CONTENT page ABOUT THE ENTERPRISE…………………..…………………………………………… 2–3 ALPHABETICAL INDEX AND PATTERN OF CHOICE OF OUR CABLES…. 4–5 TECHNICAL INFO………………………………………………........................................ 6–8 PART I. CABLES………………………………………………………………………………... 9–180 SYMMETRICAL ………………………………………………………………………………………… 10–129 For alarm and control systems (including for nuclear power plants (NPP))…………. 11–28 For security and fire protection systems «FIRE RESISTANT»……............................................... 29–42 For security and automation systems « FIRE RESISTANT » (including for NPP)................... 43–58 For industrial interface RS485 (including for NPP and Ministry of Defense (MD))……. 59–78 For industrial network ProfiBusDP (including for NPP)……………………………………………. 79–84 For industrial networks ProfiBusPA and Foundation Fieldbus (including for NPP)…….. 85–96 For connecting PLC within DCS (including for NPP)………………………........................................... 97–112 For LonWorks technology……………………………………………….......................................................... 113–118 For local area networks (including for the Ministry of Defense of the Russian Federation)……………………………… 119–128 For digital automatic telephone exchange and telephony................................................................................................................. 129–133 COAXIAL ………………………………………………………………………………………………….. 134–169 For broadcasting systems, systems of satellite and radio communication ……….. 134–150 For cable/satellite television systems and video surveollance……………………………………... 151–166 For alarm systems ………………………………………………… 167–169 HYBRID …………………………………………………………………………………………………… 170–184 For industrial systems of control of mobile objects technological processes (including for NPP)....... 171–178 For video surveillance systems……………………………………………………………………………………. 179–182 For special application according to customer’s technical requirements…………………… 183–184 PART II. COAXIAL CONNECTORS…………………………….................................. 187–192 PART III. COAXIAL ADAPTERS…………………………………………………………. 193–196 PART IV. CABLE ASSEMBLIES…………............................................................... 197–201 PART V. SMP CONNECTORS, ADAPTERS, ASSEMBLIES.............................. 202–205 Main changes in 1/11 edition (from 2/10) are on the last page of the catalogue

∗ CONTENT ∗ page ABOUT THE ENTERPRISE…………………..…………………………………………… 2–3 ALPHABETICAL INDEX AND PATTERN OF CHOICE OF

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

  •  

    ∗ CONTENT ∗    page 

    ABOUT  THE  ENTERPRISE…………………..……………………………………………  2–3 ALPHABETICAL INDEX AND PATTERN OF CHOICE OF OUR CABLES….  4–5 TECHNICAL INFO………………………………………………........................................  6–8 PART I. CABLES………………………………………………………………………………...  9–180 SYMMETRICAL…………………………………………………………………………………………  10–129 For alarm and control systems (including for nuclear power plants (NPP))………….  11–28 For security and fire protection systems «FIRE RESISTANT»……...............................................  29–42 For security and automation systems « FIRE RESISTANT » (including for NPP)...................  43–58 For industrial interface RS485 (including for NPP and Ministry of Defense (MD))…….  59–78 For industrial network ProfiBusDP (including for NPP)…………………………………………….  79–84 

    For industrial networks ProfiBusPA and Foundation Fieldbus (including for NPP)……..  85–96 For connecting PLC within DCS (including for NPP)………………………...........................................  97–112 For LonWorks technology………………………………………………..........................................................  113–118 For local area networks (including for the Ministry of Defense of the Russian Federation)………………………………  119–128 For digital automatic  telephone exchange and telephony.................................................................................................................  129–133 COAXIAL…………………………………………………………………………………………………..  134–169 For broadcasting systems, systems of satellite and radio communication ………..  134–150 For cable/satellite television systems and video surveollance……………………………………... 

    151–166 

    For alarm systems …………………………………………………  167–169 

    HYBRID……………………………………………………………………………………………………  170–184 For industrial systems of control of mobile objects technological processes (including for NPP)….......  171–178 For video surveillance systems…………………………………………………………………………………….  179–182 For special application according to customer’s technical requirements……………………  183–184 PART II. COAXIAL CONNECTORS……………………………..................................  187–192 PART III. COAXIAL ADAPTERS………………………………………………………….  193–196 PART IV. CABLE ASSEMBLIES…………...............................................................  197–201 PART V. SMP CONNECTORS, ADAPTERS, ASSEMBLIES..............................  202–205 

    ∗ Main changes in №1/11 edition (from №2/10) are on the last page of the catalogue ∗

  • CONTACTS Address: ZIP 107497, Moscow, Birusinka str., 6, bld.1-5, Research-and-development company «Spetskabel» Tel.: (495) 921-4099 (multichannel), 603-0920, 603-0781 or

    (499) 268-3406, 268-0855/ Fax: (495) 730-57-19 E-mail: [email protected] Internet web-site: www.spcable.ru и www.spcable.com

    ABOUT THE ENTERPRISE DESINGING–PRODUCTION–REALIZATION

    Research-and-development enterprise «Spetskabel» has a specialized cable production, up-to-date technology and

    test base. Our company has rights nearly for all series-produced products most of which are certified in «GOST

    R» and «Fire Safety» systems. Also there are the type approval certificates from the Russian marine registry of

    shipping , the licenses of the Federal service for ecological, technological and nuclear monitoring for designing and

    producing the equipment for nuclear power plants.

    The range of the designed and series-produced production includes:

    - cables for security and fire protection systems (addressable FAS, WEC);

    - cables for industrial automation (RS-485, Profibus ); - fire resistant cables for alarm systems; - cables for local area networks (non-typical installation conditions); - cables for digital telephony (stream Е1); - radio-frequency cables (cable TV systems, radio- and cellular communication); - tribo-electrical cables (for vibration alarm systems); - hybrid cables (including for video surveiilance).

    Our enterprise produces radio-

    frequency cable assemblies (parts of cable assembled with connectors) for radio-electronic equipment and antenna-and-feeder transmission lines in which the transmission parameters in the frequency range up to 20 GHz are set.

    Accredited test laboratory and

    quality control system guarantee a high level of our prodction.

    «Spetskabel» has developed,

    documented, introduced a quality management system satisfying the requirements of GOST R ISO 9001, GOST RV 15.002, RD V 319.015, NP-011. That is confirmed by the annual inspection audits held by the quality management system certification authorities.

    «Spetskabel» is a permanent

    participant of the International specialized exhibitions such as «Svyaz-Expocom», «Navy Fair», «PTA», «Oil and Gas», «Expoelectronika», «ASU-EXPO», «Safety and security technologies».

    Among the consumers of our products there are such companies as Gasprom, Transneft, Lukoil,

    Kaliningradskaya, Rostovskaya, Smolenskaya, Balakovskaya nuclear power plants, Norilskiy Nikel, Siberia chemical plant, MTS, «Tactical military rocketry» corporation, Traffic Ministry, RZD, NIIDAR, TSNIIRTI, NII TP, «Krosna», NII IT and many others.

    The cables produced by our enterprise can be delivered practically to all Russian cities and all the countries

    abroad. The products of our enterprise are realized by the trading house «Spetskabel». «Spetskabel» is open to cooperation, takes any orders for producing special cables according to technical

    requirements of the customers, advises on the issues concerning the application of our products.

    2

  • ABOUT  THE   INTERPR ISE  

    TEST BASE

    One of the most  important departments of the “Spetskabel”  is a test  laboratory which provides main kinds of testing of cable products. 

    The test laboratory is arranged in the specially equipped promises meeting the testing requirements.  

    It is provided with certified testing equipment and proven instruments for measurement which are necessary for testing the cable products in accordance with the test procedure requirements currently in force.  

    As for conducting of electric testing, the following kinds of works can be done: 

    • Measuring of main transmission parameters of radio frequency cables, cables assemblies and connectors, high-frequency communication cables over the frequency range up to 20 GHz with the help of the vector analyzer of circuits of the type ZVB 20 of the company Rohde & Schwarz;

    • Measuring of a full set of parameters stated in the IEC standards 61156 for symmetrical cables of pair twisting of 7 category or a lower category and testing of structured cable systems of class E or a lower class over the frequency range up to 350 MHz by using a cable analyzer of the type DSP-4000 of the company Fluke Corporation and a cable tester of the type PentaScanner+ of the compony Microtest and over the frequency range up to 600 MHz by using the analyzer of circuits of the compony Agilent Technologies E 5062A and impedance buffer (baluns)of the company Nort Hills;

    • Measuring of DC current-carrying conductors resistance from 10-6 to 103 Ohm; • Measuring of DC insulation resistance from 106 to 1015 Ohm; • DC (up to 10 kV) and AC (up to 50 kV) voltage test. The test laboratory area of environmental tests provides cable product tests of exposure factors over the range of

    temperatures -80 to +200°С and humidity up to 98 %. Cable product tests of mechanical exposure are held in the test laboratory area of construction tests and mechanical tests.  

    The  test  laboratory  has  all  the  necessary  organizational  and  methodical  and  normative  documents  containing  the requirements  for  tested  products  and  methods  of  product  testing  (domestic  and  international  requirements,  technical specifications for particular kinds of cable products).  

    The test laboratory possesses all the necessary IEC standards for radiofrequency cables (coaxial communication cables), for nearly all existing kinds of radiofrequency cable connectors, coaxial cable assemblies, cables of pair twisting and others.

    The test laboratory uses the German standards (DIN, VDE), the American ones (ASTM, TIA/EIA, Mil), the British ones (BS EN) contained in the laboratory normative document fund.

    With the view to holding certificate tests of cable products the test laboratory has been accredited by the certification system GOST R and has an accreditation certificate № ROSS RU. 0001. 22KB17.

    The test laboratory is accredited to hold the certification tests of the following cable products: • Radio frequency cables, communication cables, input and jumper cables, ant vibration and triboelectric cables;  • Symmetrical  cables of pair  twisting  for  the digital  communication  systems of 3‐6  category,  the networks of  industrial 

    automation and  fire alarm systems and office cables for installation inside a rack and between racks.  • Power cables and wires;  • Ship cables;  • Optical, control cables, cables for blocking and signaling for electrical units;  • Flexible aerial cables, for electrosubmersible pump;  • General wiring cables, for rolling stock;  • Wires  for  industrial blasting,  провода для промышленных взрывных работ, motor and  tractor equipment,  contact, 

    thermocouple wires and wires for household use;  • Cable radio frequency, hybrid assemblies and assemblies for special purpose ;  • Coaxial radiofrequency connectors. The test laboratory is accredited by the EMERCOM of Russia to hold conformation tests of cable products compliance with 

    the  fire  safety  requirements  established by  the  Federal  law «Technical  regulations on  fire  safety»  (flame  retardance  at  single installation of a cable, wire, cord). 

    Holding  certification  tests  of  cable  products  the  test  laboratory  cooperates with  the  certification  authorities  such  as “Srrtinform VNIINMASh”, “Technoneftegas”, Rostest‐Russia, OOO NTSC “Batty”.  

