© Copyright 2008 HVAC Design Solutions 1
Quick and Easy “Ventilation Rate Procedure”
Compliance Calculations
Quick and Easy “Ventilation Rate Procedure”
Compliance Calculations
HVAC DESIGN SOLUTIONS ENGINEERING SOFTWARE
62.1-2007 Comply from HVAC Design Solutions is a package of software programs for establishing compliance with the ASHRAE Standard 62.1-2007 “Ventilation Rate Procedure”.
Includes Proprietary “Auto-Optimize”© and “VAV Scheduler”© which provide significant improvements over current “ASHRAE 62.1 User’s Manual Spreadsheet” and over the ventilation calculations in current “Equipment Manufacturer’s Load Calc” software.
© Copyright 2008 HVAC Design Solutions 2
Portions of the included information, descriptions, procedures, and forms are excerpts from ANSI/ASHRAE Standard 62.1-2007 (© 2007 American Society of Heating, Refrigeration and Air-Conditioning Engineers, Inc. (www.ashrae.org) Used by permission.)
© Copyright 2007 HVAC Design Solutions 3
ANSI/ASHRAE Standard 62.1-2007 has made significant advancements in calculations and directives to help improve ventilation air delivery to the occupants.
These changes and additional calculations, especially for multiple zone systems, have made it more difficult for engineers to determine the required outdoor air quantities.
© Copyright 2008 HVAC Design Solutions 4
(Vps)
(Vps - Vot)
(1-Ep)(Vdz)
(Vdz)
Zone
(1-Ez)(Vdz)
(Ez)(Vdz)
Figure 2: Ventilation System Schematic
Secondary Recirculation (Where Applicable)
VAV Box (Where
Applicable)
(Vbz) = (RpPz + RaAz)
(Vpz) = (Ep)(Vdz)
Fully Mixed Fraction of Secondary Recirculation (Where Applicable)
(Er)(1-Ep)(Vdz)
Exhaust Air
Relief AirOutdoor Air
IntakeFan or AHU
Breathing Zone
Secondary Recirculation
Directly from Zone (Where Applicable)
(1-Er)(1-Ep)(Vdz)
© Copyright 2008 HVAC Design Solutions 5
Ventilation calculations can become quite complex.
A few necessary formulas:
© Copyright 2007 HVAC Design Solutions 6
E v z = 1 + X s - Z d
Evz
= (
Fa +
Xs*F
b –
Zd
*Fc
)/F
a
E v = m i n i m u m ( E v z )
V b z = R p P z + R a A z
T = 3 v / V b z
V o t = V o z
V o z = V b z / E z
V o t = a l l z o n e s V o z
Z p = V o z / V p z
V o u = D a l l z o n e s R p P z +
a l l z o n e s R a A z
D = P s / a l l z o n e s P z
V o t = V o u / E v
Keeping track of all the required formulas and calculations can be difficult.
Input Occupancy Category Number Input Zone Square Footage Input Number of Occupants, or use
defaults Input Air Distribution Config. Number Input Design and Minimum Air Quantities Perform Quick Optimization Procedure Print out Compliance Documents Quick and Easy
© Copyright 2007 HVAC Design Solutions 7
Our software programs Minimize your Time and Efforts, and give you the Required OA Quantities, Min. VAV Settings, and Compliance Documents
The following example of a typical multiple zone system calculation will show the Quick and Easy input for 62.1-2007 Comply, and the Ventilation Rate Procedure compliance calculations.
Optimization procedures will show the actual reduction from an original 5,423 CFM outdoor air requirement to a final “Optimized” quantity of 2,824 CFM. This can result in a significant reduction in Owner energy and operating costs, while still complying with ASHRAE 62.1-2007.
© Copyright 2008 HVAC Design Solutions 8
© Copyright 2007 HVAC Design Solutions 9
HELP
CLIENT CONTACT NAME:
BASIC PROJECT INFORMATION
"Your Company Name"
Bob Findley
Office
30
Berkley Plaza
125-07
5/3/2007
PROJECT NAME :PROJECT NUMBER :DATE :TYPE OF BUILDING :DESIGN WINTER OA TEMP. (F) :PROJECT MANAGER :PROJECT ENGINEER :CLIENT :
© 2007 hvacdesignsolutions.com
Curt Billings
Aztec ArchitectsPhil Longley, AIA
Your company name will appear on all output sheets and compliance documents
This project information will automatically transfer to all relative project calculations.
© Copyright 2007 HVAC Design Solutions 10
HELP
ASHRAE STD. 62.1-2007 COMPLIANCE
MINIMUM PRIMARY AIRFLOW TO ZONE (MIN. VAV PRIMARY OA & RA) (CFM)
(Vpzm)
DESIGN PRIMARY AIRFLOW TO ZONE (INCL. PRIMARY OA & RA) (CFM) (Vpz)
AIR DISTRIB. CONFIG. NUMBER (SEE TABLE 6-2)
CALCULATIONS TAKE-OFF FORM
IF SPACE IS INTERMITTENT USAGE (EG. CONFERENCE ROOM) (SPACE
HEIGHT - FT.)
PEAK OCCUPANCY - IF KNOWN (EG. MEETING IN AN OFFICE)
(NUMBER OF PEOPLE)
NORMAL OCCUPANCY - IF KNOWN (EG. ONE PER OFFICE) (NUMBER OF PEOPLE)
ZONE FLOOR AREA (SQ. FT.) (Az)
OCCUPANCY CATEGORY NUMBER (SEE TABLE 6-1)
5/3/2007
"Your Company Name"
AIR HANDLING UNIT TAG NUMBER (AHU-1, ETC.)
