Upload
kadsandeep
View
30
Download
2
Tags:
Embed Size (px)
DESCRIPTION
modcell
Citation preview
Issue 3March 2000
401-703-340
Lucent Technologies — ProprietaryThis document contains proprietary information ofLucent Technologies and is not to be disclosed or used
except in accordance with applicable agreements
Copyright © 2000 Lucent TechnologiesUnpublished and Not for Publication
All Rights Reserved
FLEXENT™ CDMA Microcell
Site Preparation Guidelines
Lucent Technologies — ProprietaryUse Pursuant to Company Instructions
This material is protected by the copyright and trade secret laws of the United States and other countries. It may not be reproduced, distributed or altered in any fashion by any entity, including other Lucent Technologies Business Units or Divisions, without the express written consent of the Customer Training and Information Products Organization.
For permission to reproduce or distribute please contact:
Product Development Manager 1-800-645-6759 (domestic); 1-317-322-6847 (international)
NoticeEvery effort was made to ensure that the information in this document was complete and accurate at the time of printing. However, information is subject to change.
TrademarksFLEXENT is a trademark of Lucent Technologies, Inc.PowerHouse is a trademark of Lucent Technologies, Inc.
Ordering InformationThe ordering number for this information product is 401-703-340. To order this document by phone, use one of the following numbers to contact the Lucent Technologies Customer Information Center.
Within the United States of America: 1-888-LUCENT8 (1-888-582-3688; Fax: 1-800-566-9568)
From Canada: +1-317-322-6619 (Fax +1-317-322-6359)
From Europe, the Middle East, and Africa: +1-317-322-6416 (Fax +1-317-322-6699)
From Asia, Central and South America, and the Caribbean and Pacific regions: +1-317-322-6411 (Fax +1-317-322-6699)
Support Telephone Numbers
Information Product Support NumberLucent Technologies provides a telephone number and contact person for you to report errors or to ask questions about the information in this document.
Technical Support Telephone NumberLucent Technologies provides a telephone number for technical assistance support from the Wireless Technical Support Center (WTSC). The support number is:
Developed by the Lucent Technologies Customer Training and Information Products Organization.
Rich Essick 1-336-727-3371(Fax 1-336-727-3132)
1-800-CALL-4NSC (1-800-225-4672)
How Are We Doing?
Title
Iden
Luccan
1. P
2. P
oooooo
Ple
3. W
4. F
If w
Nam
Com
Add
Whe or F
: Flexent™ CDMA Microcell Site Preparation Guidelines
tification No. sue No ate
ent Technolo be of great v
lease rate th
lease check
Improve theImprove theImprove theInclude morAdd more eAdd more d
ase provide
hat did you
eel free to w
e may contac
e:
pany/Organ
ress:
n you have ax to: (336)-
Ease of Use
Clarity
Completeness
Accuracy
Organization
Appearance
Examples
Illustrations
Overall Satisfac
: Is401-703-340
gies welcomes your feedback on this Infoalue in helping us improve our IPs.e effectiveness of this IP in the following
the ways you feel we could improve this
overview/introduction o Make it mo table of contents o Add more s organization o Add more te figures o Make it lesxamples o Add more/betail o Improve th
details for the suggested improvement.
like most about this IP?
rite any comments below or on an attach
t you concerning your comments, please
T
ization:
completed this form, please fold, tape and727-3132.
Excellent Good
tion
.: D3
rmation Product (IPareas:
IP.
re concise/brieftep-by-step procedroubleshooting infos technicaletter quick referenc
e index
ed sheet.
complete the follow
elephone Number:
Date
return to address o
Fair
Poo
: March 2000
). Your commentsures/tutorialsrmation
e aids
ing:
:
n back
r Not
Applicable
////////////////////////////////////
//////////////////
//////////////////
//////////////////
//////////////////
//////////////////
BUSINESS REPLY MAILFIRST CLASS PERMIT NO. 1999 GREENSBORO, NC
POSTAGE WILL BE PAID BY ADDRESSEE
NO POSTAGENECESSARY
IF MAILEDIN THE
UNITED STATES
---------------------------------------------------------- Do Not Cut — Fold Here And Tape --------------------------------------------------------------------
DOCUMENTATION SERVICES2400 Reynolda RoadWinston-Salem, NC 27199-2029
Contents
� About this Information Product ix
Reason for Reissue ix
Purpose ix
Scope x
Safety Labels xi
Related Documentation xii
Site Preparation Checklists xiii
Cell Site Configuration Sheets xiii
� Equipment Overview 1
Flexent™ CDMA Microcell 1
Primary Distribution Cabinet (Optional) 2
Network Interface Unit (Optional) 4
Power Backup Cabinet (Optional) 5
Metric Hardware 5
� Microcell Antenna Architecture and Configurations 6
Architecture 6
Configurations 6
� Environmental Requirements 9
Overview 9
Heat Dissipation 9
Minimum Clearances 9
Operational Outdoor Environmental Requirements 10
Operational Indoor Environmental Requirements 11
� Cell Site Equipment Installation Options 12
Mounting Requirements and Guidelines 12
Microcell Mounting Configurations 12
PDC Mounting Configurations 12
� Typical Mounting Configurations 13
Single-Sector Pole- Mounted Configuration 13
Two-Sector Integrated Antenna Pole-Mounted Configuration 14
Three-Sector Pole- Mounted Configuration 15
Pole Mounting Bracket Layout 16
Lucent Technologies — ProprietarySee notice on first page
Issue 3 March 2000 i
Contents
Single-Sector Wall- Mounted Configuration 17
Three-Sector Wall- Mounted Configuration 19
Floor Stand Configuration 21
Floor Stand Anchor Hole Layout 22
