Page 1 of 79 This Modbus list is valid for LCS6000.3.2.0 7960-791 is valid for LCS6000.1.1.0 7960-791A is valid for LCS6000.2.000 through LCS6000.2.1.0 7960-791B is valid for LCS6000.3.000 through LCS6000.3.1.0 The LC6000 is capable of being remotely monitored through the integrated Ethernet port. Through this port the controller will respond to Modbus commands allowing access to setpoints, alarms, temperature measurements and humidity measurements for each zone. The controller has the following connection settings: Protocol: Modbus TCP/IP Address: 1 Timeout: 3000 ms IP Address: 192.168.0.14 Subnet: 255.255.255.0 The IP settings are defaulted to the values listed above; however, in general for remote monitoring of these values the IP settings will have to be adjusted to match the shelter network settings. To change the IP settings of the LC6000: 1. Press MENU key to go to the Main Menu screen. 2. Use UP or DOWN keys and ENTER key to enter USER password 1313. 3. Press UP or DOWN keys to scroll to Settings; press ENTER key. 4. Press UP or DOWN keys to scroll to Network Config; press ENTER key. Bard Manufacturing Company, Inc. Bryan, Ohio 43506 www.bardhvac.com Manual: 7960-791D Supersedes: 7960-791C Date: 2-10-20 Modbus Supplemental Manual for LC6000 Controller SUPPLEMENTAL INSTRUCTIONS 5. Press ENTER key to scroll down the screen (see Figure 1). Press the UP or DOWN keys to change the value of each parameter to match the setting required for the network the LC will be added to. 6. Once settings have been entered, change Update Config? from No to Yes to save the settings. Figure 1 The units of the values retrieved during communication are determined by the controller unit of measure setting. This is configured onsite and cannot be changed remotely. The values on the Modbus list are in degrees Fahrenheit. When the unit of measure is changed by the user, the temperature values in the Modbus will change to degrees Celsius. For more information about how to use each of these values, please refer to the latest version of the 2100-669 LC6000 Service Instructions manual.

7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Page 1: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Page 1 of 79

This Modbus list is valid for LCS6000.3.2.0

7960-791 is valid for LCS6000.1.1.0

7960-791A is valid for LCS6000.2.000 through LCS6000.2.1.0

7960-791B is valid for LCS6000.3.000 through LCS6000.3.1.0

The LC6000 is capable of being remotely monitored through the integrated Ethernet port. Through this port the controller will respond to Modbus commands allowing access to setpoints, alarms, temperature measurements and humidity measurements for each zone.

The controller has the following connection settings:

Protocol: Modbus TCP/IP

Address: 1

Timeout: 3000 ms

IP Address: 192.168.0.14

Subnet: 255.255.255.0

The IP settings are defaulted to the values listed above; however, in general for remote monitoring of these values the IP settings will have to be adjusted to match the shelter network settings.

To change the IP settings of the LC6000:

1. Press MENU key to go to the Main Menu screen.

2. Use UP or DOWN keys and ENTER key to enter USER password 1313.

3. Press UP or DOWN keys to scroll to Settings; press ENTER key.

4. Press UP or DOWN keys to scroll to Network Config; press ENTER key.

Bard Manufacturing Company, Inc. Bryan, Ohio 43506

www.bardhvac.com

Manual: 7960-791DSupersedes: 7960-791CDate: 2-10-20

Modbus Supplemental Manual for LC6000 Controller

SUPPLEMENTAL INSTRUCTIONS

5. Press ENTER key to scroll down the screen (see Figure 1). Press the UP or DOWN keys to change the value of each parameter to match the setting required for the network the LC will be added to.

6. Once settings have been entered, change Update Config? from No to Yes to save the settings.

Figure 1

The units of the values retrieved during communication are determined by the controller unit of measure setting. This is configured onsite and cannot be changed remotely.

The values on the Modbus list are in degrees Fahrenheit. When the unit of measure is changed by the user, the temperature values in the Modbus will change to degrees Celsius.

For more information about how to use each of these values, please refer to the latest version of the 2100-669 LC6000 Service Instructions manual.

Page 2: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 2 of 79

Unit Status Message

Unit Status Message ID MULTI-TEC

FUSION-TEC

MEGA-TEC

Orphan Mode 1 X X X

th_Tune_Online 2 X - -

LC Online 3 X X X

N/A 4 - - -

Continuous Blower 5 X X X

Off by th_Tune 6 X - -

Power Loss Mode 7 - X -

Inverter Mode 8 - X -

Freecooling 9 X X X

Optimized Mode 10 X X X

Cooling 11 X X X

Heating 12 X X X

Active Dehum 13 X X X

Self Test 14 X X X

PT Online 15 X X X

Off by Alarm 16 X X X

Off by BMS 17 - X -

Off by Time Band 18 - X -

Off by Digital Input 19 - X -

Off by LC 20 X X X

N/A 21 - - -

Off by Keypad 22 X X X

Manual Mode 23 - X -

Emergency Vent 24 X X X

Emergency Cool 25 X X X

Emergency Off 26 X X X

Passive Dehum 27 X X X

Standalone Mode 28 - - X

Model Invalid 29 X X X

Off by Standalone Display

30 - - X

Comfort Mode 31 - - X

Unit of Measure BMS

ID

NC 0

SI 1

USA 2

UK 3

CANADA 4

LON 5

Continuous Blower

ID

No Units 0

Lead Unit 1

All Units 2

Custom 3

Rotation Type

ID

FIFO 0

LIFO 1

Demand 2

Dehum Type

ID

None 0

Electric Reheat 1

Mechanical Reheat 2

Cyclic Reheat 3

Humidity Setup

ID

None 0

Z1 & Z2 1

Z1, Z2 & Z3 2

Humidity Type

ID

Relay 0

Comm 1

Page 3: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 3 of 79

LC6000 Unit of Measure

ID

NC 0

SI 1

USA 2

UK 3

CANADA 4

LON 5

Unit Type

ID

None 0

MULTI-TEC 2

MEGA-TEC 4

WR 5

Compressor Status

ID

Compressor Off 0

Compressor Start-Up 1

Compressor On or at 25% 2

Compressor at 50% 3

Compressor at 75% 4

Compressor at 100% 5

Compressor Forced Off 6

Compressor Limited to 25% 7

Compressor Limited to 50% 8

Compressor Limited to 75% 9

Compressor Off by Alarm 10

Compressor Off by Time 11

Compressor On by Time 12

Manual Mode 13

Compressor On by Pump-Down 14

Page 4: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 4 of 79

Modbus Register List – LC6000

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

Coil 0 R Off/On = 0/1 0-1 Turns LC On/Off from the BMS X

DiscreteInput 0 R Off/On = 0/1 0-1 Generator Running Alarm Active X

HoldingRegister 0 R/W 0,1,2,3,4,5 0-5 Sets Units of BMS variables X

InputRegister 0 R ### 1-14 Number of units configured X

DiscreteInput 1 R Off/On = 0/1 0-1 Emergency Off Input X

InputRegister 1 R 0,1,2,3 0-3 Configured zones for humidification X

DiscreteInput 2 R Off/On = 0/1 0-1 Generator Run Input X

InputRegister 2 R Off/On = 0/10=Relay 1=Comm

Humidification Control Type X

DiscreteInput 3 R Off/On = 0/1 0-1 Emergency Vent Input X

InputRegister 3 R 0,1,2,3,4,5 0-5Sets the Unit Of Measure for the LC6000 User Interface

X

DiscreteInput 4 R Off/On = 0/1 0-1 LC Outdoor Air Temperature Sensor Failure X

DiscreteInput 5 R Off/On = 0/1 0-1 LC Outdoor Air Humidity Sensor Failure X

DiscreteInput 6 R Off/On = 0/1 0-1 LC Bard Guard Alarm X

DiscreteInput 7 R Off/On = 0/1 0-1 Unit 1 Offline X

DiscreteInput 8 R Off/On = 0/1 0-1 Unit 2 Offline X

DiscreteInput 9 R Off/On = 0/1 0-1 Unit 3 Offline X

DiscreteInput 10 R Off/On = 0/1 0-1 Unit 4 Offline X

DiscreteInput 11 R Off/On = 0/1 0-1 Unit 5 Offline X

DiscreteInput 12 R Off/On = 0/1 0-1 Unit 6 Offline X

DiscreteInput 13 R Off/On = 0/1 0-1 Unit 7 Offline X

DiscreteInput 14 R Off/On = 0/1 0-1 Unit 8 Offline X

DiscreteInput 15 R Off/On = 0/1 0-1 Unit 9 Offline X

DiscreteInput 16 R Off/On = 0/1 0-1 Unit 10 Offline X

DiscreteInput 17 R Off/On = 0/1 0-1 Unit 11 Offline X

DiscreteInput 18 R Off/On = 0/1 0-1 Unit 12 Offline X

DiscreteInput 19 R Off/On = 0/1 0-1 Unit 13 Offline X

DiscreteInput 20 R Off/On = 0/1 0-1 Unit 14 Offline X

DiscreteInput 21 R Off/On = 0/1 0-1 Unit 15 Offline X

DiscreteInput 22 R Off/On = 0/1 0-1 Unit 16 Offline X

DiscreteInput 23 R Off/On = 0/1 0-1 Unit 17 Offline X

DiscreteInput 24 R Off/On = 0/1 0-1 Unit 18 Offline X

DiscreteInput 25 R Off/On = 0/1 0-1 Unit 19 Offline X

DiscreteInput 26 R Off/On = 0/1 0-1 Unit 20 Offline X

DiscreteInput 27 R Off/On = 0/1 0-1 Unit 21 Offline X

DiscreteInput 28 R Off/On = 0/1 0-1 Unit 22 Offline X

DiscreteInput 29 R Off/On = 0/1 0-1 Unit 23 Offline X

DiscreteInput 30 R Off/On = 0/1 0-1 Unit 24 Offline X

DiscreteInput 100 R Off/On = 0/1 0-1Zone 1 Emergency Off Input Active (prev:Zone 1 Smoke Alarm Active)

X

HoldingRegister 100 R/W ###.# NA Zone 1 Cooling temperature setpoint X

InputRegister 100 R ###.#0-100%

RHZone 1 Indoor Humidity Measurement X

DiscreteInput 101 R Off/On = 0/1 0-1Zone 1 Emergency Vent Input Active (prev:Zone 1 Hydrogen Alarm Active)

X

HoldingRegister 101 R/W ###.# NA Zone 1 Heating temperature setpoint X

InputRegister 101 R ###.# NA Zone 1 Indoor Temperature Measurement X

DiscreteInput 102 R Off/On = 0/1 0-1 Zone 1 Temperature Sensor Alarm X

Page 5: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 5 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

HoldingRegister 102 R/W ###.#0%/45%

RHZone 1 Humidification Setpoint X

InputRegister 102 R ###.# NA Remote Zone1 Air Switch X

DiscreteInput 103 R Off/On = 0/1 0-1 Zone 1 Remote Temp. Sensor Alarm X

HoldingRegister 103 R/W ###.#46%/99%

RHZone 1 Dehumidification Setpoint X

DiscreteInput 104 R Off/On = 0/1 0-1 Zone 1 Humidity Sensor Alarm X

HoldingRegister 104 R/W ###.#36 Deg.

F/66 Deg. F

Zone 1 Low Temperature setpoint X

DiscreteInput 105 R Off/On = 0/1 0-1 Zone 1 Indoor Temp Low Limit Alarm X

HoldingRegister 105 R/W ###.#70°F

/120°FZone 1 High Temperature Warning Setpoint X

DiscreteInput 106 R Off/On = 0/1 0-1 Zone 1 Indoor Temp High Limit Warning X

HoldingRegister 106 R/W ###.#70°F

/120°FZone 1 High Temperature Alarm Setpoint X

DiscreteInput 107 R Off/On = 0/1 0-1 Zone 1 Indoor Temp High Limit Alarm X

HoldingRegister 107 R/W ###.#0/100%

RHZone 1 Low Humidity Alarm Setpoint X

DiscreteInput 108 R Off/On = 0/1 0-1 Zone 1 Humidity Low Limit Alarm X

HoldingRegister 108 R/W ###.#0/100%

RHZone 1 High Humidity Alarm Setpoint X

DiscreteInput 109 R Off/On = 0/1 0-1 Zone 1 Humidity High Limit Alarm X

HoldingRegister 109 R/W 0,1,2,3 0-3Zone 1 Determines Continuous blower settings for zone

X

DiscreteInput 110 R Off/On = 0/1 0-1 No Temperature Sensor Present in Zone 1 X

HoldingRegister 110 R/W 0,1,2 0-2 Zone 1 Determines rotation setting for zone X

HoldingRegister 111 R/W 0,1,2,3 0-3Zone 1 Determines method for dehumidification for zone

X

HoldingRegister 112 R/W ###.#46%/99%

RHZone 1 Humidity level required to start passive dehumidification

X

HoldingRegister 113 R/W ###.#46%/99%

RHZone 1 Humidity level required to start active dehumidification

X

HoldingRegister 114 R/W ###.# 1-14 Zone 1 Staging Free Cooling delay on X

HoldingRegister 115 R/W ###.# 1-14 Zone 1 Staging Free Cooling delay off X

HoldingRegister 116 R/W ###.# 1-14 Zone 1 Staging Cooling delay on X

HoldingRegister 117 R/W ###.# 1-14 Zone 1 Staging Cooling delay off X

HoldingRegister 118 R/W ###.# 1-14 Zone 1 Staging Heating delay on X

HoldingRegister 119 R/W ###.# 1-14 Zone 1 Staging Heating delay off X

DiscreteInput 200 R Off/On = 0/1 0-1Zone 2 Emergency Off Input Active (prev:Zone 2 Smoke Alarm Active)

X

HoldingRegister 200 R/W ###.# 1-14 Zone 2 Cooling temperature setpoint X

InputRegister 200 R ###.#0-100%

RHZone 2 Indoor Humidity Measurement X

DiscreteInput 201 R Off/On = 0/1 0-1Zone 2 Emergency Vent Input Active (prev:Zone 2 Hydrogen Alarm Active)

X

HoldingRegister 201 R/W ###.# NA Zone 2 Heating temperature setpoint X

InputRegister 201 R ###.# NA Remote Zone2 Air Switch X

DiscreteInput 202 R Off/On = 0/1 0-1 Zone 2 Temperature Sensor Alarm X

HoldingRegister 202 R/W ###.#0%/45%

RHZone 2 Humidification Setpoint X

HoldingRegister 203 R/W ###.#46%/99%

RHZone 2 Dehumidification Setpoint X

DiscreteInput 204 R Off/On = 0/1 0-1 Zone 2 Humidity Sensor Alarm X

Page 6: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 6 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

HoldingRegister 204 R/W ###.#36

Deg.F/66 Deg. F

Zone 2 Low Temperature setpoint X

DiscreteInput 205 R Off/On = 0/1 0-1 Zone 2 Indoor TempLow Limit Alarm X

HoldingRegister 205 R/W ###.#70°F

/120°FZone 2 High Temperature Warning Setpoint X

DiscreteInput 206 R Off/On = 0/1 0-1 Zone 2 Indoor Temp High Limit Warning X

HoldingRegister 206 R/W ###.#70°F

/120°FZone 2 High Temperature Alarm Setpoint X

DiscreteInput 207 R Off/On = 0/1 0-1 Zone 2 Indoor Temp High Limit Alarm X

HoldingRegister 207 R/W ###.#0/100%

RHZone 2 Low Humidity Alarm Setpoint X

DiscreteInput 208 R Off/On = 0/1 0-1 Zone 2 Humidity Low Limit Alarm X

HoldingRegister 208 R/W ###.#0/100%

RHZone 2 High Humidity Alarm Setpoint X

DiscreteInput 209 R Off/On = 0/1 0-1 Zone 2 Humidity High Limit Alarm X

HoldingRegister 209 R/W 0,1,2,3 0-3Zone 2 Determines Continuous blower settings for zone

X

DiscreteInput 210 R Off/On = 0/1 0-1 No Temperature Sensor Present in Zone 2 X

HoldingRegister 210 R/W 0,1,2 0-2 Zone 2 Determines rotation setting for zone X

HoldingRegister 211 R/W 0,1,2,3 0-3Zone 2 Determines method for dehumidification for zone

X

HoldingRegister 212 R/W ###.#46%/99%

RHZone 2 Humidity level required to start passive dehumidification

X

HoldingRegister 213 R/W ###.#46%/99%

RHZone 2 Humidity level required to start active dehumidification

X

HoldingRegister 214 R/W ###.# 1-14 Zone 2 Staging Free Cooling delay on X

HoldingRegister 215 R/W ###.# 1-14 Zone 2 Staging Free Cooling delay off X

HoldingRegister 216 R/W ###.# 1-14 Zone 2 Staging Cooling delay on X

HoldingRegister 217 R/W ###.# 1-14 Zone 2 Staging Cooling delay off X

HoldingRegister 218 R/W ###.# 1-14 Zone 2 Staging Heating delay on X

HoldingRegister 219 R/W ###.# 1-14 Zone 2 Staging Heating delay off X

DiscreteInput 300 R Off/On = 0/1 0-1Zone 3 Emergency Off Input Active (prev:Zone 3 Smoke Alarm Active)

X

HoldingRegister 300 R/W ###.# 1-14 Zone 3 Cooling temperature setpoint X

InputRegister 300 R ###.#0-100%

RHZone 3 Indoor Humidity Measurement X

DiscreteInput 301 R Off/On = 0/1 0-1Zone 3 Emergency Vent Input Active (prev:Zone 3 Hydrogen Alarm Active)

X

HoldingRegister 301 R/W ###.# NA Zone 3 Heating temperature setpoint X

InputRegister 301 R ###.# NA Remote Zone3 Air Switch X

DiscreteInput 302 R Off/On = 0/1 0-1 Zone 3 Temperature Sensor Alarm X

HoldingRegister 302 R/W ###.#0%/45%

RHZone 3 Humidification Setpoint X

HoldingRegister 303 R/W ###.#46%/99%

RHZone 3 Dehumidification Setpoint X

DiscreteInput 304 R Off/On = 0/1 0-1 Zone 3 Humidity Sensor Alarm X

HoldingRegister 304 R/W ###.#36ºF/66ºF

Zone 3 Low Temperature setpoint X

DiscreteInput 305 R Off/On = 0/1 0-1 Zone 3 Indoor TempLow Limit Alarm X

HoldingRegister 305 R/W ###.#70°F/120°F

Zone 3 High Temperature Warning Setpoint X

DiscreteInput 306 R Off/On = 0/1 0-1 Zone 3 Indoor Temp High Limit Warning X

HoldingRegister 306 R/W ###.#70°F/120°F

Zone 3 High Temperature Alarm Setpoint X

Page 7: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 7 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

DiscreteInput 307 R Off/On = 0/1 0-1 Zone 3 Indoor Temp High Limit Alarm X

HoldingRegister 307 R/W ###.#0/100%

RHZone 3 Low Humidity Alarm Setpoint X

DiscreteInput 308 R Off/On = 0/1 0-1 Zone 3 Humidity Low Limit Alarm X

HoldingRegister 308 R/W ###.#0/100%

RHZone 3 High Humidity Alarm Setpoint X

DiscreteInput 309 R Off/On = 0/1 0-1 Zone 3 Humidity High Limit Alarm X

HoldingRegister 309 R/W 0,1,2,3 0-3Zone 3 Determines Continuous blower settings for zone

X

DiscreteInput 310 R Off/On = 0/1 0-1 No Temperature Sensor Present in Zone 3 X

HoldingRegister 310 R/W 0,1,2 0-2 Zone 3 Determines rotation setting for zone X

HoldingRegister 311 R/W 0,1,2,3 0-3Zone 3 Determines method for dehumidification for zone

X

HoldingRegister 312 R/W ###.#46%/99%

RHZone 3 Humidity level required to start passive dehumidification

X

HoldingRegister 313 R/W ###.#46%/99%

RHZone 3 Humidity level required to start active dehumidification

X

HoldingRegister 314 R/W ###.# 1-14 Zone 3 Staging Free Cooling delay on X

HoldingRegister 315 R/W ###.# 1-14 Zone 3 Staging Free Cooling delay off X

HoldingRegister 316 R/W ###.# 1-14 Zone 3 Staging Cooling delay on X

HoldingRegister 317 R/W ###.# 1-14 Zone 3 Staging Cooling delay off X

HoldingRegister 318 R/W ###.# 1-14 Zone 3 Staging Heating delay on X

HoldingRegister 319 R/W ###.# 1-14 Zone 3 Staging Heating delay off X

DiscreteInput 1000 R Off/On = 0/1 0-1 Unit 1 Dirty Filter 1 Alarm X X X

DiscreteInput 1001 R Off/On = 0/1 0-1 Unit 1 Dirty Filter 2 Alarm X

DiscreteInput 1002 R Off/On = 0/1 0-1 Unit 1 Dirty Filter 3 Alarm

DiscreteInput 1003 R Off/On = 0/1 0-1 Unit 1 Blower 1 Is Running X X

InputRegister 1003 R 0-14 0-14 Unit 1 Compressor 1 Status X X X

DiscreteInput 1004 R Off/On = 0/1 0-1 Unit 1 Blower 2 Is Running

InputRegister 1004 R 0-14 0-14 Unit 1 Compressor 2 Status X

DiscreteInput 1005 R Off/On = 0/1 0-1 Unit 1 Low Pressure Switch 1 X

DiscreteInput 1006 R Off/On = 0/1 0-1 Unit 1 Low Pressure Switch 2

DiscreteInput 1007 R Off/On = 0/1 0-1 Unit 1 Damper Switch 1 Open X X X

DiscreteInput 1008 R Off/On = 0/1 0-1 Unit 1 Damper Switch 2 Open X

DiscreteInput 1009 R Off/On = 0/1 0-1 Unit 1 Damper Switch 3 Open X

DiscreteInput 1010 R Off/On = 0/1 0-1 Unit 1 Damper Switch 4 Open

InputRegister 1011 R ###.# NA Unit 1 Mixed Air Temperature Sensor 1 X X X

DiscreteInput 1012 R Off/On = 0/1 0-1 Unit 1 Activates Reheat Valve for Dehum X

InputRegister 1013 R ###.# NA Unit 1 Mixed Air Temperature Sensor 2 X

InputRegister 1014 R Zone1, 2, or 3 1-3 Unit 1 Zone Options X X X

InputRegister 1015 R ###.# NA Unit 1 Outdoor Air Temperature Sensor 1 X X X

InputRegister 1017 R ###.# NA Unit 1 Outdoor Air Temperature Sensor 2

InputRegister 1019 R ###.# NA Unit 1 Return Air Temperature Sensor 1 X X X

InputRegister 1021 R ###.# NA Unit 1 Return Air Temperature Sensor 2 X

InputRegister 1023 R ###.# 0-100% Unit 1 Outdoor Humidity Sensor 1 X X

InputRegister 1025 R ###.# 0-100% Unit 1 Outdoor Humidity Sensor 2

InputRegister 1027 R ###.# NA Unit 1 Freeze Sensor 1 X

DiscreteInput 1029 R Off/On = 0/1 0-1 Unit 1 Heat 1 On/Off X X X

InputRegister 1029 R ###.# NA Unit 1 Freeze Sensor 2

DiscreteInput 1030 R Off/On = 0/1 0-1 Unit 1 Heat 2 On/Off X X X

DiscreteInput 1031 R Off/On = 0/1 0-1 Unit 1 Heat 3 On/Off X

Page 8: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 8 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

DiscreteInput 1032 R Off/On = 0/1 0-1 Unit 1 Heat 4 On/Off

DiscreteInput 1033 R Off/On = 0/1 0-1 Unit 1 FreeCool Is Available X X X

DiscreteInput 1034 R Off/On = 0/1 0-1 Unit 1 Dirty Filter Indicator X X

InputRegister 1034 R ### 0-100% Unit 1 Blower Speed 1 X X

DiscreteInput 1035 R Off/On = 0/1 0-1 Unit 1 Cooling 1 On/Off X X X

InputRegister 1035 R ### 0-100% Unit 1 Blower Speed 2

DiscreteInput 1036 R Off/On = 0/1 0-1 Unit 1 Cooling 2 On/Off X X X

InputRegister 1036 R ### 0-45 bar Unit 1 Discharge Pressure Transducer 1

DiscreteInput 1037 R Off/On = 0/1 0-1 Unit 1 Cooling 3 On/Off X

InputRegister 1037 R ### 0-45 bar Unit 1 Discharge Pressure Transducer 2

DiscreteInput 1038 R Off/On = 0/1 0-1 Unit 1 Cooling 4 On/Off

InputRegister 1038 R ###.# NA Unit 1 Discharge Temperature 1

DiscreteInput 1039 R Off/On = 0/1 0-1 Unit 1 Indicates No Air Flow X X

InputRegister 1039 R ###.# NA Unit 1 Discharge Temperature 2

DiscreteInput 1040 R Off/On = 0/1 0-1 Unit 1 Indicates No Air Flow 2

InputRegister 1040 R ### 0-100% Unit 1 Dust Sensor 1 X X

DiscreteInput 1041 R Off/On = 0/1 0-1 Unit 1 High Pressure Event X X X

InputRegister 1041 R ### 0-100% Unit 1 Dust Sensor 2

DiscreteInput 1042 R Off/On = 0/1 0-1 Unit 1 High Pressure 2 Event X

DiscreteInput 1043 R Off/On = 0/1 0-1 Unit 1 Power Loss Detected Alarm X X

DiscreteInput 1044 R Off/On = 0/1 0-1 Unit 1 Is Disabled X X X

InputRegister 1044 R ###.# NA Unit 1 Liquid Temperature 1 X X

InputRegister 1045 R ###.# NA Unit 1 Liquid Temperature 2 X

InputRegister 1046 R ### NA Unit 1 Liquid Pressure 1 X

InputRegister 1047 R ### NA Unit 1 Liquid Pressure 2

InputRegister 1048 R ### NA Unit 1 Suction Pressure 1 X X

InputRegister 1049 R ### NA Unit 1 Suction Pressure 2

InputRegister 1050 R ###.# NA Unit 1 Suction Temperature 1 X X

InputRegister 1051 R ###.# NA Unit 1 Suction Temperature 2

InputRegister 1052 R ###.# NA Unit 1 Supply Air Temperature 1 X X

InputRegister 1053 R ###.# NA Unit 1 Supply Air Temperature 2 X

InputRegister 1056 R ### 0-100% Unit 1 Condenser Fan Speed 1 X X

InputRegister 1057 R ### 0-100% Unit 1 Condenser Fan Speed 2 X

InputRegister 1058 R ### 0-100% Unit 1 Damper Position 1 X X X

InputRegister 1059 R ### 0-100% Unit 1 Damper Position 2 X

InputRegister 1060 R ### 0-100% Unit 1 Damper Position 3 X

InputRegister 1061 R ### 0-100% Unit 1 Damper Position 4 X

InputRegister 1062 R ### 0-100% Unit 1 EEV1 Position X X X

InputRegister 1063 R ### 0-100% Unit 1 EEV2 Position X

InputRegister 1064 R ### NA Unit 1 Declares number of Cooling Stages X X

InputRegister 1065 R ### NA Unit 1 Declares number of Heating Stages X X

InputRegister 1066 R ### NA Unit 1 Declares number of Freecooling Stages X X

InputRegister 1067 R ### °F Unit 1 Outdoor Air Dewpoint X

InputRegister 1068 R ### 0,1,2,3 Unit 1 Dehumidification Type X X

InputRegister 1069 R ###.# NA Unit 1 Suction Saturation Temperature 1

InputRegister 1070 R ###.# NA Unit 1 Suction Saturation Temperature 2

InputRegister 1071 R ### NA Unit 1 Subcooling 1 X

InputRegister 1072 R ### NA Unit 1 Superheat 1

InputRegister 1073 R ### NA Unit 1 Superheat 2

Page 9: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 9 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

InputRegister 1074 R ###.# NA Unit 1 Liquid Saturated Temperature 1

InputRegister 1075 R ###.# NA Unit 1 Liquid Saturated Temperature 2

InputRegister 1076 R ### NA Unit 1 Subcooling 2

InputRegister 1080 R ### NA Unit 1 Major Revision Number X X X

InputRegister 1081 R ### NA Unit 1 Minor Revision Number X X X

InputRegister 1082 R ### NA Unit 1 Bug Fixes X X X

InputRegister 1083 R ### NAUnit 1 How long the unit has been running in minutes

X X X

InputRegister 1084 R ## NA Unit 1 How many times unit has started X X X

InputRegister 1085 R ### NA Unit 1 How long the Fan is running in minutes X X

InputRegister 1086 R ## NA Unit 1 How many times Fan turned on X X

InputRegister 1087 R ### NA Unit 1 How long the Fan is running in minutes

InputRegister 1088 R ## NA Unit 1 How many times Fan turned on

InputRegister 1089 R ### NA Unit 1 How long the Blower is running in minutes X X X

InputRegister 1090 R ## NA Unit 1 How many times Blower turned on X X

InputRegister 1091 R ### NA Unit 1 How long the Blower is running in minutes

InputRegister 1092 R ## NA Unit 1 How many times Blower turned on

InputRegister 1093 R ### NA Unit 1 How long unit is running in Freecooling X X

InputRegister 1094 R ### NAUnit 1 How many times unit has been in Freecooling

X X

InputRegister 1095 R ### NA Unit 1 How long unit is running in Freecooling

InputRegister 1096 R ### NAUnit 1 How many times unit has been in Freecooling

InputRegister 1097 R ### NA Unit 1 How long unit is running in Cooling X X X

InputRegister 1098 R ### NA Unit 1 How many times unit has been in Cooling X X X

InputRegister 1099 R ### NA Unit 1 How long unit is running in Cooling X X

InputRegister 1100 R ### NA Unit 1 How many times unit has been in Cooling X X

InputRegister 1101 R ### NA Unit 1 How long unit is running in Cooling X

InputRegister 1102 R ### NA Unit 1 How many times unit has been in Cooling X

InputRegister 1103 R ### NA Unit 1 How long unit is running in Cooling

InputRegister 1104 R ### NA Unit 1 How many times unit has been in Cooling

InputRegister 1105 R ### NA Unit 1 How long unit is running in Heating X X X

InputRegister 1106 R ### NA Unit 1 How many times unit has been in Heating X X X

InputRegister 1107 R ### NA Unit 1 How long unit is running in Heating X X

InputRegister 1108 R ### NA Unit 1 How many times unit has been in Heating X X

InputRegister 1109 R ### NA Unit 1 How long unit is running in Heating

InputRegister 1110 R ### NA Unit 1 How many times unit has been in Heating

InputRegister 1111 R ### NA Unit 1 How long unit is running in Heating

InputRegister 1112 R ### NA Unit 1 How many times unit has been in Heating

InputRegister 1113 R ### 0-999999 Unit 1 life time in Hours (Update every Hour) X X X

InputRegister 1115 R ### 0-999999Unit 1 Blower life time in Hours (Update every Hour)

X X

InputRegister 1117 R ### 0-999999Unit 1 Blower life time in Hours (Update every Hour)

InputRegister 1119 R ### 0-999999 Unit 1 Fan life time in hours (Update every Hour) X

InputRegister 1121 R ### 0-999999 Unit 1 Fan life time in hours (Update every Hour)

InputRegister 1123 R ### 0-999999Unit 1 Cooling life time in hours (Update ever Hour)

X X

InputRegister 1125 R ### 0-999999Unit 1 Cooling life time in hours (Update ever Hour)

X

InputRegister 1127 R ### 0-999999Unit 1 Cooling life time in hours (Update ever Hour)

Page 10: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 10 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

InputRegister 1129 R ### 0-999999Unit 1 Cooling life time in hours (Update ever Hour)

InputRegister 1131 R ### 0-999999Unit 1 Heating life time in hours (Update ever Hour)

X X

InputRegister 1133 R ### 0-999999Unit 1 Heating life time in hours (Update ever Hour)

InputRegister 1135 R ### 0-999999Unit 1 Heating life time in hours (Update ever Hour)

InputRegister 1137 R ### 0-999999Unit 1 Heating life time in hours (Update ever Hour)

InputRegister 1139 R ### 0-999999Unit 1 FreeCooling life time in hours (Update ever Hour)

X X

InputRegister 1141 R ### 0-999999Unit 1 FreeCooling life time in hours (Update ever Hour)

InputRegister 1143 R ### 0-5Unit 1 Indicates what unit types are running on the network

X X X

InputRegister 1154 R ### 0-29 Unit 1 Indicates Current Status Of Units X X X

DiscreteInput 1500 R Off/On = 0/1 0-1Unit 1 Error in the number of retain memory writings Alarm

X X X

DiscreteInput 1501 R Off/On = 0/1 0-1 Unit 1 Error in retain memory writings Alarm X X X

DiscreteInput 1502 R Off/On = 0/1 0-1 Unit 1 Return Air Temperature Sensor Alarm X X X

DiscreteInput 1503 R Off/On = 0/1 0-1 Unit 1 High Return Air Temperature Alarm X X

DiscreteInput 1504 R Off/On = 0/1 0-1 Unit 1 Mixed Air Temperature Sensor Alarm X X

DiscreteInput 1505 R Off/On = 0/1 0-1 Unit 1 Mixed Air High Temperature Alarm X X

DiscreteInput 1506 R Off/On = 0/1 0-1 Unit 1 Mixed Air Low Temperature Alarm X X

DiscreteInput 1507 R Off/On = 0/1 0-1 Unit 1 Supply Air Temperature Sensor Alarm X X

DiscreteInput 1508 R Off/On = 0/1 0-1 Unit 1 High Supply Air Temperature Alarm X

DiscreteInput 1509 R Off/On = 0/1 0-1 Unit 1 Low Supply Air Temperature Alarm X

DiscreteInput 1510 R Off/On = 0/1 0-1 Unit 1 Outdoor Air Temperature Sensor Alarm X X X

DiscreteInput 1511 R Off/On = 0/1 0-1 Unit 1 Outdoor Air Humidity Sensor Alarm X X X

DiscreteInput 1512 R Off/On = 0/1 0-1 Unit 1 Dust Sensor Alarm X X

DiscreteInput 1513 R Off/On = 0/1 0-1 Unit 1 Dust Sensor High Dust Detection Alarm X X

DiscreteInput 1514 R Off/On = 0/1 0-1 Unit 1 Liquid Line Temp Sensor Alarm X X

DiscreteInput 1515 R Off/On = 0/1 0-1 Unit 1 Discharge Temp Sensor Alarm

DiscreteInput 1516 R Off/On = 0/1 0-1 Unit 1 Liquid Line Pressure Sensor Alarm X

DiscreteInput 1517 R Off/On = 0/1 0-1 Unit 1 Suction Temperature Sensor Alarm X X X

DiscreteInput 1518 R Off/On = 0/1 0-1 Unit 1 Suction Pressure Sensor Alarm X X X

DiscreteInput 1519 R Off/On = 0/1 0-1 Unit 1 Low Pressure Alarm X X X

DiscreteInput 1520 R Off/On = 0/1 0-1 Unit 1 High Pressure Alarm X X X

DiscreteInput 1521 R Off/On = 0/1 0-1 Unit 1 Damper 1 Failed to Open X X X

DiscreteInput 1522 R Off/On = 0/1 0-1 Unit 1 Damper 1 Failed to Close X X X

DiscreteInput 1523 R Off/On = 0/1 0-1 Unit 1 Freeze Temperature Sensor Alarm X X

DiscreteInput 1524 R Off/On = 0/1 0-1 Unit 1 Freeze Condition X X X

DiscreteInput 1525 R Off/On = 0/1 0-1 Unit 1 Blower Fail Alarm X X

DiscreteInput 1526 R Off/On = 0/1 0-1 Unit 1 Dirty Filter 1 Alarm X X X

DiscreteInput 1527 R Off/On = 0/1 0-1 Unit 1 Dirty Condenser Coil Alarm

DiscreteInput 1528 R Off/On = 0/1 0-1 Unit 1 Emergency Ventilation Mode Active Alarm X X X

DiscreteInput 1529 R Off/On = 0/1 0-1 Unit 1 Emergency Cooling Mode Active Alarm X X X

DiscreteInput 1530 R Off/On = 0/1 0-1Unit 1 Extreme High Return Temp Alarm (Heat Cutout) Alarm

X X X

DiscreteInput 1531 R Off/On = 0/1 0-1 Unit 1 Disable/Smoke Detector Alarm X X X

DiscreteInput 1532 R Off/On = 0/1 0-1 Unit 1 Power Loss Detected Alarm X

Page 11: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 11 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

DiscreteInput 1533 R Off/On = 0/1 0-1 Unit 1 Low SuperHeat Alarm X X X

DiscreteInput 1534 R Off/On = 0/1 0-1 Unit 1 Low Evaporation Pressure Alarm X X X

DiscreteInput 1535 R Off/On = 0/1 0-1 Unit 1 High Evaporation Pressure Alarm X X X

DiscreteInput 1536 R Off/On = 0/1 0-1 Unit 1 High Condenser Temperature Alarm X X X

DiscreteInput 1537 R Off/On = 0/1 0-1 Unit 1 Low Suction pressure Alarm X X X

DiscreteInput 1538 R Off/On = 0/1 0-1 Unit 1 EEV motor error Alarm X X X

DiscreteInput 1539 R Off/On = 0/1 0-1 Unit 1 SelfTuning error Alarm X X X

DiscreteInput 1540 R Off/On = 0/1 0-1 Unit 1 Emergency close Alarm X X X

DiscreteInput 1541 R Off/On = 0/1 0-1 Unit 1 High Delta Temperature Alarm

DiscreteInput 1542 R Off/On = 0/1 0-1 Unit 1 High Delta Pressure Alarm

DiscreteInput 1543 R Off/On = 0/1 0-1 Unit 1 Range Error Alarm X X X

DiscreteInput 1544 R Off/On = 0/1 0-1 Unit 1 Service Position Percent Alarm X X X

DiscreteInput 1545 R Off/On = 0/1 0-1 Unit 1 Valve ID Alarm X X X

DiscreteInput 1546 R Off/On = 0/1 0-1 Unit 1 Return Air Temperature Sensor 2 Alarm X

DiscreteInput 1547 R Off/On = 0/1 0-1 Unit 1 High Return Air Temperature 2 Alarm X

DiscreteInput 1548 R Off/On = 0/1 0-1 Unit 1 Mixed Air Temperature Sensor 2 Alarm X

DiscreteInput 1549 R Off/On = 0/1 0-1 Unit 1 Mixed Air High Temperature 2 Alarm

DiscreteInput 1550 R Off/On = 0/1 0-1 Unit 1 Mixed Air Low Temperature 2 Alarm

DiscreteInput 1551 R Off/On = 0/1 0-1 Unit 1 Supply Air Temperature Sensor 2 Alarm X

DiscreteInput 1552 R Off/On = 0/1 0-1 Unit 1 High Supply Air Temperature 2 Alarm

DiscreteInput 1553 R Off/On = 0/1 0-1 Unit 1 Low Supply Air Temperature 2 Alarm

DiscreteInput 1554 R Off/On = 0/1 0-1 Unit 1 Dust Sensor 2 Alarm

DiscreteInput 1555 R Off/On = 0/1 0-1 Unit 1 Dust Sensor High Dust Detection 2 Alarm

DiscreteInput 1556 R Off/On = 0/1 0-1 Unit 1 Liquid Line Temp Sensor 2 Alarm X

DiscreteInput 1557 R Off/On = 0/1 0-1 Unit 1 Liquid Line Pressure Sensor 2 Alarm

DiscreteInput 1558 R Off/On = 0/1 0-1 Unit 1 Discharge Temp Sensor 2 Alarm

DiscreteInput 1559 R Off/On = 0/1 0-1 Unit 1 Discharge Pressure Sensor 2 Alarm X

DiscreteInput 1560 R Off/On = 0/1 0-1 Unit 1 Discharge Pressure Sensor 2 Alarm X

DiscreteInput 1561 R Off/On = 0/1 0-1 Unit 1 Suction Temperature Sensor 2 Alarm X

DiscreteInput 1562 R Off/On = 0/1 0-1 Unit 1 Suction Pressure Sensor 2 Alarm X

DiscreteInput 1563 R Off/On = 0/1 0-1 Unit 1 Low Pressure 2 Alarm X

DiscreteInput 1564 R Off/On = 0/1 0-1 Unit 1 High Pressure 2 Alarm X

DiscreteInput 1565 R Off/On = 0/1 0-1 Unit 1 Damper 2 Failed to Open X

DiscreteInput 1566 R Off/On = 0/1 0-1 Unit 1 Damper 2 Failed to Close X

DiscreteInput 1567 R Off/On = 0/1 0-1 Unit 1 Damper 3 Failed to Open X

DiscreteInput 1568 R Off/On = 0/1 0-1 Unit 1 Damper 3 Failed to Close X

DiscreteInput 1569 R Off/On = 0/1 0-1 Unit 1 Damper 4 Failed to Open

DiscreteInput 1570 R Off/On = 0/1 0-1 Unit 1 Damper 4 Failed to Close

DiscreteInput 1571 R Off/On = 0/1 0-1 Unit 1 Freeze Temperature Sensor 2 Alarm X

DiscreteInput 1572 R Off/On = 0/1 0-1 Unit 1 Freeze 2 Condition Alarm X

DiscreteInput 1573 R Off/On = 0/1 0-1 Unit 1 Blower 2 Fail Alarm

DiscreteInput 1574 R Off/On = 0/1 0-1 Unit 1 Dirty Filter 2 Alarm

DiscreteInput 1575 R Off/On = 0/1 0-1 Unit 1 Dirty Filter 3 Alarm

DiscreteInput 1576 R Off/On = 0/1 0-1 Unit 1 Dirty Filter 4 Alarm

DiscreteInput 1577 R Off/On = 0/1 0-1 Unit 1 Dirty Condenser Coil 2 Alarm

DiscreteInput 1578 R Off/On = 0/1 0-1 Unit 1 Power Loss 2 Detected Alarm

DiscreteInput 1579 R Off/On = 0/1 0-1 Unit 1 Low SuperHeat 2 Alarm X

DiscreteInput 1580 R Off/On = 0/1 0-1 Unit 1 Low Evaporation Pressure 2 Alarm X

DiscreteInput 1581 R Off/On = 0/1 0-1 Unit 1 High Evaporation Pressure 2 Alarm X

Page 12: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 12 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

DiscreteInput 1582 R Off/On = 0/1 0-1 Unit 1 High Condenser Temperature 2 Alarm X

DiscreteInput 1583 R Off/On = 0/1 0-1 Unit 1 Low Suction pressure 2 Alarm X

DiscreteInput 1584 R Off/On = 0/1 0-1 Unit 1 EEV motor 2 error Alarm X

DiscreteInput 1585 R Off/On = 0/1 0-1 Unit 1 SelfTuning 2 error Alarm X

DiscreteInput 1586 R Off/On = 0/1 0-1 Unit 1 Emergency close 2 Alarm X

DiscreteInput 1587 R Off/On = 0/1 0-1 Unit 1 High Delta Temperature 2 Alarm

DiscreteInput 1588 R Off/On = 0/1 0-1 Unit 1 High Delta Pressure 2 Alarm

DiscreteInput 1589 R Off/On = 0/1 0-1 Unit 1 Range Error 2 Alarm X

DiscreteInput 1590 R Off/On = 0/1 0-1 Unit 1 Service Position Percent 2 Alarm X

DiscreteInput 1591 R Off/On = 0/1 0-1 Unit 1 Valve ID 2 Alarm X

DiscreteInput 1592 R Off/On = 0/1 0-1 Unit 1 Th-Tune Device Offline Alarm X

DiscreteInput 1593 R Off/On = 0/1 0-1 Unit 1 Th-Tune Temperature Probe Alarm X

DiscreteInput 1594 R Off/On = 0/1 0-1 Unit 1 Th-Tune Humidity Probe Alarm X

DiscreteInput 1595 R Off/On = 0/1 0-1 Unit 1 Th-Tune Clock Board Alarm X

DiscreteInput 1596 R Off/On = 0/1 0-1 Unit 1 cpCOe Offline Alarm X

DiscreteInput 1597 R Off/On = 0/1 0-1 Unit 1 Blower 1 Offline Alarm X

DiscreteInput 1598 R Off/On = 0/1 0-1 Unit 1 Blower 1 Alarm X

DiscreteInput 1599 R Off/On = 0/1 0-1 Unit 1 Blower 2 Offline Alarm

DiscreteInput 1600 R Off/On = 0/1 0-1 Unit 1 Blower 2 Alarm

DiscreteInput 1601 R Off/On = 0/1 0-1 Unit 1 Condenser 1 Offline Alarm X

DiscreteInput 1602 R Off/On = 0/1 0-1 Unit 1 Condenser 1 Alarm X

DiscreteInput 1603 R Off/On = 0/1 0-1 Unit 1 Condenser 2 Offline Alarm

DiscreteInput 1604 R Off/On = 0/1 0-1 Unit 1 Condenser 2 Alarm

DiscreteInput 1605 R Off/On = 0/1 0-1 Unit 1 Low Return Air Temperature 1 Alarm X

DiscreteInput 1606 R Off/On = 0/1 0-1 Unit 1 Low Return Air Temperature 2 Alarm X

