7154 VFD 7154 VFD Presentation #3 Presentation #3 May 2002 May 2002 Paul Weingartner Paul Weingartner

7154 VFD Presentation #3 May 2002 Paul Weingartner

Embed Size (px)

Citation preview

Page 1: 7154 VFD Presentation #3 May 2002 Paul Weingartner

7154 VFD7154 VFDPresentation #3Presentation #3

May 2002May 2002

Paul WeingartnerPaul Weingartner

Page 2: 7154 VFD Presentation #3 May 2002 Paul Weingartner

Motor insulation infoMotor insulation info

The Ten Degree Rule indicates that a ten degree temperature increase cuts insulation life span approximately in half

and vice-versa.

Page 3: 7154 VFD Presentation #3 May 2002 Paul Weingartner

Insulation life spanInsulation life span

Page 4: 7154 VFD Presentation #3 May 2002 Paul Weingartner

Material taken fromMaterial taken from

Page 5: 7154 VFD Presentation #3 May 2002 Paul Weingartner

RC snubber circuitsRC snubber circuits

RC SnubbersRC SnubbersThe RC snubber is the simplest and lowest cost of The RC snubber is the simplest and lowest cost of methods employed. In its simplest form it consists of methods employed. In its simplest form it consists of resistors and capacitors configured as shown in Fig. 3.1. resistors and capacitors configured as shown in Fig. 3.1. The RC snubber is typically installed at the motor The RC snubber is typically installed at the motor terminals and acts as an impedance matching network. terminals and acts as an impedance matching network. The snubber components are carefully selected to cause The snubber components are carefully selected to cause the load impedance to match the characteristic the load impedance to match the characteristic impedance of the motor cables. When the motor surge impedance of the motor cables. When the motor surge impedance is equal to the line characteristic impedance, impedance is equal to the line characteristic impedance, then voltage reflection does not occur and excessive then voltage reflection does not occur and excessive voltage will not be experienced at the motor terminals.voltage will not be experienced at the motor terminals.

Page 6: 7154 VFD Presentation #3 May 2002 Paul Weingartner

RC snubber circuitRC snubber circuit

Page 7: 7154 VFD Presentation #3 May 2002 Paul Weingartner

Before and after waveformsBefore and after waveforms

Page 8: 7154 VFD Presentation #3 May 2002 Paul Weingartner

LC filtersLC filters

The LC filter combines a load reactor and a capacitor The LC filter combines a load reactor and a capacitor network to form a low pass filter as illustrated in Figure network to form a low pass filter as illustrated in Figure 4.1 . The basic concept is that the filter network has a 4.1 . The basic concept is that the filter network has a resonant frequency of approximately 1 to 1.5 kHz and resonant frequency of approximately 1 to 1.5 kHz and frequencies higher than that will be absorbed by the filter frequencies higher than that will be absorbed by the filter and not passed on to the motor. Of course it is important and not passed on to the motor. Of course it is important that the inverter switching frequency be set to 5khz to that the inverter switching frequency be set to 5khz to prevent excessive filter current and drive malfunction. In prevent excessive filter current and drive malfunction. In fact, it has been found that the performance of this basic fact, it has been found that the performance of this basic LC filter network, while very good at 5 kHz, actually LC filter network, while very good at 5 kHz, actually improves as the switching frequency is increased. improves as the switching frequency is increased.

Page 9: 7154 VFD Presentation #3 May 2002 Paul Weingartner

LC filter schematicLC filter schematic

Page 10: 7154 VFD Presentation #3 May 2002 Paul Weingartner

Before and after waveformsBefore and after waveforms

Page 11: 7154 VFD Presentation #3 May 2002 Paul Weingartner

Line reactor ratingsLine reactor ratings

Page 12: 7154 VFD Presentation #3 May 2002 Paul Weingartner

Line reactorsLine reactors

Page 13: 7154 VFD Presentation #3 May 2002 Paul Weingartner

Reactor specs (from MTE)Reactor specs (from MTE)Each variable frequency drive must be equipped with an input reactor offering noless than 4.5% effective impedance at rated motor amps (the fundamentalcurrent).They must be harmonic compensated and be UL-506 and UL-508 approved. Nema 1 enclosed units must be UL Listed. The continuous current rating of the reactor must be equal to or greater than the rms input current rating of the drive. Reactors must be copper wound with a UL class H (180 C) insulation system. They must be suitable for an ambient temperature of 45 C and a have a maximum temperature rise of 115 C. Their watts loss must be less than 1% of the rated load. Box lug type terminals must be provided on all reactors rated from 2 amps thru 400 amps. Higher current reactors may be supplied with copper tab type terminals. Reactor must be MTE Corporation type “RL” series.

