Date Generated March 19 2015 03:07:03 pm
Device Information
Part Number 0487E32648XXC2X4H624XXX
FID SEL-487E-3-RXXX-V0-Z103101-D20121108
BFID SLBT-4XX-R205-V0-Z001002-D20100128
Config
Special
Displayed Setting Groups
Global
Group 1
Settings Legend
Visible Setting
Hidden Setting
Invalid Setting
Page 1 of 9
19-03-2015file:///C:/Users/pbanerjee/AppData/Roaming/SEL/AcSELerator/QuickSet/Session_00...
Global Top
Setting Description Range Value
SID Station IdentifierRange = ASCII string with a maximum length of 40.
HADCO
RID Relay IdentifierRange = ASCII string with a maximum length of 40.
SGT
NFREQ Nominal System Frequency Select: 50, 60 60
PHROT System Phase Rotation Select: ABC, ACB ABC
EICISEnable Independent Control Input Settings
Select: Y, N N
EPMUEnable Synchronized Phasor Measurements
Select: Y, N N
IN1XXDDebounce Time For Mainboard Contact Inputs
Range = 0.0 to 30.0 2.0
IN2XXDDebounce Time For Interface Board # 1 Contact Inputs
Range = 0.0 to 30.0 2.0
SS1Condition(s) to Enable Setting Group 1 Equation
Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG
1
SS2Condition(s) to Enable Setting Group 2 Equation
Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG
NA
SS3Condition(s) to Enable Setting Group 3 Equation
Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG
NA
SS4Condition(s) to Enable Setting Group 4 Equation
Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG
NA
SS5Condition(s) to Enable Setting Group 5 Equation
Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG
NA
SS6Condition(s) to Enable Setting Group 6 Equation
Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG
NA
TGR Group Change Delay Range = 1 to 54000 180
FRQSTPrimary Frequency Source Terminal
Select: V, Z, ADV or OFF V
DATE_F Date Format Select: MDY, YMD, DMY MDY
IRIGCIRIG-B Control Bits Definition
Select: NONE, C37.118 NONE
UTCOFFOffset From UTC to Local Time
Range = -15.5 to 15.5 -8.0
BEG_DST Begin DST
Select: "0,1,2,3,4,5,6,7,8,9,10,11,12,13,14,15,16,17,18,19,20,21,22,23", "1,2,3,L", "1,2,3,4,5,6,7", "1,2,3,4,5,6,7,8,9,10,11,12"
2, 2, 1, 3
END_DST End DST
Select: "0,1,2,3,4,5,6,7,8,9,10,11,12,13,14,15,16,17,18,19,20,21,22,23", "1,2,3,L", "1,2,3,4,5,6,7", "1,2,3,4,5,6,7,8,9,10,11,12"
2, 1, 1, 11
RST_DEMCondition(s) for Resetting of Demand Metering Data Equation
Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG
NA
Condition(s) for Resetting of Valid range = The legal
Page 2 of 9
19-03-2015file:///C:/Users/pbanerjee/AppData/Roaming/SEL/AcSELerator/QuickSet/Session_00...
RST_PDMPeak Demand Metering Data Equation
operators: AND OR NOT R_TRIG F_TRIG
NA
RST_ENECondition(s) for Resetting of Energy Metering Data Equation
Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG
NA
RSTTRGTCondition(s) for Resetting of Target LEDs Equation
Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG
NA
RSTDNPECondition(s) for Resetting of DNP Fault Summary Data Equation
Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG
TRGTR
RST_HALCondition(s) for Resetting of Warning Alarm Pulsing Equation
Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG
NA
EVELOCK Event Summary Lock Period Range = 0 to 1000 0
DNPSRC DNP Session Time Base Select: LOCAL, UTC UTC
Global Top
Page 3 of 9
19-03-2015file:///C:/Users/pbanerjee/AppData/Roaming/SEL/AcSELerator/QuickSet/Session_00...