PROJECT NUMBER:
VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY
ZONE NUMBER (EG: 1-1, 1-2)
PROJECT NAME: Berkley Plaza
125-07
DATE:
DESIGN OA TEMP.: 30
PRINTRESET/CLEAR
You can print out blank forms for easy project take-off. Makes calculation input Quick and Easy.
© Copyright 2007 HVAC Design Solutions 11
HELP
"Your Company Name"ASHRAE STD. 62.1-2007 COMPLIANCE
PROJECT NAME: Berkley Plaza
30
8
AIR HANDLING UNIT TAG NUMBER (AHU-1, ETC.)
ZONE NUMBER (EG: 1-1, 1-2)
125-07
DATE: 5/3/2007
DESIGN OA TEMP.:
VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY
MULTIPLE ZONE SYSTEMS (WITHOUT ZONE LEVEL RECIRCULATION)
PROJECT NUMBER:
6 7RECORD NUMBER > > > > 1 2 3 4 5
OCCUPANCY CATEGORY NUMBER (SEE TABLE 6-1)
0 0 0 0OCCUPANCY CATEGORY 0 0 0 0
PEOPLE OUTDOOR AIR RATE (CFM/PERSON) (Rp) 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0.00 0.00 0.00AREA OUTDOOR AIR RATE
(CFM/SQ. FT.) (Ra)0.00 0.00 0.00 0.00 0.00
FOURTH TRIAL - CHANGE 4 OF OPTIMIZATION
PRINTRESET/CLEAR
Input Form for OA ventilation compliance calculations - Multiple Zone systems
HELP
"Your Company Name"ASHRAE STD. 62.1-2007 COMPLIANCE
PROJECT NAME: Berkley P laza
30
8
1-4 1-5
AIR HANDLING UNIT TAG NUMBER (AHU-1, ETC.)
ZONE NUMBER (EG: 1-1, 1-2) 1-1 1-2 1-3
AHU-1
125-07
DATE: 5/3/2007
DESIGN OA TEMP.:
VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY
MULTIPLE ZONE SYSTEMS (WITHOUT ZONE LEVEL RECIRCULATION)
PROJECT NUMBER:
6 7RECORD NUMBER > > > > 1 2 3 4 5
OCCUPANCY CATEGORY NUMBER (SEE TABLE 6-1)
0 0 0 0OCCUPANCY CATEGORY 0 0 0 0
PEOPLE OUTDOOR AIR RATE (CFM/PERSON) (Rp) 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0.00 0.00 0.00AREA OUTDOOR AIR RATE
(CFM/SQ. FT.) (Ra)0.00 0.00 0.00 0.00 0.00
PRINTRESET/CLEAR
© Copyright 2007 HVAC Design Solutions 12
Quick input of AHU and associated zone numbers.
© Copyright 2007 HVAC Design Solutions 13
HELP
1 Cell 5 2.5 0.12 0.6 25 10 4.9 22 Day room 5 2.5 0.06 0.3 30 7 3.5 13 Guard stations 5 2.5 0.06 0.3 15 9 4.5 14 Booking/waiting 7.5 3.8 0.06 0.3 50 9 4.4 2
5 Daycare (through age 4) 10 5 0.18 0.9 25 17 8.6 26 Classrooms (ages 5-8) 10 5 0.12 0.6 25 15 7.4 17 Classrooms (age 9 plus) 10 5 0.12 0.6 35 13 6.7 18 Lecture classroom 7.5 3.8 0.06 0.3 65 8 4.3 19 Lecture hall (f ixed seats) 7.5 3.8 0.06 0.3 150 8 4.0 110 Art classroom 10 5 0.18 0.9 20 19 9.5 211 University/Sci. laboratories 10 5 0.18 0.9 25 17 8.6 ---12 Wood/metal shop 10 5 0.18 0.9 20 19 9.5 213 Computer lab 10 5 0.12 0.6 25 15 7.4 114 Media center 10 5 0.12 0.6 A 25 15 7.4 115 Music/theater/dance 10 5 0.06 0.3 35 12 5.9 116 Multi-use assembly 7.5 3.8 0.06 0.3 100 8 4.1 1
17 Restaurant dining rooms 7.5 3.8 0.18 0.9 70 10 5.1 218 Cafeteria/fast food dining 7.5 3.8 0.18 0.9 100 9 4.7 219 Bars, cocktail lounges 7.5 3.8 0.18 0.9 100 9 4.7 2
20 Conference/meeting 5 2.5 0.06 0.3 50 6 3.1 1
Correctional Facilities
Educational Facilities
Food and Beverage Service
General
Air Class
Occupant Density
(see Note 4)
Combined Outdoor Air Rate (see Note 5)
#/1000 ft2 or
#/100m2cfm/person L/s•personcfm/person L/s•person cfm/sq. ft. L/s•m2
(This table is not valid in isolation; it must be used in conjunction with the accompanying notes.)
Notes
Default Values
ANSI/ASHRAE STANDARD 62.1-2007 COMPLIANCE
TABLE 6-1 MINIMUM VENTILATION RATES IN BREATHING ZONE
Occ. Category Number
Occupancy Category
People Outdoor Air Rate Rp
Area Outdoor Air Rate Ra
Category Numbers assigned to ASHRAE “Table 1” categories. Appropriate rates automatically transfer to program calculations.
© Copyright 2007 HVAC Design Solutions 14
HELP
"Your Company Name"ASHRAE STD. 62.1-2007 COMPLIANCE
PROJECT NAME: Berkley Plaza
30
8
1-4 1-5
AIR HANDLING UNIT TAG NUMBER (AHU-1, ETC.)
