LLP 2-35 LLP 2-35 LLP 2-35 LLP 2-35 LLP 2-35 Key Features Single Point Adjustment Single Point Adjustment Single Point Adjustment Single Point Adjustment Single Point Adjustment—no tools required to make settings and adjustments; one intelligence shelf controls up to 56 PCUs • Remote Access Remote Access Remote Access Remote Access Remote Access—options allow users to view, control and interact with all power systems in a network from a remote location • Plug’n’Play Plug’n’Play Plug’n’Play Plug’n’Play Plug’n’Play—add PCUs without adjustments and settings; no system shutdown • Front Accessible • Front Accessible • Front Accessible • Front Accessible • Front Accessible—allows for easy installation, additions and maintenance • Modular Design • Modular Design • Modular Design • Modular Design • Modular Design—simple to install and operate; allows users to grow system in cost- effective increments • High Density • High Density • High Density • High Density • High Density—compact design takes up less floor space; houses four PCUs per 10.5"(26.67cm) high x 23"(58.42cm) wide shelf • Optional • Optional • Optional • Optional • Optional Temperature emperature emperature emperature emperature Compensation Compensation Compensation Compensation Compensation—provides automatic adjustment of PCU output voltage when battery temperature increases or decreases • Saf • Saf • Saf • Saf • Safety Compliance ety Compliance ety Compliance ety Compliance ety Compliance—UL listed to UL subject 1801 50-2,400 amp, -48 VDC Vortex ® Power System with 50 or 65 amp PCUs Description The Vortex power platform with 50 or 65 amp power conversion units (PCUs) is a modular power system providing up to 2,400 amps of power for -48 volt systems. The basic components of a Vortex power system include an intelligence shelf, which houses the meter– control–alarm microprocessor (MCA) and PCUs; expansion shelves for additional PCUs; and up to three modular distribution cabinets with rear copper bus interbay power connections. The system can be expanded to either side of the main bay. The intelligence shelf can accommodate up to four PCUs, and the expansion shelves, also housing up to four PCUs each, can be added for larger load requirements. The intelligence and expansion shelves are 23" (58.42cm) wide x 10.5" (26.67cm) high. In addition to housing the PCUs, the intelligence shelf provides a powerful, microprocessor- based meter–control–alarm system which is capable of monitoring and controlling up to 56 PCUs. The front of the intelligence shelf provides a 16-character alphanumeric display which can be activated at the touch of a keypad. Vortex distribution is modular by row and position. Each distribution cabinet provides four rows with a maximum of 96 positions per cabinet, 288 per system. Users can combine any number of 1-150 amp circuit breakers and 1-50 amp TPA-style fuses to customize power plants. GJ-style circuit breakers and TPL-style fuses are also available. Application The Vortex system, powered with 50 or 65 amp PCUs, is ideal for wireline and wireless applications such as switch sites, co-location, huts and large CUE sites. Additional Information For additional specification, engineering and installation information, specify spec. numbers 582122200 (power system), 588703600 (260 amp power shelf and 65 amp PCUs) or 588700701 (200 amp power shelf and 50 amp PCUs). For ordering information, request SAG582122200, PD588703600 or PD588700701.

50-2,400 amp, -48 VDC Vortex Power System with 50 or …voxtechnologies.com/Marconi/pdf/2_35.pdfGJ-style circuit breakers and TPL-style fuse options allow for protection devices of

  • Upload
    lythuan

  • View
    222

  • Download
    7

Embed Size (px)

Citation preview

LLP 2-35LLP 2-35LLP 2-35LLP 2-35LLP 2-35

Key Features

••••• Single Point AdjustmentSingle Point AdjustmentSingle Point AdjustmentSingle Point AdjustmentSingle Point Adjustment—notools required to makesettings and adjustments; oneintelligence shelf controls upto 56 PCUs

• Remote Access Remote Access Remote Access Remote Access Remote Access—optionsallow users to view, controland interact with all powersystems in a network from aremote location

• Plug’n’PlayPlug’n’PlayPlug’n’PlayPlug’n’PlayPlug’n’Play—add PCUswithout adjustments andsettings; no system shutdown

• Front Accessible• Front Accessible• Front Accessible• Front Accessible• Front Accessible—allows foreasy installation, additionsand maintenance

• Modular Design• Modular Design• Modular Design• Modular Design• Modular Design—simple toinstall and operate; allowsusers to grow system in cost-effective increments

• High Density• High Density• High Density• High Density• High Density—compactdesign takes up less floorspace; houses four PCUs per10.5"(26.67cm) high x23"(58.42cm) wide shelf

• Optional • Optional • Optional • Optional • Optional TTTTTemperatureemperatureemperatureemperatureemperatureCompensationCompensationCompensationCompensationCompensation—providesautomatic adjustment of PCUoutput voltage when batterytemperature increases ordecreases

• Saf• Saf• Saf• Saf• Safety Complianceety Complianceety Complianceety Complianceety Compliance—UL listedto UL subject 1801

50-2,400 amp, -48 VDC Vortex® PowerSystem with 50 or 65 amp PCUsDescription

The Vortex power platform with 50 or 65 amp power conversion units (PCUs) is a modularpower system providing up to 2,400 amps of power for -48 volt systems. The basiccomponents of a Vortex power system include an intelligence shelf, which houses the meter–control–alarm microprocessor (MCA) and PCUs; expansion shelves for additional PCUs;and up to three modular distribution cabinets with rear copper bus interbay powerconnections. The system can be expanded to either side of the main bay.

