    Date Generated March 19 2015 03:07:03 pm

    Device Information

    Part Number 0487E32648XXC2X4H624XXX

    FID SEL-487E-3-RXXX-V0-Z103101-D20121108

    BFID SLBT-4XX-R205-V0-Z001002-D20100128

    Config

    Special

    Displayed Setting Groups

    Global

    Group 1

    Settings Legend

    Visible Setting

    Hidden Setting

    Invalid Setting

    Page 1 of 9

    19-03-2015file:///C:/Users/pbanerjee/AppData/Roaming/SEL/AcSELerator/QuickSet/Session_00...

  • Global Top

    Setting Description Range Value

    SID Station IdentifierRange = ASCII string with a maximum length of 40.

    HADCO

    RID Relay IdentifierRange = ASCII string with a maximum length of 40.

    SGT

    NFREQ Nominal System Frequency Select: 50, 60 60

    PHROT System Phase Rotation Select: ABC, ACB ABC

    EICISEnable Independent Control Input Settings

    Select: Y, N N

    EPMUEnable Synchronized Phasor Measurements

    Select: Y, N N

    IN1XXDDebounce Time For Mainboard Contact Inputs

    Range = 0.0 to 30.0 2.0

    IN2XXDDebounce Time For Interface Board # 1 Contact Inputs

    Range = 0.0 to 30.0 2.0

    SS1Condition(s) to Enable Setting Group 1 Equation

    Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG

    1

    SS2Condition(s) to Enable Setting Group 2 Equation

    Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG

    NA

    SS3Condition(s) to Enable Setting Group 3 Equation

    Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG

    NA

    SS4Condition(s) to Enable Setting Group 4 Equation

    Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG

    NA

    SS5Condition(s) to Enable Setting Group 5 Equation

    Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG

    NA

    SS6Condition(s) to Enable Setting Group 6 Equation

    Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG

    NA

    TGR Group Change Delay Range = 1 to 54000 180

    FRQSTPrimary Frequency Source Terminal

    Select: V, Z, ADV or OFF V

    DATE_F Date Format Select: MDY, YMD, DMY MDY

    IRIGCIRIG-B Control Bits Definition

    Select: NONE, C37.118 NONE

    UTCOFFOffset From UTC to Local Time

    Range = -15.5 to 15.5 -8.0

    BEG_DST Begin DST

    Select: "0,1,2,3,4,5,6,7,8,9,10,11,12,13,14,15,16,17,18,19,20,21,22,23", "1,2,3,L", "1,2,3,4,5,6,7", "1,2,3,4,5,6,7,8,9,10,11,12"

    2, 2, 1, 3

    END_DST End DST

    Select: "0,1,2,3,4,5,6,7,8,9,10,11,12,13,14,15,16,17,18,19,20,21,22,23", "1,2,3,L", "1,2,3,4,5,6,7", "1,2,3,4,5,6,7,8,9,10,11,12"

    2, 1, 1, 11

    RST_DEMCondition(s) for Resetting of Demand Metering Data Equation

    Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG

    NA

    Condition(s) for Resetting of Valid range = The legal

    Page 2 of 9

    19-03-2015file:///C:/Users/pbanerjee/AppData/Roaming/SEL/AcSELerator/QuickSet/Session_00...

  • RST_PDMPeak Demand Metering Data Equation

    operators: AND OR NOT R_TRIG F_TRIG

    NA

    RST_ENECondition(s) for Resetting of Energy Metering Data Equation

    Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG

    NA

    RSTTRGTCondition(s) for Resetting of Target LEDs Equation

    Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG

    NA

    RSTDNPECondition(s) for Resetting of DNP Fault Summary Data Equation

    Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG

    TRGTR

    RST_HALCondition(s) for Resetting of Warning Alarm Pulsing Equation

    Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG

    NA

    EVELOCK Event Summary Lock Period Range = 0 to 1000 0

    DNPSRC DNP Session Time Base Select: LOCAL, UTC UTC

    Global Top

    Page 3 of 9

    19-03-2015file:///C:/Users/pbanerjee/AppData/Roaming/SEL/AcSELerator/QuickSet/Session_00...