Page 14: 7154 VFD Presentation #3 May 2002 Paul Weingartner

Motor efficiencyMotor efficiency

Because harmonic currents and frequencies cause Because harmonic currents and frequencies cause additional watts loss in both the copper windings and the additional watts loss in both the copper windings and the iron of a motor, the actual mechanical ability of the motor iron of a motor, the actual mechanical ability of the motor is reduced. These watts are expended as heat instead of is reduced. These watts are expended as heat instead of as mechanical power. When a harmonic compensated as mechanical power. When a harmonic compensated reactor is added to the VFD output, harmonics are reactor is added to the VFD output, harmonics are reduced, causing motor watts loss to be reduced. The reduced, causing motor watts loss to be reduced. The motor is able to deliver more power to the load at greater motor is able to deliver more power to the load at greater efficiency. Utility tests conducted on VFD's with and efficiency. Utility tests conducted on VFD's with and without output reactors have documented efficiency without output reactors have documented efficiency increases of as much as eight percent (at 75% load) increases of as much as eight percent (at 75% load) when the harmonic compensated reactors were used. when the harmonic compensated reactors were used. Even greater efficiency improvements are realized as the Even greater efficiency improvements are realized as the load is increased. load is increased.

Page 15: 7154 VFD Presentation #3 May 2002 Paul Weingartner

Motor noiseMotor noise

Because the carrier frequency and harmonic spectrum of many Because the carrier frequency and harmonic spectrum of many Pulse Width Modulated (PWM) drives is in the human audible Pulse Width Modulated (PWM) drives is in the human audible range, we can actually hear the higher frequencies in motors which range, we can actually hear the higher frequencies in motors which are being operated by these drives. A five percent impedance are being operated by these drives. A five percent impedance harmonic compensated reactor will virtually eliminate the higher harmonic compensated reactor will virtually eliminate the higher order harmonics (11th & up) and will substantially reduce the lower order harmonics (11th & up) and will substantially reduce the lower order harmonics (5th & 7th). By reducing these harmonics, the order harmonics (5th & 7th). By reducing these harmonics, the presence of higher frequencies is diminished and thus the audible presence of higher frequencies is diminished and thus the audible noise is reduced. Depending on motor size, load, speed, and noise is reduced. Depending on motor size, load, speed, and construction the audible noise can typically be reduced from 3 - 6 construction the audible noise can typically be reduced from 3 - 6 dB when a five percent impedance harmonic compensated reactor dB when a five percent impedance harmonic compensated reactor is installed on the output of a PWM drive. Because we humans hear is installed on the output of a PWM drive. Because we humans hear logarithmically, every 3dB cuts the noise in half to our ears. This logarithmically, every 3dB cuts the noise in half to our ears. This means the motor is quieter and the remaining noise will not travel as means the motor is quieter and the remaining noise will not travel as far. far.

Page 16: 7154 VFD Presentation #3 May 2002 Paul Weingartner

Info fromInfo from

Page 17: 7154 VFD Presentation #3 May 2002 Paul Weingartner

ANSI 519 CurrentANSI 519 Current

Page 18: 7154 VFD Presentation #3 May 2002 Paul Weingartner

ANSI 519 VoltageANSI 519 Voltage

Page 19: 7154 VFD Presentation #3 May 2002 Paul Weingartner

Sizing the reactorSizing the reactor

Page 20: 7154 VFD Presentation #3 May 2002 Paul Weingartner

What do they look like?What do they look like?

Page 21: 7154 VFD Presentation #3 May 2002 Paul Weingartner

VFD issuesVFD issues

Catching a spinning loadCatching a spinning load

V/Hz boost on big loadsV/Hz boost on big loads