Upload
piyush-agarwal
View
212
Download
0
Embed Size (px)
DESCRIPTION
bbb
Citation preview
7/18/2019 aa
http://slidepdf.com/reader/full/aa55cf882e55034664618e20fc 1/7
The Effect of Ammonia on HCl Emissions
Technical PaperBR-1880
Authors:G.E. Pavlovicz
A.A. Silva
Babcock & Wilcox
Power Generaon Group, Inc.
Barberton, Ohio, U.S.A.
M.J. Mullen
DTE Energy
Detroit, Michigan, U.S.A.
Presented to:Power Plant Air Pollutant
Control “MEGA” Symposium
Date:
August 20-23, 2012
Locaon:
Balmore, Maryland, U.S.A.
7/18/2019 aa
http://slidepdf.com/reader/full/aa55cf882e55034664618e20fc 2/7
Babcock & Wilcox Power Generation Group 1
The Effect of Ammonia on HCl Emissions
G.E. Pavlovicz
A.A. Silva
Babcock & Wilcox Power Generation Group, Inc.
Barberton, Ohio, USA
Presented at:
Power Plant Air Pollutant Control “MEGA” Symposium
Baltimore, Maryland, U.S.A. August 20-23, 2012
BR-1880
Abstract
The U.S. Environmental Protection Agency (EPA) issued
the Mercury and Air Toxics Standards (MATS) regulations
stating that existing coal-red power plants must achieve <
0.002 lb/MMBtu emissions of hydrogen chloride (HCl). EPA
Method 26A is the approved test method for halides, includ-
ing HCl, but this method can skew the HCl results high in the
presence of ammonium chloride (NH4Cl). At Detroit Edi-
son’s Monroe Power Plant Units 3 and 4, it was discovered
that a high ammonia slip from a selective catalytic reduc-
tion (SCR) system resulted in the formation of ammoniumchloride. The ne ammonium chloride particulate escapes
complete capture in the wet ue gas desulfurization (FGD)
system, and can be subsequently detected by EPA Method
26A and reported as HCl. In some cases, this can result in
HCl values being erroneously reported higher than permitted
limits. Stack testing was completed using Fourier transform
infrared (FTIR) spectrometry at various operating conditions
to understand the formation of ammonium chloride in the
system and yield the correct HCl emissions results.
Introduction
In 2009, Babcock & Wilcox Power Generation Group,
Inc. (B&W PGG) installed wet ue gas desulfurization
scrubbers at Detroit Edison’s Monroe Power Plant Units 3
and 4 to control sulfur dioxide (SO2), other acid gases, and
lterable particulate matter emissions. As part of B&W
PGG’s ongoing R&D efforts, multi-pollutant testing across
one of the new scrubbers was performed in 2010. Wet FGD
testing provides valuable information as to the performance
of the scrubbers and the results can lead to new insight on
the operation of the unit. One such insight that resulted from
this testing involved how free ammonia (NH3) can affect the
hydrogen chloride removal in the wet FGD.
The Monroe Power Plant is owned and operated by De-
troit Edison, a subsidiary of DTE Energy, and is located in
Monroe, Michigan. The plant has four (4) coal-red electric
generating units, referred to as Units 1, 2, 3 and 4. These
units were placed in service between 1971 and 1974, and
have a total electric generating capacity of 3,135 megawatts
(gross). Unit 3 is rated at approximately 785 net megawatts
(823 MW gross). Unit 4 is rated at approximately 775 net
megawatts (817 MW gross). Both units are B&W PGGsuper-critical boilers that typically burn coal at full load at
a rate of about 350 tons/hr. The typical coal blend for both
units is 65% low-sulfur western (LSW) / 35% mid-sulfur
eastern (MSE). Fuel oil is sometimes used to supplement
coal during start-up and upset situations.
Along with the B&W PGG wet FGD scrubbers, both units
are also equipped with an electrostatic precipitator (ESP)
that can achieve particulate removal efciency greater than
99%, a sulfur trioxide ue gas conditioning system that is
used to lower the resistivity of the y ash for better collection
by the ESP, and a vanadium-based SCR to reduce nitrogen
oxides (NOx) emissions.
