Detailed Installer GuideProgrammable Thermostats
1 Specifications 2 Installation and Wiring 3 Quick Reference 4 Installer Settings 5 System Testing
• Possible electric shock or damage to equipment can occur.• Disconnect power before beginning installation.
Caution
This thermostat requires 24 Volt AC Power or 2 properly installed “AA” Alkaline batteries for proper operation. When connecting 24 Volt AC Power the batteries may be installed as a backup.
For use only as described in this manual. Any other use will void warranty.
5020 Single Stage Heat / Cool Conventional or Heat Pump
5220 Up to 3 Heat / 2 Cool Heat Pump Up to 2 Heat / 2 Cool Conventional
Warning For installation by experienced service technicians only.
®
This thermostat is compatible with: • Singlestageheat/coolconventionalandheatpumpsystems • Conventionalsystemsupto2stagesofheatingand2stagesofcooling(5220only) • Heatpumpsystemsupto3stagesofheatingand2stagesofcooling(5220only) • 250–750millivoltheatingonlysystems • 2or3wirehydroniczonesystems
Electrical and control specifications: • ElectricalRating:24VoltAC • 1ampmaximumloadperterminal • ACPower:18–30VoltsAC • DCPower:3.0VoltDC(2“AA”AlkalineBatteriesIncluded) • ControlRange:45°–90°F(7°–32°C) • TemperatureAccuracy:+/-1°F(+/-.5°C) • OutdoorTemperatureDisplayRange:-40°-120°F(-40°-49°C)
Terminations • 5020:Rc,Rh,W1,C,Y1,O/B/V3,G,S2,S1 • 5220:Rc,Rh,W2,W1/E/W3,C,L,Y2,Y1,O/B/V3,G,S2,S1
1 Specifications
5020W-100-04
Model number is located on back of thermostat.
PREMIERSERIES
Thermostat LocationInstallthethermostatapproximately5feet(1.5m)abovethefloorinanareathathasagoodamountofaircirculationandmaintainsanaverageroomtemperature.
Avoidinstallationinlocationswherethethermostatcanbeaffectedbydrafts,deadairspots,hotorcoldairducts,sunlight,appliances,concealedpipes,chimneysandoutsidewalls.
Installer Guide 2
Install your new Braeburn thermostat in 4 basic steps:1 InstalltheSub-Base2 ProvidePower3 ConnectYourWires4 AttachThermostattoSub-Base
Install the Sub-Base: •Removethesub-basefromthebodyofthethermostat.•Mountthesub-baseasshownbelow:
Warning Disconnect power before beginning installation.
2 Installation and Wiring
1
UP UP
Drill 3/16” pilot holes in your desired location. Use supplied anchors for drywall or plaster.
3 Installer Guide
Provide Power
C
24VAC Power Terminal (C)
2
Wiring Terminations for model 5020
Terminal Function Description
Rc Input 24VoltACCoolingTransformer (DualTransformerSystemsOnly)
Rh Input PowerConnection(24VoltACHeating TransformerorMillivoltPowerSource)
G Output FanControl
W1 Output ConventionalHeatRelay
O/B/V3 Output (O)CoolActiveReversingValve (B)HeatActiveReversingValve (V3)ZoneValvePowerClose
Y1 Output CompressorRelay
C Input 24VoltACTransformerCommon
S1
S2
Connect Your Wires3
Input OptionalRemoteSensor(indoororoutdoor)
+
+
• For24VoltACpower,youmustconnectthecommonsideofthetransformertotheCterminalonthethermostatsub-base.In dualtransformerinstallations,thetransformercommonmustcomefromthecoolingtransformer.
• Forbatterypower,insertthe2supplied“AA”typealkalinebatteriesintothebatterycompartmentlocatedintherear housingofthethermostat.MakesuretopositionthePositive(+)andNegative(-)sidesofthebatteriescorrectlywith the+/-symbolsinthebatterycompartment.
