5638 e1 1500 CA Pro 220 Rev.3_ Construction Procedure for Tank Hydrostatic Test

Embed Size (px)

Citation preview

  • 7/25/2019 5638 e1 1500 CA Pro 220 Rev.3_ Construction Procedure for Tank Hydrostatic Test

    1/29

    FORCONSTRUCTION

    OF OIL TERMINAL AT HFZ(EPC-1)

    AGREEMENT NO. 10-5638-E-1

    ABU DHABIOIL REFINING COMPANY PROJECT PROCEDURE

    CONSTRUCTION PROCEDURE FOR

    TANK HYDROSTATIC TESTDOC.NO.:5638-E1-1500-CA-PRO-220 Page

    1/18

    Rev.3

    PROCEDURE

    FOR

    TANK HYDROSTATIC TEST

  • 7/25/2019 5638 e1 1500 CA Pro 220 Rev.3_ Construction Procedure for Tank Hydrostatic Test

    2/29

    FORCONSTRUCTION

    OF OIL TERMINAL AT HFZ(EPC-1)

    AGREEMENT NO. 10-5638-E-1

    ABU DHABIOIL REFINING COMPANY PROJECT PROCEDURE

    CONSTRUCTION PROCEDURE FOR

    TANK HYDROSTATIC TESTDOC.NO.:5638-E1-1500-CA-PRO-220 Page

    2/18

    Rev.3

    This page is a record of all revision of this document. All previous issues are hereby superseded

    and are to be destroyed.

    REV DATE DESCRIPTION PRPD CHKD REVD APPRD COMPANY

    3 19/Dec/13Approved for

    ConstructionLQL TCS ZHQ AJL

    2 12/Dec/13Reissued for

    Approval withAmendment

    LQL TCS JHB AJL

    1 26/Nov/13Reissued for

    Approval withAmendment

    LQL TCS JHB AJL

    0 26/Apr/12Approved for

    ConstructionLQL AGS JHB AJL

    B 16/Mar/12

    CommentsIncorporated and

    Reissued ForApproval

    LQL AGS JHB AJL

    A 05/Mar/12For Approval/

    CommentLQL AGS JHB AJL

    SIGNED(Initials)

    QA/QC manager

  • 7/25/2019 5638 e1 1500 CA Pro 220 Rev.3_ Construction Procedure for Tank Hydrostatic Test

    3/29

    FORCONSTRUCTION

    OF OIL TERMINAL AT HFZ(EPC-1)

    AGREEMENT NO. 10-5638-E-1

    ABU DHABIOIL REFINING COMPANY PROJECT PROCEDURE

    CONSTRUCTION PROCEDURE FOR

    TANK HYDROSTATIC TESTDOC.NO.:5638-E1-1500-CA-PRO-220 Page

    3/18

    Rev.3

    PARAGRAPHS REVISED IN THIS ISSUE

    Para. No. Para. No. Para. No. Para. No.

  • 7/25/2019 5638 e1 1500 CA Pro 220 Rev.3_ Construction Procedure for Tank Hydrostatic Test

    4/29

    FORCONSTRUCTION

    OF OIL TERMINAL AT HFZ(EPC-1)

    AGREEMENT NO. 10-5638-E-1

    ABU DHABIOIL REFINING COMPANY PROJECT PROCEDURE

    CONSTRUCTION PROCEDURE FOR

    TANK HYDROSTATIC TESTDOC.NO.:5638-E1-1500-CA-PRO-220 Page

    4/18

    Rev.3

    TABLE OF CONTENTS

    No. DESCRIPTION PAGE

    1 INTRODUCTION ............................................................................................................... 5

    1.1 General ......................................................................................................................... 5

    1.2 Scope ............................................................................................................................ 5

    2 DEFINITIONS .................................................................................................................... 5

    3 REFERENCE CODES AND DOCUMENTS .................................................................... 6

    4 RESPONSIBILITIES .......................................................................................................... 7

    5 WATER TEST .................................................................................................................... 7

    6 HYDROSTATIC TESTING REQUIREMENTS FROM CODE ....................................... 8

    7 TANK FILLING ................................................................................................................. 9

    7.1 Initial Filling: ............................................................................................................... 9

    7.2 Water Filling: ............................................................................................................. 10

    8 MONITORING AND SETTLEMENT LIMITS .............................................................. 11

    9 TESTING OF THE ROOF ................................................................................................ 14

    9.1 Fixed Dome roof ........................................................................................................ 14

    9.2 Floating Roof (Single Deck Pontoon Type) ............................................................ 14

    9.3 Roof Drains ................................................................................................................ 15

  • 7/25/2019 5638 e1 1500 CA Pro 220 Rev.3_ Construction Procedure for Tank Hydrostatic Test

    5/29

    FORCONSTRUCTION

    OF OIL TERMINAL AT HFZ(EPC-1)

    AGREEMENT NO. 10-5638-E-1

    ABU DHABIOIL REFINING COMPANY PROJECT PROCEDURE

    CONSTRUCTION PROCEDURE FOR

    TANK HYDROSTATIC TESTDOC.NO.:5638-E1-1500-CA-PRO-220 Page

    5/18

    Rev.3

    1 INTRODUCTION

    1.1 General

    The purpose of this procedure is to establish the job instruction for hydrostatic testing of StorageTanks shall be tested in accordance with API standard 650 and compliance with the requirementsof the project specification.

    This job instruction in conjunction with job safety is intended to describe the sequence of activitiesto be carried out to ensure hydrostatic and pneumatic testing is conducted in a safe andcontrolled manner.

