425-2-Heating Load-2007

Embed Size (px)

Citation preview

  • 8/2/2019 425-2-Heating Load-2007

    1/13

    ME 425 Heating Load Calculation

    1

    Heating Load Calculation

    ME 425

    Air Conditioning System Design

    Keith E. Elder, P.E.

    Heating Load Calculation

    The heating load calculation begins with thedetermination of heat loss through a varietyof building envelope components andsituations.

    Walls Roofs

    Windows Doors

    Exposed Floors Slab-on-Grade Floors Basement Walls Basement Floors

    Infiltration Ventilation

    Duct Loss Building Pickup

  • 8/2/2019 425-2-Heating Load-2007

    2/13

    ME 425 Heating Load Calculation

    2

    The Heat Loss Equation

    q = Uo x A ( Ti - To )

    Where:

    Uo =the overall heat transfercoefficient, Btu/hr/ft2/F

    A = the surface area, ft2

    Ti = the indoor design temperature, FTo = the outdoor design temperature, F

    Heat Loss Equation Assumptions

    Steady State Conditions

    No Thermal Storage

    Heat Transfer is Instantaneous

    One-Dimensional Parallel "Heat Flow"

    Thermally Homogeneous Construction

    Construction Anomalies can be Accounted for by

    Transmission Weighting Corrections Heat flow path ignores temperature variations

    due to construction anomalies

  • 8/2/2019 425-2-Heating Load-2007

    3/13

    ME 425 Heating Load Calculation

    3

    Solving the Heat Loss Equation

    Area Takeoffs (from plans with est. zoning)

    Design Temperatures (05F28 CD & Std. 55)

    Assembly U-factors, Uo:

    Uo = 1/ RTotal

    RTotal = R1 + R2 + Rn + ...

    R1, R2 and Rn represent the thermal resistance of each ofthe elements in the path of the "heat flow.

    Properties of typical construction materials can be foundin Table 3 of 05F25.

    Construction Material Properties

  • 8/2/2019 425-2-Heating Load-2007

    4/13

    ME 425 Heating Load Calculation

    4

    Air Film PropertiesFrom 05F25.2

    Air Gap PropertiesFrom 05F25.4

  • 8/2/2019 425-2-Heating Load-2007

    5/13

    ME 425 Heating Load Calculation

    5

    Wall with no Framing Elements

    What is the U-factor of a 3-1/2 inch wallcomposed of 4 inch brick, R-11insulation and 5/8 inch gypboard?

    Ri

    Outside Air Film

    4" Brick

    R-11 Batt Insulation

    5/8" Gypboard

    Inside Air Film

    Total R =

    Uo = 1/R

    = 1/12.81

    = 0.078 Btu

    0.17

    0.40

    11.00

    0.56

    0.68

    12.81

    Hr-SF-deg F

    Correcting for Cavity Depth

    The R-value of batt insulation is rated bymanufacturers for predetermined depths.Corrections must be made to calculations forinstallation in non-standard cavities.

    TABLE 20-A

    R-Value of Fiberglass Batts Compressed within Various Depth Cavities

    Insulation R-Value at Standard Thickness

    R-Value 38 30 22 21 19 15 13 11 8 5 3

    Standard Thickness 12" 9- " 6- " 5- " 6- " 3- " 3-5/8" 3- " 2- " 1- " "

    Nominal

    LumberSizes,

    Inches

    Actual

    Depth ofCavity,

    Inches

    Insulation R-Values when Installed in a Confined Cavity

    2 x 12 11-1/4 37 -- -- -- -- -- -- -- -- -- --

    2 x 10 9-1/4 32 30 -- -- -- -- -- -- -- -- --

    2 x 8 7-1/4 27 26 -- -- -- -- -- -- -- -- --

    2 x 6 5-1/2 -- 21 20 21 18 -- -- -- -- -- --

    2 x 4 3-1/2 -- -- 14 -- 13 15 13 11 -- -- --

    2 x 3 2-1/2 -- -- -- -- -- -- 9.8 -- -- -- --

    2 x 2 1-1/2" -- -- -- -- -- -- 6.3 6.0 5.7 5.0 --

    2 x 1 3/4" -- -- -- -- -- -- -- -- -- 3.2 3.0

  • 8/2/2019 425-2-Heating Load-2007

    6/13

    ME 425 Heating Load Calculation

    6

    Correcting for Wood Framing

    What is the U-factor of the previousexample if the wall is framed withDouglas Fir studs spaced 16" on-center.

