60- Surge Arresters

Embed Size (px)

Citation preview

  • 7/28/2019 60- Surge Arresters

    1/69

    1

    Surge Arresters

  • 7/28/2019 60- Surge Arresters

    2/69

    2

    Surge Arresters

    Gaps and gapless

    Silicon Carbide and Metal Oxide

    Class

    Tests and Ratings Installation

    Field testing and Failures

    IEEE C62.11-1999

  • 7/28/2019 60- Surge Arresters

    3/69

    3

    I=kVa

    No Gap:

  • 7/28/2019 60- Surge Arresters

    4/69

    4

    Series Gap:

  • 7/28/2019 60- Surge Arresters

    5/69

    5

    Shunt Gap:

  • 7/28/2019 60- Surge Arresters

    6/69

    6

    I=kVa

    Silicon Carbide Arresters:

    Silicon carbide blocks

    Duty Cycle Rating

    Protective level

    ma Ln Current ka

    A

    rrestervoltage

    Metal Oxide Blocks

    Gradingcircuitr

    y

    Series Gaps

    Operating voltage

  • 7/28/2019 60- Surge Arresters

    7/69

    7

    Silicon Carbide Arrester

    Valve Block

    Gap

    Elements

    Gap

    Elements

  • 7/28/2019 60- Surge Arresters

    8/69

    8

    Silicon Carbide Arresters

    Blocks cannot conduct continuously Series gaps

    Fast transients cause the series gaps to short over and insertthe silicon carbide blocks

    Gaps must reseal after the arrester operates (gradingcircuitry)

    Duty cycle rating is the maximum 60hz voltage where thegaps can still re-seal against power follow current

    Subject to external contamination

    Doble study shows that 50% of silicon carbide arresterstested cannot meet original protection characteristics

    Problem with moisture contamination and gaps changingcharacteristics

    Oldest SiC arresters do not have a pressure relief rating

  • 7/28/2019 60- Surge Arresters

    9/69

  • 7/28/2019 60- Surge Arresters

    10/69

    10

    Arrester

    Class:

    IEEE C62.11-1999

  • 7/28/2019 60- Surge Arresters

    11/69

    11

    Arrester Class:

    The key test for determining class is the Pressure Relief Test: Arrester must vent at or below the rated current for both the high and

    low current values

    Parts of the arrester must not fall outside a circle with the radius equalto the height of the arrester (it can fall down!)

  • 7/28/2019 60- Surge Arresters

    12/69

    12

    Metal Oxide arresters

    Station Class Metal Oxide arresters were firstintroduced around 1980 for transmissionapplications

    Originally three varieties: GaplessWestinghouse 4 discs

    Shunt gapGeneral Electric 3 discs

    Series gapOhio Brass 3 discs

    Today all station class arresters are gapless Intermediate and distribution ratings introduced in

    mid 80s (gapless)

    Polymer housings introduced in 90s

  • 7/28/2019 60- Surge Arresters

    13/69

    13

    MOVDesign

    Tests

    Arrester class

  • 7/28/2019 60- Surge Arresters

    14/69

    14

    Tests and Ratings

    Protective Characteristics

    Discharge current

    Lightning impulse

    Switching impulse Arrester Survival

    MCOV

    Temporary over-voltage (TOV)

    Duty Cycle (accelerated aging) Transmission line discharge

    Pressure Relief tests (arrester class)

    Porcelain vs polymer

  • 7/28/2019 60- Surge Arresters

    15/69

    15

    Discharge Current:The surge current that flows through an arrester.

    In a gapless arrester the peak voltage that appears across the

    arrester at the discharge current is the protective level.A series of 8/20 current waves are used with the peak

    amplitudes listed below:

    1500a

    3000a 5000a

    10000a

    15000a (500kv only)

    20000a (distribution & subtransmission

    - unshielded)

    40000a

    These points are used to compare to the equipment BIL.