ZONE NUMBER (EG: 1-1, 1-2) 1-1 1-2 1-3
AHU-1
125-07
DATE: 5/3/2007
DESIGN OA TEMP.:
VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY
MULTIPLE ZONE SYSTEMS (WITHOUT ZONE LEVEL RECIRCULATION)
PROJECT NUMBER:
6 7RECORD NUMBER > > > > 1 2 3 4 5
1-6 1-7 1-8
OCCUPANCY CATEGORY NUMBER (SEE TABLE 6-1) 28 27 29 20 29 27 8
Telephone/data entry
Office space
Lecture classroom
0OCCUPANCY CATEGORYReception areas
Office space
Telephone/data entry
Conference/meetin
g
PEOPLE OUTDOOR AIR RATE (CFM/PERSON) (Rp) 5.0 5.0 5.0 5.0 5.0 5.0 7.5 0.0
0.06 0.06 0.00AREA OUTDOOR AIR RATE
(CFM/SQ. FT.) (Ra)0.06 0.06 0.06 0.06 0.06
PRINTRESET/CLEAR
Quick input of Occupancy Category numbers - brings the People and Area OA rates into the calculations
OCCUPANCY CATEGORYReception areas
Office space
Telephone/data
entry
Conference/meeti
ng
Telephone/data
entry
Office space
Lecture classroo
m
Lobbies/prefuncti
on
PEOPLE OUTDOOR AIR RATE (CFM/PERSON) (Rp)
5.0 5.0 5.0 5.0 5.0 5.0 7.5 7.5
AREA OUTDOOR AIR RATE (CFM/SQ. FT.) (Ra)
0.06 0.06 0.06 0.06 0.06 0.06 0.06 0.06
ZONE FLOOR AREA (SQ. FT.) (Az)
400 600 3000 500 400 700
NORMAL OCCUPANCY - IF KNOWN (EG. ONE PER OFFICE) (NUMBER OF PEOPLE)
PEAK OCCUPANCY - IF KNOWN (EG. MEETING IN AN OFFICE)
(NUMBER OF PEOPLE) IF SPACE IS INTERMITTENT USAGE
(EG. CONFERENCE ROOM) (SPACE HEIGHT - FT.)
CORRECTED OCCUPANCY FOR INTERMITTENT USAGE SPACES
(NUMBER OF PEOPLE)0 0 0 0 0 0 0 0
CALCULATED OCCUPANCY (NUMBER OF PEOPLE) (Pz)
0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
DEFAULT OCCUPANCY (NUMBER OF PEOPLE) (Pz)
12.0 3.0 180.0 25.0 24.0 3.5 0.0 0.0
© Copyright 2007 HVAC Design Solutions 15
Quick input of each zone’s Floor Area.
DEFAULT OCCUPANCY (NUMBER OF PEOPLE) (Pz) 12.0 3.0 180.0 25.0 24.0 3.5 61.8 12.0
0.020.0 24.0 5.0 0.0CALCULATED OCCUPANCY (NUMBER OF PEOPLE) (Pz) 12.0 3.0 180.0
CORRECTED OCCUPANCY FOR INTERMITTENT USAGE SPACES
(NUMBER OF PEOPLE)12 3 180 20 24 0 0 0
8 8IF SPACE IS INTERMITTENT USAGE
(EG. CONFERENCE ROOM) (SPACE HEIGHT - FT.)
8 8 8
PEAK OCCUPANCY - IF KNOWN (EG. MEETING IN AN OFFICE)
(NUMBER OF PEOPLE) 12 6 180 20 24
0 12 5NORMAL OCCUPANCY - IF KNOWN
(EG. ONE PER OFFICE) (NUMBER OF PEOPLE)
4 2 140
ZONE FLOOR AREA (SQ. FT.) (Az) 400 600 3000 500 400 700 950 400
0.060.06 0.06 0.06 0.06AREA OUTDOOR AIR RATE
(CFM/SQ. FT.) (Ra) 0.06 0.06 0.06
PEOPLE OUTDOOR AIR RATE (CFM/PERSON) (Rp) 5.0 5.0 5.0 5.0 5.0 5.0 7.5 7.5
Lobbies/prefuncti
on
Conference/meeti
ng
Telephone/data
entry
Office space
Lecture classroo
mOCCUPANCY CATEGORY
Reception areas
Office space
Telephone/data
entry
© Copyright 2007 HVAC Design Solutions 16
Easy input of normal and peak occupancy, if known. If left blank, the ASHRAE default occupancy numbers will be used.
© Copyright 2007 HVAC Design Solutions 17
HELP
1 Ceiling supply of cool air 1.0
2 Ceiling supply of warm air and floor return 1.0
8 Floor supply of warm air and floor return 1.0 1.0
9 Floor supply of warm air and ceiling return 0.7 0.7
11 Makeup supply drawn in near to the exhaust and/or return location 0.5
GENERAL NOTES FOR TABLE 6-21. “Cool air” is air cooler than space temperature.
ANSI/ASHRAE STANDARD 62.1-2007 COMPLIANCE
3 Ceiling supply of warm air 15°F (8°C) or more above space temperature and ceiling return.
0.8
TABLE 6-2 Zone Air Distribution Effectiveness
Configuration Number
Air Distribution Configuration Effectiveness
Ez
4Ceiling supply of warm air less than 15°F (8°C) above space temperature and ceiling return, provided that the 150 fpm (0.8 m/s) supply air jet reaches to within 4.5 ft (1.4 m) of floor level.
1.0
5Ceiling supply of warm air less than 15°F (8°C) above space temperature and ceiling return, with the supply air jet reaching to within 4.5 ft (1.4 m) of f loor level of less than 150 fpm (0.8 m/s) velocity.
