IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV Sponsored by the Insulated Conductors Committee IEEE 3 Park Avenue New York, NY 10016-5997 USA IEEE Power and Energy Society IEEE Std 575™-2014 (Revision of IEEE Std 575-1988) Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

  • Upload
    aryoel06

  • View
    3.023

  • Download
    1.379

Embed Size (px)

DESCRIPTION

575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

Citation preview

Page 1: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

Sponsored by the Insulated Conductors Committee

IEEE 3 Park Avenue New York, NY 10016-5997 USA

IEEE Power and Energy Society

IEEE Std 575™-2014 (Revision of

IEEE Std 575-1988)

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 2: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 3: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575™-2014 (Revision of

IEEE Std 575-1988)

IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

Sponsor Insulated Conductors Committee of the IEEE Power and Energy Society Approved 12 June 2014 IEEE-SA Standards Board

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 4: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

Abstract: The most common shield/sheath-bonding systems now in use on medium through extra high-voltage (5 kV to 500 kV) single-conductor shielded power cables and the methods of calculating the corresponding shield/sheath voltages and currents, when the cables are operated as part of a three-phase system, with the neutral grounded directly or through an impedance, are described in this guide.

Keywords: bonding, cross bonding, distribution cable, grounding, high-voltage cable, IEEE 575™, medium-voltage cable, power cable, sheath, sheath bonding, sheath voltage limiters, shield, shield bonding, shield voltage limiters, single-point bonding, special bonding, SVL, transmission cable •

The Institute of Electrical and Electronics Engineers, Inc. 3 Park Avenue, New York, NY 10016-5997, USA Copyright © 2014 by The Institute of Electrical and Electronics Engineers, Inc. All rights reserved. Published 18 September 2014. Printed in the United States of America. IEEE, National Electrical Safety Code, and NESC are registered trademarks in the U.S. Patent & Trademark Office, owned by The Institute of Electrical and Electronics Engineers, Incorporated. PDF: ISBN 978-0-7381-9228-4 STD98728 Print: ISBN 978-0-7381-9229-1 STDPD98728 IEEE prohibits discrimination, harassment, and bullying. For more information, visit http://www.ieee.org/web/aboutus/whatis/policies/p9-26.html. No part of this publication may be reproduced in any form, in an electronic retrieval system or otherwise, without the prior written permission of the publisher.

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 5: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

Important Notices and Disclaimers Concerning IEEE Standards Documents

IEEE documents are made available for use subject to important notices and legal disclaimers. These notices and disclaimers, or a reference to this page, appear in all standards and may be found under the heading “Important Notice” or “Important Notices and Disclaimers Concerning IEEE Standards Documents.”

Notice and Disclaimer of Liability Concerning the Use of IEEE Standards Documents

IEEE Standards documents (standards, recommended practices, and guides), both full-use and trial-use, are developed within IEEE Societies and the Standards Coordinating Committees of the IEEE Standards Association (“IEEE-SA”) Standards Board. IEEE (“the Institute”) develops its standards through a consensus development process, approved by the American National Standards Institute (“ANSI”), which brings together volunteers representing varied viewpoints and interests to achieve the final product. Volunteers are not necessarily members of the Institute and participate without compensation from IEEE. While IEEE administers the process and establishes rules to promote fairness in the consensus development process, IEEE does not independently evaluate, test, or verify the accuracy of any of the information or the soundness of any judgments contained in its standards.

IEEE does not warrant or represent the accuracy or content of the material contained in its standards, and expressly disclaims all warranties (express, implied and statutory) not included in this or any other document relating to the standard, including, but not limited to, the warranties of: merchantability; fitness for a particular purpose; non-infringement; and quality, accuracy, effectiveness, currency, or completeness of material. In addition, IEEE disclaims any and all conditions relating to: results; and workmanlike effort. IEEE standards documents are supplied “AS IS” and “WITH ALL FAULTS.” Use of an IEEE standard is wholly voluntary. The existence of an IEEE standard does not imply that there are no other ways to produce, test, measure, purchase, market, or provide other goods and services related to the scope of the IEEE standard. Furthermore, the viewpoint expressed at the time a standard is approved and issued is subject to change brought about through developments in the state of the art and comments received from users of the standard.

In publishing and making its standards available, IEEE is not suggesting or rendering professional or other services for, or on behalf of, any person or entity nor is IEEE undertaking to perform any duty owed by any other person or entity to another. Any person utilizing any IEEE Standards document, should rely upon his or her own independent judgment in the exercise of reasonable care in any given circumstances or, as appropriate, seek the advice of a competent professional in determining the appropriateness of a given IEEE standard.

IN NO EVENT SHALL IEEE BE LIABLE FOR ANY DIRECT, INDIRECT, INCIDENTAL, SPECIAL, EXEMPLARY, OR CONSEQUENTIAL DAMAGES (INCLUDING, BUT NOT LIMITED TO: PROCUREMENT OF SUBSTITUTE GOODS OR SERVICES; LOSS OF USE, DATA, OR PROFITS; OR BUSINESS INTERRUPTION) HOWEVER CAUSED AND ON ANY THEORY OF LIABILITY, WHETHER IN CONTRACT, STRICT LIABILITY, OR TORT (INCLUDING NEGLIGENCE OR OTHERWISE) ARISING IN ANY WAY OUT OF THE PUBLICATION, USE OF, OR RELIANCE UPON ANY STANDARD, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE AND REGARDLESS OF WHETHER SUCH DAMAGE WAS FORESEEABLE.

Translations

The IEEE consensus development process involves the review of documents in English only. In the event that an IEEE standard is translated, only the English version published by IEEE should be considered the approved IEEE standard.

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 6: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

Official statements

A statement, written or oral, that is not processed in accordance with the IEEE-SA Standards Board Operations Manual shall not be considered or inferred to be the official position of IEEE or any of its committees and shall not be considered to be, or be relied upon as, a formal position of IEEE. At lectures, symposia, seminars, or educational courses, an individual presenting information on IEEE standards shall make it clear that his or her views should be considered the personal views of that individual rather than the formal position of IEEE.

Comments on standards

Comments for revision of IEEE Standards documents are welcome from any interested party, regardless of membership affiliation with IEEE. However, IEEE does not provide consulting information or advice pertaining to IEEE Standards documents. Suggestions for changes in documents should be in the form of a proposed change of text, together with appropriate supporting comments. Since IEEE standards represent a consensus of concerned interests, it is important that any responses to comments and questions also receive the concurrence of a balance of interests. For this reason, IEEE and the members of its societies and Standards Coordinating Committees are not able to provide an instant response to comments or questions except in those cases where the matter has previously been addressed. For the same reason, IEEE does not respond to interpretation requests. Any person who would like to participate in revisions to an IEEE standard is welcome to join the relevant IEEE working group.

Comments on standards should be submitted to the following address:

Secretary, IEEE-SA Standards Board 445 Hoes Lane Piscataway, NJ 08854 USA

Laws and regulations

Users of IEEE Standards documents should consult all applicable laws and regulations. Compliance with the provisions of any IEEE Standards document does not imply compliance to any applicable regulatory requirements. Implementers of the standard are responsible for observing or referring to the applicable regulatory requirements. IEEE does not, by the publication of its standards, intend to urge action that is not in compliance with applicable laws, and these documents may not be construed as doing so.

Copyrights

IEEE draft and approved standards are copyrighted by IEEE under U.S. and international copyright laws. They are made available by IEEE and are adopted for a wide variety of both public and private uses. These include both use, by reference, in laws and regulations, and use in private self-regulation, standardization, and the promotion of engineering practices and methods. By making these documents available for use and adoption by public authorities and private users, IEEE does not waive any rights in copyright to the documents.

Photocopies

Subject to payment of the appropriate fee, IEEE will grant users a limited, non-exclusive license to photocopy portions of any individual standard for company or organizational internal use or individual, non-commercial use only. To arrange for payment of licensing fees, please contact Copyright Clearance Center, Customer Service, 222 Rosewood Drive, Danvers, MA 01923 USA; +1 978 750 8400. Permission to photocopy portions of any individual standard for educational classroom use can also be obtained through the Copyright Clearance Center.

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 7: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

Updating of IEEE Standards documents

Users of IEEE Standards documents should be aware that these documents may be superseded at any time by the issuance of new editions or may be amended from time to time through the issuance of amendments, corrigenda, or errata. An official IEEE document at any point in time consists of the current edition of the document together with any amendments, corrigenda, or errata then in effect.

Every IEEE standard is subjected to review at least every ten years. When a document is more than ten years old and has not undergone a revision process, it is reasonable to conclude that its contents, although still of some value, do not wholly reflect the present state of the art. Users are cautioned to check to determine that they have the latest edition of any IEEE standard.

In order to determine whether a given document is the current edition and whether it has been amended through the issuance of amendments, corrigenda, or errata, visit the IEEE-SA Website at http://ieeexplore.ieee.org/xpl/standards.jsp or contact IEEE at the address listed previously. For more information about the IEEE SA or IEEE’s standards development process, visit the IEEE-SA Website at http://standards.ieee.org.

Errata

Errata, if any, for all IEEE standards can be accessed on the IEEE-SA Website at the following URL: http://standards.ieee.org/findstds/errata/index.html. Users are encouraged to check this URL for errata periodically.

Patents

Attention is called to the possibility that implementation of this standard may require use of subject matter covered by patent rights. By publication of this standard, no position is taken by the IEEE with respect to the existence or validity of any patent rights in connection therewith. If a patent holder or patent applicant has filed a statement of assurance via an Accepted Letter of Assurance, then the statement is listed on the IEEE-SA Website at http://standards.ieee.org/about/sasb/patcom/patents.html. Letters of Assurance may indicate whether the Submitter is willing or unwilling to grant licenses under patent rights without compensation or under reasonable rates, with reasonable terms and conditions that are demonstrably free of any unfair discrimination to applicants desiring to obtain such licenses.

Essential Patent Claims may exist for which a Letter of Assurance has not been received. The IEEE is not responsible for identifying Essential Patent Claims for which a license may be required, for conducting inquiries into the legal validity or scope of Patents Claims, or determining whether any licensing terms or conditions provided in connection with submission of a Letter of Assurance, if any, or in any licensing agreements are reasonable or non-discriminatory. Users of this standard are expressly advised that determination of the validity of any patent rights, and the risk of infringement of such rights, is entirely their own responsibility. Further information may be obtained from the IEEE Standards Association.

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 8: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

Participants

At the time this IEEE guide was completed, the C2 Cable System Bonding Working Group had the following membership:

Michael D. Buckweitz, Chair Thomas C. Champion, Vice Chair

Torben Aabo Richard W. Allen, Jr. Pierre Argaut Ray Awad Earle C. Bascom, III Mohamed Chaaban John H. Cooper

Dennis F. DeCosta Swapan K. Dey Anthony Ernst William G. Hansen Wolfgang B. Haverkamp Dennis E. Johnson

Arthur J. Kroese Frederic Lesur Allen MacPhail Neal K. Parker Ray E. Saccany William D. Wilkens Jay A. Williams

The following members of the individual balloting committee voted on this guide. Balloters may have voted for approval, disapproval, or abstention.

Saleman Alibhay Senthil Kumar Asok Kumar Peter Balma Thomas Barnes G. Bartok Earle E. Bascom, III Wallace Binder William Bloethe Kenneth Bow Gustavo Brunello William Bush Mark Bushnell William Byrd John Cancelosi Paul Cardinal Weijen Chen Robert Christman Luis Coronado Frank Di Guglielmo Gary Donner Randall Dotson Dana Dufield Donald Dunn Gary Engmann Cliff Erven Dan Evans Jorge Fernandez Daher Rabiz Foda David Garrett David Gilmer Edwin Goodwin Todd Goyette Randall Groves Richard Harp

Timothy Hayden Jeffrey Helzer Steven Hensley Lee Herron Gary Heuston Lauri Hiivala Robert Hoerauf Edward Jankowich Dennis E. Johnson A. Jones Gael Kennedy Yuri Khersonsky Robert Kluge Robert Konnik Jim Kulchisky Saumen Kundu Chung-Yiu Lam Michael Lauxman Greg Luri Glenn Luzzi Arturo Maldonado Michael Maytum William McBride Gary Michel Daleep Mohla Rachel Mosier Jerry Murphy Arun Narang Dennis Neitzel Arthur Neubauer Michael Newman Joe Nims Gary Nissen Lorraine Padden Bansi Patel

S. Patel Percy Pool Moises Ramos Robert Resuali Michael Roberts Lei Rong Thomas Rozek Bartien Sayogo Dennis Schlender Hamid Sharifnia Devki Sharma Gil Shultz Michael Smalley Jerry Smith John Spare Nagu Srinivas Gregory Stano Ryan Stargel Gary Stoedter Peter Sutherland David Tepen Peter Tirinzoni James Tomaseski John Vergis Mark Walton Daniel Ward Lee Welch Yingli Wen Kenneth White Jonathan Woodworth Jian Yu Dawn Zhao Tiebin Zhao J. Zimnoch

Copyright © 2014 IEEE. All rights reserved.

vi

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 9: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

When the IEEE-SA Standards Board approved this guide on 12 June 2014, it had the following membership:

John Kulick, Chair Jon Walter Rosdahl, Vice Chair Richard H. Hulett, Past Chair

Konstantinos Karachalios, Secretary

Peter Balma Farooq Bari Ted Burse Clint Chaplain Stephen Dukes Jean-Phillippe Faure Gary Hoffman

Michael Janezic Jeffrey Katz Joseph L. Koepfinger* David J. Law Hung Ling Oleg Logvinov Ted Olsen Glenn Parsons

Ron Peterson Adrian Stephens Peter Sutherland Yatin Trivedi Phil Winston Don Wright Yu Yuan

*Member Emeritus

Also included are the following nonvoting IEEE-SA Standards Board liaisons:

Richard DeBlasio, DOE Representative Michael Janezic, NIST Representative

Don Messina IEEE-SA Standards Technical Community

Malia Zaman IEEE-SA Standards Technical Community

Copyright © 2014 IEEE. All rights reserved.

vii

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 10: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

Introduction

This introduction is not part of IEEE Std 575™-2014, IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV.

This document is a revision of IEEE 575-1988, which had been reaffirmed multiple times without change in years past. The current revision changes the document title to more appropriately reflect the intent of the guide. Most clauses of the guide were revised and updated to better clarify recommendations and procedures. Advances in computer technology now allow many of the equations to be programmed and solved rapidly using software that can analyze the corresponding circuit configuration and make recommendations for application of specialized bonding. Considerations for shield/sheath optimization have been included in Clause 5. A major addition is Annex F, which provides new information on current and voltage distribution on cable shields/sheaths in situations involving installations with multiple cables per phase.

Copyright © 2014 IEEE. All rights reserved.

viii

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 11: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

Contents

1. Overview .................................................................................................................................................... 1 1.1 Scope ................................................................................................................................................... 1 1.2 Purpose ................................................................................................................................................ 2

2. Normative references .................................................................................................................................. 2

3. Definitions .................................................................................................................................................. 2 3.1 Special terms........................................................................................................................................ 5

4. Background ................................................................................................................................................ 5

5. Shield optimization ..................................................................................................................................... 6

6. Special bonding techniques ........................................................................................................................ 7 6.1 Design .................................................................................................................................................. 9 6.2 Safety considerations for specially bonded cable systems ................................................................. 10 6.3 Single-point bonding ......................................................................................................................... 10 6.4 Impedance-bonding methods ............................................................................................................. 14 6.5 Cross bonding .................................................................................................................................... 15 6.6 Sheath sectionalizing joints ............................................................................................................... 20 6.7 Choice of bonding system ................................................................................................................. 20 6.8 Sheath standing voltage ..................................................................................................................... 22 6.9 Transient voltage analysis .................................................................................................................. 23

7. Sheath voltage limiters ............................................................................................................................. 24 7.1 Introduction ....................................................................................................................................... 24 7.2 Nonlinear resistances ......................................................................................................................... 25 7.3 Nonlinear resistances in series with spark gap .................................................................................. 25 7.4 Spark gaps ......................................................................................................................................... 25 7.5 Selection of shield/sheath voltage limiters ........................................................................................ 26 7.6 Use of shield/sheath voltage limiters ................................................................................................. 29

8. Effect on parallel communication and control cables ............................................................................... 29 8.1 Coupling ............................................................................................................................................ 30 8.2 Shielding ............................................................................................................................................ 30 8.3 Common-mode and metallic voltages ............................................................................................... 30

Annex A (informative) Bibliography ........................................................................................................... 32

Annex B (informative) Discussion of early practices and problems ............................................................ 35

Annex C (informative) Current practice for shield/sheath standing voltages ............................................... 36

Annex D (informative) Calculation of induced voltages .............................................................................. 39

Annex E (informative) Transient voltages and voltage withstand requirements of protective jackets ......... 44

Annex F (informative) Current and voltage distribution on cable shields/sheaths with multiple cables per phase ......................................................................................................................... 53

Copyright © 2014 IEEE. All rights reserved.

ix

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 12: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 13: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

IMPORTANT NOTICE: IEEE Standards documents are not intended to ensure safety, security, health, or environmental protection, or ensure against interference with or from other devices or networks. Implementers of IEEE Standards documents are responsible for determining and complying with all appropriate safety, security, environmental, health, and interference protection practices and all applicable laws and regulations.

This IEEE document is made available for use subject to important notices and legal disclaimers. These notices and disclaimers appear in all publications containing this document and may be found under the heading “Important Notice” or “Important Notices and Disclaimers Concerning IEEE Documents.” They can also be obtained on request from IEEE or viewed at http://standards.ieee.org/IPR/disclaimers.html.

1. Overview

Large investment costs, generally associated with the installation of underground transmission circuits, typically mandate optimizing cable operation from the standpoint of efficiency and power throughput capacity. With the popularity of single-conductor cables and the use of low loss, high dielectric-strength insulating materials and improved cable jackets in the mid-1960s, and their application at sub-transmission and transmission voltages, there is significant interest in the use of single-conductor cables and the problems of the induced voltages and currents associated with their use. Many of these problems (for example, failure of shield/sheath insulators, failure of cable jackets, and shield/sheath corrosion) have been recognized since metallic-sheathed cables were first used, and the fundamentals of calculating shield/sheath voltages and currents have been defined for many years. However, increasingly, ampacity requirements and short-circuit capabilities of modern power systems have accentuated some problems, while improvements in shield/sheath insulations have virtually eliminated others.

Thus it is evident that there is a need for some guidelines whereby the cable engineer can select the shield/sheath-bonding method that best fits the needs of a particular installation.

1.1 Scope

This guide describes the most common special shield/sheath-bonding systems now in use on high-voltage single-conductor shielded power cables and the methods of calculating shield/sheath voltages and currents, particularly as applied to three-phase systems operating at 60 kV and above, with the cable neutral grounded directly or as part of a special bonding system as described in the guide.

