97%High Efficiency
AC switch
Charge ACDCElectric double layer capacitor
Commercial power
Bi-directional inverter
Facility equipment・Factory equipment・Power plant, etc.
Reduction in Running Costs2
A long-lived electric double layer capacitor has been adopted instead of the lead battery to reduce replacement costs.
■ Reduced replacement costs
Adopts a parallel processing method, and achieves 97% efficiency. *Efficiency of 10kVA type (Model No.C23A103) is 96%.
Reduces running costs, and contributes to preservation of environment.
■ High efficiency
1 High quality
Supplies pure sine wave power without any interruption even when there is an instantaneous voltage dip or power outage.It prevents malfunction of facilities and reliability of power supply is enhanced.
■ No interruption of output power
Voltage
Current
Instantaneous power outageCommercial power
Operational status
Normal Instantaneous voltage dip NormalCommercial and inverter parallel
operation
Commercial and inverter parallel
operation
Inverter power supply (Electric double layer capacitor feeding)
Input
Output
Normal NormalCommercial and inverter parallel
operation
Commercial and inverter parallel
operation
Inverter power supply (Electric double layer capacitor feeding)
Commercial power
Operational status
Completely without interruptionof output power. Completely without interruption
of output power.
110kVA(8kW)
20kVA(16kW)
30kVA(24kW)
50kVA(40kW)
100kVA(80kW)
200kVA(160kW)
Highly Reliable / Energy-Saving Voltage Dip Compensators
AC210V AC210V
150kVA(120kW)
300kVA(240kW)
AC420V AC420V
Backup time
Standard
sec.
Backup time
Standard
OutputInput
OutputInput
3 phase 3 wire 3 phase 3 wire
3 phase 3 wire 3 phase 3 wire
Output capacity
Output capacity
1 sec.
Instantaneous voltage dip Instantaneous power outage
0
80
160
(kW)
Time0
80
160
(kW)
Time
High performance3
Compensates for power peaks generated by factory facilities and production lines.Reduction of required plant power capacity contributes to facility downsizing.
■ Peak cut function
Regenerative electric power generated by motors and machine tools can be used effectively.This contributes to power conservation.
■ Use of regenerative electric power
Without peak cut function With peak cut function
Large peak curent flows when starting motors and so forth.
Electric double layer capacitor provides compensating power to suppress peaks.
Inputpower
※Please consult us for information regarding volume of regenerative power reclamation.
Inputpower
High reliability4
During parallel redundant operation
UPS system using a completely independent control systems
UPS No.1
UPS No.2
Control unit
Conventional UPS system using a common control system
Control unit
Facility equipment・Factory equipment・Power plant, etc.
UPS No.1
Commercialpower
Commercialpower
UPS No.2
AC switch
Commercial power
Harmonic cancellation
Output currentCurrents that include harmonics generated from equipment and
devices
Compensation currentReverse current for harmonic current
Input currentThe commercial power
side is a sine wave with no harmonic components
Facility equipment・Factory equipment・Power plant, etc.
A bi-directional inverter makes the UPS input current into a sine wave, so that the commercial power supply is removed harmonic current.At the same time, power factor is improved to approximately 1.0.
■ Active filter function
Bi-directional inverter
Electric double layer capacitor
C33A can perform parallel redundant operation. In addition, it uses a completely independent control system that enables control units in each UPS to support parallel operation. This ability to support parallel redundant operation with independent control units makes the system highly reliable.
■ Parallel redundant operation(SANUPS C33A only)
Facility equipment・Factory equipment・Power plant, etc.
Control unit
(SANUPS C33A)
3
97%High Efficiency
AC switch
Charge ACDCElectric double layer capacitor
Commercial power
Bi-directional inverter
Facility equipment・Factory equipment・Power plant, etc.
Reduction in Running Costs2
A long-lived electric double layer capacitor has been adopted instead of the lead battery to reduce replacement costs.
■ Reduced replacement costs
Adopts a parallel processing method, and achieves 97% efficiency. *Efficiency of 10kVA type (Model No.C23A103) is 96%.
Reduces running costs, and contributes to preservation of environment.
■ High efficiency
1 High quality
Supplies pure sine wave power without any interruption even when there is an instantaneous voltage dip or power outage.It prevents malfunction of facilities and reliability of power supply is enhanced.
■ No interruption of output power
Voltage
Current
Instantaneous power outageCommercial power
Operational status
Normal Instantaneous voltage dip NormalCommercial and inverter parallel
operation
Commercial and inverter parallel
operation
Inverter power supply (Electric double layer capacitor feeding)
Input
Output
Normal NormalCommercial and inverter parallel
operation
Commercial and inverter parallel
operation
Inverter power supply (Electric double layer capacitor feeding)
Commercial power
Operational status
Completely without interruptionof output power. Completely without interruption
of output power.
