    S&C ELECTRIC COMPANYSpecialists in Electric Power Switching and Protection

    Instructions for Installation and Operation

    S&C Omni-Rupter SwitchesOutdoor DistributionOmni-Rupter Automated Switching SystemsUpright and Upright (Extra Mounting Pole Clearance) 14.4 kV and 25 kV

    Instruction Sheet 765-503August 16, 2004 2004

    Supersedes Instruction Sheet 765-503 dated 12-16-02

    Section Page Section Page

    INTRODUCTIONQualied Persons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2Read this Instruction Sheet . . . . . . . . . . . . . . . . . . . . . 2Retain this Instruction Sheet . . . . . . . . . . . . . . . . . . . . 2Proper Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

    SAFETY INFORMATIONUnderstanding Safety-Alert Messages . . . . . . . . . . . . 3Following Safety Instructions . . . . . . . . . . . . . . . . . . . 3Replacement Instructions and Labels. . . . . . . . . . . . . 3Location of Safety Labels . . . . . . . . . . . . . . . . . . . . . . 4

    SAFETY PRECAUTIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . 6INSPECTION AND HANDLING

    Packing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

    INSTALLATIONPole Drilling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

    Inserting Pole Mounting Hardware . . . . . . . . . . . . . . 9

    INSTALLATIONContinuedSwitch Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Installing Surge Arresters . . . . . . . . . . . . . . . . . . . . . 12Preparing Connector and Terminal Pad Surfaces . 12Dead-Ending Conductors . . . . . . . . . . . . . . . . . . . . . 13Connecting High-Voltage Conductors . . . . . . . . . . . 13

    Installing the Control Unit . . . . . . . . . . . . . . . . . . . . . 16Connecting the Control Cable . . . . . . . . . . . . . . . . . . 17Checking Operation . . . . . . . . . . . . . . . . . . . . . . . . . . 19Installing the Wildlife Protection Option . . . . . . . . . 20Before Starting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

    OPERATIONSwitch Energization . . . . . . . . . . . . . . . . . . . . . . . . . . 26Push Button Operation . . . . . . . . . . . . . . . . . . . . . . . 27Remote Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . 27Emergency Manual Operation . . . . . . . . . . . . . . . . . 28

    SPECIFICATIONSCatalog Number Description . . . . . . . . . . . . . . . . . . . 29

    TABLE OF CONTENTS

  • 8/9/2019 765-503 Manual Instalacion Omni Rupter

    2/30

    765-503 2

    Qualied Persons WARNINGThe equipment covered by this publication must be installed, operated, and maintainedby qualied persons who are knowledgeable in the installation, operation, and

    maintenance of overhead electric power distribution equipment along with associatedhazards. A qualied person is one who is trained and competent in:

    The skills and techniques necessary to distinguish exposed live parts from nonlive parts of electrica l equipment.

    The skills and techniques necessary to determine the proper approach distancescorresponding to the voltage to which the qualied person will be exposed.

    The proper use of the special precautionary techniques, personal protective equip-ment, insulating and shielding materials, and insulated tools for working on ornear exposed energized parts of electrical equipment.

    These instructions are intended only for such qualified persons. They are not intended to be a substitute for adequate training and exper ience in safety proceduresfor this type of equipment.

    Read thisInstruction Sheet

    Thoroughly and carefully read this instruction sheet before installing or operating yourS&C Omni-Rupter Automated Switching System. Familiarize yourself with SAFETYINFORMATION on pages 3 through 5.

    Retain thisInstruction Sheet

    This instruction sheet is a permanent part of your S&C Omni-Rupter AutomatedSwitching System. Designate a location where you can easily retrieve and refer to this

    publication.

    Proper Application CAUTIONThe equipment in this publication must be selected for a specic application. Theapplication must be within the ratings furnished for the equipment. Refer to S&CSpecication Bulletin 765 -31 for complete application information.

    Warranty The standard warranty contained in S&Cs standard conditions of sale, as set forth inPrice Sheet 150, is applicable to the S&C Omni-Rupter Automated Switching System.

    INTRODUCTION

  • 8/9/2019 765-503 Manual Instalacion Omni Rupter

    3/30

    765-5033

    SAFETY INFORMAT

    UnderstandingSafety-AlertMessages

    There are several types of safety-alert messages which may appear throughout thisinstruction sheet as well as on labels and tags attached to the Omni-Rupter AutomatedSwitching System. Familiarize yourself with these types of messages and the importanceof the various signal words, as explained below.

    DANGERDANGER identies the most serious and immediate hazards which will likely result in serious personal injury or death if instructions, including recommended

    precautions, are not followed.

    WARNINGWARNING identies hazards or unsafe practices which can result in serious

    persona l injury or death if instructions, including recommended precautions, arenot followed.

    CAUTIONCAUTION identies haza rds or unsafe practices which can result in minor personalinjury or product or property damage if instructions, including recommended

    precautions, are not followed.

    NOTICENOTICE identies important procedures or requirements that, if not followed, can result in product or property damage if instructions are not followed.

    Following SafetyInstructions

    If you do not understand any portion of this instruction sheet and need assistance, contact your nearest S&C Sa les Ofce or S&C Authorized Dis tributor, or call S&C Headquartersat (773) 338-1000, Monday through Friday between 8:30 AM and 5:00 PM Central StandardTime. (In Canada , call S&C Electr ic Canada Ltd. at (416) 249 -9171, Monday through Fridaybetween 8:00 AM and 5:00 PM Eastern Standard Time.)