Copyright © 2014 IEEE. All rights reserved.

1

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 14: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

Although special bonding has been used predominantly in the past on higher voltage cable systems, more recent attention to shield and sheath losses on distribution class cables has prompted users to consider special bonding on lower voltage class cable systems as well. This is particularly applicable on the collector systems for wind farms, where long cable runs interconnect the individual wind turbines. While this guide on induced voltages and currents in metallic shields and sheaths is written largely around high-voltage cables operating at 60 kV and above, the fundamental principles in this document apply equally to single-conductor medium-voltage shielded power cables when installed and operated as outlined in this guide.

The user is cautioned to make sure that the installation/operating design does not contravene any local or national regulations.

1.2 Purpose

The purpose of this guide is to provide the cable engineer with recommendations for consideration when designing new power cable delivery systems as well as evaluating existing cable systems. This guide addresses the reduction of cable operational losses and increase in cable current carrying capacity through use of special cable bonding and grounding methods. The guide will also assist the user in calculating the standing shield/sheath voltages for various bonding and grounding methods.

2. Normative references

The following referenced documents are indispensable for the application of this document (i.e., they must be understood and used, so each referenced document is cited in text and its relationship to this document is explained). For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments or corrigenda) applies.

AEIC CS9, Specification for Extruded Insulation Power Cables and their Accessories Rated above 46 kV through 345 kV ac.1

ANSI/ICEA S-108-720, Standard for Extruded Insulation Power Cables Rated above 46 kV through 345 kV.2

ICEA Publication P-32-382, Short-Circuit Characteristics of Insulated Cables.3

IEC 60287-1, Electric cables—Calculation of the current rating—Part 1: Current rating equations (100% load factor) and calculation of losses.4

3. Definitions

For the purposes of this document, the following terms and definitions apply. The IEEE Standards Dictionary Online should be consulted for terms not defined in this clause. 5

1 AEIC publications are available from the Association of Edison Illuminating Companies (http://www.aeic.org/). 2 ANSI publications are available from the American National Standards Institute (http://www.ansi.org/). 3 ICEA publications are available from the Insulated Cable Engineers Association (http://www.icea.net/). 4 IEC publications are available from the International Electrotechnical Commission (http://www.iec.ch/). IEC publications are also available in the United States from the American National Standards Institute (http://www.ansi.org/). 5 IEEE Standards Dictionary Online subscription is available at: http://www.ieee.org/portal/innovate/products/standard/standards_dictionary.html.

Copyright © 2014 IEEE. All rights reserved.

2

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 15: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

bonding lead: The insulated conductor connecting the shield/sheath of a shielded cable segment to an adjacent cable segment or bonding accessory for the purpose of providing a fault current path. A bonding lead may connect the shield/sheath of a cable segment or cable accessory to: (1) the shield/sheath on another cable segment, (2) a cable accessory, such as a joint casing, a termination bell, or a link box, or (3) a grounding point, such as a grounding bus, a ground rod, or a ground continuity conductor (GCC).

continuous cross bonding: A form of cross bonding applicable to circuits consisting of at least four minor sections in which the cable metallic shields/sheaths are successively cross-bonded at each junction between adjacent minor sections throughout the cable route. At each end of the route the shields/sheaths are solidly bonded and grounded.

cross bonding: The form of special bonding in which the metallic shields/sheaths of different phase cables in successive minor sections are cross connected in such a way so as to attain partial or full cancellation of induced currents on the metallic shields/sheaths.

flat formation: Three cables laid in one plane with normally equal spacing between adjacent cables.

ground continuity conductor (GCC): A conductor laid parallel and in close proximity to a cross-bonded or single-point bonded cable circuit to provide a continuous metallic ground connection between the grounding systems at the ends of the cable route and along the run.

impedance bonding: A bonding scheme in which an impedance, such as a reactor or a resistance, is inserted into the shield/sheath current path for the purpose of limiting fault currents or load losses.

insulated shield/sheath system: A cable system in which the metallic shield/sheath of each cable is individually insulated throughout its length except where any necessary grounding or inter-shield/sheath connections are made.

joint sleeve insulation: The external insulation applied over the metallic sheath/shield of a cable joint.

link box: A box in which bonding and grounding connections are made through removable links. The box may also contain shield/sheath voltage limiters.

major section: A set of consecutive minor cable sections between solidly bonded shields/sheaths that are connected in such a way so as to minimize cable shield/sheath current losses on each phase cable. For three-phase systems, three consecutive minor sections are required to form a major section to minimize shield/sheath currents on all three phases.

minor section: The length of cable between shield/sheath sectionalizing insulators, and between sheath insulators and sheath end-bells at the cable terminations.

multiple single-point bonding: The form of special bonding in which the three cable shields/sheaths are solidly bonded and grounded to a ground continuity conductor (GCC) at one end of a section, and connected to ground through shield/sheath voltage limiters at the other end; done at multiple locations along a route.

power frequency: The operating frequency of the ac power cable system.

NOTE—The basic principles presented in this guide apply to 50 Hz and 60 Hz systems once appropriate adjustments of constants are made. Examples in this guide assume either a 50 Hz or 60 Hz frequency as indicated.6

6 Notes in text, tables, and figures of a standard are given for information only and do not contain requirements needed to implement this standard.

Copyright © 2014 IEEE. All rights reserved.

3

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 16: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

screening conductor: A conductor laid in parallel with a current-carrying loop and itself forming part of a closed circuit in which induced currents can flow whose magnetic field will oppose the field of the current-carrying loop.

sectionalized cross bonding: The form of cross bonding in which three consecutive minor sections are taken to form a single cross-bonded unit (see major section). The three shields/sheaths are solidly bonded at both ends of a major section and may be grounded at these points. At the two intermediate positions the cables are transposed and the shields/sheaths are interconnected in such a way so that each continuous shield/sheath circuit through the major section occupies the same geometrical position in the cable formation. For long cable routes there will usually be a number of major sections.

sheath: Historically the term implied an extruded lead sheath that provided a moisture impervious barrier for the inner cable core while simultaneously providing the requisite metallic shielding for the cable. More recently extruded aluminum sheathing and copper foil laminates have been employed in order to provide moisture tightness.

sheath interrupt: A break or interruption, incorporated into the metallic shield/sheath and semiconducting shield of a cable at a joint in order to provide electrical isolation between adjacent cable shield sections.

sheath sectionalizing insulator: An insulating member inserted into the joint and metallic joint casing (if present) in order to electrically isolate the shields of adjacent cable lengths, of the same phase, from each other; typically this insulating member is a ring made of epoxy or porcelain.

sheath sectionalizing joint: A joint in which the metallic screen and metallic casing, if present, are electrically interrupted by means of a shield/sheath sectionalizing insulator.

sheath standing voltage: The voltage to ground appearing on the metallic shield/sheath of a specially bonded cable when balanced full-load currents are flowing in the cable conductors; typically specified at the point along the cable length at which it is a maximum (that is, at the ungrounded extremity of a minor section in the case of single-point bonding and at a cross-bonding point in the case of cross bonding). When the voltages differ for the three-phase cables, the highest value is typically specified.

sheath voltage limiter (SVL): A surge protective device connected between the metallic shield/sheath and ground on specially bonded cables to limit shield/sheath overvoltages during system transients.

shield: A non-moisture impervious metallic outer conductor of single conductor power cables, such as concentric wires and concentric copper tapes, that provide grounding and a fault current path for the cable.

shield/sheath: See 3.1.

single-point bonding: The form of special bonding in which the three cable shields/sheaths of a minor section are solidly bonded together and grounded at one point only. For long cable routes this may be repeated a number of times. See also: multiple single-point bonding.

solid bond: A metallic connection between shields/sheaths or between shields/sheaths and ground.

special bonding: Methods of bonding and grounding the metallic shields/sheaths of single-conductor cables so as to minimize the shield/sheath circulating currents resulting from induction of conductor currents.

transposition of power cables: The practice of laying single-conductor cables so that each phase cable successively occupies, optimally over equal lengths of the route, each of the three geometric lay positions in the formation.

Copyright © 2014 IEEE. All rights reserved.

4

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 17: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

transposition of the parallel ground continuity conductor (GCC): The practice of laying a parallel ground conductor alongside a minor section of untransposed power cables so that the conductor occupies over half of the section’s length one position and over the other half occupies a symmetrically opposite position.

trefoil: The formation of three cables positioned so that the cable centers are equidistant (when viewed in cross section, lines drawn through the cable centers form an equilateral triangle).

uniform major section: A section consisting of three similar uniform minor subsections having equal lengths.

3.1 Special terms

shield/sheath: For the purpose of this guide and in order to simplify the discussion, the terms sheath and shield, as used in the context of this document, are intended to refer to the metallic, electrically conducting portion of the cable sheath or shield and as such both terms are used interchangeably when referring to the outer conductor of a single conductor medium- or high-voltage power cable.

4. Background

Single conductor medium- and high-voltage power cables employ a coaxial design essentially consisting of a metallic center conductor surrounded by insulation and an outer metallic shield or sheath (outer conductor). Semiconducting layers are provided at the interface between the conductor and the insulation, and between the insulation and the metallic shield or sheath in order to provide a smooth electrical interface for the insulation and thus establish a uniform electrical stress pattern within the insulation. Cable core conductors are normally comprised of aluminum or copper wires but can be of solid construction.

Present day cable insulation materials generally consist of impregnated paper, ethylene propylene rubber (EPR), or cross-linked polyethylene (XLPE). The cables are constructed with an outer metallic shield or sheath, which is primarily comprised of one of the following:

Concentrically applied copper wires, aluminum wires, or helically applied copper tapes

Extruded lead or aluminum sheathes

Longitudinally applied corrugated copper tapes sealed at the overlap

Longitudinally applied thin copper or aluminum foil laminates sealed at the overlap

Combination of wires with any of the above copper tapes

NOTE—Since this document deals primarily with the electrical aspects of shields and sheaths, and to simplify the discussion, the cable metallic shields or sheaths will be referred to interchangeably as the shield or sheath unless otherwise indicated.

Covering the metallic shield/sheath is normally an insulating jacket typically consisting of extruded polyethylene (PE) or comparable electrically insulating jacketing material, which protects the underlying metallic shield/sheath from electrolysis.

The magnetic field resulting from current flow through the core conductor couples the metallic shield/sheath and any other adjacent conductors. If the shield is also part of a continuous closed loop electric path, transformer action induces a current flow in the coupled shield/sheath and other adjacent conductors. Resistive losses due to the circulating currents in the shield then contribute to the temperature rise of the cable, limiting the amount of current that can be carried by the cable and reducing cable

Copyright © 2014 IEEE. All rights reserved.

5

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 18: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

efficiency. Conversely, if the electric path is interrupted through use of special bonding techniques, the shield/sheath circulating currents will be reduced or eliminated resulting in greater loading capability for the cable but at the disadvantage of developing a rise in shield/sheath voltage. Consequently, special bonding and grounding arrangements have been developed to limit the magnitude of sheath voltages and to minimize the flow of circulating currents.

To assure proper performance of specially bonded systems, the jacket’s electrical integrity should be checked as part of factory testing and upon installation. To ensure that an adequate ground is available for field testing of the cable jacket in the field, the outer surface of the jacket is either coated during manufacture with a graphite coating or alternatively a semiconducting layer is extruded overall during manufacture. Typical field practices include testing the jacket’s integrity by subjecting the jacket to a 10 kV dc test for one minute as follows:

a) After delivery and prior to installation

b) Immediately after laying each cable length

c) After cable jointing (splicing)

d) As part of final commissioning of the circuit

e) Periodically thereafter as part of a routine maintenance program as recommended by the manufacturer

CAUTION

It is essential with specially bonded cable systems to ensure that all disconnecting links are properly reconnected after completion of the jacket tests or any other related testing. Operation of cables with

shields/sheaths improperly connected (grounded) will often result in cable failure. To obviate this potential risk, formal link box commissioning, inspection, certification, and

link box locking procedures should be established.

Safety and cost considerations often do not justify application of special bonding for cable operation below transmission voltage class. Many distribution cable installations are also multipoint grounded because they are installed in random lay with communication cables and the installations are governed by Accredited Standards Committee C2-2012, National Electrical Safety Code® (NESC®) [B1] Rule 354D.7 Conversely, on higher voltage power cable systems that carry large bulk of power, it is often economical and practical to employ special bonding in order to limit shield/sheath losses and thus maximize loading capability.

For distribution class cables, the metallic shield is for the most part normally installed multipoint solidly grounded. This is due to safety concerns associated with making sure that all shield components of a specially bounded distribution cable would remain effectively insulated in the field after installation/during operation. The initial installation cost and additional maintenance associated with specially bonded installations makes this option often also less economically attractive for distribution class feeders, which have relatively lower power transfer requirements as compared to their transmission class counterpart. Thus special bonding techniques may be justified in some instances on distribution class feeders once safety aspects have been adequately addressed and the additional initial installation and subsequent maintenance costs have been effectively considered.

5. Shield optimization

For distribution class cables, shield losses can sometimes be reduced by increasing the shield impedance through a reduction of the metal content of the shield. However, this approach is generally limited by fault current magnitude and duration requirements for the shield. The fault duration requirement will need to

7 The numbers in brackets correspond to those of the bibliography in Annex A.

Copyright © 2014 IEEE. All rights reserved.

6

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 19: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

consider any delay introduced by failure of the primary circuit protection and dependence on a backup protection scheme. Cable designs typically specify a maximum temperature on the shield under this worst-case condition. The required amount of metal in the shield is then specified as a fraction of the cross-sectional area of the core conductor. For example, the shield can be full, 1/2, 1/3, 1/6, or even 1/12 the cross-sectional area of the core conductor. Designs with large surface areas compared to the volume of metal allow for increased heat dissipation into surrounding materials through thermal conduction. Thin corrugated shields tend to incorporate the highest shield to core conductor ratios because of the very large surface area presented for the minimum amount of metal present. The design results in some of the highest heat dissipation for the amount of metal included in the shield while reducing resistive losses by exhibiting high impedance. The most commonly used shield configuration for distribution class cables is concentric wires.

Incorporating an impervious moisture barrier into the design of a transmission class cable is an important requirement. For this reason, transmission cables have historically employed tubular lead sheaths because these could be readily extruded as a continuous, uninterrupted layer over the cable core while simultaneously providing the requisite metallic shield. More recent moisture-tight designs have often replaced lead with extruded corrugated aluminum sheaths and various combinations of corrugated and flat copper tapes in conjunction with copper wires. Where extruded metallic sheaths are not part of the design, metallic shields are supplemented with moisture-tight alternative polymeric and other designs in order to assure the high degree of operational reliability required of a transmission cable. Balancing the choices between designs, materials, electrical properties, and economics in the selection of the cable metallic shields/sheaths is referred to as shield optimization.

In many early cable designs, the shield was exposed and in direct contact with the earth, water, mud, and conduit. This resulted in corrosion problems caused by ac electrolysis, leading to shield damage. Early efforts to limit such damage placed restriction on the maximum magnitude of shield/sheath voltage, limiting these voltages to the range from about 12 V to 17 V. Newer cable designs generally include an outer jacket that is insulating and the likelihood of corrosion is thus effectively eliminated as long as the jacket remains intact. Since application of special bonding results in the build-up of significant voltage levels on the shield during faults and other abnormal operating conditions, designs take advantage of the state-of-the-art electrical insulating properties for the jacket to meet needed voltage withstand requirements. A graphite coating or an outer semiconductive layer is usually applied over the jacket at the factory to allow for testing of the jacket’s electrical integrity.

6. Special bonding techniques

With heavier loads on single conductor cable circuits, shield circulating current losses resulting from multipoint solidly bonded and grounded systems can be excessive for the intended application. To mitigate these losses, alternative shield grounding methods are available, and these are collectively referred to as special bonding techniques. Because long circuits and high currents tend to be more common on transmission class circuits, special bonding techniques tend to be more applicable on these types of circuits. However, special bonding techniques can be applied on distribution circuits when operating conditions dictate a reduction in circuit losses.

Shield losses also increase with the spacing between cables, particularly when multiple point grounded, single-conductor cables are installed with wide spacing, such as when cables are placed in separate ducts or when they are direct buried in spaced configurations. When cables are spaced apart, significantly higher currents flow on the shield of solidly grounded systems, resulting in higher induced shield circulating current losses. Increased spacing decreases the effects of mutual heating but increases the effect of magnetic coupling and therefore, increases shield circulating current losses resulting in lower current ratings. The purpose of special shield bonding is to eliminate or significantly reduce shield circulating current losses on single-conductor cables.

Copyright © 2014 IEEE. All rights reserved.

7

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 20: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

Some special bonding options include the following:

Single-point bonding

Multiple single-point bonding

Impedance bonding

Sectionalized cross bonding

Continuous cross bonding

The simplest and most effective method of special shield bonding is single-point bonding, in which one end of the circuit is grounded and the other end is isolated from ground. The maximum cable section length is governed by the permissible shield standing voltage allowed at the isolated end. For typically permitted shield voltage rise levels (i.e., no higher than about 200 V), this method is generally employed on line lengths of up to about 2 km (1.2 mi).

For longer line lengths or when shield voltages become excessive due to very high fault currents, cross bonding is generally preferred and is the most widely used form of special bonding. (Note, however, that most ac submarine cable circuits are solidly bonded because it is not practical to install shield break insulators along their run). The shields of cross-bonded cables are generally expected to be nominally at ground potential, but specially bonded systems can have appreciable voltages with respect to ground, even under normal load conditions. Under some circumstances, even solidly bonded and grounded shields can develop voltages well above ground potential along the circuit run. With present day jacketing materials and appropriate jacket thicknesses, some utilities have allowed shield standing voltages as high as 600 V under normal operation on specially bonded transmission class cable systems. See Annex B for additional information.

An alternative scheme that can be applied to long line lengths is multiple single-point bonding. Single-point bonding should always employ a separate ground-return conductor, except for the case where a circuit is installed totally within a station area having a ground grid that provides a low impedance return ground path.

In all cases, special shield bonding designs must effectively address the following functions:

Provide grounding for the cable

Maintain a continuous fault-current return path either through the shield/sheath and/or a ground continuity conductor (GCC)

Limit normal steady-state shield voltages to acceptable and safe levels

Significantly reduce or eliminate shield losses

Limit transient overvoltages to acceptable levels in combination with surge protective devices

To meet these requirements, special bonding techniques are used that divide the cable shield into a number of sections along the cable run, using shield sectionalizing joints. The length of each section is determined by the permissible shield voltage under normal and fault conditions. Shield sectionalizing is normally accomplished at joint and termination locations where access to the shield is readily available. The ability to site joints and terminations at a particular location affects the system shield voltages and currents that will develop, and can affect the type of shield bonding selected. Complete suppression of circulating shield currents may not always be possible because of practical limitations imposed on cable lengths by the spacing of manholes and other access points. In these cases, it may be necessary to calculate the residual shield currents and assess their effect on the cable rating.