� Outdoor Installation Physical Requirements 23
� Indoor Installation Physical Requirements 24
� Installation Equipment and Material Required for Site Preparation 25
� AC Power Requirements 26
General Requirements 26
AC Input Scenarios 26
AC Input Requirements 26
Main Circuit Breaker Requirement 27
� DC Power Requirements 28
General Requirements 28
DC Regulation and Operating Conditions 28
DC Cable Feeders 28
Lightning Surge Protection 29
Grounding of DC Return Conductors 29
� PDC and PBC Power Support Considerations 30
� Use of a PDC Equivalent 31
General 31
Power Requirements 31
PDC Equivalent Requirements 32
T1/E1 Lightning Protection 32
AC Lightning Protection 32
� No PDC Configuration 33
General 33
Surge and Lightning Protection 33
Metallic Conduits 34
Power Requirements 34
Power Cables 35
Connection of AC Power Cables in Microcell 36
Lucent Technologies — ProprietarySee notice on first page
ii Issue 3 March 2000
Contents
Connection of DC Power Cables in Microcell 37
Microcell Input/Output Cables 38
� Use of a PBC Equivalent 41
General 41
PBC Equivalent Requirements for AC Power 41
PBC Equivalent Requirements for DC Power 41
� Grounding and Lightning Protection Bonding Requirements 42
General 42
Grounding Equipment 43
Grounding of Metal Pole 43
Wooden Pole Grounding Configuration 44
Metal Pole Grounding Configuration 45
Wall-Mounted Grounding Configuration 46
� Antenna Interface Requirements 47
General Requirements 47
� RF Antenna Requirements 48
Mounting Options 48
Integrated Antenna Restrictions for Cellular CDMA 48
Antenna Specifications 48
In-Building Antenna Considerations 49
� GPS Antenna Requirements 50
GPS Antenna Configuration 50
Antenna Ordering Information 51
Recommended Cable Types 51
Antenna Selection Based on Losses 52
GPS Antenna Installation 52
Verify GPS Installation and Line of Sight 52
� T1/E1 Facilities Requirements 53
T1/E1 Input Lines 53
T1/E1 Daisy-Chaining 53
Verify T1/E1 Facilities 54
Lucent Technologies — ProprietarySee notice on first page
Issue 3 March 2000 iii
Contents
Appendix A Site Preparation Checklists� Overview A-1
Purpose A-1
Contents A-1
� SP-GEN Cell Site General Information A-3
� SP-1 Site Preparation General Checklist A-5
� SP-2 Site Preparation Power Source Checklist A-7
� SP-3 Site Preparation Grounding Checklist A-9
� SP-4 Site Preparation RF Antenna Checklist A-15
� SP-5 Site Preparation GPS Antenna Checklist A-17
� SP-6 Site Preparation Punchlist Sheet A-21
� SP-6A Site Preparation Punchlist Continuation Sheet A-23
Appendix B Cell Site Information
� Overview B-1
Purpose B-1
Contents B-1
� CSC-1 Cell Site Configuration Information B-3
Glossary
Lucent Technologies — ProprietarySee notice on first page
iv Issue 3 March 2000
Figures
1. Flexent CDMA Microcell with Dimensions and Weight 12. Single and Multiple PDC with Dimensions and Weight 33. Single-Sector Flexent CDMA Microcell Configuration 74. Two-Sector Directional Antenna Flexent CDMA
Microcell Configuration 85. Three-Sector Directional Antenna Flexent CDMA
Microcell Configuration 86. Typical Single-Sector Pole-Mounted Configuration 137. Typical Two-Sector Integrated Antenna Pole-Mounted Configuration 148. Typical Three-Sector Pole-Mounted Configuration 159. Typical Pole Mounting Bracket Layout 1610. Typical Single-Sector Wall-Mounted Configuration 1711. Layout for Typical Single-Sector
Wall-Mounted Configuration 1812. Typical Three-Sector Wall-Mounted Configuration 1913. Layout for Typical Three-Sector
Wall-Mounted Configuration 2014. Fully Configured Floor Stand 2115. Floor Stand Anchor Hole Layout 2216. I/O Protection Module Cable Connections 3817. Typical Wooden Pole Installation Grounding Configuration4418. Typical Metal Pole Installation Grounding Configuration 4519. Typical Wall-Mounted Installation Grounding Configuration4620. GPS Antenna Serving Three Flexent CDMA Microcells 50
Lucent Technologies — ProprietarySee notice on first page
Issue 3 March 2000 v
Figures
Lucent Technologies — ProprietarySee notice on first page
vi Issue 3 March 2000
Tables
1. On-Line Power PBC Information 52. Flexent CDMA Microcell Configuration Options 63. Flexent CDMA Microcell and Ancillary Cabinet
Heat Dissipation 94. Minimum Clearances for Indoor Application 95. Outdoor Environmental Requirements 106. Indoor Environmental Requirements 117. AC Input Power Requirements 278. Flexent CDMA Microcell AC Power Requirements 319. Circuit Breakers for Microcell 3110. Protector Characteristics 3211. AC Surge Arrestor Electrical Characteristics 3312. Power Cable Information 3513. I/O Cable and Connector Information 3814. I/O Connector Pin Information 3915. GPS Antennas 5116. GPS Cable Characteristics 5117. Antenna Selection Data 52
Lucent Technologies — ProprietarySee notice on first page
Issue 3 March 2000 vii
Tables
Lucent Technologies — ProprietarySee notice on first page
viii Issue 3 March 2000
Lucent Technologies —See notice on fir
About this Information Product 0
Purpose 0 This document describes basic site requirements that can be used to plan a Flexent™ CDMA Microcell site. It also details the specific tasks that must be completed at the job site before the installation of a microcell can begin. For information on site requirements for the international version of this equipment, refer to FLEXENT™ CDMA Microcell Site Preparation Guidelines (International) (401-703-352).
Reason for Reissue 0 This document is being reissued to update outdoor environmental requirements for the Flexent™ CDMA Microcell and backup times for the Power Backup Cabinet (PBC).
