Copyright 2013 ABB. All rights reserved.
Type des. Part no.
Prep. PSAC/TPTC / Johanna C. Olsson
2016-07-05 Doc. kind Declaration of conformity No. of p.
Appr. / Svensson Johan O 2017-03-29 Title ABB 670 and 650 series version 2.2 Ed1 - MICS
153Resp. dept PSAC/TPTC Approved
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 1
FILE: ABB 650 & 670 series version 2.2 Ed1 - MICS.docx; SAVEDATE: 2017-02-07 17:45; TEMPLATE: Techn_Doc_Stand_P.dot C; SKELETON:
ABB 670 and 650 series version 2.2 – IEC 61850 Ed.1 MICS
(Model Implementation Conformance Statement)
Template version 0.1
Date: April 24, 2008
UCA International Users Group
Testing Sub Committee
Document Review Summary:
Reviewer Role Reviewer Name
Organization Review Date
Review Status
Product Architect Johan Sälj TPTE 2017-02-07 No remarks
To be revised
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 2
ABB 670 and 650 series version 2.2 – IEC 61850 Ed.1 MICS........................................ 1
1 Introduction.............................................................................................................. 7
1.1 Scope........................................................................................................... 71.2 Denominations ............................................................................................. 7
2 Logical Nodes List ................................................................................................... 8
3 Logical Node Extensions ...................................................................................... 11
3.1 New Logical Nodes .................................................................................... 113.1.1 SCHLCCH Revision 1................................................................... 113.1.2 RCHLCCH Revision 1 .................................................................. 123.1.3 QCBAY Revision 1 ....................................................................... 133.1.4 QCRSV......................................................................................... 133.1.5 L4UFCNT ..................................................................................... 143.1.6 IB16FCVB .................................................................................... 153.1.7 B16IFCVI...................................................................................... 153.1.8 ZCLCPLAL ................................................................................... 163.1.9 ZCVPSOF Revision 3 ................................................................... 163.1.10 CCSRDIF Revision 2 .................................................................... 163.1.11 SDDRFUF .................................................................................... 173.1.12 VDRFUF....................................................................................... 173.1.13 CCRPLD....................................................................................... 183.1.14 ZMRPSL Revision 2 ..................................................................... 183.1.15 SSCBR Revision 3........................................................................ 193.1.16 FTAQFVR Revision 1 ................................................................... 203.1.17 LOLSPTR Revision 1.................................................................... 21
3.2 Extended Logical Nodes............................................................................. 213.2.1 PHPIOC........................................................................................ 283.2.2 PHPIOC Revision 1 ...................................................................... 293.2.3 AEGGAPC Revision 2 .................................................................. 293.2.4 PAPGAPC Revision 1................................................................... 303.2.5 STBPTOC .................................................................................... 303.2.6 COUVPTUV.................................................................................. 313.2.7 COUVLLN0 .................................................................................. 313.2.8 COUVPTOV ................................................................................. 323.2.9 LCCRPTRC Revision 1 ................................................................ 323.2.10 SCILO........................................................................................... 333.2.11 HZPDIF Revision 2 ....................................................................... 333.2.12 LAPPLLN0.................................................................................... 343.2.13 LAPPPDUP .................................................................................. 343.2.14 LAPPPUPF................................................................................... 343.2.15 ZPCPSCH .................................................................................... 353.2.16 ZPCWPSCH................................................................................. 363.2.17 OV2PTOV .................................................................................... 363.2.18 GEN2LLN0 ................................................................................... 373.2.19 OOSPPAM Revision 1.................................................................. 373.2.20 FMPSPDIS ................................................................................... 383.2.21 SLGGIO Revision 7 ...................................................................... 383.2.22 GENPDIF Revision 1 .................................................................... 393.2.23 ZMHPDIS ..................................................................................... 403.2.24 ZSMGAPC Revision 2 .................................................................. 403.2.25 SMPPTRC Revision 3 .................................................................. 413.2.26 STSGGIO..................................................................................... 423.2.27 LDLPDIF....................................................................................... 423.2.28 CCRBRF ...................................................................................... 433.2.29 CCRWRBRF................................................................................. 433.2.30 EFPIOC........................................................................................ 443.2.31 CVMMXN Revision 1 .................................................................... 44
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 3
3.2.32 SCCVPTOC.................................................................................. 453.2.33 ZGVPDIS...................................................................................... 453.2.34 ZGVLLN0 ..................................................................................... 463.2.35 ZGVPTUV .................................................................................... 463.2.36 LCNSPTOC.................................................................................. 473.2.37 LCNSPTOV .................................................................................. 473.2.38 LCZSPTOV .................................................................................. 483.2.39 LCZSPTOC .................................................................................. 483.2.40 ZMCAPDIS................................................................................... 493.2.41 ZMCPDIS ..................................................................................... 493.2.42 ZMMAPDIS .................................................................................. 503.2.43 FDPSPDIS Revision 2 .................................................................. 503.2.44 FPSRPDIS ................................................................................... 523.2.45 ZMMPDIS..................................................................................... 533.2.46 ZMRAPDIS................................................................................... 543.2.47 ZMRPDIS ..................................................................................... 543.2.48 ZMQAPDIS................................................................................... 553.2.49 ZMQPDIS ..................................................................................... 553.2.50 BUSPTRC .................................................................................... 563.2.51 BBSPLLN0 ................................................................................... 563.2.52 BCZSPDIF.................................................................................... 573.2.53 BZNSPDIF Revision 1 .................................................................. 573.2.54 BZISGGIO .................................................................................... 583.2.55 SMBRREC Revision 1 .................................................................. 593.2.56 LCP3PTOC .................................................................................. 603.2.57 LCP3PTUC................................................................................... 613.2.58 ZMFCLLN0................................................................................... 613.2.59 PSFPDIS ...................................................................................... 623.2.60 ZMFPDIS...................................................................................... 623.2.61 ZMFPDIS Revision 1 .................................................................... 633.2.62 ZMFPTRC .................................................................................... 633.2.63 ZMMMXU Revision 3.................................................................... 643.2.64 ZMFLLN0 ..................................................................................... 643.2.65 LT6CPDIF Revision 2 ................................................................... 643.2.66 L6CPDIF Revision 2 ..................................................................... 663.2.67 LT3CPDIF Revision 2 ................................................................... 673.2.68 L3CPDIF Revision 2 ..................................................................... 683.2.69 SSIMG Revision 1 ........................................................................ 693.2.70 SSIML Revision 1 ......................................................................... 703.2.71 T2WPDIF Revision 1 .................................................................... 713.2.72 T3WPDIF Revision 1 .................................................................... 723.2.73 GRPTTR Revision 1 ..................................................................... 743.2.74 GSPTTR Revision 1 ..................................................................... 743.2.75 CBPLLN0 Revision 1 .................................................................... 753.2.76 CBPMMXU Revision 1.................................................................. 753.2.77 RP3PDOP Revision 1................................................................... 763.2.78 PH3PTOC .................................................................................... 773.2.79 PH3PTOC Revision 3 ................................................................... 773.2.80 HOLPTOV Revision 1................................................................... 783.2.81 HPH1PTOV Revision 1................................................................. 783.2.82 PH3PTUC..................................................................................... 783.2.83 BBTPLLN0 ................................................................................... 793.2.84 BUTPTRC .................................................................................... 793.2.85 BRCPTOC Revision 3 .................................................................. 803.2.86 ZCRWPSCH Revision 2 ............................................................... 803.2.87 ZCRWPSCH Revision 3 ............................................................... 813.2.88 LOVPTUV Revision 2 ................................................................... 823.2.89 ECRWPSCH Revision 2 ............................................................... 82
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 4
3.2.90 STEFPHIZ Revision 2................................................................... 833.2.91 ZMRPSB Revision 2 ..................................................................... 843.2.92 PSPPPAM Revision 3................................................................... 843.2.93 GEN2LLN0 Revision 1.................................................................. 853.2.94 VDCPTOV Revision 2................................................................... 853.2.95 LEXPDIS Revision 1..................................................................... 863.2.96 BCZTPDIF.................................................................................... 873.2.97 UV2PTUV Revision 2 ................................................................... 873.2.98 STTIPHIZ Revision 2 .................................................................... 873.2.99 ECPSCH Revision 1 ..................................................................... 883.2.100 ROTIPHIZ Revision 2 ................................................................... 893.2.101 BZNTPDIF Revision 3 .................................................................. 893.2.102 GUPPDUP Revision 1 .................................................................. 903.2.103 ROV2PTOV Revision 1 ................................................................ 913.2.104 GOPPDOP Revision 1.................................................................. 913.2.105 OEXPVPH Revision 3................................................................... 923.2.106 BZITGGIO .................................................................................... 933.2.107 SWSGGIO.................................................................................... 933.2.108 ZCPSCH Revision 2 ..................................................................... 943.2.109 OC4LLN0 ..................................................................................... 943.2.110 PH3PTRC Revision 5 ................................................................... 953.2.111 REFPDIF Revision 1..................................................................... 953.2.112 MVGGIO Revision 1 ..................................................................... 963.2.113 SPGGIO Revision 1...................................................................... 963.2.114 SP16GGIO Revision 2.................................................................. 973.2.115 VSGGIO Revision 1...................................................................... 973.2.116 PCGGIO....................................................................................... 983.2.117 TR8ATCC Revision 17 ................................................................. 983.2.118 TR1ATCC Revision 15 ............................................................... 1033.2.119 OCNDLLN0 ................................................................................ 1053.2.120 AUT1RSYN Revision 2............................................................... 1053.2.121 MAN1RSYN Revision 2 .............................................................. 1063.2.122 SYNRSYN Revision 3................................................................. 1073.2.123 RSY1LLN0 Revision 2 ................................................................ 1073.2.124 NS2LLN0 Revision 1 .................................................................. 1083.2.125 NS2PTOC Revision 1 ................................................................. 1093.2.126 NS2PTRC Revision 2 ................................................................. 1093.2.127 GF2LLN0.................................................................................... 1103.2.128 GF2MMXN Revision 3 ................................................................ 1103.2.129 PH1PTUV................................................................................... 1113.2.130 VRLLN0...................................................................................... 1113.2.131 VRPVOC .................................................................................... 1123.2.132 CCSRBRF .................................................................................. 1123.2.133 SAPFRC Revision 1 ................................................................... 1133.2.134 SDEPSDE Revision 1................................................................. 1133.2.135 ETPMMTR Revision 3 ................................................................ 1143.2.136 SAPTOF Revision 1.................................................................... 1163.2.137 SAPTUF Revision 1.................................................................... 1163.2.138 GEN4PHAR Revision 3 .............................................................. 1173.2.139 GF2PHAR Revision 2 ................................................................. 1173.2.140 GF2PTOV Revision 2 ................................................................. 1183.2.141 GF2PTUC Revision 2 ................................................................. 1183.2.142 GF2PTUV Revision 2 ................................................................. 1193.2.143 GF2PVOC Revision 2................................................................. 1193.2.144 LMBRFLO Revision 2 ................................................................. 1203.2.145 PH1BPTOC Revision 1............................................................... 1203.2.146 PH1PTRC Revision 3 ................................................................. 1213.2.147 LCPTTR ..................................................................................... 121
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 5
3.2.148 LFPTTR...................................................................................... 1223.2.149 DRPRDRE.................................................................................. 1233.2.150 SCSWI Revision 1 ...................................................................... 1233.2.151 SPC8GGIO Revision 2 ............................................................... 1243.2.152 TCMYLTC Revision 5 ................................................................. 1243.2.153 TCLYLTC Revision 5 .................................................................. 1253.2.154 CBPPTRC .................................................................................. 1263.2.155 SECLLN0 Revision 1 .................................................................. 1263.2.156 CMMXU Revision 4 .................................................................... 1273.2.157 VMMXU Revision 1..................................................................... 1273.2.158 VNMMXU Revision 4 .................................................................. 1283.2.159 CMSQI Revision 3 ...................................................................... 1283.2.160 VMSQI Revision 3 ...................................................................... 1293.2.161 LPHD Revision 6 ........................................................................ 1293.2.162 TEIGGIO .................................................................................... 1293.2.163 TEILGGIO Revision 1 ................................................................. 1303.2.164 SXCBR Revision 1...................................................................... 1313.2.165 SXSWI Revision 1 ...................................................................... 1313.2.166 DPGGIO..................................................................................... 1323.2.167 TRPTTR Revision 4.................................................................... 1323.2.168 EF4LLN0 Revision 1................................................................... 1333.2.169 EF4PTRC Revision 3.................................................................. 1333.2.170 EF4PTRC Revision 4.................................................................. 1343.2.171 EF4RDIR Revision 6................................................................... 1353.2.172 PH1PTOC Revision 3 ................................................................. 1353.2.173 EF4PTRC Revision 4.................................................................. 1353.2.174 LLN0 Revision 4 ......................................................................... 1363.2.175 TMAGGIO .................................................................................. 1363.2.176 ALMCALH Revision 1 ................................................................. 1373.2.177 INDCALH Revision 1 .................................................................. 1373.2.178 WRNCALH Revision 1................................................................ 1383.2.179 ZGTLLN0.................................................................................... 1383.2.180 ZGPDIS...................................................................................... 1393.2.181 ZGPTRC..................................................................................... 1393.2.182 TPPIOC...................................................................................... 1393.2.183 EF2LLN0 .................................................................................... 1403.2.184 EF2PTRC................................................................................... 1403.2.185 EF2RDIR .................................................................................... 1413.2.186 GEN2PHAR................................................................................ 1413.2.187 EFRWPIOC ................................................................................ 1423.2.188 U2RWPTUV ............................................................................... 1423.2.189 O2RWPTOV............................................................................... 1433.2.190 BRPTOC .................................................................................... 1433.2.191 D2LLN0 ...................................................................................... 1433.2.192 D2PTOC..................................................................................... 1443.2.193 AGSAL Revision 2...................................................................... 1443.2.194 BBS6LLN0 Revision 1 ................................................................ 1453.2.195 BDZSGAPC................................................................................ 1453.2.196 BFPTRC..................................................................................... 1463.2.197 BICPTRC.................................................................................... 1463.2.198 BZNPDIF Revision 2................................................................... 1473.2.199 BCZPDIF Revision 1................................................................... 1473.2.200 L4CLLN0 Revision 2................................................................... 1483.2.201 L4CPDIF..................................................................................... 1483.2.202 L4CPDIF Revision 1 ................................................................... 1493.2.203 L4CPTRC................................................................................... 149
4 Common Data Class Extensions ........................................................................ 150
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 6
5 Enum types Extensions....................................................................................... 151
6 Control Block Extensions ................................................................................... 152
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 7
1 Introduction
This model implementation conformance statement is applicable for ABB 670 Series (REB670, REC670, RED670, REG670, REL670, RES670 and RET670) and 650 Series (REB650, REC650, RED650, REL650, REQ650 and RET650) of version 2.2 when configured in Edition 1 mode.
This MICS document specifies the modelling extensions compared to IEC 61850 edition 1Clause 2 contains the list of implemented logical nodes. Clause 3 describes the new and extended logical nodes. Clause 4 describes the new and extended common data classes (if any).Clause 5 describes the new and extended enum types. Clause 6 describes any other extensions.
1.1 Scope
The purpose of this document is to serve as the MICS, Modelling Implementation Conformance Statement according to IEC 61850-10. It covers the content of the products within ABB 670 and 650Series of version 2.2.The document contains the description and layout of the Logical Node types, the vendor specific Logical Nodes and the vendor specific additions to the standard Logical Nodes.The details of the respective DATA types are described in the ICD file for the respective products, mentioned above.There is no vendor specific Common Data Classes defined in these products.
This document describes the layout of the Logical Nodes types used in the ABB 670 and 650 Series product platform. Each Logical Node type represents a function or a part of a function. The descriptions of the functions and their connection to the logical nodes are described in the Technical reference manuals. From the products definitions, it is a strict relation between the version of a function and the version of each Logical Node type and these are re-used in different products based upon ABB 670 and 650 Series platform. Note that the type versions of the Logical Nodes and their attributes are only unique for each ICD file. This means that during engineering, creating the SCD file(s) of the communication, the tool may change or add content to the type names.
1.2 Denominations
Although not required nor defined in IEC 61850, the ABB 670 and 650 Series supports version handling of the Logical Node types. The reason is that it shall be easy to distinguish between the LN types used in different version of the products based upon the same platform and the version of the platform. The revisions of LN type higher than 0 have Revision<No> concatenated with the LN type name.DATA types are not version handled.
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 8
2 Logical Nodes List
The following table contains the list of logical nodes implemented in the device:
A: Logical Nodes for automatic control
ATCC (Automatic tap changer control)
C: Logical Nodes for control
CBAY (Bay control)
CILO (Interlocking)
CRSV (Bay reserve)
CSWI (Switch controller)
F: Logical Nodes for conversion functions
FCNT (Counter)
FCVB (Integer to Boolean converter)
FCVI (Boolean to integer converter)
G: Logical Nodes for generic references
GAPC (Generic automatic process control)
GGIO (Generic process I/O)
GSAL (Generic security application)
L: System Logical Nodes
LCCH (Physical communication channel supervision)
LPHD (Physical device information)
LLN0 (Logical node zero)
P: Logical Nodes for protection functions
PDIF (Differential protection)
PDIS (Distance protection)
PDOP (Directional overpower)
PDUP (Directional underpower)
PFRC (Rate of change of frequency)
PHAR (Harmonic distortion)
PHIZ (Ground detector)
PIOC (Instantaneous overcurrent)
PLAL (Local acceleration logic)
PPAM (Phase angle measuring)
PSCH (Protection scheme)
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 9
PSDE (Sensitive directional earthfault)
PSOF (Switch onto fault logic)
PTOC (Time overcurrent)
PTOF (Overfrequency)
PTOV (Overvoltage)
PTRC (Protection trip conditioning)
PTTR (Thermal overload)
PTUC (Time undercurrent)
PTUF (Underfrequency)
PTUV (Undervoltage)
PUPF (Underpower factor)
PVOC (Voltage controlled time overcurrent)
PVPH (Volts per Hz)
R: Logical nodes for protection related functions
RBRF (Breaker failure protection)
RDIF (Differential supervision)
RDIR (Directional element)
RDRE (Disturbance recorder)
RFLO (Fault locator)
RFUF (Fuse failure supervision)
RPLD (Pole discordance protection)
RPSB (Power swing detection)
RPSL (Power Swing Logic)
RREC (Autoreclosing)
RSYN (Synchronising)
M: Logical Nodes for metering and measurement
MMTR (Metering)
MMXN (Non phased related measurement)
MMXU (Measurement)
MSQI (Sequence and imbalance)
Q: Logical Nodes for power quality events
QFVR (Frequency variation)
S: Logical Nodes for sensors and monitoring
SCBR (Circuit breaker monitoring)
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 10
SIMG (Insulation medium supervision (gas))
SIML (Insulation medium supervision (liquid))
SPTR (Power transformer supervision)
X: Logical Nodes for switchgear
XCBR (Circuit breaker)
XSWI (Switch)
Y: Logical Nodes for power transformers
YLTC (Tap changer)
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 11
3 Logical Node Extensions
The following table use
M : Data is mandatory in the IEC-61850-7-4.
O: Data is optional in the IEC-61850-7-4 and is used in the device.
E: Data is an extension to the IEC-61850-7-4.