DiscreteInput 1607 R Off/On = 0/1 0-1 Unit 1 Panel Open Alarm X

DiscreteInput 2000 R Off/On = 0/1 0-1 Unit 2 Dirty Filter 1 Alarm X X X

DiscreteInput 2001 R Off/On = 0/1 0-1 Unit 2 Dirty Filter 2 Alarm X

DiscreteInput 2002 R Off/On = 0/1 0-1 Unit 2 Dirty Filter 3 Alarm

DiscreteInput 2003 R Off/On = 0/1 0-1 Unit 2 Blower 1 Is Running X X

InputRegister 2003 R 0-14 0-14 Unit 2 Compressor 1 Status X X X

DiscreteInput 2004 R Off/On = 0/1 0-1 Unit 2 Blower 2 Is Running

InputRegister 2004 R 0-14 0-14 Unit 2 Compressor 2 Status X

DiscreteInput 2005 R Off/On = 0/1 0-1 Unit 2 Low Pressure Switch 1 X

DiscreteInput 2006 R Off/On = 0/1 0-1 Unit 2 Low Pressure Switch 2

DiscreteInput 2007 R Off/On = 0/1 0-1 Unit 2 Damper Switch 1 Open X X X

DiscreteInput 2008 R Off/On = 0/1 0-1 Unit 2 Damper Switch 2 Open X

DiscreteInput 2009 R Off/On = 0/1 0-1 Unit 2 Damper Switch 3 Open X

DiscreteInput 2010 R Off/On = 0/1 0-1 Unit 2 Damper Switch 4 Open

InputRegister 2011 R ###.# NA Unit 2 Mixed Air Temperature Sensor 1 X X X

DiscreteInput 2012 R Off/On = 0/1 0-1 Unit 2 Activates Reheat Valve for Dehum X

InputRegister 2013 R ###.# NA Unit 2 Mixed Air Temperature Sensor 2 X

InputRegister 2014 R Zone1, 2, or 3 1-3 Unit 2 Zone Options X X X

InputRegister 2015 R ###.# NA Unit 2 Outdoor Air Temperature Sensor 1 X X X

InputRegister 2017 R ###.# NA Unit 2 Outdoor Air Temperature Sensor 2

InputRegister 2019 R ###.# NA Unit 2 Return Air Temperature Sensor 1 X X X

InputRegister 2021 R ###.# NA Unit 2 Return Air Temperature Sensor 2 X

InputRegister 2023 R ###.# 0-100% Unit 2 Outdoor Humidity Sensor 1 X X

InputRegister 2025 R ###.# 0-100% Unit 2 Outdoor Humidity Sensor 2

Page 13: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 13 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

InputRegister 2027 R ###.# NA Unit 2 Freeze Sensor 1 X

DiscreteInput 2029 R Off/On = 0/1 0-1 Unit 2 Heat 1 On/Off X X X

InputRegister 2029 R ###.# NA Unit 2 Freeze Sensor 2

DiscreteInput 2030 R Off/On = 0/1 0-1 Unit 2 Heat 2 On/Off X X X

DiscreteInput 2031 R Off/On = 0/1 0-1 Unit 2 Heat 3 On/Off X

DiscreteInput 2032 R Off/On = 0/1 0-1 Unit 2 Heat 4 On/Off

DiscreteInput 2033 R Off/On = 0/1 0-1 Unit 2 FreeCool Is Available X X X

DiscreteInput 2034 R Off/On = 0/1 0-1 Unit 2 Dirty Filter Indicator X X

InputRegister 2034 R ### 0-100% Unit 2 Blower Speed 1 X X

DiscreteInput 2035 R Off/On = 0/1 0-1 Unit 2 Cooling 1 On/Off X X X

InputRegister 2035 R ### 0-100% Unit 2 Blower Speed 2

DiscreteInput 2036 R Off/On = 0/1 0-1 Unit 2 Cooling 2 On/Off X X X

InputRegister 2036 R ### 0-45 bar Unit 2 Discharge Pressure Transducer 1

DiscreteInput 2037 R Off/On = 0/1 0-1 Unit 2 Cooling 3 On/Off X

InputRegister 2037 R ### 0-45 bar Unit 2 Discharge Pressure Transducer 2

DiscreteInput 2038 R Off/On = 0/1 0-1 Unit 2 Cooling 4 On/Off

InputRegister 2038 R ###.# NA Unit 2 Discharge Temperature 1

DiscreteInput 2039 R Off/On = 0/1 0-1 Unit 2 Indicates No Air Flow X X

InputRegister 2039 R ###.# NA Unit 2 Discharge Temperature 2

DiscreteInput 2040 R Off/On = 0/1 0-1 Unit 2 Indicates No Air Flow 2

InputRegister 2040 R ### 0-100% Unit 2 Dust Sensor 1 X X

DiscreteInput 2041 R Off/On = 0/1 0-1 Unit 2 High Pressure Event X X X

InputRegister 2041 R ### 0-100% Unit 2 Dust Sensor 2

DiscreteInput 2042 R Off/On = 0/1 0-1 Unit 2 High Pressure 2 Event X

DiscreteInput 2043 R Off/On = 0/1 0-1 Unit 2 Power Loss Detected Alarm X X

DiscreteInput 2044 R Off/On = 0/1 0-1 Unit 2 Is Disabled X X X

InputRegister 2044 R ###.# NA Unit 2 Liquid Temperature 1 X X

InputRegister 2045 R ###.# NA Unit 2 Liquid Temperature 2 X

InputRegister 2046 R ### NA Unit 2 Liquid Pressure 1 X

InputRegister 2047 R ### NA Unit 2 Liquid Pressure 2

InputRegister 2048 R ### NA Unit 2 Suction Pressure 1 X X

InputRegister 2049 R ### NA Unit 2 Suction Pressure 2

InputRegister 2050 R ###.# NA Unit 2 Suction Temperature 1 X X

InputRegister 2051 R ###.# NA Unit 2 Suction Temperature 2

InputRegister 2052 R ###.# NA Unit 2 Supply Air Temperature 1 X X

InputRegister 2053 R ###.# NA Unit 2 Supply Air Temperature 2 X

InputRegister 2056 R ### 0-100% Unit 2 Condenser Fan Speed 1 X X

InputRegister 2057 R ### 0-100% Unit 2 Condenser Fan Speed 2 X

InputRegister 2058 R ### 0-100% Unit 2 Damper Position 1 X X X

InputRegister 2059 R ### 0-100% Unit 2 Damper Position 2 X

InputRegister 2060 R ### 0-100% Unit 2 Damper Position 3 X

InputRegister 2061 R ### 0-100% Unit 2 Damper Position 4 X

InputRegister 2062 R ### 0-100% Unit 2 EEV1 Position X X X

InputRegister 2063 R ### 0-100% Unit 2 EEV2 Position X

InputRegister 2064 R ### NA Unit 2 Declares number of Cooling Stages X X

InputRegister 2065 R ### NA Unit 2 Declares number of Heating Stages X X

InputRegister 2066 R ### NA Unit 2 Declares number of Freecooling Stages X X

InputRegister 2067 R ### °F Unit 2 Outdoor Air Dewpoint X

InputRegister 2068 R ### 0,1,2,3 Unit 2 Dehumidification Type X X

Page 14: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 14 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

InputRegister 2069 R ###.# NA Unit 2 Suction Saturation Temperature 1

InputRegister 2070 R ###.# NA Unit 2 Suction Saturation Temperature 2

InputRegister 2071 R ### NA Unit 2 Subcooling 1 X

InputRegister 2072 R ### NA Unit 2 Superheat 1

InputRegister 2073 R ### NA Unit 2 Superheat 2

InputRegister 2074 R ###.# NA Unit 2 Liquid Saturated Temperature 1

InputRegister 2075 R ###.# NA Unit 2 Liquid Saturated Temperature 2

InputRegister 2076 R ### NA Unit 2 Subcooling 2

InputRegister 2080 R ### NA Unit 2 Major Revision Number X X X

InputRegister 2081 R ### NA Unit 2 Minor Revision Number X X X

InputRegister 2082 R ### NA Unit 2 Bug Fixes X X X

InputRegister 2083 R ### NAUnit 2 How long the unit has been running in minutes

X X X

InputRegister 2084 R ## NA Unit 2 How many times unit has started X X X

InputRegister 2085 R ### NA Unit 2 How long the Fan is running in minutes X X

InputRegister 2086 R ## NA Unit 2 How many times Fan turned on X X

InputRegister 2087 R ### NA Unit 2 How long the Fan is running in minutes

InputRegister 2088 R ## NA Unit 2 How many times Fan turned on

InputRegister 2089 R ### NA Unit 2 How long the Blower is running in minutes X X X

InputRegister 2090 R ## NA Unit 2 How many times Blower turned on X X

InputRegister 2091 R ### NA Unit 2 How long the Blower is running in minutes

InputRegister 2092 R ## NA Unit 2 How many times Blower turned on

InputRegister 2093 R ### NA Unit 2 How long unit is running in Freecooling X X

InputRegister 2094 R ### NAUnit 2 How many times unit has been in Freecooling

X X

InputRegister 2095 R ### NA Unit 2 How long unit is running in Freecooling

InputRegister 2096 R ### NAUnit 2 How many times unit has been in Freecooling

InputRegister 2097 R ### NA Unit 2 How long unit is running in Cooling X X X

InputRegister 2098 R ### NA Unit 2 How many times unit has been in Cooling X X X

InputRegister 2099 R ### NA Unit 2 How long unit is running in Cooling X X

InputRegister 2100 R ### NA Unit 2 How many times unit has been in Cooling X X

InputRegister 2101 R ### NA Unit 2 How long unit is running in Cooling X

InputRegister 2102 R ### NA Unit 2 How many times unit has been in Cooling X

InputRegister 2103 R ### NA Unit 2 How long unit is running in Cooling

InputRegister 2104 R ### NA Unit 2 How many times unit has been in Cooling

InputRegister 2105 R ### NA Unit 2 How long unit is running in Heating X X X

InputRegister 2106 R ### NA Unit 2 How many times unit has been in Heating X X X

InputRegister 2107 R ### NA Unit 2 How long unit is running in Heating X X

InputRegister 2108 R ### NA Unit 2 How many times unit has been in Heating X X

InputRegister 2109 R ### NA Unit 2 How long unit is running in Heating

InputRegister 2110 R ### NA Unit 2 How many times unit has been in Heating

InputRegister 2111 R ### NA Unit 2 How long unit is running in Heating

InputRegister 2112 R ### NA Unit 2 How many times unit has been in Heating

InputRegister 2113 R ### 0-999999 Unit 2 life time in Hours (Update every Hour) X X X

InputRegister 2115 R ### 0-999999Unit 2 Blower 1 life time in Hours (Update every Hour)

X X

InputRegister 2117 R ### 0-999999Unit 2 Blower 2 life time in Hours (Update every Hour)

InputRegister 2119 R ### 0-999999Unit 2 Fan 1 life time in hours (Update every Hour)

X

Page 15: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 15 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

InputRegister 2121 R ### 0-999999Unit 2 Fan 2 life time in hours (Update every Hour)

InputRegister 2123 R ### 0-999999Unit 2 Cooling 1 life time in hours (Update ever Hour)

X X

InputRegister 2125 R ### 0-999999Unit 2 Cooling 2 life time in hours (Update ever Hour)

X

InputRegister 2127 R ### 0-999999Unit 2 Cooling 3 life time in hours (Update ever Hour)

InputRegister 2129 R ### 0-999999Unit 2 Cooling 4 life time in hours (Update ever Hour)

InputRegister 2131 R ### 0-999999Unit 2 Heating 1 life time in hours (Update ever Hour)

X X

InputRegister 2133 R ### 0-999999Unit 2 Heating 2 life time in hours (Update ever Hour)

InputRegister 2135 R ### 0-999999Unit 2 Heating 3 life time in hours (Update ever Hour)

InputRegister 2137 R ### 0-999999Unit 2 Heating 4 life time in hours (Update ever Hour)

InputRegister 2139 R ### 0-999999Unit 2 FreeCooling 1 life time in hours (Update ever Hour)

X X

InputRegister 2141 R ### 0-999999Unit 2 FreeCooling 2 life time in hours (Update ever Hour)

InputRegister 2143 R ### 0-5Unit 2 Indicates what unit types are running on the network

X X X

DiscreteInput 2500 R Off/On = 0/1 0-1Unit 2 Error in the number of retain memory writings Alarm

X X X

DiscreteInput 2501 R Off/On = 0/1 0-1 Unit 2 Error in retain memory writings Alarm X X X

DiscreteInput 2502 R Off/On = 0/1 0-1 Unit 2 Return Air Temperature Sensor Alarm X X X

DiscreteInput 2503 R Off/On = 0/1 0-1 Unit 2 High Return Air Temperature Alarm X X

DiscreteInput 2504 R Off/On = 0/1 0-1 Unit 2 Mixed Air Temperature Sensor Alarm X X

DiscreteInput 2505 R Off/On = 0/1 0-1 Unit 2 Mixed Air High Temperature Alarm X X

DiscreteInput 2506 R Off/On = 0/1 0-1 Unit 2 Mixed Air Low Temperature Alarm X X

DiscreteInput 2507 R Off/On = 0/1 0-1 Unit 2 Supply Air Temperature Sensor Alarm X X

DiscreteInput 2508 R Off/On = 0/1 0-1 Unit 2 High Supply Air Temperature Alarm X

DiscreteInput 2509 R Off/On = 0/1 0-1 Unit 2 Low Supply Air Temperature Alarm X

DiscreteInput 2510 R Off/On = 0/1 0-1 Unit 2 Outdoor Air Temperature Sensor Alarm X X X

DiscreteInput 2511 R Off/On = 0/1 0-1 Unit 2 Outdoor Air Humidity Sensor Alarm X X X

DiscreteInput 2512 R Off/On = 0/1 0-1 Unit 2 Dust Sensor Alarm X X

DiscreteInput 2513 R Off/On = 0/1 0-1 Unit 2 Dust Sensor High Dust Detection Alarm X X

DiscreteInput 2514 R Off/On = 0/1 0-1 Unit 2 Liquid Line Temp Sensor Alarm X X

DiscreteInput 2515 R Off/On = 0/1 0-1 Unit 2 Discharge Temp Sensor Alarm

DiscreteInput 2516 R Off/On = 0/1 0-1 Unit 2 Liquid Line Pressure Sensor Alarm X

DiscreteInput 2517 R Off/On = 0/1 0-1 Unit 2 Suction Temperature Sensor Alarm X X X

DiscreteInput 2518 R Off/On = 0/1 0-1 Unit 2 Suction Pressure Sensor Alarm X X X

DiscreteInput 2519 R Off/On = 0/1 0-1 Unit 2 Low Pressure Alarm X X X

DiscreteInput 2520 R Off/On = 0/1 0-1 Unit 2 High Pressure Alarm X X X

DiscreteInput 2521 R Off/On = 0/1 0-1 Unit 2 Damper 1 Failed to Open X X X

DiscreteInput 2522 R Off/On = 0/1 0-1 Unit 2 Damper 1 Failed to Close X X X

DiscreteInput 2523 R Off/On = 0/1 0-1 Unit 2 Freeze Temperature Sensor Alarm X X

DiscreteInput 2524 R Off/On = 0/1 0-1 Unit 2 Freeze Condition X X X

DiscreteInput 2525 R Off/On = 0/1 0-1 Unit 2 Blower Fail Alarm X X

DiscreteInput 2526 R Off/On = 0/1 0-1 Unit 2 Dirty Filter 1 Alarm X X X

DiscreteInput 2527 R Off/On = 0/1 0-1 Unit 2 Dirty Condenser Coil Alarm

DiscreteInput 2528 R Off/On = 0/1 0-1 Unit 2 Emergency Ventilation Mode Active Alarm X X X

Page 16: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 16 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

DiscreteInput 2529 R Off/On = 0/1 0-1 Unit 2 Emergency Cooling Mode Active Alarm X X X

DiscreteInput 2530 R Off/On = 0/1 0-1Unit 2 Extreme High Return Temp Alarm (Heat Cutout) Alarm

X X X

DiscreteInput 2531 R Off/On = 0/1 0-1 Unit 2 Disable/Smoke Detector Alarm X X X

DiscreteInput 2532 R Off/On = 0/1 0-1 Unit 2 Power Loss Detected Alarm X

DiscreteInput 2533 R Off/On = 0/1 0-1 Unit 2 Low SuperHeat Alarm X X X

DiscreteInput 2534 R Off/On = 0/1 0-1 Unit 2 Low Evaporation Pressure Alarm X X X

DiscreteInput 2535 R Off/On = 0/1 0-1 Unit 2 High Evaporation Pressure Alarm X X X

DiscreteInput 2536 R Off/On = 0/1 0-1 Unit 2 High Condenser Temperature Alarm X X X

DiscreteInput 2537 R Off/On = 0/1 0-1 Unit 2 Low Suction pressure Alarm X X X

DiscreteInput 2538 R Off/On = 0/1 0-1 Unit 2 EEV motor error Alarm X X X

DiscreteInput 2539 R Off/On = 0/1 0-1 Unit 2 SelfTuning error Alarm X X X

DiscreteInput 2540 R Off/On = 0/1 0-1 Unit 2 Emergency close Alarm X X X

DiscreteInput 2541 R Off/On = 0/1 0-1 Unit 2 High Delta Temperature Alarm

DiscreteInput 2542 R Off/On = 0/1 0-1 Unit 2 High Delta Pressure Alarm

DiscreteInput 2543 R Off/On = 0/1 0-1 Unit 2 Range Error Alarm X X X

DiscreteInput 2544 R Off/On = 0/1 0-1 Unit 2 Service Position Percent Alarm X X X

DiscreteInput 2545 R Off/On = 0/1 0-1 Unit 2 Valve ID Alarm X X X

DiscreteInput 2546 R Off/On = 0/1 0-1 Unit 2 Return Air Temperature Sensor 2 Alarm X

DiscreteInput 2547 R Off/On = 0/1 0-1 Unit 2 High Return Air Temperature 2 Alarm X

DiscreteInput 2548 R Off/On = 0/1 0-1 Unit 2 Mixed Air Temperature Sensor 2 Alarm X

DiscreteInput 2549 R Off/On = 0/1 0-1 Unit 2 Mixed Air High Temperature 2 Alarm

DiscreteInput 2550 R Off/On = 0/1 0-1 Unit 2 Mixed Air Low Temperature 2 Alarm

DiscreteInput 2551 R Off/On = 0/1 0-1 Unit 2 Supply Air Temperature Sensor 2 Alarm X

DiscreteInput 2552 R Off/On = 0/1 0-1 Unit 2 High Supply Air Temperature 2 Alarm

DiscreteInput 2553 R Off/On = 0/1 0-1 Unit 2 Low Supply Air Temperature 2 Alarm

DiscreteInput 2554 R Off/On = 0/1 0-1 Unit 2 Dust Sensor 2 Alarm

DiscreteInput 2555 R Off/On = 0/1 0-1 Unit 2 Dust Sensor High Dust Detection 2 Alarm

DiscreteInput 2556 R Off/On = 0/1 0-1 Unit 2 Liquid Line Temp Sensor 2 Alarm X

DiscreteInput 2557 R Off/On = 0/1 0-1 Unit 2 Liquid Line Pressure Sensor Alarm

DiscreteInput 2558 R Off/On = 0/1 0-1 Unit 2 Discharge Temp Sensor 2 Alarm

DiscreteInput 2559 R Off/On = 0/1 0-1 Unit 2 Discharge Pressure Sensor 2 Alarm X

DiscreteInput 2560 R Off/On = 0/1 0-1 Unit 2 Discharge Pressure Sensor 2 Alarm X

DiscreteInput 2561 R Off/On = 0/1 0-1 Unit 2 Suction Temperature Sensor 2 Alarm X

DiscreteInput 2562 R Off/On = 0/1 0-1 Unit 2 Suction Pressure Sensor 2 Alarm X

DiscreteInput 2563 R Off/On = 0/1 0-1 Unit 2 Low Pressure 2 Alarm X

DiscreteInput 2564 R Off/On = 0/1 0-1 Unit 2 High Pressure 2 Alarm X

DiscreteInput 2565 R Off/On = 0/1 0-1 Unit 2 Damper 2 Failed to Open X

DiscreteInput 2566 R Off/On = 0/1 0-1 Unit 2 Damper 2 Failed to Close X

DiscreteInput 2567 R Off/On = 0/1 0-1 Unit 2 Damper 3 Failed to Open X

DiscreteInput 2568 R Off/On = 0/1 0-1 Unit 2 Damper 3 Failed to Close X

DiscreteInput 2569 R Off/On = 0/1 0-1 Unit 2 Damper 4 Failed to Open

DiscreteInput 2570 R Off/On = 0/1 0-1 Unit 2 Damper 4 Failed to Close

DiscreteInput 2571 R Off/On = 0/1 0-1 Unit 2 Freeze Temperature Sensor Alarm X

DiscreteInput 2572 R Off/On = 0/1 0-1 Unit 2 Freeze Condition Alarm X

DiscreteInput 2573 R Off/On = 0/1 0-1 Unit 2 Blower Fail Alarm

DiscreteInput 2574 R Off/On = 0/1 0-1 Unit 2 Dirty Filter 2 Alarm

DiscreteInput 2575 R Off/On = 0/1 0-1 Unit 2 Dirty Filter 3 Alarm

DiscreteInput 2576 R Off/On = 0/1 0-1 Unit 2 Dirty Filter 4 Alarm

DiscreteInput 2577 R Off/On = 0/1 0-1 Unit 2 Dirty Condenser Coil 2 Alarm

Page 17: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 17 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

DiscreteInput 2578 R Off/On = 0/1 0-1 Unit 2 Power Loss 2 Detected Alarm

DiscreteInput 2579 R Off/On = 0/1 0-1 Unit 2 Low SuperHeat 2 Alarm X

DiscreteInput 2580 R Off/On = 0/1 0-1 Unit 2 Low Evaporation Pressure 2 Alarm X

DiscreteInput 2581 R Off/On = 0/1 0-1 Unit 2 High Evaporation Pressure 2 Alarm X

DiscreteInput 2582 R Off/On = 0/1 0-1 Unit 2 High Condenser Temperature 2 Alarm X

DiscreteInput 2583 R Off/On = 0/1 0-1 Unit 2 Low Suction pressure 2 Alarm X

DiscreteInput 2584 R Off/On = 0/1 0-1 Unit 2 EEV motor 2 error Alarm X

DiscreteInput 2585 R Off/On = 0/1 0-1 Unit 2 SelfTuning 2 error Alarm X

DiscreteInput 2586 R Off/On = 0/1 0-1 Unit 2 Emergency close 2 Alarm X

DiscreteInput 2587 R Off/On = 0/1 0-1 Unit 2 High Delta Temperature 2 Alarm

DiscreteInput 2588 R Off/On = 0/1 0-1 Unit 2 High Delta Pressure 2 Alarm

DiscreteInput 2589 R Off/On = 0/1 0-1 Unit 2 Range Error 2 Alarm X

DiscreteInput 2590 R Off/On = 0/1 0-1 Unit 2 Service Position Percent 2 Alarm X

DiscreteInput 2591 R Off/On = 0/1 0-1 Unit 2 Valve ID 2 Alarm X

DiscreteInput 2592 R Off/On = 0/1 0-1 Unit 2 Th-Tune Device Offline Alarm X

DiscreteInput 2593 R Off/On = 0/1 0-1 Unit 2 Th-Tune Temperature Probe Alarm X

DiscreteInput 2594 R Off/On = 0/1 0-1 Unit 2 Th-Tune Humidity Probe Alarm X

DiscreteInput 2595 R Off/On = 0/1 0-1 Unit 2 Th-Tune Clock Board Alarm X

DiscreteInput 2596 R Off/On = 0/1 0-1 Unit 2 cpCOe Offline Alarm X

DiscreteInput 2597 R Off/On = 0/1 0-1 Unit 2 Blower 1 Offline Alarm X

DiscreteInput 2598 R Off/On = 0/1 0-1 Unit 2 Blower 1 Alarm X

DiscreteInput 2599 R Off/On = 0/1 0-1 Unit 2 Blower 2 Offline Alarm

DiscreteInput 2600 R Off/On = 0/1 0-1 Unit 2 Blower 2 Alarm

DiscreteInput 2601 R Off/On = 0/1 0-1 Unit 2 Condenser 1 Offline Alarm X

DiscreteInput 2602 R Off/On = 0/1 0-1 Unit 2 Condenser 1 Alarm X

DiscreteInput 2603 R Off/On = 0/1 0-1 Unit 2 Condenser 2 Offline Alarm

DiscreteInput 2604 R Off/On = 0/1 0-1 Unit 2 Condenser 2 Alarm

DiscreteInput 2605 R Off/On = 0/1 0-1 Unit 2 Low Return Air Temperature 1 Alarm X

DiscreteInput 2606 R Off/On = 0/1 0-1 Unit 2 Low Return Air Temperature 2 Alarm X

DiscreteInput 2607 R Off/On = 0/1 0-1 Unit 2 Panel Open Alarm X

DiscreteInput 3000 R Off/On = 0/1 0-1 Unit 3 Dirty Filter 1 Alarm X X X

DiscreteInput 3001 R Off/On = 0/1 0-1 Unit 3 Dirty Filter 2 Alarm X

DiscreteInput 3002 R Off/On = 0/1 0-1 Unit 3 Dirty Filter 3 Alarm

DiscreteInput 3003 R Off/On = 0/1 0-1 Unit 3 Blower 1 is Running X X

InputRegister 3003 R 0-14 0-14 Unit 3 Compressor 1 Status X X X

DiscreteInput 3004 R Off/On = 0/1 0-1 Unit 3 Blower 2 Is Running

InputRegister 3004 R 0-14 0-14 Unit 3 Compressor 2 Status X

DiscreteInput 3005 R Off/On = 0/1 0-1 Unit 3 Low Pressure Switch 1 X

DiscreteInput 3006 R Off/On = 0/1 0-1 Unit 3 Low Pressure Switch 2

DiscreteInput 3007 R Off/On = 0/1 0-1 Unit 3 Damper Switch 1 Open X X X

DiscreteInput 3008 R Off/On = 0/1 0-1 Unit 3 Damper Switch 2 Open X

DiscreteInput 3009 R Off/On = 0/1 0-1 Unit 3 Damper Switch 3 Open X

DiscreteInput 3010 R Off/On = 0/1 0-1 Unit 3 Damper Switch 4 Open

InputRegister 3011 R ###.# NA Unit 3 Mixed Air Temperature Sensor 1 X X X

DiscreteInput 3012 R Off/On = 0/1 0-1 Unit 3 Activates Reheat Valve for Dehum X

InputRegister 3013 R ###.# NA Unit 3 Mixed Air Temperature Sensor 2 X

InputRegister 3014 R Zone1, 2, or 3 1-3 Unit 3 Zone Options X X X

InputRegister 3015 R ###.# NA Unit 3 Outdoor Air Temperature Sensor 1 X X X

InputRegister 3017 R ###.# NA Unit 3 Outdoor Air Temperature Sensor 2

Page 18: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 18 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

InputRegister 3019 R ###.# NA Unit 3 Return Air Temperature Sensor 1 X X X

InputRegister 3021 R ###.# NA Unit 3 Return Air Temperature Sensor 2 X

InputRegister 3023 R ###.# 0-100% Unit 3 Outdoor Humidity Sensor 1 X X

InputRegister 3025 R ###.# 0-100% Unit 3 Outdoor Humidity Sensor 2

InputRegister 3027 R ###.# NA Unit 3 Freeze Sensor 1 X

DiscreteInput 3029 R Off/On = 0/1 0-1 Unit 3 Heat 1 On/Off X X X

InputRegister 3029 R ###.# NA Unit 3 Freeze Sensor 2

DiscreteInput 3030 R Off/On = 0/1 0-1 Unit 3 Heat 2 On/Off X X X

DiscreteInput 3031 R Off/On = 0/1 0-1 Unit 3 Heat 3 On/Off X

DiscreteInput 3032 R Off/On = 0/1 0-1 Unit 3 Heat 4 On/Off

DiscreteInput 3033 R Off/On = 0/1 0-1 Unit 3 FreeCool Is Available X X X

DiscreteInput 3034 R Off/On = 0/1 0-1 Unit 3 Dirty Filter Indicator X X

InputRegister 3034 R ### 0-100% Unit 3 Blower Speed 1 X X

DiscreteInput 3035 R Off/On = 0/1 0-1 Unit 3 Cooling 1 On/Off X X X

InputRegister 3035 R ### 0-100% Unit 3 Blower Speed 2

DiscreteInput 3036 R Off/On = 0/1 0-1 Unit 3 Cooling 2 On/Off X X X

InputRegister 3036 R ### 0-45 bar Unit 3 Discharge Pressure Transducer 1

DiscreteInput 3037 R Off/On = 0/1 0-1 Unit 3 Cooling 3 On/Off X

InputRegister 3037 R ### 0-45 bar Unit 3 Discharge Pressure Transducer 2

DiscreteInput 3038 R Off/On = 0/1 0-1 Unit 3 Cooling 4 On/Off

InputRegister 3038 R ###.# NA Unit 3 Discharge Temperature 1

DiscreteInput 3039 R Off/On = 0/1 0-1 Unit 3 Indicates No Air Flow X X

InputRegister 3039 R ###.# NA Unit 3 Discharge Temperature 2

DiscreteInput 3040 R Off/On = 0/1 0-1 Unit 3 Indicates No Air Flow 2

InputRegister 3040 R ### 0-100% Unit 3 Dust Sensor 1 X X

DiscreteInput 3041 R Off/On = 0/1 0-1 Unit 3 High Pressure Event X X X

InputRegister 3041 R ### 0-100% Unit 3 Dust Sensor 2

DiscreteInput 3042 R Off/On = 0/1 0-1 Unit 3 High Pressure 2 Event X

DiscreteInput 3043 R Off/On = 0/1 0-1 Unit 3 Power Loss X X

DiscreteInput 3044 R Off/On = 0/1 0-1 Unit 3 Is Disabled (Power Off) X X X

InputRegister 3044 R ###.# NA Unit 3 Liquid Temperature 1 X X

InputRegister 3045 R ###.# NA Unit 3 Liquid Temperature 2 X

InputRegister 3046 R ### NA Unit 3 Liquid Pressure 1 X

InputRegister 3047 R ### NA Unit 3 Liquid Pressure 2

InputRegister 3048 R ### NA Unit 3 Suction Pressure 1 X X

InputRegister 3049 R ### NA Unit 3 Suction Pressure 2

InputRegister 3050 R ###.# NA Unit 3 Suction Temperature 1 X X

InputRegister 3051 R ###.# NA Unit 3 Suction Temperature 2

InputRegister 3052 R ###.# NA Unit 3 Supply Air Temperature 1 X X

InputRegister 3053 R ###.# NA Unit 3 Supply Air Temperature 2 X

InputRegister 3056 R ### 0-100% Unit 3 Condenser Fan Speed 1 X X

InputRegister 3057 R ### 0-100% Unit 3 Condenser Fan Speed 2 X

InputRegister 3058 R ### 0-100% Unit 3 Damper Position 1 X X X

InputRegister 3059 R ### 0-100% Unit 3 Damper Position 2 X

InputRegister 3060 R ### 0-100% Unit 3 Damper Position 3 X

InputRegister 3061 R ### 0-100% Unit 3 Damper Position 4 X

InputRegister 3062 R ### 0-100% Unit 3 EEV1 Position X X X

InputRegister 3063 R ### 0-100% Unit 3 EEV2 Position X

InputRegister 3064 R ### NA Unit 3 Declares number of Cooling Stages X X

Page 19: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 19 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

InputRegister 3065 R ### NA Unit 3 Declares number of Heating Stages X X

InputRegister 3066 R ### NA Unit 3 Declares number of Freecooling Stages X X

InputRegister 3067 R ### °F Unit 3 Outdoor Air Dewpoint X

InputRegister 3068 R ### 0,1,2,3 Unit 3 Dehumidification Type X X

InputRegister 3069 R ###.# NA Unit 3 Suction Saturation Temperature 1

InputRegister 3070 R ###.# NA Unit 3 Suction Saturation Temperature 2

InputRegister 3071 R ### NA Unit 3 Subcooling 1 X

InputRegister 3072 R ### NA Unit 3 Superheat 1

InputRegister 3073 R ### NA Unit 3 Superheat 2

InputRegister 3074 R ###.# NA Unit 3 Liquid Saturated Temperature 1

InputRegister 3075 R ###.# NA Unit 3 Liquid Saturated Temperature 2

InputRegister 3076 R ### NA Unit 3 Subcooling 2

InputRegister 3080 R ### NA Unit 3 Major Revision Number X X X

InputRegister 3081 R ### NA Unit 3 Minor Revision Number X X X

InputRegister 3082 R ### NA Unit 3 Bug Fixes X X X

InputRegister 3083 R ### NAUnit 3 How long the unit has been running in minutes

X X X

InputRegister 3084 R ## NA Unit 3 How many times unit has started X X X

InputRegister 3085 R ### NA Unit 3 How long the Fan is running in minutes X X

InputRegister 3086 R ## NA Unit 3 How many times Fan turned on X X

InputRegister 3087 R ### NA Unit 3 How long the Fan is running in minutes

InputRegister 3088 R ## NA Unit 3 How many times Fan turned on

InputRegister 3089 R ### NA Unit 3 How long the Blower is running in minutes X X X

InputRegister 3090 R ## NA Unit 3 How many times Blower turned on X X

InputRegister 3091 R ### NA Unit 3 How long the Blower is running in minutes

InputRegister 3092 R ## NA Unit 3 How many times Blower turned on

InputRegister 3093 R ### NA Unit 3 How long unit is running in Freecooling X X

InputRegister 3094 R ### NAUnit 3 How many times unit has been in Freecooling

X X

InputRegister 3095 R ### NA Unit 3 How long unit is running in Freecooling

InputRegister 3096 R ### NAUnit 3 How many times unit has been in Freecooling

InputRegister 3097 R ### NA Unit 3 How long unit is running in Cooling X X X

InputRegister 3098 R ### NA Unit 3 How many times unit has been in Cooling X X X

InputRegister 3099 R ### NA Unit 3 How long unit is running in Cooling X X

InputRegister 3100 R ### NA Unit 3 How many times unit has been in Cooling X X

InputRegister 3101 R ### NA Unit 3 How long unit is running in Cooling X

InputRegister 3102 R ### NA Unit 3 How many times unit has been in Cooling X

InputRegister 3103 R ### NA Unit 3 How long unit is running in Cooling

InputRegister 3104 R ### NA Unit 3 How many times unit has been in Cooling

InputRegister 3105 R ### NA Unit 3 How long unit is running in Heating X X X

InputRegister 3106 R ### NA Unit 3 How many times unit has been in Heating X X X

InputRegister 3107 R ### NA Unit 3 How long unit is running in Heating X X

InputRegister 3108 R ### NA Unit 3 How many times unit has been in Heating X X

InputRegister 3109 R ### NA Unit 3 How long unit is running in Heating

InputRegister 3110 R ### NA Unit 3 How many times unit has been in Heating

InputRegister 3111 R ### NA Unit 3 How long unit is running in Heating

InputRegister 3112 R ### NA Unit 3 How many times unit has been in Heating

InputRegister 3113 R ### 0-999999 Unit 3 life time in Hours (Update every Hour) X X X

InputRegister 3115 R ### 0-999999Unit 3 Blower 1 life time in Hours (Update every Hour)

X X

Page 20: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 20 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

InputRegister 3117 R ### 0-999999Unit 3 Blower 2 life time in Hours (Update every Hour)

InputRegister 3119 R ### 0-999999Unit 3 Fan 1 life time in hours (Update every Hour)

X

InputRegister 3121 R ### 0-999999Unit 3 Fan 2 life time in hours (Update every Hour)

InputRegister 3123 R ### 0-999999Unit 3 Cooling 1 life time in hours (Update ever Hour)

X X

InputRegister 3125 R ### 0-999999Unit 3 Cooling 2 life time in hours (Update ever Hour)

X

InputRegister 3127 R ### 0-999999Unit 3 Cooling 3 life time in hours (Update ever Hour)

InputRegister 3129 R ### 0-999999Unit 3 Cooling 4 life time in hours (Update ever Hour)

InputRegister 3131 R ### 0-999999Unit 3 Heating 1 life time in hours (Update ever Hour)

X X

InputRegister 3133 R ### 0-999999Unit 3 Heating 2 life time in hours (Update ever Hour)

InputRegister 3135 R ### 0-999999Unit 3 Heating 3 life time in hours (Update ever Hour)

InputRegister 3137 R ### 0-999999Unit 3 Heating 4 life time in hours (Update ever Hour)

InputRegister 3139 R ### 0-999999Unit 3 FreeCooling 1 life time in hours (Update ever Hour)

X X

InputRegister 3141 R ### 0-999999Unit 3 FreeCooling 2 life time in hours (Update ever Hour)

InputRegister 3143 R ### 0-5Unit 3 Indicates what unit types are running on the network

X X X

DiscreteInput 3500 R Off/On = 0/1 0-1Unit 3 Error in the number of retain memory writings Alarm

X X X

DiscreteInput 3501 R Off/On = 0/1 0-1 Unit 3 Error in retain memory writings Alarm X X X

DiscreteInput 3502 R Off/On = 0/1 0-1 Unit 3 Return Air Temperature Sensor Alarm X X X

DiscreteInput 3503 R Off/On = 0/1 0-1 Unit 3 High Return Air Temperature Alarm X X

DiscreteInput 3504 R Off/On = 0/1 0-1 Unit 3 Mixed Air Temperature Sensor Alarm X X

DiscreteInput 3505 R Off/On = 0/1 0-1 Unit 3 Mixed Air High Temperature Alarm X X

DiscreteInput 3506 R Off/On = 0/1 0-1 Unit 3 Mixed Air Low Temperature Alarm X X

DiscreteInput 3507 R Off/On = 0/1 0-1 Unit 3 Supply Air Temperature Sensor Alarm X X

DiscreteInput 3508 R Off/On = 0/1 0-1 Unit 3 High Supply Air Temperature Alarm X

DiscreteInput 3509 R Off/On = 0/1 0-1 Unit 3 Low Supply Air Temperature Alarm X

DiscreteInput 3510 R Off/On = 0/1 0-1 Unit 3 Outdoor Air Temperature Sensor Alarm X X X

DiscreteInput 3511 R Off/On = 0/1 0-1 Unit 3 Outdoor Air Humidity Sensor Alarm X X X

DiscreteInput 3512 R Off/On = 0/1 0-1 Unit 3 Dust Sensor Alarm X X

DiscreteInput 3513 R Off/On = 0/1 0-1 Unit 3 Dust Sensor High Dust Detection Alarm X X

DiscreteInput 3514 R Off/On = 0/1 0-1 Unit 3 Liquid Line Temp Sensor Alarm X X

DiscreteInput 3515 R Off/On = 0/1 0-1 Unit 3 Discharge Temp Sensor Alarm

DiscreteInput 3516 R Off/On = 0/1 0-1 Unit 3 Liquid Line Pressure Sensor Alarm X

DiscreteInput 3517 R Off/On = 0/1 0-1 Unit 3 Suction Temperature Sensor Alarm X X X

DiscreteInput 3518 R Off/On = 0/1 0-1 Unit 3 Suction Pressure Sensor Alarm X X X

DiscreteInput 3519 R Off/On = 0/1 0-1 Unit 3 Low Pressure Alarm X X X

DiscreteInput 3520 R Off/On = 0/1 0-1 Unit 3 High Pressure Alarm X X X

DiscreteInput 3521 R Off/On = 0/1 0-1 Unit 3 Damper Failed to Open Alarm X X X

DiscreteInput 3522 R Off/On = 0/1 0-1 Unit 3 Damper Failed to Close Alarm X X X

DiscreteInput 3523 R Off/On = 0/1 0-1 Unit 3 Freeze Temperature Sensor Alarm X X

DiscreteInput 3524 R Off/On = 0/1 0-1 Unit 3 Freeze Condition Alarm X X X

Page 21: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 21 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

DiscreteInput 3525 R Off/On = 0/1 0-1 Unit 3 Blower Fail Alarm X X

DiscreteInput 3526 R Off/On = 0/1 0-1 Unit 3 Dirty Filter 1 Alarm X X X

DiscreteInput 3527 R Off/On = 0/1 0-1 Unit 3 Dirty Condenser Coil Alarm

DiscreteInput 3528 R Off/On = 0/1 0-1 Unit 3 Emergency Ventilation Mode Active Alarm X X X

DiscreteInput 3529 R Off/On = 0/1 0-1 Unit 3 Emergency Cooling Mode Active Alarm X X X

DiscreteInput 3530 R Off/On = 0/1 0-1Unit 3 Extreme High Return Temp Alarm (Heat Cutout) Alarm

X X X

DiscreteInput 3531 R Off/On = 0/1 0-1 Unit 3 Disable/Smoke Detector Alarm X X X

DiscreteInput 3532 R Off/On = 0/1 0-1 Unit 3 Power Loss Detected Alarm X

DiscreteInput 3533 R Off/On = 0/1 0-1 Unit 3 Low SuperHeat Alarm X X X

DiscreteInput 3534 R Off/On = 0/1 0-1 Unit 3 Low Evaporation Pressure Alarm X X X

DiscreteInput 3535 R Off/On = 0/1 0-1 Unit 3 High Evaporation Pressure Alarm X X X

DiscreteInput 3536 R Off/On = 0/1 0-1 Unit 3 High Condenser Temperature Alarm X X X

DiscreteInput 3537 R Off/On = 0/1 0-1 Unit 3 Low Suction pressure Alarm X X X

DiscreteInput 3538 R Off/On = 0/1 0-1 Unit 3 EEV motor error Alarm X X X

DiscreteInput 3539 R Off/On = 0/1 0-1 Unit 3 SelfTuning error Alarm X X X

DiscreteInput 3540 R Off/On = 0/1 0-1 Unit 3 Emergency close Alarm X X X

DiscreteInput 3541 R Off/On = 0/1 0-1 Unit 3 High Delta Temperature Alarm

DiscreteInput 3542 R Off/On = 0/1 0-1 Unit 3 High Delta Pressure Alarm

DiscreteInput 3543 R Off/On = 0/1 0-1 Unit 3 Range Error Alarm X X X

DiscreteInput 3544 R Off/On = 0/1 0-1 Unit 3 Service Position Percent Alarm X X X

DiscreteInput 3545 R Off/On = 0/1 0-1 Unit 3 Valve ID Alarm X X X

DiscreteInput 3546 R Off/On = 0/1 0-1 Unit 3 Return Air Temperature Sensor 2 Alarm X

DiscreteInput 3547 R Off/On = 0/1 0-1 Unit 3 High Return Air Temperature 2 Alarm X

DiscreteInput 3548 R Off/On = 0/1 0-1 Unit 3 Mixed Air Temperature Sensor 2 Alarm X

DiscreteInput 3549 R Off/On = 0/1 0-1 Unit 3 Mixed Air High Temperature 2 Alarm

DiscreteInput 3550 R Off/On = 0/1 0-1 Unit 3 Mixed Air Low Temperature 2 Alarm

DiscreteInput 3551 R Off/On = 0/1 0-1 Unit 3 Supply Air Temperature Sensor 2 Alarm X

DiscreteInput 3552 R Off/On = 0/1 0-1 Unit 3 High Supply Air Temperature 2 Alarm

DiscreteInput 3553 R Off/On = 0/1 0-1 Unit 3 Low Supply Air Temperature 2 Alarm

DiscreteInput 3554 R Off/On = 0/1 0-1 Unit 3 Dust Sensor 2 Alarm

DiscreteInput 3555 R Off/On = 0/1 0-1 Unit 3 Dust Sensor High Dust Detection 2 Alarm

DiscreteInput 3556 R Off/On = 0/1 0-1 Unit 3 Liquid Line Temp Sensor 2 Alarm X

DiscreteInput 3557 R Off/On = 0/1 0-1 Unit 3 Liquid Line Pressure Sensor 2 Alarm

DiscreteInput 3558 R Off/On = 0/1 0-1 Unit 3 Discharge Temp Sensor 2 Alarm

DiscreteInput 3559 R Off/On = 0/1 0-1 Unit 3 Discharge Pressure Sensor 2 Alarm X

DiscreteInput 3560 R Off/On = 0/1 0-1 Unit 3 Discharge Pressure Sensor 2 Alarm X

DiscreteInput 3561 R Off/On = 0/1 0-1 Unit 3 Suction Temperature Sensor 2 Alarm X

DiscreteInput 3562 R Off/On = 0/1 0-1 Unit 3 Suction Pressure Sensor 2 Alarm X

DiscreteInput 3563 R Off/On = 0/1 0-1 Unit 3 Low Pressure 2 Alarm X

DiscreteInput 3564 R Off/On = 0/1 0-1 Unit 3 High Pressure 2 Alarm X

DiscreteInput 3565 R Off/On = 0/1 0-1 Unit 3 Damper 2 Failed to Open Alarm X

DiscreteInput 3566 R Off/On = 0/1 0-1 Unit 3 Damper 2 Failed to Close Alarm X

DiscreteInput 3567 R Off/On = 0/1 0-1 Unit 3 Damper 3 Failed to Open Alarm X

DiscreteInput 3568 R Off/On = 0/1 0-1 Unit 3 Damper 3 Failed to Close Alarm X

DiscreteInput 3569 R Off/On = 0/1 0-1 Unit 3 Damper 4 Failed to Open Alarm

DiscreteInput 3570 R Off/On = 0/1 0-1 Unit 3 Damper 4 Failed to Close Alarm

DiscreteInput 3571 R Off/On = 0/1 0-1 Unit 3 Freeze Temperature Sensor 2 Alarm X

DiscreteInput 3572 R Off/On = 0/1 0-1 Unit 3 Freeze 2 Condition Alarm X

Page 22: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 22 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

DiscreteInput 3573 R Off/On = 0/1 0-1 Unit 3 Blower 2 Fail Alarm

DiscreteInput 3574 R Off/On = 0/1 0-1 Unit 3 Dirty Filter 2 Alarm

DiscreteInput 3575 R Off/On = 0/1 0-1 Unit 3 Dirty Filter 3 Alarm

DiscreteInput 3576 R Off/On = 0/1 0-1 Unit 3 Dirty Filter 4 Alarm

DiscreteInput 3577 R Off/On = 0/1 0-1 Unit 3 Dirty Condenser Coil 2 Alarm

DiscreteInput 3578 R Off/On = 0/1 0-1 Unit 3 Power Loss 2 Detected Alarm

DiscreteInput 3579 R Off/On = 0/1 0-1 Unit 3 Low SuperHeat 2 Alarm X

DiscreteInput 3580 R Off/On = 0/1 0-1 Unit 3 Low Evaporation Pressure 2 Alarm X

DiscreteInput 3581 R Off/On = 0/1 0-1 Unit 3 High Evaporation Pressure 2 Alarm X

DiscreteInput 3582 R Off/On = 0/1 0-1 Unit 3 High Condenser Temperature 2 Alarm X