  • Group 1 Top

    Setting Description Range Value

    ECTTERM Enable the Following Current TerminalsSelect: Combination of S, T, U, W, X or OFF

    S, T

    EPTTERM Enable the Following Voltage TerminalsSelect: Combination of V, Z or OFF

    V

    E87Include the Following Terminals in the Differential Element

    Select: Combination of S, T or OFF

    S, T

    EREFEnable the Following Number of Restricted Earth Fault Elements

    Select: N, 1-3 1

    E50Enable Definite Time Overcurrent Elements for the Following Terminals

    Select: Combination of S, T or OFF

    S, T

    E51Enable the Following Number of Inverse Time Overcurrent Elements

    Select: N, 1-10 4

    E46Enable Current Unbalance Elements for the Following Terminals

    Select: Combination of S, T or OFF

    OFF

    E59 Enable the Following Number of Overvoltage Elements Select: N, 1-5 N

    E27 Enable the Following Number of Undervoltage Elements Select: N, 1-5 N

    E81Enable the Following Number of Over/Under Frequency Elements

    Select: N, 1-6 N

    E24 Enable Volts per Hertz Protection Select: N, Y Y

    EBFLEnable Breaker Failure Protection for the Following Terminals

    Select: Combination of S, T or OFF

    T

    EPCALEnable Active, Reactive and Apparent Power Calculations for the Following Terminals

    Select: Combination of S, T or OFF

    OFF

    EDEMSelect the Number of Demand Metering Elements Required

    Select: N, 1-10 N

    PTRV Potential Transformer Ratio for Terminal V Range = 1.0 to 10000.0 2000.0

    PTCONV Potential Transformer Connection For Terminal V Select: Y, D Y

    PTCOMPVPotential Transformer Compensation Angle for Terminal V

    Range = -179.99 to 180.00 0.00

    VNOMVPotential Transformer Nominal Line-to-Line Voltage For Terminal V

    Range = 30 to 300 110

    CTRS Current Transformer Ratio For Terminal S Range = 1 to 50000 400

    CTCONS Current Transformer Connection For Terminal S Select: Y, D Y

    CTRT Current Transformer Ratio For Terminal T Range = 1 to 50000 2400

    CTCONT Current Transformer Connection For Terminal T Select: Y, D Y

    CTRY1 Current Transformer Ratio for Terminal Y, Channel 1 Range = 1 to 50000 100

    VREFS Select Voltage Reference for Terminal S Select: OFF, V V

    VREFT Select Voltage Reference for Terminal T Select: OFF, V OFF

    ICOM Internal CT Connection Matrix Compensation Enabled Select: Y, N Y

    MVA Enter Transformer Maximum MVA Rating Range = 1 to 5000, OFF 120

    E87TSInclude Terminal S in the Differential Element for the Following Conditions

    Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG

    1

    TSCTC Terminal S CT Connection Compensation Range = 0 to 12 12

    VTERMS Terminal S Line-to-Line Voltage Range = 1.00 to 1000.00 380.00

    E87TTInclude Terminal T in the Differential Element for the Following Conditions

    Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG

    1

    Page 4 of 9

    19-03-2015file:///C:/Users/pbanerjee/AppData/Roaming/SEL/AcSELerator/QuickSet/Session_00...

  • TTCTC Terminal T CT Connection Compensation Range = 0 to 12 12

    VTERMT Terminal T Line-to-Line Voltage Range = 1.00 to 1000.00 33.00

    O87P Differential Element Operating Current Pickup Range = 0.10 to 4.00 0.25

    SLP1 Slope 1 Setting Range = 5.00 to 90.00 33.00

    SLP2 Slope 2 Setting Range = 5.00 to 90.00 90.00

    U87P Unrestrained Element Current Pickup Range = 1.00 to 20.00 8.00

    DIOPR Incremental Operate Current Pickup Range = 0.10 to 10.00 1.20

    DIRTR Incremental Restraint Current Pickup Range = 0.10 to 10.00 1.20

    E87HB Enable Harmonic Blocking Differential Element Select: Y, N Y

    E87HR Enable Harmonic Restraint Differential Element Select: Y, N Y

    PCT2 Second-Harmonic Percentage (% of fundamental) Range = 5 to 100, OFF 15

    PCT4 Fourth-Harmonic Percentage (% of fundamental) Range = 5 to 100, OFF 15

    PCT5 Fifth-Harmonic Percentage (% of fundamental) Range = 5 to 100, OFF 50

    TH5P Fifth-Harmonic Alarm Threshold Range = 0.2 to 3.2, OFF OFF

    87QPNegative Sequence Differential Element Operating Current Pickup

    Range = 0.05 to 1.00 0.30

    SLPQ1 Negative Sequence Differential Slope Range = 5 to 100 25

    87QD Negative Sequence Differential Element Delay Range = 2.000 to 9999.000 10.000