    NOTICE

    Thoroughly and carefully read thisinstruction sheet before operating yourS&C Omni-Rupter Switch.

    ReplacementInstructions andLabels

    If you need additional copies of this instruction sheet, contact your nearest S&C SalesOfce, S&C Authorized Distributor; S&C Headquarters, or S&C Electric Canada Ltd.

    It is important that any missing, damaged, or faded labels on the equipment be replacedimmediately. Replacement labels are available by contacting your nearest S&C Sales Office,S&C Authorized Distributor, S&C Headquarters, or S&C Electric Canada Ltd.

  • 8/9/2019 765-503 Manual Instalacion Omni Rupter

    4/30

    765-503 4

    Location of Safety Labels

    SAFETY INFORMATION

    NOTICEDo not remove this liftingbracket until switch has beenlifted into place and bolteddown.

    G-4776R1

    Shorting blocks for sensor secondaries areshipped installed in switch connector. Removeshorting blocks before connecting control cable.Save shorting blocks and this cover for futureuse.G-6351

    NOTICE

    NOTICEBlade contacts are greaseless andself-lubricating. Do not applylubricant to the blade contacts.

    G-9041

    H

    CA

    B

    E

    F

    G

    D

    J

  • 8/9/2019 765-503 Manual Instalacion Omni Rupter

    5/30

    765-5035

    Reorder Information for Safety Labels

    Location Safety Alert Message Description Number

    A WARNING Stored-energy operator and switch contain fast-moving parts . . . G-6868

    B NOTICE For manual operation, pull ring using a hookstick G-6811

    C DANGER Electrocution HazardAlways consider parts live . . . G-6580-2

    D NOTICE Shorting blocks for sensor secondaries are shipped installed inswitch connector . . . G-6351

    E WARNINGElectrocution HazardSwitch and control unit enclosure must beinstalled and grounded only by qualified personnel . . . G-6815

    F WARNING Lifting instructions G-5928R3

    G NOTICE Do not remove this lifting bracket . . . G-4776R1H NOTICE Blade contacts are greaseless and self-lubrication . . . G-9041

    J NOTICE To avoid overloading the terminal pads . . . G-9094

    SAFETY INFORMAT

    This label is placed on both sides of switch base on opposite ends.

    Available only on switches equipped with sensors.

    This part is a tag which is to be removed and discarded after the switch is installed and adjusted.

  • 8/9/2019 765-503 Manual Instalacion Omni Rupter

    6/30

    765-503 6

    DANGER

    Omni-Rupter Switches operate at high voltage. Failure to observe the pre-cautions below will result in serious personal in jury or death.

    Some of these precautions may differ from company operating procedures andrules. Where a discrepancy exists, users should follow their companys operating

    procedures and rules.

    SAFETY PRECAUTIONS

    1. QUALIFIED PERSONS. Access to switches and con-trols must be restricted only to qualied persons. SeeQualied Persons on page 2.

    2. SAFETY PROCEDURES. Always follow safe operat-ing procedures and rules.

    3. PERSONAL PROTECTIVE EQUIPMENT. Alwaysuse suitable protective equipment such as rubbergloves, rubber mats, hard hats, safety glasses, and ashclothing in accordance with safe operating proceduresand rules.

    4. SAFETY LABELS AND TAGS. Do not remove orobscure any of the DANGER, WARNING, CAU-TION, or NOTICE labels and tags. Remove tags ONLYif instructed to do so.

    5. OPERATOR AND SWITCH. Stored energy operatorand switch contain fast-moving par ts that can severelyinjure ngers. Do not remove or disassemble operatorunless directed by S&C Electric Company.

    6. ENERGIZED COMPONENTS. Always consider all parts live unti l de- energized, tested, and grounded.

    7. GROUNDING. Before energization and at all times when energized,

    the switch base and control unit enclosure must be con-nected to suitable earth ground at the base of pole, inaccordance with information covered in this instructionsheet.

    The switch base ground must also be connected tothe system neutral. If the system neutral is not present,

    proper precautions must be taken to ensure that thelocal earth ground cannot be severed or removed.

    8. LOAD-INTERRUPTER SWITCH POSITION.c Always conrm the open/close position of load-inter-rupter switches by visually observing the position ofthe blades.

    c Switches may be energized from either side and withthe blades in any position.

    9. MAINTAINING PROPER CLEARANCE. Alwaysmaintain proper clearance from energized compo-nents.

  • 8/9/2019 765-503 Manual Instalacion Omni Rupter

    7/30

    765-5037

    INSPECTION AND HAND

    Packing The S&C Automated S&C Omni-Rupter Switch includes the following items:

    1. A three-pole group-operated integer style upright mounted Automated Omni-Rupter Switch,complete with interphase dr ive and stored-energy operator; factory-assembled on a singlebase.

    2. Hardware for lockout/tagout feature.

    3. Miscellaneous mounting hardware (less through-bolts) for securing the Automated Omni-Rupter switch to the utility pole.

    4. An ED drawing and wiring d iagrams for the Omni-Rupter Automated Switching Systemwill be found in a water-resistant envelope shipped with the switch. Study these drawingscarefully and check the parts lists to verify that a ll parts are at hand.

    Also included in the water -resistant envelope is a yellow card containing magnitude ratiosand phase-angle measurements for S&C Current Sensor and S&C Current/Voltage Sensors (ifapplicable). These values must be entered into the RTU instal led with the switch, if applicable,in order to offset unit-to -unit var iation in the sensors. Refer to the S&C instruction sheet pro-

    vided with the control unit for further details.