Copyright © 2014 IEEE. All rights reserved.

8

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 21: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

Special bonding designs depend in part on the insulating properties of a cable jacket to withstand induced voltages. Jackets for specially bonded cable systems typically incorporate an outer conductive layer, such as a graphite coating, to allow periodic testing of the jacket integrity and thus assure proper in service performance. However, the jacket is only part of the bonding system and proper design and coordination with other components, such as shield interrupts, link boxes, and shield voltage limiters (SVLs) is necessary in order to arrive at the proper design for a specially bonded system. The design and ratings of these components is determined based on factors such as the following:

Maximum allowable magnitude of steady-state shield voltage

Maximum allowable magnitude of transient shield voltage under fault conditions

Dielectric breakdown voltage (puncture voltage) of the cable jacket under fault conditions

Flashover voltage of the shield joint insulator (shield interrupt) under fault conditions

6.1 Design

In the design of special sheath-bonding arrangements, consideration must be given to the following aspects:

a) Cable sheaths on short transmission cable circuits and most distribution circuits are usually expected to be nominally at ground potential. However, in a specially bonded system the shields/sheaths can have appreciable voltages with respect to ground and shields/sheaths should never be assumed to be at ground potential. Appropriate precautions must be taken to ensure that personnel are aware of the potential hazard and proper safety procedures. Consideration should be given to effective installation of appropriate barriers, warning devices, etc., as warranted by expected shield/sheath voltages.

b) Complete suppression of circulating shield/sheath currents may not always be possible because of practical difficulties in the choice of cable lengths and cable spacing. It is then necessary to calculate the residual sheath currents and assess their effect on the cable rating.

d) The use of special bonding gives rise to sheath overvoltages during system transients and faults, and the magnitudes of those overvoltages must be considered in the design of the cable system. For higher voltage systems, a shield/sheath voltage limiter will be generally needed and in all cases consideration must be given to the coordination of the jacket insulation levels, the voltages to which the jacket will be subjected, and the characteristics of surge voltage protective devices.

e) Failure of a part of the jacket or of a sheath voltage limiter (SVL) can result in excessive shield/sheath currents and losses and cause overheating of the cables. Consideration must therefore be given to the duty imposed on the shield/sheath voltage-limiting device and to the monitoring and maintenance of the complete systems.

For single-conductor cable circuits carrying currents in excess of about 500 A, special bonding is often economically desirable as the reduction in losses allows an appreciably smaller conductor size to be used. Very often, employing special bonding will permit the use of a single cable per phase installation where, otherwise, multiple cables per phase would be required with the use of solid bonding. There is no clear-cut load level at which special bonding should be introduced and the extra cost of the larger conductor cable or multiple cables per phase system needed for a solidly bonded system must be weighed against the cost of the additional equipment and the maintenance cost arising from the greater complexity of a specially bonded system.

The use of special bonding gives rise to high shield overvoltages during system transients and faults. Failure of components employed in special bonding systems can result in significant shield currents and losses leading to cable overheating. The magnitude of overvoltages must be considered during system design and the protective capabilities of SVLs properly coordinated with the expected shield insulation

Copyright © 2014 IEEE. All rights reserved.

9

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 22: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

levels. Prudent circuit design requires that consideration be given to the duty imposed on the shield-voltage-limiting device and to periodic monitoring and maintenance of the complete system during operation

6.2 Safety considerations for specially bonded cable systems

WARNING

Potentially hazardous voltages can be present on the exposed portions of the metallic shields/sheaths of high-voltage cables, the outer surface of conducting cable jackets, the conductor of bonding cables, the conductor of grounding leads, across exposed shield/sheath interrupts, the SVLs, and various hardware

connections within the link boxes and other equipment connected to or associated with specially bonded cable systems. Appropriate precautions must be taken to provide access control to these areas to ensure that

safety procedures are followed in order to protect both personnel and equipment.

Exposed portions of the metallic shield, sheath, bond cable, or other conductive connections in electrical contact with the cable’s shield/sheath, or bond cable of a specially bonded cable system, should never be assumed to be at ground potential. The allowable shield/sheath voltage at full load varies considerably among utilities and among countries. The shield/sheath voltage will be significantly higher during system transients and short circuit conditions. As a consequence, appropriate protection and precautions must be taken to ensure that personnel who may come into contact with any of the above conductive components are familiar with the design, take adequate protection against potentially related hazards, and follow proper safety procedures.

6.3 Single-point bonding

The simplest form of special bonding consists in grounding the sheaths of the three cables at only one common point (for all three cables) along the cable run. In these types of installations, a voltage is induced on the sheath of the cable during operation, progressively increasing with distance away from the grounded point and reaching a maximum at the farthest point away from the grounded end. The sheaths must therefore be adequately insulated from ground by means of an effective insulating jacket. Since there is no continuous closed loop electrical path for the shield/sheath, current does not flow longitudinally along the shields/sheaths and shield circulating current losses are thus eliminated (sheath eddy losses will still be present).

SVLs should always be used if the expected surge voltage level exceeds 75% of the BIL of the jacket or of the shield/sheath sectionalizing insulator.

Copyright © 2014 IEEE. All rights reserved.

10

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 23: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

0

100

200

300

400

1 10

E (V

/km

); I

= 10

00 A

Ratio S/d

Cables in trefoil and center cable of group in flat formation

Outer cables of group in flat formation

2 3 5 7 20 30 50

f = 60 Hz

Figure 1 —Induced shield/sheath voltage gradient for a conductor current of 1000 A

6.3.1 Shield/sheath standing voltages

Values of sheath standing voltage can be found using Figure 1.

As an example, for a typical circuit having a conductor current I = 1000 A and S/d = 2

where S is the center-to-center cable spacing d is the mean sheath diameter

The shield/sheath voltage will be 103 V/km (166 V/mi) and 138 V/km (222 V/mi) for trefoil and flat formations, respectively, under normal three-phase operation. It should be also recognized that the shield/sheath voltages will be significantly higher during system transients and short circuit conditions.

6.3.2 Multiple lengths

When the circuit length is such that the sheath-standing voltage limitation is exceeded when the ground is connected at one end of the circuit, the ground connection may be moved to some other location along the circuit run, for example, the center of the length. The shield/sheath standing voltage on each of the two sections thus formed is then correspondingly reduced. When the circuit is too long to be dealt with by this means, it may be sectionalized by the use of shield/sheath sectionalizing joints (multiple single-point bonding) so that the shield/sheath standing voltage for each minor section is within the limitation imposed.

6.3.3 Parallel ground continuity conductor

During a ground fault on the power system, the zero-sequence current carried by the cable conductors returns by whatever external paths are available. Since a single-point, bonded cable shield/sheath is grounded at one position only, it cannot, except in the case of a cable fault, carry any of the returning current. This being so, unless some parallel external conductor is available or is provided to serve as an alternative path, the return current can flow only by way of the ground itself. Because the resistivity of the

Copyright © 2014 IEEE. All rights reserved.

11

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 24: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

ground is very high compared with that of good conductors, the return current is widely diffused through the ground and the mean effective depth of the current is hundreds of meters deep. Because the returning current path is significantly remote from the cable, the voltage induced along parallel conductors, including the cable shields/sheaths, tend to be very high.

Furthermore, in the absence of a parallel GCC, the occurrence of a ground fault in the immediate vicinity of a cable could cause a major difference in potential to arise between the two ends of a cable system. Depending to some extent on the particular design of the voltage limiters employed, hazards could then ensue to personnel or equipment.

Accordingly, it is recommended that single-point bonded and multiple single-point bonded cable installations be provided with a parallel GCC that is grounded at both ends of the route as shown in Figure 2. The spacing of this conductor from the cable circuit should be sufficiently close to limit the voltage rise of the shield/sheath to an acceptable level during a single-phase fault. The size of this conductor must be adequate to carry the full, expected fault current for the cable system.

Although a GCC is not required for cross-bonded systems since the cable shields/sheaths form an end-to-end path for fault currents, many utilities, especially those in the U.S., do install GCCs to insure a solid end-to-end conductor, and to give a low impedance connection point for grounding the shield/sheath voltage limiters and cable shields/sheaths in vaults. Note that circulating currents can be induced in the GCCs, especially in imbalanced cross-bonded systems, and the resulting losses should be considered when calculating cable ampacity.

The parallel GCC is usually insulated so as to avoid any corrosion risk since it will be subjected to voltage induction from the power cables in the same way as any other parallel conductor. To avoid circulating currents and losses in this conductor, it is preferable, when the power cables are not transposed, to transpose the parallel GCC as shown in Figure 2, using the methods described in Annex D, D.3.

Figure 2 —Transposition of parallel ground continuity conductor to reduce induced shield/sheath voltages on power cables in flat or trefoil formation

Copyright © 2014 IEEE. All rights reserved.

12

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 25: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

6.3.4 Circuit arrangements

The application of single-point bonding to single length circuits is shown in Figure 3 and to multiple length circuits in Figure 4. These diagrams do not show the disconnecting boxes to permit testing of the shield/sheath insulation.

(a) End-point bonding (b) Midpoint Bonding

NOTE―Other patterns of ground conductor transposition may be used. See Annex D, D.4.

Figure 3 —Single-point bonding diagrams for circuits comprised of only one cable length

Figure 4 —Single-point bonding diagram for a circuit comprised of three cable lengths

Copyright © 2014 IEEE. All rights reserved.

13

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 26: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

6.4 Impedance-bonding methods

In impedance-bonding methods, the cable shield/sheath sections are bonded together in some manner through an inserted impedance. This impedance can consist of simple reactors or of devices such as saturable reactors and bonding transformers. In all these methods a certain amount of shield/sheath current is permitted so as to reduce losses and shield/sheath voltages. To provide ground connections, the impedance devices are typically designed with center taps or grounding points.

At one time resistors were used, however, in general, resistance bonding is not practical, since the resistors have to be sized to take the fault currents and they are considered very large for high fault currents.

Although a partial suppression of induced shield/sheath voltages is obtained using impedance-bonding methods, there are a number of disadvantages that limit the application of these methods. The principal disadvantages are as follows:

a) Additional vault space is required.

b) The impedance devices are relatively expensive since they must be designed to withstand fault currents.

c) In normal operation, 3rd harmonics can be introduced into the shield/sheath, and these can cause interference on nearby telephone lines.

d) Stray direct currents entering through the grounding can cause saturation of the iron cores and upset the operation of the reactors or transformers.

6.4.1 Description of transformer shield/sheath bonding for single-conductor cables

Another special shield/sheath bonding method to minimize induced shield/sheath currents is called transformer shield/sheath bonding. In the transformer shield/sheath bonding method, both ends of each cable shield/sheath are electrically connected to a three-phase shield/sheath bonding transformer as shown in Figure 5.

SBT SBTSBTSBT

MANHOLE MANHOLE

Sheath BondingTransformers

LocalDrivenGround

Cable Sheath

LocalDrivenGround

Sheath Voltage Limiters

Sheath InterruptSheath Interrupt

Figure 5 —Schematic of transformer shield/sheath bonding

The shield/sheath-bonding transformer is a specially wound transformer (Figure 6) that is electrically the same as a zigzag grounding transformer. This type of transformer is designed to give a high impedance between the three shield/sheath connections (A, B, and C) and ground (N) when the voltages applied to terminals A, B, and C are balanced three-phase voltages. The shield/sheath bonding transformer has a low

Copyright © 2014 IEEE. All rights reserved.

14

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 27: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

impedance between any of the three shield/sheath bonding terminals (A, B, and C) and ground (N) if a single-phase or zero sequence voltage is applied. In other words, the shield/sheath bonding transformer is a high impedance to ground for positive sequence voltages and a low impedance to ground for zero sequence voltages applied to the terminals A, B, and C.

A B C N

Steel Core

Figure 6 —Schematic of shield/sheath bonding transformer

During normal cable operation the induced shield/sheath voltages on the three cable shields/sheaths are approximately equal and 120 electrical degrees out of phase. Consequently, there is very little current that flows through the cable shields/sheaths to ground via the shield/sheath bonding transformers. Single-line-to-ground fault conditions produce a zero sequence voltage that appears across the bonding transformer and the fault flows to ground through relatively low impedance. The shield/sheath bonding transformers must be designed so that they will not saturate as a result of induced shield/sheath voltages produced by normal and short-term emergency operating currents.

The cable shields/sheaths are also connected to local ground by means of shield/sheath voltage limiters (see Figure 5). The shield/sheath voltage limiters protect the cable jackets, shield/sheath interrupts, and the shield/sheath bonding transformer from transient overvoltages.

The primary advantage of the shield/sheath bonding transformer scheme is that it is effective in limiting induced shield/sheath currents regardless of whether or not the distances between cable vaults are equal or unequal. The primary disadvantage of the shield/sheath bonding transformer scheme is that additional space is required in the joint vaults to accommodate the additional components (compared to other special shield/sheath bonding methods). The cost of the equipment for implementing transformer bonding is also generally higher than single-point or cross-bonding schemes.

6.5 Cross bonding

6.5.1 Basic circuit arrangement

Cross bonding consists essentially in sectionalizing the shields/sheaths into minor sections and cross connecting them so as to approximately neutralize the total induced voltage in three consecutive sections, as shown in Figure 7.

With untransposed cables, as illustrated in Figure 7, it is impossible to achieve an exact balance of induced shield/sheath voltages unless the cables are laid in trefoil. When, for the reasons given in Annex D, D.3, the

Copyright © 2014 IEEE. All rights reserved.

15

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 28: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

cable conductors are transposed at each joint position, the induced shield/sheath voltages will be neutralized irrespective of cable formation provided the three minor sections are identical. Figure 8 shows how this can be accomplished for a circuit consisting of three minor sections. The shields/sheaths are bonded and grounded at both ends of the route. In this arrangement, the three minor sections together are referred to as a major section.

Transposition is preferred in order to provide the best balance of the shield/sheath voltages. However, practical difficulties that lie with transposing large and heavy high-voltage cables generally prevent these from being installed in a transposed configuration.

Figure 7 —Cross-bonded cables without transposition

Figure 8 —Cross-bonded cables with transposition

6.5.2 Longer cable circuits

Cross bonding can be extended to longer cable circuits by the methods described in 6.5.3 through 6.5.7.

6.5.3 Sectionalized cross bonding

This cross-bonding system is often called Kirke-Searing bonding, although the system used by Searing and Kirke [B45] did not involve transposition of cables. When the number of minor sections is divisible exactly by three, the circuit can be arranged to consist of one or more major sections in series. At the junction of two major sections and at the ends of the circuit, the shields/sheaths are bonded together and grounded, although the grounds at the junctions of major sections will generally be only local ground rods and the GCC if one is provided. (See Figure 9 in which each separate major section is connected as in Figure 8).

Copyright © 2014 IEEE. All rights reserved.

16

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 29: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

NOTE―Asterisk (*) indicates that these joints can be without shield/sheath sectionalizing insulators and may be connected directly to the local ground.

Figure 9 —Sectionalized cross-bonded cable with three major sections

6.5.4 Modified sectionalized cross bonding

In this modified version of the sectionalized cross-bonding system, it is not necessary to have the number of minor sections exactly divisible by three. Balanced voltage conditions within a given major section consisting of four minor sections can be achieved by subdividing one minor section into two subsections, as follows:

a) One short length (or subsection) followed by two equal lengths (or minor sections) with another short length (or subsection) completing the major section; the combined length of the two subsections should be equal to the length of one minor section as shown on Figure 10 and Figure 11.

b) One short length (or subsection) followed by one longer length (or minor section) then another short length (or subsection) followed by one longer length (or minor section) to complete the major section; the two longer lengths (or minor sections) should be equal and the combined length of the two subsections should be equal to the length of one minor section as shown on Figure 12 and Figure 13. In this case, the first cross bonding must be reversed.

*

*

*

*

*

*

Copyright © 2014 IEEE. All rights reserved.

17

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 30: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

L1 and L2 = Length of subsections L = Length of minor sections

L1 + L2 = L

Figure 10 —Modified sectionalized cross-bonding type without transpositions

L1 and L2 = Length of subsections L = Length of minor sections

L1 + L2 = L

Figure 11 —Modified sectionalized cross-bonding type with transpositions

L1 and L2 = Length of subsections L = Length of minor sections

L1 + L2 = L

Figure 12 —Modified sectionalized cross-bonding type without transpositions

Copyright © 2014 IEEE. All rights reserved.

18

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 31: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

L1 and L2 = Length of subsections L = Length of minor sections

L1 + L2 = L

Figure 13 —Modified sectionalized cross-bonding type with transpositions

6.5.5 Continuous cross bonding

In this system the shields/sheaths are cross-bonded at the end of each minor section throughout the whole cable route. The three shields/sheaths are bonded and grounded at the two ends of the route only, as shown in Figure 14. It is again generally desirable that the cables are transposed so that each conductor occupies each of the three positions for one third of the total length. The number of matched minor sections should preferably be exactly divisible by three, but this becomes less important as the total number of minor sections increases (see 6.5.7).

Figure 14 —Continuous cross bonding

6.5.6 Mixed systems

When the number of minor sections is not exactly divisible by three, the system can consist of a mixture of Kirke-Searing (regular and modified) and single-point bonded lengths. When necessary, on account of a large number of minor sections having unequal lengths, the cross bonding can be of the continuous type. Figure 15 shows the arrangement of a final single-point bonded length at the end of a cross-bonded system.

Copyright © 2014 IEEE. All rights reserved.

19

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 32: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

Figure 15 —Termination of cross-bonded system with single-point bonded length

6.5.7 Imbalanced systems

It is not generally possible to divide the route length into exactly matched minor section lengths, nor is it always possible to maintain a constant spacing of the cables throughout the route. In continuous cross-bonded systems, it may also be desirable to have a total number of minor sections not exactly divisible by three. In practical systems, there is therefore generally some imbalance, and it may be necessary to calculate the circulating shield/sheath currents that are present so as to assess their effect on the cable rating. See IEC 60287-1, Kuwahara and Doench [B32], and Annex D for methods of calculation.8

6.6 Sheath sectionalizing joints

When the shield/sheath losses of single-conductor cables must be reduced or eliminated, shield/sheath sectionalizing joints are required for interrupting the electrical continuity of the shield/sheath circuit. To perform their function satisfactorily there are several major factors involved in the design of these joints. Mechanically, they must be rugged, impervious to moisture, and fluid tight under all operating conditions. Electrically, they must be designed to withstand the voltage stresses occurring under fault, lightning, and switching surge conditions or be effectively protected by suitable surge protective devices. This subject is discussed in more detail in Annex C.