C: Data is conditional in the IEC-61850-7-4.
3.1 New Logical Nodes
New logical nodes have the lnNs attribute in the Name plate. The value of lnNs is $, which in this case is a reference to the MICS document.
The ABB 670 and 650 Series platform contains the following new functions:
LN Class Prefix LN Type Description
LCCH
RCH RCHLCCHPhysical communication channel supervision, redundant channels
SCH SCHLCCHPhysical communication channel supervision, singlechannel (none redundant)
CBAY Q QCBAY Bay function
CRSV Q QCRSV Bay reserve function. FCNT L4U L4UFCNT Limit Counter
FCVB IB16 IB16FCVB Integer to Boolean converter
FCVI B16I B16IFCVI Boolean to integer converter
PLAL ZCLC ZCLCPLAL Local acceleration logic.
PSOF ZCV ZCVPSOF Automatic switch onto fault logic.
RDIF CCS CCSRDIF Current circuit supervision, current based.
RFUF SDD SDDRFUFFuse failure supervision, Zero sequence and du/dt and di/dt based.
VD VDRFUF Fuse failure supervision based on voltage difference.
RPLD CC CCRPLDPole-discordance protection, current and/or contact based.
RPSL ZM ZMRPSL Power Swing Logic
SCBR S SSCBR Circuit breaker condition monitoring.
SPTR LOL LOLSPTR Power transformer supervision
QFVR FTA FTAQFVR Frequency time accumulation protection
3.1.1 SCHLCCH Revision 1
LCCH class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 12
LCCHPhysical communication
channel supervision
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_b_dLPL Name plate M lnNs=$ refers to the MICS
Status Information
ChLiv ABB_a_dSPS Physical channel status; true, if channel receives telegrams within a specified time interval
M
3.1.2 RCHLCCH Revision 1
LCCH class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
LCCH
Physical communication
channel supervision,
redundant channels
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_b_dLPL Name plate M lnNs=$ refers to the MICS
Status Information
ChLiv ABB_a_dSPS Physical channel status; true, if channel receives telegrams within a specified time interval
M
RedChLiv ABB_a_dSPS Physical channel status of redundant channel
C
FerCh ABB_b_dINS Frame error rate on this channel
O
RedFerCh ABB_b_dINS Frame error rate on redundant channel
O
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 13
3.1.3 QCBAY Revision 1
CBAY class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
CBAY Bay function
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_b_dLPL Name plate MlnNs=$ refers to the MICS
Status Information
LocSwPos ABB_v1_dINS The position of the local
switch
E
SrcOpPrm ABB_v1_dINS Permitted Source To Operate E
BlkCmd ABB_v1_dSPC Block commands E Controllable
BlkMeas ABB_v1_dSPS Block measureand E
BlkUpd ABB_v1_dSPC Block update E Controllable
Loc ABB_v1_dSPS Local operation E
Rem ABB_v1_dSPS Remote operation E
3.1.4 QCRSV
CRSV class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
CRSV Bay reserve function.
Data
Common Logical Node Information
Mod ABB_aINC Mode M
Beh ABB_aINS Behaviour M
Health ABB_cINS Health M
NamPlt ABB_bLPL Name plate MlnNs=$ refers to the MICS
Status Information
AckRsvBay ABB_v1SPS Acknowledge to other bays E
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 14
that this bay is reserved
PrmOp1 ABB_v1SPS Reservation is made and the
app. 1 is allowed to operate
E
PrmOp2 ABB_v1SPS Reservation is made and the
app. 2 is allowed to operate
E
PrmOp3 ABB_v1SPS Reservation is made and the
app. 3 is allowed to operate
E
PrmOp4 ABB_v1SPS Reservation is made and the
app. 4 is allowed to operate
E
PrmOp5 ABB_v1SPS Reservation is made and the
app. 5 is allowed to operate
E
PrmOp6 ABB_v1SPS Reservation is made and the
app. 6 is allowed to operate
E
PrmOp7 ABB_v1SPS Reservation is made and the
app. 7 is allowed to operate
E
PrmOp8 ABB_v1SPS Reservation is made and the
app. 8 is allowed to operate
E
RqRsvBay ABB_v1SPS Request for reservation of
other bays
E
Rsv ABB_v1SPS Indicates that the bay is
reserved
E
3.1.5 L4UFCNT
FCNT class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
FCNT Limit Counter
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_b_dLPL Name plate MlnNs=$ refers to the MICS
Status Information
CntRs ABB_a_dBCR Counter M
RsCnt ABB_v1_Dspc Reset of the function E
Lim1 ABB_v1_dSPS Countervalue larger than limit
1
E
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 15
Lim2 ABB_v1_dSPS Countervalue larger than limit
2
E
Lim3 ABB_v1_dSPS Countervalue larger than limit
3
E
Lim4 ABB_v1_dSPS Countervalue larger than limit
4
E
3.1.6 IB16FCVB
FCVB class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
FCVBInteger to Boolean16
converter
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_b_dLPL Name plate M lnNs=$ refers to the MICS
Status Information
ISCSO ABB_b_dINC Integer status controllable status output
Controllable
3.1.7 B16IFCVI
FCVI class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
FCVIBoolean16 to Integer
converter
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_b_dLPL Name plate M lnNs=$ refers to the MICS
Status Information
OutInt ABB_b_dINS Integer output M
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 16
3.1.8 ZCLCPLAL
PLAL class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PLAL Local acceleration logic
Data
Common Logical Node Information
Mod ABB_aINC Mode M
Beh ABB_aINS Behaviour M
Health ABB_cINS Health M
NamPlt ABB_bLPL Name plate MlnNs=$ refers to the MICS
Status Information
OpLosLod ABB_v2ACT Trip by loss of load E
OpZnExd ABB_v2ACT Trip by zone extension E
3.1.9 ZCVPSOF Revision 3
PSOF class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PSOF Switch onto fault logic.
Data
Common Logical Node Information
Mod ABB_aINC Mode M
Beh ABB_aINS Behaviour M
Health ABB_cINS Health M
NamPlt ABB_bLPL Name plate MlnNs=$ refers to the MICS
Status Information
Op ABB_bACT Trip output E
3.1.10 CCSRDIF Revision 2
RDIF class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
RDIF Differential current supervision
Data
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 17
Common Logical Node Information
Mod ABB_aINC Mode M
Beh ABB_aINS Behaviour M
Health ABB_cINS Health M
NamPlt ABB_bLPL Name plate MlnNs=$ refers to the MICS
Status Information
Op ABB_bACT Detection of current circuit
failure
E
Alm ABB_v1SPS Alarm for current circuit failure E
3.1.11 SDDRFUF
RFUF class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
RFUF
Fuse failure supervision,
Zero sequence and du/dt and
di/dt based.
Data
Common Logical Node Information
Mod ABB_aINC Mode M
Beh ABB_aINS Behaviour M
Health ABB_cINS Health M
NamPlt ABB_bLPL Name plate MlnNs=$ refers to the MICS
Status Information
Str3Ph ABB_v2ACD Three-phase start of function E
Str ABB_v2ACD General start of function E
StrRst ABB_v2ACD Start of current and voltage
controlled function
E
3.1.12 VDRFUF
RFUF class
Attribute
Name
DATA
TypeExplanatio
M/O/E
/CRemarks
RFUFFuse failure supervision
based on voltage difference
Data
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 18
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_b_dLPL Name plate MlnNs=$ refers to the MICS
Status Information
Str ABB_a_dACD Start (Fuse failure) M
AlmRef ABB_v1_dACD Alarm pilot reference E
3.1.13 CCRPLD
RPLD class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
RPLD Pole discordance.
Data
Common Logical Node Information
Mod ABB_aINC Mode M
Beh ABB_aINS Behaviour M
Health ABB_cINS Health M
NamPlt ABB_bLPL Name plate MlnNs=$ refers to the MICS
Status Information
Op ABB_bACT Trip signal M
Str ABB_v2ACD Started. Trip condition true,
waiting for delay time to expire
E
3.1.14 ZMRPSL Revision 2
RPSL class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
RPSL Power Swing Logic
Data
Common Logical Node Information
Mod ABB_aINC Mode M
Beh ABB_aINS Behaviour M
Health ABB_cINS Health M
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 19
NamPlt ABB_bLPL Name plate MlnNs=$ refers to the MICS
Status Information
Op ABB_bACT Operate (TRIP) E
OpUnRchZn ABB_v2ACT underReachZoneOperate E
BlkLoSetZn ABB_v1SPS blockLowSetProtZone E
BlkHiSetZn ABB_v1SPS blockHighSetProtZone E
CarSend ABB_v2ACT carrierSend E
3.1.15 SSCBR Revision 3
SCBR class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
SCBRCircuit breaker condition
monitoring
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_b_dLPL Name plate M lnNs=$ refers to the MICS
Status Information
OpCnt ABB_v5_dINS Number of CB operations E
OpnAlm ABB_v1_dSPS Open Alarm E
RsAccAPwr ABB_v1_dSPC Reset Energy EControllable
TmmsCls ABB_v2_dMV CB close travel time E
ClsAlm ABB_v1_dSPS Close Alarm E
OpNumAlm ABB_v1_dSPS Number of CB Operations
exceeds alarm limit
E
OpNumLO ABB_v1_dSPS Number of CB operations
exceeds lock out limit
E
APwrAlm ABB_v1_dSPS Accumulated energy exceeds
Alarm setting
E
APwrLO ABB_v1_dSPS Accumulated Energy excceds
lock out setting
E
LonTmAlm ABB_v1_dSPS CB Not operated for long time E
SprChaAlm ABB_v1_dSPS Spring Charging time
exceeds threshold setting
E
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 20
PresAlm ABB_v3_dSPS Pressure below alarm level E
InaTmdCnt ABB_v1_dINS Number of Days CB has been
Inactive
E
PosOpn ABB_v1_dSPS CB is in Open position E
PosIvd ABB_v1_dSPS CB position is invalid E
PosCls ABB_v1_dSPS CB is in Close Position E
CBLifAlm ABB_v1_dSPS Life of CB below Alarm level E
TmmsOpn ABB_v2_dMV CB Open Travel Time E
TmsSprCha ABB_v2_dMV Charging Time of the CB
Spring
E
RmnLif ABB_v1_dINS Remaining Life of CB E
RsCBWear ABB_v1_dSPC Reset operation counter EControllable
AccAPwr ABB_v2_dMV Accumulated currents power E
PresLO ABB_v1_dSPS Pressure below lockout level E
RsTrvTm ABB_v1_dSPC Reset travel times and related
alarms
EControllable
RsSprChaTm ABB_v1_dSPC Reset spring charge time and
related alarm
EControllable
ColOpn ABB_v1_dSPS Open command of trip coil E
3.1.16 FTAQFVR Revision 1
QFVR class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
QFVR Frequency Variation
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_b_dLPL Name plate MlnNs=$ refers to the MICS
Status Information
VarStr ABB_a_dSPS Start of the frequency
variation event
M
HzVaTm ABB_a_dMV Frequency variation
duration of the last
O
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 21
completed event
AccHzVaTm ABB_v1_dMV Accumulated frequency
variation duration
E
3.1.17 LOLSPTR Revision 1
SPTR class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
SPTRPower transformer
supervision
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_b_dLPL Name plate M lnNs=$ refers to the MICS
Status Information
AgeRte ABB_b_dMV Aging rate O
HPTmpClc ABB_b_dMV Calculated winding hotspot temperature
O
HPTmpAlm ABB_a_dSPS Winding hotspot temperature alarm
O
HPTmpOp ABB_a_dSPS Winding hotspot temperature operate
O
HPTmpTr ABB_a_dSPS Winding hotspot temperature trip
O
AgeRf ABB_a_dSPC Refresh age outputs E
TopTmp ABB_c_dMV Calculated top oil temperature
E
RmnAge ABB_c_dMV Remaining transformer age
E
PctAge ABB_c_dMV Percentage loss of age E
3.2 Extended Logical Nodes
The following logical nodes are included in the product. All extra data that has been added, is marked as
“E” (Extended), these data contains the “dataNs” attribute with a reference the MICS.
LN Class Prefix
(default)
LN Type Description
LLN0
LLN0 General LN0 for LD0
BBS6 BBS6LLN0 LN0 for 6 zone Busbar protection
BBSP BBSPLLN0 LN0 for Busbar protection, 1 phases
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 22
BBTP BBTPLLN0 LN0 for Busbar protection, 3 phases
CBP CBPLLN0 LN0 for Capacitor Bank Protection
COUV COUVLLN0LN0 for Compensated overvoltage and undervoltage protection function for DTT scheme
D2 D2LLN0LLN0 for two-step directional overcurrent protection
EF2 EF2LLN0LN0 for Two-step time-delayed non-directional/directional residual overcurrent protection
EF4 EF4LLN0LN0 for Four-step time-delayed non-directional/directional residual overcurrent protection
GEN2 GEN2LLN0 LN0 for 2 step protection functions
GF2 GF2LLN0LN0 for general multipurpose protection function
L4C L4CLLN0 LLN0 for L4C
LAPP LAPPLLN0LN0 for Low active power and power factor detection function for DTT scheme
NS2 NS2LLN0LN0 for Negativ phase sequence overcurrent protection, 2 Steps
OC4 OC4LLN0LN0 for Four-step time-delayed non-directional / directional phase overcurrent protection
OCND OCNDLLN0LN0 for Over current single phase non direction
SEC SECLLN0 LN0 for SECAUD
RSY1 RSY1LLN0 LN0 for synchrocheck function
VR VRLLN0LLN0 for Voltage-restrained time overcurrent protection
ZGT ZGTLLN0 LLN0 for ZGT
ZGV ZGVLLN0LLN0 for Underimpedance protection for generators and transformers
ZMFC ZMFCLLN0LLN0 for Directional distance protection with phase selection, series compensation
ZMF ZMFLLN0LLN0 for Directional distance protection with phase selection
LPHD LPHD Physical device information
ATCCTR1 TR1ATCC Automatic Tap Changer Control
TR8 TR8ATCC Automatic Tap Changer Control
CALH
ALM ALMCALH Alarm handling, alarm
IND INDCALH Alarm handling, indication
WRN WRNCALH Alarm handling, warning
CILO S SCILO
Interlocking modules for three single or two double CB bays or one 1½ CB diameter incl. single and multiple command function blocks
CSWI S SCSWI Switch controller
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 23
GAPC
AEG AEGGAPCAccidental energisation protection for generator
BDZS BDZSGAPCBusbar differential protection, dynamic zone selection
PAP PAPGAPC Radial Feeder Protection
ZSM ZSMGAPCImpedance supervision logic for Mho Distance function
TEIL TEILGAPC Running hour-meter
GGIO
BZIT BZITGGIOBusbar differential protection zone interconnection, 3 Phases
BZIS BZISGGIOBusbar differential protection zone interconnection, 1 Phase
DP DPGGIO Generic double point status
MV MVGGIO Generic measured value
PC PCGGIO Pulse counter for energy metering
SL SLGGIO Selector/rotary switch
SP SPGGIO Generic single point status
SP16 SP16GGIO Generic single point status, 16 outputs
SPC8 SPC8GGIO Single point command, 8 SPC’s
STS STSGGIOStartupscheme function for Differential protection
SWS SWSGGIO Switch status used for Busbar protection
TMA TMAGGIO Trip Matrix
E VSGGIO Versatile Switch
GSAL A AGSAL Security alarm for IED
MMTR ETP ETPMMTR Energy Three Phase Measurement
MMXN
CV CVMMXN Service value reading of power
GF2 GF2MMXNNon phase related measurements for General Multipurpose protection
MMXU
CBP CBPMMXU Current monitoring
C CMMXU Current monitoring
V VMMXU Voltage monitoring
VN VNMMXU Voltage monitoring Ph-Gnd
ZM ZMMMXU Impedance monitoring
MSQIC CMSQI Current monitoring, sequence values
V VMSQI Voltage monitoring, sequence values
PDIF
BCZ BCZPDIF Busbar differential protection, check zone
BCZT BCZTPDIFBusbar differential protection check zone, 3 Phases
BCZS BCZSPDIFBusbar differential protection check zone, 1 Phases
BZN BZNPDIF Busbar differential protection, zone
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 24
BZNT BZNTPDIFBusbar differential protection zone, 3 Phases
BZNS BZNSPDIFBusbar differential protection zone, 1 Phases
GEN GENPDIF Generator Differential Protection
HZ HZPDIFClassic high impedance DifferentialProtection
HZR HZRPDIFClassic restricted earth fault with harmonic filtered overcurrent, high impedance measuring, external VDR
L3C L3CPDIFLine differential protection, phase segregated
L4C L4CPDIF PDIF for L4C
L6C L6CPDIFLine differential protection, phase segregated
LDL LDLPDIFLogical element for line differential function
LT3C LT3CPDIFLine differential protection, phase segregated including add-on for transformer in protected zone
LT6C LT6CPDIFLine differential protection, phase segregated including add-on for transformer in protected zone
REF REFPDIF Restricted earth fault protection
T2W T2WPDIFTransformer Differential protection, two winding
T3W T3WPDIFTransformer Differential protection, three winding
PDIS
FDPS FDPSPDISCombined phase selection and general fault-criteria, impedance and current based
FMPS FMPSPDIS Phase selection logic
FPSR FPSRPDISCombined phase selection and general fault-criteria, impedance and current based
LEX LEXPDIS Under and Loss of Excitation
PSF PSFPDISDirectional distance protection with phase selection
ZG ZGPDIS Distance Mho protection
ZGV ZGVPDISUnderimpedance protection for generators and transformers
ZMF ZMFPDISDirectional distance protection with phase selection
ZMC ZMCPDISFull-scheme distance measuring zone for series compensation, quadrilateral characteristic, Zone 1
ZMCA ZMCAPDISFull-scheme distance measuring zone for series compensation, additional zones
ZMH ZMHPDIS Mho Distance function
ZMM ZMMPDISFull-scheme distance measuring zone, quadrilateral characteristic
ZMMA ZMMAPDISFull-scheme distance measuring zone, additional
ZMQ ZMQPDISFull-scheme distance measuring zone, quadrilateral characteristic, Zone 1
ZMQA ZMQAPDISFull-scheme distance measuring zone, additional zones
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 25
ZMR ZMRPDIS Full-scheme distance measuring zone,Quadilateral
ZMRA ZMRAPDIS Full-scheme distance measuring zone,Quadilateral
PDOPGOP GOPPDOP Reverse Power Protection
RP3 RP3PDOP Reactive Power Protection
PDUP
GUP GUPPDUP Low Forward Power Protection
LAPP LAPPPDUPLow Active power and power factor protection for under power
PFRC SA SAPFRCSelectable over-and under-frequency function
PHAR
GEN2 GEN2PHARHarmonic restraint for 2-stage protection function
GEN4 GEN4PHARHarmonic restraint for 4-stage protection function
GF2 GF2PHARHarmonic restraint used in General MultiPurpose protection function
PHIZ
ROTI ROTIPHIZ100% Rotor earthfault protection by using injection
STEF STEFPHIZ 100% Stator Earth Fault Protection
STTI STTIPHIZ100% Stator earthfault protection by using injection
PIOC
EF EFPIOCInstantaneous non-directional residual overcurrent protection
PH PHPIOCInstantaneous non-directional phase overcurrent protection
TP TPPIOC Tank protection
PPAMOOS OOSPPAM Out of step protection
PSP PSPPPAM Pole slip generator protection
PSCH
EC ECPSCHScheme communication logic for residual overcurrent protection
ECRW ECRWPSCHCurrent reversal and weak-end infeed logic for residual over-current protection
ZC ZCPSCHScheme communication logic for residual overcurrent protection