0.8
6Floor supply of cool air and ceiling return provided that the 150 fpm (0.8 m/s) supply jet reaches 4.5 ft (1.4 m) or more above the f loor. Note: Most underfloor air distribution systems comply with this proviso.
1.0
7Floor supply of cool air and ceiling return, provided low velocity displacement ventilation achieves unidirectional flow and thermal stratification.
1.2
10 Makeup supply drawn in on the opposite side of the room from the exhaust and/or return.
0.8
Configuration Numbers assigned to ASHRAE “Table 2” Air Distribution Configuration descriptions.
CORRECTED OCCUPANCY FOR INTERMITTENT USAGE SPACES
(NUMBER OF PEOPLE)12 3 180 20 24 0 40 16
CALCULATED OCCUPANCY (NUMBER OF PEOPLE) (Pz)
12.0 3.0 180.0 20.0 24.0 5.0 40.0 16.0
DEFAULT OCCUPANCY (NUMBER OF PEOPLE) (Pz)
12.0 3.0 180.0 25.0 24.0 3.5 61.8 12.0
DESIGN OCCUPANCY (CALCULATED, IF KNOWN OR DEFAULT)
(NUMBER OF PEOPLE) (Pz)12 3 180 20 24 5 40 16
PEOPLE OUTDOOR AIR (CFM) (Rp x Pz)
60 15 900 100 120 25 300 120
AREA OUTDOOR AIR (CFM) (Ra x Az)
24 36 180 30 24 42 57 24
BREATHING ZONE OUTDOOR AIRFLOW (CFM) (Vbz)
84 51 1080 130 144 67 357 144
AIR DISTRIB. CONFIG. NUMBER (SEE TABLE 6-2)
1 1 3 1 3 1
ZONE AIR DISTRIBUTION EFFECTIVENESS (Ez)
1.0 1.0 0.8 1.0 0.8 1.0 0.0 0.0
ZONE OUTDOOR AIRFLOW (CFM) (Voz)
84 51 1350 130 180 67
© Copyright 2007 HVAC Design Solutions 18
Quick input of Air Distribution Config. Number - brings Zone Air Distribution Effectiveness (Ez) into the calculations.
1400
357
OA QUANTITY IS OPTIMIZED WHEN REQ'D. OA INTAKE CHANGE IS LESS THAN:
REQUIRED OA INTAKE FLOW (CFM) (Vot)
291
0.88
FOR OPTIMIZATION, ADD TO KEY "MINIMUM VAV
AIRFLOW TO ZONE" (CFM):
OCCUPANT DIVERSITY (SYSTEM POPULATION / SUM OF
DESIGN POPULATION) (D)114.5
UNCORRECTED OUTDOOR AIR INTAKE (CFM) (Vou)
SYSTEM POPULATION (SUM OF NORMAL OCCUPANCIES) (Ps)
CALC. ORIGINAL
0.51 0.48 0.52 0.21 0.30
CHANGE 1 CHANGE 2
5423 5423
114.5
CHANGE 3
7
300
1000
600
600 1200 400
0.20 0.75 0.43 0.60 0.22
650 850600
300 300
DESIGN PRIMARY AIRFLOW TO ZONE (INCL. PRIMARY OA & RA) (CFM) (Vpz)
ZONE PRIMARY OUTDOOR AIR FRACTION (Zp)
500 800 5000
MINIMUM VAV AIRFLOW TO ZONE (INCL. PRIMARY OA & RA) (CFM) (Vdz) 250 250 1800
2255
0.34
150 300300 700
130 180 144 310 31 9167ZONE OUTDOOR AIRFLOW
(CFM) (Voz)84 51 1350
62 12 16 2NORMAL ZONE OCCUPANCY
(EITHER KNOWN OR DEFAULT) (NUMBER OF PEOPLE)
4 2 140 25 12 5
ZONE POPULATION (LARGEST TYPICAL OCCUPANCY)
(SUM (Pz))330 630 630
MAXIMUM ZONE PRIMARY OUTDOOR AIR FRACTION (Zp)
0.750 AUTO-OPTIMIZE
© Copyright 2008 HVAC Design Solutions 19
Easy input of each zone’s Design Airflow and Minimum Airflow. Alert colors automatically indicate which zones are least efficient at delivering OA to occupants.Yellow highlight in row for
“Zone Primary Outdoor Air Fraction” (Zp) indicates the ventilation-critical zone. Preliminary “Required
OA Intake Flow” is calculated during zone CFM input.
1400
357
OA QUANTITY IS OPTIMIZED WHEN REQ'D. OA INTAKE CHANGE IS LESS THAN:
REQUIRED OA INTAKE FLOW (CFM) (Vot)
291
0.88
FOR OPTIMIZATION, ADD TO KEY "MINIMUM VAV
AIRFLOW TO ZONE" (CFM):
OCCUPANT DIVERSITY (SYSTEM POPULATION / SUM OF
DESIGN POPULATION) (D)114.5
UNCORRECTED OUTDOOR AIR INTAKE (CFM) (Vou)
SYSTEM POPULATION (SUM OF NORMAL OCCUPANCIES) (Ps)
CALC. ORIGINAL
0.51 0.48 0.52 0.21 0.30
CHANGE 1 CHANGE 2
5423 5423
114.5
CHANGE 3
7
300
1000
600
600 1200 400
0.20 0.75 0.43 0.60 0.22
650 850600
300 300
DESIGN PRIMARY AIRFLOW TO ZONE (INCL. PRIMARY OA & RA) (CFM) (Vpz)
ZONE PRIMARY OUTDOOR AIR FRACTION (Zp)
500 800 5000
MINIMUM VAV AIRFLOW TO ZONE (INCL. PRIMARY OA & RA) (CFM) (Vdz) 250 250 1800
2255
0.34
150 300300 700
130 180 144 310 31 9167ZONE OUTDOOR AIRFLOW
(CFM) (Voz)84 51 1350
62 12 16 2NORMAL ZONE OCCUPANCY
(EITHER KNOWN OR DEFAULT) (NUMBER OF PEOPLE)
4 2 140 25 12 5
ZONE POPULATION (LARGEST TYPICAL OCCUPANCY)
(SUM (Pz))330 630 630
MAXIMUM ZONE PRIMARY OUTDOOR AIR FRACTION (Zp)
0.750 AUTO-OPTIMIZE
© Copyright 2008 HVAC Design Solutions 20
“Critical Zone” before Optimization
After completing the zone Design and Minimum air quantity input, the next step is to “Optimize” the system and required OA quantity.
