8 c Stribling

Embed Size (px)

Citation preview

  • 7/27/2019 8 c Stribling

    1/17

    A critical review of the energy savings and

    cost payback issues of double facades

    David StriblingBuro Happold Glasgow

    Byron StiggeBuro Happold New York

    Summary

    This paper presents a dynamic thermal modelling study to show estimated energy savings and

    projected payback periods for various double faade construction systems in different climates and

    orientations. It concludes that although the economic case for a double faade based purely on energy

    cost savings may be marginal, many other factors must be considered. Climate, construction type,

    construction cost, and energy cost significantly contribute to the feasibility of each unique case and

    must be assessed for each building.

    Introduction

    Double facades are an effective means of buffering and controlling heat, light, air and noise through a

    building envelope. They do, however, have a premium cost associated with them compared to

    conventional facade systems. Justification of their inclusion in a building design, therefore is typically

    on the basis of energy efficiency and associated cost savings. Qualitative benefits of solar control,

    moderated surface temperatures, noise reduction, reduced glare, reduced heating/cooling demand,

    moderated access to fresh air, aesthetic purity and increased daylighting are generally seen only as

    intangible bonus benefits.

    The principle of a double skin faade is an additional layer of glass offset from the conventional

    curtain wall forming an interstitial space that acts as a thermal buffer. Blinds are typically incorporated

    into the void space to prevent solar heat gains from entering the occupied space. Blinds may be

    automatically or manually operated. On the outer surface of glazing, operable vents are located top and

    bottom to prevent the void from overheating in the summer. In the winter the vents are generally

    closed to trap heat in the void and reduce heat loss through the interior windows. In the mid-season

  • 7/27/2019 8 c Stribling

    2/17

    condition, the inner curtain wall normally has

    operable windows for natural ventilation. An

    additional benefit is that modulating outer vents

    can be used to control the void temperature and

    thus extend the period suitable for natural

    ventilation.

    Despite this sophistication, detailed energy

    savings analyses rarely conclude double skin

    facades have affordable paybacks at todays

    relatively low energy prices although there is no

    doubt that they do provide better overall energy

    efficiency. The aim of this paper is to

    investigate which scenarios may approach

    affordable payback periods and to what extent

    these are influenced by different factorsFigure 1 Typical double faade components

    To this end, dynamic thermal modelling (DTM) has been applied to the problem using the TAS

    software from EDSL (1). DTM techniques employ a three dimensional virtual model of the building

    and calculate the time based thermal loads on a building based on its fabric, solar shading and

    historical weather data. It has been used previously in the application of double faade analysis and

    validated against detailed CFD analysis in this respect (2).

    Faade Construction Costs

    A double skinned faade is a significant capital investment and an estimate of construction cost is

    necessary in order to make a calculation as to the likely payback period. There are wide variations

    depending on the level of sophistication of the faade, location, construction method and contractors

    experience. Many suppliers give ranges because of these factors but the figures assumed for the Las

    Vegas, USA analysis have been 300/m2($50/ft

    2) for a conventional curtain wall faade with low-e

    glass and 800/m2($130/ft2) for a simple, flat, double faade with operable vents, blinds and windows

    for a large building and manufactured in a factory. These figures are estimates rather than quotes and

    are based on experience and conversations with suppliers for the mid west US. As an example of

  • 7/27/2019 8 c Stribling

    3/17

    regional variations, the same faade installed in New York might cost 50% more, in the UK 40% more

    and in Germany 20% more.

    Orientation

    A basic office building model was

    simulated with the intent of isolating the

    annual HVAC energy savings of a double

    faade over a conventional faade for

    various orientations. In order to do this a

    model of a four-storey office block was

    created with solid walls on three sides. The

    fourth side was a fully glazed faade which

    was rotated through 8 different orientations

    with annual energy consumption calculated

    for each and for three different climates. Figures 2, 3 and 4 summarise the model geometry whilst the

    other modelling assumptions are detailed in Appendix A. London was selected as a mild, cloudy

    climate (Figures 5 and 6). Las Vegas was selected as a hot, dry sunny climate (Figures 7 and 8). And

    Winnipeg, Canada was selected as a cold climate (Figures 9 and 10).