Group 1 Top
Setting Description Range Value
ECTTERM Enable the Following Current TerminalsSelect: Combination of S, T, U, W, X or OFF
S, T
EPTTERM Enable the Following Voltage TerminalsSelect: Combination of V, Z or OFF
V
E87Include the Following Terminals in the Differential Element
Select: Combination of S, T or OFF
S, T
EREFEnable the Following Number of Restricted Earth Fault Elements
Select: N, 1-3 1
E50Enable Definite Time Overcurrent Elements for the Following Terminals
Select: Combination of S, T or OFF
S, T
E51Enable the Following Number of Inverse Time Overcurrent Elements
Select: N, 1-10 4
E46Enable Current Unbalance Elements for the Following Terminals
Select: Combination of S, T or OFF
OFF
E59 Enable the Following Number of Overvoltage Elements Select: N, 1-5 N
E27 Enable the Following Number of Undervoltage Elements Select: N, 1-5 N
E81Enable the Following Number of Over/Under Frequency Elements
Select: N, 1-6 N
E24 Enable Volts per Hertz Protection Select: N, Y Y
EBFLEnable Breaker Failure Protection for the Following Terminals
Select: Combination of S, T or OFF
T
EPCALEnable Active, Reactive and Apparent Power Calculations for the Following Terminals
Select: Combination of S, T or OFF
OFF
EDEMSelect the Number of Demand Metering Elements Required
Select: N, 1-10 N
PTRV Potential Transformer Ratio for Terminal V Range = 1.0 to 10000.0 2000.0
PTCONV Potential Transformer Connection For Terminal V Select: Y, D Y
PTCOMPVPotential Transformer Compensation Angle for Terminal V
Range = -179.99 to 180.00 0.00
VNOMVPotential Transformer Nominal Line-to-Line Voltage For Terminal V
Range = 30 to 300 110
CTRS Current Transformer Ratio For Terminal S Range = 1 to 50000 400
CTCONS Current Transformer Connection For Terminal S Select: Y, D Y
CTRT Current Transformer Ratio For Terminal T Range = 1 to 50000 2400
CTCONT Current Transformer Connection For Terminal T Select: Y, D Y
CTRY1 Current Transformer Ratio for Terminal Y, Channel 1 Range = 1 to 50000 100
VREFS Select Voltage Reference for Terminal S Select: OFF, V V
VREFT Select Voltage Reference for Terminal T Select: OFF, V OFF
ICOM Internal CT Connection Matrix Compensation Enabled Select: Y, N Y
MVA Enter Transformer Maximum MVA Rating Range = 1 to 5000, OFF 120
E87TSInclude Terminal S in the Differential Element for the Following Conditions
Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG
1
TSCTC Terminal S CT Connection Compensation Range = 0 to 12 12
VTERMS Terminal S Line-to-Line Voltage Range = 1.00 to 1000.00 380.00
E87TTInclude Terminal T in the Differential Element for the Following Conditions
Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG
1
Page 4 of 9
19-03-2015file:///C:/Users/pbanerjee/AppData/Roaming/SEL/AcSELerator/QuickSet/Session_00...
TTCTC Terminal T CT Connection Compensation Range = 0 to 12 12
VTERMT Terminal T Line-to-Line Voltage Range = 1.00 to 1000.00 33.00
O87P Differential Element Operating Current Pickup Range = 0.10 to 4.00 0.25
SLP1 Slope 1 Setting Range = 5.00 to 90.00 33.00
SLP2 Slope 2 Setting Range = 5.00 to 90.00 90.00
U87P Unrestrained Element Current Pickup Range = 1.00 to 20.00 8.00
DIOPR Incremental Operate Current Pickup Range = 0.10 to 10.00 1.20
DIRTR Incremental Restraint Current Pickup Range = 0.10 to 10.00 1.20
E87HB Enable Harmonic Blocking Differential Element Select: Y, N Y
E87HR Enable Harmonic Restraint Differential Element Select: Y, N Y
PCT2 Second-Harmonic Percentage (% of fundamental) Range = 5 to 100, OFF 15
