124
CONTENTS 3 Page INTRODUCTION ..........................................................................................................................................................................................................5&6 SECTION ONE - FIXED WIRING & MAINS CABLES PVC insulated wiring cable 6491X (1.5mm 2 to 630mm 2 ) ..............................................................................................................................8 PVC insulated PVC sheathed surface wiring cable type 6181Y (1mm 2 to 35mm 2 ) ............................................................................9 XLPE insulated mains and control cable (1.5mm 2 to 16mm 2 ) ....................................................................................................................10 XLPE insulated mains cable (25mm 2 to 400mm 2 ) ..........................................................................................................................................11 XLPE insulated mains cable 3300v (16mm 2 to 400mm 2 ) ............................................................................................................................12 XLPE insulated mains cable with aluminium conductors (25mm 2 to 300mm 2 )................................................................................13 XLPE insulated single core non-armoured mains cable (50mm 2 to 1000mm 2 )..................................................................................14 XLPE insulated single core armoured mains cable (50mm 2 to 1000mm 2 ) ..........................................................................................15 XLPE insulated non-armoured and armoured single core cable for cathodic protection (6mm 2 to 185mm 2 ) ....................16 Low smoke insulated wiring cable 6491B (1.5mm 2 to 630mm 2 ) ..............................................................................................................17 XLPE insulated low smoke mains and control cable (1.5mm 2 to 16mm 2 ) ............................................................................................18 XLPE insulated low smoke mains cable (25mm 2 to 400mm 2 ) ..................................................................................................................19 XLPE insulated low smoke single core non-armoured mains cable 1000 volt (50mm 2 to 1000mm 2 ) ....................................20 XLPE insulated low smoke single core armoured mains cable (50mm 2 to 1000mm 2 ) ....................................................................21 Mechanically protected wiring cable (1.0mm 2 to 6.0mm 2 ) ........................................................................................................................22 XLPE insulated medium voltage mains cable 11000 volt (25mm 2 to 400mm 2 ) and (50mm 2 to 630mm 2 ) ..........................23 XLPE insulated medium voltage mains cable 11000 volt (95mm 2 to 300mm 2 ) ................................................................................24 XLPE insulated low smoke medium voltage mains cable 11000 volt (35mm 2 to 300mm 2 and (50mm 2 to 630mm 2 ) ............25 Paper insulated medium voltage mains cable 11000 volt (25mm 2 to 400mm 2 ) ..............................................................................26 Paper insulated corrugated aluminium sheathed medium voltage mains cable 11000 volt (95mm 2 to 300mm 2 ) ..........27 XLPE insulated mains cable with 60% conductivity in armour. (Mines & quarries & British Coal) (10mm 2 to 300mm 2 )........28 XLPE insulated lead sheathed control cable for petro-chemical industries (1.5mm 2 to 4mm 2 ) ................................................29 XLPE insulated lead sheathed mains cable for petro-chemical industries (25mm 2 to 300mm 2 ) ..............................................30 XLPE insulated lead sheathed mains cable for petro-chemical industries (1.5mm 2 to 16mm 2 ) ................................................31 XLPE insulated lead sheathed mains cable for petro-chemical industries 3300 volt (25mm 2 to 300mm 2 ) ..........................32 PVC insulated single phase split and straight concentric service cable (4mm 2 to 35mm 2 ) ..........................................................33 SECTION TWO - FLEXIBLE CABLES PVC insulated flexible cords type 318*y (0.5mm 2 to 2.5mm 2 ) ..................................................................................................................36 PVC insulated heat resisting flexible cords type 309*y (0.5mm 2 to 2.5mm 2 ) ......................................................................................37 LSF insulated flexible cords type 318*B (0.75mm 2 to 2.5mm 2 ) ..................................................................................................................38 PVC insulated flexible power and control cable type “YY” (0.75mm 2 to 1.5mm 2 ) and (2.5mm 2 to 50mm 2 ) ..............39 & 40 LSF insulated flexible control cable type “YY” (1.5mm 2 to 4.0mm 2 ) ........................................................................................................41 PVC insulated braided flexible control cable type “SY”(0.75mm 2 to 2.5mm 2 ) and (4mm 2 to 95mm 2 ) ........................42 & 43 PVC insulated braid screened flexible power and control cable type “CY”(0.75mm 2 to 10mm 2 ) ..............................................44 Tri-rated and Bi-rated switch gear and control panel wire (0.5mm 2 to 400mm 2 ) ............................................................................45 EPR insulated HOFR sheathed flexible power and control cable (0.75mm 2 to 2.5mm 2 ) ................................................................46 EPR insulated heavy duty HOFR sheathed flexible mains cable (4mm 2 ) ..............................................................................................47 EPR insulated HOFR sheathed power and control cable (6mm 2 to 630mm 2 ) ....................................................................................48 Rubber insulated neoprene sheathed flexible power cable (1.5mm 2 to 300mm 2 ) ..........................................................................49 EPR insulated braided screen flexible mains and control cable (1.0mm 2 to 16mm 2 ) ......................................................................50 EPR insulated flexible coil lead (0.5mm 2 to 400mm 2 )....................................................................................................................................51 EPR insulated flexible welding cable type 0361TQ (16mm 2 to 185mm 2 ) ............................................................................................52 Rubber insulated flat cable (1.5mm 2 to 70mm 2 ) and PVC insulated flat cable (1.5mm 2 to 95mm 2 ) ......................................53 Silicone insulated flexible cable (0.75mm 2 to 2.5mm 2 ) ................................................................................................................................54

6629983 Cleveland Catalogue

Embed Size (px)

Citation preview

Page 1: 6629983 Cleveland Catalogue

CON

TENTS

3

Page

INTRODUCTION ..........................................................................................................................................................................................................5&6

SECTION ONE - FIXED WIRING & MAINS CABLES

PVC insulated wiring cable 6491X (1.5mm2 to 630mm2) ..............................................................................................................................8

PVC insulated PVC sheathed surface wiring cable type 6181Y (1mm2 to 35mm2) ............................................................................9

XLPE insulated mains and control cable (1.5mm2 to 16mm2)....................................................................................................................10

XLPE insulated mains cable (25mm2 to 400mm2) ..........................................................................................................................................11

XLPE insulated mains cable 3300v (16mm2 to 400mm2) ............................................................................................................................12

XLPE insulated mains cable with aluminium conductors (25mm2 to 300mm2)................................................................................13

XLPE insulated single core non-armoured mains cable (50mm2 to 1000mm2)..................................................................................14

XLPE insulated single core armoured mains cable (50mm2 to 1000mm2) ..........................................................................................15

XLPE insulated non-armoured and armoured single core cable for cathodic protection (6mm2 to 185mm2) ....................16

Low smoke insulated wiring cable 6491B (1.5mm2 to 630mm2)..............................................................................................................17

XLPE insulated low smoke mains and control cable (1.5mm2 to 16mm2) ............................................................................................18

XLPE insulated low smoke mains cable (25mm2 to 400mm2) ..................................................................................................................19

XLPE insulated low smoke single core non-armoured mains cable 1000 volt (50mm2 to 1000mm2) ....................................20

XLPE insulated low smoke single core armoured mains cable (50mm2 to 1000mm2)....................................................................21

Mechanically protected wiring cable (1.0mm2 to 6.0mm2) ........................................................................................................................22

XLPE insulated medium voltage mains cable 11000 volt (25mm2 to 400mm2) and (50mm2 to 630mm2) ..........................23

XLPE insulated medium voltage mains cable 11000 volt (95mm2 to 300mm2) ................................................................................24

XLPE insulated low smoke medium voltage mains cable 11000 volt (35mm2 to 300mm2 and (50mm2 to 630mm2) ............25

Paper insulated medium voltage mains cable 11000 volt (25mm2 to 400mm2) ..............................................................................26

Paper insulated corrugated aluminium sheathed medium voltage mains cable 11000 volt (95mm2 to 300mm2)..........27

XLPE insulated mains cable with 60% conductivity in armour. (Mines & quarries & British Coal) (10mm2 to 300mm2)........28

XLPE insulated lead sheathed control cable for petro-chemical industries (1.5mm2 to 4mm2) ................................................29

XLPE insulated lead sheathed mains cable for petro-chemical industries (25mm2 to 300mm2) ..............................................30

XLPE insulated lead sheathed mains cable for petro-chemical industries (1.5mm2 to 16mm2) ................................................31

XLPE insulated lead sheathed mains cable for petro-chemical industries 3300 volt (25mm2 to 300mm2) ..........................32

PVC insulated single phase split and straight concentric service cable (4mm2 to 35mm2)..........................................................33

SECTION TWO - FLEXIBLE CABLES

PVC insulated flexible cords type 318*y (0.5mm2 to 2.5mm2) ..................................................................................................................36

PVC insulated heat resisting flexible cords type 309*y (0.5mm2 to 2.5mm2)......................................................................................37

LSF insulated flexible cords type 318*B (0.75mm2 to 2.5mm2)..................................................................................................................38

PVC insulated flexible power and control cable type “YY” (0.75mm2 to 1.5mm2) and (2.5mm2 to 50mm2) ..............39 & 40

LSF insulated flexible control cable type “YY” (1.5mm2 to 4.0mm2) ........................................................................................................41

PVC insulated braided flexible control cable type “SY” (0.75mm2 to 2.5mm2) and (4mm2 to 95mm2) ........................42 & 43

PVC insulated braid screened flexible power and control cable type “CY” (0.75mm2 to 10mm2) ..............................................44

Tri-rated and Bi-rated switch gear and control panel wire (0.5mm2 to 400mm2) ............................................................................45

EPR insulated HOFR sheathed flexible power and control cable (0.75mm2 to 2.5mm2) ................................................................46

EPR insulated heavy duty HOFR sheathed flexible mains cable (4mm2) ..............................................................................................47

EPR insulated HOFR sheathed power and control cable (6mm2 to 630mm2) ....................................................................................48

Rubber insulated neoprene sheathed flexible power cable (1.5mm2 to 300mm2) ..........................................................................49

EPR insulated braided screen flexible mains and control cable (1.0mm2 to 16mm2) ......................................................................50

EPR insulated flexible coil lead (0.5mm2 to 400mm2)....................................................................................................................................51

EPR insulated flexible welding cable type 0361TQ (16mm2 to 185mm2) ............................................................................................52

Rubber insulated flat cable (1.5mm2 to 70mm2) and PVC insulated flat cable (1.5mm2 to 95mm2) ......................................53

Silicone insulated flexible cable (0.75mm2 to 2.5mm2) ................................................................................................................................54

Page 2: 6629983 Cleveland Catalogue

CON

TEN

TS4

SECTION THREE - INSTRUMENTATION, CONTROL & COMMUNICATION CABLES

Control and instrumentation cable non-armoured with collective screen (0.5mm2 to 1.5mm2) ..............................................56

Control and instrumentation cable non-armoured with individual and collective screens (0.5mm2 to 1.5mm2)..............57

Control and instrumentation cable armoured with collective screen (0.5mm2 to 2.5mm2) ........................................................58

Control and instrumentation cable armoured with individual and collective screens (0.5mm2 to 1.5mm2)........................59

Control and instrumentation cable lead sheathed armoured with collective screen (0.75mm2 to 1.5mm2) ......................60

Control and instrumentation cable lead sheathed armoured with individual and collective screens (0.75mm2 to 1.5mm2) ..........61

BS5308 part 1 core identification ..........................................................................................................................................................................62

BS5308 part 2 core identification ..........................................................................................................................................................................63

Instrumentation cable to British Steel specification CES20 type 134 (0.75mm2) ............................................................................64

Instrumentation cable to British Steel specification CES20 type 143 (0.75mm2) ............................................................................65

Internal telephone cable type CW1308 ..............................................................................................................................................................66

PVC insulated multipair armoured cable to ESI standard ................................................................................................................67 & 68

ESI 09-6 section 3.6 core identification ................................................................................................................................................................69

ESI 09-6 section 4.5 core identification ................................................................................................................................................................70

Petroleum jelly filled telemetry cable to BS3573 and CW1128/1198 ....................................................................................................71

Defence screened multicore cable ‘C’ type..........................................................................................................................................................72

Defence standard 61-12 parts 4 &5 core identification ..............................................................................................................................73

PVC insulated collective screened thermocouple extension and compensating cable (0.75mm2)............................................74

PVC insulated armoured traffic signal cable, loop feeder cable and loop detector cable ..................................................75 & 76Colour coding of thermocouple extension and compensating cable ....................................................................................................77

SECTION FOUR - RAILWAY CABLES

Signalling cables types A1, A2, A3, B1 and B2 (0.75mm2 to 95mm2) ......................................................................................................80

Signalling cables types C1, C2, C3, D1, D2, D3, E1, E2 & E3 (0.75mm2 to 35mm2) ..........................................................................81

Power cables and Trackfeeder cables (16mm2 to 1000mm2)......................................................................................................................82

SECTION FIVE - MARINE & OFFSHORE CABLES

EPR insulated non-armoured shipwiring cable (1.5mm2 to 6mm2) ........................................................................................................84

EPR insulated non-armoured shipwiring cable (10mm2 to 630mm2) ....................................................................................................85

EPR insulated braided armour shipwiring cable (1.5mm2 to 4mm2) ......................................................................................................86

EPR insulated braided armoured shipwiring cable (6mm2 to 300mm2)................................................................................................87

EPR insulated single core braided shipwiring cable (6mm2 to 630mm2) ..............................................................................................88

SECTION SIX - FIREPROOF CABLES

Mineral insulated cable ..............................................................................................................................................................................................90

Fire resistant security cable (1.0mm2 to 4mm2) ..............................................................................................................................................91

Fire resistant power and control cable (1.5mm2 to 16mm2) ......................................................................................................................92

Fire resistant power cable (25mm2 to 400mm2) ..............................................................................................................................................93

SECTION SEVEN - INSTALLATION ACCESSORIES ................................................................................................................................................95

SECTION EIGHT - CURRENT RATINGS ................................................................................................................................................................109

Page 3: 6629983 Cleveland Catalogue

CLEV

ELAN

DC

AB

LECO

MPA

NY

5

Cleveland Cable CompanyCleveland Cable Company, established in 1978, isundoubtedly the foremost distributor of electricalcables in Great Britain and possibly Europe.

The Head Office and principal

stocking location is located at

Middlesbrough in the North East of

England. This site covers an area of

twelve acres and includes over

160,000 square feet of warehousing.

Additionally there are regional depots

at Bristol, Glasgow, London, Milton

Keynes, Newcastle and Warrington.

Each location holds comprehensive

stocks and is equipped with the most

modern handling and measuring

equipment. Deliveries

are made by our own fleet of

purpose-designed vehicles, all of

which are fitted with hydraulic

lifting equipment for safe offloading

onsite and also efficient collection of

empty drums.

Page 4: 6629983 Cleveland Catalogue

CLE

VEL

AN

DC

AB

LECO

MPA

NY

6

As is illustrated within our catalogue, we stock anextremely large range of cables for everyconceivable application. All types shown areconsidered as standard items to our range and arealways available for immediate delivery. Our stocksare extremely large and unrivalled in the industry.

We are fortunate to have a very

experienced and dedicated team of

people who are able to assist and

advise. Additionally our policy of

continuing investment in the best

available technology, warehousing,

handling and measuring equipment

and delivery vehicles enables us to

guarantee all our customers an

extremely high quality service.

Enquiries are welcome from

customers worldwide. Our export

service is efficient and reliable with

the ability to ship by air or sea freight

to any destination.

Please feel free to contact the depot of yourchoice for an immediate, professionaland trouble free service.

Page 5: 6629983 Cleveland Catalogue

7

FIXED WIRING ANDMAINS CABLES

FIXED

WIR

ING

AN

D M

AIN

S CA

BLES

Page 6: 6629983 Cleveland Catalogue

FIX

ED W

IRIN

G A

ND

MA

INS

CA

BLE

S8

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

FIXED WIRING AND MAINS CABLESStranded plain annealed compacted circular copper conductor, PVC outer sheath.

Ref 6491X. Harmonised code HO7V-R. 450 volts grade to BS6004. Flame propagation to BS4066 PT1 and IEC 332 PT1.

CCC CONDUCTOR STRANDING WEIGHT OVERALLCODE SIZE (MM2) (MM) KG/KM DIAMETER

(MM)6491X1/5 1.5 7/0.53 21 3.56491X2/5 2.5 7/0.67 35 4.2

6491X4 4.0 7/0.85 50 4.86491X6 6.0 7/1.04 71 5.4

6491X10 10.0 7/1.35 120 6.86491X16 16.0 7/1.70 180 8.06491X25 25.0 7/2.14 280 9.86491X35 35.0 19/1.53 380 11.06491X50 50.0 19/1.78 510 13.06491X70 70.0 19/2.14 720 15.06491X95 95.0 19/2.52 990 17.0

6491X120 120.0 37/2.03 1200 19.06491X150 150.0 37/2.25 1500 21.06491X185 185.0 37/2.52 1900 23.56491X240 240.0 61/2.25 2500 26.56491X300 300.0 61/2.52 3000 29.56491X400 400.0 61/2.85 3950 33.56491X500 500.0 61/3.20 4950 37.06491X630 630.0 127/2.50 6250 41.0

PVC INSULATED WIRINGCABLE 6491X

(1.5MM2 TO 630MM2)

Temperature limits: -15 to +70°C.

Bending radius:up to 10mm2 - 3 x overall diameter.above 25mm2 - 6 x overall diameter.

Standard colours available: 1.5mm2 & 2.5mm2 - Brown, Black,Grey, Blue, Green/Yellow, White,Orange, Turquoise, Violet, Pink.

4mm2-630mm2 - Brown, Black, Grey,Blue, Green/Yellow.

Should not be installed attemperatures below 0°C.

Current ratings see page 110

Page 7: 6629983 Cleveland Catalogue

FIXED

WIR

ING

AN

D M

AIN

S CA

BLES

9

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

FIXED WIRING AND MAINS CABLESPlain annealed stranded circular copper conductor, single core, PVC insulated,PVC sheathed, Ref 6181 Y. 300/500 volts grade to BS6004. Brown/Grey or Blue/Grey. Flame propagation to BS4066 PT1 and IEC 332 PT1.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND SINGLECODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE CLEAT

(MM) (MM)6181Y1 1.0 1/1.13 1 28 4.5 20/16

6181Y1/5 1.5 1/1.38 1 36 5.1 20/166181Y2/5 2.5 1/1.78 1 51 6.0 20/16

6181Y4 4.0 7/0.85 1 75 6.8 20/166181Y6 6.0 7/1.04 1 98 7.4 20/16

6181Y10 10.0 7/1.35 1 150 8.8 20S6181Y16 16.0 7/1.70 1 220 10.5 20S 0.56181Y25 25.0 7/2.14 1 340 12.5 20 0.56181Y35 35.0 19/1.53 1 440 13.5 25 0.66181Y50 50.0 19/1.78 1 540 14.38 25A26181Y70 70.0 19/2.14 1 750 15.3 25A26181Y95 95.0 19.2.52 1 1010 17.7 25A2

6181Y120 120.0 37/2.03 1 1250 19.3 32A2

XLPE INSULATEDLSOH SHEATHED SURFACE

WIRING CABLETYPE 6181B

1MM2 TO 35MM2

Plain annealed stranded circular copper conductor, single core, XLPE insulated,(LSOH) sheathed, Ref 6181B. 300/500 volts grade to BS7889. Brown/Grey orBlue/Grey. Flame propagation to BS4066 PT1 and IEC332 PT1.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLANDCODE SIZE (MM2) (MM) CORES KG/KM DIAMETER REF

(MM) 6181B1 1.0 1/1.13 1 28 4.5 20/16

6181B1/5 1.5 1/1.38 1 34 5.1 20/166181B2/5 2.5 1/1.78 1 49 6.0 20/16

6181B4 4.0 7/0.85 1 75 6.8 20/166181B6 6.0 7/1.04 1 99 7.4 20/16

6181B10 10.0 7/1.35 1 155 8.8 20s6181B16 16.0 7/1.04 1 225 10.5 20s6181B25 25.0 7/2.14 1 340 12.5 206181B35 35.0 19/1.53 1 440 13.5 25

Temperature limits:-15 to +70°C.

Bending radius:up to 10mm2 - 3 x overall diameter.over 10mm2 - 4 x overall diameter.

Should not be installed attemperatures below 0°C.

PVC INSULATEDPVC SHEATHED SURFACE

WIRING CABLETYPE 6181Y

1MM2 TO 120MM2

Page 8: 6629983 Cleveland Catalogue

FIX

ED W

IRIN

G A

ND

MA

INS

CA

BLE

S10

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

FIXED WIRING AND MAINS CABLESStranded plain annealed copper conductors, XLPE insulated, PVC bedding,galvanised steel wire armour, PVC outer sheath. Black. 600/1000 volts grade toBS5467. Flame propagation to IEC 332 PT1 and BS4066 PT1.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND SINGLECODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE CLEAT

(MM) (MM)XLPE2X1/5 1.5 7/0.53 2 305 12.4 20/16 0.5XLPE3X1/5 1.5 7/0.53 3 338 12.9 20/16 0.6XLPE4X1/5 1.5 7/0.53 4 381 13.7 20S 0.6XLPE5X1/5 1.5 7/0.53 5 426 14.2 20S 0.6XLPE7X1/5 1.5 7/0.53 7 488 15.6 20S 0.7XLPE8X1/5 1.5 7/0.53 8 501 16.7 20 0.7

XLPE10X1/5 1.5 7/0.53 10 777 18.7 20 0.8XLPE12X1/5 1.5 7/0.53 12 817 20.1 20 0.8XLPE19X1/5 1.5 7/0.53 19 1225 24.0 25 1.0XLPE27X1/5 1.5 7/0.53 27 1553 27.7 32 1.1XLPE37X1/5 1.5 7/0.53 37 1859 30.3 32 1.2XLPE48X1/5 1.5 7/0.53 48 2236 32.3 32 1.4XLPE2X2/5 2.5 7/0.67 2 352 13.2 20S 0.6XLPE3X2/5 2.5 7/0.67 3 397 13.8 20S 0.6XLPE4X2/5 2.5 7/0.67 4 452 14.7 20S 0.6XLPE5X2/5 2.5 7/0.67 5 549 16.3 20S 0.6XLPE7X2/5 2.5 7/0.67 7 685 17.6 20 0.7

XLPE10X2/5 2.5 7/0.67 10 1000 21.4 25 0.9XLPE12X2/5 2.5 7/0.67 12 910 21.8 25 0.9XLPE19X2/5 2.5 7/0.67 19 1500 26.1 25 1.1XLPE27X2/5 2.5 7/0.67 27 1928 30.3 32 1.2XLPE37X2/5 2.5 7/0.67 37 2360 33.4 32 1.4XLPE48X2/5 2.5 7/0.67 48 3888 38.8 40 1.6

XLPE2X4 4.0 7/0.85 2 419 14.3 20S 0.6XLPE3X4 4.0 7/0.85 3 481 14.9 20S 0.6XLPE4X4 4.0 7/0.85 4 563 16.2 20 0.7XLPE5X4 4.0 7/0.85 5 810 18.9 20 0.8XLPE7X4 4.0 7/0.85 7 912 19.7 20 0.8

XLPE12X4 4.0 7/0.85 12 1400 25.0 25 1.0XLPE19X4 4.0 7/0.85 19 1852 28.1 32 1.2XLPE27X4 4.0 7/0.85 27 2630 35.2 40 1.4XLPE2X6 6.0 7/1.04 2 498 15.4 20S 0.7XLPE3X6 6.0 7/1.04 3 639 17.4 20 0.7XLPE4X6 6.0 7/1.04 4 795 18.3 20 0.8XLPE5X6 6.0 7/1.04 5 970 20.5 25 0.8XLPE7X6 6.0 7/1.04 7 1180 21.9 25 0.9

XLPE2X10 10.0 7/1.35 2 764 17.9 20 0.8XLPE3X10 10.0 7/1.35 3 908 18.9 25 0.8XLPE4X10 10.0 7/1.35 4 1064 20.3 25 0.8XLPE5X10 10.0 7/1.35 5 1150 22.0 25 0.9XLPE7X10 10.0 7/1.35 7 1560 25.0 25 1.0XLPE2X16 16.0 7/1.70 2 900 21.9 25 0.9XLPE3X16 16.0 7/1.70 3 1220 24.4 25 1.0XLPE4X16 16.0 7/1.70 4 1410 26.3 25 1.1XLPE5X16 16.0 7/1.70 5 1800 26.0 25 1.1XLPE7X16 16.0 7/1.70 7 2237 28.1 32 1.2

XLPE INSULATED MAINS AND

CONTROL CABLE(1.5MM2 TO 16MM2)

Temperature limits: -15 to +90°C.

Bending radius: 6 x overall diameter.

Core identification: 2 core - Brown, Blue.3 core - Brown, Black, Grey.4 core - Brown, Black, Grey, Blue.5 core and above - up to 6mm2 -White with Black numbers.

5 core and above - 10mm2 and16mm2 - Brown, Black, Grey, Blue,Green/Yellow

1.5 & 2.5 - 2,3,4 core also available inwhite numbered cores to ESI 09-6

Should not be installed attemperatures below 0°C.

Current ratings, see page 112.

Page 9: 6629983 Cleveland Catalogue

FIXED WIRING AND MAINS CABLESStranded plain annealed copper conductors, XLPE insulated, PVC bedding,galvanised steel wire armour, PVC outer sheath. Black. 600/1000 volts grade toBS5467. Flame propagation to IEC 332 PT1 and BS4066 PT1.

11

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND SINGLECODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE CLEAT

(MM) (MM)6942X25 25 7/2.14 2 1000 20.4 25 0.96943X25 25 7/2.14 3 1500 23.6 32 1.06944X25 25 7/2.14 4 1950 26.1 32 1.26945X25 25 7/2.14 5 2370 31.0 32 1.26942X35 35 7/2.52 2 1490 27.9 32 1.26943X35 35 7/2.52 3 1940 29.6 32 1.26944X35 35 7/2.52 4 2350 32.1 32 1.46945X35 35 7/2.52 5 3150 35.0 40 1.46942X50 50 19/1.78 2 1750 25.8 32 1.26943X50 50 19/1.78 3 2225 28.5 32 1.26944X50 50 19/1.78 4 2875 32.0 32 1.46945X50 50 19/1.78 5 4260 40.0 50S 1.66942X70 70 19/2.14 2 2300 29.0 32 1.26943X70 70 19/2.14 3 3025 32.2 32 1.46944X70 70 19/2.14 4 4250 37.7 40 1.66945X70 70 19/2.14 5 5685 43.0 50S 1.86942X95 95 19/2.52 2 3100 33.1 40 1.66943X95 95 19/2.52 3 4275 37.0 40 1.66944X95 95 19/2.52 4 5475 41.7 50S 1.86945X95 95 19/2.52 5 7700 52.0 50 R9

6942X120 120 37/2.03 2 3700 36.1 40 1.66943X120 120 37/2.03 3 5250 40.4 50S 1.86944X120 120 37/2.03 4 7175 47.1 50 2.06942X150 150 37/2.25 2 4400 39.3 40 1.86943X150 150 37/2.25 3 6650 45.5 50S 2.06944X150 150 37/2.25 4 8475 51.4 50 R96942X185 185 37/2.52 2 5700 44.7 50S 2.06943X185 185 37/2.52 3 8000 49.8 50 2.06944X185 185 37/2.52 4 10350 56.6 63S R106942X240 240 61/2.25 2 7100 49.0 50 2.06943X240 240 61/2.25 3 10150 55.1 63S R96944X240 240 61/2.25 4 13000 63.0 63 R106942X300 300 61/2.52 2 8500 53.5 63S R96943X300 300 61/2.52 3 12400 60.2 63 R106944X300 300 61/2.52 4 15750 68.8 75S R116942X400 400 61/2.85 2 10650 58.0 63S R106943X400 400 61/2.85 3 14770 65.8 75S R116944X400 400 61/2.85 4 19950 75.4 90 R12

XLPE INSULATED MAINS CABLE

(25MM2 TO 400MM2)

FIXED

WIR

ING

AN

D M

AIN

S CA

BLES

Temperature limits: -15 to +90°C.

Bending radius: 8 x overall diameter.

Core identification:2 core - Brown, Blue.3 core - Brown, Black, Grey.4 core - Brown, Black, Grey, Blue.5 core - Brown, Black, Grey, Blue,Green/Yellow.

Should not be installed attemperatures below 0°C.

Current ratings, see page 112.

Page 10: 6629983 Cleveland Catalogue

FIX

ED W

IRIN

G A

ND

MA

INS

CA

BLE

S12

XLPE INSULATED MAINS CABLE

3300 VOLT(16MM2 TO 400MM2)

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

FIXED WIRING AND MAINS CABLESStranded plain annealed copper conductors, XLPE insulated, PVC bedding,galvanised steel wire armour, PVC outer sheath. Black. 1900/3300 volts gradeto BS5467. Flame propagation to BS4066 PT1 and IEC 332 PT1.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND SINGLECODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE CLEAT

(MM) (MM)XLPE3X16/3 16 7/1.70 3 1600 29.5 32 1.2XLPE3X25/3 25 7/2.14 3 2060 32.3 32 1.4XLPE3X35/3 35 7/2.52 3 2330 35.0 40 1.4XLPE3X50/3 50 19/1.78 3 3040 34.9 40 1.4XLPE3X70/3 70 19/2.14 3 3800 38.0 40 1.6XLPE3X95/3 95 19/2.52 3 4730 41.4 50S 1.8

XLPE3X120/3 120 37/2.03 3 6070 45.6 50S 1.8XLPE3X150/3 150 37/2.25 3 7010 48.3 50 2.0XLPE3X185/3 185 37/2.52 3 8270 51.6 50 R9XLPE3X240/3 240 61/2.25 3 10310 56.5 63S R9XLPE3X300/3 300 61/2.52 3 12300 60.7 63 R10XLPE3X400/3 400 61/2.85 3 14780 65.8 75S R11

Temperature limits: -15 to +90°C.

Bending radius: 8 x overall diameter.

Core identification:Brown, Black, Grey.

Should not be installed attemperatures below 0°C.

Current ratings, see page 116.

Page 11: 6629983 Cleveland Catalogue

FIXED WIRING AND MAINS CABLESSolid plain aluminium sectoral conductors, XLPE insulated, PVC bedding,galvanised steel wire armour, PVC outer sheath. Black. 600/1000 volts grade toBS5467. Flame propagation to BS4066 PT1 and IEC 332 PT1.

CCC CONDUCTOR NO. OF WEIGHT OVERALL GLAND SINGLECODE SIZE (MM2) CORES KG/KM DIAMETER SIZE CLEAT

(MM) (MM)SAC4X25 25 4 1235 25.4 25 1.0SAC4X35 35 4 1515 28.9 32 1.2SAC4X50 50 4 1686 29.5 32 1.2SAC4X70 70 4 2401 34.7 40 1.4SAC4X95 95 4 2905 38.3 40 1.6

SAC4X120 120 4 3705 42.2 50S 1.8SAC4X150 150 4 4550 46.0 50 2.0SAC4X185 185 4 5076 51.1 50 9SAC4X240 240 4 6104 56.4 63S 9SAC4X300 300 4 7212 61.4 63 10

FIXED

WIR

ING

AN

D M

AIN

S CA

BLES

13

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

XLPE INSULATED MAINS CABLE

WITH ALUMINIUMCONDUCTORS

(25MM2 TO 300MM2)

Temperature limits: -15 to +90°C.

Bending radius: 8 x overall diameter.

Core identification: Brown, Black, Grey, Blue.

Should not be installed attemperatures below 0°C.

Current ratings, see page 114.

Page 12: 6629983 Cleveland Catalogue

FIXED WIRING AND MAINS CABLESPlain annealed stranded compacted circular copper conductor, single core,XLPE insulated, PVC outer sheath Black. 600/1000 volts grade to BS7889/97. Flame propagation to BS4066 PT1 and IEC 332 PT1.

CCC CONDUCTOR STRANDING WEIGHT OVERALL GLAND SINGLE TREFOILCODE SIZE (MM2) (MM) KG/KM DIAMETER SIZE CLEAT CLEAT

(MM) (MM)6181X50 50 19/1.78 540 13.6 25 0.66181X70 70 19/2.14 750 15.6 25 0.76181X95 95 19/2.52 1010 17.5 25 0.7

6181X120 120 37/2.03 1250 19.2 32 0.86181X150 150 37/2.25 1530 21.3 32 0.96181X185 185 37/2.52 1900 23.4 32 1.0 2076181X240 240 61/2.25 2470 26.3 40 1.1 5026181X300 300 61/2.52 3080 29.0 40 1.2 5046181X400 400 61/2.85 3890 32.7 50S 1.4 5066181X500 500 61/3.20 4970 36.6 50S 1.6 5096181X630 630 127/2.52 6370 41.3 50 1.8 5116181X800 800 127/2.85 8150 46.3 63S 2.0 515

6181X1000 1000 127/3.20 9860 53.0 63 R9 519

FIX

ED W

IRIN

G A

ND

MA

INS

CA

BLE

S14

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

XLPE INSULATED SINGLE CORE

NON-ARMOUREDMAINS CABLE

(50MM2 TO 1000MM2)

Temperature limits:-15 to +90°C.

Bending radius:8 x overall diameter.

Core identification:Brown inner / Black outer.

Should not be installed attemperatures below 0°C.

Current ratings, see page 116.

Page 13: 6629983 Cleveland Catalogue

FIXED WIRING AND MAINS CABLESStranded plain annealed compacted circular copper conductor, XLPE insulated,PVC bedding, aluminium wire armour, PVC outer sheath. Black. 600/1000 voltsgrade to BS5467. Flame propagation to BS4066 PT1 and IEC 332 PT1.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND SINGLE TREFOILCODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE CLEAT CLEAT

(MM) (MM)6941AX50 50 19/1.78 1 800 17.7 20 0.86941AX70 70 19/2.14 1 940 19.6 25 0.96941AX95 95 19/2.52 1 1220 21.5 25 1.0

6941AX120 120 37/2.03 1 1490 23.2 25 1.26941AX150 150 37/2.25 1 1870 26.3 32 1.2 5026941AX185 185 37/2.52 1 2290 28.7 32 1.4 5046941AX240 240 61/2.25 1 2880 31.4 40 1.4 5056941AX300 300 61/2.52 1 3520 34.1 40 1.8 5076941AX400 400 61/2.85 1 4520 38.9 50S 1.8 5106941AX500 500 61/3.20 1 5680 42.8 50S 1.8 5126941AX630 630 127/2.52 1 7120 47.3 50 2.0 5156941AX800 800 127/2.85 1 9220 53.9 63S R9 519

6941AX1000 1000 127/3.20 1 11270 58.8 63S R10 523

FIXED

WIR

ING

AN

D M

AIN

S CA

BLES

15

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

XLPE INSULATED SINGLE CORE ARMOURED

MAINS CABLE(50MM2 TO 1000MM2)

Temperature limits:-15 to +90°C.

Bending radius:6 x overall diameter.

Core identification:Brown inner / Black outer.

Should not be installed attemperatures below 0°C.

Current ratings, see page 111.

Page 14: 6629983 Cleveland Catalogue

FIXED WIRING AND MAINS CABLESPlain annealed compacted circular copper conductor, XLPE insulated, PVCouter sheath, 600/1000 volts grade generally to BS5467 & IEC 502/1. ColoursBlack/Black or Red/Red.

CCC CONDUCTOR STRANDING WEIGHT OVERALL GLANDCODE SIZE (MM2) (MM) KG/KM DIAMETER SIZE

(MM) (MM)6181X6 6 7/1.04 105 7.2 20/16

6181X10 10 7/1.35 150 8.1 20/166181X16 16 7/1.70 210 9.0 20S6181X25 25 7/2.14 305 10.6 20S6181X35 35 7/2.52 395 11.6 206181X50 50 19/1.78 515 13.0 206181X70 70 19/2.14 725 14.9 256181X95 95 19/2.52 1230 17.5 25

6181X120 120 37/2.03 1355 19.2 326181X150 150 37/2.25 1695 21.3 326181X185 185 37/2.52 2110 23.4 32

Plain annealed compacted circular copper conductor, XLPE insulated, PVCbedding, galvanised steel wire armour, PVC outer sheath. Black. 600/1000volts grade generally to IEC 502/1 & BS5467.