    Figure 2 - Plan diagram of simulation model

    investigating effect of orientation on

    energy savings of double facade

    It should be noted that these results are not representative of actual office energy consumption figures

    due to the simplistic nature of the model. The results are intended purely as a comparison between the

    energy savings associated with each orientation for one design of double facade.

    Figure 3 - Section diagram of simulation

    model for baseline office

    building without a double

    facade

    Figure 4 - Section diagram of simulation

    model for office building with a

    double facade

  • 7/27/2019 8 c Stribling

    4/17

    0

    30

    60

    90

    120

    DF

    Base

    DF

    Base

    DF

    Base

    DF

    Base

    DF

    Base

    DF

    Base

    DF

    Base

    DF

    Base

    N NE E SE S SW W NW

    EnergyConsumption

    (kWh/m2)

    Heating Fans

    Cooling Pumps

    Figure 5 LONDON: Energy consumption intensity results for 8 orientations for conventional

    faade (Base) and double faade (DF)

    0%

    10%

    20%

    30%

    N NE E SE S SW W NW N

    Orientation

    HVACEnergySavin

    gs

    Percentage cost saving

    Percentage energy saving

    Figure 6 LONDON: Percentage energy savings through faade for different orientations

    For London, the most significant savings in HVAC energy consumption are achieved with SW and S

    facades and are in the order of 23%. This is because the void captures solar gain in the winter

    providing an insulating layer and rejects solar gain in the summer. Other orientations have less solar

    gain and thus heat up less in the winter and block less solar gain in the summer. Nevertheless, even

    the N faade shows 14% savings in energy consumption due to a greatly increased overall U-value.

  • 7/27/2019 8 c Stribling

    5/17

    0

    50

    100

    150

    200

    DF

    Base

    DF

    Base

    DF

    Base

    DF

    Base

    DF

    Base

    DF

    Base

    DF

    Base

    DF

    Base

    N NE E SE S SW W NW

    EnergyConsumption

    (kWh/m2)

    Heating FansCooling Pumps

    Figure 7 LAS VEGAS: Energy consumption intensity results for 8 orientations for

    conventional faade (Base) and double faade (DF)

    0%

    10%

    20%

    30%

    N NE E SE S SW W NW N

    Orientation

    HVACEner

    gySavings

    Percentage cost saving

    Percentage energy saving

    Figure 8 LAS VEGAS: Percentage energy savings through faade for different orientations

    Las Vegas sees more energy savings from a double faade (in the region of 27%) because it is a sunny,

    hot climate and double facades do well to reduce cooling loads from solar gain.

  • 7/27/2019 8 c Stribling

    6/17

    Figure 9 WINNIPEG: Energy consumption intensity results for 8 orientations for conventional

    faade (Base) and double faade (DF)

    Cooling Pumps

    0

    100

    200

    300

    DF

    Base

    DF

    Base

    DF

    Base

    DF

    Base

    DF

    Base

    DF

    Base

    DF

    Base

    DF

    Base

    N NE E SE S SW W NW

    EnergyConsumption

    (kWh/m2)

    Heating Fans

    0%

    10%

    20%

    30%

    N NE E SE S SW W NW N

    Orientation

    HVACEnergySavings

    Percentage cost saving

    Percentage energy saving

    Figure 10 WINNIPEG: Percentage energy savings through faade for different orientations

    Winnipeg shows higher annual energy consumption than both London and Las Vegas with

    predominantly a heating load due to the cold climate. Energy savings shown are best on the South

    Eastern side and are quite modest at 12%. This suggests one or a combination of two things. That the

    design of faade selected in this analysis works more efficiently in a warm climate with high cooling

    load than it does in a cold climate and/or the fact that because solar heat gains are low in this climate,

    that the low-e faade is already more efficient than it is in Las Vegas or London.