PCT4 Fourth-Harmonic Percentage (% of fundamental) Range = 5 to 100, OFF 15
PCT5 Fifth-Harmonic Percentage (% of fundamental) Range = 5 to 100, OFF 50
TH5P Fifth-Harmonic Alarm Threshold Range = 0.2 to 3.2, OFF OFF
87QPNegative Sequence Differential Element Operating Current Pickup
Range = 0.05 to 1.00 0.30
SLPQ1 Negative Sequence Differential Slope Range = 5 to 100 25
87QD Negative Sequence Differential Element Delay Range = 2.000 to 9999.000 10.000
REFRF1 Select the Restraint Quantity for REF Element 1Select: Combination of S, T or OFF
OFF
REF50P1REF (50P) Operate Current Instantaneous Overcurrent 1 Pickup
Range = 0.05 to 20.00, OFF OFF
REF51P1REF (51P) Operate Current Inverse Time Overcurrent Element 1 Pickup
Range = 0.05 to 3.20, OFF 0.05
REF51C1 REF Inverse Time Overcurrent Element 1 Curve Select: U1-U5, C1-C5 C4
RF51TD1REF Inverse Time Overcurrent Element 1 Time Dial Setting
Range = 0.05 to 1.00 0.15
RF51RS1REF Inverse Time Overcurrent Element 1 Electromechanical Reset
Select: Y, N Y
RF51TC1REF Inverse Time Overcurrent Element 1 Torque Control Equation
Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG
1
E50S Enable the Type of Overcurrent Elements for Terminal SSelect: Combination of P, Q, G
P, G
E67S Enable Directional Elements Select: Y, N N
50SP1P Phase Instantaneous Overcurrent Pickup Level 1 Range = 0.05 to 20.00, OFF 8.00
67SP1TC Phase Instantaneous Overcurrent Level 1 Torque ControlValid range = The legal operators: AND OR NOT R_TRIG F_TRIG
SF32P AND PLT03
67SP1D Phase Instantaneous Overcurrent Level 1 Delay Range = 0.00 to 16000.00 3.00
50SG1P Zero-Seq Inst O/C Pickup Level 1 Range = 0.05 to 20.00, OFF OFF
50SP2P Phase Instantaneous Overcurrent Pickup Level 2 Range = 0.05 to 20.00, OFF OFF
E50T Enable the Type of Overcurrent Elements for Terminal TSelect: Combination of P, Q, G
P, G
50TP1P Phase Instantaneous Overcurrent Pickup Level 1 Range = 0.05 to 20.00, OFF 9.00
67TP1TC Phase Instantaneous Overcurrent Level 1 Torque ControlValid range = The legal operators: AND OR NOT R_TRIG F_TRIG
TF32P AND PLT03
67TP1D Phase Instantaneous Overcurrent Level 1 Delay Range = 0.00 to 16000.00 3.00
50TG1P Zero-Seq Inst O/C Pickup Level 1 Range = 0.05 to 20.00, OFF OFF
50TP2P Phase Instantaneous Overcurrent Pickup Level 2 Range = 0.05 to 20.00, OFF OFF
EXBFT Enabling Condition(s) for External Breaker FailureValid range = The legal operators: AND OR NOT
NA
Page 5 of 9
19-03-2015file:///C:/Users/pbanerjee/AppData/Roaming/SEL/AcSELerator/QuickSet/Session_00...
R_TRIG F_TRIG
EBFPUT External Breaker Failure Initiate Pickup Delay Range = 0.000 to 6000.000 6.000
50FPUT Fault Current Pickup Range = 0.10 to 10.00 9.00
BFPUT Breaker Failure Initiate Pickup Delay Range = 0.000 to 6000.000 12.000
RTPUT Retrip Delay Range = 0.000 to 6000.000 6000.000
BFIT Breaker Fail Initiate Condition(s)Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG
NA
ATBFIT Alternate Breaker Fail Initiate Condition(s)Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG
NA
ENINBFT Enabling Condition(s) for Neutral Breaker FailureValid range = The legal operators: AND OR NOT R_TRIG F_TRIG
NA
INFPUT Neutral Current Pickup Range = 0.10 to 10.00 0.10
EBFIST Breaker Failure Initiate Seal-In Select: Y, N N
BFIDOT Breaker Failure Initiate Dropout Delay Range = 0.000 to 1000.000 1.500
51O01 Inverse Time Overcurrent Element 01 Operate Quantity
Select: 3I0TM, 3I2TM, I1TM, IATFM, IATRMS, IBTFM, IBTRMS, ICTFM, ICTRMS, IMAXTF, IMAXTR, 3I0SM, 3I2SM, I1SM, IASFM, IASRMS, IBSFM, IBSRMS, ICSFM, ICSR ...