CCC CONDUCTOR STRANDING WEIGHT OVERALL GLANDCODE SIZE (MM2) (MM) KG/KM DIAMETER SIZE

(MM) (MM)6941X6 6 7/1.04 285 11.5 20/16

6941X10 10 7/1.35 355 12.5 20/166941X16 16 7/1.70 435 13.5 20S6941X25 25 7/2.14 585 15.0 20S6941X35 35 7/2.52 685 16.0 206941X50 50 19/1.17 835 17.5 206941X70 70 19/2.14 1080 19.5 206941X95 95 19/2.52 1375 21.6 25

6941X120 120 37/2.03 1685 23.4 256941X150 150 37/2.25 2120 26.4 256941X185 185 37/2.52 2505 28.9 32

FIX

ED W

IRIN

G A

ND

MA

INS

CA

BLE

S16

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

XLPE INSULATED NON-ARMOURED AND

ARMOURED SINGLE CORECABLE FOR CATHODIC

PROTECTION(6MM2 TO 185MM2)

Bending radius:4 x overall diameter.

Should not be installed attemperatures below 0°C.

Bending radius:4 x overall diameter.

Should not be installed attemperatures below 0°C.

Page 15: 6629983 Cleveland Catalogue

17

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

FIXED WIRING AND MAINS CABLESStranded plain annealed compacted circular copper conductor, low smoke andzero halogen (LSOH) outer sheath. 450/750 volts grade to BS7211. Flamepropagation to BS4066 PT1 and IEC 332 PT1.

CCC CONDUCTOR STRANDING WEIGHT OVERALLCODE SIZE (MM2) (MM) KG/KM DIAMETER

(MM)6491B1/5 1.5 7/0.53 22 3.56491B2/5 2.5 7/0.67 33 4.2

6491B4 4.0 7/0.85 49 4.86491B6 6.0 7/1.04 69 5.4

6491B10 10.0 7/1.35 116 6.86491B16 16.0 7/1.70 175 8.06491B25 25.0 7/2.14 273 9.86491B35 35.0 19/1.53 367 11.06491B50 50.0 19/1.78 510 11.86491B70 70.0 19/2.14 715 13.66491B95 95.0 19/2.52 990 15.9

6491B120 120.0 37/2.03 1230 17.56491B150 150.0 37/2.25 1510 19.46491B185 185.0 37/2.52 1900 21.76491B240 240.0 61/2.25 2490 24.56491B300 300.0 61/2.52 3050 27.56491B400 400.0 61/2.85 3842 28.56491B500 500.0 61/3.20 4900 32.06491B630 630.0 127/2.50 6334 38.2

FIXED

WIR

ING

AN

D M

AIN

S CA

BLES

LOW SMOKE ZEROHALOGEN INSULATED WIRING CABLE 6491B(1.5MM2 TO 630MM2)

Temperature limits: -15 to +70°C.

Bending radius: up to 10mm2 - 3 x overall diameterabove 25mm2 - 6 x overall diameter

Standard colours available: 1.5mm2 & 2.5mm2 - Brown, Black,Grey, Blue, Green/Yellow, White,Orange, Turquoise, Violet, Pink.

Should not be installed attemperatures below 0°C.

Current ratings, see page 110.

Brass A2 gland size only.

Page 16: 6629983 Cleveland Catalogue

FIX

ED W

IRIN

G A

ND

MA

INS

CA

BLE

S18

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

FIXED WIRING AND MAINS CABLESPlain annealed stranded copper conductors, XLPE insulated, low smoke andzero halogen (LSOH) bedding, galvanised steel wire armour, low smoke andzero halogen (LSOH) outer sheath. Black. 600/1000 volts grade to BS6724.Flame propagation to BS4066 PT1 and IEC 332 PT1.

(Bunched cables to BS4066 PT3 and IEC 332 PT3).

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND SINGLECODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE CLEAT

(MM) (MM)LSF2X1/5 1.5 7/0.53 2 310 12.5 20/16 0.5LSF3X1/5 1.5 7/0.53 3 340 13.0 20S 0.6LSF4X1/5 1.5 7/0.53 4 390 14.0 20S 0.6LSF5X1/5 1.5 7/0.53 5 426 14.2 20 0.6LSF7X1/5 1.5 7/0.53 7 490 15.9 20 0.7

LSF12X1/5 1.5 7/0.53 12 830 20.2 20 0.8LSF19X1/5 1.5 7/0.53 19 1070 23.2 25 1.0LSF27X1/5 1.5 7/0.53 27 1580 27.9 32 1.2LSF37X1/5 1.5 7/0.53 37 1880 30.6 32 1.4LSF48X1/5 1.5 7/0.53 48 2236 32.2 32 1.4LSF2X2/5 2.5 7/0.67 2 360 13.6 20S 0.6LSF3X2/5 2.5 7/0.67 3 410 14.1 20S 0.6LSF4X2/5 2.5 7/0.67 4 470 15.0 20S 0.6LSF5X2/5 2.5 7/0.67 5 549 16.3 20 0.7LSF7X2/5 2.5 7/0.67 7 600 17.1 20 0.7

LSF12X2/5 2.5 7/0.67 12 1020 22.4 25 0.9LSF19X2/5 2.5 7/0.67 19 1530 26.6 25 1.1LSF27X2/5 2.5 7/0.67 27 1960 30.7 32 1.4LSF37X2/5 2.5 7/0.67 37 2370 33.8 40 1.4LSF48X2/5 2.5 7/0.67 48 3888 38.8 40 1.6

LSF2X4 4.0 7/0.85 2 430 14.7 20S 0.6LSF3X4 4.0 7/0.85 3 500 15.3 20S 0.7LSF4X4 4.0 7/0.85 4 580 16.4 20 0.7LSF5X4 4.0 7/0.85 5 810 18.9 20 0.8LSF7X4 4.0 7/0.85 7 950 20.4 20 0.9

LSF12X4 4.0 7/0.85 12 1400 25.0 25 1.0LSF27X4 4.0 7/0.85 27 2630 35.2 40 1.4LSF2X6 6.0 7/1.04 2 500 15.9 20 0.7LSF3X6 6.0 7/1.04 3 770 16.6 20 0.7LSF4X6 6.0 7/1.04 4 820 18.7 20 0.8LSF5X6 6.0 7/1.04 5 970 20.5 25 0.9LSF7X6 6.0 7/1.04 7 1180 21.9 25 0.9

LSF2X10 10.0 7/1.35 2 800 18.0 20 0.8LSF3X10 10.0 7/1.35 3 900 19.5 25 0.8LSF4X10 10.0 7/1.35 4 1060 21.1 25 0.9LSF5X10 10.0 7/1.35 5 1131 22.0 25 0.9LSF7X10 10.0 7/1.35 7 1560 25.0 25 1.0LSF2X16 16.0 7/1.70 2 940 20.0 20 0.8LSF3X16 16.0 7/1.70 3 1180 21.2 25 0.9LSF4X16 16.0 7/1.70 4 1410 22.9 25 1.0LSF5X16 16.0 7/1.70 5 1880 26.2 25 1.1LSF7X16 16.0 7/1.70 7 2237 28.1 32 1.2

XLPE INSULATED LOW SMOKE ZERO

HALOGEN MAINS AND CONTROL CABLE

(1.5MM2 TO 16MM2)

Temperature limits:to +90°C.

Bending radius:6 x overall diameter.

Core identification:2 core - Brown, Blue.3 core - Brown, Black, Grey.4 core - Brown, Black, Grey, Blue.5 core and above - Up to 6mm2 -White with Black numbers.5 core and above - 10mm2 and16mm2 - Brown, Black, Grey, Blue,Green/Yellow.

1.5 & 2.5 - 2,3,4 core also available inwhite numbered cores to ESI 09-6

Should not be installed attemperatures below 0°C.

Current ratings, see page 112.

Page 17: 6629983 Cleveland Catalogue

FIXED WIRING AND MAINS CABLESStranded plain annealed copper conductors, XLPE insulated, low smoke andzero halogen (LSOH) extruded bedding, galvanised steel wire armour, lowsmoke and zero halogen (LSOH) outer sheath. Black. 600/1000 volts grade toBS6724. Flame propagation to BS4066 PT1 and IEC 332 PT1.

(Bunched cables to BS4066 PT3 and IEC 332 PT3).

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND SINGLECODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE CLEAT

(MM) (MM)LSF2X25 25 7/2.14 2 1250 24.3 25 1.2LSF3X25 25 7/2.14 3 1720 26.9 32 1.2LSF4X25 25 7/2.14 4 2090 29.1 32 1.2LSF5X25 25 7/2.14 5 2370 31.0 32 1.4LSF2X35 35 7/2.52 2 1720 27.9 32 1.2LSF3X35 35 7/2.52 3 2130 29.6 32 1.2LSF4X35 35 7/2.52 4 2590 32.1 32 1.4LSF5X35 35 7/2.52 5 3150 35.0 40 1.4LSF2X50 50 19/1.78 2 1800 25.3 32 1.2LSF3X50 50 19/1.78 3 2380 28.4 32 1.2LSF4X50 50 19/1.78 4 2960 31.3 32 1.4LSF5X50 50 19/1.78 5 4260 40.0 50S 1.6LSF2X70 70 19/2.14 2 2330 28.1 40 1.2LSF3X70 70 19/2.14 3 3150 32.0 32 1.4LSF4X70 70 19/2.14 4 4240 36.8 40 1.6LSF5X70 70 19/2.14 5 5685 43.0 50S 1.8LSF2X95 95 19/2.52 2 3170 31.9 32 1.6LSF3X95 95 19/2.52 3 4320 36.7 40 1.6LSF4X95 95 19/2.52 4 5410 40.6 50S 1.8LSF5X95 95 19/2.52 5 7700 52.0 50 R9

LSF2X120 120 37/2.03 2 3810 35.1 40 1.6LSF3X120 120 37/2.03 3 5200 40.0 50S 1.8LSF4X120 120 37/2.03 4 6980 45.8 50 2.0LSF5X120 120 37/2.03 5 9030 56.7 63S R9LSF2X150 150 37/2.25 2 4530 38.2 40 1.8LSF3X150 150 37/2.25 3 6630 45.1 50S 2.0LSF4X150 150 37/2.25 4 8320 49.9 50 R9LSF2X185 185 37/2.52 2 5860 43.3 50S 2.0LSF3X185 185 37/2.52 3 7980 49.3 50 2.0LSF4X185 185 37/2.52 4 10080 54.9 63S R9LSF2X240 240 61/2.25 2 7300 48.3 50 2.0LSF3X240 240 61/2.25 3 9960 54.5 63S R9LSF4X240 240 61/2.25 4 12690 61.0 63 R10LSF2X300 300 61/2.52 2 8790 52.5 63S R9LSF3X300 300 61/2.52 3 12060 59.5 63 R10LSF4X300 300 61/2.52 4 15420 66.5 75S R11LSF3X400 400 61/2.85 3 15330 68.0 75S R11LSF4X400 400 61/2.85 4 20215 77.5 75 R12M

XLPE INSULATED LOW SMOKE ZERO

HALOGEN MAINS CABLE(25MM2 TO 400MM2)

FIXED

WIR

ING

AN

D M

AIN

S CA

BLES

19

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

Temperature limits:-25 to +90°C.

Bending radius:8 x overall diameter.

Core identification:2 core - Brown, Blue.3 core - Brown, Black, Grey.4 core - Brown, Black, Grey, Blue.5 core - Brown, Black, Grey, Blue,Green/Yellow.

Should not be installed attemperatures below 0°C.

Current ratings, see page 112.

Page 18: 6629983 Cleveland Catalogue

FIX

ED W

IRIN

G A

ND

MA

INS

CA

BLE

S20

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

FIXED WIRING AND MAINS CABLESPlain annealed stranded compacted circular copper conductor, single core,XLPE insulated, low smoke and zero halogen (LSOH) outer sheath. Black.600/1000 volts grade to BS6724.

Flame propagation to BS4066 PT1 and IEC 332 PT1.

(Bunched cables to BS4066 PT3 and IEC PT3).

CCC CONDUCTOR STRANDING WEIGHT OVERALL GLAND SINGLE TREFOILCODE SIZE (MM2) (MM) KG/KM DIAMETER SIZE CLEAT CLEAT

(MM) (MM)6181B50 50 19/1.78 540 13.6 25 0.66181B70 70 19/2.14 750 15.6 25 0.76181B95 95 19/2.52 1010 17.5 25 0.7

6181B120 120 37/2.03 1250 19.2 32 0.86181B150 150 37/2.25 1530 21.3 32 0.96181B185 185 37/2.52 1900 23.4 32 1.0 2076181B240 240 61/2.25 2470 26.3 40 1.1 5026181B300 300 61/2.52 3080 29.0 40 1.2 5046181B400 400 61/2.52 3890 32.7 50S 1.4 5066181B500 500 61/3.20 4970 36.6 50S 1.6 5096181B630 630 127/2.52 6370 41.3 50 1.8 5116181B800 800 127/2.85 8150 46.3 63S 2.0 515

6181B1000 1000 127/3.20 9860 53.00 63 R9 519

XLPE INSULATED LOW SMOKE ZERO

HALOGEN SINGLE CORE NON-ARMOURED

MAINS CABLE1000 VOLT

(50MM2 TO 1000MM2)

Temperature limits:-25 to +90°C.

Bending radius:6 x overall diameter.

Core identification:Brown inner/Black outer.

Should not be installed attemperatures below 0°C.

Current ratings, see page 116.

Page 19: 6629983 Cleveland Catalogue

FIXED WIRING AND MAINS CABLESStranded plain annealed compacted circular copper conductor, XLPE insulated,low smoke and zero halogen (LSOH) extruded bedding, aluminium wirearmour, low smoke and zero halogen (LSOH) outer sheath. Black. 600/1000volts grade to BS6724. Flame propagation to BS4066 PT1 and IEC 332 PT1.(Bunched cables to BS4066 PT3 and IEC 332 PT3).

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND SINGLE TREFOILCODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE CLEAT CLEAT

(MM) (MM)6941AB50 50 19/1.78 1 800 17.7 20 0.86941AB70 70 19/2.14 1 940 19.6 25 0.96941AB95 95 19/2.52 1 1220 21.5 25 1.0

6941AB120 120 37/2.03 1 1490 23.2 25 1.26941AB150 150 37/2.25 1 1870 26.3 32 1.2 5026941AB185 185 37/2.52 1 2290 28.7 32 1.4 5046941AB240 240 61/2.25 1 2880 31.4 40 1.4 5056941AB300 300 61/2.52 1 3520 34.1 40 1.8 5076941AB400 400 61/2.85 1 4520 38.9 50S 1.8 5106941AB500 500 61/3.20 1 5680 42.8 50S 1.8 5126941AB630 630 127/2.52 1 7120 47.3 50 2.0 5156941AB800 800 127/2.85 1 9220 53.9 63S R9 519

6941AB1000 1000 127/3.20 1 11270 58.8 635 R10 523

FIXED

WIR

ING

AN

D M

AIN

S CA

BLES

21

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

XLPE INSULATED LOW SMOKE ZERO

HALOGEN SINGLE COREARMOURED MAINS CABLE

(50MM2 TO 1000MM2)

Temperature limits:-25 to +90°C.

Bending radius:6 x overall diameter.

Core identification:Brown inner/Black outer.

Should not be installed attemperatures below 0°C.

Current ratings, see page 111.

Page 20: 6629983 Cleveland Catalogue

SCREENED FIXED WIRING AND MAINS CABLES TO BS 8436Plain annealed stranded copper, XLPE insulated, tinned annealed strandedcopper earth wire, bonded aluminium tube applied longitudinally low smokeand zero halogen (LSOH) outer sheath, to BS EN 50267-1:1998 and BS EN50268-2:2000, UV Stable. 300/500v to BS8436, White.

FIX

ED W

IRIN

G A

ND

MA

INS

CA

BLE

S22

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND 1 HOLE GLANDCODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE CLIP REF

(MM) (MM) REFFSX2X1WH 1.0 7/0.44 2 85 8.60 20S RCHL20 20SA2FSX3X1WH 1.0 7/0.44 3 105 9.40 20S RCHL20 20SA2FSX4X1WH 1.0 7/0.44 4 130 10.00 20 RCHL20 20A2

FSX2X1/5WH 1.5 7/0.53 2 106 9.80 20 RCHL20 20A2FSX3X1/5WH 1.5 7/0.53 3 140 10.40 20 RCHL20 20A2FSX4X1/5WH 1.5 7/0.53 4 158 11.30 20 RCHL20 20A2FSX2X2/5WH 2.5 7/0.67 2 135 10.80 20 RCHL20 20A2FSX3X2/5WH 2.5 7/0.67 3 182 11.10 20 RCHL20 20A2FSX4X2/5WH 2.5 7/0.67 4 259 12.60 20 RCHL20 20A2

FSX2X4WH 4 7/0.85 2 206 11.50 20 RCHL20 20A2FSX3X4WH 4 7/0.85 3 265 13.10 25 RCHL25 25A2FSX4X4WH 4 7/0.85 4 320 13.90 25 RCHL25 25A2FSX2X6WH 6 7/1.04 2 258 13.10 25 RCHL25 25A2FSX3X6WH 6 7/1.04 3 328 14.20 25 RCHL25 25A2FSX4X6WH 6 7/1.04 4 450 14.90 25 RCHL25 25A2

MECHANICALLYPROTECTED

WIRING CABLE

Minimum installation temperature: -10°C.

Maximum continuous conductorsoperating temperature: +90°C.

Core identification:2 core - Brown, Blue.3 core - Brown, Black, Grey.4 core - Brown, Black, Grey, Blue.

*Solid cores available on request.Different sheath and core coloursavailable on request.

10mm2 and 16mm2 available on request

Page 21: 6629983 Cleveland Catalogue

FIXED WIRING AND MAINS CABLESStranded plain annealed circular compacted copper conductors, XLPEinsulated, semi-conducting tape insulated, each core copper tape screened,PVC bedding, galvanised steel wire armour, PVC outer sheath - Red.6350/11000 volts grade to BS6622 and IEC 502/1. Flame retardant to BS 4066PT1 and IEC 332 PT1.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND SINGLE RAYCHEMCODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE CLEAT TERMINATION

(MM) (MM) REFERENCE11KV XLPE3X25RD 25 7/2/14 3 4400 48.8 50 2.0 EPKT 17A3XIH211KV XLPE3X35RD 35 19/1/53 3 4900 51.6 50 R9 EPKT 17B3XIH211KV XLPE3X50RD 50 19/1/78 3 5600 54.6 63S R9 EPKT 17B3XIH211KV XLPE3X70RD 70 19/2/14 3 6500 58.5 63S R10 EPKT 17B3XIH211KV XLPE3X95RD 95 19/2/52 3 7800 62.6 63 R10 EPKT 17C3XIH211KV XLPE3X120RD 120 37/2/03 3 8900 66.6 75S R11 EPKT 17C3XIH211KV XLPE3X150RD 150 37/2/25 3 10000 68.8 75S R11 EPKT 17C3XIH211KV XLPE3X185RD 185 37/2/52 3 11600 74.1 75 R12 EPKT 17C3XIH211KV XLPE3X240RD 240 61/2/25 3 14800 81.2 90 R14 EPKT 17C3XIH211KV XLPE3X300RD 300 61/2/52 3 17300 86.8 90 R15 EPKT 1D3XIH211KV XLPE3X400RD 400 61/2/85 3 19300 93.0 R15 EPKT 17D3XIH2

Stranded plain annealed circular compacted copper conductors, XLPEinsulated, semi-conducting tape insulated, copper tape screen, PVC bedding,aluminium wire armour, PVC outer sheath - Red. 6350/11000 volts grade toBS6622 and IEC 502/1.

Flame retardant to BS4066 PT1 and IEC 332 PT1.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND SINGLE TREFOIL RAYCHEMCODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE CLEAT CLEAT TERMINATION

(MM) (MM) REFERENCE10001 50 19/1.78 1 1200 28.0 32 1.2 503/504 EPKT 17B1XI10002 70 19/2.14 1 1500 29.9 32 1.2 504 EPKT 17B1XI10003 95 19/2.52 1 1600 31.7 32 1.4 506 EPKT 17C1XI10004 120 37/2.03 1 2100 33.3 40 1.4 506 EPKT 17C1XI10005 150 37/2.25 1 2500 35.7 40 1.6 508/509 EPKT 17C1XI10006 185 37/2.52 1 2900 37.5 40 1.6 508/509 EPKT 17C1XI10007 240 61/2.25 1 3600 40.1 50S 1.6 510/511 EPKT 17C1XI10008 300 61/2.52 1 4300 42.4 50S 1.8 512/513 EPKT 17D1XI10009 400 61/2.85 1 5200 45.8 50S 2.0 514 EPKT 17D1XI10010 500 61/3.20 1 6500 50.5 50 2.0 516/517 EPKT 17E1XI10011 630 127/2.52 1 8000 54.7 63S R9 519/521 EPKT 17E1XI

FIXED

WIR

ING

AN

D M

AIN

S CA

BLES

23

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

Temperature limits:up to 90°C.

Bending radius:12 x overall diameter.

Core identification:Brown, Black, Grey tapes.

Should not be installed attemperatures below 0°C.

Current ratings, see page 119.

Temperature limits:up to 90°C.

Bending radius:12 x overall diameter.

Core identification:Brown.

Should not be installed attemperatures below 0°C.

Current ratings, see page 118.

3 COREXLPE INSULATED

MEDIUM VOLTAGEMAINS CABLE 11000 VOLT

(25MM2 TO 400MM2)AND SINGLE CORE

(50MM2 TO 630MM2)

Page 22: 6629983 Cleveland Catalogue

FIX

ED W

IRIN

G A

ND

MA

INS

CA

BLE

S24

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND SINGLE RAYCHEMCODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE CLEAT TERMINATION

(MM) (MM) REFERENCE10115RD 95 19/2.52 3 5800 62.6 63 R10 EPKT 17C3XIH210116RD 120 37/2.03 3 6400 66.6 75S R11 EPKT 17C3XIH210117RD 150 37/2.25 3 7000 68.6 75S R11 EPKT 17C3XIH210118RD 185 37/2.52 3 7800 74.1 75 R12 EPKT 17C3XIH210119RD 240 61/2.25 3 9800 81.2 90 R14 EPKT 17C3XIH210120RD 300 61/2.52 3 11000 86.8 90 R15 EPKT 17D3XIH2

FIXED WIRING AND MAINS CABLESPlain stranded aluminium conductors, XLPE insulated, semi-conducting tapeinsulated, each core copper tape screened, PVC bedding (extruded), galvanisedsteel wire armour, PVC outer sheath.

Red. 6350/11000 volts grade to BS6622 and IEC 502/1. Flame propagation toBS4066 PT1 and IEC 332 PT1

XLPE INSULATED MEDIUM VOLTAGE

MAINS CABLE 11000 VOLT

(95MM2 TO 300MM2)

Temperature limits:up to 90°C.

Bending radius:13 x overall diameter.

Core identification:Brown, Black, Grey tapes.

Should not be installed attemperatures below 0°C.

Current ratings see page 120.

Page 23: 6629983 Cleveland Catalogue

FIXED WIRING AND MAINS CABLESStranded plain annealed compacted circular copper conductors, XLPEinsulated, semi-conducting tape insulated, each core copper tape screened,low smoke and zero halogen (LSOH) bedding, galvanised steel wire armour,low smoke and zero halogen (LSOH) outer sheath - Red. 6350/11000 voltsgrade to BS7835. Flame retardant to BS4066 PT1 and IEC 332 PT1.

(Bunched cables to BS4066 PT3 and IEC 332 PT3).

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND SINGLE RAYCHEMCODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE CLEAT TERMINATION

(MM) (MM) REFERENCE10302RD 35 19/1.53 3 4900 51.6 50 R9 EPKT 17B3XIH210304RD 50 19/1.78 3 5600 54.6 63S R9 EPKT 17B3XIH210306RD 70 19/2.14 3 6500 58.5 63S R10 EPKT 17B3XIH210308RD 95 19/2.52 3 7800 62.6 63 R10 EPKT 17C3XIH210310RD 120 37/2.03 3 8900 66.6 75S R11 EPKT 17C3XIH210312RD 150 37/2.25 3 10000 68.8 75 R11 EPKT 17C3XIH210314RD 185 37/2.52 3 11600 74.1 75 R12 EPKT 17C3XIH210316RD 240 61/2.25 3 14800 81.2 90 R14 EPKT 17C3XIH210318RD 300 61/2.52 3 17300 86.8 90 R15 EPKT 17D3XIH2

Stranded plain annealed compacted circular copper conductor, XLPE insulated,semi-conducting tape insulated, copper tape screen, low smoke and zerohalogen (LSOH) bedding, aluminium wire armour, low smoke and zerohalogen (LSOH) outer sheath - Red. 6350/11000 volts grade to BS7835. Flameretardant to BS4066 PT1 and IEC 332 PT1.

(Bunched cables to BS4066 PT3 and IEC 332 PT3).

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND SINGLE TREFOIL RAYCHEMCODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE CLEAT CLEAT TERMINATION

(MM) (MM) REFERENCE10050 50 19/1.78 1 1200 28.8 32 1.2 504 EPKT 17B1XI10051 70 19/2.14 1 1500 29.9 32 1.2 504 EPKT 17B1XI10052 95 19/2.52 1 1600 31.7 32 1.4 505 EPKT 17C1XI10053 120 37/2.03 1 2100 33.3 40 1.4 506 EPKT 17C1XI10054 150 37/2.25 1 2500 35.7 40 1.6 508 EPKT 17C1XI10055 185 37/2.52 1 2900 37.5 40 1.6 509 EPKT 17C1XI10056 240 61/2.25 1 3600 40.1 50S 1.6 511 EPKT 17C1XI10057 300 61/2.52 1 4300 42.4 50S 1.8 512 EPKT 17D1XI10058 400 61/2.85 1 5200 45.8 50S 2.0 514 EPKT 17D1XI10059 500 61X3.20 1 6500 50.5 50 2.0 517 EPKT 17E1XI10060 630 127X2.52 1 8000 54.7 63S R9 520 EPKT 17E1XI

FIXED

WIR

ING

AN

D M

AIN

S CA

BLES

25

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

Temperature limits:up to 90°C.

Bending radius:15 x overall diameter.

Core identification:Brown.

Should not be installed attemperatures below 0°C.

Current ratings, see page 118.

Temperature limits:up to 90°C.

Bending radius:12 x overall diameter.

Core identification:Brown, Black, Grey tapes.

Should not be installed attemperatures below 0°C.

Current ratings, see page 119.

3 COREXLPE INSULATED LOW

SMOKE ZERO HALOGENMEDIUM VOLTAGE

MAINS CABLE 11000 VOLT(35MM2 TO 300MM2)

AND SINGLE CORE(50MM2 TO 630MM2)

Page 24: 6629983 Cleveland Catalogue

FIX

ED W

IRIN

G A

ND

MA

INS

CA

BLE

S26

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

FIXED WIRING AND MAINS CABLESPlain annealed copper conductors, paper insulated, paper belted, semi-conducting carbon paper tape bedding, lead sheathed, textile compoundbedding, galvanised steel wire armour, PVC outer sheath - Red. 6350/11000volts grade to BS6480/88. Flame propagation to BS4066 PT1 and IEC 332 PT1.

CCC CONDUCTOR STRANDING No. OF WEIGHT OVERALL SINGLE RAYCHEMCODE SIZE (MM2) (MM) CORES KG/KM DIAMETER CLEAT TERMINATION

(MM) REFERENCEPILC3X25RD 25 7/2.14 3 5230 43.6 1.8 EPKT 17A3MIH2PILC3X35RD 35 19/1.53 3 5890 42.3 2.0 EPKT 17B3MIH2PILC3X50RD 50 19/1.78 3 6620 45.6 2.0 EPKT 17B3MIH2PILC3X70RD 70 19/2.14 3 7820 49.7 2.0 EPKT 17B3MIH2PILC3X95RD 95 19/2.52 3 9240 53.3 R9 EPKT 17C3MIH2

PILC3X120RD 120 37/2.03 3 10400 56.2 R9 EPKT 17C3MIH2PILC3X150RD 150 37/2.25 3 11770 59.2 R10 EPKT 17C3MIH2PILC3X185RD 185 37/2.52 3 13550 62.8 R10 EPKT 17C3MIH2PILC3X240RD 240 61/2.25 3 16390 67.8 R11 EPKT 17C3MIH2PILC3X300RD 300 61/2.52 3 19870 73.6 R12 EPKT 17D3MIH2PILC3X400RD 400 61/2.85 3 23700 79.4 R14 EPKT 17D3MIH2

Plain aluminium stranded conductors, paper insulated, paper belted, semi-conducting carbon paper tape bedding, lead sheathed, textile compoundbedding, galvanised steel wire armour, PVC outer sheath - Red. 6350/11000volts grade to BS6480/88. Flame propagation to BS4066 PT1 and IEC 332 PT1.

CCC CONDUCTOR STRANDING No. OF WEIGHT OVERALL SINGLE RAYCHEMCODE SIZE (MM2) (MM) CORES KG/KM DIAMETER CLEAT TERMINATION

(MM) REFERENCE10100RD 95 19/2.52 3 7115 53.2 R9 EPKT 17C3MIH210103RD 185 37/2.52 3 9521 63.5 R11 EPKT 17C3MIH210105RD 300 61/2.52 3 13403 71.5 R12 EPKT 17D3MIH2

PAPER INSULATED MEDIUM VOLTAGE

MAINS CABLE11000 VOLT

(25MM2 TO 400MM2)

Temperature limits:up to 65°C.

Bending radius:13 x overall diameter.

Core identification:White printed numbers on insulating papers.

Should not be installed attemperatures below 0°C.

Temperature limits:up to 65°C.

Bending radius:13 x overall diameter.

Core identification:White printed numbers on insulating papers.

Should not be installed attemperatures below 0°C.

Page 25: 6629983 Cleveland Catalogue

FIXED WIRING AND MAINS CABLESStranded aluminium conductors, paper insulated, (mass impregnated, non-draining type), carbon paper tape belted, corrugated aluminium sheathed, PVCouter sheath. Red. 6350/11000 volts grade to ESI 09-12.

CCC CONDUCTOR STRANDING No. OF WEIGHT OVERALL SINGLE RAYCHEMCODE SIZE (MM2) (MM) CORES KG/KM DIAMETER CLEAT TERMINATION

(MM) REFERENCEPICAS3X95 95 19/2.52 3 3400 49.0 2.0 EPKT 17C3MIH2

PICAS3X120 120 37/2.03 3 4000 53.2 R9 EPKT 17C3MIH2PICAS3X150 150 37/2.25 3 4500 56.6 R9 EPKT 17C3MIH2PICAS3X185 185 37/2.52 3 5200 60.7 R10 EPKT 17C3MIH2PICAS3X240 240 61/2.25 3 6400 66.8 R11 EPKT 17D3MIH2PICAS3X300 300 61/2.52 3 7500 72.5 R12 EPKT 17D3MIH2

FIXED

WIR

ING

AN

D M

AIN

S CA

BLES

27

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

PAPER INSULATED CORRUGATED

ALUMINIUM SHEATHED MEDIUM VOLTAGE

MAINS CABLE 11000 VOLT

(95MM2 TO 300MM2)

Temperature limits:up to 65°C.

Bending radius:13 x overall diameter.

Core identification:White numbers printed on insulating papers.

Should not be installed attemperatures below 0°C.

Page 26: 6629983 Cleveland Catalogue

FIX

ED W

IRIN

G A

ND

MA

INS

CA

BLE

S28

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

FIXED WIRING AND MAINS CABLESPlain annealed stranded copper conductors, XLPE insulated, PVC extrudedbedding, galvanised steel wire armour incorporating tinned copper wires toprovide 60% conductivity of any one phase, PVC outer sheath. Black. 600/1000volts grade generally to BS5467 and BC295.

Flame propagation to BS4066 PT1 and IEC 332 PT1.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND SINGLECODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE CLEAT

(MM) (MM)NCB3X10/1 10 7/1.04 3 896 18.9 20 0.8NCB4X10/1 10 7/1.04 4 1038 20.3 20 0.8NCB3X16/1 16 7/1.70 3 1205 23.1 25 1.0NCB4X16/1 16 7/1.70 4 1675 26.3 25 1.1

NCB3X25 25 7/2.14 3 1550 26.9 25 1.1NCB4X25 25 7/2.14 4 1880 29.1 32 1.2NCB3X35 35 7/2.52 3 1940 29.6 32 1.2NCB4X35 35 7/2.52 4 2350 32.1 32 1.4NCB3X50 50 19/1.78 3 2360 28.4 32 1.2NCB4X50 50 19/1.78 4 2950 31.3 32 1.4NCB3X70 70 19/2.14 3 3120 32.0 32 1.4NCB4X70 70 19/2.14 4 4230 36.8 40 1.6NCB3X95 95 19/2.52 3 4310 36.7 40 1.6NCB4X95 95 19/2.52 4 5390 40.6 50S 1.6

NCB3X120 120 37/2.03 3 5160 40.0 50S 1.6NCB4X120 120 37/2.03 4 6980 45.8 50S 2.0NCB3X150 150 37/2.25 3 6610 45.1 50S 1.8NCB4X150 150 37/2.25 4 8300 49.9 50 2.0NCB3X185 185 37/2.52 3 7920 49.3 50 2.0NCB4X185 185 37/2.52 4 10070 54.9 63S R9NCB3X240 240 61/2.25 3 9930 54.5 63S R9NCB4X240 240 61/2.25 4 12680 61.0 63 R10NCB3X300 300 61/2.52 3 11970 59.5 63 R10NCB4X300 300 61/2.52 4 15380 66.5 75S R11

XLPE INSULATED MAINSCABLE WITH 60% CONDUCTIVITY

IN ARMOUR. (MINES & QUARRIES &

BRITISH COAL)(10MM2 TO 300MM2)

Plain annealed stranded copper conductors, XLPE insulated, PVC extrudedbedding, galvanised steel wire armour incorporating tinned copper wires toprovide 60% conductivity of any one phase, PVC outer sheath. Black.1900/3300 volts grade generally to BS5467 and BC295.

Flame propagation to BS4066 PT1 and IEC 332 PT1.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND SINGLECODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE CLEAT

(MM) (MM)NCB3X16/3 16 7/1.70 3 1600 29.5 32 1.2NCB3X25/3 25 19/1.35 3 2060 32.3 32 1.4NCB3X35/3 35 19/1.53 3 2330 35.0 40 1.4NCB3X50/3 50 19/1.78 3 3040 34.9 40 1.4NCB3X70/3 70 19/2.14 3 3800 38.0 40 1.6NCB3X95/3 95 19/2.52 3 4730 41.4 50S 1.8

NCB3X120/3 120 37/2.03 3 6070 45.6 50S 1.8NCB3X150/3 150 37/2.25 3 7010 48.3 50 2.0NCB3X185/3 185 37/2.52 3 8270 51.6 50 R9NCB3X240/3 240 61/2.25 3 10310 56.5 63S R9NCB3X300/3 300 61/2.25 3 12300 60.7 63 R10

Temperature limits:-15 to +90°C.

Bending radius:up to 16mm2 - 6 x overall diameter.over 25mm2 - 8 x overall diameter.

Core identification:Brown, Black, Grey.

Should not be installed attemperatures below 0°C.

Current ratings, see page 112.

Temperature limits:-15 to +70°C.

Bending radius:up to 16mm2 - 6 x overall diameter.over 16mm2 - 8 x overall diameter.

Core identification: 3 core - Brown, Black, Grey.4 core - Brown, Black, Grey, Blue.

Should not be installed attemperatures below 0°C.

Current ratings, see page 112.

Page 27: 6629983 Cleveland Catalogue

FIXED WIRING AND MAINS CABLESPlain annealed stranded copper conductors, XLPE insulated, lead sheathed,PVC bedding, galvanised steel wire armour, PVC outer sheath. Cores Whitewith Black numbers. 600/1000 volts grade to BS5467 and EEMUA 133. Flame propogation to BS 4066 PT1 and IEC 332 PT1.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND SINGLECODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE CLEAT

(MM) (MM)EEMUA2X1/5 ESI 1.5 7/0.53 2 566 15.3 20S 0.6EEMUA3X1/5 ESI 1.5 7/0.53 3 593 15.8 20 0.6EEMUA4X1/5 ESI 1.5 7/0.53 4 813 16.64 20 0.7EEMUA5X1/5 1.5 7/0.53 5 695 16.8 20 0.7EEMUA7X1/5 1.5 7/0.53 7 1072 17.7 20 0.8EEMUA12X1/5 1.5 7/0.53 12 1387 22.3 25 0.9EEMUA19X1/5 1.5 7/0.53 19 1686 24.8 25 1.0EEMUA27X1/5 1.5 7/0.53 27 2418 30.0 32 1.2EEMUA37X1/5 1.5 7/0.53 37 2850 32.7 40 1.4EEMUA2X2/5ESI 2.5 7/0.67 2 772 16.68 20 0.7EEMUA3X2/5ESI 2.5 7/0.67 3 842 17.21 20 0.7EEMUA4X2/5ESI 2.5 7/0.67 4 934 18.28 25 0.7EEMUA5X2/5 2.5 7/0.67 5 1038 18.4 20 0.8EEMUA7X2/5 2.5 7/0.67 7 1324 20.02 25 0.9EEMUA12X2/5 2.5 7/0.67 12 1750 25.19 32 1.0EEMUA19X2/5 2.5 7/0.67 19 2489 29.9 32 1.2EEMUA27X2/5 2.5 7/0.67 27 3248 34.17 40 1.4EEMUA37X2/5 2.5 7/0.67 37 3840 42.81 50S 1.6

EEMUA5X4 4.0 7/0.85 5 1014 20.6 25 0.9EEMUA7X4 4.0 7/0.85 7 1110 21.5 25 0.9

FIXED

WIR

ING

AN

D M

AIN

S CA

BLES

29

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

XLPE INSULATED LEADSHEATHED CONTROL

CABLE FOR PETRO-CHEMICAL

INDUSTRIES(1.5MM2 TO 4MM2)

Temperature limits:-15 to +90°C.