110kVA(8kW)
20kVA(16kW)
30kVA(24kW)
50kVA(40kW)
100kVA(80kW)
200kVA(160kW)
Highly Reliable / Energy-Saving Voltage Dip Compensators
AC210V AC210V
150kVA(120kW)
300kVA(240kW)
AC420V AC420V
Backup time
Standard
sec.
Backup time
Standard
OutputInput
OutputInput
3 phase 3 wire 3 phase 3 wire
3 phase 3 wire 3 phase 3 wire
Output capacity
Output capacity
1 sec.
Instantaneous voltage dip Instantaneous power outage
0
80
160
(kW)
Time0
80
160
(kW)
Time
High performance3
Compensates for power peaks generated by factory facilities and production lines.Reduction of required plant power capacity contributes to facility downsizing.
■ Peak cut function
Regenerative electric power generated by motors and machine tools can be used effectively.This contributes to power conservation.
■ Use of regenerative electric power
Without peak cut function With peak cut function
Large peak curent flows when starting motors and so forth.
Electric double layer capacitor provides compensating power to suppress peaks.
Inputpower
※Please consult us for information regarding volume of regenerative power reclamation.
Inputpower
High reliability4
During parallel redundant operation
UPS system using a completely independent control systems
UPS No.1
UPS No.2
Control unit
Conventional UPS system using a common control system
Control unit
Facility equipment・Factory equipment・Power plant, etc.
UPS No.1
Commercialpower
Commercialpower
UPS No.2
AC switch
Commercial power
Harmonic cancellation
Output currentCurrents that include harmonics generated from equipment and
devices
Compensation currentReverse current for harmonic current
Input currentThe commercial power
side is a sine wave with no harmonic components
Facility equipment・Factory equipment・Power plant, etc.
A bi-directional inverter makes the UPS input current into a sine wave, so that the commercial power supply is removed harmonic current.At the same time, power factor is improved to approximately 1.0.
■ Active filter function
Bi-directional inverter
Electric double layer capacitor
C33A can perform parallel redundant operation. In addition, it uses a completely independent control system that enables control units in each UPS to support parallel operation. This ability to support parallel redundant operation with independent control units makes the system highly reliable.
■ Parallel redundant operation(SANUPS C33A only)
Facility equipment・Factory equipment・Power plant, etc.
Control unit
(SANUPS C33A)
4
ー 150kVA
150kVA 300kVA
■ Auto operation checkAutomatically carries out regular circuit checks in order to maintain secure back up operation.
The test is performed while power is supplied from the commercial power supply.When the electric double layer capacitor is worn out, a replacement alarm sounds.The automatic electric double layer capacitor operation test cycle can be changed.
Start of operation check
Periodic check
AC switchAC switch
Normal operation Check of electric double layer capacitor operation
InverterInverter Electric doublelayer capacitor
Electric doublelayer capacitor
Commercialpower
Commercialpower
EquipmentEquipment
Expanding capacity with unit extensions (SANUPS C33A only)
If necessary, capacity can be expanded by adding 150kVA units. Up to 300kVA of expansion is possible.*Consider using an I/O power cabinet that matches the maximum expected UPS capacity at the beginning of the installation.
Parallel operation output capacity
Parallel redundant operation output capacity (N+1 units)
Parallel processing type
A conventional on-line UPS uses double conversion. However, the SANUPS C uses parallel processing in which the utility power supply and inverter always operate in parallel in the normal mode.This assures supply of superior quality power to facility equipment and so on.Because of this operation, power supplied by the SANUPS C is highly efficient and reliable.
