Upload
others
View
2
Download
0
Embed Size (px)
Citation preview
Aalborg Universitet
Pulse Pattern-Modulated Strategy for Harmonic Current Components Reduction inThree-Phase AC–DC ConvertersDavari, Pooya; Zare, Firuz; Blaabjerg, Frede
Published in:I E E E Transactions on Industry Applications
DOI (link to publication from Publisher):10.1109/TIA.2016.2539922
Publication date:2016
Document VersionEarly version, also known as pre-print
Link to publication from Aalborg University
Citation for published version (APA):Davari, P., Zare, F., & Blaabjerg, F. (2016). Pulse Pattern-Modulated Strategy for Harmonic CurrentComponents Reduction in Three-Phase AC–DC Converters. I E E E Transactions on Industry Applications,52(4), 3182-3192. DOI: 10.1109/TIA.2016.2539922
General rightsCopyright and moral rights for the publications made accessible in the public portal are retained by the authors and/or other copyright ownersand it is a condition of accessing publications that users recognise and abide by the legal requirements associated with these rights.
? Users may download and print one copy of any publication from the public portal for the purpose of private study or research. ? You may not further distribute the material or use it for any profit-making activity or commercial gain ? You may freely distribute the URL identifying the publication in the public portal ?
Take down policyIf you believe that this document breaches copyright please contact us at [email protected] providing details, and we will remove access tothe work immediately and investigate your claim.
Downloaded from vbn.aau.dk on: April 30, 2017
1
Pulse Pattern Modulated Strategy for Harmonic Current Components Reduction in
Three-Phase AC-DC Converters
Pooya Davari Member, IEEE
Department of Energy Technology Aalborg University
9220 Aalborg, Denmark [email protected]
Firuz Zare Senior Member, IEEE
Danfoss Power Electronics A/S 6300 Gråsten, Denmark
Frede Blaabjerg Fellow, IEEE
Department of Energy Technology Aalborg University
9220 Aalborg, Denmark [email protected]
Abstract -- Generated harmonic current as a consequence of
employing power electronics converter is known as an important
power quality issue in distribution networks. From industry
point of view complying with international standards is
mandatory, however cost and efficiency are two other important
features, which need to be considered in order to be competitive
in the market. Therefore, having a flexibility to meet various
requirements imposed by the standard recommendations or
costumer needs is at most desirable. This makes the generated
harmonic current mitigation a challenging task especially with
three-phase diode bridge rectifier, which still is preferred in
many power electronic systems. This paper addresses a novel
current modulation strategy using a single-switch boost three-
phase diode bridge rectifier. The proposed method can
selectively mitigate current harmonics, which makes it suitable
for different applications. The obtained results at experimental
and simulation levels verify and confirm the robustness of the
proposed approach.
Index Terms--Selective harmonic mitigation, three-phase
rectifier, current control, modulation, electronic inductor.
I. INTRODUCTION
AC to DC conversion is an inevitable stage in most power
electronic systems, but it is responsible for generating line
current harmonics especially if the conventional topologies
such as six-pulse diode rectifier are employed. The level of
generated current harmonics of this conversion stage is of
significant importance as it can easily deteriorate the supply
network quality [1]-[6]. Although the power electronics
technology has brought new insight in many applications,
however controlling their generated harmonics at certain
levels is not achievable without additional cost and circuitry.
The basic topology for AC to DC conversion has started by
utilizing a diode bridge rectifier due to many reasons such as
simplicity, reliability, robustness, and being cost-effective
compared to other complex systems such as active front end
systems. However, the diode rectifiers impose a higher level
of line current harmonics. Over the past years, many
approaches have been studied and introduced from absolutely
passive up to fully active methods [1], [4]-[10]. A majority of
these methods have targeted pure sinusoidal waveform
generation, and as a consequence cost and complexity have
been significantly increased. Of course having a low Total
Harmonic Current Distortion (THDi) improves the system
efficiency but this is of interest for specific applications such
as space and airborne industry, where the cost of the power
converter is not the main concern. But with most applications
such as industrial Adjustable Speed Drives (ASDs), switch
mode power supplies, home appliances and etc, the key of
success is to perform a trade-off between efficiency and cost
since many manufacturers are competing in the market.
Therefore, as long as the power electronic system complies
with the recommended standards there is no need to obtain a
pure sinusoidal current waveform. Moreover, due to the cost,
power density and components limited power ratings many of
the prior-art approaches are not applicable at medium and
high power levels.
With the rapid growth of power electronics applications,
the standard recommendations such as IEC61000 are
continuously updating and becoming more stringent. In
addition, the demands on various power level and costumer
needs are extending. These bring the absolute interest of
having a flexible system which can be adapted with varied
situation as it can reduce the cost of the system significantly.
This paper proposes a novel current modulation strategy to
reduce low order harmonic current components. The
objective of the proposed method is to address a flexible
selective harmonic mitigation technique suitable for various
applications. One of the main aims in this study was to apply
an active filtering method as an intermediate circuit to the
conventional three-phase diode-rectifier. This way, no major
modifications is required for the systems which are equipped
with the three-phase diode rectifier. Therefore, the proposed
current modulation strategy is applied to a single-switch boost
topology operating in Continuous Conduction Mode (CCM).