Bending radius:12 x overall diameter.

Core identification:White with Black numbers.

Page 28: 6629983 Cleveland Catalogue

FIX

ED W

IRIN

G A

ND

MA

INS

CA

BLE

S30

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

FIXED WIRING AND MAINS CABLESPlain annealed stranded copper conductors, XLPE insulated, lead sheathed,PVC bedding, galvanised steel wire armour, PVC outer sheath. Black. 600/1000volts grade to BS5467 and EEMUA 133 (formerly OCMA 4B). Flamepropagation to BS4066 PT1 and IEC 332 PT1.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND SINGLECODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE CLEAT

(MM) (MM)EEMUA2X25 25 7/2.14 2 2094 27.5 32 1.1EEMUA3X25 25 7/2.14 3 2673 30.5 32 1.2EEMUA4X25 25 7/2.14 4 3204 32.5 40 1.4EEMUA2X35 35 19/1.53 2 2868 27.5 32 1.4EEMUA3X35 35 19/1.53 3 3338 31.0 32 1.4EEMUA4X35 35 19/1.53 4 4043 33.5 40 1.4EEMUA2X50 50 19/1.78 2 2783 28.1 32 1.2EEMUA3X50 50 19/1.78 3 3572 34 40 1.4EEMUA4X50 50 19/1.78 4 4456 37.5 40 1.4EEMUA2X70 70 19/2.14 2 3566 31.1 32 1.4EEMUA3X70 70 19/2.14 3 4639 37.5 40 1.4EEMUA4X70 70 19/2.14 4 6160 43.5 50S 1.6EEMUA2X95 95 19/2.52 2 4678 35.1 40 1.4EEMUA3X95 95 19/2.52 3 6023 43 50S 1.6EEMUA4X95 95 19/2.52 4 7592 47.5 50 1.8

EEMUA2X120 120 37/2.03 2 5641 38.5 50S 1.6EEMUA3X120 120 37/2.03 3 7392 46.5 50S 1.8EEMUA4X120 120 37/2.03 4 9802 53 63S 2.0EEMUA2X150 150 37/2.25 2 6660 41.8 50S 1.8EEMUA3X150 150 37/2.25 3 9242 52.5 50 2.0EEMUA4X150 150 37/2.25 4 11757 58 63S R9EEMUA2X185 185 37/2.52 2 8457 47.1 50 2.0EEMUA3X185 185 37/2.52 3 11054 56.5 63S R9EEMUA4X185 185 37/2.52 4 14117 63 63 R10EEMUA2X240 240 61/2.25 2 10286 52.3 63S R9EEMUA3X240 240 61/2.25 3 13792 55.9 63S R9EEMUA4X240 240 61/2.25 4 17700 65.8 75S R11EEMUA2X300 300 61/2.52 2 12245 56.7 63S R9EEMUA3X300 300 61/2.52 3 16519 64.1 63 R11EEMUA4X300 300 61/2.52 4 21173 71.5 75S R12

XLPE INSULATED LEAD SHEATHED MAINS

CABLE FOR PETRO-CHEMICAL

INDUSTRIES(25MM2 TO 300MM2)

Temperature limits:-15 to +90°C.

Bending radius:12 x overall diameter.

Core identification:2 core - Brown, Blue3 core - Brown, Black, Grey.4 core - Brown, Black, Grey, Blue.

Should not be installed attemperatures below 0°C.

Page 29: 6629983 Cleveland Catalogue

FIXED WIRING AND MAINS CABLESPlain annealed stranded copper conductors, XLPE insulated, lead sheathed,PVC bedding, galvanised steel wire armour, PVC outer sheath. Black. 600/1000volts grade to BS5467 and EEMUA 133 (formerly OCMA 4B). Flamepropagation to BS4066 PT1 and IEC 332 PT1.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND SINGLECODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE CLEAT

(MM) (MM)EEMUA2X1/5 1.5 7/0.53 2 690 15.32 20S 0.6EEMUA3X1/5 1.5 7/0.53 3 744 15.76 20 0.6EEMUA4X1/5 1.5 7/0.53 4 813 16.64 20 0.7EEMUA2X2/5 2.5 7/0.67 2 772 16.68 20 0.7EEMUA3X2/5 2.5 7/0.67 3 842 17.21 20 0.7EEMUA4X2/5 2.5 7/0.67 4 934 18.28 25 0.7

EEMUA2X4 4.0 7/0.85 2 883 17.66 20 0.7EEMUA3X4 4.0 7/0.85 3 1190 18.27 20 0.7EEMUA4X4 4.0 7/0.85 4 1310 19.5 25 0.8EEMUA2X6 6.0 7/1.04 2 1001 18.66 25 0.8EEMUA3X6 6.0 7/1.04 3 1122 19.35 25 0.8EEMUA4X6 6.0 7/1.04 4 1402 21.64 25 0.9

EEMUA2X10 10.0 7/1.35 2 1227 20.66 25 0.8EEMUA3X10 10.0 7/1.35 3 1493 22.2 25 0.9EEMUA4X10 10.0 7/1.35 4 1710 24.07 25 1.0EEMUA2X16 16.0 7/1.70 2 1565 23.30 25 1.0EEMUA3X16 16.0 7/1.70 3 1813 24.69 32 1.0EEMUA4X16 16.0 7/1.70 4 2191 26.68 32 1.1

FIXED

WIR

ING

AN

D M

AIN

S CA

BLES

31

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

XLPE INSULATED LEADSHEATHED MAINS CABLE

FOR PETRO-CHEMICALINDUSTRIES

(1.5MM2 TO 16MM2)

Temperature limits:-15 to +90°C.

Bending radius:12 x overall diameter.

Core identification:2 core - Brown, Blue.3 core - Brown, Black, Grey.4 core - Brown, Black, Grey, Blue.

Should not be installed attemperatures below 0°C.

Page 30: 6629983 Cleveland Catalogue

FIX

ED W

IRIN

G A

ND

MA

INS

CA

BLE

S32

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

FIXED WIRING AND MAINS CABLESPlain annealed stranded copper conductors, XLPE insulated, lead sheathed,PVC bedding, galvanised steel wire armour, PVC outer sheath. Black.1900/3300 volts grade to BS5467 and EEMUA 133 (formerly OCMA 4B). Flame propagation to BS4066 PT1 and IEC 332 PT1.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND SINGLECODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE CLEAT

(MM) (MM)EEMUA3X25/3 25 7/2.14 3 3400 32.5 32 1.4EEMUA3X35/3 35 19/1.53 3 3560 38.4 40 1.6EEMUA3X50/3 50 19/1.78 3 4520 38.1 40 1.6EEMUA3X70/3 70 19/2.14 3 5550 41.4 50s 1.8EEMUA3X95/3 95 19/2.52 3 6770 45.0 50s 2.0EEMUA3X120/3 120 37/2.03 3 8390 49.4 50 2.0EEMUA3X150/3 150 37/2.25 3 9630 52.3 50 R9EEMUA3X185/3 185 37/2.52 3 11270 55.8 63s R9EEMUA3X240/3 240 61/2.25 3 13720 60.9 63 R10EEMUA3X300/3 300 61/2.52 3 16380 65.3 75s R11

XLPE INSULATEDLEAD SHEATHED MAINS

CABLE FOR PETRO-CHEMICAL

INDUSTRIES 3300 VOLT

(25MM2 TO 300MM2)

Temperature limits:-15 to +90°C.

Bending radius:12 x overall diameter.

Core identification:Brown, Black, Grey.

Should not be installed attemperatures below 0°C.

Page 31: 6629983 Cleveland Catalogue

FIXED WIRING AND MAINS CABLESSPLIT CONCENTRICPlain annealed stranded copper phase conductor, XLPE insulated surroundedby a concentric layer of plain annealed solid copper neutral conductors. XLPEinsulated and plain annealed solid strand bare copper earth conductors, PVCouter sheath. Black. 600/1000 volts grade to BS 4553/88.

CCC CONDUCTOR STRANDING WEIGHT OVERALL GLANDCODE SIZE (MM2) (MM) KG/KM DIAMETER SIZE

(MM) (MM)4 SPLITCON 4 7/0.85 206 9.6 20S6 SPLITCON 6 7/1.04 281 11.4 20

10 SPLITCON 10 7/1.35 394 12.7 2016 SPLITCON 16 7/1.70 583 14.6 2525 SPLITCON 25 *7/2.14 843 18.7 3235 SPLITCON 35 7/2.52 1300 23.0 40

Straight CONCENTRIC (CNE)Plain annealed stranded copper phase conductor, PVC insulated surrounded bya concentric layer of plain annealed solid copper neutral/earth conductors inconcentric layer, PVC outer sheath. Black. 600/1000 volts grade to BS 4553/88& ESI 09-7.

CCC CONDUCTOR STRANDING WEIGHT OVERALL GLANDCODE SIZE (MM2) (MM) KG/KM DIAMETER SIZE

(MM) (MM)4 STRCON 4 7/0.85 180 9.0 20S6 STRCON 6 7/1.04 230 10.0 20S

16 STRCON 16 7/1.70 440 12.0 2025 STRCON 25 7/2.14 600 15.0 2535 STRCON 35 7/2.25 850 16.0 25

FIXED

WIR

ING

AN

D M

AIN

S CA

BLES

33

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

XLPE INSULATED SINGLEPHASE SPLIT AND

STRAIGHT CONCENTRIC SERVICE CABLE

(4MM2 TO 35MM2)

* Stranding of neutral is the same asphase conductor except 25 sq mmwhich has 11 x 1.70mm.

Conductor identification: Brown Live/Blue Neutral.

Should not be installed attemperatures below 0°C.

Also available in Violet outer sheathin 6mm, 10mm, 16mm & 25mm.

Temperature limits:-15 to +70°C.

Bending radius:10 x overall diameter.

Should not be installed attemperatures below 0°C.

Page 32: 6629983 Cleveland Catalogue

34

Page 33: 6629983 Cleveland Catalogue

FLEXIBLE CABLES

FLEXIB

LE CA

BLES

35

Page 34: 6629983 Cleveland Catalogue

FLEX

IBLE

CA

BLE

S36

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

FLEXIBLE CABLESPVC INSULATED FLEXIBLE CORDS TYPE 318*YPlain annealed flexible copper conductors, PVC insulated, PVC outer sheath.Black or White. 300/500 volts grade to BS6500. (Harmonized code HO5VV-F).Flame propagation to BS4066 PT1 and IEC 332 PT1. (*HO3VV-F)

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLANDCODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE

(MM) (MM)2182Y/5 0.5 16/0.2 2 36 5.4 20/16

2182Y/75 0.75 24/0.2 2 45 5.8 20/162183Y/5 0.5 16/0.2 3 44 5.6 20/16

2183Y/75 0.75 24/0.2 3 55 6.1 20/163182Y/5 0.5 16/0.2 2 52 6.3 20/163183Y/5 0.5 16/0.2 3 5 6.3 20/16

3182Y/75 0.75 24/0.20 2 59 6.8 20/163183Y/75 0.75 24/0.20 3 70 7.2 20/163184Y/75 0.75 24/0.20 4 85 7.7 20/163185Y/75 0.75 24/0.20 5 110 8.5 20S

3182Y1 1.0 24/0.20 2 69 7.2 20/163183Y1 1.0 32/0.20 3 82 7.6 20/163184Y1 1.0 32/0.20 4 105 8.5 20S3185Y1 1.0 32/0.20 5 130 9.1 20S

3182Y1/5 1.5 30/0.25 2 95 8.2 20/163183Y1/5 1.5 30/0.25 3 120 8.9 20S3184Y1/5 1.5 30/0.25 4 150 10.0 20S3185Y1/5 1.5 30/0.25 5 180 11.0 203182Y2/5 2.5 50/0.25 2 145 9.9 20S3183Y2/5 2.5 50/0.25 3 180 10.8 20S3184Y2/5 2.5 50/0.25 4 220 11.3 203185Y2/5 2.5 50/0.25 5 265 12.8 20

PVC INSULATED FLEXIBLE CORDS

TYPE 318*Y & 218*Y(0.5MM2 TO 2.5MM2)

Temperature limits:Fixed - -5 to +60°C.Flexing - +5 to +60°C.

Bending radius:Fixed 2 x overall diameter.Flexing 6 x overall diameter.

Core identification:2 core - Blue, Brown.3 core - Blue, Brown, Green/Yellow.

4 core - Blue, Brown, Black,Green/Yellow.5 core - Blue, Brown, Black, Black,Green/Yellow.

Should not be installed attemperatures below 0°C.

Current ratings, see page 115.

Page 35: 6629983 Cleveland Catalogue

FLEXIB

LE CA

BLES

37

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

FLEXIBLE CABLESPVC INSULATED HEAT RESISTING FLEXIBLE CORDS TYPE 309*YPlain annealed flexible copper conductors heat resisting PVC outer sheath. White300/500 volts grade to BS6141. Flame propagation to BS4066 PT1 and IEC 332 PT1.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLANDCODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE

(MM) (MM)3092Y/5 0.5 16/0.20 2 46 6.3 20/163093Y/5 0.5 16/0.20 3 66 6.5 20/163094Y/5 0.5 16/0.20 4 70 7.2 20/16

3092Y/75 0.75 24/0.20 2 56 6.8 20S3093Y/75 0.75 24/0.20 3 68 7.2 20S3094Y/75 0.75 24/0.20 4 85 7.7 20S

3092Y1 1.0 32/0.20 2 65 7.2 20S3095Y/75 0.75 24/0.2 5 104 8.5 20S

3093Y1 1.0 32/0.20 3 77 7.6 20S3094Y1 1.0 32/0.20 4 100 8.5 20S

3092Y1/5 1.5 30/0.25 2 80 8.2 20S3093Y1/5 1.5 30/0.25 3 100 8.9 20S3094Y1/5 1.5 30/0.25 4 130 10.0 203092Y2/5 2.5 50/0.25 2 135 10.0 20S3093Y2/5 2.5 50/0.25 3 150 10.8 203094Y2/5 2.5 50/0.25 4 195 11.8 20

PVC INSULATED FLEXIBLE CORDS

TYPE 309*Y (0.5MM2 TO 2.5MM2)

Temperature limits:Fixed - -5 to +90°C.Flexing - +5 to +90°C.

Bending radius:Fixed - 2 x overall diameter.Flexing - 6 x overall diameter.

Current ratings, see page 115.

Core identification:2 core - Blue, Brown.3 core - Blue, Brown, Green/Yellow.

4 core - Blue, Brown, Black,Green/Yellow.

Should not be installed attemperatures below 0°C.

Page 36: 6629983 Cleveland Catalogue

FLEX

IBLE

CA

BLE

S38

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

FLEXIBLE CABLESPlain annealed copper conductors, Low smoke and zero halogen (LS0H) insulated,low smoke and zero halogen (LS0H) outer sheath. Black or white. 300/500 voltsgrade (Generally to BS6500) flame propagation to BS4066 PT1 and IEC 332 PT1.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLANDCODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE

(MM) (MM)3182B/75 0.75 24/0.2 2 6.8 59 20/163183B/75 0.75 24/0.2 3 7.2 70 20/163184B/75 0.75 24/0.2 4 7.7 85 20/163185B/75 0.75 24/0.2 5 8.5 110 20S

3182B1 1.00 32/0.2 2 7.2 69 20/163183B1 1.00 32/0.2 3 7.6 82 20/163184B1 1.00 32/0.2 4 8.5 105 20S3185B1 1.0 32/0.2 5 130 9.1 20S

3182B1/5 1.5 30/0.25 2 8.2 95 20/163183B1/5 1.5 30/0.25 3 8.9 120 20S3184B1/5 1.5 30/0.25 4 10 150 20S3185B1/5 1.5 30/0.25 5 11 180 203182B2/5 2.5 50/0.25 2 9.9 145 20S3183B2/5 2.5 50/0.25 3 10.8 180 20S3184B2/5 1.5 50/0.25 4 11.3 220 203185B2/5 2.5 50/0.25 5 265 12.8 20

LOW SMOKEZERO HALOGEN FLEXIBLE

CORDS TYPE 318*B(0.75MM2 TO 2.5MM2)

Temperature limits:-15 to +70°c

Bending radius:Fixed 4x overall diameterFlexing 6x overall diameter

Core identification:2 core - Brown, Blue.3 core - Blue, Brown, Green/Yellow.4 core - Blue, Brown, Black,Green/Yellow.5core - Blue, Brown, Black, Black,Green/Yellow.

Page 37: 6629983 Cleveland Catalogue

FLEXIB

LE CA

BLES

39

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

FLEXIBLE CABLESPlain annealed flexible copper conductors, PVC insulated, PVC sheathed. Grey.300/500 volts grade, generally to BS6500 and VDE 0250.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLANDCODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE

(MM) (MM)YY2X/75 0.75 24/0.20 2 53 6.0 20/16YY3X/75 0.75 24/0.20 3 63 6.3 20/16YY4X/75 0.75 24/0.20 4 76 6.9 20/16YY5X/75 0.75 24/0.20 5 93 7.5 20/16YY7X/75 0.75 24/0.20 7 116 8.2 20/16

YY12X/75 0.75 24/0.20 12 194 11.1 20SYY18X/75 0.75 24/0.20 18 278 13.0 20YY25X/75 0.75 24/0.20 25 379 15.9 25YY34X/75 0.75 24/0.20 34 516 18.2 25YY50X/75 0.75 24/0.20 50 734 21.7 32YY65X/75 0.75 24/0.20 65 912 24.3 32

YY2X1 1.0 32/0.20 2 60 6.2 20/16YY3X1 1.0 32/0.20 3 73 6.5 20/16YY4X1 1.0 32/0.20 4 89 7.1 20/16YY5X1 1.0 32/0.20 5 109 7.8 20/16YY7X1 1.0 32/0.20 7 137 8.5 20S

YY12X1 1.0 32/0.20 12 229 11.5 20YY18X1 1.0 32/0.20 18 331 13.5 25YY25X1 1.0 32/0.20 25 452 16.5 25YY34X1 1.0 32/0.20 34 615 18.9 25YY41X1 1.0 32/0.20 41 770 21.0 32YY50X1 1.0 32/0.20 50 879 22.5 32YY65X1 1.0 32/0.20 65 1171 26.5 40YY2X1/5 1.5 30/0.25 2 77 6.8 20/16YY3X1/5 1.5 30/0.25 3 95 7.2 20/16YY4X1/5 1.5 30/0.25 4 117 7.8 20/16YY5X1/5 1.5 30/0.25 5 144 8.6 20SYY7X1/5 1.5 30/0.25 7 183 9.4 20SYY8X1/5 1.5 30/0.25 8 232 12.5 20

YY10X1/5 1.5 30/0.25 10 265 12.4 20YY12X1/5 1.5 30/0.25 12 307 12.8 20YY18X1/5 1.5 30/0.25 18 461 15.4 25YY25X1/5 1.5 30/0.25 25 627 18.8 25YY34X1/5 1.5 30/0.25 34 850 21.4 32YY50X1/5 1.5 30/0.25 50 1212 25.4 40YY65X1/5 1.5 30/0.25 65 1602 29.5 40

PVC INSULATED FLEXIBLEPOWER AND CONTROL

CABLE TYPE “YY”(0.75MM2 TO 1.5MM2)

Temperature limits:-5 to +70°C.

Bending radius:Static - 6 x overall diameter.Flexing - 15 x overall diameter.

Core identification:2 core - Black with White numbers.3 core and above - Black with Whitenumbers plus Green/Yellow.

Should not be installed attemperatures below -5°C.

Page 38: 6629983 Cleveland Catalogue

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLANDCODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE

(MM) (MM)YY2X2/5 2.5 50/0.25 2 114 8.0 20/16YY3X2/5 2.5 50/0.25 3 143 8.5 20SYY4X2/5 2.5 50/0.25 4 177 9.3 20SYY5X2/5 2.5 50/0.25 5 229 10.6 20SYY7X2/5 2.5 50/0.25 7 293 11.6 20YY8X2/5 2.5 50/0.25 8 333 13.5 25

YY12X2/5 2.5 50/0.25 12 488 15.7 25YY18X2/5 2.5 50/0.25 18 729 18.8 25YY25X2/5 2.5 50/0.25 25 989 22.9 32YY34X2/5 2.5 50/0.25 34 1338 26.0 40

YY3X4 4.0 56/0.30 3 230 11.6 20YY4X4 4.0 56/0.30 4 289 12.0 20YY5X4 4.0 56/0.30 5 357 13.2 20YY7X4 4.0 56/0.30 7 457 14.4 25YY3X6 6.0 84/0.30 3 326 13.2 20YY4X6 6.0 84/0.30 4 480 14.4 25YY5X6 6.0 84/0.30 5 583 16.6 25YY7X6 6.0 84/0.30 7 782 18.6 25

YY3X10 10.0 80/0.40 3 610 16.7 25YY4X10 10.0 80/0.40 4 737 18.8 25YY5X10 10.0 80/0.40 5 914 20.9 32YY3X16 16.0 126/0.40 3 812 18.5 25YY4X16 16.0 126/0.40 4 1087 22.2 32YY5X16 16.0 126/0.40 5 1370 25.0 32YY4X25 25.0 196/0.40 4 960 25.8 32YY5X25 25.0 196/0.40 5 1200 29.3 40YY4X35 35.0 276/0.40 4 1344 28.9 40YY5X35 35.0 276/0.40 5 1680 33.1 50SYY4X50 50.0 396/0.40 4 1920 34.5 50S

FLEXIBLE CABLES

FLEX

IBLE

CA

BLE

S40

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

PVC INSULATED FLEXIBLEPOWER AND CONTROL

CABLE TYPE “YY”(2.5MM2 TO 50MM2)

Temperature limits:-5 to +70°C.

Bending radius:Static - 6 x overall diameter.Flexing - 15 x overall diameter.

Core identification:2 core - Black with White numbers.3 core and above - Black with Whitenumbers plus Green/Yellow.

Should not be installed attemperatures below -5°C.

Page 39: 6629983 Cleveland Catalogue

FLEXIBLE CABLESPlain annealed flexible copper conductors, low smoke and zero halogen (LSOH)insulated, low smoke and zero halogen (LSOH) sheathed. Grey. 300/500 voltsgrade, generally to BS6500 and VDE 0250.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLANDCODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE

(MM) (MM)YY2X1/5LSF 1.5 30/0.25 2 77 6.80 20/16YY3X1/5LSF 1.5 30/0.25 3 95 7.20 20/16YY4X1/5LSF 1.5 30/0.25 4 117 7.80 20/16YY5X1/5LSF 1.5 30/0.25 5 144 8.60 20SYY7X1/5LSF 1.5 30/0.25 7 183 9.40 20S

YY12X1/5LSF 1.5 30/0.25 12 307 12.80 20YY18X1/5LSF 1.5 30/0.25 18 461 15.40 25YY25X1/5LSF 1.5 30/0.25 25 627 18.80 25YY34X1/5LSF 1.5 30/0.25 34 850 21.40 32YY2X2/5LSF 2.5 50/0.25 2 114 8.00 20/16YY3X2/5LSF 2.5 50/0.25 3 143 8.50 20SYY4X2/5LSF 2.5 50/0.25 4 177 9.30 20SYY5X2/5LSF 2.5 50/0.25 5 229 10.60 20S

YY3X4LSF 4.0 56/0.30 3 230 11.60 20

FLEXIB

LE CA

BLES

41

LSOH SHEATHEDFLEXIBLE POWER AND

CONTROL CABLETYPE ‘YY’

(1.5MM2 TO 4.0MM2)

Plain annealed flexible copper conductors, low smoke and zero halogen (LSOH)insulated, mylar taped, tinned copper wire braid, low smoke and zero halogen (LSOH)outer sheath. Grey. 300/500 volts grade, generally to BS6500 and VDE 0250.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLANDCODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE

(MM) (MM)CY2X/75LSF 0.75 24/0.20 2 55 6.50 20SCY3X/75LSF 0.75 24/0.20 3 77 7.00 20SCY4X/75LSF 0.75 24/0.20 4 92 7.60 20SCY2X1/5LSF 1.5 30/0.25 2 86 7.50 20SCY3X1/5LSF 1.5 30/0.25 3 118 8.30 20SCY4X1/5LSF 1.5 30/0.25 4 142 8.90 20SCY5X1/5LSF 1.5 30/0.25 5 171 9.70 20S

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

Temperature limits:-5 to +70°C

Bending radius:Static6 x Overall Diameter

Flexing:15 x Overall Diameter

Core identification:2 Core - Black with white numbers3 Core and aboveBlack with white numbers plusGreen/Yellow

Should not be installed attemperatures below -5°C.

Temperature limits:-5 to 70°C

Bending radius:Static6 x Overall Diameter

Flexible:15 x Overall Diameter

Core identification:2 Core - Black with White numbers3 Core and aboveBlack with White numbers plusGreen/Yellow

Should not be installed attemperatures below -5°C.

Page 40: 6629983 Cleveland Catalogue

FLEX

IBLE

CA

BLE

S42

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

FLEXIBLE CABLESPlain annealed flexible copper conductors, PVC insulated, extruded PVCbedding, galvanised steel wire braid armour, transparent PVC outer sheath.300/500 volts grade generally to BS6500 and VDE 0250 class 5.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLANDCODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE

(MM) (MM)SY2X/75 0.75 24/0.20 2 87 9.0 20/16SY3X/75 0.75 24/0.20 3 121 9.1 20/16SY4X/75 0.75 24/0.20 4 138 9.7 20/16SY5X/75 0.75 24/0.20 5 164 10.3 20/16SY7X/75 0.75 24/0.20 7 190 11.0 20/16

SY12X/75 0.75 24/0.20 12 302 14.3 20SSY18X/75 0.75 24/0.20 18 433 16.8 20SY25X/75 0.75 24/0.20 25 569 19.7 20SY34X/75 0.75 24/0.20 34 684 21.8 25

SY2X1 1.0 32/0.20 2 101 9.2 20/16SY3X1 1.0 32/0.20 3 133 9.3 20/16SY4X1 1.0 32/0.20 4 152 9.9 20/16SY5X1 1.0 32/0.20 5 181 10.6 20/16SY7X1 1.0 32/0.20 7 213 11.3 20/16

SY12X1 1.0 32/0.20 12 361 14.7 20SSY18X1 1.0 32/0.20 18 490 17.3 20SY25X1 1.0 32/0.20 25 647 20.3 20SY34X1 1.0 32/0.20 34 810 21.8 25SY50X1 1.0 32/0.20 50 1112 23.9 25SY2X1/5 1.5 30/0.25 2 114 9.8 20/16SY3X1/5 1.5 30/0.25 3 159 10.0 20/16SY4X1/5 1.5 30/0.25 4 189 10.6 20/16SY5X1/5 1.5 30/0.25 5 220 11.4 20/16SY7X1/5 1.5 30/0.25 7 273 12.6 20/16

SY12X1/5 1.5 30/0.25 12 460 16.6 20SY18X1/5 1.5 30/0.25 18 633 19.2 20SY25X1/5 1.5 30/0.25 25 882 23.2 25SY34X1/5 1.5 30/0.25 34 1108 26.2 25SY50X1/5 1.5 30/0.25 50 1583 32.8 32SY2X2/5 2.5 50/0.25 2 143 11.0 20/16SY3X2/5 2.5 50/0.25 3 218 11.3 20/16SY4X2/5 2.5 50/0.25 4 267 12.5 20/16SY5X2/5 2.5 50/0.25 5 334 13.8 20SSY7X2/5 2.5 50/0.25 7 425 15.0 20S

SY12X2/5 2.5 50/0.25 12 738 22.1 25SY18X2/5 2.5 50/0.25 18 1100 26.5 25SY25X2/5 2.5 50/0.25 25 1450 31.5 32SY34X2/5 2.5 50/0.25 34 1870 33.7 32

PVC INSULATED BRAIDED FLEXIBLE CONTROL CABLE

TYPE “SY”(0.75MM2 TO 2.5MM2)

Temperature limits:-5 to +70°C.

Bending radius:Static - 10 x overall diameter.Flexing - 20 x overall diameter.

Core identification:2 core - Black with White numbers.3 core and above - Black with Whitenumbers plus Green/Yellow.

Should not be installed attemperatures below -5°C.

Page 41: 6629983 Cleveland Catalogue

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLANDCODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE

(MM) (MM)SY3X4 4.0 56/0.30 3 312 14.8 20SSY4X4 4.0 56/0.30 4 384 15.8 20SY5X4 4.0 56/0.30 5 556 18.1 20SY7X4 4.0 56/0.30 7 685 19.6 20SY3X6 6.0 84/0.30 3 407 16.2 20SY4X6 6.0 84/0.30 4 508 17.9 20SY5X6 6.0 84/0.30 5 663 19.3 20SY7X6 6.0 84/0.30 7 789 21.4 25

SY3X10 10.0 80/0.40 3 621 17.2 20CXSY4X10 10.0 80/0.40 4 779 21.9 25SY5X10 10.0 80/0.40 5 1157 25.6 25SY3X16 16.0 126/0.40 3 857 20.6 25CXSY4X16 16.0 126/0.40 4 1384 27.5 32SY5X16 16.0 126/0.40 5 1567 28.3 32SY4X25 25.0 196/0.40 4 2021 33.8 40SY5X25 25.0 196/0.40 5 2464 37.4 40SY4X35 35.0 276/0.40 4 2500 34.5 40SY5X35 35.0 276/0.40 5 3185 36.7 40SY4X50 50.0 396/0.40 4 3518 40.3 505SY4X70 70.0 356/0.50 4 4810 44.2 50SCXSY4X95 95.0 485/0.5 4 6360 50.2 50CX

FLEXIBLE CABLES

FLEXIB

LE CA

BLES

43

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

PVC INSULATED BRAIDEDFLEXIBLE CONTROL CABLE

TYPE “SY”(4MM2 TO 95MM2)

Temperature limits:-5 to +70°C.

Bending radius:Static - 10 x overall diameter.Flexing - 20 x overall diameter.

Core identification:2 core - Black with White numbers.3 core and above - Black with Whitenumbers plus Green/Yellow.

Should not be installed attemperatures below -5°C.

Page 42: 6629983 Cleveland Catalogue

FLEX

IBLE

CA

BLE

S44

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

FLEXIBLE CABLESPlain annealed flexible copper conductors, PVC insulated, mylar taped, tinnedcopper wire braid screen, PVC outer sheath. Grey. 300/500 volts gradegenerally to BS6500 and VDE 0250.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLANDCODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE

(MM) (MM)CY2X/75 0.75 24/0.20 2 55 6.5 20SCY3X/75 0.75 24/0.20 3 77 7.0 20SCY4X/75 0.75 24/0.20 4 92 7.6 20SCY5X/75 0.75 24/0.20 5 121 8.6 20SCY7X/75 0.75 24/0.20 7 145 9.3 20S

CY12X/75 0.75 24/0.20 12 225 11.8 20CY18X/75 0.75 24/0.20 18 328 14.1 25CY25X/75 0.75 24/0.20 25 430 16.8 25

CY34X1 1 32/0.20 34 860 17.1 25CY2X1 1.0 32/0.20 2 78 7.1 20SCY3X1 1.0 32/0.20 3 87 7.2 20SCY4X1 1.0 32/0.20 4 115 8.2 20SCY5X1 1.0 32/0.20 5 136 8.9 20SCY7X1 1.0 32/0.20 7 166 9.6 20S

CY12X1 1.0 32/0.20 12 271 12.6 20CY18X1 1.0 32/0.20 18 381 14.6 25CY25X1 1.0 32/0.20 25 532 17.8 25CY34X1 1.0 32/0.20 34 735 21.1 32CY2X1/5 1.5 30/0.25 2 86 7.5 20SCY3X1/5 1.5 30/0.25 3 118 8.3 20SCY4X1/5 1.5 30/0.25 4 142 8.9 20SCY5X1/5 1.5 30/0.25 5 171 9.7 20SCY7X1/5 1.5 30/0.25 7 217 10.5 20

CY12X1/5 1.5 30/0.25 12 354 13.9 25CY18X1/5 1.5 30/0.25 18 534 16.7 25CY25X1/5 1.5 30/0.25 25 704 19.7 32CY34X1/5 1.5 30/0.25 34 896 22.4 32CY42X1/5 1.5 30/0.25 42 1133 23.9 32CY2X2/5 2.5 50/0.25 2 140 8.1 20/16CY3X2/5 2.5 50/0.25 3 164 9.6 20SCY4X2/5 2.5 50/0.25 4 206 10.4 20SCY5X2/5 2.5 50/0.25 5 252 11.3 20CY7X2/5 2.5 50/0.25 7 327 12.7 20

CY12X2/5 2.5 50/0.25 12 557 17.0 25CY2X4 4.0 56/0.30 2 206 11.7 20CY3X4 4.0 56/0.30 3 269 12.4 20CY4X4 4.0 56/0.30 4 305 12.7 20CY5X4 4.0 56/0.30 5 396 14.9 25CY4X6 6.0 84/0.30 4 411 14.4 25

CY4X10 10.0 80/0.40 4 783 16.2 25

PVC INSULATED BRAIDSCREENED FLEXIBLE

POWER AND CONTROLCABLETYPE “CY”

(0.75MM2 TO 10MM2)

Temperature limits:Static - -20 to +80°C.Flexing - -5 to +70°C.

Bending radius:Static - 6 x overall diameter.Flexing - 15 x overall diameter.

Core identification:2 core - Black with White numbers.3 core and above - Black with Whitenumbers plus Green/Yellow.

Should not be installed attemperatures below -5°C.

Page 43: 6629983 Cleveland Catalogue

FLEXIBLE CABLESPlain annealed stranded circular copper conductors, circular high temperaturePVC outer sheath. UL & CSA approved also to BS6231. 600/1000 volts grade.

CCC CONDUCTOR STRANDING WEIGHT OVERALL GLANDCODE SIZE (MM2) (MM) KG/KM DIAMETER SIZE

(MM) (MM)TRI0/5 0.5 16/0.20 12 2.7 -TRI/75 0.75 24/0.20 15 2.9 -

TRI1 1.0 32/0.20 18 3.1 -TRI1/5 1.5 30/0.25 23 3.3 20/16TRI2/5 2.5 50/0.25 34 3.7 20/16

TRI4 4.0 56/0.30 50 4.3 20/16TRI6 6.0 84/0.30 71 4.9 20/16

TRI10 10.0 80/0.40 123 6.3 20/16TRI16 16.0 126/0.40 207 9.0 20STRI25 25.0 196/0.40 303 10.4 20STRI35 35.0 276/0.40 412 11.9 20TRI50 50.0 396/0.40 607 14.7 25TRI70 70.0 360/0.50 837 16.8 25TRI95 95.0 475/0.50 1079 18.8 25

TRI120 120.0 608/0.50 1280 19.9 32BI150 150 756/0.50 1619 22.9 32BI185 185 925/0.50 1948 24.1 32BI240 240 1221/0.50 2518 28.6 40BI300 300 1525.0.50 3112 32.2 505BI400 400 2013/0.50 4051 36 50

45

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

TRI-RATED SWITCHGEAR AND CONTROL

PANEL WIRE(0.5MM2 TO 400MM2)

FLEXIB

LE CA

BLES

Temperature limits: -30 to +105°C.

Should not be installed attemperatures below 0°C.

Standard colours available:0.5mm2 - 2.5mm2 - Brown, Black,Grey, Blue, Green/Yellow, Red, Yellow,White, Orange, Pink, Violet.

4.0mm2 - 16mm2 - Brown, Black, Grey,Blue, Green/Yellow, Red, Yellow, White.

25.0mm2 - 120mm2 - Brown, Black,Grey, Blue, Green/Yellow, Red, Yellow.

150-400 - Black.

Current ratings on page 124

Page 44: 6629983 Cleveland Catalogue

FLEX

IBLE

CA

BLE

S46

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

FLEXIBLE CABLESTinned annealed flexible copper conductors, ethylene propylene rubber (EPR)insulated, chlorosulphonated polyethylene (CSP) outer sheath. 300/500 voltsgrade to BS6500.