ZCRW ZCRWPSCHCurrent reversal and weak-end infeed logic for distance protection
ZPC ZPCPSCH Phase segregated communication logic function
ZPCW ZPCWPSCHPhase Segregated Current reversal and weak-end infeed logic for distance protection
PSDE SDE SDEPSDESensitive Directional earth Fault Protection WEF
PTOC
BRC BRCPTOC Broken conductor monitoring
BR BRPTOC Binary release overcurrent protection
D2 PTOCOvercurrent protection used in two-step directional overcurrent function
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 26
LCNS LCNSPTOCNegative Sequence over current for local criteria
LCP3 LCP3PTOCThree phase over current LN for Local Criterion Check
LCZS LCZSPTOCZero sequence over current for local criteria
NS2 NS2PTOCNegativ phase sequence overcurrent protection, 2 Steps
PH1B PH1BPTOCSingle phase over-current protection 4 stages for Busbar
PH1 PH1PTOCOver-current protection used in four-stage protection function, one phase
PH3 PH3PTOCOver-current protection used in four-stage protection functions, three phase
SCCV SCCVPTOC Sudden change in current variation
STB STBPTOC Stub protection
PTOF SA SAPTOFSelectable over-and under-frequency function
PTOV
COUV COUVPTOVOver voltage for MAF of Compensated over and under voltage
GF2 GF2PTOVOver-voltage function for General Multipurpose protection
HOL HOLPTOVPTOV for Harmonic over load in IDMT stage capbankprot
HPH1 HPH1PTOVPTOV for Harmonic over load in DT stage capbankprot
LCNS LCNSPTOVNegative sequence over voltage for Local criteria
LCZS LCZSPTOVZero sequence over voltage for local criteria
OV2 OV2PTOVOver-voltage for 2 step over-volt protection
ROV2 ROV2PTOVOver-voltage function for 2 step over-volt protection
U2RW U2RWPTOVOver-voltage for 2 step over-volt protection
VDC VDCPTOV Voltage differential function (for US)
PTRC
BF BFPTRCBusbar differential protection, single phase feeder
BIC BICPTRCBusbar differential protection, bus interconnection
BUS BUSPTRCBusbar differential protection bay unit, 1 Phases
BUT BUTPTRCBusbar differential protection bay unit, 3 Phases
CBP CBPPTRC Trip Logic for Capacitor bank protection
EF2 EF2PTRC Trip logic for 2-stage earth fault protection
EF4 EF4PTRC Trip logic for 4-stage earth fault protection
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 27
L4C L4CPTRC PTRC for L4C
NS2 NS2PTRCTrip logic for Negativ phase sequence overcurrent protection, 2 Steps
LCCR LCCRPTRC Carrier receive logic for DTT
PH1 PH1PTRCTrip logic for aggregated functions, one phase
PH3 PH3PTRCTrip logic for aggregated functions, three phase
ZG ZGPTRC Trip logic for Distance Mho protection
ZMF ZMFPTRC Trip logic for Fast Distance protection
PTTR
GR GRPTTRRotor overload protection
GS GSPTTRStator overload protection
LC LCPTTRThermal overload 1 time constants (unit Celsius)
LF LFPTTRThermal overload 1 time constants (unit Fahrenheit)
SMP SMPPTRC Single, two or three pole tripping logic
TR TRPTTRThermal overload 2 time constants for transformers
PTUC
GF2 GF2PTUCUndercurrent for General Multipurpose protection
LCP3 LCP3PTUCUnder Current Protection LN for Local criterion check in DTT
PH3 PH3PTUC Undercurrent protection, three phase
PTUF
SA SAPTUFSelectable over-and under-frequency function
COUV COUVPTUFUnder voltage for MAF of Compensated over and under voltage
PTUV
COUV COUVPTUVUndervoltage function for Compensated over- and undervoltage protection
GF2 GF2PTUVUndervoltage function for General Multipurpose protection
LOV LOVPTUV Loss of Voltage Check Function
PH1 PH1PTUVUndervoltage function for General Multipurpose protection
U2RW U2RWPTUVUndervoltage function for 2 step undervolt protection
UV2 UV2PTUVUndervoltage function for 2 step undervolt protection
ZGV ZGVPTUV
Undervoltage function for Underimpedance protection for generators and transformers
PUPF LAPP LAPPPUPFUnder power factor protection LN for LAPP
PVOC GF2 GF2PVOCOvercurrent function for General Multipurpose protection
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 28
VR VRPVOCOvercurrent function for Voltage-restrained time overcurrent protection
PVPH OEX OEXPVPH Overexcitation protection
RBRF
CC CCRBRF Breaker failure protection
CCRW CCRWRBRF Breaker failure protection
CCS CCSRBRFBreaker failure protection single phase function
RDIR
EF2 EF2RDIRDirectional element used for 2-stage earth fault protection
EF4 EF4RDIRDirectional element used for 4-stage earth fault protection
RDRE DRP DRPRDRE Disturbance recorder
RFLO LMB LMBRFLO Fault locator
RPSB ZM ZMRPSB Power-swing detection
RREC SMB SMBRRECAutorecloser - 1-, 2-, and/or 3-phase, single circuit breaker, 1 1/2 or double circuit breaker
RSYN
AUT1 AUT1RSYN
Auto control of synchrocheck and energizing check, single circuit breaker, 11/2 or double circuit breaker, for automatic purpose
MAN1 MAN1RSYN
Manual control of synchrocheck and energizing check, single circuit breaker, 11/2 or double circuit breaker, for manual purpose
SYN SYNRSYNAuto control of synchrocheck and energizing check, single circuit breaker, 11/2 or double circuit breaker
SIMG S SSIMG Insulation gas monitoring function
SIML S SSIML Insulation liquid monitoring function
XCBR S SXCBR Circuit breaker
XSWI S SXSWI Circuit switch
YLTC
TCL TCLYLTC(large) Load Tap Changer, 32 Binary Input for tap
TCM TCMYLTC(mini) Load Tap Changer, 6 Binary Input for tap
3.2.1 PHPIOC
PIOC class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PIOC
Instantaneous non-
directional phase
overcurrent protection
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 29
Data
Common Logical Node Information
Mod ABB_aINC Mode M
Beh ABB_aINS Behaviour M
Health ABB_cINS Health M
NamPlt ABB_aLPL Name plate M
Status Information
Op ABB_aACT Operate M
3.2.2 PHPIOC Revision 1
PIOC class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PIOC
Instantaneous non-
directional phase
overcurrent protection
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Op ABB_b_dACT Operate M
3.2.3 AEGGAPC Revision 2
GAPC class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
GAPCAccidental energisation
protection for generator
Data
Common Logical Node Information
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 30
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Nam plate M
Status Information
Str ABB_b_dACD accidental energization
generator protection start
M
Armed ABB_v1_dSPS undervoltage activated E
Op ABB_b_dACT Accidental energization
generator protection
operate
M
3.2.4 PAPGAPC Revision 1
GAPC class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
GAPC Radial Feeder Protection
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Nam plate M
Status Information
Str ABB_b_dACD Start M
Op ABB_e_dACT Operate M
AutoRecStr ABB_v2_dSPS Start of auto reclosing E
ARStrTP ABB_v2_dSPS Start of auto reclosing,
three phase
E
3.2.5 STBPTOC
PTOC class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PTOC STUB protection
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 31
Data
Common Logical Node Information
Mod ABB_aINC Mode M
Beh ABB_aINS Behaviour M
Health ABB_cINS Health M
NamPlt ABB_aLPL Name plate M
Status Information
Str ABB_aACD Start M
Op ABB_aACT Trip M
3.2.6 COUVPTUV
PTUV class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PTUV
Under voltage for MAF of
Compensated over and
under voltage
Data
Common Logical Node Information
Mod ABB_c_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Str ABB_a_dACD Start M
Op ABB_a_dACT Operate M
3.2.7 COUVLLN0
LLN0 class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
LLN0 Logical node 0 (for COUV)
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 32
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_ln0_dLPL Name plate M
Status Information
3.2.8 COUVPTOV
PTOV class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PTOV
Over voltage for MAF of
Compensated over and
under voltage
Data
Common Logical Node Information
Mod ABB_c_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name Plate M
Status Information
Str ABB_a_dACD Start M
Op ABB_a_dACT Operate O
3.2.9 LCCRPTRC Revision 1
PTRC class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PTRC Carrier receive logic for DTT
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 33
Op ABB_a_dACT Operate (combination of
subscribed Op from
protection functions)
C
Str ABB_a_dACD Sum of all starts of all
connected Logical Nodes
O
3.2.10 SCILO
CILO class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
CILO Interlocking
Data
Common Logical Node Information
Mod ABB_aINC Mode M
Beh ABB_aINS Behaviour M
Health ABB_cINS Health M
NamPlt ABB_aLPL Name plate M
Status Information
EnaOpn ABB_aSPS Enable Open M
EnaCls ABB_aSPS Enable Close M
3.2.11 HZPDIF Revision 2
PDIF class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PDIF
Classic high impedance
differential protection,
external VDR
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Op ABB_b_dACT Trip signal M
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 34
Alm ABB_a_dSPS Alarm signal E
3.2.12 LAPPLLN0
LLN0 class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
LLN0
Logical node 0 (for
aggregated function
LAPP)
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_ln0_dLPL Name plate M
Status Information
3.2.13 LAPPPDUP
PDUP class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PDUP
Low Active power and power
factor protection for under
power
Data
Common Logical Node Information
Mod ABB_c_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Str ABB_a_dACD Start M
Op ABB_b_dACT Operate M
3.2.14 LAPPPUPF
PUPF class
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 35
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PUPFUnder power factor
protection LN for LAPP
Data
Common Logical Node Information
Mod ABB_c_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Str ABB_a_dACD Start M
Op ABB_a_dACT Operate M
3.2.15 ZPCPSCH
PSCH class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PSCHPhase segregated
communication logic function
Data
Common Logical Node Information
Mod ABB_aINC Mode M
Beh ABB_aINS Behaviour M
Health ABB_cINS Health M
NamPlt ABB_aLPL Name plate M
Status Information
ProTx ABB_aSPS Teleprotection signal
transmitted
M
ProRx ABB_aSPS Teleprotection signal
received
M
Str ABB_aACD Carrier Send M
Op ABB_aACT Operate M
CarRx ABB_aACT Carrier received after unblock
logic
O
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 36
3.2.16 ZPCWPSCH
PSCH class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PSCH
Phase Segregated Current
reversal and weak-end infeed
logic for distance protection
Data
Common Logical Node Information
Mod ABB_aINC Mode M
Beh ABB_aINS Behaviour M
Health ABB_cINS Health M
NamPlt ABB_aLPL Name plate M
Status Information
ProTx ABB_aSPS Teleprotection signal
transmitted
M
ProRx ABB_aSPS Teleprotection signal
received
M
Str ABB_aACD Carrier Send M
Op ABB_aACT Operate M
RvABlk ABB_aACT Block signal from current
reversal function
O
3.2.17 OV2PTOV
PTOV class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PTOVOvervoltage function for two-
step overvoltage protection
Data
Common Logical Node Information
Mod ABB_cINC Mode M
Beh ABB_aINS Behaviour M
Health ABB_cINS Health M
NamPlt ABB_aLPL Name Plate M
Status Information
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 37
Str ABB_aACD Start M
Op ABB_aACT Operate O
3.2.18 GEN2LLN0
LLN0 class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
LLN0Logical node 0 (for
aggregated function GEN2)
Data
Common Logical Node Information
Mod ABB_aINC Mode M
Beh ABB_aINS Behaviour M
Health ABB_cINS Health M
NamPlt ABB_ln0LPL Name plate M
Status Information
3.2.19 OOSPPAM Revision 1
PPAM class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PPAM Out of step protection
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Str ABB_b_dACD Start M
Op ABB_b_dACT Operate M
Zn1SlpDet ABB_v1_dSPS Trip 1 E
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 38
Zn2SlpDet ABB_v1_dSPS Trip 2 E
Gen ABB_v1_dSPS Generator mode E
Mot ABB_v1_dSPS Motor mode E
3.2.20 FMPSPDIS
PDIS class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PDIS Phase selection logic
Data
Common Logical Node Information
Mod ABB_aINC Mode M
Beh ABB_aINS Behaviour M
Health ABB_cINS Health M
NamPlt ABB_aLPL Name plate M
Status Information
Str ABB_aACD Start M
Op ABB_aACT Operate M
EFlt ABB_v1SPS Ground fault detected E
3.2.21 SLGGIO Revision 7
GGIO class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
GGIO Selector switch
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
IntIn ABB_b_dINS Integer status inputO
SPCCO ABB_v6_dSPC Raise/Lower CommandsE
Controllable
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 39
SwPosC1 ABB_v5_dISC Integer step controllable
output
EControllable
3.2.22 GENPDIF Revision 1
PDIF class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PDIFGenerator Differential
Protection
Data
Common Logical Node Information
Mod ABB_aINC Mode M
Beh ABB_aINS Behaviour M
Health ABB_cINS Health M
NamPlt ABB_aLPL Name plate M
Status Information
Str ABB_aACD Start O
Op ABB_bACT Operate M
BlkHPhA ABB_v1SPS Harmonic block L1 E
BlkHPhB ABB_v1SPS Harmonic block L2 E
BlkHPhC ABB_v1SPS Harmonic block L3 E
OpRst ABB_v1SPS tripRestrained E
OpUnRst ABB_v1SPS tripUnrestrained E
OpNSUnRst ABB_v1SPS tripNegSeqUnrestrained E
OpNSSen ABB_v1SPS tripNegSeqSensitive E
ItrFlt ABB_v1SPS InternalFault E
ExFlt ABB_v1SPS ExternalFault E
BlkH ABB_v1SPS harmonicBlock E
DifANS ABB_v2MV currDiffNegSeq E
RstMaxA ABB_v2MV currBias E
OpnCT ABB_v1SPS An open CT was detected E
OpnCTVal ABB_v1INS Open CT side : 1 -> Terminal
side, 2 -> Neutral side
E
OpnCTIn ABB_v1INS Open CT on Input : 1 for
input 1, 2 for input 2
E
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 40
OpnCTPh ABB_v1INS Open CT in Phase : 1 for L1,
2 for L2, 3 for L3
E
OpnCTAlm ABB_v1SPS Open CT Alarm output
signal. Issued after a delay
E
3.2.23 ZMHPDIS
PDIS class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PDIS Mho Distance function
Data
Common Logical Node Information
Mod ABB_aINC Mode M
Beh ABB_aINS Behaviour M
Health ABB_cINS Health M
NamPlt ABB_aLPL Name plate M
Status Information
Str ABB_aACD Start M
Op ABB_aACT Operate M
StrPP ABB_v1SPS Phase - phase start signal E
StrPh ABB_v1SPS Phase - earth start signal E
OpPP ABB_v1SPS Phase - phase trip signal E
OpPh ABB_v1SPS Phase - earth trip signal E
3.2.24 ZSMGAPC Revision 2
GAPC class
Attribute
Name
DATA
TypeExplanation
M/O/
E/CRemarks
GAPC
Impedance supervision
logic for Mho Distance
function
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 41
NamPlt ABB_a_dLPL Name plate M
Status Information
StopCarTx ABB_v1_dSPS Stops the blocking signal to
remote end
E
BlkTDmnImp ABB_v1_dSPS Block signal for blocking of
time domained mho
E
CarTcBlk ABB_v1_dSPS Blocking signal to remote
end to block overreaching
zone
E
FLtIncp ABB_v1_dSPS Fault inception detected for
any phase voltage
E
IndHiSIR ABB_v1_dSPS Indication of source
impedance ratio above set
limit
E
3.2.25 SMPPTRC Revision 3
PTRC class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PTRC Trip logic
Data
Common Logical Node Information
Mod ABB_aINC Mode M
Beh ABB_aINS Behaviour M
Health ABB_cINS Health M
NamPlt ABB_aLPL Name plate M
Status Information
Op ABB_a_dACT Operate (combination of
subscribed Op from
protection functions)
C
Str ABB_a_dACD Start O
LORs ABB_v1_dSPC Reset Lockout E Controllable
SPTr ABB_v1_dSPS Single Pole Trip E
TwoPTr ABB_v1_dSPS Two Pole Trip E
TPTr ABB_v1_dSPS Three Pole Trip E
ClsLO ABB_v1_dSPS Close Lockout E
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 42
3.2.26 STSGGIO
GGIO class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
GGIOStartupscheme function
for Differential protection
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Startup ABB_v1_dSPS Startup signal output E
StUpCV1 ABB_v1_dSPS Startup for current
variation phase 23
E
StUpCV2 ABB_v1_dSPS Startup for current
variation phase 31
E
StUpCV3 ABB_v1_dSPS Startup for current
variation phase 12
E
StUpZroA ABB_v1_dSPS Startup for zero seq
current
E
StUpLoVol ABB_v1_dSPS Startup for Low voltage
signal
E
StUpLoCurr ABB_v1_dSPS Startup for Low current
signal
E
3.2.27 LDLPDIF
PDIF class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PDIFLogical element for line
differential function
Data
Common Logical Node Information
Mod ABB_aINC Mode M
Beh ABB_aINS Behaviour M
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 43
Health ABB_cINS Health M
NamPlt ABB_aLPL Name plate M
Status Information
Op ABB_aACT Operate M
OpLoc ABB_v1ACT Operation local differential
function
E
OpRem ABB_v2ACT Operation from remote
differential function
E
LocDifBlk ABB_v1SPS Local differential function
blocked
E
3.2.28 CCRBRF
RBRF class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
RBRF Breaker failure protection
Data
Common Logical Node Information
Mod ABB_aINC Mode M
Beh ABB_aINS Behaviour M
Health ABB_cINS Health M
NamPlt ABB_aLPL Name plate M
Status Information
OpEx ABB_bACT Breaker failure trip (external
trip)
C
OpIn ABB_aACT Operate, retrip (internal trip) C
OpEx2 ABB_v2ACT Extarnal trip E
3.2.29 CCRWRBRF
RBRF class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
RBRF Breaker failure protection
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 44
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
OpEx ABB_b_dACT Breaker failure trip (external
trip)
C
OpIn ABB_a_dACT Operate, retrip (internal trip) C
3.2.30 EFPIOC
PIOC class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PIOC
Instantaneous non-directional
residual overcurrent
protection
Data
Common Logical Node Information
Mod ABB_aINC Mode M
Beh ABB_aINS Behaviour M
Health ABB_cINS Health M
NamPlt ABB_aLPL Name plate M
Status Information
Op ABB_bACT Operate M
3.2.31 CVMMXN Revision 1
MMXN class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
MMXNService value reading of
power
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 45
NamPlt ABB_a_dLPL Name plate M
Status Information
Amp ABB_a_dMV Current I (rms) not allocated
to a phase
O
Vol ABB_a_dMV Voltage V (rms) not allocated
to a phase
O
