4
8 - CHANNEL SCANNER ISOTHERM · Upto 8 inputs / 4 relays / 2 isolated 4~20 mA outputs · Universal input : 8 thermocouples, Pt100, mV or mA input front panel selection without DIP reconfiguring for each channel · RS485 with MODBUS RTU · 3 key, 5 level programming · Tactile membrane keypad · 85~265 V AC SMPS · Powerful, flexible SCADA software available CAT#275R6/P1/4/310316/A 8 CHANNELS, 4 RELAYS, 2 x 4-20mA OUT, RS485 www.radix.co.in BASIC Note : Setpoint 1 corresponds to channel 1, etc. Example No. of inputs : 8 No. of setpoints : 4 No. of relays : 4 No. of current output : 2 SP1 RLY1 CH1 SP2 RLY2 CH2 SP3 RLY3 CH3 SP4 RLY4 CH4 Channels Relays Setpoints Current output 8 4 4 2 Maximum No. Fig 2 INDICATOR Note : No alarms / relays Example No. of inputs : 8 No. of setpoints : None No. of relays : None No. of current output : 2 CH1 CH2 CH8 Channels Relays Setpoints Current output 8 0 0 2 Maximum No. Fig 1 TABLE 1 : SOFTWARE VERSIONS VERSION NO. VERSION NAME DESCRIPTION Indicator Basic No alarms/relays Setpoint 1 corresponds to channel 1, setpoint 2 to channel 2, etc. 30.XX 30.XX REFERENCE Fig2 Fig1 TABLE 2 SENSOR / INPUT LOW SCALE HIGH SCALE Pt - 6% Rh / Pt - 30% RH (B) Chromel / Constantan (E) Iron / Constantan (J) Chromel / Alumel (K) Nicrosil / Nisil (N) Pt / Pt - 13% Rh (R) Pt / Pt - 10% Rh (S) Copper / Constantan (T) Pt100, 3-wire Linear (0~50 mV, 0~20 mA, 4~20 mA) 400 -270 -210 -270 -270 0 0 -270 -200 -19999 1820 1000 760 1372 1300 1760 1760 400 850 19999 RANGE LIMIT (°C / EU) LOW SCALE HIGH SCALE 400 -270 -210 -270 -270 0 0 -270 -200 -19999 1820 1000 760 1372 1300 1760 1760 400 850 19999 RANGE IN WHICH ACCURACY IS SPECIFIED TYPICAL ACCURACY AT 30 °C (°C / EU) ± 3 ± 1 ± 1 ± 1 ± 1 ± 2 ± 2 ± 1 ± 0.5 ± 10 EU WORST CASE ACCURACY (°C / EU) ± 5 ± 3 ± 3 ± 3 ± 3 ± 5 ± 5 ± 3 ± 1.0 ± 50 EU

8 - CHANNEL SCANNER ISOTHERM - Radix

  • Upload
    others

  • View
    7

  • Download
    0

Embed Size (px)

Citation preview

Page 1: 8 - CHANNEL SCANNER ISOTHERM - Radix

8 - CHANNEL SCANNER ISOTHERM

· Upto 8 inputs / 4 relays / 2 isolated 4~20 mA outputs

· Universal input : 8 thermocouples, Pt100, mV or mA input front panel selection without DIP reconfiguring for each channel

· RS485 with MODBUS RTU

· 3 key, 5 level programming

· Tactile membrane keypad

· 85~265 V AC SMPS

· Powerful, flexible SCADA software available

CA

T#275R

6/P

1/4

/310316/A

8 CHANNELS, 4 RELAYS, 2 x 4-20mA OUT, RS485

www.radix.co.in

BASIC

Note : Setpoint 1 corresponds to channel 1, etc.

Example

• No. of inputs : 8

• No. of setpoints : 4

• No. of relays : 4

• No. of current output : 2

SP1

RLY1

CH1

SP2

RLY2

CH2

SP3

RLY3

CH3

SP4

RLY4

CH4

Channels

Relays

Setpoints

Current output

8

4

4

2

Maximum No.

Fig 2

INDICATOR

Note : No alarms / relays

Example

• No. of inputs : 8

• No. of setpoints : None

• No. of relays : None

• No. of current output : 2

CH1

CH2

CH8

Channels

Relays

Setpoints

Current output

8

0

0

2

Maximum No.

Fig 1

TABLE 1 : SOFTWARE VERSIONS

VERSION NO. VERSION NAME DESCRIPTION

Indicator

Basic

No alarms/relays

Setpoint 1 corresponds to channel 1, setpoint 2 to channel 2, etc.