Proprietaryst page
Issue 3 March 2000 ix
401-703-340
Scope 0 This document provides the following information:
� An overview of microcell architecture and configuration
� Environmental and physical requirements for the cell site
� Cell site equipment installation options
� Typical mounting configurations
� Tools and equipment required for site preparation
� Outdoor installation physical requirements
� Indoor installation physical requirements
� Power requirements
� Grounding and lightning protection requirements
� Antenna interface requirements and information
� T1/E1 facility requirements
� Site preparation checklist
� Cell site configuration sheets
Lucent Technologies — ProprietarySee notice on first page
x Issue 3 March 2000
About this Information Product
Safety Labels 0 Various safety labels and cautionary sttements appear on the equipment covered in this information product. Definition of three types of safety labels are as follows:
! DANGER:Indicates the presence of a hazard that will cause death or severe personal injury if the hazard is not avoided.
! WARNING:Indicates the presence of a hazard that will or can cause death or severe personal injury if the hazard is not avoided.
! CAUTION:Indicates the presence of a hazard that will or can cause minor personal injury or property damage if the hazard is not avoided.
Lucent Technologies — ProprietarySee notice on first page
Issue 3 March 2000 xi
401-703-340
Related Documentation 0
Cell site planners and site preparation personnel must have the appropriate reference materials as outlined below: i
Document Number Title
NFPA 70 National Electric Code
NFPA 780 Standard for Installation of Lightning Protection Systems
NESC 1943-1990 National Electric Safety Code
UL 50 Underwriters Laboratories Publication #50
UL 1950 Underwriters Laboratories Publication #1950
UL 1778 Underwriters Laboratories Publication, Uninterruptible Power Supplies and Rectifying Equipment and Specialty Transformers
IEEE/ANSI C62.41 IEEE Recommended Practice on Surge Voltages in Low-voltage AC Power Circuits
Lucent Technologies 401-200-115
Grounding and Lightning Protection Guidelines for Lucent Technologies Network Wireless System Cell Sites
Lucent TechnologiesED-3R128-10
Flexent™ Microcell Cabinet Installation Requirements
Lucent Technologies401-703-341
Flexent™ CDMA Microcell Installation Manual
Lucent Technologies401-660-128
Base Station CDMA Reference Frequency Timing Generator and Antenna System Description, Operation, Installation and Maintenance
AT&T900-200-318
Outside Plant Engineering Handbook
CSA-CEC Canadian Standards Association, Part 1, 1998
BellcoreGR-63
Core Section 4.1.2 Environmental Requirements
Lucent Technologies — ProprietarySee notice on first page
xii Issue 3 March 2000
About this Information Product
Site Preparation Checklists 0
It is highly recommended that the completion of all site preparation activities, as well as adherence to the guidelines, be verified prior to installing the microcell equipment and the associated ancillary hardware. Various checklists and a punchlist sheet have been provided in Appendix A of this document to aid customers and Lucent personnel during a cell site verification. The checklists can be used and should be completed during the Cell Site Method of Procedure (MOP) walk-through prior to equipment installation.
Utilization of the checklists will help to ensure a quality installation and provide a cell site history file for later reference during capacity growth, etc. The punchlist can be used to track the completion of any outstanding site preparation items, and aid in project managing installation resources.
Cell Site Configuration Sheets 0
Cell site configuration sheets have been provided in Appendix B of this document to aid the customer, Equipment Engineering and Wireless Project Management during the various stages of product deployment. The configuration sheets can be used to document the cell site equipment configuration, conditions and other pertinent information for reference during the product deployment, and later addition of microcells and ancillary equipment. The sheets should be completed during the equipment engineering phase. Reference to this information during the Cell Site MOP walk-through is often helpful in completing the site preparation checklists.
Lucent Technologies — ProprietarySee notice on first page
Issue 3 March 2000 xiii
401-703-340
Lucent Technologies — ProprietarySee notice on first page
xiv Issue 3 March 2000
FLEXENT™ CDMA MicrocellSite Preparation Guidelines
Equipment Overview 0
Flexent™ CDMA Microcell 0
The Flexent CDMA Microcell is a compact, self-contained unit, suitable for indoor and outdoor operation, that can be mounted on a pole, solid concrete wall or floor stand.
The CDMA Microcell implements the requirements for the air interface as found in IS-95A and IS-97A (cellular band), and ANSI J-STD-008 and J-STD-019 (PCS band).
Figure 1 shows the Flexent CDMA Microcell, along with its dimensions and weight.
Figure 1. Flexent™ CDMA Microcell with Dimensions and Weight
5 00 M M (1 9.55 IN )
930
MM
(3
6.56
IN)
2 80 M M (11 IN )
W E IG H T = 54 .5 4 K G (12 0 LB S .)
)
)
)
Lucent Technologies — ProprietarySee notice on first page
Issue 3 March 2000 1
401-703-340
Primary Distribution Cabinet (Optional) 0
The Primary Distribution Cabinet (PDC) is an optional cabinet that provides a centralized point of demarcation for the various interfaces into and out of the microcell. It contains the components and interfaces necessary to properly connect customer-owned/maintained (and outside service provider-owned/maintained) equipment to the microcell cabinet.
There are two types of PDCs:
� Single PDC (supports one microcell)
� Multiple PDC (supports up to three microcells)
The following interfaces are provided by the PDC:
� AC utility power
� Peripheral bus
� T1/E1 facilities
� POTS line
� External alarm relay contacts
� Maintenance and test ports
� AC generator
� External power backup
To ensure surge protection operation, the PDC must be located within 14.5 meters (50 feet) of the microcell(s) it is serving.
For safety reasons, the PDC should be located within view of the microcell(s) it is serving. If the PDC is not in view of the microcell(s) it is serving, it must be equipped with a circuit breaker lock-out/tag-out feature.
If the PDC is located more than 2.9 meters (10 feet) from the microcell(s) it is serving, a customer-supplied duplex convenience outlet must be provided within 2.9 meters (10 feet) of the microcell.
