97 - Sanyo€¦ · Bi-directional inverter Facility equipment ・Factory equipment ・Power plant, etc. 2 Reduction in Running Costs A long-lived electric double layer capacitor has

  • Upload
    others

  • View
    6

  • Download
    0

Embed Size (px)

Citation preview

Page 1: 97 - Sanyo€¦ · Bi-directional inverter Facility equipment ・Factory equipment ・Power plant, etc. 2 Reduction in Running Costs A long-lived electric double layer capacitor has
Page 2: 97 - Sanyo€¦ · Bi-directional inverter Facility equipment ・Factory equipment ・Power plant, etc. 2 Reduction in Running Costs A long-lived electric double layer capacitor has

2

97%High Efficiency

AC switch

Charge ACDCElectric double layer capacitor

Commercial power

Bi-directional inverter

Facility equipment・Factory equipment・Power plant, etc.

Reduction in Running Costs2

A long-lived electric double layer capacitor has been adopted instead of the lead battery to reduce replacement costs.

■ Reduced replacement costs

Adopts a parallel processing method, and achieves 97% efficiency. *Efficiency of 10kVA type (Model No.C23A103) is 96%.

Reduces running costs, and contributes to preservation of environment.

■ High efficiency

1 High quality

Supplies pure sine wave power without any interruption even when there is an instantaneous voltage dip or power outage.It prevents malfunction of facilities and reliability of power supply is enhanced.

■ No interruption of output power

Voltage

Current

Instantaneous power outageCommercial power

Operational status

Normal Instantaneous voltage dip NormalCommercial and inverter parallel

operation

Commercial and inverter parallel

operation

Inverter power supply (Electric double layer capacitor feeding)

Input

Output

Normal NormalCommercial and inverter parallel

operation

Commercial and inverter parallel

operation

Inverter power supply (Electric double layer capacitor feeding)

Commercial power

Operational status

Completely without interruptionof output power. Completely without interruption

of output power.

110kVA(8kW)

20kVA(16kW)

30kVA(24kW)

50kVA(40kW)

100kVA(80kW)

200kVA(160kW)

Highly Reliable / Energy-Saving Voltage Dip Compensators

AC210V AC210V

150kVA(120kW)

300kVA(240kW)

AC420V AC420V

Backup time

Standard

sec.

Backup time

Standard

OutputInput

OutputInput

3 phase 3 wire 3 phase 3 wire

3 phase 3 wire 3 phase 3 wire

Output capacity

Output capacity

1 sec.

Instantaneous voltage dip Instantaneous power outage

0

80

160

(kW)

Time0

80

160

(kW)

Time

High performance3

Compensates for power peaks generated by factory facilities and production lines.Reduction of required plant power capacity contributes to facility downsizing.

■ Peak cut function

Regenerative electric power generated by motors and machine tools can be used effectively.This contributes to power conservation.

■ Use of regenerative electric power

Without peak cut function With peak cut function

Large peak curent flows when starting motors and so forth.

Electric double layer capacitor provides compensating power to suppress peaks.

Inputpower

※Please consult us for information regarding volume of regenerative power reclamation.

Inputpower

High reliability4

During parallel redundant operation

UPS system using a completely independent control systems

UPS No.1

UPS No.2

Control unit

Conventional UPS system using a common control system

Control unit

Facility equipment・Factory equipment・Power plant, etc.

UPS No.1

Commercialpower

Commercialpower

UPS No.2

AC switch

Commercial power

Harmonic cancellation

Output currentCurrents that include harmonics generated from equipment and

devices

Compensation currentReverse current for harmonic current

Input currentThe commercial power

side is a sine wave with no harmonic components

Facility equipment・Factory equipment・Power plant, etc.

A bi-directional inverter makes the UPS input current into a sine wave, so that the commercial power supply is removed harmonic current.At the same time, power factor is improved to approximately 1.0.

■ Active filter function

Bi-directional inverter

Electric double layer capacitor

C33A can perform parallel redundant operation. In addition, it uses a completely independent control system that enables control units in each UPS to support parallel operation. This ability to support parallel redundant operation with independent control units makes the system highly reliable.