Considering this situation its only counterpart harmonic
mitigation methods with boost capability which are applied to
the conventional diode rectifier are Δ-rectifier and boost
converter operating in Discontinuous Conduction Mode
(DCM) [5]. The Δ-rectifier principle is based on phase-
modular Power Factor Correction (PFC), meaning that three-
phase diode rectifiers with boost converter at their DC-links
are applied to each phase. Its advantage is ability to
significantly improve the input current quality; however the
2
(a) (b)
Fig. 1. Simplified circuit diagram of a three-phase diode rectifier with a controlled DC-link current, (a) ideal three-phase input currents, (b) systems schematic.
main drawback of this topology is the presence of high
number of power switches, high complexity and lower
efficiency comparing with a single-switch boost converter.
The DCM single-switch boost converter requires three
inductors at the AC-side of the diode rectifier. More
importantly this topology suffers from the large EMI
(Electromagnetic Interference) filtering effort (i.e., due to the
DCM operation) and for effective harmonic mitigation its
output voltage should be boosted above 1 kV (i.e., for grid
phase voltages of 220 or 230 Vrms) [5].
This paper is structured as follows. Section II provides
detailed analysis of selective harmonic mitigation using the
proposed current modulation strategy. In Section III, practical
design considerations with respect to the boost inductor and
modulation signal generation are pointed out. The obtained
experimental results that are summarized in Section IV
validate the performance of the proposed method. Section V
recalls a brief overview on the perspectives of the proposed
method in multi-pulse rectifier systems based on comparative
numerical simulation results. Finally, concluding remarks are
given in Section VI by highlighting the main achievements
and providing suggestions for further studies.
II. PROPOSED CURRENT MODULATION STRATEGY
A. Principle of the Proposed Method
In order to understand the basic principle of the proposed
method, let’s first consider the circuit diagram depicted in
Fig. 1. As it can be seen, the current source at the DC-link
side of the rectifier draws a constant current which is equal to
I0. Therefore, the input current will be a square-wave with
120 degrees conduction due to the fact that at each instant of
time only two phases conduct and circulate DC-link current
through the main supply. Due to the nature of a three-phase
system (120o phase shift), the corresponding phase shift for
any triple harmonic would be a multiple of 360o and since the
currents at each instant are identical with opposite amplitude,
the sum of line currents ia, ib, and ic is zero at all instants of
time, which makes them to be free from triple harmonics in a
balanced system. The currents are also void of even
harmonics because of the half-wave symmetry of the
waveforms which as a matter of fact makes the most
prominent harmonics in this system to be the fifth, seventh,
eleventh, and thirteenth [11].
The proposed idea is based on adding (or subtracting)
phase-displaced current levels to the square-wave current
waveform in order to manipulate the current harmonic
components [12], [13]. To keep the above mentioned
properties (free of triple and even harmonics) the new added
pulse should be repeated 1/6 of the period. For instance, Fig.
1 depicted two sectors of 1 and 2, where at each sector ia is
circulated through one of the other phases current. Now, if the
new level is added at sector 1 it should be exactly repeated in
sector 2 (see Fig. 2(a)). This means that the frequency of the
added pulse at the DC-link should be six times of the
fundamental frequency so it can be repeated at each phase
current.
Fig. 2(a) illustrates detailed analysis of the proposed idea
for only one new level added to a constant square wave. As
can be seen the proposed current waveform is comprises of
three square-wave signals with different magnitudes and pulse
widths. The first current waveform has the magnitude of I0
with the conduction phase angle of 30o, which is defined
based on the normal operating modes of a three-phase diode
rectifier and the conduction phase angle cannot be altered.
The second current waveform has the magnitude of I1 with the
conduction phase angle of α. The third current waveform has
the magnitude of I1 but with a different conduction phase
angle (α). These current waveforms can be analyzed based
on a periodic square-wave Fourier series in which the
fundamental input current magnitude and its harmonics can be
calculated as follows:
0 1 1 1 11
4cos( 30) cos( ) cos( )ni I n I n I n
n
(1)
Equation (1) shows that the fundamental current can be
3
(a)
(b)
Fig. 2. Detailed analysis of the proposed current modulation technique with: (a) one new added level, (b) generalized m-level pulse modulated.
defined by selecting the variables I0, I1, 1 and 11 but a main
consequence will be on harmonic magnitudes. According to
the line current waveform depicted in Fig. 2(a) the following
condition should be valid:
11 1,
2 6where
(2)
Considering (1) and (2) and having 1 and 11 as the
switching angles, up to two selected low order harmonics (ih
and ij) can be cancelled out. The mathematical statement of
these conditions can be expressed as (3). This is a system of
three transcendental equations with three unknown variables
I0, I1, 1:
1 0 1 1 1 1
0 1 1 1 1
0 1 1 1 1
4 2cos cos cos
6 3
4 2cos cos cos 0
6 3
4 2cos cos cos 0
6 3
a
h
j
i I I I M
i I h I h I hh
i I j I j I jj
(3)
The proposed method can be further extended to a
multilevel current waveform. Fig. 2(b) illustrates a
generalized pulse modulated current waveform, where m is
the number of switching angles. By extending (3) and using
Fourier series, the amplitude of any odd nth
harmonic of the
stepped current waveform can be expressed as:
0
1
4 1 2cos cos( ) cos
6 3
n
m
k k k k
k
i
I n I n I nn
(4)
According to Fig. 2(b), 1 to m must satisfy the following condition:
1 2 3
6 2m
(5)
From (5) it can be seen that the degree of freedom in
manipulating the current waveform is only 60o, which makes
the control of the harmonic components a difficult task.