DiscreteInput 3583 R Off/On = 0/1 0-1 Unit 3 Low Suction pressure 2 Alarm X

DiscreteInput 3584 R Off/On = 0/1 0-1 Unit 3 EEV motor 2 error Alarm X

DiscreteInput 3585 R Off/On = 0/1 0-1 Unit 3 SelfTuning 2 error Alarm X

DiscreteInput 3586 R Off/On = 0/1 0-1 Unit 3 Emergency close 2 Alarm X

DiscreteInput 3587 R Off/On = 0/1 0-1 Unit 3 High Delta Temperature 2 Alarm

DiscreteInput 3588 R Off/On = 0/1 0-1 Unit 3 High Delta Pressure 2 Alarm

DiscreteInput 3589 R Off/On = 0/1 0-1 Unit 3 Range Error 2 Alarm X

DiscreteInput 3590 R Off/On = 0/1 0-1 Unit 3 Service Position Percent 2 Alarm X

DiscreteInput 3591 R Off/On = 0/1 0-1 Unit 3 Valve ID 2 Alarm X

DiscreteInput 3592 R Off/On = 0/1 0-1 Unit 3 Th-Tune Device Offline Alarm X

DiscreteInput 3593 R Off/On = 0/1 0-1 Unit 3 Th-Tune Temperature Probe Alarm X

DiscreteInput 3594 R Off/On = 0/1 0-1 Unit 3 Th-Tune Humidity Probe Alarm X

DiscreteInput 3595 R Off/On = 0/1 0-1 Unit 3 Th-Tune Clock Board Alarm X

DiscreteInput 3596 R Off/On = 0/1 0-1 Unit 3 cpCOe Offline Alarm X

DiscreteInput 3597 R Off/On = 0/1 0-1 Unit 3 Blower 1 Offline Alarm X

DiscreteInput 3598 R Off/On = 0/1 0-1 Unit 3 Blower 1 Alarm X

DiscreteInput 3599 R Off/On = 0/1 0-1 Unit 3 Blower 2 Offline Alarm

DiscreteInput 3600 R Off/On = 0/1 0-1 Unit 3 Blower 2 Alarm

DiscreteInput 3601 R Off/On = 0/1 0-1 Unit 3 Condenser 1 Offline Alarm X

DiscreteInput 3602 R Off/On = 0/1 0-1 Unit 3 Condenser 1 Alarm X

DiscreteInput 3603 R Off/On = 0/1 0-1 Unit 3 Condenser 2 Offline Alarm

DiscreteInput 3604 R Off/On = 0/1 0-1 Unit 3 Condenser 2 Alarm

DiscreteInput 3605 R Off/On = 0/1 0-1 Unit 3 Low Return Air Temperature Alarm X

DiscreteInput 3606 R Off/On = 0/1 0-1 Unit 3 Low Return Air Temperature 2 Alarm X

DiscreteInput 3607 R Off/On = 0/1 0-1 Unit 3 Panel Open Alarm X

DiscreteInput 4000 R Off/On = 0/1 0-1 Unit 4 Dirty Filter 1 Alarm X X X

DiscreteInput 4001 R Off/On = 0/1 0-1 Unit 4 Dirty Filter 2 Alarm X

DiscreteInput 4002 R Off/On = 0/1 0-1 Unit 4 Dirty Filter 3 Alarm

DiscreteInput 4003 R Off/On = 0/1 0-1 Unit 4 Blower Is Running X X

InputRegister 4003 R 0-14 0-14 Unit 4 Compressor 1 Status X X X

DiscreteInput 4004 R Off/On = 0/1 0-1 Unit 4 Blower 2 Is Running

InputRegister 4004 R 0-14 0-14 Unit 4 Compressor 2 Status X

DiscreteInput 4005 R Off/On = 0/1 0-1 Unit 4 Low Pressure Switch 1 X

DiscreteInput 4006 R Off/On = 0/1 0-1 Unit 4 Low Pressure Switch 2

DiscreteInput 4007 R Off/On = 0/1 0-1 Unit 4 Damper Switch 1 Open X X X

DiscreteInput 4008 R Off/On = 0/1 0-1 Unit 4 Damper Switch 2 Open X

DiscreteInput 4009 R Off/On = 0/1 0-1 Unit 4 Damper Switch 3 Open X

DiscreteInput 4010 R Off/On = 0/1 0-1 Unit 4 Damper Switch 4 Open

InputRegister 4011 R ###.# NA Unit 4 Mixed Air Temperature Sensor 1 X X X

Page 23: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 23 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

DiscreteInput 4012 R Off/On = 0/1 0-1 Unit 4 Activates Reheat Valve for Dehum X

InputRegister 4013 R ###.# NA Unit 4 Mixed Air Temperature Sensor 2 X

InputRegister 4014 R Zone1, 2, or 3 1-3 Unit 4 Zone Options X X X

InputRegister 4015 R ###.# NA Unit 4 Outdoor Air Temperature Sensor 1 X X X

InputRegister 4017 R ###.# NA Unit 4 Outdoor Air Temperature Sensor 2

InputRegister 4019 R ###.# NA Unit 4 Return Air Temperature Sensor 1 X X X

InputRegister 4021 R ###.# NA Unit 4 Return Air Temperature Sensor 2 X

InputRegister 4023 R ###.# 0-100% Unit 4 Outdoor Humidity Sensor 1 X X

InputRegister 4025 R ###.# 0-100% Unit 4 Outdoor Humidity Sensor 2

InputRegister 4027 R ###.# NA Unit 4 Freeze Sensor 1 X

DiscreteInput 4029 R Off/On = 0/1 0-1 Unit 4 Heat 1 On/Off X X X

InputRegister 4029 R ###.# NA Unit 4 Freeze Sensor 2

DiscreteInput 4030 R Off/On = 0/1 0-1 Unit 4 Heat 2 On/Off X X X

DiscreteInput 4031 R Off/On = 0/1 0-1 Unit 4 Heat 3 On/Off X

DiscreteInput 4032 R Off/On = 0/1 0-1 Unit 4 Heat 4 On/Off

DiscreteInput 4033 R Off/On = 0/1 0-1 Unit 4 FreeCool Is Available X X X

DiscreteInput 4034 R Off/On = 0/1 0-1 Unit 4 Dirty Filter Indicator X X

InputRegister 4034 R ### 0-100% Unit 4 Blower Speed 1 X X

DiscreteInput 4035 R Off/On = 0/1 0-1 Unit 4 Cooling 1 On/Off X X X

InputRegister 4035 R ### 0-100% Unit 4 Blower Speed 2

DiscreteInput 4036 R Off/On = 0/1 0-1 Unit 4 Cooling 2 On/Off X X X

InputRegister 4036 R ### 0-45 bar Unit 4 Discharge Pressure Transducer 1

DiscreteInput 4037 R Off/On = 0/1 0-1 Unit 4 Cooling 3 On/Off X

InputRegister 4037 R ### 0-45 bar Unit 4 Discharge Pressure Transducer 2

DiscreteInput 4038 R Off/On = 0/1 0-1 Unit 4 Cooling 4 On/Off

InputRegister 4038 R ###.# NA Unit 4 Discharge Temperature 1

DiscreteInput 4039 R Off/On = 0/1 0-1 Unit 4 Indicates No Air Flow X X

InputRegister 4039 R ###.# NA Unit 4 Discharge Temperature 2

DiscreteInput 4040 R Off/On = 0/1 0-1 Unit 4 Indicates No Air 2 Flow

InputRegister 4040 R ### 0-100% Unit 4 Dust Sensor 1 X X

DiscreteInput 4041 R Off/On = 0/1 0-1 Unit 4 High Pressure Event X X X

InputRegister 4041 R ### 0-100% Unit 4 Dust Sensor 2

DiscreteInput 4042 R Off/On = 0/1 0-1 Unit 4 High Pressure 2 Event X

DiscreteInput 4043 R Off/On = 0/1 0-1 Unit 4 Power Loss Detected Alarm X X

DiscreteInput 4044 R Off/On = 0/1 0-1 Unit 4 Is Disabled X X X

InputRegister 4044 R ###.# NA Unit 4 Liquid Temperature 1 X X

InputRegister 4045 R ###.# NA Unit 4 Liquid Temperature 2 X

InputRegister 4046 R ### NA Unit 4 Liquid Pressure 1 X

InputRegister 4047 R ### NA Unit 4 Liquid Pressure 2

InputRegister 4048 R ### NA Unit 4 Suction Pressure 1 X X

InputRegister 4049 R ### NA Unit 4 Suction Pressure 2

InputRegister 4050 R ###.# NA Unit 4 Suction Temperature 1 X X

InputRegister 4051 R ###.# NA Unit 4 Suction Temperature 2

InputRegister 4052 R ###.# NA Unit 4 Supply Air Temperature 1 X X

InputRegister 4053 R ###.# NA Unit 4 Supply Air Temperature 2 X

InputRegister 4056 R ### 0-100% Unit 4 Condenser Fan Speed 1 X X

InputRegister 4057 R ### 0-100% Unit 4 Condenser Fan Speed 2 X

InputRegister 4058 R ### 0-100% Unit 4 Damper Position 1 X X X

InputRegister 4059 R ### 0-100% Unit 4 Damper Position 2 X

Page 24: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 24 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

InputRegister 4060 R ### 0-100% Unit 4 Damper Position 3 X

InputRegister 4061 R ### 0-100% Unit 4 Damper Position 4 X

InputRegister 4062 R ### 0-100% Unit 4 EEV1 Position X X X

InputRegister 4063 R ### 0-100% Unit 4 EEV2 Position X

InputRegister 4064 R ### NA Unit 4 Declares number of Cooling Stages X X

InputRegister 4065 R ### NA Unit 4 Declares number of Heating Stages X X

InputRegister 4066 R ### NA Unit 4 Declares number of Freecooling Stages X X

InputRegister 4067 R ### °F Unit 4 Outdoor Air Dewpoint X

InputRegister 4068 R ### 0,1,2,3 Unit 4 Dehumidification Type X X

InputRegister 4069 R ###.# NA Unit 4 Suction Saturation Temperature 1

InputRegister 4070 R ###.# NA Unit 4 Suction Saturation Temperature 2

InputRegister 4071 R ### NA Unit 4 Subcooling 1 X

InputRegister 4072 R ### NA Unit 4 Superheat 1

InputRegister 4073 R ### NA Unit 4 Superheat 2

InputRegister 4074 R ###.# NA Unit 4 Liquid Saturated Temperature 1

InputRegister 4075 R ###.# NA Unit 4 Liquid Saturated Temperature 2

InputRegister 4076 R ### NA Unit 4 Subcooling 2

InputRegister 4080 R ### NA Unit 4 Major Revision Number X X X

InputRegister 4081 R ### NA Unit 4 Minor Revision Number X X X

InputRegister 4082 R ### NA Unit 4 Bug Fixes X X X

InputRegister 4083 R ### NAUnit 4 How long the unit has been running in minutes

X X X

InputRegister 4084 R ## NA Unit 4 How many times unit has started X X X

InputRegister 4085 R ### NA Unit 4 How long the Fan is running in minutes X X

InputRegister 4086 R ## NA Unit 4 How many times Fan turned on X X

InputRegister 4087 R ### NA Unit 4 How long the Fan is running in minutes

InputRegister 4088 R ## NA Unit 4 How many times Fan turned on

InputRegister 4089 R ### NA Unit 4 How long the Blower is running in minutes X X X

InputRegister 4090 R ## NA Unit 4 How many times Blower turned on X X

InputRegister 4091 R ### NA Unit 4 How long the Blower is running in minutes

InputRegister 4092 R ## NA Unit 4 How many times Blower turned on

InputRegister 4093 R ### NA Unit 4 How long unit is running in Freecooling X X

InputRegister 4094 R ### NAUnit 4 How many times unit has been in Freecooling

X X

InputRegister 4095 R ### NA Unit 4 How long unit is running in Freecooling

InputRegister 4096 R ### NAUnit 4 How many times unit has been in Freecooling

InputRegister 4097 R ### NA Unit 4 How long unit is running in Cooling X X X

InputRegister 4098 R ### NA Unit 4 How many times unit has been in Cooling X X X

InputRegister 4099 R ### NA Unit 4 How long unit is running in Cooling X X

InputRegister 4100 R ### NA Unit 4 How many times unit has been in Cooling X X

InputRegister 4101 R ### NA Unit 4 How long unit is running in Cooling X

InputRegister 4102 R ### NA Unit 4 How many times unit has been in Cooling X

InputRegister 4103 R ### NA Unit 4 How long unit is running in Cooling

InputRegister 4104 R ### NA Unit 4 How many times unit has been in Cooling

InputRegister 4105 R ### NA Unit 4 How long unit is running in Heating X X X

InputRegister 4106 R ### NA Unit 4 How many times unit has been in Heating X X X

InputRegister 4107 R ### NA Unit 4 How long unit is running in Heating X X

InputRegister 4108 R ### NA Unit 4 How many times unit has been in Heating X X

InputRegister 4109 R ### NA Unit 4 How long unit is running in Heating

Page 25: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 25 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

InputRegister 4110 R ### NA Unit 4 How many times unit has been in Heating

InputRegister 4111 R ### NA Unit 4 How long unit is running in Heating

InputRegister 4112 R ### NA Unit 4 How many times unit has been in Heating

InputRegister 4113 R ### 0-999999 Unit 4 life time in Hours (Update every Hour) X X X

InputRegister 4115 R ### 0-999999Unit 4 Blower 1 life time in Hours (Update every Hour)

X X

InputRegister 4117 R ### 0-999999Unit 4 Blower 2 life time in Hours (Update every Hour)

InputRegister 4119 R ### 0-999999Unit 4 Fan 1 life time in hours (Update every Hour)

X

InputRegister 4121 R ### 0-999999Unit 4 Fan 2 life time in hours (Update every Hour)

InputRegister 4123 R ### 0-999999Unit 4 Cooling 1 life time in hours (Update ever Hour)

X X

InputRegister 4125 R ### 0-999999Unit 4 Cooling 2 life time in hours (Update ever Hour)

X

InputRegister 4127 R ### 0-999999Unit 4 Cooling 3 life time in hours (Update ever Hour)

InputRegister 4129 R ### 0-999999Unit 4 Cooling 4 life time in hours (Update ever Hour)

InputRegister 4131 R ### 0-999999Unit 4 Heating 1 life time in hours (Update ever Hour)

X X

InputRegister 4133 R ### 0-999999Unit 4 Heating 2 life time in hours (Update ever Hour)

InputRegister 4135 R ### 0-999999Unit 4 Heating 3 life time in hours (Update ever Hour)

InputRegister 4137 R ### 0-999999Unit 4 Heating 4 life time in hours (Update ever Hour)

InputRegister 4139 R ### 0-999999Unit 4 FreeCooling 1 life time in hours (Update ever Hour)

X X

InputRegister 4141 R ### 0-999999Unit 4 FreeCooling 2 life time in hours (Update ever Hour)

InputRegister 4143 R ### 0-5Unit 4 Indicates what unit types are running on the network

X X X

DiscreteInput 4500 R Off/On = 0/1 0-1Unit 4 Error in the number of retain memory writings Alarm

X X X

DiscreteInput 4501 R Off/On = 0/1 0-1 Unit 4 Error in retain memory writings Alarm X X X

DiscreteInput 4502 R Off/On = 0/1 0-1 Unit 4 Return Air Temperature Sensor Alarm X X X

DiscreteInput 4503 R Off/On = 0/1 0-1 Unit 4 High Return Air Temperature Alarm X X

DiscreteInput 4504 R Off/On = 0/1 0-1 Unit 4 Mixed Air Temperature Sensor Alarm X X

DiscreteInput 4505 R Off/On = 0/1 0-1 Unit 4 Mixed Air High Temperature X X

DiscreteInput 4506 R Off/On = 0/1 0-1 Unit 4 Mixed Air Low Temperature X X

DiscreteInput 4507 R Off/On = 0/1 0-1 Unit 4 Supply Air Temperature Sensor Alarm X X

DiscreteInput 4508 R Off/On = 0/1 0-1 Unit 4 High Supply Air Temperature Alarm X

DiscreteInput 4509 R Off/On = 0/1 0-1 Unit 4 Low Supply Air Temperature Alarm X

DiscreteInput 4510 R Off/On = 0/1 0-1 Unit 4 Outdoor Air Temperature Sensor Alarm X X X

DiscreteInput 4511 R Off/On = 0/1 0-1 Unit 4 Outdoor Air Humidity Sensor Alarm X X X

DiscreteInput 4512 R Off/On = 0/1 0-1 Unit 4 Dust Sensor Alarm X X

DiscreteInput 4513 R Off/On = 0/1 0-1 Unit 4 Dust Sensor High Dust Detection Alarm X X

DiscreteInput 4514 R Off/On = 0/1 0-1 Unit 4 Liquid Line Temp Sensor Alarm X X

DiscreteInput 4515 R Off/On = 0/1 0-1 Unit 4 Discharge Temp Sensor Alarm

DiscreteInput 4516 R Off/On = 0/1 0-1 Unit 4 Liquid Line Pressure Sensor Alarm X

DiscreteInput 4517 R Off/On = 0/1 0-1 Unit 4 Suction Temperature Sensor Alarm X X X

DiscreteInput 4518 R Off/On = 0/1 0-1 Unit 4 Suction Pressure Sensor Alarm X X X

DiscreteInput 4519 R Off/On = 0/1 0-1 Unit 4 Low Pressure Alarm X X X

Page 26: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 26 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

DiscreteInput 4520 R Off/On = 0/1 0-1 Unit 4 High Pressure Alarm X X X

DiscreteInput 4521 R Off/On = 0/1 0-1 Unit 4 Damper Failed to Open Alarm X X X

DiscreteInput 4522 R Off/On = 0/1 0-1 Unit 4 Damper Failed to Close Alarm X X X

DiscreteInput 4523 R Off/On = 0/1 0-1 Unit 4 Freeze Temperature Sensor Alarm X X

DiscreteInput 4524 R Off/On = 0/1 0-1 Unit 4 Freeze Condition Alarm X X X

DiscreteInput 4525 R Off/On = 0/1 0-1 Unit 4 Blower Fail Alarm X X

DiscreteInput 4526 R Off/On = 0/1 0-1 Unit 4 Dirty Filter 1 Alarm X X X

DiscreteInput 4527 R Off/On = 0/1 0-1 Unit 4 Dirty Condenser Coil Alarm

DiscreteInput 4528 R Off/On = 0/1 0-1 Unit 4 Emergency Ventilation Mode Active Alarm X X X

DiscreteInput 4529 R Off/On = 0/1 0-1 Unit 4 Emergency Cooling Mode Active Alarm X X X

DiscreteInput 4530 R Off/On = 0/1 0-1Unit 4 Extreme High Return Temp Alarm (Heat Cutout) Alarm

X X X

DiscreteInput 4531 R Off/On = 0/1 0-1 Unit 4 Disable/Smoke Detector Alarm X X X

DiscreteInput 4532 R Off/On = 0/1 0-1 Unit 4 Power Loss Detected Alarm X

DiscreteInput 4533 R Off/On = 0/1 0-1 Unit 4 Low SuperHeat Alarm X X X

DiscreteInput 4534 R Off/On = 0/1 0-1 Unit 4 Low Evaporation Pressure Alarm X X X

DiscreteInput 4535 R Off/On = 0/1 0-1 Unit 4 High Evaporation Pressure Alarm X X X

DiscreteInput 4536 R Off/On = 0/1 0-1 Unit 4 High Condenser Temperature Alarm X X X

DiscreteInput 4537 R Off/On = 0/1 0-1 Unit 4 Low Suction pressure Alarm X X X

DiscreteInput 4538 R Off/On = 0/1 0-1 Unit 4 EEV motor error Alarm X X X

DiscreteInput 4539 R Off/On = 0/1 0-1 Unit 4 SelfTuning error Alarm X X X

DiscreteInput 4540 R Off/On = 0/1 0-1 Unit 4 Emergency close Alarm X X X

DiscreteInput 4541 R Off/On = 0/1 0-1 Unit 4 High Delta Temperature Alarm

DiscreteInput 4542 R Off/On = 0/1 0-1 Unit 4 High Delta Pressure Alarm

DiscreteInput 4543 R Off/On = 0/1 0-1 Unit 4 Range Error Alarm X X X

DiscreteInput 4544 R Off/On = 0/1 0-1 Unit 4 Service Position Percent Alarm X X X

DiscreteInput 4545 R Off/On = 0/1 0-1 Unit 4 Valve ID Alarm X X X

DiscreteInput 4546 R Off/On = 0/1 0-1 Unit 4 Return Air Temperature Sensor 2 Alarm X

DiscreteInput 4547 R Off/On = 0/1 0-1 Unit 4 High Return Air Temperature 2 Alarm X

DiscreteInput 4548 R Off/On = 0/1 0-1 Unit 4 Mixed Air Temperature Sensor 2 Alarm X

DiscreteInput 4549 R Off/On = 0/1 0-1 Unit 4 Mixed Air High Temperature 2 Alarm

DiscreteInput 4550 R Off/On = 0/1 0-1 Unit 4 Mixed Air Low Temperature 2 Alarm

DiscreteInput 4551 R Off/On = 0/1 0-1 Unit 4 Supply Air Temperature Sensor 2 Alarm X

DiscreteInput 4552 R Off/On = 0/1 0-1 Unit 4 High Supply Air Temperature 2 Alarm

DiscreteInput 4553 R Off/On = 0/1 0-1 Unit 4 Low Supply Air Temperature 2 Alarm

DiscreteInput 4554 R Off/On = 0/1 0-1 Unit 4 Dust Sensor 2 Alarm

DiscreteInput 4555 R Off/On = 0/1 0-1 Unit 4 Dust Sensor High Dust Detection 2 Alarm

DiscreteInput 4556 R Off/On = 0/1 0-1 Unit 4 Liquid Line Temp Sensor 2 Alarm X

DiscreteInput 4557 R Off/On = 0/1 0-1 Unit 4 Liquid Line Pressure Sensor 2 Alarm

DiscreteInput 4558 R Off/On = 0/1 0-1 Unit 4 Discharge Temp Sensor 2 Alarm

DiscreteInput 4559 R Off/On = 0/1 0-1 Unit 4 Discharge Pressure Sensor 2 Alarm X

DiscreteInput 4560 R Off/On = 0/1 0-1 Unit 4 Discharge Pressure Sensor 2 Alarm X

DiscreteInput 4561 R Off/On = 0/1 0-1 Unit 4 Suction Temperature Sensor 2 Alarm X

DiscreteInput 4562 R Off/On = 0/1 0-1 Unit 4 Suction Pressure Sensor 2 Alarm X

DiscreteInput 4563 R Off/On = 0/1 0-1 Unit 4 Low Pressure 2 Alarm X

DiscreteInput 4564 R Off/On = 0/1 0-1 Unit 4 High Pressure 2 Alarm X

DiscreteInput 4565 R Off/On = 0/1 0-1 Unit 4 Damper 2 Failed to Open Alarm X

DiscreteInput 4566 R Off/On = 0/1 0-1 Unit 4 Damper 2 Failed to Close Alarm X

DiscreteInput 4567 R Off/On = 0/1 0-1 Unit 4 Damper 3 Failed to Open Alarm X

Page 27: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 27 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

DiscreteInput 4568 R Off/On = 0/1 0-1 Unit 4 Damper 3 Failed to Close Alarm X

DiscreteInput 4569 R Off/On = 0/1 0-1 Unit 4 Damper 4 Failed to Open Alarm

DiscreteInput 4570 R Off/On = 0/1 0-1 Unit 4 Damper 4 Failed to Close Alarm

DiscreteInput 4571 R Off/On = 0/1 0-1 Unit 4 Freeze Temperature Sensor 2 Alarm X

DiscreteInput 4572 R Off/On = 0/1 0-1 Unit 4 Freeze Condition Alarm X

DiscreteInput 4573 R Off/On = 0/1 0-1 Unit 4 Blower Fail Alarm

DiscreteInput 4574 R Off/On = 0/1 0-1 Unit 4 Dirty Filter 2 Alarm

DiscreteInput 4575 R Off/On = 0/1 0-1 Unit 4 Dirty Filter 3 Alarm

DiscreteInput 4576 R Off/On = 0/1 0-1 Unit 4 Dirty Filter 4 Alarm

DiscreteInput 4577 R Off/On = 0/1 0-1 Unit 4 Dirty Condenser Coil 2 Alarm

DiscreteInput 4578 R Off/On = 0/1 0-1 Unit 4 Power Loss 2 Detected Alarm

DiscreteInput 4579 R Off/On = 0/1 0-1 Unit 4 Low SuperHeat 2 Alarm X

DiscreteInput 4580 R Off/On = 0/1 0-1 Unit 4 Low Evaporation Pressure 2 Alarm X

DiscreteInput 4581 R Off/On = 0/1 0-1 Unit 4 High Evaporation Pressure 2 Alarm X

DiscreteInput 4582 R Off/On = 0/1 0-1 Unit 4 High Condenser Temperature 2 Alarm X

DiscreteInput 4583 R Off/On = 0/1 0-1 Unit 4 Low Suction pressure 2 Alarm X

DiscreteInput 4584 R Off/On = 0/1 0-1 Unit 4 EEV motor error 2 Alarm X

DiscreteInput 4585 R Off/On = 0/1 0-1 Unit 4 SelfTuning error 2 Alarm X

DiscreteInput 4586 R Off/On = 0/1 0-1 Unit 4 Emergency close 2 Alarm X

DiscreteInput 4587 R Off/On = 0/1 0-1 Unit 4 High Delta Temperature 2 Alarm

DiscreteInput 4588 R Off/On = 0/1 0-1 Unit 4 High Delta Pressure 2 Alarm

DiscreteInput 4589 R Off/On = 0/1 0-1 Unit 4 Range Error 2 Alarm X

DiscreteInput 4590 R Off/On = 0/1 0-1 Unit 4 Service Position Percent 2 Alarm X

DiscreteInput 4591 R Off/On = 0/1 0-1 Unit 4 Valve ID 2 Alarm X

DiscreteInput 4592 R Off/On = 0/1 0-1 Unit 4 Th-Tune Device Offline Alarm X

DiscreteInput 4593 R Off/On = 0/1 0-1 Unit 4 Th-Tune Temperature Probe Alarm X

DiscreteInput 4594 R Off/On = 0/1 0-1 Unit 4 Th-Tune Humidity Probe Alarm X

DiscreteInput 4595 R Off/On = 0/1 0-1 Unit 4 Th-Tune Clock Board Alarm X

DiscreteInput 4596 R Off/On = 0/1 0-1 Unit 4 cpCOe Offline Alarm X

DiscreteInput 4597 R Off/On = 0/1 0-1 Unit 4 Blower 1 Offline Alarm X

DiscreteInput 4598 R Off/On = 0/1 0-1 Unit 4 Blower 1 Alarm X

DiscreteInput 4599 R Off/On = 0/1 0-1 Unit 4 Blower 2 Offline Alarm

DiscreteInput 4600 R Off/On = 0/1 0-1 Unit 4 Blower 2 Alarm

DiscreteInput 4601 R Off/On = 0/1 0-1 Unit 4 Condenser 1 Offline Alarm X

DiscreteInput 4602 R Off/On = 0/1 0-1 Unit 4 Condenser 1 Alarm X

DiscreteInput 4603 R Off/On = 0/1 0-1 Unit 4 Condenser 2 Offline Alarm

DiscreteInput 4604 R Off/On = 0/1 0-1 Unit 4 Condenser 2 Alarm

DiscreteInput 4605 R Off/On = 0/1 0-1 Unit 4 Low Return Air Temperature Alarm X

DiscreteInput 4606 R Off/On = 0/1 0-1 Unit 4 Low Return Air Temperature 2 Alarm X

DiscreteInput 4607 R Off/On = 0/1 0-1 Unit 4 Panel Open Alarm X

DiscreteInput 5000 R Off/On = 0/1 0-1 Unit 5 Dirty Filter 1 Alarm X X X

DiscreteInput 5001 R Off/On = 0/1 0-1 Unit 5 Dirty Filter 2 Alarm X

DiscreteInput 5002 R Off/On = 0/1 0-1 Unit 5 Dirty Filter 3 Alarm

DiscreteInput 5003 R Off/On = 0/1 0-1 Unit 5 Indicates Blower 1 Is Running In Unit X X

InputRegister 5003 R 0-14 0-14 Unit 5 Compressor 1 Status X X X

DiscreteInput 5004 R Off/On = 0/1 0-1 Unit 5 Indicates Blower 2 Is Running In Unit

InputRegister 5004 R 0-14 0-14 Unit 5 Compressor 2 Status X

DiscreteInput 5005 R Off/On = 0/1 0-1 Unit 5 Low Pressure Switch 1 X

DiscreteInput 5006 R Off/On = 0/1 0-1 Unit 5 Low Pressure Switch 2

Page 28: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 28 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

DiscreteInput 5007 R Off/On = 0/1 0-1 Unit 5 Damper Switch 1 Open X X X

DiscreteInput 5008 R Off/On = 0/1 0-1 Unit 5 Damper Switch 2 Open X

DiscreteInput 5009 R Off/On = 0/1 0-1 Unit 5 Damper Switch 3 Open X

DiscreteInput 5010 R Off/On = 0/1 0-1 Unit 5 Damper Switch 4 Open

InputRegister 5011 R ###.# NA Unit 5 Mixed Air Temperature Sensor 1 X X X

DiscreteInput 5012 R Off/On = 0/1 0-1 Unit 5 Activates Reheat Valve for Dehum X

InputRegister 5013 R ###.# NA Unit 5 Mixed Air Temperature Sensor 2 X

InputRegister 5014 R Zone1, 2, or 3 1-3 Unit 5 Zone Options X X X

InputRegister 5015 R ###.# NA Unit 5 Outdoor Air Temperature Sensor 1 X X X

InputRegister 5017 R ###.# NA Unit 5 Outdoor Air Temperature Sensor 2

InputRegister 5019 R ###.# NA Unit 5 Return Air Temperature Sensor 1 X X X

InputRegister 5021 R ###.# NA Unit 5 Return Air Temperature Sensor 2 X

InputRegister 5023 R ###.# 0-100% Unit 5 Outdoor Humidity Sensor 1 X X

InputRegister 5025 R ###.# 0-100% Unit 5 Outdoor Humidity Sensor 2

InputRegister 5027 R ###.# NA Unit 5 Freeze Sensor 1 X

DiscreteInput 5029 R Off/On = 0/1 0-1 Unit 5 Heat 1 On/Off X X X

InputRegister 5029 R ###.# NA Unit 5 Freeze Sensor 2

DiscreteInput 5030 R Off/On = 0/1 0-1 Unit 5 Heat 2 On/Off X X X

DiscreteInput 5031 R Off/On = 0/1 0-1 Unit 5 Heat 3 On/Off X

DiscreteInput 5032 R Off/On = 0/1 0-1 Unit 5 Heat 4 On/Off

DiscreteInput 5033 R Off/On = 0/1 0-1 Unit 5 Indicates FreeCool Is Available X X X

DiscreteInput 5034 R Off/On = 0/1 0-1 Unit 5 Dirty Filter Indicator X X

InputRegister 5034 R ### 0-100% Unit 5 Blower Speed 1 X X

DiscreteInput 5035 R Off/On = 0/1 0-1 Unit 5 Cooling 1 On/Off X X X

InputRegister 5035 R ### 0-100% Unit 5 Blower Speed 2

DiscreteInput 5036 R Off/On = 0/1 0-1 Unit 5 Cooling 2 On/Off X X X

InputRegister 5036 R ### 0-45 bar Unit 5 Discharge Pressure Transducer 1

DiscreteInput 5037 R Off/On = 0/1 0-1 Unit 5 Cooling 3 On/Off X

InputRegister 5037 R ### 0-45 bar Unit 5 Discharge Pressure Transducer 2

DiscreteInput 5038 R Off/On = 0/1 0-1 Unit 5 Cooling 4 On/Off

InputRegister 5038 R ###.# NA Unit 5 Discharge Temperature 1

DiscreteInput 5039 R Off/On = 0/1 0-1 Unit 5 Indicates No Air Flow X X

InputRegister 5039 R ###.# NA Unit 5 Discharge Temperature 2

DiscreteInput 5040 R Off/On = 0/1 0-1 Unit 5 Indicates No Air Flow

InputRegister 5040 R ### 0-100% Unit 5 Dust Sensor 1 X X

DiscreteInput 5041 R Off/On = 0/1 0-1 Unit 5 Indicates High Pressure Event X X X

InputRegister 5041 R ### 0-100% Unit 5 Dust Sensor 2

DiscreteInput 5042 R Off/On = 0/1 0-1 Unit 5 Indicates High Pressure Event X

DiscreteInput 5043 R Off/On = 0/1 0-1 Unit 5 Indicates Unit Power Loss X X

DiscreteInput 5044 R Off/On = 0/1 0-1 Unit 5 Is Disabled X X X

InputRegister 5044 R ###.# NA Unit 5 Liquid Temperature 1 X X

InputRegister 5045 R ###.# NA Unit 5 Liquid Temperature 2 X

InputRegister 5046 R ### NA Unit 5 Liquid Pressure 1 X

InputRegister 5047 R ### NA Unit 5 Liquid Pressure 2

InputRegister 5048 R ### NA Unit 5 Suction Pressure 1 X X

InputRegister 5049 R ### NA Unit 5 Suction Pressure 2

InputRegister 5050 R ###.# NA Unit 5 Suction Temperature 1 X X

InputRegister 5051 R ###.# NA Unit 5 Suction Temperature 2

InputRegister 5052 R ###.# NA Unit 5 Supply Air Temperature 1 X X

Page 29: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 29 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

InputRegister 5053 R ###.# NA Unit 5 Supply Air Temperature 2 X

InputRegister 5056 R ### 0-100% Unit 5 Condenser Fan Speed 1 X X

InputRegister 5057 R ### 0-100% Unit 5 Condenser Fan Speed 2 X

InputRegister 5058 R ### 0-100% Unit 5 Damper Position 1 X X X

InputRegister 5059 R ### 0-100% Unit 5 Damper Position 2 X

InputRegister 5060 R ### 0-100% Unit 5 Damper Position 3 X

InputRegister 5061 R ### 0-100% Unit 5 Damper Position 4 X

InputRegister 5062 R ### 0-100% Unit 5 EEV1 Position X X X

InputRegister 5063 R ### 0-100% Unit 5 EEV2 Position X

InputRegister 5064 R ### NA Unit 5 Declares number of Cooling Stages X X

InputRegister 5065 R ### NA Unit 5 Declares number of Heating Stages X X

InputRegister 5066 R ### NA Unit 5 Declares number of Freecooling Stages X X

InputRegister 5067 R ### °F Unit 5 Outdoor Air Dewpoint X

InputRegister 5068 R ### 0,1,2,3 Unit 5 Dehumidification Type X X

InputRegister 5069 R ###.# NA Unit 5 Suction Saturation Temperature 1

InputRegister 5070 R ###.# NA Unit 5 Suction Saturation Temperature 2

InputRegister 5071 R ### NA Unit 5 Subcooling 1 X

InputRegister 5072 R ### NA Unit 5 Superheat 1

InputRegister 5073 R ### NA Unit 5 Superheat 2

InputRegister 5074 R ###.# NA Unit 5 Liquid Saturated Temperature 1

InputRegister 5075 R ###.# NA Unit 5 Liquid Saturated Temperature 2

InputRegister 5076 R ### NA Unit 5 Subcooling 2

InputRegister 5080 R ### NA Unit 5 Major Revision Number X X X

InputRegister 5081 R ### NA Unit 5 Minor Revision Number X X X

InputRegister 5082 R ### NA Unit 5 Bug Fixes X X X

InputRegister 5083 R ### NAUnit 5 How long the unit has been running in minutes

X X X

InputRegister 5084 R ## NA Unit 5 How many times unit has started X X X

InputRegister 5085 R ### NA Unit 5 How long the Fan is running in minutes X X

InputRegister 5086 R ## NA Unit 5 How many times Fan turned on X X

InputRegister 5087 R ### NA Unit 5 How long the Fan is running in minutes

InputRegister 5088 R ## NA Unit 5 How many times Fan turned on

InputRegister 5089 R ### NA Unit 5 How long the Blower is running in minutes X X X

InputRegister 5090 R ## NA Unit 5 How many times Blower turned on X X

InputRegister 5091 R ### NA Unit 5 How long the Blower is running in minutes

InputRegister 5092 R ## NA Unit 5 How many times Blower turned on

InputRegister 5093 R ### NA Unit 5 How long unit is running in Freecooling X X

InputRegister 5094 R ### NAUnit 5 How many times unit has been in Freecooling

X X

InputRegister 5095 R ### NA Unit 5 How long unit is running in Freecooling

InputRegister 5096 R ### NAUnit 5 How many times unit has been in Freecooling

InputRegister 5097 R ### NA Unit 5 How long unit is running in Cooling X X X

InputRegister 5098 R ### NA Unit 5 How many times unit has been in Cooling X X X

InputRegister 5099 R ### NA Unit 5 How long unit is running in Cooling X X

InputRegister 5100 R ### NA Unit 5 How many times unit has been in Cooling X X

InputRegister 5101 R ### NA Unit 5 How long unit is running in Cooling X

InputRegister 5102 R ### NA Unit 5 How many times unit has been in Cooling X

InputRegister 5103 R ### NA Unit 5 How long unit is running in Cooling

InputRegister 5104 R ### NA Unit 5 How many times unit has been in Cooling

Page 30: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 30 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

InputRegister 5105 R ### NA Unit 5 How long unit is running in Heating X X X

InputRegister 5106 R ### NA Unit 5 How many times unit has been in Heating X X X

InputRegister 5107 R ### NA Unit 5 How long unit is running in Heating X X

InputRegister 5108 R ### NA Unit 5 How many times unit has been in Heating X X

InputRegister 5109 R ### NA Unit 5 How long unit is running in Heating

InputRegister 5110 R ### NA Unit 5 How many times unit has been in Heating

InputRegister 5111 R ### NA Unit 5 How long unit is running in Heating

InputRegister 5112 R ### NA Unit 5 How many times unit has been in Heating

InputRegister 5113 R ### 0-999999 Unit 5 life time in Hours (Update every Hour) X X X

InputRegister 5115 R ### 0-999999Unit 5 Blower 1 life time in Hours (Update every Hour)

X X

InputRegister 5117 R ### 0-999999Unit 5 Blower 2 life time in Hours (Update every Hour)

InputRegister 5119 R ### 0-999999Unit 5 Fan 1 life time in hours (Update every Hour)

X

InputRegister 5121 R ### 0-999999Unit 5 Fan 2 life time in hours (Update every Hour)

InputRegister 5123 R ### 0-999999Unit 5 Cooling 1 life time in hours (Update ever Hour)

X X

InputRegister 5125 R ### 0-999999Unit 5 Cooling 2 life time in hours (Update ever Hour)

X

InputRegister 5127 R ### 0-999999Unit 5 Cooling 3 life time in hours (Update ever Hour)

InputRegister 5129 R ### 0-999999Unit 5 Cooling 4 life time in hours (Update ever Hour)

InputRegister 5131 R ### 0-999999Unit 5 Heating 1 life time in hours (Update ever Hour)

X X

InputRegister 5133 R ### 0-999999Unit 5 Heating 2 life time in hours (Update ever Hour)

InputRegister 5135 R ### 0-999999Unit 5 Heating 3 life time in hours (Update ever Hour)

InputRegister 5137 R ### 0-999999Unit 5 Heating 4 life time in hours (Update ever Hour)

InputRegister 5139 R ### 0-999999Unit 5 FreeCooling 1 life time in hours (Update ever Hour)

X X

InputRegister 5141 R ### 0-999999Unit 5 FreeCooling 2 life time in hours (Update ever Hour)

InputRegister 5143 R ### 0-5Unit 5 Indicates what unit types are running on the network

X X X

DiscreteInput 5500 R Off/On = 0/1 0-1Unit 5 Error in the number of retain memory writings

X X X

DiscreteInput 5501 R Off/On = 0/1 0-1 Unit 5 Error in retain memory writings X X X

DiscreteInput 5502 R Off/On = 0/1 0-1Unit 5 Circuit 1 Return Air Temperature Sensor Alarm

X X X

DiscreteInput 5503 R Off/On = 0/1 0-1Unit 5 Circuit 1 High Return Air Temperature Alarm

X X

DiscreteInput 5504 R Off/On = 0/1 0-1Unit 5 Circuit 1 Mixed Air Temperature Sensor Alarm

X X

DiscreteInput 5505 R Off/On = 0/1 0-1 Unit 5 Circuit 1 Mixed Air High Temperature X X

DiscreteInput 5506 R Off/On = 0/1 0-1 Unit 5 Circuit 1 Mixed Air Low Temperature X X

DiscreteInput 5507 R Off/On = 0/1 0-1Unit 5 Circuit 1 Supply Air Temperature Sensor Alarm

X X

DiscreteInput 5508 R Off/On = 0/1 0-1Unit 5 Circuit 1 High Supply Air Temperature Alarm

X

DiscreteInput 5509 R Off/On = 0/1 0-1Unit 5 Circuit 1 Low Supply Air Temperature Alarm

X

DiscreteInput 5510 R Off/On = 0/1 0-1 Unit 5 Outdoor Air Temperature Sensor Alarm X X X

Page 31: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 31 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

DiscreteInput 5511 R Off/On = 0/1 0-1 Unit 5 Outdoor Air Humidity Sensor Alarm X X X

DiscreteInput 5512 R Off/On = 0/1 0-1 Unit 5 Circuit 1 Dust Sensor Alarm X X

DiscreteInput 5513 R Off/On = 0/1 0-1Unit 5 Circuit 1 Dust Sensor High Dust Detection Alarm

X X

DiscreteInput 5514 R Off/On = 0/1 0-1 Unit 5 Circuit 1 Liquid Line Temp Sensor Alarm X X

DiscreteInput 5515 R Off/On = 0/1 0-1 Unit 5 Circuit 1 Discharge Temp Sensor Alarm

DiscreteInput 5516 R Off/On = 0/1 0-1Unit 5 Circuit 1 Liquid Line Pressure Sensor Alarm

X

DiscreteInput 5517 R Off/On = 0/1 0-1Unit 5 Circuit 1 Suction Temperature Sensor Alarm

X X X

DiscreteInput 5518 R Off/On = 0/1 0-1 Unit 5 Circuit 1 Suction Pressure Sensor Alarm X X X

DiscreteInput 5519 R Off/On = 0/1 0-1 Unit 5 Circuit 1 Low Pressure Alarm X X X

DiscreteInput 5520 R Off/On = 0/1 0-1 Unit 5 Circuit 1 High Pressure Alarm X X X

DiscreteInput 5521 R Off/On = 0/1 0-1 Unit 5 Damper 1 Failed to Open X X X

DiscreteInput 5522 R Off/On = 0/1 0-1 Unit 5 Damper 1 Failed to Close X X X

DiscreteInput 5523 R Off/On = 0/1 0-1 Unit 5 Circuit 1 Freeze Temperature Sensor Alarm X X

DiscreteInput 5524 R Off/On = 0/1 0-1 Unit 5 Circuit 1 Freeze Condition X X X

DiscreteInput 5525 R Off/On = 0/1 0-1 Unit 5 Blower Fail Alarm X X

DiscreteInput 5526 R Off/On = 0/1 0-1 Unit 5 Dirty Filter 1 Alarm X X X

DiscreteInput 5527 R Off/On = 0/1 0-1 Unit 5 Circuit 1 Dirty Condenser Coil Alarm

DiscreteInput 5528 R Off/On = 0/1 0-1 Unit 5 Emergency Ventilation Mode Active X X X

DiscreteInput 5529 R Off/On = 0/1 0-1 Unit 5 Emergency Cooling Mode Active X X X

DiscreteInput 5530 R Off/On = 0/1 0-1Unit 5 Extreme High Return Temp Alarm (Heat Cutout)

X X X

DiscreteInput 5531 R Off/On = 0/1 0-1 Unit 5 Unit Disable/Smoke Detector Alarm X X X

DiscreteInput 5532 R Off/On = 0/1 0-1 Unit 5 Circuit 1 Power Loss Detected X

DiscreteInput 5533 R Off/On = 0/1 0-1 Unit 5 Circuit 1 Low SuperHeat X X X

DiscreteInput 5534 R Off/On = 0/1 0-1 Unit 5 Circuit 1 Low Evaporation Pressure X X X

DiscreteInput 5535 R Off/On = 0/1 0-1 Unit 5 Circuit 1 High Evaporation Pressure X X X

DiscreteInput 5536 R Off/On = 0/1 0-1 Unit 5 Circuit 1 High Condenser Temperature X X X

DiscreteInput 5537 R Off/On = 0/1 0-1 Unit 5 Circuit 1 Low Suction pressure X X X

DiscreteInput 5538 R Off/On = 0/1 0-1 Unit 5 Circuit 1 EEV motor error X X X

DiscreteInput 5539 R Off/On = 0/1 0-1 Unit 5 Circuit 1 SelfTuning error X X X

DiscreteInput 5540 R Off/On = 0/1 0-1 Unit 5 Circuit 1 Emergency close X X X

DiscreteInput 5541 R Off/On = 0/1 0-1 Unit 5 Circuit 1 High Delta Temperature

DiscreteInput 5542 R Off/On = 0/1 0-1 Unit 5 Circuit 1 High Delta Pressure

DiscreteInput 5543 R Off/On = 0/1 0-1 Unit 5 Circuit 1 Range Error X X X

DiscreteInput 5544 R Off/On = 0/1 0-1 Unit 5 Circuit 1 Service Position Percent X X X

DiscreteInput 5545 R Off/On = 0/1 0-1 Unit 5 Circuit 1 Valve ID X X X

DiscreteInput 5546 R Off/On = 0/1 0-1Unit 5 Circuit 2 Return Air Temperature Sensor Alarm

X

DiscreteInput 5547 R Off/On = 0/1 0-1Unit 5 Circuit 2 High Return Air Temperature Alarm

X

DiscreteInput 5548 R Off/On = 0/1 0-1Unit 5 Circuit 2 Mixed Air Temperature Sensor Alarm

X

DiscreteInput 5549 R Off/On = 0/1 0-1 Unit 5 Circuit 2 Mixed Air High Temperature

DiscreteInput 5550 R Off/On = 0/1 0-1 Unit 5 Circuit 2 Mixed Air Low Temperature

DiscreteInput 5551 R Off/On = 0/1 0-1Unit 5 Circuit 2 Supply Air Temperature Sensor Alarm