■ Parallel redundant operation(SANUPS C33A only)

Facility equipment・Factory equipment・Power plant, etc.

Control unit

(SANUPS C33A)

Page 3: 97 - Sanyo€¦ · Bi-directional inverter Facility equipment ・Factory equipment ・Power plant, etc. 2 Reduction in Running Costs A long-lived electric double layer capacitor has

3

97%High Efficiency

AC switch

Charge ACDCElectric double layer capacitor

Commercial power

Bi-directional inverter

Facility equipment・Factory equipment・Power plant, etc.

Reduction in Running Costs2

A long-lived electric double layer capacitor has been adopted instead of the lead battery to reduce replacement costs.

■ Reduced replacement costs

Adopts a parallel processing method, and achieves 97% efficiency. *Efficiency of 10kVA type (Model No.C23A103) is 96%.

Reduces running costs, and contributes to preservation of environment.

■ High efficiency

1 High quality

Supplies pure sine wave power without any interruption even when there is an instantaneous voltage dip or power outage.It prevents malfunction of facilities and reliability of power supply is enhanced.

■ No interruption of output power

Voltage

Current

Instantaneous power outageCommercial power

Operational status

Normal Instantaneous voltage dip NormalCommercial and inverter parallel

operation

Commercial and inverter parallel

operation

Inverter power supply (Electric double layer capacitor feeding)

Input

Output

Normal NormalCommercial and inverter parallel

operation

Commercial and inverter parallel

operation

Inverter power supply (Electric double layer capacitor feeding)

Commercial power

Operational status

Completely without interruptionof output power. Completely without interruption

of output power.

110kVA(8kW)

20kVA(16kW)

30kVA(24kW)

50kVA(40kW)

100kVA(80kW)

200kVA(160kW)

Highly Reliable / Energy-Saving Voltage Dip Compensators

AC210V AC210V

150kVA(120kW)

300kVA(240kW)

AC420V AC420V

Backup time

Standard

sec.

Backup time

Standard

OutputInput

OutputInput

3 phase 3 wire 3 phase 3 wire

3 phase 3 wire 3 phase 3 wire

Output capacity

Output capacity

1 sec.

Instantaneous voltage dip Instantaneous power outage

0

80

160

(kW)

Time0

80

160

(kW)

Time

High performance3

Compensates for power peaks generated by factory facilities and production lines.Reduction of required plant power capacity contributes to facility downsizing.

■ Peak cut function

Regenerative electric power generated by motors and machine tools can be used effectively.This contributes to power conservation.

■ Use of regenerative electric power

Without peak cut function With peak cut function

Large peak curent flows when starting motors and so forth.

Electric double layer capacitor provides compensating power to suppress peaks.

Inputpower

※Please consult us for information regarding volume of regenerative power reclamation.

Inputpower

High reliability4

During parallel redundant operation

UPS system using a completely independent control systems

UPS No.1

UPS No.2

Control unit

Conventional UPS system using a common control system

Control unit

Facility equipment・Factory equipment・Power plant, etc.

UPS No.1

Commercialpower

Commercialpower

UPS No.2

AC switch

Commercial power

Harmonic cancellation

Output currentCurrents that include harmonics generated from equipment and

devices

Compensation currentReverse current for harmonic current

Input currentThe commercial power

side is a sine wave with no harmonic components

Facility equipment・Factory equipment・Power plant, etc.

A bi-directional inverter makes the UPS input current into a sine wave, so that the commercial power supply is removed harmonic current.At the same time, power factor is improved to approximately 1.0.

■ Active filter function

Bi-directional inverter

Electric double layer capacitor

C33A can perform parallel redundant operation. In addition, it uses a completely independent control system that enables control units in each UPS to support parallel operation. This ability to support parallel redundant operation with independent control units makes the system highly reliable.

■ Parallel redundant operation(SANUPS C33A only)

Facility equipment・Factory equipment・Power plant, etc.