Batteries Installed as Shown
Installer Guide 4
Wiring Terminations for model 5220
Terminal Function Description
Rc Input 24VoltACCoolingTransformer (DualTransformerSystemsOnly)
Rh Input PowerConnection(24VoltACHeating TransformerorMillivoltPowerSource)
G Output FanControl
W1/E/W3 Output (W1)1stStageConventionalHeat, (E)EmergencyHeat, (W3)3rdStageAuxiliaryHeat
W2 Output 2ndStageConventionalHeat
O/B/V3 Output (O)CoolActiveReversingValve (B)HeatActiveReversingValve (V3)ZoneValvePowerClose
Y1 Output 1stStageCompressor
Y2 Output 2ndStageCompressor
L Input SystemMalfunctionIndicator
C Input 24VoltACTransformerCommon
S1
S2
Connecting Your Wires (continued)3
Input OptionalRemoteSensor(indoororoutdoor)
5 Installer Guide
Heat Only or Millivolt Set System Type to 11CONV
Rh PowerConnection[note 2]
W1 HeatRelay
G FanRelay[note 4]
C 24VoltACTransformerCommon[note 1, 3]
1 HEAT / 1 COOL Single or Dual Transformer Set System Type to 11CONV
Rh 24VoltACPower(heatingtransformer)[note 2]
Rc 24VoltACPower(coolingtransformer)[note 2]
W1 HeatRelay
Y1 CompressorRelay
G FanRelay
C 24VoltACTransformerCommon[note 1, 3]
NOTES - Conventional Systems[1]Optional24VoltACcommonconnection.[2]Onlyremovefactoryinstalledjumperfordual transformersystems.[3] Indualtransformersystems,transformer commonmustcomefromcoolingtransformer.[4] Ifneededforsystem.
Provide disconnect and overload protection as required.
2 HEAT / 2 COOL Single or Dual transformer Set System Type to 22CONV
Rh 24VoltACPower(heatingtransformer)[note 2]
Rc 24VoltACPower(coolingtransformer)[note 2]
W1 HeatRelayStage1
W2 HeatRelayStage2
Y1 CompressorRelayStage1
Y2 CompressorRelayStage2 [note 4]
G FanRelay
C 24VoltACTransformerCommon[note 1, 3]
Typical Wiring ConfigurationsNOTE: The “System Type” option will be configured in the Installer Settings section. The 5020 is a single stage thermostat and not intended for multi stage equipment.
Conventional Systems
NOTE: Additional options are configured in the Installer Settings section.
S1
S2
NOTES - Additional Wiring Options[1]Theseterminalscanbeusedtoconnecta Braeburn® indoororoutdoorremotesensor.
Additional Wiring Options
IndoororOutdoorRemoteSensor[note 1]
Hydronic Heat Only Set System Type to 1HD Rh 24VoltACPower(heatingtransformer)[note 2]
W1 ZoneValvePowerOpen
V3 ZoneValvePowerClose
G FanRelay[note 4]
C 24VoltACTransformerCommon[note 1]
Hydronic Heat / 1 Cool Set System Type to 11HD
Rh 24VoltACPower(heatingtransformer)[note 2]
Rc 24VoltACPower(coolingtransformer)[note 2]
W1 ZoneValvePowerOpen
V3 ZoneValvePowerClose
Y1 CompressorRelay
G FanRelay
C 24VoltACTransformerCommon[note 1, 3]
Installer Guide 6
