Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
BELT DRIVEProduct Specifications
HorizontalChilled Water / Hot Water / DX
500 THROUGH 10,000 CFM
Double Wall ConstructionChilled Water • Hot Water • DX
Table of Contents
Features 2Engineering Guide Specifications 3-5Nomenclature 6Physical Data 7Filters 8-9Mixing Box 10Hydronic Manifold 11-12DX Manifold 13-148-12 Cooling Performance 1516-20 Cooling Performance 1630-40 Cooling Performance 1760-80 Cooling Performance 18
8-20 DX 4 Row (R22) Cooling 1930-40 DX 4 Row (R22) Cooling 208-20 DX 6 Row (R22) Cooling 2130-80 DX 6 Row (R22) Cooling 228-20 DX 4 Row (R410A) Cooling 2330-40 DX 4 Row (R410A) Cooling 24Heating Perormance 25-26Hand Connections 27Blower Curves 28-35Water Pressure Drop 36-43Shipping Weights 44
8-40AWH
60-80AWH
®
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
FEATURESProduct SpecificationsHorizontal
Chilled Water / Hot Water / DX
GENERAL: Unit is a completely factory assembled, single-piece air handler. Unit includes a fan and coil section with factory installed chilled water or direct expansion coil, preheat or reheat hot water coil position, and a 2” filter section. Field mounted com-ponents include a mixing box, 2” or 4” flat filter section and a 2” or 4” (4” only available for unit sized 16-80) angled filter section.
-2-
STANDARD FEATURES Unit Cabinet, 1” double wall construction fabricated from a mini-mum of 18 gauge LFQ (lock forming quality) galvanized steel outer panels and a minimum 24 gauge inner liner fabricated from galva-nized steel. Post and panel construction allows for large access panels to permit full access to internal components. The structural integrity of the cabinets remain unaffected by the removal of any or all access panels.
Unit panels shall consist of 1” thick 1.5lb fiberglass insulation sandwiched between galvanized steel exterior and interior panels. Panels are fastened with captured thumb-screws that hold panels in place with a closed cell neoprene gasket in between the panel and the post to prevent thermal bridging from the interior to the exterior of the unit.
Coils are 1/2 inch staggered tube type construction with seamless copper tubes and headers, and deep corrugated aluminum fins with straight edges. Fins are manufactured with full depth collars, drawn in the fin stock to provide accurate control of fin spacing and completely cover the copper tubes to lengthen coil life. The tubes are mechanically expanded into the fins for a permanent primary to secondary surface bond, assuring maximum heat transfer ef-ficiency. The coils are to be tested at 350 pounds air pressure for operation at 300 PSI gauge working pressure.
Drain pans are made from an UL94-5V rated, rigid PVC material with a three-way slope for positive drainage.
Fan Wheels are double width, double inlet (DWDI), forward curved, centrifugal type. They are statically and dynamically balanced for smooth, quiet operation. The Class I housing is con-structed of heavy gauge steel with die-formed inlet cones.
Motors and Drives: Belt drive motors are standard duty, 1725 RPM, open, drip-proof construction. Single phase and most three phase motors are resilient mount with automatic reset thermal protection. Motor sheaves are variable pitch, cast iron with a split-tapered hub.
Blower and Motor mounting platform is constructed from 12 gauge LFQ (lock forming quality) galvanized steel. Platform is mounted to cabinet support rails with rubber in compression isola-tors for quiet vibration free operation. Blower exits cabinet through rubber-isolated frame.
Filter Section includes 2” pleated Merv 7 disposable type fiber-glass filters. The 2” filter section is an integral part of the cabinet with easy tool free access.
OPTIONS
Coils are available with 2 circuit options for high or low flow applications. Coil rows options include 1, 2, 4, or 6 rows with a maximum total of 10 rows.
Drain pan options include stainless steel with an insulating coat-ing.
Electric Heat: Discharge mounted electric heat available in a wide range of KW’s and voltages. Available voltages are 120/1/60, 208/230/1/60, 277/1/60, 208/230/460/3/60, 575/3/60, 110/220/1/50, and 220/380/440-3-50.
Spring Isolators: Kits are available by unit size and coil rows with and without mixing boxes.
Motor options include 2-speed, TEFC, or (HE) High Efficient. Voltage options include 120/1/60, 208/1/60, 240/1/60, 277/1/60, 208/3/60, 240/3/60, 480/3/60, 575/3/60. Contact Factory for avail-ability of 50HZ motors.
Motor Control Box: For use with standard motors with internal overload protection. The 986FF control box is factory installed and wired. Features include a Disconnect switch, HOA switch, power fusing, motor contactor, 24V control transformer and low voltage terminal block.
Motor Control Starters: For use with non-standard motors without internal overload protection. The 986FR starter box is fac-tory installed and wired. Features include a non-fused disconnect switch with thru-the-door pad lockable handle, HOA switch, built-in overload and magnetic trip, 24V control transformer and low volt-age terminal block.
Filter Section options include Double Wall flat filter sections avail-able for filters up to 4”. Double Wall angled filter sections accept 2” and 4” (4” only available for unit sized 16-80) deep filters. Filters are arranged in a “V” formation. Double wall access doors are standard on flat and angled filter sections.
Mixing Boxes are double wall construction with parallel blade, interconnecting outside-air and return-air dampers. Damper blades include stiffing breaks and are attached with 1/2” diameter steel rods rotating in nylon bushings and mounted in rigid galvanized steel frames. Dampers are rated as low-leakage, having a leakage rate not to exceed 2% of airflow. Damper blades are gasketed and include edge seal strips.
®
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
GUIDESPECIFICATIONS
Product SpecificationsHorizontal
Chilled Water / Hot Water / DX
PART 1: GENERAL
1.01 Section Includes A. Air Handling Units
1.02 REFERENCESAFBMA 9 – Load Ratings and Fatigue Life for Ball Bearings
AMCA 99 – Standards Handbook
AMCA 210 -- Laboratory Methods for Testing Fans for Rating Purposes
AMCA 300 – Test Code for Sound Rating Air Moving Devices
AMCA 500 – Test Methods for Louver, Dampers, and Shutters
AG.ARI 430 – Central-Station Air-Handling Units
ARI 435 – Application of Central-Station Air-Handling Units
NEMA MGI – Motors and Generators
NFPA 70 – National Electric Code
SMACNA – HVAC Duct Construction Standards – Metal and Flexible
UL 900 – Test Performance of Air Filter Units
UL 1995 – Standard for Heating and Cooling Equip-ment
1.03 SUBMITTALSA. Shop drawings: Indicate assembly, unit dimen-sions, weight loading, required clearances, construc-tion details, field connection details, and electrical characteristics and connection requirements. Com-puter generated fan curves for each air handling unit shall be submitted with specific design operating point noted. A computer generated psychometric chart shall be submitted for each cooling coil with design points and final operating point clearly noted.
B. Product Data: 1. Provide literature that indicates dimensions, weights, capacities, ratings, fan performance, fin ishes of materials, and electrical characteristics and connection requirements.
2. Provide data of filter media, filter performance data, filter assembly, and filter frames. 3. Manufacturer’s Installation Instructions.
1.04 OPERATION AND MAINTENANCE DATAA. Maintenance Data: Include instructions for lubrica-tion, filter replacement and motor and drive replace-ment.
1.05 QUALIFICATIONSA. Manufacturer: Company specializing in manu-facturing the Products Specified in this section with a minimum 10 years documented experience, which issues complete catalog data on total product.
1.06 DELIVERY, STORAGE, AND HANDLINGA. Deliver, store, and handle product to siteB. Accept products on site on factory-installed ship-ping skids. Inspect for damage.C. Store in clean dry place and protect from weather and construction traffic. Handle carefully to avoid damage to components, enclosures, and finish.
1.07 ENVIRONMENTAL REQUIREMENTS
A. Do not operate units for any purpose, temporary or permanent, until ductwork is clean, filters are in place, bearings lubricated, and fan has been test run under observation.
-3-
®
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
PART 2: PRODUCTS
2.01 MANUFACTURERSA. The following manufacturers are approved for use. No substitutions will be permitted. 1. Applied Environmental Air (AE-Air)2.02 CASINGA. Unit panels shall consist of 1” thick 1.5lb fiberglass insulation sandwiched between galva- nized steel exterior and interior panels. Panels are fastened to post with captured thumb-screws that hold panels in place with a closed cell neoprene gasket in between the panel and the post to pre- vent thermal bridging from the interior to the exte- rior of the unit.B. Removable panels on both sides of unit shall pro- vide full access to unit components. Blower and filter access panels shall have tool free fasteners.C. Drain pans shall be an UL94-5 rated, rigid PVC material with a three way slope for positive drain- age of condensate. Optional drain pan shall be heavy gauge stainless steel with an insulating coating. Secondary drain connections shall extend to cabinet exterior to comply with International Building Code and International Mechanical Code. Drain pans shall be removable for cleaning or replacement without removing coils or disturbing coil connections. Coil vents and drains shall be ac- cessible from separate access panel.
2.03 SUPPLY FANA. Provide DWDI forward-curved supply fans. Fan as semblies shall be statically and dynamically bal- anced by manufacturer. The housings are con- structed from heavy gauge galvanized steel with die-formed inlet cones.B. Bearings shall be self-aligning , ball or roller bear- ings.C. Fan and motor mounting platform shall be a mini- mum of 12 gauge LFQ galvanized steel.
2.04 DRIVESA. Shafts shall be solid, hot rolled steel, ground and polished, keyed to shaft, and protectively coated with lubricating oil. Hollow shafts are not accept- able.B. V-belt drives shall be cast iron or steel sheaves, dy- namically balanced, bored to fit shafts and keyed. Variable and adjustable pitch sheaves selected so required RPM is obtained with sheaves set at mid- position and rated based on motor horsepower.
2.05 ELECTRICALA. Motors: provide (ODP) (TEFC) type with (EPACT) (premium) efficiency. Electrical characteristics shall be as shown in schedule.
2.07 COOLING AND HEATING COIL SECTIONSA. Provide access to coils from connection side of unit for service and cleaning. Enclose coil headers and return bends fully within unit cabinet. Drain and vent connections shall be accessible by sepa- rate access panel. Coil connections must exit manifold panel through grommets on the exterior of unit casing to minimize air leakage and condensa- tion nside panel assembly.B. Water Coils: fins shall have full drawn collars to provide a continuous surface cover over the entire tube for maximum heat transfer. Tubes shall be mechanically expanded into the fins to provide a continuous primary-to-secondary compression bond over the entire finned length for maximum heat transfer rates. Bare copper tube shall not be visible between fins. Coil tubes shall be seamless copper, expanded into fins, brazed at joints. Coil connections shall be copper with connection size to be determined by manufacturer based upon the most efficient coil circuiting. Vent connections shall be provided at the highest point of the header to assure proper venting. Coils shall be tested with 350 pounds air pressure and suitable for 300 psig working pressure. Coil casings shall be a formed channel frame of galvanized steel.
GUIDESPECIFICATIONS
Product SpecificationsHorizontal
Chilled Water / Hot Water / DX
-4-
®
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
C. Refrigerant Coils: Coils designed for use with Refrigerant (R-22) (R-410a). Fins shall be of alu- minum with full drawn collars to provide a continu- ous surface cover over the entire tube for maximum heat transfer. Tubes shall be mechanically expanded into the fins to provide a continuous primary-to-sec- ondary compression bond over the entire finned length for maximum heat transfer rates. Bare copper tube shall not be visible between fins. Coils to be manufactured from rifled enhanced copper tubing. 2.08 FILTERSA. Filter sections shall be Double wall construction.B. (Angled) (Flat) arrangement with (2”) (4”) deep pleated panel filters (4” only available for unit sized 16-80)C. Filter shall be MERV 7 (or MERV 8)D. Filter media shall be UL 900listed, Class I or Class II.
2.09 MIXING BOXESA. Optional mixing box consist of the same construction as described in “2.02 Casings.” Section shall include factory mounted outside and return air dampers. Boxes shall be double wall construction with parallel blade, interconnecting outside-air and return-air dampers. Damper blades shall include stiffing breaks and attached with 1/2” diameter steel rods rotating in nylon bushings and mounted in rigid galvanized steel frames. Dampers shall be rated as low-leak age, having a leakage rate not to exceed 2% of airflow. Damper blades shall be gasketed and in clude edge seal strips.
PART 3: EXECUTION3.01 INSTALLATIONA. Install in accordance with manufacturer’s instructions
GUIDESPECIFICATIONS
Product SpecificationsHorizontal
Chilled Water / Hot Water / DX
-5-
®
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
NOMENCLATURESELECTION PROCEDURE
Product SpecificationsHorizontal
Chilled Water / Hot Water / DX
-6-
12 A W H D * * - 4Q - 2H - * - R - 0.75 - 231
Nominal CFM 08 - 800 12 - 1200 16 - 1600 20 - 2000 30 - 3000 40 - 4000 60 - 6000 80 - 8000
OEM ID A - AE - Air
Unit Type W - Water X - DX
Configuration H - Horizontal
Construction Type D - Double Wall
Open
Model Revision
2nd Coil Position
3rd Coil Position
1st Coil Position 1Q 1 row - quarter circuit 2F 2 row - full circuit 2H 2 row - half circuit
4H 4 row - half circuit 4Q 4 row - quarter circuit
6H 6 row - half circuit 6Q 6 row - quarter circuit
4A 4 row - STD DX coil-R22 4B 4 row - STD DX coil-R410A
Coil Connection
R Right HandL Left Hand
Horsepower 0.25 0.33 0.50 0.75 1.0 1.5 2.0 3.0 5.0 7.5 10.0
Voltage151 115V-1Ph-60Hz201 208V-1Ph-60Hz231 230V-1Ph-60Hz271 277V-1Ph-60Hz
111 110V-1Ph-50Hz221 220V-1Ph-50Hz
203 208V-3Ph-60Hz233 230V-3Ph-60Hz463 460V-3Ph-60Hz573 575V-3Ph-60Hz
223 220V-3Ph-50Hz383 380V-3Ph-50Hz443 440V-3Ph-50Hz