    In the laboratory there is an area for measuring screening characteristics of cable products (coaxial and symmetrical cables, coaxial connectors and adapters, cable assemblies) over the range of frequencies 300 kHz up to 3000 MHz by using a measuring system  “CoMeT” produced  jointly by  such  companies as Bedea and Rosenberger  (Germany). This  system makes  it possible  to estimate transfer impedance of the magnitude from several µOhm/m and screening attenuation of the magnitude above 125 dB (at the moment it is possible to estimate transfer impedance of the magnitude from several mOhm/m and screening attenuation up to 120 dB). The circuit analyzer of the company Agilent Technologies E5062A is used as a measuring device.  

    The  “Spetskabel”  offers  holding  screening  efficiency  estimation  of  the  cable  products mentioned  above with  a  screen diameter from 2,3 up to 14,8 mm in accordance with the IEC standards of the series 62153‐4. 

    3

  • GENERAL APPROACH TO CHOOSING OF A CABLE

    4

    Cable designation – electrical characteristics – foreign analogues

    Halogen – free cables – such cables which do not contain any materials with chlorine or fluorine additives which can generate corrosion active gaseous products when a cable burns or smoulders.

    Installation conditions

    outdoors and indoors

    provided that there is a

    protection from direct solar

    radiation and atmospheric precipitation.

    outdoors direct solar

    radiation direct solar radiation

    and atmospheric precipitatio

    Cables with any sheath except a PE

    one

    Cables with a PE or

    halogen-free composition

    sheath of black color

    Cables with a PVC sheath of

    high cold-resistance of black color; with braid

    armour made of round steel zinc-

    coated wires

    Pulling through complex

    highways with high mechanical

    stress

    armoured cables

    in partly flooded

    premises

    Cables with a PE,

    polyurethane or halogen

    free polymer composition

    sheath

    installation in the ground

    Armoured cables with

    a jacket

    armoured cables

    Cables with a polyurethane

    sheath

    Cables with a PVC sheath of high oil and petrol

    resistance or a halogen free polymer composition

    sheath

    Exposure to oil and petrol

    and other mediums

    Exposure to oil and

    gas

    Rodent -proofness

    In the chemically

    active mediums

    to -40 to -50 to -60 (-10 ÷ +50) (-20 ÷ +50) (-30 ÷ +50)

    Cables with any sheath Cables with a halogen-

    free polymer composition or PE or polyurethane sheath

    or a PVC of high cold-resistance and low fire

    risk sheath

    Cables witha halogen-

    free polymercomposition

    or PE or polyurethane

    sheath

    Cables with a PE orpolyurethane or PVC of

    high heat-resistance sheath

    Cables with a polyurethane orPVC of high heat-resistance

    sheath

    Cables with any sheath

    with a polyurethane or PE sheath

    Cables with a PE orpolyurethane or PVC of

    high cold-resistance sheath

    Minimum radius of cables for single bending at operation = N х maximum outer size (diameter) of a cable

    Minimum radius of cables for multiplebending at installation = N х maximum

    outer size (diameter) of a cable

    Cables without armour Cables with braid armour made of round steel zinc-coated wiresCables with steel

    corrugated tape armor

    Operating temperatures range oCoperation instalation

    N=7 N=10 N=15 N=10 N=15 N=20

    to 80-85

    to 70 to 90-105 operation

    Flame retardance at single installation Fire safety requirements

    halogen free Flame retardance at singleinstallation halogen free

    fire-resistance

    halogen free

    Cables installed in bunches with

    low gas and fume emission

    of the types ng-HF

    Cables installed in bunches with

    low gas and fume emission of the

    types ng-LS, ng-HF

    Cables of single

    installation with any

    sheath except a PE one

    Cables of single

    installation with a

    polyurethane sheath

    Fire-resistant cables installed in bunches

    with low gas and fume emission of the

    types ng-FRLS, ng-FRHF

    Fire-resistant cables installed in bunches

    with low gas and fume emission of the

    types ng-FRHF

    no yes

    yes

    nono

    yes

  •  

    ALPHABETIC INDEX OF CABLE PRODUCT TYPES  

    KАEfP 115 KIPEVKG 62 KPSESng(A)-FRLS 37, 39 KVPEf‐5е  121, 181KAEfPng(A)-LS 117 KIPEVKGm 62 KPSng(A)-FRHF 32, 34 KVPEfM  125KAEfU 115 KIPEVKGng(A)-LS 70 KPSng(A)-FRLS 32, 34 KVPEfMKG  125KAEfV 115 KIPEVKGt 62 KPSSng(A)-FRHF 36, 38 KVPEfMU  124KAEfVng(A)-LS 117 KIPEVKng(A)-BG 72 KPSSng(A)-FRLS 36, 38 KVPEfng(A)‐HF‐5е 127KAP 114 KIPEVKng(A)-HF 72 KPSVEPs 13 KVPEfng(A)‐LS‐5е 127KAPng(A)-HF 116 KIPEVKV 64 KPSVEPsBPs 19 KVPEfP‐5е  121KASGEfEfKGng(A)-HF 110 KIPEVKVm 64 KPSVEPsKG 15 KVPEfU‐5е  121KASGEfEfKng(A)-HF 111 KIPEVKVng(A)-LS 72 KPSVEPsKPs 17 KVPEfVP‐5е  123KASGEfEfng(A)-HF 108 KIPEVKVt 64 KPSVEV 13 KVPng(A)‐HF‐5е 126KASGEfEfV 101 KIPEVm 60 KPSVEVBVm 19 KVPng(A)‐LS‐5е 126KASGEfEfVKG 103 KIPEVng(A)-LS 68 KPSVEVBVng(A)-LS 27 KVPP‐5е  120KASGEfEfVKGng(A)-LS 110 KIPEVt 60 KPSVEVKGm 15 KVPU‐5е  120KASGEfEfVKV 104 KIPvEBng(A)-BG 75 KPSVEVKGng(A)-LS 23 KVPVP‐5е  122KASGEfEfVKVng(A)-LS 111 KIPvEBng(A)-HF 75 KPSVEVKVm 17 RK 50‐3‐14  136KASGEfEfVng(A)-LS 108 KIPvEKGng(A)-BG 71 KPSVEVKVng(A)-LS 25 RK 50‐3‐14л  136KAU 114 KIPvEKGng(A)-HF 71 KPSVEVm 13 RK 50‐3‐15  137KAV 114 KIPvEKng(A)-BG 73 KPSVEVng(A)-LS 21 RK 50‐3‐16  137KAVng(A)-LS 116 KIPvEKng(A)-HF 73 KPSVEVt 13 RK 50‐3‐210  150KGPEfng(A)-HF 91, 93  KIPvEng(A)-BG 69 KPSVPs 12 RK 50‐3‐211  150KGPEfP 86, 88  KIPvEng(A)-HF 69 KPSVPSBPs 18 RK 50‐3‐34  138KGPEfU 86,88 KIPvEP 61 KPSVPsKG 14 RK 50‐3‐35  138KGPEfV 86, 88  KIPvEPBP 67 KPSVPsKPs 16 RK 50‐3‐38  139KGPEfVm 86, 88  KIPvEPKG 63 KPSVV 12 RK 50‐3‐39  139KGPEfVng(A)-LS 91, 93?  KIPvEPKP 65 KPSVVBVm 18 RK 50‐4,8‐31  140KGPEfVt 86, 88  KIPvEV 61 KPSVVBVng(A)-LS 26 RK 50‐4,8‐32  140KGPEng(A)-HF 105, 106 KIPvEVBV 67 KPSVVKGm 14 RK 50‐4,8‐33ng(C)‐HF 145KGPEP 98, 99  KIPvEVBVm 67 KPSVVKGng(A)-LS 22 RK 50‐4,8‐34  141KGPEU 98, 99  KIPvEVBVng(A)-LS 75 KPSVVKVm 16 RK 50‐4,8‐35  141KGPEV 98, 99  KIPvEVBVt 67 KPSVVKVng(A)-LS 24 RK 50‐4,8‐36ng(C)‐HF 146KGPEVm 98, 99  KIPvEVKG 63 KPSVVm 12 RK 50‐7‐311  143KGPEVng(A)-LS 105, 106 KIPvEVKGm 63 KPSVVng(A)-LS 20 RK 50‐7‐312  143KGPEVt 98, 99  KIPvEVKGng(A)-

    LS71 KPSVVt 12 RK 50‐7‐313ng(C)‐HF 148

    KGPpEfng(A)-HF 94, 95  KIPvEVKGt 63 KSBGKng(A)-FRHF 49 RK 50‐7‐314  144KGPpEfP 89, 90  KIPvEVKV 65 KSBGKng(A)-FRLS 49 RK 50‐7‐315  144KGPpEfU 89, 90  KIPvEVKVm 65 KSBGng(A)-FRHF 45 RK 50‐7‐316ng(C)‐HF 149KGPpEfV 89, 90  KIPvEVKVng(A)-

    LS73 KSBGng(A)-FRLS 45 RK 50‐7‐35  142

    KGPpEfVm 89, 90  KIPvEVKVt 65 KSBGSKng(A)-FRHF 51 RK 50‐7‐36  142KGPpEfVng(A)-LS 94, 95  KIPvEVm 61 KSBGSKng(A)-FRLS 51 RK 50‐7‐37ng(C)‐HF 147KGPpEfVt 89, 90  KIPvEVng(A)-LS 69 KSBGSng(A)-FRHF 47 RK 75‐3,7‐311f 154KGPpEng(A)-HF 83, 107  KIPvEVt 61 KSBGSng(A)-FRLS 47 RK 75‐3,7‐330fng(C)‐HF 159KGPpEP 81, 100  KMS-2U 130 KSBKng(A)-FRHF 48 RK 75‐3,7‐331fng(C)‐HF 160KGPpEU 81, 100  KMS-2V 132, 133 KSBKng(A)-FRLS 48 RK 75‐3,7‐332f 154KGPpEV 81, 100  KPAPEfV 106 KSBng(A)-FRHF 44 RK 75‐3,7‐333fng(C)‐HF 161KGPpEVm 81, 100  KPAPEfVng-LS 109 KSBng(A)-FRLS 44 RK 75‐3,7‐33f 152KGPpEVng(A)-LS 83, 107  KPpEfng(A)-HF 92 KSBSKng(A)-FRHF 50 RK 75‐3,7‐34f 152KGPpEVt 81, 100  KPpEfP 87 KSBSKng(A)-FRLS 50 RK 75‐3,7‐35f 153, 182KIPEBng(A)-BG 74 KPpEfU 87 KSBSng(A)-FRHF 46 RK 75‐3,7‐36f 153, 182KIPEBng(A)-HF 74 KPpEfV 87 KSBSng(A)-FRLS 46 RK 75‐3‐17   166KIPEKGng(A)-BG 70 KPpEfVm 87 KShSEng(A)-FRHF 31 RK 75‐4,8‐31f 155KIPEKGng(A)-HF 70 KPpEfVng(A)-LS 92 KShSEng(A)-FRLS 31 RK 75‐4,8‐32f 155KIPEng(A)-BG 68 KPpEfVt 87 KShSGEng(A)-FRHF 30 RK 75‐4,8‐330fng(C)‐HF 162KIPEng(A)-HF 68 KPpEng(A)-HF 82 KShSGEng(A)-FRLS 31 RK 75‐4,8‐331fng(C)‐HF 163KIPEP 60 KPpEP 80 KShSGng(A)-FRHF 30 RK 75‐4,8‐33f 156KIPEPBP 66 KPpEU 80 KShSGng(A)-FRLS 30 RK 75‐4,8‐34f 156KIPEPKG 62 KPpEV 80 KShSng(A)-FRHF 31 RK 75‐7‐316f‐S 157KIPEPKP 64 KPpEVm 80 KShSng(A)-FRLS 30 RK 75‐7‐317f‐S 158KIPEV 60 KPpEVng(A)-LS 82 KSPvEP 131 RK 75‐7‐319f‐S 157KIPEVBV 66 KPpEVt 80 KSPvEV 131 RK 75‐7‐320f‐Sng(C)‐HF 164KIPEVBVm 66 KPSEng(A)-FRHF 33, 35 KTDZ 169  RK 75‐7‐321f‐S 158KIPEVBVng(A)-LS 74 KPSEng(A)-FRLS 33, 35 KTM 168  RK 75‐7‐323f‐Sng(C)‐HF 165KIPEVBVt 66 KPSESng(A)-FRHF 37, 39 KVP‐5е 120, 180  