If a Lucent Technologies PDC is not utilized, refer to page 31 of this document for PDC equivalent requirements.
Lucent Technologies — ProprietarySee notice on first page
2 Issue 3 March 2000
FLEXENT™ CDMA MicrocellSite Preparation Guidelines
Figure 2 shows the Single PDC and Multiple PDC with dimensions and weights.
Figure 2. Single and Multiple PDC with Dimensions and Weight
440m m (17.17")
540m
m (
21.1
8")
2 4 0m m (9.3 6 ")
540m m (21 .17")
640
mm
(25
.18"
)
2 4 0m m (9.3 6 ")
SING LE PR IM ARYDISTR IB UTIO N C AB IN ET
M ULT IPL E PRIMA RYDISTR IB UTIO N C AB IN ET
(FRO NT V IE W ) (S IDE V IE W ) (FRO NT V IE W ) (S IDE V IE W )
SINGLE PDC WEIGHT = 12.27 KG (27 LBS) MULTIPLE PDC WEIGHT = 19.32 KG (42.5 LBS)
)
Lucent Technologies — ProprietarySee notice on first page
Issue 3 March 2000 3
401-703-340
Network Interface Unit (Optional) 0
The Network Interface Unit (NIU) provides a central point for converting E1 coaxial signaling to balanced signaling required by the microcell. The conversion is from 75-ohm unbalanced to 120-ohm balanced cabling. The NIU also provides coaxial protection for two E1 transmit/receive circuits with expansion to four E1 circuits.
The NIU must be located within 6.1 meters (20 feet) of the PDC that it is serving. If a PDC is not used, the NIU must be located within 6.1 meters (20 feet) of the microcell that it is serving.
The dimensions of the NIU are 254 mm (height) x 254 mm (width) x 95 mm (depth) (10 inches x 10 inches x 3.75 inches).
Lucent Technologies — ProprietarySee notice on first page
4 Issue 3 March 2000
FLEXENT™ CDMA MicrocellSite Preparation Guidelines
Power Backup Cabinet (Optional) 0
An optional internal battery is available for the Flexent CDMA Microcell that can provide backup power for ten seconds at full transmit power capability.
If the customer requires a longer power backup capability, Lucent Technologies recommends the use of a Power Backup Cabinet (PBC) from OnLine Power, Inc. The toll-free number for OnLine Power is 1-800-227-8899.
The PBC contains an Uninterruptible Power Supply (UPS) that conditions the utility power under normal operating conditions. If the power utility should fail, the PBC will maintain AC power to the microcell from its internal batteries via a converter. Table 1 provides information on the OnLine Power PBCs.
Table 1. OnLine Power PBC Information
Up to three PBCs can be mounted on a pole.
If another type of backup power cabinet will be used, the customer should refer to page 41 of this document.
Metric Hardware 1 All hardware associated with the Flexent CDMA Microcell is metric.
CabinetMicrocell
ConfigurationBackup Time
(Hours) Mounting
Height x Width x Depth Meters (Inches)
Weight kg
(lbs)
650-W UPS 1 microcell without heater
2.0 Pole, Pad .50 x .55 x .51(19.5 x 21.5 x 20)
154.5(340)
1.3-kW UPS
1 microcell without heater
4.0
Pole, Pad.50 x .55 x .51(19.5 x 21.5 x 20)
211.8(466)
1 microcell with heater
0.45
2 microcells without heater
1.6
3 microcells without heater
1.1
Lucent Technologies — ProprietarySee notice on first page
Issue 3 March 2000 5
401-703-340
Microcell Antenna Architecture and Configurations 1
Architecture 1 The basic architecture of the Flexent CDMA Microcell provides one transmit path and two diversity receive paths for full duplex communication. The RF paths of the microcell can be configured in either simplex or duplex mode. In the simplex mode, each RF path requires an individual antenna. In the duplex mode, the transmit path and the first diversity receive path utilize a common antenna interface port. The second diversity receive path remains a simplex receive and utilizes an individual antenna interface port.
Configurations 1 The configuration options of the Flexent CDMA Microcell are driven by the requirements of the application that it is intended to serve. A combination of microcells can be deployed to provide various cell site configurations.
Table 2 shows the configurations that are supported.
Table 2. Flexent™ CDMA Microcell Configuration Options
* Requires 1:3 GPS splitter.
Number of Sectors
Number of Carriers
Number of Microcells
GPS Antennas Cell Site RF Antennas
Simplex Duplex
1 1 1 1 3 2
2 1 2 1* or 2 6 4
3 1 3 1* or 3 9 6
Lucent Technologies — ProprietarySee notice on first page
6 Issue 3 March 2000
FLEXENT™ CDMA MicrocellSite Preparation Guidelines
The microcell supports the following antenna configurations:
� 3 ports simplex: Tx, Rx0 and Rx1 for diversity
� 2 ports: Tx/Rx0 duplex and Rx1 for diversity
� Built-in antenna, duplexed Tx and Rx dual polarization diversity
� No diversity receive for in-building applications
� Simulcast control and traffic for rural highway applications. (Simulcast refers to the transmission and reception of the same RF information on separate physical antenna faces. The purpose is to direct the capacity of a single microcell to a very specific coverage area.)
The most basic application of the Flexent CDMA Microcell is for a single carrier with an omni-directional or directional antenna.
Figure 3 illustrates the single-sector single-carrier configuration.
Figure 3. Single-Sector Flexent CDMA Microcell Configuration
Lucent Technologies — ProprietarySee notice on first page
Issue 3 March 2000 7
401-703-340
Multiple microcells with directional antennas can be collocated and controlled by a single Radio Cluster Server (RCS) to form a sectorized cell site. Figure 4 and Figure 5 illustrate examples of this.