5
Apparent powerEffective power
At capacitor operation
At 100 % rectifier load
Electric double layer capacitor3 phase 3 wire
Up to rated capacity
85 % or higher compensation
3 phase 3 wire210 V(200 V, 220 V) Within +10 % and -8 %
Within ± 2 %
Within ± 4 %Within ± 0.1 %
0 sec(Without interruption)1 sec or higher (Under rated load)
Specifications
Input capacity and heating value
External transfer signals and output conditions
ModelItem
Rated output capacity
Acoustic noiseEnvironment
Remarks
Steel-sheet independent board closure type(Protection code IP2X)Parallel processing typeForced air
Cabinet structureOperation systemCooling systemEnergy storage device
Number of phases / wires
Rated voltage 210 V(200 V, 220 V)
Commercial parallel operationCapacitor operation
Rated frequency
50 Hz / 60 Hz
50 Hz / 60 Hz
Compensation capacity
Capacitor operationRating
Voltage imbalance
Input power factor 0.98 or higher
2 % or less
2 % or less
50 ms or less200 % (30 seconds), 800 % (0.5 seconds)
5 % or less
50 % or less
240 sec or less 180 sec or less 60 sec or less10 sec or less59 dB or less 65 dB or less
0.8 (lagging)
0.7 to 1.0 (lagging)
At rated operation
Same as AC input
Setting can be changedNote 1
Note 1
Note 2
Note 3
Unit rating comparison
Capacitor voltage 0 to 100%After compensating for a one-second voltage dipA-weighting
Insertion of 1/3 of total capacity over one line
Settling time
Harmonic current2 to 20 order harmonicCompensation order
Number of phases / wires
Overload capacity (output circuit)
Commercial parallel operation
Variation rangeLinear load
Rectifier load
Variability
Max. regenerative powerMax. regenerative electrical energy
Voltage dip compensation timeInitial charging timeRecharging time
Voltage accuracy
Frequency accuracy
Load power factor
Transient voltagefluctuation
Voltage wave form distortion rate
Rated voltage
Overcurrent protection
Output power regeneration processing
Rated frequency
Time for switching to capacitor power supply
※ The calculated values in this chart are based on a 0.8 load power factor.The indicated heating values for rated output after the electric double layer capacitor completes charging.
Distortedcurrentcompensation
Within ±5 %
When current reaches 110% of rated capacity, inverter shuts down and power is supplied directly from commercial power supply.Up to the rated current, inverter starts automatically and operates constantly.
Ambient temperature:0 to 40℃,Relative humidity:30 to 90 %(non-condensing)
External transfer signalsModel
Output conditions
AC input abnormality Input voltage deviates from rated value
Serious event An event that results in inverter shutdown
Minor event An event that does not prevent continued inverter operation
Output overcurrent Output current exceeds rated value
Parallel power supply Power supplied simultaneously from commercial power supply and inverter
Capacitor power supply Inverter operation using energy stored in the capacitor
Inverter operating When the inverter is operating
Commercial power supply Power supplied only from commercial power supply
Inverter stopped When the inverter is stopped
All output stopped When the unit’s output is completely stopped
● Indicates non-voltage contact output.
Note 1:Shows inverter performance upon shifting to capacitor operation from rated input voltage and rated frequency.Note 2:Continuous state (short-term fluctuations allowed within the maximum amount of regenerative power).Note 3:Conditions: 80% lagging power factor load, ambient temperature of 25 degrees Celsius.Voltage dip compensation time can be extended. Please inquire for details.
Item Model
150 kVA
180 kVA or higher
3.8 kW
300 kVA
360 kVA or higher
7.5 kW
C33A154 C33A304
○
○
○
○
○
○
○
○
○
○
-
○
○
○
○
○
○
○
-
-
-
○ Capacitor voltage drop When the capacitor voltage drops below the rated level
ACinput
ACOutput
10 kVA
16 kVA or higher
0.52 kW
20 kVA
25 kVA or higher
1.0 kW
30 kVA
38kVA or higher
1.6 kW
50 kVA
56 kVA or higher
2.6 kW
100 kVA
116 kVA or higher
5.1 kW
200 kVA
232 kVA or higher
10.2 kW
10 kVA8 kW
20 kVA16 kW
30 kVA24 kW
50 kVA40 kW
100 kVA 200 kVA
C23A103 C23A203 C23A303 C23A503 C23A104 C23A204
C23A103
C23A*** C33A***
C23A203 C23A303 C23A503 C23A104 C23A204
80 kW 160 kW
10 kWs 20 kWs 30 kWs 50 kWs 100 kWs 200 kWs
Rated capacity
Input capacity
Heating value
75% or higher compensation
420 V(380, 400, 415 V)
420 V(380, 400, 415 V)
0.97 or higher
70 dB or less
150 kVA120 kW
300 kVA240 kW
C33A154 C33A304
150 kWs 300 kWs
6
Dimensions (unit: mm)
W D H1 H2
C23A103
C23A203
C23A303
C23A503
C23A104
C23A204
10 kVA
20 kVA
30 kVA
50 kVA
100 kVA
200 kVA
Model Output capacity
Weight : 230 kg Weight : 450 kg
Weight : 650 kg Weight : 1100 kg
H1
W
H2
D
H1
W
H2
D
H1
W
H2
D
H1
W
H2
D
750 700 1650 125
1050 800 1825 125
1550 800 1825 250
125500 700 1400
C23A103(10kVA),C23A203(20kVA),C23A303(30kVA)
C23A104(100kVA)
C23A503(50kVA)
C23A204(200kVA)
Front Side
Front Side Front Side
Front Side
7
Dimensions (unit: mm)
UPS unit ×1, EDLC cabinetC33A154
C33A304
150 kVA
300 kVA
Model Output capacity Configuration
EDLC cabinets are designed individually. Please inquire regarding dimensions and specifications.
