18
Light sensitive switches Out of darkness comes light!

7. MG IC2000

Embed Size (px)

Citation preview

Page 1: 7. MG IC2000

Light sensitive switchesOut of darkness comes light!

Page 2: 7. MG IC2000
Page 3: 7. MG IC2000

�UT0003�_03-2007_EN

Presentation 2

Choicetable IC�00, IC200, IC2000, IC2000P+, IC Astro 4

Technicaldatas IC�00, IC200 5 IC2000 6IC2000P+ 8 IC Astro ��

ConnectionandcataloguenumberIC�00, IC200, IC2000 7 IC2000P+ 9 IC Astro �2

PracticaladviceIC2000P+ �0 IC Astro �3

DimensionsIC�00, IC200, IC2000, IC2000P+, IC Astro �4

Summary

Page 4: 7. MG IC2000

2

Light sensitive switches

UT0003�_03-2007_EN

IC light-sensitive switches automatically control lighting, roller blinds, etc. according to brightness and/or the time of the day.

Energy savingsWhatever the type of building or infrastructure, it is important nowadays to optimize your energy costs.With the IC light-sensitive switches range’s wide diversity and time and geographic programming, you can optimize your lighting and avoid pointless consumption.

Convenient useIC light-sensitive switches are used to manage and control lighting whenever and however you wish. Self-contained and automatic, they provide you with light, simply and at the right time.

Increased securityProtection against vandalism is provided by lighting up dark areas.

Lighting of public building

Public lighting

PresentationOut of darkness comes light!

Easy installationExtremely simple to implement and install, the switches fit all electrical and modular enclosures. IC 2000 is equipped with screw-less terminals for fast, easy connection.

Lighting of a car park

Page 5: 7. MG IC2000

3UT0003�_03-2007_EN

IC100Adjustable from 2 to �00 lux. It comes with a wall-mounted cell.

P83

235-

42

P83

237-

38

IC2000Adjustable from 2 to 2000 lux. It comes with a wall-mounted cell.

P93

585

P93

367

IC2000P+It has 3 customisable pre-set programs and 3 setting ranges from 2 to 2100 lux. Its 4 keys and large screen facilitate its programming. It comes with a wall-mounted cell.

P83

236-

40

P83

237-

38

IC AstroIt operates without photoelectric cell and calculates sunrise and sunset times according to its geographic position. it can be customised by using its programmation function.

PB

�002

07-4

0

DB

�092

�7

IC200Adjustable from 2 to 200 lux. It comes with a switchboard cell.

P94

774

Page 6: 7. MG IC2000

4

Light sensitive switches

UT0003�_03-2007_EN

IC100 IC200 IC2000 IC2000P+ ICAstroCataloguenumbers 15482 15284 CCT15368 15483 15223 15224Control by brightness detection b b b b Coupling with weekly programming b b b Control by calculation of sunrise/sunset times

b b

TechnicaldataVoltage (+�0 %, -�5 %) 230 V AC 230 V AC 230 V AC 230 V AC 230 V AC 230 V ACFrequency 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 HzAdjustable brightness threshold

2 to �00 lx 2 to 200 lx 2 to 2000 lx 2 to 50 lx 60 to 300 lx 350 to 2�00 lx

Consumption 6 VA 3 VA 6 VA 3 VA 4 VA 4 VASwitching capacity (cos j = �) �6 A �0 A �6 A �6 A �6 A �6 AMonitoring indicator light, not time delayed lit when brightness is less than the threshold