1 HEAT / 1 COOL - No Auxiliary HeatSet System Type to 11HP
Rh 24VoltACPower
Rc ConnectedtoRhwithsuppliedJumperWire
O/BChangeoverValve [note 2]
Y1 CompressorRelay
G FanRelay
C 24VoltACTransformerCommon [note 1]
3 HEAT / 2 COOL – Including Auxiliary HeatSet System Type to 32HP
Rh 24VoltACPower
Rc ConnectedtoRhwithsuppliedJumperWire
O/B ChangeoverValve [note 2]
Y1 Compressor1Relay(1ststageheating/cooling)
Y2 Compressor2Relay(2ndstageheating/cooling)
W3 AuxiliaryHeatRelay(3rdstageheating)[note 5]
G FanRelay
C 24VoltACTransformerCommon[note 1]
L OptionalSystemFaultMonitor[note 4]
2 HEAT / 1 COOL - Including Auxiliary Heat Set System Type to 22HP
Rh 24VoltACPower
Rc ConnectedtoRhwithsuppliedJumperWire
O/BChangeoverValve[note 2]
Y1 CompressorRelay(1ststageheating/cooling)
W2 AuxiliaryHeatRelay(2ndstageheating)[note 3]
E EmergencyHeatRelay[note 3]
G FanRelay
C 24VoltACTransformerCommon[note 1]
L OptionalSystemFaultMonitor[note 4]
2 HEAT / 2 COOL - No Auxiliary HeatSet System Type to 32HP
Rh 24VoltACPower
Rc ConnectedtoRhwithsuppliedJumperWire
O/BChangeoverValve[note 2]
Y1 Compressor1Relay(1ststageheating/cooling)
Y2 Compressor2Relay(2ndstageheating/cooling)
G FanRelay
C 24VoltACTransformerCommon[note 1]
L OptionalSystemFaultMonitor[note 4]
NOTES - Heat Pump Systems[1] Optional24VoltACcommonconnection.[2] O(coolactive)orB(heatactive)isselectedin theInstallerSettingsmenu.[3] Installafieldsuppliedjumperbetweenthe W2andW1/E/W3terminalsifthereis noseparateemergencyheatrelayinstalled.
[4] IftheLterminalisused,the24VoltACcommon mustbeconnected(Cterminal).[5] Ifaseparateemergencyheatrelayisinstalled,the W1/E/W3terminalshouldhaveboththeauxiliary heat1relayandemergencyheatrelayconnected.
Provide disconnect and overload protection as required.
Typical Wiring Configurations NOTE: The “System Type” option will be configured in the Installer Settings section. The 5020 is a single stage thermostat and not intended for multi stage equipment.
Heat Pump Systems
NOTE: Additional options are configured in the Installer Settings section.
S1
S2
NOTES - Additional Wiring Options[1]Theseterminalscanbeusedtoconnecta Braeburn® indoororoutdoorremotesensor.
Additional Wiring Options
IndoororOutdoorRemoteSensor[note 1]
INSTRUCTIONS
DAY/TIME
7 Installer Guide
NOTE: This thermostat ships configured as a 1H/1C conventional thermostat. Confirm installer settings. See page 10.
UP UP
S1
S2
G
Y1
Y2
A
H
L
C
W1/E/AUX1
W2/AUX2
W3/O/B
RH
RC
L S1L
S2
G
C
W1/E/AUX/AUX/AUX/AUX1111
4 Attach Thermostat to Sub-Base
3) InsertQuickReferenceCardintoslot ontopofthermostat.
1) Lineupthethermostatbodywiththesub-base.2) Carefullypushthethermostatbodyagainstthe sub-baseuntilitsnapsinplace.