The intelligence shelf can accommodate up to four PCUs, and the expansion shelves, alsohousing up to four PCUs each, can be added for larger load requirements. The intelligenceand expansion shelves are 23" (58.42cm) wide x 10.5" (26.67cm) high.

In addition to housing the PCUs, the intelligence shelf provides a powerful, microprocessor-based meter–control–alarm system which is capable of monitoring and controlling up to 56PCUs. The front of the intelligence shelf provides a 16-character alphanumeric display whichcan be activated at the touch of a keypad.

Vortex distribution is modular by row and position. Each distribution cabinet provides fourrows with a maximum of 96 positions per cabinet, 288 per system. Users can combine anynumber of 1-150 amp circuit breakers and 1-50 amp TPA-style fuses to customize powerplants. GJ-style circuit breakers and TPL-style fuses are also available.

Application

The Vortex system, powered with 50 or 65 amp PCUs, is ideal for wireline and wirelessapplications such as switch sites, co-location, huts and large CUE sites.

Additional InformationFor additional specification,engineering and installationinformation, specify spec.numbers 582122200 (powersystem), 588703600 (260 amppower shelf and 65 amp PCUs) or588700701 (200 amp power shelfand 50 amp PCUs).

For ordering information, requestSAG582122200, PD588703600 orPD588700701.

50-2,400 amp, -48 VDC Vortex Power System with 50 or65 amp PCUsThe System

DistributionThe Vortex platform includesa modular distributionproduct line that can bedesigned with one to threedistribution cabinets - eachcapable of housing fourdistribution panels. Eachpanel is rated at 500 ampsload. The maximum load perdistribution cabinet is 1200amps. Each modular panelcan be configured with anycombination of distributionpositions, low voltagedisconnect and batterydisconnect panels. Distribution cabinets are front accessible, modular in design and are initially configured in the factory. Eachdistribution cabinet is 24.375”(61.91cm)wide x 33.25”(84.46cm) high x 21.5”(54.61cm) deep and is mounted in a 7’ highwelded construction relay rack. Circuit breakers and/or fuse modules snap into the multi-position distribution blocks toprovide for easy installation. GJ-style circuit breakers and TPL-style fuse options allow for protection devices of up to 600amps for both load and battery disconnect.

Intelligence ShelfA front access intelligence shelf houses up to four PCUs.Available shelf ratings are 200 amps (with 50 amp PCUs) and260 amps (with 65 amp PCUs). The intelligence shelf includesthe MCA, which provides a single point of adjustment for suchfeatures as float voltage, test/equalize voltage, high voltageshutdown and current limit adjustments for all PCUs in theentire power system. The intelligence shelf allows users to viewspecific alarm conditions, system measurements and systemsettings. All adjustments can be performed locally via thealphanumeric display panel on the front of the intelligence shelf or remotely via optional software and hardware. The MCAprovides local indicators and the ability to transmit various alarm conditions such as PCU failure, high voltage shutdown andAC failure.

LLP 2-36LLP 2-36LLP 2-36LLP 2-36LLP 2-36

Intelligence ShelfIntelligence ShelfIntelligence ShelfIntelligence ShelfIntelligence Shelf

Expansion ShelfEach relay rack can hold up to four front-access power shelves, eachof which houses up to four PCUs. The main bay contains theintelligence shelf and up to three expansion shelves. A complete three-bay system can be configured with eleven expansion shelves (48 PCUstotal) all of which are controlled by the intelligence shelf. Each shelfmeasures 23" (58.42cm) wide, 10.5" (26.67cm) high and 14.88"(37.78cm) deep.

Power Conversion UnitsThe modular, high frequency, switch-mode Vortex PCUs are the foundation of the Vortex platform. Plug’n’play technologyallows for easy system configuration. System capacity can be increased by simply plugging an additional PCU into an existingintelligence or expansion shelf – no adjustments or setup are required. The Vortex power system can house up to 48 PCUswhich provide load power, battery float current and battery recharge current. The PCUs are monitored and controlled by theintelligence shelf. The PCUs allow the user to appropriately size a power plant (50 to 2,400 amps) to meet specific applications.