Black or White. Flame propagation to BS4066 PT1 and IEC 332 PT1. Heat andoil resistant and flame retardant (HOFR).

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLANDCODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE

(MM) (MM)3182TQ/75 0.75 24/0.20 2 58 6.3 20/163183TQ/75 0.75 24/0.20 3 72 6.8 20/163184TQ/75 0.75 24/0.20 4 86 7.4 20/16

3182TQ1 1.0 32/0.20 2 80 8.8 20S3183TQ1 1.0 32/0.20 3 90 9.2 20S3184TQ1 1.0 32/0.20 4 110 10.0 20S

3181TQ1/5 1.5 30/0.25 1 38 4.9 20/163182TQ1/5 1.5 30/0.25 2 115 10.5 20S3183TQ1/5 1.5 30/0.25 3 135 11.0 20S3184TQ1/5 1.5 30/0.25 4 170 12.5 203185TQ1/5 1.5 30/0.25 5 200 13.5 253186TQ1/5 1.5 30/0.25 6 335 12.2 203187TQ1/5 1.5 30/0.25 7 366 13.6 25

3180/12TQ1/5 1.5 30/0.25 12 410 17.1 253180/16TQ1/5 1.5 30/0.25 16 570 19.3 253180/20TQ1/5 1.5 30/0.25 20 710 21.8 323180/27TQ1/5 1.5 30/0.25 27 920 28.2 403180/37TQ1/5 1.5 30/0.25 37 1260 28.9 40

3181TQ2/5 2.5 50/0.25 1 41 5.5 20/163182TQ2/5 2.5 50/0.25 2 160 12.5 203183TQ2/5 2.5 50/0.25 3 195 13.0 203184TQ2/5 2.5 50/0.25 4 245 14.0 203185TQ2/5 2.5 50/0.25 5 300 15.5 253187TQ2/5 2.5 50/0.25 7 424 15.8 25

3180/12TQ2/5 2.5 50/0.25 12 600 20.0 323180/16TQ2/5 2.5 50/0.25 16 780 22.5 323180/20TQ2/5 2.5 50/0.25 20 1050 25.4 323180/27TQ2/5 2.5 50/0.25 27 1390 29.1 403180/37TQ2/5 2.5 50/0.25 37 1720 36.8 50S

EPR INSULATED HOFRSHEATHED FLEXIBLE

POWER AND CONTROL CABLE

(0.75MM2 TO 2.5MM2)

Temperature limits:-25 to +90°C.

Bending radius:Fixed - 6 x overall diameter.Flexing - 15 x overall diameter.

Core identification:2 core - Blue, Brown.3 core - Blue, Brown, Green/Yellow.4 core - Grey, Black, Brown,Green/Yellow.5 core - Grey, Black, Brown, Blue,Green/Yellow.6 core and above - Black with Whitenumbers plus Green/Yellow.

Should not be installed attemperatures below -25°C.

Current ratings, see page 115.

Page 45: 6629983 Cleveland Catalogue

FLEXIBLE CABLESTinned annealed flexible copper conductors, ethylene propylene rubber (EPR)insulated, chlorosulphonated polyethylene (CSP) outer sheath. Black. 450/750volts grade to BS6007.

Heat and oil resistant and flame retardant (HOFR). Flame propagation toBS4066 PT1 and IEC 322 PT1.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLANDCODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE

(MM) (MM)6381TQ4 4.0 56/0.30 1 105 9.0 20S6382TQ4 4.0 56/0.30 2 275 15.0 256383TQ4 4.0 56/0.30 3 335 16.0 256384TQ4 4.0 56/0.30 4 420 18.0 256385TQ4 4.0 56/0.30 5 515 19.5 326387TQ4 4.0 56/0.30 7 773 21.6 32

6380/12TQ4 4.0 56/0.30 12 1183 26.2 40

47

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

EPR INSULATED HEAVY DUTY

HOFR SHEATHED FLEXIBLEMAINS CABLE (4MM2)

FLEXIB

LE CA

BLES

Temperature limits:-25 to +90°C.

Bending radius:Fixed - 6 x overall diameter.Flexing - 7 x overall diameter.

Core identification:2 core - Blue, Brown.3 core - Blue, Brown, Green/Yellow.4 core - Grey, Black, Brown,Green/Yellow.5 core - Grey, Black, Brown, Blue,Green/Yellow.6 core and above - Black with Whitenumbers plus Green/Yellow.

Current ratings, see page 123.

Page 46: 6629983 Cleveland Catalogue

FLEX

IBLE

CA

BLE

S48

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

FLEXIBLE CABLESTinned annealed flexible copper conductors, ethylene propylene rubber (EPR)insulated, chlorosulphonated polyethylene (CSP) outer sheath. Black. 450/750volts grade to BS6007.

Heat and oil resistant and flame retardant (HOFR). Flame propagation toBS4066 PT1 and IEC 322 PT1.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLANDCODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE

(MM) (MM)6381TQ6 6 84/0.30 1 130 11.0 20S6382TQ6 6 84/0.30 2 370 15.6 256383TQ6 6 84/0.30 3 450 16.6 256384TQ6 6 84/0.30 4 565 18.5 256385TQ6 6 84/0.30 5 690 20.5 326387TQ6 6 84/0.30 7 904 25.7 406388TQ6 6 84/0.30 8 1040 27.2 40

6381TQ10 10 80/0.40 1 200 12.5 206382TQ10 10 80/0.40 2 690 20.6 326383TQ10 10 80/0.40 3 835 22.1 326384TQ10 10 80/0.40 4 1020 24.1 326385TQ10 10 80/0.40 5 1240 26.5 406381TQ16 16 126/0.40 1 275 14.5 256382TQ16 16 126/0.40 2 910 23.2 326383TQ16 16 126/0.40 3 1120 24.8 326384TQ16 16 126/0.40 4 1380 27.1 406385TQ16 16 126/0.40 5 1695 30.1 406381TQ25 25 196/0.40 1 400 16.5 256382TQ25 25 196/0.40 2 1290 27.4 406383TQ25 25 196/0.40 3 1600 29.3 406384TQ25 25 196/0.40 4 2140 32.5 50S6385TQ25 25 196/0.40 5 2470 36.1 50S6381TQ35 35 276/0.40 1 520 18.5 256382TQ35 35 276/0.40 2 1308 30.4 406383TQ35 35 276/0.40 3 2080 32.9 50S6384TQ35 35 276/0.40 4 2610 36.5 50S6385TQ35 35 276/0.40 5 3187 40.5 506381TQ50 50 396/0.40 1 730 21.0 326383TQ50 50 396/0.40 3 2890 38.5 506384TQ50 50 396/0.40 4 3650 42.6 506385TQ50 50 396/0.40 5 4450 47.3 63S6381TQ70 70 360/0.50 1 980 23.5 326383TQ70 70 360/0.50 3 3850 43.6 63S6384TQ70 70 360/0.50 4 4880 48.6 63S6385TQ70 70 360/0.50 5 5938 54.0 636381TQ95 95 475/0.50 1 1270 26.0 406383TQ95 95 475/0.50 3 4970 50.0 636384TQ95 95 475/0.50 4 6390 56.0 75S6385TQ95 95 475/0.50 5 7924 62.0 75

6381TQ120 120 608/0.50 1 1570 28.5 406383TQ120 120 608/0.50 3 6350 56.8 75S6384TQ120 120 608/0.50 4 7750 59.9 75S6381TQ150 150 756/0.50 1 1960 31.5 406383TQ150 150 756/0.50 3 7700 59.9 75S6384TQ150 150 756/0.50 4 9780 66.8 756381TQ185 185 925/0.50 1 2380 34.5 50S6383TQ185 185 925/0.50 3 9350 65.9 756384TQ185 185 925/0.50 4 11900 73.5 906381TQ240 240 1221/0.50 1 3100 38.0 506383TQ240 240 1221/0.50 3 12000 74.7 906384TQ240 240 1221/0.50 4 15330 83.26381TQ300 300 1525/0.50 1 3790 41.5 506383TQ300 300 1525/0.50 3 14910 83.26384TQ300 300 1525/0.50 4 19030 92.86381TQ400 400 2013/0.50 1 4880 46.5 63S6381TQ500 500 1769/0.60 1 6070 51.5 636381TQ630 630 2257/0.60 1 7460 56.5 75S

Temperature limits:-25 to +90°C.

Bending radius:Fixed - 5 x overall diameter.Flexing - 7 x overall diameter.

Core identification:2 core - Blue, Brown.3 core - Blue, Brown, Green/Yellow.

4 core - Grey, Black, Brown,Green/Yellow.5 core - Grey, Black, Brown, Blue,Green/Yellow.6 core and above - Black with Whitenumbers plus Green/Yellow.

Should not be installed attemperatures below -25°C.

EPR INSULATED HOFR SHEATHED

POWER AND CONTROL CABLE

(6MM2 TO 630MM2)

Page 47: 6629983 Cleveland Catalogue

FLEXIBLE CABLESPlain annealed flexible copper conductors, rubber insulated, heavy dutypolychloroprene (PCP) outer sheath 450/750 volts grade. Black. Harmonizedcode type HO7RN-F.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLANDCODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE

(MM) (MM)3182P1/5 1.5 30/0.25 2 132 9.3 203183P1/5 1.5 30/0.25 3 165 10.3 20S3184P1/5 1.5 30/0.25 4 200 11.2 20S3185P1/5 1.5 30/0.25 5 240 12.3 203187P1/5 1.5 30/0.25 7 385 14.6 25

3180/12P1/5 1.5 30/0.25 12 520 20.3 323182P2/5 2.5 50/0.25 2 193 12.0 203183P2/5 2.5 50/0.25 3 235 11.8 203184P2/5 2.5 50/0.25 4 290 12.6 203185P2/5 2.5 50/0.25 5 345 14.3 253187P2/5 2.5 50/0.25 7 520 16.6 25

3180/12P2/5 2.5 50/0.25 12 810 22.0 323182P4 4.0 56/0.30 2 275 15.0 253183P4 4.0 56/0.30 3 320 13.7 253184P4 4.0 56/0.30 4 395 15.1 253185P4 4.0 56/0.30 5 485 16.9 256382P6 6.0 84/0.30 2 350 18.5 256383P6 6.0 84/0.30 3 495 15.2 256384P6 6.0 84/0.30 4 610 16.9 256385P6 6.0 84/0.30 5 760 18.8 25

6381P10 10 80/0.40 1 230 10.7 20S6382P10 10 80/0.40 2 640 24.0 326383P10 10 80/0.40 3 880 21.9 326384P10 10 80/0.40 4 1060 24.0 326385P10 10 80/0.40 5 1300 25.5 326381P16 16 126/0.40 1 320 12.0 206382P16 16 126/0.40 2 850 27.5 406383P16 16 126/0.40 3 1090 24.7 326384P16 16 126/0.40 4 1345 27.0 406385P16 16 126/0.40 5 1680 30.0 406381P25 25 196/0.40 1 450 14.1 256382P25 25 196/0.40 2 1210 31.5 406383P25 25 196/0.40 3 1394 29.4 406384P25 25 196/0.40 4 1995 32.6 50S6385P25 25 196/0.40 5 2470 36.1 50S6381P35 35 276/0.40 1 605 15.8 256383P35 35 276/0.40 3 1850 32.8 50S6384P35 35 276/0.40 4 2645 36.3 50S6385P35 35 276/0.40 5 2930 39.8 506381P50 50 396/0.40 1 825 18.3 256384P50 50 396/0.40 4 3635 41.9 506381P70 70 360/0.50 1 1090 20.7 326384P70 70 360/0.50 4 4830 48.2 63S6381P95 95 475/0.50 1 1405 23.4 326384P95 95 475/0.50 4 6320 55.0 75S

6381P120 120 608/0.50 1 1745 25.6 406381P150 150 756/0.50 1 1824 28.3 406381P185 185 925/0.50 1 2202 31.0 406381P240 240 1221/0.50 1 2847 34.5 50S6381P300 300 1525/0.50 1 3495 37.7 50

FLEXIB

LE CA

BLES

49

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

RUBBER INSULATED NEOPRENE SHEATHED

FLEXIBLE POWER CABLE

(1.5MM2 TO 300MM2)

Temperature limits:-25 to +85°C.

Bending radius:Static - 6 x overall diameter.Flexing - 15 x overall diameter.

Core identification:2 core - Blue, Brown.3 core - Blue, Brown, Green/Yellow.

4 core - Grey, Black, Brown,Green/Yellow.5 core - Grey, Black, Brown, Blue,Green/Yellow.6 core and above - Black with Whitenumbers plus Green/Yellow.

Should not be installed attemperatures below 0°C.

Page 48: 6629983 Cleveland Catalogue

FLEX

IBLE

CA

BLE

S50

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

FLEXIBLE CABLESFlexible tinned annealed copper conductors, ethylene propylene rubberinsulated, chlorosulphonated polyethylene bedding (CSP), tinned copper wirebraid screen, chlorosulphonated polyethylene (CSP) outer sheath. 300/500volts grade to BS6500/75 and 450/750 Volts grade to BS6007/75 (whereapplicable). Black. Flame propogation to BS 4066 PT1 and IEC 332 PT1. Heat and oil resistant and flame retardant (HOFR).

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLANDCODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE

(MM) (MM)3802TQ1 1.0 32/0.20 2 170 11.1 20/163803TQ1 1.0 32/0.20 3 200 11.4 20/163804TQ1 1.0 32/0.20 4 230 12.1 20/16

3802TQ1/5 1.5 30/0.25 2 225 12.3 20/163803TQ1/5 1.5 30/0.25 3 270 13.1 20S3804TQ1/5 1.5 30/0.25 4 320 14.2 20S3802TQ2/5 2.5 50/0.25 2 300 14.8 20S3803TQ2/5 2.5 50/0.25 3 350 15.6 203804TQ2/5 2.5 50/0.25 4 420 17.0 20

3803TQ4 4.0 56/0.30 3 715 21.3 253804TQ4 4.0 56/0.30 4 865 23.6 256803TQ6 6.0 84/0.30 3 973 24.8 256804TQ6 6.0 84/0.30 4 1166 27.1 32

6803TQ10 10.0 90/0.40 3 1592 30.7 326804TQ10 10.0 90/0.40 4 1878 33.3 406803TQ16 16.0 126/0.40 3 1992 33.8 406804TQ16 16.0 126/0.40 4 2452 37.2 40

EPR INSULATED BRAIDEDSCREEN FLEXIBLE MAINS

AND CONTROL CABLE(1.0MM2 TO 16MM2)

Temperature limits:-25 to +90°C.

Bending radius:8 x overall diameter.

Core identification:2 core - Blue, Brown.3 core - Blue, Brown, Green/Yellow.4 core - Grey, Black, Brown, Blue,Green/Yellow.

Should not be installed attemperatures below 0°C.

Current ratings, see page 122&123.

Page 49: 6629983 Cleveland Catalogue

FLEXIBLE CABLESFlexible tinned annealed copper conductors composite ethylene propylene rubberchlorosulphonated polyethylene (EPR-CSP) insulation to BS6195/69 Type 4.

A. 300/500 volts grade E. 3800/6600 volts gradeC. 600/1000 volts grade F. 6350/11000 volts gradeD. 1900/3300 volts grade

CONDUCTOR RADIAL THICKNESS OF INSULATION VOLTAGE CATEGORY

SIZE STRANDING MAX APPROX. A C D E F CCC CODE (MM2) (MM2) DIA. OF DIA. OF (MM) (MM) (MM) (MM) (MM)

WIRES COND. (MM) (MM)

0.5 16/0.20 0.21 0.93 0.8 1.4 - - -0.75 24/0.20 0.21 1.14 0.8 1.4 - - -1.0 32/0.20 0.21 1.32 0.8 1.4 - - -

TYPE 4 1/5 1.5 30/0.25 0.26 1.60 0.8 1.4 - - -TYPE 4 2/5 2.5 50/0.25 0.26 2.00 0.9 1.4 2.8 - -

TYPE 4 4 4 56/0.30 0.31 2.6 1.0 1.4 - -TYPE 4 6 6 84/0.30 0.31 3.6 1.0 1.5 - - -

TYPE 4 10 10 80/0.40 0.41 4.6 1.2 1.5 - - -TYPE 4 16 16 126/0.40 0.41 5.7 - 1.5 2.8 5.0 7.6TYPE 4 25 25 196/0.40 0.41 7.1 - 1.6 2.8 5.0 7.6TYPE 4 35 35 276/0.40 0.41 8.5 - 1.6 2.8 5.0 7.6TYPE 4 50 50 396/0.40 0.41 10.3 - 1.7 2.8 5.0 7.6TYPE 4 70 70 360/0.50 0.51 12.4 - 1.8 2.8 5.0 7.6TYPE 4 95 95 475/0.50 0.51 14.5 - 2.0 3.0 5.0 7.6

TYPE 4 120 120 608/0.50 0.51 16.0 - 2.2 3.0 5.0 7.6TYPE 4 150 150 756/0.50 0.51 18.0 - 2.3 3.0 5.0 7.6TYPE 4 185 185 925/0.50 0.51 20.0 - 2.4 3.0 5.0 7.6TYPE 4 240 240 1221/0.50 0.51 23.0 - 2.4 3.0 5.0 7.6TYPE 4 300 300 1525/0.50 0.51 26.0 - 2.6 3.0 - -TYPE 4 400 400 2013/0.50 0.51 30.0 - 2.8 3.0 - -

MINIMUM OVERALL DIAMETER WEIGHT VOLTAGE CATEGORY VOLTAGE CATEGORY

CCC CODE A C D E F A C D E F(MM) (MM) (MM) (MM) (MM) KG/KM KG/KM KG/KM KG/KM KG/KM

3.3 4.5 - - - 12 17 - - -3.5 4.7 - - - 16 21 - - -3.7 4.9 - - - 19 24 - - -

TYPE 4 1/5 4.0 5.2 - - - 25 30 - - -TYPE 4 2/5 4.6 5.6 8.5 - - 37 41 76 - -

TYPE 4 4 5.4 6.3 - - - 57 66 - - -TYPE 4 6 6.5 7.5 - - - 80 93 - - -

TYPE 4 10 7.9 8.5 - - - 130 136 - - -TYPE 4 16 - 9.6 12.4 17.2 22.9 - 206 255 384 566TYPE 4 25 - 11.4 13.8 18.6 24.1 - 300 351 495 680TYPE 4 35 - 12.8 15.2 20.0 25.5 - 406 458 613 810TYPE 4 50 - 14.8 17.1 21.1 27.3 - 573 616 796 997TYPE 4 70 - 17.2 19.2 24.2 29.4 - 793 820 1020 1237TYPE 4 95 - 19.7 22.0 26.3 31.5 - 1028 1097 1287 1520

TYPE 4 120 - 21.9 23.5 27.8 33.3 - 1285 1340 1542 1804TYPE 4 150 - 24.1 25.5 29.8 35.3 - 1562 1635 1853 2131TYPE 4 185 - 26.3 27.5 32.1 37.3 - 1914 1973 2225 2503TYPE 4 240 - 29.3 30.5 35.1 40.3 - 2431 2504 2782 3081TYPE 4 300 - 33.0 33.8 - - - 3024 3098 - -TYPE 4 400 - 37.4 37.8 - - - 3948 4045 -

FLEXIB

LE CA

BLES

51

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

EPR INSULATED FLEXIBLE COIL LEAD

(0.5MM2 TO 400MM2)

Temperature limits:-20 to +90°C.

Bending radius:6 x overall diameter.

Should not be installed attemperatures below -25°C.

Page 50: 6629983 Cleveland Catalogue

FLEX

IBLE

CA

BLE

S52

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

FLEXIBLE CABLESTinned annealed flexible circular copper conductors, ethylene propylenerubber (EPR) insulated, chlorosulphonated polyethylene (CSP) outer sheath.Orange. Ref 0361TQ.

To BS638 Part 4.

CCC CONDUCTOR STRANDING WEIGHT OUTSIDE GLANDCODE SIZE (MM2) (MM) KG/KM DIAMETER SIZE

(MM) (MM)0361TQ16OR 16 513/0.20 235 11.5 20S0361TQ25OR 25 783/0.20 330 13.0 200361TQ35OR 35 1107/0.20 440 14.5 250361TQ50OR 50 1566/0.20 610 17.0 250361TQ70OR 70 2214/0.20 840 19.5 320361TQ95OR 95 2997/0.20 1120 22.0 32

0361TQ120OR 120 608/0.50 1410 24.0 320361TQ185OR 185 925/0.50 2100 29.0 40

EPR INSULATED FLEXIBLE WELDING CABLE

TYPE 0361TQ(16MM2 TO 185MM2)

Temperature limits:-20 to +85°C.

Bending radius:6 x overall diameter.

Page 51: 6629983 Cleveland Catalogue

FLEXIB

LE CA

BLES

53

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

FLEXIBLE CABLESRUBBER INSULATED FLAT CABLEFlexible plain copper conductors, thermoplastic rubber insulated (TPR)thermoplastic outer sheath (TPR). Black. 600/1000 volts grade.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL MAX CURRENTCODE SIZE (MM2) (MM) CORES KG/KM DIMENSIONS RATINGS

(MM) (AMPS)FLAT4X1/5R 1.5 30/0.25 4 110 16X5 22

FLAT12X1/5R 1.5 30/0.25 12 320 29X5 12FLAT4X2/5R 2.5 50/0.25 4 170 19X6 30FLAT7X2/5R 2.5 50/0.25 7 300 33X7 20

FLAT12X2/5R 2.5 50/0.25 12 490 51X6 20FLAT4X4R 4 56/0.30 4 250 21X7 40FLAT4X6R 6 84/0.30 4 330 24X7 52

FLAT4X10R 10 80/0.40 4 550 29X9 70FLAT4X16R 16 126/0.40 4 800 35X10 95FLAT4X25R 25 196/0.40 4 1350 46X14 127FLAT4X35R 35 276/0.40 4 1800 51X15 157FLAT4X50R 50 396/0.40 4 2400 56X17 190FLAT4X70R 70 360/0.50 4 3250 63X18 242

RUBBER INSULATED FLAT CABLE

(1.5MM2 TO 70MM2)AND PVC INSULATED

FLAT CABLE(1.5MM2 TO 95MM2)

PVC INSULATED FLAT CABLEFlexible plain copper conductors, PVC insulated, special PVC outer sheath. Black.450/750 volts grade type H07VVH6-F. CENELEC HD 359 S2 IEC 227 part 6.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL MAX CURRENTCODE SIZE (MM2) (MM) CORES KG/KM DIMENSIONS RATINGS

(MM) (AMPS)FLAT4X1/5V 1.5 30/0.25 4 150 15X5 20

FLAT12X1/5V 1.5 30/0.25 12 420 41X5 11FLAT4X2/5V 2.5 50/0.25 4 210 19X6 27

FLAT12X2/5V 2.5 50/0.25 12 620 51X6 16FLAT4X4V 4 56/0.30 4 300 21X7 36FLAT4X6V 6 84/0.30 4 385 23X7 48

FLAT4X10V 10 80/0.40 4 620 29X9 63FLAT4X16V 16 126/0.40 4 990 37X11 85FLAT4X25V 25 196/0.40 4 1550 46X14 112FLAT4X35V 35 276/0.40 4 2030 51X15 138FLAT4X50V 50 396/0.40 4 2650 56X17 168FLAT4X70V 70 360/0.50 4 3650 63X18 213FLAT4X95V 95 475/0.50 4 4550 73X21 258

Temperature limits:-35 to +85°C.

Bending radius:10 x overall diameter.

Core identification:4 core - Black, Grey, Brown,Green/Yellow.

7 and 12 core - Black cores withWhite numbers and oneGreen/Yellow.

Should not be installed attemperatures below 0°C.

Temperature limits:-25 to +70°C.

Bending radius:10 x overall diameter.

Core identification:4 core - Black, Grey, Brown,Green/Yellow.

12 core - Black cores with whitenumbers and one Green/Yellow.

Should not be installed attemperatures below 0°C.

Page 52: 6629983 Cleveland Catalogue

FLEXIBLE CABLESFlexible tinned annealed copper conductors, silicone insulated, silicone outersheath. 300/500 volts grade to VDE 0250 PT816.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLANDCODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE

(MM) (MM)BIHF2X/75 0.75 24/0.20 2 53.4 6.5 20/16BIHF3X/75 0.75 24/0.20 3 63.7 6.9 20/16BIHF4X/75 0.75 24/0.20 4 83.6 7.9 20/16BIHF5X/75 0.75 24/0.20 5 101.2 8.6 20SBIHF7X/75 0.75 24/0.20 7 124.9 9.3 20S

BIHF2X1 1.0 32/0.20 2 59.9 6.7 20/16BIHF3X1 1.0 32/0.20 3 78.3 7.5 20/16BIHF4X1 1.0 32/0.20 4 94.6 8.1 20SBIHF5X1 1.0 32/0.20 5 116.1 8.9 20SBIHF7X1 1.0 32/0.20 7 144.3 9.6 20S

BIHF2X1/5 1.5 30/0.25 2 82.0 7.6 20/16BIHF3X1/5 1.5 30/0.25 3 98.0 8.0 20/16BIHF4X1/5 1.5 30/0.25 4 122.0 8.8 20SBIHF5X1/5 1.5 30/0.25 5 148.0 9.6 20SBIHF7X1/5 1.5 30/0.25 7 187.0 10.4 20SBIHF2X2/5 2.5 50/0.25 2 135.0 8.9 20SBIHF3X2/5 2.5 50/0.25 3 152.0 9.1 20SBIHF4X2/5 2.5 50/0.25 4 188.0 10.1 20SBIHF5X2/5 2.5 50/0.25 5 230.0 10.9 20SBIHF7X2/5 2.5 50/0.25 7 293.0 13.1 20

FLEX

IBLE

CA

BLE

S54

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

SILICONE INSULATED FLEXIBLE CABLE

(0.75MM2 TO 2.5MM2)

Temperature limits:-60 to +180°C.

Bending radius:Fixed - 5 x overall diameter.Flexing - 15 x overall diameter.

Core identification:2 core - Blue, Brown.3 core - Blue, Brown, Green/Yellow.4 core - Grey, Black, Brown,Green/Yellow.5 core and above - Grey, Black, Brown,Blue, Green/Yellow6 core and above - Black with Whitenumbers plus Green/Yellow.

Should not be installed attemperatures below 0°C.

Page 53: 6629983 Cleveland Catalogue

55

INSTRUMENTATION,CONTROL ANDCOMMUNICATIONCABLES

INSTR

UM

ENTATIO

N, CO

NTRO

L AN

D CO

MM

UN

ICATIO

N C

AB

LES

Page 54: 6629983 Cleveland Catalogue

INST

RU

MEN

TATI

ON

, CO

NTR

OL

AN

D C

OM

MU

NIC

ATIO

N C

AB

LES

56

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

INSTRUMENTATION, CONTROL ANDCOMMUNICATION CABLESPART 1 CONSTRUCTIONPlain annealed flexible copper conductors, polyethylene insulated, laid up toform pairs, collective aluminium/mylar tape screen complete with 0.5mm2

drain wire, PVC outer sheath reduced propagation, Blue or Black to BS5308Part 1 Type 1. Flame propagation to BS4066 PT1 and IEC 332 PT1. (Bunchedcables to BS4066 PT3 and IEC 332 PT3).

PART 2 CONSTRUCTIONPlain annealed flexible copper conductors, PVC insulated, laid up to form pairs,collective aluminium/mylar tape screen complete with 0.5mm2 drain wire,PVC outer sheath reduced propagation. Blue or Black to BS5308 Part 2 Type1.Flame propagation to BS4066 PT3 and IEC 332 PT3.

BS5308 PART 1, LSFPlain annealed flexible copper conductors, polyethylene insulated, laid up to formpairs, collective aluminium/mylar tape screen complete with 0.5mm2 drain wire,low smoke and fume (LSF) sheath, Blue or Black, to BS5308 Part 1, Type 1 LSF.

CCC CODE CONDUCTOR STRANDING NO. OF WEIGHT OUTSIDE GLANDPT1 PT2 SIZE (MM2) (MM) PAIRS KG/KM DIAMETER SIZE

(MM) (MM)7100 7300 0.5 16/0.20 1 60 6.4 20/167101 7301 0.5 16/0.20 2 80 7.3 20/167102 7302 0.5 16/0.20 5 200 12.5 207103 7303 0.5 16/0.20 10 340 16.6 257104 7304 0.5 16/0.20 20 570 21.7 327105 7305 0.5 16/0.20 30 790 26.3 407106 7306 0.5 16/0.20 50 1270 33.3 50S7107 7307 0.5 16/0.20 1 TRIPLE 69 6.6 20/167136 7336 0.75 24/0.20 1 75 6.7 20/167137 7337 0.75 24/0.20 2 100 7.7 20/167138 7338 0.75 24/0.20 5 250 13.7 257139 7339 0.75 24/0.20 10 450 18.1 257140 7340 0.75 24/0.20 20 800 23.9 327141 7341 0.75 24/0.20 30 1130 28.9 407142 7342 0.75 24/0.20 50 1840 36.8 50S7143 7343 0.75 24/0.20 1 TRIPLE 88 6.9 20/167173 7373 1.5 7/0.53 1 100 7.7 20/167174 7374 1.5 7/0.53 2 150 9.1 20S7175 7375 1.5 7/0.53 5 360 15.8 257176 7376 1.5 7/0.53 10 670 21.0 327177 7377 1.5 7/0.53 20 1230 27.9 40N/A N/A 1.5 7/0.53 30 1720 33.7 50SN/A N/A 1.5 7/0.53 50 2750 43.6 63S

7178 7378 1.5 7/0.53 1 TRIPLE 128 8.1 20/16

CONTROL ANDINSTRUMENTATION CABLE

NON-ARMOURED WITHCOLLECTIVE SCREEN

(0.5MM2 TO 1.5MM2)

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLANDCODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE

(MM) (MM)7246 0.75 24/0.20 1 75 6.7 20/167247 0.75 24/0.20 2 100 7.7 20/167248 0.75 24/0.20 5 250 13.7 257249 0.75 24/0.20 10 450 18.1 257250 0.75 24/0.20 20 800 23.9 32

Temperature limits:-20 to +65°C.

Bending radius:5 x overall diameter.

Core identification:Part 1 colour code chart on page 62Part 2 colour code chart on page 63

Should not be installed attemperatures below 0°C.

Page 55: 6629983 Cleveland Catalogue

INSTRUMENTATION, CONTROL ANDCOMMUNICATION CABLESBS5308 PART 1, TYPE 1Plain annealed flexible copper conductors, polyethylene insulated, laid up toform pairs, each pair individually aluminium/mylar foil tape screened,complete with 0.5mm2 drain wire, collective aluminium/mylar foil tape screencomplete with 0.5mm2 drain wire, PVC outer sheath reduced propagation.Blue or Black. Flame propagation to BS4066 PT1 and IEC 332 PT1. (Bunchedcables to BS4066 PT3 and IEC 332 PT3).

BS5308 PART 2, TYPE 1Plain annealed flexible copper conductors, PVC insulated, laid up to form pairs,each pair individually aluminium/mylar foil tape screened complete with0.5mm2 drain wire, collective aluminium/mylar foil tape screen complete with0.5mm2 drain wire, PVC outer sheath reduced propagation. Blue or Black.Flame propagation to BS4066 PT1 and IEC 332 PT1. (Bunched cables to BS4066PT3 and IEC 332 PT3).

BS5308 PART 1, TYPE 1 LS0HPlain annealed flexible copper conductors, polyethylene insulated, laid up toform pairs, each pair individually aluminium/mylar tape screened. Completewith 0.5mm2 drain wire, collective aluminium/mylar tape screen completewith 0.5mm2 drain wire, low smoke zero halogen (LS0H) outer sheath, Black orBlue, generally to BS5308 Part 1, Type 1 LS0H.

CCC CODE CONDUCTOR STRANDING NO. OF WEIGHT OUTSIDE GLANDPT1 PT2 SIZE (MM2) (MM) PAIRS KG/KM DIAMETER SIZE

(MM) (MM)7112 7312 0.5 16/0/20 2 160 11.4 20S7113 7313 0.5 16/0/20 5 250 14.6 257114 7314 0.5 16/0/20 10 480 20.5 327115 7315 0.5 16/0/20 20 780 26.7 407116 7316 0.5 16/0/20 30 1100 31.7 407117 7317 0.5 16/0/20 50 1590 41.1 507149 7349 0.75 24/0/20 2 190 12.2 207150 7350 0.75 24/0/20 5 270 15.7 257151 7351 0.75 24/0/20 10 550 21.8 327152 7352 0.75 24/0/20 20 960 28.5 407153 7353 0.75 24/0/20 30 1320 33.7 50S7154 7354 0.75 24/0/20 50 2120 44.0 63S7185 7385 1.5 7/0.53 2 250 13.7 257186 7386 1.5 7/0.53 5 400 17.8 257187 7387 1.5 7/0.53 10 800 25.2 327188 7388 1.5 7/0.53 20 1400 33.8 50S

1.5 7/0.53 30 2040 40.4 501.5 7/0.53 50 3260 52.2 63

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLANDCODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE

(MM) (MM)71149 0.75 24/0.20 2 190 12.2 2071150 0.75 24/0.20 5 270 15.7 2571151 0.75 24/0.20 10 550 21.8 3271152 0.75 24/0.20 20 960 28.5 40

57

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

CONTROL ANDINSTRUMENTATION CABLE

NON-ARMOURED WITHINDIVIDUAL AND

COLLECTIVE SCREENS(0.5MM2 TO 1.5MM2)

INSTR

UM

ENTATIO

N, CO

NTRO

L AN

D CO

MM

UN

ICATIO

N C

AB

LES

Temperature limits:-20 to +65°C.

Bending radius:5 x overall diameter.

Core identification:Part 1 colour code chart on page 62.Part 2 colour code chart on page 63.

Should not be installed attemperatures below 0°C.

Page 56: 6629983 Cleveland Catalogue

INST

RU

MEN

TATI

ON

, CO

NTR

OL

AN

D C

OM

MU

NIC

ATIO

N C

AB

LES

58

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

INSTRUMENTATION, CONTROL ANDCOMMUNICATION CABLESBS5308 PART 1, TYPE 2Plain annealed flexible copper conductors, polyethylene insulated, laid up toform pairs, collective aluminium/mylar foil tape screen, complete with0.5mm2 drain wire, Polytheylene bedding, galvanised steel wire armour, PVCouter sheath reduced propagation. Blue or Black. Flame propagation toBS4066 PT1 and IEC 332 PT1. (Bunched cables to BS4066 PT3 and IEC 332 PT3).

BS5308 PART 2, TYPE 2Plain annealed flexible copper conductors, PVC insulated, laid up to form pairs,collective aluminium/mylar foil tape screen complete with 0.5mm2 drain wire,Polytheylenebedding, galvanised steel wire armour, PVC outer sheath reducedpropagation. Blue or Black. Flame propagation to BS4066 PT1 and IEC 332 PT1.(Bunched cables to BS4066 PT3 and IEC 332 PT3).