2010 Field testing – Unit 3
In cooperation with Detroit Edison, B&W PGG initially
planned to test Unit 4 in October 2010, but an unscheduled
Unit 4 boiler outage lead to the test program being conducted
on Unit 3 instead. Though the SCR catalyst was known to be
nearing its end of life on Unit 3, it was decided to proceed
with the test program to investigate how multi-pollutants
may be affected by the catalyst.
As part of this testing, three (3) runs were performed
M.J. Mullen
DTE Energy
Detroit, Michigan, USA
7/18/2019 aa
http://slidepdf.com/reader/full/aa55cf882e55034664618e20fc 3/7
2 Babcock & Wilcox Power Generation Group
following EPA Method 26A, “Determination of Hydrogen
Halide and Halogen Emissions from Stationary Sources
Isokinetic Method,” to obtain the concentration of HCl in
the ue gas coming into and out of the wet FGD. The inlet
duct dimensions are 20 ft. x 45.5 ft. (H x W) with seven (7)
test ports spaced equally across the width. EPA Method 26A
was performed in the central ve (5) test ports. The ue in
the stack is 28 ft. in diameter with four (4) test ports spaced
90 degrees apart from each other. Testing was performedin all four (4) test ports. The results of the HCl testing are
shown in Table 1.
The results were unexpected. A high removal efciency
SO2 limestone wet FGD is expected to remove at least 99%
of the HCl entering the absorber or, at a minimum, to match
the equivalent SO2 removal in the absorber. The apparent
HCl removal was only 84%, while the SO2 removal during
the time of the test runs was measured to be an average of
~98.9% by the plant’s continuous emissions monitoring
system (CEMS). The apparent three (3) run average of the
measured HCl emission was calculated to be 0.0077 lb/
MMBtu. The HCl emission limit for Unit 3 is 0.0024 lb/
MMBtu, established by the most current State of Michigan
permit which covered the installation/operation of the FGD
system. The limit was established based upon "Best Avail-
able Control Technology." Since the EPA Method 26A test-
ing yielded apparent results that were three times the permit
limit, there was reason to believe that some form of inter -
ference with the test method was causing the high values.
After noticing that the HCl removal was unexpectedly
low, the other test data was analyzed. Three (3) runs of EPA
CTM-027, “Procedure for Collection and Analysis of Am-
monia in Stationary Sources,” were also performed around
the wet FGD. These test results, presented in Table 2, showed
abnormally high free ammonia loading to the scrubber.As shown in Table 2, Unit 3 was experiencing free am-
monia levels up to 23.5 ppmdv @ 3% O2, much higher than
the 2 ppmdv @ 3% O2 free ammonia typically expected
downstream of a properly functioning SCR catalyst. Some-
what higher ammonia levels were expected for Unit 3 due to
the age of its catalyst. However, this surprisingly high free
ammonia loading to the wet FGD was not only due to the
aging catalyst, but also because more ammonia than usual
was needed to obtain the required NOx control on account
of calibration issues with the outlet NOx meter. During the
week of testing, the SCR catalyst was also experiencing
high pressure drop.
Given these test results with high free NH3 content in
the ue gas stream, it is probable that ammonium chloride
formed. Ammonium chloride is a condensable particulate
before the air heater and forms a ne aerosol as the ue gas
gets quenched in the wet FGD. Fine particulate is not easilyremoved by a wet FGD. Flue gas sampling and emission
testing using EPA Method 26A may have erroneously cat-
egorized ammonium chloride as a free halide rather than a
particulate, which would skew the results of the test high.