X

DiscreteInput 5552 R Off/On = 0/1 0-1Unit 5 Circuit 2 High Supply Air Temperature Alarm

DiscreteInput 5553 R Off/On = 0/1 0-1Unit 5 Circuit 2 Low Supply Air Temperature Alarm

Page 32: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 32 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

DiscreteInput 5554 R Off/On = 0/1 0-1 Unit 5 Circuit 2 Dust Sensor Alarm

DiscreteInput 5555 R Off/On = 0/1 0-1Unit 5 Circuit 2 Dust Sensor High Dust Detection Alarm

DiscreteInput 5556 R Off/On = 0/1 0-1 Unit 5 Circuit 2 Liquid Line Temp Sensor Alarm X

DiscreteInput 5557 R Off/On = 0/1 0-1Unit 5 Circuit 2 Liquid Line Pressure Sensor Alarm

DiscreteInput 5558 R Off/On = 0/1 0-1 Unit 5 Circuit 2 Discharge Temp Sensor Alarm

DiscreteInput 5559 R Off/On = 0/1 0-1 Unit 5 Circuit 1 Discharge Pressure Sensor Alarm X

DiscreteInput 5560 R Off/On = 0/1 0-1 Unit 5 Circuit 2 Discharge Pressure Sensor Alarm X

DiscreteInput 5561 R Off/On = 0/1 0-1Unit 5 Circuit 2 Suction Temperature Sensor Alarm

X

DiscreteInput 5562 R Off/On = 0/1 0-1 Unit 5 Circuit 2 Suction Pressure Sensor Alarm X

DiscreteInput 5563 R Off/On = 0/1 0-1 Unit 5 Circuit 2 Low Pressure Alarm X

DiscreteInput 5564 R Off/On = 0/1 0-1 Unit 5 Circuit 2 High Pressure Alarm X

DiscreteInput 5565 R Off/On = 0/1 0-1 Unit 5 Damper 2 Failed to Open X

DiscreteInput 5566 R Off/On = 0/1 0-1 Unit 5 Damper 2 Failed to Close X

DiscreteInput 5567 R Off/On = 0/1 0-1 Unit 5 Damper 3 Failed to Open X

DiscreteInput 5568 R Off/On = 0/1 0-1 Unit 5 Damper 3 Failed to Close X

DiscreteInput 5569 R Off/On = 0/1 0-1 Unit 5 Damper 4 Failed to Open

DiscreteInput 5570 R Off/On = 0/1 0-1 Unit 5 Damper 4 Failed to Close

DiscreteInput 5571 R Off/On = 0/1 0-1 Unit 5 Circuit 2 Freeze Temperature Sensor Alarm X

DiscreteInput 5572 R Off/On = 0/1 0-1 Unit 5 Circuit 2 Freeze Condition X

DiscreteInput 5573 R Off/On = 0/1 0-1 Unit 5 Circuit 2 Blower Fail Alarm

DiscreteInput 5574 R Off/On = 0/1 0-1 Unit 5 Dirty Filter 2 Alarm

DiscreteInput 5575 R Off/On = 0/1 0-1 Unit 5 Dirty Filter 3 Alarm

DiscreteInput 5576 R Off/On = 0/1 0-1 Unit 5 Dirty Filter 4 Alarm

DiscreteInput 5577 R Off/On = 0/1 0-1 Unit 5 Circuit 2 Dirty Condenser Coil Alarm

DiscreteInput 5578 R Off/On = 0/1 0-1 Unit 5 Power Loss Detected

DiscreteInput 5579 R Off/On = 0/1 0-1 Unit 5 Circuit 2 Low SuperHeat X

DiscreteInput 5580 R Off/On = 0/1 0-1 Unit 5 Circuit 2 Low Evaporation Pressure X

DiscreteInput 5581 R Off/On = 0/1 0-1 Unit 5 Circuit 2 High Evaporation Pressure X

DiscreteInput 5582 R Off/On = 0/1 0-1 Unit 5 Circuit 2 High Condenser Temperature X

DiscreteInput 5583 R Off/On = 0/1 0-1 Unit 5 Circuit 2 Low Suction pressure X

DiscreteInput 5584 R Off/On = 0/1 0-1 Unit 5 Circuit 2 EEV motor error X

DiscreteInput 5585 R Off/On = 0/1 0-1 Unit 5 Circuit 2 SelfTuning error X

DiscreteInput 5586 R Off/On = 0/1 0-1 Unit 5 Circuit 2 Emergency close X

DiscreteInput 5587 R Off/On = 0/1 0-1 Unit 5 Circuit 2 High Delta Temperature

DiscreteInput 5588 R Off/On = 0/1 0-1 Unit 5 Circuit 2 High Delta Pressure

DiscreteInput 5589 R Off/On = 0/1 0-1 Unit 5 Circuit 2 Range Error X

DiscreteInput 5590 R Off/On = 0/1 0-1 Unit 5 Circuit 2 Service Position Percent X

DiscreteInput 5591 R Off/On = 0/1 0-1 Unit 5 Circuit 2 Valve ID X

DiscreteInput 5592 R Off/On = 0/1 0-1 Unit 5 Th-Tune Device Offline X

DiscreteInput 5593 R Off/On = 0/1 0-1 Unit 5 Th-Tune Temperature Probe Alarm X

DiscreteInput 5594 R Off/On = 0/1 0-1 Unit 5 Th-Tune Humidity Probe Alarm X

DiscreteInput 5595 R Off/On = 0/1 0-1 Unit 5 Th-Tune Clock Board Alarm X

DiscreteInput 5596 R Off/On = 0/1 0-1 Unit 5 cpCOe Offline X

DiscreteInput 5597 R Off/On = 0/1 0-1 Unit 5 Blower 1 Offline X

DiscreteInput 5598 R Off/On = 0/1 0-1 Unit 5 Blower 1 Alarm X

DiscreteInput 5599 R Off/On = 0/1 0-1 Unit 5 Blower 2 Offline

DiscreteInput 5600 R Off/On = 0/1 0-1 Unit 5 Blower 2 Alarm

Page 33: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 33 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

DiscreteInput 5601 R Off/On = 0/1 0-1 Unit 5 Condenser Fan 1 Offline X

DiscreteInput 5602 R Off/On = 0/1 0-1 Unit 5 Condenser Fan 1 Alarm X

DiscreteInput 5603 R Off/On = 0/1 0-1 Unit 5 Condenser Fan 2 Offline

DiscreteInput 5604 R Off/On = 0/1 0-1 Unit 5 Condenser Fan 2 Alarm

DiscreteInput 5605 R Off/On = 0/1 0-1 Unit 5 Low Return Air Temperature 1 Alarm X

DiscreteInput 5606 R Off/On = 0/1 0-1 Unit 5 Low Return Air Temperature 2 Alarm X

DiscreteInput 5607 R Off/On = 0/1 0-1 Unit 5 Panel Open Alarm X

DiscreteInput 6000 R Off/On = 0/1 0-1 Unit 6 Dirty Filter 1 Alarm X X X

DiscreteInput 6001 R Off/On = 0/1 0-1 Unit 6 Dirty Filter 2 Alarm X

DiscreteInput 6002 R Off/On = 0/1 0-1 Unit 6 Dirty Filter 3 Alarm

DiscreteInput 6003 R Off/On = 0/1 0-1 Unit 6 Indicates Blower 1 Is Running In Unit X X

InputRegister 6003 R 0-14 0-14 Unit 6 Compressor 1 Status X X X

DiscreteInput 6004 R Off/On = 0/1 0-1 Unit 6 Indicates Blower 2 Is Running In Unit

InputRegister 6004 R 0-14 0-14 Unit 6 Compressor 2 Status X

DiscreteInput 6005 R Off/On = 0/1 0-1 Unit 6 Low Pressure Switch 1 X

DiscreteInput 6006 R Off/On = 0/1 0-1 Unit 6 Low Pressure Switch 2

DiscreteInput 6007 R Off/On = 0/1 0-1 Unit 6 Damper Switch 1 Open X X X

DiscreteInput 6008 R Off/On = 0/1 0-1 Unit 6 Damper Switch 2 Open X

DiscreteInput 6009 R Off/On = 0/1 0-1 Unit 6 Damper Switch 3 Open X

DiscreteInput 6010 R Off/On = 0/1 0-1 Unit 6 Damper Switch 4 Open

InputRegister 6011 R ###.# NA Unit 6 Mixed Air Temperature Sensor 1 X X X

DiscreteInput 6012 R Off/On = 0/1 0-1 Unit 6 Activates Reheat Valve for Dehum X

InputRegister 6013 R ###.# NA Unit 6 Mixed Air Temperature Sensor 2 X

InputRegister 6014 R Zone1, 2, or 3 1-3 Unit 6 Zone Options X X X

InputRegister 6015 R ###.# NA Unit 6 Outdoor Air Temperature Sensor 1 X X X

InputRegister 6017 R ###.# NA Unit 6 Outdoor Air Temperature Sensor 2

InputRegister 6019 R ###.# NA Unit 6 Return Air Temperature Sensor 1 X X X

InputRegister 6021 R ###.# NA Unit 6 Return Air Temperature Sensor 2 X

InputRegister 6023 R ###.# 0-100% Unit 6 Outdoor Humidity Sensor 1 X X

InputRegister 6025 R ###.# 0-100% Unit 6 Outdoor Humidity Sensor 2

InputRegister 6027 R ###.# NA Unit 6 Freeze Sensor 1 X

DiscreteInput 6029 R Off/On = 0/1 0-1 Unit 6 Heat 1 On/Off X X X

InputRegister 6029 R ###.# NA Unit 6 Freeze Sensor 2

DiscreteInput 6030 R Off/On = 0/1 0-1 Unit 6 Heat 2 On/Off X X X

DiscreteInput 6031 R Off/On = 0/1 0-1 Unit 6 Heat 3 On/Off X

DiscreteInput 6032 R Off/On = 0/1 0-1 Unit 6 Heat 4 On/Off

DiscreteInput 6033 R Off/On = 0/1 0-1 Unit 6 FreeCool Is Available X X X

DiscreteInput 6034 R Off/On = 0/1 0-1 Unit 6 Dirty Filter Indicator X X

InputRegister 6034 R ### 0-100% Unit 6 Blower Speed 1 X X

DiscreteInput 6035 R Off/On = 0/1 0-1 Unit 6 Cooling 1 On/Off X X X

InputRegister 6035 R ### 0-100% Unit 6 Blower Speed 2

DiscreteInput 6036 R Off/On = 0/1 0-1 Unit 6 Cooling 2 On/Off X X X

InputRegister 6036 R ### 0-45 bar Unit 6 Discharge Pressure Transducer 1

DiscreteInput 6037 R Off/On = 0/1 0-1 Unit 6 Cooling 3 On/Off X

InputRegister 6037 R ### 0-45 bar Unit 6 Discharge Pressure Transducer 2

DiscreteInput 6038 R Off/On = 0/1 0-1 Unit 6 Cooling 4 On/Off

InputRegister 6038 R ###.# NA Unit 6 Discharge Temperature 1

DiscreteInput 6039 R Off/On = 0/1 0-1 Unit 6 Indicates No Air Flow X X

InputRegister 6039 R ###.# NA Unit 6 Discharge Temperature 2

Page 34: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 34 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

DiscreteInput 6040 R Off/On = 0/1 0-1 Unit 6 Indicates No Air Flow 2

InputRegister 6040 R ### 0-100% Unit 6 Dust Sensor 1 X X

DiscreteInput 6041 R Off/On = 0/1 0-1 Unit 6 High Pressure 1 Event X X X

InputRegister 6041 R ### 0-100% Unit 6 Dust Sensor 2

DiscreteInput 6042 R Off/On = 0/1 0-1 Unit 6 High Pressure 2 Event X

DiscreteInput 6043 R Off/On = 0/1 0-1 Unit 6 Power Loss Detected Alarm X X

DiscreteInput 6044 R Off/On = 0/1 0-1 Unit 6 Is Disabled X X X

InputRegister 6044 R ###.# NA Unit 6 Liquid Temperature 1 X X

InputRegister 6045 R ###.# NA Unit 6 Liquid Temperature 2 X

InputRegister 6046 R ### NA Unit 6 Liquid Pressure 1 X

InputRegister 6047 R ### NA Unit 6 Liquid Pressure 2

InputRegister 6048 R ### NA Unit 6 Suction Pressure 1 X X

InputRegister 6049 R ### NA Unit 6 Suction Pressure 2

InputRegister 6050 R ###.# NA Unit 6 Suction Temperature 1 X X

InputRegister 6051 R ###.# NA Unit 6 Suction Temperature 2

InputRegister 6052 R ###.# NA Unit 6 Supply Air Temperature 1 X X

InputRegister 6053 R ###.# NA Unit 6 Supply Air Temperature 2 X

InputRegister 6056 R ### 0-100% Unit 6 Condenser Fan Speed 1 X X

InputRegister 6057 R ### 0-100% Unit 6 Condenser Fan Speed 2 X

InputRegister 6058 R ### 0-100% Unit 6 Damper Position 1 X X X

InputRegister 6059 R ### 0-100% Unit 6 Damper Position 2 X

InputRegister 6060 R ### 0-100% Unit 6 Damper Position 3 X

InputRegister 6061 R ### 0-100% Unit 6 Damper Position 4 X

InputRegister 6062 R ### 0-100% Unit 6 EEV1 Position X X X

InputRegister 6063 R ### 0-100% Unit 6 EEV2 Position X

InputRegister 6064 R ### NA Unit 6 Declares number of Cooling Stages X X

InputRegister 6065 R ### NA Unit 6 Declares number of Heating Stages X X

InputRegister 6066 R ### NA Unit 6 Declares number of Freecooling Stages X X

InputRegister 6067 R ### NA Unit 6 Outdoor Air Dewpoint X

InputRegister 6068 R ### 0,1,2,3 Unit 6 Dehumidification Type X X

InputRegister 6069 R ###.# NA Unit 6 Suction Saturation Temperature 1

InputRegister 6070 R ###.# NA Unit 6 Suction Saturation Temperature 2

InputRegister 6071 R ### NA Unit 6 Subcooling 1 X

InputRegister 6072 R ### NA Unit 6 Superheat 1

InputRegister 6073 R ### NA Unit 6 Superheat 2

InputRegister 6074 R ###.# NA Unit 6 Liquid Saturated Temperature 1

InputRegister 6075 R ###.# NA Unit 6 Liquid Saturated Temperature 2

InputRegister 6076 R ### NA Unit 6 Subcooling 2

InputRegister 6080 R ### NA Unit 6 Major Revision Number X X X

InputRegister 6081 R ### NA Unit 6 Minor Revision Number X X X

InputRegister 6082 R ### NA Unit 6 Bug Fixes X X X

InputRegister 6083 R ### NAUnit 6 How long the unit has been running in minutes

X X X

InputRegister 6084 R ## NA Unit 6 How many times unit has started X X X

InputRegister 6085 R ### NA Unit 6 How long the Fan is running in minutes X X

InputRegister 6086 R ## NA Unit 6 How many times Fan turned on X X

InputRegister 6087 R ### NA Unit 6 How long the Fan is running in minutes

InputRegister 6088 R ## NA Unit 6 How many times Fan turned on

InputRegister 6089 R ### NA Unit 6 How long the Blower is running in minutes X X X

Page 35: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 35 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

InputRegister 6090 R ## NA Unit 6 How many times Blower turned on X X

InputRegister 6091 R ### NA Unit 6 How long the Blower is running in minutes

InputRegister 6092 R ## NA Unit 6 How many times Blower turned on

InputRegister 6093 R ### NA Unit 6 How long unit is running in Freecooling X X

InputRegister 6094 R ### NAUnit 6 How many times unit has been in Freecooling

X X

InputRegister 6095 R ### NA Unit 6 How long unit is running in Freecooling

InputRegister 6096 R ### NAUnit 6 How many times unit has been in Freecooling

InputRegister 6097 R ### NA Unit 6 How long unit is running in Cooling X X X

InputRegister 6098 R ### NA Unit 6 How many times unit has been in Cooling X X X

InputRegister 6099 R ### NA Unit 6 How long unit is running in Cooling X X

InputRegister 6100 R ### NA Unit 6 How many times unit has been in Cooling X X

InputRegister 6101 R ### NA Unit 6 How long unit is running in Cooling X

InputRegister 6102 R ### NA Unit 6 How many times unit has been in Cooling X

InputRegister 6103 R ### NA Unit 6 How long unit is running in Cooling

InputRegister 6104 R ### NA Unit 6 How many times unit has been in Cooling

InputRegister 6105 R ### NA Unit 6 How long unit is running in Heating X X X

InputRegister 6106 R ### NA Unit 6 How many times unit has been in Heating X X X

InputRegister 6107 R ### NA Unit 6 How long unit is running in Heating X X

InputRegister 6108 R ### NA Unit 6 How many times unit has been in Heating X X

InputRegister 6109 R ### NA Unit 6 How long unit is running in Heating

InputRegister 6110 R ### NA Unit 6 How many times unit has been in Heating

InputRegister 6111 R ### NA Unit 6 How long unit is running in Heating

InputRegister 6112 R ### NA Unit 6 How many times unit has been in Heating

InputRegister 6113 R ### 0-999999 Unit 6 life time in Hours (Update every Hour) X X X

InputRegister 6115 R ### 0-999999Unit 6 Blower 1 life time in Hours (Update every Hour)

X X

InputRegister 6117 R ### 0-999999Unit 6 Blower 2 life time in Hours (Update every Hour)

InputRegister 6119 R ### 0-999999Unit 6 Fan 1 life time in hours (Update every Hour)

X

InputRegister 6121 R ### 0-999999Unit 6 Fan 2 life time in hours (Update every Hour)

InputRegister 6123 R ### 0-999999Unit 6 Cooling 1 life time in hours (Update ever Hour)

X X

InputRegister 6125 R ### 0-999999Unit 6 Cooling 2 life time in hours (Update ever Hour)

X

InputRegister 6127 R ### 0-999999Unit 6 Cooling 3 life time in hours (Update ever Hour)

InputRegister 6129 R ### 0-999999Unit 6 Cooling 4 life time in hours (Update ever Hour)

InputRegister 6131 R ### 0-999999Unit 6 Heating 1 life time in hours (Update ever Hour)

X X

InputRegister 6133 R ### 0-999999Unit 6 Heating 2 life time in hours (Update ever Hour)

InputRegister 6135 R ### 0-999999Unit 6 Heating 3 life time in hours (Update ever Hour)

InputRegister 6137 R ### 0-999999Unit 6 Heating 4 life time in hours (Update ever Hour)

InputRegister 6139 R ### 0-999999Unit 6 FreeCooling 1 life time in hours (Update ever Hour)

X X

InputRegister 6141 R ### 0-999999Unit 6 FreeCooling 2 life time in hours (Update ever Hour)

Page 36: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 36 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

InputRegister 6143 R ### 0-5Unit 6 Indicates what unit types are running on the network

X X X

DiscreteInput 6500 R Off/On = 0/1 0-1Unit 6 Error in the number of retain memory writings Alarm

X X X

DiscreteInput 6501 R Off/On = 0/1 0-1 Unit 6 Error in retain memory writings Alarm X X X

DiscreteInput 6502 R Off/On = 0/1 0-1 Unit 6 Return Air Temperature Sensor Alarm X X X

DiscreteInput 6503 R Off/On = 0/1 0-1 Unit 6 High Return Air Temperature Alarm X X

DiscreteInput 6504 R Off/On = 0/1 0-1 Unit 6 Mixed Air Temperature Sensor Alarm X X

DiscreteInput 6505 R Off/On = 0/1 0-1 Unit 6 Mixed Air High Temperature Alarm X X

DiscreteInput 6506 R Off/On = 0/1 0-1 Unit 6 Mixed Air Low Temperature Alarm X X

DiscreteInput 6507 R Off/On = 0/1 0-1 Unit 6 Supply Air Temperature Sensor Alarm X X

DiscreteInput 6508 R Off/On = 0/1 0-1 Unit 6 High Supply Air Temperature Alarm X

DiscreteInput 6509 R Off/On = 0/1 0-1 Unit 6 Low Supply Air Temperature Alarm X

DiscreteInput 6510 R Off/On = 0/1 0-1 Unit 6 Outdoor Air Temperature Sensor Alarm X X X

DiscreteInput 6511 R Off/On = 0/1 0-1 Unit 6 Outdoor Air Humidity Sensor Alarm X X X

DiscreteInput 6512 R Off/On = 0/1 0-1 Unit 6 Dust Sensor Alarm X X

DiscreteInput 6513 R Off/On = 0/1 0-1 Unit 6 Dust Sensor High Dust Detection Alarm X X

DiscreteInput 6514 R Off/On = 0/1 0-1 Unit 6 Liquid Line Temp Sensor Alarm X X

DiscreteInput 6516 R Off/On = 0/1 0-1 Unit 6 Discharge Temp Sensor Alarm

DiscreteInput 6517 R Off/On = 0/1 0-1 Unit 6 Liquid Line Pressure Sensor Alarm X

DiscreteInput 6518 R Off/On = 0/1 0-1 Unit 6 Suction Temperature Sensor Alarm X X X

DiscreteInput 6519 R Off/On = 0/1 0-1 Unit 6 Suction Pressure Sensor Alarm X X X

DiscreteInput 6520 R Off/On = 0/1 0-1 Unit 6 Low Pressure Alarm X X X

DiscreteInput 6521 R Off/On = 0/1 0-1 Unit 6 High Pressure Alarm X X X

DiscreteInput 6522 R Off/On = 0/1 0-1 Unit 6 Damper 1 Failed to Open X X X

DiscreteInput 6523 R Off/On = 0/1 0-1 Unit 6 Damper 1 Failed to Close X X X

DiscreteInput 6524 R Off/On = 0/1 0-1 Unit 6 Freeze Temperature Sensor Alarm X X

DiscreteInput 6525 R Off/On = 0/1 0-1 Unit 6 Freeze Condition X X X

DiscreteInput 6526 R Off/On = 0/1 0-1 Unit 6 Blower Fail Alarm X X

DiscreteInput 6527 R Off/On = 0/1 0-1 Unit 6 Dirty Filter 1 Alarm X X X

DiscreteInput 6528 R Off/On = 0/1 0-1 Unit 6 Dirty Condenser Coil Alarm

DiscreteInput 6529 R Off/On = 0/1 0-1 Unit 6 Emergency Ventilation Mode Active Alarm X X X

DiscreteInput 6530 R Off/On = 0/1 0-1 Unit 6 Emergency Cooling Mode Active Alarm X X X

DiscreteInput 6531 R Off/On = 0/1 0-1Unit 6 Extreme High Return Temp Alarm (Heat Cutout) Alarm

X X X

DiscreteInput 6532 R Off/On = 0/1 0-1 Unit 6 Disable/Smoke Detector Alarm X X X

DiscreteInput 6533 R Off/On = 0/1 0-1 Unit 6 Power Loss Detected Alarm X

DiscreteInput 6534 R Off/On = 0/1 0-1 Unit 6 Low SuperHeat Alarm X X X

DiscreteInput 6535 R Off/On = 0/1 0-1 Unit 6 Low Evaporation Pressure Alarm X X X

DiscreteInput 6536 R Off/On = 0/1 0-1 Unit 6 High Evaporation Pressure Alarm X X X

DiscreteInput 6537 R Off/On = 0/1 0-1 Unit 6 High Condenser Temperature Alarm X X X

DiscreteInput 6538 R Off/On = 0/1 0-1 Unit 6 Low Suction pressure Alarm X X X

DiscreteInput 6539 R Off/On = 0/1 0-1 Unit 6 EEV motor error Alarm X X X

DiscreteInput 6540 R Off/On = 0/1 0-1 Unit 6 SelfTuning error Alarm X X X

DiscreteInput 6541 R Off/On = 0/1 0-1 Unit 6 Emergency close Alarm X X X

DiscreteInput 6542 R Off/On = 0/1 0-1 Unit 6 High Delta Temperature Alarm

DiscreteInput 6543 R Off/On = 0/1 0-1 Unit 6 High Delta Pressure Alarm

DiscreteInput 6544 R Off/On = 0/1 0-1 Unit 6 Range Error Alarm X X X

DiscreteInput 6545 R Off/On = 0/1 0-1 Unit 6 Service Position Percent Alarm X X X

DiscreteInput 6546 R Off/On = 0/1 0-1 Unit 6 Valve ID Alarm X X X

Page 37: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 37 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

DiscreteInput 6547 R Off/On = 0/1 0-1 Unit 6 Return Air Temperature Sensor 2 Alarm X

DiscreteInput 6548 R Off/On = 0/1 0-1 Unit 6 High Return Air Temperature 2 Alarm X

DiscreteInput 6549 R Off/On = 0/1 0-1 Unit 6 Mixed Air Temperature Sensor 2 Alarm X

DiscreteInput 6550 R Off/On = 0/1 0-1 Unit 6 Mixed Air High Temperature 2 Alarm

DiscreteInput 6551 R Off/On = 0/1 0-1 Unit 6 Mixed Air Low Temperature 2 Alarm

DiscreteInput 6552 R Off/On = 0/1 0-1 Unit 6 Supply Air Temperature Sensor 2 Alarm X

DiscreteInput 6553 R Off/On = 0/1 0-1 Unit 6 High Supply Air Temperature 2 Alarm

DiscreteInput 6554 R Off/On = 0/1 0-1 Unit 6 Low Supply Air Temperature 2 Alarm

DiscreteInput 6555 R Off/On = 0/1 0-1 Unit 6 Dust Sensor 2 Alarm

DiscreteInput 6556 R Off/On = 0/1 0-1 Unit 6 Dust Sensor High Dust Detection 2 Alarm

DiscreteInput 6557 R Off/On = 0/1 0-1 Unit 6 Liquid Line Temp Sensor 2 Alarm X

DiscreteInput 6558 R Off/On = 0/1 0-1 Unit 6 Liquid Line Pressure Sensor Alarm

DiscreteInput 6559 R Off/On = 0/1 0-1 Unit 6 Discharge Temp Sensor 2 Alarm

DiscreteInput 6560 R Off/On = 0/1 0-1 Unit 6 Discharge Pressure Sensor 2 Alarm X

DiscreteInput 6561 R Off/On = 0/1 0-1 Unit 6 Discharge Pressure Sensor 2 Alarm X

DiscreteInput 6562 R Off/On = 0/1 0-1 Unit 6 Suction Temperature Sensor 2 Alarm X

DiscreteInput 6563 R Off/On = 0/1 0-1 Unit 6 Suction Pressure Sensor 2 Alarm X

DiscreteInput 6564 R Off/On = 0/1 0-1 Unit 6 Low Pressure 2 Alarm X

DiscreteInput 6565 R Off/On = 0/1 0-1 Unit 6 High Pressure 2 Alarm X

DiscreteInput 6566 R Off/On = 0/1 0-1 Unit 6 Damper 2 Failed to Open X

DiscreteInput 6567 R Off/On = 0/1 0-1 Unit 6 Damper 2 Failed to Close X

DiscreteInput 6568 R Off/On = 0/1 0-1 Unit 6 Damper 3 Failed to Open X

DiscreteInput 6569 R Off/On = 0/1 0-1 Unit 6 Damper 3 Failed to Close X

DiscreteInput 6570 R Off/On = 0/1 0-1 Unit 6 Damper 4 Failed to Open

DiscreteInput 6571 R Off/On = 0/1 0-1 Unit 6 Damper 4 Failed to Close

DiscreteInput 6572 R Off/On = 0/1 0-1 Unit 6 Freeze Temperature Sensor Alarm X

DiscreteInput 6573 R Off/On = 0/1 0-1 Unit 6 Freeze Condition Alarm X

DiscreteInput 6574 R Off/On = 0/1 0-1 Unit 6 Blower Fail Alarm

DiscreteInput 6575 R Off/On = 0/1 0-1 Unit 6 Dirty Filter 2 Alarm

DiscreteInput 6576 R Off/On = 0/1 0-1 Unit 6 Dirty Filter 3 Alarm

DiscreteInput 6577 R Off/On = 0/1 0-1 Unit 6 Dirty Filter 4 Alarm

DiscreteInput 6578 R Off/On = 0/1 0-1 Unit 6 Dirty Condenser Coil 2 Alarm

DiscreteInput 6579 R Off/On = 0/1 0-1 Unit 6 Power Loss 2 Detected Alarm

DiscreteInput 6580 R Off/On = 0/1 0-1 Unit 6 Low SuperHeat 2 Alarm X

DiscreteInput 6581 R Off/On = 0/1 0-1 Unit 6 Low Evaporation Pressure 2 Alarm X

DiscreteInput 6582 R Off/On = 0/1 0-1 Unit 6 High Evaporation Pressure 2 Alarm X

DiscreteInput 6583 R Off/On = 0/1 0-1 Unit 6 High Condenser Temperature 2 Alarm X

DiscreteInput 6584 R Off/On = 0/1 0-1 Unit 6 Low Suction pressure 2 Alarm X

DiscreteInput 6585 R Off/On = 0/1 0-1 Unit 6 EEV motor 2 error Alarm X

DiscreteInput 6586 R Off/On = 0/1 0-1 Unit 6 SelfTuning 2 error Alarm X

DiscreteInput 6587 R Off/On = 0/1 0-1 Unit 6 Emergency close 2 Alarm X

DiscreteInput 6588 R Off/On = 0/1 0-1 Unit 6 High Delta Temperature 2 Alarm

DiscreteInput 6589 R Off/On = 0/1 0-1 Unit 6 High Delta Pressure 2 Alarm

DiscreteInput 6590 R Off/On = 0/1 0-1 Unit 6 Range Error 2 Alarm X

DiscreteInput 6591 R Off/On = 0/1 0-1 Unit 6 Service Position Percent 2 Alarm X

DiscreteInput 6592 R Off/On = 0/1 0-1 Unit 6 Valve ID 2 Alarm X

DiscreteInput 6593 R Off/On = 0/1 0-1 Unit 6 Th-Tune Device Offline Alarm X

DiscreteInput 6594 R Off/On = 0/1 0-1 Unit 6 Th-Tune Temperature Probe Alarm X

DiscreteInput 6595 R Off/On = 0/1 0-1 Unit 6 Th-Tune Humidity Probe Alarm X

Page 38: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 38 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

DiscreteInput 6596 R Off/On = 0/1 0-1 Unit 6 Th-Tune Clock Board Alarm X

DiscreteInput 6597 R Off/On = 0/1 0-1 Unit 6 cpCOe Offline Alarm X

DiscreteInput 6598 R Off/On = 0/1 0-1 Unit 6 Blower 1 Offline Alarm X

DiscreteInput 6599 R Off/On = 0/1 0-1 Unit 6 Blower 1 Alarm X

DiscreteInput 6600 R Off/On = 0/1 0-1 Unit 6 Blower 2 Offline Alarm

DiscreteInput 6601 R Off/On = 0/1 0-1 Unit 6 Blower 2 Alarm

DiscreteInput 6602 R Off/On = 0/1 0-1 Unit 6 Condenser 1 Offline Alarm X

DiscreteInput 6603 R Off/On = 0/1 0-1 Unit 6 Condenser 1 Alarm X

DiscreteInput 6604 R Off/On = 0/1 0-1 Unit 6 Condenser 2 Offline Alarm

DiscreteInput 6605 R Off/On = 0/1 0-1 Unit 6 Condenser 2 Alarm

DiscreteInput 6606 R Off/On = 0/1 0-1 Unit 6 Low Return Air Temperature 1 Alarm X

DiscreteInput 6607 R Off/On = 0/1 0-1 Unit 6 Low Return Air Temperature 2 Alarm X

DiscreteInput 6608 R Off/On = 0/1 0-1 Unit 6 Panel Open Alarm X

DiscreteInput 7000 R Off/On = 0/1 0-1 Unit 7 Dirty Filter 1 Alarm X X X

DiscreteInput 7001 R Off/On = 0/1 0-1 Unit 7 Dirty Filter 2 Alarm X

DiscreteInput 7002 R Off/On = 0/1 0-1 Unit 7 Dirty Filter 3 Alarm

DiscreteInput 7003 R Off/On = 0/1 0-1 Unit 7 Indicates Blower 1 Is Running In Unit X X

InputRegister 7003 R 0-14 0-14 Unit 7 Compressor 1 Status X X X

DiscreteInput 7004 R Off/On = 0/1 0-1 Unit 7 Indicates Blower 2 Is Running In Unit

InputRegister 7004 R 0-14 0-14 Unit 7 Compressor 2 Status X

DiscreteInput 7005 R Off/On = 0/1 0-1 Unit 7 Low Pressure Switch 1 X

DiscreteInput 7006 R Off/On = 0/1 0-1 Unit 7 Low Pressure Switch 2

DiscreteInput 7007 R Off/On = 0/1 0-1 Unit 7 Damper Switch 1 Open X X X

DiscreteInput 7008 R Off/On = 0/1 0-1 Unit 7 Damper Switch 2 Open X

DiscreteInput 7009 R Off/On = 0/1 0-1 Unit 7 Damper Switch 3 Open X

DiscreteInput 7010 R Off/On = 0/1 0-1 Unit 7 Damper Switch 4 Open

InputRegister 7011 R ###.# NA Unit 7 Mixed Air Temperature Sensor 1 X X X

DiscreteInput 7012 R Off/On = 0/1 0-1 Unit 7 Activates Reheat Valve for Dehum X

InputRegister 7013 R ###.# NA Unit 7 Mixed Air Temperature Sensor 2 X

InputRegister 7014 R Zone1, 2, or 3 1-3 Unit 7 Zone Options X X X

InputRegister 7015 R ###.# NA Unit 7 Outdoor Air Temperature Sensor 1 X X X

InputRegister 7017 R ###.# NA Unit 7 Outdoor Air Temperature Sensor 2

InputRegister 7019 R ###.# NA Unit 7 Return Air Temperature Sensor 1 X X X

InputRegister 7021 R ###.# NA Unit 7 Return Air Temperature Sensor 2 X

InputRegister 7023 R ###.# 0-100% Unit 7 Outdoor Humidity Sensor 1 X X

InputRegister 7025 R ###.# 0-100% Unit 7 Outdoor Humidity Sensor 2

InputRegister 7027 R ###.# NA Unit 7 Freeze Sensor 1 X

DiscreteInput 7029 R Off/On = 0/1 0-1 Unit 7 Heat 1 On/Off X X X

InputRegister 7029 R ###.# NA Unit 7 Freeze Sensor 2

DiscreteInput 7030 R Off/On = 0/1 0-1 Unit 7 Heat 2 On/Off X X X

DiscreteInput 7031 R Off/On = 0/1 0-1 Unit 7 Heat 3 On/Off X

DiscreteInput 7032 R Off/On = 0/1 0-1 Unit 7 Heat 4 On/Off

DiscreteInput 7033 R Off/On = 0/1 0-1 Unit 7 FreeCool Is Available X X X

DiscreteInput 7034 R Off/On = 0/1 0-1 Unit 7 Dirty Filter Indicator X X

InputRegister 7034 R ### 0-100% Unit 7 Blower Speed 1 X X

DiscreteInput 7035 R Off/On = 0/1 0-1 Unit 7 Cooling 1 On/Off X X X

InputRegister 7035 R ### 0-100% Unit 7 Blower Speed 2

DiscreteInput 7036 R Off/On = 0/1 0-1 Unit 7 Cooling 2 On/Off X X X

InputRegister 7036 R ### 0-45 bar Unit 7 Discharge Pressure Transducer 1

Page 39: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 39 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

DiscreteInput 7037 R Off/On = 0/1 0-1 Unit 7 Cooling 3 On/Off X

InputRegister 7037 R ### 0-45 bar Unit 7 Discharge Pressure Transducer 2

DiscreteInput 7038 R Off/On = 0/1 0-1 Unit 7 Cooling 4 On/Off

InputRegister 7038 R ###.# NA Unit 7 Discharge Temperature 1

DiscreteInput 7039 R Off/On = 0/1 0-1 Unit 7 Indicates No Air Flow X X

InputRegister 7039 R ###.# NA Unit 7 Discharge Temperature 2

DiscreteInput 7040 R Off/On = 0/1 0-1 Unit 7 Indicates No Air Flow 2

InputRegister 7040 R ### 0-100% Unit 7 Dust Sensor 1 X X

DiscreteInput 7041 R Off/On = 0/1 0-1 Unit 7 High Pressure 1 Event X X X

InputRegister 7041 R ### 0-100% Unit 7 Dust Sensor 2

DiscreteInput 7042 R Off/On = 0/1 0-1 Unit 7 High Pressure 2 Event X

DiscreteInput 7043 R Off/On = 0/1 0-1 Unit 7 Power Loss detected Alarm X X

DiscreteInput 7044 R Off/On = 0/1 0-1 Unit 7 Is Disabled X X X

InputRegister 7044 R ###.# NA Unit 7 Liquid Temperature 1 X X

InputRegister 7045 R ###.# NA Unit 7 Liquid Temperature 2 X

InputRegister 7046 R ### NA Unit 7 Liquid Pressure 1 X

InputRegister 7047 R ### NA Unit 7 Liquid Pressure 2

InputRegister 7048 R ### NA Unit 7 Suction Pressure 1 X X

InputRegister 7049 R ### NA Unit 7 Suction Pressure 2

InputRegister 7050 R ###.# NA Unit 7 Suction Temperature 1 X X

InputRegister 7051 R ###.# NA Unit 7 Suction Temperature 2

InputRegister 7052 R ###.# NA Unit 7 Supply Air Temperature 1 X X

InputRegister 7053 R ###.# NA Unit 7 Supply Air Temperature 2 X

InputRegister 7056 R ### 0-100% Unit 7 Condenser Fan Speed 1 X X

InputRegister 7057 R ### 0-100% Unit 7 Condenser Fan Speed 2 X

InputRegister 7058 R ### 0-100% Unit 7 Damper Position 1 X X X

InputRegister 7059 R ### 0-100% Unit 7 Damper Position 2 X

InputRegister 7060 R ### 0-100% Unit 7 Damper Position 3 X

InputRegister 7061 R ### 0-100% Unit 7 Damper Position 4 X

InputRegister 7062 R ### 0-100% Unit 7 EEV1 Position X X X

InputRegister 7063 R ### 0-100% Unit 7 EEV2 Position X

InputRegister 7064 R ### NA Unit 7 Declares number of Cooling Stages X X

InputRegister 7065 R ### NA Unit 7 Declares number of Heating Stages X X

InputRegister 7066 R ### NA Unit 7 Declares number of Freecooling Stages X X

InputRegister 7067 R ### NA Unit 7 Outdoor Air Dewpoint X

InputRegister 7068 R ### 0,1,2,3 Unit 7 Dehumidification Type X X

InputRegister 7069 R ###.# NA Unit 7 Suction Saturation Temperature 1

InputRegister 7070 R ###.# NA Unit 7 Suction Saturation Temperature 2

InputRegister 7071 R ### NA Unit 7 Subcooling 1 X

InputRegister 7072 R ### NA Unit 7 Superheat 1

InputRegister 7073 R ### NA Unit 7 Superheat 2

InputRegister 7074 R ###.# NA Unit 7 Liquid Saturated Temperature 1

InputRegister 7075 R ###.# NA Unit 7 Liquid Saturated Temperature 2

InputRegister 7076 R ### NA Unit 7 Subcooling 2

InputRegister 7080 R ### NA Unit 7 Major Revision Number X X X

InputRegister 7081 R ### NA Unit 7 Minor Revision Number X X X

InputRegister 7082 R ### NA Unit 7 Bug Fixes X X X

InputRegister 7083 R ### NAUnit 7 How long the unit has been running in minutes

X X X

Page 40: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 40 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

InputRegister 7084 R ## NA Unit 7 How many times unit has started X X X

InputRegister 7085 R ### NA Unit 7 How long the Fan is running in minutes X X

InputRegister 7086 R ## NA Unit 7 How many times Fan turned on X X

InputRegister 7087 R ### NA Unit 7 How long the Fan is running in minutes

InputRegister 7088 R ## NA Unit 7 How many times Fan turned on

InputRegister 7089 R ### NA Unit 7 How long the Blower is running in minutes X X X

InputRegister 7090 R ## NA Unit 7 How many times Blower turned on X X

InputRegister 7091 R ### NA Unit 7 How long the Blower is running in minutes

InputRegister 7092 R ## NA Unit 7 How many times Blower turned on

InputRegister 7093 R ### NA Unit 7 How long unit is running in Freecooling X X

InputRegister 7094 R ### NAUnit 7 How many times unit has been in Freecooling

X X

InputRegister 7095 R ### NA Unit 7 How long unit is running in Freecooling

InputRegister 7096 R ### NAUnit 7 How many times unit has been in Freecooling

InputRegister 7097 R ### NA Unit 7 How long unit is running in Cooling X X X

InputRegister 7098 R ### NA Unit 7 How many times unit has been in Cooling X X X

InputRegister 7099 R ### NA Unit 7 How long unit is running in Cooling X X

InputRegister 7100 R ### NA Unit 7 How many times unit has been in Cooling X X

InputRegister 7101 R ### NA Unit 7 How long unit is running in Cooling X

InputRegister 7102 R ### NA Unit 7 How many times unit has been in Cooling X

InputRegister 7103 R ### NA Unit 7 How long unit is running in Cooling

InputRegister 7104 R ### NA Unit 7 How many times unit has been in Cooling

InputRegister 7105 R ### NA Unit 7 How long unit is running in Heating X X X

InputRegister 7106 R ### NA Unit 7 How many times unit has been in Heating X X X

InputRegister 7107 R ### NA Unit 7 How long unit is running in Heating X X

InputRegister 7108 R ### NA Unit 7 How many times unit has been in Heating X X

InputRegister 7109 R ### NA Unit 7 How long unit is running in Heating

InputRegister 7110 R ### NA Unit 7 How many times unit has been in Heating

InputRegister 7111 R ### NA Unit 7 How long unit is running in Heating

InputRegister 7112 R ### NA Unit 7 How many times unit has been in Heating

InputRegister 7113 R ### 0-999999 Unit 7 life time in Hours (Update every Hour) X X X

InputRegister 7115 R ### 0-999999Unit 7 Blower 1 life time in Hours (Update every Hour)

X X

InputRegister 7117 R ### 0-999999Unit 7 Blower 2 life time in Hours (Update every Hour)

InputRegister 7119 R ### 0-999999Unit 7 Fan 1 life time in hours (Update every Hour)

X

InputRegister 7121 R ### 0-999999Unit 7 Fan 2 life time in hours (Update every Hour)

InputRegister 7123 R ### 0-999999Unit 7 Cooling 1 life time in hours (Update ever Hour)

X X

InputRegister 7125 R ### 0-999999Unit 7 Cooling 2 life time in hours (Update ever Hour)

X

InputRegister 7127 R ### 0-999999Unit 7 Cooling 3 life time in hours (Update ever Hour)

InputRegister 7129 R ### 0-999999Unit 7 Cooling 4 life time in hours (Update ever Hour)

InputRegister 7131 R ### 0-999999Unit 7 Heating 1 life time in hours (Update ever Hour)

X X

InputRegister 7133 R ### 0-999999Unit 7 Heating 2 life time in hours (Update ever Hour)

InputRegister 7135 R ### 0-999999Unit 7 Heating 3 life time in hours (Update ever Hour)

Page 41: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 41 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

InputRegister 7137 R ### 0-999999Unit 7 Heating 4 life time in hours (Update ever Hour)

InputRegister 7139 R ### 0-999999Unit 7 FreeCooling 1 life time in hours (Update ever Hour)

X X

InputRegister 7141 R ### 0-999999Unit 7 FreeCooling 2 life time in hours (Update ever Hour)

InputRegister 7143 R ### 0-5Unit 7 Indicates what unit types are running on the network

X X X

DiscreteInput 7500 R Off/On = 0/1 0-1Unit 7 Error in the number of retain memory writings Alarm

X X X

DiscreteInput 7501 R Off/On = 0/1 0-1 Unit 7 Error in retain memory writings Alarm X X X

DiscreteInput 7502 R Off/On = 0/1 0-1 Unit 7 Return Air Temperature Sensor Alarm X X X

DiscreteInput 7503 R Off/On = 0/1 0-1 Unit 7 High Return Air Temperature Alarm X X

DiscreteInput 7504 R Off/On = 0/1 0-1 Unit 7 Mixed Air Temperature Sensor Alarm X X

DiscreteInput 7505 R Off/On = 0/1 0-1 Unit 7 Mixed Air High Temperature Alarm X X

DiscreteInput 7506 R Off/On = 0/1 0-1 Unit 7 Mixed Air Low Temperature Alarm X X

DiscreteInput 7507 R Off/On = 0/1 0-1 Unit 7 Supply Air Temperature Sensor Alarm X X

DiscreteInput 7508 R Off/On = 0/1 0-1 Unit 7 High Supply Air Temperature Alarm X

DiscreteInput 7509 R Off/On = 0/1 0-1 Unit 7 Low Supply Air Temperature Alarm X

DiscreteInput 7510 R Off/On = 0/1 0-1 Unit 7 Outdoor Air Temperature Sensor Alarm X X X

DiscreteInput 7511 R Off/On = 0/1 0-1 Unit 7 Outdoor Air Humidity Sensor Alarm X X X

DiscreteInput 7512 R Off/On = 0/1 0-1 Unit 7 Dust Sensor Alarm X X

DiscreteInput 7513 R Off/On = 0/1 0-1 Unit 7 Dust Sensor High Dust Detection Alarm X X

DiscreteInput 7514 R Off/On = 0/1 0-1 Unit 7 Liquid Line Temp Sensor Alarm X X

DiscreteInput 7515 R Off/On = 0/1 0-1 Unit 7 Discharge Temp Sensor Alarm

DiscreteInput 7516 R Off/On = 0/1 0-1 Unit 7 Liquid Line Pressure Sensor Alarm X

DiscreteInput 7517 R Off/On = 0/1 0-1 Unit 7 Suction Temperature Sensor Alarm X X X

