AFFICHEURS DÉPORTÉS - REMOTE INTERFACES ATyS D10 & D20 Notice d’utilisation - Operating instructions F GB SOCOMEC GROUP SWITCHING PROTECTION & UPS MAKE YOUR BUSINESS SAFE

532_212_a_gb

Embed Size (px)

Citation preview

  • AFFICHEURS DPORTS - REMOTE INTERFACESATyS D10 & D20

    Notice dutilisation - Operating instructionsF GB

    SOCOMEC GROUP SWITCHING PROTECTION & UPS

    MAKE YOUR BUSINESS SAFE

    532_212_a 9/02/05 9:00 Page 1

  • SOCOMEC - Rf. : 532 212 A2

    PRSENTATION GNRALE ATyS D10 et D20 _______3INSTALLATION ATyS D10 et D20 ___________________4

    Montage _______________________________________4Raccordements _________________________________4Caractristiques_________________________________4

    UTILISATION ATyS D10 ___________________________5Affichage_______________________________________5

    UTILISATION ATyS D20 ___________________________6Affichage_______________________________________6Clavier _________________________________________7Version logiciel __________________________________7Programmation _________________________________8Exploitation____________________________________18Fonctionnement________________________________20Visualisation ___________________________________20

    Som

    mai

    re

    F

    GENERAL PRESENTATION ATyS D10 & D20________23INSTALLATION ATyS D10 & D20___________________24

    Mounting _____________________________________24Connection____________________________________24Characteristics_________________________________24

    OPERATION ATYS D10___________________________25Display _______________________________________25

    OPERATION ATyS D20 ___________________________26Display _______________________________________26Keypad _______________________________________27Software version _______________________________27Programming __________________________________28Control and Test modes_________________________38Operational sequences__________________________40Visualisation ___________________________________40

    Sum

    mar

    y

    GB

    532_212_a 9/02/05 9:00 Page 2

  • ATyS D10 and D20 models are remote interfacesdesigned for easy integration on front panels. They canbe connected to ATyS 6e, 6m and C30 products to allowremote access to display or control features.

    23SOCOMEC - Rf.: 532 212 A

    Remote interfaces ATySGENERAL PRESENTATIONATyS D10 & D20

    532_212_a 9/02/05 9:00 Page 23

  • Mounting

    Door fixing: 2 holes, diameter 22.5 mm Maximum thickness of the door: 20 mm

    Connection

    Connection only on AtyS 6e, 6m or C30 products.

    > CableRJ45 type 8/8 not isolated

    > Maximum cable length3 m

    > Tightning torque4 N.m

    Characteristics

    > IPIP21 standardIP54 using gasket

    > Operation Temperature: -10 to + 55 C hygrometry: 80% humidity at 55 C

    95% humidity at 40 C

    Remote interfaces ATySINSTALLATIONATyS D10 & D20

    24 SOCOMEC - Rf.: 532 212 A

    1

    ATY

    S 1

    47 A

    (1) RJ45 plug for ATyS connection

    22.5

    4036

    20

    = =

    96 x 96

    ATY

    S 1

    61 A

    Door drilling

    ATyS C30

    Type RJ45

    ATyS D10/D20

    43

    21

    ATY

    S 3

    13 A

    GB

    532_212_a 9/02/05 9:00 Page 24

  • 25SOCOMEC - Rf.: 532 212 A

    ATyS D10 allows remote display of transfer systempositions, sources availability and operational mode.Programming and operations remain available directly onmaster product (ATyS 6e, 6m or C30).

    Remote interfaces ATySOPERATIONATyS D10

    Display

    Source 1 available Power On

    ATyS Product faulty, transfer error Possible to reset after error

    disappearance the power suppliesof the master product (ATyS 6e,6m, C30) for 3 minutes

    Transfer system inposition 1

    Transfer system inAutomatic mode

    Transfer system inposition 0

    Transfer system inposition 2

    Source 2 available

    ATY

    S 1

    45 B

    532_212_a 9/02/05 9:00 Page 25

  • Remote interfaces ATySOPERATIONATyS D20

    26 SOCOMEC - Rf.: 532 212 A

    DisplayKeypadSoftware versionProgrammingControl and Test modesOperational sequencesVisualisation

    Display

    ATyS D20 allows remote display of transfer systempositions, sources availability, operational mode andmetering. Programming and operations (Test andControl) are also available. Master product (ATyS 6e, 6mor C30) display is deactivated as soon as the remoteinterface is connected.

