distance between each lamp)”.

It is possible to change the data of the lamps on the cable side by clicking over the lamp-

shaped icon.

Lights Window, definition of the cable

Page 168: ABB DOC User Manual

Page 168 of 170

Capacitor bank

The “Capacitor bank” allows the power factor to be corrected at a point in the network.

Therefore, in its window it is possible to:

Display the present Power factor of the busbar it is connected to.

Set any value of capacitive reactive Power.

Capacitor bank Window

The “Calculate” button allows the program to automatically select the capacitive reactive

Power needed to achieve a given Power factor, starting from the present value.

By confirming the calculation with “Ok”, the capacitive reactive Power calculated will be

added to the Capacitor banks.

Window for automatic power factor correction

Page 169: ABB DOC User Manual

DOC – User Manual - Page 169

Connection – Dashed Connection

The “Connection” and ”Dashed Connection” Single Objects serve to connect different

Single Objects with each other. It is therefore possible to define the demand factor.

Connection and Dashed Connection Window

Horizontal Departure line link – Vertical Departure line link

The “Horizontal Departure line link” and ”Vertical Departure line link” Single Objects

connect Single Objects placed on different pages with each other.

The label which identifies each single departure line is assigned automatically by the

program, whereas the user can add a description.

Departure line Window

The “Go to” button links you directly to the connected arrival line.

Horizontal Arrival line link – Vertical Arrival line link

The “Horizontal Arrival line link” and “Vertical Arrival line link” Single Objects connect

Single Objects placed on different pages with each other.

The label which identifies each arrival line is assigned by the user by means of the “Link

arrival to departure…” window.

“Connect arrival page to departure…” Window

Page 170: ABB DOC User Manual

Page 170 of 170

The user can add a description.

Arrival line Window

The “Go to” button links you directly to the connected departure line.

The “…” button re-opens the “Connect arrival to departure…” window button.