Red b Red

Contact switching indicator light Green GreenLCD liquid crystal display Back-lit Back-lit Back-litProgram saving by lithium battery b b b Operating reserve 5-6 years 6 years 6 yearsOperating temperature -20 to +50 °C -�0 to +50 °C -25 to +55 °C -20 to +50 °C -20 to +50 °C -20 to +50 °CSimplified leaflet incorporated in the “leaflet holder” slot under the swivel cover

b b b b b

Width (9 mm modules) 2 5 5 5 5 5� screw connection per pole for cables up to 6 mm²

b b b b b

2 screw-less connection per pole for cables up to 2.5 mm²

b

Mechanical compatibility with electrical distribution comb busbars

b

Cabling test function with a push-button on front face

b

Languages fr, gb, es, it, de, pt, se, dk/no, fi, nl

fr, gb, es, it, de, pt

fr, gb, se, dk/no, fi, nl

Delivered with wall-mounted cell cat. no. �5268

b b

Delivered with wall-mounted cell, cat. no. CCT�5268

b

Delivered with switchboard cell cat. no. �528�

b

CellchoicetableforsparepartsSparecell Cat.no.Switchboard cell, IP65 �528�Wall-mounted cell, IP54 ( compatible with all products) CCT�5268

ChoicetableIC�00, IC200, IC2000, IC2000P+, IC Astro

Switchboard cell cat. no. �528�

Wall-mounted cell cat. no. �5268

Wall-mounted cell cat. no. CCT�5268

P83

237-

38

DB

�092

�7

P93

585

Page 7: 7. MG IC2000

5UT0003�_03-2007_EN

TechnicaldataIC�00, IC200

FunctionThe light sensitive switch controls closing of a contact when brightness decreases and drops below the selected threshold. It controls opening of a contact when brightness increases and rises above the selected threshold.

TechnicaldataIC100b Adjustable brightness threshold: 2 to �00 lux.b Time delay: on closing: 20 s, on contact breaking: 80 s.b Contact opening: < 3 mm.b Insulation class: class II.b Degree of protection: IP20B.b Compatible with electrical distribution comb busbars.b Delivered with wall-mounted cell and its fixing device.b Contact rating: v �6 A under 250 V AC (cos j = �), v �0 A under 250 V AC (cos j = 0.6). b IC�00 load table:Typeoflighting Max.power230 V incandescent and halogen lamps 2300 WNon-corrected/ serial-corrected/ dual mounted fluorescent tubes with conventional ballast

2300 VA

Fluocompact lamps with conventional ballast �500 VA

Non-corrected/ serial-corrected mercury and sodium vapour lamps

�000 VA

Parallel-corrected mercury/ sodium vapour lamps and parallel-corrected fluorescent tubes with conventional ballast

400 VA

Fluorescent tubes/ dual mounted with electronic ballast 300 VAFluocompact lamps with electronic ballast 9 x 7 W, 7 x �� W, 7 x �5 W, 7 x 20 W,

7 x 23 W

IC200b Brightness threshold: adjustable from 2 to 200 lux.b Time delay on contact closing and breaking: ≥ 40 s.b Delivered with switchboard front face cell.b Contact rating: v �6 A under 250 V AC (cos j = �), v �0 A under 250 V AC (cos j = 0.6). b IC200 load table:Typeoflighting Max.power230 V incandescent, halogen lamps and fluocompact lamp with conventional ballast

2300 W

Non-corrected/ serial-corrected fluorescent tubeswith conventional ballast

46 x 36 W, 23 x 58 W, �4 x �00 W

Parallel-corrected fluorescent tubes with conventional ballast

�0 x 36 W, 6 x 58 W, 2 x �00 W

Dual-mounted fluorescent tubes with conventional ballast

�� x (2 x 58 W), 6 x (2 x �00 W)

Fluorescent tubes with electronic ballast 9 x 36 W, 7 x 58 WDual-mounted fluorescent tubes with electronic ballast 5 x (2 x 36 W), 4 x (2 x 58 W)Fluocompact lamps with electronic ballast 6 x 7 W, 8 x �� W, 6 x �5 W, 6 x 20 WParallel-corrected mercury and sodium vapour lamps 250 W

Wall-mountedcell-cat.no.15268(delivered with product and its fixing device)b Cell connection: by double insulation 2-conductor cable, not to be laid next to mains cables or water ducts, maximum length: 25 m for IC�00,b Degree of protection: IP54, IK05.b Operating temperature: -40°C to +70°C.