    Inspection Examine the shipment for external evidence of damage as soon after receipt as possible, preferably before removal from the carriers conveyance. Check the bill of lading to make surethat shipping skids, crates, and containers listed thereon are present.

    If there is visible loss and/or damage:

    1. Notify the delivering carrier immediately.

    2. Ask for a carrier inspection.

    3. Note condition of shipment on all copies of the delivery receipt.

    4. File a claim with the carrier.

    If concealed damage is discovered:

    1. Notify the delivering car rier within 15 days of receipt of shipment.

    2. Ask for a carrier inspection.3. File a claim with the carrier.

    Also noti fy S&C Electric Company in all instances of loss and/or damage.

  • 8/9/2019 765-503 Manual Instalacion Omni Rupter

    8/30

    765-503 8

    Handling

    CAUTION

    Do not lift the switch by rigging on the live parts or pole-unit bases, nor subject these par ts to undue stress from slings or fal llines. Misalignment of the contacts and theinterrupters may result.

    Switches are provided with two liftingbrackets, which are bolted to woodensupport members attached to the switchbase. Since the wooden supports are par t ofthe shipping skid, use care to avoid damagingthem during unpacking.

    Make sure that the switch is fully closed.

    Attach hoisting slings to the lift ing bracketsand take a light strain. Unbolt the wooden sup-

    ports from the skid. Then slowly and carefullyhoist the switch as shown in Figure 1. Use carewhen removing wooden supports and liftingbrackets to prevent damage to sensor cables(if applicable).

    The switch is shipped closed and the stored-energy operator is shipped discharged. It is notnecessary to pre-charge the stored-energyoperator before installation.

    INSPECTION AND HANDLING

    Wood support members attached to switch base(remove and discard after switch is mounted)

    Figure 1. Hoisting the Automated Omni- Rupter switch into position.

    Lifting brackets

  • 8/9/2019 765-503 Manual Instalacion Omni Rupter

    9/30

    765-5039

    INSTALLATION

    Pole Drilling

    Step 1Drill two -inch (17-mm) diameter holes in

    the front of the utility pole at the desired heightfor mounting the switch. See Figure 2. Refer tothe ED drawing. The centerline- to- centerlinedistance of the holes must be 14 inches (356mm).

    Inserting Pole MountingHardware

    Step 2Insert two -inch diameter through-bolts (notfurnished) in the holes drilled in Step 1. Securethese bolts loosely with necessary washers

    and nuts in such a manner that the heads ofthe bolts project sufciently, approximately3 inches (76 mm), from the face of the poleto engage the switch mounting bracket. SeeFigure 2.

    Note: When mounting the switch to a wood pole, it is recommended tha t suitable sizedsquare washers be placed under the nutsagainst the wood pole. The use of spring-typewashers between the square washers andnuts is also recommended to compensate forwood-pole shrinkage and thus maintain fas-tener tightness.

    Switch InstallationStep 3

    CAUTIONDo not lift the switch by rigging on thelive parts or pole-unit bases, nor subjectthese parts to undue stress from slings orfall lines. Misalignment of the contactsand the interrupters may result from suchhandling.

    Handle and lift the switch as described in theHandling section of this instruction sheet.When the switch is hoisted to its mountinglevel, guide the assembly so that the through -bolts projecting from the utility pole slip intothe holes in the switch mounting bracket.(The bracket is provided with a keyhole and

    Figure 2. Drilling holes for mounting switch.

    Through-bolts (provided by customer)

  • 8/9/2019 765-503 Manual Instalacion Omni Rupter

    10/30

    765-503 10

    INSTALLATION

    the switch slightly so that it bears on thethrough-bolts. Fully tighten the through-bolts,making sure that the at washer for each bolt isbetween the bolt head and the switch mounting

    bracket. See Figure 3.Step 4

    Secure the pole band (furnished) to themounting bracket on the switch, using the

    J- bolts provided. Two 1 3 stiffeningblocks are furnished to be used behind the

    pole- band anges, and underneath the J -boltnuts. Fully tighten the nuts. Fasten the poleband to the back side of the pole through thehole in the center of the band, using one of thethree -inch diameter lag screws provided.Then, fasten the mounting bracket to the poleusing the two remaining -inch lag screws as

    shown in Figure 3. After al l of the nuts and lag screws have

    been fully tightened, remove the lifting brack-ets and wood support members that were pro-

    vided to facilitate hoist ing of the switch. Ifdesired, a user-furnished crossarm brace maybe attached to the base. Mounting brackets forcrossarm braces must be specified separately.Consult your nearest S&C Sales Office.

    The operating mechanism is fully assembledand adjusted at the factory, thus no adjust-ments are required by the customer.

    NOTICEBlade contacts are greaseless and self-lubricating. DO NOT apply lubricant tothe blade contacts.

    Figure 3. Typical pole- band attachment detail.

    1 3 stiffening block

    d Second lag screw installed diagonally opposite on lower corner ofmounting bracket.

    -inch lag screw d

    Switch-base mounting bracket

    Pole band

    J-bolt

    Flat washerThrough-bolts(provided by customer)

  • 8/9/2019 765-503 Manual Instalacion Omni Rupter

    11/30

    765-50311

    INSTALLATIO

    Grounding

    Step 5Ground the switch by solidly connecting the

    end of a Number 2 AWG wire (or two Number6 AWG wires, or wires having an equivalentcross-sectional area) to the grounding point onthe switch mounting bracket. See Figure 4. Agrounding lug is to be user-furnished. Connectthe other ends of the wires to a su itable earthground at the base of the pole and bond themto the system neutral, if present.