Required Order Information
1. Model number with rows and circuit 2. CFM and external static pressure 3. Motor HP 4. Actual voltage motor is to be wired to. 5. Hot water coil installed in preheat or reheat position 6. Hand connections with air hitting you in back of head
®
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
PHYSICAL DATAProduct SpecificationsHorizontal
Chilled Water / Hot Water / DX
�
�
Rear View(Return)
Side View(Left Hand Connection)
-7-
UNIT CABINET DIMENSIONS
UNITMODEL
A B C D E F G H JFILTERS(MERV7)
8AWH 32-1/4 10-7/8 7-1/2 24 16 1-3/4 2 19 53-1/4 (2) 16X25X2
12AWH 36-1/4 10-7/8 8-7/8 24 16 1-3/4 2 19 53-1/4 (2) 16X25X2
16AWH 40-1/4 12 10-1/4 32 18-1/2 2-1/4 2 21-1/2 53-1/4 (2) 18X20X2
20AWH 46-1/4 14-1/8 12-7/8 38 18-1/2 2-1/4 2 21-1/2 53-1/4(1) 18X20X2(1) 18X24X2
30AWH 46-1/4 16-1/2 15-1/4 36 31 8 2 34 66-1/8 (4) 16X20X2
40AWH 57-1/4 16-1/2 19-1/4 47 31 7-7/8 2 34 66-1/8 (4) 16X25X2
UNIT CABINET DIMENSIONS
UNITMODEL
A B C D E F G HFILTERS(MERV7)
60AWH 66-1/4 19-1/2 22-1/2 56 41 10-3/4 4 44 (9) 15x20x2
80AWH 66-1/4 19-1/2 22-1/2 56 53-1/2 23-1/4 4 58-1/2 (9) 18x20x2
Plan View
����� ������
����� ������
�
Std. 2”Filter Access
D
E
1.00
G Return End
A
Top View
A
H F
C
15 3/8
B
Supply End
Std. 2”Filter Access
75 1/41
4 3 1/2
14 3/4
1 5/8
1
Right SideStd. 2”Filter Access
Front View(Supply)
®
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
FILTERSProduct Specifications
HorizontalChilled Water / Hot Water / DX
OPTIONAL FLAT FILTER SECTION
Top View
End View
SUSPENSION POINT
NOTE: Unit comes standard with 2” filter mounted in cabinet
-8-
ANGLED FILTER BOX
UNIT SIZE
PART NUMBER
FILTERSIZE
A B C D E F G HFILTER
SIZE(Qty)
89BDAF12A29BDAF12A4
2”4”
26.78 18.32 20.88 24.57 16.21 1 1 1 (2) 25 X16
129BDAF12A29BDAF12A4
2”4”
26.78 18.32 20.88 24.57 16.21 1 1 1 (2) 25 X 16
169BDAF16A29BDAF16A4
2”4”
37.28 21.57 28.68 35.07 19.71 1 1 1 (2) 18 X 24
209BDAF20A29BDAF20A4
2”4”
41.28 21.57 28.68 39.07 19.71 1 1 1 (2) 20 X 24
OPTIONAL ANGLED FILTER SECTION
End View
Top ViewSUSPENSION POINT
FLAT FILTER BOX
UNITSIZE
PARTNUMBER
FILTERSIZE
A B C D E F G HFILTER
SIZE(Qty)
89BDAF12F29BDAF12F4
2”4”
26-13/16 18-3/8 9-7/16 24-1/2 16-1/4 1 1 1 (1) 25 X 16
129BDAF12F29BDAF12F4
2”4”
26-13/16 18-3/8 9-7/16 24-1/2 16-1/4 1 1 1 (1) 25 X 16
169BDAF16F29BDAF16F4
2”4”
37-1/4 21-1/2 9-7/16 35 19-3/4 1 1 1(1) 16 X 20(1) 20 X 20
209BDAF20F29BDAF20F4
2”4”
41-1/4 21-1/2 9-7/16 39 19-3/4 1 1 1 (2) 20 X 20
309BDAF30F29BDAF30F4
2”4”
41-13/16 34 9-3/8 39-5/8 32 1 1 1 (4) 16 X 20
409BDAF40F29BDAF40F4
2”4”
51 34 9-3/8 48-7/8 32 1 1 1 (4) 16 X 25
609BDAF60F29BDAF60F4
2”4”
61 44 9-3/8 58-7/8 42 1 1 1 (6) 20 X 20
809BDAF80F29BDAF80F4
2”4”
61 56-1/2 9-3/8 58-7/8 54-1/4 1 1 1 (9) 20 X 18
®
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
FILTERSProduct Specifications
HorizontalChilled Water / Hot Water / DX
OPTIONAL ANGLED FILTER SECTION
“A”
“C”
“D” “G”
“1.25
“2.50
“B” “E”
“F”
“H”
NOTE: Unit comes standard with 2” filter mounted in cabinet
NOTE: Unit comes standard with 2” filter mounted in cabinet
“E”
“A”
“D”
“1.25
“2.5
“2.5
“1.5
“B”
“F” “C”
“G”
“3.62
“2.75
-9-
ANGLED FILTER BOX
UNIT SIZE
PART NUMBER
FILTER SIZE
A B C D E F G HFILTER
SIZE(Qty)
309BDAF30A29BDAF30A4
2”4”
41-13/16 34 28 39-5/8 32 1 1 1 (4) 20 X 25
409BDAF40A29BDAF40A4
2”4”
51 34 27 48-7/8 32 1 1 1(4) 16 X 24(2) 18 x 24
ANGLED FILTER BOX
UNIT SIZE
PART NUMBER
FILTER SIZE
A B C D E F G HFILTER
SIZE(Qty)
609BDAF60A29BDAF60A4
2”4”
61 44 21-3/8 58-7/8 42 1 1 1 (9) 16 X 20
809BDAF80A29BDAF80A4
2”4”
61 56-1/2 28-1/2 58-7/8 54-1/4 1 1 1(3) 20 X 18(6) 20 x 25
®
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
Product SpecificationsHorizontal
Chilled Water / Hot Water / DXMIXING BOX
-10-
8-20 MIXING BOX DIMENSIONS
UNITMODEL
A B C D E F G H I J K
9BDAM08 26.78 18.31 16.91 21.00 8.00 5.00 1.00 6.81 3.35 7.48 5.44
9BDAM12 26.78 18.31 16.91 21.00 8.00 5.00 1.00 6.81 3.35 7.48 5.44
9BDAM16 37.28 21.57 16.91 32.00 10.00 4.00 1.00 8.05 3.35 9.71 5.44
9BDAM20 41.28 21.57 16.91 36.00 10.00 4.00 1.00 8.05 3.35 9.71 5.44
30-40 MIXING BOX DIMENSIONS
UNITMODEL
A B C D E F G H I J K
9BDAM30 37-13/16 34 16-15/16 36 12 3 1 11 3-3/8 16-3/8 5-3/8
9BDAM40 52-13/16 34 17 46 12 3 1 11 3-3/8 16-3/8 5-3/8
60-80 MIXING BOX DIMENSIONS
UNITMODEL
A B C D E F G H I J K L M N
9BDAM60 61 43-5/16 22 56 14 4-9/16 1 14-11/16 8-1/2 11-1/4 4-7/8 5-7/8 7-1/2 15-3/16
9BDAM80 61 55-7/8 22 56 14 4-9/16 1 20-15/16 8-1/2 17-1/2 4-7/8 5-13/16 7-9/16 21-7/16
®
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
HYDRONIC MANIFOLD
Product SpecificationsHorizontal
Chilled Water / Hot Water / DX
-11-
COIL MANIFOLD CONNECTIONSPLASTIC CONDENSATE PAN
CONNECTIONSSS CONDENSATE PAN
CONNECTIONS
UNITMODEL
1 ROW 2 ROW 4 ROW 6 ROW PRIMARY SECONDARY PRIMARY SECONDARY
8AWH 7/8” O.D. 7/8” O.D. 7/8” O.D. 7/8” O.D. 3/4” PVC I.D. 1/2” PVC SLIP I.D. 3/4” MPT 3/4” MPT
12AWH 7/8” O.D. 7/8” O.D. 7/8” O.D. 7/8” O.D. 3/4” PVC I.D. 1/2” PVC SLIP I.D. 3/4” MPT 3/4” MPT
16AWH 7/8” O.D. 7/8” O.D. 1-1/8” O.D. 1-1/8” O.D. 3/4” PVC I.D. 1/2” PVC SLIP I.D. 3/4” MPT 3/4” MPT
20AWH 7/8” O.D. 7/8” O.D. 1-1/8” O.D. 1-1/8” O.D. 3/4” PVC I.D. 1/2” PVC SLIP I.D. 3/4” MPT 3/4” MPT
30AWH 1-3/8” O.D. 1-3/8” O.D. 1-3/8” O.D. 1-3/8” O.D. 3/4” PVC I.D. 1/2” PVC SLIP I.D. 3/4” MPT 3/4” MPT
40AWH 1-3/8” O.D. 1-3/8” O.D. 1-3/8” O.D. 1-3/8” O.D. 3/4” PVC I.D. 1/2” PVC SLIP I.D. 3/4” MPT 3/4” MPT
COIL CONNECTIONS ARE COPPER SWEAT FITTINGS PVC CONNECTIONS MPT CONNECTIONS
®
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
HYDRONIC MANIFOLD
Product SpecificationsHorizontal
Chilled Water / Hot Water / DX
COIL MANIFOLD CONNECTIONSPLASTIC CONDENSATE PAN
CONNECTIONSSS CONDENSATE PAN
CONNECTIONS
UNITMODEL
1 ROW 2 ROW 4 ROW 6 ROW PRIMARY SECONDARY PRIMARY SECONDARY
60AWH 1-3/8” O.D. 1-3/8” O.D. 1-3/8” O.D. 1-3/8” O.D. 3/4” PVC I.D. 1/2” PVC SLIP I.D. 3/4” MPT 3/4” MPT
80AWH 1-3/8” O.D. 1-3/8” O.D. 1-3/8” O.D. 1-3/8” O.D. 3/4” PVC I.D. 1/2” PVC SLIP I.D. 3/4” MPT 3/4” MPT
COIL CONNECTIONS ARE COPPER SWEAT FITTINGS PVC CONNECTIONS MPT CONNECTIONS
60AWH80AWH
7-9/163-1/4 5-7/8
30-3/4
9-1/84-7/87-1/16
5-7/87-1/45-7/16
30-3/4
3-3/410-1/2
5-7/87-1/47-9/16
30-3/4
12-5/83-3/4
5-7/87-1/45-3/32
30-3/4
10-1/25-3/32
7-9/163-1/4 5-3/4
43-1/4
9-1/84-7/87-1/16
7-9/163-1/4 5-3/4
43-1/4
10-3/43-3/4
7-9/167-9/16 5-3/4
12-15/16 3-3/4
43-1/4
7-9/165-3/32 5-3/4
10-3/4 5-3/32
43-1/4
60AWH 80AWH
-12-
(4-2)(6-2)
(4-2)(6-2)
(4-2) (4-2)
(6-2) (6-2)
(4-4) (4-4)
®
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
Product SpecificationsHorizontal
Chilled Water / Hot Water / DX
8-12AXH 16-20AXH
DX MANIFOLD
-13-
4-1/87-1/4 6-7/8
12
10-1/28-3/8
8-5/
89-
1/8
11-7
/8
3-3/4
4
1-1/87-1/48-7/8
2-11/16
1/2
7-1/88-3/169-1/8
5-3/48-5/8
4-1/167-1/4
2-1/
22
11-1
/8
10-1/2
3-3/48-5/16 6-7/8
7-1/8
11-5
/8
8-7/81-1/8
7-1/42-3/4
45-3/4
1/2
9-1/
169-
5/8
11-5
/8
(4-2) (6-2)
(2-4) (2-6)
(4-2) (6-2)
(2-4) (2-6)
Single Circuit Coil Connections Drain Pan Connections
Unit ModelDX Connections
Hot Water Connections
Plastic Pan Connections (Standard)
SS Pan Connections (Optional)
Liguid Line
Suction Line
1-Row 2-Row Primary Secondary Primary Secondary
08AXH-4 Row 3/8” 3/4”7/8” O.D. 7/8” O.D. 3/4” PVC I.D.
1/2” PVC Slip I.D.
3/4” MPT 3/4” MPT08AXH-6 Row 3/8” 3/4”
12AXH-4 Row 3/8” 3/4”7/8” O.D. 7/8” O.D. 3/4” PVC I.D.
1/2” PVC Slip I.D.
3/4” MPT 3/4” MPT12AXH-6 Row 3/8” 3/4”
16AXH-4 Row 1/2” 7/8”7/8” O.D. 7/8” O.D. 3/4” PVC I.D.
1/2” PVC Slip I.D.
3/4” MPT 3/4” MPT16AXH-6 Row 1/2” 7/8”
20AXH-4 Row 1/2” 7/8”7/8” O.D. 7/8” O.D. 3/4” PVC I.D.
1/2” PVC Slip I.D.
3/4” MPT 3/4” MPT20AXH-6 Row 1/2” 7/8”
Coil Connections are Copper Sweat Fittings PVC Connections Male Pipe Thread Connections
All Direct Expansion (DX) Coils Include Factory Mounted R-410A Thermal Expansion Valve (TXV’s)
®
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
Product SpecificationsHorizontal
Chilled Water / Hot Water / DX
DX MANIFOLD
60-80AXH
30AXH
-14-
7-1/44-7/8 6-15/16
2-3/322-9/164-3/810-1/2
10-1/29-7/326-1/16 7-9/16
11-13/162-3/32
5-15/16
8-7/
1614
-7/8
14-9
/16
12-1
/16
2-3/
47/8
2-1/25-1/165-15/16
5-15/16
20-3
/420-7
/16
16-3
/16
8-9/
16
1-5/86-1/168-23/3210-7/16
7-5/82-3/8
6-3/165-1/8
3/16
11-1/2 17-1
/222
-1/211
1-1/2
7-3/84-7/89-5/32
2-5/164-13/16
7-9/16
6-7/84-3/8
11-1/4
1-1/2
1314
5/16
7-3/84-13/169-5/32
13/16 5-15/16
10-3/4
16-3
/418
-5/8
20-3
/4
11-7/16
3/8
1-15/16
7
6-1/1610-3/16
11-11/1614-11/16
7-9/165-1/8
3/4 12-1/4
10
16-1
/4
5-5/16
1-5/16
7-3/84-7/1611-5/8
(4-2) (6-2)
(2-4) (2-6)
(4-2) (6-2)
(2-4) (2-6)
(4-2) (6-2)
(2-4) (2-6)
Single Circuit Coil Connections Drain Pan Connections
Unit ModelDX Connections
Hot Water Connections
Plastic Pan Connections (Standard)
SS Pan Connections (Optional)
Liguid Line
Suction Line
1-Row 2-Row Primary Secondary Primary Secondary
30AXH-4 Row 5/8" 1-1/8"1-3/8" O.D. 1-3/8" O.D. 3/4" PVC I.D.
1/2" PVC Slip I.D.
3/4" MPT 3/4" MPT30AXH-6 Row 5/8" 1-1/8"
Dual Circuit DX Coil Connections (2 each)
Single Circuit (1 each) Drain Pan Connections
Unit ModelDX Connections
Hot Water Connections
Plastic Pan Connections (Standard)
SS Pan Connections (Optional)
Liguid Line
Suction Line
1-Row 2-Row Primary Secondary Primary Secondary
40AXH-4 Row 1/2" (2) 1-1/8" (2)1-3/8" O.D. 1-3/8" O.D. 3/4" PVC I.D.
1/2" PVC Slip I.D.
3/4" MPT 3/4" MPT40AXH-6 Row 1/2" (2) 1-1/8" (2)
60AXH-4 Row 5/8" (2) 1-1/8" (2)1-3/8" O.D. 1-3/8" O.D. 3/4" PVC I.D.
1/2" PVC Slip I.D.
3/4" MPT 3/4" MPT60AXH-6 Row 5/8" (2) 1-1/8" (2)
80AXH-4 Row 5/8" (2) 1-1/8" (2)1-3/8" O.D. 1-3/8" O.D. 3/4" PVC I.D.
1/2" PVC Slip I.D.
3/4" MPT 3/4" MPT80AXH-6 Row 5/8" (2) 1-1/8" (2)
Coil Connections are Copper Sweat Fittings PVC Connections Male Pipe Thread Connections
All Direct Expansion (DX) Coils Include ( 2 ) Factory Mounted R-410A Thermal Expansion Valves (TXV's)
®
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
8AWH - 12AWHCHILLED WATER
COOLING PERFORMANCE
Product SpecificationsHorizontal
Chilled Water / Hot Water / DX
8AWH (4 ROW - QUARTER CIRCUIT) (45o EWT)
CFM GPMP.D.FT.
75 F DB / 63 F WB 80 F DB / 67 F WB 85 F DB / 71 F WB
TOTALMBH
SENSIBLEMBH
TEMP.RISE
LADB LAWBTOTALMBH
SENSIBLEMBH
TEMP.RISE
LADB LAWBTOTALMBH
SENSIBLEMBH
TEMP.RISE
LADB LAWB
600800
10004.1 2.8
17.820.322.5
14.017.120.2
8.79.911.0
53.355.156.3
52.954.555.5
23.426.629.5
16.219.622.9
11.413.014.4
55.157.358.8
54.556.657.9
29.333.437.0
18.221.925.5
14.316.318.1
56.959.661.3
56.458.860.4
600800
10006.1 5.9
20.123.326.3
14.918.321.6
6.67.68.6
51.953.755.0
51.453.154.2
26.430.534.4
17.321.124.8
8.610.011.3
53.255.657.1
52.754.956.2
33.138.343.2
19.623.827.8
10.912.614.2
54.757.559.3
54.156.758.3
600800
10008.1 10.1
21.324.928.3
15.419.022.4
5.36.17.0
51.253.054.2
50.752.453.4
27.932.637.1
10.021.925.8
6.98.09.2
52.354.656.1
51.853.955.2
35.040.846.5
20.424.729.0
8.610.111.5
53.556.358.2
52.955.857.2
Contact factory for additional coil circuting options
-15-
8AWH (6 ROW - QUARTER CIRCUIT) (45o EWT)
CFM GPMP.D.FT.
75 F DB / 63 F WB 80 F DB / 67 F WB 85 F DB / 71 F WB
TOTALMBH
SENSIBLEMBH
TEMP.RISE
LADB LAWBTOTALMBH
SENSIBLEMBH
TEMP.RISE
LADB LAWBTOTALMBH
SENSIBLEMBH
TEMP.RISE
LADB LAWB
600800
10003.4 2.4
19.422.324.9
14.818.321.6
11.413.114.6
52.153.955.0
51.953.654.7
25.529.232.6
17.220.924.6
15.017.219.2
53.555.857.2
53.555.856.8
31.936.640.8
19.423.527.5
18.821.524.0
55.157.859.5
54.857.559.1
600800
10005.4 5.6
22.826.730.6
16.220.123.9
8.59.9
11.3
50.051.852.9
49.751.452.6
29.935.040.1
18.923.327.5
11.113.014.8
50.853.154.5
50.552.854.2
37.543.950.3
21.226.331.0
13.916.318.6
52.254.556.3
51.954.255.9
600800
10007.4 10.0
24.529.133.6
16.921.025.1
6.67.99.1
48.850.651.8
48.650.451.4
32.138.144.0
19.724.529.1
8.710.311.9
49.651.653.1
49.351.352.7
40.347.855.2
22.227.932.9
10.912.914.9
50.752.754.5
50.552.454.1
12AWH (4 ROW - QUARTER CIRCUIT) (45o EWT)
CFM GPMP.D.FT.
75 F DB / 63 F WB 80 F DB / 67 F WB 85 F DB / 71 F WB
TOTALMBH
SENSIBLEMBH
TEMP.RISE
LADB LAWBTOTALMBH
SENSIBLEMBH
TEMP.RISE
LADB LAWBTOTALMBH
SENSIBLEMBH
TEMP.RISE
LADB LAWB
100012001400
4.7 3.624.827.128.9
21.224.227.0
10.511.512.3
55.456.357.2
54.755.556.2
32.435.437.8
24.227.530.5
13.815.116.1
57.658.859.8
56.957.958.7
40.744.547.4
27.030.633.9
17.318.920.2
60.061.362.6
59.260.461.4
100012001400
6.7 6.728.131.133.5
22.525.728.7
8.49.3
10.0
54.255.156.0
53.554.355.0
36.840.743.9
25.829.532.8
11.012.213.1
56.157.358.3
55.356.357.2
46.251.155.1
29.033.036.6
13.815.216.4
58.159.560.8
57.358.559.6
100012001400
8.7 10.829.933.236.1
23.226.629.8
6.97.68.3
53.554.555.3
52.853.654.3
39.143.547.3
26.730.534.1
9.010.010.9
55.256.457.5
54.555.556.4
49.154.659.4
30.134.338.2
11.312.613.7
57.158.559.7
56.357.558.6
12AWH (6 ROW - QUARTER CIRCUIT) (45o EWT)
CFM GPMP.D.FT.
75 F DB / 63 F WB 80 F DB / 67 F WB 85 F DB / 71 F WB
TOTALMBH
SENSIBLEMBH
TEMP.RISE
LADB LAWBTOTALMBH
SENSIBLEMBH
TEMP.RISE
LADB LAWBTOTALMBH
SENSIBLEMBH
TEMP.RISE
LADB LAWB
100012001400
4.0 3.527.530.432.6
22.726.129.3
13.815.216.3
54.054.955.6
53.754.555.2
36.139.842.7
26.029.833.3
18.019.921.4
55.957.058.0
55.656.657.5
45.349.953.6
29.233.537.2
22.625.026.8
58.059.360.4
57.658.960.0
100012001400
6.0 7.532.536.439.7
24.728.532.1
10.812.113.2
52.153.053.8
51.852.753.4
42.647.651.9
28.632.836.8
14.215.917.3
53.654.755.7
53.254.355.2
53.459.865.2
32.337.041.4
17.819.921.7
55.156.457.6
54.756.057.2
100012001400
8.0 13.135.239.643.6
25.829.833.6
8.89.9
10.9
51.152.052.7
50.851.652.3
46.151.957.1
29.934.538.8
11.513.014.3
52.353.454.3
51.953.053.9
57.865.171.6
34.039.143.8
14.516.317.9
53.554.856.0
53.154.455.5
®
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
16AWH - 20AWHCHILLED WATER
COOLING PERFORMANCE
Product SpecificationsHorizontal
Chilled Water / Hot Water / DX
Contact factory for additional coil circuting options
-16-
16AWH (4 ROW - QUARTER CIRCUIT) (45o EWT)
CFM GPMP.D.FT.
75 F DB / 63 F WB 80 F DB / 67 F WB 85 F DB / 71 F WB
TOTALMBH
SENSIBLEMBH
TEMP.RISE
LADB LAWBTOTALMBH
SENSIBLEMBH
TEMP.RISE
LADB LAWBTOTALMBH
SENSIBLEMBH
TEMP.RISE
LADB LAWB
140016001800
5.5 4.232.433.935.7
28.731.434.2
11.812.313.0
56.056.857.4
55.356.056.5
42.544.446.7
32.735.638.6
15.416.217.0
58.459.460.1
57.658.559.1
53.355.758.6
36.439.642.9
19.420.321.3
60.962.162.9
60.161.161.8
140016001800
8.5 9.138.440.843.4
31.134.137.2
9.19.610.2
54.455.355.9
53.754.454.9
50.453.556.8
35.739.042.4
11.912.613.4
56.457.458.2
55.656.557.2
63.267.171.3
40.043.647.4
14.915.816.8
58.559.760.6
57.758.759.5
140016001800
11.5 15.541.444.347.4
32.335.538.7
7.27.78.3
53.754.555.1
52.953.654.1
54.358.062.1
37.240.744.4
9.410.110.8
55.456.457.2
54.655.556.1
68.172.877.9
41.945.849.8
11.812.713.6
57.358.559.4
56.557.558.3
16AWH (6 ROW - QUARTER CIRCUIT) (45o EWT)
CFM GPMP.D.FT.