Control unit

(SANUPS C33A)

Page 4: 97 - Sanyo€¦ · Bi-directional inverter Facility equipment ・Factory equipment ・Power plant, etc. 2 Reduction in Running Costs A long-lived electric double layer capacitor has

4

ー 150kVA

150kVA 300kVA

■ Auto operation checkAutomatically carries out regular circuit checks in order to maintain secure back up operation.

The test is performed while power is supplied from the commercial power supply.When the electric double layer capacitor is worn out, a replacement alarm sounds.The automatic electric double layer capacitor operation test cycle can be changed.

Start of operation check

Periodic check

AC switchAC switch

Normal operation Check of electric double layer capacitor operation

InverterInverter Electric doublelayer capacitor

Electric doublelayer capacitor

Commercialpower

Commercialpower

EquipmentEquipment

Expanding capacity with unit extensions (SANUPS C33A only)

If necessary, capacity can be expanded by adding 150kVA units. Up to 300kVA of expansion is possible.*Consider using an I/O power cabinet that matches the maximum expected UPS capacity at the beginning of the installation.

Parallel operation output capacity

Parallel redundant operation output capacity (N+1 units)

Parallel processing type

A conventional on-line UPS uses double conversion. However, the SANUPS C uses parallel processing in which the utility power supply and inverter always operate in parallel in the normal mode.This assures supply of superior quality power to facility equipment and so on.Because of this operation, power supplied by the SANUPS C is highly efficient and reliable.

Page 5: 97 - Sanyo€¦ · Bi-directional inverter Facility equipment ・Factory equipment ・Power plant, etc. 2 Reduction in Running Costs A long-lived electric double layer capacitor has

5

Apparent powerEffective power

At capacitor operation

At 100 % rectifier load

Electric double layer capacitor3 phase 3 wire

Up to rated capacity

85 % or higher compensation

3 phase 3 wire210 V(200 V, 220 V) Within +10 % and -8 %

Within ± 2 %

Within ± 4 %Within ± 0.1 %

0 sec(Without interruption)1 sec or higher (Under rated load)

Specifications

Input capacity and heating value

External transfer signals and output conditions

ModelItem

Rated output capacity

Acoustic noiseEnvironment

Remarks

Steel-sheet independent board closure type(Protection code IP2X)Parallel processing typeForced air

Cabinet structureOperation systemCooling systemEnergy storage device

Number of phases / wires

Rated voltage 210 V(200 V, 220 V)

Commercial parallel operationCapacitor operation

Rated frequency

50 Hz / 60 Hz

50 Hz / 60 Hz

Compensation capacity

Capacitor operationRating

Voltage imbalance

Input power factor 0.98 or higher

2 % or less

2 % or less

50 ms or less200 % (30 seconds), 800 % (0.5 seconds)

5 % or less

50 % or less

240 sec or less 180 sec or less 60 sec or less10 sec or less59 dB or less 65 dB or less

0.8 (lagging)

0.7 to 1.0 (lagging)

At rated operation

Same as AC input

Setting can be changedNote 1

Note 1

Note 2

Note 3

Unit rating comparison

Capacitor voltage 0 to 100%After compensating for a one-second voltage dipA-weighting

Insertion of 1/3 of total capacity over one line

Settling time

Harmonic current2 to 20 order harmonicCompensation order

Number of phases / wires

Overload capacity (output circuit)

Commercial parallel operation

Variation rangeLinear load

Rectifier load

Variability

Max. regenerative powerMax. regenerative electrical energy

Voltage dip compensation timeInitial charging timeRecharging time

Voltage accuracy

Frequency accuracy

Load power factor

Transient voltagefluctuation

Voltage wave form distortion rate

Rated voltage

Overcurrent protection

Output power regeneration processing

Rated frequency

Time for switching to capacitor power supply

※ The calculated values in this chart are based on a 0.8 load power factor.The indicated heating values for rated output after the electric double layer capacitor completes charging.

Distortedcurrentcompensation

Within ±5 %

When current reaches 110% of rated capacity, inverter shuts down and power is supplied directly from commercial power supply.Up to the rated current, inverter starts automatically and operates constantly.