Watt ABB_a_dMV Power (P) not allocated to a
phase
O
VolAmpr ABB_a_dMV Reactive Power (Q) not
allocated to a phase
O
VolAmp ABB_a_dMV Apparent Power (S) not
allocated to a phase
O
PwrFact ABB_a_dMV Power Factor not allocated to
a phase
O
Hz ABB_a_dMV Frequency O
ALd ABB_v1_dSPS Current is leading voltage E
ALg ABB_v1_dSPS Current is lagging voltage E
3.2.32 SCCVPTOC
PTOC class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PTOCSudden change in current
variation
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Str ABB_b_dACD Start M
Op ABB_b_dACT Operate M
3.2.33 ZGVPDIS
PDIS class
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 46
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PDISunderZ for distance
protection LN
Data
Common Logical Node Information
Mod ABB_c_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Str ABB_b_dACD Start M
Op ABB_b_dACT Operate M
3.2.34 ZGVLLN0
LLN0 class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
LLN0 underZ for general LN
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_ln0_dLPL Name plate M
Status Information
3.2.35 ZGVPTUV
PTUV class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PTUVunderV seal in for distance
protection LN
Data
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 47
Common Logical Node Information
Mod ABB_c_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Str ABB_b_dACD Start M
Op ABB_b_dACT Operate M
3.2.36 LCNSPTOC
PTOC class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PTOCNegative Sequence over
current for local criteria
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Str ABB_d_dACD Start M
Op ABB_b_dACT Operate M
3.2.37 LCNSPTOV
PTOV class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PTOVNegatavie sequence over
voltage for Local criteria
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 48
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name Plate M
Status Information
Str ABB_d_dACD Start M
Op ABB_b_dACT Trip Signal E
3.2.38 LCZSPTOV
PTOV class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PTOVZero sequence over voltage
for local criteria
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name Plate M
Status Information
Str ABB_d_dACD Start M
Op ABB_b_dACT Operate O
3.2.39 LCZSPTOC
PTOC class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PTOCZero sequence over current
for local criteria
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 49
Str ABB_d_dACD Start M
Op ABB_b_dACT Operate M
3.2.40 ZMCAPDIS
PDIS class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PDIS
Full-scheme distance
measuring zone for series
compensation, additional
zones
Data
Common Logical Node Information
Mod ABB_aINC Mode M
Beh ABB_aINS Behaviour M
Health ABB_cINS Health M
NamPlt ABB_aLPL Name plate M
Status Information
Str ABB_aACD Start M
Op ABB_aACT Operate M
StrNDir ABB_v1SPS Non-directional start, issued
from any phase or loop
E
3.2.41 ZMCPDIS
PDIS class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PDIS
Full-scheme distance
measuring zone for series
compensation, quadrilateral
characteristic, Zone 1
Data
Common Logical Node Information
Mod ABB_aINC Mode M
Beh ABB_aINS Behaviour M
Health ABB_cINS Health M
NamPlt ABB_aLPL Name plate M
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 50
Status Information
Str ABB_aACD Start M
Op ABB_aACT Operate M
StrNDir ABB_v1SPS Non-directional start, issued
from any phase or loop
E
3.2.42 ZMMAPDIS
PDIS class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PDISFull-scheme distance
measuring zone, additional
Data
Common Logical Node Information
Mod ABB_aINC Mode M
Beh ABB_aINS Behaviour M
Health ABB_cINS Health M
NamPlt ABB_aLPL Name plate M
Status Information
Str ABB_aACD Start M
Op ABB_aACT Operate M
StrNDir ABB_v1SPS Non-directional start, issued
from any phase or loop
E
3.2.43 FDPSPDIS Revision 2
PDIS class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PDIS
Combined phase selection
and general fault-criteria,
impedance and current
based
Data
Common Logical Node Information
Mod ABB_aINC Mode M
Beh ABB_aINS Behaviour M
Health ABB_cINS Health M
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 51
NamPlt ABB_aLPL Name plate M
Status Information
Str ABB_aACD Start M
Op ABB_bACT Operate M
StrFwdPhA ABB_v1SPS Fault detected in phase L1 -
forward direction
E
StrFwdPhB ABB_v1SPS Fault detected in phase L2 -
forward direction
E
StrFwdPhC ABB_v1SPS Fault detected in phase L3 -
forward direction
E
StrFwdGnd ABB_v1SPS Earth fault detected in
forward direction
E
StrRvPhA ABB_v1SPS Fault detected in phase L1 -
reverse direction
E
StrRvPhB ABB_v1SPS Fault detected in phase L2 -
reverse direction
E
StrRvPhC ABB_v1SPS Fault detected in phase L3 -
reverse direction
E
StrRvGnd ABB_v1SPS Earth fault detected in
reverse direction
E
StrNDPhA ABB_v1SPS Fault detected in phase L1-
non directional
E
StrNDPhB ABB_v1SPS Fault detected in phase L2-
non directional
E
StrNDPhC ABB_v1SPS Fault detected in phase L3-
non directional
E
StrNDGnd ABB_v1SPS Earth fault detected- non
directional
E
Str1Ph ABB_v1SPS Single-phase fault detected
in forward direction
E
Str2Ph ABB_v1SPS Two-phase fault detected in
forward direction
E
Str3Ph ABB_v1SPS Three-phase fault detected in
forward direction
E
RelGnd ABB_v1SPS Current conditions release of
phase-to-earth measuring
elements
E
RelPP ABB_v1SPS Current conditions release of
phase-to-phase measuring
E
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 52
elements
StrCndZ ABB_v1INS Start condition (PHS,LE and I
based)
E
StrCndA ABB_v1INS Start condition (LE and I
based)
E
3.2.44 FPSRPDIS
PDIS class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PDIS
Combined phase selection
and general fault-criteria,
impedance and current
based
Data
Common Logical Node Information
Mod ABB_aINC Mode M
Beh ABB_aINS Behaviour M
Health ABB_cINS Health M
NamPlt ABB_aLPL Name plate M
Status Information
Str ABB_aACD Start M
Op ABB_bACT Operate M
StrFwdPhA ABB_v1SPS Fault detected in phase L1 -
forward direction
E
StrFwdPhB ABB_v1SPS Fault detected in phase L2 -
forward direction
E
StrFwdPhC ABB_v1SPS Fault detected in phase L3 -
forward direction
E
StrFwdGnd ABB_v1SPS Earth fault detected in
forward direction
E
StrRvPhA ABB_v1SPS Fault detected in phase L1 -
reverse direction
E
StrRvPhB ABB_v1SPS Fault detected in phase L2 -
reverse direction
E
StrRvPhC ABB_v1SPS Fault detected in phase L3 -
reverse direction
E
StrRvGnd ABB_v1SPS Earth fault detected in E
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 53
reverse direction
StrNDPhA ABB_v1SPS Fault detected in phase L1-
non directional
E
StrNDPhB ABB_v1SPS Fault detected in phase L2-
non directional
E
StrNDPhC ABB_v1SPS Fault detected in phase L3-
non directional
E
StrNDGnd ABB_v1SPS Earth fault detected- non
directional
E
Str1Ph ABB_v1SPS Single-phase fault detected
in forward direction
E
Str2Ph ABB_v1SPS Two-phase fault detected in
forward direction
E
Str3Ph ABB_v1SPS Three-phase fault detected in
forward direction
E
RelGnd ABB_v1SPS Current conditions release of
phase-to-earth measuring
elements
E
RelPP ABB_v1SPS Current conditions release of
phase-to-phase measuring
elements
E
StrCndZ ABB_v1INS Start condition (PHS,LE and I
based)
E
StrCndA ABB_v1INS Start condition (LE and I
based)
E
3.2.45 ZMMPDIS
PDIS class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PDIS
Full-scheme distance
measuring zone,
quadrilateral characteristic
Data
Common Logical Node Information
Mod ABB_aINC Mode M
Beh ABB_aINS Behaviour M
Health ABB_cINS Health M
NamPlt ABB_aLPL Name plate M
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 54
Status Information
Str ABB_aACD Start M
Op ABB_aACT Operate M
StrNDir ABB_v1SPS Non-directional start, issued
from any phase or loop
E
3.2.46 ZMRAPDIS
PDIS class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PDISFull-scheme distance
measuring zone,Quadilateral
Data
Common Logical Node Information
Beh ABB_aINS Behaviour M
Health ABB_cINS Health M
Mod ABB_aINC Mode M
NamPlt ABB_aLPL Name plate M
Status Information
Op ABB_aACT Operate M
Str ABB_aACD Start M
StrNDir ABB_v1SPS Non-directional start, issued
from any phase or loop
E
3.2.47 ZMRPDIS
PDIS class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PDISFull-scheme distance
measuring zone,Quadilateral
Data
Common Logical Node Information
Mod ABB_aINC Mode M
Beh ABB_aINS Behaviour M
Health ABB_cINS Health M
NamPlt ABB_aLPL Name plate M
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 55
Status Information
Str ABB_aACD Start M
Op ABB_aACT Operate M
StrNDir ABB_v1SPS Non-directional start, issued
from any phase or loop
E
3.2.48 ZMQAPDIS
PDIS class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PDIS
Full-scheme distance
measuring zone, additional
zones
Data
Common Logical Node Information
Mod ABB_aINC Mode M
Beh ABB_aINS Behaviour M
Health ABB_cINS Health M
NamPlt ABB_aLPL Name plate M
Status Information
Str ABB_aACD Start M
Op ABB_aACT Operate M
StrNDir ABB_v1SPS Non-directional start, issued
from any phase or loop
E
3.2.49 ZMQPDIS
PDIS class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PDIS
Full-scheme distance
measuring zone,
quadrilateral characteristic,
Zone 1
Data
Common Logical Node Information
Mod ABB_aINC Mode M
Beh ABB_aINS Behaviour M
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 56
Health ABB_cINS Health M
NamPlt ABB_aLPL Name plate M
Status Information
Str ABB_aACD Start M
Op ABB_aACT Operate M
StrNDir ABB_v1SPS Non-directional start, issued
from any phase or loop
E
3.2.50 BUSPTRC
PTRC class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PTRCBusbar differential protection
bay unit, 1 Phases
Data
Common Logical Node Information
Mod ABB_cINC Mode M
Beh ABB_aINS Behaviour M
Health ABB_cINS Health M
NamPlt ABB_aLPL Name plate M
Status Information
Tr ABB_bACT Trip C
Zn1 ABB_v1SPS Bay is connected to zone A E
Zn2 ABB_v1SPS Bay is connected to zone B E
3.2.51 BBSPLLN0
LLN0 class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
LLN0 Logical node 0 (for BBSP)
Data
Common Logical Node Information
Mod ABB_aINC Mode M
Beh ABB_aINS Behaviour M
Health ABB_cINS Health M
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 57
NamPlt ABB_ln0LPL Name plate M
Status Information
3.2.52 BCZSPDIF
PDIF class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PDIFBusbar differential protection
check zone, 1 Phases
Data
Common Logical Node Information
Mod ABB_cINC Mode M
Beh ABB_aINS Behaviour M
Health ABB_cINS Health M
NamPlt ABB_aLPL Name plate M
Status Information
Op ABB_bACT Operate M
3.2.53 BZNSPDIF Revision 1
PDIF class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PDIFBusbar differential protection
zone, 1 Phases
Data
Common Logical Node Information
Mod ABB_cINC Mode M
Beh ABB_aINS Behaviour M
Health ABB_cINS Health M
NamPlt ABB_aLPL Name plate M
Status Information
Op ABB_bACT Operate M
IndOpExBay ABB_v1SPS Zone trip due to external trip
from one of the connected
bays
E
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 58
IndOpExZn ABB_v1SPS Zone trip due to external
input signal
E
IndOpSen ABB_v1SPS Sensitive differential function
start
E
OpnCTAlm ABB_v1SPS General open CT alarm E
ADifAlm ABB_v1SPS Differential current alarm E
OpRs ABB_v1SPC Trip reset used by command
handling
E Controllable
OpnCTRs ABB_v1SPC Open CT reset used by
command handling
E Controllable
IndOpDif ABB_v1SPS Differential trip E
RstA ABB_g_dWYE Restraint Current, Sum of
incomming currents if Zone,
RMS value, Value in phsA
O
DifAClc ABB_g_dWYE Differential Current, between
incoming and outhoing of
Zone, non phase related
RMS value, value in phsA
O
3.2.54 BZISGGIO
GGIO class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
GGIO
Busbar differential
protection zone
interconnection, 1 Phase
Data
Common Logical Node Information
Mod ABB_cINC Mode M
Beh ABB_aINS Behaviour M
Health ABB_cINS Health M
NamPlt ABB_aLPL Name plate M
Status Information
Alm ABB_bSPS General single alarm O
Act ABB_v1SPS Load Transfer/Zone
Interconnection active
E
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 59
3.2.55 SMBRREC Revision 1
RREC class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
RREC Autorecloser
Data
Common Logical Node Information
Mod ABB_aINC Mode M
Beh ABB_aINS Behaviour M
Health ABB_cINS Health M
NamPlt ABB_aLPL Name plate M
Status Information
BlkRec ABB_bSPC Block AR/The AR is in
blocked state
O Controllable
Op ABB_bACT Operate (used here to
provide close to XCBR)
M
AutoRecSt ABB_dINS Auto Reclosing Status M
OpRs ABB_v1SPC Reset counters E Controllable
RdyRec ABB_v1SPS Indicates that the AR function
is ready for a new sequence
E
ActRec ABB_v1SPS Reclosing sequence in
progress
E
SucRec ABB_v1SPS Activated if CB closes during
the time tUnsucCl
E
UnsRec ABB_v1SPS Reclosing unsuccessful,
signal resets after the reclaim
time
E
PrgRec ABB_v1SPS Reclosing shot in progress,
activated during open time
E
PrgRec11 ABB_v1SPS Single-phase reclosing is in
progress, shot 1
E
PrgRec21 ABB_v1SPS Two-phase reclosing is in
progress, shot 1
E
PrgRec31 ABB_v1SPS Three-phase reclosing is in
progress, shot 1
E
PrgRec32 ABB_v1SPS Three-phase reclosing is in
progress, shot 2
E
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 60
PrgRec33 ABB_v1SPS Three-phase reclosing is in
progress, shot 3
E
PrgRec34 ABB_v1SPS Three-phase reclosing is in
progress, shot 4
E
PrgRec35 ABB_v1SPS Three-phase reclosing is in
progress, shot 5
E
Prm1PhOp ABB_v1SPS Permit single-phase trip,
inverse signal to PREP3P
E
Prp3PhOp ABB_v1SPS Prepare three-phase trip,
control of the next trip
opreation
E
WtMst ABB_v1SPS Signal to Slave issued by
MAster for sequential
reclosing
E
Rec1PhCnt ABB_v1INS Counting the number of
single-phase reclosing shots
E
Rec2PhCnt ABB_v1INS Counting the number of two-
phase reclosing shots
E
Rec31Cnt ABB_v1INS Counting the number of
three-phase reclosing shot 1
E
Rec32Cnt ABB_v1INS Counting the number of
three-phase reclosing shot 2
E
Rec33Cnt ABB_v1INS Counting the number of
three-phase reclosing shot 3
E
Rec34Cnt ABB_v1INS Counting the number of
three-phase reclosing shot 4
E
Rec35Cnt ABB_v1INS Counting the number of
three-phase reclosing shot 5
E
TotRecCnt ABB_v1INS Counting total number of
reclosing shots
E
EnaRec ABB_v1SPS Reclose enabled E
3.2.56 LCP3PTOC
PTOC class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PTOCThree phase over current LN
for Local Criterion Check
Data
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 61
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Str ABB_a_dACD Start M
Op ABB_a_dACT Operate M
3.2.57 LCP3PTUC
PTUC class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PTUC
Under Current Protection LN
for Local criterion check in
DTT
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Str ABB_a_dACD Start M
Op ABB_a_dACT Operate M
3.2.58 ZMFCLLN0
LLN0 class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
LLN0LLN0 for Fast Distance
Protection (advanced)
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 62
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_ln0_dLPL Name plate M
Status Information
3.2.59 PSFPDIS
PDIS class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PDISPhase selection for Fast
Distance Protection
Data
Common Logical Node Information
Mod ABB_c_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Str ABB_a_dACD Start M
Op ABB_a_dACT Operate M
3.2.60 ZMFPDIS
PDIS class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PDISMeasuring zone for Fast
Distance Protection
Data
Common Logical Node Information
Mod ABB_c_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Str ABB_b_dACD Start M
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 63
Op ABB_b_dACT Operate M
3.2.61 ZMFPDIS Revision 1
PDIS class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PDISMeasuring zone for Fast
Distance Protection
Data
Common Logical Node Information
Mod ABB_c_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Str ABB_b_dACD Start M
Op ABB_a_dACT Operate M
3.2.62 ZMFPTRC
PTRC class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PDISTrip matrix for Fast Distance
Protection
Data
Common Logical Node Information
Mod ABB_c_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Str ABB_a_dACD Sum of all starts of all
connected Logical Nodes
O
Op ABB_a_dACT Operate (combination of
subscribed Op from
protection functions)
C
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 64
3.2.63 ZMMMXU Revision 3
MMXU class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
MMXU Impedance monitoring
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Z ABB_m_dWYE Phase impedance O
3.2.64 ZMFLLN0
LLN0 class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
LLN0LLN0 for Fast Distance
Protection (basic)
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_ln0_dLPL Name plate M
Status Information
3.2.65 LT6CPDIF Revision 2
PDIF class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PDIF
Line differential protection,
phase segregated including
add-on for transformer in
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 65
protected zone
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Str ABB_a_dACD Common, main, start output signal
O
Op ABB_a_dACT Operate M
Blk2HPhB ABB_v1_dSPS Block signal due to 2nd harmonic, phase L2
E
Blk2HPhC ABB_v1_dSPS Block signal due to 2nd harmonic, phase L3
E
Blk5HPhA ABB_v1_dSPS Block signal due to 5th harmonic, phase L1
E
Blk5HPhB ABB_v1_dSPS Block signal due to 5th harmonic, phase L2
E
Blk5HPhC ABB_v1_dSPS Block signal due to 5th harmonic, phase L3
E
Blk2H ABB_v1_dSPS Common, block, due to 2-nd harmonic
E
Blk5H ABB_v1_dSPS Common, block, due to 5-th harmonic
E
ExFlt ABB_v1_dSPS External fault has been detected
E
ItrFlt ABB_v1_dSPS Internal fault has been detected
E
StrNSUnRst ABB_v1_dSPS Trip by enhanced restrained differential protection
E
StrRst ABB_v1_dSPS Trip by restrained differential protection
E
StrUnRst ABB_v1_dSPS Trip by unrestrained differential protection
E
OpnCT ABB_v1_dSPS An open CT was detected E
OpnCTAlm ABB_v1_dSPS Open CT Alarm output signal. Issued after a delay ...