75 F DB / 63 F WB 80 F DB / 67 F WB 85 F DB / 71 F WB
TOTALMBH
SENSIBLEMBH
TEMP.RISE
LADB LAWBTOTALMBH
SENSIBLEMBH
TEMP.RISE
LADB LAWBTOTALMBH
SENSIBLEMBH
TEMP.RISE
LADB LAWB
140016001800
4.0 3.332.834.236.1
29.532.435.5
16.417.118.0
55.556.356.8
55.255.956.4
43.044.747.2
33.536.740.0
21.522.423.6
57.858.859.4
57.558.459.0
53.956.259.3
37.440.844.4
27.028.129.7
60.361.462.2
56.961.061.7
140016001800
6.5 7.742.044.647.6
33.136.439.9
12.913.714.7
53.153.954.5
52.853.654.1
54.958.562.4
38.141.845.7
16.918.019.2
54.855.856.5
54.455.456.1
68.973.478.3
42.947.051.2
21.222.624.1
56.657.858.7
56.257.458.2
140016001800
9.0 13.647.050.554.3
35.238.842.6
10.411.212.1
51.752.553.1
51.452.252.7
61.566.171.1
40.744.849.0
13.714.715.8
53.154.154.8
52.753.754.5
77.283.089.3
46.150.655.3
17.218.519.8
54.555.756.6
54.155.356.1
20AWH (4 ROW - QUARTER CIRCUIT) (45o EWT)
CFM GPMP.D.FT.
75 F DB / 63 F WB 80 F DB / 67 F WB 85 F DB / 71 F WB
TOTALMBH
SENSIBLEMBH
TEMP.RISE
LADB LAWBTOTALMBH
SENSIBLEMBH
TEMP.RISE
LADB LAWBTOTALMBH
SENSIBLEMBH
TEMP.RISE
LADB LAWB
180020002200
6.0 5.539.240.342.2
35.838.441.2
13.113.514.1
56.657.257.6
55.856.356.7
51.352.855.3
40.643.446.5
17.117.618.4
59.159.960.4
58.258.959.4
64.466.369.4
45.248.251.6
21.522.123.1
61.762.763.3
60.861.662.1
180020002200
8.5 10.045.747.650.1
38.341.244.2
10.811.211.8
55.355.956.4
54.555.055.4
59.862.365.6
43.846.950.3
14.114.715.4
57.458.358.8
56.657.357.8
75.178.282.3
49.152.456.1
17.718.419.4
59.760.761.4
58.859.760.3
180020002200
11.0 15.749.451.854.7
39.842.846.0
9.09.4
10.0
54.555.255.6
53.754.354.6
64.767.871.7
45.748.952.6
11.812.313.0
56.557.357.9
55.656.456.8
81.285.089.9
51.354.958.8
14.815.516.4
58.659.660.3
57.758.659.1
20AWH (6 ROW - QUARTER CIRCUIT) (45o EWT)
CFM GPMP.D.FT.
75 F DB / 63 F WB 80 F DB / 67 F WB 85 F DB / 71 F WB
TOTALMBH
SENSIBLEMBH
TEMP.RISE
LADB LAWBTOTALMBH
SENSIBLEMBH
TEMP.RISE
LADB LAWBTOTALMBH
SENSIBLEMBH
TEMP.RISE
LADB LAWB
180020002200
4.5 4.740.041.043.2
37.139.843.0
17.818.219.2
55.956.656.9
55.656.256.5
52.453.756.6
42.045.048.5
23.323.925.2
58.459.259.6
58.058.859.2
65.767.471.0
46.849.953.8
29.230.031.6
60.961.962.4
60.661.561.9
180020002200
7.0 10.151.053.356.4
41.144.548.1
14.615.216.1
53.754.454.8
53.454.054.4
66.869.873.9
47.551.054.9
19.120.021.1
55.656.456.9
55.256.056.5
83.987.692.7
53.457.261.5
24.025.026.5
57.558.559.1
57.258.158.7
180020002200
9.5 17.357.360.464.3
43.947.451.2
12.112.713.5
52.453.153.5
52.152.753.1
75.179.184.1
50.754.658.8
15.816.717.7
53.954.755.2
53.654.354.8
94.299.2105.6
57.361.566.2
19.820.922.2
55.556.557.1
55.156.156.7
®
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
Product SpecificationsHorizontal
Chilled Water / Hot Water / DX
30AWH - 40AWHCHILLED WATER
COOLING PERFORMANCE
-17-
30AWH (4 ROW - QUARTER CIRCUIT) (45o EWT)
CFM GPMP.D.FT.
75 F DB / 63 F WB 80 F DB / 67 F WB 85 F DB / 71 F WB
TOTALMBH
SENSIBLEMBH
TEMP.RISE
LADB LAWBTOTALMBH
SENSIBLEMBH
TEMP.RISE
LADB LAWBTOTALMBH
SENSIBLEMBH
TEMP.RISE
LADB LAWB
250030003500
9.0 6.057.462.666.6
51.358.765.5
12.813.914.8
56.056.957.7
55.356.156.7
75.282.087.2
58.366.473.9
16.718.219.4
58.459.560.5
57.758.659.4
94.3102.9109.4
65.073.881.9
21.022.924.3
60.962.263.3
60.261.362.2
250030003500
12.0 10.165.472.177.4
54.462.369.6
10.912.012.9
54.955.856.6
54.255.055.6
85.694.4101.4
62.271.079.0
14.315.716.9
57.058.159.1
56.257.258.1
107.4118.4127.2
68.779.388.1
17.919.721.2
59.260.561.7
58.459.660.6
250030003500
15.0 14.970.578.284.6
56.464.772.4
9.410.411.3
54.155.055.9
53.554.254.9
92.3102.3110.7
64.874.082.5
12.313.614.8
56.057.258.2
55.356.357.2
115.8128.4139.0
72.883.092.2
15.417.118.5
58.059.460.6
57.358.559.5
30AWH (6 ROW - QUARTER CIRCUIT) (45o EWT)
CFM GPMP.D.FT.
75 F DB / 63 F WB 80 F DB / 67 F WB 85 F DB / 71 F WB
TOTALMBH
SENSIBLEMBH
TEMP.RISE
LADB LAWBTOTALMBH
SENSIBLEMBH
TEMP.RISE
LADB LAWBTOTALMBH
SENSIBLEMBH
TEMP.RISE
LADB LAWB
250030003500
8.0 6.764.270.775.9
54.963.371.2
16.117.719.0
54.755.556.2
54.455.155.8
84.192.699.4
62.772.080.6
21.023.124.9
56.857.858.7
56.557.458.3
105.5116.1124.7
70.280.389.7
26.429.031.2
59.060.261.3
58.759.860.8
250030003500
10.0 10.072.280.286.7
58.167.075.3
14.416.017.4
53.554.355.1
53.254.054.7
94.5105.0113.6
66.776.785.9
18.921.022.7
55.356.357.3
55.056.056.9
118.6131.7142.5
75.085.695.6
23.726.328.5
57.258.659.7
56.958.259.3
250030003500
12.0 13.978.087.295.0
60.469.878.6
13.014.515.8
52.653.554.2
52.353.153.8
102.2114.2124.3
69.780.290.0
17.019.020.7
54.255.356.2
53.954.955.8
128.2143.3156.0
78.289.6
100.3
21.423.926.0
56.057.358.5
55.756.958.0
40AWH (4 ROW - QUARTER CIRCUIT) (45o EWT)
CFM GPMP.D.FT.
75 F DB / 63 F WB 80 F DB / 67 F WB 85 F DB / 71 F WB
TOTALMBH
SENSIBLEMBH
TEMP.RISE
LADB LAWBTOTALMBH
SENSIBLEMBH
TEMP.RISE
LADB LAWBTOTALMBH
SENSIBLEMBH
TEMP.RISE
LADB LAWB
340011.013.015.0
10.113.617.7
76.583.088.0
69.171.673.6
13.912.811.7
56.255.555.0
55.554.854.3
100.1108.7115.2
78.481.684.1
18.216.715.4
58.657.857.1
57.957.056.4
125.6136.4144.5
87.491.294.2
22.821.019.3
61.260.259.4
60.459.458.6
40011.013.015.0
10.113.617.7
83.390.896.6
78.281.183.3
15.214.012.9
56.956.255.7
56.155.454.9
109.1118.9126.4
88.592.194.9
19.818.316.9
59.558.758.0
58.657.857.2
136.9149.3158.6
98.4102.7106.0
24.923.021.2
62.261.260.5
61.360.359.5
460011.013.015.0
10.113.617.7
88.797.2103.7
86.689.892.3
16.115.013.8
57.856.956.4
56.656.055.5
116.2127.3135.8
97.7101.7104.9
21.119.618.1
60.359.558.9
59.358.557.9
145.8159.7170.4
108.4113.2116.9
26.524.622.7
63.262.261.5
62.161.160.4
40AWH (6 ROW - QUARTER CIRCUIT) (45o EWT)
CFM GPMP.D.FT.
75 F DB / 63 F WB 80 F DB / 67 F WB 85 F DB / 71 F WB
TOTALMBH
SENSIBLEMBH
TEMP.RISE
LADB LAWBTOTALMBH
SENSIBLEMBH
TEMP.RISE
LADB LAWBTOTALMBH
SENSIBLEMBH
TEMP.RISE
LADB LAWB
34008.010.011.5
9.112.215.6
77.986.593.5
71.074.477.2
18.317.316.3
55.754.754.0
55.454.453.7
102.0113.3122.5
80.784.988.2
24.022.721.3
58.056.956.0
57.756.655.7
128.0142.2153.7
89.993.496.5
30.128.426.7
60.559.658.7
60.259.258.4
40008.010.011.5
9.112.215.6
85.595.3103.4
81.084.888.0
20.119.118.0
56.255.454.6
55.955.054.3
111.9124.8135.4
91.795.798.7
26.325.023.5
58.857.957.1
58.457.556.8
140.4156.6169.8
99.7103.4107.3
33.031.329.5
61.961.160.2
61.560.759.8
46008.010.011.5
9.112.215.6
91.6102.5111.5
90.494.689.1
21.520.519.4
56.856.055.3
56.455.654.9
119.9134.2146.0
101.7105.2108.7
28.226.825.4
59.558.858.1
59.158.457.7
150.4168.4183.3
108.5112.8117.3
35.433.731.9
63.262.361.4
62.761.860.9
®
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
Product SpecificationsHorizontal
Chilled Water / Hot Water / DX
60AWH - 80AWHCHILLED WATER
COOLING PERFORMANCE
80AWH (4 ROW - HALF CIRCUIT) (45o EWT)
CFM GPMP.D.FT.
75 F DB / 63 F WB 80 F DB / 67 F WB 85 F DB / 71 F WB
TOTALMBH
SENSIBLEMBH
TEMP.RISE
LADB LAWBTOTALMBH
SENSIBLEMBH
TEMP.RISE
LADB LAWBTOTALMBH
SENSIBLEMBH
TEMP.RISE
LADB LAWB
6000800010000
27.0 10.8151.3171.3185.2
128.9158.4184.9
11.212.713.7
55.156.757.9
54.555.956.9
198.1224.3242.5
147.2179.5208.3
14.716.618.0
57.359.260.7
56.758.459.7
248.6281.5304.2
164.7199.7230.7
18.420.922.5
59.661.963.6
58.961.062.5
6000800010000
32.0 14.8162.6186.4203.4
133.4164.2191.8
10.211.612.7
54.456.057.2
53.855.256.3
212.8244.0266.4
152.8186.8217.0
13.315.316.6
56.458.459.9
55.857.658.9
267.1306.2334.2
171.5208.5241.0
16.719.120.9
58.560.962.7
57.960.061.6
6000800010000
37.0 19.4171.5198.4218.3
136.9168.9197.4
9.310.711.8
53.955.556.7
53.354.755.7
224.5259.8285.8
157.3192.7224.0
12.114.015.4
55.757.759.3
55.156.958.2
281.7326.0358.6
176.9215.6249.5
15.217.619.4
57.760.161.9
57.059.260.8
80AWH (6 ROW - HALF CIRCUIT) (45o EWT)
CFM GPMP.D.FT.
75 F DB / 63 F WB 80 F DB / 67 F WB 85 F DB / 71 F WB
TOTALMBH
SENSIBLEMBH
TEMP.RISE
LADB LAWBTOTALMBH
SENSIBLEMBH
TEMP.RISE
LADB LAWBTOTALMBH
SENSIBLEMBH
TEMP.RISE
LADB LAWB
6000800010000
22.0 8.2161.7183.9200.1
135.1167.2196.9
14.716.718.2
54.255.756.8
53.955.456.4
211.8240.7262.0
154.6189.8222.2
19.321.923.8
56.258.159.4
55.957.759.0
265.7302.1328.8
173.3211.5246.5
24.227.529.9
58.360.562.2
57.960.161.7
6000800010000
27.0 11.9178.8206.7227.8
141.9176.0207.4
13.215.316.9
53.154.655.8
52.954.355.4
234.1270.6298.3
163.2201.0235.5
17.320.122.1
54.856.758.2
54.556.457.8
293.8339.6374.2
183.8225.0262.4
21.825.227.7
56.6595.060.7
56.358.660.3
6000800010000
32.0 16.2192.2224.9250.2
147.2183.2216.1
12.014.115.6
52.353.855.0
52.053.554.6
251.6194.4327.6
170.1210.1246.5
15.718.420.5
53.855.757.2
53.855.356.8
315.7369.4411.1
192.3236.1275.6
19.723.125.7
55.357.759.5
55.057.359.0
-18-
60AWH (4 ROW - HALF CIRCUIT) (45o EWT)
CFM GPMP.D.FT.
75 F DB / 63 F WB 80 F DB / 67 F WB 85 F DB / 71 F WB
TOTALMBH
SENSIBLEMBH
TEMP.RISE
LADB LAWBTOTALMBH
SENSIBLEMBH
TEMP.RISE
LADB LAWBTOTALMBH
SENSIBLEMBH
TEMP.RISE
LADB LAWB
520060006800
23.0 9.0127.4137.2142.9
109.8122.2132.9
11.111.912.4
55.556.156.9
54.855.456.0
166.8179.7187.1
125.2138.9150.5
14.515.616.3
57.758.659.5
57.057.758.6
209.3225.5234.8
139.9154.9167.4
18.219.620.4
60.161.162.2
59.360.261.2
520060006800
27.0 12.2136.2147.4154.5
113.3126.2137.3
10.110.911.4
54.855.556.3
54.254.855.4
178.4193.0202.3
129.6143.9156.1
13.214.315.0
56.957.858.7
56.257.057.8
223.9242.2253.8
145.2160.9174.1
16.617.918.8
59.260.261.3
58.459.360.3
520060006800
31.0 15.8143.2155.5163.7
116.0129.3140.9
9.210.010.6
54.355.155.8
53.754.354.9
187.6203.6214.3
133.1147.9160.6
12.113.113.8
56.357.258.1
55.656.357.2
235.4255.5268.9
149.5165.8179.5
15.216.517.4
58.459.460.6
57.658.559.6
60AWH (6 ROW - HALF CIRCUIT) (45o EWT)
CFM GPMP.D.FT.
75 F DB / 63 F WB 80 F DB / 67 F WB 85 F DB / 71 F WB
TOTALMBH
SENSIBLEMBH
TEMP.RISE
LADB LAWBTOTALMBH
SENSIBLEMBH
TEMP.RISE
LADB LAWBTOTALMBH
SENSIBLEMBH
TEMP.RISE
LADB LAWB
520060006800
17.0 5.9130.1140.5145.7
112.9126.3137.8
15.316.517.1
54.955.556.2
54.655.255.9
170.4183.9190.8
128.8143.6156.0
20.021.622.5
57.157.858.8
56.857.558.4
213.8230.8239.4
144.0160.2173.4
25.227.228.2
59.460.361.4
59.159.961.0
520060006800
21.0 8.9145.5158.1165.7
119.0133.2145.5
13.915.115.8
53.854.555.2
53.554.154.8
190.6207.0217.0
136.5152.3165.7
18.219.720.7
55.756.557.4
55.456.257.1
239.1259.7272.2
153.3170.6185.1
22.824.725.9
57.758.759.8
57.458.359.4
520060006800
25.0 12.4157.5171.9181.5
123.8138.7151.6
12.613.814.5
53.053.654.4
52.753.354.0
206.3225.1237.6
142.6159.2173.5
16.518.019.0
54.655.456.4
54.355.156.0
258.8282.4298.2
160.7179.1194.5
20.722.623.9
56.457.458.5
56.157.058.1
®
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
Product SpecificationsHorizontal
Chilled Water / Hot Water / DX
8AXH - 20AXHHORIZONTAL DX
COOLING PERFORMANCE
8AXH (4 ROW DX COIL)
SUCTIONTEMP.
FCFM
75 F DB / 63 F WB 80 F DB / 67 F WB 85 F DB / 71 F WB
TOTALMBH
SENSIBLEMBH
LADB LAWBTOTALMBH
SENSIBLEMBH
LADB LAWBTOTALMBH
SENSIBLEMBH
LADB LAWB
406008001000
23.728.031.4
15.619.021.9
50.953.054.7
49.150.952.2
29.835.339.6
17.921.725.0
52.454.956.9
50.552.754.3
36.042.547.7
19.924.117.6
54.357.159.4
52.354.856.8
456008001000
18.622.024.6
13.516.619.3
54.155.857.2
52.453.754.7
24.829.632.8
15.819.322.3
55.657.659.3
53.755.456.7
30.936.540.9
17.921.725.1
57.459.861.8
55.457.559.1
506008001000
13.115.417.3
11.314.116.5
57.558.759.8
55.756.657.6
19.222.725.4
13.716.819.6
58.860.561.8
57.058.359.3
25.330.033.6
15.819.422.5
60.662.564.2
58.660.261.5
12AXH (4 ROW DX COIL)
SUCTIONTEMP.
FCFM
75 F DB / 63 F WB 80 F DB / 67 F WB 85 F DB / 71 F WB
TOTALMBH
SENSIBLEMBH
LADB LAWBTOTALMBH
SENSIBLEMBH
LADB LAWBTOTALMBH
SENSIBLEMBH
LADB LAWB
40100012001400
35.438.841.3
23.826.729.2
52.954.455.7
50.751.953.0
44.548.852.0
27.230.433.1
54.856.558.1
52.554.056.2
53.758.862.7
30.233.636.5
57.159.060.8
54.656.357.8
45100012001400
27.830.432.3
20.823.425.7
55.856.958.0
53.454.555.3
37.040.443.1
24.227.229.7
57.659.060.3
55.356.457.4
46.150.553.8
27.330.533.3
59.761.463.0
57.858.759.9
50100012001400
19.521.322.0
17.619.922.0
58.759.660.5
56.557.260.5
28.731.433.4
21.123.826.2
60.561.662.7
58.259.059.8
37.841.444.1
24.227.329.9
52.563.965.2
60.161.262.2
16AXH (4 ROW DX COIL)
SUCTIONTEMP.
FCFM
75 F DB / 63 F WB 80 F DB / 67 F WB 85 F DB / 71 F WB
TOTALMBH
SENSIBLEMBH
LADB LAWBTOTALMBH
SENSIBLEMBH
LADB LAWBTOTALMBH
SENSIBLEMBH
LADB LAWB
40140016001800
48.651.854.4
32.835.738.1
53.354.455.4
51.051.952.7
61.165.268.5
37.440.643.3
55.256.557.7
52.853.954.9
73.778.382.6
41.544.947.8
57.559.060.4
55.056.357.4
45140016001800
38.140.642.6
28.631.233.5
56.156.957.8
53.854.555.1
50.754.056.7
33.336.338.8
57.959.060.0
55.556.457.2
63.267.470.8
37.540.743.5
60.261.462.6
57.658.759.6
50140016001800
26.828.529.8
24.326.628.6
59.059.660.3
56.757.257.6
39.341.944.0
29.131.734.1
60.761.662.4
58.459.059.6
51.955.358.1
33.436.439.0
62.963.964.9
60.461.261.9
20AXH (4 ROW DX COIL)
SUCTIONTEMP.