CCC CODE CONDUCTOR STRANDING No. OF WEIGHT OVERALL GLAND CLEATPT1 PT2 SIZE (MM2) (MM) PAIRS KG/KM DIAMETER SIZE SIZE

(MM) (MM) (MM)7118 7318 0.5 16/0/20 1 250 10.8 20/16 0.57119 7319 0.5 16/0/20 2 300 11.7 20/16 0.57120 7320 0.5 16/0/20 5 560 17.3 20 0.77121 7321 0.5 16/0/20 10 970 22.3 25 0.97122 7322 0.5 16/0/20 20 1640 28.5 32 1.27123 7323 0.5 16/0/20 30 2110 33.3 40 1.47124 7324 0.5 16/0/20 50 3270 41.5 50S 1.87125 7325 0.5 16/0/20 1 TRIPLE 276 11.0 20/16 0.57155 7355 0.75 24/0/20 1 280 11.1 20/16 0.57156 7356 0.75 24/0/20 2 330 12.3 20/16 0.57157 7357 0.75 24/0/20 5 750 19.2 20 0.87158 7358 0.75 24/0/20 10 1260 24.7 25 1.07159 7359 0.75 24/0/20 20 1890 30.7 32 1.47160 7360 0.75 24/0/20 30 2440 36.9 40 1.67161 7361 0.75 24/0/20 50 3890 46.4 50 2.07162 7362 0.75 24/0/20 1 TRIPLE 307 11.4 20/16 0.57189 7389 1.5 7/0/53 1 330 12.3 20/16 0.57190 7390 1.5 7/0/53 2 420 13.7 20S 0.67191 7391 1.5 7/0/53 5 940 21.5 25 0.97192 7392 1.5 7/0/53 10 1050 27.8 32 1.27193 7393 1.5 7/0/53 20 2400 35.1 40 1.47194 7394 1.5 7/0/53 30 3120 41.9 50S 1.87195 7395 1.5 7/0/53 50 5310 53.4 63S R97196 7396 1.5 7/0/53 1 TRIPLE 376 12.6 20/16 0.57208 7408 2.5 7/0/67 1 395 13.1 20S 0.67209 7409 2.5 7/0/67 2 490 15.9 20 0.67210 7410 2.5 7/0/67 5 1430 26.5 20 1.17211 7411 2.5 7/0/67 10 2235 35.1 40 1.47212 7412 2.5 7/0/67 20 3935 46.7 50 2.07213 7413 2.5 7/0/67 1 TRIPLE 407 13.7 20S 0.6

CONTROL ANDINSTRUMENTATION CABLE

ARMOURED WITHCOLLECTIVE SCREEN

(0.5MM2 TO 2.5MM2)

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND CLEATCODE SIZE (MM2) (MM) PAIRS KG/KM DIAMETER SIZE SIZE

(MM) (MM) (MM)7255 0.75 24/0.20 1 280 11.1 20/16 0.57256 0.75 24/0.20 2 330 12.3 20/16 0.57257 0.75 24/0.20 5 750 19.2 20 0.87258 0.75 24/0.20 10 1260 24.7 25 1.07259 0.75 24/0.20 20 1890 30.7 32 1.47289 1.5 7/0.53 1 330 12.3 20/16 0.57290 1.5 7/0.53 2 420 13.7 205 0.67291 1.5 7/0.53 5 940 21.5 25 0.97292 1.5 7/0.53 10 1050 27.8 32 1.27293 1.5 7/0.53 20 2400 35.1 40 1.4

Temperature limits:-20 to +65°C.

Bending radius:6 x overall diameter..

Core identification:Part 1 colour code chart on page 62.Part 2 colour code chart on page 63.

Should not be installed attemperatures below 0°C.

BS5308 PART 1, TYPE 2 LS0HPlain annealed flexible copper conductors, polyethylene insulated, laid up to formpairs, collective aluminium/mylar foil tape screen, complete with 0.5mm2 drain wire,low smoke zero halogen bedding (LS0H), galvanised steel wire armour, low smokezero halogen (LS0H) sheath, Black or Blue, generally to BS5308 Part 1, Type 2 LS0H.

Page 57: 6629983 Cleveland Catalogue

INSTR

UM

ENTATIO

N, CO

NTRO

L AN

D CO

MM

UN

ICATIO

N C

AB

LES

INSTRUMENTATION, CONTROL ANDCOMMUNICATION CABLESBS5308 PART 1, TYPE 2Plain annealed flexible copper conductors, polyethylene insulated, laid up toform pairs, each pair individually aluminium/mylar foil tape screened, completewith 0.5mm2 drain wire, collective aluminium/mylar foil tape screen, completewith 0.5mm2 drain wire, polyethylene bedding, galvanised steel wire armour,PVC outer sheath reduced propagation. Blue or Black. Flame propagation toBS4066 PT1 and IEC 332 PT1. (Bunched cables to BS4066 PT3 and IEC 332 PT3).

BS5308 PART 2, TYPE 2Plain annealed flexible copper conductors, PVC insulated, laid up to form pairs,each pair individually aluminium/mylar foil tape screened, complete with0.5mm2 drain wire, collective aluminium/mylar foil tape screen complete with0.5mm2 drain wire, PVC bedding, galvanised steel wire armour, PVC outersheath reduced propagation. Blue or Black. Flame propagation to BS4066 PT1and IEC 332 PT1. (Bunched cables to BS4066 PT3 and IEC 332 PT3).

CCC CODE CONDUCTOR STRANDING No. OF WEIGHT OVERALL GLAND CLEATPT1 PT2 SIZE (MM2) (MM) PAIRS KG/KM DIAMETER SIZE SIZE

(MM) (MM) (MM)7130 7330 0.5 16/0/20 2 460 16.8 20 0.77131 7331 0.5 16/0/20 5 760 20.9 25 0.97132 7332 0.5 16/0/20 10 1300 27.9 32 1.27133 7333 0.5 16/0/20 20 1870 34.3 40 1.47134 7334 0.5 16/0/20 30 2620 40.5 50S 1.67135 7335 0.5 16/0/20 50 4180 51.5 50 R97167 7367 0.75 24/0/20 2 500 17.6 20 0.77168 7368 0.75 24/0/20 5 920 22.0 25 0.97169 7369 0.75 24/0/20 10 1610 29.5 32 1.27170 7370 0.75 24/0/20 20 2420 37.8 40 1.67171 7371 0.75 24/0/20 30 3120 43.9 50S 1.87172 7372 0.75 24/0/20 50 4910 55.0 63S R97201 7401 1.5 7/0/53 2 730 20.4 20 0.97202 7402 1.5 7/0/53 5 1180 25.4 25 1.07203 7403 1.5 7/0/53 10 1820 33.5 40 1.47204 7404 1.5 7/0/53 20 3030 42.6 50S 1.87205 7405 1.5 7/0/53 30 3650 50.8 50 R97206 7406 1.5 7/0/53 50 5640 62.6 63 R10

CCC CODE CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND CLEATSIZE (MM2) (MM) PAIRS KG/KM DIAMETER SIZE SIZE

(MM) (MM) (MM)7267 0.75 24/0.20 2 500 17.6 20 0.77268 0.75 24/0.20 5 920 22.0 25 0.97269 0.75 24/0.20 10 1610 29.5 32 1.27270 0.75 24/0.20 20 2420 37.8 40 1.67298 1.5 7/0.53 2 730 20.4 20 0.97299 1.5 7/0.53 5 1180 25.4 25 1.07297 1.5 7/0.53 10 1820 33.5 40 1.47296 1.5 7/0.53 20 3030 42.6 505 1.8

59

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

CONTROL ANDINSTRUMENTATION CABLE

ARMOURED WITHINDIVIDUAL AND

COLLECTIVE SCREEN(0.5MM2 TO 1.5MM2)

Temperature limits:-20 to +65°C.

Bending radius:6 x overall diameter.

Core identification:Part 1 colour code chart on page 62.Part 2 colour code chart on page 63.

Should not be installed attemperatures below 0°C.

BS5308 PART 1, TYPE 2 LS0HPlain annealed flexible copper conductors, polyethylene insulated, laid up to formpairs, each pair individually aluminium/mylar foil tape screened, complete with0.5mm2 drain wire, collective aluminium/mylar foil tape screen, complete with0.5mm2 drain wire, low smoke zero halogen (LS0H) bedding, galvanised steel wirearmour, low smoke zero halogen (LS0H) sheath, Blue or Black, generally to BS5308.

Page 58: 6629983 Cleveland Catalogue

INST

RU

MEN

TATI

ON

, CO

NTR

OL

AN

D C

OM

MU

NIC

ATIO

N C

AB

LES

60

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

INSTRUMENTATION, CONTROL ANDCOMMUNICATION CABLESBS5308 PART 1, TYPE 3Plain annealed copper conductors, polyethylene insulated, laid up to formpairs, each pair individually aluminium/mylar foil tape screened completewith 0.5mm2 drain wire, collective aluminium/mylar foil tape screen completewith 0.5mm2 drain wire, polyethylene bedding, lead sheathed, galvanised steelwire armour, PVC outer sheath reduced propagation. Blue or Black. Flamepropagation to BS4066 PT1 and IEC 332 PT1. (Bunched cables to BS4066 PT3and IEC 332 PT3).

BS5308 PART 2, TYPE 3Plain annealed flexible copper conductors, PVC insulated laid up to form pairs,each pair individually aluminium/mylar foil tape screened complete with0.5mm2 drain wire, collective aluminium/mylar foil tape screen complete with0.5mm2 drain wire, PVC bedding, lead sheathed, galvanised steel wire armour,PVC outer sheath reduced propagation. Blue or Black. Flame propagation toBS4066 PT1 and IEC 332 PT1. (Bunched cables to BS4066 PT3 and IEC 332 PT3.

CONTROL ANDINSTRUMENTATION CABLE

LEAD SHEATHEDARMOURED WITH

COLLECTIVE SCREEN(0.75MM2 TO 1.5MM2)

CCC CODE CONDUCTOR STRANDING No. OF WEIGHT OVERALL GLAND CLEATPT1 PT2 SIZE (MM2) (MM) PAIRS KG/KM DIAMETER SIZE SIZE

(MM) (MM) (MM)7821 7921 0.75 24/0.20 1 700 15.7 20 0.77822 7922 0.75 24/0.20 2 795 16.8 20 0.77823 7923 0.75 24/0.20 5 1598 25.1 25 1.07824 7924 0.75 24/0.20 10 2280 29.4 32 1.27825 7925 0.75 24/0.20 20 3630 37.3 40 1.67826 7926 0.75 24/0.20 30 4385 43.1 50S 1.87827 7927 0.75 24/0.20 50 6895 53.1 63S R97971 - 1.0 1/1.13 1 710 15.8 20 0.77972 - 1.0 1/1.13 2 828 17.0 20 0.77973 - 1.0 1/1.13 5 1627 25.0 25 1.07974 - 1.0 1/1.13 10 2275 29.6 32 1.27975 - 1.0 1/1.13 20 3149 37.6 40 1.67976 - 1.0 1/1.13 30 4420 42.6 50S 1.87977 - 1.0 1/1.13 50 6964 53.5 63S R97851 7951 1.5 7/0.53 1 940 16.9 20 0.77852 7952 1.5 7/0.53 2 1051 19.0 20 0.87853 7953 1.5 7/0.53 5 1973 27.4 32 1.17854 7954 1.5 7/0.53 10 2823 33.2 32 1.47855 7955 1.5 7/0.53 20 4498 42.1 50S 1.87856 7956 1.5 7/0.53 30 6207 50.1 50 2.07857 7957 1.5 7/0.53 50 8961 61.0 63 R10

Temperature limits:-20 to +63°C.

Bending radius:5 x overall diameter.

Core identification:Part 1 colour code chart on page 62.Part 2 colour code chart on page 63.

Should not be installed attemperatures below 0°C.

Page 59: 6629983 Cleveland Catalogue

INSTR

UM

ENTATIO

N, CO

NTRO

L AN

D CO

MM

UN

ICATIO

N C

AB

LES

INSTRUMENTATION, CONTROL ANDCOMMUNICATION CABLESBS5308 PART 1, TYPE 3Plain annealed flexible copper conductors, polyethylene insulated, laid up toform pairs, collective aluminium/mylar tape screen, complete with 0.5mm2

drain wire, polyethylene bedding, lead sheathed, galvanised steel wire armour,PVC outer sheath reduced propagation. Blue or Black. Flame propagation toBS4066 PT1 and IEC 332 PT1. (Bunched cables to BS4066 PT3 and IEC 332 PT3).

BS5308 PART 2, TYPE 3Plain annealed flexible copper conductors, PVC insulated, laid up to form pairs,collective aluminium/mylar foil tape screen complete with 0.5mm2 drain wire,PVC bedding, lead sheathed, galvanised steel wire armour, PVC outer sheathreduced propagation. Blue or Black. Flame propagation to BS4066 PT1 and IEC332 PT1. (Bunched cables to BS4066 PT3 and IEC 332 PT3).

CCC CODE CONDUCTOR STRANDING No. OF WEIGHT OVERALL GLAND CLEATPT1 PT2 SIZE (MM2) (MM) PAIRS KG/KM DIAMETER SIZE SIZE

(MM) (MM) (MM)7830 7930 0.75 24/0.20 2 1280 21.5 25 0.97831 7931 0.75 24/0.20 5 1810 26.0 25 1.17832 7932 0.75 24/0.20 10 2720 32.7 32 1.47833 7933 0.75 24/0.20 20 4270 40.9 50S 1.87834 7934 0.75 24/0.20 30 6000 46.3 50S 2.07835 7935 0.75 24/0.20 50 8330 58.5 63S R10N/A N/A 1.0 1/1.13 2 1280 22.3 25 0.9N/A N/A 1.0 1/1.13 5 1820 27.2 25 1.1N/A N/A 1.0 1/1.13 10 2750 34.2 40 1.4N/A N/A 1.0 1/1.13 20 4350 43.8 50S 1.8N/A N/A 1.0 1/1.13 30 6110 51.4 50 R9N/A N/A 1.0 1/1.13 50 8350 62.5 63 R10

7870 7970 1.5 7/0.53 2 1680 25.5 25 1.17871 7971 1.5 7/0.53 5 2300 30.0 32 1.27872 7972 1.5 7/0.53 10 4000 40.1 50S 1.67873 7973 1.5 7/0.53 20 6300 50.2 50 2.07874 7974 1.5 7/0.53 30 8110 57.6 63S R107875 7975 1.5 7/0.53 50 11160 70.6 75S R12

61

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

CONTROL ANDINSTRUMENTATION CABLE

LEAD SHEATHEDARMOURED WITHINDIVIDUAL AND

COLLECTIVE SCREENS(0.75MM2 TO 1.5MM2)

Temperature limits:-20 to +65°C.

Bending radius:15 x overall diameter.

Core identification:Part 1 colour code chart on page 62.Part 2 colour code chart on page 63.

Should not be installed attemperatures below 0°C.

Page 60: 6629983 Cleveland Catalogue

INST

RU

MEN

TATI

ON

, CO

NTR

OL

AN

D C

OM

MU

NIC

ATIO

N C

AB

LES

62

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

INSTRUMENTATION, CONTROL ANDCOMMUNICATION CABLESBS5308 PART 1

PAIR A B PAIR A BNUMBER WIRE WIRE NUMBER WIRE WIRE

1 BLACK BLUE 26 WHITE YELLOW2 BLACK GREEN 27 RED YELLOW3 BLUE GREEN 28 ORANGE YELLOW4 BLACK BROWN 29 BLACK GREY5 BLUE BROWN 30 BLUE GREY6 GREEN BROWN 31 GREEN GREY7 BLACK WHITE 32 BROWN GREY8 BLUE WHITE 33 WHITE GREY9 GREEN WHITE 34 RED GREY

10 BROWN WHITE 35 ORANGE GREY11 BLACK RED 36 YELLOW GREY12 BLUE RED 37 BLACK VIOLET13 GREEN RED 38 BLUE VIOLET14 BROWN RED 39 GREEN VIOLET15 WHITE RED 40 BROWN VIOLET16 BLACK ORANGE 41 WHITE VIOLET17 BLUE ORANGE 42 RED VIOLET18 GREEN ORANGE 43 ORANGE VIOLET19 BROWN ORANGE 44 YELLOW VIOLET20 WHITE ORANGE 45 GREY VIOLET21 RED ORANGE 46 BLACK TURQUOISE22 BLACK YELLOW 47 BLUE TURQUOISE23 BLUE YELLOW 48 GREEN TURQUOISE24 GREEN YELLOW 49 BROWN TURQUOISE25 BROWN YELLOW 50 WHITE TURQUOISE

BS5308 PART 1 CORE IDENTIFICATION

For individual screened pairs, identification will be Black/Blue numbered pairs.

Two pair collectively screened cables are in quad formation colour coded inrotation, Black, Blue, Green, Brown.

Single triple will be Black, Blue, Turquoise.

Page 61: 6629983 Cleveland Catalogue

INSTR

UM

ENTATIO

N, CO

NTRO

L AN

D CO

MM

UN

ICATIO

N C

AB

LES

INSTRUMENTATION, CONTROL ANDCOMMUNICATION CABLESBS5308 PART 2

63

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

BS5308 PART 2 CORE IDENTIFICATION

PAIR A B PAIR A BNUMBER WIRE WIRE NUMBER WIRE WIRE

1 WHITE BLUE 26 RED/BLUE BLUE2 WHITE ORANGE 27 RED/BLUE ORANGE3 WHITE GREEN 28 RED/BLUE GREEN4 WHITE BROWN 29 RED/BLUE WHITE5 WHITE GREY 30 RED/BLUE BROWN6 RED BLUE 31 BLUE/BLACK BLUE7 RED ORANGE 32 BLUE/BLACK ORANGE8 RED GREEN 33 BLUE/BLACK GREEN9 RED BROWN 34 BLUE/BLACK BROWN

10 RED GREY 35 BLUE/BLACK GREY11 BLACK BLUE 36 YELLOW/BLUE BLUE12 BLACK ORANGE 37 YELLOW/BLUE ORANGE13 BLACK GREEN 38 YELLOW/BLUE GREEN14 BLACK BROWN 39 YELLOW/BLUE BROWN15 BLACK GREY 40 YELLOW/BLUE GREY16 YELLOW BLUE 41 WHITE/ORANGE BLUE17 YELLOW ORANGE 42 WHITE/ORANGE ORANGE18 YELLOW GREEN 43 WHITE/ORANGE GREEN19 YELLOW BROWN 44 WHITE/ORANGE BROWN20 YELLOW GREY 45 WHITE/ORANGE GREY21 WHITE/BLUE BLUE 46 ORANGE/RED BLUE22 WHITE/BLUE ORANGE 47 ORANGE/RED ORANGE23 WHITE/BLUE GREEN 48 ORANGE/RED GREEN24 WHITE/BLUE BROWN 49 ORANGE/RED BROWN25 WHITE/BLUE GREY 50 ORANGE/RED GREY

For individual screened pairs, identification will be White/Blue numbered pairs.

Two pair collectively screened cables are in quad formation colour coded inrotation, Blue, Green, Orange, Brown.

Single triple will be Blue, White, Green.

Page 62: 6629983 Cleveland Catalogue

INST

RU

MEN

TATI

ON

, CO

NTR

OL

AN

D C

OM

MU

NIC

ATIO

N C

AB

LES

64

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

INSTRUMENTATION, CONTROL ANDCOMMUNICATION CABLESPlain annealed flexible copper conductors, PVC bedding, tinned annealedcopper wire braid screen, PVC bedding, galvanised steel wire armour, PVCouter sheath. Grey. 300/500 volts grade to British Steel specification CES 20part 4, Type 134. Flame propagation to BS4066 PT1 and IEC 332 PT1.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OUTSIDE GLAND SINGLECODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE CLEAT

(MM) (MM)

BSC1342C 0.75 24/0/2 2 420 13.4 20S 0.6BSC1343C 0.75 24/0/2 3 452 13.8 20S 0.6BSC1344C 0.75 24/0/2 4 490 14.4 20S 0.6BSC1347C 0.75 24/0/2 7 579 15.9 20S 0.7

BSC13412C 0.75 24/0/2 12 906 19.5 20 0.8BSC13419C 0.75 24/0/2 19 1091 21.5 20 0.9BSC13427C 0.75 24/0/2 27 1562 25.5 25 1.1BSC13437C 0.75 24/0/2 37 1872 28.1 32 1.2

CORE IDENTIFICATION:

INSTRUMENTATION CABLETO BRITISH STEEL

SPECIFICATION CES20 TYPE 134

(0.75MM2)

NO. OF COLOURCORES

2 BROWN BLUE3 BROWN BLUE GREEN/YLW4 BROWN GREY GREEN/YLW BLACK7 RED BLUE GREEN YELLOW WHITE BLACK BROWN

12 RED BLUE GREEN YELLOW WHITE BLACK BROWNVIOLET ORANGE PINK TURQUOISE GREY

19 RED BLUE GREEN YELLOW WHITE BLACK BROWNVIOLET ORANGE PINK TURQUOISE GREY

RED/BLUE RED/GREEN RED/YELLOW RED/WHITE RED/BLACK RED/BROWN BLUE/YELLOW27 RED BLUE GREEN YELLOW WHITE BLACK BROWN

VIOLET ORANGE PINK TURQUOISE GREY RED/BLUE RED/GREENRED/YELLOW RED/WHITE RED/BLACK RED/BROWN BLUE/YELLOW BLUE/WHITE BLUE/BLACKBLUE/ORANGE BLUE/GREEN BLUE./GREY GREEN/YLW GREEN/WHITE GREEN/BLACK

37 RED BLUE GREEN YELLOW WHITE BLACK BROWNVIOLET ORANGE PINK TURQUOISE GREY RED/BLUE RED/GREEN

RED/YELLOW RED/WHITE RED/BLACK RED/BROWN BLUE/YELLOW BLUE/WHITE BLUE/BLACKBLUE/ORANGE BLUE/GREEN BLUE./GREY GREEN/YLW GREEN/WHITE GREEN/BLACK GRN/ORANGEGREEN/GREY BROWN/YLW BRN/WHITE BRN/BLACK BROWN/GREY VIOLET/YLW VIOLET/BLACKVIOLET/WHT RED/GREY

Temperature limits:-20 to +70°C.

Bending radius:6 x overall diameter.

Should not be installed attemperatures below 0°C.

Page 63: 6629983 Cleveland Catalogue

INSTR

UM

ENTATIO

N, CO

NTRO

L AN

D CO

MM

UN

ICATIO

N C

AB

LES

INSTRUMENTATION, CONTROL ANDCOMMUNICATION CABLESTinned annealed flexible copper conductors, PVC insulated and laid up to formpairs, collective aluminium/mylar foil tape screen, complete with 0.5mm2

drain wire, PVC bedding, galvanised steel wire armour, PVC outer sheath.Orange. 300/500 volts grade.

Type 143. Flame propagation to BS4066 PT1 and IEC 332 PT1.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OUTSIDE GLAND SINGLECODE SIZE (MM2) (MM) PAIRS KG/KM DIAMETER SIZE CLEAT

(MM) (MM)BSC1431P 0.75 24/0.20 1 280 11.4 20/16 0.5BSC1432P 0.75 24/0.20 2 400 14.1 20S 0.6BSC1435P 0.75 24/0.20 5 630 18.0 20 0.8

BSC14310P 0.75 24/0.20 10 950 22.2 25 0.9BSC14320P 0.75 24/0.20 20 1550 28.2 32 1.2BSC14330P 0.75 24/0.20 30 2000 32.3 32 1.4BSC14350P 0.75 24/0.20 50 3200 40.6 50S 1.6

PAIR A B PAIR A BNUMBER WIRE WIRE NUMBER WIRE WIRE

1 BLACK BLUE 26 WHITE YELLOW2 BLACK ORANGE 27 WHITE VIOLET3 BLACK GREEN 28 BLUE RED4 BLACK BROWN 29 BLUE YELLOW5 BLACK GREY 30 BLUE VIOLET6 BLUE WHITE 31 GREEN RED7 BLUE ORANGE 32 GREEN YELLOW8 BLUE GREEN 33 GREEN VIOLET9 BLUE BROWN 34 RED GREY

10 BLUE GREY 35 RED ORANGE11 ORANGE WHITE 36 RED YELLOW12 ORANGE GREEN 37 RED BROWN13 ORANGE BROWN 38 RED VIOLET14 ORANGE GREY 39 GREY YELLOW15 GREEN WHITE 40 GREY VIOLET16 GREEN BROWN 41 ORANGE YELLOW17 GREEN GREY 42 ORANGE VIOLET18 BROWN WHITE 43 YELLOW BROWN19 BROWN GREY 44 YELLOW VIOLET20 GREY WHITE 45 BROWN VIOLET21 BLACK WHITE 46 TURQUOISE BLACK22 BLACK RED 47 TURQUOISE BLUE23 BLACK YELLOW 48 TURQUOISE RED24 BLACK VIOLET 49 TURQUOISE ORANGE25 WHITE RED 50 TURQUOISE YELLOW

CORE IDENTIFICATION:

65

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

INSTRUMENTATION CABLETO BRITISH STEEL

SPECIFICATION CES20 TYPE 143

(0.75MM2)

Temperature limits:-20 to +70°C.

Bending radius:6 x overall diameter.

Should not be installed attemperatures below 0°C.

Page 64: 6629983 Cleveland Catalogue

INST

RU

MEN

TATI

ON

, CO

NTR

OL

AN

D C

OM

MU

NIC

ATIO

N C

AB

LES

66

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

INSTRUMENTATION, CONTROL ANDCOMMUNICATION CABLESSolid tinned annealed copper conductors, PVC insulated, polyester taped, PVCsheathed. To BPO CW(M) 1308. Sheath colour: White. Flame propagation toBS4066 PT1 and IEC 332 PT1.

Solid plain annealed copper conductors, cellular polyethylene insulated,Petroleum jelly filled, PE outer sheath. Black. To CW1128A. Flame propagationto BS4066 PT1 and IEC 332 PT1.

CCC STRANDING No. OF WEIGHT OVERALL GLANDCODE (MM2) PAIRS KGS/KM DIAMETER SIZE

(MM) (MM)13000 1/0.50 2 18 4.1 20/1613001 1/0.50 3 24 4.8 20/1613002 1/0.50 4 35 5.8 20/1613003 1/0.50 6 46 6.8 20/1613004 1/0.50 10 70 8.3 20/1613005 1/0.50 10+E 90 8.6 20S13006 1/0.50 12 80 9.1 20S13007 1/0.50 15 95 9.8 20S13008 1/0.50 20+E 146 12.0 2013009 1/0.50 25+E 163 11.4 2013010 1/0.50 30+E 200 12.2 2013012 1/0.50 40+E 297 15.0 2513014 1/0.50 50+E 356 17.8 2513016 1/0.50 60+E 412 20.9 3213018 1/0.50 80+E 552 22.5 3213020 1/0.50 100+E 697 24.1 3213022 1/0.50 160+E 1135 30.5 4013023 1/0.50 320+E 2306 39.5 50

INTERNAL TELEPHONE CABLE TYPE CW1308

PAIR A B PAIR A BNUMBER WIRE WIRE NUMBER WIRE WIRE

1 WHITE/BLUE BLUE/WHITE 16 YELLOW/BLUE BLUE/YELLOW2 WHITE/ORANGE ORANGE/WHITE 17 YELLOW/ORANGE ORANGE/YELLOW3 WHITE/GREEN GREEN/WHITE 18 YELLOW/GREEN GREEN/YELLOW4 WHITE/BROWN BROWN/WHITE 19 YELLOW/BROWN BROWN/YELLOW5 WHITE/GREY GREY/WHITE 20 YELLOW/GREY GREY/YELLOW6 RED/BLUE BLUE/RED 21 VIOLET/BLUE BLUE/VIOLET7 RED/ORANGE ORANGE/RED 22 VIOLET/ORANGE ORANGE/VIOLET8 RED/GREEN GREEN/RED 23 VIOLET/GREEN GREEN/VIOLET9 RED/BROWN BROWN/RED 24 VIOLET/BROWN BROWN/VIOLET

10 RED/GREY GREY/RED 25 VIOLET/GREY GREY/VIOLET11 BLACK/BLUE BLUE/BLACK 26 PINK/BLUE BLUE/PINK12 BLACK/ORANGE ORANGE/BLACK 27 PINK/ORANGE ORANGE/PINK13 BLACK/GREEN GREEN/BLACK 28 PINK/GREEN GREEN/PINK14 BLACK/BROWN BROWN/BLACK 29 PINK/BROWN BROWN/PINK15 BLACK/GREY GREY/BLACK 30 PINK/GREY GREY/PINK

CORE IDENTIFICATION:

CCC STRANDING No. OF WEIGHT OUTSIDE GLANDCODE (MM) PAIRS KG/KM DIAMETER SIZE

(MM)13030 1/0.50 5 76 7.8 20/1613031 1/0.50 10 113 9.1 20S13032 1/0.50 20 154 11.3 2013034 1/0.50 50 381 15.5 2513035 1/0.50 100 710 20.7 32

E. denotes earth core.

Temperature limits:-20 to +70°C.

Bending radius:5 x overall diameter.

Should not be installed attemperatures below 0°C.

Page 65: 6629983 Cleveland Catalogue

INSTR

UM

ENTATIO

N, CO

NTRO

L AN

D CO

MM

UN

ICATIO

N C

AB

LES

INSTRUMENTATION, CONTROL ANDCOMMUNICATION CABLESSolid tinned annealed copper conductors, PVC insulated, twisted to form pairs,PVC bedding, galvanised steel wire armour, PVC outer sheath. Black. To ESI 09-6:Issue 5 Section 3.6. Flame propagation to BS4066 PT1 and IEC 332 PT1.

Solid tinned annealed copper conductors, PVC insulated, twisted to form pairs, PVC bedding,galvanised steel wire armour, PVC outer sheath. Black. To ESI 09-6: Issue 5 Section 3.6.

Flame propagation to BS4066 PT1 and IEC 332 PT1.

Solid tinned annealed copper conductors, PVC insulated, twisted to form pairs,collective aluminium/mylar foil tape screen complete with 0.5mm2 drain wire,PVC bedding, galvanised steel wire armour, PVC outer sheath. Black. To ESI 09-6:Issue 5 Section 3.6. Flame propagation to BS4066 PT1 and IEC 332 PT1.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND CLEATCODE SIZE (MM2) (MM) PAIRS KG/KM DIAMETER SIZE SIZE

(MM) (MM) SINGLE13050 0.28 1/0.6 *2 145 8.0 20/16 0.413051 0.28 1/0.6 5 221 10.0 20/16 0.413052 0.28 1/0.6 10 314 12.3 20/16 0.613053 0.28 1/0.6 20 463 15.0 20S 0.613054 0.28 1/0.6 30 697 18.0 20 0.813055 0.28 1/0.6 50 977 21.8 25 0.913056 0.28 1/0.6 100 1793 29.9 32 1.2

* 2 pair laid up in quad formation.

Temperature limits:-20 to +70°C.

Core identification:See colour chart on page 69.

Should not be installed attemperatures below 0°C.

* 2 pair laid up in quad formation.

Temperature limits:-20 to +70°C.

Bending radius: 6 x overall diameter.

Core identification:See colour chart on page 69.

Should not be installed attemperatures below 0°C.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND CLEATCODE SIZE (MM2) (MM) PAIRS KG/KM DIAMETER SIZE SIZE

(MM) (MM) SINGLE13081 0.63 1/0.9 *2 250 10.1 20/16 0.513083 0.63 1/0.9 5 350 14.1 20S 0.613084 0.63 1/0.9 10 650 18.6 20 0.813085 0.63 1/0.9 15 800 21.0 25 0.913086 0.63 1/0.9 20 1000 22.7 25 0.913087 0.63 1/0.9 25 1250 25.4 25 1.013088 0.63 1/0.9 30 1400 26.7 25 1.113089 0.63 1/0.9 40 1700 29.3 32 1.213090 0.63 1/0.9 50 2000 32.6 32 1.4

- 0.63 1/0.9 60 2690 36.6 40 1.6- 0.63 1/0.9 75 2900 38.4 40 1.6

13091 0.63 1/0.9 100 3650 44.1 50S 1.8

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND CLEATCODE SIZE (MM2) (MM) PAIRS KG/KM DIAMETER SIZE SIZE

(MM) (MM) SINGLE13101 0.63 1/0.9 *2 258 11.0 20/16 0.513103 0.63 1/0.9 5 445 15.3 20S 0.613104 0.63 1/0.9 10 735 19.2 20 0.813105 0.63 1/0.9 15 908 21.4 25 0.913106 0.63 1/0.9 20 1046 23.1 25 1.213107 0.63 1/0.9 25 1750 25.8 25 1.213108 0.63 1/0.9 30 1512 27.1 32 1.213109 0.63 1/0.9 40 1804 30.2 32 1.213110 0.63 1/0.9 50 2166 33.6 40 1.4

- 0.63 1/0.9 100 3870 45.4 50S 2.0

67

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

PVC INSULATEDMULTIPAIR ARMOURED

CABLE TO ESI STANDARD

Page 66: 6629983 Cleveland Catalogue

INST

RU

MEN

TATI

ON

, CO

NTR

OL

AN

D C

OM

MU

NIC

ATIO

N C

AB

LES

68

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

INSTRUMENTATION, CONTROL ANDCOMMUNICATION CABLESSolid tinned annealed copper conductors, PVC insulated, twisted to form pairs,PVC bedding, galvanised steel wire armour, PVC outer sheath. Black. To ESI 09-6: Issue 6 Section 4.5. Flame propagation to BS4066 PT1 and IEC 332 PT1.

Solid tinned annealed copper conductors, PVC insulated, twisted to form pairs,collective aluminium/mylar foil tape screen complete with 0.5mm2 drain wire,PVC bedding, galvanised steel wire armour, PVC outer sheath. Black. To ESI 09-6: Section 4.5. Flame propagation to BS4066 PT1 and IEC 332 PT1.

Solid tinned annealed copper, polyethylene insulated, low smoke and zerohalogen (LS0H) bedding, galvanised steel wire armour, low smoke and zerohalogen (LS0H) sheath. Black. Generally to ESI 09-6: Issue 6 Section 4.5.

PVC INSULATEDMULTIPAIR ARMOURED

CABLE TO ESI STANDARD

* 2 pair laid up in quad formation.

Temperature limits:-20 to +70°C.

Bending radius: 8 x overall diameter.

Core identification:See colour chart on page 70.

Should not be installed attemperatures below 0°C.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND CLEATCODE SIZE (MM2) (MM) PAIRS KG/KM DIAMETER SIZE SIZE

(MM) (MM) SINGLE13381 0.5 1/0.8 *2 200 9.5 20/16 0.513383 0.5 1/0.8 5 290 13.1 20S 0.613384 0.5 1/0.8 10 450 17.0 20 0.713385 0.5 1/0.8 15 630 18.9 20 0.813386 0.5 1/0.8 20 770 20.5 20 0.913387 0.5 1/0.8 25 1159 23.2 25 1.013388 0.5 1/0.8 30 1110 26.2 25 1.113389 0.5 1/0.8 40 1450 31.8 32 1.413390 0.5 1/0.8 50 1770 33.4 40 1.413391 0.5 1/0.8 100 3000 43.4 50S 1.8

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND CLEATCODE SIZE (MM2) (MM) PAIRS KG/KM DIAMETER SIZE SIZE

(MM) (MM) SINGLE13401 0.5 1/0.8 *2 260 10.9 20/16 0.513403 0.5 1/0.8 5 380 14.1 20S 0.613404 0.5 1/0.8 10 660 17.8 20 0.713405 0.5 1/0.8 15 795 19.4 20 0.813406 0.5 1/0.8 20 900 21.1 25 0.913407 0.5 1/0.8 25 1159 23.5 25 1.013408 0.5 1/0.8 30 1380 27.1 32 1.113409 0.5 1/0.8 40 1800 33.0 32 1.413410 0.5 1/0.8 50 2220 34.9 40 1.413411 0.5 1/0.8 100 3041 44.7 50S 1.8

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND CLEATCODE SIZE (MM2) (MM) PAIRS KG/KM DIAMETER SIZE SIZE

(MM) (MM) SINGLE13501 0.5 1/0.8 *2 200 9.5 20/16 0.513503 0.5 1/0.8 5 290 13.1 20S 0.613504 0.5 1/0.8 10 450 17.0 20 0.713506 0.5 1/0.8 20 770 20.5 20 0.9

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND CLEATCODE SIZE (MM2) (MM) PAIRS KG/KM DIAMETER SIZE SIZE

(MM) (MM) SINGLE13601 0.5 1/0.8 *2 260 10.9 20/16 0.513603 0.5 1/0.8 5 380 14.1 20S 0.613604 0.5 1/0.8 10 660 17.8 20 0.713606 0.5 1/0.8 20 900 21.1 25 0.9

Solid tinned, annealed copper conductors, polyethylene insulated, twisted to formpairs, collective aluminium/mylar foil tape screen complete with 0.5mm2 drain, wire,low smoke zero halogen (LS0H) bedding, galvanised steel wire armour, low smokeand zero halogen (LS0H) sheath. Black. Generally to ESI 09-6: Issue 6 Section 4.5.

Page 67: 6629983 Cleveland Catalogue

INSTR

UM

ENTATIO

N, CO

NTRO

L AN

D CO

MM

UN

ICATIO

N C

AB

LES

INSTRUMENTATION, CONTROL ANDCOMMUNICATION CABLESESI 09-6 SECTION 3

PAIR A B PAIR A BNUMBER WIRE WIRE NUMBER WIRE WIRE

1 BLACK BLUE 26 WHITE YELLOW2 BLACK ORANGE 27 WHITE VIOLET3 BLACK GREEN 28 BLUE RED4 BLACK BROWN 29 BLUE YELLOW5 BLACK GREY 30 BLUE VIOLET6 BLUE WHITE 31 GREEN RED7 BLUE ORANGE 32 GREEN YELLOW8 BLUE GREEN 33 GREEN VIOLET9 BLUE BROWN 34 RED GREY

10 BLUE GREY 35 RED ORANGE11 ORANGE WHITE 36 RED YELLOW12 ORANGE GREEN 37 RED BROWN13 ORANGE BROWN 38 RED VIOLET14 ORANGE GREY 39 GREY YELLOW15 GREEN WHITE 40 GREY VIOLET16 GREEN BROWN 41 ORANGE YELLOW17 GREEN GREY 42 ORANGE VIOLET18 BROWN WHITE 43 YELLOW BROWN19 BROWN GREY 44 YELLOW VIOLET20 GREY WHITE 45 BROWN VIOLET21 BLACK WHITE 46 TURQUOISE BLACK22 BLACK RED 47 TURQUOISE BLUE23 BLACK YELLOW 48 TURQUOISE RED24 BLACK VIOLET 49 TURQUOISE ORANGE25 WHITE RED 50 TURQUOISE YELLOW

PAIR COLOURNUMBER WIRE A WIRE B

1 WHITE BLUE2 WHITE ORANGE3 WHITE GREEN4 WHITE BROWN5 WHITE GREY6 RED BLUE7 RED ORANGE8 RED GREEN9 RED BROWN

10 RED GREY11 BLACK BLUE12 BLACK ORANGE13 BLACK GREEN14 BLACK BROWN15 BLACK GREY16 YELLOW BLUE17 YELLOW ORANGE18 YELLOW GREEN19 YELLOW BROWN20 YELLOW GREY

69

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

ESI 09-6 SECTION 3.6

CORE IDENTIFICATION

All two pair cables are in quad formation and colour coded in rotation - Blue,Orange, Green, Brown.