Therefore, to give more flexibility to (4) the new added levels
should not necessarily have same amplitude. In addition, the
amplitude could be positive or negative, which totally
depends on the targeted harmonics and the desired
modulation index Ma (fundamental harmonic content). As the
equations are nonlinear, numerical solutions are required to
find proper values for these variables.
B. Optimum Harmonic Reduction
To target more harmonic components the number of the
current levels need to be increased, but on the other hand it
reduces the feasibility of practical implementation since the
new added levels and switching angles depends on the
tracking performance of the power electronics unit and its
controller. Therefore, in order to keep the number of the
added current levels to minimum while obtaining desirable
outcome an optimization needs to be performed. The basic
principle of the applied optimization is to consider the
maximum permissible harmonic levels allowed by the
application or the grid code. In other word, instead of fully
nullifying, the harmonic components could be reduced to
acceptable levels by adding suitable constraints (Ln) to the set
of the above mentioned equations. The problem is now
described as an optimization function (Fn) that searches a set
of m and Im values over the allowable intervals.
1 1 1
1
, where 5,7,11,13,
a
n
n n
F M i L
iF L n
i
(6)
Based on (6) an objective function needs to be formed to
obtain a minimum error. The objective function (Fobj) plays
an important role in leading the optimization algorithm to the
suitable set of solution. Here Fobj is formed based on squared
error with more flexibility by adding constant weight values
4
(a)
(b)
Fig. 3. The implemented three-phase AC-DC system with the proposed selective harmonic elimination method, (a) overal system schematic and
control structure, (b) photograph of the implemented hardware setup.
(Wn) to each squared error function [14]. The value of the Wn
in the objective function prioritized the included functions as
follows:
2, where 1,5,7,11,13,obj n n nF W F L n (7)
III. IMPLEMENTATION DETAILS AND HARDWARE SETUP
To control the DC-link current shape and magnitude
following the waveforms shown in Fig. 2, a boost converter
topology based on electronic inductor [12], [13], [15]-[19]
concept is employed. Fig. 3 depicts the overall system
structure and the implemented hardware setup. Using the
conventional boost topology has the advantage of boosting
the output DC voltage which is suitable when the DC-link is
fed to an inverter. Moreover, as the DC-link current is
controlled based on the load power it has the advantage of
keeping the THDi independent of load profile.
Fig. 3(b) shows the implemented prototype. Here, one
SEMIKRON-SKD30 was used as a three-phase bridge
rectifier and one SEMIKRON-SK60GAL125 IGBT-diode
module is employed in the boost topology. A Texas
Instrument TMS320F28335 is used for control purposes and
LEM current and voltage transducers are used as
measurement unit.
To synchronize the current controller with the grid a
Second-Order Generalized Integrator (SOGI) based phase
locked loop (PLL) system is adopted [20]. As Fig. 3(a)
depicted, for the simplicity, one line-to-line voltage is fed to
the PLL and therefore the result will have 30o phase shift
regarding to the phase voltage, which should be corrected
within the reference current generator algorithm. In order to
obtain a discrete-time integrator for PLL and PI controller,
the trapezoidal discretization method is used.
A. Boost Inductor
Selection of the boost inductor is a challenging task as it
contributes to the system loss, power density and current
ripple. To better understand this, the inductor current in a
steady-state CCM is analyzed. Here the switching frequency
is considered to be high enough so that the rectified voltage
and output voltage are constant during one switching cycle.
Therefore, the inductor value can be calculated as,
,
, ,
(1 ) 1 1o
dc sw avg
sw avg L pk pk sw on off
V D DL where f
f I T T T
(8)
where Vo is the output voltage, fsw,avg is the average switching
frequency, ∆IL,pk-pk is the peak to peak inductor current ripple
and D is the steady-state duty cycle of the boost converter.
Using (8) the minimum required switching frequency (fsw,avg)
can be selected by considering the maximum peak to peak
inductor current ripple (D = 0.5) as,
,
, ,max4
o
sw avg
dc L pk pk
Vf
L I
(9)
Following (8) and (9) the optimum switching frequency
can be selected by making a tradeoff among the system
efficiency, size and cost [21]. For example the system
efficiency can be optimized by minimizing the switching
frequency by allowing more ripple current for high power
applications and it will result in lower switching losses.
As mentioned before the THDi can be independent of the
load profile. Equation (10) can be rewritten based on the
output average current as
2, ,
,
(1 )(1 )where
L pk pk L pk pko
dc ripple
sw avg ripple out L out
I I DV D DL k
f k I I I
(10)
with kripple being the peak-to-peak ripple factor, IL the average inductor current and Iout the average output current. Hence, keeping the ripple factor as a constant value will make the input current quality independent of the load profile. However, careful selection of the ripple factor is needed as it
5
Fig. 4. Detailed analysis of the three different modulation types: (a) proposed current modulation with one new added level, (b) conventional flat current modulation, (c) proposed current modulation with one new
subtracted level.
has direct impact on the ripple current, which as stated in (9) can affect the inductor size, system efficiency and cost [21].
