DEPARTMENT OF TRANSPORTATION AND COMMUNICATIONS Republic of the Philippines CONSTRUCTION OF TOILET FACILITIES Prepared by : Assistant Secretary for Project Management Planning Officer III ENGR. MANUEL C. DEL CARMEN Sheet Content: Sheet No.: Sheet No.: TS S - - - - P S R A F N A R T M T O T N E O O C D N A T R A N O I T P C I N U A E D S N O I T M M PROJECT NAME : Submitted by: Recommending Approval: Approved: Regional Director Atty ALIM D. PANGANDAMAN ILDEFONSO T. PATDU, JR. ATTY. EFREN C. MONCUPA Undersecretary for Project Implementation and Special Concerns LOCATION : CARAGA REGION XIII TOILET FOUNDATION PLAN F1 - C1 F1 - C1 F1 - C1 F1 - C1 F1 - C1 F1 - C1 WF WF WF WF WF WF WF WF WF LENGTH LENGTH / 4 LENGTH / 4 TYPICAL DETAIL OF BEAM 10mm stirrups spaced @ 5-.05 m 5-.10 m 5-.15 m rest @ .20 m 12 mm horizontal bars 12161 600 600 4154 5154 1000 BUILDING LINE FIREWALL 2"X3" C-PURLINS 1.2 THICK TRUSS TRUSS TRUSS TRUSS TRUSS TRUSS TRUSS FASCIA FASCIA FASCIA TOILET ROOF FRAMING PLAN 10961 800 250 800 250 4-12mmØ VERT. BARS W/ 10mmØ LATERAL TIES SPACED; 3 @ 50mm, 3@100mm, 3@ 150mm, REST @ 200mm 7-16mmØ MATTING BARS BOTHWAYS PLAN 300 800 N.G.L. SECTION 4-12mmØ VERT. BARS W/ 10mmØ LATERAL TIES SPACED; 3 @ 50mm, 3@100mm, 3@ 150mm, REST @ 200mm F1-C1 TRUSS DETAIL DIAGRAM 6" CONCRETE HOLLOW BLOCKS PRE-PAINTED RIB TYPE ROOFING 2" X 4" C-PURLINS 2" X 6" CHANNEL BAR RAFTER ORDINARY GUTTER FASCIA BOARD 250 NAT. GRD. LINE FIN. GRD. LINE FIN. FLR. LINE 600 VERIFY 200 150mm THK. CHB WITH 10mmØ HOR. AND VERTICAL BARS @ 600mm O.C. 3-10mmØ LONG BARS 450 ELEVATION SURIGAO DISTRICT OFFICE CAPITOL COMPOUND, SURIGAO CITY AS SHOWN LTO.13.CR.P3.E1.L1.1 LTO.13.CR.P3.E1.L1.0 LTO.13.CR.P3.E1.L1.2

6 CONCRETE HOLLOW BLOCKS...EFREN C. MONCUPA Undersecretary for Project Implementation and Special Concerns LOCATION : CARAGA REGION XIII TOILET FOUNDATION PLAN F1 - C1 F1 - C1 F1 -

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Page 1: 6 CONCRETE HOLLOW BLOCKS...EFREN C. MONCUPA Undersecretary for Project Implementation and Special Concerns LOCATION : CARAGA REGION XIII TOILET FOUNDATION PLAN F1 - C1 F1 - C1 F1 -

DEPARTMENT OF TRANSPORTATIONAND COMMUNICATIONS

Republic of the Philippines

CONSTRUCTION OF TOILETFACILITIES

Prepared by :

Assistant Secretary for ProjectManagement

Planning Officer III

ENGR. MANUEL C. DEL CARMEN

Sheet Content:

Sheet No.:Sheet No.:

TSS --

--

PS

RA

F

NART

MT

OT

N E

O

O

CD

N

ATRA

NOIT

P

CIN

U

AE D SN OI T

MM

PROJECT NAME :

Submitted by:

Recommending Approval:

Approved:

Regional DirectorAtty ALIM D. PANGANDAMAN

ILDEFONSO T. PATDU, JR.

ATTY. EFREN C. MONCUPAUndersecretary for Project

Implementation and Special Concerns

LOCATION : CARAGA REGION XIII

TOILET FOUNDATION PLAN

F1 - C1 F1 - C1 F1 - C1

F1 - C1

F1 - C1

F1 - C1

WF

WF

WFWF

WF

WF

WF

WF

WF

LENGTH

LENGTH / 4 LENGTH / 4

TYPICAL DETAIL OF BEAM

10mm stirrups spaced @ 5-.05 m5-.10 m5-.15 mrest @ .20 m

12 mm horizontal bars

12161

600600

4154 51

54

1000

BUILDING LINEFIREWALL

2"X3" C-PURLINS 1.2 THICK

TRU

SS

TRU

SS

TRU

SS

TRU

SS

TRU

SS

TRU

SS

TRU

SS

FASCIA

FASC

IA

FASC

IA

TOILET ROOF FRAMING PLAN

10961

800

250

800

2504-12mmØ VERT. BARS W/ 10mmØLATERAL TIES SPACED; 3 @ 50mm,3@100mm, 3@ 150mm, REST @200mm

7-16mmØ MATTING BARS BOTHWAYSPLAN

300

800

N.G.L.

SECTION

4-12mmØ VERT. BARS W/ 10mmØLATERAL TIES SPACED; 3 @ 50mm,3@100mm, 3@ 150mm, REST @200mm

F1-C1

TRUSS DETAIL DIAGRAM

6" CONCRETEHOLLOW BLOCKS

PRE-PAINTED RIB TYPE ROOFING

2" X 4" C-PURLINS

2" X 6" CHANNEL BAR RAFTER

ORDINARY GUTTER

FASCIA BOARD

250

NAT. GRD. LINE

FIN. GRD. LINE

FIN. FLR. LINE

600

VERI

FY20

0

150mm THK. CHB WITH 10mmØ HOR.AND VERTICAL BARS @ 600mm O.C.

3-10mmØ LONG BARS

450

ELEVATION

SURIGAO DISTRICT OFFICECAPITOL COMPOUND, SURIGAO CITY

AS SHOWN

LTO.13.CR.P3.E1.L1.1LTO.13.CR.P3.E1.L1.0

LTO.13.CR.P3.E1.L1.2

Page 2: 6 CONCRETE HOLLOW BLOCKS...EFREN C. MONCUPA Undersecretary for Project Implementation and Special Concerns LOCATION : CARAGA REGION XIII TOILET FOUNDATION PLAN F1 - C1 F1 - C1 F1 -

DEPARTMENT OF TRANSPORTATIONAND COMMUNICATIONS

Republic of the Philippines

CONSTRUCTION OF TOILETFACILITIES

Prepared by :

Assistant Secretary for ProjectManagement

Planning Officer III

ENGR. MANUEL C. DEL CARMEN

Sheet Content:

Sheet No.:Sheet No.:

TSA --

--

PS

RA

F

NART

MT

OT

N E

O

O

CD

N

ATRA

NOIT

P

CIN

U

AE D SN OI T

MM

PROJECT NAME :

Submitted by:

Recommending Approval:

Approved:

Regional DirectorAtty ALIM D. PANGANDAMAN

ILDEFONSO T. PATDU, JR.

ATTY. EFREN C. MONCUPAUndersecretary for Project

Implementation and Special Concerns

850 850 850 1700

977

952

979

PWD

765

600

1500

600

3308

RAMP-UP

TOILET FLOOR PLAN

A A

B

B

33048304

TOILET FLOOR PLAN

9379

4308

FRONT ELEVATION

10104

1850

900

2750

2000

2734

360

1428

319

SEE TRUSS-1

G.I. SHEETS

FIREWALL

#26 CORRUGATED

W.C.

GUTTER

FASCIA

TOILET ELEVATION/SECTION "B-B"

TOILET SECTION "A-A"

1850

651

900

1850

900

2750

8891700

W.C.LAV.

