Upload
m-ahmed-latif
View
218
Download
0
Embed Size (px)
Citation preview
8/12/2019 80.Volume Controls
1/19
Insdustrial Hydraulics
Manual
Chapter X
Volume Controls
8/12/2019 80.Volume Controls
2/19
Contents
1.Flow control methods
2.Type of flow controls
3.Questions
8/12/2019 80.Volume Controls
3/19
Introduction
Volume or flow control valves are used to regulate speed. As
was developed in earlier chapters, the speed of an actuator depends
on how much oil is pumped into it per unit of time. It is possible toregulate flow with a variable displacement pump, but in many
circuits it is more practical to use a fixed displacement pump and
regulate flow with a volume control valve.
8/12/2019 80.Volume Controls
4/19
I. Flow Control Methods
There are three basic methods of applying volume control valves
to control actuator speeds. They are meter-in, meter-out and bleed-off.
Meter-In Circuit
Meter-in operation, the flow control valve is placed between the pump
and actuator (Fig. 10-1). In this way, it controls the amount of fluid
going into the actuator. Pump delivery in excess of the metered amount is
diverted to tank over the relief valve.With the flow control valve installed in the cylinder line as shown,
flow is controlled in one direction. A check valve must be included
in the flow control or placed in parallel with it for return flow. If
it is desired to control speed in both directions, the flow control canbe installed in the pump outlet line prior to the directional valve.
The meter-in method is highly accurate. It is used in applications
where the load continually resists movement of the actuator, such as
raising a vertical cylinder under load or pushing a load at acontrolled speed.
8/12/2019 80.Volume Controls
5/19
I. Flow Control Methods
8/12/2019 80.Volume Controls
6/19
I. Flow Control Methods
Meter-Out Circuit
Meter-out control (Fig. 10-2) is used where the load might tend to "runaway. " The flow control is located where it will restrict exhaust flow from
the actuator.To regulate speed in both directions,the valve is installed in the tank line
from the directional valve. More often control is needed in only onedirection and it is placed in the line between the actuator and directionalvalve. Here too a bypass check valve would be required for a rapidreturn stroke.
Bleed-Off Circuit
In a bleed-off arrangement (Fig. 10-3), the flow control is teed off thesupply line from the pump and determines the actuator speed by meteringa portion of the pump delivery to tank. The advantage is that the pumpoperates at the pressure required by the work, since excess fluid returns to
tank through the flow control instead of through the relief valve.Its disadvantage is some loss of accuracy because the measured flow is to
tank rather than into the cylinder, making the latter subject to variations inthe pump delivery due to changing work loads.
Bleed-off circuits should not be used in applications where there is apossibility of the load running away.
8/12/2019 80.Volume Controls
7/19
I. Flow Control Methods
8/12/2019 80.Volume Controls
8/19
I. Flow Control Methods
8/12/2019 80.Volume Controls
9/19
II. Type of flow controls
Flow control valves fall into two basic categories: pressure
compensated and non-pressure compensated. The latter being used
where load pressures remain relatively constant and feed rates are nottoo critical. They may be as simple as a fixed orifice or an adjustable
needle valve, although more sophisticated units may even include a
check valve (Fig. 10-4) for free flow in the reverse direction. Use
of non-pressure compensated valves is somewhat limited, since
flow through an orifice is essentially proportional to the square root
of the pressure drop ( P) across it. This means that any
appreciable change in the work load would affect the feed rate.
Pressure compensated flow controls are further classified as
restrictor and by-pass types. Both utilize a compensator or
hydrostatic to maintain a constant pressure drop across an adjustable
throttle.
8/12/2019 80.Volume Controls
10/19
II. Type of flow controls
8/12/2019 80.Volume Controls
11/19
II. Type of flow controls
The By-Pass Type - combines overload protection with pressure
compensated control of flow (Fig. 10-5). It has a normally closed
hydrostat which opens to divert fluid, in excess of the throttle setting, to thetank. Pressure required by the work load is sensed in the chamber above
the hydrostat and together with a light spring tends to hold it closed.
Pressure in the chamber below the hydrostat increases due to the
restriction of the throttle and causes it to raise diverting any excess flow
to tank when the difference in pressure is sufficient to overcome the spring.This difference, usually 20 psi, is maintained across the throttle providing a
constant flow regardless of the work load. Some horsepower saving is
accomplished in that the pump need operate at only 20 psi above work load
pressure. Overload protection is provided by an adjustable spring loaded
poppet which limits the maximum pressure above the hydrostat, causing it to
function as a compound relief valve whenever work load requirements
exceed its setting. The bypass flow control can only be used in a meter-in
circuit. If used for metering out, exhaust oil which could not get through the
throttle would be diverted to tank permitting the load to run away.
8/12/2019 80.Volume Controls
12/19
II. Type of flow controls
8/12/2019 80.Volume Controls
13/19
II. Type of flow controls
The Restrictor Type Flow Control - also maintains a constant 20psi differential across its throttle by means of a hydrostat (Fig. 10-
6). In this valve, the hydrostat is normally open and tends to closeoff blocking all flow in excess of the throttle setting. In these units,the work load pressure acts with a light spring above the hydrostatto hold it open. Pressure at the throttle inlet and under thehydrostat tends to close it, permitting only that oil to enter the
valve that 20 psi can force through the throttle. Because of theirtendency to close off when flow tries to exceed the throttle setting,restrictor type valves may be used in meter-in, meter-out and bleed-off circuits. Unlike the by-pass type, two or more restrictor valvesmay be used with the same pump since the excess pump delivery
returns to tank through the relief valve.When placed in cylinder lines an integral check valve is optional
to provide free flow for a rapid return stroke (Fig. 10-7). Onewould not be required for valves placed in the main supply line, thetank line of a directional valve or when they are used in bleed-off
circuits.
8/12/2019 80.Volume Controls
14/19
II. Type of flow controls
8/12/2019 80.Volume Controls
15/19
II. Type of flow controls
8/12/2019 80.Volume Controls
16/19
II. Type of flow controls
Temperature Compensated Flow Control Valve
Flow through a pressure compensated flow control valve is subject to
change with variations in oil temperature. Later design Vickers valvesincorporate a temperature compensating feature.
Although oil flows more freely when it is hot, constant flow can be
maintained by decreasing the size of the throttle opening as the
temperature rises. This is accomplished through a compensating rod which
lengthens with heat and contracts when cold (Fig. 10-8). The throttle is asimple plunger that is moved in and out of the control port. The
compensating rod is installed between the throttle and its adjuster. This
design also is available with a reverse free-flow check valve.
Remote Flow Control ValvesRemote flow control valves (Fig. 10-9) permit adjustment of the throttle
size by an electrical signal. The throttle spool is linked to the armature of a
torque motor and moves in response to signals to the torque motor. Operation is
otherwise the same as a pressure compensated flow control valve.
8/12/2019 80.Volume Controls
17/19
II. Type of flow controls
8/12/2019 80.Volume Controls
18/19
8/12/2019 80.Volume Controls
19/19
III. Questions
1. Name two ways of regulating flow to an actuator.
2. What are the three methods of applying flow control valves?
3. Under what conditions would you use each?
4. How can the same valve control flow in both directions of
actuator movement?
5. What is the difference between a bypass and restrictor type flow
control?
6. What is pressure compensation?
7. How is temperature compensation indicated in a valve symbol?
8. When might temperature compensation be needed?
9. What is the advantage of the flow control and relief valve
over a conventional flow control?
10. How is the throttle positioned in a remote flow control valve?