Figure 4. Two-Sector Directional Antenna Flexent CDMA Microcell Configuration
Figure 5. Three-Sector Directional Antenna Flexent CDMA Microcell Configuration
Lucent Technologies — ProprietarySee notice on first page
8 Issue 3 March 2000
FLEXENT™ CDMA MicrocellSite Preparation Guidelines
Environmental Requirements 2
Overview 2 This section outlines the environmental requirements related to the installation and operation of the Flexent CDMA Microcell, Primary Distribution Cabinet (PDC) and Power Backup Cabinet (PBC).
Heat Dissipation 2 Table 3 lists heat dissipation for various Flexent CDMA Microcells, PDCs and PBCs.
Table 3. Flexent CDMA Microcell and Ancillary Cabinet Heat Dissipation
Minimum Clearances3 Table 4 lists the minimum clearances for a microcell installation. These clearances must be maintained to ensure that proper ventilation and access are provided for the equipment.
Table 4. Minimum Clearances for Indoor Application
CabinetHeat Energy Dissipated
(Watts)
Flexent CDMA Microcell with heater 1,020 average1,400 maximum
Flexent CDMA Microcell without heater 400
Single PDC 0
Multiple PDC 0
OnLine Power 650-W UPS 300
OnLine Power 1.3-kW UPS 350
BetweenMinimum Clearance
mm (Inches)
Top cap of microcell and ceiling 152 (6)
Bottom of microcell and floor or any bottom obstruction 152 (6)
Rear of microcell plenum and rear wall 76 (3)
Left side of microcell (side with door latches) and left wall 102 (4)
Right side of microcell and right wall or any right side obstruction
456 (18)
Lucent Technologies — ProprietarySee notice on first page
Issue 3 March 2000 9
401-703-340
Operational Outdoor Environmental Requirements 4
Table 5 lists the operational outdoor environmental requirements of this equipment.
Table 5. Operational Outdoor Environmental Requirements
Parameter Specification
Ambient Operating Temperature
-40 to +52° C with no wind-30 to +52° with 10 MPH maximum wind-20 to +52° with 20 MPH maximum wind-10 to +52° with 30 MPH maximum wind
Operating Relative Humidity
5 to 95% non-condensing (for door open repair activity)
Solar Loading 70 W/square foot
Operating Altitude -290 M to +3,048 M(-1,000 to 10,000 feet), referenced to sea
level
Rate of Temperature Change (Operating)
30° C/hour
Lucent Technologies — ProprietarySee notice on first page
10 Issue 3 March 2000
FLEXENT™ CDMA MicrocellSite Preparation Guidelines
Operational Indoor Environmental Requirements 5
The indoor/closet environment must be controlled within the limitations specified in Bellcore GR-63-Core Section 4.1.2. If the microcell is located in a closet or enclosure, there must be a minimum of 100 CFM of fresh air flow for each microcell.
Table 6 lists the operational indoor environmental requirements of this equipment.
Table 6. Operational Indoor Environmental Requirements
Note: Short term is defined as not more than 96 consecutive hours and a total of not more than 15 days per year.
Parameter Specification
Ambient Operating Temperature
0 to +46° C
Ambient Short Term Temperature
-5 to +50° C
Ambient Operating Relative Humidity
5% to 85%
Ambient Short Term Relative Humidity
5% to 90% not to exceed 0.124 kg water /kg air
Lucent Technologies — ProprietarySee notice on first page
Issue 3 March 2000 11
401-703-340
Cell Site Equipment Installation Options6
Mounting Requirements and Guidelines 6
The Flexent CDMA Microcell and its associated equipment can be installed in several different mounting configurations. It cannot be installed in a hazardous environment as defined by NEC Article 500. The customer is responsible for engineering and safety requirements for collocating the microcell and its associated equipment with other utilities. All installations must comply with NESC 1943-1990 and local codes. The top of the microcell must be a minimum of 610 mm (2 feet) from the lowest utility wire. See NESC 1943-1990 and refer to local codes for complete mounting restrictions.
Detailed mounting requirements and guidelines can be found in FLEXENT™ Microcell Cabinet Installation Requirements (ED3R128-10).
Microcell and PDC Mounting Configurations 6
The following Flexent CDMA Microcell and PDC mounting configurations are supported:
� Pole-Mounted (pole diameters from 203 mm to 432 mm (8” to 17”))
� Single microcell
� Two microcells, evenly spaced 180° apart
� Three microcells, evenly spaced 120° apart
� Wall-Mounted on a solid concrete wall
� Floor Stand-Mounted
NOTE:Various building materials and construction methods dictate that the Flexent CDMA Microcell and its ancillary cabinets be fastened to the wall with appropriate mounting hardware. It is the responsibility of the customer to provide any necessary support material and structures to ensure that the installation will be in compliance with Building Officials and Code Administrators (BOCA), Uniform Building Code (UBC) and all local codes.
PBC Mounting Configurations 6
The following PBC mounting configurations are supported:
� Pole-Mounted (pole diameters from 203 mm to 432 mm (8” to 17”))
� Up to three PBCs can be mounted on a pole
� Floor Stand-Mounted
Lucent Technologies — ProprietarySee notice on first page
12 Issue 3 March 2000
FLEXENT™ CDMA MicrocellSite Preparation Guidelines
Typical Mounting Configurations 6
Single-Sector Pole- Mounted Configuration 6
Figure 6 shows a typical single-sector pole-mounted configuration.
Figure 6. Typical Single-Sector Pole-Mounted Configuration
G PS AN TE N N A
EN C LO SU R E BR AC KET
FLEXEN T M IC R O C ELL C ABIN ET
SIN G LE PR IM ARY D ISTR IBU TIO N C ABIN ET
FIN ISH G R AD E O R TO P O F FO U N D ATIO N
R F AN TEN N A
T
T
Lucent Technologies — ProprietarySee notice on first page
Issue 3 March 2000 13
401-703-340
Two-Sector Integrated Antenna Pole-Mounted Configuration 6
Figure 7 shows a typical two-sector integrated antenna pole-mounted configuration with two PBCs.