DiscreteInput 7518 R Off/On = 0/1 0-1 Unit 7 Suction Pressure Sensor Alarm X X X

DiscreteInput 7519 R Off/On = 0/1 0-1 Unit 7 Low Pressure Alarm X X X

DiscreteInput 7520 R Off/On = 0/1 0-1 Unit 7 High Pressure Alarm X X X

DiscreteInput 7521 R Off/On = 0/1 0-1 Unit 7 Damper 1 Failed to Open X X X

DiscreteInput 7522 R Off/On = 0/1 0-1 Unit 7 Damper 1 Failed to Close X X X

DiscreteInput 7523 R Off/On = 0/1 0-1 Unit 7 Freeze Temperature Sensor Alarm X X

DiscreteInput 7524 R Off/On = 0/1 0-1 Unit 7 Freeze Condition X X X

DiscreteInput 7525 R Off/On = 0/1 0-1 Unit 7 Blower Fail Alarm X X

DiscreteInput 7526 R Off/On = 0/1 0-1 Unit 7 Dirty Filter 1 Alarm X X X

DiscreteInput 7527 R Off/On = 0/1 0-1 Unit 7 Dirty Condenser Coil Alarm

DiscreteInput 7528 R Off/On = 0/1 0-1 Unit 7 Emergency Ventilation Mode Active Alarm X X X

DiscreteInput 7529 R Off/On = 0/1 0-1 Unit 7 Emergency Cooling Mode Active Alarm X X X

DiscreteInput 7530 R Off/On = 0/1 0-1Unit 7 Extreme High Return Temp Alarm (Heat Cutout) Alarm

X X X

DiscreteInput 7531 R Off/On = 0/1 0-1 Unit 7 Disable/Smoke Detector Alarm X X X

DiscreteInput 7532 R Off/On = 0/1 0-1 Unit 7 Power Loss Detected Alarm X

DiscreteInput 7533 R Off/On = 0/1 0-1 Unit 7 Low SuperHeat Alarm X X X

DiscreteInput 7534 R Off/On = 0/1 0-1 Unit 7 Low Evaporation Pressure Alarm X X X

DiscreteInput 7535 R Off/On = 0/1 0-1 Unit 7 High Evaporation Pressure Alarm X X X

DiscreteInput 7536 R Off/On = 0/1 0-1 Unit 7 High Condenser Temperature Alarm X X X

DiscreteInput 7537 R Off/On = 0/1 0-1 Unit 7 Low Suction pressure Alarm X X X

DiscreteInput 7538 R Off/On = 0/1 0-1 Unit 7 EEV motor error Alarm X X X

DiscreteInput 7539 R Off/On = 0/1 0-1 Unit 7 SelfTuning error Alarm X X X

DiscreteInput 7540 R Off/On = 0/1 0-1 Unit 7 Emergency close Alarm X X X

Page 42: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 42 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

DiscreteInput 7541 R Off/On = 0/1 0-1 Unit 7 High Delta Temperature Alarm

DiscreteInput 7542 R Off/On = 0/1 0-1 Unit 7 High Delta Pressure Alarm

DiscreteInput 7543 R Off/On = 0/1 0-1 Unit 7 Range Error Alarm X X X

DiscreteInput 7544 R Off/On = 0/1 0-1 Unit 7 Service Position Percent Alarm X X X

DiscreteInput 7545 R Off/On = 0/1 0-1 Unit 7 Valve ID Alarm X X X

DiscreteInput 7546 R Off/On = 0/1 0-1 Unit 7 Return Air Temperature Sensor 2 Alarm X

DiscreteInput 7547 R Off/On = 0/1 0-1 Unit 7 High Return Air Temperature 2 Alarm X

DiscreteInput 7548 R Off/On = 0/1 0-1 Unit 7 Mixed Air Temperature Sensor 2 Alarm X

DiscreteInput 7549 R Off/On = 0/1 0-1 Unit 7 Mixed Air High Temperature 2 Alarm

DiscreteInput 7550 R Off/On = 0/1 0-1 Unit 7 Mixed Air Low Temperature 2 Alarm

DiscreteInput 7551 R Off/On = 0/1 0-1 Unit 7 Supply Air Temperature Sensor 2 Alarm X

DiscreteInput 7552 R Off/On = 0/1 0-1 Unit 7 High Supply Air Temperature 2 Alarm

DiscreteInput 7553 R Off/On = 0/1 0-1 Unit 7 Low Supply Air Temperature 2 Alarm

DiscreteInput 7554 R Off/On = 0/1 0-1 Unit 7 Dust Sensor 2 Alarm

DiscreteInput 7555 R Off/On = 0/1 0-1 Unit 7 Dust Sensor High Dust Detection 2 Alarm

DiscreteInput 7556 R Off/On = 0/1 0-1 Unit 7 Liquid Line Temp Sensor 2 Alarm X

DiscreteInput 7557 R Off/On = 0/1 0-1 Unit 7 Liquid Line Pressure Sensor Alarm

DiscreteInput 7558 R Off/On = 0/1 0-1 Unit 7 Discharge Temp Sensor 2 Alarm

DiscreteInput 7559 R Off/On = 0/1 0-1 Unit 7 Discharge Pressure Sensor 2 Alarm X

DiscreteInput 7560 R Off/On = 0/1 0-1 Unit 7 Discharge Pressure Sensor 2 Alarm X

DiscreteInput 7561 R Off/On = 0/1 0-1 Unit 7 Suction Temperature Sensor 2 Alarm X

DiscreteInput 7562 R Off/On = 0/1 0-1 Unit 7 Suction Pressure Sensor 2 Alarm X

DiscreteInput 7563 R Off/On = 0/1 0-1 Unit 7 Low Pressure 2 Alarm X

DiscreteInput 7564 R Off/On = 0/1 0-1 Unit 7 High Pressure 2 Alarm X

DiscreteInput 7565 R Off/On = 0/1 0-1 Unit 7 Damper 2 Failed to Open X

DiscreteInput 7566 R Off/On = 0/1 0-1 Unit 7 Damper 2 Failed to Close X

DiscreteInput 7567 R Off/On = 0/1 0-1 Unit 7 Damper 3 Failed to Open X

DiscreteInput 7568 R Off/On = 0/1 0-1 Unit 7 Damper 3 Failed to Close X

DiscreteInput 7569 R Off/On = 0/1 0-1 Unit 7 Damper 4 Failed to Open

DiscreteInput 7570 R Off/On = 0/1 0-1 Unit 7 Damper 4 Failed to Close

DiscreteInput 7571 R Off/On = 0/1 0-1 Unit 7 Freeze Temperature Sensor Alarm X

DiscreteInput 7572 R Off/On = 0/1 0-1 Unit 7 Freeze Condition Alarm X

DiscreteInput 7573 R Off/On = 0/1 0-1 Unit 7 Blower Fail Alarm

DiscreteInput 7574 R Off/On = 0/1 0-1 Unit 7 Dirty Filter 2 Alarm

DiscreteInput 7575 R Off/On = 0/1 0-1 Unit 7 Dirty Filter 3 Alarm

DiscreteInput 7576 R Off/On = 0/1 0-1 Unit 7 Dirty Filter 4 Alarm

DiscreteInput 7577 R Off/On = 0/1 0-1 Unit 7 Dirty Condenser Coil 2 Alarm

DiscreteInput 7578 R Off/On = 0/1 0-1 Unit 7 Power Loss 2 Detected Alarm

DiscreteInput 7579 R Off/On = 0/1 0-1 Unit 7 Low SuperHeat 2 Alarm X

DiscreteInput 7580 R Off/On = 0/1 0-1 Unit 7 Low Evaporation Pressure 2 Alarm X

DiscreteInput 7581 R Off/On = 0/1 0-1 Unit 7 High Evaporation Pressure 2 Alarm X

DiscreteInput 7582 R Off/On = 0/1 0-1 Unit 7 High Condenser Temperature 2 Alarm X

DiscreteInput 7583 R Off/On = 0/1 0-1 Unit 7 Low Suction pressure 2 Alarm X

DiscreteInput 7584 R Off/On = 0/1 0-1 Unit 7 EEV motor 2 error Alarm X

DiscreteInput 7585 R Off/On = 0/1 0-1 Unit 7 SelfTuning 2 error Alarm X

DiscreteInput 7586 R Off/On = 0/1 0-1 Unit 7 Emergency close 2 Alarm X

DiscreteInput 7587 R Off/On = 0/1 0-1 Unit 7 High Delta Temperature 2 Alarm

DiscreteInput 7588 R Off/On = 0/1 0-1 Unit 7 High Delta Pressure 2 Alarm

DiscreteInput 7589 R Off/On = 0/1 0-1 Unit 7 Range Error 2 Alarm X

Page 43: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 43 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

DiscreteInput 7590 R Off/On = 0/1 0-1 Unit 7 Service Position Percent 2 Alarm X

DiscreteInput 7591 R Off/On = 0/1 0-1 Unit 7 Valve ID 2 Alarm X

DiscreteInput 7592 R Off/On = 0/1 0-1 Unit 7 Th-Tune Device Offline Alarm X

DiscreteInput 7593 R Off/On = 0/1 0-1 Unit 7 Th-Tune Temperature Probe Alarm X

DiscreteInput 7594 R Off/On = 0/1 0-1 Unit 7 Th-Tune Humidity Probe Alarm X

DiscreteInput 7595 R Off/On = 0/1 0-1 Unit 7 Th-Tune Clock Board Alarm X

DiscreteInput 7596 R Off/On = 0/1 0-1 Unit 7 cpCOe Offline Alarm X

DiscreteInput 7597 R Off/On = 0/1 0-1 Unit 7 Blower 1 Offline Alarm X

DiscreteInput 7598 R Off/On = 0/1 0-1 Unit 7 Blower 1 Alarm X

DiscreteInput 7599 R Off/On = 0/1 0-1 Unit 7 Blower 2 Offline Alarm

DiscreteInput 7600 R Off/On = 0/1 0-1 Unit 7 Blower 2 Alarm

DiscreteInput 7601 R Off/On = 0/1 0-1 Unit 7 Condenser 1 Offline Alarm X

DiscreteInput 7602 R Off/On = 0/1 0-1 Unit 7 Condenser 1 Alarm X

DiscreteInput 7603 R Off/On = 0/1 0-1 Unit 7 Condenser 2 Offline Alarm

DiscreteInput 7604 R Off/On = 0/1 0-1 Unit 7 Condenser 2 Alarm

DiscreteInput 7605 R Off/On = 0/1 0-1 Unit 7 Low Return Air Temperature 1 Alarm X

DiscreteInput 7606 R Off/On = 0/1 0-1 Unit 7 Low Return Air Temperature 2 Alarm X

DiscreteInput 7607 R Off/On = 0/1 0-1 Unit 7 Panel Open Alarm X

DiscreteInput 8000 R Off/On = 0/1 0-1 Unit 8 Dirty Filter 1 Alarm X X X

DiscreteInput 8001 R Off/On = 0/1 0-1 Unit 8 Dirty Filter 2 Alarm X

DiscreteInput 8002 R Off/On = 0/1 0-1 Unit 8 Dirty Filter 3 Alarm

DiscreteInput 8003 R Off/On = 0/1 0-1 Unit 8 Indicates Blower 1 Is Running In Unit X X

InputRegister 8003 R 0-14 0-14 Unit 8 Compressor 1 Status X X X

DiscreteInput 8004 R Off/On = 0/1 0-1 Unit 8 Indicates Blower 2 Is Running In Unit

InputRegister 8004 R 0-14 0-14 Unit 8 Compressor 2 Status X

DiscreteInput 8005 R Off/On = 0/1 0-1 Unit 8 Low Pressure Switch 1 X

DiscreteInput 8006 R Off/On = 0/1 0-1 Unit 8 Low Pressure Switch 2

DiscreteInput 8007 R Off/On = 0/1 0-1 Unit 8 Damper Switch 1 Open X X X

DiscreteInput 8008 R Off/On = 0/1 0-1 Unit 8 Damper Switch 2 Open X

DiscreteInput 8009 R Off/On = 0/1 0-1 Unit 8 Damper Switch 3 Open X

DiscreteInput 8010 R Off/On = 0/1 0-1 Unit 8 Damper Switch 4 Open

InputRegister 8011 R ###.# NA Unit 8 Mixed Air Temperature Sensor 1 X X X

DiscreteInput 8012 R Off/On = 0/1 0-1 Unit 8 Activates Reheat Valve for Dehum X

InputRegister 8013 R ###.# NA Unit 8 Mixed Air Temperature Sensor 2 X

InputRegister 8014 R Zone1, 2, or 3 1-3 Unit 8 Zone Options X X X

InputRegister 8015 R ###.# NA Unit 8 Outdoor Air Temperature Sensor 1 X X X

InputRegister 8017 R ###.# NA Unit 8 Outdoor Air Temperature Sensor 2

InputRegister 8019 R ###.# NA Unit 8 Return Air Temperature Sensor 1 X X X

InputRegister 8021 R ###.# NA Unit 8 Return Air Temperature Sensor 2 X

InputRegister 8023 R ###.# 0-100% Unit 8 Outdoor Humidity Sensor 1 X X

InputRegister 8025 R ###.# 0-100% Unit 8 Outdoor Humidity Sensor 2

InputRegister 8027 R ###.# NA Unit 8 Freeze Sensor 1 X

DiscreteInput 8029 R Off/On = 0/1 0-1 Unit 8 Heat 1 On/Off X X X

InputRegister 8029 R ###.# NA Unit 8 Freeze Sensor 2

DiscreteInput 8030 R Off/On = 0/1 0-1 Unit 8 Heat 2 On/Off X X X

DiscreteInput 8031 R Off/On = 0/1 0-1 Unit 8 Heat 3 On/Off X

DiscreteInput 8032 R Off/On = 0/1 0-1 Unit 8 Heat 4 On/Off

DiscreteInput 8033 R Off/On = 0/1 0-1 Unit 8 FreeCool Is Available X X X

DiscreteInput 8034 R Off/On = 0/1 0-1 Unit 8 Dirty Filter Indicator X X

Page 44: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 44 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

InputRegister 8034 R ### 0-100% Unit 8 Blower Speed 1 X X

DiscreteInput 8035 R Off/On = 0/1 0-1 Unit 8 Cooling 1 On/Off X X X

InputRegister 8035 R ### 0-100% Unit 8 Blower Speed 2

DiscreteInput 8036 R Off/On = 0/1 0-1 Unit 8 Cooling 2 On/Off X X X

InputRegister 8036 R ### 0-45 bar Unit 8 Discharge Pressure Transducer 1

DiscreteInput 8037 R Off/On = 0/1 0-1 Unit 8 Cooling 3 On/Off X

InputRegister 8037 R ### 0-45 bar Unit 8 Discharge Pressure Transducer 2

DiscreteInput 8038 R Off/On = 0/1 0-1 Unit 8 Cooling 4 On/Off

InputRegister 8038 R ###.# NA Unit 8 Discharge Temperature 1

DiscreteInput 8039 R Off/On = 0/1 0-1 Unit 8 Indicates No Air Flow X X

InputRegister 8039 R ###.# NA Unit 8 Discharge Temperature 2

DiscreteInput 8040 R Off/On = 0/1 0-1 Unit 8 Indicates No Air Flow 2

InputRegister 8040 R ### 0-100% Unit 8 Dust Sensor 1 X X

DiscreteInput 8041 R Off/On = 0/1 0-1 Unit 8 High Pressure 1 Event X X X

InputRegister 8041 R ### 0-100% Unit 8 Dust Sensor 2

DiscreteInput 8042 R Off/On = 0/1 0-1 Unit 8 High Pressure 2 Event X

DiscreteInput 8043 R Off/On = 0/1 0-1 Unit 8 Power Loss Detected Alarm X X

DiscreteInput 8044 R Off/On = 0/1 0-1 Unit 8 Is Disabled X X X

InputRegister 8044 R ###.# NA Unit 8 Liquid Temperature 1 X X

InputRegister 8045 R ###.# NA Unit 8 Liquid Temperature 2 X

InputRegister 8046 R ### NA Unit 8 Liquid Pressure 1 X

InputRegister 8047 R ### NA Unit 8 Liquid Pressure 2

InputRegister 8048 R ### NA Unit 8 Suction Pressure 1 X X

InputRegister 8049 R ### NA Unit 8 Suction Pressure 2

InputRegister 8050 R ###.# NA Unit 8 Suction Temperature 1 X X

InputRegister 8051 R ###.# NA Unit 8 Suction Temperature 2

InputRegister 8052 R ###.# NA Unit 8 Supply Air Temperature 1 X X

InputRegister 8053 R ###.# NA Unit 8 Supply Air Temperature 2 X

InputRegister 8056 R ### 0-100% Unit 8 Condenser Fan Speed 1 X X

InputRegister 8057 R ### 0-100% Unit 8 Condenser Fan Speed 2 X

InputRegister 8058 R ### 0-100% Unit 8 Damper Position 1 X X X

InputRegister 8059 R ### 0-100% Unit 8 Damper Position 2 X

InputRegister 8060 R ### 0-100% Unit 8 Damper Position 3 X

InputRegister 8061 R ### 0-100% Unit 8 Damper Position 4 X

InputRegister 8062 R ### 0-100% Unit 8 EEV1 Position X X X

InputRegister 8063 R ### 0-100% Unit 8 EEV2 Position X

InputRegister 8064 R ### NA Unit 8 Declares number of Cooling Stages X X

InputRegister 8065 R ### NA Unit 8 Declares number of Heating Stages X X

InputRegister 8066 R ### NA Unit 8 Declares number of Freecooling Stages X X

InputRegister 8067 R ### NA Unit 8 Outdoor Air Dewpoint X

InputRegister 8068 R ### 0,1,2,3 Unit 8 Dehumidification Type X X

InputRegister 8069 R ###.# NA Unit 8 Suction Saturation Temperature 1

InputRegister 8070 R ###.# NA Unit 8 Suction Saturation Temperature 2

InputRegister 8071 R ### NA Unit 8 Subcooling 1 X

InputRegister 8072 R ### NA Unit 8 Superheat 1

InputRegister 8073 R ### NA Unit 8 Superheat 2

InputRegister 8074 R ###.# NA Unit 8 Liquid Saturated Temperature 1

InputRegister 8075 R ###.# NA Unit 8 Liquid Saturated Temperature 2

InputRegister 8076 R ### NA Unit 8 Subcooling 2

Page 45: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 45 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

InputRegister 8080 R ### NA Unit 8 Major Revision Number X X X

InputRegister 8081 R ### NA Unit 8 Minor Revision Number X X X

InputRegister 8082 R ### NA Unit 8 Bug Fixes X X X

InputRegister 8083 R ### NAUnit 8 How long the unit has been running in minutes

X X X

InputRegister 8084 R ## NA Unit 8 How many times unit has started X X X

InputRegister 8085 R ### NA Unit 8 How long the Fan is running in minutes X X

InputRegister 8086 R ## NA Unit 8 How many times Fan turned on X X

InputRegister 8087 R ### NA Unit 8 How long the Fan is running in minutes

InputRegister 8088 R ## NA Unit 8 How many times Fan turned on

InputRegister 8089 R ### NA Unit 8 How long the Blower is running in minutes X X X

InputRegister 8090 R ## NA Unit 8 How many times Blower turned on X X

InputRegister 8091 R ### NA Unit 8 How long the Blower is running in minutes

InputRegister 8092 R ## NA Unit 8 How many times Blower turned on

InputRegister 8093 R ### NA Unit 8 How long unit is running in Freecooling X X

InputRegister 8094 R ### NAUnit 8 How many times unit has been in Freecooling

X X

InputRegister 8095 R ### NA Unit 8 How long unit is running in Freecooling

InputRegister 8096 R ### NAUnit 8 How many times unit has been in Freecooling

InputRegister 8097 R ### NA Unit 8 How long unit is running in Cooling X X X

InputRegister 8098 R ### NA Unit 8 How many times unit has been in Cooling X X X

InputRegister 8099 R ### NA Unit 8 How long unit is running in Cooling X X

InputRegister 8100 R ### NA Unit 8 How many times unit has been in Cooling X X

InputRegister 8101 R ### NA Unit 8 How long unit is running in Cooling X

InputRegister 8102 R ### NA Unit 8 How many times unit has been in Cooling X

InputRegister 8103 R ### NA Unit 8 How long unit is running in Cooling

InputRegister 8104 R ### NA Unit 8 How many times unit has been in Cooling

InputRegister 8105 R ### NA Unit 8 How long unit is running in Heating X X X

InputRegister 8106 R ### NA Unit 8 How many times unit has been in Heating X X X

InputRegister 8107 R ### NA Unit 8 How long unit is running in Heating X X

InputRegister 8108 R ### NA Unit 8 How many times unit has been in Heating X X

InputRegister 8109 R ### NA Unit 8 How long unit is running in Heating

InputRegister 8110 R ### NA Unit 8 How many times unit has been in Heating

InputRegister 8111 R ### NA Unit 8 How long unit is running in Heating

InputRegister 8112 R ### NA Unit 8 How many times unit has been in Heating

InputRegister 8113 R ### 0-999999 Unit 8 life time in Hours (Update every Hour) X X X

InputRegister 8115 R ### 0-999999Unit 8 Blower 1 life time in Hours (Update every Hour)

X X

InputRegister 8117 R ### 0-999999Unit 8 Blower 2 life time in Hours (Update every Hour)

InputRegister 8119 R ### 0-999999Unit 8 Fan 1 life time in hours (Update every Hour)

X

InputRegister 8121 R ### 0-999999Unit 8 Fan 2 life time in hours (Update every Hour)

InputRegister 8123 R ### 0-999999Unit 8 Cooling 1 life time in hours (Update ever Hour)

X X

InputRegister 8125 R ### 0-999999Unit 8 Cooling 2 life time in hours (Update ever Hour)

X

InputRegister 8127 R ### 0-999999Unit 8 Cooling 3 life time in hours (Update ever Hour)

InputRegister 8129 R ### 0-999999Unit 8 Cooling 4 life time in hours (Update ever Hour)

Page 46: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 46 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

InputRegister 8131 R ### 0-999999Unit 8 Heating 1 life time in hours (Update ever Hour)

X X

InputRegister 8133 R ### 0-999999Unit 8 Heating 2 life time in hours (Update ever Hour)

InputRegister 8135 R ### 0-999999Unit 8 Heating 3 life time in hours (Update ever Hour)

InputRegister 8137 R ### 0-999999Unit 8 Heating 4 life time in hours (Update ever Hour)

InputRegister 8139 R ### 0-999999Unit 8 FreeCooling 1 life time in hours (Update ever Hour)

X X

InputRegister 8141 R ### 0-999999Unit 8 FreeCooling 2 life time in hours (Update ever Hour)

InputRegister 8143 R ### 0-5Unit 8 Indicates what unit types are running on the network

X X X

DiscreteInput 8500 R Off/On = 0/1 0-1Unit 8 Error in the number of retain memory writings Alarm

X X X

DiscreteInput 8501 R Off/On = 0/1 0-1 Unit 8 Error in retain memory writings Alarm X X X

DiscreteInput 8502 R Off/On = 0/1 0-1 Unit 8 Return Air Temperature Sensor Alarm X X X

DiscreteInput 8503 R Off/On = 0/1 0-1 Unit 8 High Return Air Temperature Alarm X X

DiscreteInput 8504 R Off/On = 0/1 0-1 Unit 8 Mixed Air Temperature Sensor Alarm X X

DiscreteInput 8505 R Off/On = 0/1 0-1 Unit 8 Mixed Air High Temperature Alarm X X

DiscreteInput 8506 R Off/On = 0/1 0-1 Unit 8 Mixed Air Low Temperature Alarm X X

DiscreteInput 8507 R Off/On = 0/1 0-1 Unit 8 Supply Air Temperature Sensor Alarm X X

DiscreteInput 8508 R Off/On = 0/1 0-1 Unit 8 High Supply Air Temperature Alarm X

DiscreteInput 8509 R Off/On = 0/1 0-1 Unit 8 Low Supply Air Temperature Alarm X

DiscreteInput 8510 R Off/On = 0/1 0-1 Unit 8 Outdoor Air Temperature Sensor Alarm X X X

DiscreteInput 8511 R Off/On = 0/1 0-1 Unit 8 Outdoor Air Humidity Sensor Alarm X X X

DiscreteInput 8512 R Off/On = 0/1 0-1 Unit 8 Dust Sensor Alarm X X

DiscreteInput 8513 R Off/On = 0/1 0-1 Unit 8 Dust Sensor High Dust Detection Alarm X X

DiscreteInput 8514 R Off/On = 0/1 0-1 Unit 8 Liquid Line Temp Sensor Alarm X X

DiscreteInput 8515 R Off/On = 0/1 0-1 Unit 8 Discharge Temp Sensor Alarm

DiscreteInput 8516 R Off/On = 0/1 0-1 Unit 8 Liquid Line Pressure Sensor Alarm X

DiscreteInput 8517 R Off/On = 0/1 0-1 Unit 8 Suction Temperature Sensor Alarm X X X

DiscreteInput 8518 R Off/On = 0/1 0-1 Unit 8 Suction Pressure Sensor Alarm X X X

DiscreteInput 8519 R Off/On = 0/1 0-1 Unit 8 Low Pressure Alarm X X X

DiscreteInput 8520 R Off/On = 0/1 0-1 Unit 8 High Pressure Alarm X X X

DiscreteInput 8521 R Off/On = 0/1 0-1 Unit 8 Damper 1 Failed to Open X X X

DiscreteInput 8522 R Off/On = 0/1 0-1 Unit 8 Damper 1 Failed to Close X X X

DiscreteInput 8523 R Off/On = 0/1 0-1 Unit 8 Freeze Temperature Sensor Alarm X X

DiscreteInput 8524 R Off/On = 0/1 0-1 Unit 8 Freeze Condition X X X

DiscreteInput 8525 R Off/On = 0/1 0-1 Unit 8 Blower Fail Alarm X X

DiscreteInput 8526 R Off/On = 0/1 0-1 Unit 8 Dirty Filter 1 Alarm X X X

DiscreteInput 8527 R Off/On = 0/1 0-1 Unit 8 Dirty Condenser Coil Alarm

DiscreteInput 8528 R Off/On = 0/1 0-1 Unit 8 Emergency Ventilation Mode Active Alarm X X X

DiscreteInput 8529 R Off/On = 0/1 0-1 Unit 8 Emergency Cooling Mode Active Alarm X X X

DiscreteInput 8530 R Off/On = 0/1 0-1Unit 8 Extreme High Return Temp Alarm (Heat Cutout) Alarm

X X X

DiscreteInput 8531 R Off/On = 0/1 0-1 Unit 8 Disable/Smoke Detector Alarm X X X

DiscreteInput 8532 R Off/On = 0/1 0-1 Unit 8 Power Loss Detected Alarm X

DiscreteInput 8533 R Off/On = 0/1 0-1 Unit 8 Low SuperHeat Alarm X X X

DiscreteInput 8534 R Off/On = 0/1 0-1 Unit 8 Low Evaporation Pressure Alarm X X X

DiscreteInput 8535 R Off/On = 0/1 0-1 Unit 8 High Evaporation Pressure Alarm X X X

Page 47: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 47 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

DiscreteInput 8536 R Off/On = 0/1 0-1 Unit 8 High Condenser Temperature Alarm X X X

DiscreteInput 8537 R Off/On = 0/1 0-1 Unit 8 Low Suction pressure Alarm X X X

DiscreteInput 8538 R Off/On = 0/1 0-1 Unit 8 EEV motor error Alarm X X X

DiscreteInput 8539 R Off/On = 0/1 0-1 Unit 8 SelfTuning error Alarm X X X

DiscreteInput 8540 R Off/On = 0/1 0-1 Unit 8 Emergency close Alarm X X X

DiscreteInput 8541 R Off/On = 0/1 0-1 Unit 8 High Delta Temperature Alarm

DiscreteInput 8542 R Off/On = 0/1 0-1 Unit 8 High Delta Pressure Alarm

DiscreteInput 8543 R Off/On = 0/1 0-1 Unit 8 Range Error Alarm X X X

DiscreteInput 8544 R Off/On = 0/1 0-1 Unit 8 Service Position Percent Alarm X X X

DiscreteInput 8545 R Off/On = 0/1 0-1 Unit 8 Valve ID Alarm X X X

DiscreteInput 8546 R Off/On = 0/1 0-1 Unit 8 Return Air Temperature Sensor 2 Alarm X

DiscreteInput 8547 R Off/On = 0/1 0-1 Unit 8 High Return Air Temperature 2 Alarm X

DiscreteInput 8548 R Off/On = 0/1 0-1 Unit 8 Mixed Air Temperature Sensor 2 Alarm X

DiscreteInput 8549 R Off/On = 0/1 0-1 Unit 8 Mixed Air High Temperature 2 Alarm

DiscreteInput 8550 R Off/On = 0/1 0-1 Unit 8 Mixed Air Low Temperature 2 Alarm

DiscreteInput 8551 R Off/On = 0/1 0-1 Unit 8 Supply Air Temperature Sensor 2 Alarm X

DiscreteInput 8552 R Off/On = 0/1 0-1 Unit 8 High Supply Air Temperature 2 Alarm

DiscreteInput 8553 R Off/On = 0/1 0-1 Unit 8 Low Supply Air Temperature 2 Alarm

DiscreteInput 8554 R Off/On = 0/1 0-1 Unit 8 Dust Sensor 2 Alarm

DiscreteInput 8555 R Off/On = 0/1 0-1 Unit 8 Dust Sensor High Dust Detection 2 Alarm

DiscreteInput 8556 R Off/On = 0/1 0-1 Unit 8 Liquid Line Temp Sensor 2 Alarm X

DiscreteInput 8557 R Off/On = 0/1 0-1 Unit 8 Liquid Line Pressure Sensor Alarm

DiscreteInput 8558 R Off/On = 0/1 0-1 Unit 8 Discharge Temp Sensor 2 Alarm

DiscreteInput 8559 R Off/On = 0/1 0-1 Unit 8 Discharge Pressure Sensor 2 Alarm X

DiscreteInput 8560 R Off/On = 0/1 0-1 Unit 8 Discharge Pressure Sensor 2 Alarm X

DiscreteInput 8561 R Off/On = 0/1 0-1 Unit 8 Suction Temperature Sensor 2 Alarm X

DiscreteInput 8562 R Off/On = 0/1 0-1 Unit 8 Suction Pressure Sensor 2 Alarm X

DiscreteInput 8563 R Off/On = 0/1 0-1 Unit 8 Low Pressure 2 Alarm X

DiscreteInput 8564 R Off/On = 0/1 0-1 Unit 8 High Pressure 2 Alarm X

DiscreteInput 8565 R Off/On = 0/1 0-1 Unit 8 Damper 2 Failed to Open X

DiscreteInput 8566 R Off/On = 0/1 0-1 Unit 8 Damper 2 Failed to Close X

DiscreteInput 8567 R Off/On = 0/1 0-1 Unit 8 Damper 3 Failed to Open X

DiscreteInput 8568 R Off/On = 0/1 0-1 Unit 8 Damper 3 Failed to Close X

DiscreteInput 8569 R Off/On = 0/1 0-1 Unit 8 Damper 4 Failed to Open

DiscreteInput 8570 R Off/On = 0/1 0-1 Unit 8 Damper 4 Failed to Close

DiscreteInput 8571 R Off/On = 0/1 0-1 Unit 8 Freeze Temperature Sensor Alarm X

DiscreteInput 8572 R Off/On = 0/1 0-1 Unit 8 Freeze Condition Alarm X

DiscreteInput 8573 R Off/On = 0/1 0-1 Unit 8 Blower Fail Alarm

DiscreteInput 8574 R Off/On = 0/1 0-1 Unit 8 Dirty Filter 2 Alarm

DiscreteInput 8575 R Off/On = 0/1 0-1 Unit 8 Dirty Filter 3 Alarm

DiscreteInput 8576 R Off/On = 0/1 0-1 Unit 8 Dirty Filter 4 Alarm

DiscreteInput 8577 R Off/On = 0/1 0-1 Unit 8 Dirty Condenser Coil 2 Alarm

DiscreteInput 8578 R Off/On = 0/1 0-1 Unit 8 Power Loss 2 Detected Alarm

DiscreteInput 8579 R Off/On = 0/1 0-1 Unit 8 Low SuperHeat 2 Alarm X

DiscreteInput 8580 R Off/On = 0/1 0-1 Unit 8 Low Evaporation Pressure 2 Alarm X

DiscreteInput 8581 R Off/On = 0/1 0-1 Unit 8 High Evaporation Pressure 2 Alarm X

DiscreteInput 8582 R Off/On = 0/1 0-1 Unit 8 High Condenser Temperature 2 Alarm X

DiscreteInput 8583 R Off/On = 0/1 0-1 Unit 8 Low Suction pressure 2 Alarm X

DiscreteInput 8584 R Off/On = 0/1 0-1 Unit 8 EEV motor 2 error Alarm X

Page 48: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 48 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

DiscreteInput 8585 R Off/On = 0/1 0-1 Unit 8 SelfTuning 2 error Alarm X

DiscreteInput 8586 R Off/On = 0/1 0-1 Unit 8 Emergency close 2 Alarm X

DiscreteInput 8587 R Off/On = 0/1 0-1 Unit 8 High Delta Temperature 2 Alarm

DiscreteInput 8588 R Off/On = 0/1 0-1 Unit 8 High Delta Pressure 2 Alarm

DiscreteInput 8589 R Off/On = 0/1 0-1 Unit 8 Range Error 2 Alarm X

DiscreteInput 8590 R Off/On = 0/1 0-1 Unit 8 Service Position Percent 2 Alarm X

DiscreteInput 8591 R Off/On = 0/1 0-1 Unit 8 Valve ID 2 Alarm X

DiscreteInput 8592 R Off/On = 0/1 0-1 Unit 8 Th-Tune Device Offline Alarm X

DiscreteInput 8593 R Off/On = 0/1 0-1 Unit 8 Th-Tune Temperature Probe Alarm X

DiscreteInput 8594 R Off/On = 0/1 0-1 Unit 8 Th-Tune Humidity Probe Alarm X

DiscreteInput 8595 R Off/On = 0/1 0-1 Unit 8 Th-Tune Clock Board Alarm X

DiscreteInput 8596 R Off/On = 0/1 0-1 Unit 8 cpCOe Offline Alarm X

DiscreteInput 8597 R Off/On = 0/1 0-1 Unit 8 Blower 1 Offline Alarm X

DiscreteInput 8598 R Off/On = 0/1 0-1 Unit 8 Blower 1 Alarm X

DiscreteInput 8599 R Off/On = 0/1 0-1 Unit 8 Blower 2 Offline Alarm

DiscreteInput 8600 R Off/On = 0/1 0-1 Unit 8 Blower 2 Alarm

DiscreteInput 8601 R Off/On = 0/1 0-1 Unit 8 Condenser 1 Offline Alarm X

DiscreteInput 8602 R Off/On = 0/1 0-1 Unit 8 Condenser 1 Alarm X

DiscreteInput 8603 R Off/On = 0/1 0-1 Unit 8 Condenser 2 Offline Alarm

DiscreteInput 8604 R Off/On = 0/1 0-1 Unit 8 Condenser 2 Alarm

DiscreteInput 8605 R Off/On = 0/1 0-1 Unit 8 Low Return Air Temperature 1 Alarm X

DiscreteInput 8606 R Off/On = 0/1 0-1 Unit 8 Low Return Air Temperature 2 Alarm X

DiscreteInput 8607 R Off/On = 0/1 0-1 Unit 8 Panel Open Alarm X

DiscreteInput 9000 R Off/On = 0/1 0-1 Unit 9 Dirty Filter 1 Alarm X X X

DiscreteInput 9001 R Off/On = 0/1 0-1 Unit 9 Dirty Filter 2 Alarm X

DiscreteInput 9002 R Off/On = 0/1 0-1 Unit 9 Dirty Filter 3 Alarm

DiscreteInput 9003 R Off/On = 0/1 0-1 Unit 9 Indicates Blower 1 Is Running In Unit X X

InputRegister 9003 R 0-14 0-14 Unit 9 Compressor 1 Status X X X

DiscreteInput 9004 R Off/On = 0/1 0-1 Unit 9 Indicates Blower 2 Is Running In Unit

InputRegister 9004 R 0-14 0-14 Unit 9 Compressor 2 Status X

DiscreteInput 9005 R Off/On = 0/1 0-1 Unit 9 Low Pressure Switch 1 X

DiscreteInput 9006 R Off/On = 0/1 0-1 Unit 9 Low Pressure Switch 2

DiscreteInput 9007 R Off/On = 0/1 0-1 Unit 9 Damper Switch 1 Open X X X

DiscreteInput 9008 R Off/On = 0/1 0-1 Unit 9 Damper Switch 2 Open X

DiscreteInput 9009 R Off/On = 0/1 0-1 Unit 9 Damper Switch 3 Open X

DiscreteInput 9010 R Off/On = 0/1 0-1 Unit 9 Damper Switch 4 Open

InputRegister 9011 R ###.# NA Unit 9 Mixed Air Temperature Sensor 1 X X X

DiscreteInput 9012 R Off/On = 0/1 0-1 Unit 9 Activates Reheat Valve for Dehum X

InputRegister 9013 R ###.# NA Unit 9 Mixed Air Temperature Sensor 2 X

InputRegister 9014 R Zone1, 2, or 3 1-3 Unit 9 Zone Options X X X

InputRegister 9015 R ###.# NA Unit 9 Outdoor Air Temperature Sensor 1 X X X

InputRegister 9017 R ###.# NA Unit 9 Outdoor Air Temperature Sensor 2

InputRegister 9019 R ###.# NA Unit 9 Return Air Temperature Sensor 1 X X X

InputRegister 9021 R ###.# NA Unit 9 Return Air Temperature Sensor 2 X

InputRegister 9023 R ###.# 0-100% Unit 9 Outdoor Humidity Sensor 1 X X

InputRegister 9025 R ###.# 0-100% Unit 9 Outdoor Humidity Sensor 2

InputRegister 9027 R ###.# NA Unit 9 Freeze Sensor 1 X

DiscreteInput 9029 R Off/On = 0/1 0-1 Unit 9 Heat 1 On/Off X X X

InputRegister 9029 R ###.# NA Unit 9 Freeze Sensor 2

Page 49: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 49 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

DiscreteInput 9030 R Off/On = 0/1 0-1 Unit 9 Heat 2 On/Off X X X

DiscreteInput 9031 R Off/On = 0/1 0-1 Unit 9 Heat 3 On/Off X

DiscreteInput 9032 R Off/On = 0/1 0-1 Unit 9 Heat 4 On/Off

DiscreteInput 9033 R Off/On = 0/1 0-1 Unit 9 FreeCool Is Available X X X

DiscreteInput 9034 R Off/On = 0/1 0-1 Unit 9 Dirty Filter Indicator X X

InputRegister 9034 R ### 0-100% Unit 9 Blower Speed 1 X X

DiscreteInput 9035 R Off/On = 0/1 0-1 Unit 9 Cooling 1 On/Off X X X

InputRegister 9035 R ### 0-100% Unit 9 Blower Speed 2

DiscreteInput 9036 R Off/On = 0/1 0-1 Unit 9 Cooling 2 On/Off X X X

InputRegister 9036 R ### 0-45 bar Unit 9 Discharge Pressure Transducer 1

DiscreteInput 9037 R Off/On = 0/1 0-1 Unit 9 Cooling 3 On/Off X

InputRegister 9037 R ### 0-45 bar Unit 9 Discharge Pressure Transducer 2

DiscreteInput 9038 R Off/On = 0/1 0-1 Unit 9 Cooling 4 On/Off

InputRegister 9038 R ###.# NA Unit 9 Discharge Temperature 1

DiscreteInput 9039 R Off/On = 0/1 0-1 Unit 9 Indicates No Air Flow X X

InputRegister 9039 R ###.# NA Unit 9 Discharge Temperature 2

DiscreteInput 9040 R Off/On = 0/1 0-1 Unit 9 Indicates No Air Flow 2

InputRegister 9040 R ### 0-100% Unit 9 Dust Sensor 1 X X

DiscreteInput 9041 R Off/On = 0/1 0-1 Unit 9 High Pressure 1 Event X X X

InputRegister 9041 R ### 0-100% Unit 9 Dust Sensor 2

DiscreteInput 9042 R Off/On = 0/1 0-1 Unit 9 High Pressure 2 Event X

DiscreteInput 9043 R Off/On = 0/1 0-1 Unit 9 Power Loss X X

DiscreteInput 9044 R Off/On = 0/1 0-1 Unit 9 Is Disabled (Power Off) X X X

InputRegister 9044 R ###.# NA Unit 9 Liquid Temperature 1 X X

InputRegister 9045 R ###.# NA Unit 9 Liquid Temperature 2 X

InputRegister 9046 R ### NA Unit 9 Liquid Pressure 1 X

InputRegister 9047 R ### NA Unit 9 Liquid Pressure 2

InputRegister 9048 R ### NA Unit 9 Suction Pressure 1 X X

InputRegister 9049 R ### NA Unit 9 Suction Pressure 2

InputRegister 9050 R ###.# NA Unit 9 Suction Temperature 1 X X

InputRegister 9051 R ###.# NA Unit 9 Suction Temperature 2

InputRegister 9052 R ###.# NA Unit 9 Supply Air Temperature 1 X X

InputRegister 9053 R ###.# NA Unit 9 Supply Air Temperature 2 X

InputRegister 9056 R ### 0-100% Unit 9 Condenser Fan Speed 1 X X

InputRegister 9057 R ### 0-100% Unit 9 Condenser Fan Speed 2 X

InputRegister 9058 R ### 0-100% Unit 9 Damper Position 1 X X X

InputRegister 9059 R ### 0-100% Unit 9 Damper Position 2 X

InputRegister 9060 R ### 0-100% Unit 9 Damper Position 3 X

InputRegister 9061 R ### 0-100% Unit 9 Damper Position 4 X

InputRegister 9062 R ### 0-100% Unit 9 EEV1 Position X X X

InputRegister 9063 R ### 0-100% Unit 9 EEV2 Position X

InputRegister 9064 R ### NA Unit 9 Declares number of Cooling Stages X X

InputRegister 9065 R ### NA Unit 9 Declares number of Heating Stages X X

InputRegister 9066 R ### NA Unit 9 Declares number of Freecooling Stages X X

InputRegister 9067 R ### NA Unit 9 Outdoor Air Dewpoint X

InputRegister 9068 R ### 0,1,2,3 Unit 9 Dehumidification Type X X

InputRegister 9069 R ###.# NA Unit 9 Suction Saturation Temperature 1

InputRegister 9070 R ###.# NA Unit 9 Suction Saturation Temperature 2

InputRegister 9071 R ### NA Unit 9 Subcooling 1 X

Page 50: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 50 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

InputRegister 9072 R ### NA Unit 9 Superheat 1

InputRegister 9073 R ### NA Unit 9 Superheat 2

InputRegister 9074 R ###.# NA Unit 9 Liquid Saturated Temperature 1

InputRegister 9075 R ###.# NA Unit 9 Liquid Saturated Temperature 2

InputRegister 9076 R ### NA Unit 9 Subcooling 2

InputRegister 9080 R ### NA Unit 9 Major Revision Number X X X

InputRegister 9081 R ### NA Unit 9 Minor Revision Number X X X

InputRegister 9082 R ### NA Unit 9 Bug Fixes X X X

InputRegister 9083 R ### NAUnit 9 How long the unit has been running in minutes

X X X

InputRegister 9084 R ## NA Unit 9 How many times unit has started X X X

InputRegister 9085 R ### NA Unit 9 How long the Fan is running in minutes X X

InputRegister 9086 R ## NA Unit 9 How many times Fan turned on X X

InputRegister 9087 R ### NA Unit 9 How long the Fan is running in minutes

InputRegister 9088 R ## NA Unit 9 How many times Fan turned on

InputRegister 9089 R ### NA Unit 9 How long the Blower is running in minutes X X X

InputRegister 9090 R ## NA Unit 9 How many times Blower turned on X X

InputRegister 9091 R ### NA Unit 9 How long the Blower is running in minutes

InputRegister 9092 R ## NA Unit 9 How many times Blower turned on

InputRegister 9093 R ### NA Unit 9 How long unit is running in Freecooling X X

InputRegister 9094 R ### NAUnit 9 How many times unit has been in Freecooling

X X

InputRegister 9095 R ### NA Unit 9 How long unit is running in Freecooling

InputRegister 9096 R ### NAUnit 9 How many times unit has been in Freecooling

InputRegister 9097 R ### NA Unit 9 How long unit is running in Cooling X X X

InputRegister 9098 R ### NA Unit 9 How many times unit has been in Cooling X X X

InputRegister 9099 R ### NA Unit 9 How long unit is running in Cooling X X

InputRegister 9100 R ### NA Unit 9 How many times unit has been in Cooling X X

InputRegister 9101 R ### NA Unit 9 How long unit is running in Cooling X

InputRegister 9102 R ### NA Unit 9 How many times unit has been in Cooling X

InputRegister 9103 R ### NA Unit 9 How long unit is running in Cooling

InputRegister 9104 R ### NA Unit 9 How many times unit has been in Cooling

InputRegister 9105 R ### NA Unit 9 How long unit is running in Heating X X X

InputRegister 9106 R ### NA Unit 9 How many times unit has been in Heating X X X

InputRegister 9107 R ### NA Unit 9 How long unit is running in Heating X X

InputRegister 9108 R ### NA Unit 9 How many times unit has been in Heating X X

InputRegister 9109 R ### NA Unit 9 How long unit is running in Heating

InputRegister 9110 R ### NA Unit 9 How many times unit has been in Heating

InputRegister 9111 R ### NA Unit 9 How long unit is running in Heating

InputRegister 9112 R ### NA Unit 9 How many times unit has been in Heating

InputRegister 9113 R ### 0-999999 Unit 9 life time in Hours (Update every Hour) X X X

InputRegister 9115 R ### 0-999999Unit 9 Blower 1 life time in Hours (Update every Hour)

X X

InputRegister 9117 R ### 0-999999Unit 9 Blower 2 life time in Hours (Update every Hour)

InputRegister 9119 R ### 0-999999Unit 9 Fan 1 life time in hours (Update every Hour)

X

InputRegister 9121 R ### 0-999999Unit 9 Fan 2 life time in hours (Update every Hour)

InputRegister 9123 R ### 0-999999Unit 9 Cooling 1 life time in hours (Update ever Hour)

X X

Page 51: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 51 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

InputRegister 9125 R ### 0-999999Unit 9 Cooling 2 life time in hours (Update ever Hour)