BACK NEXT
Installer Guide 8
3 Quick Reference
1
2
3 4
7 8
9
10
11
5 6
12
13
14
Room Temperature...................... Displaysthecurrentroomtemperature
Set Temperature.......................... Displaysthecurrentsetpointtemperature
BACK Indicator*........................... BACKbuttonisactive
NEXT Indicator*............................ NEXTbuttonisactive
Outdoor Temperature Indicator... Displaysalongwiththeoutdoortemperaturereading**
Service Indicators ...................... Displaysvariousservice/maintenanceinformation
Fan Indicator................................ Indicateswhenthesystemfanisrunning
Low Battery Indicator.................. Indicateswhenthebatteriesneedtobereplaced
Hold Mode Indicator ................... IndicatesifthethermostatisinHOLDmode
Lock Mode Indicator ................... Indicatesifthethermostatislocked
System Status Indicator ............. Displaysinformationaboutthestatusofthesystem
Day of the Week........................... Displaysthecurrentdayoftheweek
Program Event Indicator.............. Displaystheprogramevent
Time of Day ................................. Displaysthecurrenttimeofday
1
2
3
4
5
6
7
8
9
10
11
Thermostat Display
12
13
14
*BACKand NEXTaresecondaryfunctionsofthePROGandHOLDbuttons.Wheninprogrammingor configurationmodes,BACKandNEXTappearinthedisplayscreenindicatingthatthePROGand HOLDbuttonsnowfunctionasBACKandNEXT.
**Alsosee#24onpage9.
9 Installer Guide
INSTRUCTIONS
DAY/TIME
BACK NEXT
15
16
23
17 18 19 20 21
22
Room Temperature...................... Displaysthecurrentroomtemperature
Set Temperature.......................... Displaysthecurrentsetpointtemperature
BACK Indicator*........................... BACKbuttonisactive
NEXT Indicator*............................ NEXTbuttonisactive
Outdoor Temperature Indicator... Displaysalongwiththeoutdoortemperaturereading**
Service Indicators ...................... Displaysvariousservice/maintenanceinformation
Fan Indicator................................ Indicateswhenthesystemfanisrunning
Low Battery Indicator.................. Indicateswhenthebatteriesneedtobereplaced
Hold Mode Indicator ................... IndicatesifthethermostatisinHOLDmode
Lock Mode Indicator ................... Indicatesifthethermostatislocked
System Status Indicator ............. Displaysinformationaboutthestatusofthesystem
Day of the Week........................... Displaysthecurrentdayoftheweek
Program Event Indicator.............. Displaystheprogramevent
Time of Day ................................. Displaysthecurrenttimeofday
*BACKand NEXTaresecondaryfunctionsofthePROGandHOLDbuttons.Wheninprogrammingor configurationmodes,BACKandNEXTappearinthedisplayscreenindicatingthatthePROGand HOLDbuttonsnowfunctionasBACKandNEXT.
**Alsosee#24onpage9.
24
Reset Button ............................... Resetscurrenttime,programandusersettings
SYSTEM Button............................ Selectsthesystemyouwanttocontrol
DAY/TIME Button.......................... Setsthecurrenttimeanddayoftheweek
PROG Button................................. Selectsprogrammingmodeorpressfor3secondstoselectSpeedSet® BACK Button*............................... SecondaryfunctionofthePROGbutton-movesbackasetting
HOLD Button................................. Enters/ExitstheHOLDmode(programbypass) NEXT Button*............................... SecondaryfunctionoftheHOLDbutton-movestonextsetting
RETURN Button............................ Returnstonormalmodefromprogramorsettingmodes
FAN Button................................... Selectsthesystemfanmode
Quick Reference Instructions...... Storedinslotlocatedattopofthermostat
SpeedBar® ................................... Increasesordecreasessettings(time,temperature,etc.)
Outdoor Temperature................... IfaBraeburn®outdoorsensorwasconnectedyoucanviewtheoutdoor temperaturebypressingthePROGandHOLDbuttonsatthesametime.
Battery Compartment.................. Locatedinthebackofthermostat
Thermostat15
16
17
18
19
20
21
22
23
24
*BACKand NEXTaresecondaryfunctionsofthePROGandHOLDbuttons.Wheninprogrammingor configurationmodes,BACKandNEXTappearinthedisplay,indicatingthatthePROGandHOLDbuttons nowfunctionasBACKandNEXT.