E
OpnCTIn ABB_v1_dINS Open CT on Input : 1 for input 1, 2 for input 2
E
OpnCTPh ABB_v1_dINS Open CT in Phase : 1 for L1, 2 for L2, 3 for L3
E
Blk2HPhA ABB_v1_dSPS Block signal due to 2nd harmonic, phase L1
E
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 66
3.2.66 L6CPDIF Revision 2
PDIF class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PDIFLine differential protection,
phase segregated
Data
Common Logical Node Information
Mod ABB_aINC Mode M
Beh ABB_aINS Behaviour M
Health ABB_cINS Health M
NamPlt ABB_aLPL Name plate M
Status Information
Str ABB_a_dACD Common, main, start output
signal
O
Op ABB_a_dACT Common, main, trip output
signal
M
Blk2HPhA ABB_v1_dSPS Block signal due to 2nd
harmonic, phase L1
E
Blk2HPhB ABB_v1_dSPS Block signal due to 2nd
harmonic, phase L2
E
Blk2HPhC ABB_v1_dSPS Block signal due to 2nd
harmonic, phase L3
E
Blk5HPhA ABB_v1_dSPS Block signal due to 5th
harmonic, phase L1
E
Blk5HPhB ABB_v1_dSPS Block signal due to 5th
harmonic, phase L2
E
Blk5HPhC ABB_v1_dSPS Block signal due to 5th
harmonic, phase L3
E
Blk2H ABB_v1_dSPS Common, block, due to 2-nd
harmonic
E
Blk5H ABB_v1_dSPS Common, block, due to 5-th
harmonic
E
ExFlt ABB_v1_dSPS External fault has been
detected
E
ItrFlt ABB_v1_dSPS Internal fault has been
detected
E
StrNSUnRst ABB_v1_dSPS Trip by enhanced restrained E
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 67
differential protection
StrRst ABB_v1_dSPS Trip by restrained differential
protection
E
StrUnRst ABB_v1_dSPS Trip by unrestrained
differential protection
E
OpnCT ABB_v1_dSPS An open CT was detected E
OpnCTAlm ABB_v1_dSPS Open CT Alarm output
signal. Issued after a delay ...
E
OpnCTIn ABB_v1_dINS Open CT on Input : 1 for
input 1, 2 for input 2
E
OpnCTPh ABB_v1_dINS Open CT in Phase : 1 for L1,
2 for L2, 3 for L3
E
3.2.67 LT3CPDIF Revision 2
PDIF class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PDIF
Line differential protection,
phase segregated including
add-on for transformer in
protected zone
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Str ABB_a_dACD Common, main, start output signal
O
Op ABB_a_dACT Operate M
Blk2HPhA ABB_v1_dSPS Block signal due to 2nd harmonic, phase L1
E
Blk2HPhB ABB_v1_dSPS Block signal due to 2nd harmonic, phase L2
E
Blk2HPhC ABB_v1_dSPS Block signal due to 2nd harmonic, phase L3
E
Blk5HPhA ABB_v1_dSPS Block signal due to 5th harmonic, phase L1
E
Blk5HPhB ABB_v1_dSPS Block signal due to 5th harmonic, phase L2
E
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 68
Blk5HPhC ABB_v1_dSPS Block signal due to 5th harmonic, phase L3
E
Blk2H ABB_v1_dSPS Common, block, due to 2-nd harmonic
E
Blk5H ABB_v1_dSPS Common, block, due to 5-th harmonic
E
ExFlt ABB_v1_dSPS External fault has been detected
E
ItrFlt ABB_v1_dSPS Internal fault has been detected
E
StrNSUnRst ABB_v1_dSPS Trip by enhanced restrained differential protection
E
StrRst ABB_v1_dSPS Trip by restrained differential protection
E
StrUnRst ABB_v1_dSPS Trip by unrestrained differential protection
E
OpnCT ABB_v1_dSPS An open CT was detected E
OpnCTAlm ABB_v1_dSPS Open CT Alarm output signal. Issued after a delay ...
E
OpnCTIn ABB_v1_dINS Open CT on Input : 1 for input 1, 2 for input 2
E
OpnCTPh ABB_v1_dINS Open CT in Phase : 1 for L1, 2 for L2, 3 for L3
E
3.2.68 L3CPDIF Revision 2
PDIF class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PDIFLine differential protection,
phase segregated
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Str ABB_a_dACD Common, main, start output signal
O
Op ABB_a_dACT Common, main, trip output signal
M
Blk2HPhA ABB_v1_dSPS Block signal due to 2nd harmonic, phase L1
E
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 69
Blk2HPhB ABB_v1_dSPS Block signal due to 2nd harmonic, phase L2
E
Blk2HPhC ABB_v1_dSPS Block signal due to 2nd harmonic, phase L3
E
Blk5HPhA ABB_v1_dSPS Block signal due to 5th harmonic, phase L1
E
Blk5HPhB ABB_v1_dSPS Block signal due to 5th harmonic, phase L2
E
Blk5HPhC ABB_v1_dSPS Block signal due to 5th harmonic, phase L3
E
Blk2H ABB_v1_dSPS Common, block, due to 2-nd harmonic
E
Blk5H ABB_v1_dSPS Common, block, due to 5-th harmonic
E
ExFlt ABB_v1_dSPS External fault has been detected
E
ItrFlt ABB_v1_dSPS Internal fault has been detected
E
StrNSUnRst ABB_v1_dSPS Trip by enhanced restrained differential protection
E
StrRst ABB_v1_dSPS Trip by restrained differential protection
E
StrUnRst ABB_v1_dSPS Trip by unrestrained differential protection
E
OpnCT ABB_v1_dSPS Open Current Transformer E
OpnCTIn ABB_v1_dINS Open CT on Input : 1 for input 1, 2 for input 2
E
OpnCTPh ABB_v1_dINS Open CT in Phase : 1 for L1, 2 for L2, 3 for L3
E
OpnCTAlm ABB_v1_dSPS Open CT Alarm output signal. Issued after a delay ...
E
3.2.69 SSIMG Revision 1
SIMG class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
SIMG Insulation gas monitoring
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 70
NamPlt ABB_a_dLPL Name plate M
Status Information
Pres ABB_b_dMV Isolation gas pressure O
Tmp ABB_b_dMV Isolation gas temperature O
InsAlm ABB_a_dSPS Isolation gas critical ( refill
isolation medium )
M
InsBlk ABB_a_dSPS Isolation gas not safe (refill
isolation medium)
O
PresAlm ABB_a_dSPS Isolation gas pressure alarm O
TmpAlm ABB_a_dSPS Isolation gas temperature
alarm
O
LORs ABB_v1_dSPC Reset of lockout E Controllable
3.2.70 SSIML Revision 1
SIML class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
SIML Insulation liquid monitoring
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Tmp ABB_b_dMV Isolation Liquid Temperature E
Pres ABB_b_dMV Isolation Liquid Pressure E
InsAlm ABB_a_dSPS Insulation liquid critical ( refill isolation medium )
M
InsBlk ABB_a_dSPS Isolation gas not safe (refill
isolation medium)
O
TmpAlm ABB_a_dSPS Insulation liquid temperature alarm
O
PresAlm ABB_a_dSPS Insulation liquid pressure alarm
O
LORs ABB_v1_dSPC Reset of lockout E Controllable
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 71
3.2.71 T2WPDIF Revision 1
PDIF class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PDIFTransformer Differential
protection, two winding
Data
Common Logical Node Information
Mod ABB_aINC Mode M
Beh ABB_aINS Behaviour M
Health ABB_cINS Health M
NamPlt ABB_aLPL Name plate M
Status Information
Str ABB_aACD Main, common start signal O
Op ABB_bACT Main, common trip command M
Blk2HPhA ABB_v1SPS Second harmonic block signal, phase L1
E
Blk2HPhB ABB_v1SPS Second harmonic block signal, phase L2
E
Blk2HPhC ABB_v1SPS Second harmonic block signal, phase L3
E
Blk5HPhA ABB_v1SPS Fifth harmonic block signal, phase L1
E
Blk5HPhB ABB_v1SPS Fifth harmonic block signal, phase L2
E
Blk5HPhC ABB_v1SPS Fifth harmonic block signal, phase L3
E
BlkWavPhA ABB_v1SPS Block signal, waveform criterion, phase L1
E
BlkWavPhB ABB_v1SPS Block signal, waveform criterion, phase L2
E
BlkWavPhC ABB_v1SPS Block signal, waveform criterion, phase L3
E
OpRst ABB_v1SPS Trip request signal from restrained differential protection
E
OpNSSen ABB_v1SPS Trip request from negative sequence sensitive differential protection
E
OpNSUnRst ABB_v1SPS Trip request from negative sequence unrestrained differential protection
E
OpUnRst ABB_v1SPS Trip request signal from unrestrained differential
E
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 72
protection
Blk2H ABB_v1SPS Common second harmonic block signal
E
Blk5H ABB_v1SPS Common fifth harmonic block signal
E
BlkWav ABB_v1SPS Common block signal, waveform criterion
E
ExFlt ABB_v1SPS Binary output signal, external fault detected
E
ItrFlt ABB_v1SPS Binary output signal, internal fault detected
E
OpnCT ABB_v1SPS An open CT was detected E
OpnCTVal ABB_v1INS Open CT side : 1 -> W 1 (pri), 2 -> W 2 (sec), 3 -> W 3
E
OpnCTIn ABB_v1INS Open CT on Input : 1 for input 1, 2 for input 2
E
OpnCTPh ABB_v1INS Open CT in Phase : 1 for L1, 2 for L2, 3 for L3
E
OpnCTAlm ABB_v1SPS Open CT Alarm output signal. Issued after a delay
E
DifAlm ABB_v1SPS Alarm for sustained differential current
E
3.2.72 T3WPDIF Revision 1
PDIF class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PDIFTransformer Differential
protection, three winding
Data
Common Logical Node Information
Mod ABB_aINC Mode M
Beh ABB_aINS Behaviour M
Health ABB_cINS Health M
NamPlt ABB_aLPL Name plate M
Status Information
Str ABB_aACD Main, common start signal O
Op ABB_bACT Main, common trip command M
Blk2HPhA ABB_v1SPS Second harmonic block
signal, phase L1
E
Blk2HPhB ABB_v1SPS Second harmonic block
signal, phase L2
E
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 73
Blk2HPhC ABB_v1SPS Second harmonic block
signal, phase L3
E
Blk5HPhA ABB_v1SPS Fifth harmonic block signal,
phase L1
E
Blk5HPhB ABB_v1SPS Fifth harmonic block signal,
phase L2
E
Blk5HPhC ABB_v1SPS Fifth harmonic block signal,
phase L3
E
BlkWavPhA ABB_v1SPS Block signal, waveform
criterion, phase L1
E
BlkWavPhB ABB_v1SPS Block signal, waveform
criterion, phase L2
E
BlkWavPhC ABB_v1SPS Block signal, waveform
criterion, phase L3
E
OpRst ABB_v1SPS Trip request signal from
restrained differential
protection
E
OpNSSen ABB_v1SPS Trip request from negative
sequence sensitive
differential protection
E
OpNSUnRst ABB_v1SPS Trip request from negative
sequence unrestrained
differential protection
E
OpUnRst ABB_v1SPS Trip request signal from
unrestrained differential
protection
E
Blk2H ABB_v1SPS Common second harmonic
block signal
E
Blk5H ABB_v1SPS Common fifth harmonic block
signal
E
BlkWav ABB_v1SPS Common block signal,
waveform criterion
E
ExFlt ABB_v1SPS Binary output signal, external
fault detected
E
ItrFlt ABB_v1SPS Binary output signal, internal
fault detected
E
OpnCT ABB_v1SPS An open CT was detected E
OpnCTVal ABB_v1INS Open CT side : 1 -> W 1
(pri), 2 -> W 2 (sec), 3 -> W 3
E
OpnCTIn ABB_v1INS Open CT on Input : 1 for E
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 74
input 1, 2 for input 2
OpnCTPh ABB_v1INS Open CT in Phase : 1 for L1,
2 for L2, 3 for L3
E
OpnCTAlm ABB_v1SPS Open CT Alarm output
signal. Issued after a delay
E
DifAlm ABB_v1SPS Alarm for sustained
differential current
E
3.2.73 GRPTTR Revision 1
PTTR class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PTTR Rotor overload protection
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Str ABB_b_dACD Start O
Op ABB_b_dACT Operate M
BlkGnStr ABB_v1_dSPS Block machine closing
command
E
TmpPct ABB_v2_dMV Overload in percent of set trip
level
E
LO ABB_v1_dSPS Trip lockout output E
AlmRpl ABB_v1_dSPS Ripple alarm E
OpAUn ABB_v2_dACT Under current trip signal E
StrAUn ABB_v2_dACD Under current start signal E
3.2.74 GSPTTR Revision 1
PTTR class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PTTR Stator overload protection
Data
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 75
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Str ABB_b_dACD Start O
Op ABB_b_dACT Operate M
BlkGnStr ABB_v1_dSPS Block machine closing
command
E
TmpPct ABB_v2_dMV Overload in percent of set trip
level
E
LO ABB_v1_dSPS Trip lockout output E
3.2.75 CBPLLN0 Revision 1
LLN0 class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
LLN0 Logical node 0 (for CBP)
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_ln0_dLPL Name plate M
Status Information
3.2.76 CBPMMXU Revision 1
MMXU class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
MMXU Current monitoring
Data
Common Logical Node Information
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 76
Mod ABB_c_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
APeakPhA ABB_v2_dMVPeak value of current for phase L1
E
APeakPhB ABB_v2_dMVPeak value of current for phase L2
E
APeakPhC ABB_v2_dMVPeak value of current for phase L3
E
VRMSPhA ABB_v2_dMVCalculated voltage for phase L1
E
VRMSPhB ABB_v2_dMV Calculated voltage for phase
L2
E
VRMSPhC ABB_v2_dMV Calculated voltage for phase
L3
E
VArPhA ABB_v2_dMV Reactive power value for
phase L1
E
VArPhB ABB_v2_dMV Reactive power value for
phase L2
E
VArPhC ABB_v2_dMV Reactive power value for
phase L3
E
3.2.77 RP3PDOP Revision 1
PDOP class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PDOP Reactive Power Protection
Data
Common Logical Node Information
Mod ABB_c_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Str ABB_a_dACD Start M
Op ABB_a_dACT Operate M
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 77
3.2.78 PH3PTOC
PTOC class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PTOC
Overcurrent function used in
four-stage protections, three
phase
Data
Common Logical Node Information
Mod ABB_c_INC Mode M
Beh ABB_a_INS Behaviour M
Health ABB_c_INS Health M
NamPlt ABB_a_LPL Name plate M
Status Information
Str ABB_a_ACD Start M
Op ABB_a_ACT Operate M
3.2.79 PH3PTOC Revision 3
PTOC class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PTOC
Overcurrent function used in
four-stage protections, three
phase
Data
Common Logical Node Information
Mod ABB_c_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Str ABB_a_dACD Start M
Op ABB_a_dACT Operate M
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 78
3.2.80 HOLPTOV Revision 1
PTOV class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PTOVPTOV for Harmonic over load
in IDMT stage capbankprot
Data
Common Logical Node Information
Mod ABB_c_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name Plate M
Status Information
Str ABB_a_dACD Start M
Op ABB_b_dACT Operate O
3.2.81 HPH1PTOV Revision 1
PTOV class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PTOVPTOV for Harmonic over load
in DT stage capbankprot
Data
Common Logical Node Information
Mod ABB_c_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name Plate M
Status Information
Str ABB_a_dACD Start M
Op ABB_b_dACT Operate O
3.2.82 PH3PTUC
PTUC class
Attribute DATA Explanation M/O/E Remarks
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 79
Name Type/C
PTUCThree phase undercurrent
protection
Data
Common Logical Node Information
Mod ABB_c_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Str ABB_a_dACD Start M
Op ABB_a_dACT Operate M
StrDur ABB_v2_dMV Start Duration E
3.2.83 BBTPLLN0
LLN0 class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
LLN0 Logical node 0 (for BBTP)
Data
Common Logical Node Information
Mod ABB_aINC Mode M
Beh ABB_aINS Behaviour M
Health ABB_cINS Health M
NamPlt ABB_ln0LPL Name plate M
Status Information
3.2.84 BUTPTRC
PTRC class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PTRCBusbar differential protection
bay unit, 3 Phases
Data
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 80
Common Logical Node Information
Mod ABB_cINC Mode M
Beh ABB_aINS Behaviour M
Health ABB_cINS Health M
NamPlt ABB_aLPL Name plate M
Status Information
Tr ABB_bACT Trip C
Zn1 ABB_v1SPS Bay is connected to zone A E
Zn2 ABB_v1SPS Bay is connected to zone B E
3.2.85 BRCPTOC Revision 3
PTOC class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PTOC Broken conductor monitoring
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Str ABB_b_dACD Start M
Op ABB_b_dACT Operate M
UnbA ABB_v2_dMV Current Unbalance E
StrDur ABB_v2_dMV Start Duration E
3.2.86 ZCRWPSCH Revision 2
PSCH class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PSCH
Current reversal and weak-
end infeed logic for distance
protection
Data
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 81
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
ProTx ABB_a_dSPS Carrier send by WEI logic M
ProRx ABB_a_dSPS Carrier signal received from remote end
M
Str ABB_b_dACD Carrier send by WEI logic M
Op ABB_a_dACT Trip of WEI logic M
Echo ABB_b_dACT Carrier send by WEI logic O
WeiOp ABB_b_dACT Trip of WEI logic O
RvABlk ABB_b_dACT Operation of current reversal function
O
3.2.87 ZCRWPSCH Revision 3
PSCH class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PSCH
Current reversal and weak-
end infeed logic for distance
protection
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
ProTx ABB_a_dSPS Carrier send by WEI logic M
ProRx ABB_a_dSPS Carrier signal received from remote end
M
Str ABB_b_dACD Carrier send by WEI logic M
Op ABB_b_dACT Trip of WEI logic M
Echo ABB_b_dACT Carrier send by WEI logic O
WeiOp ABB_b_dACT Trip of WEI logic O
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 82
RvABlk ABB_b_dACT Operation of current reversal function
O
3.2.88 LOVPTUV Revision 2
PTUV class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PTUV Loss of voltage check
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Str ABB_b_dACD Start M
Op ABB_b_dACT Operate M
3.2.89 ECRWPSCH Revision 2
PSCH class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PSCH
Current reversal and weak-
end infeed logic for residual
over-current protection
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
ProTx ABB_a_dSPS Teleprotection signal transmitted
M
ProRx ABB_a_dSPS Teleprotection signal received
M
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 83
Str ABB_b_dACD Carrier Send M
Op ABB_b_dACT Operate M
Echo ABB_b_dACT Carrier send by WEI logic O
WeiOp ABB_b_dACT Trip of WEI logic O
RvABlk ABB_b_dACT Operation of current reversal logic
O
3.2.90 STEFPHIZ Revision 2
PHIZ class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PHIZ100% Stator Earth Fault