In addition to the HCl and free NH3 tests, ve (5) test runs
were performed to capture condensable particulate at the wet
FGD inlet in accordance with EPA OTM-28, “Dry Impinger
Method for Determining Condensable Particulate Emissions
from Stationary Sources.” A combined sampling train of
EPA OTM-28 and EPA OTM-27, “Determination of PM10
and PM2.5 Emissions from Stationary Sources (Constant
Sampling Rate Procedure),” was used. After the collec-
tion period, the condensable particulate matter (CPM) wasanalyzed to determine the captured organic and inorganic
amounts. The inorganic catch at the inlet was also tested for
SO42-, NO2
-, NO3-, NH4
+ and Cl-. The results of the NO2- and
NO3- particulate analysis were below the detection limits.
The results of the remaining ions are shown in Table 3.
The data is fairly consistent throughout each testing day.
When comparing day-to-day results, note that the average
CPM ammonium ion concentration on 10/19 was 0.0424
lb/MMBtu, approximately six times greater than the 0.0068
lb/MMBtu average measured on 10/22. This tracked with a
review of the CEMS data, which recorded that the ammonia
ow to the SCR was higher on 10/19 compared to 10/22.
On 10/19, the average ammonia ow was 6.3 klb/hr com- pared to 4.5 klb/hr on 10/22. The constituent analyses of the
CPM indicate that the excess ammonia (converted to NH4+)
reacted with Cl- and SO42- to form ammonium chloride and
ammonium sulfate. When converting Table 3 to moles, the
balance works out well (Figure 1).
It is apparent that the ammonia slip on 10/19, triggered
by the higher ammonia ow to the SCR, resulted in the
abnormally high CPM readings.
After reviewing the data, and with the knowledge that
the SCR catalyst was being replaced in the spring of 2011,
Table 1HCl in the Flue Gas around the DTE Monroe Unit 3
Wet FGD in 2010
Run 1 2 3 Avg
2010 HCl at Inlet, ppmdv @3% O2
49.6 44.5 40.7 44.9
2010 HCl at Stack, ppmdv @3% O2
5.6 7.5 8.3 7.1
2010 HCl at Stack,lb/MMBtu
0.0060 0.0081 0.0090 0.0077
Table 2Free Ammonia in the Flue Gas around the
DTE Monroe Unit 3 Wet FGD in 2010
Run 1 2 3 Avg
2010 Free NH3 – WFGDInlet, ppmdv @3% O2
14.3 19.7 23.5 19.2
2010 Free NH3 – Stack,
ppmdv @3% O2 9.1 9.5 11.1 9.9Ammonia flow – North (A),
klb/hr 2.12 2.12 2.22 2.15
Ammonia flow – South (B),klb/hr
2.23 2.26 2.43 2.31
SCR NOx removal setting – North (A)
79.8% 79.8% 79.9% 79.8%
SCR NOx removal setting –South (B)
90.0% 90.0% 90.1% 90.0%
7/18/2019 aa
http://slidepdf.com/reader/full/aa55cf882e55034664618e20fc 4/7
Babcock & Wilcox Power Generation Group 3
Detroit Edison and B&W PGG agreed it would be benecial
to retest some key pollutants, including free NH3 and HCl.
The retesting would aim to better understand the effect that
the higher ammonia ow rates associated with the aging
catalyst likely had on emissions.
2011 Field testing – Unit 3
Once the catalyst had been replaced in the Unit 3 SCR,
testing was repeated in October and November of 2011.
Although an attempt was made to achieve the same condi-
tions as in 2010, there were a few minor differences. For the
new tests, Unit 3 was burning a 60% / 40% (LSW / MSE)
coal blend throughout the duration of the test, compared to
the 65/35 blend used in the 2010 test. Table 4 shows the dif -
ferences in the operating conditions between testing years.
Similar to 2010, three (3) test runs of EPA Method 26A
were performed, but this time the tests were only performed
at the stack. The results, along with the 2010 data, are pre-sented in Table 5.
The HCl measurements in the stack were substantially
lower than the previous year. In the 2010 testing, the inlet
HCl concentration was 44.9 ppmdv @ 3% O2 averaged over
three (3) test runs. Since the 2011 fuel chloride levels were
comparable, one can reasonably assume the 2011 inlet HCl
concentration was also comparable, which would indicate
that the wet FGD was removing >99% of the incoming HCl
as expected.