X

InputRegister 9127 R ### 0-999999Unit 9 Cooling 3 life time in hours (Update ever Hour)

InputRegister 9129 R ### 0-999999Unit 9 Cooling 4 life time in hours (Update ever Hour)

InputRegister 9131 R ### 0-999999Unit 9 Heating 1 life time in hours (Update ever Hour)

X X

InputRegister 9133 R ### 0-999999Unit 9 Heating 2 life time in hours (Update ever Hour)

InputRegister 9135 R ### 0-999999Unit 9 Heating 3 life time in hours (Update ever Hour)

InputRegister 9137 R ### 0-999999Unit 9 Heating 4 life time in hours (Update ever Hour)

InputRegister 9139 R ### 0-999999Unit 9 FreeCooling 1 life time in hours (Update ever Hour)

X X

InputRegister 9141 R ### 0-999999Unit 9 FreeCooling 2 life time in hours (Update ever Hour)

InputRegister 9143 R ### 0-5Unit 9 Indicates what unit types are running on the network

X X X

DiscreteInput 9500 R Off/On = 0/1 0-1Unit 9 Error in the number of retain memory writings Alarm

X X X

DiscreteInput 9501 R Off/On = 0/1 0-1 Unit 9 Error in retain memory writings Alarm X X X

DiscreteInput 9502 R Off/On = 0/1 0-1 Unit 9 Return Air Temperature Sensor Alarm X X X

DiscreteInput 9503 R Off/On = 0/1 0-1 Unit 9 High Return Air Temperature Alarm X X

DiscreteInput 9504 R Off/On = 0/1 0-1 Unit 9 Mixed Air Temperature Sensor Alarm X X

DiscreteInput 9505 R Off/On = 0/1 0-1 Unit 9 Mixed Air High Temperature Alarm X X

DiscreteInput 9506 R Off/On = 0/1 0-1 Unit 9 Mixed Air Low Temperature Alarm X X

DiscreteInput 9507 R Off/On = 0/1 0-1 Unit 9 Supply Air Temperature Sensor Alarm X X

DiscreteInput 9508 R Off/On = 0/1 0-1 Unit 9 High Supply Air Temperature Alarm X

DiscreteInput 9509 R Off/On = 0/1 0-1 Unit 9 Low Supply Air Temperature Alarm X

DiscreteInput 9510 R Off/On = 0/1 0-1 Unit 9 Outdoor Air Temperature Sensor Alarm X X X

DiscreteInput 9511 R Off/On = 0/1 0-1 Unit 9 Outdoor Air Humidity Sensor Alarm X X X

DiscreteInput 9512 R Off/On = 0/1 0-1 Unit 9 Dust Sensor Alarm X X

DiscreteInput 9513 R Off/On = 0/1 0-1 Unit 9 Dust Sensor High Dust Detection Alarm X X

DiscreteInput 9514 R Off/On = 0/1 0-1 Unit 9 Liquid Line Temp Sensor Alarm X X

DiscreteInput 9515 R Off/On = 0/1 0-1 Unit 9 Discharge Temp Sensor Alarm

DiscreteInput 9516 R Off/On = 0/1 0-1 Unit 9 Liquid Line Pressure Sensor Alarm X

DiscreteInput 9517 R Off/On = 0/1 0-1 Unit 9 Suction Temperature Sensor Alarm X X X

DiscreteInput 9518 R Off/On = 0/1 0-1 Unit 9 Suction Pressure Sensor Alarm X X X

DiscreteInput 9519 R Off/On = 0/1 0-1 Unit 9 Low Pressure Alarm X X X

DiscreteInput 9520 R Off/On = 0/1 0-1 Unit 9 High Pressure Alarm X X X

DiscreteInput 9521 R Off/On = 0/1 0-1 Unit 9 Damper 1 Failed to Open X X X

DiscreteInput 9522 R Off/On = 0/1 0-1 Unit 9 Damper 1 Failed to Close X X X

DiscreteInput 9523 R Off/On = 0/1 0-1 Unit 9 Freeze Temperature Sensor Alarm X X

DiscreteInput 9524 R Off/On = 0/1 0-1 Unit 9 Freeze Condition X X X

DiscreteInput 9525 R Off/On = 0/1 0-1 Unit 9 Blower Fail Alarm X X

DiscreteInput 9526 R Off/On = 0/1 0-1 Unit 9 Dirty Filter 1 Alarm X X X

DiscreteInput 9527 R Off/On = 0/1 0-1 Unit 9 Dirty Condenser Coil Alarm

DiscreteInput 9528 R Off/On = 0/1 0-1 Unit 9 Emergency Ventilation Mode Active Alarm X X X

DiscreteInput 9529 R Off/On = 0/1 0-1 Unit 9 Emergency Cooling Mode Active Alarm X X X

DiscreteInput 9530 R Off/On = 0/1 0-1Unit 9 Extreme High Return Temp Alarm (Heat Cutout) Alarm

X X X

Page 52: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 52 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

DiscreteInput 9531 R Off/On = 0/1 0-1 Unit 9 Disable/Smoke Detector Alarm X X X

DiscreteInput 9532 R Off/On = 0/1 0-1 Unit 9 Power Loss Detected Alarm X

DiscreteInput 9533 R Off/On = 0/1 0-1 Unit 9 Low SuperHeat Alarm X X X

DiscreteInput 9534 R Off/On = 0/1 0-1 Unit 9 Low Evaporation Pressure Alarm X X X

DiscreteInput 9535 R Off/On = 0/1 0-1 Unit 9 High Evaporation Pressure Alarm X X X

DiscreteInput 9536 R Off/On = 0/1 0-1 Unit 9 High Condenser Temperature Alarm X X X

DiscreteInput 9537 R Off/On = 0/1 0-1 Unit 9 Low Suction pressure Alarm X X X

DiscreteInput 9538 R Off/On = 0/1 0-1 Unit 9 EEV motor error Alarm X X X

DiscreteInput 9539 R Off/On = 0/1 0-1 Unit 9 SelfTuning error Alarm X X X

DiscreteInput 9540 R Off/On = 0/1 0-1 Unit 9 Emergency close Alarm X X X

DiscreteInput 9541 R Off/On = 0/1 0-1 Unit 9 High Delta Temperature Alarm

DiscreteInput 9542 R Off/On = 0/1 0-1 Unit 9 High Delta Pressure Alarm

DiscreteInput 9543 R Off/On = 0/1 0-1 Unit 9 Range Error Alarm X X X

DiscreteInput 9544 R Off/On = 0/1 0-1 Unit 9 Service Position Percent Alarm X X X

DiscreteInput 9545 R Off/On = 0/1 0-1 Unit 9 Valve ID Alarm X X X

DiscreteInput 9546 R Off/On = 0/1 0-1 Unit 9 Return Air Temperature Sensor 2 Alarm X

DiscreteInput 9547 R Off/On = 0/1 0-1 Unit 9 High Return Air Temperature 2 Alarm X

DiscreteInput 9548 R Off/On = 0/1 0-1 Unit 9 Mixed Air Temperature Sensor 2 Alarm X

DiscreteInput 9549 R Off/On = 0/1 0-1 Unit 9 Mixed Air High Temperature 2 Alarm

DiscreteInput 9550 R Off/On = 0/1 0-1 Unit 9 Mixed Air Low Temperature 2 Alarm

DiscreteInput 9551 R Off/On = 0/1 0-1 Unit 9 Supply Air Temperature Sensor 2 Alarm X

DiscreteInput 9552 R Off/On = 0/1 0-1 Unit 9 High Supply Air Temperature 2 Alarm

DiscreteInput 9553 R Off/On = 0/1 0-1 Unit 9 Low Supply Air Temperature 2 Alarm

DiscreteInput 9554 R Off/On = 0/1 0-1 Unit 9 Dust Sensor 2 Alarm

DiscreteInput 9555 R Off/On = 0/1 0-1 Unit 9 Dust Sensor High Dust Detection 2 Alarm

DiscreteInput 9556 R Off/On = 0/1 0-1 Unit 9 Liquid Line Temp Sensor 2 Alarm X

DiscreteInput 9557 R Off/On = 0/1 0-1 Unit 9 Liquid Line Pressure Sensor Alarm

DiscreteInput 9558 R Off/On = 0/1 0-1 Unit 9 Discharge Temp Sensor 2 Alarm

DiscreteInput 9559 R Off/On = 0/1 0-1 Unit 9 Discharge Pressure Sensor 2 Alarm X

DiscreteInput 9560 R Off/On = 0/1 0-1 Unit 9 Discharge Pressure Sensor 2 Alarm X

DiscreteInput 9561 R Off/On = 0/1 0-1 Unit 9 Suction Temperature Sensor 2 Alarm X

DiscreteInput 9562 R Off/On = 0/1 0-1 Unit 9 Suction Pressure Sensor 2 Alarm X

DiscreteInput 9563 R Off/On = 0/1 0-1 Unit 9 Low Pressure 2 Alarm X

DiscreteInput 9564 R Off/On = 0/1 0-1 Unit 9 High Pressure 2 Alarm X

DiscreteInput 9565 R Off/On = 0/1 0-1 Unit 9 Damper 2 Failed to Open X

DiscreteInput 9566 R Off/On = 0/1 0-1 Unit 9 Damper 2 Failed to Close X

DiscreteInput 9567 R Off/On = 0/1 0-1 Unit 9 Damper 3 Failed to Open X

DiscreteInput 9568 R Off/On = 0/1 0-1 Unit 9 Damper 3 Failed to Close X

DiscreteInput 9569 R Off/On = 0/1 0-1 Unit 9 Damper 4 Failed to Open

DiscreteInput 9570 R Off/On = 0/1 0-1 Unit 9 Damper 4 Failed to Close

DiscreteInput 9571 R Off/On = 0/1 0-1 Unit 9 Freeze Temperature Sensor Alarm X

DiscreteInput 9572 R Off/On = 0/1 0-1 Unit 9 Freeze Condition Alarm X

DiscreteInput 9573 R Off/On = 0/1 0-1 Unit 9 Blower Fail Alarm

DiscreteInput 9574 R Off/On = 0/1 0-1 Unit 9 Dirty Filter 2 Alarm

DiscreteInput 9575 R Off/On = 0/1 0-1 Unit 9 Dirty Filter 3 Alarm

DiscreteInput 9576 R Off/On = 0/1 0-1 Unit 9 Dirty Filter 4 Alarm

DiscreteInput 9577 R Off/On = 0/1 0-1 Unit 9 Dirty Condenser Coil 2 Alarm

DiscreteInput 9578 R Off/On = 0/1 0-1 Unit 9 Power Loss 2 Detected Alarm

DiscreteInput 9579 R Off/On = 0/1 0-1 Unit 9 Low SuperHeat 2 Alarm X

Page 53: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 53 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

DiscreteInput 9580 R Off/On = 0/1 0-1 Unit 9 Low Evaporation Pressure 2 Alarm X

DiscreteInput 9581 R Off/On = 0/1 0-1 Unit 9 High Evaporation Pressure 2 Alarm X

DiscreteInput 9582 R Off/On = 0/1 0-1 Unit 9 High Condenser Temperature 2 Alarm X

DiscreteInput 9583 R Off/On = 0/1 0-1 Unit 9 Low Suction pressure 2 Alarm X

DiscreteInput 9584 R Off/On = 0/1 0-1 Unit 9 EEV motor 2 error Alarm X

DiscreteInput 9585 R Off/On = 0/1 0-1 Unit 9 SelfTuning 2 error Alarm X

DiscreteInput 9586 R Off/On = 0/1 0-1 Unit 9 Emergency close 2 Alarm X

DiscreteInput 9587 R Off/On = 0/1 0-1 Unit 9 High Delta Temperature 2 Alarm

DiscreteInput 9588 R Off/On = 0/1 0-1 Unit 9 High Delta Pressure 2 Alarm

DiscreteInput 9589 R Off/On = 0/1 0-1 Unit 9 Range Error 2 Alarm X

DiscreteInput 9590 R Off/On = 0/1 0-1 Unit 9 Service Position Percent 2 Alarm X

DiscreteInput 9591 R Off/On = 0/1 0-1 Unit 9 Valve ID 2 Alarm X

DiscreteInput 9592 R Off/On = 0/1 0-1 Unit 9 Th-Tune Device Offline Alarm X

DiscreteInput 9593 R Off/On = 0/1 0-1 Unit 9 Th-Tune Temperature Probe Alarm X

DiscreteInput 9594 R Off/On = 0/1 0-1 Unit 9 Th-Tune Humidity Probe Alarm X

DiscreteInput 9595 R Off/On = 0/1 0-1 Unit 9 Th-Tune Clock Board Alarm X

DiscreteInput 9596 R Off/On = 0/1 0-1 Unit 9 cpCOe Offline Alarm X

DiscreteInput 9597 R Off/On = 0/1 0-1 Unit 9 Blower 1 Offline Alarm X

DiscreteInput 9598 R Off/On = 0/1 0-1 Unit 9 Blower 1 Alarm X

DiscreteInput 9599 R Off/On = 0/1 0-1 Unit 9 Blower 2 Offline Alarm

DiscreteInput 9600 R Off/On = 0/1 0-1 Unit 9 Blower 2 Alarm

DiscreteInput 9601 R Off/On = 0/1 0-1 Unit 9 Condenser 1 Offline Alarm X

DiscreteInput 9602 R Off/On = 0/1 0-1 Unit 9 Condenser 1 Alarm X

DiscreteInput 9603 R Off/On = 0/1 0-1 Unit 9 Condenser 2 Offline Alarm

DiscreteInput 9604 R Off/On = 0/1 0-1 Unit 9 Condenser 2 Alarm

DiscreteInput 9605 R Off/On = 0/1 0-1 Unit 9 Low Return Air Temperature 1 Alarm X

DiscreteInput 9606 R Off/On = 0/1 0-1 Unit 9 Low Return Air Temperature 2 Alarm X

DiscreteInput 9607 R Off/On = 0/1 0-1 Unit 9 Panel Open Alarm X

DiscreteInput 10000 R Off/On = 0/1 0-1 Unit 10 Dirty Filter 1 Alarm X X X

DiscreteInput 10001 R Off/On = 0/1 0-1 Unit 10 Dirty Filter 2 Alarm X

DiscreteInput 10002 R Off/On = 0/1 0-1 Unit 10 Dirty Filter 3 Alarm

DiscreteInput 10003 R Off/On = 0/1 0-1 Unit 10 Indicates Blower 1 Is Running In Unit X X

InputRegister 10003 R 0-14 0-14 Unit 10 Compressor 1 Status X X X

DiscreteInput 10004 R Off/On = 0/1 0-1 Unit 10 Indicates Blower 2 Is Running In Unit

InputRegister 10004 R 0-14 0-14 Unit 10 Compressor 2 Status X

DiscreteInput 10005 R Off/On = 0/1 0-1 Unit 10 Low Pressure Switch 1 X

DiscreteInput 10006 R Off/On = 0/1 0-1 Unit 10 Low Pressure Switch 2

DiscreteInput 10007 R Off/On = 0/1 0-1 Unit 10 Damper Switch 1 Open X X X

DiscreteInput 10008 R Off/On = 0/1 0-1 Unit 10 Damper Switch 2 Open X

DiscreteInput 10009 R Off/On = 0/1 0-1 Unit 10 Damper Switch 3 Open X

DiscreteInput 10010 R Off/On = 0/1 0-1 Unit 10 Damper Switch 4 Open

InputRegister 10011 R ###.# NA Unit 10 Mixed Air Temperature Sensor 1 X X X

DiscreteInput 10012 R Off/On = 0/1 0-1 Unit 10 Activates Reheat Valve for Dehum X

InputRegister 10013 R ###.# NA Unit 10 Mixed Air Temperature Sensor 2 X

InputRegister 10014 R Zone1, 2, or 3 1-3 Unit 10 Zone Options X X X

InputRegister 10015 R ###.# NA Unit 10 Outdoor Air Temperature Sensor 1 X X X

InputRegister 10017 R ###.# NA Unit 10 Outdoor Air Temperature Sensor 2

InputRegister 10019 R ###.# NA Unit 10 Return Air Temperature Sensor 1 X X X

InputRegister 10021 R ###.# NA Unit 10 Return Air Temperature Sensor 2 X

Page 54: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 54 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

InputRegister 10023 R ###.# 0-100% Unit 10 Outdoor Humidity Sensor 1 X X

InputRegister 10025 R ###.# 0-100% Unit 10 Outdoor Humidity Sensor 2

InputRegister 10027 R ###.# NA Unit 10 Freeze Sensor 1 X

DiscreteInput 10029 R Off/On = 0/1 0-1 Unit 10 Heat 1 On/Off X X X

InputRegister 10029 R ###.# NA Unit 10 Freeze Sensor 2

DiscreteInput 10030 R Off/On = 0/1 0-1 Unit 10 Heat 2 On/Off X X X

DiscreteInput 10031 R Off/On = 0/1 0-1 Unit 10 Heat 3 On/Off X

DiscreteInput 10032 R Off/On = 0/1 0-1 Unit 10 Heat 4 On/Off

DiscreteInput 10033 R Off/On = 0/1 0-1 Unit 10 FreeCool Is Available X X X

DiscreteInput 10034 R Off/On = 0/1 0-1 Unit 10 Dirty Filter indicator X X

InputRegister 10034 R ### 0-100% Unit 10 Blower Speed 1 X X

DiscreteInput 10035 R Off/On = 0/1 0-1 Unit 10 Cooling 1 On/Off X X X

InputRegister 10035 R ### 0-100% Unit 10 Blower Speed 2

DiscreteInput 10036 R Off/On = 0/1 0-1 Unit 10 Cooling 2 On/Off X X X

InputRegister 10036 R ### 0-45 bar Unit 10 Discharge Pressure Transducer 1

DiscreteInput 10037 R Off/On = 0/1 0-1 Unit 10 Cooling 3 On/Off X

InputRegister 10037 R ### 0-45 bar Unit 10 Discharge Pressure Transducer 2

DiscreteInput 10038 R Off/On = 0/1 0-1 Unit 10 Cooling 4 On/Off

InputRegister 10038 R ###.# NA Unit 10 Discharge Temperature 1

DiscreteInput 10039 R Off/On = 0/1 0-1 Unit 10 Indicates No Air Flow X X

InputRegister 10039 R ###.# NA Unit 10 Discharge Temperature 2

DiscreteInput 10040 R Off/On = 0/1 0-1 Unit 10 Indicates No Air Flow 2

InputRegister 10040 R ### 0-100% Unit 10 Dust Sensor 1 X X

DiscreteInput 10041 R Off/On = 0/1 0-1 Unit 10 High Pressure 1 Event X X X

InputRegister 10041 R ### 0-100% Unit 10 Dust Sensor 2

DiscreteInput 10042 R Off/On = 0/1 0-1 Unit 10 High Pressure 2 Event X

DiscreteInput 10043 R Off/On = 0/1 0-1 Unit 10 Power Loss X X

DiscreteInput 10044 R Off/On = 0/1 0-1 Unit 10 Is Disabled X X X

InputRegister 10044 R ###.# NA Unit 10 Liquid Temperature 1 X X

InputRegister 10045 R ###.# NA Unit 10 Liquid Temperature 2 X

InputRegister 10046 R ### NA Unit 10 Liquid Pressure 1 X

InputRegister 10047 R ### NA Unit 10 Liquid Pressure 2

InputRegister 10048 R ### NA Unit 10 Suction Pressure 1 X X

InputRegister 10049 R ### NA Unit 10 Suction Pressure 2

InputRegister 10050 R ###.# NA Unit 10 Suction Temperature 1 X X

InputRegister 10051 R ###.# NA Unit 10 Suction Temperature 2

InputRegister 10052 R ###.# NA Unit 10 Supply Air Temperature 1 X X

InputRegister 10053 R ###.# NA Unit 10 Supply Air Temperature 2 X

InputRegister 10056 R ### 0-100% Unit 10 Condenser Fan Speed 1 X X

InputRegister 10057 R ### 0-100% Unit 10 Condenser Fan Speed 2 X

InputRegister 10058 R ### 0-100% Unit 10 Damper Position 1 X X X

InputRegister 10059 R ### 0-100% Unit 10 Damper Position 2 X

InputRegister 10060 R ### 0-100% Unit 10 Damper Position 3 X

InputRegister 10061 R ### 0-100% Unit 10 Damper Position 4 X

InputRegister 10062 R ### 0-100% Unit 10 EEV1 Position X X X

InputRegister 10063 R ### 0-100% Unit 10 EEV2 Position X

InputRegister 10064 R ### NA Unit 10 Declares number of Cooling Stages X X

InputRegister 10065 R ### NA Unit 10 Declares number of Heating Stages X X

InputRegister 10066 R ### NA Unit 10 Declares number of Freecooling Stages X X

Page 55: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 55 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

InputRegister 10067 R ### NA Unit 10 Outdoor Air Dewpoint X

InputRegister 10068 R ### 0,1,2,3 Unit 10 Dehumidification Type X X

InputRegister 10069 R ###.# NA Unit 10 Suction Saturation Temperature 1

InputRegister 10070 R ###.# NA Unit 10 Suction Saturation Temperature 2

InputRegister 10071 R ### NA Unit 10 Subcooling 1 X

InputRegister 10072 R ### NA Unit 10 Superheat 1

InputRegister 10073 R ### NA Unit 10 Superheat 2

InputRegister 10074 R ###.# NA Unit 10 Liquid Saturated Temperature 1

InputRegister 10075 R ###.# NA Unit 10 Liquid Saturated Temperature 2

InputRegister 10076 R ### NA Unit 10 Subcooling 2

InputRegister 10080 R ### NA Unit 10 Major Revision Number X X X

InputRegister 10081 R ### NA Unit 10 Minor Revision Number X X X

InputRegister 10082 R ### NA Unit 10 Bug Fixes X X X

InputRegister 10083 R ### NAUnit 10 How long the unit has been running in minutes

X X X

InputRegister 10084 R ## NA Unit 10 How many times unit has started X X X

InputRegister 10085 R ### NA Unit 10 How long the Fan is running in minutes X X

InputRegister 10086 R ## NA Unit 10 How many times Fan turned on X X

InputRegister 10087 R ### NA Unit 10 How long the Fan is running in minutes

InputRegister 10088 R ## NA Unit 10 How many times Fan turned on

InputRegister 10089 R ### NAUnit 10 How long the Blower is running in minutes

X X X

InputRegister 10090 R ## NA Unit 10 How many times Blower turned on X X

InputRegister 10091 R ### NAUnit 10 How long the Blower is running in minutes

InputRegister 10092 R ## NA Unit 10 How many times Blower turned on

InputRegister 10093 R ### NA Unit 10 How long unit is running in Freecooling X X

InputRegister 10094 R ### NAUnit 10 How many times unit has been in Freecooling

X X

InputRegister 10095 R ### NA Unit 10 How long unit is running in Freecooling

InputRegister 10096 R ### NAUnit 10 How many times unit has been in Freecooling

InputRegister 10097 R ### NA Unit 10 How long unit is running in Cooling X X X

InputRegister 10098 R ### NA Unit 10 How many times unit has been in Cooling X X X

InputRegister 10099 R ### NA Unit 10 How long unit is running in Cooling X X

InputRegister 10100 R ### NA Unit 10 How many times unit has been in Cooling X X

InputRegister 10101 R ### NA Unit 10 How long unit is running in Cooling X

InputRegister 10102 R ### NA Unit 10 How many times unit has been in Cooling X

InputRegister 10103 R ### NA Unit 10 How long unit is running in Cooling

InputRegister 10104 R ### NA Unit 10 How many times unit has been in Cooling

InputRegister 10105 R ### NA Unit 10 How long unit is running in Heating X X X

InputRegister 10106 R ### NA Unit 10 How many times unit has been in Heating X X X

InputRegister 10107 R ### NA Unit 10 How long unit is running in Heating X X

InputRegister 10108 R ### NA Unit 10 How many times unit has been in Heating X X

InputRegister 10109 R ### NA Unit 10 How long unit is running in Heating

InputRegister 10110 R ### NA Unit 10 How many times unit has been in Heating

InputRegister 10111 R ### NA Unit 10 How long unit is running in Heating

InputRegister 10112 R ### NA Unit 10 How many times unit has been in Heating

InputRegister 10113 R ### 0-999999 Unit 10 life time in Hours (Update every Hour) X X X

InputRegister 10115 R ### 0-999999Unit 10 Blower 1 life time in Hours (Update every Hour)

X X

Page 56: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 56 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

InputRegister 10117 R ### 0-999999Unit 10 Blower 2 life time in Hours (Update every Hour)

InputRegister 10119 R ### 0-999999Unit 10 Fan 1 life time in hours (Update every Hour)

X

InputRegister 10121 R ### 0-999999Unit 10 Fan 2 life time in hours (Update every Hour)

InputRegister 10123 R ### 0-999999Unit 10 Cooling 1 life time in hours (Update ever Hour)

X X

InputRegister 10125 R ### 0-999999Unit 10 Cooling 2 life time in hours (Update ever Hour)

X

InputRegister 10127 R ### 0-999999Unit 10 Cooling 3 life time in hours (Update ever Hour)

InputRegister 10129 R ### 0-999999Unit 10 Cooling 4 life time in hours (Update ever Hour)

InputRegister 10131 R ### 0-999999Unit 10 Heating 1 life time in hours (Update ever Hour)

X X

InputRegister 10133 R ### 0-999999Unit 10 Heating 2 life time in hours (Update ever Hour)

InputRegister 10135 R ### 0-999999Unit 10 Heating 3 life time in hours (Update ever Hour)

InputRegister 10137 R ### 0-999999Unit 10 Heating 4 life time in hours (Update ever Hour)

InputRegister 10139 R ### 0-999999Unit 10 FreeCooling 1 life time in hours (Update ever Hour)

X X

InputRegister 10141 R ### 0-999999Unit 10 FreeCooling 2 life time in hours (Update ever Hour)

InputRegister 10143 R ### 0-5Unit 10 Indicates what unit types are running on the network

X X X

DiscreteInput 10500 R Off/On = 0/1 0-1Unit 10 Error in the number of retain memory writings Alarm

X X X

DiscreteInput 10501 R Off/On = 0/1 0-1 Unit 10 Error in retain memory writings Alarm X X X

DiscreteInput 10502 R Off/On = 0/1 0-1 Unit 10 Return Air Temperature Sensor Alarm X X X

DiscreteInput 10503 R Off/On = 0/1 0-1 Unit 10 High Return Air Temperature Alarm X X

DiscreteInput 10504 R Off/On = 0/1 0-1 Unit 10 Mixed Air Temperature Sensor Alarm X X

DiscreteInput 10505 R Off/On = 0/1 0-1 Unit 10 Mixed Air High Temperature Alarm X X

DiscreteInput 10506 R Off/On = 0/1 0-1 Unit 10 Mixed Air Low Temperature Alarm X X

DiscreteInput 10507 R Off/On = 0/1 0-1 Unit 10 Supply Air Temperature Sensor Alarm X X

DiscreteInput 10508 R Off/On = 0/1 0-1 Unit 10 High Supply Air Temperature Alarm X

DiscreteInput 10509 R Off/On = 0/1 0-1 Unit 10 Low Supply Air Temperature Alarm X

DiscreteInput 10510 R Off/On = 0/1 0-1 Unit 10 Outdoor Air Temperature Sensor Alarm X X X

DiscreteInput 10511 R Off/On = 0/1 0-1 Unit 10 Outdoor Air Humidity Sensor Alarm X X X

DiscreteInput 10512 R Off/On = 0/1 0-1 Unit 10 Dust Sensor Alarm X X

DiscreteInput 10513 R Off/On = 0/1 0-1 Unit 10 Dust Sensor High Dust Detection Alarm X X

DiscreteInput 10514 R Off/On = 0/1 0-1 Unit 10 Liquid Line Temp Sensor Alarm X X

DiscreteInput 10515 R Off/On = 0/1 0-1 Unit 10 Discharge Temp Sensor Alarm

DiscreteInput 10516 R Off/On = 0/1 0-1 Unit 10 Liquid Line Pressure Sensor Alarm X

DiscreteInput 10517 R Off/On = 0/1 0-1 Unit 10 Suction Temperature Sensor Alarm X X X

DiscreteInput 10518 R Off/On = 0/1 0-1 Unit 10 Suction Pressure Sensor Alarm X X X

DiscreteInput 10519 R Off/On = 0/1 0-1 Unit 10 Low Pressure Alarm X X X

DiscreteInput 10520 R Off/On = 0/1 0-1 Unit 10 High Pressure Alarm X X X

DiscreteInput 10521 R Off/On = 0/1 0-1 Unit 10 Damper 1 Failed to Open X X X

DiscreteInput 10522 R Off/On = 0/1 0-1 Unit 10 Damper 1 Failed to Close X X X

DiscreteInput 10523 R Off/On = 0/1 0-1 Unit 10 Freeze Temperature Sensor Alarm X X

DiscreteInput 10524 R Off/On = 0/1 0-1 Unit 10 Freeze Condition X X X

Page 57: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 57 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

DiscreteInput 10525 R Off/On = 0/1 0-1 Unit 10 Blower Fail Alarm X X

DiscreteInput 10526 R Off/On = 0/1 0-1 Unit 10 Dirty Filter 1 Alarm X X X

DiscreteInput 10527 R Off/On = 0/1 0-1 Unit 10 Dirty Condenser Coil Alarm

DiscreteInput 10528 R Off/On = 0/1 0-1 Unit 10 Emergency Ventilation Mode Active Alarm X X X

DiscreteInput 10529 R Off/On = 0/1 0-1 Unit 10 Emergency Cooling Mode Active Alarm X X X

DiscreteInput 10530 R Off/On = 0/1 0-1Unit 10 Extreme High Return Temp Alarm (Heat Cutout) Alarm

X X X

DiscreteInput 10531 R Off/On = 0/1 0-1 Unit 10 Disable/Smoke Detector Alarm X X X

DiscreteInput 10532 R Off/On = 0/1 0-1 Unit 10 Power Loss Detected Alarm X

DiscreteInput 10533 R Off/On = 0/1 0-1 Unit 10 Low SuperHeat Alarm X X X

DiscreteInput 10534 R Off/On = 0/1 0-1 Unit 10 Low Evaporation Pressure Alarm X X X

DiscreteInput 10535 R Off/On = 0/1 0-1 Unit 10 High Evaporation Pressure Alarm X X X

DiscreteInput 10536 R Off/On = 0/1 0-1 Unit 10 High Condenser Temperature Alarm X X X

DiscreteInput 10537 R Off/On = 0/1 0-1 Unit 10 Low Suction pressure Alarm X X X

DiscreteInput 10538 R Off/On = 0/1 0-1 Unit 10 EEV motor error Alarm X X X

DiscreteInput 10539 R Off/On = 0/1 0-1 Unit 10 SelfTuning error Alarm X X X

DiscreteInput 10540 R Off/On = 0/1 0-1 Unit 10 Emergency close Alarm X X X

DiscreteInput 10541 R Off/On = 0/1 0-1 Unit 10 High Delta Temperature Alarm

DiscreteInput 10542 R Off/On = 0/1 0-1 Unit 10 High Delta Pressure Alarm

DiscreteInput 10543 R Off/On = 0/1 0-1 Unit 10 Range Error Alarm X X X

DiscreteInput 10544 R Off/On = 0/1 0-1 Unit 10 Service Position Percent Alarm X X X

DiscreteInput 10545 R Off/On = 0/1 0-1 Unit 10 Valve ID Alarm X X X

DiscreteInput 10546 R Off/On = 0/1 0-1 Unit 10 Return Air Temperature Sensor 2 Alarm X

DiscreteInput 10547 R Off/On = 0/1 0-1 Unit 10 High Return Air Temperature 2 Alarm X

DiscreteInput 10548 R Off/On = 0/1 0-1 Unit 10 Mixed Air Temperature Sensor 2 Alarm X

DiscreteInput 10549 R Off/On = 0/1 0-1 Unit 10 Mixed Air High Temperature 2 Alarm

DiscreteInput 10550 R Off/On = 0/1 0-1 Unit 10 Mixed Air Low Temperature 2 Alarm

DiscreteInput 10551 R Off/On = 0/1 0-1 Unit 10 Supply Air Temperature Sensor 2 Alarm X

DiscreteInput 10552 R Off/On = 0/1 0-1 Unit 10 High Supply Air Temperature 2 Alarm

DiscreteInput 10553 R Off/On = 0/1 0-1 Unit 10 Low Supply Air Temperature 2 Alarm

DiscreteInput 10554 R Off/On = 0/1 0-1 Unit 10 Dust Sensor 2 Alarm

DiscreteInput 10555 R Off/On = 0/1 0-1 Unit 10 Dust Sensor High Dust Detection 2 Alarm

DiscreteInput 10556 R Off/On = 0/1 0-1 Unit 10 Liquid Line Temp Sensor 2 Alarm X

DiscreteInput 10557 R Off/On = 0/1 0-1 Unit 10 Liquid Line Pressure Sensor Alarm

DiscreteInput 10558 R Off/On = 0/1 0-1 Unit 10 Discharge Temp Sensor 2 Alarm

DiscreteInput 10559 R Off/On = 0/1 0-1 Unit 10 Discharge Pressure Sensor 2 Alarm X

DiscreteInput 10560 R Off/On = 0/1 0-1 Unit 10 Discharge Pressure Sensor 2 Alarm X

DiscreteInput 10561 R Off/On = 0/1 0-1 Unit 10 Suction Temperature Sensor 2 Alarm X

DiscreteInput 10562 R Off/On = 0/1 0-1 Unit 10 Suction Pressure Sensor 2 Alarm X

DiscreteInput 10563 R Off/On = 0/1 0-1 Unit 10 Low Pressure 2 Alarm X

DiscreteInput 10564 R Off/On = 0/1 0-1 Unit 10 High Pressure 2 Alarm X

DiscreteInput 10565 R Off/On = 0/1 0-1 Unit 10 Damper 2 Failed to Open X

DiscreteInput 10566 R Off/On = 0/1 0-1 Unit 10 Damper 2 Failed to Close X

DiscreteInput 10567 R Off/On = 0/1 0-1 Unit 10 Damper 3 Failed to Open X

DiscreteInput 10568 R Off/On = 0/1 0-1 Unit 10 Damper 3 Failed to Close X

DiscreteInput 10569 R Off/On = 0/1 0-1 Unit 10 Damper 4 Failed to Open

DiscreteInput 10570 R Off/On = 0/1 0-1 Unit 10 Damper 4 Failed to Close

DiscreteInput 10571 R Off/On = 0/1 0-1 Unit 10 Freeze Temperature Sensor Alarm X

DiscreteInput 10572 R Off/On = 0/1 0-1 Unit 10 Freeze Condition Alarm X

Page 58: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 58 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

DiscreteInput 10573 R Off/On = 0/1 0-1 Unit 10 Blower Fail Alarm

DiscreteInput 10574 R Off/On = 0/1 0-1 Unit 10 Dirty Filter 2 Alarm

DiscreteInput 10575 R Off/On = 0/1 0-1 Unit 10 Dirty Filter 3 Alarm

DiscreteInput 10576 R Off/On = 0/1 0-1 Unit 10 Dirty Filter 4 Alarm

DiscreteInput 10577 R Off/On = 0/1 0-1 Unit 10 Dirty Condenser Coil 2 Alarm

DiscreteInput 10578 R Off/On = 0/1 0-1 Unit 10 Power Loss 2 Detected Alarm

DiscreteInput 10579 R Off/On = 0/1 0-1 Unit 10 Low SuperHeat 2 Alarm X

DiscreteInput 10580 R Off/On = 0/1 0-1 Unit 10 Low Evaporation Pressure 2 Alarm X

DiscreteInput 10581 R Off/On = 0/1 0-1 Unit 10 High Evaporation Pressure 2 Alarm X

DiscreteInput 10582 R Off/On = 0/1 0-1 Unit 10 High Condenser Temperature 2 Alarm X

DiscreteInput 10583 R Off/On = 0/1 0-1 Unit 10 Low Suction pressure 2 Alarm X

DiscreteInput 10584 R Off/On = 0/1 0-1 Unit 10 EEV motor 2 error Alarm X

DiscreteInput 10585 R Off/On = 0/1 0-1 Unit 10 SelfTuning 2 error Alarm X

DiscreteInput 10586 R Off/On = 0/1 0-1 Unit 10 Emergency close 2 Alarm X

DiscreteInput 10587 R Off/On = 0/1 0-1 Unit 10 High Delta Temperature 2 Alarm

DiscreteInput 10588 R Off/On = 0/1 0-1 Unit 10 High Delta Pressure 2 Alarm

DiscreteInput 10589 R Off/On = 0/1 0-1 Unit 10 Range Error 2 Alarm X

DiscreteInput 10590 R Off/On = 0/1 0-1 Unit 10 Service Position Percent 2 Alarm X

DiscreteInput 10591 R Off/On = 0/1 0-1 Unit 10 Valve ID 2 Alarm X

DiscreteInput 10592 R Off/On = 0/1 0-1 Unit 10 Th-Tune Device Offline Alarm X

DiscreteInput 10593 R Off/On = 0/1 0-1 Unit 10 Th-Tune Temperature Probe Alarm X

DiscreteInput 10594 R Off/On = 0/1 0-1 Unit 10 Th-Tune Humidity Probe Alarm X

DiscreteInput 10595 R Off/On = 0/1 0-1 Unit 10 Th-Tune Clock Board Alarm X

DiscreteInput 10596 R Off/On = 0/1 0-1 Unit 10 cpCOe Offline Alarm X

DiscreteInput 10597 R Off/On = 0/1 0-1 Unit 10 Blower 1 Offline Alarm X

DiscreteInput 10598 R Off/On = 0/1 0-1 Unit 10 Blower 1 Alarm X

DiscreteInput 10599 R Off/On = 0/1 0-1 Unit 10 Blower 2 Offline Alarm

DiscreteInput 10600 R Off/On = 0/1 0-1 Unit 10 Blower 2 Alarm

DiscreteInput 10601 R Off/On = 0/1 0-1 Unit 10 Condenser 1 Offline Alarm X

DiscreteInput 10602 R Off/On = 0/1 0-1 Unit 10 Condenser 1 Alarm X

DiscreteInput 10603 R Off/On = 0/1 0-1 Unit 10 Condenser 2 Offline Alarm

DiscreteInput 10604 R Off/On = 0/1 0-1 Unit 10 Condenser 2 Alarm

DiscreteInput 10605 R Off/On = 0/1 0-1 Unit 10 Low Return Air Temperature 1 Alarm X

DiscreteInput 10606 R Off/On = 0/1 0-1 Unit 10 Low Return Air Temperature 2 Alarm X

DiscreteInput 10607 R Off/On = 0/1 0-1 Unit 10 Panel Open Alarm X

DiscreteInput 11000 R Off/On = 0/1 0-1 Unit 11 Dirty Filter 1 Alarm X X X

DiscreteInput 11001 R Off/On = 0/1 0-1 Unit 11 Dirty Filter 2 Alarm X

DiscreteInput 11002 R Off/On = 0/1 0-1 Unit 11 Dirty Filter 3 Alarm

DiscreteInput 11003 R Off/On = 0/1 0-1 Unit 11 Indicates Blower 1 Is Running In Unit X X

InputRegister 11003 R 0-14 0-14 Unit 11 Compressor 1 Status X X X

DiscreteInput 11004 R Off/On = 0/1 0-1 Unit 11 Indicates Blower 2 Is Running In Unit

InputRegister 11004 R 0-14 0-14 Unit 11 Compressor 2 Status X

DiscreteInput 11005 R Off/On = 0/1 0-1 Unit 11 Low Pressure Switch 1 X

DiscreteInput 11006 R Off/On = 0/1 0-1 Unit 11 Low Pressure Switch 2

DiscreteInput 11007 R Off/On = 0/1 0-1 Unit 11 Damper Switch 1 Open X X X

DiscreteInput 11008 R Off/On = 0/1 0-1 Unit 11 Damper Switch 2 Open X

DiscreteInput 11009 R Off/On = 0/1 0-1 Unit 11 Damper Switch 3 Open X

DiscreteInput 11010 R Off/On = 0/1 0-1 Unit 11 Damper Switch 4 Open

InputRegister 11011 R ###.# NA Unit 11 Mixed Air Temperature Sensor 1 X X X

Page 59: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 59 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

DiscreteInput 11012 R Off/On = 0/1 0-1 Unit 11 Activates Reheat Valve for Dehum X

InputRegister 11013 R ###.# NA Unit 11 Mixed Air Temperature Sensor 2 X

InputRegister 11014 R Zone1, 2, or 3 1-3 Unit 11 Zone Options X X X

InputRegister 11015 R ###.# NA Unit 11 Outdoor Air Temperature Sensor 1 X X X

InputRegister 11017 R ###.# NA Unit 11 Outdoor Air Temperature Sensor 2

InputRegister 11019 R ###.# NA Unit 11 Return Air Temperature Sensor 1 X X X

InputRegister 11021 R ###.# NA Unit 11 Return Air Temperature Sensor 2 X

InputRegister 11023 R ###.# 0-100% Unit 11 Outdoor Humidity Sensor 1 X X

InputRegister 11025 R ###.# 0-100% Unit 11 Outdoor Humidity Sensor 2

InputRegister 11027 R ###.# NA Unit 11 Freeze Sensor 1 X

DiscreteInput 11029 R Off/On = 0/1 0-1 Unit 11 Heat 1 On/Off X X X

InputRegister 11029 R ###.# NA Unit 11 Freeze Sensor 2

DiscreteInput 11030 R Off/On = 0/1 0-1 Unit 11 Heat 2 On/Off X X X

DiscreteInput 11031 R Off/On = 0/1 0-1 Unit 11 Heat 3 On/Off X

DiscreteInput 11032 R Off/On = 0/1 0-1 Unit 11 Heat 4 On/Off

DiscreteInput 11033 R Off/On = 0/1 0-1 Unit 11 FreeCool Is Available X X X

DiscreteInput 11034 R Off/On = 0/1 0-1 Unit 11 Dirty Filter Indicator X X

InputRegister 11034 R ### 0-100% Unit 11 Blower Speed 1 X X

DiscreteInput 11035 R Off/On = 0/1 0-1 Unit 11 Cooling 1 On/Off X X X

InputRegister 11035 R ### 0-100% Unit 11 Blower Speed 2

DiscreteInput 11036 R Off/On = 0/1 0-1 Unit 11 Cooling 2 On/Off X X X

InputRegister 11036 R ### 0-45 bar Unit 11 Discharge Pressure Transducer 1

DiscreteInput 11037 R Off/On = 0/1 0-1 Unit 11 Cooling 3 On/Off X

InputRegister 11037 R ### 0-45 bar Unit 11 Discharge Pressure Transducer 2

DiscreteInput 11038 R Off/On = 0/1 0-1 Unit 11 Cooling 4 On/Off

InputRegister 11038 R ###.# NA Unit 11 Discharge Temperature 1

DiscreteInput 11039 R Off/On = 0/1 0-1 Unit 11 Indicates No Air Flow X X

InputRegister 11039 R ###.# NA Unit 11 Discharge Temperature 2

DiscreteInput 11040 R Off/On = 0/1 0-1 Unit 11 Indicates No Air Flow 2

InputRegister 11040 R ### 0-100% Unit 11 Dust Sensor 1 X X

DiscreteInput 11041 R Off/On = 0/1 0-1 Unit 11 High Pressure 1 Event X X X

InputRegister 11041 R ### 0-100% Unit 11 Dust Sensor 2

DiscreteInput 11042 R Off/On = 0/1 0-1 Unit 11 High Pressure 2 Event X

DiscreteInput 11043 R Off/On = 0/1 0-1 Unit 11 Power Loss X X

DiscreteInput 11044 R Off/On = 0/1 0-1 Unit 11 Is Disabled X X X

InputRegister 11044 R ###.# NA Unit 11 Liquid Temperature 1 X X

InputRegister 11045 R ###.# NA Unit 11 Liquid Temperature 2 X

InputRegister 11046 R ### NA Unit 11 Liquid Pressure 1 X

InputRegister 11047 R ### NA Unit 11 Liquid Pressure 2

InputRegister 11048 R ### NA Unit 11 Suction Pressure 1 X X

InputRegister 11049 R ### NA Unit 11 Suction Pressure 2

InputRegister 11050 R ###.# NA Unit 11 Suction Temperature 1 X X

InputRegister 11051 R ###.# NA Unit 11 Suction Temperature 2

InputRegister 11052 R ###.# NA Unit 11 Supply Air Temperature 1 X X

InputRegister 11053 R ###.# NA Unit 11 Supply Air Temperature 2 X

InputRegister 11056 R ### 0-100% Unit 11 Condenser Fan Speed 1 X X

InputRegister 11057 R ### 0-100% Unit 11 Condenser Fan Speed 2 X

InputRegister 11058 R ### 0-100% Unit 11 Damper Position 1 X X X

InputRegister 11059 R ### 0-100% Unit 11 Damper Position 2 X

Page 60: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 60 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

InputRegister 11060 R ### 0-100% Unit 11 Damper Position 3 X

InputRegister 11061 R ### 0-100% Unit 11 Damper Position 4 X

InputRegister 11062 R ### 0-100% Unit 11 EEV1 Position X X X

InputRegister 11063 R ### 0-100% Unit 11 EEV2 Position X

InputRegister 11064 R ### NA Unit 11 Declares number of Cooling Stages X X

InputRegister 11065 R ### NA Unit 11 Declares number of Heating Stages X X

InputRegister 11066 R ### NA Unit 11 Declares number of Freecooling Stages X X

InputRegister 11067 R ### NA Unit 11 Outdoor Air Dewpoint X

InputRegister 11068 R ### 0,1,2,3 Unit 11 Dehumidification Type X X

InputRegister 11069 R ###.# NA Unit 11 Suction Saturation Temperature 1

InputRegister 11070 R ###.# NA Unit 11 Suction Saturation Temperature 2

InputRegister 11071 R ### NA Unit 11 Subcooling 1 X

InputRegister 11072 R ### NA Unit 11 Superheat 1

InputRegister 11073 R ### NA Unit 11 Superheat 2

InputRegister 11074 R ###.# NA Unit 11 Liquid Saturated Temperature 1

InputRegister 11075 R ###.# NA Unit 11 Liquid Saturated Temperature 2

InputRegister 11076 R ### NA Unit 11 Subcooling 2

InputRegister 11080 R ### NA Unit 11 Major Revision Number X X X

InputRegister 11081 R ### NA Unit 11 Minor Revision Number X X X

InputRegister 11082 R ### NA Unit 11 Bug Fixes X X X

InputRegister 11083 R ### NAUnit 11 How long the unit has been running in minutes