Protection
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Str ABB_b_dACD Start O
Op ABB_b_dACT Operate O
Op3rdH ABB_v1_dSPS Trip by one of two 3rd
harmonic voltage
E
OpUN ABB_v1_dSPS Trip by fund. freq. neutral
over-voltage
E
Str3rdH ABB_v1_dSPS Start by one of two 3rd
harmonic voltage
E
StrUN ABB_v1_dSPS Start by fund. freq. neutral
over-voltage
E
VT3rdH ABB_v2_dMV Magnitude of 3rd harmonic
voltage at generator terminal
side
E
VN3rdH ABB_v2_dMV Magnitude of 3rd harmonic
voltage at generator neutral
side
E
E3 ABB_v2_dMV Total induced (source) stator
3rd harmonic voltage
E
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 84
VDif3rdH ABB_v2_dMV Diff. between
voltT3rdHarmonic,
voltN3rdHarmonic
E
VBias3rdH ABB_v2_dMV Bias voltage, a part of
voltN3rdHarmonic
E
UN ABB_v2_dMV Fund. frequency voltage at
generator neutral
E
VolAngClc ABB_v2_dMV Angle between
voltT3rdHarmonic and
voltN3rdHarmonic
E
3.2.91 ZMRPSB Revision 2
RPSB class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
RPSB Power swing detection
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Str ABB_b_dACD Power swing detected C
BlkZn ABB_a_dSPS Blocking of correlated PDIS zone
C
ZOuter ABB_v1_dSPS Measured impedance within outer impedance boundary
E
ZInner ABB_v1_dSPS Measured impedance within inner impedance boundary
E
3.2.92 PSPPPAM Revision 3
PPAM class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PPAM Pole slip generator protection
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 85
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Str ABB_b_dACD Start M
Op ABB_b_dACT Operate M
Gen ABB_v1_dSPS Generator E
Mot ABB_v1_dSPS Motor E
N2SlpDet ABB_v1_dSPS Trip 2 E
SlpZ1 ABB_v1_dSPS First slip in zone1 region E
SlpZ2 ABB_v1_dSPS First slip in zone2 region E
N1SlpDet ABB_v1_dSPS Trip 1 E
SlpHz ABB_v2_dMV slipFrequncy E
SlpZOhm ABB_v2_dMV slipImpedance_Ohm E
CosUkV ABB_v2_dMV uCosPhi_KV E
3.2.93 GEN2LLN0 Revision 1
LLN0 class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
LLN0Logical node 0 (for
aggregated function GEN2)
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_ln0_dLPL Name plate M
Status Information
3.2.94 VDCPTOV Revision 2
PTOV class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 86
PTOVVoltage differential function
(for US)
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name Plate M
Status Information
Str ABB_b_dACD Start M
Op ABB_b_dACT Operate O
3.2.95 LEXPDIS Revision 1
PDIS class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PDIS Under and Loss of Excitation
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Str ABB_b_dACD Start M
Op ABB_b_dACT Operate M
OpZ1 ABB_v1_dSPS Trip signal from impedance zone Z1
E
OpZ2 ABB_v1_dSPS Trip signal from impedance zone Z2
E
StrZ1 ABB_v1_dSPS Start signal from impedance zone Z1
E
StrZ2 ABB_v1_dSPS Start signal from impedance zone Z2
E
PriRis ABB_v2_dMV Resistance in Primary Ohms E
PriReact ABB_v2_dMV Reactance in Primary Ohms E
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 87
3.2.96 BCZTPDIF
PDIF class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PDIFBusbar differential protection
check zone, 3 Phases
Data
Common Logical Node Information
Mod ABB_cINC Mode M
Beh ABB_aINS Behaviour M
Health ABB_cINS Health M
NamPlt ABB_aLPL Name plate M
Status Information
Op ABB_aACT Operate M
3.2.97 UV2PTUV Revision 2
PTUV class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PTUVTwo step undervoltage
protection
Data
Common Logical Node Information
Mod ABB_c_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Str ABB_a_dACD Start M
Op ABB_a_dACT Operate M
3.2.98 STTIPHIZ Revision 2
PHIZ class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PHIZ 100% Stator earthfault
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 88
protection by using injection
Data
Common Logical Node Information
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
Mod ABB_a_dINC Mode M
NamPlt ABB_a_dLPL Name plate M
Status Information
Op ABB_b_dACT Operate O
Str ABB_d_dACD Start O
Alm ABB_v1_dSPS Alarm stator E
OpnCir ABB_v1_dSPS Open stator injection circuit E
Error ABB_v1_dSPS Error stator E
ErrorSt ABB_v1_dINS Error status stator E
3.2.99 ECPSCH Revision 1
PSCH class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PSCH
Scheme communication logic
for residual overcurrent
protection
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
ProTx ABB_a_dSPS Teleprotection signal transmitted
M
ProRx ABB_a_dSPS Teleprotection signal received
M
Str ABB_b_dACD Carrier Send M
Op ABB_b_dACT Operate M
CarRx ABB_b_dACT Carrier Signal received signal from Communication Logic
O
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 89
LosOfGrd ABB_a_dSPS Loss of carrier guard signal O
3.2.100 ROTIPHIZ Revision 2
PHIZ class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PHIZ100% Rotor earthfault
protection by using injection
Data
Common Logical Node Information
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
Mod ABB_a_dINC Mode M
NamPlt ABB_a_dLPL Name plate M
Status Information
Op ABB_b_dACT Operate O
Str ABB_b_dACD Start O
OpDC ABB_v2_dACT Trip for rotor ground fault (on DC-side of exciter)
E
OpAC ABB_v2_dACT Trip for ground fault on AC-side of exciter
E
StrDC ABB_v2_dACD Start for rotor ground fault (on DC-side of exciter)
E
StrAC ABB_v2_dACD Start for ground fault on AC-side of exciter
E
Alm ABB_v1_dSPS Alarm rotor E
OpnCir ABB_v1_dSPS Open rotor injection circuit E
Error ABB_v1_dSPS Error rotor E
ErrorSt ABB_v1_dINS Error status rotor E
ErrorH ABB_v1_dSPS Error block harmonic rotor E
3.2.101 BZNTPDIF Revision 3
PDIF class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PDIFBusbar differential protection
zone, 3 Phases
Data
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 90
Common Logical Node Information
Mod ABB_c_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Op ABB_b_dACT Operate M
DifAClc ABB_n_dWYE Differential Current O
RstA ABB_n_dWYE Restraint Current O
IndOpExBay ABB_v1_dSPS Zone trip due to external trip from one of the connected bays
E
IndOpExZn ABB_v1_dSPS Zone trip due to external input signal
E
IndOpSen1 ABB_v1_dSPS Sensitive differential function trip phase 1
E
OpnCTAlm ABB_v1_dSPS General open CT alarm E
ADifAlm1 ABB_v1_dSPS Differential current alarm phase 1
E
OpRs ABB_v1_dSPC Trip reset used by command handling
EControllable
OpnCTRs ABB_v1_dSPC Open CT reset used by command handling
EControllable
IndOpDif1 ABB_v1_dSPS Differential trip phase 1 E
IndOpDif2 ABB_v1_dSPS Differential trip phase 2 E
IndOpDif3 ABB_v1_dSPS Differential trip phase 3 E
IndOpSen2 ABB_v1_dSPS Sensitive differential function trip phase 2
E
IndOpSen3 ABB_v1_dSPS Sensitive differential function trip phase 3
E
ADifAlm2 ABB_v1_dSPS Differential current alarm phase 2
E
ADifAlm3 ABB_v1_dSPS Differential current alarm phase 3
E
3.2.102 GUPPDUP Revision 1
PDUP class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PDUPGenerator power protection,
forward
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 91
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Str ABB_b_dACD Start M
Op ABB_b_dACT Operate M
OpZ1 ABB_v1_dSPS Trip of stage 1 E
OpZ2 ABB_v1_dSPS Trip of stage 2 E
StrZ1 ABB_v1_dSPS Start of stage 1 E
StrZ2 ABB_v1_dSPS Start of stage 2 E
MW ABB_v2_dMV Active Power in MW E
MVAr ABB_v2_dMV Reactive power in MVar E
3.2.103 ROV2PTOV Revision 1
PTOV class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PTOVOvervoltage function for two-
step overvoltage protection
Data
Common Logical Node Information
Mod ABB_c_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name Plate M
Status Information
Str ABB_b_dACD Start M
Op ABB_b_dACT Operate O
3.2.104 GOPPDOP Revision 1
PDOP class
Attribute DATA Explanation M/O/E Remarks
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 92
Name Type/C
PDOPGenerator power protection,
reverse
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Str ABB_b_dACD Start M
Op ABB_b_dACT Operate M
OpZ1 ABB_v1_dSPS Trip of stage 1 E
OpZ2 ABB_v1_dSPS Trip of stage 2 E
StrZ1 ABB_v1_dSPS Start of stage 1 E
StrZ2 ABB_v1_dSPS Start of stage 2 E
MW ABB_v2_dMV Active Power in MW E
MVAr ABB_v2_dMV Reactive power in MVar E
3.2.105 OEXPVPH Revision 3
PVPH class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PVPH Overexcitation protection
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Str ABB_b_dACD Overexcitation alarm limit exceeded (instantaneous)
M
Op ABB_b_dACT Common trip overexcitation M
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 93
VHzRat ABB_v2_dMV Relative voltage to frequency ratio E
GenFctFlt ABB_v1_dSPS General function error E
ExtAlm ABB_v1_dSPS Overexcitation alarm limit exceeded (delayed)
E
3.2.106 BZITGGIO
GGIO class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
GGIO
Busbar differential
protection zone
interconnection, 3 Phases
Data
Common Logical Node Information
Mod ABB_cINC Mode M
Beh ABB_aINS Behaviour M
Health ABB_cINS Health M
NamPlt ABB_aLPL Name plate M
Status Information
Alm ABB_bSPS General single alarm O
Act ABB_v1SPS Load Transfer/Zone Interconnection active
E
3.2.107 SWSGGIO
GGIO class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
GGIOSwitch status used for
Busbar protection
Data
Common Logical Node Information
Mod ABB_aINC Mode M
Beh ABB_aINS Behaviour M
Health ABB_cINS Health M
NamPlt ABB_aLPL Name plate M
Status Information
Alm ABB_bSPS General single alarm O
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 94
Fcd ABB_v1SPS Primary object status forced to open or closed by setting
E
3.2.108 ZCPSCH Revision 2
PSCH class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PSCH
Scheme communication logic
for residual overcurrent
protection
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
ProTx ABB_a_dSPS Teleprotection signal transmitted for a forward fault
M
ProRx ABB_a_dSPS Teleprotection signal received for a forward fault
M
Str ABB_b_dACD Carrier Send by Communication Scheme Logic
M
Op ABB_b_dACT Trip by Communication Scheme Logic-Residual
M
CarRx ABB_b_dACT Carrier Signal received or missing carrier guard signal
O
LosOfGrd ABB_a_dSPS Loss of carrier guard signal O
StopTxBlk ABB_v1_dSPS Stops sending blocking signal to remote end
E
3.2.109 OC4LLN0
LLN0 class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
LLN0Logical node 0 (for
aggregated function OC4)
Data
Common Logical Node Information
Mod ABB_aINC Mode M
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 95
Beh ABB_aINS Behaviour M
Health ABB_cINS Health M
NamPlt ABB_ln0LPL Name plate M
Status Information
IvdCrv ABB_v1SPS Invalid coefficients for user programmable curve
E
3.2.110 PH3PTRC Revision 5
PTRC class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PTRCTrip logic for aggregated
functions, three phase
Data
Common Logical Node Information
Mod ABB_cINC Mode M
Beh ABB_aINS Behaviour M
Health ABB_cINS Health M
NamPlt ABB_aLPL Name plate M
Status Information
Op ABB_aACT Operate (combination of subscribed Op from protection functions)
C
Str ABB_aACD Sum of all starts of all connected Logical Nodes
O
3.2.111 REFPDIF Revision 1
PDIF class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PDIFRestricted earth fault
protection
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 96
NamPlt ABB_a_dLPL Name plate M
Status Information
Str ABB_b_dACD Start by restricted earth fault protection function
O
Op ABB_b_dACT Trip by restricted earth fault protection function
M
Blk2H ABB_v1_dSPS Block due to 2-nd harmonic E
ItrFlt ABB_v1_dSPS Directional Criteria has operated for internal fault
E
3.2.112 MVGGIO Revision 1
GGIO class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
GGIO Generic measured value
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
AnIn ABB_a_dMV Measured value O
3.2.113 SPGGIO Revision 1
GGIO class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
GGIO Generic single point status
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Ind ABB_c_dSPS Output status O
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 97
3.2.114 SP16GGIO Revision 2
GGIO class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
GGIOGeneric single point status,
16 outputs
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Ind ABB_c_dSPS General indication (binary input)
O
GrInd ABB_v1_dSPS OR of all indications 1-16 E
Ind2 ABB_v1_dSPS General indication no 2 E
Ind3 ABB_v1_dSPS General indication no 3 E
Ind4 ABB_v1_dSPS General indication no 4 E
Ind5 ABB_v1_dSPS General indication no 5 E
Ind6 ABB_v1_dSPS General indication no 6 E
Ind7 ABB_v1_dSPS General indication no 7 E
Ind8 ABB_v1_dSPS General indication no 8 E
Ind9 ABB_v1_dSPS General indication no 9 E
Ind10 ABB_v1_dSPS General indication no 10 E
Ind11 ABB_v1_dSPS General indication no 11 E
Ind12 ABB_v1_dSPS General indication no 12 E
Ind13 ABB_v1_dSPS General indication no 13 E
Ind14 ABB_v1_dSPS General indication no 14 E
Ind15 ABB_v1_dSPS General indication no 15 E
Ind16 ABB_v1_dSPS General indication no 16 E
3.2.115 VSGGIO Revision 1
GGIO class
Attribute DATA ExplanationM/O/E
/CRemarks
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 98
Name Type
GGIO Versatile switch
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
DPCSO ABB_d_dDPC Double point controllable status output
O
3.2.116 PCGGIO
GGIO class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
GGIO Pulse counter
Data
Common Logical Node Information
Mod ABB_aINC Mode M
Beh ABB_aINS Behaviour M
Health ABB_cINS Health M
NamPlt ABB_aLPL Name plate M
Status Information
AnIn ABB_bMV Scaled measured value since the last reset
O
TotVal ABB_v1BCR Measured value since last reset
E
ValUpd ABB_v1SPS A new pulse counter value is generated
E
IcpCyc ABB_v1SPS The reported value does not compromise a complete cycle
E
3.2.117 TR8ATCC Revision 17
ATCC class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 99
ATCCAutomatic Tap Changer
Control
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Loc ABB_a_dSPS Local operation M
TapChg ABB_a_dBSC Change tap position stop,
higher, lower
C Controllable
ParOp ABB_h_dSPC Parallel/Independent
operation
M Controllable
LTCBlk ABB_a_dSPC Block (B Inhibit ) Automatic
control of LTC
O Controllable
CtlV ABB_b_dMV Control voltage M
LodA ABB_b_dMV Load current O
CircA ABB_b_dMV Circulating current O
HiTapPos ABB_b_dINS High tap position O
LoTapPos ABB_b_dINS Low tap position O
VCTRStatus ABB_v10_dINS VCTR Control word (horiz
com)
E
Adapt ABB_v1_dSPS The transformer is adapting E
LodARe ABB_v17_dMV Real part of load current
(horiz com)
E
LodAIm ABB_v18_dMV Imaginary part of load current
(horiz com)
E
AutoCtl ABB_v1_dSPC Automatic/Manual control E Controllable
SetV ABB_v22_dMV Voltage setpoint (horiz com) E
AutoRedV ABB_v2_dMV Load dependent automatic
reduction voltage
E
PosRel ABB_v19_dMV Relative tap position (horiz
com)
E
AutoSlave ABB_v1_dSPS Auto slave activated E
BusV ABB_v20_dMV Busbar voltage (horiz com) E
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 100
AvBusV ABB_v2_dMV Average of measured busbar
voltage
E
AverA ABB_v2_dMV Average of three phase
current
E
BndCtrAct ABB_v2_dMV Actual voltage setpoint E
BndCtrPar ABB_v2_dMV Voltage setpoint parallel E
BndCtrSet ABB_v16_dMV Voltage setpoint set by user E
BndCtrSng ABB_v2_dMV Voltage setpoint single E
CCAV ABB_v2_dMV Circulating Current Adjusted
Voltage
E
CircABlk ABB_v1_dSPS Block from high circulating
current
E
CircALim ABB_v2_dMV Alarm level for high
circulating current
E
CircV ABB_v2_dMV Calculated circulating voltage E
CommFlt ABB_v1_dSPS Bay to bay communication
error
E
DayHuntAlm ABB_v1_dSPS Alarm for to many commands
within the latest day
E
ExLowerBlk ABB_v1_dSPS External block of lower
command activated
E
ExRaiseBlk ABB_v1_dSPS External block of raise
command activated
E
ForceMast ABB_v1_dSPC Force transformer to master E Controllable
HiABlk ABB_v1_dSPS One phase current is above
the settable limit
E
HiV ABB_v1_dSPS Voltage above max limit E
HiVArFwd ABB_v1_dSPS Reactive power forward
alarm
E
HiVArRv ABB_v1_dSPS Reactive power reverse
alarm
E
HiWFwd ABB_v1_dSPS Active power forward alarm E
HiWRv ABB_v1_dSPS Active power reverse alarm E
Homing ABB_v1_dSPS Homing activated E
HrHuntAlm ABB_v1_dSPS Alarm for to many commands
within the latest hour
E
HuntAlm ABB_v1_dSPS Alarm from to many
commands in opposite
E
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 101
direction
LodV ABB_v2_dMV Load voltage E
LoV ABB_v1_dSPS Voltage below min limit E
LTCId ABB_v1_dINS Identity of transformer E
LVA1On ABB_v1_dSPC Activation of load voltage
adjust. factor 1
E Controllable
LVA1V ABB_v2_dMV Value 1 for load voltage
adjustment
E
LVA2On ABB_v1_dSPC Activation of load voltage
adjust. factor 2
E Controllable
LVA2V ABB_v2_dMV Value 2 for load voltage
adjustment
E
LVA3On ABB_v1_dSPC Activation of load voltage
adjust. factor 3
E Controllable
LVA3V ABB_v2_dMV Value 3 for load voltage
adjustment
E
LVA4On ABB_v1_dSPC Activation of load voltage
adjust. factor 4
E Controllable
LVA4V ABB_v2_dMV Value 4 for load voltage
adjustment
E
LVAReset ABB_v1_dSPC Deactivation of load voltage
adjust.