    WARNINGBefore energization and at all times whenenergized, the Automated Omni-RupterSwitch base and control unit enclosure mustbe connected to a suitable earth ground atthe base of the pole and bonded to the systemneutral, if present, in accordance with thisinstruction sheet. Proper precautions mustbe taken to ensure that the local earthground cannot be severed or removed.Failure to observe these instructionscan result in serious personal injuryor death.

    NOTICEThe switch must be grounded to avoiddamage to the control unit, control cable,and switch and also to ensure voltage sensoraccuracy.

    Proper precautions must be taken toensure that the local earth ground cannotbe severed or removed.

    Figure 4. Grounding the switch.

    Groundingpoint

  • 8/9/2019 765-503 Manual Instalacion Omni Rupter

    12/30

    765-503 12

    Installing Surge Arresters

    Step 6Instal l surge arr esters (provided by others),

    if applicable, using the mounting provisions provided . See F igure 5. Each su rge ar resterbracket is provided with three -inch (14 -mm) diameter unthreaded holes. Mount thesurge arre ster using one of the unthreadedholes and connect the surge arre ster groundto one of the other holes. When properlyinsta lled and connected, the surge arrestersare grounded through the switch base. Aseparate ground wire can be run betweenthe arresters at the users discretion.

    Preparing Connector andTerminal Pad Surfaces

    Step 7Prior to installation of connectors to termina l

    pads, use the following procedure to preparetheir surfaces:

    a. Thoroughly wire-brush the current-transfersurfaces of each connector and immediatelyapply a liberal coating of electrical joint

    preparation compound to the brushedsurfaces. Avoid getting lubricant or jointcompound on the blade contacts.

    b. Wire-brush each sensor terminal pad, ifapplicable, and apply a coating of electrical

    joint preparation compound beforesecuring the connectors to the terminal

    pads. See Figure 6.

    c. Do not wire-brush hinge terminal pads. Apply a coating of electrical joint preparation compound to these pads beforesecuring the connectors to the terminal

    pads. See Figure 6.

    d. Prepare the conductors using established procedures before clamping them in their

    respective connectors.

    Figure 5. Installing surge arresters.

    Mounting provisions for surge arresters

    Figure 6. Preparing terminal pad surfaces.

    Sensor terminal pad Hinge terminal pad

    INSTALLATION

  • 8/9/2019 765-503 Manual Instalacion Omni Rupter

    13/30

    765-50313

    Dead-Ending ConductorsDead-ending provisions are standard on

    Automated Omni -Rupter sw itche s havingupright and upright (extra mounting pole

    clearance) configurations. When dead- endingto these brackets, extension-link assemblies are required. See Figure 7 :

    Maximum dead-end loading for S&C dead-ending brackets on switches with steel bases:

    a. 2000 pounds per conductor where pull- offforces are applied to only one side of theswitch.

    b. 8000 pounds per conductor where equal pull -off forces are applied to both sides ofthe switch.

    c. 1500 pounds per conductor for uprightswitches with extra mounting pole clear-ance where pull-off forces are applied toonly one side of the switch.

    Maximum dead-end loading for S&C dead-ending brackets on switches with insulatedbases:

    a. 750 pounds or 500 pounds per conductor,14.4-kV and 25 -kV respectively, where pull-off forces are applied to only one side ofthe switch, including upright switches withextra mounting pole clearance

    b. 8000 pounds per conductor for 14.4-kV and

    25-kV switches, where equal pull- off forcesare applied to both sides of the switch.

    Connecting High-VoltageConductors

    WARNINGConductors must be de-energized andgrounded in accordance with standard sys-tem operating practice. Failure to do socan result in serious injury or death.

    NOTICETo avoid overloading the terminal pads, S&Crecommends making the jumper connectionto the line conductor before securing jumperfasteners to the terminal pad.

    Extension-link assemblies can be provided by addingsufx -D to the catalog number of the switch, or equiva-lent user-furnished extension means may be used.

    Figure 7. Dead-ending brackets (triangular mounting configurationshown).

    Extension linkassemblies

    Dead-end-ing bracket

    INSTALLATIO

    Jumper

    Line conductor

  • 8/9/2019 765-503 Manual Instalacion Omni Rupter

    14/30

    765-503 14

    INSTALLATION

    Step 8The Omni-Rupter terminal pads are silver

    plated and do not require abrasive cleaningas a part of their preparation. Wipe any dirt

    or grease from the surface, and apply a thickcoating of Penetrox A or other appropriateconductor preparation compound. DO NOTwire-brush the terminal pads. Wire brushingmay scratch the plating.

    Step 9

    WARNINGUse care not to apply excessive load tothe terminal pads during installation of the

    jumper connector. Jumper connector mustbe in-line with and level to the terminal pad

    bolt holes before securing jumper fasten-ers to the terminal pad. Failure to attach

    jumpers properly can result in switchdamage, causing improper operationor arcing.

    When high-voltage conductors are to beconnected using aluminum-alloy connectors ,the following procedures should beemployed:

    a. Thoroughly wire-brush the current- transfersurfaces of each connector and immedi-ately apply a liberal coating of Penetrox

    A (available from Burndy Corporation) oranother appropriate conductor preparationcompound to the brushed surfaces.

    b. Prepare the conductors using established procedures and clamp them in their respec-tive connectors.

    For other types of connector, follow themanufacturers recommended preparation

    procedure before connecting to Omni -Rupterterminal pads.