Similar differences in the outlet emissions from year to
year also occurred with the free ammonia (Table 6).
There was a signicant decrease of free ammonia in the
ue gas at the inlet of wet FGD from 2010 to 2011. With a
new SCR catalyst in place, NOx limits were met with tight
control of ammonia ow, resulting in very little ammonia
slip. The dramatic decrease in both free ammonia at the
wet FGD inlet and outlet and HCl at the outlet supports the
assertion that ammonium chloride caused the EPA Method26A results to skew the HCl measurements higher than what
was actually present.
2011 Field testing – Units 3 & 4 – FTIR
While retesting Unit 3 in 2011, Unit 4 was experienc-
ing aging catalyst issues – the same as Unit 3 in 2010. In
2011, DTE Energy also studied HCl emissions, but with
FTIR spectrometry on both units. This provided additional
information to validate the theory that ammonium chloride
forms in the presence of excess ammonia and can result
in false HCl readings. A portion of the testing using FTIR
spectrometry was performed on Unit 4, which at that time
was operating with an aging catalyst. The FTIR data on
NO, HCl and NH3 was collected using an MKS MultiGas
2030 FTIR spectrometer and adhered to EPA Method 320
and ASTM Method D6348-3 testing procedures.1 The goal
of this testing was to view the relationship between the
NH3 and HCl emissions since the FTIR could continuously
record measurements of each compound. The results are
shown in Figure 2.
The test started with the probe and lter being heated
to ~376F. After the probe was inserted into the stack, a
spike recovery was performed, which resulted in an 83%
recovery. The results of the spike recovery suggest that theHCl level was most likely near 1 ppm, which was the level
before the spike.1
After the spike recovery, the levels of HCl and NH3
steadily increased to abnormally high levels, similar to those
seen during the 2010 measurements on Unit 3 when that unit
still had the aging catalyst. Of even more interest though,
Figure 2 shows that when the probe/lter temperature was
reduced to 150F, the NH3 and HCl dropped to ~1 ppm or less,
Fig. 1 Molar comparison of condensable particulate at
Unit 3 wet FGD inlet.
Table 3Summary of Condensable Particulate Matter at Unit 3 Wet FGD Inlet
Date (2010) Oct 19 Oct 19 Oct 22 Oct 22 Oct 22
Test Run 1 2 3 4 5
CPM lb/MMBtu 0.1626 0.1634 0.0202 0.0386 0.0158
CPM – Inorganic NH4+ lb/MMBtu 0.0434 0.0413 0.0053 0.0106 0.0046
CPM – Inorganic SO42- lb/MMBtu 0.103 0.108 0.0027 0.0046 0.0035
CPM – Inorganic Cl- lb/MMBtu 0.0115 0.0083 0.0095 0.0190 0.0063
CPM – Inorganic Other lb/MMBtu 0.0035 0.0041 0.0016 0.0030 0.0004
CPM – Organics lb/MMBtu 0.0012 0.0017 0.0011 0.0014 0.0010
Ammonia Flow to SCR klb/hr 6.13 6.40 4.35 4.37 4.66
7/18/2019 aa
http://slidepdf.com/reader/full/aa55cf882e55034664618e20fc 5/7
4 Babcock & Wilcox Power Generation Group
concentrations that would be expected downstream of a wet
FGD. It appears that at the high temperature of 376F, am-
monium chloride disassociated in the probe, passed through
the lter, and was being measured as NH3 and HCl. When
the probe/lter temperature was decreased, the ammonium
chloride could not decompose, and it appears that the ne
NH4Cl aerosol was caught on the 0.01μ borosilicate glass
lter of the test apparatus. When the temperature was later
increased to 250F, the NH3 and HCl emissions started to
increase, indicating that ammonium chloride still disassoci-
ates at that temperature. This provides an explanation as to
why the EPA Method 26A test performed in 2010 indicated
high HCl emissions, since that test method operates at an
equivalent temperature. After the temperature increase, the
fact that both the HCl and NH3 trend lines increased at the
same rate suggests that the only source of these gases was
the NH4Cl decomposition.1
Additional FTIR testing was performed in December of
2011 on both Unit 3 (with a new SCR catalyst) and Unit 4
(with an aging SCR catalyst) to see the contrast. These tests
were conducted at both the wet FGD inlet and outlet loca-
tions, and incorporated changing the NOx setting controls
for the SCR to vary the amount of free ammonia at the wetFGD inlet. In addition to HCl and NH3, HF was also moni-
tored at all locations.