INSTRUCTIONS
DAY/TIME
TheInstallerSettingsmustbeproperlyconfiguredinorderforthisthermostattooperatecorrectly.TheInstallerSettingsaremenudriven.Theportionofthesesettingsthatdonotapplytoyoursetupwillbeskipped.Thesesettingsareindicatedbelowwithcomments.Moredetailoneachsettingfollowsthistable.
Installer Guide 10
1. PressandholddowntheRETURNand buttonsfor3seconds.2. Releasebothbuttonsandthefirstinstaller settingwillbedisplayed.3. Changesettingsasrequiredusingthe orportionoftheSpeedBar®.4. PressNEXT (HOLD)orBACK (PROG)to movetothenextorprevioussetting, pressRETURNtoexit.
No. Installer Setting Factory Setting Comments (Notes follow this table) Default Options (More information follows this table)
1 Residentialor RES RES SelectforResidentialprofile orCommercialProfile COMM SelectforCommercialprofile
2 ProgrammingMode 7PROG 7PROG Selectfor7dayprogrammingmode [note 1] 52PROG Selectfor5-2dayprogrammingmode NOPROG Selectfornon-programmablemode
3 ClockFormat 12HR 12HR Selectfor12hourclock 24HR Selectfor24hourclock
4 TemperatureScale FDEG FDEG SelectforFahrenheitdisplay CDEG SelectforCelsiusdisplay
5 AutoChangeover oFAUTO oFAUTO DisablesAutoChangeovermode ONAUTO EnablesAutoChangeovermode 11CONV Selectfor1H/1CConventionalsystem 22CONV Selectfor2H/2CConventionalsystem
6 SystemType 11CONV 11HP Selectfor1H/1CHeatPumpsystem 22HP Selectfor2H/2CHeatPumpsystem 32HP Selectfor3H/2CHeatPumpsystem 1HD SelectforHeatOnlyHydronicsystem 11HD SelectforHydronicHeat/1Csystem
7 1stStageDifferential 0.5DIF1 0.5,1.0or Selecta1ststagetemperaturedifferentialof.5°, 2.0DIF1 1°or2°F(.25°,.5°or2°C)
8 2ndStageDifferential 2.0DIF2 1.0,2.0,3.0, Selecta2ndstagetemperaturedifferentialof1°, [note 2] 4.0,5.0or 2°,3°,4°,5°or6°F(.5°,1°,1.5°,2°,2.5°or3°C) 6.0DIF29 3rdStageDifferential 2.0DIF3 1.0,2.0,3.0, Selecta3rdstagetemperaturedifferentialof1°,2°, [note 2] 4.0,5.0or 3°,4°,5°or6°F(.5°,1°,1.5°,2°,2.5°or3°C) 6.0DIF3
4 Installer Settings
NOTE: Shaded areas below do not apply to the 5020.
INSTRUCTIONS
DAY/TIME
BACK NEXT
11 Installer Guide
No. Installer Setting Factory Setting Comments (Notes follow this table) Default Options (More information follows this table)
10 1stStageFanControl HGFAN1 HGFAN1 Selectfor1ststageGasheating [note 3] HEFAN1 Selectfor1ststageElectricheating
11 EmergencyHeat] HEEMER HEEMER SelectforElectricEmergencyHeat FanControl[note 4] HGEMER SelectforGasEmergencyHeat
12 ReversingValve REVO REVO SelectforcoolactiveReversingValve(Oterminal) (O/BTerminal)[note 5] REVB SelectforheatactiveReversingValve(Bterminal)
13 FossilFuel AEAUX AEAUX SelectforElectricAuxiliaryheat(withcompressor) BackupHeat[note 4] AGAUX SelectforGasAuxiliaryheat(withoutcompressor)
14 CompressorPowerOutage oFCPOP oFCPOP DisablesPowerOutageLockoutDelay Protection [notes 4, 6] onCPOP EnablesPowerOutageLockoutDelay
15 ACPowerInterrupt ACoFMONR ACoFMONR DisablesACPowerInterruptWarning Warning[note 6] AConMONR EnablesACPowerInterruptWarning
16 CompressorShort 5CSCP 5,4,3,2or Selectacompressorshortcycleprotectiondelayof5, CycleProtection[note 7] 0CSCP 4,3,2or0minutes