FCFM
75 F DB / 63 F WB 80 F DB / 67 F WB 85 F DB / 71 F WB
TOTALMBH
SENSIBLEMBH
LADB LAWBTOTALMBH
SENSIBLEMBH
LADB LAWBTOTALMBH
SENSIBLEMBH
LADB LAWB
40180020002200
60.963.966.3
41.444.046.4
53.754.655.5
51.352.052.7
76.780.583.6
47.250.152.8
55.756.857.8
53.254.154.9
92.597.0100.8
52.255.458.3
58.159.360.5
55.556.557.4
45180020002200
47.850.152.0
36.138.640.8
56.457.157.8
54.054.655.1
63.666.769.2
42.044.847.3
58.459.260.1
55.856.657.2
79.483.886.5
47.350.353.0
60.761.762.7
58.058.859.6
50180020002200
33.635.136.4
30.732.834.9
59.259.860.3
56.957.257.6
49.351.753.6
36.739.341.6
61.161.862.5
58.659.159.6
65.168.370.9
42.245.047.5
63.364.265.0
60.761.361.9
-19-
R-22
®
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
30AXH (4 ROW DX COIL)
SUCTIONTEMP.
FCFM
75 F DB / 63 F WB 80 F DB / 67 F WB 85 F DB / 71 F WB
TOTALMBH
SENSIBLEMBH
LADB LAWBTOTALMBH
SENSIBLEMBH
LAB LAWBTOTALMBH
SENSIBLEMBH
LADB LAWB
40250030003500
90.499.9107.8
60.968.975.9
52.453.754.9
50.551.552.5
113.7125.7135.7
69.678.486.2
54.255.857.2
52.253.554.6
137.0151.6163.7
77.286.895.2
56.458.259.8
54.255.857.1
45250030003500
71.078.484.5
53.160.366.7
55.356.457.4
53.454.254.9
94.3104.2112.5
61.970.177.3
57.158.459.5
55.056.157.0
117.6130.1140.4
69.778.786.7
59.260.762.1
57.058.359.4
50250030003500
49.855.059.2
44.951.357.1
58.459.259.9
56.457.057.5
73.280.887.1
53.961.368.0
60.061.162.0
58.058.759.4
96.5106.7115.1
62.170.477.8
62.063.364.4
59.960.961.7
Product SpecificationsHorizontal
Chilled Water / Hot Water / DX
30AXH - 80AXHHORIZONTAL DX
COOLING PERFORMANCE
-20-
80AXH (4 ROW DX COIL)
SUCTIONTEMP.
FCFM
75 F DB / 63 F WB 80 F DB / 67 F WB 85 F DB / 71 F WB
TOTALMBH
SENSIBLEMBH
LADB LAWBTOTALMBH
SENSIBLEMBH
LADB LAWBTOTALMBH
SENSIBLEMBH
LADB LAWB
4060008000
10000
227.7266.7295.0
151.2183.2209.5
51.754.055.6
49.851.653.0
286.3335.7371.6
173.0208.6237.7
53.355.958.0
51.353.555.2
345.0404.7448.3
192.2230.9262.4
55.458.360.7
53.355.857.8
4560008000
10000
178.9209.3231.2
131.2160.2184.5
54.856.558.0
52.854.255.3
237.5278.3307.9
153.4186.3213.5
56.358.560.3
54.356.157.5
296.2347.3384.5
173.2209.4239.2
58.360.862.9
56.258.359.9
5060008000
10000
125.8146.8158.2
110.5136.2158.2
58.059.360.4
56.157.0---
184.4215.8238.4
133.1163.0188.1
59.561.262.6
57.558.859.9
243.1284.8315.1
153.5187.0214.9
61.363.465.1
59.360.962.2
R-22
40AXH (4 ROW DX COIL)
SUCTIONTEMP.
FCFM
75 F DB / 63 F WB 80 F DB / 67 F WB 85 F DB / 71 F WB
TOTALMBH
SENSIBLEMBH
LADB LAWBTOTALMBH
SENSIBLEMBH
LADB LAWBTOTALMBH
SENSIBLEMBH
LADB LAWB
40340040004600
120.9131.9141.1
81.891.199.3
51.753.955.0
50.751.752.5
152.2166.1177.6
93.4103.6112.8
54.656.057.3
52.453.654.7
183.4200.2214.3
103.5114.7124.5
56.858.559.9
54.655.957.2
45340040004600
95.0103.5110.6
71.379.787.3
55.656.557.4
53.654.355.0
126.2137.7147.2
83.192.6101.1
57.458.659.6
55.256.257.0
157.4171.8183.8
93.6104.1113.4
59.560.962.2
57.358.459.4
50340040004600
66.772.677.4
60.367.874.7
58.659.360.0
56.557.057.5
97.9106.7114.0
72.481.189.0
60.361.262.1
58.158.859.5
129.2140.9150.6
83.393.0101.8
62.363.564.5
60.161.061.8
60AXH (4 ROW DX COIL)
SUCTIONTEMP.
FCFM
75 F DB / 63 F WB 80 F DB / 67 F WB 85 F DB / 71 F WB
TOTALMBH
SENSIBLEMBH
LADB LAWBTOTALMBH
SENSIBLEMBH
LADB LAWBTOTALMBH
SENSIBLEMBH
LADB LAWB
40520060006800
186.5201.3213.8
125.6138.0149.2
52.653.754.7
50.651.552.3
234.6253.3269.3
143.4157.2169.6
54.555.856.9
52.353.454.4
282.7305.4324.7
159.1174.1187.5
56.758.159.5
62.363.364.2
45520060006800
146.4158.0167.7
109.4120.7130.9
55.556.457.2
53.554.154.7
194.6210.0223.2
127.6140.3151.9
57.358.359.3
55.156.056.7
242.7262.1278.6
143.8157.8170.4
59.460.761.8
57.258.259.1
50520060006800
102.9110.8117.5
92.5102.5111.8
58.559.259.8
56.557.057.4
151.0162.9172.9
111.1122.7133.3
60.261.161.8
58.158.759.3
199.1215.0228.4
127.8140.8152.7
62.363.364.2
60.060.861.5
®
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
20AXH (6 ROW DX COIL)
SUCTIONTEMP.
FCFM
75 F DB / 63 F WB 80 F DB / 67 F WB 85 F DB / 71 F WB
TOTALMBH
SENSIBLEMBH
LADB LAWBTOTALMBH
SENSIBLEMBH
LADB LAWBTOTALMBH
SENSIBLEMBH
LADB LAWB
40180020002200
77.381.985.8
50.253.857.2
49.250.140.9
47.848.649.4
97.2103.080.7
57.761.765.4
50.351.452.4
48.949.950.8
117.0124.0130.0
64..68.772.7
51.953.254.4
50.451.652.7
45180020002200
60.864.467.4
43.346.649.6
52.753.454.1
51.351.952.5
80.785.589.5
50.854.658.1
53.854.755.6
52.453.253.9
100.5106.5111.6
57.661.765.5
55.456.457.4
53.954.855.7
50180020002200
42.945.347.5
36.139.041.8
56.456.957.4
55.055.455.8
62.766.469.5
43.847.250.3
57.558.258.8
56.056.657.2
82.687.491.6
50.754.558.1
58.959.760.6
57.458.158.8
Product SpecificationsHorizontal
Chilled Water / Hot Water / DX
8AXH - 20AXHHORIZONTAL DX
COOLING PERFORMANCE
12AXH (6 ROW DX COIL)
SUCTIONTEMP.
FCFM
75 F DB / 63 F WB 80 F DB / 67 F WB 85 F DB / 71 F WB
TOTALMBH
SENSIBLEMBH
LADB LAWBTOTALMBH
SENSIBLEMBH
LADB LAWBTOTALMBH
SENSIBLEMBH
LADB LAWB
40100012001400
44.149.153.1
28.432.335.8
48.650.051.3
47.348.649.8
55.461.766.8
32.737.140.9
49.751.452.9
48.349.851.3
66.874.480.5
36.541.345.4
51.153.155.0
49.751.653.3
45100012001400
34.738.641.7
24.528.031.1
52.353.454.4
51.052.052.8
46.051.355.4
28.832.836.3
63.354.756.0
52.053.254.3
57.363.969.1
32.737.141.0
54.756.357.9
53.354.856.2
50100012001400
24.427.229.3
20.423.426.2
56.156.957.6
54.855.456.0
35.839.843.0
24.828.431.6
57.058.159.1
55.756.657.5
47.152.456.7
27.832.836.4
58.459.760.9
57.058.159.2
16AXH (6 ROW DX COIL)
SUCTIONTEMP.
FCFM
75 F DB / 63 F WB 80 F DB / 67 F WB 85 F DB / 71 F WB
TOTALMBH
SENSIBLEMBH
LADB LAWBTOTALMBH
SENSIBLEMBH
LADB LAWBTOTALMBH
SENSIBLEMBH
LADB LAWB
40140016001800
60.965.769.8
39.443.246.6
48.950.051.0
47.648.54934
76.582.687.8
45.349.653.4
50.051.352.5
48.649.850.9
92.199.5105.7
50.555.259.3
51.653.154.5
50.151.552.8
45140016001800
47.951.754.8
33.937.440.5
52.553.454.2
51.251.952.6
63.568.672.8
39.943.847.4
53.654.655.6
52.253.154.0
79.185.590.8
45.349.653.5
55.156.357.5
53.654.855.8
50140016001800
33.736.438.6
28.331.334.1
56.356.957.4
54.955.455.9
49.453.356.5
34.437.941.1
57.358.158.8
55.956.657.2
65.070.274.5
39.843.847.4
58.759.660.6
57.258.158.9
-21-
R-22(contact factory for R410a)
8AXH (6 ROW DX COIL)
SUCTIONTEMP.
FCFM
75 F DB / 63 F WB 80 F DB / 67 F WB 85 F DB / 71 F WB
TOTALMBH
SENSIBLEMBH
LABD LAWBTOTALMBH
SENSIBLEMBH
LADB LAWBTOTALMBH
SENSIBLEMBH
LADB LAWB
406008001000
28.835.140.1
18.222.726.6
46.948.750.3
45.847.448.9
36.244.050.4
21.026.130.5
47.549.851.7
46.448.550.3
43.553.060.7
23.529.133.9
48.651.353.6
47.549.952.0
456008001000
22.627.631.5
15.619.523.1
50.952.453.6
49.851.152.2
30.036.641.8
18.423.027.0
51.553.455.0
50.452.153.5
37.445.652.1
21.026.130.5
52.654.856.7
51.453.555.2
506008001000
16.019.422.2
12.916.319.4
55.156.157.0
54.054.955.6
23.328.432.5
15.719.823.4
55.757.158.3
54.655.856.8
30.737.448.0
19.322.926.1
56.758.460.8
55.557.159.4
®
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
Product SpecificationsHorizontal
Chilled Water / Hot Water / DX
30AXH - 80AXHHORIZONTAL DX
COOLING PERFORMANCE
30AXH (6 ROW DX COIL)
SUCTIONTEMP.
FCFM
75 F DB / 63 F WB 80 F DB / 67 F WB 85 F DB / 71 F WB
TOTALMBH
SENSIBLEMBH
LADB LAWBTOTALMBH
SENSIBLEMBH
LADB LAWBTOTALMBH
SENSIBLEMBH
LADB LAWB
40250030003500
111.8125.8137.7
72.182.692.1
48.349.550.6
47.158.249.2
140.5158.2173.2
83.094.8105.4
49.350.752.1
48.049.450.6
169.1190.5208.6
92.7105.6117.1
50.752.454.0
49.451.052.5
45250030003500
88.098.9108.3
62.071.379.9
52.053.053.9
50.851.752.4
116.6131.3143.7
73.083.793.4
52.954.255.3
51.752.853.8
145.3163.6179.2
82.994.8105.5
54.355.757.1
53.054.355.5
50250030003500
62.069.776.2
51.659.767.3
55.956.657.2
54.755.255.8
90.7102.0111.6
62.872.381.1
56.857.758.5
55.556.357.1
119.2134.3147.1
72.883.693.5
58.059.260.3
56.857.858.4
40AXH (6 ROW DX COIL)
SUCTIONTEMP.
FCFM
75 F DB / 63 F WB 80 F DB / 67 F WB 85 F DB / 71 F WB
TOTALMBH
SENSIBLEMBH
LADB LAWBTOTALMBH
SENSIBLEMBH
LADB LAWBTOTALMBH
SENSIBLEMBH
LADB LAWB
40340040004600
149.8166.0179.9
96.9109.2120.4
48.649.750.8
47.448.449.3
188.2208.7226.1
111.5125.3137.7
49.651.052.3
48.449.650.8
226.6251.3272.4
124.5139.5153.1
51.152.754.2
49.851.352.6
45340040004600
117.8130.5141.4
83.598.6104.5
52.353.254.0
51.051.852.5
156.2173.2187.6
98.2110.8122.2
53.254.455.4
52.053.053.9
194.7215.8233.9
111.4125.4138.0
54.756.057.2
53.354.655.7
50340040004600
83.191.999.4
69.679.188.1
56.156.757.3
54.855.355.8
121.5134.6145.7
84.595.7106.1
57.057.858.6
55.756.457.1
159.9177.2192.0
98.0110.7122.4
58.359.460.4
57.057.958.8
-22-
60AXH (6 ROW DX COIL)
SUCTIONTEMP.
FCFM
75 F DB / 63 F WB 80 F DB / 67 F WB 85 F DB / 71 F WB
TOTALMBH
SENSIBLEMBH
LADB LAWBTOTALMBH
SENSIBLEMBH
LADB LAWBTOTALMBH
SENSIBLEMBH
LADB LAWB
40520060006800
226.8248.3266.9
147.3163.5178.5
48.849.850.7
47.648.449.3
285.0312.0335.6
169.3187.6204.3
49.951.152.2
48.650.050.7
343.2375.8404.2
188.9208.9227.1
51.452.854.1
50.151.452.6
45520060006800
178.4195.2209.8
126.9141.5155.0
52.453.253.9
51.251.852.5
236.6259.0278.4
149.2165.8181.2
53.454.455.3
52.253.053.9
294.8322.8347.1
169.2187.7204.6
54.956.157.2
53.654.656.0
50520060006800
125.7137.4147.6
105.9118.6130.5
56.256.757.2
54.955.455.8
183.9201.2216.3
128.5143.4157.3
57.257.958.6
55.956.557.1
242.1265.0284.9
148.9165.7181.4
58.559.460.3
57.258.058.8
80AXH (6 ROW DX COIL)
SUCTIONTEMP.
FCFM
75 F DB / 63 F WB 80 F DB / 67 F WB 85 F DB / 71 F WB
TOTALMBH
SENSIBLEMBH
LADB LAWBTOTALMBH
SENSIBLEMBH
LADB LAWBTOTALMBH
SENSIBLEMBH
LADB LAWB
406000800010000
271.9327.7370.2
174.8216.6252.2
48.150.051.7
46.948.650.2
341.6411.9465.6
201.3248.3287.9
49.051.353.4
47.849.951.8
411.3496.1561.1
224.9276.4319.5
50.353.055.4
49.151.653.8
456000800010000
213.9257.6290.8
150.3187.5219.8
51.853.354.7
50.752.053.2
283.6341.8386.3
287.9219.7256.3
52.754.656.3
51.553.254.7
353.3426.1481.7
201.0248.5288.8
54.056.358.3
52.854.856.6
506000800010000
150.9181.4204.4
124.9157.3186.2
55.756.857.8
54.655.556.3
220.5265.6299.8
152.0190.0223.4
56.658.059.3
55.456.757.7
290.2349.8395.3
176.5219.6257.0
57.859.661.2
56.658.259.6
R-22(contact factory for R410a)
®
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
Product SpecificationsHorizontal
Chilled Water / Hot Water / DX
8AXH - 20AXHHORIZONTAL DX
COOLING PERFORMANCE
8AXH (4 ROW DX COIL)
SUCTIONTEMP.
FCFM
75 F DB / 63 F WB 80 F DB / 67 F WB 85 F DB / 71 F WB
TOTALMBH
SENSIBLEMBH
LADB LAWBTOTALMBH
SENSIBLEMBH
LADB LAWBTOTALMBH
SENSIBLEMBH
LADB LAWB
406008001000
23.729.835.4
15.619.723.6
50.352.053.1
48.849.850.7
29.436.843.6
17.822.727.3
52.153.654.9
50.551.652.8
35.444.652.3
20.025.130.1
53.956.057.4
52.253.955.3
456008001000
18.823.728.0
13.217.120.6
53.954.955.8
52.152.953.5
24.430.736.5
15.619.723.7
55.357.058.1
53.754.655.6
30.538.545.3
17.722.826.7
57.558.660.5
55.456.857.7
506008001000
13.316.920.1
10.814.117.0
57.558.359.1
55.556.156.4
18.924.028.3
13.216.820.7
58.960.360.8
57.057.758.3
25.131.737.4
15.319.823.8
60.962.063.1
58.159.460.3
12AXH (4 ROW DX COIL)
SUCTIONTEMP.
FCFM
75 F DB / 63 F WB 80 F DB / 67 F WB 85 F DB / 71 F WB
TOTALMBH
SENSIBLEMBH
LADB LAWBTOTALMBH
SENSIBLEMBH
LADB LAWBTOTALMBH
SENSIBLEMBH
LADB LAWB
40100012001400
37.042.747.8
24.828.632.7
52.053.153.6
50.150.851.4
46.052.959.0
28.332.936.6
53.954.956.1
51.952.753.4
55.864.071.5
31.736.441.5
56.057.458.1
54.055.055.9
45100012001400
29.233.637.7
21.124.327.9
55.356.356.8
53.253.754.1
38.243.849.0
24.328.731.9
57.558.159.2
55.055.656.1
47.654.661.1
28.033.036.8
59.359.961.1
56.757.558.3
50100012001400
20.523.726.5
17.020.123.0
59.159.560.0
56.256.656.9
29.533.937.8
20.724.427.9
60.861.361.8
58.058.558.9
38.944.850.0
24.428.832.0
62.563.164.2
59.760.461.0
16AXH (4 ROW DX COIL)
SUCTIONTEMP.
FCFM
75 F DB / 63 F WB 80 F DB / 67 F WB 85 F DB / 71 F WB
TOTALMBH
SENSIBLEMBH
LADB LAWBTOTALMBH
SENSIBLEMBH
LADB LAWBTOTALMBH
SENSIBLEMBH
LADB LAWB
40140016001800
49.454.459.1
33.536.540.1
53.154.254.7
50.951.551.8
61.157.473.4
37.642.046.2
55.556.156.8
52.953.554.1
74.081.588.6
42.647.651.6
57.458.159.1
55.155.856.3
45140016001800
38.442.646.3
28.631.234.3
56.357.257.4
53.854.354.7
50.255.660.2
33.636.640.3
58.159.259.7
55.756.356.6
63.169.475.6
37.742.246.3
60.561.161.8
57.858.358.9
50140016001800
27.029.832.3
23.026.528.4
59.860.360.7
56.957.157.3
38.742.646.1
27.931.334.4
61.862.262.7
58.759.159.4
51.556.561.3
32.936.840.4
63.664.264.7
60.661.161.5
20AXH (4 ROW DX COIL)
SUCTIONTEMP.