Figure 7. Typical Two-Sector Integrated Antenna Pole-Mounted Configuration
MICROCELL #2
PBC #2
MULTIPLEPDC
MICROCELL #1
PBC #1
Lucent Technologies — ProprietarySee notice on first page
14 Issue 3 March 2000
FLEXENT™ CDMA MicrocellSite Preparation Guidelines
Three-Sector Pole- Mounted Configuration 6
Figure 8 shows a typical three-sector pole-mounted configuration.
Figure 8. Typical Three-Sector Pole-Mounted Configuration
Lucent Technologies — ProprietarySee notice on first page
Issue 3 March 2000 15
401-703-340
Pole Mounting Bracket Layout 6
Figure 9 shows a typical layout for single-sector mounting brackets. The same measurements also apply to a three-sector application.
Figure 9. Typical Pole Mounting Bracket Layout
M
Lucent Technologies — ProprietarySee notice on first page
16 Issue 3 March 2000
FLEXENT™ CDMA MicrocellSite Preparation Guidelines
Single-Sector Wall- Mounted Configuration 6
Figure 10 shows a typical single-sector wall-mounted configuration.
Figure 10. Typical Single-Sector Wall-Mounted Configuration
Lucent Technologies — ProprietarySee notice on first page
Issue 3 March 2000 17
401-703-340
Figure 11 shows a typical single-sector layout for mounting a microcell and PDC on the wall of a building.
Figure 11. Layout for Typical Single-Sector Wall-Mounted Configuration
497 mm(19.56”)
470 mm(18.5”)
1.5 M (5 FT)
OR
15 M (49 FT)MAX
SPRING NUT SEPARATION83 mm (3.25”) TYP
SPRING NUT SEPARATION268 mm (14.5”)
GUIDELINES FOR STRUTSTO SUPPORTSINGLE PDC
GUIDELINES TOSUPPORT STRUTSFOR MICROCELL
Lucent Technologies — ProprietarySee notice on first page
18 Issue 3 March 2000
FLEXENT™ CDMA MicrocellSite Preparation Guidelines
Three-Sector Wall- Mounted Configuration 6
Figure 12 shows a typical three-sector wall-mounted configuration.
Figure 12. Typical Three-Sector Wall-Mounted Configuration
2
1
Lucent Technologies — ProprietarySee notice on first page
Issue 3 March 2000 19
401-703-340
Figure 13 shows a typical three-sector layout for mounting microcells and a Multiple PDC on the wall of a building.
Figure 13. Layout for Typical Three-Sector Wall-Mounted Configuration
GUIDELINES TOSUPPORT STRUTSFOR MICROCELL
GUIDELINES TOSUPPORT STRUTSFOR MULTIPLE PDC
572 mm(22.5”)
497 mm(19.56”)
1.21M (4 FT)MIN
MAX15M (49 FT)
SPRING NUT SEPARATION83 MM (3.25”) TYP
OR
1.5 M (5 FT)
15 M (49 FT)MAX
SPRING NUT SEPARATION470 mm (18.5”)
Lucent Technologies — ProprietarySee notice on first page
20 Issue 3 March 2000
FLEXENT™ CDMA MicrocellSite Preparation Guidelines
Floor Stand Configuration 6
Figure 14 shows a fully configured floor stand with three microcells, an MPDC and a PBC.
Figure 14. Fully Configured Floor Stand
Lucent Technologies — ProprietarySee notice on first page
Issue 3 March 2000 21
401-703-340
Floor Stand Anchor Hole Layout 6
Figure 15 shows the anchor hole layout for the floor stand.
Figure 15. Floor Stand Anchor Hole Layout
Lucent Technologies — ProprietarySee notice on first page
22 Issue 3 March 2000
FLEXENT™ CDMA MicrocellSite Preparation Guidelines
Outdoor Installation Physical Requirements 6
For a typical outdoor cell site, the following requirements must be satisfied before installation of the Flexent CDMA Microcell and associated equipment can begin (see SP-1 through SP-5 in Appendix A).
� Adequate clearance provided around cabinets for service access and ventilation
� AC service installed
� DC power facilities installed (optional)
� External main circuit breaker and circuit breaker enclosure installed (always required in Canada, required in U.S. if PBC is utilized)
� T1/E1 facilities installed
� Grounding electrode system installed
� #2 AWG solid, bare, tinned copper ground wire bonded to grounding electrode system and coiled at bottom of pole or wall, or attached to pole or wall for temporary grounding of RF and GPS antenna cable shields
� RF and GPS antennas installed
� RF and GPS antenna runs installed (if required)
� RF and GPS antenna cable shields temporarily grounded
� Wall-mounted cabinet support structure installed (if required)
� Floor stand installed (if required)
� Concrete pad ready (if required for Power Backup Cabinet)
� Tower light power installed (if required)
� Tower light alarm installed (if required)
� Cell translations available
Lucent Technologies — ProprietarySee notice on first page
Issue 3 March 2000 23
401-703-340
Indoor Installation Physical Requirements 6
For a typical indoor cell site, the following requirements must be satisfied before installation of the Flexent CDMA Microcell and associated equipment can begin (see SP-1 through SP-5 in Appendix A).
� Cable ducts installed
� All required room construction completed
� Cell site support structure installed
� HVAC and environmental control system installed
� Adequate clearance provided around cabinets for service access and ventilation
� AC service installed
� DC power facilities installed (optional)
� Power line surge protector installed
� External main circuit breaker and circuit breaker enclosure installed (always required in Canada, required in U.S. if PBC is utilized)
� T1/E1 facilities installed
� Grounding electrode system installed
� #2 AWG solid, bare, tinned copper ground wire bonded to grounding electrode system and coiled at wall, or attached to wall for temporary grounding of RF antenna cable shields
� RF and GPS antennas installed
� RF and GPS antenna runs installed (if required)
� RF and GPS antenna cable shields temporarily grounded
� Wall-mounted cabinet support structure installed (if required)
� Floor stand installed (if required)
� Tower light power installed (if required)
� Tower light alarm installed (if required)
� Cell translations available
Lucent Technologies — ProprietarySee notice on first page
24 Issue 3 March 2000
FLEXENT™ CDMA MicrocellSite Preparation Guidelines
Installation Equipment and Material Required for Site Preparation 6
The equipment and materials required to install the Flexent CDMA Microcell mounting hardware and PDC are listed below.