2 pair (quad) cables - white, red, blueand orange (in order of rotation)

Page 68: 6629983 Cleveland Catalogue

INST

RU

MEN

TATI

ON

, CO

NTR

OL

AN

D C

OM

MU

NIC

ATIO

N C

AB

LES

70

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

INSTRUMENTATION, CONTROL ANDCOMMUNICATION CABLESESI 09-6 SECTION 4

PAIR A BNUMBER WIRE WIRE

1 WHITE BLUE2 WHITE ORANGE3 WHITE GREEN4 WHITE BROWN5 WHITE GREY6 RED BLUE7 RED ORANGE8 RED GREEN9 RED BROWN

10 RED GREY11 BLACK BLUE12 BLACK ORANGE13 BLACK GREEN14 BLACK BROWN15 BLACK GREY16 YELLOW BLUE17 YELLOW ORANGE18 YELLOW GREEN19 YELLOW BROWN20 YELLOW GREY

ESI 09-6 SECTION 4.5

CORE IDENTIFICATION

UNIT 1 BLUEUNIT 2 ORANGEUNIT 3 GREENUNIT 4 BROWNUNIT 5 GREY

Each unit is lapped with coloured tape for identification as follows

All two pair cables are in quadformation and colour coded inrotation - White, Red, Blue, Orange.

For 30 pair cables the formation willbe 3 X 10 pair units numbered - 1, 2and 3.

For 40 pair cables the formation will be2 X 20 pair units numbered - 1 and 2.

For 50 pair cables the formation willbe 5 X 10 pair units numbered - 1, 23, 4 and 5.

Page 69: 6629983 Cleveland Catalogue

INSTR

UM

ENTATIO

N, CO

NTRO

L AN

D CO

MM

UN

ICATIO

N C

AB

LES

INSTRUMENTATION, CONTROL ANDCOMMUNICATION CABLESSolid plain annealed copper conductors, cellular polyethylene insulated, petroleumjelly filled, collective aluminium/mylar tape screen plus 0.5mm2 drain wire,polyethylene bedding, galvanised steel wire armour, PVC outer sheath. Black. ToBS3573 and CW1128/1198. Flame propagation to BS4066 PT1 and IEC 332 PT1.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND CLEATCODE SIZE (MM2) (MM) PAIRS KG/KM DIAMETER SIZE SIZE

(MM) (MM) SINGLE13150 0.63 1/0.9 5 392 16.7 20 0.713151 0.63 1/0.9 10 620 19.9 20 0.813153 0.63 1/0.9 20 1078 24.8 25 1.013154 0.63 1/0.9 50 2155 34.5 40 1.6

Cables may be manufactured using 5-pair sub-units coloured as 1-5 and 6-10

If sub-units are used binders forcorresponding sub-units shall be thesame colour.

COLOUR SCHEME FOR BS3573 - UNIT CONSTRUCTION

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND CLEATCODE SIZE (MM2) (MM) PAIRS KG/KM DIAMETER SIZE SIZE

(MM) (MM) SINGLE13040 0.196 1/0.5 5 470 11.78 20/16 0.513041 0.196 1/0.5 10 721 12.30 20S 0.513042 0.196 1/0.5 20 1204 14.78 20S 0.613043 0.196 1/0.5 50 2347 22.78 25 0.913044 0.196 1/0.5 100 3660 29.77 32 1.2

Solid plain annealed copper conductors, cellular polyethylene insulated,petroleum jelly filled solid polyethylene bedding, galvanised steel wire armour,PE outer sheath. Black.

To BPO CW 1128A/1198A. (Concentric construction). Flame propagation toBS4066 PT1 and IEC 332 PT1.

PAIR A BNUMBER WIRE WIRE

1 WHITE BLUE2 WHITE ORANGE3 WHITE GREEN4 WHITE BROWN5 WHITE GREY6 RED BLUE7 RED ORANGE8 RED GREEN9 RED BROWN

10 RED GREY

UNIT 1 BLUEUNIT 2 ORANGEUNIT 3 GREENUNIT 4 BROWNUNIT 5 GREY

71

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

PETROLEUMJELLY FILLED TELEMETRYCABLE TO BS3573 AND

CW1128/1198

Page 70: 6629983 Cleveland Catalogue

INST

RU

MEN

TATI

ON

, CO

NTR

OL

AN

D C

OM

MU

NIC

ATIO

N C

AB

LES

72

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

INSTRUMENTATION, CONTROL ANDCOMMUNICATION CABLESTinned annealed flexible copper conductors, PVC insulated, non-hygroscopic bindertape, tinned annealed copper wire braid screen, PVC outer sheath. Black. 440 voltsgrade. To Ministry of Defence Standard DEF 61-12 (Part 4 for 7/0.2 conductors, Part5 for 16/0.2 conductors). Flame propogation to BS4066 PT1 and IEC 332 PT1.

Tinned annealed flexible copper conductors, low smoke and zero halogen(LS0H) insulation, non-hygroscopic binder tape, tinned annealed copper wirebraid screen, low smoke and zero halogen (LS0H) outer sheath. Black. 440 voltgrade. Generally to ministry of Defence Standard DEF61-12 Part 5 LSF.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLANDCODE SIZE (MM2) (MM2) CORES KG/KM DIAMETER SIZE

(MM) (MM)722C 0.22 7/0.20 2 23 4.1 16723C 0.22 7/0.20 3 27 4.3 16724C 0.22 7/0.20 4 32 4.6 16726C 0.22 7/0.20 6 55 5.9 16728C 0.22 7/0.20 8 69 6.0 16

7212C 0.22 7/0.20 12 83 7.2 167218C 0.22 7/0.20 18 110 8.5 207225C 0.22 7/0.20 25 150 9.8 207236C 0.22 7/0.20 36 200 11.2 207250C 0.22 7/0.20 50 270 13.0 257260C 0.22 7/0.20 60 310 13.8 251622C 0.50 16/0.20 2 69 6.9 161623C 0.50 16/0.20 3 79 7.2 161624C 0.50 16/0.20 4 92 7.7 161626C 0.50 16/0.20 6 120 8.7 201628C 0.50 16/0.20 8 146 8.9 20

16210C 0.50 16/0.20 *10 190 11.8 2016212C 0.50 16/0.20 12 198 11.0 2016218C 0.50 16/0.20 18 250 12.5 2016225C 0.50 16/0.20 25 320 14.6 2516236C 0.50 16/0.20 36 450 16.7 2516250C 0.50 16/0.20 50 564 18.5 3216260C 0.50 16/0.20 60 670 20.3 32

DEFENCE STANDARD SCREENED

MULTICORE CABLE ‘C’ TYPE

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLANDCODE SIZE (MM2) (MM2) CORES KG/KM DIAMETER SIZE

(MM) (MM)LSF1622C 0.50 16/0.20 2 69 6.9 16LSF1623C 0.5 16/0.20 3 79 7.2 16LSF1624C 0.5 16/0.20 4 92 7.7 16LSF1626C 0.5 16/0.20 6 120 8.7 20

LSF16212C 0.5 16/0.20 12 198 11.0 20LSF16218C 0.5 16/0.20 18 250 12.5 20LSF16225C 0.5 16/0.20 25 320 14.6 25

* Laid up in a pair configuration.

Temperature limits:-55 to +70°C.

Bending radius:6 x overall diameter.

Core identification: See colour chart on page 73.

Should not be installed attemperatures below 0°C.

Page 71: 6629983 Cleveland Catalogue

INSTR

UM

ENTATIO

N, CO

NTRO

L AN

D CO

MM

UN

ICATIO

N C

AB

LES

INSTRUMENTATION, CONTROL ANDCOMMUNICATION CABLESCOLOUR CODES

CORE COLOURNUMBER

1 RED2 BLUE3 GREEN4 YELLOW5 WHITE6 BLACK7 BROWN8 VIOLET9 ORANGE

10 PINK11 TURQUOISE12 GREY13 RED/BLUE14 GREEN/RED15 YELLOW/RED16 WHITE/RED17 RED/BLACK18 YELLOW/BLUE19 YELLOW/BLUE20 WHITE/BLUE21 BLUE/BLACK22 ORANGE/BLUE23 GREEN/BLUE24 GREY/BLUE25 YELLOW/GREEN26 WHITE/GREEN27 GREEN/BLACK28 ORANGE/GREEN29 GREY/GREEN30 YELLOW/BROWN31 WHITE/BROWN32 BROWN/BLACK33 GREY/BROWN34 YELLOW/VIOLET35 VIOLET/BLACK35 VIOLET/BLACK36 WHITE/VIOLET

DEFENCE STANDARD 61-12 PARTS 4 & 5 COREIDENTIFICATION

73

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

Where 2 colours are shown the coreis striped e.g. Red/Blue - the core isstriped Red with Blue.

Page 72: 6629983 Cleveland Catalogue

INST

RU

MEN

TATI

ON

, CO

NTR

OL

AN

D C

OM

MU

NIC

ATIO

N C

AB

LES

74

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

INSTRUMENTATION, CONTROL ANDCOMMUNICATION CABLESNON-ARMOUREDPlain annealed flexible conductors, PVC insulated, laid up to form pairs,collective aluminium mylar foil tape screen, complete with 0.5mm2 drainwire, PVC outer sheath.

Thermocouple wires calibrated to BS4937, ANSI 96.1 and IEC 584.3.

Flame propagation to BS4066 PT1 and IEC 332 PT1.

NO OF SIZE STRANDING OVERALL GLAND JX CCC KCB CCC KX CCC TX CCCPAIRS (MM2) (MM) DIAMETER SIZE CODE CODE CODE CODE

(MM) (MM) (WAS VX)1 0.75 24/0.20 6.7 20/16 7500 7530 7570 75502 0.75 24/0.20 7.7 20/16 7501 7531 7571 75515 0.75 24/0.20 13.7 25 7503 7533 7573 7553

10 0.75 24/0.20 18.1 25 7505 7537 7575 755720 0.75 24/0.20 23.9 32 7507 7539 7577 7559

PVC INSULATEDCOLLECTIVE SCREENED

THERMOCOUPLEEXTENSION AND

COMPENSATING CABLE(0.75MM2)

ARMOUREDPlain annealed flexible conductors, PVC insulated, laid up to form pairs,collective aluminium mylar foil tape screen, complete with 0.5mm2 drainwire, PVC bedding, galvanised steel wire armour, PVC outer sheath.Thermocouple wires calibrated to BS4937, ANSI 96.1 and IEC 584.3. Flame propagation to BS4066 PT1 and IEC 332 PT1.

NO OF SIZE STRANDING OVERALL GLAND JX CCC KCB CCC KX CCC TX CCCPAIRS (MM2) (MM) DIAMETER SIZE CODE CODE CODE CODE

(MM) (MM) (WAS VX)1 0.75 24/0.20 11.1 20/16 7600 7640 7700 76602 0.75 24/0.20 12.3 20/16 7601 7641 7701 76615 0.75 24/0.20 19.2 20 7603 7643 7703 7663

10 0.75 24/0.20 24.7 25 7605 7645 7705 766520 0.75 24/0.20 30.7 32 7607 7647 7707 7667

Temperature limits:-30 to +105°C.

Bending radius:5 x overall diameter.

Core identification:See colour chart on page 77.

Should not be installed attemperatures below 0°C.

Temperature limits:-30 to +105°C.

Bending radius:6 x overall diameter.

Core identification: See colour chart on page 77.

Should not be installed attemperatures below 0°C.

Page 73: 6629983 Cleveland Catalogue

INSTR

UM

ENTATIO

N, CO

NTRO

L AN

D CO

MM

UN

ICATIO

N C

AB

LES75

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

INSTRUMENTATION, CONTROL ANDCOMMUNICATION CABLESTRAFFIC CONTROL CABLEPlain annealed solid conductors, PVC insulated, PVC bedding, galvanised steelwire armour, PVC outer sheath, colour orange, generally to BS6346/87

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE

(MM) (MM)TRAF4X1 1.0 1/1.13 4 325 13.3 20STRAF8X1 1.0 1/1.13 8 413 15.6 20S

TRAF12X1 1.0 1/1.13 12 567 17.9 20TRAF16X1 1.0 1/1.13 16 774 19.9 20TRAF20X1 1.0 1/1.13 20 905 22.0 25TRAF4X1/5 1.5 1/1.38 4 363 12.5 20STRAF8X1/5 1.5 1/1.38 8 534 15.8 20

TRAF12X1/5 1.5 1/1.38 12 704 18.5 20TRAF16X1/5 1.5 1/1.38 16 836 20.0 20TRAF20X1/5 1.5 1/1.38 20 1040 21.5 25

TRAF8X1E 1.0 1/1.13 8 533 16.3 20

PVC INSULATEDARMOURED

TRAFFIC SIGNAL CABLE,LOOP FEEDER CABLE

AND LOOP DETECTOR CABLE

TRAFFIC CONTROL CABLE UNARMOUREDPlain annealed solid conductors, PVC insulated, PVC sheathed, colour orange,generally to BS6346/87, 600/1000v grade.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE

(MM) (MM)TRAF8X1NA 1.0 1/1.13 8 218 12.6 20

TRAF12X1NA 1.0 1/1.13 12 305 13.5 25

Temperature limits:-15 to +70°C.

Core identification:4 core - Red, White, Blue, Black.8 core - Red, White, Blue, Black, Green,Yellow, Brown, Orange.12 core - Red, White, Blue, Black,Green, Yellow, Brown, Orange, Grey,Violet, White/Red, Blue/Red.16 core - Red, White, Blue, Black,Green, Yellow, Brown, Orange, Grey,

Violet, White/Red, Blue/Red,Black/Red, Grey/Red, Yellow/Red,Brown/Red.20 core - Red, White, Blue, Black,Green, Yellow, Brown, Orange, Grey,Violet, White/Red, Blue/Red,Black/Red, Grey/Red, Yellow/Red,Brown/Red, Green/Red, Orange/Red,Violet/Red, Blue/White.

Should not be installed attemperatures below 0°C.

Page 74: 6629983 Cleveland Catalogue

INST

RU

MEN

TATI

ON

, CO

NTR

OL

AN

D C

OM

MU

NIC

ATIO

N C

AB

LES

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE

(MM) (MM)LOOP2X1/5SWA 1.5 1/1.38 2 (1pr) 235 11.8 20SLOOP4X1/5SWA 1.5 1/1.38 4 (2pr) 300 12.7 20SLOOP2X2/5SWA 2.5 1/1.78 2 (1pr) 279 12.5 20SLOOP4X2/5SWA 2.5 1/1.78 4 (2pr) 383 15.0 20

INSTRUMENTATION, CONTROL ANDCOMMUNICATION CABLESLOOP FEEDER ARMOURED CABLEPlain annealed solid conductors, polythene insulated, polythene bedding,galvanised steel wire armour, polythene outer sheath. Generally to BS6346/87.Outer sheath colour: Orange. 600/1000 volts grade.

76

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

LOOP FEEDER CABLEPlain annealed solid conductors, polyethylene insulated, polyethylene outersheath, colour orange, 600/1000v grade.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE

(MM) (MM)LOOP2X2/5 2.5 1/1.78 2 (1pr) 10.4 9.3 20SLOOP4X2/5 2.5 1/1.78 4 (2pr) 16.0 10.7 20S

LOOP DETECTOR CABLETinned flexible copper conductor, ethylene propylene rubber insulated (EPR),polychloroprene sheathed (PCP), 600/100v generally to BS6500 + BS6195,sheath colour black.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND CODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE

(MM) (MM)LOOP1/5 1.5 30/.025 1 53.8 7.0 20SLOOP2/5 2.5 50/0.25 1 64.0 7.9 20S

Temperature limits:-15 to +70°C.

Bending radius:6 x overall diameter.

Core identification:2 core - Brown, Blue4 core - Brown, Black, Grey, Blue.

Should not be installed attemperatures below 0°C.

Temperature limits:-15 to +70°C.

Bending radius:6 x overall diameter.

Core identification:2 core - Brown, Blue4 core - Brown, Black, Grey, Blue.

Should not be installed attemperatures below 0°C.

Temperature limits:-30 to +85°C.

Bending radius: 6 x overall diameter.

Should not be installed attemperatures below -25°C.

Page 75: 6629983 Cleveland Catalogue

INSTRUMENTATION, CONTROL ANDCOMMUNICATION CABLES

INSTR

UM

ENTATIO

N, CO

NTRO

L AN

D CO

MM

UN

ICATIO

N C

AB

LES77

COLOUR CODING OFTHERMOCOUPLEEXTENSION AND

COMPENSATING CABLE

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

+ -EX

+ -JX

+ -KX

+ -NX

+ -TX

+ -UX

+ -VX

RC/SC KCB

CODE

BRITISHBS1843: 1952

+ - + - + - + - + - + - + -

AMERICANANSI

+ - + - + - + - + -

GERMANDIN

+ - + - + - + - + - + -

IEC 584-3

+ - + - + - + - + - + -

IEC 584-3INTRINSICALLYSAFE

Page 76: 6629983 Cleveland Catalogue

78

Page 77: 6629983 Cleveland Catalogue

RAILWAY CABLES

RA

ILWAY

CA

BLES

79

Page 78: 6629983 Cleveland Catalogue

RA

ILW

AY C

AB

LES

RAILWAY CABLESSIGNALLING CABLESStranded or flexible tinned copper conductors to BS6360, EPR insulated to BS7655 fortypes B1, LSZH insulated for types A1, A2, A3. PCP sheath for types A1 & B1, LSZHsheath for types A2 & A3. Manufactured to Railtrack specification RT/E/PS/00005.

CCC RAIL RAIL CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLANDCODE CODE TYPE SIZE CORES (KG/KM) DIAMETER SIZE

(MM2)A11X/75BR 6/120002 A1 Brown 0.75 7/0.37 1 16 2.95 N/AA11X/75RD 6/120003 A1 Red 0.75 7/0.37 1 16 2.95 N/AA11X/75OR 6/120004 A1 Orange 0.75 7/0.37 1 16 2.95 N/AA11X/75GY 6/120005 A1 Grey 0.75 7/0.37 1 16 2.95 N/AA11X/75VIR 6/120006 A1 Violet 0.75 7/0.37 1 16 2.95 N/AA11X/75BK 6/120007 A1 Black 0.75 7/0.37 1 16 2.95 N/AA11X115BK 6/120008 A1 Black 1.15 16/0.30 1 20 3.25 N/A

A21X/75 6/120020 A2 0.75 7/0.37 1 30 4.50 N/AA21X115 6/120024 A2 1.15 16/0.30 1 35 4.80 20/16A32X/75 6/120040 A3 0.75 7/0.37 2 67 7.75 20/16A34X/75 6/120041 A3 0.75 7/0.37 4 108 9.20 20SA36X/75 6/120042 A3 0.75 7/0.37 6 160 11.10 20S

A310X/75 6/120043 A3 0.75 7/0.37 10 259 14.35 25A314X/75 6/120044 A3 0.75 7/0.37 14 495 15.75 25A336X/75 6/120045 A3 0.75 7/0.37 36 752 24.20 32A348X/75 6/120046 A3 0.75 7/0.37 48 963 27.50 40B11X2/5 6/120061 B1 2.5 7/0.67 1 34 8.05 20/16B11X10 6/120062 B1 10 7/1.35 1 205 10.60 20SB11X35 6/120063 B1 35 19/1.53 1 495 14.50 25B22X1/5 6/120081 B2 1.5 7/0.53 2 135 10.75 20SB22X2/5 6/120082 B2 2.5 7/0.67 2 17 11.80 20B22X10 6/120083 B2 10 7/1.35 2 443 16.85 25B22X16 6/120113 B2 16 7/1.70 2 625 18.80 25B22X35 6/120084 B2 35 19/1.53 2 1232 25.05 32B22X70 6/120085 B2 70 19/2.14 2 2043 64.80 75B22X95 6/120086 B2 95 19/2.52 2 2945 74.70 90B24X/75 6/120087 B2 0.75 7/0.37 4 150 11.50 20SB24X1/5 6/120088 B2 1.5 7/0.53 4 220 12.30 20B24X2/5 6/120089 B2 2.5 7/0.67 4 295 13.35 20B27X/75 6/120090 B2 0.75 7/0.37 7 225 13.25 20B27X1/5 6/120091 B2 1.5 7/0.53 7 370 14.20 25B27X2/5 6/120092 B2 2.5 7/0.67 7 500 15.50 25

B210X/75 6/120093 B2 0.75 7/0.37 10 280 16.20 25B210X1/5 6/120094 B2 1.5 7/0.53 10 401 17.50 25B210X2/5 6/120095 B2 2.5 7/0.67 10 680 19.20 25B212X/75 6/120096 B2 0.75 7/0.37 12 321 16.65 25B26PX/75 6/120111 B2 0.75 7/0.37 6pr 469 22.15 32B212X1/5 6/120097 B2 1.5 7/0.53 12 410 18.00 25B212X2/5 6/120098 B2 2.5 7/0.67 12 730 19.80 25B219X/75 6/120099 B2 0.75 7/0.37 19 425 19.15 25B219X1/5 6/120100 B2 1.5 7/0.53 19 615 20.80 32B219X2/5 6/120101 B2 2.5 7/0.67 19 815 22.95 32B227X/75 6/120102 B2 0.75 7/0.37 27 606 22.60 32B227X1/5 6/120103 B2 1.5 7/0.53 27 897 25.00 32B227X2/5 6/120104 B2 2.5 7/0.67 27 1200 27.65 40B237X/75 6/120105 B2 0.75 7/0.37 37 786 22.60 32B237X1/5 6/120106 B2 1.5 7/0.53 37 1126 28.25 40B237X2/5 6/120107 B2 2.5 7/0.67 37 1600 31.25 40B248X/75 6/120108 B2 0.75 7/0.37 48 972 28.95 40B248X1/5 6/120109 B2 1.5 7/0.53 48 1280 31.60 40B248X2/5 6/120110 B2 2.5 7/0.67 48 1960 35.10 50S

80

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

Page 79: 6629983 Cleveland Catalogue

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

RA

ILWAY

CA

BLES

RAILWAY CABLESSIGNALLING CABLES

81

CCC RAIL RAIL CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLANDCODE CODE TYPE SIZE CORES (KG/KM) DIAMETER SIZE

(MM2)C1X2/5 6/120130 C1 2.5 50/0.25 1 174 12.60 25

C22X2/5 6/120140 C2 2.5 50/0.25 2 342 16.85 25C24X2/5 6/120141 C2 2.5 50/0.25 4 445 18.65 25C27X2/5 6/120142 C2 2.5 50/0.25 7 590 42.40 50

C210X2/5 6/120143 C2 2.5 50/0.25 10 784 25.55 40C212X2/5 6/120144 C2 2.5 50/0.25 12 868 26.25 40C216X2/5 6/160145 C2 2.5 50/0.25 16 980 28.65 40C3TPWS 6/160086 C3TPWS 2.5 50/0.25 1pr 250 17.50 25D11X/75 6/120211 D1 0.75 7/0.37 1 25 7.30 20/16D11X1/5 6/120212 D1 1.5 7/0.53 1 30 7.65 20/16D11X2/5 6/120213 D1 2.5 7/0.67 1 34 8.05 20/16D11X10 6/120214 D1 10 7/1.35 1 205 10.60 20SD11X35 6/120215 D1 35 19/1.53 1 495 14.50 25D22X1/5 6/120216 D2 1.5 7/0.53 2 135 10.75 20SD22X2/5 6/120217 D2 2.5 7/0.67 2 170 11.80 20D22X10 6/120218 D2 10 7/1.35 2 443 16.85 25D22X35 6/120219 D2 35 19/1.53 2 1232 25.05 40

D227X/75 6/120238 D2 0.75 7/0.37 27 606 22.60 32D227X1/5 6/120239 D2 1.5 7/0.53 27 897 25.00 32D227X2/5 D2 2.5 7/0.67 27 1200 27.65 40D237X/75 6/120241 D2 0.75 7/0.37 37 786 25.55 32D237X1/5 6/120242 D2 1.5 7/0.53 37 1126 28.25 40D237X2/5 D2 2.5 7/0.67 37 1600 31.25 40D248X/75 6/120244 D2 0.75 7/0.37 48 972 28.95 40D248X1/5 6/120245 D2 1.5 7/0.53 48 1280 31.60 40D248X2/5 6/120246 D2 2.5 7/0.67 48 1960 35.10 50SE11X2/5 6/120172 E1 2.5 50/0.25 1 174 12.60 20E22X2/5 6/120170 E2 2.5 50/0.25 2 342 16.85 25E24X2/5 6/120171 E2 2.5 50/0.25 4 445 18.65 25E27X2/5 6/120173 E2 2.5 50/0.25 7 590 21.20 32

E210X2/5 6/120174 E2 2.5 50/0.25 10 784 25.55 32E212X2/5 6/120175 E2 2.5 50/0.25 12 868 26.25 40E3TPWS 6/160090 E3TPWS 2.5 50/0.25 1pr 250 17.50 25

Page 80: 6629983 Cleveland Catalogue

RAILWAY CABLESPOWER CABLESSolid plain aluminium sectoral conductors XLPE insulated, PVC outer sheath,Black to BR800 06/142639. 600/1000 volts grade to BS 5467.

82R

AIL

WAY

CA

BLE

S

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

CCC RAIL CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLANDCODE CODE SIZE CORES (KG/KM) DIAMETER SIZE

(MM2)SAC2X16NA 6/142419 16 2 420 14.30 25SAC2X25NA 6/142519 25 2 455 16.60 25SAC2X35NA 6/142609 35 2 525 18.00 25SAC2X50NA 6/142629 50 2 620 20.40 32SAC2X70NA 6/142639 70 2 840 22.80 32SAC2X95NA 6/142644 95 2 1020 26.20 40SAC4X70NA 6/151469 70 4 1750 30.60 40

TRACK FEEDER CABLESUncompacted circular stranded aluminium to BS6360 or uncompacted circularstranded tinned copper to BS6360. CSP sheathed type RS4 to BS6899, black.

CCC RAIL POLARITY CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLANDCODE CODE SIZE CORES (KG/KM) DIAMETER SIZE

(MM2)TRACK150 6/116601 NEGATIVE 150 AL 37/2.25 1 540 19.40 25TRACK161 6/132340 NEGATIVE 161 CU 91/1.53 1 1887 24.80 32TRACK240 6/132990 NEGATIVE 240 AL 61/2.25 1 1076 28.30 40TRACK500 6/132840 POSITIVE 500 AL 61/3.20 1 2245 40.20 50

TRACK500CU 6/132992 NEGATIVE 500 CU 91/2.65 1 5291 40.60 50TRACK630CU 6/116612 POSITIVE 630 CU 127/2.52 1 6692 44.20 63S

TRACK800 6/132991 NEGATIVE 800 AL 127/2.85 1 3255 48.50 63STRACK1000 6/116610 POSITIVE 1000 AL 127/3.20 1 3943 53.00 63

Page 81: 6629983 Cleveland Catalogue

83

MARINE ANDOFFSHORE CABLES

MA

RIN

E AN

D O

FFSHO

RE C

AB

LES

Page 82: 6629983 Cleveland Catalogue

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLANDCODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE

(MM) (MM)6571TQ1/5 1.5 7/0.53 1 49 5.5 20/166572TQ1/5 1.5 7/0.53 2 125 8.9 20S6573TQ1/5 1.5 7/0.53 3 150 9.4 20S6574TQ1/5 1.5 7/0.53 4 180 10.3 20S6575TQ1/5 1.5 7/0.53 5 190 11.0 20S6576TQ1/5 1.5 7/0.53 6 240 12.2 206577TQ1/5 1.5 7/0.53 7 275 12.5 206578TQ1/5 1.5 7/0.53 8 295 13.3 25

6570/10TQ1/5 1.5 7/0.53 10 360 16.2 256570/12TQ1/5 1.5 7/0.53 12 440 16.4 256570/19TQ1/5 1.5 7/0.53 19 740 19.3 326570/27TQ1/5 1.5 7/0.53 27 970 23.5 326570/30TQ1/5 1.5 7/0.53 30 1015 24.3 326570/37TQ1/5 1.5 7/0.53 37 1220 26.0 40

6571TQ2/5 2.5 7/0.67 1 63 6.0 20/166572TQ2/5 2.5 7/0.67 2 160 9.8 20S6573TQ2/5 2.5 7/0.67 3 190 10.4 20S6574TQ2/5 2.5 7/0.67 4 240 11.4 206575TQ2/5 2.5 7/0.67 5 280 12.6 206576TQ2/5 2.5 7/0.67 6 470 16.9 256577TQ2/5 2.5 7/0.67 7 355 13.7 256578TQ2/5 2.5 7/0.67 8 398 15.3 25

6570/10TQ2/5 2.5 7/0.67 10 519 17.7 256570/12TQ2/5 2.5 7/0.67 12 650 18.3 256570/19TQ2/5 2.5 7/0.67 19 860 21.7 326570/27TQ2/5 2.5 7/0.67 27 1220 26.3 406570/30TQ2/5 2.5 7/0.67 30 1270 27.1 406570/37TQ2/5 2.5 7/0.67 37 1610 29.5 40

6571TQ4 4.0 7/0.85 1 90 6.9 20/166572TQ4 4.0 7/0.85 2 240 12.0 206573TQ4 4.0 7/0.85 3 280 12.7 206574TQ4 4.0 7/0.85 4 360 13.9 256575TQ4 4.0 7/0.85 5 425 15.3 256577TQ4 4.0 7/0.85 7 530 17.7 256571TQ6 6.0 7/1.04 1 115 7.5 20/166572TQ6 6.0 7/1.04 2 305 13.1 206573TQ6 6.0 7/1.04 3 370 13.9 256574TQ6 6.0 7/1.04 4 475 15.4 25

84

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

MARINE AND OFFSHORE CABLESTinned annealed stranded copper conductors, ethylene propylene rubber (EPR)insulated, low smoke, zero halogen (LSOH) outer sheath. Black. 600/1000 voltsgrade to BS6883 and IEC 92-3.

EPR INSULATED NON-ARMOURED

SHIPWIRING CABLE(1.5MM2 TO 6MM2)

MA

RIN

E A

ND

OFF

SHO

RE

CA

BLE

S

Core identification:White with Black numbers.

Single cores available in either Blackor Green/Yellow outer sheath.

Should not be installed attemperatures below -15°C.

Page 83: 6629983 Cleveland Catalogue

MA

RIN

E AN

D O

FFSHO

RE C

AB

LES

MARINE AND OFFSHORE CABLESTinned annealed stranded copper conductors, ethylene propylene rubber (EPR)insulated, low smoke, zero halogen (LSOH) outer sheath. Black. 600/1000 voltsgrade to BS6883 type SW4 and IEC 92-3.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLANDCODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE

(MM) (MM)6571TQ10 10 7/1.35 1 165 9.0 20S6572TQ10 10 7/1.35 2 470 16.0 256573TQ10 10 7/1.35 3 595 17.2 256574TQ10 10 7/1.35 4 745 18.9 256571TQ16 16 7/1.70 1 230 10.1 20S6572TQ16 16 7/1.70 2 655 18.3 256573TQ16 16 7/1.70 3 830 19.5 326574TQ16 16 7/1.70 4 1045 21.7 326571TQ25 25 19/1.35 1 380 12.4 206572TQ25 25 19/1.35 2 1090 22.9 326573TQ25 25 19/1.35 3 1340 24.4 326574TQ25 25 19/1.35 4 1680 27.1 406571TQ35 35 19/1.53 1 490 13.6 256572TQ35 35 19/1.53 2 1310 25.3 326573TQ35 35 19/1.53 3 1630 27.1 406574TQ35 35 19/1.53 4 2130 30.1 406571TQ50 50 19/1.78 1 640 15.5 256572TQ50 50 19/1.78 2 1720 29.0 406573TQ50 50 19/1.78 3 2210 30.9 406574TQ50 50 19/1.78 4 2840 34.6 50S6571TQ70 70 19/2.14 1 870 17.5 256573TQ70 70 19/2.14 3 3080 35.3 50S6574TQ70 70 19/2.14 4 3950 39.2 506571TQ95 95 37/1.78 1 1150 19.6 326573TQ95 95 37/1.78 3 4060 40.3 506574TQ95 95 37/1.78 4 5170 45.1 63S

6571TQ120 120 37/2.03 1 1440 21.4 326573TQ120 120 37/2.03 3 5130 44.4 63S6571TQ150 150 37/2.25 1 1770 23.8 326571TQ185 185 37/2.52 1 2200 26.3 406571TQ240 240 61/2.25 1 2780 29.5 406571TQ300 300 61/2.52 1 3450 32.6 50S6571TQ400 400 91/2.36 1 4400 36.7 50S6571TQ500 500 91/2.65 1 5600 40.5 506571TQ630 630 127/2.52 1 6910 44.4 63S

EPR INSULATED NON-ARMOURED

SHIPWIRING CABLE(10MM2 TO 630MM2)

85

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

Single core cables are available inBlack or Green/Yellow outer sheath.

Temperature limits:-30 to +85°C.

Bending radius:up to 25mm - 4 x overall diameter.above 25mm - 6 x overall diameter.

Core identification:White with Black numbers.

Should not be installed attemperatures below -15°C.

Page 84: 6629983 Cleveland Catalogue

MA

RIN

E A

ND

OFF

SHO

RE

CA

BLE

S86

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

MARINE AND OFFSHORE CABLESTinned annealed stranded copper conductors, ethylene propylene rubber (EPR)insulated, low smoke, zero halogen (LSOH) bedding, galvanised steel wirebraid armour, low smoke, zero halogen (LSOH) SW4 outer sheath. Black.600/1000 volts grade to BS6883 IEE 92-3.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLANDCODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE

(MM) (MM)6582TQ1/5 1.5 7/0.53 2 300 13.3 20S6583TQ1/5 1.5 7/0.53 3 325 13.8 20S6584TQ1/5 1.5 7/0.53 4 395 15.0 20S6585TQ1/5 1.5 7/0.53 5 407 15.2 20S6586TQ1/5 1.5 7/0.53 6 425 16.5 206587TQ1/5 1.5 7/0.53 7 525 17.2 20

6580/12TQ1/5 1.5 7/0.53 12 790 21.7 256580/19TQ1/5 1.5 7/0.53 19 1090 24.7 256580/27TQ1/5 1.5 7/0.53 27 1515 29.3 326580/37TQ1/5 1.5 7/0.53 37 1870 33.2 32

6582TQ2/5 2.5 7/0.67 2 350 14.2 20S6583TQ2/5 2.5 7/0.67 3 400 15.0 20S6584TQ2/5 2.5 7/0.67 4 470 16.1 206585TQ2/5 2.5 7/0.67 5 485 16.9 206586TQ2/5 2.5 7/0.67 6 550 18.2 206587TQ2/5 2.5 7/0.67 7 635 18.5 20

6580/12TQ2/5 2.5 7/0.67 12 990 23.9 256580/19TQ2/5 2.5 7/0.67 19 1390 27.6 326580/27TQ2/5 2.5 7/0.67 27 1990 33.2 326580/37TQ2/5 2.5 7/0.67 37 2500 36.7 40

6582TQ4 4.0 7/0.85 2 480 16.6 206583TQ4 4.0 7/0.85 3 530 17.3 206584TQ4 4.0 7/0.85 4 585 18.4 206585TQ4 4.0 7/0.85 5 700 20.2 206587TQ4 4.0 7/0.85 7 897 22.7 25

EPR INSULATED BRAIDED ARMOURSHIPWIRING CABLE(1.5MM2 TO 4MM2)

Temperature limits:-30 to +85°C.

Bending radius:6 x overall diameter.

Core identification:White with Black numbers.

Should not be installed attemperatures below -15˚C.