6.7 Choice of bonding system

Impedance bonding methods are generally considered less satisfactory than the other methods described. For this reason these methods are not recommended for general use.

Bonding transformers can be economical in some isolated cases such as when:

a) Suitable balancing for cross bonding is impossible and single-point bonding is unacceptable (that is, no empty duct is available for a GCC).

b) A spare cable (a fourth cable for a single circuit or a seventh cable for a double circuit) is installed; in this case, reconnecting the cross bonding whenever the spare cable is needed is a lengthy and complex operation, whereas reconnecting of bonding transformers is simple and straightforward.

8 Information on references can be found in Clause 2.

Copyright © 2014 IEEE. All rights reserved.

20

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 33: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

Users of this method may refer to 6.4.1 and Halperin, Clem, and Miller [B23], Halperin and Miller [B24], Watson and Erven [B47], Wollaston and Kidd [B49], and Report No. 55-286 [B39].

Further discussion will therefore be limited to consideration of the other bonding methods.

6.7.1 Use of single-point bonding

A minimum of three minor sections is needed to form a cross-bonded system. Hence, cross bonding is not applicable to cable circuits comprised of only one or two lengths of cable, and for such circuits, single-point bonding would be employed unless it were feasible to reconfigure the circuit into three minor sections.

For longer cable systems, multiple single-point bonding can also be employed in lieu of cross bonding. This is especially useful when a spare cable is installed in addition to the phase cables (a fourth cable in the case of a single circuit or a seventh cable in for a double circuit line), or where the section lengths are very unequal.

6.7.2 Advantages of cross bonding

Although the cable shields/sheaths of a single-point bonded system are generally of a cross-sectional area and conductivity that makes them quite capable of carrying short-circuit currents due to through faults in the power system, they are unable to do so because they are grounded at one point only. A parallel GCC is therefore recommended (see 6.3.3), and this adds appreciably to the cost of the cable system.

The principal advantage of cross bonding is that, while induced shield/sheath currents are inhibited during normal balanced load operation, the shields/sheaths do form a continuous path from end to end of the cable circuit and are grounded at both ends. Shield/sheath currents can, therefore, flow during ground faults, and the necessity for the parallel GCC is removed. In addition to the economy achieved by the elimination of the ground conductor, the cable shields/sheaths function more effectively as screening conductors during ground faults than a parallel GCC. Hence, the voltages induced in parallel cables, communication lines, pipe lines, fences, etc., are less during ground faults in a cross-bonded system than for a similar single-point bonded system.

6.7.3 Choice of cross-bonded system

For long cable circuits, there is a choice between sectionalized cross bonding (see 6.5.3 and 6.5.4) and continuous cross bonding (see 6.5.5). The relative advantages are as follows.

6.7.3.1 Advantages of sectionalized cross bonding

a) Since each major section forms a separate electrical mesh, it is relatively straightforward to calculate the shield/sheath currents when the lengths or spacing of the minor sections are not uniform. In a non-uniform section having an equilateral cable configuration, the ratio of shield/sheath loss with cross bonding to that with solid bonding is given by Equation (1):

( )[ ]32312131 λλλλλλ ++−=yx

(1)

Copyright © 2014 IEEE. All rights reserved.

21

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 34: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

where

x is cross-bonded loss y is solidly bonded loss λ1, λ2, λ3 are per unit lengths of the three minor sections; that is: λ1+λ2+λ3=1

EXAMPLE: When λ1 = 0.4, λ2 = 0.2, λ3 =0.4, the loss with cross-bonded shields/sheaths is 4% of the loss compared with solidly bonded shields/sheaths.

b) The shield/sheath bond at the junction of each major section allows fault current due to a cable failure to be distributed among the three shields/sheaths except within the major section containing the fault.

c) The shield/sheath bonds and grounds at the junction of major sections tend to reduce transient shield/sheath voltages.

d) The number of shield/sheath voltage limiters required is reduced.

e) The shield/sheath bonds at the junction of major sections ensure that there will be no charging current flow beyond the neutral points of the bonds irrespective of any inequality in the lengths of the minor sections.

6.7.3.2 Advantages of continuous cross bonding

a) The effects of non-uniform minor sections can be reduced when they form part of a total shield/sheath circuit containing a number of sections. It may also be possible to use a total number of sections not exactly divisible by three.

b) It is possible to monitor shield/sheath currents throughout the whole circuit, irrespective of the number of minor sections, at one point along the length.

c) At least for low resistance faults, the monitoring of the shield/sheath insulation and shield/sheath voltage limiters becomes easier because there are only two shield/sheath bonds and ground links to be removed, even on a long circuit, to enable tests to be applied from the ends of the cable circuit.

6.8 Sheath standing voltage

6.8.1 Single-point bonding

Figure 1 shows the shield/sheath voltages per kilometer due to balanced loads in the cable conductors.

6.8.2 Sectionalized cross bonding

In a minor section, the shield/sheath standing voltage per kilometer will be as stated in Figure 1 and the longest minor section should be taken for calculating the maximum standing voltage. With the modified bonding method described in item a) in 6.5.4, the maximum standing voltage thus calculated is reduced as much as 13% (see Annex D, D.4). This maximum reduction applies when the two short lengths (or subsections) are equal (that is, L1 = L2 = 0.5L). See Figure 10 and Figure 11.

When the major section is non-uniform, the shield/sheath standing voltage can be taken as that calculated for the longer of the two grounded minor section lengths. When the non-uniformity causes appreciable shield/sheath current, there will be some reduction of the shield/sheath standing voltage.

Copyright © 2014 IEEE. All rights reserved.

22

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 35: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

6.8.3 Continuous cross bonding

When the whole system between shield/sheath bonds consists of a number of uniform minor sections exactly divisible by three and the cables are transposed so that each conductor occupies each of the three positions for one third of the total length, then no shield/sheath current flows, and the maximum shield/sheath standing voltages per kilometer for each section are as stated in Figure 1. In a practical system having variable lengths of minor sections, the shield/sheath standing voltage can be taken as that calculated for the longest minor section length. The shield/sheath standing voltages are reduced when appreciable shield/sheath current flows.

6.8.4 Double-circuit systems

Where two closely spaced circuits are present, the shield/sheath standing voltages are modified by the presence of the second circuit.

Because of the infinite variety of geometrical arrangements coupled with differences in individual cable loading and phase rotation, a universal solution to shield/sheath standing voltages on multiple circuits cannot be given here. Some of the more common double-circuit geometries are described in Kuwahara and Doench [B32] and Simmons [B46].

A general solution requires the use of a digital computer and linear algebra. However, when discretion is used in the selection of phase rotation and position, the effect of adjacent circuits does not significantly increase standing voltages provided these circuits have equal or lower balanced phase currents.

A solution to a simple parallel double circuit is given in Annex D, D.2.4.

6.9 Transient voltage analysis

It is well known (Marti, Grainger, and Morched [B34] and Itoh, Nagaoka, and Ametiani [B29]) that relatively high shield/sheath transient voltages can occur when transmission cable shields/sheaths are single-point bonded or cross-bonded to minimize induced shield/sheath currents. A study by Ontario Hydro (Erven and Ringler [B19]) reported that the shield/sheath to ground voltages at cross-bonding locations can reach 20% of the magnitude of the incoming surge on the main conductors, while voltages across the shield/sheath joint insulators can reach 40% the magnitude of the incoming surge. These transient overvoltages are typically caused by the following:

a) Lightning current impulses entering an underground cable system from overhead lines

b) Fault conditions

c) Switching transients, such as line energization Sheath voltage limiters (SVLs) are commonly used to limit the voltage of the cable shields/sheaths during transient overvoltage conditions; however, the amount of energy that the SVLs must dissipate increases with lower protective levels and increased distances between SVLs.

The shield/sheath overvoltages are primarily the result of two factors. The first is the mutual coupling among the cable phases that occurs when the magnetic flux created by one cable links the other cables in the same trench. The second transient overvoltage phenomenon is caused by the discontinuity to traveling waves presented by the shield/sheath interrupts. Traveling waves created by lightning, switching, and faults reflect at the shield/sheath interrupts, resulting in superposition of the incident and reflected waves.

Copyright © 2014 IEEE. All rights reserved.

23

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 36: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

While it is possible to estimate the power frequency component of fault-current-initiated shield/sheath overvoltages using methods described in the other sections of this guide, more sophisticated calculation tools are required to accurately model transient shield/sheath voltages and to determine the amount of energy that SVLs must dissipate due to high frequency (i.e., traveling wave) transients. Prior to the development of computer simulation tools for power systems electrical transients, such as the electromagnetic transients program (EMTP), it was common practice to make conservative assumptions when specifying equipment for shield/sheath transient overvoltage protection for cross-bonded and single-point bonded cable systems (Dommel [B15]). However, with the trend to longer distances between SVLs and increased standing voltage limits (Emin, Basak, and Ferguson [B17]), it is often necessary to perform EMTP simulations to determine maximum overvoltages and SVL energy dissipation requirements (Erven and Ringler [B19]).

In general, an electromagnetic transients computer program that is capable of modeling frequency dependent effects (see Emin, Basak, and Ferguson [B17]) is required to accurately calculate energy dissipation requirements of SVLs when special shield/sheath bonding methods are used.

7. Sheath voltage limiters

7.1 Introduction

Sheath voltage limiters (SVLs) have been developed to protect shield/sheath sectionalizing insulators and cable jackets from flashovers or punctures caused by transient overvoltages typically associated with the following:

a) Lightning

b) Switching surges

c) Faults

The use of shield/sheath voltage limiters reduces the likelihood of failures for shield/sheath insulators and cable jackets, which was a problem encountered in early installations that utilized special bonding techniques.

The three main types of shield/sheath voltage limiters are as follows:

1) Nonlinear resistances, such as metal oxide varistors (MOVs)

2) Nonlinear resistances, such as silicone carbide (SiC) blocks, in series with spark gaps

3) Spark gaps

The introduction of MOVs into shield/sheath voltage limiter applications offered a number of advantages over older limiter designs incorporating SiC and/or spark gaps. MOV designs offer faster response to transients, a more compact design, and better ac voltage withstand recovery following a transient. Because of these characteristics, MOV based shield/sheath voltage limiters have rapidly displaced other designs. Some limiter designs utilized commercially available metal oxide surge arresters in either a porcelain or polymer housing or a specially designed housing containing MOVs.

Because shield/sheath voltage limiters and associated components can be installed in underground vaults or other outdoor environment, and thus be exposed to weather, moisture, or flooding, these devices should be protected by a suitable casing or encapsulation that permits continuous, proper operation under potentially adverse conditions. Appropriate access control to the devices should be provided for periodic checks and maintenance of the units.

Copyright © 2014 IEEE. All rights reserved.

24

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 37: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

7.2 Nonlinear resistances

Nonlinear resistances, such as MOVs, can provide good protection from transient voltages. MOVs exhibit a conduction curve with a sharply defined knee that breaks the curve into two linear resistance segments. Conduction current is very small below the knee as applied voltage rises. Once the knee is crossed, current through the device rises rapidly for a small increase in applied voltage. This “voltage clamping” effect shunts overvoltages through the device. MOVs do, however, have a limited capacity to absorb energy, being a thermally limited device, and are not designed to carry the actual 50 Hz/60 Hz fault current. They must be sized to withstand 60 Hz fault-current overvoltages due to system faults external to the cable circuit, although they are not typically expected to survive overvoltages resulting from faults internal to the cable circuit. The surge energy and 50 Hz/60 Hz voltages, to which the resistor is subjected, dictate the required characteristics of the limiter. Distribution class arresters are often adequate for the surge energy requirements when selected to withstand the power-frequency fault voltage without discharging.

Current solid-state SVLs employ for the most part metal oxide varistors zinc oxide (MOV-ZnO) technology. The MOV provides continuous operation under applied service voltage and has negligible power dissipation. Because MOV resistance below the operation threshold is very high, MOVs can allow jacket testing without the need to physically disconnect the SVL. Care must be exercised to stay below the temporary overvoltage capability of the MOV device to prevent damage during high-voltage diagnostic testing.

Progress in the development of MOV-ZnO technology has essentially eliminated the use of other non-linear resistance and spark gap type SVLs in favor of MOVs. Currently available compact MOV SVLs have a high transient energy withstand capability (kJ/kV) and allow a direct connection of SVLs to the lead of a sectionalized joint or base of termination with the other end directly connected to the GCC.

7.3 Nonlinear resistances in series with spark gap

Nonlinear resistance devices like SiC-based materials exhibit an approximately exponential conduction curve without a sharp transition threshold. Consequently, the device may conduct considerable current at normal operating voltages. To limit these energy losses, spark gaps should be inserted in series with the SiC voltage limiter. The voltage flashover characteristics of the gap will control the initiation of conduction while the SiC will provide the needed voltage recovery characteristics. In such designs, although the SiC-based limiter will spark over with a minimum of overvoltage on steeply rising waves, its response will be slowed by the spark gap. The primary advantage of this approach is an improvement in voltage-withstand performance under 50 Hz/ 60Hz overvoltage conditions but at the cost of a slower response for fast rise-time transient overvoltages and the design should be carefully evaluated for the intended application. In contrast, MOV voltage limiters based on ZnO technology have a sharply defined voltage transition threshold and do not therefore require the use of a spark gap.

7.4 Spark gaps

The spark gap is the oldest and simplest of the three types of voltage limiters, and it has some disadvantages. Spark gaps can be physically damaged by high 50 Hz/60 Hz currents following initial spark over (metal vaporizes off the gap electrodes) and the gap response is slow, particularly to very steeply rising transient overvoltages. If the gap length is increased so that 50 Hz/60 Hz fault-current voltages will not maintain an arc, the protection level of the spark gap will be decrease, particularly for steeply rising voltage waves. Some of the simplest spark gap designs incorporated two metal spheres separated by an air gap. The spark gap flashover characteristics depend on the characteristics of the material within the air gap. When the gap is in ambient air, outdoor pollution or changing moisture content in the air can change the surge voltage withstand characteristics of the gap, which could cause flashover at normal operating voltages. To minimize the problem, limiter gaps can be sealed through encapsulation.

Copyright © 2014 IEEE. All rights reserved.

25

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 38: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

A spark gap developed by Ontario Hydro (see Report No. 66-242 [B41]) is claimed to provide improved surge protection reliability compared to a simple spark gap. The electrode arrangement of the spark gap (referred to as a ring gap) is designed to cause a motoring action of the arc that eliminates serious erosion of the electrodes. These spark gaps are capable of conducting arcs of high current densities without deterioration of the electrodes, and are used for protecting cable shields/sheaths at the terminals on circuits up to 10 km in length.

Spark gaps require periodic inspection and maintenance. Gaps should only be used to protect single-point bonded circuits at the terminations, where the gap is readily accessible. Gaps should not be used in cross-bonded systems where the gaps can be installed in underground boxes that are relatively inaccessible.

7.5 Selection of shield/sheath voltage limiters

In selecting a shield/sheath voltage limiter, the following criteria should be considered:

a) The limiter should be suitable for continuous operation with an applied voltage equal to the shield/sheath standing voltage under either normal or emergency loads (6.9).

b) The surge voltage limiter must be designed to dissipate the energy associated with the transient overvoltages impressed upon it.

c) The limiter and the shield/sheath joint insulator must be able to withstand the 50 Hz/60 Hz overvoltages resulting from system faults, including external cable faults. Caution should be used in the selection of nonlinear resistance-type limiters to ensure that they can handle 50 Hz/60 Hz induced overvoltages as discussed in 7.2 (see Annex D).

d) For nonlinear resistance-type (MOV) limiters, a maximum time should be specified for the duration of the 50 Hz/60 Hz overvoltage resulting from fault currents external to the cable. In order to allow for breaker reclosure, the time typically considered is twice that of the maximum fault clearing time of the system.

e) When calculating 50 Hz/60 Hz voltages appearing across shield/sheath voltage limiters, allowance should be made for the limiters that are star or delta connected.

A nonlinear resistance-type limiter should be able to absorb, without damage, the energy dissipated due to switching, including switching associated with a fault external to the cable circuit. Experience and calculations indicate that the energy dissipated in the nonlinear resistances due to switching is not an important design criterion for typical cross-bonded circuits. However, for long single-point bonded circuits or lengths of single-point bonded cable that terminates long circuits, the switching surge energy can be important, and calculations should be made for these cases (see EPRI Project RP-7893-1 [B18], Buller [B9], and Hassler, Potter, Reid, and Secrest [B25]). The calculations should be performed using a computer, since manual methods cannot readily be used because of the presence of the nonlinear circuit element. Typical switching transient waveshapes should be assumed. See Ball and Occhini [B6], Ball, Occhini, and Luoni [B7], Clark and Shanklin [B13], Haga and Kusano [B22], Halperin, Clem, and Miller [B23], Kuwahara and Doench [B32], Ogorodnikov [B36], Watson and Erven [B47], Report No. 66-242 [B41], Report No. 55-286 [B39], and Report No. 62-78 [B40].

7.5.1 Link boxes

7.5.1.1 Introduction

In order to facilitate the installation, protection, and connection of SVLs, various outer coverings or housings are available. At present the following options are predominantly used to protect or house SVLs and connection links:

Copyright © 2014 IEEE. All rights reserved.

26

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 39: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

a) Heat shrinkable tubing b) Box-type enclosures (fiberglass, stainless steel, or non-corroding cast iron)

One of the principal features of link boxes is that these can be provided with a water tight seal. The degree of water tightness can be specified based on external water pressure requirements according to NEMA Type 4X or IEC 60059 (IP Class). Link boxes are expected to be corrosion resistant and match different installation requirements such as pole or gantry mounting, placement in vaults or shallow pits, or at times to be even direct buried. AEIC CS9 also provides some guidance on the selection of link boxes.

7.5.1.2 Heat shrinkable insulation housing

This provides one of the simplest and effective means of moisture protection. An adhesive coated heat shrinkable polymeric sleeve seals the MOV and insulated ground cable(s) to protect the SVL and cable connections from the elements.

7.5.1.3 Box-type enclosures

A box-type enclosure can house the SVL(s), copper links, ground cable terminals, and cable entry sockets. The enclosure may be constructed of fiberglass, stainless steel, or non-corroding cast iron. The cable entry should be designed to accommodate either coaxial insulated cable lead connections or single-conductor insulated cables as required. All mechanical box fasteners should be made of stainless steel to alleviate potential corrosion problems. The cable lead entry socket seals and lugs should be watertight and sealed at the transition between the lug barrel and the core insulation. In addition to the cable entry socket seals, it is essential that the cable lugs be watertight and sealed at the transition between the lug barrel and core insulation. Water tight seals should be tested to a maximum external pressure of 100 kPa (14.5 psig). When appropriately designed, the enclosure can be direct buried or located inside an underground vault or concrete pit for mechanical protection and subsequent accessibility. Metal box enclosures may be installed on a gantry or pole since these provide a more durable and vandal resistant enclosure than fiberglass. The design of the enclosure should also incorporate an interlock system that provides entry only with an appropriate tool/key to prevent inadvertent or improper connection settings.