Depending on the application requirement the converter
may operate in partial loading conditions such as in ASD
applications. In partial loading condition the DC-link current
iL can become discontinuous which adversely affect the
harmonic reduction performance of the proposed method.
However, by suitable selection of the converter parameters,
the converter can cover wide range of loading conditions.
Therefore, in order to guarantee CCM operation of the
converter the parameters (i.e., fsw, Ldc, ΔIL) should be
calculated based on the minimum intended output power. This
condition based on Boundary Condition Mode (BCM)
operation (IL = ΔIL,pk-pk/2) is,
1
2 2
1
1
61 60
11 60
21 6
601
o
M M
o o
dc
sw,avg O min
M M o
M
r r
D D V KL with K
f Pr r
r
(11)
with rM being the ratio between the calculated current levels
rM = I1/I0, and K a coefficient factor which depends on the
applied modulation type as depicted in Fig. 4. As it can be
seen from Fig. 4, three different modulations can be
considered. The first type is when a new current level is
added to the square-wave waveform (i.e., α1 < 60o). The
second type is conventional square-wave (i.e., α1 = 60o). The
third type is when a new current level is subtracted from the
square-wave current (i.e., α1 > 60o). In order to guarantee the
CCM operation the minimum applied current level should be
considered. This condition is reflected using the calculated K
factor in (11). Therefore, considering the minimum intended
output power level the converter parameters should be
selected based on the applied current modulation type. For
instance under same condition, the first and second types of
modulation can operate in CCM operation at lower power
levels comparing with the third modulation type which the
current becomes discontinuous at higher power levels.
B. Modulation Signal
As Fig. 3(a) illustrates, the reference current is formed by
multiplying the voltage controller output by a pre-
programmed modulation signal. Fig. 5 depicts the basic
concept in generating the modulation signal (i.e., iM)
following Fig. 2(a). As it can be seen, iM can be generated
based on the sum of absolute values of three-phase input
currents. The illustrated switching parameters (i.e., I0, I1 and
1) at both grid side and DC-link currents helps to better
understand this relation. As it can be seen the period of the
modulation signal iM is 1/6 of the input currents iabc.
Therefore, the simplest way to generate and synchronize the
modulation signal inside the controller is to compare it with a
sinusoidal signal (i.e., |sin(3ω0t)|) using the PLL estimated
angular frequency (ω0). Comparing the switching angles with
the sinusoidal waveform yields the following simple
conditions:
0
0 1
1 11
0
0
0 1
1 11
0
( sin(3 ) sin(3 ))
:
( sin(3 ) sin(3 ))
:
M
M
M
M
if t
i I I
else
i I
if t
i I I
else
i I
(12)
Here, based on the fact that the proposed method is adding
or subtracting phase-displaced current levels, two conditions
have been considered, which results in different modulation
signals. It can be known from Fig. 2(a) that adding a phase-
displaced current level requires to have α1 < α11. However to
reduce a specific set of harmonic components, phase
displaced current level needs to be subtracted. Therefore, for
those situations α1 should be set above α11 (α1 > α11). The
above equation can easily be extended to multi-level situation
by applying (12) to each switching parameters and summing
up the corresponding modulation signals.
As it is mentioned, the reference tracking performance of
the current controller has an important role in the harmonic
mitigation performance. Therefore, the bandwidth of the
6
Fig. 5. Synthesis of the modulation signal (i.e., iM ) at the DC-link based on three-phase input currents.
Fig. 6. Obtained results for sqaure-wave modulation using hysteresis current control at Vo = 700 Vdc and Po = 3kW (Po = 60%): (a) simulation results of three-phase input currents with Fast Fourier Transform (FFT)
of the input current (ia), (b) measured experimental results of three-phase input currents with FFT of the input current (ia).
current controller should be high enough to accurately follow
the applied multi-pulse pattern modulation. For the traditional
PWM-based PI current controller the control loop bandwidth
needs to be less than 1/5 of the switching frequency (i.e., in
the case of using Tustin or Trapezoidal discretization
method). This may result in having a high switching
frequency, which can either exceeds the power switching
device limits or increase the switching losses. Hence,
employing a fast current control method like hysteresis or
dead-beat are recommended.
Here, the hysteresis current control method is used.
Notably, using the hysteresis current control in the proposed
method will not result in a well-known significantly dispersed
frequency spectrum as the input voltage is a rectified voltage
with a small ripple as shown in Fig. 1 (i.e., 0.9069Vr ≤ vr ≤
1.0472Vr). Considering the boost converter CCM operation,
steady-state duty cycle D and rectified voltage Vr, the
switching frequency is changing within the following range,
0 0494 1 0966 0 0844 0 8225
r sw r
. . D . . DV f V
L I L I
(13)
To better understand this small variation, the considered
system parameters in this paper (Table I) is applied to (8),
0 241 0 302r rsw
V V. f .
L I L I
(14)
IV. RESULTS
In this section the circuit operation and the proposed
current modulation scheme are verified through different
simulation and experiments using the implemented prototype
(Fig. 3(b)). Here the flexibility of the proposed method by
targeting different set of harmonic components is illustrated.
The system parameters are listed in Table I. Notably, for all
of the harmonic reduction cases, simulation results are also
carried out to show its close agreement with the measured
experimental results.
For the sake of comparison, the conventional square-wave
(flat) current modulation has been considered as the first case.
Fig. 6 shows both the simulated and obtained measured
results along with the harmonic distribution of the input
current at phase a.