1729

260317293166

LEFT ELEVATION RIGHT ELEVATION

5007

5007

3308 3308

900

6411157

600

600

2100

SCHEDULE OF DOORS AND WINDOWS ( CLASS-A)

LOCATION :

CARAGA REGION XIII PATIN-AY DISTRICT OFFICE

PROSPERIDAD, AGUSAN DEL SUR

AS SHOWN

LTO.13.CR.P2.S1.L1.1LTO.13.CR.P2.S1.L1.0

LTO.13.CR.P2.S1.L1.2

LTO.13.CR.P2.S1.L1.1

LTO.13.CR.P2.S1.L1.0LTO.13.CR.P2.S1.L1.2

Page 3: 6 CONCRETE HOLLOW BLOCKS...EFREN C. MONCUPA Undersecretary for Project Implementation and Special Concerns LOCATION : CARAGA REGION XIII TOILET FOUNDATION PLAN F1 - C1 F1 - C1 F1 -

DEPARTMENT OF TRANSPORTATIONAND COMMUNICATIONS

Republic of the Philippines

CONSTRUCTION OF TOILETFACILITIES

Prepared by :

Assistant Secretary for ProjectManagement

Planning Officer III

ENGR. MANUEL C. DEL CARMEN

Sheet Content:

Sheet No.:Sheet No.:

TSP --

--

PS

RA

F

NART

MT

OT

N E

O

O

CD

N

ATRA

NOIT

P

CIN

U

AE D SN OI T

MM

PROJECT NAME :

Submitted by:

Recommending Approval:

Approved:

Regional DirectorAtty ALIM D. PANGANDAMAN

ILDEFONSO T. PATDU, JR.

ATTY. EFREN C. MONCUPAUndersecretary for Project

Implementation and Special Concerns

TO SEPTIC TANK

F.D.

F.D.

C.O.

F.D.

TOILET SANITARY LAYOUT

10mmØ VERTICAL BARS SPACED@ 400mm ON CENTERS

10mmØ HORIZONTAL BARSPLACED EVERY 2 LAYERS OF CHB

11-10mmØ MATTING BARSSPACED EQUALLY AS SHOWN

1536

200

1536 307

DIGESTIVECHAMBER

LEACHINGCHAMBER

300

38

WATER LEVELWATER LEVEL

AIR SPACE AIR SPACE

500 500

926" THICK CHB

12mmØ MATTINGBARS SPACED @400mm ONCENTERS

3-10mm.Ø HORIZONTALTEMPERATURE BARS

MANHOLE MANHOLE

4" Ø PVC OUTLET

1500

500

MANHOLE MANHOLE

P1 40020001:20

DETAILED PLAN OF SEPTIC TANK5

P1 40020001:20

DETAILED SECTION OF SEPTIC TANK4

307

192

LEACHINGCHAMBER

38

WATER LEVEL

AIR SPACE300

10mmØ MATTINGBARS SPACED @400mm ONCENTERS

3-10mm.Ø HORIZONTALTEMPERATURE BARS

MANHOLE

4" Ø PVC OUTLET

MANHOLE

500

500

4000

2000 1000 1000

VENT STACK THRU ROOF

PLUMBING LEGEND:

VENT STACKVSVSTR

WM

GV

HB

FWATER METERHOSE BIBB

FAUCET

GATE VALVE

WC

CO

URFD

CLEAN-OUT

WATER CLOSET

FLOOR DRAINURINAL

LAV LAVATORY

CV CHECK VALVE

FCO FLOOR CLEAN-OUT

RD ROOF DRAINCB CATCH BASINDS DOWNSPOUTG.I.P. GALVANIZED IRON PIPE

SPECIFICATION :

LICENSED MASTER PLUMBER.8. ALL WORKS HEREIN SHALL BE DONE UNDER THE DIRECT SUPERVISION OF A DULY

DOUBLE CHECKED TO ENSURE WATER TIGHT PLUMBING SYSTEM.7. ALL WORKS HEREIN SHALL BE DONE OF CLASS A WORKMANSHIP, PIPING SYSTEM MUST BE

OF A TYPICAL APPROVED TANK.6. SEPTIC VAULT SHALL BE WATER TIGHT. COMPLETE WITH THE NECESSARY REQUIREMENTS

1/2" diameter PVC PIPES.5. MAIN WATER SUPPLY PIPES MUST BE 1" diameter AND BRANCH SUPPLY PIPES MUST BE4. ALL CLEAR WATER SUPPLY SYSTEM SHALL BE OF PVC PIPES, SCHEDULE 40, MOLDEX BLUE.3. USE SANIMOLD BY MOLDEX PRODUCTS FOR SANITARY WASTE SYSTEM.

2. ALL MATERIALS TO BE USED SHALL BE OF BRAND NEW AND OF APPROVED TYPE FORLOCATION AND PURPOSE.

PHILIPPINE PLUMBING CODE AND WITH THE LOCAL SANITARY AGENCY.1. ALL WORKS HEREIN SHALL BE DONE IN ACCORDANCE WITH THE PROVISION OF THE

LOCATION :

CARAGA REGION XIII PATIN-AY DISTRICT OFFICE

PROSPERIDAD, AGUSAN DEL SUR

AS SHOWN

LTO.13.CR.P2.S1.L1.1LTO.13.CR.P2.S1.L1.0

LTO.13.CR.P2.S1.L1.2

Page 4: 6 CONCRETE HOLLOW BLOCKS...EFREN C. MONCUPA Undersecretary for Project Implementation and Special Concerns LOCATION : CARAGA REGION XIII TOILET FOUNDATION PLAN F1 - C1 F1 - C1 F1 -

DEPARTMENT OF TRANSPORTATIONAND COMMUNICATIONS

Republic of the Philippines

CONSTRUCTION OF TOILETFACILITIES

Prepared by :

Assistant Secretary for ProjectManagement

Planning Officer III

ENGR. MANUEL C. DEL CARMEN

Sheet Content:

Sheet No.:Sheet No.:

TSE --

--

PS

RA

F

NART

MT

OT

N E

O

O

CD

N

ATRA

NOIT

P

CIN

U

AE D SN OI T

MM

PROJECT NAME :

Submitted by:

Recommending Approval:

Approved:

Regional DirectorAtty ALIM D. PANGANDAMAN

ILDEFONSO T. PATDU, JR.

ATTY. EFREN C. MONCUPAUndersecretary for Project

Implementation and Special Concerns

baSab

SS

S

LIGHTING LAYOUT PLAN ( CLASS-B)

POWER LAYOUT PLAN ( CLASS-B)

FROM ELECTRICALPOWER SOURCE

FROM ELECTRICALPOWER SOURCE

Legend & Symbols:

32 WATTS CIRCULAR FLUORESCENT LAMP

S SINGLE SWITCH

DUPLEX THREE PRONG-GROUNDED RECEPTACLE OUTLET

S3 TRIPLEX SWITCH

1x36 WATTS FLUORESCENT LAMP IN 0.30m. x 1.20m. FLUORESCENTFIXTURE, MIRRORIZED REFLECTOR AND LUOVER

CONDUIT RUN EMBEDDED ON WALLS & CEILING

1. All electrical works herein shall be done in accordance with the provisions of

the latest edition of the Philippine Electrical Code, existing rules and

ordinances of the Local Government, and with requirements of the Local

Power Company.

2. Type of power service shall be 230 volts, 2-wire, 60 hz., single phase, line

to ground.

3. All wirings shall be installed in standard PVC/RSC pipes inside a concrete

structure and inside ceiling spaces.

4. All materials to be used shall be brand new and of approved type.

5. Minimum size of wire and conduit to be used shall be 2.0 mm. sq. and 20

mm. dia. respectively.

6. Wherever required and necessary, pull boxes or junction boxes of proper

sizes shall be installed at convenient and inconspicuous locations, although

such boxes are not shown on the plan nor mentioned in the specifications.

7. The electrical works shall be done under the direct and immediate supervision

of a duly licensed electrical practitioner.

General notes:

LOCATION :

CARAGA REGION XIII PATIN-AY DISTRICT OFFICE

PROSPERIDAD, AGUSAN DEL SUR

AS SHOWN

LTO.13.CR.P2.S1.L1.1LTO.13.CR.P2.S1.L1.0

LTO.13.CR.P2.S1.L1.2

Page 5: 6 CONCRETE HOLLOW BLOCKS...EFREN C. MONCUPA Undersecretary for Project Implementation and Special Concerns LOCATION : CARAGA REGION XIII TOILET FOUNDATION PLAN F1 - C1 F1 - C1 F1 -

DEPARTMENT OF TRANSPORTATIONAND COMMUNICATIONS

Republic of the Philippines

CONSTRUCTION OF TOILETFACILITIES

Prepared by :

Assistant Secretary for ProjectManagement

Planning Officer III

ENGR. MANUEL C. DEL CARMEN

Sheet Content:

Sheet No.:Sheet No.:

TSS --

--

PS

RA

F

NART

MT

OT

N E

O

O

CD

N

ATRA

NOIT

P

CIN

U

AE D SN OI T

MM

PROJECT NAME :

Submitted by:

Recommending Approval:

Approved:

Regional DirectorAtty ALIM D. PANGANDAMAN

ILDEFONSO T. PATDU, JR.