    Mass anode type connectors, such as the CatalogNumber 5300 series offered by S&C, which have been des-ignated by the connector manufacturer as being suitablefor direct attachment to copper alloy terminal pads.

  • 8/9/2019 765-503 Manual Instalacion Omni Rupter

    15/30

    765-50315

    INSTALLATIO

    Step 10 At tach the ju mper co nne cto rs to th ei rrespective terminal pads using flexible-conductor connections. When attaching

    connectors to the Omni-Rupter terminal pads, the connectors should be parallel to theterminal pad. Attach and form the conductorsso that no significant loading pressure isapplied to the terminal pads. See Figure 8.

    Figure 8. Connect jumper connector parallel to terminal pad.

    Terminal pad

    ConnectorConductor

  • 8/9/2019 765-503 Manual Instalacion Omni Rupter

    16/30

    765-503 16

    Installing the Control Unit

    Step 11Prior to connecting the control cable and

    energizing the Omni-Rupter AutomatedSwitching System, instal l the control unit. Alsocomplete all user connections associated withthe control unit. Refer to the S&C ins tructionsheet furnished with the control unit.

    Ground the enclosure by solidly connectingone number 6 AWG wire (or wires of equivalentcross-sectional area) to the ground lug on theback of the enclosure. See Figure 9. Solidlyconnect the enclosure ground wire to theswitch ground wire(s).

    WARNINGBefore energization and at all times whenenergized, the Automated Omni-RupterSwitch base and control unit enclosure mustbe connected to a suitable earth ground atthe base of the pole and bonded to the systemneutral, if present, in accordance with thisinstruction sheet. Proper precautions mustbe taken to ensure that the local earthground cannot be severed or removed.Failure to observe these instructionscan result in serious personal injuryor death.

    Figure 9. Grounding the enclosure.

    INSTALLATION

    Grounding lug

  • 8/9/2019 765-503 Manual Instalacion Omni Rupter

    17/30

    765-50317

    Connecting the Control Cable

    Step 12Remove the control cable from its shipping

    carton. The control cable is congured withone male and one female plug.

    Locate the female receptacle on the bottomof the adapter housing and remove the dustcover. Remove the sensor shorting blocks fromthe receptacle and plug in the male end of thecontrol cable. Secure the connection with theconnector clips. Retain the dust cover andsensor shorting blocks for future use. SeeFigure 10.

    Step 13Locate the male receptacle on the back of thecontrol unit enclosure, remove the dust cover,and attach the female end of the control cable.Secure the plug with the connector clips. SeeFigure 11. Retain the dust cover for futureuse.

    Figure 10. Connecting the control cable to the switch.

    Figure 11. Connecting the control cable to the control unit enclosure.

    INSTALLATIO

    Adapter

    Connectorreceptacle(female)

    Connector plug(male)

    Control cable

    Connector clips

    Connector plug (female)

    Connector clips

    Receptacle (male)

    Control cable

  • 8/9/2019 765-503 Manual Instalacion Omni Rupter

    18/30

    765-503 18

    Step 14Form a drip loop in the control cable whereit attaches to the control unit. Maintain a9-inch (229-mm) minimum radius when

    bending the control cable at the drip loop andat the switch connection. Adjust the controlcable along the length of the utility pole andsecure the control cable to the utility poleusing suitable guards or clamps. Form a coilwith any excess control cable, maintaining a9- inch (229-mm) minimum radius, and secureto the utility pole. See Figure 12.

    Step 15 A stai nle ss - steel securi ty belt is includedfor padlocking the multi-pin connector atthe control unit. See Figure 13. Place thesecurity belt around the connector, betweenthe connector clips and the enclosure, andinsert a padlock (not furnished) through theholes provided.

    Figure 12. Connecting the control cable to the control unit enclosure.

    Figure 13. Securing the connector at the control unit.

    INSTALLATION

    Drip loop (maintain a 9-inch[229- mm] minimum radius whenbending the control cable)

    Padlock (provided by others)

    Security belt

  • 8/9/2019 765-503 Manual Instalacion Omni Rupter

    19/30

    765-50319

    INSTALLATIO

    Checking Operation

    Step 16Open and close the switch electrically by

    pushing the open /close push button insidethe switch control or sending a remote signalto the switch control. Check to be sure that thefollowing conditions exist:

    a. Open and close the switch electrically sev-eral times. (See Steps 24 and 25 on pages27 and 28 for electrical operating instruc-tions). The switch should operate rapidlyand without hesitation during both openingand closing operations.

    b. Operate the switch manually several timeswith a hookstick. (See Step 26 on pages 28and 29 for manual operating instructions).

    The switch should operate rapidly andwithout hesitation during both openingand closing operations.

    c. With the switch in the CLOSED position, allmain contacts of the interrupter switch arein the fully closed position, with no morethan a -inch gap between the blade andthe bumper stop. See Figure 14.

    d. With the switch in the OPEN position, theswitch blades are between 85 to 90 fromthe closed position.

    If blade adjustment is required, discon-

    nect control power to the switch control andloosen the hinge-end bolts that fasten the bladeassembly to its insulator and move the switchblade until it is in the fully closed position; thenretighten the bolts making sure the interrupterswitch remains in the fully closed position. Ifadjustment is required beyond that providedby movement of the switch blade assembly,loosen the two clamping bolts and set screwthat fasten the coupling to the interphase rodand rotate the switch blade until it is in the fullyclosed position. Re-tighten the clamping boltsand set screw, making sure the interrupterswitch remains in the fully closed position.(Tighten the 16 hardware 22 ft -lbs.) Recon-nect control power to the switch control.