To Optimize, simply click the “Auto-Optimize” button.
“Required OA” before Optimization
1400
357
OA QUANTITY IS OPTIMIZED WHEN REQ'D. OA INTAKE CHANGE IS LESS THAN:
REQUIRED OA INTAKE FLOW (CFM) (Vot)
291
0.88
FOR OPTIMIZATION, ADD TO KEY "MINIMUM VAV
AIRFLOW TO ZONE" (CFM):
OCCUPANT DIVERSITY (SYSTEM POPULATION / SUM OF
DESIGN POPULATION) (D)17.8
UNCORRECTED OUTDOOR AIR INTAKE (CFM) (Vou)
SYSTEM POPULATION (SUM OF NORMAL OCCUPANCIES) (Ps)
CALC. ORIGINAL
0.34 0.32 0.34 0.21 0.30
CHANGE 1 CHANGE 2
2824 5423
114.5
CHANGE 3
7
450
1000
900
600 1200 400
0.20 0.36 0.36 0.37 0.22
650 850600
360 490
DESIGN PRIMARY AIRFLOW TO ZONE (INCL. PRIMARY OA & RA) (CFM) (Vpz)
ZONE PRIMARY OUTDOOR AIR FRACTION (Zp)
500 800 5000
MINIMUM VAV AIRFLOW TO ZONE (INCL. PRIMARY OA & RA) (CFM) (Vdz) 250 250 3800
2255
0.34
150 300300 1050
130 180 144 310 31 9167ZONE OUTDOOR AIRFLOW
(CFM) (Voz)84 51 1350
62 12 16 2NORMAL ZONE OCCUPANCY
(EITHER KNOWN OR DEFAULT) (NUMBER OF PEOPLE)
4 2 140 25 12 5
ZONE POPULATION (LARGEST TYPICAL OCCUPANCY)
(SUM (Pz))330 98 630
MAXIMUM ZONE PRIMARY OUTDOOR AIR FRACTION (Zp)
0.367 AUTO-OPTIMIZE
© Copyright 2008 HVAC Design Solutions 21
Program automatically adjusts “critical zone” VAV Minimums, which reduce the “Max. Zone OA Fraction” from original 0.75 to 0.37.
This results in a reduction of Required OA from original 5423 CFM to final 2824 CFM.
HELP
OA DESIGN DB = -4 670COOLING SUPPLY DB = 55 30DESIGN ROOM TEMP. = 70 HEATING WATER SUPPLY TEMP = 200
VAV COOLING MINIMUM VENT. OR CALC. ZONE HEAT LOSS HEAT LOSS COIL LOAD AT GPM AT HW REVISED REVISED REVISED
NUMBER AIR QUANTITY HEATING AIR QUANT. HEAT LOSS DELTA-T SAT HEAT LOSS SAT DELTA-T MIN. VENT. SAT COIL LOAD
(CFM) (CFM) (MBH) (DEG. F) (DEG. F) (MBH) (GPM) (CFM) (DEG. F) (MBH)
1-1 500 250 0.0 80.0 6.7 0.4 N/A N/A N/A1-2 800 250 0.0 80.0 6.7 0.4 N/A N/A N/A1-3 5000 3800 0.0 80.0 101.2 6.7 N/A N/A N/A1-4 600 360 0.0 80.0 9.6 0.6 N/A N/A N/A1-5 650 490 0.0 80.0 13.1 0.9 N/A N/A N/A1-6 850 300 0.0 80.0 8.0 0.5 N/A N/A N/A1-7 1400 1050 0.0 80.0 28.0 1.9 N/A N/A N/A1-8 600 450 0.0 80.0 12.0 0.8 N/A N/A N/A1-9 1200 900 0.0 80.0 24.0 1.6 N/A N/A N/A1-10 400 150 0.0 80.0 4.0 0.3 N/A N/A N/A1-11 1000 300 0.0 80.0 8.0 0.5 N/A N/A N/A1-12 600 250 0.0 80.0 6.7 0.4 N/A N/A N/A
0 0 0 0.0 80.0 0.0 0.0 N/A N/A N/A0 0 0 0.0 80.0 0.0 0.0 N/A N/A N/A0 0 0 0.0 80.0 0.0 0.0 N/A N/A N/A0 0 0 0.0 80.0 0.0 0.0 N/A N/A N/A0 0 0 0.0 80.0 0.0 0.0 N/A N/A N/A0 0 0 0.0 80.0 0.0 0.0 N/A N/A N/A0 0 0 0.0 80.0 0.0 0.0 N/A N/A N/A0 0 0 0.0 80.0 0.0 0.0 N/A N/A N/A
05/21/08DATE:
"YOUR COMPANY NAME"
(MZ TYPE A) VAV(1) - REHEAT COIL CALCULATIONS - 15 DEG. MAXIMUM ΔT
PROJECT NAME:
PROJECT NUMBER:
TEST PROJECT #2
1456-08
PROJECT ELEVATION =
HEATING WATER DELTA-T =
PRINTRESET/CLEAR
© Copyright 2008 HVAC Design Solutions 22
VAV Numbers and “Optimized” Air Quantities are automatically transferred to VAV-Reheat calculation program. (In VAV Version of software package)
Program calculates required Reheat Coil capacities, based on minimum air quantities and zone heating loads.
