Page 1 A Bulk Energy Storage Resource Case Study updated from 40% to 50% RPS Shucheng Liu Principal, Market Development 2015-2016 Transmission Planning Process California ISO Public

A Bulk Energy Storage Resource Case Study updated from 40% ... · Renewable Overbuild and Pumped Storage Capacity (MW) Solar 1,346 1,058 Wind 1,230 1,008 Pumped Storage 500 500 500

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: A Bulk Energy Storage Resource Case Study updated from 40% ... · Renewable Overbuild and Pumped Storage Capacity (MW) Solar 1,346 1,058 Wind 1,230 1,008 Pumped Storage 500 500 500

Page 1

A Bulk Energy Storage Resource Case Study updated from 40% to 50% RPS

Shucheng LiuPrincipal, Market Development

2015-2016 Transmission Planning Process

California ISO Public

Page 2: A Bulk Energy Storage Resource Case Study updated from 40% ... · Renewable Overbuild and Pumped Storage Capacity (MW) Solar 1,346 1,058 Wind 1,230 1,008 Pumped Storage 500 500 500

Page 2

Purpose of the ISO bulk energy storage case study:

• To assess a bulk storage resource’s ability to reduce– production cost– renewable curtailment– CO2 emission– renewable overbuild to achieve the RPS target

• To analyze the economic feasibility of the bulk storage resource

• To consider the locational benefits of known potential bulk energy storage locations in ISO footprint

Page 3: A Bulk Energy Storage Resource Case Study updated from 40% ... · Renewable Overbuild and Pumped Storage Capacity (MW) Solar 1,346 1,058 Wind 1,230 1,008 Pumped Storage 500 500 500

Page 3

Regarding the update to the bulk energy storage study (June 13 Stakeholder Call):

• Initial study with 40% RPS was conducted in the 2015-2016 planning cycle

• The ISO indicated that it will provide an update of the study with 50% RPS

• This material is that update

• The 2016-2017 planning cycle will include the large energy storage study using 2016-2017 updated assumptions

Page 4: A Bulk Energy Storage Resource Case Study updated from 40% ... · Renewable Overbuild and Pumped Storage Capacity (MW) Solar 1,346 1,058 Wind 1,230 1,008 Pumped Storage 500 500 500

Page 4

Update to 50% RPS – Study Assumptions

Page 5: A Bulk Energy Storage Resource Case Study updated from 40% ... · Renewable Overbuild and Pumped Storage Capacity (MW) Solar 1,346 1,058 Wind 1,230 1,008 Pumped Storage 500 500 500

Page 5

Summary of study assumptions

• The study was based on the bulk energy storage study with 40% RPS the CAISO conducted in 2015

• The 40% RPS based model was updated with the following new assumptions for California– A new load forecast, including AAEE and DG PV– A new RPS portfolio, increasing from 40% to 50%– Regulation and load-following requirements based on

the new load, solar and wind generation profiles– A higher CAISO maximum net export limit

Page 6: A Bulk Energy Storage Resource Case Study updated from 40% ... · Renewable Overbuild and Pumped Storage Capacity (MW) Solar 1,346 1,058 Wind 1,230 1,008 Pumped Storage 500 500 500

Page 6

Summary of study assumptions (cont.)

• The 40% RPS based model was updated with the following new assumptions for California– Allowing renewable to provide load following-down– Removing the 25% local minimum generation

requirements in the CAISO– Enforcing a CAISO-wide frequency response

requirement• Other updates for WECC based on the TEPPC 2024

Common Case v1.5 (from the May 12, 2014 pre-release version)

Page 7: A Bulk Energy Storage Resource Case Study updated from 40% ... · Renewable Overbuild and Pumped Storage Capacity (MW) Solar 1,346 1,058 Wind 1,230 1,008 Pumped Storage 500 500 500

Page 7

Specifics of the updates – from the 40% RPS to the 50% RPS study

• Update of CA load forecast, including AAEE and DG PV, from 2013 to 2014 CEC IEPR forecast, in which– DG PV capacity increased from 4,560 MW to 5,373

MW

• A CA 50% RPS portfolio the CPUC created for CAISO special studies (CA FCDS scenario, RPS Calculator v6.1, August 4, 2015)– Solar and wind has higher capacity factors than in the

40% RPS portfolio

Page 8: A Bulk Energy Storage Resource Case Study updated from 40% ... · Renewable Overbuild and Pumped Storage Capacity (MW) Solar 1,346 1,058 Wind 1,230 1,008 Pumped Storage 500 500 500

Page 8

Specifics of the updates – from the 40% RPS to the 50% RPS study (cont.)