    Power On

    Source 1 available

    Manualmodeactive Padlock*

    Product faulty, transfer error Possible to reset after error

    disappearance: switch off thepower supplies of the masterproduct (ATyS 6e, 6m, C30)for 3 minutes

    Transfer system inposition 1

    Transfer system inautomatic mode

    Control mode active Test mode active Programming mode active

    Transfer systemin position 0

    Transfer systemin position 2

    Source 2 available

    ATY

    S 1

    46 B

    * only on ATyS 6e and 6m

    532_212_a 9/02/05 9:00 Page 26

  • Display

    Software version

    Keypad

    Software version of the master product is displayedimmediately after ATyS 6e, 6m or C30 power on.

    Access to AUT, Test,Control and Prog modes

    Direct Access to Test and Controlfunctionalities or navigation

    Allows main menu accessin visualisation mode orvalidation

    Priority source

    Informations source 1 source 2 sources 1 & 2(split screen)

    Power factorCapacitive or inductive

    Phases (wires) displayed Units

    Values

    Signedvalues(power)

    ATY

    S 3

    18 A

    ATY

    S 1

    46 C

    ATY

    S 3

    19 A

    Remote interfaces ATyS

    OPERATION

    27SOCOMEC - Rf.: 532 212 A

    532_212_a 9/02/05 9:00 Page 27

  • Remote interfaces ATySOPERATIONATyS D20

    28 SOCOMEC - Rf.: 532 212 A

    DisplayKeypadSoftware versionProgrammingControl and Test modesOperational sequencesVisualisation

    > Enter into programming mode

    Step 1: Press the mode push button until Prog led is blinking

    Step 2: Press validation push button. PROG led becomes fixed and access code is displayed

    Step 3: Enter access code (1000 factory default) using keypad left,right, top and bottom

    Step 4: Press validation push button to enter programming mode

    > Programming mode exit

    Step 1: Press the ESC push button when not entering any value, to come back to mainprogramming menu

    Step 2: Press again on ESC push button to exit programming

    New Active mode (Automatic or Manual) depends on information from the master device (ATyS 6e, 6m ou C30)

    Programming

    532_212_a 9/02/05 9:00 Page 28

  • Programming

    > Navigation in programming mode

    Step 1: To access required menu, press navigation push buttonsleft and right

    Step 2: To access parameter to modifypress navigation push buttons top and bottom

    Step 3: To modify the parameter, press push button rightto make the required parameter blinking

    Step 4: Press push buttons top and bottom to increment ordecrement the value of the parameter

    Step 5: Press validation push button to validate

    In case of parameter displayed on 2 lines, press validation push button after first line modificationto access next one

    ESC push button allows to come back to main menu or to cancel the modification

    Remote interfaces ATyS

    OPERATION

    29SOCOMEC - Rf.: 532 212 A

    532_212_a 9/02/05 9:00 Page 29

  • Programming

    ARCHITECTURE OF THE PROGRAMMING MENU

    Remote interfaces ATySOPERATIONATyS D20

    30 SOCOMEC - Rf.: 532 212 A

    DisplayKeypadSoftware versionProgrammingControl and Test modesOperational sequencesVisualisation

    *

    **** ** ** ** **

    ** **** **

    **

    ** ** **

    ATY

    S 3

    27 A

    532_212_a 9/02/05 9:00 Page 30

  • Remote interfaces ATyS

    OPERATION

    31SOCOMEC - Rf.: 532 212 A

    *on

    ly o

    n A

    tys

    6m**

    optio

    n on

    ATy

    S 6

    e &

    6m

    ***

    only

    on

    ATyS

    C30

    ****

    visi

    ble

    if o

    ptio

    n LS

    sel

    ecte

    d a

    nd a

    ctiv

    e

    ** ** ** ** ****

    **

    ***

    ***

    ***

    532_212_a 9/02/05 9:00 Page 31

  • Programming

    VARIABLES CHARACTERISTICS

    Remote interfaces ATySOPERATIONATyS D20

    32 SOCOMEC - Rf.: 532 212 A

    DisplayKeypadSoftware versionProgrammingControl and Test modesOperational sequencesVisualisation

