7847i Internet Communication Module
Honeywell Proprietary
Honeywell.com
27847i
Agenda
• Introduction• Overview of the 7847i / 7847iE Communication Path• Features• Summary of connections• Before You Leave the Shop• Network Connectivity• Programming the Device• Registering the Device• Updating Code
Honeywell Proprietary
Honeywell.com
37847i
Introduction
The 7847i delivers highly secure, reliable, Internet communication of alarm data while the 7847i-E is suitable for enterprise private network applications using local LAN or point to point connections.
Honeywell Proprietary
Honeywell.com
47847i
Applications
• Banking Institutions• Jewelry Industry• Federal Government• Medical• Industrial• Residential
Honeywell Proprietary
Honeywell.com
57847i
Features
•Secure IP Reporting •Dialer Capture Ready •Universal Control Panel Compatibility •Full Contact ID or ADEMCO High Speed Reporting •Six Input Zones •Tamper Protected Enclosure •Remote Services Capability* •Network Friendly •Ease of installation •Upload/Download
Honeywell Proprietary
Honeywell.com
67847i
Wiring the 7847i/7847i-E
Wiring connections for ECP or 4204 modes
Wiring for ECP, 4204 and Two-4204 Modes
Connect the 7847i/7847i-E to a compatible Honeywell VISTA control panel's ECP terminals,in parallel with keypads and other peripheral devices
Honeywell Proprietary
Honeywell.com
77847i
Wiring the 7847i/7847i-E
Wiring a LynxR-I for ECP Mode
To trip the zone on the 7847i/7847i-E in V+ trigger mode, the positive triggering voltage fromthe control panel must be within 2.0V-14V.
Note:•Trigger levels above this range may cause permanent damage to the unit.•Trigger levels below this range result in unreliable operation.
To trip the zone on the 7847i/7847i-E in V- trigger mode, the negative triggering voltagemust be less than 1.0V.
Honeywell Proprietary
Honeywell.com
87847i
Wiring the 7847i/7847i-E
Wiring for Zone Trigger Mode
To trip the zone on the 7847i/7847i-E in V+ trigger mode, the positive triggering voltage from the control panel must be within 2.0V-14V.
Note:•Trigger levels above this range may cause permanent damage to the unit.•Trigger levels below this range result in unreliable operation.
To trip the zone on the 7847i/7847i-E in V- trigger mode, the negative triggering voltage must be less than 1.0V.
Honeywell Proprietary
Honeywell.com
97847i
Wiring the 7847i/7847i-E
Primary power for the 7847i/7847i-E is provided by the auxiliary power output of the control panel 9.6V –13.8V, typical, or other external power source.
Zone 1 Input to a LynxR Trigger Output
Zone 1 Input for EOL Supervised N.O./N.C. Triggers
Honeywell Proprietary
Honeywell.com
107847i
Select Programming Option
From AlarmNet Direct• If the device is already in
service go to:
• If the device is new, choose the appropriate selection:
Honeywell Proprietary
Honeywell.com
117847i
For A new account enter the following:
• Primary City ID• Primary CSID• Primary subscriber• Supervision rate• MAC ID• MAC CRC
Then select:• Enable remote services• Advanced programming
Enabling Remote Services
Remember to enable here if using Total Connect
Honeywell Proprietary
Honeywell.com
127847i
Edit Mode
• Status of the device is displayed.
• With Edit displayed in the Actions box Click GO.