� 32-tooth hack saw
� Insulation displacement tool
� Channel lock pliers
� Flat screwdriver
� Phillips screwdriver
� Open end wrenches (metric/standard)
� Ratchet set with extension (metric/standard)
� Two 16-foot ladders
� Gin boom
� Snatch block
� Rope
� Hoisting mechanism
� Four 1/4-inch anchor shackles (for lifting)
� Two 3-foot length chains for lifting (1/4-inch diameter welded link)
� Ground lug and C tap crimping tool
� Tape measure
� Chalk line
� Level
� Hammer
� Insulation stripping tool
� Drill
Lucent Technologies — ProprietarySee notice on first page
Issue 3 March 2000 25
401-703-340
AC Power Requirements 6
GeneralRequirements 6
This section describes the AC power requirements for the Flexent CDMA Microcell and Primary Distribution Cabinet (PDC).
All AC wiring and over-current protection must be installed by a licensed electrician and must be provided in accordance with the National Electric Code (NFPA-70) and local electrical codes. An appropriate earth ground connection is required before commercial AC service can be connected.
It is the customer’s responsibility to make arrangements with the local power utility to install the necessary power service, power service entrance equipment and 1-inch PDC input conduit.
For indoor installations, the customer is responsible to provide a power line surge protector on the power input line.
See FLEXENT™ CDMA Microcell Installation Manual (401-703-341, Chapter 3) for detailed instructions on the installation of AC input cables.
AC Input Scenarios 6 The AC input cables can come to the PDC (or equivalent) from four sources:
� Power Backup Cabinet (PBC)
� Power company meter
� Power panel
� AC generator
AC Input Requirements 6
The PDC can have as input either 120/240 VAC, single phase, 60-Hz power or 120/208 VAC, single phase, 60-Hz power. If, however, the customer chooses to use a 120 VAC feed, Lucent Technologies must be consulted to evaluate the application on a case-by-case basis. The AC generator option and the Multiple PDC are not available when using a 120 VAC feed.
The 208/240 VAC input requirements for the PDC (or equivalent) are shown in Table 7.
Lucent Technologies — ProprietarySee notice on first page
26 Issue 3 March 2000
FLEXENT™ CDMA MicrocellSite Preparation Guidelines
Table 7. AC Input Power Requirements
Main Circuit Breaker Requirement 7
If a PBC is utilized, the customer must provide an external main circuit breaker and circuit breaker enclosure located between the AC service meter and the PBC. The recommended equipment is a Square D main lug load center (part number QO2L70RB), and Square D circuit breaker (part number QO260). This is a type 3R weatherproof enclosure. Other manufacturers’ equivalent equipment is also acceptable.
In Canada, an external main circuit breaker and circuit breaker enclosure, as described above, are required for all applications. If a PBC is not utilized, the main circuit breaker and enclosure must be located between the AC service meter and the PDC.
Input Voltage 180 to 264 VAC, single phase, 3-wire, 60 Hz(208/240 VAC nominal)
Service 60 Amps
Wire 2 - 8 AWG copper only, 75°C temperature rating
Lucent Technologies — ProprietarySee notice on first page
Issue 3 March 2000 27
401-703-340
DC Power Requirements 7
GeneralRequirements 7
The Flexent CDMA Microcell can be powered from a +24 VDC source. For this option, the microcell must be provided with an input voltage consistent with a standard +24 VDC battery plant. The maximum ripple and noise allowed on the +24 VDC input is 100 mVp-p from DC to 20 MHz, and 30 mVrms from DC to 20 MHz, measured at the output connector of the DC power source.
DC Regulation and Operating Conditions7
DC regulation and operating conditions are extremely important to ensure that the microcell is properly powered.
! CAUTION:In order to avoid damage to the microcell and ancillary equipment, a power plant should be carefully selected and the following operating conditions must be considered: regulation range, soft start, noise and ripple, transient load response, over-voltage shutdown and over-voltage surge protection.
DC Cable Feeders 7 The wire used for DC feeders must be rated for the environmental condition in which it is used.
DC wire feeders must be sized to limit the round-trip voltage drop between the power system output terminals and the microcell input terminals. The 24 VDC nominal must be present at the microcell terminals under normal conditions, and 20 VDC must be present at the microcell terminals under the most critical operating conditions. Therefore, the location and operating conditions of the DC power plant are extremely important to the operation of the microcell.
Lucent Technologies — ProprietarySee notice on first page
28 Issue 3 March 2000
FLEXENT™ CDMA MicrocellSite Preparation Guidelines
Lightning Surge Protection 7
Lightning surge protection is required for outdoor configurations where the DC power source is located more than 7.6 meters (25 feet) from the microcell. Surge protectors must be provided and the DC feeders must be run in properly grounded metal conduit.
Lightning surge protection must be provided such that equipment shall not be degraded or damaged if the feeders are exposed to ten strikes of a surge of 500 V, 500 A 8 µsec/20 µsec pulse waveform.
If all of the cell site equipment and the DC power source are within the “zone of protection” of a higher metallic structure, surge protection on the DC feeders is not required. See Grounding and Lightning Protection Guidelines, Lucent Technologies Network Wireless System Cell Sites (401-200-115) to determine the “zone of protection”.
Grounding of DC Return Conductors 7
The DC return conductors must be bonded to the grounding electrode system at the output of the DC power source. Refer to Grounding and Lightning Protection Guidelines, Lucent Technologies Network Wireless System Cell Sites (401-200-115) for detailed grounding requirements.