Comparison of RPS Portfolios Installed Capacity (MW)

0

5,000

10,000

15,000

20,000

25,000

Biogas/Biomass Geothermal Hydro Solar Wind

Inst

alle

d Ca

paci

ty (M

W)

40% RPS 50% RPS

Page 9: A Bulk Energy Storage Resource Case Study updated from 40% ... · Renewable Overbuild and Pumped Storage Capacity (MW) Solar 1,346 1,058 Wind 1,230 1,008 Pumped Storage 500 500 500

Page 9

Specifics of the updates – from the 40% RPS to the 50% RPS study (cont.)

Comparison of RPS Portfolios Energy (GWh)

0

10,000

20,000

30,000

40,000

50,000

60,000

70,000

Biogas/Biomass Geothermal Hydro Solar Wind

Rene

wab

le E

nerg

y (G

Wh)

40% RPS 50% RPS

Page 10: A Bulk Energy Storage Resource Case Study updated from 40% ... · Renewable Overbuild and Pumped Storage Capacity (MW) Solar 1,346 1,058 Wind 1,230 1,008 Pumped Storage 500 500 500

Page 10

Specifics of the updates – from the 40% RPS to the 50% RPS study (cont.)

• CA solar and wind hourly profiles with new shapes developed by the CAISO based on NREL raw data– Solar shapes spread wider in summer months

• CAISO max net export limit increased from 0 MW to 2,000 MW

• Renewable providing load following-down up to 50% of load following-down requirement – Resulting in additional curtailment of renewable

energy that was not counted in this study yet

Page 11: A Bulk Energy Storage Resource Case Study updated from 40% ... · Renewable Overbuild and Pumped Storage Capacity (MW) Solar 1,346 1,058 Wind 1,230 1,008 Pumped Storage 500 500 500

Page 11

Specifics of the updates – from the 40% RPS to the 50% RPS study (cont.)

• Removal of the 25% local minimum generation requirement for the CAISO, SCE and SDG&E

• A CAISO-wide 376 MW frequency response requirement that can be met by the combination of battery storage and online CCGT

Page 12: A Bulk Energy Storage Resource Case Study updated from 40% ... · Renewable Overbuild and Pumped Storage Capacity (MW) Solar 1,346 1,058 Wind 1,230 1,008 Pumped Storage 500 500 500

Page 12

Specifics of the updates – from the 40% RPS to the 50% RPS study (cont.)

• Other updates for whole WECC based on the TEPPC 2024 Common Case v1.5 (from the May 12, 2014 pre-release version), including– Load forecast and renewable portfolios for areas

outside CA– Fuel prices, specifically (~25%) higher gas price and

lower coal price– Higher hydro energy, mostly in July – October

Page 13: A Bulk Energy Storage Resource Case Study updated from 40% ... · Renewable Overbuild and Pumped Storage Capacity (MW) Solar 1,346 1,058 Wind 1,230 1,008 Pumped Storage 500 500 500

Page 13

Update to 50% RPS – Study Approach

Page 14: A Bulk Energy Storage Resource Case Study updated from 40% ... · Renewable Overbuild and Pumped Storage Capacity (MW) Solar 1,346 1,058 Wind 1,230 1,008 Pumped Storage 500 500 500

Page 14

Study approach

• Using the 2014 LTPP 40% RPS in 2024 Scenario with– The updates described in the previous section– Renewable curtailment remaining unlimited

• Analyzing two renewable build baselines, with and without a new bulk energy storage resource,– No overbuild of renewable resources – Overbuilding renewables to achieve 50% RPS target

• Overbuilding only solar or wind to demonstrate the benefits of more diversified RPS portfolios

Page 15: A Bulk Energy Storage Resource Case Study updated from 40% ... · Renewable Overbuild and Pumped Storage Capacity (MW) Solar 1,346 1,058 Wind 1,230 1,008 Pumped Storage 500 500 500