E Controllable
MSMode ABB_v1_dSPS Master Slave mode activated E
Q1Conn ABB_v1_dSPS Reactive bank1 connected E
Q1VAr ABB_v2_dMV Size of reactive bank1 E
Q2Conn ABB_v1_dSPS Reactive bank2 connected E
Q2VAr ABB_v2_dMV Size of reactive bank2 E
Q3Conn ABB_v1_dSPS Reactive bank3 connected E
Q3VAr ABB_v2_dMV Size of reactive bank3 E
RvActBlk ABB_v1_dSPS Block caused by reversed
action
E
SimTap ABB_v1_dSPS Simultaneous tapping
activated
E
T1Master ABB_v1_dSPS Transformer 1 is master E
T1ParGr ABB_v1_dSPS Transformer 1 included in
parallel group
E
T2Master ABB_v1_dSPS Transformer 2 is master E
T2ParGr ABB_v1_dSPS Transformer 2 included in E
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 102
parallel group
T3Master ABB_v1_dSPS Transformer 3 is master E
T3ParGr ABB_v1_dSPS Transformer 3 included in
parallel group
E
T4Master ABB_v1_dSPS Transformer 4 is master E
T4ParGr ABB_v1_dSPS Transformer 4 included in
parallel group
E
T5Master ABB_v1_dSPS Transformer 5 is master E
T5ParGr ABB_v1_dSPS Transformer 5 included in
parallel group
E
T6Master ABB_v1_dSPS Transformer 6 is master E
T6ParGr ABB_v1_dSPS Transformer 6 included in
parallel group
E
T7Master ABB_v1_dSPS Transformer 7 is master E
T7ParGr ABB_v1_dSPS Transformer 7 included in
parallel group
E
T8Master ABB_v1_dSPS Transformer 8 is master E
T8ParGr ABB_v1_dSPS Transformer 8 included in
parallel group
E
TotVAr ABB_c_dMV Reactive power E
TotW ABB_c_dMV Active power E
VDif ABB_v1_dSPS VT supervision alarm E
X2 ABB_v21_dMV Transformer reactance
secondary side (horiz com)
E
Disc ABB_v1_dSPS Transformer is disconnected E
TotBlock ABB_v1_dSPS Auto and man commands are
blocked
E
AutoBlock ABB_v1_dSPS Auto commands are blocked E
DiffPosMF ABB_v1_dSPS To high difference in tap
positions
E
MFFlt ABB_v1_dSPS The number of masters is
different from one
E
ParSet ABB_v1_dINS Setting value for transformer
in parallel mode
E
BlkV ABB_a_dSPS Voltage below block limit E
VolSpt ABB_v6_dAPC Voltage setpoint E Controllable
EnaVolSpt ABB_v1_dSPS Voltage set point from control
DO VolSpt is enabled
E
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 103
3.2.118 TR1ATCC Revision 15
ATCC class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
ATCCAutomatic Tap Changer
Control
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Loc ABB_a_dSPS Local operation M
TapChg ABB_a_dBSC Change tap position stop, higher, lower
C
ParOp ABB_h_dSPC Parallel/Independent operation
M
LTCBlk ABB_a_dSPC Block (B Inhibit ) Automatic control of LTC
O
CtlV ABB_b_dMV Control voltage M
LodA ABB_b_dMV Load current O
HiTapPos ABB_b_dINS High tap position O
LoTapPos ABB_b_dINS Low tap position O
VCTRStatus ABB_v2_dINS VCTR Control word (horiz com)
E
LodARe ABB_v4_dMV Real part of load current (horiz com)
E
LodAIm ABB_v3_dMV Imaginary part of load current (horiz com)
E
AutoCtl ABB_v1_dSPC Automatic/Manual control E
SetV ABB_v6_dMV Voltage setpoint (horiz com) E
AutoRedV ABB_v2_dMV Load dependent automatic reduction voltage
E
PosRel ABB_v7_dMV Relative tap position (horiz com)
E
BusV ABB_v5_dMV Busbar voltage (horiz com) E
AverA ABB_v2_dMV Average of three phase current
E
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 104
BndCtrSet ABB_v16_dMV Voltage setpoint set by user E
BndCtrSng ABB_v2_dMV Voltage setpoint single E
DayHuntAlm ABB_v1_dSPS Alarm for to many commands within the latest day
E
ExLowerBlk ABB_v1_dSPS External block of lower command activated
E
ExRaiseBlk ABB_v1_dSPS External block of raise command activated
E
HiABlk ABB_v1_dSPS One phase current is above the settable limit
E
HiV ABB_v1_dSPS Voltage above max limit E
HiVArFwd ABB_v1_dSPS Reactive power forward alarm
E
HiVArRv ABB_v1_dSPS Reactive power reverse alarm
E
HiWFwd ABB_v1_dSPS Active power forward alarm E
HiWRv ABB_v1_dSPS Active power reverse alarm E
HrHuntAlm ABB_v1_dSPS Alarm for to many commands within the latest hour
E
HuntAlm ABB_v1_dSPS Alarm from to many commands in opposite direction
E
LodV ABB_v2_dMV Load voltage E
LoV ABB_v1_dSPS Voltage below min limit E
LVA1On ABB_v1_dSPC Activation of load voltage adjust. factor 1
E
LVA1V ABB_v2_dMV Value 1 for load voltage adjustment
E
LVA2On ABB_v1_dSPC Activation of load voltage adjust. factor 2
E
LVA2V ABB_v2_dMV Value 2 for load voltage adjustment
E
LVA3On ABB_v1_dSPC Activation of load voltage adjust. factor 3
E
LVA3V ABB_v2_dMV Value 3 for load voltage adjustment
E
LVA4On ABB_v1_dSPC Activation of load voltage adjust. factor 4
E
LVA4V ABB_v2_dMV Value 4 for load voltage adjustment
E
LVAReset ABB_v1_dSPC Deactivation of load voltage adjust.
E
RvActBlk ABB_v1_dSPS Block caused by reversed action
E
X2 ABB_v8_dMV Transformer reactance secondary side (horiz com)
E
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 105
TotBlock ABB_v1_dSPS Auto and man commands are blocked
E
AutoBlock ABB_v1_dSPS Auto commands are blocked E
TotW ABB_c_dMV Calculated active power E
TotVAr ABB_c_dMV Calculated reactive power E
BlkV ABB_a_dSPS Voltage below block limit E
BndCtrAct ABB_v2_dMV Actual voltage setpoint E
VolSpt ABB_v6_dAPC Voltage setpoint EControllable
EnaVolSpt ABB_v1_dSPS Voltage set point from control DO VolSpt is enabled
E
3.2.119 OCNDLLN0
LLN0 class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
LLN0Logical node 0 (for
aggregated function OCND)
Data
Common Logical Node Information
Mod ABB_aINC Mode M
Beh ABB_aINS Behaviour M
Health ABB_cINS Health M
NamPlt ABB_ln0LPL Name plate M
Status Information
IvdCrv ABB_v1SPS Invalid coefficients for user programmable curve
E
3.2.120 AUT1RSYN Revision 2
RSYN class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
RSYNAuto control of synchrocheck
and energizing check
Data
Common Logical Node Information
Mod ABB_c_dINC Mode M
Beh ABB_a_dINS Behaviour M
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 106
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Rel ABB_a_dSPS Release M
VInd ABB_a_dSPS Voltage Difference Indicator O
AngInd ABB_a_dSPS Angle Difference Indicator O
HzInd ABB_a_dSPS Frequency Difference Indicator
O
DifVClc ABB_b_dMV Calculated Difference in Voltage
O
DifHzClc ABB_b_dMV Calculated Difference in Frequency
O
DifAngClc ABB_b_dMV Calculated Difference of Phase Angle
O
EnOK ABB_v1_dSPS Auto energizing check OK E
TestSCOK ABB_v1_dSPS Auto synchro check OK test output
E
VBus ABB_v2_dMV Voltage amplitude for Bus voltage
E
VLin ABB_v2_dMV Voltage amplitude for Line voltage
E
3.2.121 MAN1RSYN Revision 2
RSYN class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
RSYN
Manual control of
synchrocheck and energizing
check
Data
Common Logical Node Information
Mod ABB_c_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Rel ABB_a_dSPS Release M
VInd ABB_a_dSPS Voltage Difference Indicator O
AngInd ABB_a_dSPS Angle Difference Indicator O
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 107
HzInd ABB_a_dSPS Frequency Difference Indicator
O
EnOK ABB_v1_dSPS Manual energizing check OK E
TestSCOK ABB_v1_dSPS Manual synchro check OK test output
E
3.2.122 SYNRSYN Revision 3
RSYN class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
RSYNAuto control of synchrocheck
and energizing check
Data
Common Logical Node Information
Mod ABB_c_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Rel ABB_a_dSPS Release M
SynPrg ABB_a_dSPS Synchronising in progress O
FailSyn ABB_v1_dSPS Synchronizing failed E
TestSynOK ABB_v1_dSPS Synchronizing OK test output E
VHiAlmSyn ABB_v1_dSPS Voltage amplitudes for synchronizing above set limits
E
VIndSyn ABB_v1_dSPS Voltage difference out of limit for synchronizing
E
HzIndSyn ABB_v1_dSPS Frequency difference out of limit for synchronizing
E
HzInBndSyn ABB_v1_dSPS Frequency difference in band for synchronizing
E
HzRCIndSyn ABB_v1_dSPS Frequency derivative out of limit for synchronizing
E
3.2.123 RSY1LLN0 Revision 2
LLN0 class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 108
LLN0
Logical node 0 (for
aggregated function
RSY1)
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_ln0_dLPL Name plate M
Status Information
Bus1Sel ABB_v1_dSPS Bus1 selected E
Bus2Sel ABB_v1_dSPS Bus2 selected E
Lin1Sel ABB_v1_dSPS Line1 selected E
Lin2Sel ABB_v1_dSPS Line2 selected E
SelFuFail ABB_v1_dSPS Selected voltage transformer fuse failed
E
TestEnOK ABB_v1_dSPS Energizing check OK test output
E
VHiAlm ABB_v1_dSPS Voltage amplitudes above set limits
E
InadCBCls ABB_v1_dSPS Inadvertent circuit breaker closing
E
3.2.124 NS2LLN0 Revision 1
LLN0 class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
LLN0Logical node 0 (for
aggregated function NS2)
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_ln0_dLPL Name plate M
Status Information
NSCurr ABB_v2_dMV Negative sequence current in primary amps
E
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 109
Alm ABB_a_dSPS Alarm signal (operated by START signal)
E
3.2.125 NS2PTOC Revision 1
PTOC class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PTOC
Negativ phase sequence
overcurrent protection, 2
Steps
Data
Common Logical Node Information
Mod ABB_c_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Str ABB_b_dACD Start M
Op ABB_b_dACT Operate M
3.2.126 NS2PTRC Revision 2
PTRC class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PTRC
Trip logic for Negativ phase
sequence overcurrent
protection, 2 Steps
Data
Common Logical Node Information
Mod ABB_c_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Op ABB_b_dACT Operate (combination of subscribed Op from
C
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 110
protection functions)
Str ABB_b_dACD Sum of all starts of all connected Logical Nodes
O
3.2.127 GF2LLN0
LLN0 class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
LLN0Logical node 0 (for
aggregated function GF2)
Data
Common Logical Node Information
Mod ABB_aINC Mode M
Beh ABB_aINS Behaviour M
Health ABB_cINS Health M
NamPlt ABB_ln0LPL Name plate M
Status Information
IvdCrv ABB_v1SPS Invalid coefficients for user programmable curves in PVOC1 and PVOC2
E
UnVBehMem ABB_v1SPS Low voltage for directional polarization
E
3.2.128 GF2MMXN Revision 3
MMXN class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
MMXN
Non phase related
measurements for General
Multipurpose protection
Data
Common Logical Node Information
Mod ABB_cINC Mode M
Beh ABB_aINS Behaviour M
Health ABB_cINS Health M
NamPlt ABB_aLPL Name plate M
Status Information
Amp ABB_bMV Measured current value O
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 111
Vol ABB_bMV Measured voltage value O
AmpPwrFact ABB_v2MV Measured current multiplied with cos (Phi)
E
VolAmpAng ABB_v2MV Angle between voltage and current
E
3.2.129 PH1PTUV
PTUV class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PTUV
Undervoltage function for
General Multipurpose
protection
Data
Common Logical Node Information
Mod ABB_c_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Str ABB_b_dACD Start M
Op ABB_b_dACT Operate M
3.2.130 VRLLN0
LLN0 class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
LLN0Logical node 0 (for
aggregated function VR2)
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_ln0_dLPL Name plate M
Status Information
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 112
3.2.131 VRPVOC
PVOC class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PVOC
Voltage restrained
overcurrent function for
General Multipurpose
protection
Data
Common Logical Node Information
Mod ABB_c_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Str ABB_b_dACD Start M
Op ABB_b_dACT Operate M
3.2.132 CCSRBRF
RBRF class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
RBRFBreaker failure protection
single phase function
Data
Common Logical Node Information
Mod ABB_aINC Mode M
Beh ABB_aINS Behaviour M
Health ABB_cINS Health M
NamPlt ABB_aLPL Name plate M
Status Information
OpEx ABB_bACT Breaker failure trip (external
trip)
C
OpIn ABB_bACT Operate, retrip (internal trip) C
OpEx2 ABB_v2ACT External trip E
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 113
3.2.133 SAPFRC Revision 1
PFRC class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PFRCFrequency gradient
protection
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Str ABB_b_dACD Start/pick-up signal for
frequencyGradient
M
Op ABB_b_dACT Operate/trip signal for
frequencyGradient
M
BlkLoMg ABB_v1_dSPS Signal indicating internal
blocking due to low amplitude
of signal from which
frequency is calculated
E
RestLd ABB_v1_dSPS Restore signal for frequency E
3.2.134 SDEPSDE Revision 1
PSDE class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PSDESensitive Directional earth
Fault Protection WEF
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Str ABB_b_dACD Start M
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 114
Op ABB_b_dACT Operate O
OpResA ABB_v1_dSPS Operate for non directional
residual over current
protection
E
OpResV ABB_v1_dSPS Operate for non directional
residual over voltage
protection
E
StrResA ABB_v1_dSPS Start for non directional
residual over current
protection
E
StrResV ABB_v1_dSPS Start for non directional
residual over voltage
protection
E
AngAV ABB_v2_dMV Angle between residual
current and polarizing
compensate voltage
E
ResA ABB_v2_dMV Measured magnitude of the
residual current
E
ResV ABB_v2_dMV Measured magnitude of the
residual voltage
E
ResP ABB_v2_dMV Magnitude of 3I03U0cosFi
the active power due to
residual current
E
StrDirResA ABB_v1_dSPS Start of directional residual
over current protection
E
OpDirResA ABB_v1_dSPS Operate of directional
residual over current
protection
E
3.2.135 ETPMMTR Revision 3
MMTR class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
MMTREnergy Three Phase
Measurement
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 115
NamPlt ABB_a_dLPL Name plate M
Status Information
SupRs ABB_v1_dSPC Reset of accumulated
energy
E Controllable
MaxDmdRs ABB_v1_dSPC Reset maximum
demands
E Controllable
StrAcc ABB_v1_dSPS Start of accumlating
energy values
E
WhFwdAlm ABB_v1_dSPS Alarm of energy active
forward for exceeding the
limit
E
WhRvAlm ABB_v1_dSPS Alarm of energy active
reverse for exceeding the
limit
E
VArhFwdAlm ABB_v1_dSPS Alarm of energy reactive
forward for exceeding the
limit
E
VArhRvAlm ABB_v1_dSPS Alarm of energy reactive
reverse for exceeding the
limit
E
VArsAccFwd ABB_v2_dBCR Accumulated forward
reactive energy
E
VArsAccRev ABB_v2_dBCR Accumulated reverse
reactive energy
E
WsAccFwd ABB_v2_dBCR Accumulated forward
active energy
E
WsAccRev ABB_v2_dBCR Accumulated reverse
active energy
E
MaxVArFwdD ABB_v2_dMV Maximum reactive power
demand value in forward
direction
E
MaxVArRvDm ABB_v2_dMV Maximum reactive power
demand value in reverse
direction
E
MaxWFwdDmd ABB_v2_dMV Maximum active power
demand value in forward
direction
E
MaxWRvDmd ABB_v2_dMV Maximum active power
demand value in reverse
direction
E
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 116
3.2.136 SAPTOF Revision 1
PTOF class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PTOF Over-frequency protection
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Str ABB_b_dACD Start/pick-up signal for frequency.
M
Op ABB_b_dACT Operate/trip signal for frequency.
M
BlkLoMg ABB_v1_dSPS Signal indicating internal blocking due to low amplitude of signal from which frequency is calculate
E
3.2.137 SAPTUF Revision 1
PTUF class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PTUF Under frequency protection
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Str ABB_b_dACD Start/pick-up signal for
frequency.
M
Op ABB_b_dACT Operate/trip signal for
frequency.
M
BlkLoMg ABB_v1_dSPS Signal indicating internal E
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 117
blocking due to low amplitude
of signal from which
frequency is calculate
RstLd ABB_v1_dSPS Restore signal for load
restoring purposes.