    The manufacturers published information shall state for each

    arrester rating the maximum discharge voltage for each

    discharge current listed. IEEE C62.11-1999

    IV

  • 7/28/2019 60- Surge Arresters

    16/69

    16

    A typical discharge current called the classifying

    current is used to determine the lightning and

    switching surge protective levels. These currentsvary depending on the nominal system voltage:

  • 7/28/2019 60- Surge Arresters

    17/69

    17

    Lightning Protective Levels:

    LPL - An 8x20 lightning impulse discharge current ispassed through the arrester to determine the dischargevoltages.

    The current magnitude is the classifying current for the

    appropriate system voltage. It simulates the currentmagnitude and shape that the arrester would have to shuntto ground due to a lightning stroke coming in on the 138kvline.

    Example: an arrester applied on a 138kv system should usea 10ka 8x20 u-sec classifying current. This produces164.9kv at the arrester. This is the protective level (LPL).

    The voltage protective level coordinates with theequipment BIL withstand value

  • 7/28/2019 60- Surge Arresters

    18/69

    18

    Front-of-Wave Protective

    Levels:

    FOWThree current impulses (1 u-sec, 2u-sec and 8 u-sec rise) are passed throughthe arrester and the three crest voltages are

    plotted against time. Again the current magnitude is the

    appropriate impulse classifying current.

    The Front-of -Wave protective level is thepoint on the curve at .5 u-seconds

    This protective level coordinates with theequipment chopped wave withstand

  • 7/28/2019 60- Surge Arresters

    19/69

    19

    Switching Surge Protective

    Levels:

    A discharge current of 45-60 u-secs rise

    time is passed through the arrester todetermine the discharge voltage

    The magnitude is the switching surge

    classifying current for the appropriatesystem voltage

    This protective level coordinates with theequipment switching surge withstand

  • 7/28/2019 60- Surge Arresters

    20/69

    20

  • 7/28/2019 60- Surge Arresters

    21/69

    21

    Tests and Ratings

    Protective Characteristics

    Discharge current

    Lightning impulse

    Switching impulse Arrester Survival

    MCOV

    Temporary over-voltage (TOV)

    Duty Cycle (accelerated aging) Transmission line discharge

    Pressure Relief tests (arrester class)

    Porcelain vs polymer

    l

  • 7/28/2019 60- Surge Arresters

    22/69

    22

    Be sure MCOV value is correct

    Class must also be

    Correct

    MOV Nameplate

  • 7/28/2019 60- Surge Arresters

    23/69

    23

    MCOVMaximum Continuous Operating Voltage

    rating is the maximum designated root-mean-squared(rms) value of power frequency voltage that may be

    applied continuously between the terminals of the

    arrester.

    (Note this is phase to ground rms volts!)

    Example 145kv to ground = 83.7kv so the minimum

    MCOV for our 138 kv system is 84kv

    This is the most important criteria for correctapplication

    IEEE C62.11-1999

  • 7/28/2019 60- Surge Arresters

    24/69

    24

    Temporary Over-voltage Curves: MOVs can

    tolerate voltages over MCOV for short periodsCheck the actual manufactures curves for each arrester.

    Note curves for prior duty and no prior duty. The prior dutycurve is for previous transmission switching duty.

  • 7/28/2019 60- Surge Arresters

    25/69

    25

    Duty Cycle RatingArrester is raised to an

    elevated 60hz voltage (duty cycle rating) andoperated 20 times at the impulse classifying current.

    If it doesnt go into thermal runaway it passes the

    test. Basically this is equivalent to the old duty cycle

    rating for silicon carbide arresters.

    Example: an 84kv MCOV translates to a 108kv duty

    cycle rating. A 98kv MCOV is a 120kv duty cycle.

    This test coupled with the high current discharge testsimulates accelerated aging of the blocks.

  • 7/28/2019 60- Surge Arresters

    26/69

    26

    Metal Oxide

    Arrester Ratings:

  • 7/28/2019 60- Surge Arresters

    27/69

    27

    Switching

    Surges:

    Z0= L/C

    Voltage doubles when closing in on an

    open line = 2 P.U. at open line terminal

    Assume that High Speed Re-closing traps a negative 1 P.U. charge on the line.