TABLE I PARAMETERS OF THE SYSTEM
Symbol Parameter Value
vabc Grid phase voltage 220 Vrms fg Grid frequency 50 Hz Lg, Rg Grid impedance 0.18 mH, 0.1 Ω
Ldc DC link inductor 2 mH Cdc DC link capacitor 470 µF Vo Output voltage 700 Vdc Kp, Ki PI controller (Boost converter) 0.01, 0.1
HB Hysteresis band 2 (A) Pomax Rated output power = 5 kW
7
Fig. 7. Obtained results for the proposed 7th and 13th harmonics cancellation using hysteresis current control at Vo = 700 Vdc and Po =
3kW (Po = 60%): (a) simulation results of three-phase input currents with Fast Fourier Transform (FFT) of the input current (ia), (b) measured
experimental results of three-phase input currents with FFT of the input
current (ia). [with I0 = 1, I1 = 0.618, 1= 42o].
Fig. 8. Obtained results for the proposed 5th and 13th harmonics cancellation using hysteresis current control at Vo = 700 Vdc and Po =
3kW (Po = 60%): (a) simulation results of three-phase input currents with Fast Fourier Transform (FFT) of the input current (ia), (b) measured
experimental results of three-phase input currents with FFT of the input
current (ia) [with I0 = 1, I1 = 0.653, 1= 70o].
Fig. 9. Calculating input current 5th and 7th harmonics magnitude
(normalized with I0 = 1) versus switching angle α1 α1 < 90oand new
added current level I1 (0 < I1 < 0.8) for two-level current modulation (i.e., transition between first and third modulation types as illustrated in Fig. 4) at DC-link following (1), where zero magnitudes (in = 0) are the possible
harmonic elimination solutions.
As the second case, adding one current level to the DC-
link current was considered to target two low order
harmonics. Hence, the cancellation of 7th
and 13th
harmonic
orders have been considered by solving (3) using MATLAB
function – “fsolve”. Fig. 7 illustrates the obtained results. As
it can be seen from Fig. 7, 7th
and 13th
harmonic components
have been significantly reduced.
In the third case as depicted in Fig. 8, 5th
and 13th
harmonics have been targeted. However, the obtained results
in Figs. 7 and 8 clearly show that the consequence of
canceling 7th
harmonic is the increase of the 5th
harmonic
order and vice versa. This results in higher THDi and power
factor (λ) comparing with the conventional square-wave case.
To better understand this relation, Fig. 9 illustrates the
possible input current magnitudes regarding to both 5th
and 7th
harmonics orders as a function of switching angle (α1) and
new added current level (I1) when a two-level current
modulation is applied to the DC-link. As can be seen, the
solutions for eliminating 5th
harmonic attained when the
switching angle is within the range 65o < α< 90
o which is in
contrary to 7th
harmonic, where 40o < α< 55
o making it
impossible to eliminate these two harmonics at the same time.
A proper selection of the harmonics to be reduced or
eliminated depends on the application needs. To exemplified,
in the second scenario adding two levels to the square-wave
current is considered following (4) and 7th
, 11th
and 13th
harmonic orders are targeted to be half of their values
comparing to the square-wave current. Here, following (7) an
8
Fig. 10. Obtained results for the proposed 7th , 11th and 13th harmonics
cancellation using hysteresis current control at Vo = 700Vdc and Po = 3kW (Po = 60%): (a) simulation results of three-phase input currents with Fast
Fourier Transform (FFT) of the input current (ia), (b) measured experimental results of three-phase input currents with FFT of the input
current (ia) [with I0 = 1, I1 = 0.7328, 1= 38.3o, I2 = 0.7328, 2= 51.5o].
Fig. 11. Simulated input current ia for the proposed 7th and 13th harmonic reduction at different power levels: (a) input current waveforms with
corresponding THDi and λ (b) FFT of the input current (ia).
optimization needs to be performed, which has been done
using a MATLAB genetic optimization algorithm. It is
important to apply a suitable restriction following (5) and (6).
As Fig. 10 shows the three harmonic orders of 7th
, 11th
and
13th
have been reduced which as explained before results in
increase of the 5th
harmonic. Table II summarizes the
obtained results based on the targeted harmonic orders and
THDi for both the proposed and the conventional square-
wave methods. As can be seen for all cases the obtained
results slightly differ from what expected which is due to the
presence of grid impedance, and consequently affects the
calculated angles.
As it was discussed in Section III.A, depending on the
application requirement the converter may operate at different
partial power. In fact, this is quite common in applications
such as ASD systems [22]. Here, the first modulation type
where 7th
and 13th
harmonic orders are targeted (Fig. 7) is
considered when the output power is changed in the range of
10% < Po < 100%. Notably, following (11) the converter
parameters have been re-calculated in order to obtain CCM
operation based on the minimum power (i.e., Po = 10%).
Therefore, Ldc and HB are changed to 4 mH and 0.5 A,
respectively. Fig. 11 shows the obtained simulation results of
input current at phase-a (ia) at different power levels along
with their corresponding harmonic distribution. As it can be
seen from Fig. 11(b), although at all power levels same THDi
is obtained, but notably at lower power levels (i.e., Po = 10%
and Po = 30%) 7th
and 13th
harmonics of interest are more
reduced. This is due to the fact that in simulation the line
impedance is constant and at lower powers the effective line
impedance reduces and consequently its effect on the current
modulation as a phase-shift error reduces as well.