FCFM
75 F DB / 63 F WB 80 F DB / 67 F WB 85 F DB / 71 F WB
TOTALMBH
SENSIBLEMBH
LADB LAWBTOTALMBH
SENSIBLEMBH
LADB LAWBTOTALMBH
SENSIBLEMBH
LADB LAWB
40180020002200
63.368.172.6
42.345.949.3
53.154.254.7
51.151.551.8
77.984.189.8
48.752.856.7
55.556.156.8
53.153.654.1
94.2101.0107.7
54.459.063.2
57.758.459.1
55.555.956.4
45180020002200
49.753.557.3
36.140.242.1
56.357.257.7
53.854.354.7
64.970.074.4
42.446.149.4
58.659.259.7
55.956.256.6
80.586.893.1
48.853.056.1
60.561.162.1
57.958.559.0
50180020002200
35.338.040.6
29.933.435.9
59.760.260.7
56.957.157.3
50.354.257.7
36.239.342.2
61.862.262.7
58.859.159.4
66.071.475.9
42.646.249.6
63.664.264.7
60.661.161.4
-23-
R410A
®
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
30AXH (4 ROW DX COIL)
SUCTIONTEMP.
FCFM
75 F DB / 63 F WB 80 F DB / 67 F WB 85 F DB / 71 F WB
TOTALMBH
SENSIBLEMBH
LADB LAWBTOTALMBH
SENSIBLEMBH
LADB LAWBTOTALMBH
SENSIBLEMBH
LADB LAWB
40250030003500
95.8109.8122.3
63.773.083.3
52.053.153.6
50.050.751.3
117.0134.2149.3
73.283.993.2
53.654.956.1
51.652.653.4
141.6161.0178.4
80.893.6105.3
56.057.058.1
53.954.955.8
45250030003500
76.287.497.6
54.464.071.2
55.355.856.8
52.953.554.0
98.2112.1125.3
63.973.283.5
57.058.158.6
54.755.455.9
122.0139.0154.9
73.484.293.5
58.659.961.1
56.757.458.2
50250030003500
54.663.070.1
46.353.159.2
58.359.159.9
56.156.456.7
76.888.098.3
54.664.271.4
60.360.861.8
57.758.258.8
100.9114.7128.1
64.173.583.8
62.063.163.6
59.560.160.7
Product SpecificationsHorizontal
Chilled Water / Hot Water / DX
30AXH - 80AXHHORIZONTAL DX
COOLING PERFORMANCE
-24-
80AXH (4 ROW DX COIL)
SUCTIONTEMP.
FCFM
75 F DB / 63 F WB 80 F DB / 67 F WB 85 F DB / 71 F WB
TOTALMBH
SENSIBLEMBH
LADB LAWBTOTALMBH
SENSIBLEMBH
LADB LAWBTOTALMBH
SENSIBLEMBH
LADB LAWB
4060008000
10000
234.6292.4340.5
157.9196.5233.8
51.453.154.2
49.850.751.5
288.8359.9418.9
181.2225.4261.3
53.054.956.8
51.352.853.9
346.3429.9501.4
202.4251.4295.1
54.957.058.8
53.254.956.2
4560008000
10000
187.3232.7272.0
135.2168.2200.2
54.956.357.2
52.753.654.3
240.3299.1349.9
158.4197.1234.5
56.458.159.2
54.455.556.3
300.3370.9432.4
177.7226.2262.2
58.659.961.8
56.457.558.7
5060008000
10000
134.8167.1195.7
112.5143.5171.0
58.359.159.9
56.056.456.9
188.9233.4274.0
135.6168.8200.9
59.961.362.2
57.558.359.1
247.6305.9356.1
159.0197.8235.3
61.463.164.2
59.360.261.1
R-410A
40AXH (4 ROW DX COIL)
SUCTIONTEMP.
FCFM
75 F DB / 63 F WB 80 F DB / 67 F WB 85 F DB / 71 F WB
TOTALMBH
SENSIBLEMBH
LADB LAWBTOTALMBH
SENSIBLEMBH
LADB LAWBTOTALMBH
SENSIBLEMBH
LADB LAWB
40340040004600
128.3145.1160.1
87.097.7109.7
52.053.153.6
50.150.851.2
158.2178.7197.9
97.5112.2124.4
54.354.955.8
51.952.653.3
191.5216.5238.9
110.2123.6138.8
56.057.458.1
54.155.055.7
45340040004600
101.4114.6126.9
72.783.693.9
55.856.356.8
53.253.754.1
131.8148.4163.9
85.298.0110.1
57.558.158.6
55.055.756.0
164.0185.0205.5
97.9112.6123.2
59.359.961.1
56.857.558.3
50340040004600
72.281.589.8
60.469.578.1
59.159.559.9
56.356.656.9
101.9115.3126.9
72.983.994.2
60.861.361.8
58.058.558.8
134.7151.5167.7
85.598.4107.7
62.563.164.2
59.860.360.9
60AXH (4 ROW DX COIL)
SUCTIONTEMP.
FCFM
75 F DB / 63 F WB 80 F DB / 67 F WB 85 F DB / 71 F WB
TOTALMBH
SENSIBLEMBH
LADB LAWBTOTALMBH
SENSIBLEMBH
LADB LAWBTOTALMBH
SENSIBLEMBH
LADB LAWB
40520060006800
195.7216.4235.7
133.6147.1162.7
52.053.153.6
50.250.751.4
240.4264.5286.8
149.7166.7182.0
54.355.256.1
52.352.953.6
285.0315.7342.6
167.1186.0200.3
56.357.458.8
54.455.456.2
45520060006800
156.6174.0190.2
114.4129.0139.3
55.355.856.8
53.053.554.0
200.9223.2243.6
130.9147.5159.1
57.558.159.2
55.055.656.1
249.1273.6298.9
150.2165.2182.7
59.360.561.1
57.057.758.5
50520060006800
115.0127.3139.0
95.1107.3118.9
58.759.159.5
56.156.456.6
158.5176.1192.6
114.7129.4139.8
60.360.861.8
57.858.358.8
206.9229.0249.0
131.3148.1159.7
62.563.164.2
59.760.360.8
®
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
HEATING PERFORMANCEProduct Specifications
HorizontalChilled Water / Hot Water / DX
8AWH (1 ROW COIL) (180O EWT)
CFM GPMP.D.FT.
ENTERING AIR - 70oF DB
TOTALMBH
TEMP.RISE
LADB
6008001000
3.0 1.226.129.432.4
17.419.621.6
110.4104.1100.1
6008001000
5.0 3.328.131.935.5
11.212.814.2
113.5107.1103.0
6008001000
8.0 8.029.333.637.5
7.38.49.4
115.4109.0104.8
8AWH (2 ROW COIL - HALF CIRCUIT) (180O EWT)
CFM GPMP.D.FT.
ENTERING AIR - 70oF DB
TOTALMBH
TEMP.RISE
LADB
600800
10003.5 1.2
41.349.456.5
23.628.332.3
133.9127.3122.4
600800
10006.5 3.9
44.654.062.2
13.716.619.1
139.1132.6127.7
600800
10009.5 8.2
46.556.565.2
9.811.913.7
141.9135.5130.5
12AWH (1 ROW COIL) (180O EWT)
CFM GPMP.D.FT.
ENTERING AIR - 70oF DB
TOTALMBH
TEMP.RISE
LADB
100012001400
4.0 2.136.539.842.7
18.319.921.4
103.9100.898.3
100012001400
7.0 6.239.643.346.7
11.312.413.4
106.8103.5101.0
100012001400
10.0 12.440.844.648.2
8.28.99.6
107.8104.5102.0
12AWH (2 ROW COIL - HALF CIRCUIT) (180O EWT)
CFM GPMP.D.FT.
ENTERING AIR - 70oF DB
TOTALMBH
TEMP.RISE
LADB
100012001400
5.0 2.662.770.076.3
25.128.030.5
128.2124.1120.6
100012001400
7.5 5.866.574.581.4
17.719.921.7
131.7127.6123.9
100012001400
10.0 10.368.877.284.5
13.815.416.9
133.9129.7126.0
16AWH (1 ROW COIL) (180O EWT)
CFM GPMP.D.FT.
ENTERING AIR - 70oF DB
TOTALMBH
TEMP.RISE
LADB
140016001800
4.0 1.747.550.052.8
23.725.026.4
101.599.097.2
140016001800
7.5 5.753.056.359.6
14.115.015.9
105.1102.7100.7
140016001800
11.0 11.655.258.862.4
10.010.711.3
106.6104.1102.2
16AWH (2 ROW COIL - HALF CIRCUIT) (180O EWT)
CFM GPMP.D.FT.
ENTERING AIR - 70oF DB
TOTALMBH
TEMP.RISE
LADB
140016001800
6.0 3.485.892.699.1
28.630.933.0
126.9123.7121.1
140016001800
9.0 7.591.398.9
105.9
20.322.023.5
130.5127.3124.6
140016001800
12.0 13.394.6
102.7110.1
15.817.118.4
132.7129.6126.8
20AWH (1 ROW COIL) (180O EWT)
CFM GPMP.D.FT.
ENTERING AIR - 70oF DB
TOTALMBH
TEMP.RISE
LADB
180020002200
5.0 3.159.662.265.0
23.924.926.0
100.798.897.4
180020002200
8.0 7.364.968.071.3
16.217.017.8
103.5101.6100.1
180020002200
11.0 13.167.470.974.3
12.312.913.5
104.7102.9101.3
20AWH (2 ROW COIL - HALF CIRCUIT) (180O EWT)
CFM GPMP.D.FT.
ENTERING AIR - 70oF DB
TOTALMBH
TEMP.RISE
LADB
180020002200
6.5 4.2106.3112.5118.8
32.734.636.6
124.8122.2120.1
180020002200
9.5 9.0113.3120.3127.1
23.825.326.8
128.4125.8123.6
180020002200
12.5 15.6117.5125.1132.3
18.820.021.2
130.6128.0125.8-25-
®
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
HEATING PERFORMANCEProduct Specifications
HorizontalChilled Water / Hot Water / DX
30AWH (1 ROW COIL) (180O EWT)
CFM GPMP.D.FT.
ENTERING AIR - 70oF DB
TOTALMBH
TEMP.RISE
LADB
250030003500
9.0 2.493.1101.1108.4
20.722.524.1
104.5101.398.7
250030003500
12.0 4.197.7106.4114.4
16.317.719.1
106.3102.9100.3
250030003500
15.0 6.1100.5109.7118.1
13.414.615.8
107.3103.9101.3
30AWH (2 ROW COIL - HALF CIRCUIT) (180O EWT)
CFM GPMP.D.FT.
ENTERING AIR - 70oF DB
TOTALMBH
TEMP.RISE
LADB
250030003500
12.5 2.0161.5180.6197.3
25.828.931.6
129.9125.9122.3
250030003500
17.0 3.6169.0189.5207.5
19.922.324.4
132.7128.6125.0
250030003500
21.5 5.7174.1195.5214.3
16.218.219.9
134.6130.4126.8
40AWH (1 ROW COIL) (180O EWT)
CFM GPMP.D.FT.
ENTERING AIR - 70oF DB
TOTALMBH
TEMP.RISE
LADB
340040004600
8.0 2.5116.4109.5132.9
29.131.333.2
101.899.096.8
340040004600
11.0 4.412.50134.6143.3
22.724.526.1
104.1101.298.9
340040004600
14.0 6.9130.3140.5149.9
18.620.121.4
105.5102.6100.2
40AWH (2 ROW COIL - HALF CIRCUIT) (180O EWT)
CFM GPMP.D.FT.
ENTERING AIR - 70oF DB
TOTALMBH
TEMP.RISE
LADB
340040004600
12.0 2.2209.3230.1249.5
34.938.541.6
127.1123.5120.3
340040004600
16.0 3.9220.5243.6264.0
27.630.533.0
130.2126.5123.2
340040004600
20.0 6.0228.2252.5274.0
22.825.327.4
132.3128.6125.2
-26-
60AWH (1 ROW COIL) (180O EWT)
CFM GPMP.D.FT.
ENTERING AIR - 70oF DB
TOTALMBH
TEMP.RISE
LADB
520060006800
11.0 3.5177.8189.6197.8
32.334.536.0
101.799.397.0
520060006800
15.0 6.3191.4204.2214.2
25.527.228.6
104.1101.699.2
520060006800
19.0 9.7199.9213.6224.8
21.022.523.7
105.78103.0100.7
60AWH (2 ROW COIL - HALF CIRCUIT) (180O EWT)
CFM GPMP.D.FT.
ENTERING AIR - 70oF DB
TOTALMBH
TEMP.RISE
LADB
520060006800
12.0 2.2297.3324.1343.7
49.654.057.3
123.0120.1116.9
520060006800
17.0 4.3321.7351.1374.5
37.941.344.1
127.4124.3121.1
520060006800
22.0 7.0337.9369.3395.4
30.733.635.9
130.3127.1123.9
80AWH (1 ROW COIL) (180O EWT)
CFM GPMP.D.FT.
ENTERING AIR - 70oF DB
TOTALMBH
TEMP.RISE
LADB
6000800010000
14.0 3.8221.4247.6270.1
31.635.438.6
104.298.795.1
6000800010000
18.0 6.2234.6264.0289.3
26.129.332.1
106.3100.696.8
6000800010000
22.0 9.1243.8275.6303.2
22.225.127.6
107.7102.098.1
80AWH (2 ROW COIL - HALF CIRCUIT) (180O EWT)
CFM GPMP.D.FT.
ENTERING AIR - 70oF DB
TOTALMBH
TEMP.RISE
LADB
6000800010000
15.0 3.2360.6423.7473.4
48.156.563.1
125.8119.1113.9
6000800010000
20.0 5.4384.0454.1510.2
38.445.451.0
129.4122.7117.3
6000800010000
25.0 8.1400.6476.2537.2
32.138.143.0
131.9125.2119.8
®
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
CONDENSATE DRAIN CONNECTION
LEAVINGCHILLED WATER
ENTERINGCHILLED WATER
LEAVINGHOT WATER
AIRFLOW
HORIZONTAL RIGHT HAND COIL
CONNECTIONS
CONNECTIONS &SERVICE CLEARANCE
Product SpecificationsHorizontal
Chilled Water / Hot Water / DX
HORIZONTAL LEFT HAND COIL
CONNECTIONS
AIRFLOW
ENTERINGHOT WATER
AIRFLOWAIRFLOW
ENTERINGHOT WATER
LEAVINGHOT WATER
LEAVINGCHILLED WATER
ENTERINGCHILLED WATER
CONDENSATE DRAIN CONNECTION
ANGLEDFILTER
SECTION
MIXINGBOX
AWHDFLATFILTER
SECTION
-27-
*MINIMUM SIDE SERVICE CLEARANCES (Same for LH or RH units)
UNITMODEL
MOTOR BLOWER
FILTER SECTION
COIL MOTOR CONTROL
BOX
MIXING BOX
CABINET
FLAT OR ANGLED
ALL ROWS TOP BOTTOM
8AWHD 36.0” 36.0” 36.0” 36.0” 36.0” 36.0”
Allow extra space for
spring isolators if applicable
If mounting unit on a plat-
form, leave space for
condensate trap
12AWHD 42.0” 42.0” 42.0” 42..0” 42.0” 42.0”
16AWHD 48.0” 48.0” 48.0” 48.0” 48.0” 48.0”
20AWHD 52.0” 52.0” 52.0” 52.0” 52.0” 52.0”
30AWHD 52.0” 52.0” 52.0” 52.0” 52.0” 52.0”
40AWHD 54.0” 54.0” 54.0” 54.0” 54.0” 54.0”
60AWHD 64.0” 64.0” 64.0” 64.0” 64.0” 64.0”
80AWHD 64.0” 64.0” 64.0” 64.0” 64.0” 64.0”
NOTES:* Minimum service clearances only allow for removal of largest unit component, it does not allow extra space for service access or local code requirements.Blower and motor access panels are on both sides of cabinetFilter access is from either side of cabinet
®
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
BLOWER CURVEProduct SpecificationsHorizontal
Chilled Water / Hot Water / DX
CFM
Stat
ic P
ress
. (in
.wg)
Size 08 Blower Curve
0 200 400 600 800 1000 1200 14000
0.25
0.5
0.75
1
1.25
1.5
1.75
2
2.25
2.5
800 rpm
1000 rpm
1200 rpm
1400 rpm
1600 rpm
1800 rpm
0.25 HP
0.33 HP
0.50 HP
0.75 HP1.0 HP
2 Ton (08) Horizontal Belt Drive Information
HP Voltage Blower RPMMotor / Drive Kit
Number
1/4 115-1-60 825 - 1065 9MD08-A1
1/4 115 / 208 - 2301-60 825 - 1065 9MD08-A2
1/4 277-1-60 825 - 1065 9MD08-A3
1/4 115-1-60 955 - 1240 9MD08-A6
1/4 115 / 208 - 230-1-60 955 - 1240 9MD08-A7
1/4 277-1-60 955 - 1240 9MD08-A8
1/3 115-1-60 825 - 1065 9MD08-B1
1/3 115 / 208- 230-1-60 825 - 1065 9MD08-B2
1/3 277-1-60 825 - 1065 9MD08-B3
1/3 208 - 230 / 460-3-60 825 - 1065 9MD08-B4
1/3 575-3-60 825 - 1065 9MD08-B5
1/3 115-1-60 955 - 1240 9MD08-B6
1/3 115 / 208- 230-1-60 955 - 1240 9MD08-B7
1/3 277-1-60 955 - 1240 9MD08-B8
1/3 208 - 230 / 460-3-60 955 - 1240 9MD08-B9
1/3 575-3-60 955 - 1240 9MD08-B10
1/3 115-1-60 1020 - 1330 9MD08-B11
1/3 115 / 208- 230-1-60 1020 - 1330 9MD08-B12
1/3 277-1-60 1020 - 1330 9MD08-B13
1/3 208 - 230 / 460-3-60 1020 - 1330 9MD08-B14
1/3 575-3-60 1020 - 1330 9MD08-B15
-28-
8AWH/8AXH
CFM
Componet Static Pressure (Inches of Water)
CABINET
Chilled Water CoilHot
Water Coil