    If full, rapid blade travel cannot be attainedby adjusting the blade, contact your nearestS&C Electric Sales Office.

    Figure 14. Check to see that there is no more than -inch gap betweenthe blade and bumper stop.

    Bumper stop

    Blade edge

  • 8/9/2019 765-503 Manual Instalacion Omni Rupter

    20/30

    765-503 20

    Installing the Wildlife ProtectionOption (Catalog NumberSuffix -W)

    WARNINGInstall the wildlife protection option whilethe Omni-Rupter switch is de-energized.If the switch is energized, ensure thatit is grounded and de-energized beforeattempting wildlife protection optioninstallation. Failure to do so could leadto serious injury or death.

    The wildlife protection option helps preventclimbing or perching animals from making

    pha se - to -grounded pa rt contact . See Fig-

    ure 15. A typical wildlife protection instal-lation includes:

    One base cover (two base covers on 25-kVswitches and switches with extra mount-ing-pole clearance). (Base covers arenot included on switches with insulatedbases)

    One adapter box cover Six wildlife disks One pole- saddle cover (not required when

    switch with extra mounting-pole clearanceis specied), pre-installed

    One berglass interphase operating rod, pre-instal led

    Figure 15. 14.4- kV Omni- Rupter with Optional Wildlife Protection (Catalog Number Suffix-W), Upright Mounting Configuration.

    Pole-saddle cover

    Wildlife disks

    Fiberglass interphaseoperating rod

    Base cover

    Wildlifedisks

    Adapter box cover

    INSTALLATION

  • 8/9/2019 765-503 Manual Instalacion Omni Rupter

    21/30

    765-50321

    CAUTIONS&C recommends installing the wildlife

    pr ot ec tion op tion afte r the sw it ch issecured to the utility pole. Damage to thewildlife disks and/or base covers is likelyto occur during lifting and installation ofthe switch.

    In Figure 15, a typical installation of the wildlife protection option is illustrated. The pole-saddlecover will be pre-installed at the factory, aswill the berglass interphase operating rod.Consult the RD drawing accompanying theswitch installation instructions for detailsspecic to your switch that may differ from theinstructions below. Following are instructionsfor a typical eld installation of the wildlife

    protection option.

    Step 17With the switch in the closed position, place thebase covers onto the steel base of the switchin the positions shown on the associated RDdrawing. If optional surge arrester mounting

    provisions (Cata log Number Sufx -A1 or-A2) have been specified for the switch,cutouts will be provided in the base covers tot around the arrester mounting brackets.

    Step 18Hook one end of the spring clip assembly intothe lip on the edge of one side of the basecover. See Figure 16. Bring the spring clipunderneath the switch base and stretch ituntil it can be hooked into the lip on the edgeof the opposite side of the base cover. Makesure the spring clip is at least one-half inchfrom the edge of the base cover. See Figure 17.Install the remaining short spring clips on theirrespective base covers in accordance with thesupplied RD drawing.

    Figure 16. Hook one end of spring clip into base cover lip. Stretchunderneath base and hook on opposite side.

    Figure 17. Make sure clips are installed -inch from edge of cover.

    -inch from edge

    Switch base

    Base cover

    Spring clip

    INSTALLATIO

  • 8/9/2019 765-503 Manual Instalacion Omni Rupter

    22/30

    765-503 22

    INSTALLATION

    Step 19Place the adapter box cover on the adapter boxas shown in Figure 18.

    Figure 18. Place cover on adapter box.

    Step 20Hook one end of the long spring clip assemblyinto the slot in the edge of one side of theadapter box cover. See Figure 19. Bring thespring clip underneath the switch base andstretch it until it can be hooked into the slot

    on the edge of the opposite side of the adapterbox cover. If necessary, feed the spring clipunderneath the sensor wiring.

    Do not compress the sensor wiring with thespring clip.

    Repeat on the opposite side with the otherlong spring clip.

    Figure 19. Hook long spring clip assembly around base.

    Spring clip

    Slot

    Sensor wire

    Adapter boxcover

    Omni-Mate

  • 8/9/2019 765-503 Manual Instalacion Omni Rupter

    23/30

    765-50323

    INSTALLATIO

    Step 21Hook the straight end of the front spring clipinto the slot in the front of the adapter boxcover. Hook the curved end of the front spring

    clip underneath the Omni-Mate mountingboss. See Figure 20.

    Repeat on the opposite side with the otherfront spring clip.

    Figure 20. Hook curved end under mounting boss.

    Spring clip(curved)

    Front springclip (straight)

    Mountingboss

  • 8/9/2019 765-503 Manual Instalacion Omni Rupter

    24/30

    765-503 24

    INSTALLATION

    Before StartingBefore install ing the wildlife disks, determinethe proper placement of the disks on the switchblade and contact insulators.

    On 14.4-kV Omni-Rupter Switches(Porcelain and Cypoxy Insulators)Instal l the wildlife disk to the bottom skirt rootof the insulator on both the blade and contactends of the switch. When the wildlife disksare properly installed, the disks will overlapslightly as shown in Figure 21.

    Figure 21. Wildlife disk placement on 14.4- kV Omni- Rupter Switches.

    Insulator

    Disks overlapblade end overcontact end

    Insulator

    Contactend

    Bladeend

    Bottomskirtroot

    Bottomskirtroot

    On 25-kV Omni-Rupter Switches(Porcelain and Cypoxy Insulators)Blade end of the switch: Install the wildlife diskon the bottom skirt root of the insulator.