X X X

InputRegister 11084 R ## NA Unit 11 How many times unit has started X X X

InputRegister 11085 R ### NA Unit 11 How long the Fan is running in minutes X X

InputRegister 11086 R ## NA Unit 11 How many times Fan turned on X X

InputRegister 11087 R ### NA Unit 11 How long the Fan is running in minutes

InputRegister 11088 R ## NA Unit 11 How many times Fan turned on

InputRegister 11089 R ### NAUnit 11 How long the Blower is running in minutes

X X X

InputRegister 11090 R ## NA Unit 11 How many times Blower turned on X X

InputRegister 11091 R ### NAUnit 11 How long the Blower is running in minutes

InputRegister 11092 R ## NA Unit 11 How many times Blower turned on

InputRegister 11093 R ### NA Unit 11 How long unit is running in Freecooling X X

InputRegister 11094 R ### NAUnit 11 How many times unit has been in Freecooling

X X

InputRegister 11095 R ### NA Unit 11 How long unit is running in Freecooling

InputRegister 11096 R ### NAUnit 11 How many times unit has been in Freecooling

InputRegister 11097 R ### NA Unit 11 How long unit is running in Cooling X X X

InputRegister 11098 R ### NA Unit 11 How many times unit has been in Cooling X X X

InputRegister 11099 R ### NA Unit 11 How long unit is running in Cooling X X

InputRegister 11100 R ### NA Unit 11 How many times unit has been in Cooling X X

InputRegister 11101 R ### NA Unit 11 How long unit is running in Cooling X

InputRegister 11102 R ### NA Unit 11 How many times unit has been in Cooling X

InputRegister 11103 R ### NA Unit 11 How long unit is running in Cooling

InputRegister 11104 R ### NA Unit 11 How many times unit has been in Cooling

InputRegister 11105 R ### NA Unit 11 How long unit is running in Heating X X X

InputRegister 11106 R ### NA Unit 11 How many times unit has been in Heating X X X

InputRegister 11107 R ### NA Unit 11 How long unit is running in Heating X X

InputRegister 11108 R ### NA Unit 11 How many times unit has been in Heating X X

Page 61: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 61 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

InputRegister 11109 R ### NA Unit 11 How long unit is running in Heating

InputRegister 11110 R ### NA Unit 11 How many times unit has been in Heating

InputRegister 11111 R ### NA Unit 11 How long unit is running in Heating

InputRegister 11112 R ### NA Unit 11 How many times unit has been in Heating

InputRegister 11113 R ### 0-999999 Unit 11 life time in Hours (Update every Hour) X X X

InputRegister 11115 R ### 0-999999Unit 11 Blower 1 life time in Hours (Update every Hour)

X X

InputRegister 11117 R ### 0-999999Unit 11 Blower 2 life time in Hours (Update every Hour)

InputRegister 11119 R ### 0-999999Unit 11 Fan 1 life time in hours (Update every Hour)

X

InputRegister 11121 R ### 0-999999Unit 11 Fan 2 life time in hours (Update every Hour)

InputRegister 11123 R ### 0-999999Unit 11 Cooling 1 life time in hours (Update ever Hour)

X X

InputRegister 11125 R ### 0-999999Unit 11 Cooling 2 life time in hours (Update ever Hour)

X

InputRegister 11127 R ### 0-999999Unit 11 Cooling 3 life time in hours (Update ever Hour)

InputRegister 11129 R ### 0-999999Unit 11 Cooling 4 life time in hours (Update ever Hour)

InputRegister 11131 R ### 0-999999Unit 11 Heating 1 life time in hours (Update ever Hour)

X X

InputRegister 11133 R ### 0-999999Unit 11 Heating 2 life time in hours (Update ever Hour)

InputRegister 11135 R ### 0-999999Unit 11 Heating 3 life time in hours (Update ever Hour)

InputRegister 11137 R ### 0-999999Unit 11 Heating 4 life time in hours (Update ever Hour)

InputRegister 11139 R ### 0-999999Unit 11 FreeCooling 1 life time in hours (Update ever Hour)

X X

InputRegister 11141 R ### 0-999999Unit 11 FreeCooling 2 life time in hours (Update ever Hour)

InputRegister 11143 R ### 0-5Unit 11 Indicates what unit types are running on the network

X X X

DiscreteInput 11500 R Off/On = 0/1 0-1Unit 11 Error in the number of retain memory writings Alarm

X X X

DiscreteInput 11501 R Off/On = 0/1 0-1 Unit 11 Error in retain memory writings Alarm X X X

DiscreteInput 11502 R Off/On = 0/1 0-1 Unit 11 Return Air Temperature Sensor Alarm X X X

DiscreteInput 11503 R Off/On = 0/1 0-1 Unit 11 High Return Air Temperature Alarm X X

DiscreteInput 11504 R Off/On = 0/1 0-1 Unit 11 Mixed Air Temperature Sensor Alarm X X

DiscreteInput 11505 R Off/On = 0/1 0-1 Unit 11 Mixed Air High Temperature Alarm X X

DiscreteInput 11506 R Off/On = 0/1 0-1 Unit 11 Mixed Air Low Temperature Alarm X X

DiscreteInput 11507 R Off/On = 0/1 0-1 Unit 11 Supply Air Temperature Sensor Alarm X X

DiscreteInput 11508 R Off/On = 0/1 0-1 Unit 11 High Supply Air Temperature Alarm X

DiscreteInput 11509 R Off/On = 0/1 0-1 Unit 11 Low Supply Air Temperature Alarm X

DiscreteInput 11510 R Off/On = 0/1 0-1 Unit 11 Outdoor Air Temperature Sensor Alarm X X X

DiscreteInput 11511 R Off/On = 0/1 0-1 Unit 11 Outdoor Air Humidity Sensor Alarm X X X

DiscreteInput 11512 R Off/On = 0/1 0-1 Unit 11 Dust Sensor Alarm X X

DiscreteInput 11513 R Off/On = 0/1 0-1 Unit 11 Dust Sensor High Dust Detection Alarm X X

DiscreteInput 11514 R Off/On = 0/1 0-1 Unit 11 Liquid Line Temp Sensor Alarm X X

DiscreteInput 11515 R Off/On = 0/1 0-1 Unit 11 Discharge Temp Sensor Alarm

DiscreteInput 11516 R Off/On = 0/1 0-1 Unit 11 Liquid Line Pressure Sensor Alarm X

DiscreteInput 11517 R Off/On = 0/1 0-1 Unit 11 Suction Temperature Sensor Alarm X X X

DiscreteInput 11518 R Off/On = 0/1 0-1 Unit 11 Suction Pressure Sensor Alarm X X X

Page 62: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 62 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

DiscreteInput 11519 R Off/On = 0/1 0-1 Unit 11 Low Pressure Alarm X X X

DiscreteInput 11520 R Off/On = 0/1 0-1 Unit 11 High Pressure Alarm X X X

DiscreteInput 11521 R Off/On = 0/1 0-1 Unit 11 Damper 1 Failed to Open X X X

DiscreteInput 11522 R Off/On = 0/1 0-1 Unit 11 Damper 1 Failed to Close X X X

DiscreteInput 11523 R Off/On = 0/1 0-1 Unit 11 Freeze Temperature Sensor Alarm X X

DiscreteInput 11524 R Off/On = 0/1 0-1 Unit 11 Freeze Condition X X X

DiscreteInput 11525 R Off/On = 0/1 0-1 Unit 11 Blower Fail Alarm X X

DiscreteInput 11526 R Off/On = 0/1 0-1 Unit 11 Dirty Filter 1 Alarm X X X

DiscreteInput 11527 R Off/On = 0/1 0-1 Unit 11 Dirty Condenser Coil Alarm

DiscreteInput 11528 R Off/On = 0/1 0-1 Unit 11 Emergency Ventilation Mode Active Alarm X X X

DiscreteInput 11529 R Off/On = 0/1 0-1 Unit 11 Emergency Cooling Mode Active Alarm X X X

DiscreteInput 11530 R Off/On = 0/1 0-1Unit 11 Extreme High Return Temp Alarm (Heat Cutout) Alarm

X X X

DiscreteInput 11531 R Off/On = 0/1 0-1 Unit 11 Disable/Smoke Detector Alarm X X X

DiscreteInput 11532 R Off/On = 0/1 0-1 Unit 11 Power Loss Detected Alarm X

DiscreteInput 11533 R Off/On = 0/1 0-1 Unit 11 Low SuperHeat Alarm X X X

DiscreteInput 11534 R Off/On = 0/1 0-1 Unit 11 Low Evaporation Pressure Alarm X X X

DiscreteInput 11535 R Off/On = 0/1 0-1 Unit 11 High Evaporation Pressure Alarm X X X

DiscreteInput 11536 R Off/On = 0/1 0-1 Unit 11 High Condenser Temperature Alarm X X X

DiscreteInput 11537 R Off/On = 0/1 0-1 Unit 11 Low Suction pressure Alarm X X X

DiscreteInput 11538 R Off/On = 0/1 0-1 Unit 11 EEV motor error Alarm X X X

DiscreteInput 11539 R Off/On = 0/1 0-1 Unit 11 SelfTuning error Alarm X X X

DiscreteInput 11540 R Off/On = 0/1 0-1 Unit 11 Emergency close Alarm X X X

DiscreteInput 11541 R Off/On = 0/1 0-1 Unit 11 High Delta Temperature Alarm

DiscreteInput 11542 R Off/On = 0/1 0-1 Unit 11 High Delta Pressure Alarm

DiscreteInput 11543 R Off/On = 0/1 0-1 Unit 11 Range Error Alarm X X X

DiscreteInput 11544 R Off/On = 0/1 0-1 Unit 11 Service Position Percent Alarm X X X

DiscreteInput 11545 R Off/On = 0/1 0-1 Unit 11 Valve ID Alarm X X X

DiscreteInput 11546 R Off/On = 0/1 0-1 Unit 11 Return Air Temperature Sensor 2 Alarm X

DiscreteInput 11547 R Off/On = 0/1 0-1 Unit 11 High Return Air Temperature 2 Alarm X

DiscreteInput 11548 R Off/On = 0/1 0-1 Unit 11 Mixed Air Temperature Sensor 2 Alarm X

DiscreteInput 11549 R Off/On = 0/1 0-1 Unit 11 Mixed Air High Temperature 2 Alarm

DiscreteInput 11550 R Off/On = 0/1 0-1 Unit 11 Mixed Air Low Temperature 2 Alarm

DiscreteInput 11551 R Off/On = 0/1 0-1 Unit 11 Supply Air Temperature Sensor 2 Alarm X

DiscreteInput 11552 R Off/On = 0/1 0-1 Unit 11 High Supply Air Temperature 2 Alarm

DiscreteInput 11553 R Off/On = 0/1 0-1 Unit 11 Low Supply Air Temperature 2 Alarm

DiscreteInput 11554 R Off/On = 0/1 0-1 Unit 11 Dust Sensor 2 Alarm

DiscreteInput 11555 R Off/On = 0/1 0-1 Unit 11 Dust Sensor High Dust Detection 2 Alarm

DiscreteInput 11556 R Off/On = 0/1 0-1 Unit 11 Liquid Line Temp Sensor 2 Alarm X

DiscreteInput 11557 R Off/On = 0/1 0-1 Unit 11 Liquid Line Pressure Sensor Alarm

DiscreteInput 11558 R Off/On = 0/1 0-1 Unit 11 Discharge Temp Sensor 2 Alarm

DiscreteInput 11559 R Off/On = 0/1 0-1 Unit 11 Discharge Pressure Sensor 2 Alarm X

DiscreteInput 11560 R Off/On = 0/1 0-1 Unit 11 Discharge Pressure Sensor 2 Alarm X

DiscreteInput 11561 R Off/On = 0/1 0-1 Unit 11 Suction Temperature Sensor 2 Alarm X

DiscreteInput 11562 R Off/On = 0/1 0-1 Unit 11 Suction Pressure Sensor 2 Alarm X

DiscreteInput 11563 R Off/On = 0/1 0-1 Unit 11 Low Pressure 2 Alarm X

DiscreteInput 11564 R Off/On = 0/1 0-1 Unit 11 High Pressure 2 Alarm X

DiscreteInput 11565 R Off/On = 0/1 0-1 Unit 11 Damper 2 Failed to Open X

DiscreteInput 11566 R Off/On = 0/1 0-1 Unit 11 Damper 2 Failed to Close X

Page 63: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 63 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

DiscreteInput 11567 R Off/On = 0/1 0-1 Unit 11 Damper 3 Failed to Open X

DiscreteInput 11568 R Off/On = 0/1 0-1 Unit 11 Damper 3 Failed to Close X

DiscreteInput 11569 R Off/On = 0/1 0-1 Unit 11 Damper 4 Failed to Open

DiscreteInput 11570 R Off/On = 0/1 0-1 Unit 11 Damper 4 Failed to Close

DiscreteInput 11571 R Off/On = 0/1 0-1 Unit 11 Freeze Temperature Sensor Alarm X

DiscreteInput 11572 R Off/On = 0/1 0-1 Unit 11 Freeze Condition Alarm X

DiscreteInput 11573 R Off/On = 0/1 0-1 Unit 11 Blower Fail Alarm

DiscreteInput 11574 R Off/On = 0/1 0-1 Unit 11 Dirty Filter 2 Alarm

DiscreteInput 11575 R Off/On = 0/1 0-1 Unit 11 Dirty Filter 3 Alarm

DiscreteInput 11576 R Off/On = 0/1 0-1 Unit 11 Dirty Filter 4 Alarm

DiscreteInput 11577 R Off/On = 0/1 0-1 Unit 11 Dirty Condenser Coil 2 Alarm

DiscreteInput 11578 R Off/On = 0/1 0-1 Unit 11 Power Loss 2 Detected Alarm

DiscreteInput 11579 R Off/On = 0/1 0-1 Unit 11 Low SuperHeat 2 Alarm X

DiscreteInput 11580 R Off/On = 0/1 0-1 Unit 11 Low Evaporation Pressure 2 Alarm X

DiscreteInput 11581 R Off/On = 0/1 0-1 Unit 11 High Evaporation Pressure 2 Alarm X

DiscreteInput 11582 R Off/On = 0/1 0-1 Unit 11 High Condenser Temperature 2 Alarm X

DiscreteInput 11583 R Off/On = 0/1 0-1 Unit 11 Low Suction pressure 2 Alarm X

DiscreteInput 11584 R Off/On = 0/1 0-1 Unit 11 EEV motor 2 error Alarm X

DiscreteInput 11585 R Off/On = 0/1 0-1 Unit 11 SelfTuning 2 error Alarm X

DiscreteInput 11586 R Off/On = 0/1 0-1 Unit 11 Emergency close 2 Alarm X

DiscreteInput 11587 R Off/On = 0/1 0-1 Unit 11 High Delta Temperature 2 Alarm

DiscreteInput 11588 R Off/On = 0/1 0-1 Unit 11 High Delta Pressure 2 Alarm

DiscreteInput 11589 R Off/On = 0/1 0-1 Unit 11 Range Error 2 Alarm X

DiscreteInput 11590 R Off/On = 0/1 0-1 Unit 11 Service Position Percent 2 Alarm X

DiscreteInput 11591 R Off/On = 0/1 0-1 Unit 11 Valve ID 2 Alarm X

DiscreteInput 11592 R Off/On = 0/1 0-1 Unit 11 Th-Tune Device Offline Alarm X

DiscreteInput 11593 R Off/On = 0/1 0-1 Unit 11 Th-Tune Temperature Probe Alarm X

DiscreteInput 11594 R Off/On = 0/1 0-1 Unit 11 Th-Tune Humidity Probe Alarm X

DiscreteInput 11595 R Off/On = 0/1 0-1 Unit 11 Th-Tune Clock Board Alarm X

DiscreteInput 11596 R Off/On = 0/1 0-1 Unit 11 cpCOe Offline Alarm X

DiscreteInput 11597 R Off/On = 0/1 0-1 Unit 11 Blower 1 Offline Alarm X

DiscreteInput 11598 R Off/On = 0/1 0-1 Unit 11 Blower 1 Alarm X

DiscreteInput 11599 R Off/On = 0/1 0-1 Unit 11 Blower 2 Offline Alarm

DiscreteInput 11600 R Off/On = 0/1 0-1 Unit 11 Blower 2 Alarm

DiscreteInput 11601 R Off/On = 0/1 0-1 Unit 11 Condenser 1 Offline Alarm X

DiscreteInput 11602 R Off/On = 0/1 0-1 Unit 11 Condenser 1 Alarm X

DiscreteInput 11603 R Off/On = 0/1 0-1 Unit 11 Condenser 2 Offline Alarm

DiscreteInput 11604 R Off/On = 0/1 0-1 Unit 11 Condenser 2 Alarm

DiscreteInput 11605 R Off/On = 0/1 0-1 Unit 11 Low Return Air Temperature 1 Alarm X

DiscreteInput 11606 R Off/On = 0/1 0-1 Unit 11 Low Return Air Temperature 2 Alarm X

DiscreteInput 11607 R Off/On = 0/1 0-1 Unit 11 Panel Open Alarm X

DiscreteInput 12000 R Off/On = 0/1 0-1 Unit 12 Dirty Filter 1 Alarm X X X

DiscreteInput 12001 R Off/On = 0/1 0-1 Unit 12 Dirty Filter 2 Alarm X

DiscreteInput 12002 R Off/On = 0/1 0-1 Unit 12 Dirty Filter 3 Alarm

DiscreteInput 12003 R Off/On = 0/1 0-1 Unit 12 Indicates Blower 1 Is Running In Unit X X

InputRegister 12003 R 0-14 0-14 Unit 12 Compressor 1 Status X X X

DiscreteInput 12004 R Off/On = 0/1 0-1 Unit 12 Indicates Blower 2 Is Running In Unit

InputRegister 12004 R 0-14 0-14 Unit 12 Compressor 2 Status X

DiscreteInput 12005 R Off/On = 0/1 0-1 Unit 12 Low Pressure Switch 1 X

Page 64: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 64 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

DiscreteInput 12006 R Off/On = 0/1 0-1 Unit 12 Low Pressure Switch 2

DiscreteInput 12007 R Off/On = 0/1 0-1 Unit 12 Damper Switch 1 Open X X X

DiscreteInput 12008 R Off/On = 0/1 0-1 Unit 12 Damper Switch 2 Open X

DiscreteInput 12009 R Off/On = 0/1 0-1 Unit 12 Damper Switch 3 Open X

DiscreteInput 12010 R Off/On = 0/1 0-1 Unit 12 Damper Switch 4 Open

InputRegister 12011 R ###.# NA Unit 12 Mixed Air Temperature Sensor 1 X X X

DiscreteInput 12012 R Off/On = 0/1 0-1 Unit 12 Activates Reheat Valve for Dehum X

InputRegister 12013 R ###.# NA Unit 12 Mixed Air Temperature Sensor 2 X

InputRegister 12014 R Zone1, 2, or 3 1-3 Unit 12 Zone Options X X X

InputRegister 12015 R ###.# NA Unit 12 Outdoor Air Temperature Sensor 1 X X X

InputRegister 12017 R ###.# NA Unit 12 Outdoor Air Temperature Sensor 2

InputRegister 12019 R ###.# NA Unit 12 Return Air Temperature Sensor 1 X X X

InputRegister 12021 R ###.# NA Unit 12 Return Air Temperature Sensor 2 X

InputRegister 12023 R ###.# 0-100% Unit 12 Outdoor Humidity Sensor 1 X X

InputRegister 12025 R ###.# 0-100% Unit 12 Outdoor Humidity Sensor 2

InputRegister 12027 R ###.# NA Unit 12 Freeze Sensor 1 X

DiscreteInput 12029 R Off/On = 0/1 0-1 Unit 12 Heat 1 On/Off X X X

InputRegister 12029 R ###.# NA Unit 12 Freeze Sensor 2

DiscreteInput 12030 R Off/On = 0/1 0-1 Unit 12 Heat 2 On/Off X X X

DiscreteInput 12031 R Off/On = 0/1 0-1 Unit 12 Heat 3 On/Off X

DiscreteInput 12032 R Off/On = 0/1 0-1 Unit 12 Heat 4 On/Off

DiscreteInput 12033 R Off/On = 0/1 0-1 Unit 12 FreeCool Is Available X X X

DiscreteInput 12034 R Off/On = 0/1 0-1 Unit 12 Dirty Filter Indicator X X

InputRegister 12034 R ### 0-100% Unit 12 Blower Speed 1 X X

DiscreteInput 12035 R Off/On = 0/1 0-1 Unit 12 Cooling 1 On/Off X X X

InputRegister 12035 R ### 0-100% Unit 12 Blower Speed 2

DiscreteInput 12036 R Off/On = 0/1 0-1 Unit 12 Cooling 2 On/Off X X X

InputRegister 12036 R ### 0-45 bar Unit 12 Discharge Pressure Transducer 1

DiscreteInput 12037 R Off/On = 0/1 0-1 Unit 12 Cooling 3 On/Off X

InputRegister 12037 R ### 0-45 bar Unit 12 Discharge Pressure Transducer 2

DiscreteInput 12038 R Off/On = 0/1 0-1 Unit 12 Cooling 4 On/Off

InputRegister 12038 R ###.# NA Unit 12 Discharge Temperature 1

DiscreteInput 12039 R Off/On = 0/1 0-1 Unit 12 Indicates No Air Flow X X

InputRegister 12039 R ###.# NA Unit 12 Discharge Temperature 2

DiscreteInput 12040 R Off/On = 0/1 0-1 Unit 12 Indicates No Air Flow 2

InputRegister 12040 R ### 0-100% Unit 12 Dust Sensor 1 X X

DiscreteInput 12041 R Off/On = 0/1 0-1 Unit 12 High Pressure 1 Event X X X

InputRegister 12041 R ### 0-100% Unit 12 Dust Sensor 2

DiscreteInput 12042 R Off/On = 0/1 0-1 Unit 12 High Pressure 2 Event X

DiscreteInput 12043 R Off/On = 0/1 0-1 Unit 12 Power Loss Detected Alarm X X

DiscreteInput 12044 R Off/On = 0/1 0-1 Unit 12 Is Disabled X X X

InputRegister 12044 R ###.# NA Unit 12 Liquid Temperature 1 X X

InputRegister 12045 R ###.# NA Unit 12 Liquid Temperature 2 X

InputRegister 12046 R ### NA Unit 12 Liquid Pressure 1 X

InputRegister 12047 R ### NA Unit 12 Liquid Pressure 2

InputRegister 12048 R ### NA Unit 12 Suction Pressure 1 X X

InputRegister 12049 R ### NA Unit 12 Suction Pressure 2

InputRegister 12050 R ###.# NA Unit 12 Suction Temperature 1 X X

InputRegister 12051 R ###.# NA Unit 12 Suction Temperature 2

Page 65: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 65 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

InputRegister 12052 R ###.# NA Unit 12 Supply Air Temperature 1 X X

InputRegister 12053 R ###.# NA Unit 12 Supply Air Temperature 2 X

InputRegister 12056 R ### 0-100% Unit 12 Condenser Fan Speed 1 X X

InputRegister 12057 R ### 0-100% Unit 12 Condenser Fan Speed 2 X

InputRegister 12058 R ### 0-100% Unit 12 Damper Position 1 X X X

InputRegister 12059 R ### 0-100% Unit 12 Damper Position 2 X

InputRegister 12060 R ### 0-100% Unit 12 Damper Position 3 X

InputRegister 12061 R ### 0-100% Unit 12 Damper Position 4 X

InputRegister 12062 R ### 0-100% Unit 12 EEV1 Position X X X

InputRegister 12063 R ### 0-100% Unit 12 EEV2 Position X

InputRegister 12064 R ### NA Unit 12 Declares number of Cooling Stages X X

InputRegister 12065 R ### NA Unit 12 Declares number of Heating Stages X X

InputRegister 12066 R ### NA Unit 12 Declares number of Freecooling Stages X X

InputRegister 12067 R ### NA Unit 12 Outdoor Air Dewpoint X

InputRegister 12068 R ### 0,1,2,3 Unit 12 Dehumidification Type X X

InputRegister 12069 R ###.# NA Unit 12 Suction Saturation Temperature 1

InputRegister 12070 R ###.# NA Unit 12 Suction Saturation Temperature 2

InputRegister 12071 R ### NA Unit 12 Subcooling 1 X

InputRegister 12072 R ### NA Unit 12 Superheat 1

InputRegister 12073 R ### NA Unit 12 Superheat 2

InputRegister 12074 R ###.# NA Unit 12 Liquid Saturated Temperature 1

InputRegister 12075 R ###.# NA Unit 12 Liquid Saturated Temperature 2

InputRegister 12076 R ### NA Unit 12 Subcooling 2

InputRegister 12080 R ### NA Unit 12 Major Revision Number X X X

InputRegister 12081 R ### NA Unit 12 Minor Revision Number X X X

InputRegister 12082 R ### NA Unit 12 Bug Fixes X X X

InputRegister 12083 R ### NAUnit 12 How long the unit has been running in minutes

X X X

InputRegister 12084 R ## NA Unit 12 How many times unit has started X X X

InputRegister 12085 R ### NA Unit 12 How long the Fan is running in minutes X X

InputRegister 12086 R ## NA Unit 12 How many times Fan turned on X X

InputRegister 12087 R ### NA Unit 12 How long the Fan is running in minutes

InputRegister 12088 R ## NA Unit 12 How many times Fan turned on

InputRegister 12089 R ### NAUnit 12 How long the Blower is running in minutes

X X X

InputRegister 12090 R ## NA Unit 12 How many times Blower turned on X X

InputRegister 12091 R ### NAUnit 12 How long the Blower is running in minutes

InputRegister 12092 R ## NA Unit 12 How many times Blower turned on

InputRegister 12093 R ### NA Unit 12 How long unit is running in Freecooling X X

InputRegister 12094 R ### NAUnit 12 How many times unit has been in Freecooling

X X

InputRegister 12095 R ### NA Unit 12 How long unit is running in Freecooling

InputRegister 12096 R ### NAUnit 12 How many times unit has been in Freecooling

InputRegister 12097 R ### NA Unit 12 How long unit is running in Cooling X X X

InputRegister 12098 R ### NA Unit 12 How many times unit has been in Cooling X X X

InputRegister 12099 R ### NA Unit 12 How long unit is running in Cooling X X

InputRegister 12100 R ### NA Unit 12 How many times unit has been in Cooling X X

InputRegister 12101 R ### NA Unit 12 How long unit is running in Cooling X

InputRegister 12102 R ### NA Unit 12 How many times unit has been in Cooling X

Page 66: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 66 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

InputRegister 12103 R ### NA Unit 12 How long unit is running in Cooling

InputRegister 12104 R ### NA Unit 12 How many times unit has been in Cooling

InputRegister 12105 R ### NA Unit 12 How long unit is running in Heating X X X

InputRegister 12106 R ### NA Unit 12 How many times unit has been in Heating X X X

InputRegister 12107 R ### NA Unit 12 How long unit is running in Heating X X

InputRegister 12108 R ### NA Unit 12 How many times unit has been in Heating X X

InputRegister 12109 R ### NA Unit 12 How long unit is running in Heating

InputRegister 12110 R ### NA Unit 12 How many times unit has been in Heating

InputRegister 12111 R ### NA Unit 12 How long unit is running in Heating

InputRegister 12112 R ### NA Unit 12 How many times unit has been in Heating

InputRegister 12113 R ### 0-999999 Unit 12 life time in Hours (Update every Hour) X X X

InputRegister 12115 R ### 0-999999Unit 12 Blower 1 life time in Hours (Update every Hour)

X X

InputRegister 12117 R ### 0-999999Unit 12 Blower 2 life time in Hours (Update every Hour)

InputRegister 12119 R ### 0-999999Unit 12 Fan 1 life time in hours (Update every Hour)

X

InputRegister 12121 R ### 0-999999Unit 12 Fan 2 life time in hours (Update every Hour)

InputRegister 12123 R ### 0-999999Unit 12 Cooling 1 life time in hours (Update ever Hour)

X X

InputRegister 12125 R ### 0-999999Unit 12 Cooling 2 life time in hours (Update ever Hour)

X

InputRegister 12127 R ### 0-999999Unit 12 Cooling 3 life time in hours (Update ever Hour)

InputRegister 12129 R ### 0-999999Unit 12 Cooling 4 life time in hours (Update ever Hour)

InputRegister 12131 R ### 0-999999Unit 12 Heating 1 life time in hours (Update ever Hour)

X X

InputRegister 12133 R ### 0-999999Unit 12 Heating 2 life time in hours (Update ever Hour)

InputRegister 12135 R ### 0-999999Unit 12 Heating 3 life time in hours (Update ever Hour)

InputRegister 12137 R ### 0-999999Unit 12 Heating 4 life time in hours (Update ever Hour)

InputRegister 12139 R ### 0-999999Unit 12 FreeCooling 1 life time in hours (Update ever Hour)

X X

InputRegister 12141 R ### 0-999999Unit 12 FreeCooling 2 life time in hours (Update ever Hour)

InputRegister 12143 R ### 0-5Unit 12 Indicates what unit types are running on the network

X X X

DiscreteInput 12500 R Off/On = 0/1 0-1Unit 12 Error in the number of retain memory writings Alarm

X X X

DiscreteInput 12501 R Off/On = 0/1 0-1 Unit 12 Error in retain memory writings Alarm X X X

DiscreteInput 12502 R Off/On = 0/1 0-1 Unit 12 Return Air Temperature Sensor Alarm X X X

DiscreteInput 12503 R Off/On = 0/1 0-1 Unit 12 High Return Air Temperature Alarm X X

DiscreteInput 12504 R Off/On = 0/1 0-1 Unit 12 Mixed Air Temperature Sensor Alarm X X

DiscreteInput 12505 R Off/On = 0/1 0-1 Unit 12 Mixed Air High Temperature Alarm X X

DiscreteInput 12506 R Off/On = 0/1 0-1 Unit 12 Mixed Air Low Temperature Alarm X X

DiscreteInput 12507 R Off/On = 0/1 0-1 Unit 12 Supply Air Temperature Sensor Alarm X X

DiscreteInput 12508 R Off/On = 0/1 0-1 Unit 12 High Supply Air Temperature Alarm X

DiscreteInput 12509 R Off/On = 0/1 0-1 Unit 12 Low Supply Air Temperature Alarm X

DiscreteInput 12510 R Off/On = 0/1 0-1 Unit 12 Outdoor Air Temperature Sensor Alarm X X X

DiscreteInput 12511 R Off/On = 0/1 0-1 Unit 12 Outdoor Air Humidity Sensor Alarm X X X

DiscreteInput 12512 R Off/On = 0/1 0-1 Unit 12 Dust Sensor Alarm X X

Page 67: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 67 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

DiscreteInput 12513 R Off/On = 0/1 0-1 Unit 12 Dust Sensor High Dust Detection Alarm X X

DiscreteInput 12514 R Off/On = 0/1 0-1 Unit 12 Liquid Line Temp Sensor Alarm X X

DiscreteInput 12515 R Off/On = 0/1 0-1 Unit 12 Discharge Temp Sensor Alarm

DiscreteInput 12516 R Off/On = 0/1 0-1 Unit 12 Liquid Line Pressure Sensor Alarm X

DiscreteInput 12517 R Off/On = 0/1 0-1 Unit 12 Suction Temperature Sensor Alarm X X X

DiscreteInput 12518 R Off/On = 0/1 0-1 Unit 12 Suction Pressure Sensor Alarm X X X

DiscreteInput 12519 R Off/On = 0/1 0-1 Unit 12 Low Pressure Alarm X X X

DiscreteInput 12520 R Off/On = 0/1 0-1 Unit 12 High Pressure Alarm X X X

DiscreteInput 12521 R Off/On = 0/1 0-1 Unit 12 Damper 1 Failed to Open X X X

DiscreteInput 12522 R Off/On = 0/1 0-1 Unit 12 Damper 1 Failed to Close X X X

DiscreteInput 12523 R Off/On = 0/1 0-1 Unit 12 Freeze Temperature Sensor Alarm X X

DiscreteInput 12524 R Off/On = 0/1 0-1 Unit 12 Freeze Condition X X X

DiscreteInput 12525 R Off/On = 0/1 0-1 Unit 12 Blower Fail Alarm X X

DiscreteInput 12526 R Off/On = 0/1 0-1 Unit 12 Dirty Filter 1 Alarm X X X

DiscreteInput 12527 R Off/On = 0/1 0-1 Unit 12 Dirty Condenser Coil Alarm

DiscreteInput 12528 R Off/On = 0/1 0-1 Unit 12 Emergency Ventilation Mode Active Alarm X X X

DiscreteInput 12529 R Off/On = 0/1 0-1 Unit 12 Emergency Cooling Mode Active Alarm X X X

DiscreteInput 12530 R Off/On = 0/1 0-1Unit 12 Extreme High Return Temp Alarm (Heat Cutout) Alarm

X X X

DiscreteInput 12531 R Off/On = 0/1 0-1 Unit 12 Disable/Smoke Detector Alarm X X X

DiscreteInput 12532 R Off/On = 0/1 0-1 Unit 12 Power Loss Detected Alarm X

DiscreteInput 12533 R Off/On = 0/1 0-1 Unit 12 Low SuperHeat Alarm X X X

DiscreteInput 12534 R Off/On = 0/1 0-1 Unit 12 Low Evaporation Pressure Alarm X X X

DiscreteInput 12535 R Off/On = 0/1 0-1 Unit 12 High Evaporation Pressure Alarm X X X

DiscreteInput 12536 R Off/On = 0/1 0-1 Unit 12 High Condenser Temperature Alarm X X X

DiscreteInput 12537 R Off/On = 0/1 0-1 Unit 12 Low Suction pressure Alarm X X X

DiscreteInput 12538 R Off/On = 0/1 0-1 Unit 12 EEV motor error Alarm X X X

DiscreteInput 12539 R Off/On = 0/1 0-1 Unit 12 SelfTuning error Alarm X X X

DiscreteInput 12540 R Off/On = 0/1 0-1 Unit 12 Emergency close Alarm X X X

DiscreteInput 12541 R Off/On = 0/1 0-1 Unit 12 High Delta Temperature Alarm

DiscreteInput 12542 R Off/On = 0/1 0-1 Unit 12 High Delta Pressure Alarm

DiscreteInput 12543 R Off/On = 0/1 0-1 Unit 12 Range Error Alarm X X X

DiscreteInput 12544 R Off/On = 0/1 0-1 Unit 12 Service Position Percent Alarm X X X

DiscreteInput 12545 R Off/On = 0/1 0-1 Unit 12 Valve ID Alarm X X X

DiscreteInput 12546 R Off/On = 0/1 0-1 Unit 12 Return Air Temperature Sensor 2 Alarm X

DiscreteInput 12547 R Off/On = 0/1 0-1 Unit 12 High Return Air Temperature 2 Alarm X

DiscreteInput 12548 R Off/On = 0/1 0-1 Unit 12 Mixed Air Temperature Sensor 2 Alarm X

DiscreteInput 12549 R Off/On = 0/1 0-1 Unit 12 Mixed Air High Temperature 2 Alarm

DiscreteInput 12550 R Off/On = 0/1 0-1 Unit 12 Mixed Air Low Temperature 2 Alarm

DiscreteInput 12551 R Off/On = 0/1 0-1 Unit 12 Supply Air Temperature Sensor 2 Alarm X

DiscreteInput 12552 R Off/On = 0/1 0-1 Unit 12 High Supply Air Temperature 2 Alarm

DiscreteInput 12553 R Off/On = 0/1 0-1 Unit 12 Low Supply Air Temperature 2 Alarm

DiscreteInput 12554 R Off/On = 0/1 0-1 Unit 12 Dust Sensor 2 Alarm

DiscreteInput 12555 R Off/On = 0/1 0-1 Unit 12 Dust Sensor High Dust Detection 2 Alarm

DiscreteInput 12556 R Off/On = 0/1 0-1 Unit 12 Liquid Line Temp Sensor 2 Alarm X

DiscreteInput 12557 R Off/On = 0/1 0-1 Unit 12 Liquid Line Pressure Sensor Alarm

DiscreteInput 12558 R Off/On = 0/1 0-1 Unit 12 Discharge Temp Sensor 2 Alarm

DiscreteInput 12559 R Off/On = 0/1 0-1 Unit 12 Discharge Pressure Sensor 2 Alarm X

DiscreteInput 12560 R Off/On = 0/1 0-1 Unit 12 Discharge Pressure Sensor 2 Alarm X

Page 68: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 68 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

DiscreteInput 12561 R Off/On = 0/1 0-1 Unit 12 Suction Temperature Sensor 2 Alarm X

DiscreteInput 12562 R Off/On = 0/1 0-1 Unit 12 Suction Pressure Sensor 2 Alarm X

DiscreteInput 12563 R Off/On = 0/1 0-1 Unit 12 Low Pressure 2 Alarm X

DiscreteInput 12564 R Off/On = 0/1 0-1 Unit 12 High Pressure 2 Alarm X

DiscreteInput 12565 R Off/On = 0/1 0-1 Unit 12 Damper 2 Failed to Open X

DiscreteInput 12566 R Off/On = 0/1 0-1 Unit 12 Damper 2 Failed to Close X

DiscreteInput 12567 R Off/On = 0/1 0-1 Unit 12 Damper 3 Failed to Open X

DiscreteInput 12568 R Off/On = 0/1 0-1 Unit 12 Damper 3 Failed to Close X

DiscreteInput 12569 R Off/On = 0/1 0-1 Unit 12 Damper 4 Failed to Open

DiscreteInput 12570 R Off/On = 0/1 0-1 Unit 12 Damper 4 Failed to Close

DiscreteInput 12571 R Off/On = 0/1 0-1 Unit 12 Freeze Temperature Sensor Alarm X

DiscreteInput 12572 R Off/On = 0/1 0-1 Unit 12 Freeze Condition Alarm X

DiscreteInput 12573 R Off/On = 0/1 0-1 Unit 12 Blower Fail Alarm

DiscreteInput 12574 R Off/On = 0/1 0-1 Unit 12 Dirty Filter 2 Alarm

DiscreteInput 12575 R Off/On = 0/1 0-1 Unit 12 Dirty Filter 3 Alarm

DiscreteInput 12576 R Off/On = 0/1 0-1 Unit 12 Dirty Filter 4 Alarm

DiscreteInput 12577 R Off/On = 0/1 0-1 Unit 12 Dirty Condenser Coil 2 Alarm

DiscreteInput 12578 R Off/On = 0/1 0-1 Unit 12 Power Loss 2 Detected Alarm

DiscreteInput 12579 R Off/On = 0/1 0-1 Unit 12 Low SuperHeat 2 Alarm X

DiscreteInput 12580 R Off/On = 0/1 0-1 Unit 12 Low Evaporation Pressure 2 Alarm X

DiscreteInput 12581 R Off/On = 0/1 0-1 Unit 12 High Evaporation Pressure 2 Alarm X

DiscreteInput 12582 R Off/On = 0/1 0-1 Unit 12 High Condenser Temperature 2 Alarm X

DiscreteInput 12583 R Off/On = 0/1 0-1 Unit 12 Low Suction pressure 2 Alarm X

DiscreteInput 12584 R Off/On = 0/1 0-1 Unit 12 EEV motor 2 error Alarm X

DiscreteInput 12585 R Off/On = 0/1 0-1 Unit 12 SelfTuning 2 error Alarm X

DiscreteInput 12586 R Off/On = 0/1 0-1 Unit 12 Emergency close 2 Alarm X

DiscreteInput 12587 R Off/On = 0/1 0-1 Unit 12 High Delta Temperature 2 Alarm

DiscreteInput 12588 R Off/On = 0/1 0-1 Unit 12 High Delta Pressure 2 Alarm

DiscreteInput 12589 R Off/On = 0/1 0-1 Unit 12 Range Error 2 Alarm X

DiscreteInput 12590 R Off/On = 0/1 0-1 Unit 12 Service Position Percent 2 Alarm X

DiscreteInput 12591 R Off/On = 0/1 0-1 Unit 12 Valve ID 2 Alarm X

DiscreteInput 12592 R Off/On = 0/1 0-1 Unit 12 Th-Tune Device Offline Alarm X

DiscreteInput 12593 R Off/On = 0/1 0-1 Unit 12 Th-Tune Temperature Probe Alarm X

DiscreteInput 12594 R Off/On = 0/1 0-1 Unit 12 Th-Tune Humidity Probe Alarm X

DiscreteInput 12595 R Off/On = 0/1 0-1 Unit 12 Th-Tune Clock Board Alarm X

DiscreteInput 12596 R Off/On = 0/1 0-1 Unit 12 cpCOe Offline Alarm X

DiscreteInput 12597 R Off/On = 0/1 0-1 Unit 12 Blower 1 Offline Alarm X

DiscreteInput 12598 R Off/On = 0/1 0-1 Unit 12 Blower 1 Alarm X

DiscreteInput 12599 R Off/On = 0/1 0-1 Unit 12 Blower 2 Offline Alarm

DiscreteInput 12600 R Off/On = 0/1 0-1 Unit 12 Blower 2 Alarm

DiscreteInput 12601 R Off/On = 0/1 0-1 Unit 12 Condenser 1 Offline Alarm X

DiscreteInput 12602 R Off/On = 0/1 0-1 Unit 12 Condenser 1 Alarm X

DiscreteInput 12603 R Off/On = 0/1 0-1 Unit 12 Condenser 2 Offline Alarm

DiscreteInput 12604 R Off/On = 0/1 0-1 Unit 12 Condenser 2 Alarm

DiscreteInput 12605 R Off/On = 0/1 0-1 Unit 12 Low Return Air Temperature 1 Alarm X

DiscreteInput 12606 R Off/On = 0/1 0-1 Unit 12 Low Return Air Temperature 2 Alarm X

DiscreteInput 12607 R Off/On = 0/1 0-1 Unit 12 Panel Open Alarm X

DiscreteInput 13000 R Off/On = 0/1 0-1 Unit 13 Dirty Filter 1 Alarm X X X

DiscreteInput 13001 R Off/On = 0/1 0-1 Unit 13 Dirty Filter 2 Alarm X

Page 69: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 69 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

DiscreteInput 13002 R Off/On = 0/1 0-1 Unit 13 Dirty Filter 3 Alarm

DiscreteInput 13003 R Off/On = 0/1 0-1 Unit 13 Indicates Blower 1 Is Running In Unit X X

InputRegister 13003 R 0-14 0-14 Unit 13 Compressor 1 Status X X X

DiscreteInput 13004 R Off/On = 0/1 0-1 Unit 13 Indicates Blower 2 Is Running In Unit

InputRegister 13004 R 0-14 0-14 Unit 13 Compressor 2 Status X

DiscreteInput 13005 R Off/On = 0/1 0-1 Unit 13 Low Pressure Switch 1 X

DiscreteInput 13006 R Off/On = 0/1 0-1 Unit 13 Low Pressure Switch 2

DiscreteInput 13007 R Off/On = 0/1 0-1 Unit 13 Damper Switch 1 Open X X X

DiscreteInput 13008 R Off/On = 0/1 0-1 Unit 13 Damper Switch 2 Open X

DiscreteInput 13009 R Off/On = 0/1 0-1 Unit 13 Damper Switch 3 Open X

DiscreteInput 13010 R Off/On = 0/1 0-1 Unit 13 Damper Switch 4 Open

InputRegister 13011 R ###.# NA Unit 13 Mixed Air Temperature Sensor 1 X X X

DiscreteInput 13012 R Off/On = 0/1 0-1 Unit 13 Activates Reheat Valve for Dehum X

InputRegister 13013 R ###.# NA Unit 13 Mixed Air Temperature Sensor 2 X

InputRegister 13014 R Zone1, 2, or 3 1-3 Unit 13 Zone Options X X X

InputRegister 13015 R ###.# NA Unit 13 Outdoor Air Temperature Sensor 1 X X X

InputRegister 13017 R ###.# NA Unit 13 Outdoor Air Temperature Sensor 2

InputRegister 13019 R ###.# NA Unit 13 Return Air Temperature Sensor 1 X X X

InputRegister 13021 R ###.# NA Unit 13 Return Air Temperature Sensor 2 X

InputRegister 13023 R ###.# 0-100% Unit 13 Outdoor Humidity Sensor 1 X X

InputRegister 13025 R ###.# 0-100% Unit 13 Outdoor Humidity Sensor 2

InputRegister 13027 R ###.# NA Unit 13 Freeze Sensor 1 X

DiscreteInput 13029 R Off/On = 0/1 0-1 Unit 13 Heat 1 On/Off X X X

InputRegister 13029 R ###.# NA Unit 13 Freeze Sensor 2

DiscreteInput 13030 R Off/On = 0/1 0-1 Unit 13 Heat 2 On/Off X X X

DiscreteInput 13031 R Off/On = 0/1 0-1 Unit 13 Heat 3 On/Off X

DiscreteInput 13032 R Off/On = 0/1 0-1 Unit 13 Heat 4 On/Off

DiscreteInput 13033 R Off/On = 0/1 0-1 Unit 13 FreeCool Is Available X X X

DiscreteInput 13034 R Off/On = 0/1 0-1 Unit 13 Dirty Filter Indicator X X

InputRegister 13034 R ### 0-100% Unit 13 Blower Speed 1 X X

DiscreteInput 13035 R Off/On = 0/1 0-1 Unit 13 Cooling 1 On/Off X X X

InputRegister 13035 R ### 0-100% Unit 13 Blower Speed 2

DiscreteInput 13036 R Off/On = 0/1 0-1 Unit 13 Cooling 2 On/Off X X X

InputRegister 13036 R ### 0-45 bar Unit 13 Discharge Pressure Transducer 1

DiscreteInput 13037 R Off/On = 0/1 0-1 Unit 13 Cooling 3 On/Off X

InputRegister 13037 R ### 0-45 bar Unit 13 Discharge Pressure Transducer 2

DiscreteInput 13038 R Off/On = 0/1 0-1 Unit 13 Cooling 4 On/Off

InputRegister 13038 R ###.# NA Unit 13 Discharge Temperature 1

DiscreteInput 13039 R Off/On = 0/1 0-1 Unit 13 Indicates No Air Flow X X

InputRegister 13039 R ###.# NA Unit 13 Discharge Temperature 2

DiscreteInput 13040 R Off/On = 0/1 0-1 Unit 13 Indicates No Air Flow 2

InputRegister 13040 R ### 0-100% Unit 13 Dust Sensor 1 X X

DiscreteInput 13041 R Off/On = 0/1 0-1 Unit 13 High Pressure 1 Event X X X

InputRegister 13041 R ### 0-100% Unit 13 Dust Sensor 2

DiscreteInput 13042 R Off/On = 0/1 0-1 Unit 13 High Pressure 2 Event X

DiscreteInput 13043 R Off/On = 0/1 0-1 Unit 13 Power Loss 2 Detected Alarm X X

DiscreteInput 13044 R Off/On = 0/1 0-1 Unit 13 Is Disabled X X X

InputRegister 13044 R ###.# NA Unit 13 Liquid Temperature 1 X X

InputRegister 13045 R ###.# NA Unit 13 Liquid Temperature 2 X

Page 70: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 70 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