       

                                                                                                                                                                                                               5

  •  TECHNICAL INFORMATION

    Electrical and thermal properties of insulation materials at normal conditions

    Electrical properties of conductor materials at normal conditions

    Material Resistivity, mOhm·m Electric resistance temperature

    coefficient, 1/K Relative

    magnetic permeability Soft copper 0,0173 0,0042 1 Hard copper 0,0180 0,0042 1 Soft silver 0,0160 0,0038 1 Hard silver 0,0165 0,0038 1 Soft aluminum 0,0275 0,0041 1 Hard aluminum 0,0283 0,0041 1 Tin 0,1140 0,0044 1 Bronze 0,0200 0,0035 1 Steel 0,1000 0,0046 200 Corrosion resistant steel 0,0750 0,0045 50 Nickel 0,0684 0,0067 70 Nichrome 1,04-1,15 0,0001 1 Lead 0,210 0,0039 1 Niobium 0,155 0,0036 1

    American and British measurement system

    Units of length Units of and volume Units of mass Units of area Units of electricity Units of

    temperature

    1mil=0,0254mm 1 inch=25,4mm 1foot=0,305m 1yard=0,914m 1chain= 20,1m 1English mile=1,523km 1 nautical mile =1,853km 1 land mile=1760yards

    1cubic inch=16,39cm3 1cubic foot=0,0283 m3 1cubic yard=0,765 mm3 1US gallon (жидк.)=3,79l 1pint=0,473l 1quart=0,946l 1gallon (Br.)=4,53l 1barrel=119,2l

    1grain=64,80mg 1drachma=1,770g 1ounce=28,35g 1pound=453,59g 1stone=6,35kg 1 Am.ton (short)=0,907t 1English ton (long)=1,016t

    1square inch=645,16mm2 1sq.foot=0,0929m2 1sq.yard=0,836m2 1acre=0,00405km2 1sq.mile=2,59km2 1sq.metre=10,764foot2

    1mcF by 1 mile=0,62mcF/km 1MOhm by 1 mile =1,61MOm/km 1MОhm by 1000foot=3,28Оhm/km 1Ohm на 1000yard=1,0936Ohm/km

    1ºF=1,8 x ºC+32 1ºC=(ºF – 32)/1,8

    6

    Material Relative dielectric constant Tangent of angle of

    dielectric loss Electric strength,

    kV/mm Thermal resistance

    HDPE (High-density polyethylene) 2,28 (3,5-5)х10

    -4 30-60 3-4

    LDPE (Low-density polyethylene) 2,33 3х10-4 30-60 3-4 Chemically foamed PE 1,65 (3-8,5)х10-4 15-20 9 Physically foamed PE 1,35-1,46 (0,9-1,18)х10-4 15-20 9-9,5 UV-resistant PE 2,40 5х10-4 15 3-3,5 PVC 3,40 6х10-2 18-40 5-7 Fluoroplastic (4) 2,02 2х10-4 20-100 5-8 Fluoroplastic (4D) 2,05 3х10-4 20-40 4-5 Fluoroplastic (4MB) 2,10 (6-8)х10-4 20-50 4 Solar cosmic rays tapes 1,75 1х10-4 20-30 6-8 Foamed PTFE 1,2 -1,4 (1-2)х10-4 10-25 10-12 Fluoroplastic (4 Osh) 2,60 1х10-2 20 4,3-4,5 Fluoroplastic (2M) 3,0 (7-12)х10-2 10 4,5-8,5 Polyamide-fluoroplast tape 2,8-3,0 4х10-3 100-150 4-5 Silicone rubber 3,0-3,5 (1-3)х10-2 15-40 5-7 Polyamide (caprone) 3,1 2х10-2 20-50 3-4 Air 1,00055 0 4-5 34-28

  • TECHNICAL INFORMATION

    Conductive round copper cable conductor make-up in accordance with GOST 22483 nom. cross-section of

    conductors, S,

    mm2

    Class 1 Class 2 Class 3 Wire

    diameter d, mm

    Number of wires in a conductor,

    n

    Estimated conductor diametr D,

    mm

    Wire diameter

    d, mm

    Number of wires in a conductor,

    n

    Estimated conductor diametr D,

    mm

    Wire diamete

    r d, mm

    Number of wires in a conductor,

    n

    Estimated conductor diametr D,

    mm 0,03 0,20 1 0,20 ⎯ ⎯ ⎯ — — — 0,05 0,26 1 0,26 — — — — — — 0,08 0,32 1 0,32 — — — — — — 0,12 0,42 1 0,42 — — — — — — 0,20 0,52 1 0,52 — — — — — — 0,35 0,68 1 0,68 — — — — ⎯ — 0,50 0,80 1 0,80 0,30 7 0,90 0,33 7 0,98 0,75 0,97 1 0,97 0,37 7 1,11 0,38 7 1,15 1,0 1,13 1 1,13 0,40 7 1,20 0,43 7 1,30 1,2 1,20 1 1,20 0,45 7 1,36 0,45 7 1,36 1,5 1,38 1 1,38 0,50 7 1,50 0,53 7 1,60 2,0 1,60 1 1,60 0,60 7 1,80 0,61 7 1,83 2,5 1,78 1 1,78 0,67 7 2,01 0,69 7 2,08

    nom. cross-section of

    conductors, S,

    mm2

    Class 4 Class 5 Class 6Wire

    diameter d, mm

    Number of wires in a conductor,

    n

    Estimated conductor diametr D,

    mm

    Wire diameter

    d, mm

    Number of wires in a conductor,

    n

    Estimated conductor diametr D,

    mm

    Wire diameter

    d, mm

    Number of wires in a conductor,

    n

    Estimated conductor diametr D,

    mm0,03 — — — 0,08 7 0,24 0,05 16 0,240,05 0,10 7 0,30 0,08 10 0,32 0,05 27 0,31

    0,08 0,12 — 7

    —0,36 0,10

    0,08 0,10

    16 10

    0,38 0,40

    0,05 —

    40 —

    0,37 —

    0,12 0,15 7 0,45 0,10 15 0,47 0,08 24 0,48

    0,20 0,20 — 7

    —0,60 —

    0,12 —

    19 —

    0,60 —

    0,10 0,08

    26 37

    0,62 0,56

    0,35 0,26 — 7

    —0,78 —

    0,12 0,15

    30 19

    0,77 0,75

    0,10 —

    45 —

    0,82 —

    0,50 0,30 7 0,90 0,20 16 0,94 0,15 28 0,96

    0,75 0,30 0,23 11 19

    1,25 1,15

    0,20 —

    24 —

    1,20 —

    0,15 —

    42 —

    1,20 —

    1,0 0,30 0,26 14 19

    1,32 1,30

    0,20 —

    32 —

    1,34 —

    0,15 —

    56 —

    1,31 —

    1,2 0,41 — — 0,26 — — 0,16 — —

    1,5 0,40 0,32 12 19

    1,66 1,60

    0,26 —

    28 —

    1,88 —

    0,15 —

    85 —

    2,03 —

    2,0 0,43 — — 0,26 0,16

    2,5 0,40 0,42 20 19

    2,12 2,10

    0,25 0,26

    50 49

    2,10 2,34

    0,15 —

    140 —

    2,39 ––

    DC resistance of 1 km of a round copper conductors at 20 °С S, mm2

    Class 1 Class 2 Class 3Non-tinned tinned Non-tinned tinned Non-tinned tinned

    0,03 588,0 617,3 — — — —0,05 347,9 365,3 — — — —0,08 225,3 238,8 — — — —0,12 130,8 138,6 — — — —0,20 88,8 90,4 — — — —0,35 50,4 51,8 — — — —0,50 36,0 36,7 36,0 36,7 39,6 40,70,75 24,5 24,8 24,5 24,8 25,5 26,01,0 18,1 18,2 18,1 18,2 21,8 22,31,2 14,8 14,9 16,8 17,1 17,3 17,61,5 12,1 12,2 12,1 12,2 14,0 14,32,0 9,01 9,10 9,43 9,61 9,71 9,902,5 7,41 7,56 7,41 7,56 7,49 7,63

    7

  •  

    TECHNICAL INFORMATION

    The length of the cables winded up on the drum depending on an outer diameter (D) of a cable

    Wooden drum sizes

    Round copper wire standards according to the American wire gauge (AWG)

    8

    D, mm A number of a drum

    5 6 8 8a 8b 10 12 12а 14 14а 14б5 860 1320 3550 3600 3610 — — — — — —7 440 690 1800 1840 1850 — — — — — —

    10 215 340 890 900 960 2200 3100 3120 — — —12 160 240 605 625 650 1520 2150 2170 — — —15 95 150 390 400 415 970 1380 1400 2750 1550 155017 — 120 300 310 335 760 1070 1090 2140 1250 125020 — 90 215 225 240 550 775 800 1650 875 87522 — — 175 185 200 450 640 660 1280 725 72525 — — 135 145 160 350 495 510 990 560 56027 — — 10 120 130 300 425 440 815 480 48030 — — 90 100 110 240 345 360 690 390 40032 — — — –– — 210 310 320 605 340 35035 — — –– — — 180 250 270 505 285 29037 — — — — — 150 225 240 450 255 26040 — — — –– — 135 205 220 385 220 230

    A number oa drum

    Drum flange

    diameter, mm

    Outer diameter of

    a barrel, mm

    Barrel length,

    mm

    Drum flangethickness,

    mm

    Barrel circle thickness,

    not less than, mm

    Barrel thickness,

    mm

    Drum lagging thickness,

    not less than, mm

    Axial bore

    diameter, mm

    Estimated mass of a drum with

    a lagging, kg

    5 500 200 230 38 25 16 16 35 186 600 200 250 38 25 19 16 35 258 800 450 230 38 25 19 16 50 43