    1.2 Scope

    The scope of this procedure covers all types of Storage Tanks like external floating roof, internalfloating roof with fixed dome roof and fixed dome roof. The test of each tank shall be carried outafter completion of all mechanical works with the mechanical completion check list witnessed byCONTRACTOR and the COMPANY.

    For hydrostatic testing the method of filling, the fill rate and flow, static and pneumatic testing,emptying or transfer the water to other tank for testing. During testing we shall verify the tanks allweld seams for leaks, settlement of tank foundation, movement of floating roof, roof drain nozzleand all fixed roof nozzles shall be in open condition during filling and emptying, All shell openingsshall be closed with temporary blind flanges and gaskets with proper size of fasteners for bolting.

    For hydrotesting of storage tanks, clean water will be used.CONTRACTOR should follow theapplicable rules and regulations and obtain the approval from HFZA , Sharjah Port Authority

    SPA. and Sharjah Municipality.

    2 DEFINITIONS

  • 7/25/2019 5638 e1 1500 CA Pro 220 Rev.3_ Construction Procedure for Tank Hydrostatic Test

    6/29

    FORCONSTRUCTION

    OF OIL TERMINAL AT HFZ(EPC-1)

    AGREEMENT NO. 10-5638-E-1

    ABU DHABIOIL REFINING COMPANY PROJECT PROCEDURE

    CONSTRUCTION PROCEDURE FOR

    TANK HYDROSTATIC TESTDOC.NO.:5638-E1-1500-CA-PRO-220 Page

    6/18

    Rev.3

    EPC = Detailed Engineering, Procurement, Construction andCommissioning

    FEED = Front End Engineering and Design

    IT = Information Technology

    Licensor = Any firm or company contracted to provide theirproprietary licensed technology for this Project

    Site = Hamriyah free Zone, Sharjah, UAE

    Project = Construction of Oil Terminal at Hamriyah Free Zone

    (EPC-1)

    Subcontractor = Any person, form, or company employed byCONTRACTOR to perform any work or duty on theirbehalf

    3 REFERENCE CODES AND DOCUMENTS

    API 650 Welded steel Tanks for oil storage

    ASME Section II, part-c Welding rods, Electrodes and Filler materials

    ASME Section V Nondestructive Examination

    ASME Section IX Welding and Bracing Qualifications

    ASME Section VIII,Div-1 Pressure Vessels

    5638-E1-1500-MEQ-DS-201-207 Data Sheet for Tanks

    5638-E1-1500-MEQ-DWG-201-231

    5638-E1-1500-MEQ-DWG-251-281

    5638-E1-1500-MEQ-DWG-301-331

  • 7/25/2019 5638 e1 1500 CA Pro 220 Rev.3_ Construction Procedure for Tank Hydrostatic Test

    7/29

    FORCONSTRUCTION

    OF OIL TERMINAL AT HFZ(EPC-1)

    AGREEMENT NO. 10-5638-E-1

    ABU DHABIOIL REFINING COMPANY PROJECT PROCEDURE

    CONSTRUCTION PROCEDURE FOR

    TANK HYDROSTATIC TESTDOC.NO.:5638-E1-1500-CA-PRO-220 Page

    7/18

    Rev.3

    5638-E1-1500-SA-PRO-001 Project HSE plan

    5638-E1-1500-SA-PRO-006 Permit To Work Procedure

    5638-E1-1500-SA-PRO-009 Fall Prevention And Protection Procedure5638-E1-1500-SA-PRO-011 Confined Space Entry Procedure

    DGS-MF-001 Design Basis Tanks

    DGS-MF-002 Field Erected Welded Steel Storage Tanks

    DGS-MW-003 Welding of Storage Tanks

    DGS-MX-001 Painting

    STD-MF-00024 Methods of Tank Erection

    DGS-PU-009 Flange bolting

    DGS-MX-002 Galvanising

    DGS-MX-004 Lining

    Hamriyah Free Zone Authority Guidelines

    Sharjah Municipality Guidelines

    SEWA - Sharjah Electricity and Water Authority

    4 RESPONSIBILITIES

    The hydrotesting of Storage Tanks shall be headed by Project Manager of the CONTRACTOR

    supported by overall project safety, quality, and tech service departmental heads. Eachdepartment shall provide designates for this work for proper control. Construction Managerreporting to Project Manager shall be responsible for related construction activities.

    Competent persons shall be assigned for the hydrotesting work. Since the hydrotesting shall beon 24 hrs basis, for proper coverage to oversee the operation, The competent personnel shall bed l d i i h hif ll Ad li h i h ll b d k f d i

  • 7/25/2019 5638 e1 1500 CA Pro 220 Rev.3_ Construction Procedure for Tank Hydrostatic Test

    8/29

    FORCONSTRUCTION

    OF OIL TERMINAL AT HFZ(EPC-1)

    AGREEMENT NO. 10-5638-E-1

    ABU DHABIOIL REFINING COMPANY PROJECT PROCEDURE

    CONSTRUCTION PROCEDURE FOR

    TANK HYDROSTATIC TESTDOC.NO.:5638-E1-1500-CA-PRO-220 Page

    8/18

    Rev.3

    Water drainage from the storage tank will be disposed to HFZA approved area or disposal ofhydrotest water shall be drained through approved agency as per the rules and regulationsof HFZA.

    6 HYDROSTATIC TESTING REQUIREMENTS

    Here are the hydrostatic testing requirements from Project codes and specifications ,Detailedplan refer to section 9 Site Tank Hydrostatic Testing Water Execution Plan subject to sitecondition.

    Tank shall be hydrotested on completion of all construction work directly associated with the

    tank and its welded attachments and on completion of all non destructive testingrequirementsexcept painting activities.