    Through

    Insulation 16" OC Stud

    Outside Air Film

    4" Brick

    R-11 Batt Insulation

    3-1/2" Fir Stud

    5/8" Gypboard

    Inside Air Film 0.68 0.68

    Total R =

    Uo =

    Uavg = 0.20 x 0.188 + 0.80 x 0.078

    = 0.100 Btu/(hr-S.F.-F)

    Through

    0.56 0.56

    3.50

    11.0

    0.40 0.400.17 0.17

    12.81 5.31

    0.078 0.188

    What About Metal Studs?

    Transmission weighting

    is not appropriate if the

    conductivity of the

    penetration exceeds that

    of the layer being

    penetrated by more than

    an order of magnitude.

    Isotherms

  • 8/2/2019 425-2-Heating Load-2007

    7/13

    ME 425 Heating Load Calculation

    7

    Correcting for Metal Studs

    ASHRAE Standard 90.1 Correction Factors

    Size of Insulation Correction

    Members Framing R-Value Factor, Fc

    2 x 4 16 in. O.C. R-11 0.50

    2 x 4 24 in. O.C. R-11 0.60

    2 x 6 16 in. O.C. R-19 0.40

    2 x 6 24 in. O.C R-19 0.45

    Using Metal Stud Factors

    What is the heat loss of the wall in thefirst example if the wall is framed with 3-1/2" metal studs spaced 16" on-center?

    Ri

    Outside Air Film

    4" Brick

    R-11 + Mtl. Stud (11.0 x 0.50) =

    5/8" Gypboard

    Inside Air Film 0.68

    Total R =

    Uo = 1/7.31 =

    0.56

    5.50

    0.400.17

    7.31

    0.137 Btu

    Hr-SF-deg F

  • 8/2/2019 425-2-Heating Load-2007

    8/13

    ME 425 Heating Load Calculation

    8

    ASHRAE Window Performance

    Because ofconductivespacers,frames & newcoatingsavailable,window U-factors cannot

    be calculatedaccurately.

    ASHRAE Window Performance

    Reasonable estimates can be found inTable 4, 05F31.8.

  • 8/2/2019 425-2-Heating Load-2007

    9/13

    ME 425 Heating Load Calculation

    9

    ASHRAE Window U-factors

    ASHRAE Window U-factors

  • 8/2/2019 425-2-Heating Load-2007

    10/13

    ME 425 Heating Load Calculation

    10

    Door U-Factors

    Door U-factorscan be found inTable 4,05F31.11.

    Floors on Grade

    qslab

    = F2 x Perimeter x T

  • 8/2/2019 425-2-Heating Load-2007

    11/13

    ME 425 Heating Load Calculation

    11

    Floors on Grade - F2 Factors

    Infiltration

    The uncontrolled inward air leakagethrough cracks and interstices in anybuilding element and around windowsand doors of a building, caused by thepressure effects of wind and/or theeffect of differences in theoutdoor/indoor air density.

    qinfiltration = 0.018QT

    Q = air flow due to infiltration, ft3/hr

  • 8/2/2019 425-2-Heating Load-2007

    12/13

    ME 425 Heating Load Calculation

    12

    Infiltration Estimates

    From the 1972 Fundamentals Manual:

    Number of Air

    Changes Taking

    Kind of Room or Building Place per Hour

    Rooms with no windows or exterior doors 1/2

    Rooms with windows/exterior doors on one side 1

    Rooms with windows/exterior doors on two sides 1-1/2

    Rooms with windows/exterior doors on three sides 2

    Entrance Halls 2

    Note: Values may be reduced by 1/3 if windows & doorsweatherstripped

    In-Class Heating Load Exercise

    What is the heat loss for a Seattle office space 12feet deep by 50 feet long, with 10 foot ceilings andfloor-to-floor spacing of 12 feet? The office zone islocated on the third floor of a five story building. Thewall is constructed of 6 inch concrete, with R-11batt insulation installed between metal studs 16inch on-center, and 5/8 inch gypsum board. Thewindow is insulated 1/4 inch glass with 1/2 inch air

    space and composes 40 percent of the gross wallarea. The window framing is metal and has nothermal break.

  • 8/2/2019 425-2-Heating Load-2007

    13/13

    ME 425 Heating Load Calculation

    13

    Building & Space Sketch

    50

    12

    10

    12

    Section Sketch

    Outside Air Film

    6 Inch Concrete

    R-11 Batt Insulation

    between mtl studs 16 O.C.

    5/8 Inch Sheet Rock

    Inside Air Film

    Total R =

    Uwall =