    8а 800 450 400 38 25 19 16 50 5186 800 450 500 38 25 19 16 50 5310 1000 545 500 50 25 22 19 50 5612 1220 650 500 50 25 22 19 70 13212а 1220 650 710 50 25 22 19 70 15114 1400 750 710 58 25 28 19 70 21714а 1400 900 500 58 25 22 19 70 200146 1400 1000 600 58 25 28 19 70 234

  •  

    Section I. CABLES 

  •  

    Symmetrical  cables 

     

     

  • SYMMETRICAL CABLES FOR ALARM AND CONTROL SYSTEMS

    For single installation Technical specification Page

    КPSVV (KPSVVm, KPSVVt) Nх2хS and TU 16.К99-002-2003 KPSVVs TU 16.К99-030-2005 12 KPSVEV (KPSVEVm, KPSVEVt) Nх2хS and TU 16.К99-002-2003 KPSVEVs TU 16.К99-030-2005 13 For single installation, armoured

    KPSVVKGm Nх2хS and KPSVPsKG Nх2хS TU 16.К99-030-2005 14 KPSVEVKGm Nх2хS and KPSVEPsKG Nх2хS TU 16.К99-030-2005 15 KPSVVKVm Nх2Хs KPSVPsKPs Nх2хS TU 16.К99-030-2005 16 KPSVEVKVm Nх2хS и KPSVEPsKPs Nх2хS TU 16.К99-030-2005 17 KPSVVBVm Nх2хS и KPSVPsBPs Nх2хS TU 16.К99-030-2005 18 KPSVEVBVm Nх2хS и KPSVEPsBPS Nх2хS TU 16.К99-030-2005 19 For installation in bunches, with low gas and fume emission

    KPSVVng(A)-LS Nх2хS TU 16.К99-002-2003 20 KPSVEVng(A)-LS Nх2хS TU 16.К99-002-2003 21 For installation in bunches, with low gas and fume emission, armoured

    KPSVVKGng(A)-LS Nх2хS TU 16.К99-030-2005 22 KPSVEVKGng(A)-LS Nх2хS TU 16.К99-030-2005 23 KPSVVKVng(A)-LS Nх2хS TU 16.К99-030-2005 24 KPSVEVKVng(A)-LS Nх2хS TU 16.К99-030-2005 25 KPSVVBVng(A)-LS Nх2хS TU 16.К99-030-2005 26 KPSVEVBVng(A)-LS Nх2хS TU 16.К99-030-2005 27 DATA SHEET 28

  • Symmetrical cables for alarm and control systems for single installation KPSVV (KPSVVt, KPSVVm) Nx2xS (Russian: КПСВВ, КПСВВт, КПСВВм Nx2xS) Technical specification TU 16.К99-002-2003 and KPSVVs Nx2xS(Russian: КПСВВ Nx2xS ) Technical specification TU 16.К99-030-2005

    Field of application Construction Symmetrical cables of pair twisting are designed for stationary single installation in the up-to-date alarm systems, access control systems and in other control and communication systems in accordance with the current legislation. The cables of the type KPSVV (KPSVVt, KPSVVm) can be used indoors and outdoors provided that there is a direct solar radiation and atmospheric precipitation protection. They also can be used in explosion hazard zones of any class. The cables of the type KPSVPs are designed to be used outdoors.

    Pairs with single-wire copper conductors with cross-section from 0,5 to 2,5 mm², PVC insulated. The sheath is PVC of normal (KPSVV) or high heat and oil-and-petrol resistance (KPSVVt) of red color or of PVC of high cold-resistance (KPSVVm) or of self-extinguishing PE (KPSVPs) of black color. The cables (one-paired and double-paired) are series-produced. At the special request the cables can be produced with a number of pairs up to 40, depending on a cross-section of conductors.

    Fire risk class of the cables in accordance with GOST R 53315–2009 – О1.8.2.3.4 (KPSVV, KPSVVt, KPSVVm) and О2.8.2.3.4 (KPSVVs)

    The cables of the type KPSVV (KPSVVt, KPSVVm) meet the requirements of the normative documents «Technical regulations on fire safety», including those stated in GOST R 53315-2009 (clause 5.2, PRGP 1) about flame retardance at single installation and have the corresponding fire safety certificate. The cables are certified in the GOST R system.

    Electrical characteristics Nominal cross-section of conductors, S,

    mm2 0,5 0,75 1,0 1,5 2,5

    DC loop resistance (two conductors of a pair) at 20 °C, equal or less than, Оhm / km 74,8 51,0 37,6 25,2 16,0

    DC insulation resistance at 20 °C, not less than, МОhm × km 100 100 100 100 100

    Mutual capacitance of a pair, equal or less than, nF/km 75 80 85 87 105

    Attenuation constant at frequency 1 kHz at 20 °С, equal or less than, dB/km 1,32 0,98 0,88 0,66 0,57

    Operating voltage, equal or less than, V 300 300 300 300 300

    Weight, size and operation parameters Number of

    pairs in cables,

    N

    Cross-section of conducto

    rs, S,

    mm2

    Outer diameter (size) of a cable, DO,

    equal or less than,

    mm

    Min. bending radius of cables,

    mm

    Estimated weight of 1

    km of cables,

    kg

    Range of permissible ambient temperatures,

    °C

    Service time of cables,

    equal or more than,

    years

    KPS

    VV

    KPS

    VV

    t

    KPS

    VV

    m

    KPS

    VV

    s

    1 0,5

    5,2

    10 × Do during

    installation and

    7 × Do fixed

    26,4

    – 10

    ÷ 5

    0 du

    ring

    inst

    alla

    tion

    and

    40 ÷

    70

    durin

    g op

    erat

    ion

    – 10

    ÷ 5

    0 du

    ring

    inst

    alla

    tion

    and

    40 ÷

    105

    dur

    ing

    oper

    atio

    n

    – 1

    5 ÷

    50

    durin

    g in

    stal

    latio

    n an

    d

    – 60

    ÷ 7

    0 du

    ring

    oper

    atio

    n

    30

    2 6,2 x 8,8 51,2 1

    0,75 5,6 34,0

    2 6,7 х 9,5 66,2 1

    1,0 6,3 40,3

    2 7,6 х 10,3 78,9 1

    1,5 6,8 56,5

    2 8,2 х 12,2 113,1 1

    2,5 8,2 79,0

    2 9,8 х 15,0 156,3

    Example of cable reference designation when ordering it and in the documents of an item: «Cable KPSVV 2×2×0,5 TU 16.K99-002-2003»

    12

  • Symmetrical cables for alarm and control systems for single installation KPSVEV (KPSVEVt, KPSVEVm) Nx2xS (Russian: КПСВЭВ, КПСВЭВт, КПСВЭВм) Technical specification TU 16.К99-002-2003 and KPSVEVs Nx2xS (Russian: КПСВЭВс Nx2xS) Technical specification TU 16.К99-030-2005

    Field of application Construction Symmetrical cables of pair twisting are designed for stationary single installation in the up-to-date alarm systems, access control systemsand in other control and communication systems in accordance with the current legislation. The cables of the type KPSVEV Nx2x0,5 can be used instead of the cable J-Y(St)Y Nx2x0,8 Lg и JE-Y(St)YNx2x0,8 Bd. The cables KPSVEV (KPSVEVt, KPSVEVm) can be used indoors andoutdoors provided that there is a direct solar radiation and atmosphericprecipitation protection. They also can be used in explosion hazard zonesof any class. The cables KPSVEVs are designed to be used outdoors.

    Pairs with single-wire copper conductors with cross-section from 0,5 to 2,5 mm², PVC insulated, with an overall screen of analum–lavsan (Al/Pet) tape with a drain conductor made of a tinned copper wire. The sheath is PVC of normal (KPSVEV) or high heat and oil-and-petrol resistance (KPSVEVt) of red color or PVC plastic of high cold-resistance (KPSVEVm) or of self-extinguishing polyethylene (KPSVEPs) of black color. The cables (one-paired and double-paired) are series-produced. At the special request the cables can be produced with a number of pairs up to 40, depending on a cross-section of conductors.

    Fire risk class of the cables in accordance with GOST R 53315–2009 – О1.8.2.3.4 (KPSVEV, KPSVEVt, KPSVEVm) and О2.8.2.3.4 (KPSVEVs)

    The cables KPSVEV (KPSVEVt, KPSVEVm) meet the requirements of the normative documents «Technical regulations on fire safety», including those stated in GOST R 53315-2009 (clause 5.2, PRGP 1) about flame retardance at single installation and have the corresponding fire safety certificates. The cables are certified in the GOST R system.

    Electrical characteristics Nominal cross-section of conductors,

    S, mm2

    0,5 0,75 1,0 1,5 2,5

    DC loop resistance (two conductors of a pair) at 20 °C, equal or less than, Оhm / km 74,8 51,0 37,6 25,2 16,0

    DC insulation resistance at 20 °C, not less than, МОhm × km 100 100 100 100 100

    Mutual capacitance of a pair, equal or less than, nF/km 110 118 120 125 150 Attenuation constant at frequency 1 kHz at 20 °С, equal or less than, dB/km 1,35 1,12 0,95 0,80 0,65

    Operating voltage, equal or less than, V 300 300 300 300 300

    Weight, size and operation parametersNumber of

    pairs in cables,

    N

    Cross-section of

    conductors, S,

    mm2

    Outer diameter (size) of a cable,

    DO, equal or less

    than,

    mm

    Min. bending radius of cables,

    mm

    Estimated weight of 1

    km of cables,

    kg

    Range of permissible ambient temperatures,

    °C

    Service time of cables,

    equal or more than,

    years KPS

    VE

    V

    KPS

    VE

    Vt

    KPS

    VE

    Vm

    KPS

    VE

    Vs

    1

    0,5

    5,4

    10 × Do during installation

    and 7 × Do fixed

    27,9

    – 10

    ÷ 5

    0 du

    ring

    inst

    alla

    tion

    and

    – 40

    ÷ 7

    0 du

    ring

    oper

    atio

    n

    – 10

    ÷ 5

    0 du

    ring

    inst

    alla

    tion

    and

    – 4

    0 ÷

    105

    durin

    g op

    erat

    ion

    – 1

    5 ÷

    50

    durin

    g in

    stal

    latio

    n an

    d –

    60 ÷

    70

    durin

    g op

    erat

    ion

    30

    2 6,2×9,0 53,7 4 10,1 102,8 8 11,1х16,3 181,5 12 16,3 254,2 16 18,1 321,9 20 20,3 507,2 32 25,2 611,5 40 27,4 752,6 1

    0,75 5,9 35,5

    2 7,0 × 9,9 68,7 1

    1,0 6,4 41,8

    2 7,7 × 11,0 81,4 1

    1,5 7,2 58,0

    2 8,6 × 12,4 113,6 1

    2,5 8,4 80,5

    2 10,0 × 15,2 159,5

    Example of cable reference designation when ordering it and in the documents of an item:

    «Cable KPSVEV 2×2×2,5 TU16.K99-002-2003» 13

  • Symmetrical cables for alarm and control systems for single installation, armoured KPSVVKGm Nx2xS (Russian: КПСВВКГм) and KPSVPsKG Nx2xS (Russian: КПСВПсКГ) Technical specification TU 16.К99-030-2005

    Field of application Construction

    Symmetrical cables of pair twisting are designed for stationary single installation in the up-to-date fire and control systems, access control systems and in other control and communication systems in accordance with the current legislation. The cables of the type KPSVVKGm can be used indoors and outdoors provided that there is a direct solar radiation and atmospheric precipitation protection. They also can be used in explosion hazard zones of any class according to the Regulations on electrical installations. The cables of the type KPSVPsKG can be used outdoors. Rodent-proof.