    No project connections are to be made between the tank and any product line until the tankand all mountings have been satisfactorily tested.

    No welding is to be carried out on the shell when the tank is full of water. Any leaks foundshall be repaired with the water level at least 300 mm below the point being repaired to anagreed welding procedure and retest.

    Internal bottom elevation measurements shall be made before and after hydrostatic testing.measurements shall be made at maximum intervals of 3m measured on diametrical linesacross the tank. The diametrical lines shall be spaced at equal angles, with a maximumseparation measured at the tank circumference of 10m. A minimum of four diametrical linesshall be used.

    All dimensional tolerances required in accordance to API Std 650.

    For fixed roof tanks, testing shall be done by filling the tanks with fresh water to the level ofthe top leg of the top curb angle, and noting any leaks over a period of at least 24 hours.

    For open top tanks and floating roof tanks the maximum test water level is approximately 150mm below the top of the shell.

    Any tank showing evidence of leakage from the bottom during test must be emptied

  • 7/25/2019 5638 e1 1500 CA Pro 220 Rev.3_ Construction Procedure for Tank Hydrostatic Test

    9/29

    FORCONSTRUCTION

    OF OIL TERMINAL AT HFZ(EPC-1)

    AGREEMENT NO. 10-5638-E-1

    ABU DHABIOIL REFINING COMPANY PROJECT PROCEDURE

    CONSTRUCTION PROCEDURE FOR

    TANK HYDROSTATIC TESTDOC.NO.:5638-E1-1500-CA-PRO-220 Page

    9/18

    Rev.3

    After completion of the hydrotest only non-structural small attachments may be welded to thetank in accordance with 7.2.1.11. Any welded joints above the test-water level shall beexamined for leakage by one of the following methods.

    1. Coating all of the joints on the inside with a high penetrating oil, such as automobile springoil, and carefully examining the outside of the joints for leakage.

    2. Applying vacuum to either side of the joints or applying internal air pressure as specifiedfor the roof test in 7.3.7 and carefully examining the joints for leakage.

    3. Using any combination of the methods stipulated in subitems 1 and 2.

    The CONTRACTOR shall be responsible for preparing the tank for testing. This shall includeremoval of all trash, debris, grease, oil, weld scale, weld spatter, and any other foreign matterfrom the interior and the roofs of the tank.

    The CONTRACTOR shall be responsible for furnishing, laying, and removing all pipe linesfrom the clean water source tie-in locations and to the water disposal point. To obtain requiredpermission for taking clean water for filling and then after testing disposal of water with priorapproval from the COMPANY and the concerned authority of HFZA and Sharjah Municipality.

    During emptying the tank or after hydrotest CONTRACTOR shall be responsible for cleaningthe tank with clean water, which is kept outside the tank on the ground with jet pump.

    The CONTRACTOR shall be responsible for monitoring the settlement measurements inaccordance to code.

    The CONTRACTOR shall be responsible for furnishing all other test materials and facilities,including blinds, bolting, and gaskets.

    The CONTRACTOR shall be responsible for checking the wind girders for proper drainageduring or following the hydrotest . If water is retained, additional drainage shall be providedsubject to the COMPANY approval.

  • 7/25/2019 5638 e1 1500 CA Pro 220 Rev.3_ Construction Procedure for Tank Hydrostatic Test

    10/29

    FORCONSTRUCTION

    OF OIL TERMINAL AT HFZ(EPC-1)

    AGREEMENT NO. 10-5638-E-1

    ABU DHABIOIL REFINING COMPANY PROJECT PROCEDURE

    CONSTRUCTION PROCEDURE FOR

    TANK HYDROSTATIC TESTDOC.NO.:5638-E1-1500-CA-PRO-220 Page

    10/18

    Rev.3

    with API 653, Appendix B. The CONTRACTOR shall take jacking and leveling into considerationfor the tank design.

    Uneven settlement of the tank on its foundation shall be reported immediately to the COMPANYand filling shall be stopped at any signs of excessive settlement pending a decision by theCONTRACTOR and the COMPANY on the action to be taken.

    In the case of excessive soil settlement, the situation shall be reported to the soil mechanicsspecialist and his recommendations considered.

    The temperature of the test water shall be not lower than that specified by API 650 for the

    conditions concerned.

    7.2 Water Filling:

    The CONTRACTOR and COMPANY representative shall witness the tank filling operations.

    The tank shall have all shell in-out connections blanked off except a nozzle used to allow asteady inflow or outflow of hydrotest water. Isolating and check valves shall be fitted to thisnozzle in case of filling failure and shall be served by mean of a manifold from the temporaryline.

    Appropriate roof connections (manholes) must be open to allow free venting of air duringfilling.

    For floating roof tanks, the maximum and minimum annular space between the shell and theroof rim plate prior to initial floatation and at the maximum test fill height shall be measuredand recorded.

    If settlement measurements are specified by the COMPANY, any differential settlementgreater than 13mm per 10m of circumference or a uniform settlement over 50mm shall bereported to the COMPANY for evaluation. Filling of the tank shall be stopped until cleared bythe COMPANY.

  • 7/25/2019 5638 e1 1500 CA Pro 220 Rev.3_ Construction Procedure for Tank Hydrostatic Test

    11/29

    FORCONSTRUCTION

    OF OIL TERMINAL AT HFZ(EPC-1)

    AGREEMENT NO. 10-5638-E-1

    ABU DHABIOIL REFINING COMPANY PROJECT PROCEDURE

    CONSTRUCTION PROCEDURE FOR

    TANK HYDROSTATIC TESTDOC.NO.:5638-E1-1500-CA-PRO-220 Page

    11/18

    Rev.3

    One day for settlement reading at 50%One day for settlement reading at 75%One day for settlement reading at 100%

    Total four days for settlement observation

    The tank shall be observed for signs of leakage. Careful inspection of all welded seams in theshell, including shell to bottom and all welds around openings and pipe joints, shall be carriedout. Besides shall be ensured there is no evidence of water seeping from beneath the tank.