    Then when the breaker re-closes the maximum voltage at the open end can

    approach a maximum of 3.5 - 4.0 P.U. for multiple reflections depending on

    damping (R):

    Trapped charge = -1.0 P.U.

    3.5 P.U.

  • 7/28/2019 60- Surge Arresters

    28/69

    28

    Transmission Line Discharges:

  • 7/28/2019 60- Surge Arresters

    29/69

    29

    Transmission Line Discharges:

    When an arrester discharges a switching surge the

    blocks heat up. Switching surges last much longer

    than lightning surges and so the arresters must

    dissipate more energy. Repetitive discharges can cause the arrester to fail

    if there isnt enough time between to allow for

    cooling

    The transmission discharge test assures the

    arrester will tolerate a standard amount of energy

  • 7/28/2019 60- Surge Arresters

    30/69

    30

    Surge impedance Line Length

  • 7/28/2019 60- Surge Arresters

    31/69

    31

    Transmission Line Discharges:

    The arrester is subjected to 20 surges:

    Six consecutive-one minute to cool-six more-

    one minute-six more-one minute-two more

    The arrester passes if:

    discharge test is successful

    Power loss is within specs (leakage current)

    Transient Network Analysis studies use a value of7 kilojoules/kv of MCOV rating for transmission

    arresters

  • 7/28/2019 60- Surge Arresters

    32/69

    32

    Pressure Relief Tests:

    If an arrester fails internally the arc creates rapidly expanding

    gasses that can cause the housing to explode violently unless

    the pressure is vented. Arresters are rated on the fault current

    magnitude that can pass through the housing. They must vent

    successfully at or below the rated current:

  • 7/28/2019 60- Surge Arresters

    33/69

    33

    Arc

    Chutes:

  • 7/28/2019 60- Surge Arresters

    34/69

    34

    Arc

    Chutes:

    Seal plates

  • 7/28/2019 60- Surge Arresters

    35/69

    35

    Failed 396kv arrester at Black Oak substation

    Failed from prolonged 60hz over-voltage:

  • 7/28/2019 60- Surge Arresters

    36/69

    36

    This arrester actually failed according to the

    standard. The pieces didnt scatter very far!

    rrester ase e t on structure

  • 7/28/2019 60- Surge Arresters

    37/69

    37

    rrester ase e t on structureafter failure.

    T i l 46 kV MOV A

  • 7/28/2019 60- Surge Arresters

    38/69

    38

    Typical 46 kV MOV Arrester

    Polymer Housing

  • 7/28/2019 60- Surge Arresters

    39/69

    39

    Failed Polymer Arrester

  • 7/28/2019 60- Surge Arresters

    40/69

    40

  • 7/28/2019 60- Surge Arresters

    41/69

    41

    Arrester Installation

    Groundingcontinuous conductor

    Better ground improves arrester

    performance

    Shortest ground lead length Can monitor leakage current if the lead is

    insulated

    Lead length & ground lead

    Corona rings/Clearances Arc chutes

    SiC change-outs

  • 7/28/2019 60- Surge Arresters

    42/69

    42

    Arc

    Chutes:

    Arc chutes should face

    away from other

    equipment or bushings

  • 7/28/2019 60- Surge Arresters

    43/69

    43

    Installed 138 kV Arrester

  • 7/28/2019 60- Surge Arresters

    44/69

    44

    Infrastructure

    Silicon Carbide ArresterReplacement Program

    Change out old SiC arresters on xfmrs starting in2006 during 5 year gauge inspections (xfmrs138kv and above)

    Replace old arresters as part of xfmr/breakerchange-outs and pin/cap insulator replacements

    If a SiC arrester fails, change out all 6

    Dont return SiC arresters to stock

    Arrester

  • 7/28/2019 60- Surge Arresters

    45/69

    45

    Arrester

    Maintenance, Field

    Tests & Failures

    Cant check protectivelevels in the field!