Remarks
UPS unit ×2, Input/output cabinet ×1, EDLC cabinet
5019
00
700 800 Weight : Approx. 550 kg
Weight : Approx. 1650 kg
800500
1900
50 800
2700
C33A154(150 kVA) UPS unit ×1(not including EDLC cabinet)
Front Side
Front Side
C33A304(300 kVA) Input/output cabinet ×1,UPS unit ×2(not including EDLC cabinet)
700 700
●Before starting installation, assembling and use, read the “Operation Manual” carefully and use the product correctly in your applications.●When you are going to use this product in the following application, the special considerations are required for operation, running, maintenance and control. Be sure to consult with our company as a part of your investigations. (a) Medical equipment and other equipment that are related directly to human life. (b) Train or elevator that can give injury to human body. (c) Socially and publicly important computer systems.
(d) And other equipment that are related to safety of human life and that can affect severe effects on maintenance of public functions.●For the applications that undergo vibration such as vehicles, ships and transportation facilities, please consult with our company. ●Never modify this product or give additional processing to this product.●For the installation andmaintenance work, please consult with our company or with specialized company.
※For any inquiry or consultation, please contact our sales representative.
Notes when investigating use of this product in your applications
CATALOG No. P0973B007 ’18.5
The names of companies and/or their products specified in this catalog are the trade names, and/or trademarks and/or registered trademarks of such respective companies.Specifications are subject to change without notice.
https://www.sanyodenki.com
TEL: +81 3 5927 1020
TEL: +86 21 6235 1107
TEL: +1 310 783 5400
TEL: +33 1 48 63 26 61
TEL: +852 2312 6250
468 Amapola Avenue Torrance, CA 90501, U.S.A.
3-33-1 Minami-Otsuka, Toshima-ku, Tokyo 170-8451, Japan
P.A. Paris Nord Ⅱ, 48 Allée des Erables-VILLEPINTE, BP.57286, F-95958 ROISSY CDG Cedex, France
Room 2106-2110, Bldg A, Far East International Plaza, No.319, Xianxia Road, Shanghai, 200051, China
TEL: +86 10 6522 2160Room1222, Tower B, Beijing COFCO Plaza, No.8 Jianguomennei Dajie, Dong Cheng District, Beijing 100005 China
Room 2305, 23/F, South Tower, Concordia Plaza, 1 Science Museum Road, TST East, Kowloon, Hong Kong
TEL: +86 755 3337 38682F 02-11, Shenzhen International Chamber of Commerce Tower, No.168 Fuhua 3 Road, Futian District, Shenzhen, 518048 China
TEL: +66 2261 8670388 Exchange Tower, 25th Floor, Unit 2501-1, Sukhumvit Road, Klongtoey, Klongtoey, Bangkok 10110 Thailand
TEL: +91 44 420 384 72#14 (Old No.6/3), Avenue Road, Nungambakkam, Chennai - 600034, Tamil Nadu, India
Beijing Branch
TEL: +86 22 2320 1186Room AB 16th Floor TEDA Building, No. 256 Jie Fang Nan Road, Hexi District, Tianjin 300042 ChinaTianjin Branch
TEL: +86 28 8661 6901Room2105B, Block A, Times Plaza, 2 Zongfu Road, Jinjiang District, Chengdu, 610016 ChinaChengdu Branch
TEL: +49 6196 76113 0
TEL: +82 2 773 5623
TEL: +886 2 2511 3938
TEL: +65 6223 1071
Frankfurter Strasse 80-82, 65760 Eschborn, Germany
988 Toa Payoh North, #04-08, Singapore 319002
N-711, 7F, Chia Hsin 2nd Bldg., No.96, Sec.2, Zhongshan N. Rd., Taipei 10449, Taiwan
15F, KDB Building, 372, Hangang-daero, Yongsan-gu, Seoul, 04323, Korea
TEL: + 62 21 252 3202Summitmas II 4th Floor, Jl. Jend. Sudirman Kav.61-62, Jakarta 12190, IndonesiaIndonesia Representative Office
TEL: +82 51 796 5151 8F, CJ Korea Express Bldg., 119, Daegyo-ro, Jung-gu, Busan, 48943, KoreaBusan Branch