    8 MONITORING AND SETTLEMENT LIMITS

    Monitoring shall be consist in the measurement of settlements along the tank circumference byoptical level instrument reading.

    Level measurement on tank circumference

    The tank shall be provided with reference points, equally spaced along the circumference andmade of steel elements welded to the shell approx. one meter above the edge of the bottomcourse. A set of level reading on all reference points shall be performed at the following times:

    a) After tank complete construction, before start of filling for hydrastatic testb) With the water level at 25% of max. levelc) With the water level at 50% of max. leveld) With the water level at 75% of max. levele) With the water level at 100% levelf) 24 hours after reaching max. level of water in the tankg) In empty tank without waterh) 24 hours after emptying of the tank

    Level measurements shall be referred to a permanent bench mark, both the bench mark and therequired permanent station joints shall be located at least 0.75 tank diameter from the tank edgeto avoid ground settlements that may influence the reading. The level instrument shall be set upat least 1 times tank diameter away from the tank when tank elevation readings are taken.

  • 7/25/2019 5638 e1 1500 CA Pro 220 Rev.3_ Construction Procedure for Tank Hydrostatic Test

    12/29

    FORCONSTRUCTION

    OF OIL TERMINAL AT HFZ(EPC-1)

    AGREEMENT NO. 10-5638-E-1

    ABU DHABIOIL REFINING COMPANY PROJECT PROCEDURE

    CONSTRUCTION PROCEDURE FOR

    TANK HYDROSTATIC TESTDOC.NO.:5638-E1-1500-CA-PRO-220 Page

    12/18

    Rev.3

    9.1.4 Water vendor will use 15-20nos water tanks of 5000 gallons each to transport water fromtheir factory to Contractor site. The sufficient water will be stored in waste water Sumpbefore hydro test start.

    9.1.5 Manpower

    Description Quant.

    Mechanical engineer 2

    QA/QC engineer 1

    Safety officer 2

    Surveyor 2

    Site supervisor 2

    Welder 4

    Fitter 2

    Rigger 4

    Driver /Operator 5Labours 6

    9.2 Water filling & drains arrangement

    9.2.1 Contractor to use T901 waste water sump as buffering pool for water filling operation.Contractor shall Clean the waste water Sump (WWS) thoroughly before using it .Sample ofwater should be taken from WWS for testing.

    9.2.2 The total 16 tanks farm site will be divided into two areas for hydrostatic testing gradually :

    (1)The first tank area testing sequence is as follows:

    T201, T202T203T204T101, T103T102, T205T211, T212

  • 7/25/2019 5638 e1 1500 CA Pro 220 Rev.3_ Construction Procedure for Tank Hydrostatic Test

    13/29

    FORCONSTRUCTION

    OF OIL TERMINAL AT HFZ(EPC-1)

    AGREEMENT NO. 10-5638-E-1

    ABU DHABIOIL REFINING COMPANY PROJECT PROCEDURE

    CONSTRUCTION PROCEDURE FOR

    TANK HYDROSTATIC TESTDOC.NO.:5638-E1-1500-CA-PRO-220 Page

    13/18

    Rev.3

  • 7/25/2019 5638 e1 1500 CA Pro 220 Rev.3_ Construction Procedure for Tank Hydrostatic Test

    14/29

    FORCONSTRUCTION

    OF OIL TERMINAL AT HFZ(EPC-1)

    AGREEMENT NO. 10-5638-E-1

    ABU DHABIOIL REFINING COMPANY PROJECT PROCEDURE

    CONSTRUCTION PROCEDURE FOR

    TANK HYDROSTATIC TESTDOC.NO.:5638-E1-1500-CA-PRO-220 Page

    14/18

    Rev.3

    9.2.4 Official hydrostatic testing water filling

    This official hydrostatic testing water filling should be followed only after all the tank fittingsand structure were completed and inspected. The water filling shall strictly comply with tankhydrostatic testing requirements and contractor to keep good water filling and settlementrecords.

    9.3 Official Tank Hydrostatic Testing Water Filling Schedule

    Categ.In.

    Dia.TankShell

    Height

    Total

    FillingHeight(HLL)

    1stStage(25%)

    Settle.Observ.

    2ndStage(50%)

    Settl.Observ

    3rdStage(75%)

    Settle.Observ.

    4thStage(100%)

    Settle.Observ.

    JET A1TANK

    41m 22m 19.81m 4.95m 24hr. 9.9m 24hr. 14.86m 24hr. 19.81m 24hr.

    ULG &GAS OIL

    TANK

    36m 22.7m 21.25m 5.31m 24hr. 10.63m 24hr. 15.94m 24hr. 21.25m 24hr.

    Note:

    (1) The total filling height is from Data Sheet for Tanks Rev.0 .HLL--- High liquid level(2) The balance tank T205, fire water tanks and slop tanks will apply to this schedule either.

    (3) Take the I.D.36m tank for calculation , using 260m/hr. pump and spend 10hr.each day to fill

    water, It will take approx. 15 days to complete High liquid level hydrostatic test (excluding waterdraining).