    Pairs with single-wire copper conductors with cross-section from 0,5 to 2,5 mm² and PVC insulated. The sheath is cold-resistant PVC (KPSVVKGm) or self-extinguishing PE (KPSVPsKG) of black color, with braid armour made of round steel zinc-coated wires, without a jacket. The cables (one-paired and double-paired) are series-produced. At the special request the cables can be produced with a number of pairs up to 40, depending on a cross-section of conductors.

    Fire risk class of the cables in accordance with GOST R 53315–2009 – O1.8.2.3.4 (KPSVVKGm) and O2.8.2.3.4 (KPSVPsKG)

    The cables of the type KPSVVKGm meet the requirements of the normative documents «Technical regulations on fire safety», including those stated in GOST R 53315-2009 (clause 5.2, PRGP 1) about flame retardance at single installation and have the corresponding fire safety certificate. The cables are certified in the GOST R system..

    Electrical characteristics Nominal cross-section of conductors, S,

    mm2

    0,5 0,75 1,0 1,5 2,5

    DC loop resistance (two conductors of a pair) at 20 °C, equal or less than, Оhm / km 74,8 51,0 37,6 25,2 16,0

    DC insulation resistance at 20 °C, not less than, МОhm × km 100 100 100 100 100

    Mutual capacitance of a pair, equal or less than, nF/km 105 110 114 115 140

    Attenuation constant at frequency 1 kHz at 20 °С, equal or less than, dB/km 1,34 1,07 0,94 0,69 0,59

    Operating voltage, equal or less than, V 300 300 300 300 300

    Weight, size and operation parameters Number of

    pairs in cables,

    N

    Cross-section of

    conductors, S,

    mm2

    Outer diameter (size) of a cable, DO,

    equal or less than,

    mm

    Min. bending radius of cables,

    mm

    Estimated weight of 1 km

    of cables,

    kg

    Range of permissible ambient temperatures,

    °C

    Service time of cables,

    equal or more than,

    years 1

    0,5 7,4

    15 × DН during installation

    and 10 × DН

    fixed

    74,0

    – 15 ÷ 50 during installation

    and – 60 ÷ 70

    during operation

    25

    2 8,2 х 11,0 125,9 1

    0,75 7,9 84,8

    2 9,0 х 11,9 145,6 1

    1,0 8,4 96,1

    2 9,2 х 13,0 162,6 1

    1,5 9,2 118,2

    2 10,6 х 14,4 212,6 1

    2,5 10,4 148,0

    2 12,0 х 17,2 264,2

    Example of cable reference designation when ordering it and in the documents of an item: 14 «Cable KPSVVKGm 2×2×0,5 TU16.К99-030-2005»

  • Symmetrical cables for alarm and control systems for single installation, armoured KPSVEVKGm Nx2xS (Russian: КПСВЭВКГм Nx2xS) and KPSVEPsKG Nx2xS (Russian:КПСВЭПсКГ Nx2xS) Technical specification TU 16.К99-030-2005

    Field of application Construction Symmetrical cables of pair twisting are designed for stationary single installation in the up-to-date alarm systems, access control systems and in other control and communication systems in accordance with the current legislation. The cables of the type KPSVEVKGm can be used indoors and outdoors provided that there is a direct solar radiation and atmospheric precipitation protection. They also can be used in explosion hazard zones of any class according to the Regulations on electrical installations. The cables of the type KPSVEPsKG can be used outdoors. Rodent-proof.

    Pairs with single-wire copper conductors with cross-section from 0,5 to 2,5 mm², PVC insulated, with an overall screen of an Al/Pet tape with a drain conductor made of a tinned copper wire. The sheath is cold-resistant PVC (KPSVEVKGm) or self-extinguishing polyethylene (KPSVEPsKG) of black color, with braid armour made of round steel zinc-coated wires, without a jacket. The cables (one-paired and double-paired) are series-produced. At the special request the cables can be produced with a number of pairs up to 40, depending on a cross-section of conductors.

    Fire risk class of the cables in accordance with GOST R 53315–2009 – O1.8.2.3.4 (KPSVEVKGm) and O2.8.2.3.4 (KPSVEPsKG)

    The cables of the type KPSVEVKGm meet the requirements of the normative documents «Technical regulations on fire safety», including those stated in GOST R 53315-2009 (clause 5.2, PRGP 1) about flame retardance at single installation and have the corresponding fire safety certificate. The cables are certified in the GOST R system.

    Electrical characteristics Nominal cross-section of conductors, S,

    mm2

    0,5 0,75 1,0 1,5 2,5

    DC loop resistance (two conductors of a pair) at 20 °C, equal or less than, Оhm / km 74,8 51,0 37,6 25,2 16,0

    DC insulation resistance at 20 °C, not less than, МОhm × km 100 100 100 100 100

    Mutual capacitance of a pair, equal or less than, nF/km 110 118 120 125 150

    Attenuation constant at frequency 1 kHz at 20 °С, equal or less than, dB/km 1,35 1,12 0,95 0,80 0,65

    Operating voltage, equal or less than, V 300 300 300 300 300

    Weight, size and operation parameters Number of

    pairs in cables,

    N

    Cross-section of

    conductors, S,

    mm2

    Outer diameter (size) of a cable,

    DO, equal or less

    than, mm

    Min. bending radius of cables,

    mm

    Estimated weight of 1 km of cables,

    kg

    Range of permissible ambient

    temperatures,

    °C

    Service time of cables,

    equal or more than,

    years

    1 0,5

    7,7

    15 × Do during installation

    and 10 × Do

    fixed

    75,5

    – 15 ÷ 50 during installation

    and – 60 ÷ 70

    during operation

    25

    2 8,5 х 11,3 127,4 1

    0,75 8,2 86,3

    2 9,3 х 12,2 147,1 1

    1,0 8,7 97,6

    2 9,5 х 13,3 164,1 1

    1,5 9,5 119,7

    2 10,9 х 14,7 214,1 1

    2,5 10,7 149,5

    2 12,3 х 17,5 265,7

    Example of cable reference designation when ordering it and in the documents of an item: «Cable KPSVEVKGm 2×2×0,5 TU16.К99-030-2005» 15

  • Symmetrical cables for alarm anв control systems for single installation, armoured KPSVVKVm Nx2xS (Russian: КПСВВКВм Nx2xS) and KPSVPsKPs Nx2xS (Russian: КПСВПсКПс Nx2xS)

    Technical specification TU 16.К99-030-2005

    Field of application Construction Symmetrical cables of pair twisting are designed for stationary single installation in the up-to-date alarm systems, access control systems and in other control and communication systems in accordance with the current legislation. The cables of the type KPSVVKVm can be used indoors and outdoors provided that there is a direct solar radiation and atmospheric precipitation protection. The cables of the type KPSVPsKPs are used outdoors. The cables can be used in explosion hazard zones of any class according to the Regulations on electrical installations. Installation in the ground of category I-III is allowed. Rodent-proof.

    Pairs with single-wire copper conductors with cross-section from 0,5 to 2,5 mm² and PVC insulated. The sheath is cold-resistant PVC (KPSVVKVm) or self-extinguishing PE (KPSVPsKPs) of black color, with braid armour made of round steel zinc-coated wires, with a jacket of cold-resistant PVC (KPSVVKVm) or self-extinguishing PE (KPSVPsKPs) of black color. The cables (one-paired and double-paired) are series-produced. At the special request the cables can be produced with a number of pairs up to 40, depending on a cross-section of conductors.

    Fire risk class of the cables in accordance with GOST R 53315–2009 – O1.8.2.3.4 The cables meet the requirements of the normative documents «Technical regulations on fire safety», including those stated in GOST R 53315-2009 (clause 5.2, PRGP 1) about flame retardance at single installation and have the corresponding fire safety certificate. The cables are certified in the GOST R system.

    Electrical characteristics Nominal cross-section of conductors, S,

    mm2 0,5 0,75 1,0 1,5 2,5

    DC loop resistance (two conductors of a pair) at 20 °C, equal or less than, Оhm / km 74,8 51,0 37,6 25,2 16,0

    DC insulation resistance at 20 °C, not less than, МОhm × km 100 100 100 100 100

    Mutual capacitance, of a pair, equal or less than, nF/km 105 110 114 115 140

    Attenuation constant at frequency 1 kHz at 20 °С, equal or less than, dB/km 1,34 1,07 0,94 0,69 0,59

    Operating voltage, equal or less than, V 300 300 300 300 300

    Weight, size and operation parameters Number of

    pairs in cables,

    N

    Cross-section of

    conductors, S,

    mm2

    Outer diameter (size) of a cable,

    DO, equal or less than,

    mm

    Min. bending radius of cables,

    mm

    Estimated weight of 1

    km of cables,

    kg

    Range of permissible ambient

    temperatures,

    °C

    Service time of cables,

    equal or more than, years

    1 0,5

    11,0

    15 × Do during installation

    and 10 × Do

    fixed

    134,7

    – 15 ÷ 50 during installation

    and – 60 ÷ 70

    during operation

    25

    2 15,1 213,3 1

    0,75 11,4 148,5

    2 15,8 238,2 1

    1,0 12,1 165,0

    2 16,6 261,1 1

    1,5 13,0 193,7

    2 18,5 325,1 1

    2,5 14,5 230,9

    2 20,3 390,1

    Example of cable reference designation when ordering it and in the documents of an item: 16 «Cable KPSVVKVm 2×2×0,5 TU 16.К99-030-2005»

  • Symmetrical cables for alarm and control systems for single installation, armoured KPSVEVKVm Nx2xS (Russian:КПСВЭВКВм Nx2xS) and KPSVEPsKPs Nx2xS (Russian:КПСВЭПсКПс Nx2xS)

    Technical specification TU 16.К99-030-2005

    Field of application Construction Symmetrical cables of pair twisting are designed for stationary single installation in the up-to-date alarm, systems, access control systems and in other control and communication systems in accordance with the current legislation. The cables of the type KPSVEVKVm can be used indoors and outdoors provided that there is a direct solar radiation and atmospheric precipitation protection. The cables of the type KPSVEPsKPs are used outdoors. The cables can be used in explosion hazard zones of any class according to the Regulations on electrical installations. Installation in the ground of category I-III is allowed. Rodent-proof.