  • 7/27/2019 8 c Stribling

    7/17

    Optimal Climate

    In order to determine what types of climate achieve the

    best energy savings through the use of double facades

    another model was simulated which was more

    representative of a typical office building. Using a

    South-West orientation, which was generally accepted as

    offering the most benefit from a double faade in the

    previous analysis, the building was simulated through 7

    cities in different climate zones throughout the world.

    The model geometry is summarised in figures 11, 12 &

    13.

    Figure 11:Plan diagram of simulation

    model investigating energysavings of double faade in

    various climates

    Figure 13:Section diagram ofsimulation model for

    office building with a

    Figure 12:Section diagram of simulationmodel for baseline office building

    without a double facade

  • 7/27/2019 8 c Stribling

    8/17

    0

    50

    100

    150

    200

    250

    300

    LE DF LE DF LE DF LE DF LE DF LE DF LE DF

    En

    ergyConsumption(kWh/m2)

    Fans

    Heating Cooling Pumps

    Winnipeg

    Munich

    New York MiamiLas Vegas

    Rome

    London

    Figure 14 Energy consumption comparison for a conventional faade (LE) and a double faade

    (DF) for different locations and climates

    The results of the analysis are shown in Figure 14 with an indication of the predicted energy

    consumption for the double faade versus a conventional double glazed faade for different global

    locations. Those generally with the greater energy consumption show the most potential for savings. It

    should also be noted that the same faade design has been used in all locations when in fact there may

    well be a different design for a warm climate as opposed to a cooler climate.

    Payback Calculation

    Although double facades are meant to save energy and hence be more environmentally friendly, it is

    energy cost savings and payback period that building owners are typically most interested to know.

    For this calculation it was necessary to make assumptions on the prices of gas and electricity for each

    of the locations considered. The figures used in the analysis are given in table 1.

    The simple payback calculations in this paper are based on HVAC energy saving cost savings

    assuming the same type of air conditioning system for the typical and double faade.

  • 7/27/2019 8 c Stribling

    9/17

    Table 1 Energy prices assumed in payback analysis

    Electricity Gas

    (/kWh) ($/kWh) (/kWh) ($/kWh) Off Peak Rate

    United Kingdom 0.07 $0.105 0.025 $0.037Electricity0.04/kWh

    12am and 7am

    USA (Nevada) 0.04 $0.06 0.013 $0.02

    USA (New York) 0.133 $0.20 0.047 $0.07

    USA (Florida) 0.053 $0.08 0.017 $0.028

    Canada 0.038 $0.055 0.012 $0.018

    Italy 0.085 $0.13 0.028 $0.042

    Germany 0.09 $0.14 0.03 $0.045

    Table 2 summarises the energy cost payback for the 7 cities modeled and shows that the ultimate

    feasibility is largely dependent on energy price. The more expensive energy locations such as New

    York, Rome and Munich show the best paybacks with the lower energy prices of Canada extending

    the payback period significantly. London shows a longer payback period partly due to a lower energy

    price, partly due to a less extreme climate and partly due to more expensive construction costs

    Table 2 Comparison of payback periods for double facades in different locations

    London Las Vegas Winnipeg New York Miami Rome Munich

    Faade area 1,040m2 1,040m2 1,040m2 1,040m2 1,040m2 1,040m2 1,040m2

    Add. faadecost

    700/m2 500/m2 500/m2 800/m2 600/m2 650/m2 600/m2

    Add. capitalinvestment

    728k 520k 520k 832k 624k 676k 624k

    Energy costsaving

    1.01/m2 1.31/m2 0.83/m2 2.57/m2 1.17/m2 2.18/m2 1.88/m2

    Floor area 3,000m2 3,000m2 3,000m2 3,000m2 3,000m2 3,000m2 3,000m2

    Annual costsaving

    3,030 3,930 2,490 7,710 3,510 6,540 5,640

    Payback

    period

    240 Yrs 132 Yrs 208 Yrs 108 Yrs 177 Yrs 103 Yrs 111 Yrs

  • 7/27/2019 8 c Stribling

    10/17

    From the results in table 2 one conclusion that applies to all locations is HVAC running costs are very

    low compared to the capital cost of the double facade. With an expected building life of 50 to 70 years

    these projected paybacks would make double facades seem to be a financially poor decision. There are

    three things that control this, the cost of construction, the energy savings, and the energy price. The

    first two of these can be considered in the design and although the third is largely a factor of market

    forces. In the following section an analysis is carried out for double faades located in Las Vegas and

    London taking these factors into consideration.