ATTY. EFREN C. MONCUPAUndersecretary for Project

Implementation and Special Concerns

LOCATION :

CARAGA REGION XIII

TOILET FOUNDATION PLAN

F1 - C1 F1 - C1 F1 - C1

F1 - C1

F1 - C1

F1 - C1

WF

WF

WFWF

WF

WF

WF

WF

WF

LENGTH

LENGTH / 4 LENGTH / 4

TYPICAL DETAIL OF BEAM

10mm stirrups spaced @ 5-.05 m5-.10 m5-.15 mrest @ .20 m

12 mm horizontal bars

12161

600600

4154 51

54

1000

BUILDING LINEFIREWALL

2"X3" C-PURLINS 1.2 THICK

TRU

SS

TRU

SS

TRU

SS

TRU

SS

TRU

SS

TRU

SS

TRU

SS

FASCIA

FASC

IA

FASC

IA

TOILET ROOF FRAMING PLAN

10961

800

250

800

2504-12mmØ VERT. BARS W/ 10mmØLATERAL TIES SPACED; 3 @ 50mm,3@100mm, 3@ 150mm, REST @200mm

7-16mmØ MATTING BARS BOTHWAYSPLAN

300

800

N.G.L.

SECTION

4-12mmØ VERT. BARS W/ 10mmØLATERAL TIES SPACED; 3 @ 50mm,3@100mm, 3@ 150mm, REST @200mm

F1-C1

TRUSS DETAIL DIAGRAM

6" CONCRETEHOLLOW BLOCKS

PRE-PAINTED RIB TYPE ROOFING

2" X 4" C-PURLINS

2" X 6" CHANNEL BAR RAFTER

ORDINARY GUTTER

FASCIA BOARD

250

NAT. GRD. LINE

FIN. GRD. LINE

FIN. FLR. LINE

600

VERI

FY20

0

150mm THK. CHB WITH 10mmØ HOR.AND VERTICAL BARS @ 600mm O.C.

3-10mmØ LONG BARS

450

ELEVATION

BISLIG DISTRICT OFFICE BISLIG CITY

AS SHOWN

LTO.13.CR.P5.N1.L1.1LTO.13.CR.P5.N1.L1.0

LTO.13.CR.P5.N1.L1.2

Page 6: 6 CONCRETE HOLLOW BLOCKS...EFREN C. MONCUPA Undersecretary for Project Implementation and Special Concerns LOCATION : CARAGA REGION XIII TOILET FOUNDATION PLAN F1 - C1 F1 - C1 F1 -

DEPARTMENT OF TRANSPORTATIONAND COMMUNICATIONS

Republic of the Philippines

CONSTRUCTION OF TOILETFACILITIES

Prepared by :

Assistant Secretary for ProjectManagement

Planning Officer III

ENGR. MANUEL C. DEL CARMEN

Sheet Content:

Sheet No.:Sheet No.:

TSA --

--

PS

RA

F

NART

MT

OT

NE

O

O

CD

N

ATRA

NOIT

P

CIN

U

AE D SN OI T

MM

PROJECT NAME :

Submitted by:

Recommending Approval:

Approved:

Regional DirectorAtty ALIM D. PANGANDAMAN

ILDEFONSO T. PATDU, JR.

ATTY. EFREN C. MONCUPAUndersecretary for Project

Implementation and Special Concerns

850 850 850 1700

977

952

979

PWD

765

600

1500

600

3308

RAMP-UP

TOILET FLOOR PLAN

A A

B

B

33048304

TOILET FLOOR PLAN

9379

4308

FRONT ELEVATION

10104

1850

900

2750

2000

2734

360

1428

319

SEE TRUSS-1

G.I. SHEETS

FIREWALL

#26 CORRUGATED

W.C.

GUTTER

FASCIA

TOILET ELEVATION/SECTION "B-B"

TOILET SECTION "A-A"

1850

651

900

1850

900

2750

8891700

W.C.LAV.

1729

260317293166

LEFT ELEVATION RIGHT ELEVATION

5007

5007

3308 3308

900

6411157

600

600

2100

SCHEDULE OF DOORS AND WINDOWS ( CLASS-A)

LOCATION :

CARAGA REGION XIII BISLIG DISTRICT OFFICE

BISLIG CITY

AS SHOWN

LTO.13.CR.P5.N1.L1.1LTO.13.CR.P5.N1.L1.0

LTO.13.CR.P5.N1.L1.2

LTO.13.CR.P5.N1.L1.1

LTO.13.CR.P5.N1.L1.0LTO.13.CR.P5.N1.L1.2

Page 7: 6 CONCRETE HOLLOW BLOCKS...EFREN C. MONCUPA Undersecretary for Project Implementation and Special Concerns LOCATION : CARAGA REGION XIII TOILET FOUNDATION PLAN F1 - C1 F1 - C1 F1 -

DEPARTMENT OF TRANSPORTATIONAND COMMUNICATIONS

Republic of the Philippines

CONSTRUCTION OF TOILETFACILITIES

Prepared by :

Assistant Secretary for ProjectManagement

Planning Officer III

ENGR. MANUEL C. DEL CARMEN

Sheet Content:

Sheet No.:Sheet No.:

TSP --

--

PS

RA

F

NART

MT

OT

N E

O

O

CD

N

ATRA

NOIT

P

CIN

U

AE D SN OI T

MM

PROJECT NAME :

Submitted by:

Recommending Approval:

Approved:

Regional DirectorAtty ALIM D. PANGANDAMAN

ILDEFONSO T. PATDU, JR.

ATTY. EFREN C. MONCUPAUndersecretary for Project

Implementation and Special Concerns

TO SEPTIC TANK

F.D.

F.D.

C.O.

F.D.

TOILET SANITARY LAYOUT

10mmØ VERTICAL BARS SPACED@ 400mm ON CENTERS

10mmØ HORIZONTAL BARSPLACED EVERY 2 LAYERS OF CHB

11-10mmØ MATTING BARSSPACED EQUALLY AS SHOWN

1536

200

1536 307

DIGESTIVECHAMBER

LEACHINGCHAMBER

300

38

WATER LEVELWATER LEVEL

AIR SPACE AIR SPACE

500 500

92

6" THICK CHB

12mmØ MATTINGBARS SPACED @400mm ONCENTERS

3-10mm.Ø HORIZONTALTEMPERATURE BARS

MANHOLE MANHOLE

4" Ø PVC OUTLET

1500

500

MANHOLE MANHOLE

P1 40020001:20

DETAILED PLAN OF SEPTIC TANK5

P1 40020001:20

DETAILED SECTION OF SEPTIC TANK4

307

192

LEACHINGCHAMBER

38

WATER LEVEL

AIR SPACE300

10mmØ MATTINGBARS SPACED @400mm ONCENTERS

3-10mm.Ø HORIZONTALTEMPERATURE BARS

MANHOLE

4" Ø PVC OUTLET

MANHOLE

500

500

4000

2000 1000 1000

VENT STACK THRU ROOF

PLUMBING LEGEND:

VENT STACKVSVSTR

WM

GV

HB

FWATER METERHOSE BIBB

FAUCET

GATE VALVE

WC

CO

URFD

CLEAN-OUT

WATER CLOSET

FLOOR DRAINURINAL

LAV LAVATORY

CV CHECK VALVE

FCO FLOOR CLEAN-OUT

RD ROOF DRAINCB CATCH BASINDS DOWNSPOUTG.I.P. GALVANIZED IRON PIPE

SPECIFICATION :

LICENSED MASTER PLUMBER.8. ALL WORKS HEREIN SHALL BE DONE UNDER THE DIRECT SUPERVISION OF A DULY

DOUBLE CHECKED TO ENSURE WATER TIGHT PLUMBING SYSTEM.7. ALL WORKS HEREIN SHALL BE DONE OF CLASS A WORKMANSHIP, PIPING SYSTEM MUST BE

OF A TYPICAL APPROVED TANK.6. SEPTIC VAULT SHALL BE WATER TIGHT. COMPLETE WITH THE NECESSARY REQUIREMENTS

1/2" diameter PVC PIPES.5. MAIN WATER SUPPLY PIPES MUST BE 1" diameter AND BRANCH SUPPLY PIPES MUST BE4. ALL CLEAR WATER SUPPLY SYSTEM SHALL BE OF PVC PIPES, SCHEDULE 40, MOLDEX BLUE.3. USE SANIMOLD BY MOLDEX PRODUCTS FOR SANITARY WASTE SYSTEM.