Switchboardcell(delivered with product and its fixing device)b Delivered with � m cable.b Degree of protection: IP65.b Operating temperature: -40°C to +70°C.

P83

235-

42

IC�00 Wall-mounted cell

IC200 Switchboard cell

P94

774

P83

237-

38

DB

�092

�7

Page 8: 7. MG IC2000

6

Light sensitive switches

UT0003�_03-2007_EN

FunctionThe light sensitive switch controls closing of a contact when brightness decreases and drops below the selected threshold. It controls opening of a contact when brightness increases and rises above the selected threshold.

Technicaldatab Adjustable brightness threshold: 2 to 2000 lx.b Time delay on contact closing and breaking: 60 s.b Cabling test function with a push-button on front face.b Contact opening: < 3 mm.b Insulation class: class II.b Degree of protection: IP20B.b Delivered with wall-mounted cell and its fixing device.b Contact rating: v �6 A under 250 V AC (cos j = �), v �0 A under 250 V AC (cos j = 0.6). b Load table:Typeoflighting Max.power230 V incandescent and halogen lamps 2300 WNon-corrected/ serial-corrected/ dual mounted fluorescent tubes with conventional ballast

2300 VA

Fluocompact lamps with conventional ballast �500 VANon-corrected/ serial-corrected mercury and sodium vapour lamps

�000 VA

Parallel-corrected mercury/ sodium vapour lamps and parallel-corrected fluorescent tubes with conventional ballast

400 VA

Fluorescent / dual-mounted fluorescent tubes with electronic ballast

300 VA

Fluocompact lamps with electronic ballast 9 x 7 W, 7 x �� W, 7 x �5 W, 7 x 20 W, 7 x 23 W

Wall-mountedcell,cat.no.CCT15268(delivered with product and its fixing device)b Cell connection: by double insulation 2-conductor cable, not to be laid next to mains cables or water ducts, maximum length: �00 m.b Horizontally orientable (90 °). b Degree of protection: IP54, IK05.b Operating temperature: -40°C to +70°C.

TechnicaldataIC2000

P93

367

IC2000

P93

585

Wall-mounted cell

Page 9: 7. MG IC2000

7UT0003�_03-2007_EN

ConnectionIC100,IC200,IC2000b Connection terminals: v � screw connection per pole for cables up to 6 mm² for IC�00 and IC200, v 2 screw-less connection per pole for cables up to 2.5 mm² for IC 2000.

IC�00 IC200 IC2000

IC100b To guarantee safety of people, it is essential to comply with positioning of the power supply (L and N terminal). Reversal of these two terminals is forbidden.b Determination of ratings according to the power of the load(s).v Power ≤ �6 A, Cos j = � (Fig. �).v Power > �6 A, Cos j = � (Fig. 2): you must relay with a contactor.

IC200,IC2000b Determination of ratings according to the power of the load(s). v Power ≤ �0 A, Cos j = 1 (fig. 3). v Power > �0 A, Cos j = 1 (fig. 4): you must relay with a contactor. b To facilitate threshold setting, mount the resistor (47 kW) supplied in place of the cell (terminals 3-5). Act on the threshold setting potentiometer until the red LED lights up.

CataloguenumbersType Cat.no.IC�00 15482IC200 15284IC2000 CCT15368

DB

�092

�2

DB

�092

�5

DB

�092

��

Fig.3

DB

�093

45

DB

�093

46

Fig.4

(1) Determination of ratings according to the power of the load(s).

DB

�090

03

Fig.2

DB

�090

02

Fig.�

ConnectionandcataloguenumberIC�00, IC200, IC2000

Page 10: 7. MG IC2000

8

Light sensitive switches

UT0003�_03-2007_EN

FunctionThe IC2000P+ controls lighting according to brightness and time. If brightness drops below the set threshold (light sensitive function: IC) and if the time program allows relay closing (time switch function), then the lighting circuit is activated.