    Pairs with single-wire copper conductors with cross-section from 0,5 to 2,5 mm² and PVC insulated, with an overall screen of an alum–lavsan (Al/Pet) tape with a drain conductor made of a tinned copper wire. The sheath is cold-resistant PVC (KPSVEVKVm) or self-extinguishing PE (KPSVEPsKPs), with braid armour made of round steel zinc-coated wires over it. The jacket over the armour is cold-resistant PVC (KPSVEVKVm) or self-extinguishing PE (KPSVEPsKPs) of black color. The cables (one-paired and double-paired) are series-produced. At the special request the cables can be produced with a number of pairs up to 40, depending on a cross-section of conductors.

    Fire risk class of the cables in accordance with GOST R 53315–2009 – O1.8.2.3.4 The cables meet the requirements of the normative documents «Technical regulations on fire safety», including those stated in GOST R 53315-2009 (clause 5.2, PRGP 1) about flame retardance at single installation and have the corresponding fire safety certificate. The cables are certified in the GOST R system.

    Electrical characteristics Nominal cross-section of conductors,

    S, mm2

    0,5 0,75 1,0 1,5 2,5

    DC loop resistance (two conductors of a pair) at 20 °C, equal or less than, Оhm /km 74,8 51,0 37,6 25,2 16,0

    Insulation resistance at 20 °C, not less than, МОhm × km 100 100 100 100 100

    Mutual capacitance, of a pair, equal or less than, nF/km 110 118 120 125 150

    Attenuation constant at frequency 1 kHz at 20 °С, equal or less than, dB/km 1,35 1,12 0,95 0,80 0,65

    Operating voltage, equal or less than, V 300 300 300 300 300

    Weight, size and operation parameters Number of

    pairs in cables,

    N

    Cross-section of

    conductors, S,

    mm2

    Outer diameter (size) of a cable,

    DO, equal or less than,

    mm

    Min. bending radius of cables,

    mm

    Estimated weight of 1

    km of cables,

    kg

    Range of permissible ambient

    temperatures,

    °C

    Service time of cables,

    equal or more than, years

    1 0,5

    11,2

    15 × Do during installation

    and 10 × Do

    fixed

    137,7

    – 15 ÷ 50 during

    installation and

    – 60 ÷ 70 during operation

    25

    2 15,3 215,8 1

    0,75 11,6 150,6

    2 16,0 240,5 1

    1,0 12,3 167,2

    2 16,8 263,6 1

    1,5 13,2 196,1

    2 18,7 327,8 1

    2,5 14,7 233,3

    2 20,5 392,8

    Example of cable reference designation when ordering it and in the documents of an item: «Cable KPSVEVKVm 2×2×1,5 TU16.К99-030-2005» 17

  • Symmetrical cables for alarm and control systems for single installation, armoured KPSVVBVm Nx2xS (Russian: КПСВВБВм Nx2xS) and KPSVPsBPs Nx2xS (Russian: КПСВПсБПс Nx2xS )

    Technical specification TU 16.К99-030-2005

    Field of application Construction Symmetrical cables of pair twisting are designed for stationary single installation in the up-to-date alarm systems, access control systems and in other control and communication systems in accordance with the current legislation. The cables of the type KPSVVBVm can be used indoors and outdoors provided that there is a direct solar radiation and atmospheric precipitation protection. The cables of the type KPSVPsBPs are used outdoors. The cables can be used in explosion hazard zones of any class according to the Regulations on electrical installations. Installation in the ground of category I-III is allowed. Rodent-proof.

    Pairs with single-wire copper conductors with cross-section from 0,5 to 2,5 mm², PVC insulated. The sheath is cold-resistant PVC (KPSVVBVm) or self-extinguishing polyethylene (KPSVPsBPs) with steel corrugated tape armour over the sheath, with a jacket made of cold-resistant PVC (KPSVVBVm) or self-extinguishing polyethylene (KPSVPsBPs) of black color. The cables (one-paired and double-paired) are series-produced. At the special request the cables can be produced with a number of pairs up to 40, depending on a cross-section of conductors.

    Fire risk class of the cables in accordance with GOST R 53315–2009 – O1.8.2.3.4 The cables meet the requirements of the normative documents «Technical regulations on fire safety», including those stated in GOST R 53315-2009 (clause 5.2, PRGP 1) about flame retardance at single installation and have the corresponding fire safety certificate. The cables are certified in the GOST R system.

    Electrical characteristics Nominal cross-section of conductors, S,

    mm2 0,5 0,75 1,0 1,5 2,5

    DC loop resistance (two conductors of a pair) at 20 °C, equal or less than, Оhm / km 74,8 51,0 37,6 25,2 16,0

    DC insulation resistance at 20 °C, not less than, МОhm × km 100 100 100 100 100

    Mutual capacitance of a pair, equal or less than, nF/km 105 110 114 115 140

    Attenuation constant at frequency 1 kHz at 20 °С, equal or less than, dB/km 1,34 1,07 0,94 0,69 0,59

    Operating voltage, equal or less than, V 300 300 300 300 300

    Weight, size and operation parameters Number of

    pairs in cables,

    N

    Cross-section of

    conductors, S,

    mm2

    Outer diameter (size) of a cable, DO,equal or less than,

    mm

    Min. bending radius of cables,

    mm

    Estimated weight of 1

    km of cables,

    kg

    Range of permissible ambient

    temperatures,

    °C

    Service time of cables,

    equal or more than, years

    1 0,5

    11,3

    20 × Do during

    installation and

    15 × Do fixed

    112,2

    – 15 ÷ 50 during

    installation and

    – 60 ÷ 70 during operation

    25

    2 15,4 177,7 1

    0,75 11,7 123,8

    2 16,1 198,5 1

    1,0 12,4 137,5

    2 16,9 217,5 1

    1,5 13,3 161,4

    2 18,8 270,9 1

    2,5 14,8 182,4

    2 20,6 325,0

    Example of cable reference designation when ordering it and in the documents of an item:

    «Cable KPSVVBVm 2×2×0,5 TU16.К99-030-2005» 18

  • Symmetrical cables for alarm and control systems for single installation, аrmoured KPSVEVBVm Nx2xS (Russian: КПСВЭВБВм Nx2xS) and KPSVEPsBPs Nx2xS (Russian: КПСВЭПсБПс Nx2xS)

    Technical specification TU 16.К99-030-2005

    Field of application Cable make-up Symmetrical cables of pair twisting are designed for stationary single installation in the up-to-date alarm systems, access control systems and in other control and communication systems in accordance with the current legislation. The cables of the type KPSVEVBVm can be used indoors and outdoors provided that there is a direct solar radiation and atmospheric precipitation protection. The cables of the type KPSVEPsBPs are used outdoors. The cables can be used in explosion hazard zones of any class according to the Regulations on electrical installations. Installation in the ground of category I-III is allowed. Rodent-proof.

    Pairs with single-wire copper conductors with cross-section from 0,5 to 2,5 mm² , PVC insulated, with an overall screen of an alum–lavsan (Al/Pet) tape with a drain conductor made of a tinned copper wire. A cold-resistant PVC (KPSVEVBVm) or self-extinguishing PE (KPSVEPsBPs) sheath with steel corrugated tape armour over it. The cable jacket over the armour is black cold-resistant PVC (KPSVEVBVm) or self-extinguishing PE (KPSVEPsBPs). The cables (one-paired and double-paired) are series-produced. At the special request the cables can be produced with a number of pairs up to 40, depending on a cross-section of conductors.

    Fire risk class of the cables in accordance with GOST R 53315–2009 – O1.8.2.3.4 The cables meet the requirements of the normative documents «Technical regulations on fire safety», including those stated in GOST R 53315-2009 (clause 5.2, PRGP 1) about flame retardance at single installation and have the corresponding fire safety certificate. The cables are certified in the GOST R system.

    Electrical characteristics Nominal cross-section of conductors,

    S, mm2

    0,5 0,75 1,0 1,5 2,5

    DC loop resistance (two conductors of a pair) at 20 °C, equal or less than, Оhm / km 74,8 51,0 37,6 25,2 16,0

    DC insulation resistance at 20 °C, not less than, МОhm × km 100 100 100 100 100

    Mutual capacitance of a pair, equal or less than, nF/km 110 118 120 125 150

    Attenuation constant at frequency 1 kHz at 20 °С, equal or less than, dB/km 1,35 1,12 0,95 0,80 0,65

    Operating voltage, equal or less than, V 300 300 300 300 300

    Weight, size and operation parameters Number of

    pairs in cables,

    N

    Cross-section of

    conductors, S,

    mm2

    Outer diameter (size) of a cable,

    DO, equal or less

    than, mm

    Min. bending radius of cables,

    mm

    Estimated weight of 1 km

    of cables,

    kg

    Range of permissible ambient

    temperatures,

    °C

    Service time of cables,

    equal or more than,

    years

    1 0,5

    11,5

    20 × Do during installation

    and 15 × Do

    fixed

    114,7

    – 15 ÷ 50 during

    installation and

    – 60 ÷ 70 during operation

    25

    2 15,6 179,8 1

    0,75 11,9 125,5

    2 16,3 200,4 1

    1,0 12,6 139,3

    2 17,1 219,6 1

    1,5 13,5 163,4

    2 19,0 273,1 1

    2,5 15,0 194,4

    2 20,8 327,3

    Example of cable reference designation when ordering it and in the documents of an item: «Cable KPSVEVBVm 2×2×2,5 TU16.К99-030-2005» 19

  • Symmetrical cable for alarm and control systems for installation in bunches, with low gas and fume emission KPSVVng(A)-LS Nx2xS (Russian: КВСВВнг(A)-LS Nx2xS)

    Technical specification TU 16.К99-002-2003

    Field of application Construction A symmetrical cable of pair twisting is designed for stationary installation in bunches in the up-to-date alarm systems, access control systems and in other control and communication systems in accordance with the current legislation. The cable can be used in the systems of nuclear power plants of safety class 3N, out of a zone inside containment. The cable is used outdoors and indoors provided that there is a protection from direct solar radiation (UV) and atmospheric precipitation and also in explosion hazard zones of any class.

    Pairs with single-wire copper conductors with cross-section from 0,5 to 2,5 mm² and insulation and red sheath of PVC of low fire risk and low smoke and fumeemission. The cables (one-paired and double-paired) are series-produced. At the special request the cables can be produced with a number of pairs up to 40, depending on a cross-section of conductors.

    Fire risk class of the cables in accordance with GOST R 53315–2009 – P1.8.2.2.2

    The cable meets the requirements of the normative documents «Technical regulations on fire safety», including those stated in GOST R 53315-2009 (clause 5.3, PRGP 1) about flame retardance at installation in bunches (category A) and has the corresponding fire safety certificate. The cable is certified in the GOST R system.