2. ALL MATERIALS TO BE USED SHALL BE OF BRAND NEW AND OF APPROVED TYPE FORLOCATION AND PURPOSE.

PHILIPPINE PLUMBING CODE AND WITH THE LOCAL SANITARY AGENCY.1. ALL WORKS HEREIN SHALL BE DONE IN ACCORDANCE WITH THE PROVISION OF THE

LOCATION :

CARAGA REGION XIII BISLIG DISTRICT OFFICE

BISLIG CITY

AS SHOWN

LTO.13.CR.P5.N1.L1.1LTO.13.CR.P5.N1.L1.0

LTO.13.CR.P5.N1.L1.2

Page 8: 6 CONCRETE HOLLOW BLOCKS...EFREN C. MONCUPA Undersecretary for Project Implementation and Special Concerns LOCATION : CARAGA REGION XIII TOILET FOUNDATION PLAN F1 - C1 F1 - C1 F1 -

DEPARTMENT OF TRANSPORTATIONAND COMMUNICATIONS

Republic of the Philippines

CONSTRUCTION OF TOILETFACILITIES

Prepared by :

Assistant Secretary for ProjectManagement

Planning Officer III

ENGR. MANUEL C. DEL CARMEN

Sheet Content:

Sheet No.:Sheet No.:

TSE --

--

PS

RA

F

NART

MT

OT

N E

O

O

CD

N

ATRA

NOIT

P

CIN

U

AE D SN OI T

MM

PROJECT NAME :

Submitted by:

Recommending Approval:

Approved:

Regional DirectorAtty ALIM D. PANGANDAMAN

ILDEFONSO T. PATDU, JR.

ATTY. EFREN C. MONCUPAUndersecretary for Project

Implementation and Special Concerns

baSab

SS

S

LIGHTING LAYOUT PLAN ( CLASS-B)

POWER LAYOUT PLAN ( CLASS-B)

FROM ELECTRICALPOWER SOURCE

FROM ELECTRICALPOWER SOURCE

Legend & Symbols:

32 WATTS CIRCULAR FLUORESCENT LAMP

S SINGLE SWITCH

DUPLEX THREE PRONG-GROUNDED RECEPTACLE OUTLET

S3 TRIPLEX SWITCH

1x36 WATTS FLUORESCENT LAMP IN 0.30m. x 1.20m. FLUORESCENTFIXTURE, MIRRORIZED REFLECTOR AND LUOVER

CONDUIT RUN EMBEDDED ON WALLS & CEILING

1. All electrical works herein shall be done in accordance with the provisions of

the latest edition of the Philippine Electrical Code, existing rules and

ordinances of the Local Government, and with requirements of the Local

Power Company.

2. Type of power service shall be 230 volts, 2-wire, 60 hz., single phase, line

to ground.

3. All wirings shall be installed in standard PVC/RSC pipes inside a concrete

structure and inside ceiling spaces.

4. All materials to be used shall be brand new and of approved type.

5. Minimum size of wire and conduit to be used shall be 2.0 mm. sq. and 20

mm. dia. respectively.

6. Wherever required and necessary, pull boxes or junction boxes of proper

sizes shall be installed at convenient and inconspicuous locations, although

such boxes are not shown on the plan nor mentioned in the specifications.

7. The electrical works shall be done under the direct and immediate supervision

of a duly licensed electrical practitioner.

General notes:

LOCATION :

CARAGA REGION XIII BISLIG DISTRICT OFFICE

BISLIG CITY

AS SHOWN

LTO.13.CR.P5.N1.L1.1LTO.13.CR.P5.N1.L1.0

LTO.13.CR.P5.N1.L1.2

Page 9: 6 CONCRETE HOLLOW BLOCKS...EFREN C. MONCUPA Undersecretary for Project Implementation and Special Concerns LOCATION : CARAGA REGION XIII TOILET FOUNDATION PLAN F1 - C1 F1 - C1 F1 -

DEPARTMENT OF TRANSPORTATIONAND COMMUNICATIONS

Republic of the Philippines

CONSTRUCTION OF TOILETFACILITIES

Prepared by :

Assistant Secretary for ProjectManagement

Planning Officer III

ENGR. MANUEL C. DEL CARMEN

Sheet Content:

Sheet No.:Sheet No.:

TSS --

--

PS

RA

F

NART

MT

OT

N E

O

O

CD

N

ATRA

NOIT

P

CIN

U

AE D SN OI T

MM

PROJECT NAME :

Submitted by:

Recommending Approval:

Approved:

Regional DirectorAtty ALIM D. PANGANDAMAN

ILDEFONSO T. PATDU, JR.

ATTY. EFREN C. MONCUPAUndersecretary for Project

Implementation and Special Concerns

LOCATION :

CARAGA REGION XIII

TOILET FOUNDATION PLAN

F1 - C1 F1 - C1 F1 - C1

F1 - C1

F1 - C1

F1 - C1

WF

WF

WFWF

WF

WF

WF

WF

WF

LENGTH

LENGTH / 4 LENGTH / 4

TYPICAL DETAIL OF BEAM

10mm stirrups spaced @ 5-.05 m5-.10 m5-.15 mrest @ .20 m

12 mm horizontal bars

12161

600600

4154 51

54

1000

BUILDING LINEFIREWALL

2"X3" C-PURLINS 1.2 THICK

TRU

SS

TRU

SS

TRU

SS

TRU

SS

TRU

SS

TRU

SS

TRU

SS

FASCIA

FASC

IA

FASC

IA

TOILET ROOF FRAMING PLAN

10961

800

250

800

2504-12mmØ VERT. BARS W/ 10mmØLATERAL TIES SPACED; 3 @ 50mm,3@100mm, 3@ 150mm, REST @200mm

7-16mmØ MATTING BARS BOTHWAYSPLAN

300

800

N.G.L.

SECTION

4-12mmØ VERT. BARS W/ 10mmØLATERAL TIES SPACED; 3 @ 50mm,3@100mm, 3@ 150mm, REST @200mm

F1-C1

TRUSS DETAIL DIAGRAM

6" CONCRETEHOLLOW BLOCKS

PRE-PAINTED RIB TYPE ROOFING

2" X 4" C-PURLINS

2" X 6" CHANNEL BAR RAFTER

ORDINARY GUTTER

FASCIA BOARD

250

NAT. GRD. LINE

FIN. GRD. LINE

FIN. FLR. LINE

600

VERI

FY20

0

150mm THK. CHB WITH 10mmØ HOR.AND VERTICAL BARS @ 600mm O.C.

3-10mmØ LONG BARS

450

ELEVATION

TANDAG DISTRICT OFFICE TANDAG CITY

AS SHOWN

LTO.13.CR.P4.S1.L1.1LTO.13.CR.P4.S1.L1.0

LTO.13.CR.P4.S1.L1.2

Page 10: 6 CONCRETE HOLLOW BLOCKS...EFREN C. MONCUPA Undersecretary for Project Implementation and Special Concerns LOCATION : CARAGA REGION XIII TOILET FOUNDATION PLAN F1 - C1 F1 - C1 F1 -

DEPARTMENT OF TRANSPORTATIONAND COMMUNICATIONS

Republic of the Philippines

CONSTRUCTION OF TOILETFACILITIES

Prepared by :

Assistant Secretary for ProjectManagement

Planning Officer III

ENGR. MANUEL C. DEL CARMEN

Sheet Content:

Sheet No.:Sheet No.:

TSA --

--

PS

RA

F

NART

MT

OT

NE

O

O

CD

N

ATRA

NOIT

P

CIN

U

AE D SN OI T

MM

PROJECT NAME :

Submitted by:

Recommending Approval:

Approved:

Regional DirectorAtty ALIM D. PANGANDAMAN

ILDEFONSO T. PATDU, JR.

ATTY. EFREN C. MONCUPAUndersecretary for Project

Implementation and Special Concerns

850 850 850 1700

977

952

979

PWD

765

600

1500

600

3308

RAMP-UP

TOILET FLOOR PLAN

A A

B

B

33048304

TOILET FLOOR PLAN

9379

4308

FRONT ELEVATION

10104

1850

900

2750

2000

2734

360

1428

319

SEE TRUSS-1

G.I. SHEETS

FIREWALL

#26 CORRUGATED

W.C.

GUTTER

FASCIA

TOILET ELEVATION/SECTION "B-B"

TOILET SECTION "A-A"

1850

651

900

1850

900

2750

8891700

W.C.LAV.