DX Coil Filter Sections
Mixing BoxDry Coil Wet Coil Dry Coil
Dry Coil
Wet Coil
2” Flat
4” Flat
2” Angled
4” Angled
4 Row
6 Row
4 Row
6 Row
*1-2 Row
4 rowMerv
7Merv
7Merv 7 Merv 7
600 0.06 0.14 0.18 0.20 0.26 0.05 0.20 0.29 0.09 0.06 0.05
NA
.10
700 0.08 0.16 0.22 0.23 0.31 0.07 0.25 0.36 0.12 0.08 0.06 .13
800 0.10 0.19 0.26 0.27 0.37 0.09 0.28 0.40 0.15 0.10 0.08 .16
900 0.12 0.22 0.30 0.31 0.43 0.11 0.31 0.44 0.18 0.12 0.10 .20
1000 0.15 0.25 0.34 0.36 0.49 0.13 0.35 0.50 0.21 0.15 0.12 .24
2 Ton (08) Horizontal Belt Drive Information
HP Voltage Blower RPMMotor / Drive Kit
Number
1/2 115-1-60 1020 - 1330 9MD08-C1
1/2 115 / 208- 230-1-60 1020 - 1330 9MD08-C2
1/2 277-1-60 1020 - 1330 9MD08-C3
1/2 208 - 230 / 460-3-60 1020 - 1330 9MD08-C4
1/2 575-3-60 1020 - 1330 9MD08-C5
1/2 115-1-60 1165 - 1520 9MD08-C6
1/2 115 / 208- 230-1-60 1165 - 1520 9MD08-C7
1/2 277-1-60 1165 - 1520 9MD08-C8
1/2 208 - 230 / 460-3-60 1165 - 1520 9MD08-C9
1/2 575-3-60 1165 - 1520 9MD08-C10
3/4 115 / 208- 230-1-60 1165 - 1520 9MD08-D2
3/4 277-1-60 1165 - 1520 9MD08-D3
3/4 208 - 230 / 460-3-60 1165 - 1520 9MD08-D4
3/4 575-3-60 1165 - 1520 9MD08-D5
3/4 115 / 208- 230-1-60 1310 - 1710 9MD08-D7
3/4 277-1-60 1310 - 1710 9MD08-D8
3/4 208 - 230 / 460-3-60 1310 - 1710 9MD08-D9
3/4 575-3-60 1310 - 1710 9MD08-D10
1 115 / 208- 230-1-60 1310 - 1710 9MD08-E2
1 277-1-60 1310 - 1710 9MD08-E3
1 208 - 230 / 460-3-60 1310 - 1710 9MD08-E4
1 575-3-60 1310 - 1710 9MD08-E5
2 TON FAN PERFORMANCE ( AWH / AWX )
Model CFM
TOTAL STATIC PRESSURE - INCHES OF WATER
0.6 0.7 0.8 0.9 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
08
600 986 0.3 1044 0.3 1103 0.3 1161 0.4 1220 0.4 1333 0.5 1439 0.5 1538 0.6 1629 0.7 --- ---
700 1042 0.3 1087 0.3 1134 0.4 1183 0.4 1232 0.4 1333 0.5 1434 0.6 1531 0.6 1624 0.7 --- ---
800 1117 0.4 1153 0.4 1191 0.4 1230 0.4 1271 0.5 1356 0.5 1443 0.6 1531 0.7 1619 0.8 --- ---
900 1204 0.5 1234 0.5 1265 0.5 1298 0.5 1331 0.5 1401 0.6 1475 0.7 1551 0.7 1629 0.8 --- ---
1000 1298 0.6 1324 0.6 1351 0.6 1378 0.6 1406 0.6 1465 0.7 1527 0.7 1592 0.8 1659 0.9 --- ---
®
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
BLOWER CURVEProduct SpecificationsHorizontal
Chilled Water / Hot Water / DX
3 Ton (12) Horizontal Belt Drive Information
HP VoltageBlower RPM
Motor / Drive Kit Number
1/3 115-1-60 695 - 890 9MD12-B1
1/3 115 / 208- 230-1-60 695 - 890 9MD12-B2
1/3 277-1-60 695 - 890 9MD12-B3
1/3 208 - 230 / 460-3-60 695 - 890 9MD12-B4
1/3 575-3-60 695 - 890 9MD12-B5
1/3 115-1-60 825 - 1065 9MD12-B6
1/3 115 / 208- 230-1-60 825 - 1065 9MD12-B7
1/3 277-1-60 825 - 1065 9MD12-B8
1/3 208 - 230 / 460-3-60 825 - 1065 9MD12-B9
1/3 575-3-60 825 - 1065 9MD12-B10
1/3 115-1-60 955 - 1240 9MD12-B11
1/3 115 / 208- 230-1-60 955 - 1240 9MD12-B12
1/3 277-1-60 955 - 1240 9MD12-B13
1/3 208 - 230 / 460-3-60 955 - 1240 9MD12-B14
1/3 575-3-60 955 - 1240 9MD12-B15
1/2 115-1-60 695 - 890 9MD12-C1
1/2 115 / 208- 230-1-60 695 - 890 9MD12-C2
1/2 277-1-60 695 - 890 9MD12-C3
1/2 208 - 230 / 460-3-60 695 - 890 9MD12-C4
1/2 575-3-60 695 - 890 9MD12-C5
1/2 115-1-60 825 - 1065 9MD12-C6
1/2 115 / 208- 230-1-60 825 - 1065 9MD12-C7
1/2 277-1-60 825 - 1065 9MD12-C8
1/2 208 - 230 / 460-3-60 825 - 1065 9MD12-C9
1/2 575-3-60 825 - 1065 9MD12-C10
1/2 115-1-60 955 - 1240 9MD12-C11
1/2 115 / 208- 230-1-60 955 - 1240 9MD12-C12
1/2 277-1-60 955 - 1240 9MD12-C13
1/2 208 - 230 / 460-3-60 955 - 1240 9MD12-C14
1/2 575-3-60 955 - 1240 9MD12-C15
1/2 115-1-60 1165 - 1520 9MD12-C16
1/2 115 / 208- 230-1-60 1165 - 1520 9MD12-C17
1/2 277-1-60 1165 - 1520 9MD12-C18
1/2 208 - 230 / 460-3-60 1165 - 1520 9MD12-C19
1/2 575-3-60 1165 - 1520 9MD12-C20
-29-
12AWH/12AXH
CFM
Componet Static Pressure (Inches of Water)
CABINET
Chilled Water CoilHot
Water Coil
DX Coil Filter Sections
Mixing BoxDry Coil Wet Coil Dry Coil
Dry Coil
Wet Coil
2” Flat
4” Flat
2” Angled
4” Angled
4 Row
6 Row
4 Row
6 Row
*1-2 Row
4 rowMerv
7Merv
7Merv 7 Merv 7
1000 0.15 0.15 0.24 0.21 0.34 0.11 0.17 0.24 0.009 0.06 0.05
NA
0.24
1100 0.18 0.17 0.26 0.24 0.37 0.13 0.20 0.29 0.12 0.08 0.06 0.28
1200 0.22 0.20 0.29 0.29 0.41 0.15 0.23 0.33 0.15 0.10 0.08 0.33
1300 0.25 0.23 0.31 0.33 0.44 0.17 0.27 0.39 0.18 0.12 0.10 0.38
1400 0.29 0.26 0.35 0.37 0.50 0.19 0.31 0.44 0.21 0.15 0.12 0.43
3 Ton (12) Horizontal Belt Drive Information
HP VoltageBlower RPM
Motor / Drive Kit Number
3/4 115 / 208- 230-1-60 825 - 1065 9MD12-D2
3/4 277-1-60 825 - 1065 9MD12-D3
3/4 208 - 230 / 460-3-60 825 - 1065 9MD12-D4
3/4 575-3-60 825 - 1065 9MD12-D5
3/4 115 / 208- 230-1-60 955 - 1240 9MD12-D7
3/4 277-1-60 955 - 1240 9MD12-D8
3/4 208 - 230 / 460-3-60 955 - 1240 9MD12-D9
3/4 575-3-60 955 - 1240 9MD12-D10
3/4 115 / 208- 230-1-60 1165 - 1520 9MD12-D12
3/4 277-1-60 1165 - 1520 9MD12-D13
3/4 208 - 230 / 460-3-60 1165 - 1520 9MD12-D14
3/4 575-3-60 1165 - 1520 9MD12-D15
3/4 115 / 208- 230-1-60 1235 - 1610 9MD12-D17
3/4 277-1-60 1235 - 1610 9MD12-D18
3/4 208 - 230 / 460-3-60 1235 - 1610 9MD12-D19
3/4 575-3-60 1235 - 1610 9MD12-D20
1 115 / 208- 230-1-60 1075 - 1400 9MD12-E2
1 277-1-60 1075 - 1400 9MD12-E3
1 208 - 230 / 460-3-60 1075 - 1400 9MD12-E4
1 575-3-60 1075 - 1400 9MD12-E5
1 115 / 208- 230-1-60 1310 - 1710 9MD12-E7
1 277-1-60 1310 - 1710 9MD12-E8
1 208 - 230 / 460-3-60 1310 - 1710 9MD12-E9
1 575-3-60 1310 - 1710 9MD12-E10
1-1/2 115 / 208- 230-1-60 1310 - 1710 9MD12-F2
1-1/2 277-1-60 1310 - 1710 9MD12-F3
1-1/2 208 - 230 / 460-3-60 1310 - 1710 9MD12-F4
1-1/2 575-3-60 1310 - 1710 9MD12-F5
CFM
Stat
ic P
ress
. (In
.wg)
Size 12 Blower Curve
0 200 400 600 800 1000 1200 1400 1600 18000
0.3
0.6
0.9
1.2
1.5
1.8
2.1
2.4
2.7
3
800 rpm
1000 rpm
1200 rpm
1400 rpm
1600 rpm
1800 rpm
0.33 HP
0.50 HP
0.75 HP
1.0 HP
1.5 HP
3 TON FAN PERFORMANCE ( AWH / AWX )
Model CFM
TOTAL STATIC PRESSURE - INCHES OF WATER
0.6 0.7 0.8 0.9 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
12
1000 1028 0.4 1077 0.4 1125 0.4 1171 0.5 1215 0.50 1301 0.6 1383 0.6 1461 0.7 1536 0.7 --- ---
1100 1068 0.5 1114 0.5 1159 0.5 1203 0.5 1246 0.6 1329 0.6 1408 0.7 1483 0.7 1556 0.8 --- ---
1200 1111 0.5 1155 0.5 1198 0.6 1239 0.6 1280 0.6 1360 0.7 1436 0.8 1509 0.8 1579 0.9 --- ---
1300 1157 0.6 1198 0.6 1239 0.7 1279 0.7 1318 0.7 1394 0.8 1467 0.9 1537 0.9 1606 1 --- ---
1400 1205 0.7 1244 0.7 1283 0.8 1321 0.8 1358 0.8 1431 0.9 1501 1.0 1569 1.0 1635 1.1 --- ---
®
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
BLOWER CURVEProduct SpecificationsHorizontal
Chilled Water / Hot Water / DX
4 Ton (16) Horizontal Belt Drive Information
HP VoltageBlower RPM
Motor / Drive Kit Number
1/3 115-1-60 695 - 890 9MD16-B1
1/3 115 / 208 - 230-1-60 695 - 890 9MD16-B2
1/3 277-1-60 695 - 890 9MD16-B3
1/3 208 - 230 / 460-3-60 695 - 890 9MD16-B4
1/3 575-3-60 695 - 890 9MD16-B5
1/2 115-1-60 695 - 890 9MD16-C1
1/2 115 / 208 - 230-1-60 695 - 890 9MD16-C2
1/2 277-1-60 695 - 890 9MD16-C3
1/2 208 - 230 / 460-3-60 695 - 890 9MD16-C4
1/2 575-3-60 695 - 890 9MD16-C5
1/2 115-1-60 825 - 1065 9MD16-C6
1/2 115 / 208 - 230-1-60 825 - 1065 9MD16-C7
1/2 277-1-60 825 - 1065 9MD16-C8
1/2 208 - 230 / 460-3-60 825 - 1065 9MD16-C9
1/2 575-3-60 825 - 1065 9MD16-C10
1/2 115-1-60 955 - 1240 9MD16-C11
1/2 115 / 208 - 230-1-60 955 - 1240 9MD16-C12
1/2 277-1-60 955 - 1240 9MD16-C13
1/2 208 - 230 / 460-3-60 955 - 1240 9MD16-C14
1/2 575-3-60 955 - 1240 9MD16-C15
3/4 115 / 208- 230-1-60 695 - 890 9MD16-D2
3/4 277-1-60 695 - 890 9MD16-D3
3/4 208 - 230 / 460-3-60 695 - 890 9MD16-D4
3/4 575-3-60 695 - 890 9MD16-D5
3/4 115 / 208- 230-1-60 825 - 1065 9MD16-D7
3/4 277-1-60 825 - 1065 9MD16-D8
3/4 208 - 230 / 460-3-60 825 - 1065 9MD16-D9
3/4 575-3-60 825 - 1065 9MD16-D10
-30-
16AWH/16AXH
CFM
Componet Static Pressure (Inches of Water)
CABINET
Chilled Water CoilHot
Water Coil
DX Coil Filter Sections
Mixing BoxDry Coil Wet Coil Dry Coil
Dry Coil
Wet Coil
2” Flat
4” Flat
2” Angled
4” Angled
4 Row
6 Row
4 Row
6 Row
*1-2 Row
4 rowMerv
7Merv
7Merv 7 Merv 7
1200 0.12 0.17 0.22 0.24 0.31 0.10 0.21 0.30 0.10 0.08 0.04 0.08 .12
1400 0.16 0.21 0.26 0.30 0.37 0.13 0.25 0.36 0.14 0.10 0.06 0.10 .16
1600 0.20 0.25 0.31 0.36 0.44 0.16 0.29 0.41 0.18 0.13 0.08 0.12 .21
1800 0.24 0.29 0.36 0.41 0.51 0.19 0.33 0.47 0.22 0.17 0.10 0.15 .27
2000 0.28 0.33 0.41 0.47 0.59 0.22 0.38 0.54 0.27 0.21 0.12 0.19 .33
4 Ton (16) Horizontal Belt Drive Information
HP VoltageBlower RPM
Motor / Drive Kit Number
3/4 115 / 208- 230-1-60 955 - 1240 9MD16-D12
3/4 277-1-60 955 - 1240 9MD16-D13
3/4 208 - 230 / 460-3-60 955 - 1240 9MD16-D14
3/4 575-3-60 955 - 1240 9MD16-D15
3/4 115 / 208- 230-1-60 1075 - 1400 9MD16-D17
3/4 277-1-60 1075 - 1400 9MD16-D18
3/4 208 - 230 / 460-3-60 1075 - 1400 9MD16-D19
3/4 575-3-60 1075 - 1400 9MD16-D20
1 115 / 208- 230-1-60 825 - 1065 9MD16-E2
1 277-1-60 825 - 1065 9MD16-E3
1 208 - 230 / 460-3-60 825 - 1065 9MD16-E4
1 575-3-60 825 - 1065 9MD16-E5
1 115 / 208- 230-1-60 955 - 1240 9MD16-E7
1 277-1-60 955 - 1240 9MD16-E8
1 208 - 230 / 460-3-60 955 - 1240 9MD16-E9
1 575-3-60 955 - 1240 9MD16-E10
1 115 / 208- 230-1-60 1075 - 1400 9MD16-E12
1 277-1-60 1075 - 1400 9MD16-E13
1 208 - 230 / 460-3-60 1075 - 1400 9MD16-E14
1 575-3-60 1075 - 1400 9MD16-E15
1 115 / 208- 230-1-60 1235 - 1610 9MD16-E17
1 277-1-60 1235 - 1610 9MD16-E18
1 208 - 230 / 460-3-60 1235 - 1610 9MD16-E19
1 575-3-60 1235 - 1610 9MD16-E20
1-1/2 115 / 208- 230-1-60 1235 - 1610 9MD16-F2
1-1/2 277-1-60 1235 - 1610 9MD16-F3
1-1/2 208 - 230 / 460-3-60 1235 - 1610 9MD16-F4
1-1/2 575-3-60 1340 - 1620 9MD16-F5
CFM
Stat
ic P
ress
. (in
.wg)
Size 16 Blower Curve
0 200 400 600 800 1000 1200 1400 1600 1800 2000 22000
0.25
0.5
0.75
1
1.25
1.5
1.75
2
2.25
2.5
2.75
3
3.25
3.5
800 rpm
1000 rpm
1200 rpm
1400 rpm
1600 rpm
1800 rpm
0.33 HP
0.50 HP
0.75 HP
1.0 HP
1.5 HP
4 TON FAN PERFORMANCE ( AWH / AWX )
Model CFM
TOTAL STATIC PRESSURE - INCHES OF WATER
0.6 0.7 0.8 0.9 1.0 1.2 1.4 1.6 1.8 2.0 2.25 2.5 2.75 3.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
16
1400 907 0.5 949 0.5 990 0.5 1030 0.6 1069 0.6 1144 0.7 1216 0.7 1285 0.8 1352 0.9 1416 0.9 1493 1.0 1568 1.1 --- --- --- ---
1500 933 0.5 974 0.6 1013 0.6 1051 0.6 1089 0.7 1161 0.7 1231 0.8 1298 0.9 1363 1.0 1426 1.0 1501 1.1 1575 1.2 --- --- --- ---
1600 961 0.6 1000 0.6 1037 0.7 1074 0.7 1110 0.7 1180 0.8 1248 0.9 1313 1.0 1376 1.0 1437 1.1 1512 1.2 1583 1.3 --- --- --- ---
1700 990 0.7 1027 0.7 1063 0.8 1099 0.8 1134 0.8 1201 0.9 1267 1.0 1330 1.0 1391 1.1 1451 1.2 1524 1.3 1593 1.4 --- --- --- ---
1800 1020 0.8 1055 0.8 1090 0.8 1125 0.9 1158 0.9 1224 1.0 1287 1.1 1349 1.1 1408 1.2 1466 1.3 1538 1.4 1607 1.5 --- --- --- ---
®
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
BLOWER CURVEProduct SpecificationsHorizontal
Chilled Water / Hot Water / DX
5 Ton (20) Horizontal Belt Drive Information
HP VoltageBlower RPM
Motor / Drive Kit Number
1/2 115-1-60 540 - 685 9MD20-C1
1/2 115 / 208 - 230-1-60 540 - 685 9MD20-C2
1/2 277-1-60 540 - 685 9MD20-C3
1/2 208 - 230 / 460-3-60 540 - 685 9MD20-C4
1/2 575-3-60 540 - 685 9MD20-C5
1/2 115-1-60 695 - 890 9MD20-C6
1/2 115 / 208 - 230-1-60 695 - 890 9MD20-C7
1/2 277-1-60 695 - 890 9MD20-C8
1/2 208 - 230 / 460-3-60 695 - 890 9MD20-C9
1/2 575-3-60 695 - 890 9MD20-C10
3/4 115 / 208- 230-1-60 540 - 685 9MD20-D2
3/4 277-1-60 540 - 685 9MD20-D3
3/4 208 - 230 / 460-3-60 540 - 685 9MD20-D4
3/4 575-3-60 540 - 685 9MD20-D5
3/4 115 / 208- 230-1-60 695 - 890 9MD20-D7
3/4 277-1-60 695 - 890 9MD20-D8
3/4 208 - 230 / 460-3-60 695 - 890 9MD20-D9
3/4 575-3-60 695 - 890 9MD20-D10
3/4 115 / 208- 230-1-60 825 - 1065 9MD20-D12
3/4 277-1-60 825 - 1065 9MD20-D13
3/4 208 - 230 / 460-3-60 825 - 1065 9MD20-D14
3/4 575-3-60 825 - 1065 9MD20-D15
