75444652 EMUA Solution for 3900 Series BTS

Embed Size (px)

Citation preview

  • 7/22/2019 75444652 EMUA Solution for 3900 Series BTS

    1/6

    EMUA Solution in 3900 Series SiteSecurity Level:

    Internal Open

    2009-06-19 HUAWEI Confidential Page1, Total6

    EMUA Solution for 3900 Series BTS

    00102313 Xiao Fei

    2009-6-101.Alarm Assignment: .....................................................................................................................1

    1.1Define EMUA alarms and port: .......................................................................................1

    1.2 Map BTS alarm to BSC alarm: .......................................................................................2

    2. Configure BSC Alarm: ...............................................................................................................3

    3. EMUA Board Configuration ......................................................................................................4

    3.1 Slot Number: .....................................................................................................................4

    3.2 Configure EMUA Board Attributes: ...............................................................................4

    3.3 Binding BTS alarm with BSC alarm:..............................................................................5

    Bind Alarm ..............................................................................................................................5

    4. Trouble Shooting .........................................................................................................................5

    In 3900 series BTS, UEIU/UPEU are used to provide environmental alarm connections,

    however, the total number of alarms of these 2 boards are only 16. If there are over 16 alarms to

    be connected, we could use EMUA board which can provide 32 Environmental Alarms.

    1. Alarm Assignment:1.1Define EMUA alarms and port:

  • 7/22/2019 75444652 EMUA Solution for 3900 Series BTS

    2/6

    EMUA Solution in 3900 Series SiteSecurity Level:

    Internal Open

    2009-06-19 HUAWEI Confidential Page2, Total6

    1.2 Map BTS alarm to BSC alarm:

    The Alarm ID arranges from 6292 to 6354.

    In BSC, the available BTS Custom Environment Alarm ID arrange from 65384 to 65533.

    For example:

    Monitoring

    Unit Port

    Port

    No.

    Alarm

    ID Alarm Name

    BSC

    Alarm

    ID Alarm Level

    S1+/S1- 1 6292 AC Main Alarm 65420 Major

    S2+/S2- 2 6294 DC High Voltage Alarm 65422 MajorS3+/S3- 3 6296 DC Low Voltage Alarm 65424 Warning

  • 7/22/2019 75444652 EMUA Solution for 3900 Series BTS

    3/6

    EMUA Solution in 3900 Series SiteSecurity Level:

    Internal Open

    2009-06-19 HUAWEI Confidential Page3, Total6

    S4+/S4- 4 6298 DC Module Alarm 65426 Major

    S5+/S5- 5 6300 65428

    S6+/S6- 6 6302 65430

    S7+/S7- 7 6304 65432

    S8+/S8- 8 6306 65434

    S9+/S9- 9 6308

    Low Voltage Load Disconnect

    Alarm 65436 Warning

    S10+/S10- 10 6310 65438

    S11+/S11- 11 6312 65440

    S12+/S12- 12 6314 65442

    S13+/S13- 13 6316 65444

    S14+/S14- 14 6318 65446

    S15+/S15- 15 6320 65448S16+/S16- 16 6322 65450

    S17+/S17- 17 6324 65452

    S18+/S18- 18 6326 65454

    S19+/S19- 19 6328 65456

    S20+/S20- 20 6330 65458

    S21+/S21- 21 6332 65460

    S22+/S22- 22 6334 65462

    S23+/S23- 23 6336 65464

    S24+/S24- 24 6338 65466

    S25+/S25- 25 6340 65468

    S26+/S26- 26 6342 65470

    S27+/S27- 27 6344 65472

    S28+/S28- 28 6346 65474

    S29+/S29- 29 6348 65476

    S30+/S30- 30 6350 65478

    S31+/S31- 31 6352 65480

    S32+/S32- 32 6354 65482

    2. Configure BSC Alarm:

    Method 1--Define on M2000 for all BSC

    Method 2 Define on BSC for each BSC

    NE Alarm Setting-Alarm Definition-Add

    Alarm Maintenance-Query Alarm Configuration

    Choose BSC, Change Alarm Name and Level

    Set Environment Aalrm Configuration

    Click "Apply"

  • 7/22/2019 75444652 EMUA Solution for 3900 Series BTS

    4/6

    EMUA Solution in 3900 Series SiteSecurity Level:

    Internal Open

    2009-06-19 HUAWEI Confidential Page4, Total6

    Board Configuration

    ard.

    UPEU MON0, the EMUA should be configured in slot0.

    .2 Configure EMUA Board Attributes:

    3. EMUA

    In BSC data, EMUA is configured as DEMU bo

    3.1 Slot Number:

    If we connect RS485 to

    If we connect RS485 to UPEU MON1, the EMUA should be configured in slot1.

    3

  • 7/22/2019 75444652 EMUA Solution for 3900 Series BTS

    5/6

    EMUA Solution in 3900 Series SiteSecurity Level:

    Internal Open

    2009-06-19 HUAWEI Confidential Page5, Total6

    In LMT:

    d Parameter Configuration Enabled: yes

    abled; chosen=disabled;

    ;(not chosen)

    High

    MM and: MOD DEMUBP.

    9 Boar9 Special Alarm Switch Enabled: not chosen=en9 Common Alarm Switch Enabled: not chosen=enabled; chosen=disabled9 Special Alarm Switch Valid Level Configuration: should be High Level9 Common Alarm Switch Valid Level Configuration: chosen= Low Level; not chosen=

    Level

    L Comm

    .3 Binding BTS alarm with BSC alarm:

    RT: SITENAME="OSV2", CN=0, SRN=2, SN=0, PN=1, SW=OPEN, AID=65420,

    E="PRAB", CN=0, SRN=2, SN=0, PN=2, SW=OPEN, AID=65422,

    E="PRAB", CN=0, SRN=2, SN=0, PN=3, SW=OPEN, AID=65424,

    E="PRAB", CN=0, SRN=2, SN=0, PN=4, SW=OPEN, AID=65426,

    E="PRAB", CN=0, SRN=2, SN=0, PN=9, SW=OPEN, AID=65436,

    rm, Board Type=70, Alarm ID: 6420.

    3

    Bind Alarm

    SET ALMPO

    PT=BOOL, AVOL=LOW;

    SET ALMPORT: SITENAM

    PT=BOOL, AVOL=LOW;

    SET ALMPORT: SITENAM

    PT=BOOL, AVOL=LOW;

    SET ALMPORT: SITENAM

    PT=BOOL, AVOL=LOW;

    SET ALMPORT: SITENAM

    PT=BOOL, AVOL=LOW;

    4. Trouble Shooting

    1. Board Communication Ala

  • 7/22/2019 75444652 EMUA Solution for 3900 Series BTS

    6/6

    EMUA Solution in 3900 Series SiteSecurity Level:

    Internal Open

    2009-06-19 HUAWEI Confidential Page6, Total6

    consistent with Physical Connection of MON Port.

    . Alarm report are opposite with actual alarm statusor is closed and vise versa.

    el.

    BBU fail to communicate with EMUA board, check:

    Power Input and DC Switch of EMUA;

    The data configuration of slot number is

    2

    For example, the door alarm report to BSC when the do

    Check: Alarm Switch Valid Level Configuration is consistent with actual voltage lev