DescriptionThe IC2000P+ uses its time programming to define lighting On and Off periods:b According to three pre-set time programs:v “DAYPROG”: On time programming from 7 am to 8 pm a validation of the IC function from 7 am to 8 pm,v “NIGHTPROG”: On time programming from 5 am to 8 am and from 6 pm to �� pm a validation of the IC function on these two operating periods,v “EMPTYPROG”: Off time programming throughout the day a no validation of the IC function. These programs can be modified if necessary.b According to a customised operating period, with possibility of copying to the other days.It is equipped with the following functions:v consideration of periods of absence (holidays),v temporary or permanent On or Off override,v remote control of lighting override by NO external contact,v consideration of change to “summer/winter” time, automatic or manual,v permanent liquid crystal display: of time and minutes, of day of the week, of the contact output status and current program.

Technicaldatab Adjustable brightness threshold over 3 ranges: v range �: 2 to 50 lx, v range 2: 60 to 300 lx, v range 3: 350 to 2�00 lx. b Time delay on contact closing and breaking: separate setting between 20 s and �40 s (80 s by default). b Contact: potential free. b Time base: quartz. b Operating accuracy: < ± � s / day at 20°C. b Number of separate switching operations: 42. b Minimum switching: � min. b Switching accuracy: � s. b Insulation class: class II. b Degree of protection: IP20B. b Contact rating: v �6 A under 250 V AC (cos j = �), v �0 A under 250 V AC (cos j = 0.6). b Load table:Typeoflighting Max.power230 V incandescent and halogen lamps 2300 WNon corrected/serial corrected fluorescent tubeswith conventional ballast

26 x 36 W, 20 x 58 W, �0 x �00 W

Parallel corrected fluorescent tubes with conventional ballast

�0 x 36 W, 6 x 58 W, 2 x �00 W

Dual-mounted fluorescent tubes with conventional ballast

�0 x (2 x 58 W), 5 x (2 x �00 W)

Fluorescent tubes with electronic ballast 9 x 36 W, 6 x 58 WDual-mounted fluorescent tubes with electronic ballast 5 x (2 x 36 W), 3 x (2 x 58 W)Fluocompact lamps with electronic ballast 9 x 7 W, 7 x �� W, 7 x �5 W, 7 x 20 WParallel-corrected mercury and sodium vapour lamps 250 W

Wall-mountedcell(delivered with product and its fixing device)b Photoresistance, connection by 2-wire cable, �00 m max. Do not install parallel to mains cables.b Degree of protection: IP54, IK05.b Operating temperature: -40°C to +70°C.Externalinputb Voltage: 230 V AC, +�0 %, -�5 %. b Frequency: 50/60 Hz. b Input current: max. 2.5 mA. b Consumption: max. 0.4 mW. b Cable length: max. �00 m.

TechnicaldataIC2000P+

P83

236-

40

P83

237-

38

IC2000P+

Wall-mounted cell

Page 11: 7. MG IC2000

9UT0003�_03-2007_EN

Connectionb Connection terminals: � screw connection per pole for cables up to 6 mm² .

CataloguenumbersType Cat.no.IC2000P+ �5483

DB

�092

�3

On override external contact

ConnectionandcataloguenumberIC2000P+

Page 12: 7. MG IC2000

�0

Light sensitive switches

UT0003�_03-2007_EN

1

0

14h 23h

0

DB

�092

22Fig. �

DB

�090

7�

Fig. 2

Time switch function

ThresholdBrightness

IC2000P+ output

ON override external contact

Applicationexample(Fig. �)Lighting of a shop window, in the evening, at a time variable according to brightness and switch-off at a set time (e.g. �� pm). Then in the morning, lighting at a set time (e.g. 4 am) and switch-off at a time variable according to brightness.