    > Setup

    LCD Denomination Setting range Default values

    nt Type of network 1BL, 2BL, 2NBL 4NBL(cf. ATyS 6 or C30 instruction manual) 3NBL, 4NBL,

    41NBL, 42NBL

    Un Network Nominal voltage 100 to 480 V 400 VPhase-Neutral voltage for 1BL & 41NBLPhase-Phase voltage for others

    ScE** Source 1 - Switch I or II configuration I, II ISource 1 (controlled and displayed) linked to switch I or II (depending on cabling)

    Fn Network nominal Frequency 50 or 60 Hz 50 Hz

    Ct* CTs primary current 50 to 5000/5 A 500/5 A(5 A secondary CT)

    Gen Genset start signal state NO, NC NONormally opened or closed

    Pri Network priority selection 1, 2 1Keypad selection (1 or 2)Also possible via external contactUsing option

    Mtf Manual Retransfer Yes, No NoActivation of the feature

    LoG Type of control logic selection IMP, CON, brE*** IMPImpulse, contactor or breaker***

    AC*** Number of position auxiliary contacts used, depending on transfer 0, 2, 3 2device type (switch, contactor, breaker)

    rn1 Allows 0 position command after loss of main source (source 1) Yes, No No

    rn2 Allows 0 position command after loss of emergency source (source 2) Yes, No No

    CrS Number of permutation counter Reset Yes, No No

    CP Programming code modification 0001 to 9999 1000Possible to change the code

    * only on AtyS 6m** only on ATyS 6e & 6m*** only on ATyS C30.

    532_212_a 9/02/05 9:00 Page 32

  • Programming

    > Voltage thresholds

    > Frequency thresholds

    Remote interfaces ATyS

    OPERATION

    33SOCOMEC - Rf.: 532 212 A

    LCD Denomination Setting range Default values

    oU Network 1 over voltage threshold 102 - 120% 115%

    oUh Network 1 over voltage threshold hysteresis 101 - 119% 110%(< oU)

    uU Network 1 under voltage threshold 80 - 98% 85%

    uUh Network 1 under voltage threshold hysteresis 81 - 99% 95%(> uU)

    oU Network 2 over voltage threshold 102 - 120% 115%

    oUh Network 2 over voltage threshold hysteresis 101 - 119% 110%(< oU)

    uU Network 2 under voltage threshold 80 - 98% 85%

    uUh Network 2 under voltage threshold hysteresis 81 - 99% 95%(> uO)

    Values defined are % of nominal values.Hysteresis thresholds must be programmed according to over and under voltage thresholds (respectively under & above).

    LCD Denomination Setting range Default values

    oF Network 1 over frequency threshold 101 to 120% 105%

    oFh Network 1 over frequency threshold hysteresis 100.5 - 119.5% 103%(< oF)

    uF Network 1 under frequency threshold 80 - 99% 95%

    uFh Network 1 under frequency threshold hysteresis 80.5 - 99.5% 97%(> uF)

    oF Network 2 over frequency threshold 101 - 120% 105%

    oFh Network 2 over frequency threshold hysteresis 100.5 - 119.5% 103%(< oF)

    uF Network 2 under frequency threshold 80 - 99% 95%

    uFh Network 2 under frequency threshold hysteresis 80.5 - 99.5% 97%(> uF)

    Values defined are % of nominal values.Hysteresis thresholds must be programmed according to over and under frequency thresholds (respectively under & above).

    532_212_a 9/02/05 9:00 Page 33

  • Programming

    Remote interfaces ATySOPERATIONATyS D20

    34 SOCOMEC - Rf.: 532 212 A

    DisplayKeypadSoftware versionProgrammingControl and Test modesOperational sequencesVisualisation

    > Timers

    LCD Denomination Setting range Default values

    Mft Main Failure Timer From 0 to 60 s 5 sDelays priority network failure detection

    dtt Delay on transfer timer From 0 to 60 s 5 sEmergency network stability validation before transfer

    OMf O Main Failure Timer From 0 to 20 s 0 sRest in O position when transferringfrom main network to emergency network

    Mrt Main Return Timer From 0 to 30 min 1 minMain network stability validation before re-transfer

    OMr O Main Return Timer From 0 to 20 s 5 sRest in O position when re-transferring from emergency network to main network

    Cdt Cool Down Timer From 0 to 10 min 4 minAllows generator cooling down period after loadsretransfer from emergency source (generator) to Main source

    > Communication

    LCD Denomination Setting range Default values

    Add Device address 1 to 247 5

    bd Communication speed 2400, 4800, 9600, 960019200, 38400

    StoP Stop bit 1, 2 1

    PAr Parity bit No, Odd, Even No

    Only on ATyS 6e or 6m in case of optional communication module.