    10 TESTING OF THE ROOF

    10.1 Fixed Dome roof (If Required)

  • 7/25/2019 5638 e1 1500 CA Pro 220 Rev.3_ Construction Procedure for Tank Hydrostatic Test

    15/29

    FORCONSTRUCTION

    OF OIL TERMINAL AT HFZ(EPC-1)

    AGREEMENT NO. 10-5638-E-1

    ABU DHABIOIL REFINING COMPANY PROJECT PROCEDURE

    CONSTRUCTION PROCEDURE FOR

    TANK HYDROSTATIC TESTDOC.NO.:5638-E1-1500-CA-PRO-220 Page

    15/18

    Rev.3

    It is essential for a floating roof to be liquid-tight for it to function safely and well. To ensure thatweld seams and joints, which are required to be liquid-tight fulfill this requirement, they shall beinspected and tested carefully. The following procedure shall be adhered to.

    Center Deck of Pontoon-Type Roofs:

    The weld seams of the single center deck plates shall be checked for liquid-tightness by thevacuum box method or by the penetration oil/chalk method.

    Pontoon of pontoon-type roofs:

    Before the top plates of the pontoons are installed the following seams in particular, shall betested for tightness, using liquid penetrates or any other test method:

    a) The single-fillet welds on the upper surface of the pontoon bottom plates.b) The single-fillet welds between the bottom and the side walls of the pontoon.c) The single-fillet welds between the bulk heads and the bottom and side walls of the pontoon.d) The welds at the bottom corners of the bulk heads. These should be tested with particular

    care, since the bulk heads are mostly shaped at these points to clear the longitudinal weldbetween the bottom and the side walls. The gaps so formed in the corners shall be closed

    thoroughly, as leaks in one compartment will allow oil to penetrate into the adjacentcompartments.

    e) The longitudinal welds joining the center deck to the pontoon.

    Before all weld seams mentioned above are tested for tightness, they shall be thoroughlycleaned of slag and dirt.

    10.3 Roof Drains

    Drain pipe systems of storm water drains shall be tested with water to a pressure of 3.6kg/cm2(g).

    During the flotation test, the roof drains shall be kept open and observed for leakage of tankcontents into the drain lines.

  • 7/25/2019 5638 e1 1500 CA Pro 220 Rev.3_ Construction Procedure for Tank Hydrostatic Test

    16/29

  • 7/25/2019 5638 e1 1500 CA Pro 220 Rev.3_ Construction Procedure for Tank Hydrostatic Test

    17/29

    FORCONSTRUCTION

    OF OIL TERMINAL AT HFZ(EPC-1)

    AGREEMENT NO. 10-5638-E-1

    ABU DHABIOIL REFINING COMPANY PROJECT PROCEDURE

    CONSTRUCTION PROCEDURE FOR

    TANK HYDROSTATIC TESTDOC.NO.:5638-E1-1500-CA-PRO-220 Page

    17/18

    Rev.3

    For the hydrotest water below valve level, suction pumps shall be utilized to remove theremaining water from the bottom sump.

    The tank shall be completely drained and free from standing water.

    15 CLEANING OF INTERNAL TANK AFTER DRAINING

    After the completion of draining of clean water from the tank, blinds covering the manholes ornozzle openings shall be removed prior to the cleaning activity. The operators and relativepersonnel will go up to the top of tank from outside spiral stair and go into tank inside floating

    deck ,which acts as the work cleaning platform , from tank inside floating stairway. PTW andconfine space entry procedure shall be always followed before work start.

    A temporary storage tank filled with potable water is to be kept outside the tank on theground and connected to a jet pump.

    The jet pump shall be positioned near the movable working platform with adequate length ofhose and spray nozzle at the end. Minimum pressure at nozzle and is approximately 30 bargauge and output is 290/600 litres/hour.

    Cleaning of the shell plates shall be start from the highest course downward by standing onthe floating deck ,using the spray nozzle from the jet pump.

    16 CALIBRATION OF TANK

    Tank shall be calibrated in the presence of Third Party Inspection approved Agency by

    COMPANY. After obtaining Third party Inspection procedure for Tank calibration and same shall

    be submitted to COMPANY for further approval.

  • 7/25/2019 5638 e1 1500 CA Pro 220 Rev.3_ Construction Procedure for Tank Hydrostatic Test

    18/29

    FORCONSTRUCTION

    OF OIL TERMINAL AT HFZ(EPC-1)

    AGREEMENT NO. 10-5638-E-1

    ABU DHABIOIL REFINING COMPANY PROJECT PROCEDURE

    CONSTRUCTION PROCEDURE FOR

    TANK HYDROSTATIC TESTDOC.NO.:5638-E1-1500-CA-PRO-220 Page

    18/18

    Rev.3

    Refer to 5638-E1-1500-QA-ITP-MEQ-01 Inspection and Test Plan for Storage Tank and ProjectQuality Plan 5638-E1-1500-QA-PRO-001. Hydro test report shall be well prepared as per sitetesting course.

  • 7/25/2019 5638 e1 1500 CA Pro 220 Rev.3_ Construction Procedure for Tank Hydrostatic Test

    19/29

  • 7/25/2019 5638 e1 1500 CA Pro 220 Rev.3_ Construction Procedure for Tank Hydrostatic Test

    20/29

    OIL TERMINAL CONSTRUCTION PROJECT (EPC-1), HFZ, SHARJAH

    RISK ASSESSMENT (Page 2 of 11)

    2 Transportatio

    n and Lifting

    of HydroTesting

    Materials

    * Collide with

    other vehicle or

    adjacent objectsduring lifting/

    swinging

    * Clash with

    adjacent operations

    *Nip points

    *Sharp edges of

    materials

    *Under load*Overload/over turn*Load failure

    *Roll over

    *Fatality

    *Injury

    *PropertyDamage*Workstoppage

    *Crane and all the lifting accessories

    shall be 3rd

    party certified and the

    serial numbers of slings shall bematched with the certificates

    *Crane operator, rigger shall be withvalid 3

    rdparty Certificate.