30.XX

30.XX

REFERENCE

Fig2

Fig1

TABLE 2

SENSOR / INPUTLOW SCALE HIGH SCALE

Pt - 6% Rh / Pt - 30% RH (B)

Chromel / Constantan (E)

Iron / Constantan (J)

Chromel / Alumel (K)

Nicrosil / Nisil (N)

Pt / Pt - 13% Rh (R)

Pt / Pt - 10% Rh (S)

Copper / Constantan (T)

Pt100, 3-wire

Linear (0~50 mV, 0~20 mA, 4~20 mA)

400

-270

-210

-270

-270

0

0

-270

-200

-19999

1820

1000

760

1372

1300

1760

1760

400

850

19999

RANGE LIMIT(°C / EU)

LOW SCALE HIGH SCALE

400

-270

-210

-270

-270

0

0

-270

-200

-19999

1820

1000

760

1372

1300

1760

1760

400

850

19999

RANGE IN WHICHACCURACY IS SPECIFIED

TYPICAL ACCURACYAT 30 °C(°C / EU)

± 3

± 1

± 1

± 1

± 1

± 2

± 2

± 1

± 0.5

± 10 EU

WORST CASEACCURACY

(°C / EU)

± 5

± 3

± 3

± 3

± 3

± 5

± 5

± 3

± 1.0

± 50 EU

Page 2: 8 - CHANNEL SCANNER ISOTHERM - Radix

8 - CHANNEL SCANNER ISOTHERM

CA

T#275

R6/P

2/4

/310316/A

8 CHANNELS, 4 RELAYS, 2 x 4-20mA OUT, RS485

Fig 3

ON OFF

HEAT COOL

SP HYST

SP HYST

SP HYST

SP HYST

HIGH ALARM LOW ALARM

� �

SPX*

HYST

SPX*

HYST

SP1

SPX*

HYST

SPX* HYST

SP1

* SPX = SP2/SP3/SP4

INBAND OUTBANDDEV HI

SP = SP1 + SPX *DEV LO

SP = SP1 - SPX *

SP HYSTSP

HYST

CONTROL FUNCTIONS

CONTROL Control functions (Fig 3) ONOFF control Heat or Cool or Cool with compressor time delay Alarm functions High alarm Low alarm Deviation high alarm Deviation low alarm Inband alarm Outband alarm Control action Direct / reverse

Hysteresis 0.1 - 99.9 °C / °F / EU

Compressor ON time delay 1 - 200 secAlarm type Autoreset, Latch, Hold, Latch+Hold Latch (Ltch) Once relay gets ON, it remains 'ON' until alarm is acknowledged by key� Hold Alarm is disabled at power ON After process variable reaches normal (non alarm) value, the alarm is enabled Ltch.Hold Combination of Latch & Hold logic Alarm Activation delay 0.0 ~ 99.9 sec

COMMUNICATION Port RS485, isolatedBaud rate User programmable, 4800 bps, 9600 bps, 19200 bps, 38400 bpsProtocol Modbus RTUSlave ID User programmable, 1~255Date type Swapped float Integer x10Minimum polling interval 250 millisecondsParameters Process variables Read only Setpoints Read & write from the host computer Alarm status Read only Relay status Read only

SOFTWARE VERSIONS See Table 1

INPUTSNo. of inputs 8Input types Thermocouple B, E, J, K, N, R, S, T RTD Pt100, 3-wire Linear input 0~50 mV, 0~20 mA, 4~20 mA (each input independently scaleable) Lead-wire resistance error (Pt100, thermocouple) <0.2 °C for 10 ohms / leadChannel scan rate < 0.8 seconds for 8 channelsChannel-to-channel isolation Suitable for low (leakage) voltages less than 3V ACInput protection Thermocouple, mV, RTD inputs ± 10 V DC max Current inputs Current limit < 30 mA, 28 V DC maxRange limits See Table 2Accuracy See Table 2 Cold junction compensation Automatic Sensor break protection User programmable

INDICATION Display type 0.56” (14.2 mm), 7 - segment LED Process variable Upper, 4 ½ digit : redSetpoint Middle, 4 ½ digit : greenChannel no. Lower, 1 digit : redStatus indication 8 red LEDs for alarm, 4 green LEDs for relay status 2 red LEDs for communication

OUTPUTSNo. of relays Indicator : None Other : 4 electromagnetic relays Maximum no. of outputs (Y) 4 Output type a) Electromagnetic relay b) SSR driveRelay contact type NO-C-NC Relay contact rating 5A / 230V AC, resistive Current output 4~20 mA / 0~20 mA, isolated from input and supply ORVoltage output 0-1 V / 0-10 V / user specifiedMaximum load for current 500 ohms output

ISOLATIONMutual isolation between 1KV AC RMS/1 minute, input/supply/curent output(s)/ 250 V AC RMS continuous RS485 port

SPECIFICATIONS All specifications at ambient of 25 °C, unless specified otherwise

www.radix.co.in

Page 3: 8 - CHANNEL SCANNER ISOTHERM - Radix

CALIBRATIONZero & span Through front panel keys & displayUser calibration Sensor span and sensor zeroCJC calibration Room temperature

OTHERKeypad Membrane, tactile, 3 keysMemory for programmed Non-volatile, indefinite duration parametersField Connections Screw type connections in plug-in terminalsPlug-in Terminal Type a) Standard (Brass nickel plated) b) Gold platedSupply voltage 85~265 V AC, 50/60 hz Power consumption 5 wattsDimensions (in mm) 96 (H) x 96 (W) x 220 (D) Mounting In panel cutout of 90x90 mm Operating ambient temperature 0 - 50 °CRelative humidity� � Below 90%, non condensing

