Transients in Offshore HVDC-systems
Anders Geisler Eriksen and Joachim Holbll
Technical University of Denmark
17thOctober 2011
Offshore HVDC grids present and future - Workshop
8/12/2019 5 Holboell Transients in Offshore HVDC-systemsV4
2/22
2 DTU Electrical Engineering, Technical University of Denmark
Transients in offshore HVDC systems,an approach
Point-to point systems
Switching and fault situations, Classical approach, Low frequent models
Multiterminal systems
Offshore/onshore
Challenges
Discussion, Focus?
8/12/2019 5 Holboell Transients in Offshore HVDC-systemsV4
3/22
3 DTU Electrical Engineering, Technical University of Denmark
The components of a point-to point system
AC Circuit breaker
AC - Filter bus
Converter bus
Voltage Source Converter
DC-Bus
DC-Circuit breaker
DC-Cables
Converter transformer
AC-grid
8/12/2019 5 Holboell Transients in Offshore HVDC-systemsV4
4/22
4 DTU Electrical Engineering, Technical University of Denmark
The system in question
Bipolar point-to-point HVDC-system
Converter technology based on Voltage Source Converters(VSC)
Offshore system cable-based system
HVDC-circuit breaker has been implemented
The transformer configuration of the VSC-stations are star/delta-configurations
Power frequency range (=models) on AC side
8/12/2019 5 Holboell Transients in Offshore HVDC-systemsV4
5/22
5 DTU Electrical Engineering, Technical University of Denmark
Multi-terminal HVDC-systems
Although the HVDC-system about to be presented is a point-to-pointconnection, the emphasis of this project will be on transients in multi-terminal HVDC-system.
However only very little attention has been given to this area of researchat this point. Therefore, it will be interesting to see how the known
transients, from point-to-point systems affect multi-terminal systems.
8/12/2019 5 Holboell Transients in Offshore HVDC-systemsV4
6/22
6 DTU Electrical Engineering, Technical University of Denmark
AC-breaker
Transients due to load swirching orclearing of AC-faults[1]
Transients arise when dischargedcapacitors placed near theconverter are charged after fault
clearing [1]
This transient could affect thesystem even more seriously ifresonance exist between the filtercapacitor and the grid[1]
AC Circuit breaker
AC - Filter bus
Converter bus
Voltage SourceConverter
DC-Bus
DC-Circuit breaker
DC-Cables
Converter transformer
AC-grid
8/12/2019 5 Holboell Transients in Offshore HVDC-systemsV4
7/22
8/12/2019 5 Holboell Transients in Offshore HVDC-systemsV4
8/22
8 DTU Electrical Engineering, Technical University of Denmark
AC-filter bus
Line-to-ground fault, overcurrenthandled by phase reactors,initiates blocking of both rectiferand inverter, voltage of adjacentlines increase by 1.73[1]
Line-to-line fault, overvoltage butno overcurrent[1]
AC Circuit breaker
AC - Filter bus
Converter bus
Voltage SourceConverter
DC-Bus
DC-Circuit breaker
DC-Cables
Converter transformer
AC-grid
[1]
8/12/2019 5 Holboell Transients in Offshore HVDC-systemsV4
9/22
9 DTU Electrical Engineering, Technical University of Denmark
Converter bus 1
Line-to-ground fault results indischarge of DC-capacitor causingovercurrent through the VSC,rapid rise of current in the affectedphase[1]
AC Circuit breaker
AC - Filter bus
Converter bus
Voltage SourceConverter
DC-Bus
DC-Circuit breaker
DC-Cables
Converter transformer
AC-grid
[1]
8/12/2019 5 Holboell Transients in Offshore HVDC-systemsV4
10/22
10 DTU Electrical Engineering, Technical University of Denmark
Converter bus 2
Line-to-line fault, no overvoltage phase reactors and convertertransformer will be exposed toshort-circuit current[1]
AC Circuit breaker
AC - Filter bus
Converter bus
Voltage SourceConverter
DC-Bus
DC-Circuit breaker
DC-Cables