Page 15

Definition of the study cases and expected takeaways

This study quantifies• reduction of production

cost, renewable curtailment and CO2 emission,

• quantity and cost of renewable overbuild

• cost and market revenue of the bulk storage resource

It does not quantify• transmission impact

C: A + Solar Overbuild

D: A + Wind Overbuild

E: B + Solar Overbuild

F: B + Wind Overbuild

No RenewableOverbuild

With Overbuild toAchieve 50% RPS

A: 50% RPS Scenario

B: A + a Bulk Storage

Without Bulk Storage

With Bulk Storage

Page 16: A Bulk Energy Storage Resource Case Study updated from 40% ... · Renewable Overbuild and Pumped Storage Capacity (MW) Solar 1,346 1,058 Wind 1,230 1,008 Pumped Storage 500 500 500

Page 16

Assumptions of the new pumped storage resource, which represents the bulk energy storage

Item ValueNumber of units 2Max pumping capacity per unit (MW) 300Minimum pumping capacity per unit (MW) 75Maximum generation capacity per unit (MW) 250Minimum generation capacity per unit (MW) 5Pumping ramp rate (MW/min) 50Generation ramp rate (MW/min) 250Round-trip efficiency 83%VOM Cost ($/MWh) 3Maintenance rate 8.65%Forced outage rate 6.10%Upper reservoir maximum capacity (GWh) 8Upper reservoir minimum capacity (GWh) 2Interval to restore upper reservoir water level MonthlyPump technology Variable speedReserves can provide in generation and pumping modes

Regulation, spinning and load following

Reserves can provide in off modes Non-spinning Location Southern California

Page 17: A Bulk Energy Storage Resource Case Study updated from 40% ... · Renewable Overbuild and Pumped Storage Capacity (MW) Solar 1,346 1,058 Wind 1,230 1,008 Pumped Storage 500 500 500

Page 17

Assumptions of revenue requirements and RA revenue of the new resources

Item

Revenue Requirement($/kW-year) NQC Peak

Factor [1]RA Revenue ($/kW-year) [2]Generation

Resource [3]Transmission

Upgrade [4]

Large Solar In-State 327.12 22.00 47% 16.13 Large Solar Out-State 306.26 22.00 47% 16.13 Small Solar In-State 376.99 11.00 47% 16.13 Solar Thermal In-State 601.71 22.00 90% 30.89 Wind In-State 286.62 16.50 17% 5.83 Wind Out-State 261.13 72.00 45% 15.44 Pumped Storage In-State 383.62 16.50 100% 34.32

[1] References https://www.caiso.com/Documents/2012TACAreaSolar-WindFactors.xls and https://www.wecc.biz/Reliability/2024-Common-Case.zip[2] Reference http://www.cpuc.ca.gov/NR/rdonlyres/2AF422A2-BFE8-4F4F-8C19-827ED4BA8E03/0/2013_14ResourceAdequacyReport.pdf[3] References https://www.wecc.biz/Reliability/2014_TEPPC_GenCapCostCalculator.xlsm and https://www.wecc.biz/Reliability/2014_TEPPC_Generation_CapCost_Report_E3.pdf[4] Reference http://www.transwestexpress.net/scoping/docs/TWE-what.pdf and the CAISO assumptions.

Page 18: A Bulk Energy Storage Resource Case Study updated from 40% ... · Renewable Overbuild and Pumped Storage Capacity (MW) Solar 1,346 1,058 Wind 1,230 1,008 Pumped Storage 500 500 500

Page 18

Update to 50% RPS – Summary of Results

Page 19: A Bulk Energy Storage Resource Case Study updated from 40% ... · Renewable Overbuild and Pumped Storage Capacity (MW) Solar 1,346 1,058 Wind 1,230 1,008 Pumped Storage 500 500 500

Page 19

1,346

1,0581,230

1,008

500

500 500

0

200

400

600

800

1,000

1,200

1,400

1,600

1,800

A B C D E F

Cpap

city

(MW

)