    REFRF1 Select the Restraint Quantity for REF Element 1Select: Combination of S, T or OFF

    OFF

    REF50P1REF (50P) Operate Current Instantaneous Overcurrent 1 Pickup

    Range = 0.05 to 20.00, OFF OFF

    REF51P1REF (51P) Operate Current Inverse Time Overcurrent Element 1 Pickup

    Range = 0.05 to 3.20, OFF 0.05

    REF51C1 REF Inverse Time Overcurrent Element 1 Curve Select: U1-U5, C1-C5 C4

    RF51TD1REF Inverse Time Overcurrent Element 1 Time Dial Setting

    Range = 0.05 to 1.00 0.15

    RF51RS1REF Inverse Time Overcurrent Element 1 Electromechanical Reset

    Select: Y, N Y

    RF51TC1REF Inverse Time Overcurrent Element 1 Torque Control Equation

    Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG

    1

    E50S Enable the Type of Overcurrent Elements for Terminal SSelect: Combination of P, Q, G

    P, G

    E67S Enable Directional Elements Select: Y, N N

    50SP1P Phase Instantaneous Overcurrent Pickup Level 1 Range = 0.05 to 20.00, OFF 8.00

    67SP1TC Phase Instantaneous Overcurrent Level 1 Torque ControlValid range = The legal operators: AND OR NOT R_TRIG F_TRIG

    SF32P AND PLT03

    67SP1D Phase Instantaneous Overcurrent Level 1 Delay Range = 0.00 to 16000.00 3.00

    50SG1P Zero-Seq Inst O/C Pickup Level 1 Range = 0.05 to 20.00, OFF OFF

    50SP2P Phase Instantaneous Overcurrent Pickup Level 2 Range = 0.05 to 20.00, OFF OFF

    E50T Enable the Type of Overcurrent Elements for Terminal TSelect: Combination of P, Q, G

    P, G

    50TP1P Phase Instantaneous Overcurrent Pickup Level 1 Range = 0.05 to 20.00, OFF 9.00

    67TP1TC Phase Instantaneous Overcurrent Level 1 Torque ControlValid range = The legal operators: AND OR NOT R_TRIG F_TRIG

    TF32P AND PLT03

    67TP1D Phase Instantaneous Overcurrent Level 1 Delay Range = 0.00 to 16000.00 3.00

    50TG1P Zero-Seq Inst O/C Pickup Level 1 Range = 0.05 to 20.00, OFF OFF

    50TP2P Phase Instantaneous Overcurrent Pickup Level 2 Range = 0.05 to 20.00, OFF OFF

    EXBFT Enabling Condition(s) for External Breaker FailureValid range = The legal operators: AND OR NOT

    NA

    Page 5 of 9

    19-03-2015file:///C:/Users/pbanerjee/AppData/Roaming/SEL/AcSELerator/QuickSet/Session_00...

  • R_TRIG F_TRIG

    EBFPUT External Breaker Failure Initiate Pickup Delay Range = 0.000 to 6000.000 6.000

    50FPUT Fault Current Pickup Range = 0.10 to 10.00 9.00

    BFPUT Breaker Failure Initiate Pickup Delay Range = 0.000 to 6000.000 12.000

    RTPUT Retrip Delay Range = 0.000 to 6000.000 6000.000

    BFIT Breaker Fail Initiate Condition(s)Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG

    NA

    ATBFIT Alternate Breaker Fail Initiate Condition(s)Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG

    NA

    ENINBFT Enabling Condition(s) for Neutral Breaker FailureValid range = The legal operators: AND OR NOT R_TRIG F_TRIG

    NA

    INFPUT Neutral Current Pickup Range = 0.10 to 10.00 0.10

    EBFIST Breaker Failure Initiate Seal-In Select: Y, N N

    BFIDOT Breaker Failure Initiate Dropout Delay Range = 0.000 to 1000.000 1.500

    51O01 Inverse Time Overcurrent Element 01 Operate Quantity

    Select: 3I0TM, 3I2TM, I1TM, IATFM, IATRMS, IBTFM, IBTRMS, ICTFM, ICTRMS, IMAXTF, IMAXTR, 3I0SM, 3I2SM, I1SM, IASFM, IASRMS, IBSFM, IBSRMS, ICSFM, ICSR ...