    Electrical characteristics Nominal cross-section of conductors, S,

    mm2 0,5 0,75 1,0 1,5 2,5

    DC loop resistance (two conductors of a pair) at 20 °C, equal or less than, Оhm /km 74,8 51,0 37,6 25,2 16,0

    DC insulation resistance at 20 °C, not less than, МОhm × km 100 100 100 100 100

    Mutual capacitance, of a pair, equal or less than, nF/km 75 80 85 87 105

    Attenuation constant at frequency 1 kHz at 20 °С, equal or less than, dB/km 1,32 0,98 0,88 0,66 0,57

    Operating voltage, equal or less than, V 300 300 300 300 300

    Weight, size and operation parameters Number of

    pairs in cables,

    N

    Cross-section of

    conductors, S,

    mm2

    Outer diameter (size) of a cable, DO,

    equal or less than,

    mm

    Min. bending radius of cables,

    mm

    Estimated weight of 1 km of cables,

    kg

    Range of permissible ambient

    temperatures,

    °C

    Service time of cables,

    equal or more than,

    years 1

    0,5 5,2

    10 × Do during

    installation and

    7 × Do fixed

    30,9

    – 10 ÷ 50 during installation

    and – 40 ÷ 70

    during operation

    30

    2 6,2 x 8,8 55,3 1

    0,75 5,6 39,0

    2 6,7 х 9,5 72,1 1

    1,0 6,3 48,3

    2 7,6 х 10,3 89,5 1

    1,5 6,8 64,7

    2 8,2 х 12,2 120,7 1

    2,5 8,2 88,5

    2 9,8 х 15,0 156,3

    Example of cable reference designation when ordering it and in the documents of an item: 20 «Cable KPSVVng(А)-LS 1×2×1,5 TU16.К99-002-2003»

  • Symmetrical cable for alarm and control systems for installation in bunches, with low gas and fume emission KPSVEVng(A)-LS Nx2xS (Russian:КПСВЭВнг(A)-LS Nx2xS)

    Technical specification TU 16.К99-002-2003

    Field of application Construction A symmetrical cable of pair twisting is designed for stationary installation in bunches in the up-to-date alarm systems, access control systems and in other control and communication systems in accordance with the current legislation. The cables KPSVEVng(A)-LS Nx2x0,5 can be used instead of the cables of the type J-Y(St)Y Nx2x0,8 Lg and JE-Y(St)Y Nx2x0,8 Bd. Also the cable is used in the systems of nuclear power plants of safety class 3N, out of a zone inside containment. The cable is used outdoors and indoors provided that there is a protection from direct solar radiation (UV) and atmospheric precipitation and also in explosion hazard zones of any class.

    Pairs with single-wire copper conductors with cross-section from 0,5 to 2,5 mm² and a red sheath and insulation of PVC of low fire risk and low smoke and fume emission, with an overall screen of an alum–lavsan (Al/Pet) tape with a drain conductor made of a tinned copper wire. The cables (one-paired and double-paired) are series-produced. At the special request the cables can be produced with a number of pairs up to 40, depending on a cross-section of conductors.

    Fire risk class of the cables in accordance with GOST R 53315–2009 –P1.8.2.2.2 The cable meets the requirements of the normative documents «Technical regulations on fire safety», including those stated in GOST R 53315-2009 (clause 5.3, PRGP 1) about flame retardance at installation in bunches (category A) and has the corresponding fire safety certificate. The cable is certified in the GOST R system.

    Electrical characteristics Nominal cross-section of conductors,

    S, mm2

    0,5 0,75 1,0 1,5 2,5

    DC loop resistance (two conductors of a pair) at 20 °C, equal or less than, Оhm / km 74,8 51,0 37,6 25,2 16,0

    DC insulation resistance at 20 °C, not less than, МОhm × km 100 100 100 100 100

    Mutual capacitance, of a pair, equal or less than, nF/km 110 118 120 125 150 Attenuation constant at frequency 1 kHz at 20 °С, equal or less than, dB/km 1,35 1,12 0,95 0,80 0,65

    Operating voltage, equal or less than, V 300 300 300 300 300

    Weight, size and operation parameters Number of

    pairs in cables,

    N

    Cross-section of conductor

    s, S,

    mm2

    Outer diameter (size) of a cable,

    DO, equal or less

    than, mm

    Min. bending radius of cables,

    mm

    Estimated weight of 1 km

    of cables,

    kg

    Range of permissible ambient

    temperatures,

    °C

    Service time of cables,

    equal or more than,

    years

    1

    0,5

    5,4

    10 × Do during

    installation and

    7 × Do fixed

    27,9

    – 10 ÷ 50 during installation

    and – 40 ÷ 70

    during operation

    30

    2 6,2×9,0 53,7 4 10,1 102,8 8 11,1х16,3 181,5 12 16,3 254,2 16 18,1 321,9 20 20,3 507,2 32 25,2 611,5 40 27,4 752,6 1

    0,75 5,9 42,1

    2 7,0 × 9,9 99,0 1

    1,0 6,4 52,0

    2 7,7 × 11,0 119,4 1

    1,5 7,2 68,4

    2 8,6 × 12,4 155,0 1

    2,5 8,4 92,9

    2 10,0 × 15,2 159,5 Example of cable reference designation when ordering it and in the documents of an item: «Cable KPSVEVng(А)-LS 1×2×1,5 TU 16.К99-002-2003» 21

  • Symmetrical cable for alarm and control systems for installation in bunches, with low gas and fume emission, armoured KPSVVKGng(А)-LS Nx2xS (Russian: КПСВВКГнг(А)-LS Nx2xS)

    Technical specification TU 16.К99-030-2005

    Field of application Cable make-up A symmetrical cable of pair twisting is designed for stationary installation in bunches in the up-to-date alarm systems, access control systems and in other control and communication systems in accordance with the current legislation. The cable is used outdoors and indoors. The cable can also be used in explosion hazard zones of any class according to the Regulations on electrical installations. Rodent-proof.

    Pairs with single-wire copper conductors with cross-section from 0,5 to 2,5 mm² and a red sheath and insulation of PVC of low fire risk and low smoke and fume emission, with braid armour of round steel zinc-coated wires, without a jacket. The cables (one-paired and double-paired) are series-produced. At the special request the cables can be produced with a number of pairs up to 40, depending on a cross-section of conductors.

    Fire risk class of the cables in accordance with GOST R 53315–2009 –P1.8.2.2.2 The cable meets the requirements of the normative documents «Technical regulations on fire safety», including those stated in GOST R 53315-2009 (clause 5.3, PRGP 1) about flame retardance at installation in bunches (category A) and has the corresponding fire safety certificate. The cable is certified in the GOST R system.

    Electrical characteristics Nominal cross-section of conductors, S,

    mm2 0,5 0,75 1,0 1,5 2,5

    DC loop resistance (two conductors of a pair) at 20 °C, equal or less than, Оhm /km 74,8 51,0 37,6 25,2 16,0

    DC insulation resistance at 20 °C, not less than, МОhm × km 100 100 100 100 100

    Mutual capacitance, of a pair, equal or less than, nF/km 105 110 114 115 140

    Attenuation constant at frequency 1 kHz at 20 °С, equal or less than, dB/km 1,34 1,07 0,94 0,69 0,59

    Operating voltage, equal or less than, V 300 300 300 300 300

    Weight, size and operation parameters Number of

    pairs in cables,

    N

    Cross-section of

    conductors, S,

    mm2

    Outer diameter (size) of a cable,

    DO, equal or less than,

    mm

    Min. bending radius of cables,

    mm

    Estimated weight of 1

    km of cables,

    kg

    Range of permissible ambient

    temperatures,

    °C

    Service time of cables,

    equal or more than, years

    1 0,5

    7,4

    15 × Do during

    installation and

    10 × Do fixed

    76,0

    – 10 ÷ 50 during installation

    and – 40 ÷ 70

    during operation

    25

    2 8,2 х 11,0 127,9 1

    0,75 7,9 86,8

    2 9,0 х 11,9 147,6 1

    1,0 8,4 98,1

    2 9,2 х 13,0 164,6 1

    1,5 9,2 120,2

    2 10,6 х 14,4 214,6 1

    2,5 10,4 150,0

    2 12,0 х 17,2 266,2

    Example of cable reference designation when ordering it and in the documents of an item: 22 «Cable KPSVVKGng (А)-LS 2×2×0,5 TU16.К99-030-2005»

  • Symmetrical cable for alarm and control systemsfor installation in bunches, with low gas and fume emission, armoured KPSVEVKGng(А)-LS Nx2xS (Russian: КПСВЭВКГнг(А)-LS Nx2xS)

    Technical specification TU 16.К99-030-2005

    Fire risk class of the cables in accordance with GOST R 53315–2009 –P1.8.2.2.2 The cable meets the requirements of the normative documents «Technical regulations on fire safety», including those stated in GOST R 53315-2009 (clause 5.3, PRGP 1) about flame retardance at installation in bunches (category A) and has the corresponding fire safety certificate. The cable is certified in the GOST R system.

    Electrical characteristics Nominal cross-section of conductors, S,

    mm2 0,5 0,75 1,0 1,5 2,5

    DC loop resistance (two conductors of a pair) at 20 °C, equal or less than, Оhm / km 74,8 51,0 37,6 25,2 16,0

    DC insulation resistance at 20 °C, not less than, МОhm × km 100 100 100 100 100

    Mutual capacitance, of a pair, equal or less than, nF/km 110 118 120 125 150

    Attenuation constant at frequency 1 kHz at 20 °С, equal or less than, dB/km 1,35 1,12 0,95 0,80 0,65

    Operating voltage, equal or less than, V 300 300 300 300 300

    Weight, size and operation parameters Number of

    pairs in cables,

    N

    Cross-section of

    conductors, S,

    mm2

    Outer diameter (size) of a cable, DO,

    equal or less than,

    mm

    Min. bending radius of cables,

    mm

    Estimated weight of 1 km

    of cables,

    kg

    Range of permissible ambient temperatures,

    °C

    Service time of cables,

    equal or more than,

    years

    1 0,5

    7,7

    15 × Do during

    installation and

    10 × Do fixed

    77,5

    – 10 ÷ 50 during installation

    and – 40 ÷ 70

    during operation

    25

    2 8,5 х 11,3 129,4 1

    0,75 8,2 88,3

    2 9,3 х 12,2 149,1 1

    1,0 8,7 99,6

    2 9,5 х 13,3 166,1 1

    1,5 9,5 121,7

    2 10,9 х 14,7 216,1 1

    2,5 10,7 151,5

    2 12,3 х 17,5 267,7

    Example of cable reference designation when ordering it and in the documents of an item: «Cable KPSVEVKGng (А)-LS 2×2×2,5 TU16.К99-030-2005» 23

    Field of application Cable make-up A symmetrical cable of pair twisting is designed for stationary installation in bunches in the up-to-date alarm systems, access control systems and in other control and communication systems in accordance with the current legislation. The cable is used outdoors and indoors. The cable can also be used in explosion hazard zones of any class according to the Regulations on electrical installations. Rodent-proof.

    Pairs with single-wire copper conductors with cross-section from 0,5 to 2,5 mm² and insulation of PVC of low fire risk and low smoke and fume emission, with an overall screen of an alum–lavsan (Al/Pet) tape with a drain conductor made of a tinned copper wire. A red sheath is PVC of low fire risk and low smoke and fume emission, with braid armour of round steel zinc-coated wires over it, without a jacket. The cables (one-paired and double-paired) are series-produced. At the special request the cables can be produced with a number of pairs up to 40, depending on a cross-section of conductors.