1 115 / 208- 230-1-60 695 - 890 9MD20-E2
1 277-1-60 695 - 890 9MD20-E3
1 208 - 230 / 460-3-60 695 - 890 9MD20-E4
1 575-3-60 695 - 890 9MD20-E5
1 115 / 208- 230-1-60 825 - 1065 9MD20-E7
1 277-1-60 825 - 1065 9MD20-E8
1 208 - 230 / 460-3-60 825 - 1065 9MD20-E9
1 575-3-60 825 - 1065 9MD20-E10
-31-
20AWH/20AXH
CFM
Componet Static Pressure (Inches of Water)
CABINET
Chilled Water CoilHot
Water Coil
DX Coil Filter Sections
Mixing BoxDry Coil Wet Coil Dry Coil
Dry Coil
Wet Coil
2” Flat
4” Flat
2” Angled
4” Angled
4 Row
6 Row
4 Row
6 Row
*1-2 Row
4 rowMerv
7Merv
7Merv 7 Merv 7
1600 0.13 0.15 0.22 0.21 0.31 0.11 0.18 0.26 0.15 0.11 0.08 0.10 0.14
1800 0.17 0.18 0.27 0.26 0.39 0.14 0.20 0.29 0.18 0.13 0.10 0.12 0.21
2000 0.21 0.20 0.32 0.29 0.46 0.17 0.23 0.33 0.22 0.15 0.12 0.15 0.26
2200 0.25 0.23 0.37 0.33 0.53 0.21 0.27 0.39 0.26 0.19 0.14 0.18 0.31
2400 0.29 0.27 0.42 0.39 0.60 0.25 0.31 0.44 0.30 0.23 0.16 0.22 0.36
5 Ton (20) Horizontal Belt Drive Information
HP VoltageBlower RPM
Motor / Drive Kit Number
1 115 / 208- 230-1-60 955 - 1240 9MD20-E12
1 277-1-60 955 - 1240 9MD20-E13
1 208 - 230 / 460-3-60 955 - 1240 9MD20-E14
1 575-3-60 955 - 1240 9MD20-E15
1-1/2 115 / 208- 230-1-60 825 - 1065 9MD20-F2
1-1/2 277-1-60 825 - 1065 9MD20-F3
1-1/2 208 - 230 / 460-3-60 825 - 1065 9MD20-F4
1-1/2 575-3-60 850 - 1010 9MD20-F5
1-1/2 115 / 208- 230-1-60 955 - 1240 9MD20-F7
1-1/2 277-1-60 955 - 1240 9MD20-F8
1-1/2 208 - 230 / 460-3-60 955 - 1240 9MD20-F9
1-1/2 575-3-60 955 - 1140 9MD20-F10
1-1/2 115 / 208- 230-1-60 1075 - 1400 9MD20-F12
1-1/2 277-1-60 1075 - 1400 9MD20-F13
1-1/2 208 - 230 / 460-3-60 1075 - 1400 9MD20-F14
1-1/2 575-3-60 1090 - 1310 9MD20-F15
2 115 / 208- 230-1-60 1025 - 1330 9MD20-G2
2 277-1-60 1025 - 1330
2 208 - 230 / 460-3-60 1025 - 1330 9MD20-G4
2 575-3-60 1060 - 1270 9MD20-G5
2 115 / 208- 230-1-60 1235 - 1610 9MD20-G7
2 277-1-60 1235 - 1610
2 208 - 230 / 460-3-60 1235 - 1610 9MD20-G9
2 575-3-60 1340 - 1620 9MD20-G10
CFM
Stat
ic P
ress
. (in
.wg)
Size 20 Blower Curve
0 400 800 1200 1600 2000 24000
0.25
0.5
0.75
1
1.25
1.5
1.75
2
2.25
2.5
2.75
3
3.25
3.5
800 rpm
1000 rpm
1200 rpm
1400 rpm
1600 rpm
0.50 HP
0.75 HP
1.0 HP
1.5 HP
2.0 HP
5 TON FAN PERFORMANCE ( AWH / AWX )
Model CFM
TOTAL STATIC PRESSURE - INCHES OF WATER
0.6 0.7 0.8 0.9 1.0 1.2 1.4 1.6 1.8 2.0 2.25 2.5 2.75 3.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
20
1800 809 0.6 847 0.7 883 0.7 919 0.8 954 0.8 1020 0.9 1085 1..0 1147 1.1 1207 1.2 1266 1.3 1337 1.4 1406 1.5 1473 1.7 --- ---
1900 827 0.7 864 0.7 899 0.8 933 0.8 967 0.9 1032 1.0 1095 1.0 1155 1.1 1214 1.2 1271 1.3 1341 1.5 1409 1.6 1475 1.8 1538 1.9
2000 846 0.8 881 .08 915 0.8 949 0.9 962 0.9 1045 1.0 1106 1.1 1165 1.2 1222 1.3 1278 1.4 1347 1.5 1413 1.7 1477 1.8 1540 2.0
2100 865 0.8 899 0.9 933 .09 965 1.0 997 1.0 1059 1.1 1119 1.2 1176 1.3 1232 1.4 1286 1.5 1354 1.6 1419 1.8 1481 1.9 1543 2.1
2200 885 0.9 918 1.0 951 1.0 983 1.0 1014 1.1 1074 1.2 1132 1.3 1188 1.4 1243 1.5 1296 1.6 1362 1.7 1426 1.9 1487 2.0 1547 2.2
®
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
BLOWER CURVEProduct SpecificationsHorizontal
Chilled Water / Hot Water / DX
7-1/2 Ton (30) Horizontal Belt Drive Information
HP Voltage Phase Blower RPMMotor / Drive Kit
Number
3/4 115 / 208 - 230 1 615 - 720 9MD30-D2
3/4 277 1 615 - 720 9MD30-D3
3/4 208 - 230 / 460 3 615 - 720 9MD30-D4
3/4 575 3 615 - 720 9MD30-D5
1 115 / 208- 230 1 615 - 720 9MD30-E2
1 277 1 615 - 720 9MD30-E3
1 208 - 230 / 460 3 615 - 720 9MD30-E4
1 575 3 615 - 720 9MD30-E5
1 115 / 208 - 230 1 665 - 785 9MD30-E7
1 277 1 665 - 785 9MD30-E8
1 208 - 230 / 460 3 665 - 785 9MD30-E9
1 575 3 665 - 785 9MD30-E10
1 115 / 208 - 230 1 730 - 865 9MD30-E12
1 277 1 730 - 865 9MD30-E13
1 208 - 230 / 460 3 730 - 865 9MD30-E14
1 575 3 730 - 865 9MD30-E15
1-1/2 115 / 208 - 230 1 730 - 865 9MD30-F2
1-1/2 277 1 730 - 865 9MD30-F3
1-1/2 208- 230 / 460 3 730 - 865 9MD30-F4
1-1/2 575 3 730 - 865 9MD30-F5
1-1/2 115 / 208 - 230 1 805 - 955 9MD30-F7
1-1/2 277 1 805 - 955 9MD30-F8
1-1/2 208- 230 / 460 3 805 - 955 9MD30-F9
1-1/2 575 3 805 - 955 9MD30-F10
-32-
30AWH/30AXH
CFM
Componet Static Pressure (Inches of Water)
CABINET
Chilled Water CoilHot
Water Coil
DX Coil Filter Sections
Mixing BoxDry Coil Wet Coil Dry Coil
Dry Coil
Wet Coil
2” Flat
4” Flat
2” Angled
4” Angled
4 Row
6 Row
4 Row
6 Row
*1-2 Row
4 rowMerv
7Merv
7Merv 7 Merv 7
2600 0.17 0.11 0.15 0.12 0.16 0.05 0.17 0.18 0.19 0.14 0.11 0.10 0.22
2800 0.18 0.12 0.17 0.13 0.18 0.06 0.21 0.23 0.20 0.15 0.12 0.11 0.25
3000 0.19 0.13 0.19 0.14 0.20 0.07 0.27 0.29 0.21 0.16 0.13 0.12 0.28
3200 0.20 0.14 0.22 0.15 0.24 0.08 0.28 0.30 0.23 0.17 0.14 0.13 0.32
3400 0.21 0.15 0.24 0.16 0.26 0.09 0.29 0.31 0.24 0.18 0.14 0.14 0.36
7-1/2 Ton (30) Horizontal Belt Drive Information
HP Voltage Phase Blower RPMMotor / Drive Kit
Number
1-1/2 115 / 208 - 230 1 850 - 1010 9MD30-F12
1-1/2 277 1 850 - 1010 9MD30-F13
1-1/2 208- 230 / 460 3 850 - 1010 9MD30-F14
1-1/2 575 3 850 - 1010 9MD30-F15
2 115 / 208 - 230 1 850 - 1010 9MD30-G2
2 277 1 850 - 1010
2 208- 230 / 460 3 850 - 1010 9MD30-G4
2 575 3 850 - 1010 9MD30-G5
2 115 / 208 - 230 1 955 - 1140 9MD30-G7
2 277 1 955 - 1140
2 208- 230 / 460 3 955 - 1140 9MD30-G9
2 575 3 955 - 1140 9MD30-G10
3 115 / 208 - 230 1 955 - 1140 9MD30-H2
3 277 1
3 208- 230 / 460 3 955 - 1140 9MD30-H4
3 575 3 955 - 1140 9MD30-H5
3 115 / 208 - 230 1 1060 - 1270 9MD30-H7
3 277 1
3 208- 230 / 460 3 1060 - 1270 9MD30-H9
3 575 3 1060 - 1270 9MD30-H10
CFM
Stat
ic P
ress
. (in
.wg)
Size 30 Blower Curve
1000 1500 2000 2500 3000 3500 40000.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
600 rpm
800 rpm
1000 rpm
1200 rpm
0.75 HP
1.0 HP
1.5 HP
2.0 HP
3.0 HP
7-1/2 TON FAN PERFORMANCE (A WH / AWX )
Model CFM
TOTAL STATIC PRESSURE - INCHES OF WATER
0.7 0.8 0.9 1.0 1.2 1.4 1.6 1.8 2.0 2.25 2.5 2.75 3.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
30
2500 637 0.7 668 0.7 699 0.8 729 0.8 786 0.9 841 1.1 894 1.2 945 1.3 --- --- --- --- --- --- --- --- --- ---
2750 654 0.8 684 0.8 713 0.9 741 1.0 796 1.1 849 1.2 899 1.3 948 1.4 996 1.6 1057 1.7 --- --- --- --- --- ---
3000 672 0.9 701 1.0 729 1.0 756 1.1 809 1.2 859 1.3 908 1.5 955 1.6 1001 1.7 1060 1.9 1114 2.1 --- --- --- ---
3250 693 1.1 720 1.1 747 1.2 773 1.2 823 1.4 872 1.5 919 1.8 964 1.8 1008 1.9 1066 2.1 1119 2.3 1169 2.5 1219 2.7
3500 715 1.2 741 1.3 767 1.3 792 1.4 840 1.5 887 1.7 932 1.8 976 2.0 1018 2.1 1075 2.3 1126 2.5 1175 2.7 1223 2.9
®
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
BLOWER CURVEProduct SpecificationsHorizontal
Chilled Water / Hot Water / DX
10 Ton (40) Horizontal Belt Drive Information
HP Voltage Phase Blower RPMMotor / Drive Kit
Number
1-1/2 115 / 208 - 230 1 695 - 825 9MD40-F2
1-1/2 277 1 695 - 825 9MD40-F3
1-1/2 208- 230 / 460 3 695 - 825 9MD40-F4
1-1/2 575 3 695 - 825 9MD40-F5
1-1/2 115 / 208 - 230 1 765 - 910 9MD40-F7
1-1/2 277 1 765 - 910 9MD40-F8
1-1/2 208- 230 / 460 3 765 - 910 9MD40-F9
1-1/2 575 3 765 - 910 9MD40-F10
2 115 / 208 - 230 1 695 - 825 9MD40-G2
2 277 1 695 - 825
2 208- 230 / 460 3 695 - 825 9MD40-G4
2 575 3 695 - 825 9MD40-G5
2 115 / 208 - 230 1 765 - 910 9MD40-G7
2 277 1 765 - 910
2 208- 230 / 460 3 765 - 910 9MD40-G9
2 575 3 765 - 910 9MD40-G10
2 115 / 208 - 230 1 850 - 1010 9MD40-G12
2 277 1
2 208- 230 / 460 3 850 - 1010 9MD40-G14
2 575 3 850 - 1010 9MD40-G15
-33-
40AWH/40AXH
CFM
Componet Static Pressure (Inches of Water)
CABINET
Chilled Water CoilHot
Water Coil
DX Coil Filter Sections
Mixing BoxDry Coil Wet Coil Dry Coil
Dry Coil
Wet Coil
2” Flat
4” Flat
2” Angled
4” Angled
4 Row
6 Row
4 Row
6 Row
*1-2 Row
4 rowMerv
7Merv
7Merv 7 Merv 7
3600 0.14 0.12 0.18 0.13 0.19 0.05 0.23 0.25 0.20 0.13 0.13 0.13 0.20
3800 0.16 0.14 0.21 0.15 0.22 0.06 0.26 0.28 0.21 0.14 0.14 0.14 0.22
4000 0.18 0.16 0.24 0.17 0.26 0.08 0.27 0.29 0.22 0.15 0.14 0.14 0.24
4200 0.20 0.18 0.27 0.19 0.29 0.10 0.29 0.31 0.23 0.15 0.15 0.15 0.27
4400 0.22 0.20 0.31 0.21 0.33 0.12 0.32 0.34 0.24 0.16 0.16 0.15 0.30
10 Ton (40) Horizontal Belt Drive Information
HP Voltage Phase Blower RPMMotor / Drive Kit
Number
3 115 / 208 - 230 1 765 - 910 9MD40-H2
3 277 1
3 208- 230 / 460 3 765 - 910 9MD40-H4
3 575 3 765 - 910 9MD40-H5
3 115 / 208 - 230 1 850 - 1010 9MD40-H7
3 277 1
3 208- 230 / 460 3 850 - 1010 9MD40-H9
3 575 3 850 - 1010 9MD40-H10
3 115 / 208 - 230 1 955 - 1140 9MD40-H12
3 277 1
3 208- 230 / 460 3 955 - 1140 9MD40-H14
3 575 3 955 - 1140 9MD40-H15
5 208- 230 / 460 3 900 - 1075 9MD40-J4
5 575 3 900 - 1075 9MD40-J5
5 208- 230 / 460 3 1015 - 1220 9MD40-J9
5 575 3 1015 - 1220 9MD40-J10
CFM
Stat
ic P
ress
. (in
.wg)
Size 40 Blower Curve
2000 2500 3000 3500 4000 4500 50000.5
1.0
1.5
2.0
2.5
3.0
3.5
600 rpm
800 rpm
1000 rpm
1200 rpm
1.0 HP
1.5 HP
2.0 HP
3.0 HP
10 TON FAN PERFORMANCE ( AWH / AWX )
Model CFM
TOTAL STATIC PRESSURE - INCHES OF WATER
0.7 0.8 0.9 1.0 1.2 1.4 1.6 1.8 2.0 2.25 2.5 2.75 3.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
40
3400 639 0.9 671 1.0 701 1.1 731 1.1 791 1.3 848 1.5 905 1.6 961 1.7 --- --- --- --- --- --- --- --- --- ---
3700 655 1.1 685 1.2 714 1.2 742 1.3 798 1.4 852 1.6 906 1.8 958 1.9 1010 2.1 --- --- --- --- --- --- --- ---
4000 673 1.2 701 1.3 728 1.4 755 1.5 808 1.6 860 1.8 910 2.2 960 2.1 1009 2.3 1072 2.5 1132 2.7 --- --- --- ---
4300 693 1.4 719 1.5 745 1.6 771 1.7 821 1.8 870 2.0 918 2.2 965 2.4 1011 2.5 1073 2.7 1132 3.0 1184 3.2 --- ---
4600 713 1.6 739 1.7 764 1.8 788 1.9 836 2.1 883 2.2 929 2.4 973 2.6 1018 2.8 1076 3.0 1132 3.2 1184 3.2 1236 3.8
®
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
BLOWER CURVEProduct SpecificationsHorizontal
Chilled Water / Hot Water / DX
CFM ( X 1000 )
Stat
ic P
ress
. ( i
n.w
g )
60WH Blower Curve
4 4.5 5 5.5 6 6.5 7 7.5 80.5
0.75
1
1.25
1.5
1.75
2
2.25
2.5
2.75
3
3.25
3.5
3.75
4
4.25
600 rpm
800 rpm
1000 rpm
1200 rpm
3 HP
5 HP
7-1/2 HP
-34-
15 Ton (60) Horizontal Belt Drive Information
HP Voltage Phase Hz Blower RPMMotor / Drive Kit
Number
3 115 / 208 - 230 1 60 615 - 720 9MD60-H2
3 277 1 60
3 208- 230 / 460 3 60 615 - 720 9MD60-H4
3 575 3 60 615 - 720 9MD60-H5
3 115 / 208 - 230 1 60 665 -785 9MD60-H7
3 277 1 60
3 208- 230 / 460 3 60 665 -785 9MD60-H9
3 575 3 60 665 -785 9MD60-H10
3 115 / 208 - 230 1 60 730 - 865 9MD60-H12
3 277 1 60
3 208- 230 / 460 3 60 730 - 865 9MD60-H14
3 575 3 60 730 - 865 9MD60-H15
5 208- 230 / 460 3 60 730 - 865 9MD60-J4
5 575 3 60 730 - 865 9MD60-J5
5 208- 230 / 460 3 60 805 - 955 9MD60-J9
5 575 3 60 805 - 955 9MD60-J10
5 208- 230 / 460 3 60 900 - 1075 9MD60-J14
5 575 3 60 900 - 1075 9MD60-J15
7-1/2 208- 230 / 460 3 60 915 - 1065 9MD60-K4
7-1/2 575 3 60 915 - 1065 9MD60-K5
7-1/2 208- 230 / 460 3 60 1020 - 1195 9MD60-K9
7-1/2 575 3 60 1020 - 1195 9MD60-K10
60AWH/60AXH
CFM
Componet Static Pressure (Inches of Water)
CABINET
Chilled Water CoilHot
Water Coil
DX Coil Filter Sections
Mixing BoxDry Coil Wet Coil Dry Coil
Dry Coil
Wet Coil
2” Flat
4” Flat
2” Angled
4” Angled
4 Row
6 Row
4 Row
6 Row
*1-2 Row
4 rowMerv
7Merv
7Merv 7 Merv 7
5600 0.01 0.14 0.20 0.15 0.21 0.06 0.18 0.19 0.16 0.16 0.16 0.15 0.23
5800 0.05 0.17 0.23 0.18 0.25 0.09 0.21 0.23 0.18 0.18 0.17 0.16 0.25
6000 0.12 0.19 0.26 0.21 0.28 0.11 0.24 0.26 0.21 0.19 0.18 0.17 0.27
6200 0.19 0.22 0.29 0.23 0.31 0.13 0.27 0.29 0.23 0.20 0.19 0.18 0.28
6400 0.25 0.24 0.32 0.26 0.35 0.15 0.30 0.32 0.26 0.23 0.20 0.19 0.30
15 TON FAN PERFORMANCE ( AWH / AWX )
Model CFM
TOTAL STATIC PRESSURE - INCHES OF WATER
0.7 0.8 0.9 1.0 1.2 1.4 1.6 1.8 2.0 2.25 2.5 2.75 3.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
60
5200 488 1.3 515 1.4 542 1.5 568 1.6 621 1.8 672 2.0 727 2.3 784 2.7 837 3.1 901 3.5 1009 4.0 1012 4.5 1060 4.9