To further verify the proposed method at different power
levels, same condition is applied to the hardware prototype
and the obtained experimental results at Po = 100% and 10%
are illustrated in Fig. 12. As it can be seen from both
simulation and experimental results, the performance of the
system in terms of THDi and λ is almost constant regardless
of the load power.
Finally, the start-up and shut-down dynamic behavior of
the implemented system are illustrated in Fig. 13. For the
start-up phase of operation, the input voltage is already
TABLE II COMPARATIVE EXPERIMENTAL RESULTS AT OUTPUT POWER LEVEL OF 3 KW
Harmonic Mitigation
Strategy
Harmonic Distribution and THDi (%)
,5
,1
a
a
i
i ,7
,1
a
a
i
i ,13
,1
a
a
i
i ,13
,1
a
a
i
i THDi λ
7th
, 13th
harmonic cancellation (Fig. 7(b))
32.7 0.5 9.4 0.8 35.3 0.93
5th
, 13th
harmonic cancellation (Fig. 8(b))
2.1 38.5 25.4 1.5 48.6 0.88
7th
,11th
,13th
harmonic cancellation (Fig. 10(b))
38.4 8 4.5 3.4 41.1 0.91
Conventional method (square-wave) (Fig. 6(b))
21 13 8.9 7 29 0.94
9
Fig. 12. Experimental results for the proposed 7th and 13th harmonics cancellation at different power levels: (a) measured three-phase input
currents with Fast Fourier Transform (FFT) of the input current (ia) at 100% of rated power (Po = 5 kW) and (b) measured three-phase input currents with Fast Fourier Transform (FFT) of the input current (ia) at 10% of rated power
(Po = 500 W). [Ldc = 4 mH, HB = 0.5 A]
Fig. 14. Extension of conventional 12-pulse rectifier system connected in parallel on DC side applying the proposed current modulation strategy. (The leakage inductances of L1 = L2 = L3 = 10 µH, winding resistance of R1 = R2
= R3 = 0.1 Ω, and winding ratio of nΔ/ny = 3 ).
(a)
(b)
Fig. 13. Measured dynamic behavior of input current ia and output voltage Vo at (a) startup and (b) shutdown at the nominal operating conditions.
applied, the load current is flowing and boost converter is in
the off-state. Turning on the DC-DC converter makes the
controller to start the pulse pattern modulation as seen from
the input current ia and changes the output voltage Vo from
515 Vdc to 700 Vdc without any large overshoot (Fig. 13(a)).
The symmetrical pulse patterns on the input current after 100
ms validate the PLL settling time. At shut-down phase of
operation the control circuit permanently turns off the IGBT
switch so it stops the current modulation and the output
voltage drops to 515 Vdc (Fig. 13(b)).
V. PERSPECTIVES
The proposed concept gives the possibility to eliminate
various sets of harmonic components in a three-phase diode
rectifier based on electronic inductor concept. Therefore,
based on the application requirement employing the proposed
method can further improve the input current quality by
reducing the low order harmonics. However, as stated before,
targeting 5th
and 7th
orders harmonic simultaneously solely
based on a single unit system is impossible. In this section,
one of the possible solutions based on combination of
nonlinear loads [22]-[24] are briefly discussed.
Here, the proposed method is applied to a multi-pulse
rectifier system [10]. Fig. 14 illustrates the application of the
proposed concept in a 12-pulse rectifier topology with a
common DC-bus. The comparative simulation results are
shown in Fig. 15. Here, except the output power which is set
to 6 kW, same parameters for the system is applied as
mentioned in Table I. Fig. 15(a) illustrates the total input
current waveform of a conventional 12-pulse rectifier system.
Basically, the 12-pulse arrangement eliminates the 5th
, 7th
,
17th
and 19th
harmonic orders (see Fig. 15(d)). The improved
input current harmonic distortion for a 12-pulse rectifier
system depending on the output power level varies between
10% < THDi < 15%. Hence, employing the proposed method
applying a two-level current modulation strategy at the DC-
link following (1) and (3) can further improve the input
current quality by targeting the remaining 11th
, 13th
harmonic
orders. Notably, here same modulation pattern is applied to
each converter. The obtained results in Figs. 15(b) and 15(d)
show that the new 12-pulse rectifier system obtained THDi ≈
5.7%, which is comparable with a conventional 18-pulse
rectifier system.
10
Fig. 15. Comparative simulation results of total input current (ia) at Po = 6 kW: (a) conventional 12-pulse rectifier (Vo = 511 Vdc), (b) proposed method with
two-level current modulation at DC-link targeting 11th and 13th harmonics (Vo = 700 Vdc) [with I0 = 1, I1 = 1.932, 1= 45o], (c) proposed method with three-
level current modulation at DC-link targeting 11th, 13th, 23th, and 25th harmonics (Vo = 700 Vdc) [with I0 = 1, I1 = 1.88, 1= 50o
, I2 = 1.97, 2= 40o], (d) THDi of total input current.