E
3.2.138 GEN4PHAR Revision 3
PHAR class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PHARHarmonic restraint for 4-
stage protection function
Data
Common Logical Node Information
Mod ABB_c_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name Plate M
Status Information
Str ABB_b_dACD Start (active when restraint is
needed)
M
3.2.139 GF2PHAR Revision 2
PHAR class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PHAR
Harmonic restraint used in
General MultiPurpose
protection function
Data
Common Logical Node Information
Mod ABB_c_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name Plate M
Status Information
Str ABB_b_dACD Start (active when restraint is needed)
M
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 118
3.2.140 GF2PTOV Revision 2
PTOV class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PTOV
Over-voltage function for
General Multipurpose
protection
Data
Common Logical Node Information
Mod ABB_c_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name Plate M
Status Information
Str ABB_b_dACD Start M
Op ABB_b_dACT Operate O
3.2.141 GF2PTUC Revision 2
PTUC class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PTUCUndercurrent for General
Multipurpose protection
Data
Common Logical Node Information
Mod ABB_c_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Str ABB_b_dACD Start M
Op ABB_b_dACT Operate M
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 119
3.2.142 GF2PTUV Revision 2
PTUV class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PTUV
Undervoltage function for
General Multipurpose
protection
Data
Common Logical Node Information
Mod ABB_c_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Str ABB_b_dACD Start M
Op ABB_b_dACT Operate M
3.2.143 GF2PVOC Revision 2
PVOC class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PVOC
Overcurrent function for
General Multipurpose
protection
Data
Common Logical Node Information
Mod ABB_c_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Str ABB_b_dACD Start M
Op ABB_b_dACT Operate M
IvdCrv ABB_v1_dSPS Invalid coefficients for user
programmable curve
E
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 120
3.2.144 LMBRFLO Revision 2
RFLO class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
RFLO Fault locator
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
FltZ ABB_d_dCMV Fault Impedance M
FltDiskm ABB_b_dMV Fault Distance in km M
FltLoop ABB_e_dINS Fault loop O
FltDisRl ABB_v2_dMV Distance to fault, relative E
ClcFlt ABB_v1_dSPS Fault calculation made E
3.2.145 PH1BPTOC Revision 1
PTOC class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PTOCSingle phase over-current
protection 4 stages for Busbar
Data
Common Logical Node Information
Mod ABB_c_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Str ABB_b_dACD Start M
Op ABB_b_dACT Operate M
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 121
3.2.146 PH1PTRC Revision 3
PTRC class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PTRCTrip logic for aggregated
functions, one phase
Data
Common Logical Node Information
Mod ABB_c_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Op ABB_b_dACT Operate (combination of
subscribed Op from
protection functions)
C
Str ABB_b_dACD Sum of all starts of all
connected Logical Nodes
O
3.2.147 LCPTTR
PTTR class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PTTRThermal overload, one time
constant (unit Celsius)
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Tmp ABB_b_dMV Calculated temperature of
the device (in Celsius)
O
TmpRl ABB_b_dMV Temperature relative to
operate temperature
O
Str ABB_b_dACD Start O
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 122
Op ABB_b_dACT Operate M
AlmThm ABB_a_dSPS Thermal Alarm O
BlkRecSt ABB_v1_dSPS Block AR start E
SenFlt ABB_v1_dSPS Error signal from the
temperature sensor
E
TmmOp ABB_v1_dINS Estimated time to trip (in min) E
TmmRsLO ABB_v1_dINS Estimated time to reset of
lockout (in min)
E
TmpAmb ABB_v2_dMV Ambient temperature used in
the calculations (in Celsius)
E
3.2.148 LFPTTR
PTTR class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PTTRThermal overload, one time
constant (unit Fahrenheit)
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Tmp ABB_b_dMV Temperature for thermal load O
TmpRl ABB_b_dMV Temperature relative to
operate temperature
E
Str ABB_b_dACD Start O
Op ABB_b_dACT Operate M
AlmThm ABB_a_dSPS Thermal Alarm O
BlkRecSt ABB_v1_dSPS Block AR start E
SenFlt ABB_v1_dSPS Error signal from the
temperature sensor
E
TmmOp ABB_v1_dINS Estimated time to trip (in min) E
TmmRsLO ABB_v1_dINS Estimated time to reset of
lockout (in min)
E
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 123
TmpAmb ABB_v2_dMV Ambient temperature used in
the calculations (in
Fahrenheit)
E
3.2.149 DRPRDRE
RDRE class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
RDRE Disturbance recorder
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
RcdMade ABB_a_dSPS Recording made M
FltNum ABB_b_dINS Fault Number M
3.2.150 SCSWI Revision 1
CSWI class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
CSWI Switch control
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Pos ABB_a_dDPC Switch, general MControllable
OpOpn ABB_b_dACT Operation “Open Switch” O
OpCls ABB_b_dACT Operation “Close Switch” O
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 124
BlkCmd ABB_v1_dSPC Block of commands EControllable
3.2.151 SPC8GGIO Revision 2
GGIO class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
GGIO Single point command
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
SPCSO1 ABB_d_dSPC Single Point Controllable 1 E Controllable
SPCSO2 ABB_d_dSPC Single Point Controllable 2 E Controllable
SPCSO3 ABB_d_dSPC Single Point Controllable 3 E Controllable
SPCSO4 ABB_d_dSPC Single Point Controllable 4 E Controllable
SPCSO5 ABB_d_dSPC Single Point Controllable 5 E Controllable
SPCSO6 ABB_d_dSPC Single Point Controllable 6 E Controllable
SPCSO7 ABB_d_dSPC Single Point Controllable 7 E Controllable
SPCSO8 ABB_d_dSPC Single Point Controllable 8 E Controllable
3.2.152 TCMYLTC Revision 5
YLTC class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
YLTC(mini) Load Tap Changer, 6
Binary Input for tap
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 125
Status Information
OpCnt ABB_b_dINS Operation counter value O
TapChg ABB_b_dBSC Change tap position stop, higher, lower
CControllable
EndPosR ABB_a_dSPS End position raise reached M
EndPosL ABB_a_dSPS End position lower reached M
CLCnt ABB_v2_dMV Contact life counter value E
CLRs ABB_v1_dSPC Reset contact life counter EControllable
HiTapPos ABB_b_dINS High tap position E
LoTapPos ABB_b_dINS Low tap position E
OpRs ABB_v1_dSPC Reset operation counter EControllable
CmdFlt ABB_v1_dSPS Alarm for a command without an expected position change
E
ConvFlt ABB_v1_dSPS General tap position conversion error
E
InvPosChg ABB_v1_dSPS Last position change was an invalid change
E
TapChgFlt ABB_v1_dSPS Alarm for none or illegal tap position change
E
TapPosFlt ABB_v1_dSPS Alarm that indicates a problem with the position indication
E
3.2.153 TCLYLTC Revision 5
YLTC class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
YLTC(large) Load Tap Changer,
32 Binary Input for tap
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
OpCnt ABB_b_dINS Operation counter value O
TapChg ABB_b_dBSC Change tap position stop, higher, lower
CControllable
EndPosR ABB_a_dSPS End position raise reached M
EndPosL ABB_a_dSPS End position lower reached M
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 126
CLCnt ABB_v2_dMV Contact life counter value E
CLRs ABB_v1_dSPC Reset contact life counter EControllable
OpRs ABB_v1_dSPC Reset operation counter EControllable
CmdFlt ABB_v1_dSPS Alarm for a command without an expected position change
E
ConvFlt ABB_v1_dSPS General tap position conversion error
E
InvPosChg ABB_v1_dSPS Last position change was an invalid change
E
TapChgFlt ABB_v1_dSPS Alarm for none or illegal tap position change
E
TapPosFlt ABB_v1_dSPS Alarm that indicates a problem with the position indication
E
HiTapPos ABB_b_dINS High tap position E
LoTapPos ABB_b_dINS Low tap position E
3.2.154 CBPPTRC
PTRC class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PTRC PTRC for MAF CBP
Data
Common Logical Node Information
Mod ABB_c_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Op ABB_b_dACT Operate (combination of subscribed Op from protection functions)
C
Str ABB_b_dACD Sum of all starts of all connected Logical Nodes
O
CapDisc ABB_v1_dSPS Signal indicating the capacitor bank status
E
Inh ABB_v1_dSPS Capacitor bank inhibit signal
E
3.2.155 SECLLN0 Revision 1
LLN0 class
Attribute DATA Explanation M/O/E Remarks
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 127
Name Type/C
LLN0Logical node 0 for
SECAUD
Data
Common Logical Node Information
Mod ABB_c_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_ln0_dLPL Name plate M
Status Information
3.2.156 CMMXU Revision 4
MMXU class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
MMXU Current monitoring
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
A ABB_n_dWYE Phase currents (IL1, IL2, IL3) O
3.2.157 VMMXU Revision 1
MMXU class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
MMXU Voltage monitoring
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 128
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
PPV ABB_a_dDEL Phase to phase voltages
(VL1VL2, …)
O
3.2.158 VNMMXU Revision 4
MMXU class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
MMXU Voltage monitoring Ph-Gnd
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
PhV ABB_n_dWYE Phase to ground voltages
(VL1ER, …)
O
3.2.159 CMSQI Revision 3
MSQI class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
MSQICurrent monitoring,
sequence values
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
SeqA ABB_b_dSEQ Positive, Negative and Zero C
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 129
Sequence Current
3.2.160 VMSQI Revision 3
MSQI class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
MSQIVoltage monitoring,
sequence values
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
SeqV ABB_b_dSEQ Positive, Negative and Zero
Sequence Voltage
C
3.2.161 LPHD Revision 6
LPHD class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
LPHDPhysical device
information
Data
Common Logical Node Information
PhyNam ABB_b_dDPL Physical device name
plate
M
PhyHealth ABB_n_dINS Physical device health M
Status Information
Proxy ABB_b_dSPS Indicates if this LN ia a
proxy
M
3.2.162 TEIGGIO
GGIO class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 130
GGIO Time Integrator
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Alm ABB_a_dSPS General single alarm O
Wrn ABB_v1_dSPS Warning E
AccTms ABB_v2_dMV Accumulated time high E
RsAccTms ABB_v1_dSPC Reset time EControllable
3.2.163 TEILGGIO Revision 1
GGIO class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
GGIO Running hour-meter
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Alm ABB_a_dSPS General single alarm O
Wrn ABB_v1_dSPS Warning E
AccmTmDay ABB_v2_dMV Accumulated time in hours E
AccmTmh ABB_v2_dMV Accumulated time in days E
RsAccTm ABB_v1_dSPC Reset accumulated time EControllable
AddTm ABB_v1_dSPC Add time to accumulated
time
EControllable
Ov ABB_v1_dSPS Overflow E
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 131
3.2.164 SXCBR Revision 1
XCBR class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
XCBR Circuit breaker
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Loc ABB_a_dSPS Local operation (local means
without substation
automation communication,
hardwired direct control)
M
OpCnt ABB_b_dINS Operation counter M
Pos ABB_c_dDPC Switch position M Controllable
BlkOpn ABB_a_dSPC Block opening M Controllable
BlkCls ABB_a_dSPC Block closing M Controllable
CBOpCap ABB_h_dINS Circuit breaker operating
capability
M
BlkUpd ABB_v1_dSPC Block update E Controllable
3.2.165 SXSWI Revision 1
XSWI class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
XSWI Circuit switch
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 132
NamPlt ABB_a_dLPL Name plate M
Status Information
Loc ABB_a_dSPS Local operation M
OpCnt ABB_b_dINS Operation counter M
Pos ABB_c_dDPC Switch position M Controllable
BlkOpn ABB_a_dSPC Block opening M Controllable
BlkCls ABB_a_dSPC Block closing M Controllable
SwTyp ABB_g_dINS Switch type M
SwOpCap ABB_f_dINS Switch operating capability M
BlkUpd ABB_v1_dSPC Block update E Controllable
3.2.166 DPGGIO
GGIO class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
GGIO Generic double point status
Data
Common Logical Node Information
Mod ABB_aINC Mode M
Beh ABB_aINS Behaviour M
Health ABB_cINS Health M
NamPlt ABB_aLPL Name plate M
Status Information
DPCSO ABB_bDPC General position indication O Controllable
3.2.167 TRPTTR Revision 4
PTTR class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PTTRThermal overload, two time
constants
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 133
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Str ABB_b_dACD Start signal O
Op ABB_b_dACT Thermal Overload trip M
AlmThm ABB_a_dSPS Thermal Alarm O
AlmThm2 ABB_a_dSPS Second level Thermal
overload alarm
E
LO ABB_v1_dSPS Thermal Overload lockout E
Wrn ABB_v1_dSPS Warning signal: Trip within
set warning time
E
TmmOp ABB_v2_dMV Estimated time to trip (in min) E
TmmRsLO ABB_v2_dMV Estimated time to reset of
lockout (in min)
E
AClcPct ABB_v2_dMV Current measured by the
function in % of rated current
E
TmpPct ABB_v2_dMV Percentage of the
heatcontent of the
transformer
E
3.2.168 EF4LLN0 Revision 1
LLN0 class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
LLN0 Logical node 0 (for EF4)
Data
Common Logical Node Information
Mod ABB_aINC Mode M
Beh ABB_aINS Behaviour M
Health ABB_cINS Health M
NamPlt ABB_ln0LPL Name plate M
Status Information
IvdCrv ABB_v1SPS Invalid coefficients for user
programmable curve
E
3.2.169 EF4PTRC Revision 3
PTRC class
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 134
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PTRC Trip logic for EF4
Data
Common Logical Node Information
Mod ABB_c_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Op ABB_b_dACT Operate (combination of
subscribed Op from
protection functions)
C
Str ABB_b_dACD Sum of all starts of all
connected Logical Nodes
O
OpSOF ABB_v2_dACT Trip signal from earth fault
switch onto fault function
E
StrSOF ABB_v2_dACD Start signal from earth fault
switch onto fault function
E
3.2.170 EF4PTRC Revision 4
PTRC class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PTRC Trip logic for EF4 (NS4)
Data
Common Logical Node Information
Mod ABB_c_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Op ABB_b_dACT Operate (combination of
subscribed Op from
protection functions)
C
Str ABB_b_dACD Sum of all starts of all
connected Logical Nodes
O
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 135
3.2.171 EF4RDIR Revision 6
RDIR class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
RDIR Directional element for EF4
Data
Common Logical Node Information
Mod ABB_c_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Dir ABB_b_dACD Direction M
3.2.172 PH1PTOC Revision 3
PTOC class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PTOC
Overcurrent function used in
four-stage protections, one
phase
Data
Common Logical Node Information
Mod ABB_c_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Str ABB_b_dACD Start M
Op ABB_b_dACT Operate M
3.2.173 EF4PTRC Revision 4
PTRC class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 136
PTRC Trip logic for EF4
Data
Common Logical Node Information
Mod ABB_c_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Op ABB_b_dACT Operate (combination of
subscribed Op from
protection functions)
C
Str ABB_b_dACD Sum of all starts of all
connected Logical Nodes
O
3.2.174 LLN0 Revision 4
LLN0 class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
LLN0 Logical node 0
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_n_dINS Health M
NamPlt ABB_ln0Root_dLPL Name plate M
Status Information
3.2.175 TMAGGIO
GGIO class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
GGIO Signal matrix
Data
Common Logical Node Information
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 137
Mod ABB_aINC Mode M
Beh ABB_aINS Behaviour M
Health ABB_cINS Health M
NamPlt ABB_aLPL Name plate M
Status Information
Out1 ABB_v1SPS OR function between
inputs 1 and 16
E
Out2 ABB_v1SPS OR function between
inputs 17 and 32
E
Out3 ABB_v1SPS OR function between
inputs 1 and 32
E
3.2.176 ALMCALH Revision 1
CALH class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
CALH Alarm handling, alarm
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_a_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
GrInd ABB_a_dSPS Group alarm O
3.2.177 INDCALH Revision 1
CALH class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
CALH Alarm handling, indication
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 138
Beh ABB_a_dINS Behaviour M
Health ABB_a_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
GrInd ABB_a_dSPS Group indication O
3.2.178 WRNCALH Revision 1
CALH class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
CALH Alarm handling, warning
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_a_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
GrWrn ABB_a_dSPS Group warning O
3.2.179 ZGTLLN0
LLN0 class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
LLN0 Logical node 0 (for ZGT)
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_ln0_dLPL Name plate M
Status Information
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 139
3.2.180 ZGPDIS
PDIS class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PDIS Distance Mho protection
Data
Common Logical Node Information
Mod ABB_c_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Str ABB_b_dACD Start M
Op ABB_b_dACT Operate M
3.2.181 ZGPTRC
PTRC class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PTRCTrip logic for Distance Mho
protection
Data
Common Logical Node Information
Mod ABB_c_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Str ABB_b_dACD Start O
Op ABB_b_dACT Operate C
3.2.182 TPPIOC
PIOC class
Attribute DATA Explanation M/O/E Remarks
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 140
Name Type/C
PIOC Tank protection
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Op ABB_b_dACT Operate M
3.2.183 EF2LLN0
LLN0 class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
LLN0 Logical node 0 (for EF2)
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_ln0_dLPL Name plate M
Status Information
3.2.184 EF2PTRC
PTRC class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PTRCTrip logic for 2-stage earth
fault protection
Data
Common Logical Node Information
Mod ABB_c_dINC Mode M
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 141
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Str ABB_b_dACD Start O
Op ABB_b_dACT Operate C
3.2.185 EF2RDIR
RDIR class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
RDIR
Directional element used for
2-stage earth fault
protection
Data
Common Logical Node Information
Mod ABB_c_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Dir ABB_b_dACD Direction M
3.2.186 GEN2PHAR
PHAR class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PHARHarmonic restraint for 2-
stage protection function
Data
Common Logical Node Information
Mod ABB_c_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 142
Status Information
Str ABB_b_dACD Start (active when restraint
is needed)
M
3.2.187 EFRWPIOC
PIOC class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PIOC
Instantaneous non-
directional residual
overcurrent protection
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Op ABB_b_dACT Operate M
3.2.188 U2RWPTUV
PTUV class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PTUV Under-voltage protection
Data
Common Logical Node Information
Mod ABB_c_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Str ABB_b_dACD Start M
Op ABB_b_dACT Operate M
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 143
3.2.189 O2RWPTOV
PTOV class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PTOV Over-voltage protection
Data
Common Logical Node Information
Mod ABB_c_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Str ABB_b_dACD Start M
Op ABB_b_dACT Operate M
3.2.190 BRPTOC
PTOC class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PTOCBinary release overcurrent
protection
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Str ABB_b_dACD Start M
Op ABB_b_dACT Operate M
3.2.191 D2LLN0
LLN0 class
Attribute DATA Explanation M/O/E Remarks
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 144
Name Type/C
LLN0 Logical node 0 (for D2)
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_ln0_dLPL Name plate M
Status Information
3.2.192 D2PTOC
PTOC class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PTOC
Overcurrent protection used
in two-step directional
overcurrent function
Data
Common Logical Node Information
Mod ABB_c_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Str ABB_b_dACD Start M
Op ABB_b_dACT Operate M
3.2.193 AGSAL Revision 2
GSAL class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
GSAL Security
Data
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 145
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
OpCntRs ABB_f_dINC Resetable Security Violations counter
M Controllable
NumCntRs ABB_o_dINS Number of counter resets M According to Edition 2
AuthFail ABB_a_dSEC Authorisation failures M
AcsCtlFail ABB_a_dSEC Access control failures detected
M
SvcViol ABB_a_dSEC Service privilege violations M
Ina ABB_a_dSEC Inactive associations M
3.2.194 BBS6LLN0 Revision 1
LLN0 class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
LLN0LN0 for 6 zone Busbar
protection
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_ln0_dLPL Name plate M
Status Information
3.2.195 BDZSGAPC
GAPC class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
GAPC
Busbar differential
protection, dynamic zone
selection
Data
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 146
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Op ABB_b_dACT Operate M
Str ABB_b_dACD Start M
IntIn ABB_v1_dINS Number of protection zones which are currently in use
E
3.2.196 BFPTRC
PTRC class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PTRC
Busbar differential
protection, single phase
feeder
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Tr ABB_b_dACT Trip C
CfgZn ABB_v1_dINS Feeder CT connection status towards the BBP zones
E
3.2.197 BICPTRC
PTRC class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PTRC
Busbar differential
protection, bus
interconnection
Data
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 147
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Tr ABB_b_dACT Trip C
CfgZn1 ABB_v1_dINS Bus-interconnection CT1 connection status towards the BBP zones
E
CfgZn2 ABB_v1_dINS Bus-interconnection CT2 connection status towards the BBP zones
E
3.2.198 BZNPDIF Revision 2
PDIF class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PDIFBusbar differential
protection, zone
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Op ABB_b_dACT Operate M
DifAClc ABB_o_dWYE Differential current O
RstA ABB_o_dWYE Restraint current O
ExBayOp ABB_v1_dSPS Zone tripped due to external trip from one of the connected bays
E
ExZnOp ABB_v1_dSPS Zone tripped due to external input signal
E
OpDif ABB_v2_dACT Differential trip E
3.2.199 BCZPDIF Revision 1
PDIF class
Attribute DATA Explanation M/O/E Remarks
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 148
Name Type/C
PDIFBusbar differential
protection, check zone
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Op ABB_b_dACT Operate M
DifAClc ABB_o_dWYE Differential current O
RstA ABB_o_dWYE Restraint current O
3.2.200 L4CLLN0 Revision 2
LLN0 class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
LLN0 LLN0 for L4C
Data
Common Logical Node Information
Mod ABB_a_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_ln0_dLPL Name plate M
Status Information
3.2.201 L4CPDIF
PDIF class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PDIF PDIF for L4C
Data
Common Logical Node Information
Mod ABB_c_dINC Mode M
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 149
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Op ABB_b_dACT Operate M
3.2.202 L4CPDIF Revision 1
PDIF class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PDIF PDIF for L4C
Data
Common Logical Node Information
Mod ABB_c_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Op ABB_a_dACT Operate M
3.2.203 L4CPTRC
PDIF class
Attribute
Name
DATA
TypeExplanation
M/O/E
/CRemarks
PTRC PTRC for L4C
Data
Common Logical Node Information
Mod ABB_c_dINC Mode M
Beh ABB_a_dINS Behaviour M
Health ABB_c_dINS Health M
NamPlt ABB_a_dLPL Name plate M
Status Information
Op ABB_a_dACT Operate C
Str ABB_b_dACT Start O
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 150
4 Common Data Class Extensions
No common data class extensions have been made.
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 151
5 Enum types Extensions
No Enum types extensions have been made.
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 152
6 Control Block Extensions
No Control block extensions have been made.
Copyright 2013 ABB. All rights reserved.
ABB AB
Doc. no. Lang. Rev. ind. Page
1MRG025249 en A 153
REVISION
Rev. ind. Page (P) Chapt. (C)
Description Date Dept./Init.
- All New Document 2016-10-11TPTC/JO
A 3.2.117-8,3.2.193
Changed LN type revision and DATA type for AGSAL, TR1ATCC and TR8ATCC
2017-02-07TPTC/JO