    Defrost Operation

    5ACV030CR

    Defrost will start if the following conditions are met for 3 minutes:-

    a. Continuous compressor operation in heating mode for at least thedefrosting interval duration (D4 setting factory default 45mins)b. Inv outdoor coil outlet temperature < 0C (D1 setting) orc. Entering water temperature > 18C

    Defrost process

    Defrost terminateWhen either of the below conditions is met, the defrost operation will beterminated:-

    a. Inv outdoor coil outlet temperature > 14Cb. Defrost time exceed 10 mins.

    ON

    ON

    Variable drivefre uenc

    Variable

    speedfan

    4-way valve(Variabledrive

    70Hz

    End Resumeheating mode

    30Hz 30Hz

    Start

  • 7/26/2019 5ACV - Defrost Operation

    2/4

    5ACV055CR & 5ACV075CR

    Defrost will start if the following conditions are met for 3 minutes:-a. Continuous compressor operation in heating mode for at least the

    defrosting interval duration (D4 setting factory default 45mins)

    b. Inv outdoor coil outlet temperature < 0C (D1 setting) orc. Entering water temperature > 18C

    Defrost process

    Defrost terminateWhen either of the below conditions is met, the defrost operation will beterminated:-

    a. Inv outdoor coil outlet temperature > 14Cb. Defrost time exceed 10 mins.c. Entering water temperature < 10C

    ON

    ON

    Variable drivefrequency

    Variablespeedfan

    4-way valve(Variabledrive

    90Hz

    End Resumeheating mode

    30Hz 30Hz

    Start

  • 7/26/2019 5ACV - Defrost Operation

    3/4

    Variable drivecom ressor

    Starts defrosting

    Variable

    speedfan

    ON

    ON

    ON

    4-way valve(Variabledrive

    2 seconds

    10 seconds15 seconds30 seconds2 seconds

    Targeted frequency 70Hz

    2 seconds

    Ends defrosting Starts heatingmode

    High fan

    Fixed drivecompressor

    Starts defrosting

    Fixedspeedfan

    ON

    ON

    ON

    4-wayvalve(Fixeddrive)

    2 seconds

    10 seconds15 seconds30 seconds2 seconds

    2 seconds

    Ends defrosting Starts heating

    mode

    High fan

    5ACV100CR & 5ACV135CR

    Defrost will start if the following conditions are met for 3 minutes:-a. Continuous compressor operation in heating mode for at least the

    defrosting interval duration (D4 setting factory default 45mins)

    b. Inv and fixed drive outdoor coil outlet temperature < -8C (D1 setting) orc. Entering water temperature > 23C ord. Differential of ambient and coil temperature > 4C

    Defrost processInverter drive

    Fixed drive

    Defrost terminateWhen either of the below conditions is met, the defrost operation will beterminated:-

    a. Inv or fixed drive outdoor coil outlet temperature > 14Cb. Defrost time exceed 10 mins.c. Entering water temperature < 12C

  • 7/26/2019 5ACV - Defrost Operation

    4/4

    ON

    ON

    Variable compfre uenc

    System 1soutdoor fan

    System 1s 4-way valve

    90Hz

    EndResumeheating mode

    Start

    System 1sfixed comp

    ON

    Fixed drivecom ressor

    Start

    Fixedspeedfan

    ON

    ON

    ON

    4-wayvalve(Fixeddrive)

    60s

    EndResumeheatin mode

    60s

    5ACV210CR

    Defrost will start if the following conditions are met for 3 minutes:-a. Continuous compressor operation in heating mode for at least the

    defrosting interval duration (D4 setting factory default 45mins)

    b. Inv and fixed drive outdoor coil outlet temperature < -8C (D1 setting) orc. Entering water temperature > 18C

    Defrost processSystem 1 (with Inverter Compressor)

    System 2

    Defrost terminateWhen either of the below conditions is met, the defrost operation will beterminated:-

    a. Inv or fixed drive outdoor coil outlet temperature > 14Cb. Defrost time exceed 10 mins.c. Entering water temperature < 10C

    30Hz 30Hz