17 ResidualCooling 60FAN 90,60,30 SelectaResidualCoolingFanDelayof90,60, FanDelay[note 7] or0FAN 30or0seconds.
18 AdaptiveRecovery oFREC oFREC DisablesAdaptive(early)Recoverymode Mode(ARM™) [note 8] onREC EnablesAdaptive(early)Recoverymode
19 IndoorRemoteSensor ISENS ISENS Temperatureissensedfromthermostatonly. Control*[note 9] ESENS Temperatureissensedfromremotesensoronly. ASENS Temperatureiscombinedwiththethermostatand theremotesensor.
20 LockoutSecurityLevel 2LOCK 2LOCK Iflocked–Completelockoutisenabled 1LOCK Iflocked–Partiallockoutisenabled(SpeedBar®is stillfunctional)
21 AutoChangeover 3BAND 2,3,4or5 SelectaDeadBandof2°,3°,4°or5˚F DeadBand[note 10] BAND (1°,2°or3°C)forAutoChangeovermode.
22 CompressorBalance NOBALC NOBALC DisablesBalancePoints Point[notes 4, 11] 15-50BALC SelectaCompressorBalancePointof15°-50°F (-9°-10°C)
23 AuxiliaryHeatBalance NOBALA NOBALA DisablesBalancePoints Point[notes 4, 11] 70-40BALA SelectaAuxiliaryHeatBalancePointof70°-40°F (21°-4°C)
24 HeatSetPointUpperLimit 90LIM 90-60LIM SelectaHeatSetPointUpperLimitof90°-60°F(32°-10°C)
25 CoolSetPointLowerLimit 45LIM 45-80LIM SelectaCoolSetPointLowerLimitof45°-80°F(7°-27°C) [note 7]
*WhenaBraeburn®outdoorsensorisconnected,thethermostatautomaticallyrecognizesit.PressPROGandHOLDatthesametimetodisplayoutdoortemperature.
NOTE: Additional options such as Service Monitors, setting the lock code, etc. are located in the User Settings – See User manual for information on setting these options.
Installer Guide 12
NOTES - Installer Settings
1 OnlyavailableifResidentialprofilewasselectedinoption1.2 Onlyavailableifa2or3stagesystemtypewasselectedinoption6.3 OnlyavailableifaConventionalsystemwasselectedinoption6.4 Onlyavailableifa2or3stageHeatPumpsystemwasselectedinoption6.5 OnlyavailableifaHeatPumpsystemwasselectedinoption6.6 Onlyavailableifthe24VoltACcommonwireisconnectedtotheCterminal.7 Notavailableifaheatonlyhydronicsystemisselectedinoption6.8 Onlyavailableifaprogrammableprofilewasselectedinoption2.9 OnlyavailableifaBraeburn®indoorremotesensorwasconnected.10 Onlyavailableifautochangeoverwasenabledinoption5.11 OnlyavailableifaBraeburnoutdoorsensorwasconnected.
Detailed Explanation of Installer Settings (also see NOTES above):
1 Profile–Selectsaresidential(RES)orcommercial(COMM)profile.Ifresidentialisselected,4programming eventsperdayareavailable.Ifcommercialisselected,2event,7dayprogrammingisavailable.
2 Programming Mode [note 1]–Selectstheprogrammingmode,eitherfull7dayor5-2day(weekday/ weekend)programmingornon-programmable.
3 Clock Type–Selectseithera12houror24hourclock.
4 Temperature Scale–Selectsatemperaturescaleofeither°For°C.
5 Auto Changeover–Selectsautochangeoveronoroff.Whenautochangeovermodeisenabledand selected,thesystemautomaticallyswitchesbetweenheatingandcoolingmodes.Thereisa5minutedelay whenswitchingfromheatingtocoolingorcoolingtoheatinginautochangeovermode. NOTE: Also see “Auto Changeover Dead Band” in option 21.