Honeywell Proprietary
Honeywell.com
137847i
Select Operation ModeECP –– 4204 Emulation ––
2-4204s Emulation –– Zone
Select Options• Old Alarm Time• IP Fault Time• Fault Relay Normally On• Tamper Report• Use DHCP
– NIC IP Address– Subnet Mask– Gateway IP Address– DNS Server IP Address
• Enable Power Save
Select Mode and Options
Honeywell Proprietary
Honeywell.com
147847i
AlarmNet Direct Programming
ECP Mode• Enable Direct Wire Downloading
– Keypad Address
• Total Connect Features– Remote Access
– Keypad Address/Type
– Multimode
– Multimode Address
• Zone 6 and 7– EOLR, V+ or V-
– Invert Zone
– Zone Restore
– Zone Delay
Honeywell Proprietary
Honeywell.com
157847i
Zone Mode• Trip Inputs 1 or 2 w/Bell out
– Increases Trip Voltage to 5V for V+ mode
• Lynx Panic• Telco Zone• Open/Close Zone• Multimode
– Total Connect
• Trigger Type• Invert Zone• Zone Restore• Zone Delay• Zone Report On Arm
AlarmNet Direct Programming
Honeywell Proprietary
Honeywell.com
167847i
4204 Emulation Modes• Fault Relay Normally On• Telco Zone• Open/Close Zone• Enable Direct Wire Downloading
– Keypad Address
• Total Connect Feature– Remote Access
– Keypad Address/Type
– Set Multi Partition View
• Zone Restore• Zone Delay• Zone Report On Arm
– Zone 4 or Zone 8 Arms
AlarmNet Direct Programming
Honeywell Proprietary
Honeywell.com
177847i
If the device is powered and connected to the Internet:
• Save And Transfer Data to Device
If the device is not powered or connected to the Internet:
• Click “Save”• Click “Exit”
Return to Show Program Devices page.
AlarmNet Direct Programming
Honeywell Proprietary
Honeywell.com
187847i
7720 Programming Tool
•The device can also be programmed using a 7720P Programmer.
•This 7720P allows access to Useful Diagnostic Tools.
Honeywell Proprietary
Honeywell.com
197847i
7720P Programming
Enters programming mode.
If a password has been previously assigned, thisprompt appears.Enter a 4-digit password (0-9, A-F, N, S, T, X, Y).The next prompt appears.
NOTE: The central station can remotely block access to local device programming. If this has been done, the following prompt appears:
Strt Prog Mode?(Y/N)_
Enter Password
Program Device?(Y/N)_
Change Password?(Y/N)_
Access to ProgMode Denied
Honeywell Proprietary
Honeywell.com
207847i
Programming
In ECP mode, the 7847i/7847i-E communicates withthe panel as a Long Range Radio (LRR) device. Enterthe appropriate ECP device address. For controls, see the control panel’s Installation and Setup Guide.
Press the [space] key to scroll through the modes of operation. Press [ENTER] to select ECP mode.
• ECP• Zone Triggers• 4204 Emu• Two 4204s
Device Address(03)_
Device Mode(ECP)_
Honeywell Proprietary
Honeywell.com
217847i
Programming
Enter the 2-digit primary city ID, 01-99 (decimal).
Enter the 2-digit primary central station ID number, 01-FE (HEX).
Enter the 4-digit subscriber account number for the primary central station, 0001-9999 (decimal).
Applicable only if control supports Central Station #1and #2 Category Enable reporting for the LRR device(e.g., VISTA-128BP, FA1660C, etc.).
Enter the 2-digit secondary city ID, 01-99 (decimal).
Enter the 2-digit second central station's ID number,01-FE (HEX).
Enter the 4-digit subscriber account number for the second central station, 0001-9999.
Primary City ID?(??)_
Primary CS ID?(??)_
Primary Sub ID?(????)_
2ND City ID?(??)_
2ND CS ID?(??)_
2ND Sub ID?(????)_
2ND CS Y/N?(N)_
Honeywell Proprietary
Honeywell.com
227847i
Programming
Multi-Mode (email notification) is intended as a convenience for the user, and does not replace Central
Station reporting of critical events (alarms, troubles, etc.).
Select "4204 Sourced" to send up to four events or "2-4204 Sourced" to send eight events. Disable for normal alarm processing and go to Prompt21: "Primary City ID".
Device address must be unique fromthe normal LRR Device Address (Prompt 28), and the Keypad Address used for Remote Access or Direct Wire downloading.
Press [Y] to allow the end user to access their system via a website.
Remote Access Y/N(N)_
Multi Mode(Disabled)_
Multi Mode Addr(12)_
Honeywell Proprietary
Honeywell.com
237847i
Programming
Applies only to VISTA-128BP/250BP and FBP Series controls, and FA1600C and FA1700C Series controls.
Must be programmed if using either the Remote Access feature or Direct Wire downloading. Enter the appropriate device address.
