Upload
hunjo-femi
View
215
Download
0
Embed Size (px)
Citation preview
8/2/2019 5424Ch11[1]
1/8
FM 5-424
Building Attachments and Services 11-1
Part Four. Other Electrical Procedures
CHAPTER 11
Building Attachments and ServicesAll electrical energy supplied to power-consuming devices and appliances
within a bu ilding mu st pa ss th rough th e electr ical service-ent ra nce equipment
where it is metered, protected, and distributed through branch circuits. The
size is determined by the amount of power-consuming devices connected.
Power from militar y generat ors or t he local power compa ny is delivered intoth e building (overhea d or u ndergroun d) thr ough lead-in condu ctors.
SERVICE WIRESThe service wire from the pole to the build-
ing usually consists of two, three, or four
conductors on separate insulators at the
pole and the building or two- or three-con-
ductor, concentric-type service cables. When
installing attachments and services, use
insulated conductors. If installing an over-
head service drop is impractical, run ser-vices underground from a transformer
installation.
LENGTHKeep service drops less than 100 feet long
for No 8, 6, 4, or 2 wire. For No 0 or larger
wire, do not exceed 75-foot spans unless
proper anchoring and support is provided.
Long or large services should be guyed at
th e line pole.
SIZEAlthough No 6 wire is recommended for
overhead service cable, you should deter-
mine th e size by the ma ximum demand load
of electrical equipment used in each build-
ing. Use Table 11-1, page 11-2, to determine
the size of service conductors needed. Since
these calculations do not take motor-start-ing cur rent s into considerat ion, ma ke a sep-
arate check for objectionable flicker. The
number of wires in the service depends on
th e limits given in th e figures an d oth er fac-
tors, such as equipm ent ra ting. For t wo-wire
service, the limit is two circuits in general-
service buildings and four circuits or a 3-
kilowatt connected load in barracks. Three-
wire services ar e required for great er loads.
Use three- or four-wire service to supply
more th an one service switch.
SERVICE ATTACHMENT AT BUILDINGSAttach the service drop to the building
where outlet wires can be tapped in easily
without trailing along the building. Install
the attachment at least 10 feet above the
ground or 18 feet above a roadway. When
the building is not high enough, install a
riser or a pole to obtain proper clearance.
Figure 11-1, page 11-2, shows a correct
open-wire service installation. Figures 11-2
through 11-13, pages 11-3 through 11-6,
8/2/2019 5424Ch11[1]
2/8
FM 5-424
11-2 Building Attachments and Services
show various methods of attaching service
insulators for several types of building con-
struction. Figures 11-14 through 11-16,
pages 11-6 through 11-8, show methods of
at ta ching services to str uctur es.
Table 11-1. Conduc tor type s and sizes
Copper
(AWG or
MCM)
Aluminum or
Copper-Clad
AL (AWG or
MCM)
Ampere
Rating
4 2 100
3 1 110
2 1/0 125
1 2/0 150
1/0 3/0 175
2/0 4/0 200
3/0 250 225
4/0 300 250
250 350 300
350 500 350
400 600 400
Service house attachment Service pole attachment
Figure 11-1. Open-w ire service instal lat ion
8/2/2019 5424Ch11[1]
3/8
FM 5-424
Building Attachments and Services 11-3
Drill a 5/16 hole through sidingonly.
Wood sheathing
Wood siding 2 service insulator
With composition sheathing, use a 4 service insulatorand drill a 1/4 leader hole into the stud or the plate.
Wood sheathing
Brick veneer6 service insulator
Brick veneer
Plate or support Composition sheathing
Stud Stud
Drill aleader hole.
7 1/2 service insulator plateor special support betweenstuds if furnished
7 1/2 service insulator in studwhere no plate or support isprovided
Figu re 11-2. Wood sid ing
Figure 11-3. Brick-ven eer wood sheath ing
Figure 11-4. Brick-venee r comp osit ion sheat hing
8/2/2019 5424Ch11[1]
4/8
FM 5-424
11-4 Building Attachments and Services
9/16 x 2 wood-screw anchor
Drill a 1/2 hole, 2 1/4deep in the brick.
Brick or cement 2 service insulator
Figure 11-5. Solid mas onry, brick or ceme nt
Hollow tile orcement block
Toggle-bolt serviceinsulator
Drill a 7/8hole.
Figure 11-6. Hollow t i le or cemen t block
Service insulator
Drill a 5/16 leaderhole through theshingles only, 1 1/4above the bottomedge of the shingle.
Figure 11-7. Composit ion or
asbestos sh ingles
Stud
Drill a 11/16hole.
5/8 machine bolt
Platewashers
Figure 11-8. Wood, service-conduc tor tension
over 900 pounds
8/2/2019 5424Ch11[1]
5/8
FM 5-424
Building Attachments and Services 11-5
Drill a hole 3 deep with a7/8 drill.
1/2 x 4 machine boltset in 1/2 machine-bolt anchor
Figure 11-9. Solid masonry
Platewasher
5/8 bolt
350 MCM - 500 MCM
Figure 11-10. Attachm en t w ith dead-end spool
Figure 11-11. Service mas t
8/2/2019 5424Ch11[1]
6/8
FM 5-424
11-6 Building Attachments and Services
Feed-through dead end
Figure 11-13. Method of attachin g
mult ip le -conductor serv ices
Service head
Install straps in theopposite direction.
Weatherproofingmaterial
30
30
Sill plate
Ground wire
Ground clamp
Ground rod
Secure to thebuilding with astaple or a strap.
Note: The service cable must beproperly supported.
Figure 11-12. Expos ed service-
entrance cab le
Due to copyright restrict ions ,
this graphic i s un avai lable
ele ctron ically. You m us t
refer to the hard copy
of this product to v iew
this graphic .
Figure 11-14. Entrance he ad below the
roof l ine
8/2/2019 5424Ch11[1]
7/8
FM 5-424
Building Attachments and Services 11-7
Due to copyright restr ict ions , this
graph ic is unav ailable electronical ly.
You mu st refer to the h ard copy
of this produc t to v iew this graphic .
Figure 11-15. Typical un dergroun d servic e
8/2/2019 5424Ch11[1]
8/8
FM 5-424
11-8 Building Attachments and Services
Due to copyright restr ict ions , this
graphic is u na vailable electronic al ly.
You m ust re fer to th e h ard copy
of this product to v iew this graphic .
Figure 11-16. Typical overhead service