    Contact end of the switch: Count up twoskirts from the base and install the wildlifedisk to the insulator. When the wildlife disksare installed properly, they will be at aproxi-mately the same height. See Figure 22.

    Figure 22. Wildlife disk placement on 25-kV Omni -Rupter Switches.

    Bladeend

    Bottomskirtroot

    Contactend

    Two skirtsfrom bottomskirt root

    Insulator InsulatorDisks same height

  • 8/9/2019 765-503 Manual Instalacion Omni Rupter

    25/30

    765-50325

    INSTALLATIO

    Step 22

    a. To assemble the disks, t the disk aroundthe insulator on the blade end of the switch.See Figure 23. Then, insert the lockingtabs of one-half of the disk into the openslot on the other half to create a secureoverlapping t. Repeat the procedure onthe opposite side of the disk. When thehalves are correctly assembled, the S&Clogo will be on top of the disk on both sides.See Figure 24.

    b. Starting with the outside locking tabs rst,squeeze the overlapping sides together untilthe tabs audibly snap into place.

    Figure 23. Fit the disk halves around the insulator.

    Figure 24. Snap lower tab into open slot.

    Figure 25. Push disk halves together. Snap upper tab into place.

    Insulator

    Snap tab into open slot

    Push disk halvestogether

    Upper locking tab

    Lower locking tab

    c. Push the two halves of the disk togetherin towards the insulator so that it ts theinsulator as close as possible. See Figure 25.Snap the upper locking tab rmly into place.Both tabs should protrude through the openslot as shown in Figure 24.

    d. Repeat a. through c. above to install thewildlife disks on the contact end of theswitch.

    Slot

  • 8/9/2019 765-503 Manual Instalacion Omni Rupter

    26/30

    765-503 26

    OPERATION

    Switch Energization

    WARNING

    Before energization and at all times whenenergized, the Automated Omni-RupterSwitch base and control unit enclosuremust be connected to a suitable earthground at the base of the pole and bondedto the system neutral, if present, in accor-dance with this instruction sheet. Proper

    precautions must be taken to ensure thatthe local earth ground cannot be severedor removed. Failure to observe theseinstructions can result in serious per-sonal injury or death.

    WARNINGThe stored-energy operator and theswitch contain fast-moving parts that canseverely injure fingers. Do not removeor disassemble operator unless directed byS&C Electric Company.

    Step 23 Af ter maki ng all user connections to thecontrol unit in accordance with the S&Cinstruction sheet covering the applicablecontrol unit, energize the Omni-Rupter

    Automated Switching Sys tem according tostandard operating practices. Conrm that theappropriate power and selector switches are inthe proper positions and that the appropriateLEDs are illuminated, as discussed in theinstruction sheet furnished with the controlunit.

    DANGER Automated Omni-Rupter Switches may beenergized from either side and with bladesin any position. Before inspecting, servic-ing, or repairing this switch or working onthe conductors on either side of the switch,test for voltage using proper high-volt-age test equipment. Then install suitablegrounding equipment. Failure to observethese precautions can result in seriouspersonal injury or death.

  • 8/9/2019 765-503 Manual Instalacion Omni Rupter

    27/30

  • 8/9/2019 765-503 Manual Instalacion Omni Rupter

    28/30

    765-503 28

    Emergency Manual Operation

    Step 26In the event of electrical power loss, a standard

    or extendible hookstick can be used to openand close the switch. If the spring is fullydischarged, pull on the pull-ring seven to ninetimes to effect a change of state. If the springhas been previously charged, just a single pullis required. Refer to Figure 27.

    Operate the pull-ring until the switch iseither fully open or fully closed. DO NOT

    par tially charge the opera tor (between oneand seven times).

    WARNING

    When operating manually, DO NOT leave the stored-energy operator partiallycharged. Ensure that the operator is ineither the fully charged or fully discharged

    position. A partially charged operatormay unexpectedly change state whencontrol power is applied.

    Figure 27. Operating the switch manually using a hookstick.

    OPERATION

    Pull-ring extended

  • 8/9/2019 765-503 Manual Instalacion Omni Rupter

    29/30

    765-50329

    Catalog Number DescriptionThe following tables list the basic catalognumbers and options for S&C AutomatedOmni-Rupter Switches. Please refer to Speci-cation Bulletin 765 -32 for details.

    S&C AUTOMATED OMNI-RUPTER SWITCHESThree-Pole Side-Break Integer Style, with steel bases 12

    Mounting Conguration

    Rating 3

    Catalog Number 89Net Wt., 3-Pole

    Assembly, Lbs. (kg)kV4 Amperes, RMS

    Nom. Max BIL Cont. 5Mom.

    (Asym.) 67

    Upright 0

    14.4

    25

    17.0

    29

    110

    150

    900

    900

    40 000

    40 000

    158412

    158413

    311 (141)

    320 (145)

    Upright 0(Extra Mounting Pole Clearance)

    14.4

    25

    17.0

    29

    110

    150

    900

    900

    40 000

    40 000

    158422

    158423

    320 (145)

    345 (157)

    Tiered Outboard 0

    14.4

    25

    17.0

    29

    110

    150

    900

    900

    40 000

    40 000

    158812

    158813

    297 (135)

    327 (148)

    1 Does not include control cable. Refer to the CONTROL CABLES tableon the following page to select appropriate cable.

    2 Switches shown do not include connectors.

    3 Ratings listed apply to switches with current/voltage sensors for use on60-Hz systems. Switches furnished with current/voltage sensors for use on50-Hz system have different ratings as li sted below.

    60-HzRating kV,

    Nom.