1729

260317293166

LEFT ELEVATION RIGHT ELEVATION

5007

5007

3308 3308

900

6411157

600

600

2100

SCHEDULE OF DOORS AND WINDOWS ( CLASS-A)

LOCATION :

CARAGA REGION XIII TANDAG DISTRICT OFFICE

TANDAG CITY

AS SHOWN

LTO.13.CR.P4.S1.L1.1LTO.13.CR.P4.S1.L1.0

LTO.13.CR.P4.S1.L1.2

LTO.13.CR.P4.S1.L1.1

LTO.13.CR.P4.S1.L1.0LTO.13.CR.P4.S1.L1.2

Page 11: 6 CONCRETE HOLLOW BLOCKS...EFREN C. MONCUPA Undersecretary for Project Implementation and Special Concerns LOCATION : CARAGA REGION XIII TOILET FOUNDATION PLAN F1 - C1 F1 - C1 F1 -

DEPARTMENT OF TRANSPORTATIONAND COMMUNICATIONS

Republic of the Philippines

CONSTRUCTION OF TOILETFACILITIES

Prepared by :

Assistant Secretary for ProjectManagement

Planning Officer III

ENGR. MANUEL C. DEL CARMEN

Sheet Content:

Sheet No.:Sheet No.:

TSP --

--

PS

RA

F

NART

MT

OT

N E

O

O

CD

N

ATRA

NOIT

P

CIN

U

AE D SN OI T

MM

PROJECT NAME :

Submitted by:

Recommending Approval:

Approved:

Regional DirectorAtty ALIM D. PANGANDAMAN

ILDEFONSO T. PATDU, JR.

ATTY. EFREN C. MONCUPAUndersecretary for Project

Implementation and Special Concerns

TO SEPTIC TANK

F.D.

F.D.

C.O.

F.D.

TOILET SANITARY LAYOUT

10mmØ VERTICAL BARS SPACED@ 400mm ON CENTERS

10mmØ HORIZONTAL BARSPLACED EVERY 2 LAYERS OF CHB

11-10mmØ MATTING BARSSPACED EQUALLY AS SHOWN

1229

200

1229 246

DIGESTIVECHAMBER

LEACHINGCHAMBER

300

30

WATER LEVELWATER LEVEL

AIR SPACE AIR SPACE

500 50074

6" THICK CHB

12mmØ MATTINGBARS SPACED @400mm ONCENTERS

3-10mm.Ø HORIZONTALTEMPERATURE BARS

MANHOLE MANHOLE

4" Ø PVC OUTLET

1500

500

MANHOLE MANHOLE

P1 40020001:20

DETAILED PLAN OF SEPTIC TANK5

P1 40020001:20

DETAILED SECTION OF SEPTIC TANK4

246

154

LEACHINGCHAMBER

30

WATER LEVEL

AIR SPACE

300

10mmØ MATTINGBARS SPACED @400mm ONCENTERS

3-10mm.Ø HORIZONTALTEMPERATURE BARS

MANHOLE

4" Ø PVC OUTLET

MANHOLE

500

500

4000

2000 1000 1000

VENT STACK THRU ROOF

PLUMBING LEGEND:

VENT STACKVSVSTR

WM

GV

HB

FWATER METERHOSE BIBB

FAUCET

GATE VALVE

WC

CO

URFD

CLEAN-OUT

WATER CLOSET

FLOOR DRAINURINAL

LAV LAVATORY

CV CHECK VALVE

FCO FLOOR CLEAN-OUT

RD ROOF DRAINCB CATCH BASINDS DOWNSPOUTG.I.P. GALVANIZED IRON PIPE

SPECIFICATION :

LICENSED MASTER PLUMBER.8. ALL WORKS HEREIN SHALL BE DONE UNDER THE DIRECT SUPERVISION OF A DULY

DOUBLE CHECKED TO ENSURE WATER TIGHT PLUMBING SYSTEM.7. ALL WORKS HEREIN SHALL BE DONE OF CLASS A WORKMANSHIP, PIPING SYSTEM MUST BE

OF A TYPICAL APPROVED TANK.6. SEPTIC VAULT SHALL BE WATER TIGHT. COMPLETE WITH THE NECESSARY REQUIREMENTS

1/2" diameter PVC PIPES.5. MAIN WATER SUPPLY PIPES MUST BE 1" diameter AND BRANCH SUPPLY PIPES MUST BE4. ALL CLEAR WATER SUPPLY SYSTEM SHALL BE OF PVC PIPES, SCHEDULE 40, MOLDEX BLUE.3. USE SANIMOLD BY MOLDEX PRODUCTS FOR SANITARY WASTE SYSTEM.

2. ALL MATERIALS TO BE USED SHALL BE OF BRAND NEW AND OF APPROVED TYPE FORLOCATION AND PURPOSE.

PHILIPPINE PLUMBING CODE AND WITH THE LOCAL SANITARY AGENCY.1. ALL WORKS HEREIN SHALL BE DONE IN ACCORDANCE WITH THE PROVISION OF THE

LOCATION :

CARAGA REGION XIII TANDAG DISTRICT OFFICE

TANDAG CITY

AS SHOWN

LTO.13.CR.P4.S1.L1.1LTO.13.CR.P4.S1.L1.0

LTO.13.CR.P4.S1.L1.2

Page 12: 6 CONCRETE HOLLOW BLOCKS...EFREN C. MONCUPA Undersecretary for Project Implementation and Special Concerns LOCATION : CARAGA REGION XIII TOILET FOUNDATION PLAN F1 - C1 F1 - C1 F1 -

DEPARTMENT OF TRANSPORTATIONAND COMMUNICATIONS

Republic of the Philippines

CONSTRUCTION OF TOILETFACILITIES

Prepared by :

Assistant Secretary for ProjectManagement

Planning Officer III

ENGR. MANUEL C. DEL CARMEN

Sheet Content:

Sheet No.:Sheet No.:

TSA --

--

PS

RA

F

NART

MT

OT

N E

O

O

CD

N

ATRA

NOIT

P

CIN

U

AE D SN OI T

MM

PROJECT NAME :

Submitted by:

Recommending Approval:

Approved:

Regional DirectorAtty ALIM D. PANGANDAMAN

ILDEFONSO T. PATDU, JR.

ATTY. EFREN C. MONCUPAUndersecretary for Project

Implementation and Special Concerns

850 850 850 1700

977

952

979

PWD

765

600

1500

600

3308

RAMP-UP

TOILET FLOOR PLAN

A A

B

B

33048304

TOILET FLOOR PLAN

9379

4308

FRONT ELEVATION

10104

1850

900

2750

2000

2734

360

1428

319

SEE TRUSS-1

G.I. SHEETS

FIREWALL

#26 CORRUGATED

W.C.

GUTTER

FASCIA

TOILET ELEVATION/SECTION "B-B"

TOILET SECTION "A-A"

1850

651

900

1850

900

2750

8891700

W.C.LAV.

1729

260317293166

LEFT ELEVATION RIGHT ELEVATION

5007

5007

3308 3308

900

6411157

600

600

2100

SCHEDULE OF DOORS AND WINDOWS ( CLASS-A)

LOCATION : CARAGA REGION XIII

SURIGAO DISTRICT OFFICECAPITOL COMPOUND, SURIGAO CITY

AS SHOWN

LTO.13.CR.P3.E1.L1.1LTO.13.CR.P3.E1.L1.0

LTO.13.CR.P3.E1.L1.2

LTO.13.CR.P3.E1.L1.0

LTO.13.CR.P3.E1.L1.1

LTO.13.CR.P3.E1.L1.2

Page 13: 6 CONCRETE HOLLOW BLOCKS...EFREN C. MONCUPA Undersecretary for Project Implementation and Special Concerns LOCATION : CARAGA REGION XIII TOILET FOUNDATION PLAN F1 - C1 F1 - C1 F1 -

DEPARTMENT OF TRANSPORTATIONAND COMMUNICATIONS

Republic of the Philippines

CONSTRUCTION OF TOILETFACILITIES

Prepared by :

Assistant Secretary for ProjectManagement

Planning Officer III

ENGR. MANUEL C. DEL CARMEN

Sheet Content:

Sheet No.:Sheet No.:

TSE --

--

PS

RA

F

NART

MT

OT

N E

O

O

CD

N

ATRA

NOIT

P

CIN

U

AE D SN OI T

MM

PROJECT NAME :

Submitted by:

Recommending Approval:

Approved:

Regional DirectorAtty ALIM D. PANGANDAMAN

ILDEFONSO T. PATDU, JR.