    Optimal Faade Design & Cost

    Previous analysis has shown that the projected payback period for the considered design in Las Vegas

    is of the order of 132 years. Through simulation however, the baseline double faade design has been

    optimised to achieve 95 years. This has been achieved through optimizing the solar shading properties

    and control of the blinds and the temperature setpoints of the automatically opening vents and

    windows. The next challenge, therefore, is to reduce the construction cost of the faade and

    functionality to optimise the trade-off between energy savings and construction cost.

    Additional features such as BMS controlled vents, BMS controlled blinds, daylight dimming, BMS

    controlled operable windows, shut-off dampers to air supply when windows are open, low-iron glass

    and an occupiable (wider) void all contribute to energy savings. But all of these features contribute to

    additional construction cost, as demonstrated in figures 15 & 16. For a given climate and orientation a

    different set of these functionalities will produce an optimal payback period. This principle is

    demonstrated in theory by figure 17.

    Figure 15: Capital investment for a double

    facade per faade area vs.

    functionality features of faade

    Figure 16: % HVAC Energy Savings

    for a double facade vs.

    functionality features of

    faade

  • 7/27/2019 8 c Stribling

    11/17

    Figure 17: Payback for a double facades vs.

    functionality features of faade

    Five models with various double faade systems were run for Las Vegas to demonstrate this theory.

    Model description and capital cost assumptions are summarised in table 3.

    Table 3 Summary of simulations to investigate effect of faade design

    Model Description Additional capital costover typical faade

    1 Fully controllable faade optimised to give 95 year payback 600/m2 $90/ft2

    2 Model 1, but changing motorized vents to permanently open vents 500/m2 $75/ft2

    3Model 2, but changing blinds to static tilted blinds with solartransmittance = 0.6

    400/m2 $60/ft

    2

    4Model 3, but changing operable windows on internal faade tofixed, closed windows

    350/m2 $53/ft2

    5

    Model 4, but a full height, four storey double faade with inlet onlyat the bottom of the first floor and outlet only at the top of thefourth floor

    300/m2 $45/ft2

  • 7/27/2019 8 c Stribling

    12/17

    0.00

    1.00

    2.00

    3.00

    300 400 500 600

    Additional Investment (/m2 - facade)

    Energy

    Cos

    tS

    av

    ing

    (/m2-

    floor)

    0

    50

    100

    150

    200

    Simp

    lePay

    bac

    kPerio

    d

    (Years)

    Energy cost saving

    Payback

    Figure 18: HVAC Energy Cost Savings and payback

    period for a double facade with different

    features

    The results of the analysis are shown in figure 18. Here, the characteristic U shape described in

    figure 17 is apparent. At the lower point of the U shape, the payback period does, in fact, reach an

    optimum at an additional investment of 500/m2($75/ft2) over a conventional double glazed low-e

    curtain wall system, achieving an 86 year payback. Note this is purely an analytical analysis for the

    given assumptions for Las Vegas. The optimal model had permanently open vents, which is

    reasonable for such a hot climate, but would not be reasonable for a cold climate where closing thevents is very important.

    Energy Cost Influences Payback

    Energy costs influence payback as seen clearly back in table 2. But energy costs vary greatly across

    the world and with time making it a moving target, so it is important to look at historic price trends

    and future price predictions for perspective on payback calculations. Simple payback calculations

    done with todays energy price will not be accurate for very long.

  • 7/27/2019 8 c Stribling

    13/17

    $0.00

    $0.05

    $0.10

    $0.15

    $0.20

    $0.25

    $0.30

    1967 1977 1987 1997 2007 2017 2027 2037

    EnergyPrice($/kW

    h) Ave. Electric ity Price (in 1996$)

    Ave. Gas Price (in 1996$)

    Weighted Energy Price (82% elec,18% gas)

    20 yr payback

    40 yr payback

    60 yr payback

    Figure 19: Energy cost for Nevada 1960-2001 (in constant

    1996 dollars) compared to threshold values for

    target payback periods.