    50-Hz Ratings

    kV Amperes, RMS

    Min. Max BIL Continuous Interrupting

    14.4 14.4 17 110 900 900

    25 25 29 150 900 900

    4 Switches must be applied on effectively grounded systems at line-to-line voltages between 14.4 through 17.0 for 14.4-kV switches, and between25 through 29 for 25-kV switches.

    5 Automated Omni-Rupter switches rated 14.4 kV and 25 kV can carry upto 1000 amperes on a continuous basis for ambient temperatures to 40Cwith a minimum wind velocity of two feet per second. Emergency inter-rupting performance may be expected for currents to 1000 amperes.

    6 The 1-second rating is 25,000 amperes RMS symmetrical and the 3-sec-ond rating is 16,000 amperes RMS symmetrical.

    7 The two-time duty-cycle fault-closing rating for an automated Omni-Rupter switch is 20,000 amperes RMS symmetrical. The three-time

    duty-cycle fault-closing rating for these switches is 15,000 amperes RMSasymmetrical. The duty-cycle fault-closing rating denes the ability toclose the switch the specied number of times against a three-phase faultwith symmetrical current equal to the listed value, with the switch remain-ing operable and able to carry and interrupt rated continuous current.

    8 Catalog numbers shown include switch with stored-energy Omni-Mateoperator. A control unit (including 35-foot shielded control cable), sensors,and hinge side sensor mountings must be specied separately.

    9 Leakage distance is 14 inches for 14.4 kV and 24 inches for 25 kV.

    0 These switches include dead-ending brackets as standard. When dead-ending to these brackets, extension-link assemblies are required. Exten-sion-link assemblies can be provided by adding sufx -D to the catalognumber of the switch. Maximum dead-end loading: 2000 pounds per con-ductor where pull-off forces are applied to only one side of the switch;

    8000 points per conductor where equal pull-off forces are applied to bothsides of the switch except switches with extra mounting pole clearancefor which dead-end loading is limited to 1500 pounds per conductor where

    pull-off forces are applied to only one side of the switch).

    The loading from the jumpers shall not exceed 90 lbs. in line and 30 lbs. perpendicular to the terminal padper IEEE Standard ANSI C37.321996Section 8.8.2.2.

    Ice shields are included with all switches in the tired-outboard mount-ing conguration to ensure -inch ice-breaking capability. Ice shields arenot required for switches in upright-mounting congurations.

    SPECIFICATION

  • 8/9/2019 765-503 Manual Instalacion Omni Rupter

    30/30

    CONTROL CABLES

    ItemApplicable to

    MountingCongurations

    Sufx to be Addedto Switch

    Catalog Number

    Shielded Control Cable (35-foot [10.7 m] length is standard) 25-foot (7.6 m) length 35-foot (10.7 m) length 45-foot (13.7 m) length 75-foot (22.8 m) length 1

    100-foot (30.4 m) length 1

    All

    -C25-C35-C45-C75-C100

    Shielded Control Cable in Liquidite Flexible Metal-Wiring Conduit 25-foot (7.6 m) length 35-foot (10.7 m) length 45-foot (13.7 m) length 75-foot (22.8 m) length 1

    100-foot (30.4 m) length 1

    All

    -G25-G35-G45-G75-G100

    SENSORS AND SENSOR MOUNTINGS

    Item Description Rating, kVSufx to be

    Added to SwitchCatalog Number

    Current Sensors for use on 60-Hz and 50-Hz systems Three-Phase Current Sensing on jaw side of switch 214.4

    -I325

    Current/Voltage Sensors and mountings for use on60-Hz systems 1

    Three-Phase Current/Voltage Sensing on jaw side ofswitch 2

    14.4-E3

    25

    Three-Phase Current/Voltage Sensing on both jaw sideand hinge side of switch 34

    14.4-E33

    25

    Current/Voltage Sensors and mountings for use on50-Hz systems 1

    Three-Phase Current/Voltage Sensing on jaw side of

    switch2

    14.4-V3

    25Three-Phase Current/Voltage Sensing on both jaw sideand hinge side of switch 34

    14.4-V33

    25

    1 Three-phase current/voltage sensing is required for switches furnishedwith 5801 ASC if control power is to be furnished by the sensors.

    2 Includes mounting provisions for three surge arresters per switch.

    3 Includes mounting provisions for six surge arresters per switch.

    4 If Catalog Number Sufx -E33 or -V33 is specied, the maximumcontrol cable length is 45 feet.

    SPECIFICATIONS

    1 If Catalog Number Sufx -E33 or -V33 is specied, the maximumcontrol cable length is 45 feet.

    OPTIONAL FEATURES FOR AUTOMATED OMNI-RUPTER SWITCHES

    ItemApplicable to

    MountingCongurations

    Sufx to be Addedto Switch

    Catalog Number

    Mounting Provisions for three surge arresters per switch (used with the - I3, -E3, and -V3 options to providemounting provisions for a total of six surge arresters) 12

    All -A1

    Mounting Provisions for three surge arresters per switch (only for switches without sensors) 12 All -A2

    Extension-Link Assembly (one set of six) 3 All -D

    Lockout Handle All -L

    Wildlife ProtectionUpright, Upright with

    Extra Clearance-W

    1 Surge arrester mounting brackets designed for the Automated Omni-Rupter cannot be used on manually operated Omni-Rupter Switches.See Specication Bulletin 765 31 for mounting provisions for manual

    2 Mounting provisions for surge arresters are included on the side of theswitch (jaw, hinge, or both) on which the sensing options are mounted.