ATTY. EFREN C. MONCUPAUndersecretary for Project

Implementation and Special Concerns

baSab

SS

S

LIGHTING LAYOUT PLAN

POWER LAYOUT PLAN

FROM ELECTRICALPOWER SOURCE

FROM ELECTRICALPOWER SOURCE

Legend & Symbols:

32 WATTS CIRCULAR FLUORESCENT LAMP

S SINGLE SWITCH

DUPLEX THREE PRONG-GROUNDED RECEPTACLE OUTLET

S3 TRIPLEX SWITCH

1x36 WATTS FLUORESCENT LAMP IN 0.30m. x 1.20m. FLUORESCENTFIXTURE, MIRRORIZED REFLECTOR AND LUOVER

CONDUIT RUN EMBEDDED ON WALLS & CEILING

1. All electrical works herein shall be done in accordance with the provisions of

the latest edition of the Philippine Electrical Code, existing rules and

ordinances of the Local Government, and with requirements of the Local

Power Company.

2. Type of power service shall be 230 volts, 2-wire, 60 hz., single phase, line

to ground.

3. All wirings shall be installed in standard PVC/RSC pipes inside a concrete

structure and inside ceiling spaces.

4. All materials to be used shall be brand new and of approved type.

5. Minimum size of wire and conduit to be used shall be 2.0 mm. sq. and 20

mm. dia. respectively.

6. Wherever required and necessary, pull boxes or junction boxes of proper

sizes shall be installed at convenient and inconspicuous locations, although

such boxes are not shown on the plan nor mentioned in the specifications.

7. The electrical works shall be done under the direct and immediate supervision

of a duly licensed electrical practitioner.

General notes:

LOCATION :

CARAGA REGION XIII TANDAG DISTRICT OFFICE

TANDAG CITY

AS SHOWN

LTO.13.CR.P4.S1.L1.1LTO.13.CR.P4.S1.L1.0

LTO.13.CR.P4.S1.L1.2

Page 14: 6 CONCRETE HOLLOW BLOCKS...EFREN C. MONCUPA Undersecretary for Project Implementation and Special Concerns LOCATION : CARAGA REGION XIII TOILET FOUNDATION PLAN F1 - C1 F1 - C1 F1 -

DEPARTMENT OF TRANSPORTATIONAND COMMUNICATIONS

Republic of the Philippines

CONSTRUCTION OF TOILETFACILITIES

Prepared by :

Assistant Secretary for ProjectManagement

Planning Officer III

ENGR. MANUEL C. DEL CARMEN

Sheet Content:

Sheet No.:Sheet No.:

TSP --

--

PS

RA

F

NART

MT

OT

NE

O

O

CD

N

ATRA

NOIT

P

CIN

U

AE D SN OI T

MM

PROJECT NAME :

Submitted by:

Recommending Approval:

Approved:

Regional DirectorAtty ALIM D. PANGANDAMAN

ILDEFONSO T. PATDU, JR.

ATTY. EFREN C. MONCUPAUndersecretary for Project

Implementation and Special Concerns

TO SEPTIC TANK

F.D.

F.D.

C.O.

F.D.

TOILET SANITARY LAYOUT

10mmØ VERTICAL BARS SPACED@ 400mm ON CENTERS

10mmØ HORIZONTAL BARSPLACED EVERY 2 LAYERS OF CHB

11-10mmØ MATTING BARSSPACED EQUALLY AS SHOWN

1024

200

1024 205

DIGESTIVECHAMBER

LEACHINGCHAMBER

300

25

WATER LEVELWATER LEVEL

AIR SPACE AIR SPACE

500 50061

6" THICK CHB

12mmØ MATTINGBARS SPACED @400mm ONCENTERS

3-10mm.Ø HORIZONTALTEMPERATURE BARS

MANHOLE MANHOLE

4" Ø PVC OUTLET

1500

500

MANHOLE MANHOLE

P1 40020001:20

DETAILED PLAN OF SEPTIC TANK5

P1 40020001:20

DETAILED SECTION OF SEPTIC TANK4

205

128

LEACHINGCHAMBER

25

WATER LEVEL

AIR SPACE

300

10mmØ MATTINGBARS SPACED @400mm ONCENTERS

3-10mm.Ø HORIZONTALTEMPERATURE BARS

MANHOLE

4" Ø PVC OUTLET

MANHOLE

500

500

40002000 1000 1000

VENT STACK THRU ROOF

PLUMBING LEGEND:

VENT STACKVSVSTR

WM

GV

HB

FWATER METERHOSE BIBB

FAUCET

GATE VALVE

WC

CO

URFD

CLEAN-OUT

WATER CLOSET

FLOOR DRAINURINAL

LAV LAVATORY

CV CHECK VALVE

FCO FLOOR CLEAN-OUT

RD ROOF DRAINCB CATCH BASINDS DOWNSPOUTG.I.P. GALVANIZED IRON PIPE

SPECIFICATION :

LICENSED MASTER PLUMBER.8. ALL WORKS HEREIN SHALL BE DONE UNDER THE DIRECT SUPERVISION OF A DULY

DOUBLE CHECKED TO ENSURE WATER TIGHT PLUMBING SYSTEM.7. ALL WORKS HEREIN SHALL BE DONE OF CLASS A WORKMANSHIP, PIPING SYSTEM MUST BE

OF A TYPICAL APPROVED TANK.6. SEPTIC VAULT SHALL BE WATER TIGHT. COMPLETE WITH THE NECESSARY REQUIREMENTS

1/2" diameter PVC PIPES.5. MAIN WATER SUPPLY PIPES MUST BE 1" diameter AND BRANCH SUPPLY PIPES MUST BE4. ALL CLEAR WATER SUPPLY SYSTEM SHALL BE OF PVC PIPES, SCHEDULE 40, MOLDEX BLUE.3. USE SANIMOLD BY MOLDEX PRODUCTS FOR SANITARY WASTE SYSTEM.

2. ALL MATERIALS TO BE USED SHALL BE OF BRAND NEW AND OF APPROVED TYPE FORLOCATION AND PURPOSE.

PHILIPPINE PLUMBING CODE AND WITH THE LOCAL SANITARY AGENCY.1. ALL WORKS HEREIN SHALL BE DONE IN ACCORDANCE WITH THE PROVISION OF THE

LOCATION :

CARAGA REGION XIII SURIGAO DISTRICT OFFICECAPITOL COMPOUND, SURIGAO CITY

AS SHOWN

LTO.13.CR.P3.E1.L1.1LTO.13.CR.P3.E1.L1.0

LTO.13.CR.P3.E1.L1.2

Page 15: 6 CONCRETE HOLLOW BLOCKS...EFREN C. MONCUPA Undersecretary for Project Implementation and Special Concerns LOCATION : CARAGA REGION XIII TOILET FOUNDATION PLAN F1 - C1 F1 - C1 F1 -

DEPARTMENT OF TRANSPORTATIONAND COMMUNICATIONS

Republic of the Philippines

CONSTRUCTION OF TOILETFACILITIES

Prepared by :

Assistant Secretary for ProjectManagement

Planning Officer III

ENGR. MANUEL C. DEL CARMEN

Sheet Content:

Sheet No.:Sheet No.:

TSE --

--

PS

RA

F

NART

MT

OT

N E

O

O

CD

N

ATRA

NOIT

P

CIN

U

AE D SN OI T

MM

PROJECT NAME :

Submitted by:

Recommending Approval:

Approved:

Regional DirectorAtty ALIM D. PANGANDAMAN

ILDEFONSO T. PATDU, JR.

ATTY. EFREN C. MONCUPAUndersecretary for Project

Implementation and Special Concerns

baSab

SS

S

LIGHTING LAYOUT PLAN ( CLASS-B)

POWER LAYOUT PLAN ( CLASS-B)

FROM ELECTRICALPOWER SOURCE

FROM ELECTRICALPOWER SOURCE

Legend & Symbols:

32 WATTS CIRCULAR FLUORESCENT LAMP

S SINGLE SWITCH

DUPLEX THREE PRONG-GROUNDED RECEPTACLE OUTLET

S3 TRIPLEX SWITCH

1x36 WATTS FLUORESCENT LAMP IN 0.30m. x 1.20m. FLUORESCENTFIXTURE, MIRRORIZED REFLECTOR AND LUOVER

CONDUIT RUN EMBEDDED ON WALLS & CEILING

1. All electrical works herein shall be done in accordance with the provisions of

the latest edition of the Philippine Electrical Code, existing rules and

ordinances of the Local Government, and with requirements of the Local

Power Company.

2. Type of power service shall be 230 volts, 2-wire, 60 hz., single phase, line

to ground.

3. All wirings shall be installed in standard PVC/RSC pipes inside a concrete

structure and inside ceiling spaces.