Page 85: 6629983 Cleveland Catalogue

MA

RIN

E AN

D O

FFSHO

RE C

AB

LES

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLANDCODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE

(MM) (MM)6582TQ6 6 7/1.04 2 570 17.9 206583TQ6 6 7/1.04 3 635 18.7 206584TQ6 6 7/1.04 4 760 20.1 20

6582TQ10 10 7/1.35 2 750 21.0 256583TQ10 10 7/1.35 3 930 22.4 256584TQ10 10 7/1.35 4 1080 24.0 256582TQ16 16 7/1.70 2 1020 23.7 256583TQ16 16 7/1.70 3 1190 24.9 256584TQ16 16 7/1.70 4 1450 26.9 256582TQ25 25 19/1.35 2 1500 29.0 326583TQ25 25 19/1.35 3 1800 30.7 326584TQ25 25 19/1.35 4 2500 33.6 406582TQ35 35 19/1.53 2 1810 31.0 326583TQ35 35 19/1.53 3 2400 34.0 406584TQ35 35 19/1.53 4 2880 36.2 406582TQ50 50 19/1.78 2 2510 36.0 406583TQ50 50 19/1.78 3 3000 38.1 406584TQ50 50 19/1.78 4 3670 41.0 50S6582TQ70 70 19/2.14 2 2940 36.0 406583TQ70 70 19/2.14 3 3980 42.8 50S6584TQ70 70 19/2.14 4 4840 46.1 506582TQ95 95 37/1.78 2 3813 40.9 50S6583TQ95 95 37/1.78 3 5290 48.5 506584TQ95 95 37/1.78 4 6310 52.6 63S

6582TQ120 120 37/2.03 2 4692 44.9 50S6583TQ120 120 37/2.03 3 6480 52.9 63S6584TQ120 120 37/2.03 4 7770 57.4 63S6582TQ150 150 37/2.25 2 5634 48.9 506583TQ150 150 37/2.25 3 7700 57.9 63S6584TQ150 150 37/2.25 4 9400 63.1 636582TQ185 185 37/2.52 3 9550 63.8 636583TQ185 185 37/2.52 4 11520 69.6 75S6584TQ240 240 61/2.25 3 12300 71.5 756582TQ240 240 61/2.25 4 14840 78.3 906583TQ300 300 61/2.52 3 14850 78.8 906584TQ300 300 61/2.52 4 17938 84.9 90

MARINE AND OFFSHORE CABLESTinned annealed stranded copper conductors, ethylene propylene rubber (EPR)insulated, low smoke, zero halogen (LSOH) bedding, galvanised steel wirebraid armour, low smoke, zero halogen (LSOH) outer sheath. Black. 600/1000volts grade to BS6883 & IEE92-3 .

EPR INSULATED BRAIDED ARMOURED

SHIPWIRING CABLE (6MM2 TO 300MM2)

87

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

Temperature limits:-30 TO +85°C.

Bending radius:6 x overall diameter

Core identification:White with Black numbers.

Should not be installed attemperatures below -15°C.

Page 86: 6629983 Cleveland Catalogue

MA

RIN

E A

ND

OFF

SHO

RE

CA

BLE

S88

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

MARINE AND OFFSHORE CABLESTinned annealed stranded copper conductors, ethylene propylene rubber (EPR)insulated, low smoke, zero halogen (LSOH) bedding tinned phosphor bronzebraid armour, low smoke, zero halogen (LSOH) outer sheath. Black. 600/1000volts grade to BS6883 & IEE92-3 .

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLANDCODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE

(MM) (MM)6591TQ6 6 7/1.04 1 245 11.7 20/16

6591TQ10 10 7/1.35 1 320 13.4 20S6591TQ16 16 7/1.70 1 395 14.5 20S6591TQ25 25 19/1.35 1 565 17.3 206591TQ35 35 19/1.53 1 740 18.4 206591TQ50 50 19/1.78 1 940 20.3 206591TQ70 70 19/2.14 1 1270 22.7 256591TQ95 95 37/1.78 1 1600 25.0 25

6591TQ120 120 37/2.03 1 1930 27.2 326591TQ150 150 37/2.25 1 2330 29.5 326591TQ185 185 37/2.52 1 3000 33.1 326591TQ240 240 61/2.25 1 3710 36.6 406591TQ300 300 61/2.52 1 4480 40.0 50S6591TQ400 400 91/2.36 1 5340 43.9 50S6591TQ500 500 91/2.65 1 6540 48.1 506591TQ630 630 127/2.52 1 8000 52.3 50

EPR INSULATED SINGLECORE BRAIDED

SHIPWIRING CABLE(6MM2 TO 630MM2)

Temperature limits:-30 to +85°C.

Bending radius:6 x overall diameter.

Core identification:White.

Should not be installed attemperatures below -15°C.

Page 87: 6629983 Cleveland Catalogue

89

FIREPROOF CABLES

FIREPRO

OF C

AB

LES

Page 88: 6629983 Cleveland Catalogue

FIREPROOF CABLESSolid plain annealed copper conductors, magnesium oxide insulated, solid coppersheath to BS6207, IEC 331 and BS 6387 CWZ. Available in the following options:

(a) Light Duty = 500 volts grade (b) Outer sheath finishes, bare copper, Heavy Duty = 1000 volts grade PVC or LSF

(c) Outer sheath colours. Orange, Redor White.

SIZE BARE SHEATHED OVERALL OVERALL GLAND SINGLE HOLE CLIP NOMINALREF. KG/KM KG/KM DIAMETER DIAMETER FOR USE REFERENCE STD DRUM

BARE SHEATHED WITH RPS BARE SHEATHED LTHS (MTS)(MM) (MM) SEALS

2L1.0 105 126 5.1 6.4 20 20 26 5002L1.5 131 154 5.7 7.0 20 20 28 5002L2.5 180 206 6.6 7.9 20 26 32 5002L4.0 262 322 7.7 9.2 20 30 37 5003L1.0 136 159 5.8 7.1 20 22 28 5003L1.5 168 194 6.4 7.7 20 24 30 5003L2.5 222 272 7.3 8.8 20 28 34 5004L1.0 162 187 6.3 7.6 20 24 30 5004L1.5 203 231 7.0 8.3 20 28 34 5004L2.5 286 336 8.1 9.6 20 32 37 5007L1.5 310 351 8.4 9.9 25 32 40 3807L2.5 433 475 9.7 11.2 25 37 43 2851H6.0 173 213 6.4 7.7 20 24 34 6501H10 233 273 7.3 8.8 20 28 34 5101H16 321 361 8.3 9.8 20 32 37 4001H25 456 506 9.6 11.1 20 37 43 2751H35 600 650 10.7 12.2 20 40 47 2221H50 782 842 12.1 13.6 25 47 54 1701H70 1087 1147 13.7 15.2 25 54 59 1901H95 1450 1520 15.4 17.4 25 59 67 155

1H120 1790 1870 16.8 18.8 32 63 75 1351H150 2130 2230 18.4 20.4 32 71 79 1101H240 3146 3312 23.3 26.1 40 88 101 67

Temperature limits:PVC sheath -20 to +70°C.LSF sheath -20 to +80C.

Bending radius: 6 x overall diameter.

Should not be installed attemperatures below 0°C.

Should not be installed attemperatures below 0°C.

SIZE BARE SHEATHED OVERALL OVERALL GLAND SINGLE HOLE CLIP NOMINALREF. KG/KM KG/KM DIAMETER DIAMETER FOR USE REFERENCE STD DRUM

BARE SHEATHED WITH RPS BARE SHEATHED LTHS (MTS)(MM) (MM) SEALS

2H1.5 224 259 7.9 9.4 20 30 37 5002H2.5 275 314 8.7 10.2 20 34 40 5002H4.0 355 398 9.8 11.3 20 37 43 5002H6.0 433 483 10.9 12.4 20 43 47 5002H10 637 697 12.7 14.2 25 47 54 5002H16 888 968 14.7 16.2 25 54 63 1122H25 1175 1275 17.1 19.1 32 67 75 803H1.5 253 290 8.3 9.8 20 32 37 5003H2.5 324 365 9.3 10.8 20 37 43 5003H4.0 416 461 10.4 11.9 20 40 47 5003H6.0 530 590 11.5 13.0 25 43 51 1843H10 783 853 13.6 15.1 25 54 59 1303H16 1000 1080 15.6 17.1 25 59 71 1003H25 1442 1548 18.2 20.2 40 71 79 704H1.5 303 344 9.1 10.6 20 34 43 5004H2.5 385 430 10.1 11.6 20 40 47 5004H4.0 517 577 11.4 12.9 25 43 54 1954H6.0 658 718 12.7 14.2 25 47 54 1444H10 980 1050 14.8 16.3 25 54 63 1104H16 1300 1390 17.3 19.3 32 67 75 894H25 1800 1943 20.1 22.3 40 79 88 607H1.5 431 478 10.8 12.3 25 43 47 2457H2.5 561 614 12.1 13.6 25 47 54 195

12H2.5 875 970 15.6 17.9 32 59 71 14819H1.5 989 1086 16.6 18.9 40 63 71 112

MINERAL INSULATED CABLE

FIR

EPRO

OF

CA

BLE

S90

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

Page 89: 6629983 Cleveland Catalogue

FIREPRO

OF C

AB

LES91

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

FIREPROOF CABLESPlain annealed copper conductor, silicon rubber insulated aluminium/polyestertape screen, tinned annealed copper earth wire, low smoke halogen free (LSOH)outer sheath. Red, White, Orange or Black. Fire resistant to IEC 331 and BS6387.Flame retardant to BS5839-1:2003 and IEC 332 PT3 CAT CWZ.

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND 1 HOLE GLANDCODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE CLIP REF REF

(MM) (MM)FP2X1 1.0 1/1.13 2+E 90 7.5 20 32 251FP3X1 1.0 1/1.13 3+E 110 8.0 20 34 251FP4X1 1.0 1/1.13 4+E 135 8.8 20 40 251FP7X1 1.0 1/1.13 7+E 170 10.5 20 47 252

FP12X1 1.0 1/1.13 12+E 270 13.7 25 59 254FP2X1/ 5 1.5 1/1.38 2+E 110 8.0 20 34 251FP3X1/ 5 1.5 1/1.38 3+E 130 8.4 20 40 251FP4X1/5 1.5 1/1.38 4+E 160 9.5 20 43 251FP7X1/5 1.5 1/1.38 7+E 230 11.3 20 51 252

FP12X1/5 1.5 1/1.38 12+E 365 15.2 25 67 254FP19X1/5 1.5 1/1.38 19+E 540 17.8 25 79 254FP2X2/5 2.5 7/0.67 2+E 160 9.0 20 40 252FP3X2/5 2.5 7/0.67 3+E 200 10.5 20 47 252FP4X2/5 2.5 7/0.67 4+E 250 11.7 20 47 252FP7X2/5 2.5 7/0.67 7+E 285 13.7 20 54 252

FP12X2/5 2.5 7/0.67 12+E 470 17.9 25 75 254FP19X2/5 2.5 7/0.67 19+E 720 21.4 32 88 255

FP2X4 4.0 7/0.85 2+E 260 11.3 20 43 252FP3X4 4.0 7/0.85 3+E 315 12.1 25 54 254FP4X4 4.0 7/0.85 4+E 380 13.3 25 54 254

FIRE RESISTANTSECURITY CABLE

(1.0MM2 TO 4MM2)

E= Earth conductor.

Temperature limits:-10 to +80°C.

Bending radius:6 x overall diameter.

Core identification:2 core - Brown, Blue.3 core - Brown, Black, Grey.4 core - Brown, Black, Grey, Blue.7 core and above - White with Blacknumbers.

Should not be installed attemperatures below 0°C.

Page 90: 6629983 Cleveland Catalogue

FIREPROOF CABLESPlain annealed stranded copper conductor, mica fire resistant tape, XLPEinsulated, low smoke halogen free (LSOH) bedding, galvanised steel wirearmour, low smoke halogen free (LSOH) outer sheath. Black. 600/1000 volts.Fire resistant to IEC 331 & BS7846 / BS6387 & CWZ.

Flame propagation to BS4066 PT1 and IEC 332 PT1 (PT3 for bunched cables).

CCC CONDUCTOR STRANDING NO. OF WEIGHT OUTSIDE GLAND SINGLECODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE CLEAT

(MM) (MM)6942F1/5 1.5 7/0.53 2 340 13.6 20S 0.66943F1/5 1.5 7/0.53 3 380 14.2 20S 0.66944F1/5 1.5 7/0.53 4 420 15.1 20S 0.66947F1/5 1.5 7/0.53 7 500 17.3 20 0.7

6940/12F1/5 1.5 7/0.53 12 820 22.1 25 0.96940/19F1/5 1.5 7/0.53 19 1080 25.8 25 1.16940/27F1/5 1.5 7/0.53 27 1550 30.4 32 1.26940/37F1/5 1.5 7/0.53 37 1850 33.4 32 1.4

6942F2/5 2.5 7/0.67 2 390 15.1 20S 0.66943F2/5 2.5 7/0.67 3 430 15.7 20S 0.76944F2/5 2.5 7/0.67 4 500 16.8 20 0.76947F2/5 2.5 7/0.67 7 730 19.8 20 0.8

6940/12F2/5 2.5 7/0.67 12 1020 24.9 25 1.06940/19F2/5 2.5 7/0.67 19 1530 29.5 32 1.26940/27F2/5 2.5 7/0.67 27 1950 34.4 40 1.46940/37F2/5 2.5 7/0.67 37 2440 37.8 40 1.6

6942F4 4 7/0.85 2 460 16.1 20 0.76943F4 4 7/0.85 3 530 16.9 20 0.76944F4 4 7/0.85 4 700 18.1 20 0.86947F4 4 7/0.85 7 840 21.6 25 0.96942F6 6 7/1.04 2 640 17.3 20 0.76943F6 6 7/1.04 3 730 18.1 20 0.86944F6 6 7/1.04 4 850 20.3 20 0.8

6942F10 10 7/1.35 2 820 20.0 20 0.86943F10 10 7/1.35 3 940 21.0 25 0.96944F10 10 7/1.35 4 1090 22.6 25 0.96942F16 16 7/1.70 2 1025 22.1 25 0.96943F16 16 7/1.70 3 1370 23.5 25 1.06944F16 16 7/1.70 4 1560 26.0 25 1.1

FIRE RESISTANT POWERAND CONTROL CABLE(1.5MM2 TO 16MM2)

FIR

EPRO

OF

CA

BLE

S92

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

Temperature limits:-25 to +90°C.

Bending radius:8 x overall diameter.

Core identification:2 core - Brown, Blue.3 core - Brown, Black, Grey.4 core - Brown, Black, Grey, Blue.7 core and above - White with Black numbers.

Should not be installed attemperatures below 0°C.

Page 91: 6629983 Cleveland Catalogue

93

Please note that cleat sizes are intended to be indicative and may vary according to different manufacturers tolerances.

FIREPRO

OF C

AB

LES

FIREPROOF CABLESPlain annealed stranded copper conductor, mica fire resistant tape, XLPEinsulated, low smoke, zero halogen (LSOH) bedding, galvanised steel wirearmour, low smoke, zero halogen (LSOH) outer sheath. Black. 600/1000 voltsgrade. Fire resistant to BS6387/7846 & CWZ.

Flame propagation to BS4066 PT1 and IEC 332 PT1 (PT3 for bunched cables).

CCC CONDUCTOR STRANDING NO. OF WEIGHT OVERALL GLAND SINGLECODE SIZE (MM2) (MM) CORES KG/KM DIAMETER SIZE CLEAT

(MM) (MM)FP 2X25 25 7/2.14 2 1200 22.0 25 0.9FP 3X25 25 7/2.14 3 1800 27.4 25 1.1FP 4X25 25 7/2.14 4 2100 29.1 32 1.2FP 2X35 35 7/2.52 2 1600 24.8 25 1.0FP 3X35 35 7/2.52 3 2100 29.2 32 1.2FP 4X35 35 7/2.52 4 2500 32.2 32 1.4FP 2X50 50 19/1.78 2 2000 28.0 32 1.2FP 3X50 50 19/1.78 3 2600 33.0 32 1.4FP 4X50 50 19/1.78 4 3200 35.0 40 1.4FP 2X70 70 19/2.14 2 2400 30.7 40 1.4FP 3X70 70 19/2.14 3 3400 37.0 40 1.6FP 4X70 70 19/2.14 4 4500 40.2 50S 1.6FP 2X95 95 19/2.52 2 3300 35.3 40 1.4FP 3X95 95 19/2.52 3 4500 40.6 50S 2.0FP 4X95 95 19/2.52 4 5600 44.0 50S 1.8

FP 2X120 120 37/2.03 2 3800 36.6 40 1.6FP 3X120 120 37/2.03 3 5500 43.8 50S 1.8FP 4X120 120 37/2.03 4 7200 48.4 50 2.0FP 2X150 150 37/2.25 2 4400 39.3 40 1.6FP 3X150 150 37/2.25 3 6900 48.0 50 2.0FP 4X150 150 37/2.25 4 8500 52.5 50 R9FP 2X185 185 37/2.52 2 5700 44.2 50S 1.8FP 3X185 185 37/2.52 3 8200 52.0 50 R9FP 4X185 185 37/2.52 4 10300 57.1 63S R10FP 2X240 240 61/2.25 2 7200 48.0 50 2.0FP 3X240 240 61/2.25 3 10200 57.1 63S R10FP 4X240 240 61/2.25 4 12800 62.7 63 R10FP 2X300 300 61/2.52 2 8300 51.8 63S R9FP 3X300 300 61/2.52 3 12200 63.0 63 R10FP 4X300 300 61/2.52 4 15600 69.6 75S R11FP 3X400 400 61/2.85 3 15000 69.5 75S R11FP 4X400 400 61/2.85 4 20400 78.0 75 R12

FIRE RESISTANT POWER CABLE

(25MM2 TO 400MM2)

Temperature limits:-25 to +90°C.

Bending radius:8 x overall diameter.

Core identification:2 core - Brown, Blue.3 core - Brown, Black, Grey.4 core - Brown, Black, Grey, Blue.

Should not be installed attemperatures below 0°C.

Page 92: 6629983 Cleveland Catalogue

94

Page 93: 6629983 Cleveland Catalogue

INSTALLATIONACCESSORIES

INSTA

LLATION

ACC

ESSOR

IES95

Page 94: 6629983 Cleveland Catalogue
Page 95: 6629983 Cleveland Catalogue

LML

LML Products LimitedSince its inception in 1968, LML has designed, manufactured and supplied acomprehensive range of copper tube terminals including bespoke specials.With in-house tooling and electroplating facilities, LML will always provide asolution for its quality focused customers in compliance with BS EN ISO9001:2000

Copper Tube TerminalsLML terminals are manufactured from seamless copper tube to BS EN 12449and feature bell mouth entry up to 400mm2 and chamfered entry from500mm2 to 1000mm2. All terminals and splices (other than parallel splices)are provided with an inspection hole to ensure the conductor is fully insertedbefore crimping. Internal barrel diameters suit standard cables as defined inBS EN 6360.

Standard finish is bright electro tin plating to BS EN 1872. Other finishes canbe provided, e.g. nickel or silver. Terminals are independently tested to complywith BS EN 61238-1, and are also approved for military use and by LondonUnderground.

Crimp ToolingLML Products also supply a large range of manual hydraulic tools for crimpingterminals from 1.5mm2 to 1000mm2. LML also supplies a range of hydrauliccrimping tools with rechargeable battery.

Med/High Voltage Crimp TerminalsLML Products manufactures a range of copper tube terminals to suit 11kv and33kv. We also manufacture water blocked splices and terminals.

97

Page 96: 6629983 Cleveland Catalogue
Page 97: 6629983 Cleveland Catalogue
Page 98: 6629983 Cleveland Catalogue
Page 99: 6629983 Cleveland Catalogue

RAXTON LIMITED

Raxton products are designed to solve the fundamental difficulties whichexist due to the variety of thread forms currently in use within the electricalindustry. These thread forms are predominantly Isometric, Imperial, N.P.T., BSPand PG.

Problems caused by dissimilar threads can occur in many environmentsincluding industrial, EExd, EExe and mining. Raxton conversions are fullyapproved to meet these requirements, being certified by leading testauthorities including BASEEFA, SIRA, ISSEP, KEMA, DET NORSKE VERITAS andStandards Association of Australia. They are marked accordingly.

Standard material is brass and readily available alternatives include mild steel, stainless steel and aluminium. Our EExe range is also available in glassfilled nylon.

ADAPTORSREDUCERSHEXAGON HEAD PLUGSRIGHT ANGLE ADAPTORSMALE TO MALE ADAPTORSUNIONSSTOPPING PLUGSEARTH LEAD ADAPTORSTHREADED EARTH PLATES

NYLON GLANDSSCREWED NIPPLING COUPLERSBUSHESSHROUDSLOCKNUTS/LOCKRINGSEARTH TAGSWASHERS

101

Page 100: 6629983 Cleveland Catalogue
Page 101: 6629983 Cleveland Catalogue
Page 102: 6629983 Cleveland Catalogue

W. J. FURSE & COMPANY LIMITED

E-Klips is a division of W J Furse & Co Ltd, a multi-disciplined engineering andmarketing company employing nearly 200 people worldwide.

We are the largest UK manufacturer of a comprehensive range of industrialfasteners, which are made available to the electrical/mechanical industry.

They provide a quick, efficient method of fixing without drilling or bracket making.

Our commitment to quality has set industry standards while our new designsbring you all the benefits of E-Klips continuous product development philosophy.

Wholly manufactured in the UK, E-Klips fasteners can be found throughoutEurope and in many other countries in the world where our unequalledcombination of speed and quality is properly appreciated.

This combination can give you savings of up to 60% over a completeinstallation – a very significant competitive advantage!

E-Klips are available for every type of installation through our establisheddistributor network who are fully supported by our stocks and service.

So, if you would like to use the faster fastener, simply specify E-Klips and putyour opposition in the shade.

104

Page 103: 6629983 Cleveland Catalogue

W. J. FURSE & COMPANY LIMITED

As a recognised world leader in the Earthing and Lightning Protection Industry,W J Furse has a proven track record spanning over one hundred years.

The range complies with the requirements of relevant British and Worldstandards, and our design and manufacturing quality control systems areindependently assessed and approved to ISO9001. W J Furse can also offer alevel of competitiveness, service and technical support that is the envy ofcompetitors both in the UK and overseas.

Our extensive range includes the following:

Earth Rods Copperbond, solid copper and stainless steel.

Earth PitsLightweight, high performance plastic and regular duty concrete pits.

FittingsClamps, bonds, clips and accessories in copper and aluminium alloys andplastics suitable for flat tape and solid circular conductor systems.

ConductorsAn extensive range of copper and aluminium conductors available bare andPVC covered.

Specialist ProductsIncluding weldable and adhesive conductor clips and earth rod seals.

Furseweld ProcessAn exothermic welding process with a simple self contained method offorming high quality electrical connections which do not require externalpower or heat source, making the process completely portable.

105

Page 104: 6629983 Cleveland Catalogue

106

CF1

CF2

CF9CF14

CF21

CF3

CF4

CF5

CF15CF22

CF10/1 CF16 CF23

CF11 CF17 CF24

CF6

CF7

CF19

CF20

CF25

CF26

CF18

CF12

CF13

CF8

CF27

CF28

CF29

CF34

CF35

CF36

CF37

CF38/1CF38/2

CF39

CF40

CF41*

CF42*

CF44

CF45*

CF46

PL1 PVCGL1 Galv

CA1Available in 150, 300,450, 600, 750mm

CA2Available in 150, 300,450, 600, 750mm

CA3Available in 150, 300,450, 600, 750mm

FA1Pvc 2

Pvc 1

M6, M8, M10M12 x 3MTR Lengthsof Threaded Rod

CF47

CCC1 41x21x2.5Available in Both Plain and Slotted

CCC3 41x41x2.5Available in Both Plain and Slotted

CCC2 41x21x2.5 Double

CCC4 41x41x2.5 DoubleAvailable FinishesPre Galvanised to BS 2989HDG TO BS 729Stainless Steel 316

Long Spring Channel Nuts

M6 ZL6M8 ZL8M10 ZL10M12 ZL12

Short Spring Channel Nuts

M6 ZS6M8 ZS8M10 ZS10M12 ZS12

Plain Channel Nuts

M6 ZN6M8 ZN8M10 ZN10M12 ZN12

M10 x 40Cone PointedSet Screws

M6 x 12, 16, 20, 25,30, 35 40 and 50mmRoofing Nutsand Bolts

M6 x 8, M10 andM12 x 20, 25, 30,35, 40 and 50mmHex HeadSet Screws

M6, M8, M10 andM12Hex Nuts, Flatand SpringWashers

FRAMING AND SUPPORT SYSTEMS

Page 105: 6629983 Cleveland Catalogue

107

CF1

CF2

CF9CF14

CF21

CF3

CF4

CF5

CF15CF22

CF10/1 CF16 CF23

CF11 CF17 CF24

CF6

CF7

CF19

CF20

CF25

CF26

CF18

CF12

CF13

CF8

CF27

CF28

CF29

CF34

CF35

CF36

CF37

CF38/1CF38/2

CF39

CF40

CF41*

CF42*

CF44

CF45*

CF46

PL1 PVCGL1 Galv

CA1Available in 150, 300,450, 600, 750mm

CA2Available in 150, 300,450, 600, 750mm

CA3Available in 150, 300,450, 600, 750mm

FA1Pvc 2

Pvc 1

M6, M8, M10M12 x 3MTR Lengthsof Threaded Rod

CF47

CCC1 41x21x2.5Available in Both Plain and Slotted

CCC3 41x41x2.5Available in Both Plain and Slotted

CCC2 41x21x2.5 Double

CCC4 41x41x2.5 DoubleAvailable FinishesPre Galvanised to BS 2989HDG TO BS 729Stainless Steel 316

Long Spring Channel Nuts

M6 ZL6M8 ZL8M10 ZL10M12 ZL12

Short Spring Channel Nuts

M6 ZS6M8 ZS8M10 ZS10M12 ZS12

Plain Channel Nuts

M6 ZN6M8 ZN8M10 ZN10M12 ZN12

M10 x 40Cone PointedSet Screws

M6 x 12, 16, 20, 25,30, 35 40 and 50mmRoofing Nutsand Bolts

M6 x 8, M10 andM12 x 20, 25, 30,35, 40 and 50mmHex HeadSet Screws

M6, M8, M10 andM12Hex Nuts, Flatand SpringWashers

Page 106: 6629983 Cleveland Catalogue

108

Page 107: 6629983 Cleveland Catalogue

CURRENT RATINGS

CU

RR

ENT

RATIN

GS

109

Page 108: 6629983 Cleveland Catalogue

110C

UR

REN

TR

ATIN

GS

PVC AND LSF CONDUIT WIRING CABLESPVC INSULATED ONLY, SINGLE CORE GENERAL PURPOSE WIRING CABLES TO BS6004 XL-LSF INSULATED ONLY, SINGLE CORE WIRING CABLES TO BS7211

Current Carrying Capacity (Amperes)

Note: Where the conductor is to be protected by a semi-enclosed fuse to BS3036, see item 6.2 of the preface toappendix 4 of BS7671, the 16th Edition of the IEE Wiring Regulations.

The current-carrying capacities in columns 2 to 5 are also applicable to flexible cables to BS 7211 Table 3(b) where thecables are used in fixed installations.

For cable in rigid PVC conduit the values stated in Table 4D1 of BS 7671, the 16th Edition of the IEE Wiring Regulationsare applicable (See Regulations 521-05).

Where a conductor operates at a temperature exceeding 70°C it shall be ascertained that the equipment connectedto the conductor is suitable for the conductor operating temperature (See Regulation 512-02 of BS 7671, the 16thEdition of the IEE Wiring Regulations).

Table derived from IEE copyright information.

BS 7671 - 16th Edition, IEE Wiring Regulations.

Ambient temperature: 30°C.

Conductor operating temperature: 90°C.

CONDUCTOR REFERENCE METHOD 4 REFERENCE METHOD 3 REFERENCE METHOD 1 REFERENCE METHOD 11 REFERENCE METHOD 12 (FREE AIR)CROSS (ENCLOSED IN CONDUIT (ENCLOSED IN CONDUIT (CLIPPED DIRECT) (ON A PERFORATED

SECTIONAL IN THERMALLY ON A WALL OR IN CABLE TRAY HORIZONTAL VERTICAL TREFOILAREA INSULATING WALL ETC.) TRUNKING ETC.) HORIZONTAL OR FLAT SPACED FLAT SPACED

VERTICAL)2 CABLES 3 OR 4 2 CABLES 3 OR 4 2 CABLES 3 OR 4 2 CABLES 3 OR 4 2 CABLES 2 CABLES 3 CABLES

SINGLE CABLES 3 SINGLE CABLES SINGLE CABLES SINGLE CABLES SINGLE SINGLE TREFOILPHASE PHASE A. C PHASE 3 PHASE PHASE 3 PHASE PHASE 3 PHASE PHASE PHASE 3 PHASE

A.C. or D.C A.C. OR D.C. A.C. A.C. OR D.C. A.C FLAT & A.C or D.C. A.C. FLAT & A.C. OR D.C. A.C. OR D.C. A.C.FLAT & TOUCHING FLAT & TOUCHING OR 3 CABLES OR 3 CABLES

TOUCHING OR TREFOIL TOUCHING OR TREFOIL 3 PHASE 3 PHASE1 2 3 4 5 6 7 8 9 10 11 12

MM2 AMP AMP AMP AMP AMP AMP AMP AMP AMP AMP AMP1 14 13 17 15 19 17.5 - - - - -

1.5 18 17 22 19 25 23 - - - - -2.5 24 23 30 26 34 31 - - - - -4 33 30 40 35 46 41 - - - - -6 43 39 51 45 59 54 - - - - -

10 58 53 71 63 81 74 - - - - -16 76 70 95 85 109 99 - - - - -25 100 91 126 111 143 130 158 140 183 163 13835 124 111 156 138 176 161 195 176 226 203 17150 149 135 189 168 228 209 293 215 274 246 20970 189 170 240 214 293 268 308 279 351 318 27095 228 205 290 259 355 326 375 341 426 389 330

120 263 235 336 299 413 379 436 398 495 453 385150 300 270 375 328 476 436 505 461 570 524 445185 341 306 426 370 545 500 579 530 651 600 511240 400 358 500 433 644 590 686 630 769 711 606300 459 410 513 493 743 681 794 730 886 824 701400 - - 683 584 868 793 915 849 1065 984 820500 - - 783 666 990 904 1044 973 1228 1150 936630 - - 900 764 1130 1033 1191 1115 1423 1338 1069800 - - - - 1288 1179 1358 1275 1581 1485 1214

1000 - - - - 1443 1323 1520 1436 1775 1671 1349

Page 109: 6629983 Cleveland Catalogue

111

SINGLE CORE CABLES HAVING THERMOSETTING INSULATION (NON-MAGNETIC ARMOUR), COPPER CONDUCTORS BS5467 BS6724.

Current Carrying Capacity (Amperes)

Voltage Drop per Ampere per metre (mV)

Note: Spacings larger than those specified in Method 12 (see Table 4A, BS7671 - 16th Edition, IEE Wiring Regulations)will result in larger voltage drop.

Table derived from IEE copyright information.

Conductor operating temperature: 90°C.

CONDUCTOR REFERENCE METHOD 1 REFERENCE METHOD 2 REFERENCE METHOD 12 (FREE AIR)CROSS (CLIPPED DIRECT) (ON A PERFORATED

SECTIONAL CABLE TRAY) 2 CABLES 2 CABLES D.C. 3 OR 4 CABLES, 3 PHASE A.C.AREA SINGLE PHASE A.C.

2 CABLES 3 OR 4 2 CABLES 3 OR 4 HORIZONTAL VERTICAL HORIZONTAL VERTICAL HORIZONTAL VERTICAL 3 CABLESSINGLE CABLES 3 SINGLE CABLES 3 FLAT FLAT SPACED SPACED FLAT FLAT TREFOILPHASE PHASE A.C. PHASE PHASE SPACED SPACED SPACED SPACED

A.C. OR D.C FLAT & A.C. FLAT & A.C. FLAT &FLAT & TOUCHING TOUCHING TOUCHING

TOUCHING2 3 4 5 6 7 8 9 10 11 12

MM2 AMP AMP AMP AMP AMP AMP AMP AMP AMP AMP AMP50 237 220 253 232 282 266 284 270 288 266 22270 303 277 322 293 357 337 356 349 358 331 28595 367 333 389 352 436 412 446 426 425 393 346

120 425 383 449 405 504 477 519 497 485 449 402150 488 437 516 462 566 539 600 575 549 510 463185 557 496 587 524 643 614 688 660 618 574 529240 656 579 689 612 749 714 815 782 715 666 625300 755 662 792 700 842 805 943 906 810 755 720400 853 717 899 767 929 889 1137 1094 848 797 815500 962 791 1016 851 1032 989 1314 1266 923 871 918630 1082 861 1146 935 1139 1092 1528 1474 992 940 1027800 1170 904 1246 987 1204 1155 1809 1744 1042 978 1119

1000 1261 961 1345 1055 1289 1238 2100 2026 1110 1041 1214

CONDUCTOR 2 2 CABLES - SINGLE PHASE A.C. 3 OR 4 CABLES - 3 PHASE A.C.CROSS CABLES

SECTIONAL D.C.AREA

REFERENCE METHODS REFERENCE METHOD REFERENCE METHODS REFERENCE METHODS REFERENCE METHOD1 & 11 (TOUCHING) 12 (SPACED) 1, 11 & 12 1 & 11 12

(IN TREFOIL TOUCHING) FLAT & TOUCHING) (FLAT SPACED)1 2 3 4 5 6 7

MM2 MV MV MV MV MV MVr x z r x z r x z r x z r x z

50 0.98 0.99 0.21 1.00 0.98 0.29 1.00 0.86 0.180 0.87 0.84 0.25 0.88 0.84 0.33 0.9070 0.67 0.68 0.200 0.71 0.69 0.29 0.75 0.59 0.170 0.62 0.60 0.25 0.65 0.62 0.32 0.7095 0.49 0.51 0.195 0.55 0.53 0.28 0.60 0.44 0.170 0.47 0.46 0.24 0.52 0.49 0.31 0.58

120 0.39 0.41 0.190 0.45 0.43 0.27 0.51 0.35 0.165 0.39 0.38 0.24 0.44 0.41 0.30 0.51150 0.31 0.33 0.185 0.38 0.36 0.27 0.45 0.29 0.160 0.33 0.31 0.23 0.39 0.34 0.29 0.45185 0.25 0.27 0.185 0.33 0.30 0.26 0.40 0.23 0.160 0.28 0.26 0.23 0.34 0.29 0.29 0.41240 0.195 0.21 0.180 0.28 0.24 0.26 0.35 0.180 0.155 0.24 0.21 0.22 0.30 0.24 0.28 0.37300 0.155 0.170 0.175 0.25 0.195 0.25 0.32 0.145 0.150 0.21 0.170 0.22 0.28 0.20 0.27 0.34400 0.115 0.145 0.170 0.22 0.180 0.24 0.30 0.125 0.150 0.195 0.160 0.21 0.27 0.20 0.27 0.33500 0.093 0.125 0.170 0.21 0.165 0.24 0.29 0.105 0.145 0.180 0.145 0.20 0.25 0.190 0.24 0.31630 0.073 0.105 0.165 0.195 0.150 0.23 0.27 0.092 0.145 0.170 0.135 0.195 0.24 0.175 0.23 0.29800 0.056 0.090 0.160 0.190 0.145 0.23 0.27 0.086 0.140 0.165 0.130 0.180 0.23 0.175 0.195 0.26

1000 0.045 0.092 0.155 0.180 0.140 0.21 0.25 0.080 0.135 0.155 0.125 0.170 0.21 0.165 0.180 0.24

CU

RR

ENT

RATIN

GS

Page 110: 6629983 Cleveland Catalogue

CU

RR

ENT

RAT

ING

S112

MULTICORE ARMOURED CABLES HAVING THERMOSETTING INSULATIONCOPPER CONDUCTORS BS5467 BS6724.