Hazardous voltage can be present within the SVL enclosure. It is, therefore, important to follow appropriate safety procedures to protect personnel accessing the enclosure.

7.5.2 Bonding leads

Connection between SVLs and the shield/sheath of a power cable requires proper insulation coordination, taking into account insulation withstand of bonding leads, shields/sheaths, insulators, and the protective level of the shield/sheath voltage limiters. In general, it is desirable to keep bonding lead lengths as short as possible to provide proper protection against steep fronted overvoltages. Bonding leads should preferably use a low surge impedance coaxial cable design. When the use of coaxial leads is impractical due to equipment or other physical constraints, the following guidelines are suggested as a means of limiting surge protection:

a) For lead lengths of up to 3 m (10 ft), non-twisted pair of single-conductor cables can generally be employed without too much protection compromise.

b) For bonding lead lengths of between 3 m to 10 m (10 ft to 33 ft), use of twisted pair of single-conductor cables may be employed. Alternatively, when twisting is impractical, paralleling of leads with periodic ties to keep leads in close proximity to one another as much as possible should be employed.

Copyright © 2014 IEEE. All rights reserved.

27

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 40: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

c) For bonding lead lengths of between 10 m to 15 m (33 ft to 49 ft), coaxial designs are strongly suggested.

d) Bonding lead lengths greater than 15 m (49 ft) should be avoided.

Bonding leads should be as a minimum insulated as 600 V class cables and sized based on fault current duty. ICEA Publication P-32-382 provides a method for determining conductor size as a function of short circuit rating requirements. AEIC CS9 also provides some general guidance on the selection of bonding leads.

For lower impedance and faster transient response, the bonding lead constructions in Table 1 are suggested.

Table 1 ―Recommended bonding lead constructions

System kV

Single-conductor bonding cable Coaxial bonding cable

Copper conductor

size (kcmil)

XLPE/EPR/PVC insulation thickness (mm/mils)

Size of inner and outer Cu

conductor (Size of each)

(kcmil)

XLPE/EPR/PVC insulation thickness

Inner layer (mm/mils)

Outer layer (mm/mils)

69 4/0 3.3/130 4/0 4.4/175 3.3/130 115 to 138 500 3.3/130 500 4.4/175 3.3/130 161 to 230 750 3.3/130 750 4.4/175 3.3/130 345 to 500 1000 3.3/130 1000 6.6/260 3.3/130

The bonding cable insulation material(s) should be UV resistant and if feasible, the outer most layer of the coaxial design as well as that of the single-conductor cable should preferably be coated with a semiconducting layer of graphite or an extruded semiconducting polymeric layer in order to facilitate field testing.

The minimum recommended Basic Impulse Level (BIL) withstand of shield/sheath interrupts is as shown in Table 2.

Table 2 ―BIL withstand for shield/sheath interrupts

BIL withstand of joint shield interrupts Peak kV of 1.2 × 50 μs wave

System kV Across halves Each half to ground 69 to 138 60 30 161 to 230 80 40 345 to 500 120 60

7.5.3 Power cable jackets

From an electrical standpoint, the principal function of the power cable jacket on a specially bonded cable system is to electrically isolate the cable shield/sheath from ground. Depending on the system design, sustained voltage levels comparable to those seen on secondary cables can be realized on the metallic shield during normal operation and transient voltage levels in the 100 kV range and higher can be attained during lightning, switching, or fault conditions. These voltages can result from a local ground potential rise relative to a remote ground and may not be limited by surge protective devices depending on the circuit configuration. Under some conditions, a back flash can occur from the surrounding earth to the remotely grounded cable shield/sheath, leading to a puncture of the jacket material. Consequently, the jacket electrical insulating integrity needs to be checked periodically in order to assure operational reliability.

Copyright © 2014 IEEE. All rights reserved.

28

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 41: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

To achieve a reasonable likelihood for maintaining jacket integrity, an extruded layer of insulating grade polyethylene (PE), polyvinylchloride (PVC) or equivalent jacketing material is typically provided over the metallic shield/sheath in accordance with ANSI/ICEA S-108-720. The jacketing material needs to possess the appropriate dimensional and physical characteristics for the intended application and should be UV resistant. An insulating jacket should also preferably be coated with a semiconducting layer of graphite or an extruded semiconducting polymeric layer in order to facilitate electrical field testing of the jacket prior to and after installation, and periodically thereafter.

7.6 Use of shield/sheath voltage limiters

7.6.1 Single-point bonded cables

SVLs are connected between the non-solidly-grounded end of the power cable shield/sheath and ground. A separate limiter is connected to the cable shield/sheath at the base of each non-solidly-grounded cable termination or non-solidly-grounded side of a joint shield interrupt with the opposite cable end or side of a shield interrupt being solidly grounded. Generally, the end of the cable circuit that is liable to be subjected to the higher incoming transient voltages, due to lightning or switching, should be grounded. However, when the ground resistance is very much lower at one end, it is preferable to ground the shield/sheath at that end instead. It may also be preferable to install the shield/sheath voltage limiter inside a substation or other protected location, since there is some risk of explosive failure of the limiter. In any case, sheath joint insulator, cross-bonding location, or surge voltage limiter should not be accessible to the public due to safety considerations.

7.6.2 Cross-bonded systems

In direct-buried installations, cross-bonding connections are made with links in surface link boxes, so that individual cable shields/sheaths can readily be isolated for voltage testing of cable jackets. The shield/sheath voltage limiters are then located in or adjacent to the link boxes so that maintenance is possible by removing the link box cover. In these installations, the connections between the buried joint and the link box may be as long as 10 m (33 ft) but should not exceed 15 m (49 ft). Remote placement of the link box decreases the effectiveness of surge protection on the shield/sheath because lead lengths become longer and introduce additional voltage drop between the shield/sheath of the power cable and the surge voltage limiter. This can introduce sufficient voltage drop to limit the effectiveness of the SVL and cause shield/sheath sectionalizing insulator failure or cable jacket puncture. Bonding leads should be of the low surge-impedance coaxial cable type and as short as possible to minimize the effect of the connections on the efficiency of the shield/sheath voltage limiters. The bond leads must be capable of carrying the system short-circuit currents.

In tunnels or other installations where the joints are in vaults, the shield/sheath voltage limiters should be connected across the shield/sheath sectionalizing insulators with relatively short leads whenever feasible. The cross-bonding leads should also be as short as possible to minimize the effect of frontal wave surges, and the conductor cross section must be adequate to carry system short-circuit currents.

8. Effect on parallel communication and control cables

Power cables can inductively influence the currents and voltages on the shields/sheaths of communication and control cables when these are located in close proximity to power cables, even when special bonding methods are applied. The magnitude of voltages and currents induced in communication and control cables can be evaluated as described in Annex D. Annex D, D.3, provides guidelines for use in reducing such

Copyright © 2014 IEEE. All rights reserved.

29

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 42: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

interference based on optimization by transposition of circuit geometry. Some additional factors influencing coupled interference are briefly examined in the following subclauses.

8.1 Coupling

The coupling of the power circuit to the communication and control circuit is evaluated in terms of the mutual impedance. Residual or zero-sequence components of the power circuit often have a ground return (that is, overhead lines). The induced currents in the communication and control cable shield/sheath also return through the ground. Although most of the zero-sequence components of buried power cable typically return through the shield/sheath or separate neutral conductor, some portion can return through the ground. These factors introduce uncertainties in the calculations of the mutual impedance, which can, however, be calculated with reasonable accuracy using Carson’s equation (see Carson [B10]). Since the magnitude of the ground return current has a relatively large effect on the mutual impedance, the approximation that all zero-sequence current returns through the shield/sheath cannot be made.

While the coupling of the fundamental power frequency under steady-state balanced conditions can be minimized by suitable transposition, odd triple harmonics (3rd, 9th, 15th, etc.) can be present that add in phase, and therefore, are not neutralized by circuit geometry.

8.2 Shielding

The design of the communication and control cable shield/sheath and other outer coverings is a fundamental factor in the reduction of the voltage induced in the communication and control cable pairs. The reduction factor (often referred to as shielding factor) is defined as the ratio of the induced electromotive force (emf) between the cable conductors and ground to the longitudinal emf that is induced when metallic cable coverings are absent. It can be expressed (where nonmagnetic materials are used) as shown in Equation (2).

( )22e

uLR

Rrω+

= (2)

where

ru is the reduction factor of the communication cable R is the dc resistance of the grounded metallic cable coverings including the ground resistances,

Ω/km ω is the angular frequency = 2πf Le is the inductance of the ground circuit, H/km (approximately 2 mH/km)

From Equation (2), it can be seen that the induced longitudinal or common mode voltage on the enclosed pairs of the cable is equal to the IR drop in the shield/sheath ground circuit, including the grounding resistances. It is, therefore, fundamental to provide low-resistance grounds. The use of magnetic materials for outer coverings improves the shielding efficiency substantially, unless the magnetic field strength results in saturation.

8.3 Common-mode and metallic voltages

The common mode voltage or longitudinal voltage is the voltage between the cable pairs and ground. It is the prime consideration relative to connected equipment or personnel hazards and is of prime significance during faults in the power system. The so called metallic voltage is the voltage between the two wires of a

Copyright © 2014 IEEE. All rights reserved.

30

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 43: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

pair and is manifested by pair to ground imbalance that converts the longitudinal voltage to a transverse voltage. It is associated with noise introduced into the communication circuit. When the affected pair is used in a protective circuit for power circuit relaying, false tripping of a protected power circuit can occur. Objectionable audio noise can be introduced into voice frequency circuits at quite low field strengths by power frequency harmonics. Similarly, disruptive signals can be introduced onto control cables by these same harmonics.

The audio effect is the consequence of the response of the human ear, the sensitivity of which increases rapidly from 50 Hz/60 Hz to 1000 Hz.

It becomes evident that the inductive effects on parallel telephone and control cables are dependent on many factors, including circuit geometries, mutual impedance, frequency, ground resistivity, shield factors, wave shape, design of connected equipment, and the like. Quantitative estimations are facilitated by computer. In unusual situations, where established practice is not applicable, verification by field tests may be required (see Klewe [B31] and Wollaston and Kidd [B49]).

Copyright © 2014 IEEE. All rights reserved.

31

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 44: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

Annex A

(informative)

Bibliography

Bibliographical references are resources that provide additional or helpful material but do not need to be understood or used to implement this standard. Reference to these resources is made for informational use only.

[B1] Accredited Standards Committee C2-2012, National Electrical Safety Code® (NESC®).9, 10

[B2] Adamson, C., Taha, H., and Wedepohl, L. M., “Comparative Steady-State Performance of Cross-Bonded Cable Systems,” Proceedings IEEE, vol. 115, no. 8, pp. 1147–1156, August 1968.

[B3] Adamson, C., Taha, H., and Wedepohl, L. M., “Determination of the Open-Circuit Sheath Voltages of Cable Systems,” Proceedings IEEE, vol. 115, no. 8, pp. 1137–1146, August 1968.

[B4] Arnold, A. H., “The Impedances of a Three-Phase Line of Single-conductor Lead Covered Cables Arranged in a Plane, with the Middle Cable Equidistant from the Two Outer Cables,” Journal IEEE, vol. 67, pp. 90–96, 1929.

[B5] Arnold, A. H., “The Theory of Sheath Losses in Single-conductor Lead-Covered Cables,” Journal IEEE, vol. 67, pp. 69–89, 1929.

[B6] Ball, E. H., and Occhini, E., “Overvoltages in the Sheaths of High-Voltage Cables Due to Special Sheath Bonding Connections,” IEEE Winter Power Meeting, 1964.

[B7] Ball, E. H., Occhini, E., and Luoni, G., “Sheath Overvoltages in High-Voltage Cables Due to Special Sheath Bonding Connections,” IEEE Transactions on Power Apparatus and Systems, vol. PAS-84, pp. 974–988, 1965.

[B8] Berke, L. R., Geer, Jr., E. W., and Tucker, D. R., “Staged Fault Testing of Leased Audio-Tone Relaying Channels Subject to Ground Potential Rise and Induced Voltage,” IEEE Transactions on Power Apparatus and Systems, vol. PAS – 92, no. 1, pp. 89–97, Jan./Feb. 1973.

[B9] Buller, F. H., “A Technique for Calculating Inductance, Reactance, Impedance, and Sheath Voltage of Single-Conductor Cable in Duct Banks,” General Electric Review, vol. 52, pp. 40–44, March 1949.

[B10] Carson, J. R., “Wave Propagation in Overhead Wires with Ground Return,” Bell System Technical Journal, vol. 5, pp. 539–554, Oct. 1926.

[B11] Chaaban, M., “Calculation of Current Distribution and Sheath Losses in Cable Installation with Several Cables per Phase,” Presentation at the ICC Spring Meeting, Colorado Springs, Colorado, May 2002.

[B12] Clark, D. J., and Seth, I. P., “Cross Bonding Single-Core Power Cables,” Electrical Review, pp. 237–242, Feb 10, 1961.

[B13] Clark, W. S., and Shanklin, G. B., “High Tension Single-conductor Cables for Polyphase Systems,” Transactions AIEE, vol. 38, p. 917, 1919.

[B14] “Design of Special Bonded Cable Systems,” Paper presented by Working Group 07 of Study Committee No. 21, Electra, May 1973, pp. 55–81 and “Design of Specially Bonded Cable Circuits, Part II, Second Report of Working Group 07 of Study Committee No. 21, Electra, no. 47, July 1976.

9 National Electrical Safety Code and NESC are registered trademarks and service marks of The Institute of Electrical and Electronics Engineers, Inc. 10 The NESC is available from The Institute of Electrical and Electronics Engineers (http://standards.ieee.org/).

Copyright © 2014 IEEE. All rights reserved.

32

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 45: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

[B15] Dommel, H. W., “The EMTP Theory Book, Second Edition,” The University of British Columbia, 1994.

[B16] Dunsheath, P., “33 kV Cables with Metal-Sheathed Cores, with Special Reference to the S.I. Type,” Journal IEEE, vol. 65, pp. 469–478, 1927.

[B17] Emin, Z., Basak, P. K., and Ferguson, C., “Simulation Studied to Improve Design for Mid-Life 275 kV Cable Refurbishment,” paper submitted to IEEE Aug. 2001.

[B18] EPRI Project RP-7893-l, Accessories for Specially Bonded Extruded Dielectric Transmission Cable Systems, Electric Power Research Institute, Palo Alto, CA.

[B19] Erven, C. C., and Ringler, K. G., “Development of Improved Sheath Crossbonding Joint Protectors for Self Contained Underground Cables,” Report for the Canadian Electrical Association, DEA No. 072 T 223, Ontario Hydro Research Division, 1986.

[B20] Fallou, M., “Application of Symmetrical Components to the Calculation of the Voltage Rise of Metallic Single Core Cable Sheaths Due to Short Circuit from Phase-to-Ground,” General Electric, vol. 27, no. 6, pp. 358–364, 1963.

[B21] Fisher, H. W., “Losses, Induced Volts and Amperes in Armor and Lead Cover of Cables,” AIEE Transactions, vol. 29, Part II, pp. 747–767, 1989.

[B22] Haga, K and Kusano, T., “Surge Phenomena on the Sheaths of Cross-Bonded, Three-Phase Cable Systems,” Journal Institute of Electrical Engineers of Japan, p. 1580, 1959.

[B23] Halperin, H., Clem, J. C., and Miller, K. W., “Transient Voltages on Bonded Cable Sheaths,” AIEE Transactions, vol. 54, pp. 73–82, 1935.

[B24] Halperin H., and Miller, K. W., “Reduction of Sheath Losses in Single-Conductor Cables,” AIEE Transactions, vol. 48, pp. 299–416, April 1929.

[B25] Hassler, S. P., et al., “M.O.V. Arrester Protection of Shield Interrupts, on 138 kV Extruded Dielectric Cables,” IEEE Transactions on Power Apparatus and Systems, vol. PAS-103, pp. 3334–3341, Nov. 1984.

[B26] Hassler, S. P., et al., “Shield Interrupt Overvoltages on 138 kV Extruded Dielectric Cables,” IEEE Transactions on Power Apparatus and Systems, vol. PAS-103, pp. 3327–3333, Nov. 1984.

[B27] IEC 60287-1-3:2002, Electric cables, Calculation of the current rating, Part 1–3: Current rating equations (100% load factor) and calculation of losses–Current sharing between parallel single-core cables and calculation of circulating current losses.

[B28] “Induced Voltages in the Sheaths of Cross-Bonded AC Cables,” Proceedings IEEE, vol. 113, no. 12, pp. 1990–1994, Dec. 1966.

[B29] Itoh, Y., Nagaoka, N., and Ametiani, A., “Transient Analysis of a Cross-bonded Cable System Underneath a Bridge,” IEEE Transactions on Power Delivery, Vol. 5, No. 2, April 1950.

[B30] Kellam, B., Report No. 62-1, Problems and Experiences with Protective Jackets on Metal-Sheathed Cables, Ontario Hydro Research Division, Toronto, Ontario, Canada.

[B31] Klewe, H. R. S., Interference between Power Systems and Telecommunication Lines, London, Arnold, 1958.

[B32] Kuwahara, K., and Doench, C., “Evaluation of Power Frequency Sheath Currents and Voltages in Single-conductor Cables for Various Sheath-Bonding Methods,” IEEE Transactions on Power Apparatus and Systems, Special Supplement, Item 3784, pp. 206–235, 1963.

[B33] Lodwig, S. G., “Matrix Methods for Determining Voltages and Currents in Cross-bonded 138 kV XLPE Transmission Circuits,” Minutes of the Insulated Conductor Committee, Charlotte, North Carolina, May 1999.

[B34] Marti, L., Grainger, T. E., and Morched, A., “Sheath Overvoltages In HV Underground Cables,” CIGRE Paper 33-201, 1996.

Copyright © 2014 IEEE. All rights reserved.

33

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 46: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

[B35] Miller, K. W., “Sheath Currents, Sheath Losses, Induced Sheath Voltages and Apparent Conductor Impedances of Metal-Sheathed Cables Carrying Alternating Currents,” Electric Engineering Thesis, University of Illinois, 1929.

[B36] Ogorodnikov, V. E., “Surges on Metallic Cable Sheaths,” Canadian Electrical Association Winter Meeting, Paper, Montreal, 1964.

