3
-RE 1DPH /RFDWLRQ 3XUFKDVHU (QJLQHHU 6XEPLWWHG WR 5HIHUHQFH $SSURYDO &RQVWUXFWLRQ 8QLW 'HVLJQDWLRQ 6FKHGXOH 68%0,77$/ 3DJH RI 3 1RPLQDO FRROLQJ FDSDFLWLHV DUH EDVHG RQ ,QGRRU WHPSHUDWXUH ͼ) '% ͼ) :% 2XWGRRU WHPSHUDWXUH ͼ) '% ͼ) :% 1RPLQDO KHDWLQJ FDSDFLWLHV DUH EDVHG RQ ,QGRRU WHPSHUDWXUH H FD. 82H YD0 Qwvfqqt vgorgtcvwtg< 69H FD. 65H YD0 AM030KN4DCH/AA Samsung DVM S Series, 360 Cassette yyy0SamsungHVAC0eqm Shown with PC4NUNMUN (open type panel) Shown with PC4NUDMUN (ceiling type panel) Samsung HVAC ockpvckpu c rqnke{ qh qpiqkpi fgxgnqrogpv. urgekhkecvkqpu ctg uwdlgev vq ejcpig ykvjqwv pqvkeg0 © 2019 Samsung HVAC SHA-DVMS-03122019 General Information The indoor unit shall be compatible with Samsung DVM S and DVM Eco systems (AM****X*****AA). The indoor unit shall be a round ceiling cassette with 360°, even air distribution Auto-restart after power loss The indoor unit shall have a removable EEPROM that stores system programming information, unit name, and other data All indoor unit addressing and option settings shall be done digitally; the indoor unit does not contain rotary dials or setting switches. Electro-static, washable, pleated filter as standard (included with fascia panel). Built in condensate pump with maximum 29" lift from the bottom of the unit, check valve, and float switch that disables indoor unit during overflow detection Knock-out for outside air capability (with booster fan connection) Fascia panel shall have LED indicator lights and an infrared receiver The indoor unit shall have two (2) fascia panel types: 1. Ceiling Type for installation applications where a ceiling textile is present (ex. tile ceiling, gypsum). The Ceiling Type fascia panel shall be square in shape. 2. Open Type for installation applications where a ceiling textile is not present (ex. open ceiling). The Open Type fascia panel shall be circular in shape. The indoor unit shall not have air louvers or blades allowing full airflow without restriction. Air direction control shall be achieved by creating a low pressure area near air outlet causing discharge air to change direction angle. Fixed or auto-swing air direction shall be possible with wireless, touch, or premium wired controller (10° ~ 60° angle) Independent air distribution control shall be possible with wireless or premium wired controller (three directions, 10° ~ 60° angle) Construction The indoor unit shall be have a galvanized steel frame with HIPS chassis and fascia panel certified to UL94 V0. Heat Exchanger The indoor unit heat exchanger shall be mechanically bonded aluminum fin to copper tube Controls Control signal shall be a DDC type signal The unit shall integrate with the Samsung NASA Controls Network Solution Controls shall integrate with a BMS system Control wiring shall be 2 X 16 AWG shielded wire The indoor unit shall have a 12VDC output that is interlocked with fan to activate external devices (fan ON = 12VDC ON, fan OFF = 12VDC OFF, pigtail adapter plug required) Wired or wireless controls must be purchased separately Cooling (Btu/h) 30,000 Heating (Btu/h) 34,000 9.10 Voltage ø / V / Hz 1 / 208-230 / 60 0.42 W X H X D Inches 37 1/4 X 14 3/8 X 37 1/4 Weight 52.9 Sound Level H / M / L dB(a) 40 / 38 / 36 Liquid (flare) Inches 3/8 Suction (flare) Inches 5/8 1 1/4" OD, 1" ID R410A Electronic Expansion Valve BLDC (1) With Turbo Type Fan (1) Air Volume CFM (H/M/L) 901 / 795 / 706 FLA Amps 0.39 L X W X H (inches) 39 3/8 X 39 3/8 X 2 5/8 Weight (lbs.) 7.94 Diameter X H (inches) 41 15/16 X 3 3/8 Weight (lbs.) 5.95 Ceiling Type (square, white) PC4NUDMUN Ceiling Type (square, black) PC4NBDMUN Open Type (round, white) PC4NUNMUN Open Type (round, black) PC4NBNMUN Simplified MWR-SH00N Simplified Touch Controller MWR-SH11UN Premium W/Scheduling MWR-WE13UN MIM-H03UN MRW-TA AR-KH03U MIM-B14 Safety ETL (UL 1995) Specifications Performance Pipe Connections Condensate Connection Condensate (pints/hour) Power Nominal Running Current (A) Dimensions Type Fascia Panel Ceiling Type (Square) Open Type (Round) Refrigerant Type Control Method Nominal Capacity Evaporator Fan Certifications Accessories Fascia Panel Wired Controller Wi-Fi Adapter External Temperature Sensor Wireless Controller External Contact Control lbs.

68%0,77$/ AM030KN4DCH/AA 3DJH RI Samsung …...067 68%0,77$/ AM030KN4DCH/AA 3DJH 3 RI 3 Samsung DVM S Series, 360 Cassette Dimensional Drawing With Open Type Fascia Panel Units: mm

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: 68%0,77$/ AM030KN4DCH/AA 3DJH RI Samsung …...067 68%0,77$/ AM030KN4DCH/AA 3DJH 3 RI 3 Samsung DVM S Series, 360 Cassette Dimensional Drawing With Open Type Fascia Panel Units: mm

3

⁰ ⁰ ⁰ ⁰

AM030KN4DCH/AASamsung DVM S Series, 360 Cassette

SamsungHVAC m

Shown with PC4NUNMUN (open type panel)

Shown with PC4NUDMUN (ceiling type panel)

Samsung HVAC © 2019 Samsung HVAC SHA-DVMS-03122019

General Information• The indoor unit shall be compatible with Samsung DVM S and DVM Eco systems (AM****X*****AA).