ConfigurationThis consists of recording in the memory:b The languageb The year, month, day and timeb One of the 3 pre-set programs:v “DAYPROG”: “On” time programming from 7 am to 8 pm a validation of the IC function from 7 am to 8 pm,v “NIGHTPROG”: “On” time programming from 5 am to 8 am and from 6 pm to �� pm a validation of the IC function on these two operating periods,“EMPTYPROG”: “Off” time programming throughout the day a no validation of the IC function. These programs can be modified.b The brightness threshold. Once this phase is over, your IC2000P+ operates in AUTO mode according to the items you have chosen.

ProgrammingTheIC2000P+isusedtomanagetimeprograms.Itallows:b Creation of a new program with the possibility of copying to the other days,b Viewing programs in memory,b Modification of a program in memory, of the time, date, summer/winter time,b Partial or total deletion of the program (date, time and language are kept),b Modification of the brightness threshold,b Separate setting of the time delay on switch-on and switch-off.

MovetoOn/Offoverride (Fig. 3)b Press briefly (< 2 s) and simultaneously the 2 keys “-”, “+” (value setting and navigation keys) on the front face to move to “MAN ON” or “MAN OFF”.b Press the keys for more than 2 s to move to “PERM ON” or “PERM OFF”.b Supply of terminal 1 overrides the IC2000P+ output to the “On” position. This external override takes priority over the product On/Off override function.

Fig. 3

1

0

1

0

1

0

1

0

1

0 1

L

DB

�090

72

External input (On override)

Time switch function

BrightnessThreshold

IC function

IC2000P+ output

IC2000P+ output

PracticleadvicesIC2000P+

Page 13: 7. MG IC2000

��UT0003�_03-2007_EN

TechnicaldataIC Astro

PB

�002

07-4

0 FunctionThe IC Astro astronomic programmable light sensitive switch is used to start and stop an electric load (e.g. lighting) according to sunrise and sunset times, without a brightness detector.Sunrise and sunset times are calculated automatically by the IC Astro according to the geographic parameters configured by the user.

DescriptionThe IC Astro is configured according to the place of installation.b The place of installation of the IC Astro can be configured:v either by selecting a country and a town,v or by its geographic coordinates (latitude, longitude).b The IC Astro allows:v addition or deletion of a switch-off/switch-on switching operation (Off-On) between the sunset and sunrise times,v different programmes each day,v difference in sunset and/or sunrise times, adjustable separately by ± �20 min. according to local constraints (mountains, buildings, etc.),v consideration of periods of absence (holidays), remote control of lighting override by a NO contact,v re-initialisation of programmes,v automatic switching to “summer-winter” time,v permanent display by liquid crystals: hours and minutes, day of the week, contact output status, and current programme,v manual waiver of the lighting On/Off programme, permanently or temporarily (up to the next switching operation).

Technicaldatab Memory: �4 switching operations (not including sunrise/sunset).b Minimum time between 2 switching operations: � min..b Switching accuracy: � s.b Time accuracy: ± � s /day.b Programming longitude: -�80° (East) to +�80° (West) in steps of �°.b Programming latitude: -90° (South) to +90° (North) in steps of �°.b Operating temperature: -20°C to +50°C.b Degree of protection: IP 20B.b Consumption: override input: < 0.5 mA.b Contact rating: v �6 A under 250 V AC (cos j = �), v �0 A under 250 V AC (cos j = 0.6). b Load table:Typeoflighting Max.power230 V incandescent and halogen lamps 2300 WNon-corrected/ serial-corrected fluorescent tubeswith conventional ballast

26 x 36 W, 20 x 58 W, �0 x �00 W

Parallel corrected fluorescent tubes with conventional ballast

�0 x 36 W, 6 x 58 W, 2 x �00 W

Dual-mounted fluorescent tubes with conventional ballast

�0 x (2 x 58 W), 5 x (2 x �00 W)