As each current level in the proposed technique can
contribute to mitigation of two low order harmonics,
extending the number of the current level using (4) can target
larger number of harmonics. Therefore, employing a three-
level current modulation at the DC-link can target two more
harmonics of 23th
and 25th
in addition to 11th
and 13th
harmonics. The obtained total input current waveform with a
unity power factor is depicted in Fig. 15(c) and the harmonic
distribution resulting in THDi ≈ 3.8% is shown Fig. 15(d). In
fact, the only remaining 35th
and 37th
harmonics imply that
applying the proposed method with three-level modulation
improves the performance of a conventional 12-pulse rectifier
system to be comparable with a conventional 24-pulse
rectifier system. Moreover, the output voltage can be
increased to higher voltage levels using the boost topology;
this is beneficial when the DC-link voltage is fed to an
inverter. Unlike the conventional multi-pulse rectifier systems
which the performance of the system is dependent of the load
profile, applying the proposed concept can maintain the input
current THDi and power factor regardless of the output power
variation.
VI. CONCLUSION
In this paper a novel current modulation technique has
been proposed for a three-phase rectifier with an electronic
inductor at the DC-link side. The proposed method modulates
the DC-link current to control the fundamental current and to
reduce the selected line current harmonics. Moreover,
calculations of the optimum switching patterns have been
conducted based on applying the minimum number of current
levels. A main advantage of the proposed method is that the
relative values of harmonics with respect to the fundamental
value remain constant regardless of load profile variation.
Applying the proposed method to other configurations such as
12-pulse rectifier can significantly improves THDi
comparative to a 24-pulse rectifier. The performance of the
proposed method can be improved by increasing the number
of the levels in order to obtain optimum solutions for low
order harmonics which completely depends on the switching
frequency and inductor size.
REFERENCES
[1] D. Kumar and F. Zare, "Harmonic analysis of grid connected power electronic systems in low voltage distribution networks," IEEE J. Emerg. Sel. Top. Power Electron., vol. 4, no. 1, pp. 70-79, 2016.
[2] J.W. Gray and F. J. Haydock, "Industrial power quality considerations when installing adjustable speed drive systems," IEEE Trans. Ind. Appl., vol. 32, no. 3, pp. 646-652, May/Jun 1996.
[3] F. Zare, "Harmonics issues of three-phase diode rectifiers with a small DC link capacitor," in Proc. of PEMC, 2014, pp. 912-917.
[4] C. Klumpner, F. Blaabjerg, and P. Thogersen, " Alternate ASDs: evaluation of the converter topologies suited for integrated motor drives," IEEE Ind. Appl. Mag., vol. 2, no. 2, pp. 71-83, 2006.
[5] J. W. Kolar and T. Friedli, "The Essence of Three-Phase PFC Rectifier
Systems - Part I," IEEE Trans. Power Electron., vol. 28, no. 1, pp. 176-198, Jan. 2013.
[6] B. Singh, B. N. Singh, A. Chandra, K. Al-Haddad, A. Pandey, and D. P. Kothari, "A review of three-phase improved power quality AC-DC converters," IEEE Trans. Ind. Electron., vol. 51, pp. 641-660, 2004.
[7] M. Liserre, F. Blaabjerg, and S. Hansen, "Design and control of an LCL-filter-based three-phase active rectifier," IEEE Trans. Ind. Appl., vol. 41, no. 5, pp. 1281-1291, 2005.
[8] M. Liserre, A. Dell'Aquila, and F. Blaabjerg, "An overview of three-phase voltage source active rectifiers interfacing the utility," in Proc. of Power Tech Conf., 2003, vol. 3, pp. 1-8.
[9] H. Akagi, "Modern active filters and traditional passive filter," Bulletin of the polish academy of sciences technical sciences, vol. 54, 2006.
[10] H. Akagi and K. Isozaki, "A hybrid active filter for a three-phase 12-pulse diode rectifier used as the front end of a medium-voltage motor drive," IEEE Trans. Power Electron., vol. 27, no. 1, pp. 69-77, Jan. 2012.
11
[11] A. M. Trzynadlowski, Introduction to modern power electronics: John
Wiley & Sons, 2010. [12] P. Davari, F. Zare, and F. Blaabjerg, “A smart current modulation
scheme for harmonic reduction in three-phase motor drive applications”, in Proc. of EPE, 2015, pp. 1-10.
[13] P. Davari, F. Zare, and F. Blaabjerg, “Pulse pattern modulated strategy for harmonic current components reduction in three-phase AC-DC converters”, in Proc. of ECCE, 2015, pp. 5968-5975.
[14] L.G. Franquelo, J. Napoles, R.C.P. Guisado, J.I. Leon, and M.A. Aguirre, "A flexible selective harmonic mitigation technique to meet grid codes in three-level PWM converters," IEEE Trans. Ind. Electron., vol.54, no.6, pp.3022-3029, Dec. 2007.
[15] K. Mino, M. L. Heldwein, and J. W. Kolar, "Ultra compact three-phase rectifier with electronic smoothing inductor," in Proc. of APEC, 2005, pp. 522-528.
[16] J. Salmon and D. Koval, "Improving the operation of 3-phase diode rectifiers using an asymmetrical half-bridge DC-link active filter," in Proc. of IAS Annual Meeting, 2000 vol. 4, pp. 2115-2122.
[17] H. Ertl and J. W. Kolar, "A constant output current three-phase diode
bridge rectifier employing a novel "Electronic Smoothing Inductor"," IEEE Trans. Ind. Electron., vol. 52, pp. 454-461, 2005.