    *Valid PTW* Lift plan if required

    *Pipe clamps shall be appropriate tothe pipe size.

    *All the slings, clamps shall beinspected by rigger before each lift

    *Only trained and authorizedpersonnel be allowed

    *Barricades and caution sign boardsbe displayed

    *Proper supervision and pre plan oneach activity

    *Other adjacent activities are to be

    restricted during the work*Riggers must be instructed well todecide the slinging points depends tolength and weight of pipes/materials

    *Slinging techniques shall be

    implemented correctly*Wind speed must be considered*Load chart must displayed visible in

    the operator cabin.

    *Radius and angle of boom and slingsmust be planned and monitored.*SWL of slings and cranes must be

    considered and planned well.

    *Spreader shall be used always ifrequired.* Minimum two tag lines are required

    (Tag line not less than

    3m)

    4 C H *Allocation of safelocation for positioning

    of Trailer and crane,materials stacking,

    Flagman and riggers*Proper plan required

    for material handling,sequential operation

    always*Mandatory PPEs and

    accoutrements shall bedonned

    *All the equipmentsand tools shall be

    inspected as perchecklist daily and

    periodically and colourcoded.

    *Weight of each load

    shall be calculatedbefore slinging.*Fork lift shall not be

    used to lift any size ofpipe.

    *Dimension of piperacks shall beconsidered and planed

    well the lifting path

    *Man positioning,working platform shallbe planed and explained

    to the work force.

    Performer 3 C M

  • 7/25/2019 5638 e1 1500 CA Pro 220 Rev.3_ Construction Procedure for Tank Hydrostatic Test

    21/29

    OIL TERMINAL CONSTRUCTION PROJECT (EPC-1), HFZ, SHARJAH

    RISK ASSESSMENT (Page 3 of 11)

    3 Fabrication,

    Blinding/

    Weldingbefore Hydro

    testing

    * Caught under

    load

    * Collide withother objects/

    operation

    *Sharp edges

    *Electrocution

    *UV/IR radiation

    *Injury

    *Property

    Damage*Electric

    burn/Bruise

    *Arc eye

    *All the equipments, electrical

    and hand tools shall be inspected

    prior to use, maintainedperiodically and colour coded

    accordingly.

    *Equipments shall be inspected

    and certified by a 3rd party

    (Depends on the equipment).

    *All the operatives shall be

    competent and trained.* All the DBs, sockets and cables

    shall be of project standards and

    with GFCI and inspected

    monthly.

    * All the Welding machines,

    shall be calibrated & grounding

    shall be ensured for all electrical

    equipments (Oven, work-piece,welding machine).

    * All the electrical tools shall be

    with deadman switch.

    * No material shall be placed by

    creating hinder to any access, exit

    or any fire extinguisher.

    *Proper supervision shall beensured always.*PPEs for Welding-Welding shield

    shall be attached to helmet, Welding

    Gloves, shall be used apart from

    project mandatory PPEs.

    *All the electrical

    cables shall be routed

    UG/above minimum

    2m height & away from road, sharp,

    hot parts

    3 C M * Scrap & used buts

    shall be stored

    seperately andemptied regularly.

    *Proper housekeeping

    shall be ensured

    always.

    *Proper aisle,

    workspace shall be

    planned and defined.

    *Material movementshall be planned &

    executed sequentially

    *Proper lighting,

    ventilation shall be

    ensured always.

    *External ventilation,

    mechanical exaustion

    shall be provided ifrequired.

    *Man positioning,

    proper working

    platform shall be

    planed, provided and

    explained to the work

    force.

    Performer 2 B L

  • 7/25/2019 5638 e1 1500 CA Pro 220 Rev.3_ Construction Procedure for Tank Hydrostatic Test

    22/29

    OIL TERMINAL CONSTRUCTION PROJECT (EPC-1), HFZ, SHARJAH

    RISK ASSESSMENT (Page 4 of 11)

    4. Laying andfixation of

    hose, clamps,couplings,

    pressuregauges and

    other hydrotest materials

    *Falling of

    material

    *Slip, Trip Fall

    *Injury

    *Falatlity

    *Flood

    *Rooting of hose, and fixing/clamp

    points shall be planned well

    considering the integrity of structureand weight of hydro test material

    including the water volume and

    pressure.

    *Vertical and horizontal routing of

    hoses shall be routed safe duly

    ensured the tighness to avoid any

    move and burst.

    *Tightness of Hose connectors shallbe ensured.

    *All the hose, connector/couplings

    shall be rated to the required bar

    pressure and back water thrust.

    *proper ramps shall be installed at

    road crossingss and routed safely to

    avoid slip trip fall.

    *Pressure gauges shall be installedat easily monitoring height levels.

    3 C M *Personnel shall be

    trained and issued

    with proper PPE*Grounding/earthing

    shall be ensured on

    the routings.

    *Hose, Clamps,

    couplings, gauges

    shall be international

    standards towithstand the

    pressure and be

    inspected before

    installation.*Callibrated Pressure

    gauges be installed at

    each section

    *Proper access to allvalves, gauges shall

    be provided

    Performer 2 A L

  • 7/25/2019 5638 e1 1500 CA Pro 220 Rev.3_ Construction Procedure for Tank Hydrostatic Test

    23/29

    OIL TERMINAL CONSTRUCTION PROJECT (EPC-1), HFZ, SHARJAH

    RISK ASSESSMENT (Page 5 of 11)

    5 Water

    Filling , Leak

    TestingDrain, and

    Settlement

    Observation

    *High pressured

    liquid

    *Structurecollapse

    *Failure of

    flanges

    *Burst

    *Buckling

    *Fatality

    *Injury

    *Assetdamage

    *Project delay

    *PTW be obtained. Watter be filled

    stage by stage duly monitoring

    leake, pressure etc.*Involved area to be barricaded with

    Warning signs.