24 Hours• 1 Hour• US UL Line (6 Min)• CN UL Line Lvl 3 (3 Min)• US UL Line (90 Sec)• CN UL Line Lvl 4 (90 Sec)• CN UL Line Lvl 5 (75 Sec)• None• 30 Day
The AlarmNet network must hear at least one supervisory message from the module during this supervision period; otherwise, AlarmNet notifies the central station that a communication failure has occurred.
Direct Wire Y/N(N)_
Keypad Address(28)_
Supervision(24 Hours)_
Honeywell Proprietary
Honeywell.com
247847i
Programming
Sets how long an undeliverable alarm is retried for delivery to the central station.
Enter the time delay (01-99) in minutes before the7847i/7847i-E notifies the control panel that there isloss of contact with the network.
The fault open collector output is normallyenergized to ground, and de-energizes (open circuit) in the event of a module fault.
Allows the Cover Tamper to be disabled/enabled.
UL NOTE: Must be 10 Minutes
Old Alarm Time(10 Minutes)_
IP Flt Time(60 mins)_
Flt Rel ON Y/N(N)_
Tamper Rpt Y/N(Y)_
Honeywell Proprietary
Honeywell.com
257847i
Programming Mode
Use DHCP Y/N(Y) _
NIC IP Address:255.255.255.255_
Gateway IP Addr:255.255.255.255_
Subnet Mask:255.255.255.255_
DNS Serv IP Addr:255.255.255.255_
If using DHCP the screens below will not be shown. It will skip to the “PWR Save Mode” question.
Honeywell Proprietary
Honeywell.com
267847i
Programming Mode
Enable Zn 6 (Y/N)(N)
Zn 6 Trigger Type(V+)
Restore Zn 6 Y/N(Y)
Invert Zn 6 (Y/N)(N)
Delay Zn 6 (secs)(00)
Repeat for zone 7 if required
V+ 2V to 13V Trips ZoneV- 0V Ground Trips ZoneEOLR Loss of 2k EOLR Trips
No - Normal Zone ActivationYes - Faulted Zone sends normal report. - Normal Zone sends alarm report.
Yes - Zone sends Restore report.No - Zone will not send Restore report.
• Zone can be Delayed from 1 to 15 seconds• Zone must remain faulted for the full extent of delay to send report.
Honeywell Proprietary
Honeywell.com
277847i
Programming Mode
Pwr Save Mode (Y/N)(Y) _
• When Power Save Mode is enabled, the Network Interface Card (NIC) powers up, Pings a Redir, and turn back off.
• This process takes about 3 seconds and the process repeats every 20 seconds.
• Some Routers may see this as being “under attack” and shut down the Port on the router.
Devices connected to routers that shut down the port may try using Static IP Addressing, before disabling the Power Save Mode feature. Power cycle the Router to reset the port, and determine if this was the problem.
NOTE: If this feature is disabled, the device will not meet the UL Requirement for Battery Backup. It will reduce the backup time to 18 hours.
Honeywell Proprietary
Honeywell.com
287847i
Updating RootFile \
DONEResetting………
Programming Mode
Create Password?Y/N
Exit Prog Mode?Y/N
Review? Y/N
Press Enter to Continue and Exit
Press Enter to Continue and Exit
Press Shift Y then Enter to Continue and Exit
Zone Mode Setup
Honeywell Proprietary
Honeywell.com
307847i
Programming Zone Mode
Lynx Panic Y/N(N)
With a LynxR/R-EN Panel, enable Lynx Panic • Temporal Pulse = Zone 1 Report
–FIRE
• Constant or Steady = Zone 2 Report–BURG
• Single 3 second Pulse = Zone 3 Report–Silent Panic, Medical, Duress
Always program Zone 1/2 as a negative trip (V-) and install a 2k EOLR across the zone input and ground.
Honeywell Proprietary
Honeywell.com
317847i
Programming Zone Mode
Enabling this option will change the required trip voltage on zones 1, 2 and 3, as described below.
• Positive Trip – Always enable for Positive Trip.– Disabled – 2V– Enabled – 5V
• Negative Trip– Disabled – 0V ground potential– Enabled – 0V to 5V will trip. Must be greater than 5V to be normal.
This field also affects the zone 3 input.
