Air System Sizing Summary for AHU-GF-06bProject Name: 2014-09-18 Cyberjaya Skypark09/25/2014Prepared by: PECE05:59PMHourly Analysis Program v.4.4Page1of1Air System InformationAir System NameAHU-GF-06bEquipment ClassCW AHUAir System TypeSZCAV Number of zones1Floor Area346.1mLocationKuala Lumpur, Malaysia

Sizing Calculation InformationZone and Space Sizing Method:Zone L/sSum of space airflow ratesSpace L/sIndividual peak space loads Calculation MonthsJan to DecSizing DataCalculated

Central Cooling Coil Sizing DataTotal coil load89.0kWSensible coil load68.1kWCoil L/s at Aug 14005042L/sMax block L/s5042L/sSum of peak zone L/s5042L/sSensible heat ratio0.765m/kW3.9W/m257.1Water flow @ 8.9 K rise2.39L/s Load occurs atAug 1400OA DB / WB34.2 / 25.5CEntering DB / WB25.9 / 19.2CLeaving DB / WB14.7 / 14.1CCoil ADP13.5CBypass Factor0.100Resulting RH52%Design supply temp.14.4CZone T-stat Check1 of 1OKMax zone temperature deviation0.0K

Supply Fan Sizing DataActual max L/s5042L/sStandard L/s5029L/sActual max L/(s-m)14.57L/(s-m) Fan motor BHP0.00BHPFan motor kW0.00kWFan static0Pa

Outdoor Ventilation Air DataDesign airflow L/s637L/sL/(s-m)1.84L/(s-m) L/s/person4.60L/s/person