HELP
OA DESIGN DB = -4 670COOLING SUPPLY DB = 55 30DESIGN ROOM TEMP. = 70 HEATING WATER SUPPLY TEMP = 200
VAV COOLING MINIMUM VENT. OR CALC. ZONE HEAT LOSS HEAT LOSS COIL LOAD AT GPM AT HW REVISED REVISED REVISED
NUMBER AIR QUANTITY HEATING AIR QUANT. HEAT LOSS DELTA-T SAT HEAT LOSS SAT DELTA-T MIN. VENT. SAT COIL LOAD
(CFM) (CFM) (MBH) (DEG. F) (DEG. F) (MBH) (GPM) (CFM) (DEG. F) (MBH)
1-1 500 250 2.5 9.4 80.0 6.7 0.4 N/A N/A N/A1-2 800 250 3.9 14.6 84.6 7.9 0.5 N/A N/A N/A1-3 5000 3800 51.6 12.7 82.7 112.3 7.5 N/A N/A N/A1-4 600 360 0 0.0 80.0 9.6 0.6 N/A N/A N/A1-5 650 490 0 0.0 80.0 13.1 0.9 N/A N/A N/A1-6 850 300 4.1 12.8 82.8 8.9 0.6 N/A N/A N/A1-7 1400 1050 14.9 13.3 83.3 31.7 2.1 N/A N/A N/A1-8 600 450 4.6 9.6 80.0 12.0 0.8 N/A N/A N/A1-9 1200 900 11.2 11.7 81.7 25.6 1.7 N/A N/A N/A1-10 400 150 0.8 5.0 80.0 4.0 0.3 N/A N/A N/A1-11 1000 300 2.3 7.2 80.0 8.0 0.5 N/A N/A N/A1-12 600 250 3.2 12.0 82.0 7.2 0.5 N/A N/A N/A
0 0 0 0.0 80.0 0.0 0.0 N/A N/A N/A0 0 0 0.0 80.0 0.0 0.0 N/A N/A N/A0 0 0 0.0 80.0 0.0 0.0 N/A N/A N/A0 0 0 0.0 80.0 0.0 0.0 N/A N/A N/A0 0 0 0.0 80.0 0.0 0.0 N/A N/A N/A0 0 0 0.0 80.0 0.0 0.0 N/A N/A N/A0 0 0 0.0 80.0 0.0 0.0 N/A N/A N/A
05/21/08DATE:
"YOUR COMPANY NAME"
(MZ TYPE A) VAV(1) - REHEAT COIL CALCULATIONS - 15 DEG. MAXIMUM ΔT
PROJECT NAME:
PROJECT NUMBER:
TEST PROJECT #2
1456-08
PROJECT ELEVATION =
HEATING WATER DELTA-T =
PRINTRESET/CLEAR
© Copyright 2008 HVAC Design Solutions 23
User Input of zone Heating Loads (excluding OA Loads: “Envelope Loads” only).
Program calculates actual coil loads (including “Reheat Penalty”).
Also calculates required Coil GPM.
OA DESIGN DB = -4 670COOLING SUPPLY DB = 55 30DESIGN ROOM TEMP. = 70 HEATING WATER SUPPLY TEMP = 200
VAV COOLING MINIMUM ZONE
NUMBER AIR QUANTITY AIR QUANTITY COIL LOAD (1) COIL GPM (2) PIPE SIZE (3) NOTES
(CFM) (CFM) (MBH) ENTERING LEAVING ENTERING LEAVING (GPM) (IN.)
1-1 500 250 6.7 55.0 80.0 200 170 0.4 1/2 4 - 71-2 800 250 7.9 55.0 84.6 200 170 0.5 1/2 4 - 71-3 5000 3800 112.3 55.0 82.7 200 170 7.5 1 4 - 71-4 600 360 9.6 55.0 80.0 200 170 0.6 1/2 4 - 71-5 650 490 13.1 55.0 80.0 200 170 0.9 1/2 4 - 71-6 850 300 8.9 55.0 82.8 200 170 0.6 1/2 4 - 71-7 1400 1050 31.7 55.0 83.3 200 170 2.1 1/2 4 - 71-8 600 450 12.0 55.0 80.0 200 170 0.8 1/2 4 - 71-9 1200 900 25.6 55.0 81.7 200 170 1.7 1/2 4 - 71-10 400 150 4.0 55.0 80.0 200 170 0.3 1/2 4 - 71-11 1000 300 8.0 55.0 80.0 200 170 0.5 1/2 4 - 71-12 600 250 7.2 55.0 82.0 200 170 0.5 1/2 4 - 7
55.0 80.0 0.055.0 80.0 0.055.0 80.0 0.055.0 80.0 0.0
AIR TEMP. (DEG. F) WATER TEMP. (DEG. F)
HEATING WATER DELTA-T =
TEST PROJECT #2"YOUR COMPANY NAME"
DATE: 5/21/2008
PROJECT ELEVATION = PROJECT NAME:
PROJECT NUMBER: 1456-08
VARIABLE AIR VOLUME TERMINAL UNIT SCHEDULE (WITH REHEAT)REHEAT COIL DATA BASED ON MINIMUM AIR QUANTITY (COLUMN 3)
© Copyright 2008 HVAC Design Solutions 24
Automatic printout of VAV Schedule, for input to ACAD drawing schedule or for final selection by equipment manufacturers.