6 System Type–Selectsthesystemtypeforyourinstallation.NOTE: Changes made to this option will reset options 7 through 15 back to their default values dependant on the system type.
7 1st Stage Differential–Selectsa1ststagetemperaturedifferential.
8 2nd Stage Differential [note 2]–Selectsa2ndstagetemperaturedifferential.
9 3rd Stage Differential [note 2]–Selectsa3rdstagetemperaturedifferential.
10 1st Stage Fan Control [note 3]–Selectsa1ststagefancontrolofeithergasorelectricheat.
11 Emergency Heat Fan Control [note 4]–Selectsemergencyheatfancontrolofeithergasorelectricheat.
12 Reversing Valve [note 5]–SelectstheoutputstateoftheO/Bterminal.SelectOforthisterminaltobe activeinthecoolmodeorselectBforthisterminaltobeactiveintheheatmode.
13 Auxiliary Fossil Fuel Heat Pump Control [note 4]–Whensettoelectric(AEAUX),boththecompressor (1ststage)andauxiliarystage(s)willrunwhenacallforauxiliaryheatismade.Whensettogas(AGAUX), thecompressorstage(s)willbelockedoutoneminuteafteracallforauxiliaryheat.NOTE: This option can be overridden if setting an auxiliary heat balance point in Option 23.
14 Compressor Power Outage Protection [notes 4, 6]–Selectspoweroutageprotectiononoroff.When enabled,thisthermostatwillprovidecoldweathercompressorprotectionbylockingoutthecompressor stage(s)ofheatingforaperiodoftimeafterapoweroutagegreaterthan60minutes.
13 Installer Guide
15 AC Power Interrupt Warning [note 6]–Whenenabled,thethermostatwilldisplayanoutagewarning whenACpowertothethermostatislost.
16 Short Cycle Protection [note 7]–Selectsthenumberofminutesthecoolingcompressorwillbelocked outafterturningoff.Thisshortcycleprotectionisalsoactiveintheheatmodeifaheatpumpsystemwas selectedinOption6.
17 Residual Cooling Fan Delay [note 7]–Selectsadelayforthesystemfanafterthecoolingcompressor hasturnedoff.Thisdelaywillhelpremovetheremainingcoolairoutoftheductworkprovidingadditional efficiency.
18 Adaptive Recovery Mode (early recovery) [note 8]–EnablesordisablestheARMTM(adaptiverecovery mode)feature.DuringARM,roomtemperatureisrecoveredbyturningontheheatingorcoolingbeforethe endofthesetbackperiod.Thesetpointtemperatureischangedtothatoftheupcomingprogramtemperature.
19 Indoor Remote Sensor Control [note 9]–IfaBraeburn®indoorremotesensorisconnectedduring installation,thethermostatwillautomaticallydetectthesensor.Whenanindoorsensorisdetected,youmay selectbetweenthermostatonly(ISENS),remotesensoronly(ESENS)orcombiningthethermostatandthe remotesensor(ASENS).NOTE: This option does not apply to a Braeburn outdoor sensor. When an outdoor sensor is connected the thermostat automatically recognizes it and no further configuration is necessary.
20 Lockout Security Level–Selectsthelevelofkeypadlockoutwhenthethermostatislocked.Level2locks theentirethermostat(includingthefrontresetbutton).Level1lockseverythingexcepttheSpeedBar® allowingforupanddowntemperatureadjustment.NOTE: The lock code is set in the User Settings mode (see User Manual).