The Unit 3 testing on December 12, 2011 yielded results
that would be expected with a properly functioning SCR
catalyst and wet FGD – a high concentration of HCl and
very little NH3 at the wet FGD inlet and < 1 ppm of HCl
and NH3 at the wet FGD outlet (Figure 3).On December 13, the FTIR equipment was relocated to
Unit 4 which was still operating with an aging SCR catalyst.
The results were quite different from Unit 3 (Figure 4).
High concentrations of both HCl and NH3 were recorded
at the Unit 4 wet FGD inlet. Martin Spartz, Ph.D., of Prism
Analytical Technologies, Inc., noted that near 13:00, there
was a short HCl spike test performed into the exhaust and
the HCl did come up slightly while the NH3 was reduced.
This further suggests that NH4Cl was forming from the spike
since the HCl spike recovery was very poor and the NH3
Table 4Comparison of Full Load Operating Conditions
Year 2010 2011
Boiler Load, gross MW* 740 773
% S in coal** 0.97 0.98
% ash in coal** 8.9 8.6
Cl conc. in coal, ppm** 634 766
Hg conc. in coal, ppm** 0.094 0.066
*Taken from CEMS **Taken from coal analyses
Fig. 2 Wet FGD outlet readings of HCl, NH3 and NO for
Unit 4.1
Table 5Summary of HCl Around the Unit 3 Wet FGD
(2010 vs. 2011)
Run 1 2 3 Avg
2010 HCl at Inlet, ppmdv @3% O2
49.6 44.5 40.7 44.9
2010 HCl at Stack, ppmdv @3% O2 5.6 7.5 8.3 7.1
2010 HCl at Stack,lb/MMBtu
0.0060 0.0081 0.0090 0.0077
2011 HCl at Stack, ppmdv @3% O2
0.07 0.16 0.10 0.11
2011 HCl at Stack,lb/MMBtu
0.00008 0.00016 0.00011 0.00012
Table 6Summary of Free NH3 results across the Unit 3 Wet
FGD (2010 vs. 2011)
Run 1 2 3 Avg
2010 Free NH3 –WFGD Inlet, ppmdv
@3% O2
14.29 19.67 23.54 19.17
2010 Free NH3 – Stack, ppmdv @3% O2
9.10 9.54 11.10 9.92
2011 Free NH3 –WFGD Inlet, ppmdv
@3% O2
0.08 0.05 <0.04* <0.05
2011 Free NH3 – Stack, ppmdv @3% O2 0.11 0.10 0.06 0.09
2011 Ammonia flow – North (A), klb/hr
2.43 1.85 1.32
2011 Ammonia flow –South (B), klb/hr
2.28 1.62 1.10
2011 SCR NOx remov-al setting – North (A)
89.5% 69.9% 49.8%
2011 SCR NOx remov-al setting – South (B)
90.0% 70.1% 50.7%
* Below detection limit.
7/18/2019 aa
http://slidepdf.com/reader/full/aa55cf882e55034664618e20fc 6/7
Babcock & Wilcox Power Generation Group 5
level dropped.2 The corresponding data at the wet FGD outlet
showed high concentrations of HCl and NH3.
Also, the fate of HF should be noted from Figure 4. HF
and HCl are similar acid gases and both are expected to
be almost completely removed by the wet FGD and trend
at similarly low concentrations at the wet FGD outlet, as
evidenced by the Unit 3 results. Since HF remained unaf -
fected by the presence of NH3 at the wet FGD inlet and was
virtually completely removed by the wet FGD, this furthersuggests that NH4Cl formation had occurred.