[B37] Petty, K. A., “Calculation of Current Division in Parallel Single-Conductor, Power Cables for Generating Station Applications,” Proceedings of the IEEE/PES 1989 Summer Meeting, Long Beach, California, July 9–14, 1989.

[B38] Pirelli, High-voltage Cable Standards, Volume II, 1988.

[B39] Report No. 55-286, Cable Sheath Bonding Methods, Ontario Hydro Research Division, Toronto, Ontario, Canada.

[B40] Report No. 62-78, Protection of Sheath Insulating Joints on High-Voltage Cable Circuits, Ontario Hydro Research Division, Toronto, Ontario, Canada.

[B41] Report No. 66-242, A Spark Gap for Protection of Underground Cable Sheaths at the Terminal, Ontario Hydro Research Division, Toronto, Ontario, Canada.

[B42] Rhodes, D. G., and Wright A., “Induced Voltages in the Sheaths of Cross-Bonded AC Cables,” Proceedings IEEE, vol. 113 (1), pp. 99–110, 1966.

[B43] Riley, B. W., “Estimation of Voice Frequency Noise in Communication Circuits,” Proceedings of the 19th International Wire and Cable Symposium, Atlantic City, pp. 144–154, Dec. 1970.

[B44] Schurig, O. R., Kuehni, H. P., and Buller, F. H., “Losses in Armored Conductor Lead Covered AC Cables,” AIEE Transactions, vol. 48, pp. 417–435, April 1929.

[B45] Searing, H. R., and Kirke, W. B., “Reduction of Sheath Losses in Single-Conductor Cable,” Electrical World, vol. 92, pp. 685–688, Oct. 6, 1928.

[B46] Simmons, D. M., “Calculation of Electrical Problems of Underground Cables,” The Electric Journal, vol. 29, May-Nov. 1932.

[B47] Watson, W., and Erven, C. C., “Surge Potentials on Underground Cable Sheath and Joint Insulation,” AIEE Transactions, pp. 239–249, June 1963.

[B48] Wedmore, G. B., Morgan, P. D., and Whitehead, S., “A Critical Study of a Three-Phase System of Unarmored Single-Conductor Cables, from the Standpoint of the Power Losses, Line Constants, and Interference with Communication Circuits,” Journal IEEE, vol. 67, pp. 359 – 434, 1929.

[B49] Wollaston, F. D., and Kidd, K. H., “Cable Sheath Jacket Requirements to Withstand Abnormal Voltage Stresses,” AIEE Transactions on Power Apparatus and Systems, part III, pp. 1116–1123, Feb. 1962.

[B50] Woodland Jr. F., “Electrical Interference Aspects of Buried Electric Power and Telephone Lines,” IEEE Transactions on Power Apparatus and Systems, vol. PAS-89, no. 2, pp. 275–280, Feb. 1970.

Copyright © 2014 IEEE. All rights reserved.

34

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 47: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

Annex B

(informative)

Discussion of early practices and problems

Early self-contained cables were insulated with a combination of oil and paper and were constructed with a metallic sheath, which acted both as a barrier to moisture ingress and as a return path for fault currents. The most common sheathing material was lead, and outside of the U.S. these cables were frequently installed with a protective jacket with the sheaths solidly grounded.

In North America, they were usually installed in ducts and underground vaults often without a protective jacket. In Europe, particularly in Britain, cables were often armored and directly buried. Many of these directly buried cables were protected with hessian wrappings and bituminous compounds. As a general rule, power losses in the sheaths were recognized but accepted.

As system voltages and currents increased, these losses assumed a greater importance, and various methods of reducing these losses were devised over the years from 1910 to the mid-1930s. Most of these methods required the use of insulators inserted in the sheaths to break the sheath circuit into smaller electrical sections.

Although these systems were reasonably successful, the sheath insulators were often a source of problems because of leaks that permitted cable oils to leak out and moisture to penetrate the cables.

Because of factors, such as ac corrosion and personnel safety, and also because of a natural reluctance to depart too far from the practice of solidly grounding the sheaths, a sheath voltage limit of approximately 12 V to 17 V seems to have been commonly adopted in the early days.

Copyright © 2014 IEEE. All rights reserved.

35

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 48: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

Annex C

(informative)

Current practice for shield/sheath standing voltages

C.1 North American practice

C.1.1 United States

There are currently no generally accepted limits for maximum steady-state sheath standing voltage levels used in the U.S. Through the late 1960s, limits of up to about 17 V were imposed on non-jacketed lead sheathed cables in order to protect the bare lead against electrolytic corrosion. Subsequently when jacketed cable designs were introduced, steady-state sheath voltage design limits were increased to 65 V to 90 V, although there has not been much evidence to substantiate this use in the past.

Due to the lack of maximum sheath voltage limits in industry standards, current practice in the U.S. varies significantly among electric utilities. However, there has been a trend to increase the normal operating condition sheath voltage limits during the past decade. Most single-conductor underground cable systems with a length of greater than several thousand feet are designed with a maximum sheath voltage of 100 V to 200 V during normal operating conditions. Sheath voltages during emergency operating conditions are generally limited to voltages of less than 275 V. However, at least one underground cable system was designed with a maximum sheath voltage of 447 V during emergency operating conditions.

Some examples of current U.S. practices are as follows:

a) A 138 kV XLPE cable system installed by one utility with cross-bonded sheath was designed for a maximum induced sheath voltage of 202 V. The maximum sheath section length for this cable system is 3035 ft and the rated current is 1400 A.

b) A 120 kV XLPE cable system installed by another utility utilizes single-point bonding and was designed for a maximum voltage during normal operating conditions of 163 V. The maximum sheath voltage during emergency operating conditions can be as high as 447 V. The maximum sheath section length for this cable system is 7279 ft. The maximum currents during normal and emergency operating conditions are 510 A and 1400 A, respectively.

C.1.2 Canada

In Canada, practice varies from province to province. In their installations of underground low-pressure fluid-filled (LPFF) cables, one utility utilizes the sectionalized cross-bonding method to minimize sheath losses and also provide a low-impedance path for fault current. At all cross-bonded positions, 3 kV lightning arresters were installed to minimize the effects of transient overvoltage on the sheath and joint casing insulation.

Until about the 1990s, the practice was to limit sheath bonding and grounding arrangements such that the standing sheath voltage at maximum load current did not exceed 100 V to ground at any point along the cable.

In more recent years, with increased load current demands, longer circuit length installations, and present day single-conductor high-voltage cable designs, the standing voltage levels are being designed to operate in some instances with maximum standing voltages of up to 600 V. To ensure the system will adequately

Copyright © 2014 IEEE. All rights reserved.

36

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 49: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

withstand anticipated transient overvoltages, the components on the circuit acted on by these overvoltages are subjected to specified withstand levels with respect to ac and impulse voltages.

One utility has installed cross-bonded cable systems in the past without any sheath sectionalizing joint insulator protection. However, some joint insulators failed in service, causing the system to be considered unsatisfactory for use without some method of joint insulator protection. Subsequently, the utility adapted the use of single-point bonding with ring gaps at the terminals. Standing sheath voltages of 300 V to 400 V on emergency load were permitted at the terminals.

One rather unusual method of bonding had been successfully employed by another utility for cable routes with unequal lengths between underground vaults and can be described as a modified sectionalized cross-bonding scheme and described in detail in 6.5.4 of this guide.

C.2 Practices outside of North America

C.2.1 Great Britain

In Britain, cables have from very early days employed some form of outer jacket over the sheath. Initially these were constructed by lapping various layers of self-vulcanizing rubbers and PVC in conjunction with bitumen compounds in hessian tapes. Because these were electrically sound and of reasonable electrical strength, it was judged that, even when special bonding came into vogue, there was little likelihood of sheath voltages ever becoming high enough to puncture any form of anticorrosion jackets. Polyvinyl chloride, polyethylene, and high-density polyethylene extruded jackets have replaced these more complicated constructions.

Special bonding circuits were introduced into Britain in the late 1950s, at which time the maximum standing sheath voltage was limited to 50 V for below ground applications and to 25 V at the terminations. These maximum permissible levels were mandated by the central electricity generating board (CEGB) from 1959 to 1965, and subsequently increased to 65 V on cable sheaths in below ground installations. The reason for selecting 50 V in the 1950s is not clear, but it was increased to 65 V because it was affecting cable shipping lengths and increasing circuit installation costs.

The 65 V value is commonly used, except in special cases and in CEGB-owned tunnel installations. The River Severn cable circuit, for example, operates with an induced sheath voltage of 100 V at full load along the route, but the voltage on the sheath at the terminations is limited to 25 V.

C.2.2 Netherlands

In the Netherlands, a recognized limit on sheath voltages has not been agreed upon. The maximum sheath voltage currently reported as being used in the Netherlands for 400 kV extruded dielectric cables with polymeric cable jackets is 400 V.

C.2.3 France

In France, a value of 125 V was originally considered taking into account the risk of fatal contact but a conservative value of 50 V was adopted as a first step. In 1987, some tests showed that a value of 200 V would be acceptable even in the case of a sheath fault if protection devices were installed but with the specific requirement that personnel avoid contact with any related cable system components that could develop a voltage. In 1994 a maximum value of 400 V was permitted under normal operation but in practice this limit is generally not reached due to other design considerations that include: typical length of

Copyright © 2014 IEEE. All rights reserved.

37

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 50: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

elementary sections, load current design in the order of about 2000 A, and short-circuit current design criteria of about 30 kA.

C.2.4 Norway

In Norway, a fixed voltage limit has not been agreed upon, but in practice a sheath voltage limit of 60 V is used.

C.2.5 Italy

In Italy, a fixed voltage value has not been agreed upon, but exposed metal parts are typically limited to approximately 25 V.

C.2.6 Japan

In Japan, designs typically employ standing voltages of up to 200 V.

C.2.7 Other countries

Table C.1―Shield/sheath standing voltage limits in some other countries

Country Rated system voltage (kV)

Shield/sheath voltage limit

(V) UAE/Dubai 132 65

UAE/Other locations 132 12 Oman 132 65

Saudi Arabia 132 100 Saudi Arabia 230 to 380 200

Turkey 154 150 Turkey 380 200 Kuwait 275 65 Kuwait 400 200

Singapore 66 60 Singapore 230 120 Australia 132 150 Australia 330 250

South Korea 154 to 345 100

Copyright © 2014 IEEE. All rights reserved.

38

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 51: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

Annex D

(informative)

Calculation of induced voltages

D.1 Induced voltages—general

Any conductor p, lying parallel with a set of three conductors carrying balanced three-phase currents, will have a voltage gradient Ep induced along its length, given by Equation (D.1):

( )

+

×= −

ap

cpe

bp

cpapebp S

Sj

S

SSIjE log

23log

21102 2

7ω V/m (D.1)

where

Ib is the rms current (A) in conductor b ω is the angular frequency of the system (2πf) Sap is the axial spacing of the parallel conductor and phase a conductor Sbp is the axial spacing of the parallel conductor and phase b conductor Scp is the axial spacing of the parallel conductor and phase c conductor

These spacings may be in any convenient common unit.

It is assumed that the phase rotation is such that Ia = aIb and Ic = a2Ib

where

23

21 ja +−=

Ib=Io(1+j0) Io is the magnitude of the load current

Clearly, as the spacing of the parallel conductors increases in relation to the mutual spacing of the groups of cables, the induced voltage tends to zero. Similarly, if the three cables of the group are regularly transposed at even intervals, the induced voltages in the parallel conductor sum to zero over a complete cycle of transposition.

D.2 Voltage gradients induced in the cable shield/sheath

The voltage gradient induced in a cable shield/sheath may be considered as a special case in which the parallel conductor is a shield/sheath at a spacing from the conductor that it embraces equal to the mean radius of the shield/sheath. When no other current-carrying conductor is in the vicinity, the three shield/sheath voltage gradients for a group of cables in any formation carrying balanced three-phase conductor currents are then given by the following equations.

Copyright © 2014 IEEE. All rights reserved.

39

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 52: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

D.2.1 General case of any cable formation

( )

+

−×= −

dSj

dSSIjE ac

eac

abeaa

2log232log

21102

27ω V/m (D.2)

( )

+

×= −

ab

bce

bcabebb S

Sjd

SSIjE log234log

21102 2

7ω V/m (D.3)

( )

−×= −

dSj

dSSIjE ac

eac

bcecc

2log232log

21102

27ω V/m (D.4)

where

d is the geometric mean shield/sheath diameter (arithmetic mean may be assumed) Sab is the axial spacing of phases a and b Sbc is the axial spacing of phases b and c Sac is the axial spacing of phases a and c

D.2.2 Trefoil formation single circuit

For cables in trefoil where Sab = Sbc = Sac, these equations reduce to Equation (D.5), Equation (D.6), and Equation (D.7), as follows:

( )

+−×= −

dSjIjE eaa

2log23

21102 7ω V/m (D.5)

( )

×= −

dSIjE ebb

2log102 7ω V/m (D.6)

( )

−−×= −

dSjIjE ecc

2log23

21102 7ω V/m (D.7)

D.2.3 Flat formation single circuit

For the other common formation of cables laid flat in which the axial spacing of adjacent cables = S, the shield/sheath voltage gradients are given by Equation (D.8), Equation (D.9), and Equation (D.10).

( )

+−×= −

dSj

dSIjE eeaa

4log23log

21102 7ω V/m (D.8)

Copyright © 2014 IEEE. All rights reserved.

40

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 53: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

( )dSIjE ebb

2log102 7−×= ω V/m (D.9)

( )

−−×= −

dSj

dSIjE eecc

4log23log

21102 7ω V/m (D.10)

D.2.4 Double-circuit systems

It is impossible in this guide to cover all possible combinations of geometry for multiple circuits but a solution to a simple parallel double-circuit follows.

Assumptions:

a) Three or six cables are connected in three-phase circuits.

b) All conductor currents are equal in magnitude.

c) For three cables—any arrangement is permissible. For six cables—point or line symmetry is assumed. This means a line 0-0 or a point 0 can be placed between the two circuits so that the distance from cable a1 to 0 equals the distance from cable a2 to 0, where a1 is the a phase of Circuit 1 and a2 is the a phase of Circuit 2. The same must be true for cables b1 and b2 and c1 and c2.

d) Positive phase-sequence rotation (phase “A” leading) was assumed in the equations. The effect of reversing phase sequence can be simulated on input to the program by interchanging cable positions 1 and 3 and 4 and 6 in the context S1 through S9.

Conductor currents are as shown in Equation (D.11), Equation (D.12), and Equation (D.13):

23

21 jIa +−= (assigned to cables 1 and 4) (D.11)

01 jIb += (assigned to cables 2 and 5) (D.12)

23

21 jIc −−= (assigned to cables 3 and 6) (D.13)

Open-circuit voltages on shields/sheaths to neutral are as shown in Equation (D.14), Equation (D.15), and Equation (D.16):

accabbaaaa jXIjXIjXIE ×+×+×=0 V/m (D.14)

bccbbbabab jXIjXIjXIE ×+×+×=0 V/m (D.15)

cccbcbacac jXIjXIjXIE ×+×+×=0 V/m (D.16)

Copyright © 2014 IEEE. All rights reserved.

41

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 54: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

where the corresponding matrix impedances are as follows:

14

1logSr

kXsm

eaa ×= (D.17)

1512

1logSS

kX eab ×= (D.18)

1613

1logSS

kX eac ×= (D.19)

25

1logSr

kXsm

ebb ×= (D.20)

3523

1logSS

kX ebc ×= (D.21)

36

1logSr

kXsm

ecc ×= (D.22)

And where

k is a constant = 2×ω×10–7=1.257×f×10–6 S12 is distance from cable 1 to cable 2 (meters) S23 is the distance from cable 2 to cable 3 (meters) S13 is the distance from cable 1 to cable 3 (meters) S14 is the distance from cable 1 to cable 4 (meters) S25 is the distance from cable 2 to cable 5 (meters) S36 is the distance from cable 3 to cable 6 (meters) S15 is the distance from cable 1 to cable 5 (meters) S35 is the distance from cable 3 to cable 5 (meters) S16 is the distance from cable 1 to cable 6 (meters) rsm is the mean shield/sheath radius (meters)

Figure 1 of this guide shows values of the shield/sheath voltage gradient calculated from D.2, Equation (D.5), Equation (D.6), and Equation (D.7) for a single circuit in trefoil configuration or Equation (D.8), Equation (D.9), and Equation (D.10) for a single circuit in flat formation as a function of the ratio S/d.

D.3 Screening and transposition

The voltage gradients calculated by the equations in D.2 are due to the magnetic field of the three-phase currents only. When any other current-carrying conductors are in the vicinity, these voltages will be modified. In particular, if any parallel conductor is present that is bonded so as to carry induced current,

Copyright © 2014 IEEE. All rights reserved.

42

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 55: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

then the voltage gradient in any other parallel conductor will be reduced. This reduction depends on the disposition of the conductors and the impedance of the current-carrying loop of which the screening conductor forms a part.

Power cables frequently have communication or protection cables laid with them in the same trench. It is clearly desirable to reduce to a minimum the voltage induction in these parallel cables. When the shields/sheaths of single-conductor power cables are continuous and grounded at both ends of the route, they act as screening conductors and thus reduce somewhat the voltage induction in the parallel cables. In a specially bonded system, however, the power cable shields/sheaths no longer carry currents, and hence the screening effect is absent, at least for balanced loads in the power cables. (During imbalanced loads or faults, sheath currents will flow in the case of cross-bonded cables, and hence an important screening effect is present in this case. There will also generally be a screening effect due to the sheath or armor wires of the parallel cable itself).

The voltage induction in parallel cables resulting from balanced loads can be reduced or eliminated by transposition, and this is particularly desirable for specially bonded cables for the reasons previously given. Transposition has the additional advantage of balancing the impedances of the three-phase cables. The transposition of heavy power cables is not generally practicable except at joint positions, however, and hence the complete transposition cycle of the three phases will occupy three cable lengths. For cable circuits that consist of only one or two lengths, it is not usual to transpose the power cables, but the parallel conductor may be transposed as indicated below.

Figure 2 shows the methods to be used for transposition of the parallel cable or conductor. When the power cables are laid in flat formation with wide spacing, the parallel conductor should be between the power cables at the position shown. If there is insufficient space between the power cables to adopt this position precisely, the parallel conductor should still be between the power cables. If the cables are touching or in trefoil, the parallel conductor should be laid immediately alongside the power cables. In all cases the parallel conductor should be transposed at the center of the section length or route length to an identical position on the other side of the formation.

D.4 Sheath standing voltages (see 6.8.2)

The two corresponding vector diagrams for the cross-bonded sections are shown in Figure D.1.