Also calculates “most economical” pipe sizing for coil supply pipes.
© Copyright 2008 HVAC Design Solutions 25
PAGE 1
84
ZONE AIR DISTRIBUTION EFFECTIVENESS (Ez)
67 357
ASHRAE STD. 62.1-2004 COMPLIANCE
PEOPLE OUTDOOR AIR (CFM) (Rp x Pz)
60
DEFAULT OCCUPANCY (NUMBER OF PEOPLE) (Pz)
Reception areas
OCCUPANCY CATEGORY
CALCULATED OCCUPANCY (NUMBER OF PEOPLE) (Pz)
12.0
CORRECTED OCCUPANCY FOR INTERMITTENT USAGE SPACES
(NUMBER OF PEOPLE)12
PEAK OCCUPANCY - IF KNOWN (EG. MEETING IN AN OFFICE)
(NUMBER OF PEOPLE)
Office space
12.0
100 120
25.0 24.0
2515 900
3.5
Lecture classroom
Conference/meetin
g
Telephone/data entry
20 24 40
12 5
500
NORMAL OCCUPANCY - IF KNOWN (EG. ONE PER OFFICE) (NUMBER OF PEOPLE)
4 2 140
12 6 180
0.06
400 700 950ZONE FLOOR AREA (SQ. FT.)
(Az)400 600 3000
5.0 7.5
AREA OUTDOOR AIR RATE (CFM/SQ. FT.) (Ra) 0.06
1.0
10
0.06
400
7.5
61.8
3 180
20
IF SPACE IS INTERMITTENT USAGE (EG. CONFERENCE ROOM)
(SPACE HEIGHT - FT.)8 8 8 8 8 10
1 1 1
42 57 24
144
AIR DISTRIB. CONFIG. NUMBER (SEE TABLE 6-2)
1 1 3 1 3
5 40 16
120
AREA OUTDOOR AIR (CFM) (Ra x Az) 24 36 180 30 24
DESIGN OCCUPANCY (CALCULATED, IF KNOWN OR DEFAULT)
(NUMBER OF PEOPLE) (Pz)12 3 180 20 24
84 51 1350 130 180 67 357 144
1.0 1.0 0.8 1.0 0.8 1.0 1.0
130 14451 1080
Lobbies/prefunction
ZONE OUTDOOR AIRFLOW (CFM) (Voz)
BREATHING ZONE OUTDOOR AIRFLOW (CFM) (Vbz)
300
3.0 180.0
16
3.0 180.0 20.0 24.0 5.0 40.0
12.0
16.0
20 24 40
0.06 0.06 0.06 0.06 0.06
PEOPLE OUTDOOR AIR RATE (CFM/PERSON) (Rp)
5.0 5.0 5.0 5.0 5.0
ZONE NUMBER (EG: 1-1, 1-2) 1-1 1-2 1-3 1-81-4 1-5 1-6 1-7
PROJECT NAME: Berkley P laza
AIR HANDLING UNIT TAG NUMBER (AHU-1, ETC.)
AHU-1PROJECT NUMBER: 125-07
DATE: 4/3/2007
"Your Company Name"
VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITYMULTIPLE ZONE SYSTEMS (WITHOUT ZONE LEVEL RECIRCULATION)
Office space
Telephone/data entry
PAGE 2
MULTIPLE ZONE RECIRC. SYSTEM REQUIRED OA INTAKE FLOW (CFM) (Vot) 3322
CALCULATED SYSTEM VENTILATION EFFICIENCY (APPENDIX A)
(Ev) = MINIMUM (Evz)0.68
ZONE VENTILATION EFFICIENCY (Evz)
0.85 0.98 0.77 0.76 0.73 0.71
0.46 0.22 0.51 0.48
0.97 0.68
0.43
AVERAGE OUTDOOR AIR FRACTION (Xs)
0.19
DISCHARGE OUTDOOR AIR FRACTION (Zd)
0.34 0.20 0.42
SYSTEM PRIMARY AIRFLOW (CFM) (Vps)
11950
DEFAULT SYSTEM VENTILATION EFFICIENCY (Ev) 0.65
MAXIMUM ZONE PRIMARY OUTDOOR AIR FRACTION (Zp) 0.510
UNCORRECTED OUTDOOR AIR INTAKE (CFM) (Vou)
2254.893939
OCCUPANT DIVERSITY (SYSTEM POPULATION / SUM OF DESIGN
POPULATION) (D)0.88
ZONE POPULATION (LARGEST TYPICAL OCCUPANCY)
(SUM (Pz))330
61.75 12
SYSTEM POPULATION (SUM OF NORMAL OCCUPANCIES) (Ps) 290.75
0.22 0.51 0.48
NORMAL ZONE OCCUPANCY (EITHER KNOWN OR DEFAULT)
(NUMBER OF PEOPLE) 4 2 140 25 12 5
ZONE PRIMARY OUTDOOR AIR FRACTION (Zp) 0.34 0.20 0.42 0.43 0.46
600
MINIMUM VAV AIRFLOW TO ZONE (INCL. PRIMARY OA & RA) (CFM) (Vdz)
250 250 3200 300 390 300 700 300
DESIGN PRIMARY AIRFLOW TO ZONE (INCL. PRIMARY OA & RA) (CFM) (Vpz)
500 800 4000 600 500 850 1100
ZONE NUMBER (EG: 1-1, 1-2) 1-1 1-2 1-3 1-81-4 1-5 1-6 1-7
VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITYMULTIPLE ZONE SYSTEMS (WITHOUT ZONE LEVEL RECIRCULATION)
ASHRAE STD. 62.1-2004 COMPLIANCE
125-07
DATE: 4/3/2007
PROJECT NAME: Berkley Plaza
AIR HANDLING UNIT TAG NUMBER (AHU-1, ETC.)