Current Carrying Capacity (Amperes)

CONDUCTOR REFERENCE METHOD 1 REFERENCE METHOD 11CROSS SECTIONAL (CLIPPED DIRECT) (ON A PERFORATED HORIZONTAL OR VERTICAL TRAY)

AREA OR REFERENCE METHOD 13 (FREE AIR)2 CORE CABLE 3 OR 4 2 CORE CABLE 3 OR 4SINGLE PHASE CORE CABLE, SINGLE PHASE CORE CABLE,

A.C. or D.C. 3 PHASE A.C. A.C. OR D.C. 3 PHASE A.C.1 2 3 4 5

MM2 AMP AMP AMP AMP1.5 27 23 29 252.5 36 31 39 334 49 42 52 446 62 53 66 56

10 85 73 90 7816 110 94 115 9925 146 124 152 13135 180 154 188 16250 219 187 228 19770 279 238 291 25195 338 289 354 304

120 392 335 410 353150 451 386 472 406185 515 441 539 463240 607 520 636 546300 698 599 732 628400 787 673 847 728

CONDUCTOR 2 CORE 2 CORE CABLE 3 OR 4 CABLECROSS SECTIONAL CABLE D.C SINGLE PHASE A.C. 3 PHASE A.C

AREA1 2 3 4

MM2 MV MV MV1.5 31 31 272.5 19 19 164 12 12 106 7.9 7.9 6.8

10 4.7 4.7 4.016 2.9 2.9 2.5

r x z r x z25 1.85 1.85 0.160 1.90 1.60 0.140 1.6535 1.35 1.35 0.155 1.35 1.15 0.135 1.1550 0.98 0.99 0.155 1.00 0.86 0.135 0.8770 0.67 0.67 0.150 0.69 0.59 0.130 0.6095 0.49 0.50 0.150 0.52 0.43 0.130 0.45

120 0.39 0.40 0.145 0.42 0.34 0.130 0.37150 0.31 0.32 0.145 0.35 0.28 0.125 0.30185 0.25 0.26 0.145 0.29 0.22 0.125 0.26240 0.195 0.20 0.140 0.24 0.175 0.125 0.21300 0.155 0.16 0.140 0.21 0.140 0.120 0.185400 0.120 0.13 0.145 0.195 0.115 0.125 0.170

Note: 1. Where the conductor is to be protected by asemi-enclosed fuse to BS3036, see item 6.2 of thepreface to appendix 4 of BS7671, the IEE WiringRegulations, 16th Edition.

2. Where a conductor operates at a temperatureexceeding 70°C it shall be ascertained that the

equipment connected to the conductor is suitablefor the conductor operating temperature (seeRegulation 512-02 of BS 7671, the IEE WiringRegulations, 16th Edition).

Ambient temperature: 30°C.

Conductor operating temperature: 70°C.

VoLtage Drop per Ampere per Metre (mV)

Tables derived from IEE copyright information.

Conductor operating temperature: 90°C.

Page 111: 6629983 Cleveland Catalogue

113

SINGLE CORE CABLES HAVING THERMOSETTING INSULATIONCOPPER CONDUCTORS BS5467 BS6724.

Current RATINGS (ac)

=Adjacent cable surfaces separated by one cable diameter.

NOMINAL SINGLE COREAREA OF DIRECT IN GROUND IN SINGLE-WAY DUCTS IN FREE AIR

CONDUCTOR TREFOIL GROUP FLAT SPACED= TREFOIL GROUP FLAT TOUCHING TREFOIL GROUP FLAT SPACED=UNARM’D ARM’D UNARM’D ARM’D UNARM’D ARM’D UNARM’D ARM’D UNARM’D ARM’D UNARM’D ARM’D

MM2 AMP AMP AMP AMP AMP AMP AMP AMP AMP AMP AMP AMP25 - - - - - - - - - - - -35 - - - - - - - - - - - -50 220 220 230 230 225 220 220 220 235 250 295 30070 270 270 280 280 270 260 270 270 285 310 370 37095 320 320 335 335 320 305 325 325 360 375 455 460

120 360 360 380 380 360 340 370 370 415 430 520 530150 410 410 430 430 400 375 415 410 470 490 600 600185 460 455 485 485 440 410 465 460 540 550 690 690240 530 520 560 560 505 470 540 540 640 650 820 820300 600 580 640 640 560 500 610 610 740 740 940 940400 680 650 730 730 610 530 690 690 840 840 1100 1100500 750 710 830 830 680 570 790 780 990 930 1280 1280630 830 760 940 940 750 620 890 890 1110 1040 1500 1480800 920 810 1070 1060 830 660 1010 990 1270 1140 1720 1690

1000 1000 860 1180 1170 910 690 1100 1090 1400 1230 1950 1900

CU

RR

ENT

RATIN

GS

Page 112: 6629983 Cleveland Catalogue

CU

RR

ENT

RAT

ING

S114

MULTICORE ARMOURED CABLES HAVING THERMOSETTING INSULATION, ALUMINIUM CONDUCTORS BS5467 BS6724.

Current Carrying Capacity (Amperes)

Note: 1. Where the conductor is to be protected by asemi-enclosed fuse to BS3036, see item 6.2 of thepreface to appendix 4 of BS7671, the IEE WiringRegulations, 16th Edition.

2. Where a conductor operates at a temperatureexceeding 70°C it shall be ascertained that theequipment connected to the conductor is suitable

for the conductor operating temperature (seeRegulation 512-02 of BS 7671, the IEE WiringRegulations, 16th Edition).

Ambient temperature: 30°C.

Conductor operating temperature: 90°C.

Voltage Drop per Ampere per Metre (mV)

Tables derived from IEE copyright information.

Conductor operating temperature: 90°C.

CONDUCTOR REFERENCE METHOD 1 REFERENCE METHOD 2 (ON A PERFORATED CABLE TRAY)OR CROSS SECTIONAL (CLIPPED DIRECT) REFERENCE METHOD 13 (FREE AIR)

AREA2 CORE CABLE 3 OR FOUR 2 CORE CABLE 3 OR 4SINGLE PHASE CORE CABLE, SINGLE PHASE CORE CABLE,

A.C. or D.C. 3 PHASE A.C. A.C. OR D.C. 3 PHASE A.C.1 2 3 4 5

MM2 AMP AMP AMP AMP16 82 71 85 7425 108 92 112 9835 132 113 138 12050 159 137 166 14570 201 174 211 18595 242 214 254 224

120 - 249 - 264150 - 284 - 305185 - 328 - 350240 - 386 - 418300 - 441 - 488

ONDUCTOR 2 CORE 2 CORE CABLE 3 OR 4 CABLECROSS SECTIONAL CABLE D.C. SINGLE PHASE A.C. 3 PHASE A.C.

AREA 2 3 4MM2 MV MV MV

16 4.8 4.8 4.2r x z r x z

25 3.1 3.1 0.165 3.1 2.7 0.140 2.735 2.2 2.2 0.160 2.2 1.90 0.140 1.9550 1.60 1.65 0.160 1.65 1.40 0.135 1.4570 1.10 1.10 0.155 1.15 0.96 0.135 0.9795 0.82 0.82 0.150 0.84 0.71 0.130 0.72

120 - - 0.56 0.130 0.58150 - - 0.45 0.130 0.47185 - - 0.37 0.130 0.39240 - - 0.28 0.125 0.31300 - - 0.23 0.125 0.26

Page 113: 6629983 Cleveland Catalogue

115

CURRENT RATINGS FOR FLEXIBLE CORDS; RATING FACTORS, MAXIMUM AMBIENT AND OPERATING TEMPERATURES FOR CABLES AND CORDS. COPPER CONDUCTORS

Note: The tabulated voltage drop values above are for60°C PVC insulated flexible cords. For 85°C PVCinsulated flexible cords they are to be multipliedby a factor of 1.09.

Table derived from IEE copyright information.

BS 7671 - 16th Edition, IEE Wiring Regulations.

Conductor operating temperature: 60°C.

Correction factor for ambient temperature

Maximum ambient and operating temperature for cables and cords

NOMINAL CURRENT CARRYING CAPACITY (AMPERES) VOLT DROP PER AMPERE PER METRE MAXIMUM MASSCROSS SECTIONAL D.C. OR 3 PHASE D.C. OR 3 PHASE SUPPORTABLE BY TWIN

AREA OF CONDUCTOR SINGLE PHASE A.C. A.C. SINGLE PHASE A.C. A.C. FLEXIBLE CORD (SEEREGULATION 522-8-06)

1 2 3 4 5 6MM2 AMP AMP MV MV KG0.5 3 3 93 80 2

0.75 6 6 62 54 31.0 10 10 46 40 5

1.25 13 - 37 - 51.5 16 16 32 27 52.5 25 20 19 16 54.0 32 25 12 10 5

CU

RR

ENT

RATIN

GS

AMBIENT TEMPERATURE 35°C 40°C 45°C 50°C 55°CCORRECTION FACTOR 0.91 0.82 0.71 0.58 0.41

TYPE OF MAXIMUM AMBIENT TEMPERATURE MAXIMUM NORMAL OPERATING TEMPERATUREINSULATION OF SURROUNDINGS OF CABLE INSULATION OR SHEATHOR SHEATH NON FLEXIBLE CABLES LEXIBLE CABLES ALL FIXED OR FLEXIBLE CABLES PARTS OF FLEXIBLE CORDS

AND FLEXIBLE CORDS AND FLEXIBLE CORDS EXCEPT CONTAINED WITHIN A LIGHTINGAS PROVIDED IN FITTING, APPLIANCE OR

COLUMNS MARKED* ACCESSORY, AND NOT SUBJECTTO FLEXING OR OTHERMECHANICAL STRESS

°C °F °C °F °C °F °C °FGENERAL 65 179 65 149 70 58 75 167

PURPOSE PVC HEAT RESISTING 80 179 75 167 85 185 100 212

PVC

Page 114: 6629983 Cleveland Catalogue

CU

RR

ENT

RAT

ING

S116

XLPE INSULATED 600/1000 AND 1900/3300 VOLTS CABLES WITH COPPERCONDUCTORS SUSTAINED CURRENT RATING (AMP)(50HZ) ERA PARAMETERS

Cables shall only be continuously operated at theirtabulated rating if the minimum current at which circuitprotection is designed to operate does not exceed 1.45times (in the case of cables in air or in ducts) or 1.3 times(in the case of cables laid direct in the ground) the valuesgiven above.

Standard depth of laying: 0.5m for 600/1000 voltscables.0.8m for 1900/3300volts cables.

Thermal resistivity of soil: 1.2K.m/W.

Standard ground temperature: 15°C.

Ambient air temperature: 25°C.

NOMINAL 600/1000 VOLTS 3 SINGLE CORE CABLES 1900/3300 VOLTS 3 SINGLE CORE CABLESCONDUCTOR IN TREFOIL ARRANGEMENT IN TREFOIL ARRANGEMENT

AREA DIRECT DUCT AIR AIR DIRECT DUCT AIRMM2 ARMOURED ARMOURED UNARMOURED ARMOURED ARMOURED ARMOURED ARMOURED

50 231 231 223 231 222 219 24070 284 278 284 295 271 264 30095 340 327 352 362 324 310 368

120 386 366 412 420 366 342 428150 431 396 475 483 409 376 487185 485 437 551 555 460 414 556240 558 489 658 654 528 464 656300 623 534 761 745 589 506 747400 691 567 887 851 651 535 851500 765 615 1027 963 720 579 963630 841 664 1186 1084 789 624 1084800 888 692 1347 1178 831 650 1178

1000 942 735 1503 1278 880 689 1278

NOMINAL 600/1000 VOLTS TWIN CORE 600/1000 VOLTS 3 OR 4 CORE 1900/3300 VOLTS 3 CORE CONDUCTOR ARMOURED CABLE ARMOURED CABLE ARMOURED CABLE

AREA DIRECT DUCT AIR DIRECT DUCT AIR DIRECT DUCT AIRMM2

1.5 38 31 31 32 26 26 - - -2.5 49 41 41 42 34 35 - - -4 65 53 55 55 45 47 - - -6 81 67 70 69 56 59 - - -

10 109 89 95 92 75 82 - - -16 141 115 126 119 96 107 114 96 11225 183 148 164 152 124 140 147 124 14935 219 178 202 182 149 172 175 147 17750 259 211 244 217 177 209 207 174 21370 317 260 306 266 218 263 254 214 26895 381 313 378 319 263 324 304 257 328

120 433 357 437 363 300 376 345 293 380150 485 401 499 406 338 430 387 328 432185 547 455 576 458 382 495 436 371 496240 632 527 680 529 442 584 502 428 583300 708 592 775 592 496 666 563 480 667400 799 669 892 667 570 766 633 549 765

Page 115: 6629983 Cleveland Catalogue

117

REQUIREMENTS FOR INSTALLATION AND USE OF CABLES, FLEXIBLE CABLES AND CORDSMinimum bending radius for fixed wiring

INSULATION FINISH OVERALL DIAMETER FACTOR APPLIED TO O.D. OF CABLE TODETERMINE MINIMUM INTERNAL RADIUS OF BEND

PVC NON-ARMOURED NOT EXCEEDING 10mm 3EXCEEDING 10mm BUT NOT EXCEEDING 25mm 4*EXCEEDING 25mm 6*

ARMOURED ANY 6*

CU

RR

ENT

RATIN

GS

*For circular conductors only. For shaped conductor cables, the minimum bending radius factor is 8.

Suggested minimum bending radius for flexible cables and cords

DESCRIPTION OVERALL DIAMETER FACTOR APPLIED TO O.D. OF CABLE TODETERMINE MINIMUM INTERNAL RADIUS OF BEND

FIXED BENDS AND SETS MMFLEXIBLE CORDS AND CABLES UP TO 10 2

10 TO 25 3ABOVE 25 4

SUBJECT TO FLEXINGFLEXIBLE CORDS AND CABLES UP TO 25 6

ABOVE 25 8

WIRE ARMOURED, SCREENEDOR TEXTILE REINFORCED FLEXIBLE UP TO 8

CABLES AND CORDS ABOVE 25 10

Maximum spacing of supports for fixed wiring

*Taken as the measurement of the major axis, in the case of flat cables.++The spacings stated for horizontal runs may be applied also to run at an angle of more than 30° from the vertical.For runs at an angle of 30° or less from the vertical, the vertical spacings are applicable.

Suggested minimum bending radius for power distribution cables

*This also applies to individual cores of ‘SL’ cables.

OVERALL DIAMETER OF CABLES* MAXIMUM SPACING OF CLIPSNON-ARMOURED PVC SHEATHED CABLES ARMOURED CABLES AND CORRUGATED

ALUMINIUM SHEATHED CABLESHORIZONTAL ++ VERTICAL ++ HORIZONTAL ++ VERTICAL ++

1 2 3 4 5MM MM MM MM MM

NOT EXCEEDING 9 250 400 - -EXCEEDING 9 AND NOT EXCEEDING 15 300 400 350 450EXCEEDING 15 AND NOT EXCEEDING 20 350 450 400 550EXCEEDING 20 AND NOT EXCEEDING 40 400 550 450 600

CABLE TYPE FACTOR APPLIED TO O.D. OF CABLE TODETERMINE MINIMUM INTERNAL RADIUS OF BEND

XLPE & PVC INSULATED CABLES TO: 8BS 6724 (INCLUDING FIRETUF POWER OHLS), BS 5467 & BS 6346. MULTICORE SINGLE COREPAPER INSULATED CABLES TO BS 6480: 12 16Up to and including 8700/11000 voltsAbove 8700/11000 volts up to and including 12700/22000 volts 15 18*19000/33000 volts 18 21*XLPE INSULATED CABLES TO BS 6622Unarmoured 15 20Armoured 12 15

Page 116: 6629983 Cleveland Catalogue

CU

RR

ENT

RAT

ING

S118

SINGLE CORE XLPE INSULATED 6350/11000 VOLT ARMOURED CABLES TOBS6622 STRANDED COPPER CONDUCTORS

+ Cables in touching trefoil arrangement.ø Cables in touching trefoil or trefoil ducts.Standard depth of laying: 0.8m.Thermal resistivity of soil (g): 1.2K.m/W.Standard ground temperature: 15°C.Ambient air temperature: 25°C.Maximum conductor temperature: 90°C.

Short circuit ratings have been calculated on the following:-Symmetrical fault, conductor temperature rise of 90°C - 250°C.Earth fault, armour temperature rise of 80°C - 200°C.

NOMINAL INSULATION ARMOUR APPROX. THICKNESS APPROX. APPROX. MINIMUM MAXIMUM MAXIMUM RESISTANCECONDUCTOR THICKNESS WIRE DIAMETER OF OVERALL CABLE BENDING ARMOUR OF CONDUCTOR

AREA DIAMETER OVER OVERSHEATH DIAMETER WEIGHT RADIUS RESISTANCE DC AT 20°C DC AT 20°CARMOUR AT 20°C

MM2 MM MM MM MM MM KG/KM MM OHMS/KM OHMS/KM OHMS/KM50 3.4 1.6 24.9 1.8 28.5 1400 450 0.38 0.387 0.49470 3.4 1.6 26.6 1.9 30.4 1500 500 0.35 0.268 0.34195 3.4 1.6 28.3 1.9 32.1 1900 500 0.33 0.193 0.247

120 3.4 1.6 29.9 2.0 33.9 2100 550 0.32 0.153 0.196150 3.4 2.0 32.1 2.1 36.3 2500 550 0.24 0.124 0.160185 3.4 2.0 33.9 2.1 38.1 3000 600 0.22 0.0991 0.128240 3.4 2.0 36.3 2.2 40.7 3700 650 0.21 0.0754 0.098300 3.4 2.0 38.6 2.2 43.0 4300 650 0.20 0.0601 0.079400 3.4 2.0 41.7 2.4 46.5 5300 700 0.19 0.0470 0.063500 3.4 2.5 45.9 2.5 50.9 6500 800 0.14 0.0355 0.051630 3.4 2.5 49.8 2.6 55.0 8000 850 0.13 0.0283 0.041

NOMINAL INDUCTANCE REACTANCE IMPEDANCE MAXIMUM MAXIMUM SUSTAINED CURRENT RATING MAXIMUM SYMMETRICAL SHORT MAXIMUM EARTH-FAULT CONDUCTOR + AT 50HZ AT 90°C CAPACITANCE CHARGING Ø CIRCUIT CURRENT RATING SHORT CURRENT RATING

AREA + + CURRENT ATNORMALVOLTAGE & LAID IN SINGLE IN AIR FOR FOR FOR FOR FOR FORFREQUENCY DIRECT WAY DUCTS 0.2 SECS 1.0 SECS 3.0 SECS 0.2 SECS 1.0 SECS 3.0 SECS

MM2 MH/KM OHMS/KM OHMS/KM µF/KM AMP/KM AMP AMP AMP KA KA KA KA KA KA50 0.430 0.134 0.512 0.24 0.49 221 220 251 15.2 6.8 3.9 15.2 6.8 3.970 0.400 0.127 0.364 0.28 0.56 270 261 310 21.9 9.8 5.6 17.2 7.7 4.495 0.380 0.120 0.274 0.32 0.64 321 306 376 30.4 13.6 7.8 18.3 8.2 4.7

120 0.370 0.115 0.227 0.36 0.71 363 341 431 38.5 17.2 9.9 19.5 8.7 5.0150 0.360 0.113 0.195 0.39 0.77 410 375 490 47.3 21.1 12.2 25.7 11.5 6.6185 0.350 0.108 0.167 0.43 0.85 455 410 562 59.3 26.5 15.3 27.3 12.2 7.0240 0.330 0.104 0.143 0.48 0.96 520 460 650 78.1 34.9 20.1 29.3 13.1 7.6300 0.320 0.100 0.128 0.53 1.06 580 500 740 98.0 43.7 25.2 31.5 14.1 8.7400 0.310 0.097 0.116 0.59 1.18 650 531 840 >100 55.9 32.3 33.8 15.1 8.7500 0.310 0.096 0.108 0.66 1.31 710 570 931 >100 70.6 40.7 46.5 20.8 12.0630 0.290 0.092 0.101 0.74 1.47 761 620 1040 >100 90.8 52.6 50.3 22.5 13.0

Page 117: 6629983 Cleveland Catalogue

CU

RR

ENT

RATIN

GS

119

THREE CORE XLPE INSULATED 6350/11000 VOLTS ARMOURED CABLES TOBS6622 STRANDED COPPER CONDUCTORS

Standard depth of laying: 0.8m.Thermal resistivity of soil (g): 1.2K.m/W.Standard ground temperature: 15°C.Ambient air temperature: 25°C.Maximum conductor temperature: 90°C.

Short circuit ratings have been calculated on the following:-Symmetrical fault, conductor temperature rise of 90°C - 250°C.Earth fault, armour temperature rise of 80°C - 200°C.

NOMINAL INSULATION THICKNESS THICKNESS ARMOUR THICKNESS APPROX. APPROX. MINIMUM MAXIMUM MAXIMUM RESISTANCECONDUCTOR THICKNESS OF COPPER OF WIRE OF OVERALL CABLE BENDING ARMOUR OF CONDUCTOR

AREA SCREEN EXTRUDED DIAMETER OVERSHEATH DIAMETER WEIGHT RADIUS RESISTANCETAPE BEDDING AT 20°C DC AT 20°C AC AT 20°C

MM MM MM MM MM MM MM KG/KM MM OHMS/KM OHMS/KM OHMS/KM25 3.4 0.075 1.9 2.5 2.4 50.1 4400 650 0.64 0.727 0.92635 3.4 0.075 1.9 2.5 2.5 52.9 4900 650 0.58 0.524 0.66850 3.4 0.075 2.1 2.5 2.6 56.0 5600 700 0.56 0.387 0.49470 3.4 0.075 2.1 2.5 2.7 59.9 6500 750 0.52 0.268 0.34195 3.4 0.075 2.2 2.5 2.8 64.1 7800 800 0.48 0.193 0.247

120 3.4 0.075 2.4 2.5 3.0 68.2 8900 850 0.46 0.153 0.196150 3.4 0.075 2.4 2.5 3.1 71.4 10000 900 0.44 0.124 0.160185 3.4 0.075 2.5 2.5 3.2 75.7 11600 950 0.41 0.0991 0.128240 3.4 0.075 2.5 3.15 3.4 82.6 14800 1000 0.30 0.0754 0.099300 3.4 0.075 2.5 3.15 3.6 88.0 17300 1100 0.28 0.0601 0.080400 3.4 0.075 2.5 3.15 3.8 95.1 20500 1150 0.26 0.0470 0.065

NOMINAL INDUCTANCE REACTANCE IMPEDANCEMAXIMUMMAXIMUM ARMOUR SUSTAINED CURRENT RATING MAXIMUM SYMMETRICAL SHORT MAXIMUM EARTH-FAULT CONDUCTOR AT 50HZ AT 90°C CAPACITANCE CHARGING LOSS AT 50HZ CIRCUIT CURRENT RATING SHORT CURRENT RATING

AREA CURRENT AT AND AT MAX.NORMAL CURRENTVOLTAGE & RATING LAID IN SINGLE IN AIR FOR FOR FOR FOR FOR FORFREQUENCY LAID DIRECT DIRECT WAY DUCTS 0.2 SECS 1.0 SECS 3.0 SECS 0.2 SECS 1.0 SECS 3.0 SECS

MM2 MH/KM OHMS/KM OHMS/KM µF/KM AMP/KM KW/KM AMP AMP AMP KA KA KA KA KA KA25 0.36 0.114 0.93 0.19 0.38 0.22 152 131 163 8.1 3.6 2.0 8.1 3.6 2.035 0.34 0.106 0.68 0.22 0.44 0.34 181 156 197 11.2 5.0 2.9 11.2 5.0 2.950 0.32 0.101 0.51 0.24 0.49 0.50 213 182 236 15.2 6.8 3.9 15.2 6.8 3.970 0.31 0.096 0.35 0.28 0.56 0.82 260 224 291 21.9 9.8 5.6 21.9 9.8 5.695 0.29 0.092 0.26 0.32 0.64 1.3 309 263 353 30.4 13.6 7.8 30.4 13.6 7.8

120 0.28 0.088 0.22 0.36 0.71 1.8 349 306 402 38.5 17.2 9.9 35.3 15.8 9.1150 0.27 0.086 0.18 0.39 0.77 2.3 390 342 454 47.3 21.1 12.2 37.6 16.8 9.7185 0.27 0.084 0.15 0.43 0.85 3.1 436 379 515 59.3 26.5 15.3 40.0 17.9 10.3240 0.26 0.081 0.13 0.48 0.96 5.4 499 438 600 78.1 34.9 20.1 54.8 24.5 14.1300 0.25 0.080 0.11 0.53 1.06 7.0 553 481 676 98.0 43.7 25.2 58.8 26.3 15.2400 0.25 0.078 0.10 0.59 1.18 10.0 619 552 768 >100 55.9 32.3 63.7 28.5 16.5

Page 118: 6629983 Cleveland Catalogue

120

THREE CORE XLPE INSULATED 6350/11000 VOLTS ARMOURED CABLES TOBS6622 STRANDED ALUMINIUM CONDUCTORS

Standard depth of laying: 0.8m.Thermal resistivity of soil (g): 1.2K.m/W.Standard ground temperature: 15°C.Ambient air temperature: 25°C.Maximum conductor temperature: 90°C.

Short circuit ratings have been calculated on the following:-Symmetrical fault, conductor temperature rise of 90°C - 250°C.Earth fault, armour temperature rise of 80°C - 200°C.

NOMINAL INSULATION THICKNESS THICKNESS ARMOUR THICKNESS APPROX. APPROX. MINIMUM MAXIMUM MAXIMUM RESISTANCECONDUCTOR THICKNESS OF COPPER OF WIRE OF OVERALL CABLE BENDING ARMOUR OF CONDUCTOR

AREA SCREEN EXTRUDED DIAMETER OVERSHEATH DIAMETER WEIGHT RADIUS RESISTANCETAPE BEDDING AT 20°C DC AT 20°C AC AT 20°C

MM MM MM MM MM MM MM KG/KM MM OHMS/KM OHMS/KM OHMS/KM25 3.4 0.075 1.9 2.5 2.4 50.1 3800 650 0.64 1.20 1.54035 3.4 0.075 1.9 2.5 2.5 52.9 4100 650 0.58 0.868 1.11050 3.4 0.075 2.1 2.5 2.6 56.0 4500 700 0.56 0.641 0.82270 3.4 0.075 2.1 2.5 2.7 59.9 5300 750 0.52 0.443 0.57095 3.4 0.075 2.2 2.5 2.8 64.1 5800 800 0.48 0.320 0.410

120 3.4 0.075 2.4 2.5 3.0 68.2 6400 850 0.46 0.253 0.325150 3.4 0.075 2.4 2.5 3.1 71.4 7000 900 0.44 0.206 0.265185 3.4 0.075 2.5 2.5 3.2 75.7 7800 950 0.41 0.164 0.212240 3.4 0.075 2.5 3.15 3.4 82.6 9800 1000 0.30 0.125 0.161300 3.4 0.075 2.5 3.15 3.6 88.0 11000 1100 0.28 0.100 0.130400 3.4 0.075 2.5 3.15 3.8 95.1 13400 1150 0.26 0.0778 0.103

NOMINAL INDUCTANCE REACTANCE IMPEDANCEMAXIMUMMAXIMUM ARMOUR SUSTAINED CURRENT RATING MAXIMUM SYMMETRICAL SHORT MAXIMUM EARTH-FAULT CONDUCTOR AT 50HZ AT 90°C CAPACITANCE CHARGING LOSS AT 50HZ CIRCUIT CURRENT RATING SHORT CURRENT RATING

AREA CURRENT AT AND AT MAX.NORMAL CURRENTVOLTAGE & RATING LAID IN SINGLE IN AIR FOR FOR FOR FOR FOR FORFREQUENCY LAID DIRECT DIRECT WAY DUCTS 0.2 SECS 1.0 SECS 3.0 SECS 0.2 SECS 1.0 SECS 3.0 SECS

MM2 MH/KM OHMS/KM OHMS/KM µF/KM AMP/KM KW/KM AMP AMP AMP KA KA KA KA KA KA25 0.36 0.114 1.54 0.19 0.38 0.14 118 101 127 5.2 2.3 1.3 5.2 2.3 1.335 0.34 0.106 1.12 0.22 0.44 0.21 141 121 153 7.2 3.2 1.8 7.2 3.2 1.850 0.32 0.101 0.83 0.24 0.49 0.31 166 141 183 9.7 4.3 2.5 9.7 4.6 2.570 0.31 0.096 0.58 0.28 0.56 0.50 202 174 226 14.1 6.3 3.6 14.1 6.3 3.695 0.29 0.092 0.42 0.32 0.64 0.77 241 205 274 19.5 8.7 5.0 19.5 8.1 5.0

120 0.28 0.088 0.34 0.36 0.71 1.1 272 239 314 24.7 11.0 6.3 24.7 11.0 6.3150 0.27 0.086 0.28 0.39 0.77 1.4 304 267 354 30.3 13.5 7.8 30.3 13.5 7.8185 0.27 0.084 0.23 0.43 0.85 1.9 343 297 404 38.1 17.0 9.8 38.1 17.0 9.8240 0.26 0.081 0.18 0.48 0.96 3.3 395 347 473 50.1 22.4 12.9 50.1 22.4 12.9300 0.25 0.080 0.15 0.53 1.06 4.4 440 383 536 62.8 28.1 16.2 58.8 26.3 15.2400 0.25 0.078 0.13 0.59 1.18 6.5 500 446 618 80.1 35.9 20.7 63.7 28.5 16.5

CU

RR

ENT

RAT

ING

S

Page 119: 6629983 Cleveland Catalogue

121

TECHNICAL SPECIFICATIONS FOR 6381TQ

Single core, EPR insulated, HOFR sheathed. BS6007 - 6381TQ

Ratings do not apply if the cable is protected by a semi-enclosed fuse to BS3036. For further guidance refer to the 16th Edition IEE Wiring Regulations.For ambient air temperatures other than 30°C, the above factors should be applied.Ambient temperature: 30°C. Conductor operating temperature: 85°C.

Current Carrying Capacity (Amperes)

CU

RR

ENT

RATIN

GS

AMBIENT TEMPERATURE 25 30 35 40 45 50 55 60 65 70 75 80RATING FACTOR 1.02 1.0 0.95 0.90 0.85 0.80 0.74 0.67 0.60 0.52 0.43 0.30

CONDUCTOR REFERENCE METHOD 3 REFERENCE METHOD 1 REFERENCE METHOD 11 REFERENCE METHOD 12CROSS SECTIONAL (ENCLOSED IN CONDUIT ETC. (CLIPPED DIRECT) (ON A PERFORATED CABLE TRAY) (FREE AIR)

AREA IN OR ON A WALL) HORIZONTAL OR VERTICAL2 CABLES 3 OR 4 CABLES 2 CABLES 3 OR 4 CABLES 2 CABLES 3 OR 4 CABLES SINGLE PHASE 3 CABLES

SINGLE PHASE 3 PHASE A.C. SINGLE PHASE 3 PHASE A.C. SINGLE PHASE 3 PHASE A.C. A.C. OR D.C. OR TREFOIL A.C. OR D.C. A.C. OR D.C. FLAT & A.C. OR D.C. FLAT & 3 OR 4 CABLES 3 PHASE A.C.

FLAT & TOUCHING OR FLAT & TOUCHING 3 PHASE A.C.TOUCHING TREFOIL TOUCHING OR TREFOIL FLAT SPACED

HORIZONTALOR VERTICAL

1 2 3 4 5 6 7 8 9MM2 AMP AMP AMP AMP AMP AMP AMP AMP

4 40 36 45 42 - - - -6 52 46 59 54 - - - -

10 72 63 81 75 - - - -16 96 85 108 100 - - - -25 127 112 143 133 153 140 154 13435 157 138 177 164 189 174 192 16750 190 167 215 199 229 211 235 20470 242 213 274 254 293 269 303 26295 293 258 332 308 356 327 370 320

120 339 298 384 357 412 379 431 373150 372 334 442 411 475 437 499 432185 428 379 519 469 542 499 573 495240 510 443 607 553 639 589 679 587300 593 506 695 636 735 679 786 680400 719 602 827 755 860 798 929 799500 835 689 946 865 989 918 1081 919600 975 791 1088 996 1143 162 1263 1060

Page 120: 6629983 Cleveland Catalogue

CU

RR

ENT

RAT

ING

S122

FLEXIBLE CABLES AND CORDS TECHNICAL SPECIFICATIONS FOR 638*TQCURRENT CARRYING CAPACITY (Amperes)

Ratings do not apply if the cable is protected by a semi-enclosed fuse to BS3036. For further guidance refer to the 16th Edition IEE Wiring Regulations.For ambient air temperatures other than 30°C, the above factors should be applied.

Ambient temperature: 30°C.Conductor operating temperature: 85°C.Note: The current ratings tabulated are for cables in free air but may also be used for cables resting on a surface.

Current Carrying Capacity (Amperes)

AMBIENT TEMPERATURE 25 30 35 40 45 50 55 60 65 70 75 80

RATING FACTOR 1.02 1.02 0.95 0.90 0.85 0.80 0.74 0.67 0.60 0.52 0.43 0.30

CONDUCTOR CROSS D.C. OR SINGLE PHASE A.C. 3 PHASE A.C. SINGLE PHASE A.C. OR D.C.SECTIONAL AREA (2 CORE CABLE, WITH OR WITHOUT (3 CORE, 4 CORE OR 2 SINGLE CORE CABLES TOUCHING

PROTECTIVE CONDUCTOR) 5 CORE CABLE)MM2 AMP AMP AMP

4 41 36 -6 53 47 -

10 73 64 -16 99 86 -25 131 114 -35 - 140 19250 - 170 24070 - 216 29795 - 262 354

120 - 303 414150 - 348 476185 - 397 540240 - 467 645300 - 537 741400 - - 885500 - - 1017630 - - 1190

Page 121: 6629983 Cleveland Catalogue

CU

RR

ENT

RATIN

GS

123

TECHNICAL SPECIFICATIONS FOR FLEXIBLE CORDSApplicable to: 318*Y, 218*Y, 2491YX, 309*Y, 318*P/TQ, 398*P, 380*Y, 380*P, 380*TQ, 219*Y.

AMBIENT TEMPERATURE 35 40 45 50 55RATING FACTOR 0.91 0.82 0.71 0.58 0.41

85°C rubber cords having a HOFR sheath or heat-resisting PVC sheath and for 90°C heat resisting and PVC cords

Correction Factor for Ambient Temperature 60°C rubber and PVC cords

AMBIENT TEMPERATURE 35-50 55 60 65 70

RATING FACTOR 1.0 0.96 0.83 0.67 0.47

180°C rubber cords

AMBIENT TEMPERATURE 35-150 155 160 165 170 175

RATING FACTOR 1.0 0.92 0.82 0.71 0.57 0.40

BS6141 BS6500 Current Carrying Capacity (Amperes)

CONDUCTOR CROSS SECTIONAL AREA CURRENT CARRYING CAPACITY (Amperes)SINGLE PHASE A.C. 3 PHASE A.C.

1 2 3MM2 AMP AMP0.5 3 3

0.75 6 61 10 10

1.25 13 -1.5 16 162.5 25 204 32 25

Voltage Drop (per ampere per metre)

Note: The tabulated values above are for 60°C rubber insulated and PVC insulated flexible cords and for other typesof flexible cords they are to be multiplied by the following factors:

For 85°C rubber or PVC insulated: 1.09

180°C rubber insulated: 1.31

CONDUCTOR CROSS SECTIONAL AREA D.C. SINGLE PHASE A.C. 3 PHASE A.C.1 2 3

MM2 MV MV0.5 93 80

0.75 62 541 46 40

1.25 37 -1.5 32 272.5 19 164 12 10

Page 122: 6629983 Cleveland Catalogue

CU

RR

ENT

RAT

ING

S124

TRI-RATED - SWITCHGEAR WIRING CABLE

NO. OF CORES CURRENT RATING MIXIMUM DC& NOMINAL SINGLE CABLE 2 CABLES BUNCHED 3 CABLES BUNCHED CONDUCTOR

CROSS SECTIONAL RESISTANCE@AREA OF CONDUCTOR 20˚C

NO X MM2 AMP AMP AMP ΩKM1 x 0.50 11.50 10.00 7.00 39.001 x 0.75 16.00 14.00 10.50 26.001 x 1.00 19.00 16.50 12.50 19.501 x 1.50 24.00 20.00 16.00 13.301 x 2.50 32.00 28.00 22.00 7.981 x 4.00 43.00 37.00 29.00 4.951 x 6.00 56.00 49.00 39.00 3.30

1 x 10.00 79.00 69.00 57.00 1.911 x 16.00 105.00 91.00 76.00 1.121 x 25.00 141.00 123.00 104.00 0.7801 x 35.00 178.00 154.00 131.00 0.5541 x 50.00 217.00 188.00 162.00 0.3861 x 70.00 276.00 239.00 208.00 0.2721 x 95.00 337.00 292.00 257.00 0.206

1 x 120.00 400.00 347.00 305.00 0.1611 x 150.00 457.00 396.00 350.00 0.1291 x 185.00 526.00 454.00 405.00 0.1061 x 240.00 634.00 546.00 489.00 0.08011 x 300.00 730.00 610.00 560.00 0.0641

Page 123: 6629983 Cleveland Catalogue

N O T E S

Page 124: 6629983 Cleveland Catalogue

N O T E S