Trip Inputs 1 or 2 w/Bell Out (N)
Honeywell Proprietary
Honeywell.com
327847i
Programming Zone Mode
Enabling this option will cause the specified zone input to send the High Speed Telco Report to Central Station.
• Available for zones 3 through 7.• Telco Fault 5555 5155 6• Telco Restore 5555 5355 6
Telco Zone (0)
Honeywell Proprietary
Honeywell.com
337847i
Enabling this option will cause the specified zone to send a High Speed Open or Close report to central station, in the zone that was indicated.
Example uses zone 3 to indicate Open/Close
• Available for zones 3 through 7.• Arming 5545 5555 7 – Restore Report• Disarming 5525 5555 7 – Alarm Report
Note: If your trigger activates for Arming, you will need to enable INVERT for the zone. (Invert option will be discussed later.)
Programming Zone Mode
Open/Close Zone (0)
Honeywell Proprietary
Honeywell.com
347847i
Programming Zone Mode
• Enabling this option will cause the specified zone ONLY attempt to generate an email message via Total Connect Remote Services.
• When enabled, only device Supervisory Messages will be sent to Central Station, i.e. Low Batt, AC Loss, Swinger Suppression, etc. (Not Tamper)
NOTE: This option should only be enabled when using Remote Services and Alarm Reports are not desired to be received by Central Station.
Multi-mode (N)
Honeywell Proprietary
Honeywell.com
357847i
Programming Zone Mode
Zn x Trigger Type(V+)
Restore Zn x Y/N(Y)
Invert Zn x (Y/N)(N)
Delay Zn x (secs)(00)
V+ 2V to 13V Trips ZoneV- 0V Ground Trips ZoneEOLR Loss of 2k EOLR Trips
No - Normal Zone ActivationYes - Faulted Zone sends normal report. - Normal Zone sends alarm report.
Yes - Zone sends Restore report.No - Zone will not send Restore report.
• Zone can be Delayed from 1 to 15 seconds• Zone must remain faulted for the full extent of delay to send report.
Honeywell Proprietary
Honeywell.com
367847i
Exiting Program Mode Correctly
• NEVER disconnect the programmer while in program mode.• ALWAYS exit program mode AND leave the programmer
connected until the screen displays “DONE”.
If you didn’t exit correctly…
Plug the programmer back in and…• Press enter then exit as normal.
- or -• Power cycle the 7845GSM radio.
Honeywell Proprietary
Honeywell.com
377847i
Registering…
Shift
Registering…
RegistrationSuccessful
Honeywell Proprietary
Honeywell.com
387847i
Registering…PIN Replacement• When registering the GSM radio press
– Enter PIN
– Wait for acknowledgement
Registering…
PIN: _
RegistrationSUCCESS
Honeywell Proprietary
Honeywell.com
397847i
Status Codes
STATUS CODE DESCRIPTION
0000 Control Panel lost communication with panel
0880 7847i tamper detected (cover removed)
0005 7847i has lost contact with AlarmNet
000F 7847i is not registered; radio account not activated
0400 7847i Power On Reset
0C80 7847i Power On Reset & Tamper detected
0C8F 7847i Power On Reset, Tamper detected & Not Registered
The 7847i sends status messages to the control panel for tamper and network communication failures. When using Honeywell’s VISTA-10P, VISTA-15P, Vista 20P series control panels, the status is displayed on the control panel’s keypad as “Check 103 LRR” followed by a 4-digit code).
Honeywell Proprietary
Honeywell.com
407847i
Status Display LEDs
Honeywell Proprietary
Honeywell.com
417847i
Mode & Status LEDs
Press and hold the Mode & Status button to view.
The two Yellow LEDs indicate which mode the device is programmed in.
The first Green LED indicates the status of the Internet or Web connection.
Honeywell Proprietary
Honeywell.com
427847i
Network Connectivity LEDs
Honeywell Proprietary
Honeywell.com
437847i
Central Station Messages
7720P ProgrammerDiagnostic Commands
Honeywell Proprietary
Honeywell.com
457847i
Programmer Keyboard Commands
INTERNAL IP/GSMx.x.xx mm/dd/yy
MAC xxxxxxxxxxxxMAC CRC yyyy
[ A ]
[ B ]
Software Revision
MAC Address
Mon 01 Jan 200105:48:39 am
[ C ] GMT Time and Date
The 7720P Programmer is an invaluable tool for troubleshooting the device and network connection. Section 5 of the Installation
Instructions provides details of each command.