4. All materials to be used shall be brand new and of approved type.

5. Minimum size of wire and conduit to be used shall be 2.0 mm. sq. and 20

mm. dia. respectively.

6. Wherever required and necessary, pull boxes or junction boxes of proper

sizes shall be installed at convenient and inconspicuous locations, although

such boxes are not shown on the plan nor mentioned in the specifications.

7. The electrical works shall be done under the direct and immediate supervision

of a duly licensed electrical practitioner.

General notes:

LOCATION :

CARAGA REGION XIII SURIGAO DISTRICT OFFICECAPITOL COMPOUND, SURIGAO CITY

AS SHOWN

LTO.13.CR.P3.E1.L1.1LTO.13.CR.P3.E1.L1.0

LTO.13.CR.P3.E1.L1.2

Page 16: 6 CONCRETE HOLLOW BLOCKS...EFREN C. MONCUPA Undersecretary for Project Implementation and Special Concerns LOCATION : CARAGA REGION XIII TOILET FOUNDATION PLAN F1 - C1 F1 - C1 F1 -

DEPARTMENT OF TRANSPORTATIONAND COMMUNICATIONS

Republic of the Philippines

CONSTRUCTION OF TOILETFACILITIES

Prepared by :

Assistant Secretary for ProjectManagement

Planning Officer III

ENGR. MANUEL C. DEL CARMEN

Sheet Content:

Sheet No.:Sheet No.:

TSS --

--

PS

RA

F

NART

MT

OT

N E

O

O

CD

N

ATRA

NOIT

P

CIN

U

AE D SN OI T

MM

PROJECT NAME :

Submitted by:

Recommending Approval:

Approved:

Regional DirectorAtty ALIM D. PANGANDAMAN

ILDEFONSO T. PATDU, JR.

ATTY. EFREN C. MONCUPAUndersecretary for Project

Implementation and Special Concerns

LOCATION :

CARAGA REGION XIII

TOILET FOUNDATION PLAN

F1 - C1 F1 - C1 F1 - C1

F1 - C1

F1 - C1

F1 - C1

WF

WF

WFWF

WF

WF

WF

WF

WF

LENGTH

LENGTH / 4 LENGTH / 4

TYPICAL DETAIL OF BEAM

10mm stirrups spaced @ 5-.05 m5-.10 m5-.15 mrest @ .20 m

12 mm horizontal bars

12161

600600

4154 51

54

1000

BUILDING LINEFIREWALL

2"X3" C-PURLINS 1.2 THICK

TRU

SS

TRU

SS

TRU

SS

TRU

SS

TRU

SS

TRU

SS

TRU

SS

FASCIA

FASC

IA

FASC

IA

TOILET ROOF FRAMING PLAN

10961

800

250

800

2504-12mmØ VERT. BARS W/ 10mmØLATERAL TIES SPACED; 3 @ 50mm,3@100mm, 3@ 150mm, REST @200mm

7-16mmØ MATTING BARS BOTHWAYSPLAN

300

800

N.G.L.

SECTION

4-12mmØ VERT. BARS W/ 10mmØLATERAL TIES SPACED; 3 @ 50mm,3@100mm, 3@ 150mm, REST @200mm

F1-C1

TRUSS DETAIL DIAGRAM

6" CONCRETEHOLLOW BLOCKS

PRE-PAINTED RIB TYPE ROOFING

2" X 4" C-PURLINS

2" X 6" CHANNEL BAR RAFTER

ORDINARY GUTTER

FASCIA BOARD

250

NAT. GRD. LINE

FIN. GRD. LINE

FIN. FLR. LINE

600

VERI

FY20

0

150mm THK. CHB WITH 10mmØ HOR.AND VERTICAL BARS @ 600mm O.C.

3-10mmØ LONG BARS

450

ELEVATION

BUTUAN DISTRICT OFFICE CAPITOL AVE, BUTUAN CITY

AS SHOWN

LTO.13.CR.P1.N1.L1.1LTO.13.CR.P1.N1.L1.0

LTO.13.CR.P1.N1.L1.2

Page 17: 6 CONCRETE HOLLOW BLOCKS...EFREN C. MONCUPA Undersecretary for Project Implementation and Special Concerns LOCATION : CARAGA REGION XIII TOILET FOUNDATION PLAN F1 - C1 F1 - C1 F1 -

DEPARTMENT OF TRANSPORTATIONAND COMMUNICATIONS

Republic of the Philippines

CONSTRUCTION OF TOILETFACILITIES

Prepared by :

Assistant Secretary for ProjectManagement

Planning Officer III

ENGR. MANUEL C. DEL CARMEN

Sheet Content:

Sheet No.:Sheet No.:

TSA --

--

PS

RA

F

NART

MT

OT

N E

O

O

CD

N

ATRA

NOIT

P

CIN

U

AE D SN OI T

MM

PROJECT NAME :

Submitted by:

Recommending Approval:

Approved:

Regional DirectorAtty ALIM D. PANGANDAMAN

ILDEFONSO T. PATDU, JR.

ATTY. EFREN C. MONCUPAUndersecretary for Project

Implementation and Special Concerns

850 850 850 1700

977

952

979

PWD

765

600

1500

600

3308

RAMP-UP

TOILET FLOOR PLAN

A A

B

B

33048304

TOILET FLOOR PLAN

9379

4308

FRONT ELEVATION

10104

1850

900

2750

2000

2734

360

1428

319

SEE TRUSS-1

G.I. SHEETS

FIREWALL

#26 CORRUGATED

W.C.

GUTTER

FASCIA

TOILET ELEVATION/SECTION "B-B"

TOILET SECTION "A-A"

1850

651

900

1850

900

2750

8891700

W.C.LAV.

1729

260317293166

LEFT ELEVATION RIGHT ELEVATION

5007

5007

3308 3308

900

6411157

600

600

2100

SCHEDULE OF DOORS AND WINDOWS ( CLASS-A)

LOCATION :

CARAGA REGION XIII BUTUAN DISTRICT OFFICE CAPITOL AVE, BUTUAN CITY

AS SHOWN

LTO.13.CR.P1.N1.L1.1LTO.13.CR.P1.N1.L1.0

LTO.13.CR.P1.N1.L1.2

LTO.13.CR.P1.N1.L1.1

LTO.13.CR.P1.N1.L1.0LTO.13.CR.P1.N1.L1.2

Page 18: 6 CONCRETE HOLLOW BLOCKS...EFREN C. MONCUPA Undersecretary for Project Implementation and Special Concerns LOCATION : CARAGA REGION XIII TOILET FOUNDATION PLAN F1 - C1 F1 - C1 F1 -

DEPARTMENT OF TRANSPORTATIONAND COMMUNICATIONS

Republic of the Philippines

CONSTRUCTION OF TOILETFACILITIES

Prepared by :

Assistant Secretary for ProjectManagement

Planning Officer III

ENGR. MANUEL C. DEL CARMEN

Sheet Content:

Sheet No.:Sheet No.:

TSP --

--

PS

RA

F

NART

MT

OT

N E

O

O

CD

N

ATRA

NOIT

P

CIN

U

AE D SN OI T

MM

PROJECT NAME :

Submitted by:

Recommending Approval:

Approved:

Regional DirectorAtty ALIM D. PANGANDAMAN

ILDEFONSO T. PATDU, JR.

ATTY. EFREN C. MONCUPAUndersecretary for Project

Implementation and Special Concerns

TO SEPTIC TANK

F.D.

F.D.

C.O.

F.D.