    532_212_a 9/02/05 9:00 Page 34

  • Input (In2, Ft2) and output (Ou1, S1A) programming example:

    Refer to ATyS C30, 6e or 6m instruction manualfor terminals identification.

    Input/Output Function Relay State

    I1 to I4 Ft1, Ft2, Ft3, Ft4, Pri, NO or NCMtf, S2A, Man, TOL, TFL, EJP, CTS

    O1 to O4 S1A, S2A, LS, / NO

    ATY

    S 3

    28 A

    Step 1: Press right push button to makefirst variable blinking (Ft2 ou S1A)

    Step 2: press top and bottompush buttons to modify the variable

    Step 3: press validation

    Step 4: press bottom push button toacces nO variable selection

    Programming

    > Inputs/Outputs 2 inputs (In1, In2) and 2 outputs (Ou1, Ou2) as standard

    on ATyS C30.

    Possibility to connect 2 modules 2 Inputs/2 Outputson ATyS 6e & 6m.

    - First module: In1, In2, Ou1, Ou2- Second module In3, In4, Ou3, Ou4.

    Remote interfaces ATyS

    OPERATION

    35SOCOMEC - Rf.: 532 212 A

    532_212_a 9/02/05 9:00 Page 35

  • Outputs

    Programming

    Variables descriptionInputs

    Remote interfaces ATySOPERATIONATyS D20

    36 SOCOMEC - Rf.: 532 212 A

    DisplayKeypadSoftware versionProgrammingControl and Test modesOperational sequencesVisualisation

    Variable Description

    Ft1 Fault input 1. The fault led is blinking as soon as the input is active andFt1 is displayed on LCD. Reset when the input is de-activated

    Ft2 Fault input 2. The fault led is blinking as soon as the input is active and Ft2 is displayed on LCD.Reset when the input is de-activated

    Ft3* Fault input 3. The fault led is blinking as soon as the input is active and Ft3 is displayed on LCD. The transfer switch is immediately driven in 0 position.Keypad action (Esc) necessary to Reset the fault

    Ft4* Fault input 4. The fault led is blinking as soon as the input is active and Ft4 is displayed on LCD. The transfer switch is immediately driven in 0 position.Keypad action (Esc) necessary to Reset the fault

    Pri Priority network selection.Network 1 has priority when input is not activated. Network 2 has priority if input is active

    Mtf Remote manuel re-transfer. Feature identical to manual re transfert on keypad.Re-transfer from priority network to backup network is allowed from input activation (1 s front).The Mtf variable in the setup menu must be selected (Yes) to allow input recognition

    S2A Information source 2 available (Genset) used instead of voltage/ frequency measurementfrom ATyS (inhibited when S2A is selected)

    Man** Information transfer system in manual mode.All automatic commands (+ test on load and control commands) are inhibited as soon as the input is activated

    CTS** Remote transfer control. Possible to initiate transfer from priority source to backup sourcebefore DTT ends. If DTT is set to its maximum value (60s), the transfer is initiated as soon asthe input is activated (1 s front)

    TOL** Remote test on load. Started from input activation.Re-transfer is blocked until input de-activation

    TFL Remote test off load.Started from input activation (remote genset start /stop)

    EJP 2 inputs one automatically affected to EJP input 1 for EJP advice, to start generator input 2 to transfer on emergency sourceRetransfer is activated when input 2 disapears

    * only on ATyS C30, specific fault operation (Ft2 and Ft3)** only as option on ATyS C30, standard features on ATyS 6e et 6m.

    Variable Description

    S1A Source 1 available.Output activated as soon as source 1 is considered available (similar to front led source 1)

    S2A Source 2 available.Output activated as soon as source 2 is considered available (similar to front led source 2)

    LS Load shedding relay. LS timer corresponds to time available to disconnect the shed loads.The relay is activated before permutation on standby network according to LS timer.The relay is de-activated after retransfer on mains network and LS timer countdown

    532_212_a 9/02/05 9:00 Page 36

  • Programming

    Remote interfaces ATyS

    OPERATION

    37SOCOMEC - Rf.: 532 212 A

    LOAD SHEDDING CONFIGURATIONLS variable allows associated LS timer configuration.