Case

Solar Wind Pumped Storage

Capacity of renewable overbuild to achieve the 50% RPS target

No renewable overbuildA: 48.9% RPS achievedB: 49.1% RPS achieved

Renewable overbuildto achieve 50% RPS

Pumped storage plusrenewable overbuildto achieve 50% RPS

Page 20: A Bulk Energy Storage Resource Case Study updated from 40% ... · Renewable Overbuild and Pumped Storage Capacity (MW) Solar 1,346 1,058 Wind 1,230 1,008 Pumped Storage 500 500 500

Page 20

0

500

1,000

1,500

2,000

2,500

3,000

3,500

4,000

No Overbuild Solar Overbuild Wind Overbuild

Curt

ailm

ent (

GW

h)

Case

Without Pumped Storage With Pumped Storage

-425

-763

-566

A B C E D F

California renewable generation curtailment (50% RPS)

* Renewable generation is curtailed at -$300/MWh market clearing price (MCP).

50% RPS not achieved 50% RPS achieved

Curtailmentreduction

Page 21: A Bulk Energy Storage Resource Case Study updated from 40% ... · Renewable Overbuild and Pumped Storage Capacity (MW) Solar 1,346 1,058 Wind 1,230 1,008 Pumped Storage 500 500 500

Page 21

50.0

50.5

51.0

51.5

52.0

No Overbuild Solar Overbuild Wind Overbuild

CO2

Emis

sion

(mill

ion

MTo

n)

Case

Without Pumped Storage With Pumped Storage

-0.23

-0.08 -0.07

A B C E D F

California CO2 emission (50% RPS)

** California CO2 emission includes the emission from energy net import.

50% RPS not achieved 50% RPS achieved

CO2 emissionreduction

Page 22: A Bulk Energy Storage Resource Case Study updated from 40% ... · Renewable Overbuild and Pumped Storage Capacity (MW) Solar 1,346 1,058 Wind 1,230 1,008 Pumped Storage 500 500 500

Page 22

16,900

16,950

17,000

17,050

17,100

17,150

No Overbuild Solar Overbuild Wind Overbuild

Prod

uctio

n Co

st ($

mill

ion)

Case

Without Pumped Storage With Pumped Storage

-39

-28-29

A B C E D F

WECC annual production cost (50% RPS)

**** Production cost includes start-up, fuel and VOM cost, not CO2 cost.

50% RPS not achieved 50% RPS achieved

Productioncost reduction

Page 23: A Bulk Energy Storage Resource Case Study updated from 40% ... · Renewable Overbuild and Pumped Storage Capacity (MW) Solar 1,346 1,058 Wind 1,230 1,008 Pumped Storage 500 500 500

Page 23

494

388371304

183

183

183

0

100

200

300

400

500

600

A B C D E F

Leve

lized

Rev

enue

Req

uire

men

t ($m

illio

n/ye

ar)

Case

Solar Wind Pumped Storage

Renewable overbuild and pumped storage levelized annual revenue requirements (50% RPS)

No renewable overbuildA: 48.9% RPS achievedB: 49.1% RPS achieved

Renewable overbuildto achieve 50% RPS

Pumped storage plusrenewable overbuildto achieve 50% RPS

Page 24: A Bulk Energy Storage Resource Case Study updated from 40% ... · Renewable Overbuild and Pumped Storage Capacity (MW) Solar 1,346 1,058 Wind 1,230 1,008 Pumped Storage 500 500 500

Page 24

183 183 183188220

200

0

20

40

60

80

100

120

140

160

180

200

220

B - No Overbuild E - Solar Overbuild F - Wind Overbuild

($m

illio

n)

Case

Levelized Annual Revenue Requirement Net Market Revenue

Pumped storage levelized annual revenue requirement and net market revenue of 2024 (50% RPS)

***** Net revenue is revenue from generation, ancillary services and load following minus cost of operation andenergy consumed.

50% RPS not achieved 50% RPS achieved

Page 25: A Bulk Energy Storage Resource Case Study updated from 40% ... · Renewable Overbuild and Pumped Storage Capacity (MW) Solar 1,346 1,058 Wind 1,230 1,008 Pumped Storage 500 500 500

Page 25

Preliminary results by case – 50% RPS

* Renewable generation is curtailed at -$300/MWh market clearing price (MCP)** Includes the CO2 emission from net import.*** Calculated using $23.27/m-ton price.**** Includes start-up, fuel and VOM cost, not CO2 cost.***** Net revenue is revenue of energy, reserves and load following minus cost of energy and operation.