    IMAXSF

    51P01 Inverse Time Overcurrent Element 01 Pickup ValueValid range = The legal operators: AND OR NOT R_TRIG F_TRIG

    0.6

    51C01 Inverse Time Overcurrent Element 01 Curve Selection Select: U1-U5, C1-C5 C1

    51TD01 Inverse Time Overcurrent Element 01 Time DialValid range = The legal operators: AND OR NOT R_TRIG F_TRIG

    0.20

    51RS01Inverse Time Overcurrent Element 01 Electromechanical Reset Enable

    Select: Y, N Y

    51TC01 Inverse Time Overcurrent Element 01 Torque ControlValid range = The legal operators: AND OR NOT R_TRIG F_TRIG

    PLT09

    51O02 Inverse Time Overcurrent Element 02 Operate Quantity

    Select: 3I0TM, 3I2TM, I1TM, IATFM, IATRMS, IBTFM, IBTRMS, ICTFM, ICTRMS, IMAXTF, IMAXTR, 3I0SM, 3I2SM, I1SM, IASFM, IASRMS, IBSFM, IBSRMS, ICSFM, ICSR ...

    IMAXTF

    51P02 Inverse Time Overcurrent Element 02 Pickup ValueValid range = The legal operators: AND OR NOT R_TRIG F_TRIG

    1.1

    51C02 Inverse Time Overcurrent Element 02 Curve Selection Select: U1-U5, C1-C5 C1

    51TD02 Inverse Time Overcurrent Element 02 Time DialValid range = The legal operators: AND OR NOT R_TRIG F_TRIG

    0.20

    51RS02Inverse Time Overcurrent Element 02 Electromechanical Reset Enable

    Select: Y, N Y

    51TC02 Inverse Time Overcurrent Element 02 Torque ControlValid range = The legal operators: AND OR NOT R_TRIG F_TRIG

    PLT09

    Select: 3I0TM, 3I2TM,

    Page 6 of 9

    19-03-2015file:///C:/Users/pbanerjee/AppData/Roaming/SEL/AcSELerator/QuickSet/Session_00...

  • 51O03 Inverse Time Overcurrent Element 03 Operate Quantity

    I1TM, IATFM, IATRMS, IBTFM, IBTRMS, ICTFM, ICTRMS, IMAXTF, IMAXTR, 3I0SM, 3I2SM, I1SM, IASFM, IASRMS, IBSFM, IBSRMS, ICSFM, ICSR ...

    3I0SM

    51P03 Inverse Time Overcurrent Element 03 Pickup ValueValid range = The legal operators: AND OR NOT R_TRIG F_TRIG

    0.6

    51C03 Inverse Time Overcurrent Element 03 Curve Selection Select: U1-U5, C1-C5 C1

    51TD03 Inverse Time Overcurrent Element 03 Time DialValid range = The legal operators: AND OR NOT R_TRIG F_TRIG

    0.15

    51RS03Inverse Time Overcurrent Element 03 Electromechanical Reset Enable

    Select: Y, N Y

    51TC03 Inverse Time Overcurrent Element 03 Torque ControlValid range = The legal operators: AND OR NOT R_TRIG F_TRIG

    PLT09

    51O04 Inverse Time Overcurrent Element 04 Operate Quantity

    Select: 3I0TM, 3I2TM, I1TM, IATFM, IATRMS, IBTFM, IBTRMS, ICTFM, ICTRMS, IMAXTF, IMAXTR, 3I0SM, 3I2SM, I1SM, IASFM, IASRMS, IBSFM, IBSRMS, ICSFM, ICSR ...