5600 494 1.5 520 1.6 545 1.7 571 1.8 620 2.0 669 2.2 716 2.5 766 2.8 819 3.2 885 3.6 945 4.1 1000 4.6 1052 5.1
6000 502 1.7 527 1.8 551 1.9 575 2.0 622 2.2 668 2.4 713 2.7 758 3.0 802 3.3 867 3.7 928 4.2 985 4.7 1039 5.3
6400 511 1.9 535 2.0 558 2.1 581 2.2 626 2.4 670 2.7 712 2.9 755 3.2 797 3.5 853 3.8 910 4.3 968 4.8 1023 5.4
6800 521 2.1 543 2.2 566 2.4 588 2.5 631 2.7 673 3.0 714 3.2 755 3.5 794 3.8 849 4.1 898 4.5 950 4.9 1005 5.5
®
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
BLOWER CURVEProduct SpecificationsHorizontal
Chilled Water / Hot Water / DX
CFM ( X 1000 )
Stat
ic P
ress
. ( i
n.w
g )
Size 80 Blower Curve
4 5 6 7 8 9 10 11 120.5
0.75
1
1.25
1.5
1.75
2
2.25
2.5
2.75
3
3.25
3.5
3.75
4
4.25
4.5
4.75
5
600 rpm
800 rpm
1000 rpm
1200 rpm
3 HP 5 HP
7-1/2 HP
10 HP
-35-
20 Ton (80) Horizontal Belt Drive Information
HP Voltage Phase Hz Blower RPMMotor / Drive Kit
Number
3 115 / 208 - 230 1 60 615 - 720 9MD80-H2
3 277 1 60
3 208- 230 / 460 3 60 615 - 720 9MD80-H4
3 575 3 60 615 - 720 9MD80-H5
3 115 / 208 - 230 1 60 665 -785 9MD80-H7
3 277 1 60
3 208- 230 / 460 3 60 665 -785 9MD80-H9
3 575 3 60 665 -785 9MD80-H10
3 115 / 208 - 230 1 60 730 - 865 9MD80-H12
3 277 1 60
3 208- 230 / 460 3 60 730 - 865 9MD80-H14
3 575 3 60 730 - 865 9MD80-H15
5 208- 230 / 460 3 60 615 - 720 9MD80-J4
5 575 3 60 615 - 720 9MD80-J5
5 208- 230 / 460 3 60 665 -785 9MD80-J9
5 575 3 60 665 -785 9MD80-J10
5 208- 230 / 460 3 60 730 - 865 9MD80-J14
5 575 3 60 730 - 865 9MD80-J15
5 208- 230 / 460 3 60 805 - 955 9MD80-J19
5 575 3 60 805 - 955 9MD80-J20
7-1/2 208- 230 / 460 3 60 645 - 745 9MD80-K4
7-1/2 575 3 60 645 - 745 9MD80-K5
7-1/2 208- 230 / 460 3 60 700 - 805 9MD80-K9
7-1/2 575 3 60 700 - 805 9MD80-K10
7-1/2 208- 230 / 460 3 60 755 - 875 9MD80-K14
7-1/2 575 3 60 755 - 875 9MD80-K15
7-1/2 208- 230 / 460 3 60 825 - 965 9MD80-K19
7-1/2 575 3 60 825 - 965 9MD80-K20
7-1/2 208- 230 / 460 3 60 915 - 1065 9MD80-K24
7-1/2 575 3 60 915 - 1065 9MD80-K25
7-1/2 208- 230 / 460 3 60 1020 - 1195 9MD80-K29
7-1/2 575 3 60 1020 - 1195 9MD80-K30
10 208- 230 / 460 3 60 915 - 1065 9MD80-L4
10 575 3 60 915 - 1065 9MD80-L5
10 208- 230 / 460 3 60 1020 - 1195 9MD80-L9
10 575 3 60 1020 - 1195 9MD80-L10
10 208- 230 / 460 3 60 1155 - 1360 9MD80-L14
10 575 3 60 1155 - 1360 9MD80-L15
80AWH/80AXH
CFM
Componet Static Pressure (Inches of Water)
CABINET
Chilled Water CoilHot
Water Coil
DX Coil Filter Sections
Mixing BoxDry Coil Wet Coil Dry Coil
Dry Coil
Wet Coil
2” Flat
4” Flat
2” Angled
4” Angled
4 Row
6 Row
4 Row
6 Row
*1-2 Row
4 rowMerv
7Merv
7Merv 7 Merv 7
6000 0.09 0.17 0.16 0.49 0.18 0.08 0.22 0.23 0.13 0.10 0.11 0.10 0.42
7000 0.15 0.19 0.21 0.21 0.22 0.11 0.24 0.26 0.17 0.13 0.14 0.13 0.44
8000 0.32 0.23 0.27 0.25 0.29 0.15 0.30 0.32 0.22 0.17 0.18 0.17 0.47
9000 0.42 0.30 0.37 0.32 0.39 0.20 0.38 0.41 0.27 0.22 0.24 0.21 0.49
10000 0.48 0.39 0.47 0.41 0.51 0.23 0.49 0.52 0.33 0.26 0.33 0.26 0.51
20 TON FAN PERFORMANCE ( AWH / AWX )
Model CFM
TOTAL STATIC PRESSURE - INCHES OF WATER
0.7 0.8 0.9 1.0 1.2 1.4 1.6 1.8 2.0 2.25 2.5 2.75 3.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
80
6000 502 1.7 527 1.8 551 1.9 575 2.0 622 2.2 668 2.4 713 2.7 758 3.0 802 3.3 867 3.7 928 4.2 985 4.7 1039 5.3
7000 525 2.2 548 2.4 570 2.5 592 2.6 634 2.9 675 3.1 715 3.4 755 3.6 794 4.0 484 4.2 896 4.6 943 5.1 996 5.6
8000 550 2.9 572 3.1 594 3.3 615 3.4 653 3.7 691 4.0 727 4.2 764 4.5 799 4.8 849 5.1 892 5.5 935 5.9 977 6.4
9000 578 3.8 599 4.0 619 4.1 639 4.3 578 4.7 713 5.0 746 5.3 780 5.6 812 6.0 860 6.3 899 6.6 938 7.1 977 7.5
10000 610 4.8 629 5.0 647 5.1 665 5.4 702 5.8 737 6.2 770 6.6 801 7.0 831 7.3 876 7.6 913 8.1 949 8.5 --- ---
®
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
PRESSURE DROPProduct SpecificationsHorizontal
Chilled Water / Hot Water / DX
GPM
P.D
. (ft.
wtr
)
Size 08 1 Row Coil Pressure Drop
1 2 3 4 5 6 7 8 9 10 200.1
0.2
0.3
0.40.5
0.7
1
2
3
45
7
10
GPM
P.D
. (ft.
wtr
)
Size 08 2 Row Coil Pressure Drop
1 2 3 4 5 6 7 8 9 10 200.1
0.2
0.3
0.40.5
0.7
1
2
3
45
7
10
20
2Row-Full
2Row-Half
GPM
P.D
. (ft.
wtr
)
Size 08 4 Row Coil Pressure Drop
1 2 3 4 5 6 7 8 9 10 200.1
0.2
0.3
0.40.5
0.7
1
2
3
45
7
10
20
4Row-Qtr
4Row-Half
GPM
P.D
. (ft.
wtr
)
Size 08 6 Row Coil Pressure Drop
1 2 3 4 5 6 7 8 9 10 200.1
0.2
0.3
0.40.5
0.7
1
2
3
45
7
10
20
6Row-Qtr
6Row-Half
-36-
®
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
PRESSURE DROPProduct SpecificationsHorizontal
Chilled Water / Hot Water / DX
GPM
P.D
. (ft.
wtr
)
Size 12 1 Row Coil Pressure Drop
1 2 3 4 5 6 7 8 9 10 200.1
0.2
0.3
0.40.5
0.7
1
2
3
45
7
10
20
GPM
P.D
. (ft.
wtr
)
Size 12 2 Row Coil Pressure Drop
1 2 3 4 5 6 7 8 9 10 200.1
0.2
0.3
0.40.5
0.7
1
2
3
45
7
10
20
2Row-Full
2Row-Half
GPM
P.D
. (ft.
wtr
)
Size 12 4 Row Coil Pressure Drop
1 2 3 4 5 6 7 8 9 10 200.1
0.2
0.3
0.40.5
0.7
1
2
3
45
7
10
20
4Row-Half
4Row-Qtr
GPM
P.D
. (ft.
wtr
)
Size 12 6 Row Coil Pressure Drop
1 2 3 4 5 6 7 8 9 10 200.1
0.2
0.3
0.40.5
0.7
1
2
3
45
7
10
20
6Row-Qtr
6Row-Half
-37-
®
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
PRESSURE DROPProduct SpecificationsHorizontal
Chilled Water / Hot Water / DX
GPM
P.D
. (ft.
wtr
)
Size 16 1 Row Coil Pressure Drop
1 2 3 4 5 6 7 8 9 10 200.1
0.2
0.3
0.40.5
0.7
1
2
3
45
7
10
20
GPM
P.D
. (ft
. wtr
)
Size 16 2 Row Coil Pressure Drop
1 2 3 4 5 6 7 8 9 10 200.1
0.2
0.3
0.40.5
0.7
1
2
3
45
7
10
20
2Row-Half
2Row-Full
GPM
P.D
. (ft.
wtr
)
Size 16 4 Row Coil Pressure Drop
1 2 3 4 5 6 7 8 9 10 200.1
0.2
0.3
0.40.5
0.7
1
2
3
45
7
10
20
4Row-Half
4Row-Qtr
GPM
P.D
. (ft.
wtr
)
Size 16 6 Row Coil Pressure Drop
1 2 3 4 5 6 7 8 9 10 200.1
0.2
0.3
0.40.5
0.7
1
2
3
45
7
10
20
6Row-Half
6Row-Qtr
-38-
®
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
PRESSURE DROPProduct SpecificationsHorizontal
Chilled Water / Hot Water / DX
GPM
P.D
. (ft.
wtr
)
Size 20 1 Row Coil Pressure Drop
1 2 3 4 5 6 7 8 9 10 200.1
0.2
0.3
0.40.5
0.7
1
2
3
45
7
10
20
GPM
P.D
. (ft.
wtr
)
Size 20 2 Row Coil Pressure Drop
1 2 3 4 5 6 70.1
0.2
0.3
0.4
0.50.60.70.8
1
2
3
4
2Row-Full
2Row-Half
GPM
P.D
. (ft.
wtr
)
Size 20 4 Row Coil Pressure Drop
1 2 3 4 5 6 7 8 9 10 201
2
3
4
5
678910
20
4Row-Half
4Row-Qtr
GPM
P.D
. (ft.
wtr
)
Size 20 6 Row Coil Pressure Drop
1 2 3 4 5 6 7 8 9 10 201
2
3
4
5
678910
20
6Row-Half6Row-Qtr
-39-
®
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
PRESSURE DROPProduct SpecificationsHorizontal
Chilled Water / Hot Water / DX
GPM
P.D
. (ft.
wtr
)
Size 30 1 Row Coil Pressure Drop
8 9 10 20 252
3
4
5
6
7
8910
20
GPM
P.D
. (ft.
wtr
)
Size 30 6 Row Coil Pressure Drop
4 5 6 7 8 9 10 20 30 402
3
4
5
6
7
8910
20
6Row-Qtr
6Row-Half
GPM
P.D
. (ft.
wtr
)
Size 30 4 Row Coil Pressure Drop
5 6 7 8 9 10 20 30 352
3
4
5
6
7
8910
20
4Row-Qtr
4Row-Half
GPM
P.D
. (ft.
wtr
)
Size 30 2 Row Coil Pressure Drop
10 20 30 401
2
3
4
5
678910
20
2Row-Half
2Row-Full
-40-
®
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
PRESSURE DROPProduct SpecificationsHorizontal
Chilled Water / Hot Water / DX
GPM
P.D
. (ft.
wtr
)
Size 40 1 Row Coil Pressure Drop
4 5 6 7 8 9 10 201
2
3
4
5
678910
20
GPM
P.D
. (ft.
wtr
)
Size 40 2 Row Coil Pressure Drop
10 20 30 401
2
3
4
5
678910
20
2Row-Full
2Row-Half
GPM
P.D
. (ft.
wtr
)
Size 40 4 Row Coil Pressure Drop
5 6 7 8 9 10 20 30 352
3
4
5
6
7
8910
20
4Row-Qtr
4Row-Half
GPM
P.D
. (ft.
wtr
)
Size 40 6 Row Coil Pressure Drop
4 5 6 7 8 910 20 30 402
3
4
5
6
7
8910
20
6Row-Half
6Row-Qtr
-41-
®
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
PRESSURE DROPProduct SpecificationsHorizontal
Chilled Water / Hot Water / DX
GPM
P.D
. (ft.
wtr
)
Size 60 1 Row Coil Pressure Drop
8 9 10 20 302
3
4
5
6
7
8910
20
GPM
P.D
. (ft.
wtr
)
Size 60 2 Row Coil Pressure Drop
10 20 30 401
2
3
4
5
678910
20
2Row-Half
2Row-Full
GPM
P.D
. (ft.
wtr
)
Size 60 4 Row Coil Pressure Drop
8 9 10 20 30 404
5
6
7
8
9
10
20
4Row-Qtr
4Row-Half
GPM
P.D
. (ft.
wtr
)
Size 60 6 Row Coil Pressure Drop
4 5 6 7 8 9 10 20 30 402
3
4
5
6
7
8910
20
6Row-Qtr
6Row-Half
-42-
®
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
PRESSURE DROPProduct SpecificationsHorizontal
Chilled Water / Hot Water / DX
GPM
P.D
. (ft.
wtr
)
Size 80 1 Row Coil Pressure Drop
10 20 30 402
3
4
5
6
7
8910
20
GPM
P.D
. (ft.
wtr
)
Size 80 2 Row Coil Pressure Drop
10 20 30 401
2
3
4
5
678910
20
2Row-Full
2Row-Half
GPM
P.D
. (ft.
wtr
)
Size 80 4 Row Coil Pressure Drop
6 7 8 9 10 20 30 402
3
4
5
6
7
8910
20
4Row-Half
4Row-Qtr
GPM
P.D
. (ft.
wtr
)
Size 80 6 Row Coil Pressure Drop
4 5 6 7 8 9 10 20 30 402
3
4
5
6
7
8910
20
6Row-Half
6Row-Qtr
-43-
®
Applied Environmental Air - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.ae-air.com
-44-
Product SpecificationsHorizontal
Chilled Water / Hot Water / DX
ELECTRICAL DATA & WEIGHTS
Catalog No. Ahw410 (replaces ahw310)
AWHD SERIES WEIGHTS
MODEL
**BASE UNIT WEIGHTS COIL WEIGHTS ACCESSORY WEIGHTS MOTOR WEIGHTS
OPERATING WEIGHT
SHIPPING WEIGHT
COIL (LESS FLUID)
COIL FLUID
VOLUME (GALLONS)
FLUID (LBS.)
COIL (OPERATING)
WEIGHT
9BDAF_F2/4 FLAT FILTER
SECTION
9BDAF_A2/4 ANGULAR
FILTER SECTION
9BDAM_ MIXING
BOX
120/208/240/1PH 277/1/60
HP LBS LBS
8AHWD 243.0 295.0
1 ROW 5.3 0.24 2.0 7.3 SHIPPING WT SHIPPING WT SHIPPING WT 1/4 20.0 N/A
2 ROW 10.5 0.48 4.0 14.5 52.0 89.0 98.0 1/3 23.0 23.0
4 ROW 21.0 0.96 8.0 29.0 OPERATING WT OPERATING WT OPERATING WT 1/2 26.0 26.0
6 ROW 31.5 1.44 12.0 43.5 32.0 62.0 78.0 3/4 31.0 34.0
12AHWD 257.0 320.0
1 ROW 6.0 0.28 2.3 8.3 SHIPPING WT SHIPPING WT SHIPPING WT 1 33.0 42.0
2 ROW 12.0 0.56 4.7 16.7 56.0 97.0 103.0 1 1/2 42.0 49.0
4 ROW 24.0 1.13 9.4 33.4 OPERATING WT OPERATING WT OPERATING WT 2 44.0 N/A
6 ROW 36.0 1.72 14.4 50.4 36.0 70.0 83.0 208/240/480/3PH
16AHWD 295.0 361.0
1 ROW 8.3 0.37 3.1 11.4 SHIPPING WT SHIPPING WT SHIPPING WT 1/4 22.0
N/A
2 ROW 16.5 0.75 6.3 22.8 60.0 123.0 127.0 1/3 22.0
4 ROW 33.0 1.50 12.5 45.5 OPERATING WT OPERATING WT OPERATING WT 1/2 23.0
6 ROW 49.5 2.25 18.8 68.3 49.0 98.0 105.0 3/4 27.0
20AHWD 332.0 402.0
1 ROW 9.5 0.44 3.7 13.2 SHIPPING WT SHIPPING WT SHIPPING WT 1 33.0
2 ROW 19.0 0.89 7.4 26.4 67.0 137.0 146.0 1 1/2 33.0
4 ROW 38.0 1.78 14.9 52.9 OPERATING WT OPERATING WT OPERATING WT 2 41.0
6 ROW 57.0 2.67 22.3 79.3 52.0 111.0 121.0 3 58.0
5 81.0
7 1/2 117.0
10 143
30AHWD Contact Factory
40AHWD Contact Factory
60AHWD Contact Factory
80AHWD Contact Factory
**BASE UNIT WEIGHT INCLUDES BLOWER ASSEMBLY, MOTOR SHEAVE, BLOWER PULLEY, BELT AND 2” FILTER
SINGLE PHASE THREE PHASE
Motor Data Control Box Data Part Number Motor Data Control Box Data Part Number
Volt Phase HP FLA MCA Fuse/Qty Part Number Volt Phase HP FLA MCA Fuse/Qty Part Number
115 1
1/4 5.8 10 10 1 986FF11M3M
208/230 3
1/3 1.6 3 3 3 986FF33M1M
1/3 7.2 15 15 1986FF11M4M
1/2 2.4 6 6 3986FF33M2M
1/2 9.8 15 15 1 3/4 3.5 6 6 3
3/4 13.8 20 20 1 986FF11M5M 1 5.6 10 10 3986FF33M3M
1 16.4 25 25 1986FF11M6M
1.5 6.6 10 10 3
1.5 20.0 25 25 1 2 7.5 15 15 3986FF33M4M
2 24.0 30 30 1 986FF11M7M 3 10.6 15 15 3
5 16.7 25 25 3 986FF33M6M
277 1
1/3 3.0 6 6 1986FF71M2M
1/2 4.1 6 6 1
460 3
1/3 0.8 3 3 3
986FF63M1M 3/4 5.7 10 10 1986FF71M3M
1/2 1.1 3 3 3
1 6.8 10 10 1 3/4 1.6 3 3 3
1.5 8.5 15 15 1986FF71M4M
1 3.7 6 6 3
986FF63M2M2 10.0 15 15 1 1.5 3.0 6 6 3
2 3.7 6 6 3
208/230 1
1/4 2.9 6 6 2986FF31M2M
3 4.8 10 10 3986FF63M3M
1/3 3.6 6 6 2 5 7.6 10 10 3
1/2 4.9 10 10 2986FF31M3M
3/4 6.9 10 10 2
575 3
1/2 0.9 3 3 3986FF53M1M
1 8.2 15 15 2986FF31M4M
3/4 1.3 3 3 3
1.5 10.0 15 15 2 1 1.7 3 3 3
986FF53M2M 2 12.0 20 20 2 986FF31M5M 1.5 2.4 3 3 3
CONTACT FACTORY FORMOTOR CONTROLS FOR 7-1/2 & 10 HP MOTORS
2 2.7 6 6 3
3 3.9 6 6 3
5 6.1 10 10 3 986FF53M3M