    For the optimum Las Vegas design (calculated above to have an 86 year payback at todays energy

    prices) the energy split is 12% gas, 88% electricity due to the predominance of cooling in this climate.

    A weighted average energy price for the model building has therefore been calculated and plotted on

    the graph in figure 19 together with threshold prices that would achieve 20, 40 and 60 year simple

    paybacks. This analysis shows that the historic gas and electricity prices for Las Vegas, Nevada (4) in

    constant 1996 dollars would provide between 50 and 90 year simple paybacks.

    If energy prices reach $0.27/kWh (0.40/kWh) for electricity and $0.09/kWh (0.135/kWh,

    $2.60/therm) for gas the payback would be 20 years. These energy prices are close to that of New

    York City today.

  • 7/27/2019 8 c Stribling

    14/17

    In a similar exercise, the faade design for London was optimised through simulation to give an 90

    year payback at todays prices of 0.07/kWh ($0.105/kWh) for electricity and 0.025/kWh

    ($0.04/kWh) for gas. The energy split for the modelled building in London is 59% gas, 41% electricity

    resulting in a weighted, current energy price of 0.044/kWh ($0.066/kWh). Figure 20 shows the trend

    of the energy price for the UK normalised to real 1995 prices (5) together with the thresholds for 20,40

    & 60 year paybacks.

    0.00

    0.05

    0.10

    0.15

    0.20

    0.25

    1970 1980 1990 2000 2010 2020 2030

    EnergyPrice(/kWh) Ave. Electricity Price (in 1995)

    Ave. Gas Price (in 1995)

    Weighted Energy Price (41% elec, 59% gas)

    40 yr payback

    20 yr payback

    60 yr payback

    Figure 20: Energy cost for UK 1970-2001 (in constant

    1995 sterling) compared to threshold values

    for target payback periods.

    The graph shows a similar trend to the US with higher energy prices in the early eighties making the

    case for double facades more feasible. During this period, the projected payback approached 40 years.

  • 7/27/2019 8 c Stribling

    15/17

    Other Important Influences on Cost Payback

    Due to the space restrictions of this paper, other very important influences on total life-cycle payback

    of double facades cannot be fully elaborated on, but are listed below and expanded on in many

    references on double facades (3)(6). Many are soft issues which improve worker productivity, by far

    the largest portion of an office buildings life-cycle cost. Little quantifiable research has been done

    on these topics and this is an area in great need for future research.

    Additional Maintenance Costs 4 window surfaces to clean instead of 2, motor replacement, louvre

    maintenance, etc.

    Reduced Mechanical Plant Capital Costs peak load reductions allow smaller chillers, boilers, air

    handlers, ducts, or even different HVAC systems altogether.

    Glare Control operable blinds block direct solar glare and accept diffuse light

    Moderated Glass Surface Temperatures blinds block direct solar rays from striking the inner glass

    preventing it from heating to upwards of 60C (140F). In the winter, the warm void heats the

    inner glass reducing drafts and cold radiant exchange.

    Operable Windows in High-Rise Buildings the void buffers wind pressures which otherwise make

    operable windows very gusty and disruptive in tall buildings.

    Acoustical Buffering the vents and void dampen noise improving acoustics near noisy roads,

    airports, factories or rail lines.

    Increased Daylighting operable blinds actively bounce light deeper into occupied space. Improved

    U-value allows larger windows.

    Reduced Emissions greenhouse gases, SOx, NOx and other particulates are reduced as energy

    consumption is reduced.

    Aesthetic Purity the exterior rain-screen requires no thermal breaks, structural mullions or spandrel

    glass providing a visually simple faade. Blocked UV, wind and rain allow a wood framed

    interior curtain wall. External blinds provide shading, so clear glass is acceptable.