Ambient temperature:0 to 40℃,Relative humidity:30 to 90 %(non-condensing)

External transfer signalsModel

Output conditions

AC input abnormality Input voltage deviates from rated value

Serious event An event that results in inverter shutdown

Minor event An event that does not prevent continued inverter operation

Output overcurrent Output current exceeds rated value

Parallel power supply Power supplied simultaneously from commercial power supply and inverter

Capacitor power supply Inverter operation using energy stored in the capacitor

Inverter operating When the inverter is operating

Commercial power supply Power supplied only from commercial power supply

Inverter stopped When the inverter is stopped

All output stopped When the unit’s output is completely stopped

● Indicates non-voltage contact output.

Note 1:Shows inverter performance upon shifting to capacitor operation from rated input voltage and rated frequency.Note 2:Continuous state (short-term fluctuations allowed within the maximum amount of regenerative power).Note 3:Conditions: 80% lagging power factor load, ambient temperature of 25 degrees Celsius.Voltage dip compensation time can be extended. Please inquire for details.

Item Model

150 kVA

180 kVA or higher

3.8 kW

300 kVA

360 kVA or higher

7.5 kW

C33A154 C33A304

○ Capacitor voltage drop When the capacitor voltage drops below the rated level

ACinput

ACOutput

10 kVA

16 kVA or higher

0.52 kW

20 kVA

25 kVA or higher

1.0 kW

30 kVA

38kVA or higher

1.6 kW

50 kVA

56 kVA or higher

2.6 kW

100 kVA

116 kVA or higher

5.1 kW

200 kVA

232 kVA or higher

10.2 kW

10 kVA8 kW

20 kVA16 kW

30 kVA24 kW

50 kVA40 kW

100 kVA 200 kVA

C23A103 C23A203 C23A303 C23A503 C23A104 C23A204

C23A103

C23A*** C33A***

C23A203 C23A303 C23A503 C23A104 C23A204

80 kW 160 kW

10 kWs 20 kWs 30 kWs 50 kWs 100 kWs 200 kWs

Rated capacity

Input capacity

Heating value

75% or higher compensation

420 V(380, 400, 415 V) 

420 V(380, 400, 415 V) 

0.97 or higher

70 dB or less

150 kVA120 kW

300 kVA240 kW

C33A154 C33A304

150 kWs 300 kWs

Page 6: 97 - Sanyo€¦ · Bi-directional inverter Facility equipment ・Factory equipment ・Power plant, etc. 2 Reduction in Running Costs A long-lived electric double layer capacitor has

6

Dimensions (unit: mm)

W D H1 H2

C23A103

C23A203

C23A303

C23A503

C23A104

C23A204

10 kVA

20 kVA

30 kVA

50 kVA

100 kVA

200 kVA

Model Output capacity

Weight : 230 kg Weight : 450 kg

Weight : 650 kg Weight : 1100 kg

H1

W

H2

D

H1

W

H2

D

H1

W

H2

D

H1

W

H2

D

750 700 1650 125

1050 800 1825 125

1550 800 1825 250

125500 700 1400

C23A103(10kVA),C23A203(20kVA),C23A303(30kVA)

C23A104(100kVA)

C23A503(50kVA)

C23A204(200kVA)

Front Side

Front Side Front Side

Front Side

Page 7: 97 - Sanyo€¦ · Bi-directional inverter Facility equipment ・Factory equipment ・Power plant, etc. 2 Reduction in Running Costs A long-lived electric double layer capacitor has

7

Dimensions (unit: mm)

UPS unit ×1, EDLC cabinetC33A154

C33A304

150 kVA

300 kVA

Model Output capacity Configuration

EDLC cabinets are designed individually. Please inquire regarding dimensions and specifications.