InputRegister 13046 R ### NA Unit 13 Liquid Pressure 1 X

InputRegister 13047 R ### NA Unit 13 Liquid Pressure 2

InputRegister 13048 R ### NA Unit 13 Suction Pressure 1 X X

InputRegister 13049 R ### NA Unit 13 Suction Pressure 2

InputRegister 13050 R ###.# NA Unit 13 Suction Temperature 1 X X

InputRegister 13051 R ###.# NA Unit 13 Suction Temperature 2

InputRegister 13052 R ###.# NA Unit 13 Supply Air Temperature 1 X X

InputRegister 13053 R ###.# NA Unit 13 Supply Air Temperature 2 X

InputRegister 13056 R ### 0-100% Unit 13 Condenser Fan Speed 1 X X

InputRegister 13057 R ### 0-100% Unit 13 Condenser Fan Speed 2 X

InputRegister 13058 R ### 0-100% Unit 13 Damper Position 1 X X X

InputRegister 13059 R ### 0-100% Unit 13 Damper Position 2 X

InputRegister 13060 R ### 0-100% Unit 13 Damper Position 3 X

InputRegister 13061 R ### 0-100% Unit 13 Damper Position 4 X

InputRegister 13062 R ### 0-100% Unit 13 EEV1 Position X X X

InputRegister 13063 R ### 0-100% Unit 13 EEV2 Position X

InputRegister 13064 R ### NA Unit 13 Declares number of Cooling Stages X X

InputRegister 13065 R ### NA Unit 13 Declares number of Heating Stages X X

InputRegister 13066 R ### NA Unit 13 Declares number of Freecooling Stages X X

InputRegister 13067 R ### NA Unit 13 Outdoor Air Dewpoint X

InputRegister 13068 R ### 0,1,2,3 Unit 13 Dehumidification Type X X

InputRegister 13069 R ###.# NA Unit 13 Suction Saturation Temperature 1

InputRegister 13070 R ###.# NA Unit 13 Suction Saturation Temperature 2

InputRegister 13071 R ### NA Unit 13 Subcooling 1 X

InputRegister 13072 R ### NA Unit 13 Superheat 1

InputRegister 13073 R ### NA Unit 13 Superheat 2

InputRegister 13074 R ###.# NA Unit 13 Liquid Saturated Temperature 1

InputRegister 13075 R ###.# NA Unit 13 Liquid Saturated Temperature 2

InputRegister 13076 R ### NA Unit 13 Subcooling 2

InputRegister 13080 R ### NA Unit 13 Major Revision Number X X X

InputRegister 13081 R ### NA Unit 13 Minor Revision Number X X X

InputRegister 13082 R ### NA Unit 13 Bug Fixes X X X

InputRegister 13083 R ### NAUnit 13 How long the unit has been running in minutes

X X X

InputRegister 13084 R ## NA Unit 13 How many times unit has started X X X

InputRegister 13085 R ### NA Unit 13 How long the Fan is running in minutes X X

InputRegister 13086 R ## NA Unit 13 How many times Fan turned on X X

InputRegister 13087 R ### NA Unit 13 How long the Fan is running in minutes

InputRegister 13088 R ## NA Unit 13 How many times Fan turned on

InputRegister 13089 R ### NAUnit 13 How long the Blower is running in minutes

X X X

InputRegister 13090 R ## NA Unit 13 How many times Blower turned on X X

InputRegister 13091 R ### NAUnit 13 How long the Blower is running in minutes

InputRegister 13092 R ## NA Unit 13 How many times Blower turned on

InputRegister 13093 R ### NA Unit 13 How long unit is running in Freecooling X X

InputRegister 13094 R ### NAUnit 13 How many times unit has been in Freecooling

X X

InputRegister 13095 R ### NA Unit 13 How long unit is running in Freecooling

InputRegister 13096 R ### NAUnit 13 How many times unit has been in Freecooling

Page 71: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 71 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

InputRegister 13097 R ### NA Unit 13 How long unit is running in Cooling X X X

InputRegister 13098 R ### NA Unit 13 How many times unit has been in Cooling X X X

InputRegister 13099 R ### NA Unit 13 How long unit is running in Cooling X X

InputRegister 13100 R ### NA Unit 13 How many times unit has been in Cooling X X

InputRegister 13101 R ### NA Unit 13 How long unit is running in Cooling X

InputRegister 13102 R ### NA Unit 13 How many times unit has been in Cooling X

InputRegister 13103 R ### NA Unit 13 How long unit is running in Cooling

InputRegister 13104 R ### NA Unit 13 How many times unit has been in Cooling

InputRegister 13105 R ### NA Unit 13 How long unit is running in Heating X X X

InputRegister 13106 R ### NA Unit 13 How many times unit has been in Heating X X X

InputRegister 13107 R ### NA Unit 13 How long unit is running in Heating X X

InputRegister 13108 R ### NA Unit 13 How many times unit has been in Heating X X

InputRegister 13109 R ### NA Unit 13 How long unit is running in Heating

InputRegister 13110 R ### NA Unit 13 How many times unit has been in Heating

InputRegister 13111 R ### NA Unit 13 How long unit is running in Heating

InputRegister 13112 R ### NA Unit 13 How many times unit has been in Heating

InputRegister 13113 R ### 0-999999 Unit 13 life time in Hours (Update every Hour) X X X

InputRegister 13115 R ### 0-999999Unit 13 Blower 1 life time in Hours (Update every Hour)

X X

InputRegister 13117 R ### 0-999999Unit 13 Blower 2 life time in Hours (Update every Hour)

InputRegister 13119 R ### 0-999999Unit 13 Fan 1 life time in hours (Update every Hour)

X

InputRegister 13121 R ### 0-999999Unit 13 Fan 2 life time in hours (Update every Hour)

InputRegister 13123 R ### 0-999999Unit 13 Cooling 1 life time in hours (Update ever Hour)

X X

InputRegister 13125 R ### 0-999999Unit 13 Cooling 2 life time in hours (Update ever Hour)

X

InputRegister 13127 R ### 0-999999Unit 13 Cooling 3 life time in hours (Update ever Hour)

InputRegister 13129 R ### 0-999999Unit 13 Cooling 4 life time in hours (Update ever Hour)

InputRegister 13131 R ### 0-999999Unit 13 Heating 1 life time in hours (Update ever Hour)

X X

InputRegister 13133 R ### 0-999999Unit 13 Heating 2 life time in hours (Update ever Hour)

InputRegister 13135 R ### 0-999999Unit 13 Heating 3 life time in hours (Update ever Hour)

InputRegister 13137 R ### 0-999999Unit 13 Heating 4 life time in hours (Update ever Hour)

InputRegister 13139 R ### 0-999999Unit 13 FreeCooling 1 life time in hours (Update ever Hour)

X X

InputRegister 13141 R ### 0-999999Unit 13 FreeCooling 2 life time in hours (Update ever Hour)

InputRegister 13143 R ### 0-5Unit 13 Indicates what unit types are running on the network

X X X

DiscreteInput 13500 R Off/On = 0/1 0-1Unit 13 Error in the number of retain memory writings Alarm

X X X

DiscreteInput 13501 R Off/On = 0/1 0-1 Unit 13 Error in retain memory writings Alarm X X X

DiscreteInput 13502 R Off/On = 0/1 0-1 Unit 13 Return Air Temperature Sensor Alarm X X X

DiscreteInput 13503 R Off/On = 0/1 0-1 Unit 13 High Return Air Temperature Alarm X X

DiscreteInput 13504 R Off/On = 0/1 0-1 Unit 13 Mixed Air Temperature Sensor Alarm X X

DiscreteInput 13505 R Off/On = 0/1 0-1 Unit 13 Mixed Air High Temperature Alarm X X

DiscreteInput 13506 R Off/On = 0/1 0-1 Unit 13 Mixed Air Low Temperature Alarm X X

Page 72: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 72 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

DiscreteInput 13507 R Off/On = 0/1 0-1 Unit 13 Supply Air Temperature Sensor Alarm X X

DiscreteInput 13508 R Off/On = 0/1 0-1 Unit 13 High Supply Air Temperature Alarm X

DiscreteInput 13509 R Off/On = 0/1 0-1 Unit 13 Low Supply Air Temperature Alarm X

DiscreteInput 13510 R Off/On = 0/1 0-1 Unit 13 Outdoor Air Temperature Sensor Alarm X X X

DiscreteInput 13511 R Off/On = 0/1 0-1 Unit 13 Outdoor Air Humidity Sensor Alarm X X X

DiscreteInput 13512 R Off/On = 0/1 0-1 Unit 13 Dust Sensor Alarm X X

DiscreteInput 13513 R Off/On = 0/1 0-1 Unit 13 Dust Sensor High Dust Detection Alarm X X

DiscreteInput 13514 R Off/On = 0/1 0-1 Unit 13 Liquid Line Temp Sensor Alarm X X

DiscreteInput 13515 R Off/On = 0/1 0-1 Unit 13 Discharge Temp Sensor Alarm

DiscreteInput 13516 R Off/On = 0/1 0-1 Unit 13 Liquid Line Pressure Sensor Alarm X

DiscreteInput 13517 R Off/On = 0/1 0-1 Unit 13 Suction Temperature Sensor Alarm X X X

DiscreteInput 13518 R Off/On = 0/1 0-1 Unit 13 Suction Pressure Sensor Alarm X X X

DiscreteInput 13519 R Off/On = 0/1 0-1 Unit 13 Low Pressure Alarm X X X

DiscreteInput 13520 R Off/On = 0/1 0-1 Unit 13 High Pressure Alarm X X X

DiscreteInput 13521 R Off/On = 0/1 0-1 Unit 13 Damper 1 Failed to Open X X X

DiscreteInput 13522 R Off/On = 0/1 0-1 Unit 13 Damper 1 Failed to Close X X X

DiscreteInput 13523 R Off/On = 0/1 0-1 Unit 13 Freeze Temperature Sensor Alarm X X

DiscreteInput 13524 R Off/On = 0/1 0-1 Unit 13 Freeze Condition X X X

DiscreteInput 13525 R Off/On = 0/1 0-1 Unit 13 Blower Fail Alarm X X

DiscreteInput 13526 R Off/On = 0/1 0-1 Unit 13 Dirty Filter 1 Alarm X X X

DiscreteInput 13527 R Off/On = 0/1 0-1 Unit 13 Dirty Condenser Coil Alarm

DiscreteInput 13528 R Off/On = 0/1 0-1 Unit 13 Emergency Ventilation Mode Active Alarm X X X

DiscreteInput 13529 R Off/On = 0/1 0-1 Unit 13 Emergency Cooling Mode Active Alarm X X X

DiscreteInput 13530 R Off/On = 0/1 0-1Unit 13 Extreme High Return Temp Alarm (Heat Cutout) Alarm

X X X

DiscreteInput 13531 R Off/On = 0/1 0-1 Unit 13 Disable/Smoke Detector Alarm X X X

DiscreteInput 13532 R Off/On = 0/1 0-1 Unit 13 Power Loss Detected Alarm X

DiscreteInput 13533 R Off/On = 0/1 0-1 Unit 13 Low SuperHeat Alarm X X X

DiscreteInput 13534 R Off/On = 0/1 0-1 Unit 13 Low Evaporation Pressure Alarm X X X

DiscreteInput 13535 R Off/On = 0/1 0-1 Unit 13 High Evaporation Pressure Alarm X X X

DiscreteInput 13536 R Off/On = 0/1 0-1 Unit 13 High Condenser Temperature Alarm X X X

DiscreteInput 13537 R Off/On = 0/1 0-1 Unit 13 Low Suction pressure Alarm X X X

DiscreteInput 13538 R Off/On = 0/1 0-1 Unit 13 EEV motor error Alarm X X X

DiscreteInput 13539 R Off/On = 0/1 0-1 Unit 13 SelfTuning error Alarm X X X

DiscreteInput 13540 R Off/On = 0/1 0-1 Unit 13 Emergency close Alarm X X X

DiscreteInput 13541 R Off/On = 0/1 0-1 Unit 13 High Delta Temperature Alarm

DiscreteInput 13542 R Off/On = 0/1 0-1 Unit 13 High Delta Pressure Alarm

DiscreteInput 13543 R Off/On = 0/1 0-1 Unit 13 Range Error Alarm X X X

DiscreteInput 13544 R Off/On = 0/1 0-1 Unit 13 Service Position Percent Alarm X X X

DiscreteInput 13545 R Off/On = 0/1 0-1 Unit 13 Valve ID Alarm X X X

DiscreteInput 13546 R Off/On = 0/1 0-1 Unit 13 Return Air Temperature Sensor 2 Alarm X

DiscreteInput 13547 R Off/On = 0/1 0-1 Unit 13 High Return Air Temperature 2 Alarm X

DiscreteInput 13548 R Off/On = 0/1 0-1 Unit 13 Mixed Air Temperature Sensor 2 Alarm X

DiscreteInput 13549 R Off/On = 0/1 0-1 Unit 13 Mixed Air High Temperature 2 Alarm

DiscreteInput 13550 R Off/On = 0/1 0-1 Unit 13 Mixed Air Low Temperature 2 Alarm

DiscreteInput 13551 R Off/On = 0/1 0-1 Unit 13 Supply Air Temperature Sensor 2 Alarm X

DiscreteInput 13552 R Off/On = 0/1 0-1 Unit 13 High Supply Air Temperature 2 Alarm

DiscreteInput 13553 R Off/On = 0/1 0-1 Unit 13 Low Supply Air Temperature 2 Alarm

DiscreteInput 13554 R Off/On = 0/1 0-1 Unit 13 Dust Sensor 2 Alarm

Page 73: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 73 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

DiscreteInput 13555 R Off/On = 0/1 0-1 Unit 13 Dust Sensor High Dust Detection 2 Alarm

DiscreteInput 13556 R Off/On = 0/1 0-1 Unit 13 Liquid Line Temp Sensor 2 Alarm X

DiscreteInput 13557 R Off/On = 0/1 0-1 Unit 13 Liquid Line Pressure Sensor Alarm

DiscreteInput 13558 R Off/On = 0/1 0-1 Unit 13 Discharge Temp Sensor 2 Alarm

DiscreteInput 13559 R Off/On = 0/1 0-1 Unit 13 Discharge Pressure Sensor 2 Alarm X

DiscreteInput 13560 R Off/On = 0/1 0-1 Unit 13 Discharge Pressure Sensor 2 Alarm X

DiscreteInput 13561 R Off/On = 0/1 0-1 Unit 13 Suction Temperature Sensor 2 Alarm X

DiscreteInput 13562 R Off/On = 0/1 0-1 Unit 13 Suction Pressure Sensor 2 Alarm X

DiscreteInput 13563 R Off/On = 0/1 0-1 Unit 13 Low Pressure 2 Alarm X

DiscreteInput 13564 R Off/On = 0/1 0-1 Unit 13 High Pressure 2 Alarm X

DiscreteInput 13565 R Off/On = 0/1 0-1 Unit 13 Damper 2 Failed to Open X

DiscreteInput 13566 R Off/On = 0/1 0-1 Unit 13 Damper 2 Failed to Close X

DiscreteInput 13567 R Off/On = 0/1 0-1 Unit 13 Damper 3 Failed to Open X

DiscreteInput 13568 R Off/On = 0/1 0-1 Unit 13 Damper 3 Failed to Close X

DiscreteInput 13569 R Off/On = 0/1 0-1 Unit 13 Damper 4 Failed to Open

DiscreteInput 13570 R Off/On = 0/1 0-1 Unit 13 Damper 4 Failed to Close

DiscreteInput 13571 R Off/On = 0/1 0-1 Unit 13 Freeze Temperature Sensor Alarm X

DiscreteInput 13572 R Off/On = 0/1 0-1 Unit 13 Freeze Condition Alarm X

DiscreteInput 13573 R Off/On = 0/1 0-1 Unit 13 Blower Fail Alarm

DiscreteInput 13574 R Off/On = 0/1 0-1 Unit 13 Dirty Filter 2 Alarm

DiscreteInput 13575 R Off/On = 0/1 0-1 Unit 13 Dirty Filter 3 Alarm

DiscreteInput 13576 R Off/On = 0/1 0-1 Unit 13 Dirty Filter 4 Alarm

DiscreteInput 13577 R Off/On = 0/1 0-1 Unit 13 Dirty Condenser Coil 2 Alarm

DiscreteInput 13578 R Off/On = 0/1 0-1 Unit 13 Power Loss 2 Detected Alarm

DiscreteInput 13579 R Off/On = 0/1 0-1 Unit 13 Low SuperHeat 2 Alarm X

DiscreteInput 13580 R Off/On = 0/1 0-1 Unit 13 Low Evaporation Pressure 2 Alarm X

DiscreteInput 13581 R Off/On = 0/1 0-1 Unit 13 High Evaporation Pressure 2 Alarm X

DiscreteInput 13582 R Off/On = 0/1 0-1 Unit 13 High Condenser Temperature 2 Alarm X

DiscreteInput 13583 R Off/On = 0/1 0-1 Unit 13 Low Suction pressure 2 Alarm X

DiscreteInput 13584 R Off/On = 0/1 0-1 Unit 13 EEV motor 2 error Alarm X

DiscreteInput 13585 R Off/On = 0/1 0-1 Unit 13 SelfTuning 2 error Alarm X

DiscreteInput 13586 R Off/On = 0/1 0-1 Unit 13 Emergency close 2 Alarm X

DiscreteInput 13587 R Off/On = 0/1 0-1 Unit 13 High Delta Temperature 2 Alarm

DiscreteInput 13588 R Off/On = 0/1 0-1 Unit 13 High Delta Pressure 2 Alarm

DiscreteInput 13589 R Off/On = 0/1 0-1 Unit 13 Range Error 2 Alarm X

DiscreteInput 13590 R Off/On = 0/1 0-1 Unit 13 Service Position Percent 2 Alarm X

DiscreteInput 13591 R Off/On = 0/1 0-1 Unit 13 Valve ID 2 Alarm X

DiscreteInput 13592 R Off/On = 0/1 0-1 Unit 13 Th-Tune Device Offline Alarm X

DiscreteInput 13593 R Off/On = 0/1 0-1 Unit 13 Th-Tune Temperature Probe Alarm X

DiscreteInput 13594 R Off/On = 0/1 0-1 Unit 13 Th-Tune Humidity Probe Alarm X

DiscreteInput 13595 R Off/On = 0/1 0-1 Unit 13 Th-Tune Clock Board Alarm X

DiscreteInput 13596 R Off/On = 0/1 0-1 Unit 13 cpCOe Offline Alarm X

DiscreteInput 13597 R Off/On = 0/1 0-1 Unit 13 Blower 1 Offline Alarm X

DiscreteInput 13598 R Off/On = 0/1 0-1 Unit 13 Blower 1 Alarm X

DiscreteInput 13599 R Off/On = 0/1 0-1 Unit 13 Blower 2 Offline Alarm

DiscreteInput 13600 R Off/On = 0/1 0-1 Unit 13 Blower 2 Alarm

DiscreteInput 13601 R Off/On = 0/1 0-1 Unit 13 Condenser 1 Offline Alarm X

DiscreteInput 13602 R Off/On = 0/1 0-1 Unit 13 Condenser 1 Alarm X

DiscreteInput 13603 R Off/On = 0/1 0-1 Unit 13 Condenser 2 Offline Alarm

Page 74: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 74 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

DiscreteInput 13604 R Off/On = 0/1 0-1 Unit 13 Condenser 2 Alarm

DiscreteInput 13605 R Off/On = 0/1 0-1 Unit 13 Low Return Air Temperature 1 Alarm X

DiscreteInput 13606 R Off/On = 0/1 0-1 Unit 13 Low Return Air Temperature 2 Alarm X

DiscreteInput 13607 R Off/On = 0/1 0-1 Unit 13 Panel Open Alarm X

DiscreteInput 14000 R Off/On = 0/1 0-1 Unit 14 Dirty Filter 1 Alarm X X X

DiscreteInput 14001 R Off/On = 0/1 0-1 Unit 14 Dirty Filter 2 Alarm X

DiscreteInput 14002 R Off/On = 0/1 0-1 Unit 14 Dirty Filter 3 Alarm

DiscreteInput 14003 R Off/On = 0/1 0-1 Unit 14 Indicates Blower 1 Is Running In Unit X X

InputRegister 14003 R 0-14 0-14 Unit 14 Compressor 1 Status X X X

DiscreteInput 14004 R Off/On = 0/1 0-1 Unit 14 Indicates Blower 2 Is Running In Unit

InputRegister 14004 R 0-14 0-14 Unit 14 Compressor 2 Status X

DiscreteInput 14005 R Off/On = 0/1 0-1 Unit 14 Low Pressure Switch 1 X

DiscreteInput 14006 R Off/On = 0/1 0-1 Unit 14 Low Pressure Switch 2

DiscreteInput 14007 R Off/On = 0/1 0-1 Unit 14 Damper Switch 1 Open X X X

DiscreteInput 14008 R Off/On = 0/1 0-1 Unit 14 Damper Switch 2 Open X

DiscreteInput 14009 R Off/On = 0/1 0-1 Unit 14 Damper Switch 3 Open X

InputRegister 14009 R ###.# NA Unit 14 Mixed Air Temperature Sensor 1 X X X

DiscreteInput 14010 R Off/On = 0/1 0-1 Unit 14 Damper Switch 4 Open

InputRegister 14011 R ###.# NA Unit 14 Mixed Air Temperature Sensor 2 X

DiscreteInput 14012 R Off/On = 0/1 0-1 Unit 14 Activates Reheat Valve for Dehum X

InputRegister 14013 R Zone1, 2, or 3 1-3 Unit 14 Zone Options X X X

InputRegister 14014 R ###.# NA Unit 14 Outdoor Air Temperature Sensor 1 X X X

InputRegister 14015 R ###.# NA Unit 14 Outdoor Air Temperature Sensor 2

InputRegister 14017 R ###.# NA Unit 14 Return Air Temperature Sensor 1 X X X

InputRegister 14019 R ###.# NA Unit 14 Return Air Temperature Sensor 2 X

InputRegister 14021 R ###.# 0-100% Unit 14 Outdoor Humidity Sensor 1 X X

InputRegister 14023 R ###.# 0-100% Unit 14 Outdoor Humidity Sensor 2

InputRegister 14025 R ###.# NA Unit 14 Freeze Sensor 1 X

InputRegister 14027 R ###.# NA Unit 14 Freeze Sensor 2

DiscreteInput 14029 R Off/On = 0/1 0-1 Unit 14 Heat 1 On/Off X X X

DiscreteInput 14030 R Off/On = 0/1 0-1 Unit 14 Heat 2 On/Off X X X

DiscreteInput 14031 R Off/On = 0/1 0-1 Unit 14 Heat 3 On/Off X

DiscreteInput 14032 R Off/On = 0/1 0-1 Unit 14 Heat 4 On/Off

DiscreteInput 14033 R Off/On = 0/1 0-1 Unit 14 FreeCool Is Available X X X

DiscreteInput 14034 R Off/On = 0/1 0-1 Unit 14 Dirty Filter Indicator X X

InputRegister 14034 R ### 0-100% Unit 14 Blower Speed 1 X X

DiscreteInput 14035 R Off/On = 0/1 0-1 Unit 14 Cooling 1 On/Off X X X

InputRegister 14035 R ### 0-100% Unit 14 Blower Speed 2

DiscreteInput 14036 R Off/On = 0/1 0-1 Unit 14 Cooling 2 On/Off X X X

InputRegister 14036 R ### 0-45 bar Unit 14 Discharge Pressure Transducer 1

DiscreteInput 14037 R Off/On = 0/1 0-1 Unit 14 Cooling 3 On/Off X

InputRegister 14037 R ### 0-45 bar Unit 14 Discharge Pressure Transducer 2

DiscreteInput 14038 R Off/On = 0/1 0-1 Unit 14 Cooling 4 On/Off

InputRegister 14038 R ###.# NA Unit 14 Discharge Temperature 1

DiscreteInput 14039 R Off/On = 0/1 0-1 Unit 14 Indicates No Air Flow X X

InputRegister 14039 R ###.# NA Unit 14 Discharge Temperature 2

DiscreteInput 14040 R Off/On = 0/1 0-1 Unit 14 Indicates No Air Flow 2

InputRegister 14040 R ### 0-100% Unit 14 Dust Sensor 1 X X

DiscreteInput 14041 R Off/On = 0/1 0-1 Unit 14 High Pressure 1 Event X X X

Page 75: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 75 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

InputRegister 14041 R ### 0-100% Unit 14 Dust Sensor 2

DiscreteInput 14042 R Off/On = 0/1 0-1 Unit 14 High Pressure 2 Event X

DiscreteInput 14043 R Off/On = 0/1 0-1 Unit 14 Power Loss Detected Alarm X X

DiscreteInput 14044 R Off/On = 0/1 0-1 Unit 14 Is Disabled X X X

InputRegister 14044 R ###.# NA Unit 14 Liquid Temperature 1 X X

InputRegister 14045 R ###.# NA Unit 14 Liquid Temperature 2 X

InputRegister 14046 R ### NA Unit 14 Liquid Pressure 1 X

InputRegister 14047 R ### NA Unit 14 Liquid Pressure 2

InputRegister 14048 R ### NA Unit 14 Suction Pressure 1 X X

InputRegister 14049 R ### NA Unit 14 Suction Pressure 2

InputRegister 14050 R ###.# NA Unit 14 Suction Temperature 1 X X

InputRegister 14051 R ###.# NA Unit 14 Suction Temperature 2

InputRegister 14052 R ###.# NA Unit 14 Supply Air Temperature 1 X X

InputRegister 14053 R ###.# NA Unit 14 Supply Air Temperature 2 X

InputRegister 14056 R ### 0-100% Unit 14 Condenser Fan Speed 1 X X

InputRegister 14057 R ### 0-100% Unit 14 Condenser Fan Speed 2 X

InputRegister 14058 R ### 0-100% Unit 14 Damper Position 1 X X X

InputRegister 14059 R ### 0-100% Unit 14 Damper Position 2 X

InputRegister 14060 R ### 0-100% Unit 14 Damper Position 3 X

InputRegister 14061 R ### 0-100% Unit 14 Damper Position 4 X

InputRegister 14062 R ### 0-100% Unit 14 EEV1 Position X X X

InputRegister 14063 R ### 0-100% Unit 14 EEV2 Position X

InputRegister 14064 R ### NA Unit 14 Declares number of Cooling Stages X X

InputRegister 14065 R ### NA Unit 14 Declares number of Heating Stages X X

InputRegister 14066 R ### NA Unit 14 Declares number of Freecooling Stages X X

InputRegister 14067 R ### NA Unit 14 Outdoor Air Dewpoint X

InputRegister 14068 R ### 0,1,2,3 Unit 14 Dehumidification Type X X

InputRegister 14069 R ###.# NA Unit 14 Suction Saturation Temperature 1

InputRegister 14070 R ###.# NA Unit 14 Suction Saturation Temperature 2

InputRegister 14071 R ### NA Unit 14 Subcooling 1 X

InputRegister 14072 R ### NA Unit 14 Superheat 1

InputRegister 14073 R ### NA Unit 14 Superheat 2

InputRegister 14074 R ###.# NA Unit 14 Liquid Saturated Temperature 1

InputRegister 14075 R ###.# NA Unit 14 Liquid Saturated Temperature 2

InputRegister 14076 R ### NA Unit 14 Subcooling 2

InputRegister 14080 R ### NA Unit 14 Major Revision Number X X X

InputRegister 14081 R ### NA Unit 14 Minor Revision Number X X X

InputRegister 14082 R ### NA Unit 14 Bug Fixes X X X

InputRegister 14083 R ### NAUnit 14 How long the unit has been running in minutes

X X X

InputRegister 14084 R ## NA Unit 14 How many times unit has started X X X

InputRegister 14085 R ### NA Unit 14 How long the Fan is running in minutes X X

InputRegister 14086 R ## NA Unit 14 How many times Fan turned on X X

InputRegister 14087 R ### NA Unit 14 How long the Fan is running in minutes

InputRegister 14088 R ## NA Unit 14 How many times Fan turned on

InputRegister 14089 R ### NAUnit 14 How long the Blower is running in minutes

X X X

InputRegister 14090 R ## NA Unit 14 How many times Blower turned on X X

InputRegister 14091 R ### NAUnit 14 How long the Blower is running in minutes

Page 76: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 76 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

InputRegister 14092 R ## NA Unit 14 How many times Blower turned on

InputRegister 14093 R ### NA Unit 14 How long unit is running in Freecooling X X

InputRegister 14094 R ### NAUnit 14 How many times unit has been in Freecooling

X X

InputRegister 14095 R ### NA Unit 14 How long unit is running in Freecooling

InputRegister 14096 R ### NAUnit 14 How many times unit has been in Freecooling

InputRegister 14097 R ### NA Unit 14 How long unit is running in Cooling X X X

InputRegister 14098 R ### NA Unit 14 How many times unit has been in Cooling X X X

InputRegister 14099 R ### NA Unit 14 How long unit is running in Cooling X X

InputRegister 14100 R ### NA Unit 14 How many times unit has been in Cooling X X

InputRegister 14101 R ### NA Unit 14 How long unit is running in Cooling X

InputRegister 14102 R ### NA Unit 14 How many times unit has been in Cooling X

InputRegister 14103 R ### NA Unit 14 How long unit is running in Cooling

InputRegister 14104 R ### NA Unit 14 How many times unit has been in Cooling

InputRegister 14105 R ### NA Unit 14 How long unit is running in Heating X X X

InputRegister 14106 R ### NA Unit 14 How many times unit has been in Heating X X X

InputRegister 14107 R ### NA Unit 14 How long unit is running in Heating X X

InputRegister 14108 R ### NA Unit 14 How many times unit has been in Heating X X

InputRegister 14109 R ### NA Unit 14 How long unit is running in Heating

InputRegister 14110 R ### NA Unit 14 How many times unit has been in Heating

InputRegister 14111 R ### NA Unit 14 How long unit is running in Heating

InputRegister 14112 R ### NA Unit 14 How many times unit has been in Heating

InputRegister 14113 R ### 0-999999 Unit 14 life time in Hours (Update every Hour) X X X

InputRegister 14115 R ### 0-999999Unit 14 Blower 1 life time in Hours (Update every Hour)

X X

InputRegister 14117 R ### 0-999999Unit 14 Blower 2 life time in Hours (Update every Hour)

InputRegister 14119 R ### 0-999999Unit 14 Fan 1 life time in hours (Update every Hour)

X

InputRegister 14121 R ### 0-999999Unit 14 Fan 2 life time in hours (Update every Hour)

InputRegister 14123 R ### 0-999999Unit 14 Cooling 1 life time in hours (Update ever Hour)

X X

InputRegister 14125 R ### 0-999999Unit 14 Cooling 2 life time in hours (Update ever Hour)

X

InputRegister 14127 R ### 0-999999Unit 14 Cooling 3 life time in hours (Update ever Hour)

InputRegister 14129 R ### 0-999999Unit 14 Cooling 4 life time in hours (Update ever Hour)

InputRegister 14131 R ### 0-999999Unit 14 Heating 1 life time in hours (Update ever Hour)

X X

InputRegister 14133 R ### 0-999999Unit 14 Heating 2 life time in hours (Update ever Hour)

InputRegister 14135 R ### 0-999999Unit 14 Heating 3 life time in hours (Update ever Hour)

InputRegister 14137 R ### 0-999999Unit 14 Heating 4 life time in hours (Update ever Hour)

InputRegister 14139 R ### 0-999999Unit 14 FreeCooling 1 life time in hours (Update ever Hour)

X X

InputRegister 14141 R ### 0-999999Unit 14 FreeCooling 2 life time in hours (Update ever Hour)

InputRegister 14143 R ### 0-5Unit 14 Indicates what unit types are running on the network

X X X

Page 77: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 77 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

DiscreteInput 14500 R Off/On = 0/1 0-1Unit 14 Error in the number of retain memory writings Alarm

X X X

DiscreteInput 14501 R Off/On = 0/1 0-1 Unit 14 Error in retain memory writings Alarm X X X

DiscreteInput 14502 R Off/On = 0/1 0-1 Unit 14 Return Air Temperature Sensor Alarm X X X

DiscreteInput 14503 R Off/On = 0/1 0-1 Unit 14 High Return Air Temperature Alarm X X

DiscreteInput 14504 R Off/On = 0/1 0-1 Unit 14 Mixed Air Temperature Sensor Alarm X X

DiscreteInput 14505 R Off/On = 0/1 0-1 Unit 14 Mixed Air High Temperature Alarm X X

DiscreteInput 14506 R Off/On = 0/1 0-1 Unit 14 Mixed Air Low Temperature Alarm X X

DiscreteInput 14507 R Off/On = 0/1 0-1 Unit 14 Supply Air Temperature Sensor Alarm X X

DiscreteInput 14508 R Off/On = 0/1 0-1 Unit 14 High Supply Air Temperature Alarm X

DiscreteInput 14509 R Off/On = 0/1 0-1 Unit 14 Low Supply Air Temperature Alarm X

DiscreteInput 14510 R Off/On = 0/1 0-1 Unit 14 Outdoor Air Temperature Sensor Alarm X X X

DiscreteInput 14511 R Off/On = 0/1 0-1 Unit 14 Outdoor Air Humidity Sensor Alarm X X X

DiscreteInput 14512 R Off/On = 0/1 0-1 Unit 14 Dust Sensor Alarm X X

DiscreteInput 14513 R Off/On = 0/1 0-1 Unit 14 Dust Sensor High Dust Detection Alarm X X

DiscreteInput 14514 R Off/On = 0/1 0-1 Unit 14 Liquid Line Temp Sensor Alarm X X

DiscreteInput 14515 R Off/On = 0/1 0-1 Unit 14 Discharge Temp Sensor Alarm

DiscreteInput 14516 R Off/On = 0/1 0-1 Unit 14 Liquid Line Pressure Sensor Alarm X

DiscreteInput 14517 R Off/On = 0/1 0-1 Unit 14 Suction Temperature Sensor Alarm X X X

DiscreteInput 14518 R Off/On = 0/1 0-1 Unit 14 Suction Pressure Sensor Alarm X X X

DiscreteInput 14519 R Off/On = 0/1 0-1 Unit 14 Low Pressure Alarm X X X

DiscreteInput 14520 R Off/On = 0/1 0-1 Unit 14 High Pressure Alarm X X X

DiscreteInput 14521 R Off/On = 0/1 0-1 Unit 14 Damper 1 Failed to Open X X X

DiscreteInput 14522 R Off/On = 0/1 0-1 Unit 14 Damper 1 Failed to Close X X X

DiscreteInput 14523 R Off/On = 0/1 0-1 Unit 14 Freeze Temperature Sensor Alarm X X

DiscreteInput 14524 R Off/On = 0/1 0-1 Unit 14 Freeze Condition X X X

DiscreteInput 14525 R Off/On = 0/1 0-1 Unit 14 Blower Fail Alarm X X

DiscreteInput 14526 R Off/On = 0/1 0-1 Unit 14 Dirty Filter 1 Alarm X X X

DiscreteInput 14527 R Off/On = 0/1 0-1 Unit 14 Dirty Condenser Coil Alarm

DiscreteInput 14528 R Off/On = 0/1 0-1 Unit 14 Emergency Ventilation Mode Active Alarm X X X

DiscreteInput 14529 R Off/On = 0/1 0-1 Unit 14 Emergency Cooling Mode Active Alarm X X X

DiscreteInput 14530 R Off/On = 0/1 0-1Unit 14 Extreme High Return Temp Alarm (Heat Cutout) Alarm

X X X

DiscreteInput 14531 R Off/On = 0/1 0-1 Unit 14 Disable/Smoke Detector Alarm X X X

DiscreteInput 14532 R Off/On = 0/1 0-1 Unit 14 Power Loss Detected Alarm X

DiscreteInput 14533 R Off/On = 0/1 0-1 Unit 14 Low SuperHeat Alarm X X X

DiscreteInput 14534 R Off/On = 0/1 0-1 Unit 14 Low Evaporation Pressure Alarm X X X

DiscreteInput 14535 R Off/On = 0/1 0-1 Unit 14 High Evaporation Pressure Alarm X X X

DiscreteInput 14536 R Off/On = 0/1 0-1 Unit 14 High Condenser Temperature Alarm X X X

DiscreteInput 14537 R Off/On = 0/1 0-1 Unit 14 Low Suction pressure Alarm X X X

DiscreteInput 14538 R Off/On = 0/1 0-1 Unit 14 EEV motor error Alarm X X X

DiscreteInput 14539 R Off/On = 0/1 0-1 Unit 14 SelfTuning error Alarm X X X

DiscreteInput 14540 R Off/On = 0/1 0-1 Unit 14 Emergency close Alarm X X X

DiscreteInput 14541 R Off/On = 0/1 0-1 Unit 14 High Delta Temperature Alarm

DiscreteInput 14542 R Off/On = 0/1 0-1 Unit 14 High Delta Pressure Alarm

DiscreteInput 14543 R Off/On = 0/1 0-1 Unit 14 Range Error Alarm X X X

DiscreteInput 14544 R Off/On = 0/1 0-1 Unit 14 Service Position Percent Alarm X X X

DiscreteInput 14545 R Off/On = 0/1 0-1 Unit 14 Valve ID Alarm X X X

DiscreteInput 14546 R Off/On = 0/1 0-1 Unit 14 Return Air Temperature Sensor 2 Alarm X

DiscreteInput 14547 R Off/On = 0/1 0-1 Unit 14 High Return Air Temperature 2 Alarm X

Page 78: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 78 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

DiscreteInput 14548 R Off/On = 0/1 0-1 Unit 14 Mixed Air Temperature Sensor 2 Alarm X

DiscreteInput 14549 R Off/On = 0/1 0-1 Unit 14 Mixed Air High Temperature 2 Alarm

DiscreteInput 14550 R Off/On = 0/1 0-1 Unit 14 Mixed Air Low Temperature 2 Alarm

DiscreteInput 14551 R Off/On = 0/1 0-1 Unit 14 Supply Air Temperature Sensor 2 Alarm X

DiscreteInput 14552 R Off/On = 0/1 0-1 Unit 14 High Supply Air Temperature 2 Alarm

DiscreteInput 14553 R Off/On = 0/1 0-1 Unit 14 Low Supply Air Temperature 2 Alarm

DiscreteInput 14554 R Off/On = 0/1 0-1 Unit 14 Dust Sensor 2 Alarm

DiscreteInput 14555 R Off/On = 0/1 0-1 Unit 14 Dust Sensor High Dust Detection 2 Alarm

DiscreteInput 14556 R Off/On = 0/1 0-1 Unit 14 Liquid Line Temp Sensor 2 Alarm X

DiscreteInput 14557 R Off/On = 0/1 0-1 Unit 14 Liquid Line Pressure Sensor Alarm

DiscreteInput 14558 R Off/On = 0/1 0-1 Unit 14 Discharge Temp Sensor 2 Alarm

DiscreteInput 14559 R Off/On = 0/1 0-1 Unit 14 Discharge Pressure Sensor 2 Alarm X

DiscreteInput 14560 R Off/On = 0/1 0-1 Unit 14 Discharge Pressure Sensor 2 Alarm X

DiscreteInput 14561 R Off/On = 0/1 0-1 Unit 14 Suction Temperature Sensor 2 Alarm X

DiscreteInput 14562 R Off/On = 0/1 0-1 Unit 14 Suction Pressure Sensor 2 Alarm X

DiscreteInput 14563 R Off/On = 0/1 0-1 Unit 14 Low Pressure 2 Alarm X

DiscreteInput 14564 R Off/On = 0/1 0-1 Unit 14 High Pressure 2 Alarm X

DiscreteInput 14565 R Off/On = 0/1 0-1 Unit 14 Damper 2 Failed to Open X

DiscreteInput 14566 R Off/On = 0/1 0-1 Unit 14 Damper 2 Failed to Close X

DiscreteInput 14567 R Off/On = 0/1 0-1 Unit 14 Damper 3 Failed to Open X

DiscreteInput 14568 R Off/On = 0/1 0-1 Unit 14 Damper 3 Failed to Close X

DiscreteInput 14569 R Off/On = 0/1 0-1 Unit 14 Damper 4 Failed to Open

DiscreteInput 14570 R Off/On = 0/1 0-1 Unit 14 Damper 4 Failed to Close

DiscreteInput 14571 R Off/On = 0/1 0-1 Unit 14 Freeze Temperature Sensor Alarm X

DiscreteInput 14572 R Off/On = 0/1 0-1 Unit 14 Freeze Condition Alarm X

DiscreteInput 14573 R Off/On = 0/1 0-1 Unit 14 Blower Fail Alarm

DiscreteInput 14574 R Off/On = 0/1 0-1 Unit 14 Dirty Filter 2 Alarm

DiscreteInput 14575 R Off/On = 0/1 0-1 Unit 14 Dirty Filter 3 Alarm

DiscreteInput 14576 R Off/On = 0/1 0-1 Unit 14 Dirty Filter 4 Alarm

DiscreteInput 14577 R Off/On = 0/1 0-1 Unit 14 Dirty Condenser Coil 2 Alarm

DiscreteInput 14578 R Off/On = 0/1 0-1 Unit 14 Power Loss 2 Detected Alarm

DiscreteInput 14579 R Off/On = 0/1 0-1 Unit 14 Low SuperHeat 2 Alarm X

DiscreteInput 14580 R Off/On = 0/1 0-1 Unit 14 Low Evaporation Pressure 2 Alarm X

DiscreteInput 14581 R Off/On = 0/1 0-1 Unit 14 High Evaporation Pressure 2 Alarm X

DiscreteInput 14582 R Off/On = 0/1 0-1 Unit 14 High Condenser Temperature 2 Alarm X

DiscreteInput 14583 R Off/On = 0/1 0-1 Unit 14 Low Suction pressure 2 Alarm X

DiscreteInput 14584 R Off/On = 0/1 0-1 Unit 14 EEV motor 2 error Alarm X

DiscreteInput 14585 R Off/On = 0/1 0-1 Unit 14 SelfTuning 2 error Alarm X

DiscreteInput 14586 R Off/On = 0/1 0-1 Unit 14 Emergency close 2 Alarm X

DiscreteInput 14587 R Off/On = 0/1 0-1 Unit 14 High Delta Temperature 2 Alarm

DiscreteInput 14588 R Off/On = 0/1 0-1 Unit 14 High Delta Pressure 2 Alarm

DiscreteInput 14589 R Off/On = 0/1 0-1 Unit 14 Range Error 2 Alarm X

DiscreteInput 14590 R Off/On = 0/1 0-1 Unit 14 Service Position Percent 2 Alarm X

DiscreteInput 14591 R Off/On = 0/1 0-1 Unit 14 Valve ID 2 Alarm X

DiscreteInput 14592 R Off/On = 0/1 0-1 Unit 14 Th-Tune Device Offline Alarm X

DiscreteInput 14593 R Off/On = 0/1 0-1 Unit 14 Th-Tune Temperature Probe Alarm X

DiscreteInput 14594 R Off/On = 0/1 0-1 Unit 14 Th-Tune Humidity Probe Alarm X

DiscreteInput 14595 R Off/On = 0/1 0-1 Unit 14 Th-Tune Clock Board Alarm X

Page 79: 7960-791(D) (2020 02 - Bard HVAC - Delivering high performance heating and cooling ... › ... › TechDoc-PDF › 7960-791.pdf · 2020-02-10 · TEC FUSION-TEC MEGA-TEC Orphan Mode

Manual 7960-791DPage 79 of 79

Type Index R/W Off/On = 0/1 MIN/MAX Description LC6000 MULTI-TEC

WR FUSION-

TEC

MEGA-TEC

DiscreteInput 14596 R Off/On = 0/1 0-1 Unit 14 cpCOe Offline Alarm X

DiscreteInput 14597 R Off/On = 0/1 0-1 Unit 14 Blower 1 Offline Alarm X

DiscreteInput 14598 R Off/On = 0/1 0-1 Unit 14 Blower 1 Alarm X

DiscreteInput 14599 R Off/On = 0/1 0-1 Unit 14 Blower 2 Offline Alarm

DiscreteInput 14600 R Off/On = 0/1 0-1 Unit 14 Blower 2 Alarm

DiscreteInput 14601 R Off/On = 0/1 0-1 Unit 14 Condenser 1 Offline Alarm X

DiscreteInput 14602 R Off/On = 0/1 0-1 Unit 14 Condenser 1 Alarm X

DiscreteInput 14603 R Off/On = 0/1 0-1 Unit 14 Condenser 2 Offline Alarm

DiscreteInput 14604 R Off/On = 0/1 0-1 Unit 14 Condenser 2 Alarm

DiscreteInput 14605 R Off/On = 0/1 0-1 Unit 14 Low Return Air Temperature 1 Alarm X

DiscreteInput 14606 R Off/On = 0/1 0-1 Unit 14 Low Return Air Temperature 2 Alarm X

DiscreteInput 14607 R Off/On = 0/1 0-1 Unit 14 Panel Open Alarm X