50-2,400 amp, -48 VDC Vortex Power System with 50 or65 amp PCUs

Power Conversion Unit Specifications

InputVoltage: Nominal 208/240 volts AC, single phase, 50/60 Hz,with a range of 176 to 264 volts. Extended range is 150 voltAC to 290 volt AC (50 amp unit only).Inrush Current: Peak does not exceed 2 times the RMS inputat full load, under any conditions of input voltage within therated input voltage range.Frequency: 45-70 HzProtection: Each PCU is individually wired and connectionsfor individual AC input branch circuits are provided. If theAC input voltage decreases or increases beyond a non-adjustable predetermined value, the PCU power conversioncircuitry inhibits, disabling PCU output. The PCU willrecover automatically when the AC input voltage is re-established within specifications limits.Typical Power Factor: Greater than or equal to 98% for anyload greater than or equal to 50% of rated full load atnominal line. Meets IEC 1000–3–2.Typical Operating Efficiency: 90% at full load.

OutputVoltage: Nominal -48 volts DC, Positive Ground.Current: 50 amps per PCU, up to a total of 200 amps pershelf with four PCUs installed. 65 amps per PCU, up to atotal of 260 amps per shelf with four PCUs installed.Regulation: Steady state output voltage remains within±0.5% of any voltage within the range of 44.0 to 58.0 voltsDC (44.0 to 57.0 volts for 65 amp PCUs) for anycombination of frequency, normal input voltage, and loadfrom no load to full load over the temperature range of -20°C to +65° C (-4° F to +149° F) for 50 amp PCUs, -20° C to+50° C (-4° F to +122° F) for 65 amp PCUs.Filtering: On or off batteryVoice Band Noise — Less than 32 dBrndCWide Band Noise — Does not exceed 500 mv peak-to-peak,or 30 mv rmsPsophometric Noise — Does not exceed 1 mv

LLP 2-37LLP 2-37LLP 2-37LLP 2-37LLP 2-37

Easy System ExpansionEasy System ExpansionEasy System ExpansionEasy System ExpansionEasy System Expansion

LLP 2-38LLP 2-38LLP 2-38LLP 2-38LLP 2-38

© 2000 Marconi Communications Inc.Printed in the USA. All rights reserved. Any unauthorizedreproduction or transmission without the prior consent ofMarconi Communications Inc. is prohibited.

Vortex® is a trademark of Marconi Communications Inc.wwwwwwwwwwwwwww.marcon i . com.marcon i . com.marcon i . com.marcon i . com.marcon i . com /pow/pow/pow/pow/powerererererMarconi CommunicationsMarconi CommunicationsMarconi CommunicationsMarconi CommunicationsMarconi Communications1122 F StreetLorain, OH 44052800-800-1280Fax: 440-246-4876

50-2,400 amp, -48 VDC Vortex Power System with 50 or65 amp PCUsPower Conversion Unit Specifications (continued)

ProtectionCurrent Limiting — Maximum output current of each PCUcan be set from 10% to 110% (105% maximum for 65 ampPCU) of full load current.High Voltage Shutdown — If PCU output voltage exceeds anadjustable preset value, the PCU shuts down. Afterapproximately three seconds, the PCU automaticallyrestarts.

Status/Alarm Indicators and MeteringExtensive alarming and status indicators such as AC on/off,fan fail, PCU failure and open sense are displayed on the 16-character numerical display of the intelligence shelf andon the PCUs within the shelf.

EnvironmentalOperating Temperature:-40° C to +65° C (-40° F to +149° F) for 50 amp PCUs,-20° C to +50° C (-4° F to +122° F) for 65 amp PCUsStorage Temperature: -40° C to +85° C (-40° F to +185° F)Humidity: 0% to 95% relative humidity, non-condensingAltitude: The maximum operating ambient temperatureshould be derated by +10° C (+50° F) at an elevation of10,000' (3,048m) above sea level. For elevations between3,000' (914m) and 10,000' (3,048m), derate the maximumoperating ambient temperature linearly.

50 or 65 amp,50 or 65 amp,50 or 65 amp,50 or 65 amp,50 or 65 amp,-48 Volt Power-48 Volt Power-48 Volt Power-48 Volt Power-48 Volt PowerConversion UnitConversion UnitConversion UnitConversion UnitConversion Unit

Ventilation: Fan-cooled front to rearEMI/RFI Suppression: Conforms to FCC rules Part 15,Subpart B, Class A, with an option for FCC and CISPR22Class B emission ratings.Audible Noise: 3' from any vertical surface does not exceed65dBA; 55dBA with low fan speed selected.

Physical CharacteristicsMounting: Plug-in installationDimensions:Width: 5.13" (13.02cm)Height: 9.88" (25.08cm)Depth: 14.5" (36.83cm)Weight: 18 lbs. (8.16kgs)

Safety ComplianceUL recognized (UL 1950)CSA 22.2, No. 950CE