    Moisture intrusion

    Leakage current

    Power factor

    Megger Thermovision

    Visual inspections

    Failed arresters

    L k C t

  • 7/28/2019 60- Surge Arresters

    46/69

    46

    watts

    vars

    Leakage Current:Measure leakage current with the arrester energized

    Increasing resistive component of

    the leakage current indicates blocks arefailing (losses are proportional to i2)

    ma

  • 7/28/2019 60- Surge Arresters

    47/69

    47

    Inspection While Out of service:

    Weather Tight Housing

    Check for cracks in the porcelain or tears or bulges in the

    polymer.

    Clean all external surfaces of the arresterCoat all external weather tight housing surfaces with

    silicon grease to aid in water shedding if environment

    is harsh.

    Check and clean the ground connections

    Inspection and Prep for Testing:

  • 7/28/2019 60- Surge Arresters

    48/69

    48

    Effects of Contamination:

    Contamination causes an unequal voltage

    distribution across the outside surface of

    the arrester.

    In arresters with internal gaps and grading

    circuitry this can also cause an imbalance

    of voltage across the gaps and results in

    improper operation and prematurefailure of the arrester.

    P F t

  • 7/28/2019 60- Surge Arresters

    49/69

    49

    watts

    vars

    Power Factor:Apply 10kv to terminal and measure

    leakage current

    Resistive component of leakage currentindicates internal moisture contamination

    10 kv

    P F T

  • 7/28/2019 60- Surge Arresters

    50/69

    50

    Inspection While Out of service:

    Electrical Testing

    Power Factor Testing

    Should perform upon installation to establish benchmark.

    This test is generally more effective on Silicon Carbide arresters than

    MOV arresters in detecting internal contamination or breakdown of

    spark gaps or valve blocks.

    Make the measurement with the highest voltage available on the test

    set without exceeding the line to ground voltage of the arrester undertest.

    The values that are measured are the leakage current (less than 3

    milli-amperes) and watts loss (less than 150 mW). These tests can

    only be read utilizing a 10kV power factor test set.

    Power Factor Test:

  • 7/28/2019 60- Surge Arresters

    51/69

    51

    Example:

    During Class A Maintenance on the No. 2transformer at Doubs Substation, theSubstation Crew decided to perform Power

    Factor Testing on the high side arresters. Testing revealed an abnormal test pattern on

    the Z phase arrester

    The next slides show the test results of aneighboring similar arrester as well as theresults from the arrester in question.

  • 7/28/2019 60- Surge Arresters

    52/69

    52

    Arrester Details

    Nameplate Data of Arrester

    ABB

    EXLIM

    StyleT396SA318AAP

    Serial No. 00M3001

    T t R lt

  • 7/28/2019 60- Surge Arresters

    53/69

    53

    Test Results

    on a Good Arrester

    All tests were performed with the Doble Power

    Factor test set at 10 kV.

    Phase results (comparable to all arresters tested ofthe same make and model)

    mA Watts

    Top 0.357 0.060Mid 0.164 0.059

    Bot 0.318 0.083

    T t R lt

  • 7/28/2019 60- Surge Arresters

    54/69

    54

    Test Results

    on the Arrester in Question

    Z Phase results (4/28/2003)

    mA WattsZ Top 0.376 0.142

    Z Mid 0.309 1.550

    Z Bott 0.034 0.211

    Retest Results

  • 7/28/2019 60- Surge Arresters

    55/69

    55

    Retest Results

    on the Arrester in Question

    Phase results (4/30/2003) after cleaning surfaces

    mA Watts

    Top 0.360 0.113

    Mid 0.236 0.948

    Bott 0.311 0.010

    The retests did show a slight improvement of the

    readings after the cleaning. The middle sectionwas still different from a typical reading. Thedecision was made to replace the arresterassembly.

  • 7/28/2019 60- Surge Arresters

    56/69

    56

    Test Results

    on the Arrester in QuestionPhase results (4/30/2003) on the ground after

    disassembly

    mA WattsMid 0.384 1.471

    Bott 0.317 0.082

    The tests on the ground showed that the bottom

    section was of typical values but the middlesection was still different from the typicalreadings. The arrester was sent to ABB inYoungwood, PA for further investigation.

    ABB Investigation

  • 7/28/2019 60- Surge Arresters

    57/69

    57

    ABB Investigation

    6/3/2002

    ABB Received the arrester sections and performeda voltage test on all 3 sections.