To test at different levels of NH3 at the wet FGD inlet,
the NOx control set points for both the North and South
ues were reduced by 5% each. The results can be seen in
Figure 5.
Once the NOx control set points were reduced, it took
about an hour for the NH3 levels at the wet FGD inlet to
approximate steady state conditions. The HCl remained
unchanged, which suggests that the NH4Cl ne aerosol is
formed in the wet FGD. At the wet FGD outlet, as the am-
monia concentration decreased, the outlet HCl concentration
also decreased at the same rate.
Figure 5 also shows that while there was much more HCl
than NH3 at the wet FGD inlet, the NH3 emissions werealways slightly higher than HCl at the wet FGD outlet. This
provides further evidence of NH4Cl formation, suggesting
that NH3 is the limiting reagent in the formation of NH4Cl.2
Fig. 3 Wet FGD inlet and outlet readings of HCl, NH3 and HF for Unit 3.2
Fig. 4 Wet FGD inlet and outlet readings of HCl, NH3 and HF for Unit 4.2
Fig. 5 Wet FGD inlet and outlet readings of HCl, NH3 and HF for Unit 4 after a reduction in the
NOx control setting of the SCR.2
7/18/2019 aa
http://slidepdf.com/reader/full/aa55cf882e55034664618e20fc 7/7
6 Babcock & Wilcox Power Generation Group
Copyright© 2012 by Babcock & Wilcox Power Generaon Group, Inc.
a Babcock & Wilcox company
All rights reserved.
No part of this work may be published, translated or reproduced in any form or by any means, or incorporated
into any informaon retrieval system, without the wrien permission of the copyright holder. Permission re -
quests should be addressed to: Markeng Communicaons, Babcock & Wilcox Power Generaon Group, Inc.,
P.O. Box 351, Barberton, Ohio, U.S.A. 44203-0351. Or, contact us from our website at www.babcock.com.
Disclaimer
Although the informaon presented in this work is believed to be reliable, this work is published with the
understanding that Babcock & Wilcox Power Generaon Group, Inc. (B&W PGG) and the authors are supplying
general informaon and are not aempng to render or provide engineering or professional services. Neither
B&W PGG nor any of its employees make any warranty, guarantee, or representaon, whether expressed or
implied, with respect to the accuracy, completeness or usefulness of any informaon, product, process or ap-
paratus discussed in this work; and neither B&W PGG nor any of its employees shall be liable for any losses or
damages with respect to or resulng from the use of, or the inability to use, any informaon, product, process
or apparatus discussed in this work.
Summary
High ammonia levels at the wet FGD inlet can cause the
formation of NH4Cl, a ne particulate that can be detected by
EPA Method 26A and incorrectly reported as HCl. With the
new MATS regulations effective in 2015, it will be critical to
ensure that test methods accurately measure HCl emissions
in reporting to these new limits. FTIR spectrometry can be
used to track NH3 and HCl and, when performed using dif -ferent probe temperatures, to determine if NH3 is causing
the HCl emissions to read high.
Acknowledgements
The authors acknowledge and appreciate the efforts of
the Clean Air Engineering and Prism Analytical Technolo-
gies, Inc. testing crews for their valuable contribution to the
gathering of data for this project.
References
1. Spartz, M.L. Ph.D.; Kauppi, P.J.; Prism Analytical
Technologies, Inc. Detroit Edison Company Engineer -
ing HCl Emission & SCR Study, Monroe, MI – Unit 4,
October 26 – 28, 2011, Project No. 1709
2. Spartz, M.L. Ph.D.; Kauppi, P.J.; Prism Analytical
Technologies, Inc. Detroit Edison Company Engineer -
ing HCl Emission & SCR Study, Monroe, MI – Units 3& 4, December 12 – 14, 2011, Project No. 1715
Key words
Wet FGD, HCl, NH3, NH4Cl, FTIR, ammonium chloride