• The indoor unit shall be a round ceiling cassette with 360°, even air distribution

• Auto-restart after power loss

• The indoor unit shall have a removable EEPROM that stores system programming information, unit name, and other data

• All indoor unit addressing and option settings shall be done digitally; the indoor unit does not contain rotary dials or setting switches.

• Electro-static, washable, pleated filter as standard (included with fascia panel).

• Built in condensate pump with maximum 29" lift from the bottom of the unit, check valve, and float switch that disables indoor unit during overflow detection

• Knock-out for outside air capability (with booster fan connection)

• Fascia panel shall have LED indicator lights and an infrared receiver

• The indoor unit shall have two (2) fascia panel types: 1. Ceiling Type for installation applications where a ceiling textile is present (ex. tile ceiling, gypsum). The Ceiling Type fascia panel shall be square in shape.

2. Open Type for installation applications where a ceiling textile is not present (ex. open ceiling). The Open Type fascia panel shall be circular in shape.

• The indoor unit shall not have air louvers or blades allowing full airflow without restriction. Air direction control shall be achieved by creating a low pressure area near air outlet causing discharge air to change direction angle.

• Fixed or auto-swing air direction shall be possible with wireless, touch, or premium wired controller (10° ~ 60° angle)

• Independent air distribution control shall be possible with wireless or premium wired controller (three directions, 10° ~ 60° angle)

ConstructionThe indoor unit shall be have a galvanized steel frame with HIPS chassis and fascia panel certified to UL94 V0.

Heat ExchangerThe indoor unit heat exchanger shall be mechanically bonded aluminum fin to copper tube

ControlsControl signal shall be a DDC type signal

The unit shall integrate with the Samsung NASA Controls Network Solution

Controls shall integrate with a BMS system

Control wiring shall be 2 X 16 AWG shielded wire

The indoor unit shall have a 12VDC output that is interlocked with fan to activate external devices (fan ON = 12VDC ON, fan OFF = 12VDC OFF, pigtail adapter plug required)

Wired or wireless controls must be purchased separately

Cooling (Btu/h) 30,000

Heating (Btu/h) 34,000

9.10

Voltage ø / V / Hz 1 / 208-230 / 60

0.42

W X H X D Inches 37 1/4 X 14 3/8 X 37 1/4

Weight 52.9

Sound Level H / M / L dB(a) 40 / 38 / 36

Liquid (flare) Inches 3/8

Suction (flare) Inches 5/8

1 1/4" OD, 1" ID

R410A

Electronic Expansion Valve

BLDC (1) With Turbo Type Fan (1)

Air Volume CFM (H/M/L) 901 / 795 / 706

FLA Amps 0.39

L X W X H (inches) 39 3/8 X 39 3/8 X 2 5/8

Weight (lbs.) 7.94

Diameter X H (inches) 41 15/16 X 3 3/8

Weight (lbs.) 5.95

Ceiling Type (square, white) PC4NUDMUN

Ceiling Type (square, black) PC4NBDMUN

Open Type (round, white) PC4NUNMUN

Open Type (round, black) PC4NBNMUN

Simplified MWR-SH00N

Simplified Touch Controller MWR-SH11UN

Premium W/Scheduling MWR-WE13UN

MIM-H03UN

MRW-TA

AR-KH03U

MIM-B14

Safety ETL (UL 1995)

Specifications

Performance

Pipe Connections

Condensate Connection

Condensate (pints/hour)

PowerNominal Running Current (A)

Dimensions

Type

Fascia Panel

Ceiling Type (Square)

Open Type (Round)

RefrigerantType

Control Method

Nominal Capacity

Evaporator Fan

Certifications

Accessories

Fascia Panel

Wired Controller

Wi-Fi Adapter

External Temperature Sensor

Wireless Controller

External Contact Control

lbs.

Page 2: 68%0,77$/ AM030KN4DCH/AA 3DJH RI Samsung …...067 68%0,77$/ AM030KN4DCH/AA 3DJH 3 RI 3 Samsung DVM S Series, 360 Cassette Dimensional Drawing With Open Type Fascia Panel Units: mm

067www.SamsungHVAC.com

3 AM030KN4DCH/AASamsung DVM S Series, 360 Cassette Dimensional Drawing With Ceiling Type Fascia Panel

Units: mm [inches]

No. Description No. Description

1 Refrigerant Gas Pipe 7 Suction rim for air direction booster fan2 Refrigerant Liquid Pipe 8 Decoration fascia panel3 Condensate drain 9 Drain hose4 Power and wiring entry 10 Fresh air knockout hole5 Air discharge opening 11 Status display6 Air suction grille 12 Infrared receiver

Page 3: 68%0,77$/ AM030KN4DCH/AA 3DJH RI Samsung …...067 68%0,77$/ AM030KN4DCH/AA 3DJH 3 RI 3 Samsung DVM S Series, 360 Cassette Dimensional Drawing With Open Type Fascia Panel Units: mm

067www.SamsungHVAC.com

3 3 AM030KN4DCH/AASamsung DVM S Series, 360 Cassette Dimensional Drawing With Open Type Fascia Panel

Units: mm [inches]

No. Description No. Description

1 Refrigerant Gas Pipe 7 Suction rim for air direction booster fan2 Refrigerant Liquid Pipe 8 Decoration fascia panel3 Condensate drain 9 Drain hose4 Power and wiring entry 10 Fresh air knockout hole5 Air discharge opening 11 Status display6 Air suction grille 12 Infrared receiver