For Figure 7 and Figure 8 For Figure 10 and Figure 11

Figure D.1—Vector diagrams for cross-bonded sections

On both diagrams, point A corresponds to the grounded positions. In the first diagram the maximum standing voltage will occur at point B and is of magnitude E, whereas in the second diagram the maximum standing voltage will occur at point C and is of magnitude 23 E, then the voltage reduction is ( )231− 100% or 13.4%.

A

Copyright © 2014 IEEE. All rights reserved.

43

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 56: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

Annex E

(informative)

Transient voltages and voltage withstand requirements of protective

jackets

E.1 Power frequency sheath overvoltages

E.1.1 General

System faults produce an initial transient overvoltage followed by a power-frequency shield/sheath overvoltage caused by the passage of the fault current. This power frequency overvoltage is not generally high enough to be important in relation to the shield/sheath insulation design, but, as it persists for the duration of the fault, it can be important in relation to the duty requirements of the shield/sheath voltage limiters.

The cable installation must clearly be capable of safely withstanding the effects of any fault in the system external to the cables. A fault in the cables themselves inevitably involves repair work and hence it is not so important if the shield/sheath insulation adjacent to the fault is also damaged. The shield/sheath bonding design should preclude the damage cascading to other parts of the cable system. Following system faults, shield/sheath voltage limiters can be damaged, requiring inspection and possible replacement. The shield/sheath voltage gradients due to external faults are of three types as classified in Table E.1.

Table E.1—Sheath voltage gradient types

Sheath voltage gradient type Fault current type

Type 1 Three-phase symmetrical fault Type 2 Phase-to-phase fault Type 3 Single-phase to ground fault

The equations for each type of fault are described in E.1.3 and E.1.4.

In deriving these equations, the following simplifying assumptions are made:

a) The short-circuit current is known and is unaffected in value by the characteristics of the cable system.

b) For phase-to-phase and single-phase ground faults, the current in the healthy phase conductor(s) is negligible in comparison with the short-circuit current, except for the case of impedance grounding of the neutral (see E.1.2).

c) No other screening conductors are present (except for the parallel GCC in the case of single-phase ground faults on single-point bonded systems).

d) The system consists of balanced minor and major sections in the case of sectionalized cross bonding and a number of uniform minor sections exactly divisible by three in the case of continuous cross bonding. (For design purposes, it is satisfactory to use these simplified equations also for practical systems in which imbalance does exist.)

Copyright © 2014 IEEE. All rights reserved.

44

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 57: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

E.1.2 Neutral grounding

For three-phase symmetrical faults and phase-to-phase faults, no zero-sequence current flows. The equations given in E.1.3 and E.1.4 for faults of this type are, therefore, equally applicable to systems having the neutral directly grounded or to those having impedance or resonant grounding of the system.

For single-phase ground faults in systems having impedance or resonant grounding, it is no longer permissible to ignore the normal load currents in the system. The calculation of shield/sheath voltages during a single-phase ground fault therefore requires the superposition of the voltages due to the symmetrical positive sequence load currents and those due to the fault currents. The voltages due to the fault current can also be calculated by considering the asymmetrical fault currents as the superposition of an asymmetrical positive sequence system and a zero-sequence system with currents of the same magnitude. The superposition of these currents results in two currents of equal magnitude but separated in phase by an angle of 60° flowing in the unfaulted phases, while the faulted phase remains without current. The shield/sheath voltages resulting from these currents can all be calculated from the following equations and superimposed. However, in general, for systems having impedance or resonant grounding of the neutral, the shield/sheath voltages resulting from single-phase ground faults will be much lower than those due to three-phase symmetrical faults or phase-to-phase faults, and hence for design purposes single-phase ground faults in these systems can be ignored.

E.1.3 Single-point bonding

E.1.3.1 Three-phase symmetrical fault

The shield/sheath voltage gradients are given in D.2, using the appropriate value of I.

E.1.3.2 Phase-to-phase fault

In the general case of any cable formation, assuming a fault between phases a and b with no ground current flowing, when Iab is the fault current, the shield/sheath voltage gradients are shown in Equation (E.1), Equation (E.2), and Equation (E.3):

( )

×= −

dSIjE ab

eaba2log102 7ω V/m (E.1)

( )

×−= −

dSIjE ab

eabb2log102 7ω V/m (E.2)

( )

×−= −

ac

bceabc S

SIjE log102 7ω V/m (E.3)

This results in a maximum for the shields/sheaths of the outer cables laid in a flat arrangement as shown in Equation (E.4):

( )

×=−= −

dS

IjEE eabba4

log102 7ω V/m (E.4)

where S = spacing of adjacent phases

Copyright © 2014 IEEE. All rights reserved.

45

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 58: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

E.1.3.3 Single-phase ground fault (solidly grounded neutral)

Precise calculation of shield/sheath overvoltages for underground-fault conditions requires a knowledge of the proportion of the return current that flows in the ground itself and the proportion that returns by way of the parallel GCC. This depends on a number of factors, which are not usually accurately known. Fortunately, however, the overvoltages of practical interest are those between shields/sheaths and the parallel GCC, and these can be simply calculated by the assumption that this conductor carries the whole of the return current. This assumption is normally accurate and leads to shield/sheath overvoltages that are slightly higher than those observed in practice.

For a ground fault in phase a, and the general case of any cable formation when Iag is the fault current, the shield/sheath-to-ground conductor voltages are shown in Equation (E.5), Equation (E.6), and Equation (E.7):

( )

×+= −

g

agegaga dr

SjRIE

27 2

log102ω V/m (E.5)

( )

×+= −

abg

bgagegbgb Sr

SSjRIE log102 7ω V/m (E.6)

( )

×+= −

acg

cgagegcgc Sr

SSjRIE log102 7ω V/m (E.7)

where

Sag, Sbg, Scg are geometric mean spacings between cables a, b, and c, respectively, and the ground conductor

Rg is the resistance of ground conductor in Ω/m rg is the geometric mean radius of the ground conductor (for stranded conductors take

0.75 of the overall radius)

E.1.3.4 Magnitude of voltages

Typical maximum values of shield/sheath voltages calculated from these equations are given in Figure E.1 for a circuit in flat formation, for a current of 1000 A having a transposed ground conductor. For a three-phase symmetrical fault, the maximum voltage is reached in the outer cables and is the same as in Figure 1 of this guide but increased for higher current. For the phase-to-phase fault, the highest shield/sheath voltage results when the fault is between the outer cables so that Sac = 2S. For a ground fault assuming the ground conductor to be laid as shown in Figure 2 of this guide, see Equation (E.8) and Equation (E.9).

Sag = Scg = S (E.8)

Sbg = 0.7S (E.9)

Copyright © 2014 IEEE. All rights reserved.

46

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 59: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

0

100

200

300

400

500

600

1 10

E (V

/km

); I

= 10

00 A

Ratio S/d

d/rg=1510

5

Three-phase symmetrical fault

Phase-to-phase fault

2 3 5 7 20 30 50

f = 60 Hz

Single phase-to-ground fault

Figure E.1—Induced shield/sheath voltage gradient (sheath-to ground conductor) for various faults in single-point bonded-cable system (flat formation)

The highest of the three-sheath voltages for a fault in phase a is Ea, and since the effect of Rc can generally be neglected, the preceding equation for Ea can be expressed as shown in Equation (E.10):

( )

×= −

geaga r

ddSIjE

27 log102ω V/m (E.10)

Figure E.1 shows the effect of varying d/rg over a typical range of values. It is clear that the overvoltages per meter due to the single-phase fault is much greater than for the other types of fault, for systems having solidly grounded neutral. For systems having impedance or resonant grounding of the neutral, the phase-to-phase fault is the most important.

E.1.4 Cross bonding

E.1.4.1 Three-phase symmetrical fault

The shield/sheath voltage gradients are given by Annex D, D.2.3, Equation (D.8), Equation (D.9), and Equation (D.10), using the appropriate value of I and using the longest minor section length in the case of sectionalized cross bonding or continuous cross bonding.

E.1.4.2 Phase-to-phase fault

It had been previously considered that this is a balanced condition with regard to induced shield/sheath voltages, and as a result no shield/sheath currents would flow. This has been since reassessed and although use of computer calculations is required to arrive at an exact solution, it is generally considered that shield/sheath currents will flow and tend to reduce the induced sheath voltages below that of a three-phase symmetrical fault. In the case of a two phase to ground fault, voltages between sheaths will be strongly influenced by the grounding resistances.

Copyright © 2014 IEEE. All rights reserved.

47

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 60: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

E.1.4.3 Single-phase ground fault

In this case, the returning current divides between the shields/sheaths and ground, and the calculation of shield/sheath voltages becomes more complex. The effect of the ground currents is important in relation to the voltages between shields/sheaths and ground, and to calculate these it is necessary to know the values of ground resistivity and of ground-plate resistance appropriate to the circuit. The voltages between shields/sheaths can be calculated as follows for a sectionalized cross-bonded system (the behavior of continuously cross-bonded cables during faults of this type is still being studied).

E.1.4.3.1 Cables in trefoil

Figure E.2 shows a single major section of cables in trefoil having the shields/sheaths grounded at both ends.

Figure E.2—Single major section of cross-bonded cables during single-phase fault

A current Ix circulates in the path formed by the three shields/sheaths and the ground and divides equally between the three shield/sheath circuits.

The voltages induced in the three shields/sheaths of Figure E.2, minor Section No. 1 are as shown in Equation (E.11), Equation (E.12), and Equation (E.13).

( ) ( )ssssgssx

a RZIZZIE −−+= 23

V/m (E.11)

( ) sgsgssx

b IZZZIE −+= 23

V/m (E.12)

gc EE = V/m (E.13)

where

I is the fault current as shown in Figure E.2

Copyright © 2014 IEEE. All rights reserved.

48

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 61: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

The voltages between shields/sheaths at the cross-bonding points are then shown in Equation (E.14), Equation (E.15), and Equation (E.16).

( )ssssgab RZZIlV +−= V (E.14)

0=bcV V (E.15)

( )ssssgac RZZIlV +−= V (E.16)

where

Zss is the self-impedance of the shield/sheath with ground return in Ω/m, by definition

Zss = ( )

× −

dj e

2log102 7ω (E.17)

Zag is the mutual impedance of shield/sheath with ground return in Ω/m Rs is the resistance of shield/sheath in Ω/m l is the length of minor section in m

These impedances are functions of frequency and of ground resistivity but in these equations this factor disappears and

( )

×= −

dSIljV eab

2log102 7ω V (E.18)

0=bcV V (E.19)

abac VV −= V (E.20)

E.1.4.3.2 Cables in flat formation

When the cables are laid flat, the current I no longer divides equally between the shields/sheaths, but it can be assumed to do so with little error, assuming also that the ground plate resistances are zero.

++

++−=

oigoogss

oigoogsssx ZZZ

ZZRZII

4234233

A (E.21)

where

Zoog is the mutual impedance between shields/sheaths of outer cables with ground return in Ω/m

Copyright © 2014 IEEE. All rights reserved.

49

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 62: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

Zoog = ( )S

j e 21log102 7−×ω (E.22)

Zoig is the mutual impedance between shields/sheaths of inner and outer cables with ground return in Ω/m

Zoig = ( )S

j e1log102 7−×ω (E.23)

Then

( ) ( )

−−++= ssoigoogsx

a RZIZZZIE3

V/m (E.24)

( ) oigoigsx

b IZZZIE −−= 23

V/m (E.25)

( ) oogoigoogssx

c IZZZZIE −++=3

V/m (E.26)

( ) ( )

+−+−= sssoigoigoogx

ab RZZIZZIlV3

V (E.27)

( ) ( )

−+−= oigoogoogoig

xbc ZZIZZIlV 2

3 V (E.28)

( )[ ]oogsssxac ZRZIlV −−= V/m (E.29)

Substituting for Ix in the equations for Vab, Vbc,, and Vac gives Equation (E.30), Equation (E.31), and Equation (E.32).

( )[ ]FRZZZIlV sssoigoogab 3323

+−+= V (E.30)

( )[ ]FRZZIlV soigoogbc 323

+−= V (E.31)

( )[ ]oogsssac ZRZIIlV −−=3

V (E.32)

Copyright © 2014 IEEE. All rights reserved.

50

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 63: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

Where the factor F is defined as:

( )oigoogss

oogoig

ZZZZZ

F423 ++

−= (E.33)

and all terms containing Rs can generally be disregarded. Then,

( ) ( )

×= −

dSIljV eab

3/17 22log102ω V (E.34)

( ) ( )3/27 2log102 ebc IljV −×= ω V (E.35)

( )

×= −

dSIljV eac

4log102 7ω V (E.36)

E.1.4.4 Magnitude of voltages

Figure E.3 shows these voltages between shields/sheaths at the cross-bond position per unit length of 1 m of the minor section length calculated from the equations above for single-phase faults and compared with the voltages due to three-phase symmetrical faults and for phase-to-phase faults and for a short-circuit current of 1000 A. It is evident that the voltage due to the phase-to-phase fault is the greatest.

0

100

200

300

400

500

600

1 10

E (V

/km

); I

= 10

00 A

Ratio S/d

Single-phase fault

Three-phase fault

2 3 5 7 20 30 50

f = 60 Hz

Figure E.3—Maximum induced shield/sheath voltage gradients (sheath to sheath) for various faults of sectionalized cross-bonded cable systems (flat formation)

Copyright © 2014 IEEE. All rights reserved.

51

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 64: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

The shield/sheath voltage limiter generally consists of a star connected device having the star point grounded to a local ground. The resistance of these local ground plates is often high but some current will flow into the ground during a single-phase fault. The calculation of these currents and of the voltages between the shields/sheaths and the ground plates is complex and requires knowledge of the ground-plate resistances and the ground resistivity along the cable route. These values are not generally known, especially at the design stage, and hence it is usual to consider the duty of the shield/sheath voltage limiter only in terms of the voltage between shields/sheaths. Experience and measurements indicate that the shield/sheath-to-ground voltage rise is not generally sufficient to damage the shield/sheath voltage limiter, but, when there is any doubt, the star point should not be grounded, when this is permissible, with respect to transient overvoltages.

Copyright © 2014 IEEE. All rights reserved.

52

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 65: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

Annex F

(informative)

Current and voltage distribution on cable shields/sheaths with multiple

cables per phase

F.1 Scope and objectives

The previous IEEE guide (IEEE Std 575-1988) for shield/sheath-bonding methods was limited to the calculation of induced voltages and currents in cables shields/sheaths of simple three-phase installations having one cable per phase. It provided analytical equations to solve for the shield/sheath induced voltage in case of single-point bonding and for the induced current in the case of bonding at both ends. It did not address the cases of several cables per phase. Experience with such installation (see Adamson, Taha, and Wedepohl [B3]) has shown that the current distribution in the individual cables is not uniform, leading to excessive heating in some cases, and lower temperature rise in others. Also, the shield/sheath Joule losses or induced voltages are very much affected by the relative location of individual cables in the duct bank.

The present document presents a general calculation method based on complex matrix algebra to help the user solving any type of cable configuration in a duct bank. Once the system of equations is assembled, the solution can be obtained readily by using a personal computer. As will be shown later, this method is quite useful in finding the best arrangement of cables/phases in order to reduce the disparity in current distribution between cables and to reduce the shield/sheath Joule losses.

F.2 Calculation methodology

The general method of calculating the induced currents and voltages in shields/sheaths is based on Kirchhoff's laws. The first one states that at a given node in an electrical circuit, the sum of the currents entering equals the sum of the currents leaving. The second stipulates that around any closed loop, the sum of the potential differences across all elements is zero. The following shows the calculation methodology applied on a three-phase circuit. It consists of two parallel cables per phase as shown in Figure F.1 and Figure F.2. The main currents in each phase, IA, IB, and IC are known. The shields/sheaths are solidly bonded at both ends, together with a parallel GCC. The number of unknowns in this case is 13, namely the current in each individual conductors, the induced current in each shield/sheath, and the induced current in the continuity conductor. Therefore, 13 equations are needed.

Applying Kirchhoff’s first law on the shield/sheath node gives us Equation (F.1):

gwncncnbnbnanan IIIIIIII ++++++==∑ 2121210 (F.1)

Applying Kirchhoff’s first law on the node formed by conductors a1 and a2 gives us Equation (F.2):

2101 aaA IIjI +=+= (F.2)

Applying Kirchhoff’s first law on the node formed by conductors b1 and b2 gives us Equation (F.3):

218666.05.0 bbB IIjI +=−−= (F.3)

Copyright © 2014 IEEE. All rights reserved.

53

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 66: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

Figure F.1—Example of 6 parallel cables, 2 cables per phase

Figure F.2—Loops formed by the shields/sheaths of the installation shown in Figure F.1

Copyright © 2014 IEEE. All rights reserved.

54

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 67: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

Applying Kirchhoff’s first law on the node formed by conductors c1 and c2 gives us Equation (F.4):

218666.05.0 ccC IIjI +=+−= (F.4)

Applying Kirchhoff’s second law on the loop formed by both conductors of phase A gives us Equation (F.5):

−++++++− gwgwacacaananaananaanaaaaaaa IZIZIZIZIZIZIZ ,121,221,221,211,122,211,1 ....

0.... ,222,222,212,112,1 =−−−−− gwgwacacnaanaaaanaana IZIZIZIZIZ (F.5)

Similar equations can be derived for the other two loops of phase B and phase C. These loops yield a total of three equations.

Applying Kirchhoff’s second law on the loop formed by the shield/sheath of the first cable of phase A and the shield/sheath of the second cable of shield/sheath A gives us Equation (F.6):

−++++++− gwgwnacnacanaanananaanaanananananana IZIZIZIZIZIZIZ ,121,221,221,221,122,211,1 ....0.... ,222,222,212,112,1 =−−−−− gwgwnacnacanaaanaananana IZIZIZIZIZ (F.6)

Similar equations can be derived for the remaining six loops, the last one being the loop formed by the shield/sheath of the second cable of phase C and the continuity conductor.

A total of 13 equations are obtained. The system of equations, written in matrix form, is shown in Figure F.3. The solution to these equations provides the current distribution in the conductors a1 to c2, the induced current in the shields/sheaths na1 to nc2, and the induced current Igw in the GCC.

The residual voltage at the bonding node can be evaluated as shown in Equation (F.7):

( +++++×== 11,121,211,121,211,11 cnacbnabbnabanaaanaaresna IZIZIZIZIZLEE …..

++++++ 22,111,122,111,121,2 nbnbnanbnbnananananananacnac IZIZIZIZIZ …..

)gwgwnancncnancncna IZIZIZ ,122,111,1 +++ (F.7)

where

L is the cable length in meters Other symbols are summarized in Figure F.3.

Copyright © 2014 IEEE. All rights reserved.