    *Continuous supervision

    *Project Testing procedure shall be

    followed

    * Ensure that the test pack has been

    signed and released for test to

    proceed*A complete walk through

    inspection shall be done always at

    pressured.

    *Ensure that adequate number of

    spotters are in place at works

    location and boundaries

    *Ensure assigned test personnel are

    in safe position prior to start test

    *Hoses to be monitored, secured and

    kept in a tidy nad no accumulation

    of debris/sharp/hot objects.

    *Ensure all flange bolts are secure

    before test, Valves only to be

    operated by authorised personnel

    *Ensure inlet/outlet & safety valves,

    pressure gauges are functional.

    * Other personnel be removed fromthe testing area

    *Nobody will be permitted to climb

    up the roof/top portion of tank.

    *Leak repair is not permited during

    pressure test

    * The rate of draining flow shall be

    controled slowly and smooth duly

    considering the integrity of tankwalls to avoid buckling damages.

    4 C H *Medical aids and

    rescue shall be

    available foremergency

    situations.*Pressurise & De

    pressurise shall be in

    steps and as per

    specifications

    *work and water filling

    will be stoppedimmediately if sudden

    increase/decrease/leak

    monitored and be

    alarmed.

    *The whole system

    (DG, Hose routing,

    motor pump, valves,

    test tank etc) shall bemonitored for 24

    hours. Good

    communication system

    be provided and

    ensured between

    monitor, pump

    operator etc.

    *Alarm system/ overpressure valve shall be

    installed & set to

    required pressure.

    *Test pieces shall not

    be detached, repaired,

    loosen or tighten until

    clear depressurisation

    after double checked.

    *Hose be burried

    properly

    Performer 2 A L

  • 7/25/2019 5638 e1 1500 CA Pro 220 Rev.3_ Construction Procedure for Tank Hydrostatic Test

    24/29

    OIL TERMINAL CONSTRUCTION PROJECT (EPC-1), HFZ, SHARJAH

    RISK ASSESSMENT (Page 6 of 11)

    6 PneumaticTesting (if

    required)

    *High pressured

    air

    *Structurecollapse

    *Failure of

    flanges

    *Fatality

    *Injury

    *Assetdamage

    *Combustible gas are not allowed

    to be used for pnenmatic test.

    *Involved area to be barricadedwith Warning signs.

    *Continuous supervision

    *Project Testing procedure shall

    be followed

    * Ensure that the test pack has

    been signed and released for test to

    proceed

    *A complete walk throughinspection on every non-welding

    connection jont shall be done

    always at pressured.

    *Ensure assigned test personnel

    are in safe position prior to start

    test

    *Hoses to be monitored,

    securedwith whip lash arrestor, and

    kept in a tidy no accumulation of

    debris/sharp/hot objects.

    *Ensure all flange bolts are tighten

    before test, Valves be operated by

    authorised personnel only.

    *Ensure inlet/outlet & safety

    valves, pressure gauges are fixed

    properly and functional.

    * Other personnel be removed fromthe testing area, near any valces or

    blinds.

    *Nobody will be permitted to climb

    up the roof/top portion of tank.

    *Leak repair is not permited during

    pressure test.

    4 C H *First aids and

    rescue shall be

    available foremergency

    situations.*Pressurise & De

    pressurise shall be in

    steps as per

    specifications

    *Testing will be

    stopped immediately ifsudden increase/

    decrease/leak

    monitored and be

    alarmed.

    *The whole system

    (DG, Hose routing,

    motor pump, valves,

    test tank etc) shall bemonitored for 24

    hours. Good

    communication system

    be established and

    ensured between

    monitor, pump

    operator etc.

    *Alarm system/ overpressure valve shall be

    installed & set to

    required pressure.

    *Test pieces shall not

    be detached, repaired,

    loosen or tighten until

    clear depressurisation

    after double checked.

    Performer 2 A L

  • 7/25/2019 5638 e1 1500 CA Pro 220 Rev.3_ Construction Procedure for Tank Hydrostatic Test

    25/29

    OIL TERMINAL CONSTRUCTION PROJECT (EPC-1), HFZ, SHARJAH

    RISK ASSESSMENT (Page 7 of 11)

    *Work plat form shall be robust to

    withstand weight of test piece,

    testors and helpers. Proper access,fall arrestors be worn by the testors

    if required.

  • 7/25/2019 5638 e1 1500 CA Pro 220 Rev.3_ Construction Procedure for Tank Hydrostatic Test

    26/29

    OIL TERMINAL CONSTRUCTION PROJECT (EPC-1), HFZ, SHARJAH

    RISK ASSESSMENT (Page 8 of 11)

    7 Cleaning/

    Flushing the

    Tank WithHigh Pressure

    Pump (If

    required)

    *Asphyxiation

    *Hazardous Gas

    *Fall from height

    *Fatality

    *Injury

    *Propertydamage

    *Only competent and project CSE

    trained workers shall be involed in

    the work. Alone worker is notpermitted.

    *Safety supervisor, work supervisor,

    Hole watch, Pressure pump &

    compressor operator must be

    available always

    *Gas testing be done before

    personnel entry

    *All Equipment must be inspectedfor proper function.