    Output Associated funciton Setting range Default value

    O1 to O4 LS 0 to 60 s ( DTT)* 2

    > Example: load shedding configuration

    function

    timer

    Step 1: Press right push button to makefirst variable blinking (LS)

    Step 2: press push buttons top andbottom to modify the variable

    Step 3: Press validation

    Step 4: Press bottom push buttonto access timer value configuration

    ATY

    S 3

    29 A

    GB

    * In case of DTT variable configuration below LS, LS will be automatically set to to DTT value.

    532_212_a 9/02/05 9:00 Page 37

  • Control and Test modes

    It is possible to start test sequences or to controlelectrically the changeover system from keypad.

    NAVIGATION

    Remote interfaces ATySOPERATIONATyS D20

    38 SOCOMEC - Rf.: 532 212 A

    DisplayKeypadSoftware versionProgrammingControl and Test modesOperational sequencesVisualisation

    > Enter Control or Test modes

    Step 1: Press mode push button to make test or control led blinking

    Step 2: Press validation push button to make control or test led become fixed

    CONTROL MODE

    Access code is displayed directly

    TEST MODE

    It is possible to test leds and LCD without entering any code by pressing directly

    Test on load or test off load access codes are displayed after pressing or

    Enter the code 4000 using left, right, topand bottom push buttons

    Press validation push button to enter

    532_212_a 9/02/05 9:00 Page 38

  • Control and Test modes

    > Exit control or test modes

    Press ESC push button

    The new operational mode (automatic or manual) depends on information from masterATyS (6e, 6m ou C30)

    > Control or Test modes use

    Direct access by pressing and

    To start a test (off load or on load) or to control the changeover switch electrically,

    press , and push buttons

    Remote interfaces ATyS

    OPERATION

    39SOCOMEC - Rf.: 532 212 A

    532_212_a 9/02/05 9:00 Page 39

  • Operational sequences

    Visualisation

    Refer to ATyS 6e, 6m or C30 manuals for moreinformation on operational sequences and controls: sources control, tests cycles, loss of priority source sequence, priority source return sequence.

    It is possible to display controlled parameters in bothautomatic and manual modes (but not during program-ming).No code is required to perform visualisation.Permutation cycles have priority over visualisation anddisplay timer countdown during cycle operation.

    Without keypad activation or any operational sequenceduring 5 minutes, the LCD comes back to default displaymode and stops the backlight.

    > If both sources are available: One visualisation screen is split into 2 parts and

    displays simultaneously voltage and frequency valueson both networks.

    If a timer is active, on one of the source, its count-down is displayed instead of voltage and frequencyvalues.

    Examples:

    > If only one source is present: During permutation cycle, voltage and frequency

    values of the available source (active) are displayedon 2 lines. The name of the active timer and its count-down are displayed on remaining 2 lines.

    Out of a permutation cycle, phase to phase voltagesand frequency are displayed.

    Examples:

    Remote interfaces ATySOPERATIONATyS D20

    40 SOCOMEC - Rf.: 532 212 A

    DisplayKeypadSoftware versionProgrammingControl and Test modesOperational sequencesVisualisation

    Press left, right, top & bottom push buttonsto access available screens

    Press navigation push button to navigate in visualisation, displaying all available screens

    ATY

    S 3

    31 A

    ATY

    S 3

    32 A

    532_212_a 9/02/05 9:00 Page 40

  • Visualisation

    ARCHITECTURE OF VISUALISATION MENU

    Remote interfaces ATyS

    OPERATION

    41SOCOMEC - Rf.: 532 212 A

    *

    **

    ***

    ****

    ***

    ***

    ***

    ***

    * only on AtyS 6e & 6m** only U3-1 on AtyS C30*** only on ATyS 6m**** visible if option LS selected and active

    ATY

    S 3

    33 A

    532_212_a 9/02/05 9:00 Page 41

  • 532_212_a 9/02/05 9:00 Page 42

  • 532_212_a 9/02/05 9:00 Page 43

  • SOCOMEC - Ref.: 532 212 A - 02/05

    This document is not contractual. SOCOMEC reservesthe right to modify features without prior notice in view ofcontinued improvements.