    3I0TM

    51P04 Inverse Time Overcurrent Element 04 Pickup ValueValid range = The legal operators: AND OR NOT R_TRIG F_TRIG

    0.1

    51C04 Inverse Time Overcurrent Element 04 Curve Selection Select: U1-U5, C1-C5 C1

    51TD04 Inverse Time Overcurrent Element 04 Time DialValid range = The legal operators: AND OR NOT R_TRIG F_TRIG

    0.20

    51RS04Inverse Time Overcurrent Element 04 Electromechanical Reset Enable

    Select: Y, N Y

    51TC04 Inverse Time Overcurrent Element 04 Torque ControlValid range = The legal operators: AND OR NOT R_TRIG F_TRIG

    PLT09

    TRXFMR Trip Condition(s) for Transformer TerminalsValid range = The legal operators: AND OR NOT R_TRIG F_TRIG

    87R OR REFF1

    ULTXFMR Unlatch Trip Condition(s) for Transformer TerminalsValid range = The legal operators: AND OR NOT R_TRIG F_TRIG

    TRGTR

    TRS Trip Condition(s) for Terminal SValid range = The legal operators: AND OR NOT R_TRIG F_TRIG

    50SP1 OR 50SQ1

    ULTRS Unlatch Trip Condition(s) for Terminal SValid range = The legal operators: AND OR NOT R_TRIG F_TRIG

    TRGTR

    CLS Close Condition(s) for Terminal SValid range = The legal operators: AND OR NOT R_TRIG F_TRIG

    LB10

    ULCLS Unlatch Close Condition(s) for Terminal SValid range = The legal operators: AND OR NOT R_TRIG F_TRIG

    52CLS

    TRT Trip Condition(s) for Terminal TValid range = The legal operators: AND OR NOT R_TRIG F_TRIG

    50TP1 OR 50TQ1

    Page 7 of 9

    19-03-2015file:///C:/Users/pbanerjee/AppData/Roaming/SEL/AcSELerator/QuickSet/Session_00...

  • ULTRT Unlatch Trip Condition(s) for Terminal TValid range = The legal operators: AND OR NOT R_TRIG F_TRIG

    TRGTR

    CLT Close Condition(s) for Terminal TValid range = The legal operators: AND OR NOT R_TRIG F_TRIG

    LB10

    ULCLT Unlatch Close Condition(s) for Terminal TValid range = The legal operators: AND OR NOT R_TRIG F_TRIG

    52CLT

    TDURD Minimum Trip Duration Range = 2.000 to 8000.000 5.000

    ER Condition(s) for Triggering Event ReportsValid range = The legal operators: AND OR NOT R_TRIG F_TRIG

    50SQ1 OR 50TQ1

    FAULT Condition(s) for Asserting Fault BitValid range = The legal operators: AND OR NOT R_TRIG F_TRIG

    50SQ1 OR 50TQ1

    CFD Close Failure DelayRange = 2.000 to 99999.000, OFF

    4.000

    24VSRC Voltage Source for V/Hz Calculation Select: V, Z V

    24D1P Level 1 Volts/Hertz Pickup (%) Range = 100 to 200 110

    24D1D Level 1 Time Delay Range = 0.04 to 6000.00 10.00

    24TC Torque Control for Volts/Hertz ElementValid range = The legal operators: AND OR NOT R_TRIG F_TRIG

    1

    24CCS Select Level 2 Composite Curve Select: OFF, DD, U1, U2 U1

    24U1TC Torque Control for Curve 1Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG

    1

    24U1NP Select the Number of Points for Curve 1 Range = 3 to 20 7

    24U1CR Curve 1 Reset Time (seconds) Range = 0.01 to 400.00 400.00

    24U111 Curve 1, Point 01 Range = 100 to 200 110

    24U121 Curve 1, Point 01 Range = 0.04 to 6000.00 6000.00

    24U112 Curve 1, Point 02 Range = 100 to 200 115

    24U122 Curve 1, Point 02 Range = 0.04 to 6000.00 240.00

    24U113 Curve 1, Point 03 Range = 100 to 200 120

    24U123 Curve 1, Point 03 Range = 0.04 to 6000.00 60.00

    24U114 Curve 1, Point 04 Range = 100 to 200 125

    24U124 Curve 1, Point 04 Range = 0.04 to 6000.00 30.00

    24U115 Curve 1, Point 05 Range = 100 to 200 130

    24U125 Curve 1, Point 05 Range = 0.04 to 6000.00 19.00

    24U116 Curve 1, Point 06 Range = 100 to 200 135

    24U126 Curve 1, Point 06 Range = 0.04 to 6000.00 13.00

    24U117 Curve 1, Point 07 Range = 100 to 200 140

    24U127 Curve 1, Point 07 Range = 0.04 to 6000.00 10.00

    Group 1

    Top

    Page 8 of 9

    19-03-2015file:///C:/Users/pbanerjee/AppData/Roaming/SEL/AcSELerator/QuickSet/Session_00...