    *Required PPEs : high pressure

    water jet protective clothing,

    Helmet, Safety goggle & Gum Boot,

    FBH .

    *Safety and warning signs and

    emergency rescue equipments be

    made available ready.

    *On/off switches of jet system be

    out side of the tank and be

    monitored always.

    *Third party certified Manbasket

    duly written clearly the SWL be

    used by personnel going inside the

    tank. Manbasket will remain inside

    the tank until last person come out

    from the tank. Manbasket shall notbe detached from the crane until

    final removal of person from the

    tank.

    *3 Riggers will be used. 1 inside the

    tank, 1 at the curb ring and 1 at the

    vicinity of crane operator (Outside

    the tank) and manbasket be moved

    by relay the signals by the riggers.

    3 C M *Emergency rescue

    equipment, stretcher be

    made available readily.*Job rotation be done

    *Proper illumination,

    ventilation be ensured

    *all the entrant be

    worn FBH and all PPE

    * Nobody will enter

    under the floating roof,

    if water reside under it.*Bottom plate cleaning

    will be done only if the

    Bottom shell manhole

    flange is opened fully

    and possible dust

    sedimentation is

    removed.

    *Proper

    communication device,

    emergency alarm be

    provided to the

    entrants.

    *Self breathing

    apparatus will be

    available inside the

    tank always for

    emergency purpose

    Performer 1 B L

  • 7/25/2019 5638 e1 1500 CA Pro 220 Rev.3_ Construction Procedure for Tank Hydrostatic Test

    27/29

    OIL TERMINAL CONSTRUCTION PROJECT (EPC-1), HFZ, SHARJAH

    RISK ASSESSMENT (Page 9 of 11)

    8 Confined

    Space Entry

    *Gas

    *Lack of O2

    *Supervisionmissed

    *Poor

    illumination

    *Falling objects

    *Fall from height

    *Toxication

    *Asphyxiation

    *ElectricalBurn/Shock

    *Fire

    *Tumble*Injury

    *Entry restriction Only well

    trained & nominated person.

    *Verify that the ventilation andlighting equipment & service are

    well prepared and in good status

    *Verify that rescue services such

    (rope)life ladders & life line are

    available and that the means for

    summoning them are operable on

    every ingress ,egress and

    evacuation outlet*All Attendant Hole watch will be

    adequately qualified via DEC Hole

    watch training and follow up

    supervisor directed training on the

    job.

    *Frequent breaks or change of

    crews

    *Prevent unauthorized individuals

    to enter or attempt to enter the

    confined space during entry

    operations

    *Adequate warning sign board

    shall be placed.

    *Clear communication and

    coordination among crews

    *Provision of attender.

    *Verify the fitness of workers priorto entry into the tank

    *Readiness of recovery equipments,

    First aid & Respiratory apparatus.

    *Provision of fire extinguishers

    *No resting position works inside

    the tank

    *Before start of each shift work

    proper atmosphere test to be carriedout by competent persons (AGT)

    4 C H *Recording of

    personnel Entry &

    Exit.*Emergency horn

    & light to

    communicate an

    Emergency situation.

    *Provision of FBH &

    Respirator (as per

    requirement)

    *Strict Supervision*Proper illumination

    (100lux minimum)

    *Proper ventilation

    and external

    ventilation shall be

    arranged if required.

    Performer 2 C L

    OIL TERMINAL CONSTRUCTION PROJECT (EPC 1) HFZ SHARJAH

  • 7/25/2019 5638 e1 1500 CA Pro 220 Rev.3_ Construction Procedure for Tank Hydrostatic Test

    28/29

    OIL TERMINAL CONSTRUCTION PROJECT (EPC-1), HFZ, SHARJAH

    RISK ASSESSMENT (Page 10 of 11)

    9 Work At

    Height (Tank

    Top Testingor Testing

    Observation

    and Survey)

    *Trip and Fall

    *Fall of materials

    *Sharp edges

    *Injuries to

    personnel

    * Fatality*Property

    damage

    *Trip and Fall

    *proper Work platform with ladders,

    handrail, mid rail be provided

    *FBH be worn by the personnelalways

    *Testing personnel shall not enter

    into the tank without permission and

    proper arrangements and training

    3 C M *Project WAH

    procedure shall be

    implemented.

    performer 2 C M

    10 General Task

    (Applicable

    to all

    activities)

    *Machineries

    operation

    *Sound

    *Dust*Temperature

    *Debris

    *Tools

    *Extreme weather

    *Slip, Trip Fall

    * Injury

    *Fatality

    *Heat related

    illness*Fire

    *Property

    damage

    *Work

    stoppage

    *TBT to be conducted daily to brief

    the hazards of the task

    *All the workers must be

    Experienced & trained*A trained banksman/signalman

    with flourescent jacket shall be

    provided with each equipment.

    *Use Mandatory PPEs to protect

    Head, Eye, Ear, Body, Hands &

    Foot.

    *Provision of Shelter and water

    points*Fire Extinguishers

    *PTW requirement as per procedure

    *Proper housekeeing shall be

    ensured each shift start and end

    *All the activities should be stopped

    at any extreme weather conditions

    *Work shall be resumed after

    inspection on back to normalweather.

    *All tools should be inspected

    before start of work and shall be

    colour coded periodicaly.

    3 C M *Strict supervision

    *Use the right tools /

    Equipment in correct

    manner.*All project employees

    must be aware of

    emergency response

    plan.

    *Muster point must be

    visible at all times.

    *Job rotation and

    periodic rests*Home made tools are

    prohibited

    Performer 2 B M