Converter transformer
AC-grid
[1]
8/12/2019 5 Holboell Transients in Offshore HVDC-systemsV4
11/22
8/12/2019 5 Holboell Transients in Offshore HVDC-systemsV4
12/22
12 DTU Electrical Engineering, Technical University of Denmark
Voltage source converters 2
Blocking of the inverter due toground fault causes overvoltage,as the rectifier keeps on feedingpower, until it senses theovervoltage[1]
In multiterminal systems when afault on a line occurs, the VSCs ateither end will be blocking, hencethe fault current will be drawn
from the capacitors of the adjacent
VSCs[4]
AC Circuit breaker
AC - Filter bus
Converter bus
Voltage SourceConverter
DC-Bus
DC-Circuit breaker
DC-Cables
AC-grid
8/12/2019 5 Holboell Transients in Offshore HVDC-systemsV4
13/22
13 DTU Electrical Engineering, Technical University of Denmark
DC bus fault
Not a fault necessarily occuring atthe bus itself, but generally faultsoccuring between the converterand the DC bus[5]
Ground fault occuring close to the
DC-capacitor, most serious fault ifDC-capacitor already charged tothe arrester protective level[1]
AC Circuit breaker
AC - Filter bus
Converter bus
Voltage SourceConverter
DC-Bus
DC-Circuit breaker
DC-Cables
Converter transformer
AC-grid
8/12/2019 5 Holboell Transients in Offshore HVDC-systemsV4
14/22
8/12/2019 5 Holboell Transients in Offshore HVDC-systemsV4
15/22
15 DTU Electrical Engineering, Technical University of Denmark
Cable faults 1
Positive-line-to-ground fault[4]
Negative-line-to-ground fault[4]
In either of the above cases the
voltage of the unaffected pole willincrease to 2 pu.[4]
Line-to-Line fault [4]
Fault current dependent upon the
location of the fault, since thecurrent is dependent upon theinductance of the cable which isproportional to the length of thecable[4]
AC Circuit breaker
AC - Filter bus
Converter bus
Voltage SourceConverter
DC-Bus
DC-Circuit breaker
DC-Cables
Converter transformer
AC-grid
8/12/2019 5 Holboell Transients in Offshore HVDC-systemsV4
16/22
8/12/2019 5 Holboell Transients in Offshore HVDC-systemsV4
17/22
17 DTU Electrical Engineering, Technical University of Denmark
Point-to-point HVDC-system
8/12/2019 5 Holboell Transients in Offshore HVDC-systemsV4
18/22
18 DTU Electrical Engineering, Technical University of Denmark
The complete picture?
Low frequency range
Faults and fault current breaking can cause fast transients
Component models change to broad band models
Example
Transformer:
Another challenge: VSC Multi terminal HVDC system
8/12/2019 5 Holboell Transients in Offshore HVDC-systemsV4
19/22
19 DTU Electrical Engineering, Technical University of Denmark
Another challenge: VSC Multi-terminal HVDC-system(Here Kriegers flak)
8/12/2019 5 Holboell Transients in Offshore HVDC-systemsV4
20/22
20 DTU Electrical Engineering, Technical University of Denmark
Challenges, concluding
Transient events point-to-point vs. Multiterminal
Offshore: long cables, but no lightning
Broad band models
DC breaker models
Time domain simulations
Verification difficult so far
8/12/2019 5 Holboell Transients in Offshore HVDC-systemsV4
21/22
8/12/2019 5 Holboell Transients in Offshore HVDC-systemsV4
22/22
22 DTU Electrical Engineering, Technical University of Denmark
References 2
[7] Tang, Lianxiang; Ooi, Boon-Teck; Loacting and Isolating DC Faults inMulti-Terminal DC systems; pp. 1877-1884; IEEE transactions on PowerDelivery, Vol. 22, No. 3, July 2007
[8] Yang, Jie; Zheng, Jianchao; Tang, Guangfu; He, Zhiyuan;Characteristics and Recovery Performance of VSC-HVDC DC TransmissionLine Fault
[9] An Analysis of Offshore Grid Connection at Kriegers Flak in the BalticSea. Joint Pre-feasibility Study By Energinet.dk, Svenska Kraftnt,Vattenfall Europe Transmission, May 2009