TOILET SANITARY LAYOUT

10mmØ VERTICAL BARS SPACED@ 400mm ON CENTERS

10mmØ HORIZONTAL BARSPLACED EVERY 2 LAYERS OF CHB

11-10mmØ MATTING BARSSPACED EQUALLY AS SHOWN

1536

200

1536 307

DIGESTIVECHAMBER

LEACHINGCHAMBER

300

38

WATER LEVELWATER LEVEL

AIR SPACE AIR SPACE

500 500

92

6" THICK CHB

12mmØ MATTINGBARS SPACED @400mm ONCENTERS

3-10mm.Ø HORIZONTALTEMPERATURE BARS

MANHOLE MANHOLE

4" Ø PVC OUTLET

1500

500

MANHOLE MANHOLE

P1 40020001:20

DETAILED PLAN OF SEPTIC TANK5

P1 40020001:20

DETAILED SECTION OF SEPTIC TANK4

307

192

LEACHINGCHAMBER

38

WATER LEVEL

AIR SPACE300

10mmØ MATTINGBARS SPACED @400mm ONCENTERS

3-10mm.Ø HORIZONTALTEMPERATURE BARS

MANHOLE

4" Ø PVC OUTLET

MANHOLE

500

500

4000

2000 1000 1000

VENT STACK THRU ROOF

PLUMBING LEGEND:

VENT STACKVSVSTR

WM

GV

HB

FWATER METERHOSE BIBB

FAUCET

GATE VALVE

WC

CO

URFD

CLEAN-OUT

WATER CLOSET

FLOOR DRAINURINAL

LAV LAVATORY

CV CHECK VALVE

FCO FLOOR CLEAN-OUT

RD ROOF DRAINCB CATCH BASINDS DOWNSPOUTG.I.P. GALVANIZED IRON PIPE

SPECIFICATION :

LICENSED MASTER PLUMBER.8. ALL WORKS HEREIN SHALL BE DONE UNDER THE DIRECT SUPERVISION OF A DULY

DOUBLE CHECKED TO ENSURE WATER TIGHT PLUMBING SYSTEM.7. ALL WORKS HEREIN SHALL BE DONE OF CLASS A WORKMANSHIP, PIPING SYSTEM MUST BE

OF A TYPICAL APPROVED TANK.6. SEPTIC VAULT SHALL BE WATER TIGHT. COMPLETE WITH THE NECESSARY REQUIREMENTS

1/2" diameter PVC PIPES.5. MAIN WATER SUPPLY PIPES MUST BE 1" diameter AND BRANCH SUPPLY PIPES MUST BE4. ALL CLEAR WATER SUPPLY SYSTEM SHALL BE OF PVC PIPES, SCHEDULE 40, MOLDEX BLUE.3. USE SANIMOLD BY MOLDEX PRODUCTS FOR SANITARY WASTE SYSTEM.

2. ALL MATERIALS TO BE USED SHALL BE OF BRAND NEW AND OF APPROVED TYPE FORLOCATION AND PURPOSE.

PHILIPPINE PLUMBING CODE AND WITH THE LOCAL SANITARY AGENCY.1. ALL WORKS HEREIN SHALL BE DONE IN ACCORDANCE WITH THE PROVISION OF THE

LOCATION :

CARAGA REGION XIII BUTUAN DISTRICT OFFICE CAPITOL AVE, BUTUAN CITY

AS SHOWN

LTO.13.CR.P1.N1.L1.1LTO.13.CR.P1.N1.L1.0

LTO.13.CR.P1.N1.L1.2

Page 19: 6 CONCRETE HOLLOW BLOCKS...EFREN C. MONCUPA Undersecretary for Project Implementation and Special Concerns LOCATION : CARAGA REGION XIII TOILET FOUNDATION PLAN F1 - C1 F1 - C1 F1 -

DEPARTMENT OF TRANSPORTATIONAND COMMUNICATIONS

Republic of the Philippines

CONSTRUCTION OF TOILETFACILITIES

Prepared by :

Assistant Secretary for ProjectManagement

Planning Officer III

ENGR. MANUEL C. DEL CARMEN

Sheet Content:

Sheet No.:Sheet No.:

TSE --

--

PS

RA

F

NART

MT

OT

NE

O

O

CD

N

ATRA

NOIT

P

CIN

U

AE D SN OI T

MM

PROJECT NAME :

Submitted by:

Recommending Approval:

Approved:

Regional DirectorAtty ALIM D. PANGANDAMAN

ILDEFONSO T. PATDU, JR.

ATTY. EFREN C. MONCUPAUndersecretary for Project

Implementation and Special Concerns

baSab

SS

S

LIGHTING LAYOUT PLAN ( CLASS-B)

POWER LAYOUT PLAN ( CLASS-B)

FROM ELECTRICALPOWER SOURCE

FROM ELECTRICALPOWER SOURCE

Legend & Symbols:

32 WATTS CIRCULAR FLUORESCENT LAMP

S SINGLE SWITCH

DUPLEX THREE PRONG-GROUNDED RECEPTACLE OUTLET

S3 TRIPLEX SWITCH

1x36 WATTS FLUORESCENT LAMP IN 0.30m. x 1.20m. FLUORESCENTFIXTURE, MIRRORIZED REFLECTOR AND LUOVER

CONDUIT RUN EMBEDDED ON WALLS & CEILING

1. All electrical works herein shall be done in accordance with the provisions of

the latest edition of the Philippine Electrical Code, existing rules and

ordinances of the Local Government, and with requirements of the Local

Power Company.

2. Type of power service shall be 230 volts, 2-wire, 60 hz., single phase, line

to ground.

3. All wirings shall be installed in standard PVC/RSC pipes inside a concrete

structure and inside ceiling spaces.

4. All materials to be used shall be brand new and of approved type.

5. Minimum size of wire and conduit to be used shall be 2.0 mm. sq. and 20

mm. dia. respectively.

6. Wherever required and necessary, pull boxes or junction boxes of proper

sizes shall be installed at convenient and inconspicuous locations, although

such boxes are not shown on the plan nor mentioned in the specifications.

7. The electrical works shall be done under the direct and immediate supervision

of a duly licensed electrical practitioner.

General notes:

LOCATION :

CARAGA REGION XIII BUTUAN DISTRICT OFFICE CAPITOL AVE, BUTUAN CITY

AS SHOWN

LTO.13.CR.P1.N1.L1.1LTO.13.CR.P1.N1.L1.0

LTO.13.CR.P1.N1.L1.2

Page 20: 6 CONCRETE HOLLOW BLOCKS...EFREN C. MONCUPA Undersecretary for Project Implementation and Special Concerns LOCATION : CARAGA REGION XIII TOILET FOUNDATION PLAN F1 - C1 F1 - C1 F1 -

DEPARTMENT OF TRANSPORTATIONAND COMMUNICATIONS

Republic of the Philippines

CONSTRUCTION OF TOILETFACILITIES

Prepared by :

Assistant Secretary for ProjectManagement

Planning Officer III

ENGR. MANUEL C. DEL CARMEN

Sheet Content:

Sheet No.:Sheet No.:

TSS --

--

PS

RA

F

NART

MT

OT

N E

O

O

CD

N

ATRA

NOIT

P

CIN

U

AE D SN OI T

MM

PROJECT NAME :

Submitted by:

Recommending Approval:

Approved:

Regional DirectorAtty ALIM D. PANGANDAMAN

ILDEFONSO T. PATDU, JR.

ATTY. EFREN C. MONCUPAUndersecretary for Project

Implementation and Special Concerns

LOCATION :

CARAGA REGION XIII

TOILET FOUNDATION PLAN

F1 - C1 F1 - C1 F1 - C1

F1 - C1

F1 - C1

F1 - C1

WF

WF

WFWF

WF

WF

WF

WF

WF

LENGTH

LENGTH / 4 LENGTH / 4

TYPICAL DETAIL OF BEAM

10mm stirrups spaced @ 5-.05 m5-.10 m5-.15 mrest @ .20 m

12 mm horizontal bars

12161

600600

4154 51

54

1000

BUILDING LINEFIREWALL

2"X3" C-PURLINS 1.2 THICK

TRU

SS

TRU

SS

TRU

SS

TRU

SS

TRU

SS

TRU

SS

TRU

SS

FASCIA

FASC

IA

FASC

IA

TOILET ROOF FRAMING PLAN

10961

800

250

800

2504-12mmØ VERT. BARS W/ 10mmØLATERAL TIES SPACED; 3 @ 50mm,3@100mm, 3@ 150mm, REST @200mm

7-16mmØ MATTING BARS BOTHWAYSPLAN

300

800

N.G.L.

SECTION

4-12mmØ VERT. BARS W/ 10mmØLATERAL TIES SPACED; 3 @ 50mm,3@100mm, 3@ 150mm, REST @200mm

F1-C1

TRUSS DETAIL DIAGRAM

6" CONCRETEHOLLOW BLOCKS

PRE-PAINTED RIB TYPE ROOFING

2" X 4" C-PURLINS

2" X 6" CHANNEL BAR RAFTER

ORDINARY GUTTER

FASCIA BOARD

250

NAT. GRD. LINE

FIN. GRD. LINE

FIN. FLR. LINE

600

VERI

FY20

0

150mm THK. CHB WITH 10mmØ HOR.AND VERTICAL BARS @ 600mm O.C.

3-10mmØ LONG BARS

450

ELEVATION

PATIN-AY DISTRICT OFFICE PROSPERIDAD, AGUSAN DEL SUR

AS SHOWN

LTO.13.CR.P2.S1.L1.1LTO.13.CR.P2.S1.L1.0

LTO.13.CR.P2.S1.L1.2