IMAXSF
51P01 Inverse Time Overcurrent Element 01 Pickup ValueValid range = The legal operators: AND OR NOT R_TRIG F_TRIG
0.6
51C01 Inverse Time Overcurrent Element 01 Curve Selection Select: U1-U5, C1-C5 C1
51TD01 Inverse Time Overcurrent Element 01 Time DialValid range = The legal operators: AND OR NOT R_TRIG F_TRIG
0.20
51RS01Inverse Time Overcurrent Element 01 Electromechanical Reset Enable
Select: Y, N Y
51TC01 Inverse Time Overcurrent Element 01 Torque ControlValid range = The legal operators: AND OR NOT R_TRIG F_TRIG
PLT09
51O02 Inverse Time Overcurrent Element 02 Operate Quantity
Select: 3I0TM, 3I2TM, I1TM, IATFM, IATRMS, IBTFM, IBTRMS, ICTFM, ICTRMS, IMAXTF, IMAXTR, 3I0SM, 3I2SM, I1SM, IASFM, IASRMS, IBSFM, IBSRMS, ICSFM, ICSR ...
IMAXTF
51P02 Inverse Time Overcurrent Element 02 Pickup ValueValid range = The legal operators: AND OR NOT R_TRIG F_TRIG
1.1
51C02 Inverse Time Overcurrent Element 02 Curve Selection Select: U1-U5, C1-C5 C1
51TD02 Inverse Time Overcurrent Element 02 Time DialValid range = The legal operators: AND OR NOT R_TRIG F_TRIG
0.20
51RS02Inverse Time Overcurrent Element 02 Electromechanical Reset Enable
Select: Y, N Y
51TC02 Inverse Time Overcurrent Element 02 Torque ControlValid range = The legal operators: AND OR NOT R_TRIG F_TRIG
PLT09
Select: 3I0TM, 3I2TM,
Page 6 of 9
19-03-2015file:///C:/Users/pbanerjee/AppData/Roaming/SEL/AcSELerator/QuickSet/Session_00...
51O03 Inverse Time Overcurrent Element 03 Operate Quantity
I1TM, IATFM, IATRMS, IBTFM, IBTRMS, ICTFM, ICTRMS, IMAXTF, IMAXTR, 3I0SM, 3I2SM, I1SM, IASFM, IASRMS, IBSFM, IBSRMS, ICSFM, ICSR ...
3I0SM
51P03 Inverse Time Overcurrent Element 03 Pickup ValueValid range = The legal operators: AND OR NOT R_TRIG F_TRIG
0.6
51C03 Inverse Time Overcurrent Element 03 Curve Selection Select: U1-U5, C1-C5 C1
51TD03 Inverse Time Overcurrent Element 03 Time DialValid range = The legal operators: AND OR NOT R_TRIG F_TRIG
0.15
51RS03Inverse Time Overcurrent Element 03 Electromechanical Reset Enable
Select: Y, N Y
51TC03 Inverse Time Overcurrent Element 03 Torque ControlValid range = The legal operators: AND OR NOT R_TRIG F_TRIG
PLT09
51O04 Inverse Time Overcurrent Element 04 Operate Quantity
Select: 3I0TM, 3I2TM, I1TM, IATFM, IATRMS, IBTFM, IBTRMS, ICTFM, ICTRMS, IMAXTF, IMAXTR, 3I0SM, 3I2SM, I1SM, IASFM, IASRMS, IBSFM, IBSRMS, ICSFM, ICSR ...