21 Auto Changeover Dead Band [note 10]–Whenautochangeovermodeisenabledinoption5and selected,thesystemautomaticallyswitchesbetweenheatingandcoolingwhentheroomtemperature meetsthenormalcriteriaforeitheraheatingorcoolingcall.Thereisaforcedseparation(deadband) betweentheheatingandcoolingsetpointssothatthesystemsdonotworkagainsteachother.This optionselectstheamountofthisdeadbandindegreeswiththedefaultbeing3°F.
22 Compressor Balance Point [notes 4, 11]–Locksouttheuseofthecompressorheatstagewhenthe outsideairtemperatureislessthantheselectedsettingof15°Fto50°F(-9°Cto10°C)
23 Auxiliary Heat Balance Point [notes 4, 11]–Locksouttheuseoftheauxiliaryheatstagewhenthe outsideairtemperatureexceedstheselectedsettingof70°Fto40°F(21°Cto4°C).NOTE: This balance point overrides the fossil fuel compressor lockout in option 13. If this option is set to gas and the outdoor temperature is over the auxiliary balance point, the compressor will remain on during a call for auxiliary heat.
24 Heat Set Point Upper Limit–Selectstheheatingsetpointupperadjustmentlimit.
25 Cool Set Point Lower Limit [note 7]–Selectsthecoolingsetpointloweradjustmentlimit.
Installer Guide 14
Warning Read Before Testing
• Donotshort(orjumper)acrossterminalsonthegasvalveorattheheatingorcoolingsystemcontrolboard totestthethermostatinstallation.Thiscoulddamagethethermostatandvoidthewarranty.
• DonotselecttheCOOLmodeofoperationiftheoutsidetemperatureisbelow50ºF(10ºC).Thiscould possiblydamagethecontrolledcoolingsystemandmaycausepersonalinjury.
• Thisthermostatincludesanautomaticcompressorprotectionfeaturetoavoidpotentialdamagetothe compressorfromshortcycling.Whentestingthesystem,makesuretotakethisdelayintoaccount.
NOTE: The compressor delay can be bypassed by pressing the reset button on the front of the thermostat. All user settings will be returned to factory default, however all Installer settings will remain as originally programmed in section 4. 1 PresstheSYSTEMbuttonuntilthethermostatisinHEATmode.2 UsingtheSpeedBar®raisethesettemperatureaminimumof3degreesabovethecurrentroom temperature.Thesystemshouldstartwithinafewseconds.Withagasheatingsystem,thefanmay notstartrightaway.3 PressSYSTEMuntilthethermostatisintheOFFmode.Allowtheheatingsystemtofullyshutdown.4 PressSYSTEMuntilthethermostatisintheCOOLmode.5 UsingtheSpeedBarlowerthesettemperatureaminimumof3degreesbelowthecurrentroom temperature.Thesystemshouldstartwithinafewseconds(unlesscompressorshortcycleprotection isactive–Seenoteabove).6 PressSYSTEMuntilthethermostatisintheOFFmode.Allowthecoolingsystemtofullyshutdown.7 PressFANuntilthethermostatisinFANONmode.Thesystemfanshouldstartwithinafewseconds.8 PressFANuntilthethermostatisinFANAUTOmode.Allowthesystemfantoturnoff.
5 System Testing
®
Store this manual for future reference.
Limited WarrantyWheninstalledbyaprofessionalcontractor,thisproductisbackedbya5yearlimitedwarranty.Limitationsapply.Forlimitations,termsandconditions,youmayobtainafullcopyofthiswarranty:
·Visitusonline:www.braeburnonline.com/warranty
·Phoneus:866.268.5599
·Writeus:BraeburnSystemsLLC2215CornellAvenueMontgomery,IL60538
5 YEAR WARRANT YLIMITED
BraeburnSystemsLLC2215CornellAvenue•Montgomery,IL60538TechnicalAssistance:www.braeburnonline.comCallustoll-free:866-268-5599(U.S.)630-844-1968(OutsidetheU.S.)
©2016BraeburnSystemsLLC•AllRightsReserved•MadeinChina.
®
5020W-100-04