    Conclusions

    An extensive analytical investigation has been carried out into the cost versus payback benefits of

    double skin facades with respect to their energy saving potential. From this work the following

    conclusions can be drawn.

    A double faade offers the most energy saving potential on the south and south-west orientations.

  • 7/27/2019 8 c Stribling

    16/17

    Extreme climates offer more opportunity for energy savings as they require more HVAC energy

    and thus have greater potential for savings through improved building envelope.

    Energy savings can range from 10% to 50% of HVAC energy, and cost payback can range from

    30 to 200 years based on todays local energy prices. Double Facades must be assessed

    specifically on their individual merit considering climate, orientation, detailing, construction cost

    and energy price.

    The economic viability of double faades in a location is not only a result of the climate.

    Construction costs and energy price play an even more significant role in the results as there is a

    large global variation.

    Energy prices will also vary greatly over the life of the building and this should also be

    considered. Although todays climate of low energy prices prohibit significant energy cost

    savings, one might consider designing todays building for tomorrows energy prices.

    The additional benefits of double facades have not been fully explored in this paper an at present

    many of these are unquantified. Considering their importance in making a financial case for

    double facades, further research is recommended in this area.

    References

    1 Tas Software Manual, EDSL (Environmental Design Solutions Ltd, UK), 1998

    2 F. Wang, M. Davies, B. Cunliffe, P. Heath, The design of double skin faade: modellingstudy on some design parameters affecting indoor thermal conditions, CIBSE NationalConference, 1999

    3 Oesterle, Lieb, Lutz, Heusler, Double-Skin Facades: Integrated Planning, Prestel, Munich,2001

    4 Energy Information Administration, EIA, Web Page:http://www.eia.doe.gov/neic/historic/historic.htm

    5 Department of Trade and Industry "UK Energy Sector Indicators 2001", Web Page:http://www.dti.gov.uk/energy/inform/energy_indicators/2001/

    6 D. Arons Properties and Applications of Double-Skin Building Facades, MSc Thesis,Massachusetts Institute of Technology, June 2000

    http://www.eia.doe.gov/neic/historic/historic.htmhttp://www.dti.gov.uk/energy/inform/energy_indicators/2001/http://www.dti.gov.uk/energy/inform/energy_indicators/2001/http://www.eia.doe.gov/neic/historic/historic.htm
  • 7/27/2019 8 c Stribling

    17/17

    Appendix A Modelling Assumptions

    Orientation Model

    This model was 10m (30ft) deep and 50m (150ft) wide, four stories tall with solid walls and no

    glazing on three faces. On the fourth face, the faade was applied as described below.

    The baseline building has 70% glazing on facade side (U-value = 1.8 W/m2K, R-3).

    The double faade building had a double faade on the glazed side with a 1m (3ft) wide void,

    motorized blinds with total solar transmittance of 0.6, operable lower and upper vents 300mm (1ft)

    high which are open in the summer months when the void temperature reaches 24C (75F), clear

    10mm single glazing on the outer facade, and insulated low-e inner glass (U-value = 1.8 W/m2K, R-3)

    on the inner facade. The double faade model had operable windows and are open for natural

    ventilation when the void is between 16-22C (61-72F).

    Internal Heat Gains

    Occupancy - 10W/m2(sensible), 6W/m2(latent) between 8am to 6pm, 7 days per week

    Lighting 15W/m2

    Equipment 8W/m2

    Plant switched on 8am to 6pm heating 20C, cooling to 24C

    Night setback heated to 18C in winter

    Optimal Climate Model

    This model was 15m (45ft) deep and 50m (150ft) wide, four stories tall at the optimal orientation of

    SW. The baseline building has 40% glazing on all four sides (U-value = 1.8 W/m2K, R-3) which does

    not have operable windows. The double faade building has a double faade on the southwest and

    southeast facades. The double faade has a 1m (3ft) wide void, motorized blinds, motorized vents at

    500mm width inlet and outlet (0.5ft2/ft), clear single glazed outer glass, and insulated low-e inner glass

    (U-value = 1.8 W/m2K, R-3) and operable windows. All internal heat gains and plant times were the

    same as described above for the orientation model.