50% RPS Without Pumped Storage With Pumped StorageCase A C D B E F

Renewable Curtailment (GWh)* 2,673 3,781 3,188 2,247 3,018 2,622CA CO2 Emission (Million Ton)** 51.69 50.77 50.70 51.47 50.69 50.62CA CO2 Emission ($ mil)*** 1,203 1,181 1,180 1,198 1,180 1,178Production Cost ($ mil)****

WECC 17,125 17,051 17,034 17,086 17,023 17,005CA 4,016 3,990 3,963 3,959 3,938 3,913

Renewable Overbuild and Pumped Storage Capacity (MW)Solar 1,346 1,058Wind 1,230 1,008Pumped Storage 500 500 500

Levelized Annual Revenue Requirement of Renewable Overbuild and Pumped Storage ($ mil)Solar 494 388Wind 371 304Pumped Storage 183 183 183

Pumped Storage Net Market Revenue ($ mil)***** 188 220 200

Page 26: A Bulk Energy Storage Resource Case Study updated from 40% ... · Renewable Overbuild and Pumped Storage Capacity (MW) Solar 1,346 1,058 Wind 1,230 1,008 Pumped Storage 500 500 500

Page 26

Some observations

• From 40% RPS to 50% RPS, in all cases,– Renewable curtailment is lowered– Less renewable overbuild is required– CO2 emission is reduced– Production cost is increased– Wind overbuild is still more efficient than solar

overbuild – The pumped storage brings comparable benefits– It can meet its levelized revenue requirement from net

market revenue in three cases

Page 27: A Bulk Energy Storage Resource Case Study updated from 40% ... · Renewable Overbuild and Pumped Storage Capacity (MW) Solar 1,346 1,058 Wind 1,230 1,008 Pumped Storage 500 500 500

Page 27

Some observations (cont.)

• Lower renewable curtailment due to– 2,000 MW higher maximum net export limit– Allowing renewable to provide load following-down – New solar shapes and higher solar capacity factor

that reduce energy concentration in midday

• Less renewable overbuild required as– Lower renewable curtailment– Higher solar and wind capacity factors in the 50%

RPS portfolio

Page 28: A Bulk Energy Storage Resource Case Study updated from 40% ... · Renewable Overbuild and Pumped Storage Capacity (MW) Solar 1,346 1,058 Wind 1,230 1,008 Pumped Storage 500 500 500

Page 28

Some observations (cont.)

• Reduced CO2 emission because of– More renewable energy (40% to 50% RPS)– Lower load forecast (net by AAEE) and higher DG PV

• Increased production cost caused by– Higher gas price forecast

Page 29: A Bulk Energy Storage Resource Case Study updated from 40% ... · Renewable Overbuild and Pumped Storage Capacity (MW) Solar 1,346 1,058 Wind 1,230 1,008 Pumped Storage 500 500 500

Page 29

Some observations (cont.)

• Compared to solar, wind overbuild has – Less required overbuild capacity to achieve 50% RPS– Lower curtailment, CO2 emission and production cost

• As in the 40% RPS study, the pumped storage brings benefits to the system in reduction of– Overbuild needed to achieve the 50% RPS target– Renewable curtailment – CO2 emission– Production cost

Page 30: A Bulk Energy Storage Resource Case Study updated from 40% ... · Renewable Overbuild and Pumped Storage Capacity (MW) Solar 1,346 1,058 Wind 1,230 1,008 Pumped Storage 500 500 500

Page 30

Some observations (cont.)

• The pumped storage resource has net market revenue sufficient to meet its levelized revenue requirement in all three cases, mostly due to– Higher gas price that leads to higher energy and

ancillary service prices– Therefore higher net revenue from moving energy

from hours with curtailment to hours with high demand and from providing ancillary services and load-following

Page 31: A Bulk Energy Storage Resource Case Study updated from 40% ... · Renewable Overbuild and Pumped Storage Capacity (MW) Solar 1,346 1,058 Wind 1,230 1,008 Pumped Storage 500 500 500

Page 31

The End