PROGRAMMABLE PARAMETERSSetpoint Full range adjustableAlarm Full range adjustableUnit User programmableResolution User programmable 0.0001,0.001,0.01, 0.1or 1 for linear input, 0.1 or 1 for temperature

OTHER MAJOR PARAMETERS Setpoint lock Level lockDisplay scan rate 1~99 seconds/channelSKIP channel Enable / disableInput bias -99.9 ~ 99.9Power ON output activation 0.0 ~ 99.9 sec delay

SPECIFICATIONS All specifications at ambient of 25 °C, unless specified otherwise

8 - CHANNEL SCANNER ISOTHERM

8 CHANNELS, 4 RELAYS, 2 x 4-20mA OUT, RS485

CA

T#275R

6/P

3/4

/310316/A

ORDERING INFORMATION

OTHER PRODUCTS

MULTI-CHANNEL SCANNER · FLP ISOSCAN MULTI-CHANNEL SCANNER · ISOSCAN-H

MULTI-CHANNEL SCANNER · ISOSCAN-V

www.radix.co.in

Option

1 x Analog output1.

2.

3.

2 x Analog output

1 x Analog output + RS485

Details

1 x 4~20 mA

2 x 4~20 mA

1 x 4~20 mA + RS485

Configuration

01

02

03

00

Software version No. of channels (X) No. of relays (Y) RS485

Indicator 8 0 1

Basic

Basic

8

8

4

4

0

1

Indicator 8 0 0

A

A2206

ORDER CODE

Ordering Options The following ordering options are available on request.Minimum order quantity and/or minimum order value may apply.

Page 4: 8 - CHANNEL SCANNER ISOTHERM - Radix

8 - CHANNEL SCANNER ISOTHERM

8 CHANNELS, 4 RELAYS, 2 x 4-20mA OUT, RS485

CA

T#2

75R

6/P

4/4

/310316/A

· Flexible trend facility - current and historical

· Alarm function

· Allows read (acquire data) & write

(program setpoint, etc) operations

· Supports thousands of tags

· Supports upto 32 or more instruments

· Capable of storing data upto 10 years

· Compatible with a variety of Radix instruments such as Scanner,

PID & ONOFF controllers, Isolators

· Default screen selection

· 21CFR compliant version also available

ELIPSE SCADA With Ethernet

Ethernet Bus

RS485 Bus

RS232 Bus

rSCADA

rSCADA server

rSCADA

rSCADA

rSCADA clients

INSTRUMENTS

ISOTHERM ISOTHERM ISOTHERM

ISOTHERM ISOTHERM ISOTHERM

ISOTHERM ISOTHERM ISOTHERM

ISOTHERM ISOTHERM ISOTHERM

rSCADA

rSCADA

ISOTHERM ISOTHERM ISOTHERM

C:\Historical data files\Demo.dat

Radix Electrosystems Pvt Ltd

USER: Administrator

PAGE1

DATA HISTORY REPORT

Date Time PV1 PV2 PV3 PV4 PV5 PV6 PV7 PV8

24-Nov-09 14:10:00 50.5 314.4 320.2 321.1 26.7 48.6 333.2 311.5

24-Nov-09 14:25:00 50.4 314.3 320.1 321.1 26.7 48.6 333.1 311.3

24-Nov-09 14:40:00 50.5 314.3 320.2 321.1 26.5 48.5 333.1 311.4

24-Nov-09 14:55:00 50.5 314.4 320.2 321.1 26.6 48.6 333.2 311.5

24-Nov-09 15:10:00 50.5 314.4 320.1 321.1 26.5 48.6 333.1 311.4

24-Nov-09 15:25:00 50.5 314.3 320.2 321.1 26.6 48.6 333.2 311.5

START DATE & TIME: 24-Nov-09-14:10:00 STOP DATE & TIME: 24-Nov-09-15:25:33 SAMPLE INTERVAL: 900

ISO1:_GRP1

REMARK:

CHECKED BY:

MIN: 50.4 314.3 320.1 321.1 26.5 48.5 333.1 311.3

MAX: 50.5 314.4 320.2 321.1 26.7 48.6 333.2 311.5

SUMMARY: -------------- -------------- -------------- -------------- -------------- -------------- -------------- --------------

www.radix.co.inRadix Electrosystems Pvt Ltd, B-14, 2nd Floor, Ghanshyam Indl Estate, Veera Desai Road, Andheri (West), Mumbai - 400 053, IndiaTel : + 91 22 42537777 · Fax : + 91 22 42537700 · Email : [email protected] · www.radix.co.in

AN ISO 9001:2008 COMPANY

INSTRUMENTS T : + 91 22 42537777 x 701 F : + 91 22 42537700 E : [email protected]

SENSORS T : + 91 22 42537777 x 732 F : + 91 22 42537700 E : [email protected]

GAUGES T : + 91 22 42537777 x 733 F : + 91 22 42537700 E : [email protected]

AUTOMATION C : 0-9322405471 C : 09324319150 E : [email protected]