    The test applies the rated voltage to each section

    of the arrester. (118 kV for the top 2 sections and82 kV for the bottom section). The resultingleakage current is then read. The expected leakageis less than 1 mA.

    The top section and bottom section passed the test. The middle section failed the test when the applied

    voltage was only 44 kV (expected to reach 118kV)

    ABB Investigation

  • 7/28/2019 60- Surge Arresters

    58/69

    58

    ABB Investigation

    6/3/2002

    Top of Middle section Arrester with Retaining

    plate removed and seal plate exposed.

  • 7/28/2019 60- Surge Arresters

    59/69

  • 7/28/2019 60- Surge Arresters

    60/69

    ABB Investigation

  • 7/28/2019 60- Surge Arresters

    61/69

    61

    ABB Investigation

    6/3/2002

    A close inspection of the seal plate revealed a

    crack in the plate.

    ABB Investigation

  • 7/28/2019 60- Surge Arresters

    62/69

    62

    ABB Investigation

    6/3/2002

    Removal of first MOV Disc. Notice the

    surface contamination on the disc

    ABB Investigation

  • 7/28/2019 60- Surge Arresters

    63/69

    63

    ABB Investigation

    6/3/2002

    Removal of entire stack of

    MOV Discs. Notice the

    surface contamination on all

    the discs

    Megger Test:

  • 7/28/2019 60- Surge Arresters

    64/69

    64

    Inspection While Out of service:

    Electrical Testing Insulation Resistance

    An arrester is to act as an insulator a majority of its in service life. Itwill only allow current to flow to ground during high voltage transientsgenerally caused by lightning.

    Make the measurement with the highest voltage available on the testset without exceeding the line to ground voltage of the arrester undertest.

    Readings should be comparable to similar arresters. The valueshould be greater than 200 Mega Ohms. This test is generally moreeffective on Silicon Carbide arresters than MOV arresters indetecting internal contamination or breakdown of spark gaps or valveblocks.

    MOV arresters may show a high insulation resistance value after anoperation but still be failed as an open circuit.

    Megger Test:

  • 7/28/2019 60- Surge Arresters

    65/69

    65

    Infra-red Image of Arresters

    *>24.3

    *

  • 7/28/2019 60- Surge Arresters

    66/69

    66

    Inspection While in service :

    Infra red Imaging

    Infra red imaging of in-service arresters may detect damagedarresters

    Arresters while in normal service only conduct a few milli-amps of current, therefore, will not produce heat.

    If the arrester images indicate a rise in temperature fromambient temperature of 5 degrees Celsius or more,replacement should be considered.

    The blocks are probably starting to fail and are conductingtoo much current

    Infrared Imaging

    Visual Inspection

  • 7/28/2019 60- Surge Arresters

    67/69

    67

    Inspection While in service:

    Weather Tight Housing The weather tight housing is the covering of the arrester

    Generally produced from porcelain or polymer.

    Check for cracks in the porcelain or tears or bulges in the polymer.

    Make certain porcelain or polymer appears clean and free ofany debris

    Visually inspect the ground connections from the base of thearrester. A missing connection will not allow the arrester tofunction as designed.

    Multiple arrester operations with improperly sized wire may result in afailure of the ground wire.

    Improperly sized ground wire may also result in fire.

    Visual Inspection

    Failed Arresters:

  • 7/28/2019 60- Surge Arresters

    68/69

    68

    Failure assessment Suspect Arresters

    Exercise EXTREME caution while investigating problems and

    handling suspect arresters. Sealed Silicon Carbide and MOV

    arresters may be under pressure due to a build up of fault

    gasses. Visually inspect suspect arresters carefully while looking for

    burn deposits near arc chutes on Silicon Carbide arresters.

    MOV arresters may show very subtle signs of failure such as

    deformation of the polymer covering. Generally, MOV

    arresters will fail and split the polymer covering or fracture theporcelain cover.

    Failed Arresters:

  • 7/28/2019 60- Surge Arresters

    69/69

    Thanks for your attention