AHU-1PROJECT NUMBER:
After completing input and optimization, compliance documents can be printed for submittal to building department officials and for LEED submittals.
© Copyright 2007 HVAC Design Solutions 26
For more information, see our article appearing in the November, 2006 ASHRAE Journal
© Copyright 2008 HVAC Design Solutions 27
Also, with “VAV” Version
TABLE 6-4MINIMUM EXHAUST RATES ( FROM ASHRAE STANDARD 62.1-2007)
TABLE 6-3
TABLE 6-1
SYSTEM VENTILATION EFFICIENCY ( FROM ASHRAE STANDARD 62.1-2007)
TABLE 6-2ZONE AIR DISTRIBUTION EFFECTIVENESS ( FROM ASHRAE STANDARD 62.1-2007)
MINIMUM VENTILATION RATES IN BREATHING ZONE ( FROM ASHRAE STANDARD 62.1-2007)
ACAD1 (VAV)ACAD DRAWING OF SUGGESTED VAV TERMINAL UNIT SCHEDULE (WITH REHEAT)
VAV(4) REHEAT (B)CALCULATION PROGRAM FOR VAV TERMINAL AND REHEAT COIL SIZING (MULTIPLE ZONE WITH ZONE LEVEL RECIRC.) (25° ΔT MAX)
HELP1 (VAV)HELP FILE INFORMATION FOR VAV/REHEAT CALCULATIONS
VAV(2) REHEATCALCULATION PROGRAM FOR VAV TERMINAL AND REHEAT COIL SIZING (MULTIPLE ZONE WITHOUT ZONE LEVEL RECIRC.) (25° ΔT MAX)
VAV(3) REHEAT (B)CALCULATION PROGRAM FOR VAV TERMINAL AND REHEAT COIL SIZING (MULTIPLE ZONE WITH ZONE LEVEL RECIRC.) (15° ΔT MAX)
VAV(1) REHEATCALCULATION PROGRAM FOR VAV TERMINAL AND REHEAT COIL SIZING (MULTIPLE ZONE WITHOUT ZONE LEVEL RECIRC.) (15° ΔT MAX)
MULT. ZONE TYPE ACALCULATION PROGRAM FOR "SINGLE SUPPLY" SYSTEMS WHERE ALL VENTILATION IS A MIXTURE OF OA AND RA FROM A SINGLE
CALC. PROGRAM FOR SYSTEMS THAT PROVIDE PART OF THE VENTILATION BY RECIRCULATING LOCAL AIR WITHOUT DIRECTLY MIXING WITH OA
MULT. ZONE TYPE B
FORM FOR LISTING THE NECESSARY INPUT DATA FOR REQUIRED VENTILATION CALCULATIONS
CALCULATION PROGRAM FOR SYSTEMS WITH ONE AIR HANDLER SUPPLYING AIR TO ONLY ONE ZONE
100% OA SYSTEM
CALCULATION PROGRAM FOR SYSTEMS WITH ONE AIR HANDLER SUPPLYING 100% OUTDOOR AIR TO ONE OR MORE ZONES
SINGLE ZONE SYSTEM
TAKE-OFF FORM
BASIC PROJECT INFORMATION FORM
TAB CONTENTS
PROJECT INFO
Straightforward takeoff and input allows easy analysis of ALL zones, to assure that the correct “critical zones” are analyzed.
All procedures, formulas, charts, and tables as prescribed by the Ventilation Rate Procedure have been included and have been used to establish the “Optimized” outdoor intake flow rate requirements.
Capacity of over 100 zones per air handling unit, using Appendix A calculations.
© Copyright 2007 HVAC Design Solutions 28
Proprietary “Optimization” procedures to assure that the prescribed outdoor air requirements are being met while also assuring that the outdoor air quantities are not grossly excessive. Optimization can save significant energy and operating costs over the life of a facility.
Output in the form of “Compliance Documents” for submittal to appropriate code enforcement officials or building departments.
© Copyright 2007 HVAC Design Solutions 29
Separate calculation procedures for multiple zone systems with and without local recirculation systems, as well as single zone systems and 100% outdoor air systems.
Time averaging algorithms for occupancy, where allowed.
Extensive “Help Files” that are hyperlinked to each program, form, or table.
Available in either I-P Units or SI Units
© Copyright 2007 HVAC Design Solutions 30
Limited time “Special Pricing” available at our website www.hvacdesignsolutions.com
62.1-2007 Comply (Inch-Pound or SI Units) Original Price: $250 US, Special Price: $189 US
62.1-2007 Comply-VAV (I-P or SI Units) Original Price: $300 US, Special Price: $219 US
© Copyright 2008 HVAC Design Solutions 31
Current Version: 2.38, with latest update (06/04/2008) Free updates as available.
To purchase 62.1-2007 Comply, visit our website at www.hvacdesignsolutions.com and go to the Prices/Orders page
Software can be downloaded for immediate installation (with password) after purchase is confirmed
© Copyright 2008 HVAC Design Solutions 32
OS: Windows® 98, 2000, XP, 2003, Vista Processor: Pentium® or equivalent Ram: 512MB (recommended) Disk Space: 100 MB (recommended) Software: MS Word®, MS Excel®
© Copyright 2008 HVAC Design Solutions 33
Thank you for taking your time to review our 62.1-2007 Comply software package
If you have any questions or comments, you can e-mail to: steve”at”hvacdesignsolutions.com , or support”at”hvacdesignsolutions.com
We also have an interactive demo of our 62.1-2007 Comply software that can be delivered, on request, via e-mail.