[18] C. Galea and L. Asiminoaei, "New topology of electronic smoothing inductor used in three phase electric drives," in Proc. of EPQU, 2011, pp. 1-6.
[19] P. J. Grbovic, P. Delarue, and P. Le Moigne, "A Novel Three-Phase Diode Boost Rectifier Using Hybrid Half-DC-Bus-Voltage Rated Boost Converter," IEEE Trans. Ind. Electron., vol. 58, no. 4, pp. 1316-1329, 2011.
[20] M. Ciobotaru, R. Teodorescu, and F. Blaabjerg, "A New Single-Phase PLL Structure Based on Second Order Generalized Integrator," in Proc. of PESC, 2006, pp. 1-6.
[21] T. Nussbaumer, K. Raggl, and J.W. Kolar, "Design Guidelines for Interleaved Single-Phase Boost PFC Circuits," IEEE Trans. Ind. Electron., vol.56, no.7, pp.2559-2573, July 2009.
[22] P. Davari, Y. Yang, F. Zare, and F. Blaabjerg, “A multi-pulse pattern modulation scheme for harmonic mitigation in three-phase multi-motor drives,” IEEE J. Emerg. Sel. Top. Power Electron., vol. 4, no. 1, pp.
174–185, 2016. [23] S. Hansen, P. Nielsen, and F. Blaabjerg, "Harmonic cancellation by
mixing nonlinear single-phase and three-phase loads," IEEE Trans. Ind. Appl., vol. 36, no. 1, pp. 152-159, Jan/Feb 2000.
[24] Y. Yang, P. Davari, F. Zare, and F. Blaabjerg, “A DC-link modulation scheme with phase-shifted current control for harmonic cancellations in multidrive applications,” IEEE Trans. Power Electron., vol. 31, no. 3, pp. 1837–1840, Mar. 2016.
Pooya Davari (S’11–M’13) received B.Sc. and M.Sc. degrees in electronic engineering from the University of Mazandaran (Noushirvani), Babol, Iran, in 2004, 2008, respectively and the Ph.D. degree in power electronics from the Queensland University of Technology (QUT), Brisbane, Australia in 2013. From 2005 to 2010 he was involved in several electronics and
power electronics projects as a Development Engineer. During 2010-2014, he has designed and developed high-power high-voltage power electronic systems for multi-disciplinary
projects such as ultrasound application, exhaust gas emission reduction and tissue-materials sterilization. From 2013 to 2014 he was with Queensland University of Technology, Brisbane, Australia, as a Lecturer.
Dr. Davari joined the Department of Energy Technology at Aalborg University as a Postdoctoral Researcher in August 2014. Currently, he is an Assistant Professor with Department of Energy Technology at Aalborg University. He is awarded a research grant from Danish Council of Independent Research (DFF) in 2015. His current research interests include active front-end rectifiers, harmonic mitigation in adjustable speed drives, Electromagnetic Interference (EMI) in power electronics, high power density power electronics, and pulsed power applications.
Firuz Zare (S’98-M’01–SM’06) received his
Ph.D. in Power Electronics from Queensland University of Technology in 2002. He has spent several years in industry as a team leader and development engineer working on power electronics and power quality projects. Dr. Zare won a student paper prize at the Australian Universities Power Engineering Conference (AUPEC) conference in 2001 and was awarded a Symposium Fellowship by the Australian Academy of Technological Science
and Engineering in 2001. He received the Vice Chancellor’s research award in 2009 and faculty excellence award in research as an early career academic from Queensland University of Technology in 2007.
Dr. Zare has published over 150 journal and conference papers and technical reports in the area of power electronics. He is currently a Lead Engineer with Danfoss Power Electronics, Graasten, Denmark. He is a Task Force Leader of Active Infeed Converters within Working Group one at the IEC Standardization Committee. His current research interests include
problem-based learning in power electronics, power electronics topologies and control, pulsewidth modulation techniques, EMC/EMI in power electronics, and renewable energy systems.
Frede Blaabjerg (S’86-M’88–SM’97–F’03) was with ABB-Scandia, Randers, Denmark, from 1987 to 1988. From 1988 to 1992, he was a Ph.D. Student with Aalborg University, Aalborg, Denmark. He became an Assistant Professor in 1992, an Associate Professor in 1996, and a Full Professor of power electronics and drives since 1998 at Aalborg University. He
has been a part-time Research Leader with the Research Center Risoe working with wind turbines. In 2006-2010, he was the Dean of the Faculty of Engineering, Science and Medicine.
His current research interests include power electronics and its applications such as wind turbines, photovoltaic systems, reliability, harmonics and adjustable speed drives.
Prof. Blaabjerg has received 17 IEEE Prize Paper Awards, the IEEE Power Electronics Society (PELS) Distinguished Service Award in 2009, the EPE-PEMC Council Award in 2010, the IEEE William E. Newell Power Electronics Award in 2014, and the Villum Kann Rasmussen Research Award 2014. He was an Editor-in-Chief of the IEEE TRANSACTIONS ON
POWER ELECTRONICS from 2006 to 2012. He has been a Distinguished Lecturer for the IEEE Power Electronics Society from 2005 to 2007 and for the IEEE Industry Applications Society from 2010 to 2011. He is nominated in 2014 and 2015 by Thomson Reuters to be among the most 250 cited researchers in Engineering in the world.