Honeywell Proprietary
Honeywell.com
467847i
Programmer Keyboard Commands
Physical LinkGood
NIC IP Addressxxx.xxx.xxx.xxx
Subnet Maskxxx.xxx.xxx.xxx
[ D ] Network Diagnostics Display
If using DHCP, this information is assigned by the Gateway/Router.
If not using DHCP, this information must match the information provided by the site Network Administrator.
[ * ] to go to Subnet Mask
[ * ] to go to NIC IP Address
[ * ] to go to Gateway IP Address
For more information on Network Diagnostics, see Section 6 of the Installation Instructions.
Gateway IP Addrxxx.xxx.xxx.xxx
[ * ] to go to DNS Server IP
Honeywell Proprietary
Honeywell.com
477847i
Programmer Keyboard Commands
Encryption TestAES Passed!
DHCPOK
DNS Serv IPxxx.xxx.xxx.xxx
[ * ] to go to DHCP Status
[ * ] to go to encryption test
If using DHCP, this information is assigned by the Gateway/Router.
If not using DHCP, this information must match the information provided by the site Network Administrator.
If using DHCP
Run Network Diagnostic Tests
Network Diagnostics Display Continued
[ F ] Testing GatewayRedir 1
Honeywell Proprietary
Honeywell.com
487847i
Programmer Keyboard CommandsECP 67 TmPB Flt xx 5 ++ OK
1234 67 TmPB Flt5555 xx 5 ++ OK
12345678 TmPB Flt5555555x 5 ++ OK
[ S ]Status Display for ECP Mode
Status Display for 4204 Emulation Mode
Status Display for 2-4204 Emulation Mode
[ * ] = next field, [BS] = previous field
[ * ] = next field, [BS] = previous field
Bat NLd: x.xxVBat Ld: x.xxV
Status Display for Zone Trigger Mode1234567 TmPB Flt5555555 5 ++ OK
Battery Voltage Status Display
[ * ] = next field, [BS] = previous field
[ * ] = next field, [BS] = previous field
[ * ] = next field, [BS] = previous field
Honeywell Proprietary
Honeywell.com
497847i
Programmer Keyboard CommandsECP 67 TmPB Flt xx 5 ++ OK
1234 67 TmPB Flt5555 xx 5 ++ OK
12345678 TmPB Flt5555555x 5 ++ OK
[ S ]Status Display for ECP Mode
Status Display for 4204 Emulation Mode
Status Display for 2-4204 Emulation Mode
[ * ] = next field, [BS] = previous field
[ * ] = next field, [BS] = previous field
Bat NLd: x.xxVBat Ld: x.xxV
Status Display for Zone Trigger Mode1234567 TmPB Flt5555555 5 ++ OK
Battery Voltage Status Display[ * ] = next field, [BS] = previous field
[ * ] = next field, [BS] = previous field
[ * ] = next field, [BS] = previous field
Honeywell Proprietary
Honeywell.com
507847i
Programmer Keyboard Commands
[ * ] = next field, [BS] = previous field
Reset CPU Y/N
[ T ]
[ X ] Reset the 7847i
Test Msg Sent Send Test Alarm
[ * ] = next field, [BS] = previous field
[ * ] = next field, [BS] = previous field
Battery ChargerOK
Line Voltagexx.xxV
Battery Charger Status Display
Line Voltage Status Display
[ S ] Continued
Honeywell Proprietary
Honeywell.com
517847i
Programmer Keyboard Commands
Force Server Update?Y/N
Cannot UploadTry Later!_
Force Upload of Configuration File[ 0 ]
Path for Data Transmission Not Available.
Note: If the Internet is not available or if the module cannot communicate with AlarmNet, the following screen will be displayed after entering this command.
http://www.security.honeywell.com/hsc/
and click on MyWebTech
User name: honeywell
Password: support99
Honeywell Security support email: [email protected]
AlarmNet Support (800) 222-6525