Remarks

UPS unit ×2, Input/output cabinet ×1, EDLC cabinet

5019

00

700 800 Weight : Approx. 550 kg

Weight : Approx. 1650 kg

800500

1900

50 800

2700

C33A154(150 kVA) UPS unit ×1(not including EDLC cabinet)

Front Side

Front Side

C33A304(300 kVA) Input/output cabinet ×1,UPS unit ×2(not including EDLC cabinet)

700 700

Page 8: 97 - Sanyo€¦ · Bi-directional inverter Facility equipment ・Factory equipment ・Power plant, etc. 2 Reduction in Running Costs A long-lived electric double layer capacitor has

●Before starting installation, assembling and use, read the “Operation Manual” carefully and use the product correctly in your applications.●When you are going to use this product in the following application, the  special considerations are required for operation, running, maintenance and control. Be sure to consult with our company as a part of your investigations. (a) Medical equipment and other equipment that are related directly to   human life. (b) Train or elevator that can give injury to human body.  (c) Socially and publicly important computer systems.

 (d) And other equipment that are related to safety of human life and that   can affect severe effects on maintenance of public functions.●For the applications that undergo vibration such as vehicles, ships and transportation facilities, please consult with our company. ●Never modify this product or give additional processing to this product.●For the installation andmaintenance work, please consult with our company or with specialized company.

※For any inquiry or consultation, please contact our sales representative.

Notes when investigating use of this product in your applications

CATALOG No. P0973B007 ’18.5

The names of companies and/or their products specified in this catalog are the trade names, and/or trademarks and/or registered trademarks of such respective companies.Specifications are subject to change without notice.

https://www.sanyodenki.com

TEL: +81 3 5927 1020

TEL: +86 21 6235 1107

TEL: +1 310 783 5400

TEL: +33 1 48 63 26 61

TEL: +852 2312 6250

468 Amapola Avenue Torrance, CA 90501, U.S.A.

3-33-1 Minami-Otsuka, Toshima-ku, Tokyo 170-8451, Japan

P.A. Paris Nord Ⅱ, 48 Allée des Erables-VILLEPINTE, BP.57286, F-95958 ROISSY CDG Cedex, France

Room 2106-2110, Bldg A, Far East International Plaza, No.319, Xianxia Road, Shanghai, 200051, China

TEL: +86 10 6522 2160Room1222, Tower B, Beijing COFCO Plaza, No.8 Jianguomennei Dajie, Dong Cheng District, Beijing 100005 China

Room 2305, 23/F, South Tower, Concordia Plaza, 1 Science Museum Road, TST East, Kowloon, Hong Kong

TEL: +86 755 3337 38682F 02-11, Shenzhen International Chamber of Commerce Tower, No.168 Fuhua 3 Road, Futian District, Shenzhen, 518048 China

TEL: +66 2261 8670388 Exchange Tower, 25th Floor, Unit 2501-1, Sukhumvit Road, Klongtoey, Klongtoey, Bangkok 10110 Thailand

TEL: +91 44 420 384 72#14 (Old No.6/3), Avenue Road, Nungambakkam, Chennai - 600034, Tamil Nadu, India

Beijing Branch

TEL: +86 22 2320 1186Room AB 16th Floor TEDA Building, No. 256 Jie Fang Nan Road, Hexi District, Tianjin 300042 ChinaTianjin Branch

TEL: +86 28 8661 6901Room2105B, Block A, Times Plaza, 2 Zongfu Road, Jinjiang District, Chengdu, 610016 ChinaChengdu Branch

TEL: +49 6196 76113 0

TEL: +82 2 773 5623

TEL: +886 2 2511 3938

TEL: +65 6223 1071

Frankfurter Strasse 80-82, 65760 Eschborn, Germany

988 Toa Payoh North, #04-08, Singapore 319002

N-711, 7F, Chia Hsin 2nd Bldg., No.96, Sec.2, Zhongshan N. Rd., Taipei 10449, Taiwan

15F, KDB Building, 372, Hangang-daero, Yongsan-gu, Seoul, 04323, Korea

TEL: + 62 21 252 3202Summitmas II 4th Floor, Jl. Jend. Sudirman Kav.61-62, Jakarta 12190, IndonesiaIndonesia Representative Office

TEL: +82 51 796 5151 8F, CJ Korea Express Bldg., 119, Daegyo-ro, Jung-gu, Busan, 48943, KoreaBusan Branch