  • Symmetrical cable for alarm and control systems for installation in bunches, with low gas and fume emission, armoured KPSVVKVng(A) – LS Nx2xS (Russian: КПСВВКВнг(A) – LS Nx2xS)

    Technical specification TU 16.К99-030-2005

    Field of application Cable make-up A symmetrical cable of pair twisting is designed for stationary installation in bunches in the up-to-date alarm systems, access control systems and in other control and communication systems in accordance with the current legislation. The cable is used outdoors and indoors provided that there is a protection from direct solar radiation (UV) and atmospheric precipitation. The cable can be used in explosion hazard zones of any class according to the Regulations on electrical installations. Installation in the ground of category I-III is allowed. Rodent-proof.

    Pairs with single-wire copper conductors with cross-section from 0,5 to 2,5 mm² and insulation of PVC of low fire risk and low smoke and fume emission. The sheath is PVC of low fire risk and low smoke and fume emission, with braid armour of round steel zinc-coated wires over it. All the construction is inside a red jacket of PVC of low fire risk and low smoke and fume emission. The cables (one-paired and double-paired) are series-produced. At the special request the cables can be produced with a number of pairs up to 40, depending on a cross-section of conductors.

    Fire risk class of the cables in accordance with GOST R 53315–2009 –P1.8.2.2.2 The cable meets the requirements of the normative documents «Technical regulations on fire safety», including those stated in GOST R 53315-2009 (clause 5.3, PRGP 1) about flame retardance at installation in bunches (category A) and has the corresponding fire safety certificate. The cable is certified in the GOST R system.

    Electrical characteristics Nominal cross-section of conductors, S,

    mm2 0,5 0,75 1,0 1,5 2,5

    DC loop resistance (two conductors of a pair) at 20 °C, equal or less than, Оhm /km 74,8 51,0 37,6 25,2 16,0

    DC insulation resistance at 20 °C, not less than, МОhm × km 100 100 100 100 100

    Mutual capacitance, of a pair, equal or less than, nF/km 105 110 114 115 140

    Attenuation constant at frequency 1 kHz at 20 °С, equal or less than, dB/km 1,34 1,07 0,94 0,69 0,59

    Operating voltage, equal or less than, V 300 300 300 300 300

    Weight, size and operation parameters Number of

    pairs in cables,

    N

    Cross-section of

    conductors, S,

    mm2

    Outer diameter (size) of a cable, DO, equal or less than,

    mm

    Min. bending radius of cables,

    mm

    Estimated weight of 1 km

    of cables,

    kg

    Range of permissible ambient temperatures,

    °C

    Service time of cables,

    equal or more than,

    years

    1 0,5

    11,0

    15 × Do during installation

    and 10 × Do

    fixed

    152,9

    – 10 ÷ 50 during installation

    and – 40 ÷ 70

    during operation

    25

    2 15,1 239,5 1

    0,75 11,4 167,6

    2 15,8 265,9 1

    1,0 12,1 185,6

    2 16,6 290,6 1

    1,5 13,0 216,4

    2 18,5 358,9 1

    2,5 14,5 255,8

    2 20,3 427,8

    Example of cable reference designation when ordering it and in the documents of an item:

    «Cable KPSVVKVng(А)-LS 2×2×0,5 TU16.К99-030-2005» 24

  • Symmetrical cable for alarm and control systems for installation in bunches, with low gas and fume emission, armoured KPSVEVKVng(A)-LS Nx2xS (Russian: КПСВЭВКВнг(A)-LS Nx2xS)

    Technical specification TU 16.К99-030-2005

    Field of application Cable make-up A symmetrical cable of pair twisting is designed for stationary installation in bunches in the up-to-date alarm systems, access control systems and in other control and communication systems in accordance with the current legislation. The cable is used outdoors and indoors provided that there is a protection from direct solar radiation (UV) and atmospheric precipitation. The cable can be used in explosion hazard zones of any class according to the Regulations on electrical installations. Installation in the ground of category I-III is allowed. Rodent-proof.

    Pairs with single-wire copper conductors with cross-section from 0,5 to 2,5 mm² and insulation of PVC of low fire risk and low smoke and fume emission, with an overall screen of an alum–lavsan (Al/Pet) tape with a drain conductor made of a tinned copper wire. The sheath is PVC of low fire risk and low smoke and fume emission, with braid armour of round steel zinc-coated wires over it. All the construction is inside a red jacket of PVC oflow fire risk and low smoke and fume emission. The cables (one-paired and double-paired) are series-produced. At the special request the cables can be produced with a number of pairs up to40, depending on a cross-section of conductors.

    Example of cable reference designation when ordering it and in the documents of an item: «Cable KPSVEVKVng(A)-LS 2×2×0,75 TU16.К99-030-2005» 25

    Fire risk class of the cables in accordance with GOST R 53315–2009 –P1.8.2.2.2 The cable meets the requirements of the normative documents «Technical regulations on fire safety», including those stated in GOST R 53315-2009 (clause 5.3, PRGP 1) about flame retardance at installation in bunches (category A) and has the corresponding fire safety certificate. The cable is certified in the GOST R system.

    Electrical characteristics Nominal cross-section of conductors, S,

    mm2 0,5 0,75 1,0 1,5 2,5

    DC loop resistance (two conductors of a pair) at 20 °C, equal or less than, Оhm /km 74,8 51,0 37,6 25,2 16,0

    DC insulation resistance at 20 °C, not less than, МОhm × km 100 100 100 100 100

    Mutual capacitance, of a pair, equal or less than, nF/km 110 118 120 125 150

    Attenuation constant at frequency 1 kHz at 20 °С, equal or less than, dB/km 1,35 1,12 0,95 0,80 0,65

    Operating voltage, equal or less than, V 300 300 300 300 300

    Weight, size and operation parameters Number of

    pairs in cables,

    N

    Cross-section of conducto

    rs, S, mm2

    Outer diameter (size) of a cable,

    DO, equal or less than,

    mm

    Min. bending radius of cables,

    mm

    Estimated weight of 1 km

    of cables,

    kg

    Range of permissible ambient

    temperatures,

    °C

    Service time of cables,

    equal or more than, years

    1 0,5

    11,2

    15 × Do during installation

    and 10 × Do

    fixed

    156,4

    – 10 ÷ 50 during installation

    and – 40 ÷ 70

    during operation

    25

    2 15,3 242,5 1

    0,75 11,6 170,1

    2 16,0 268,7 1

    1,0 12,3 188,3

    2 16,8 293,5 1

    1,5 13,2 219,2

    2 18,7 362,0 1

    2,5 14,7 258,6

    2 20,5 431,0

  • Symmetrical cable for alarm and control systems for installation in bunches, with low gas and fume emission, armoured KPSVVBVng(А)-LS Nx2xS (Russian: КПСВВБВнг(А)-LS Nx2xS )

    Technical specification TU 16.К99-030-2005

    Field of application Cable make-up A symmetrical cable of pair twisting is designed for stationary installation in bunches in the up-to-date alarm systems, access control systems and in other control and communication systems in accordance with the current legislation. The cable is used outdoors and indoors provided that there is a protection from direct solar radiation (UV) and atmospheric precipitation. The cable can be used in explosion hazard zones of any class according to the Regulations on electrical installations. Installation in the ground of category I-III is allowed. Rodent-proof.

    Pairs with single-wire copper conductors with cross-section from 0,5 to 2,5 mm² and insulation of PVC with low fire risk and low smoke and fume emission. The sheath is PVC of low fire risk and low smoke and fume emission, with steel corrugated tape armour over it. All the construction is inside a red jacket of PVC of low fire risk and low smoke and fume emission. The cables (one-paired and double-paired) are series-produced. At the special request the cables can be produced with a number of pairs up to 40, depending on a cross-section of conductors.

    Fire risk class of the cables in accordance with GOST R 53315–2009 –P1.8.2.2.2 The cable meets the requirements of the normative documents «Technical regulations on fire safety», including those stated in GOST R 53315-2009 (clause 5.3, PRGP 1) about flame retardance at installation in bunches (category A) and has the corresponding fire safety certificate. The cable is certified in the GOST R system.

    Electrical characteristics Nominal cross-section of conductors, S,

    mm2 0,5 0,75 1,0 1,5 2,5

    DC loop resistance (two conductors of a pair) at 20 °C, equal or less than, Оhm /km 74,8 51,0 37,6 25,2 16,0

    DC insulation resistance at 20 °C, not less than, МОhm × km 100 100 100 100 100

    Mutual capacitance, of a pair, equal or less than, nF/km 105 110 114 115 140

    Attenuation constant at frequency 1 kHz at 20 °С, equal or less than, dB/km 1,34 1,07 0,94 0,69 0,59

    Operating voltage, equal or less than, V 300 300 300 300 300

    Weight, size and operation parameters Number of

    pairs in cables,

    N

    Cross-section of conductors,

    S,

    mm2

    Outer diameter (size) of a cable,

    DO, equal or less

    than, mm

    Min. bending radius of cables,

    mm

    Estimated weight of 1 km

    of cables,

    kg

    Range of permissible ambient

    temperatures,

    °C

    Service time of cables,

    equal or more than,

    years

    1 0,5

    11,3

    20 × Do during

    installation and

    15 × Do fixed

    127,4

    – 10 ÷ 50 during installation

    and – 40 ÷ 70

    during operation

    25

    2 15,4 199,6 1

    0,75 11,7 139,6

    2 16,1 221,5 1

    1,0 12,4 154,6

    2 16,9 242,1 1

    1,5 13,3 180,3

    2 18,8 299,0 1

    2,5 14,8 213,1

    2 20,6 356,5

    Example of cable reference designation when ordering it and in the documents of an item: 26 «Cable KPSVVBVng(А)-LS 2×2×1,0 ТУ16.К99-030-2005»

  • Symmetrical cable for alarm and control systems for installation in bunches, with low gas and fume emission, armoured KPSVEVBVng(A)-LS Nx2xS (Russian: КПСВЭВБВнг(A)-LS Nx2xS)

    Technical specification TU 16.К99-030-2005

    Field of application Cable make-up A symmetrical cable of pair twisting is designed for stationary installation in bunches in the up-to-date alarm systems, access control systems and in other control and communication systems in accordance with the current legislation. The cable is used outdoors and indoors provided that there is a protection from direct solar radiation (UV) and atmospheric precipitation. The cable can be used in explosion hazard zones of any class according to the Regulations on electrical installations. Installation in the ground of category I-III is allowed. Rodent-proof.

    Pairs with single-wire copper conductors with cross-section from 0,5 to 2,5 mm² and insulation of PVC of low fire risk and low smoke and fume emission, with an overall screen of an alum–lavsan (Al/Pet) tapewith a drain conductor made of a tinned copper wire. The sheath is PVC of low fire risk and low smoke and fume emission, with steelcorrugated tape armour over it. All the construction is inside a redjacket of PVC of low fire risk and low smoke and fume emission. The cables (one-paired and double-paired) are series-produced. At the special request the cables can be produced with a number of pairs up to40, depending on a cross-section of conductors.

    Fire risk class of the cables in accordance with GOST R 53315–2009 –P1.8.2.2.2 The cable meets the requirements of the normative documents