3I0TM
51P04 Inverse Time Overcurrent Element 04 Pickup ValueValid range = The legal operators: AND OR NOT R_TRIG F_TRIG
0.1
51C04 Inverse Time Overcurrent Element 04 Curve Selection Select: U1-U5, C1-C5 C1
51TD04 Inverse Time Overcurrent Element 04 Time DialValid range = The legal operators: AND OR NOT R_TRIG F_TRIG
0.20
51RS04Inverse Time Overcurrent Element 04 Electromechanical Reset Enable
Select: Y, N Y
51TC04 Inverse Time Overcurrent Element 04 Torque ControlValid range = The legal operators: AND OR NOT R_TRIG F_TRIG
PLT09
TRXFMR Trip Condition(s) for Transformer TerminalsValid range = The legal operators: AND OR NOT R_TRIG F_TRIG
87R OR REFF1
ULTXFMR Unlatch Trip Condition(s) for Transformer TerminalsValid range = The legal operators: AND OR NOT R_TRIG F_TRIG
TRGTR
TRS Trip Condition(s) for Terminal SValid range = The legal operators: AND OR NOT R_TRIG F_TRIG
50SP1 OR 50SQ1
ULTRS Unlatch Trip Condition(s) for Terminal SValid range = The legal operators: AND OR NOT R_TRIG F_TRIG
TRGTR
CLS Close Condition(s) for Terminal SValid range = The legal operators: AND OR NOT R_TRIG F_TRIG
LB10
ULCLS Unlatch Close Condition(s) for Terminal SValid range = The legal operators: AND OR NOT R_TRIG F_TRIG
52CLS
TRT Trip Condition(s) for Terminal TValid range = The legal operators: AND OR NOT R_TRIG F_TRIG
50TP1 OR 50TQ1
Page 7 of 9
19-03-2015file:///C:/Users/pbanerjee/AppData/Roaming/SEL/AcSELerator/QuickSet/Session_00...
ULTRT Unlatch Trip Condition(s) for Terminal TValid range = The legal operators: AND OR NOT R_TRIG F_TRIG
TRGTR
CLT Close Condition(s) for Terminal TValid range = The legal operators: AND OR NOT R_TRIG F_TRIG
LB10
ULCLT Unlatch Close Condition(s) for Terminal TValid range = The legal operators: AND OR NOT R_TRIG F_TRIG
52CLT
TDURD Minimum Trip Duration Range = 2.000 to 8000.000 5.000
ER Condition(s) for Triggering Event ReportsValid range = The legal operators: AND OR NOT R_TRIG F_TRIG
50SQ1 OR 50TQ1
FAULT Condition(s) for Asserting Fault BitValid range = The legal operators: AND OR NOT R_TRIG F_TRIG
50SQ1 OR 50TQ1
CFD Close Failure DelayRange = 2.000 to 99999.000, OFF
4.000
24VSRC Voltage Source for V/Hz Calculation Select: V, Z V
24D1P Level 1 Volts/Hertz Pickup (%) Range = 100 to 200 110
24D1D Level 1 Time Delay Range = 0.04 to 6000.00 10.00
24TC Torque Control for Volts/Hertz ElementValid range = The legal operators: AND OR NOT R_TRIG F_TRIG
1
24CCS Select Level 2 Composite Curve Select: OFF, DD, U1, U2 U1
24U1TC Torque Control for Curve 1Valid range = The legal operators: AND OR NOT R_TRIG F_TRIG
1
24U1NP Select the Number of Points for Curve 1 Range = 3 to 20 7
24U1CR Curve 1 Reset Time (seconds) Range = 0.01 to 400.00 400.00
24U111 Curve 1, Point 01 Range = 100 to 200 110
24U121 Curve 1, Point 01 Range = 0.04 to 6000.00 6000.00
24U112 Curve 1, Point 02 Range = 100 to 200 115
24U122 Curve 1, Point 02 Range = 0.04 to 6000.00 240.00
24U113 Curve 1, Point 03 Range = 100 to 200 120
24U123 Curve 1, Point 03 Range = 0.04 to 6000.00 60.00
24U114 Curve 1, Point 04 Range = 100 to 200 125
24U124 Curve 1, Point 04 Range = 0.04 to 6000.00 30.00
24U115 Curve 1, Point 05 Range = 100 to 200 130
24U125 Curve 1, Point 05 Range = 0.04 to 6000.00 19.00
24U116 Curve 1, Point 06 Range = 100 to 200 135
24U126 Curve 1, Point 06 Range = 0.04 to 6000.00 13.00
24U117 Curve 1, Point 07 Range = 100 to 200 140
24U127 Curve 1, Point 07 Range = 0.04 to 6000.00 10.00
Group 1
Top
Page 8 of 9
19-03-2015file:///C:/Users/pbanerjee/AppData/Roaming/SEL/AcSELerator/QuickSet/Session_00...
Page 9 of 9
19-03-2015file:///C:/Users/pbanerjee/AppData/Roaming/SEL/AcSELerator/QuickSet/Session_00...