55

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 68: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

( ) ( ) ( ) ( ) ( ) ( ) ( )( ) ( ) ( ) ( ) ( ) ( ) ( )( )( ) ( )( )( ) ( ) ( )( ) ( ) ( ) ( ) ( ) ( ) ( )( ) ( ) ( ) ( ) ( ) ( ) ( )( ) ( ) ( ) ( ) ( )

( ) ( ) ( ) ( ) ( ) ( ) ( )( ) ( ) ( ) ( ) ( ) ( ) ( )( ) ( ) ( ) ( ) ( ) ( ) ( )

+−−−+

=

×

−•••−−−−••••−−

−•••−−−−••••−−

−•••−−−−••••−−••••••••••••••••••••••••••••

−•••

−−−−••••−−

−•••−−−−••••−−

−•••−−−−••••−−

−•••−−−−••••−−

−•••−−−−••••−−

−•••−−−−••••−−

0000.866J0.50.866J0.50J1.

0000000

IIIIIIIIIIIII

c2

c1

b2

b1

a2

a1

gw

nc2

nc1

nb2

nb1

na2

na1

c2c2,Zc2c1,Za2c2,Za2c1,Za1c2,Za1c1,Zgwc2,Zgwc1,Znc2c2,Znc2c1,Zna2c2,Zna2c1,Zna1c2,Zna1c1,Zc2b2,Zc2b1,Za2b2,Za2b1,Za1b2,Za1b1,Zgwb2,Zgwb1,Znc2b2,Znc2b1,Zna2b2,Zna2b1,Zna1b2,Zna1b1,Zc2a2,Zc2a1,Za2a2,Za2a1,Za1a2,Za1a1,Zgwa2,Zgwa1,Znc2a2,Znc2a1,Zna2a2,Zna2a1,Zna1a2,Zna1a1,Z

1000000000000001100000001111

c2gw,Zc2nc2,Za2gw,Za2nc2,Za1gw,Za1nc2,Zgwgw,Zgwnc2,Znc2gw,Znc2nc2,Zna2gw,Zna2nc2,Zna1gw,Zna1nc2,Zc2nc2,Zc2nc1,Za2nc2,Za2nc1,Za1nc2,Za1nc1,Zgwnc2,Zgwnc1,Znc2nc2,Znc2nc1,Zna2nc2,Zna2nc1,Zna1nc2,Zna1nc1,Zc2nc1,Zc2nb2,Za2nc1,Za2nb2,Za1nc1,Za1nb2,Zgwnc1,Zgwnb2,Znc2nc1,Znc2nb2,Zna2nc2,Zna2nb2,Zna1nc1,Zna1nb2,Zc2nb2,Zc2nb1,Za2nb2,Za2nb1,Za1nb2,Za1nb1,Zgwnb2,Zgwnb1,Znc2nb2,Znc2nb1,Zna2nb2,Zna2nb1,Zna1nb2,Zna1nb1,Zc2nb1,Zc2na2,Za2nb1,Za2na2,Za1nb1,Za1na2,Zgwnb1,Zgwna2,Znc2nb1,Znc2na2,Zna2nb1,Zna2na2,Zna1nb1,Zna1na2,Zc2na2,Zc2na1,Za2na2,Za2na1,Za1na2,Za1na1,Zgwna2,Zgwna1,Znc2na2,Znc2na1,Zna2na2,Zna2na1,Zna1na2,Zna1na1,Z

where

Zna1,na2 is the mutual impedance between the shields/sheaths of cable 1 and cable 2 of phase A Za1,nc2 is the mutual impedance between the conductor of cable 1 of phase A and the shield/sheath of cable 2 of phase C Za1,a1 is the self-impedance between cable 1 and cable 2 of phase A Zgw,nb1 is the mutual impedance between the ground conductor and the shields/sheaths of cable 1 of phase B Inc1 is the induced current in the shield/sheath of cable 1 of phase C Ia1 is the current flowing in the conductor of cable 1 of phase A Igw is the induced current in the GCC RHS is the known phase currents (right hand side of matrix equation)

Figure F.3—System of equations describing the installation shown in Figure F.1

Copyright © 2014 IEEE. All rights reserved.

56

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 69: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

F.3 Single-point-bonding

Single-point-bonding is frequently used as an alternative to multiple point bonding, especially for short cable lengths. This technique eliminates the induced currents in the various shields/sheaths but, at the same time, causes a voltage rise along the shields/sheaths with the maximum occurring at the floating point. In order to reduce this voltage, we install a GCC that runs parallel to the cables. This conductor should be transposed at the mid-point location and solidly bonded to the ground at both ends. Figure F.4 shows a sketch of single-point-bonding with continuity conductor. The induced voltages in shields/sheaths are calculated as follows [see Equation (F.8) to Equation (F.14) and Table F.1]:

Figure F.4—Sketch of single-point-bonding (ground continuity conductor position as shown in the profile view)

[ ]

•+

=

ncgw

nbgw

nagw

gw

C

B

A

M

nc

nb

na

ZZZ

IIII

ZEEE

,

,

,

(F.8)

where

[ZM] is the mutual impedance matrix between conductors a, b, c

and shields/sheaths na, nb, nc

[ ]( ) ( ) ( )( ) ( ) ( )( ) ( ) ( )

=

nccncbnca

nbcnbbnba

nacnabnaa

M

ZZZZZZZZZ

Z

,,,

,,,

,,,

(F.9)

where

Igw is the induced current in the continuity ground conductor

Copyright © 2014 IEEE. All rights reserved.

57

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 70: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

−=

C

B

A

gwcgwbgwagwgw

gw

III

ZZZZ

I ,,,,

1 (F.10)

where

Ena is the induced voltage in the shield/sheath na Zgw,na is the mutual impedance between shield/sheath na and GCC gw Za,nb is the mutual impedance between conductor a and shield/sheath nb (Ω/m)

7

,, 101lnπ4 −×

×=

nbanba S

fjZ (Ω/m) (F.11)

7, 102lnπ4 −×

×+=

cacaaa D

fjRZα

(Ω/m) (F.12)

7, 102lnπ4 −×

×+=

nananana D

fjRZ (Ω/m (F.13)

7, 102lnπ4 −×

×+=

gwgwgwgw D

fjRZα

(Ω/m) (F.14)

where

α is the geometric mean diameter coefficient and is summarized in Table F.1 Dca is the diameter of conductor a (mm) Dgw is the diameter of ground conductor (mm) Dna is the average diameter of shield/sheath na (mm) f is the power frequency (Hz) Rca is the electrical resistance of conductor a (Ω/m) Rgw is the electrical resistance of ground conductor (Ω/m) Rna is the electrical resistance of shield/sheath na (Ω/m) Sa,nb is the axial spacing between conductor a and shield/sheath nb (mm) Za,a is the self-impedance of conductor a

Copyright © 2014 IEEE. All rights reserved.

58

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 71: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

Table F.1—Values of α

Number of wires Value of α 1 0.779 3 0.678 7 0.726

19 0.758 37 0.768 61 0.772 91 0.774 127 0.776

F.4 Cross bonding

Cross bonding of shields/sheaths eliminates or reduces significantly the circulating current in shields/sheaths. The challenge is to insure that all minor sections are of the same length. Figure F.5 shows a sketch of a cross-bonded cable installation. Figure F.6 is the equivalent electrical circuit on which we can apply the Kirchhoff’s laws.

Figure F.5—Cross bonding of shields/sheaths

Copyright © 2014 IEEE. All rights reserved.

59

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 72: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

Figure F.6—Electrical circuit of shields/sheaths cross bonding

Kirchoff’s first law gives Equation (F.15):

Ina + Inb + Inc = 0 (F.15)

For the loop formed by the shield/sheath belonging initially to phase A and the shield/sheath belonging initially to phase B, Kirchoff’s second law gives Equation (F.16):

( ) ( ) ++++++−++ AncaAnbaAnaanbnbnbnanana IZLIZLIZLIZLLLIZLLL ,3,2,1,321,321

+++++++ CnccCnbcCnacBncbBnbbBnab IZLIZLIZLIZLIZLIZL ,3,2,1,3,2,1

−++++++ ncncnbncnbnancncnanbncnanbncnbnbnbna IZLIZLIZLIZLIZLIZL ,3,2,1,3,2,1

( ) ( )−++−++− BnabBncbBnbbAnaaAncaAnba IZLIZLIZLIZLIZLIZL ,3,2,1,3,2,1

( ) ( )−++−++− nancnanancnbnanbnaCnacCnccCnbc IZLIZLIZLIZLIZLIZL ,3,2,1,3,2,1

( ) 0,3,2,1 =++− ncnbnancncnancncnb IZLIZLIZL (F.16)

A similar equation can be derived for the other loop formed by the shields/sheaths of phase B and phase C.

The set of three equations can be solved to obtain the circulating currents in individual shields/sheaths.

The induced voltage along the shield/sheath, belonging initially to phase A, is determined as indicated in the following F.4.1, F.4.2, and F.4.3.

Copyright © 2014 IEEE. All rights reserved.

60

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 73: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

F.4.1 Along minor section #1 (L = 0 → L1)

+

=

nc

nb

na

ncnanbnananana

III

ZZZLE ,,,1,

nagwgw

C

B

A

nacnabnaa ZILIII

ZZZL ,,,, ••+

+ (F.17)

F.4.2 Along minor section #2 (L = L1 → L2)

+

+=

nb

na

nc

ncnbnbnbnbnanana

III

ZZZLEE ,,,1,2,

nbgwgw

C

B

A

nbcnbbnba ZILIII

ZZZL ,,,, ••+

+ (F.18)

F.4.3 Along minor section #3 (L = L2 → L3)

+

+=

nc

nb

na

ncnanbnanananana

III

ZZZLEE ,,,2,3,

ncgwgw

C

B

A

nacnabnaa ZILIII

ZZZL ,,,, ••+

+ (F.19)

The residual voltage at the bonding point of the major section is equal to Ena,3 at L = L3.

The induced voltage along the other shields/sheaths is calculated the same way.

F.5 Practical examples

The development outlined previously can be used to calculate the induced voltages and currents in complex cable installations. The results can be used to optimize the cables/phases arrangement in a duct bank in the case of parallel multi-cables per phase. Examples of two parallel cables per phase and six parallel cables per phase with no GCCs are outlined as follows.

Copyright © 2014 IEEE. All rights reserved.

61

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 74: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

F.5.1 Configuration optimization

F.5.1.1 Two cables per phase circuit

The following example is a three-phase circuit with two cables per phase, installed in flat formation with shields/sheaths solidly bonded at both ends (see Figure F.7). The other characteristics are as follows:

Rconductor = 33.86E-6 Ω/m (1.03E-5 Ω/ft), Rsheath = 0.209E-3 Ω/m (6.37E-5 Ω/ft), Dconductor = 32.8 mm (1.29 in)

Dsheath = 48 mm (1.89 in), 50 Hz, IA = IB = IC = 100 A, cable length = 1000 m (3281 ft)

Table F.2 shows, for this particular cables/phases arrangement, the current distribution in the individual conductors and shields/sheaths and the shield/sheath loss factor, which is the ratio of losses in the shield/sheath due to induced current to the losses in the conductor. It can be seen that the phase current is not distributed uniformly as might be expected. It varies between 44.6 A and 55.7 A instead of a balanced 50 A in each one. This non-optimized arrangement impacts the losses in the shields/sheaths, giving a maximum sheath loss factor of 4.95.

The shield/sheath loss factor being defined as shown in Equation (F.20):

caca

nanana RI

RI2

2

=λ (for shield/sheath na ) (F.20)

where

Ina is the current in shield/sheath na (A) Ica is the current in conductor ca (A) Rna is the electrical resistance of shield/sheath na (Ω/m) Rca is the electrical resistance of conductor ca (Ω/m)

Figure F.7—Cable configuration, two cables per phase, initial configuration

Table F.2—Currents and losses, initial configuration

Phase current (A)

Sheath current (A) Sheath loss factor

Cable 1, Phase A 46.3 38.4 4.24 Cable 2, Phase A 53.7 34.3 2.85 Cable 3, Phase B 44.6 37.4 4.35 Cable 4, Phase B 55.7 34.8 2.42 Cable 5, Phase C 50.8 43.7 4.56 Cable 6, Phase C 49.6 44.4 4.95

(15.75 in)

Copyright © 2014 IEEE. All rights reserved.

62

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 75: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

A better cables/phases arrangement, shown in Figure F.8, can improve the current distribution in the conductors and reduce the losses in the shield/sheath as shown in Table F.3.

Figure F.8—Two cables per phase, alternate configuration 1

Table F.3—Currents and losses, alternate configuration 1

Phase current (Amps)

Sheath current (Amps) Sheath loss factor

Cable 1, Phase A 50 28.7 2.04 Cable 2, Phase B 50 28.7 2.04 Cable 3, Phase C 50 25.3 1.58 Cable 4, Phase C 50 25.3 1.58 Cable 5, Phase B 50 34.8 2.99 Cable 6, Phase A 50 34.8 2.99

With this arrangement, the current is distributed uniformly among the individual conductors (50 A each) and the losses in the shields/sheaths are reduced substantially.

An optimized trefoil configuration, as shown in Figure F.9, gives the best results (see Table F.4). In this case, the shield/sheath losses are reduced significantly, down to 0.492 instead of 2.99.

Figure F.9—Two cables per phase, alternate configuration 2

7.87 in

(7.87 in)

(2.36 in)

Copyright © 2014 IEEE. All rights reserved.

63

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 76: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

Table F.4—Currents and losses, alternate configuration 3

Phase current (A)

Sheath current (A) Sheath loss factor

Cable 1, Phase A 50 13.9 0.474 Cable 2, Phase A 50 13.9 0.474 Cable 3, Phase B 50 13.8 0.468 Cable 4, Phase B 50 13.8 0.468 Cable 5, Phase C 50 14.1 0.492 Cable 6, Phase C 50 14.1 0.492

F.5.1.2 Six cables per phase circuit

The more cables per phase we have, the greater the probability to have an important imbalance in current distribution among individual cables. Figure F.10 shows a real-life cable installation (see Petty [B37]) where the total load of a power generating station is carried by 18 cables (6 cables per phase). The measured imbalance is 280%, resulting from one cable (#6) carrying much more power (270 A) than his neighbor (#16), which carries 96 A only. The calculation, using the same methodology described previously, gives an imbalance of 268%, assuming equal cable lengths.

Figure F.10—Measured current distribution in a thermal generating station A simple rearrangement in cables-phases as shown in Figure F.11 reduces significantly the imbalance in current distribution and lowers the shield/sheath losses at the same time. In this case, the imbalance drops to 119% and the maximum shield/sheath losses factor drops from 11.4 to 3.2.

190.5 mm (7.5 in)

610 mm (24 in)

190.5 mm (7.5 in)

Copyright © 2014 IEEE. All rights reserved.

64

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 77: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

Figure F.11—Current distribution in an optimized cables/phases configuration

F.5.2 Single-point-bonding The following examples highlight the importance of transposing the GCC in order to reduce the induce voltage along the shields/sheaths. It is the case of a real cable installation (see Pirelli [B38]) having the following characteristics.

380 kV, 1200 mm2 (2400 kcmil) cable, 50 Hz, cable length = 1000 m (3281 ft)

#4/0 AWG ground conductor, 0.000173 Ω/m (5.27E-5 Ω/ft), shield/sheath diameter = 104 mm (4.1 in)

IA = IB = IC = 1675 A

F.5.3 Untransposed continuity conductor

Figure F.12 shows the arrangement of the cables and the GCC. The results for the induced voltage show a maximum of 448 V for shield/sheath na, 184 V for shield/sheath nb, and 165 V for shield/sheath nc. The induced current in the continuity conductor is equal to 614 A.

Figure F.12—Untransposed continuity conductor

190.5 mm (7.5 in)

610 mm (24 in)

190.5 mm (7.5 in)

Copyright © 2014 IEEE. All rights reserved.

65

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 78: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

F.5.4 Transposed continuity conductor

Figure F.13 shows an optimized arrangement of the cables and the transposed GCC. The induced voltage in shield/sheath na drops to 253 V, to 174 V for shield/sheath nb and increases to 213 V for shield/sheath nc. The induced current in the continuity conductor drops to 68 A.

Figure F.13—Transposed continuity conductor

F.5.5 Bonding arrangements

F.5.5.1 Cross bonding

The following examples show the impact of shield/sheath cross bonding on losses. Two cases are considered, one with perfect permutation (minor sections of equal length), the other with relatively bad permutation. The characteristics of the installation are taken from an existing one (see Lodwig [B33]). The cases involve the following parameters:

380 kV, 1200 mm2 cable (2400 kcmil), 60 Hz, cable length = 2100 m (6900 ft)

IA = IB = IC = 900 A

Cable spacing = 19 cm (7.5 in)

F.5.5.2 Perfect cross bonding

Figure F.14 shows the induced shield/sheath voltage along the cable route with perfect permutation (minor section of 700 m (2297 ft) each). The maximum calculated voltage is 111 V and the residual voltage is 33 V. The circulating current in shields/sheaths is null.

(3.5 in)

(1.0 ft) in)

Copyright © 2014 IEEE. All rights reserved.

66

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 79: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

0

20

40

60

80

100

120

0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1

Distance (% of major section)

Shea

th v

olta

ge (V

)

Sheath of phase C

Sheath of phase A

Sheath of phase B

Residual voltage

Figure F.14—Shield/sheath voltage with ideal permutation

F.5.5.3 Less than perfect cross bonding

Figure F.15 shows the induced shield/sheath voltage along the cable route with unequal minor sections, namely 420 m (1378 ft) for #1, 630 m (2067 ft) for #2, and 1050 m (3445 ft) for #3. The maximum voltage in this case increases to120 V and the residual voltage remains approximately the same.

Copyright © 2014 IEEE. All rights reserved.

67

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 80: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE Std 575-2014 IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV

0

20

40

60

80

100

120

140

0.0000 0.1000 0.2000 0.3000 0.4000 0.5000 0.6000 0.7000 0.8000 0.9000 1.0000

Distance (% of major section)

Shea

th v

olta

ge (V

)

Sheath of phase C

Sheath of phase B

Sheath of phase A

Residual voltage

Figure F.15—Shield/sheath voltage with non-ideal permutation

Copyright © 2014 IEEE. All rights reserved.

68

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 81: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 82: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

© IEEE

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.

Page 83: 575-2014 - IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 KV Through 500 KV

IEEE standards.ieee.orgPhone: +1 732 981 0060 Fax: +1 732 562 1571 © IEEE

Authorized licensed use limited to: Institut Teknologi Bandung. Downloaded on June 21,2015 at 09:52:14 UTC from IEEE Xplore. Restrictions apply.