Fluorescent tubes with electronic ballast 9 x 36 W, 6 x 58 WDual-mounted fluorescent tubes with electronic ballast

5 x (2 x 36 W), 3 x (2 x 58 W)

Fluocompact lamps with electronic ballast 9 x 7 W, 7 x �� W, 7 x �5 W, 7 x 20 WParallel-corrected mercury and sodium vapour lamps 250 W

IC Astro

Page 14: 7. MG IC2000

�2

Light sensitive switches

UT0003�_03-2007_EN

Connectionb Connection terminals: � screw connection per pole for cables up to 6 mm².

CataloguenumbersType Languages Cat.no.

IC Astro fr, gb, es, it, de, pt �5223fr, gb, se, dk/no, fi, nl �5224

DB

�092

�4

ConnectionandcataloguenumberIC Astro

On override external contact

Page 15: 7. MG IC2000

�3UT0003�_03-2007_EN

ConfigurationThis consists of writing in the memory:b The languageb The place of installation, either:v by its position (Argentina, China, etc.) and by the closest town,v by its geographic coordinates (latitude, longitude, time difference with respect to GMT) (a map is provided with the product).b The year, month, day and time.

Once this phase is complete, your IC Astro will calculate the sunrise and sunset times and propose a default programme (operation from sunset to sunrise), for example:

Paris, 20th June, sunset �0 pm and sunrise 6 am.

ProgramminganOffperiodThe IC Astro offers the possibility of adding an “Off” period (programmed switch-off and switch-on) inside the programme, between the sunrise and sunset times (by default it is proposed from �� pm to 5 am), for example:

Modifying programming and configurationThe light sensitive switch allows:b Creation of a new customised programme with possibility of copying onto the other days,b Display of programmes in memory,b Deletion, modification or addition of an automatic or programmed switching operation, b Partial or total deletion of the programme (date, time and language are kept),b Modification of time, date, summer/winter time,b Temporary cancellation of the “On” periods by configuring start and end dates and Times of absence (holidays),b Adjustment of difference in sunset and/or sunrise times by ± �20 min. according to local constraints (mountains, buildings, etc.), for example:

MovetoOn/Offoverrideb Briefly press (< 2s) at the same time on the 2 keys “-”, “+”: (value setting and navigation keys) on the front face to move to “ON TEMP” or “OFF TEMP”.b Hold down (> 2s) the keys to move to “ON PERM” or “OFF PERM”.b The supply of input 5 forces the IC Astro output to the “ON” position. This override takes priority over the product On/Off override function.

DB

�000

48

PracticleadvicesIC Astro

DB

�000

50

DB

�000

5�

DB

�026

5�

DB

�000

49

Page 16: 7. MG IC2000

�4

Light sensitive switches

UT0003�_03-2007_EN

DimensionsIC�00, IC200, IC2000, IC2000P+, IC Astro

Fixed externally in vertical position by 2 ø 4 mm screws

135-0601

Switchboardcell

135-0601

Wall-mountedcell,cat.no.15268 Wall-mountedcell,cat.no.CCT15268

94

3643.5

ø9

20ø9

Ø9

25

P93

868

015-0400

IC200

P93

87�

054-0601

IC100

P93

870

187-1003

IC2000P+,ICAstro

P93

873

P93

872IC2000

E�5

639-

BE

�564

0-B

�35-060�

Page 17: 7. MG IC2000
Page 18: 7. MG IC2000

Schneider Electric Industries SAS89, boulevard Franklin RooseveltF-92506 Rueil-Malmaison CedexTel: +33 (0)� 4� 29 85 00www.schneider-electric.com

As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication.

Publishing: Schneider Electric Industries SASDesign:Printing:

This document has been printed on ecological paper

UT0

003�

_EN

© S

chne

ider

Ele

ctric

Indu

strie

s S

AS

All

right

s re

serv

ed

03-2007Art. xxxxx