Lucent Technologies — ProprietarySee notice on first page
Issue 3 March 2000 29
401-703-340
PDC and PBC Power Support Considerations 7
7! CAUTION:
Caution must be taken when implementing PBC and PDC configurations.
� When the 650-W PBC is utilized to support one microcell, the heater circuit breaker (CB5) in the PDC must be in the OFF position and the heater wires must be permanently disconnected, since the 650-W PBC is designed to support one microcell without heaters.
� When the 1.3 kW PBC is utilized to support three microcells, the three heater circuit breakers (CB11, CB14, CB15) in the MPDC must be in the OFF position and the heater wires must be permanently disconnected, since the 1.3 kW PBC is designed to support three microcells without heaters.
Lucent Technologies — ProprietarySee notice on first page
30 Issue 3 March 2000
FLEXENT™ CDMA MicrocellSite Preparation Guidelines
Use of a PDC Equivalent 7
General 7 The Lucent Technologies PDC is specifically designed as an interface to the Flexent CDMA Microcell. If another manufacturer’s PDC equivalent is used, the following guidelines must be followed.
Power Requirements 7 If another manufacturer’s PDC equivalent is used, it must provide power to the microcell in accordance with Table 8 over all input and output conditions including no load to full load, and low line to high line.
Table 8. Flexent™ CDMA Microcell AC Power Requirements
Table 10 lists the recommended circuit breakers for the microcell equipment.
Table 9. Circuit Breakers for Microcell
Voltage RangeFrequency
Range Nominal VoltageMaximum Current
85 - 130 VAC 57 - 63 Hz 120 VAC 16 A
180 - 264 VAC 57 - 63 Hz 240 VAC 8 A
20 - 30 VDC - 24 VDC 30 A
Type Voltage Equipment
RecommendedCircuitBreaker
AC 120 PCU 20 A
AC 120 Heaters 20 A
AC 240 PCU 20 A
DC 24 PCU 30 A
Lucent Technologies — ProprietarySee notice on first page
Issue 3 March 2000 31
401-703-340
PDC Equivalent Requirements 9
If another manufacturer’s PDC equivalent is used, it must meet the following minimum requirements.
� The enclosure used to house the interface components must be rated a minimum of NEMA3R or UL50 type 3R.
� T1/E1 and AC surge protection must be properly provided per the guidelines listed below.
� A GFCI duplex convenience outlet is recommended.
� A generator inlet connector for backup power to the microcell is recommended.
� T1/E1 connection to the microcell I/O module J201 port must be provided via an RJ45 connector.
T1/E1 Lightning Protection 9
Lightning protection for the T1/E1 input and six user alarms must be provided when the PDC equivalent and microcell are located outside the cone of protection. A building protector block is recommended with 5-pin plug-in protectors, with the characteristics listed in Table 10.
Table 10. Protector Characteristics
Characteristic Value
DC breakover voltage @ 100 V/second > 265 V @ 20 mA
Impulse breakover voltage @ 100 V/microsecond
265 - 400 V
Insulation resistance @ 100 VDC > 100 MegaOhms
DC holdover, impulse 52.5 VDC/265 mA135 VDC/200 mA
On state voltage @ 100 A < 10 V
Rated impulse discharge 10 x 1000 microseconds 200 A
Capacitance > 200 pF
Operational temperature range -40 to 65° C
Balanced voltage limiting < 5 V
Lucent Technologies — ProprietarySee notice on first page
32 Issue 3 March 2000
FLEXENT™ CDMA MicrocellSite Preparation Guidelines
AC Lightning Protection 10
Surge protection must be provided on the AC line to prevent damage to the equipment as defined in IEEE/ANSI C62.41, “IEEE Recommended Practice on Surge Voltages in Low-voltage AC Power Circuits”.
Typical AC surge arrestor electrical characteristics are shown in Table 11.
Table 11. AC Surge Arrestor Electrical Characteristics
Characteristic Value
Voltage Rating (120 VAC L-N) Up to 120/240 VAC
Frequency 60 Hz
Maximum Surge Current 40,000 A/phase
Maximum Energy Dissipation 600 Joules
Protection Modes Line-to-LineLine-to-NeutralLine-to-GroundNeutral-to-Ground
Operating Temperature -40 to 52 C
Lucent Technologies — ProprietarySee notice on first page
Issue 3 March 2000 33
401-703-340
No PDC Configuration 11
General 11 The Lucent Technologies PDC is specifically designed as an interface to the Flexent CDMA Microcell. If a PDC is not used, the following guidelines must be followed.
Surge and Lightning Protection 11
Surge and lightning protection must be provided for all cables entering the microcell. Refer to “T1/E1 Lightning Protection” on page 32 and “AC Lightning Protection” on page 33.
Metallic Conduits 11 All cables entering the microcell must be run in metallic conduit such as Lucent Technologies 1-inch liquid-tight flexible steel conduit with built-in continuous copper ground or equivalent. The conduit must be grounded at both ends using surfaces that are paint-free and conductive. Power cables and I/O cables must be run in separate conduits.
Power Requirements11 If a PDC is not used, power must be provided to the microcell in accordance with Table 8 over all input and output conditions including no load to full load, and low line to high line.
Recommended circuit breakers for the microcell equipment are listed in Table 9.
Lucent Technologies — ProprietarySee notice on first page
34 Issue 3 March 2000
FLEXENT™ CDMA MicrocellSite Preparation Guidelines
Power Cables 11 The customer-supplied cables required for the microcell Power Converter Unit (PCU) vary depending on the power source that is used (120 VAC, 240 VAC or +24 VDC).
One set of AC or DC power cables must be provided for the microcell PCU. A second set of AC cables is required if the microcell is equipped with heaters.
Table 12 provides power cable information.
Table 12. Power Cable Information
Input Usage Wire Color Connection
120 VAC, 2-wire PCU Black Line In
120 VAC, 2-wire PCU White Neutral
120 VAC, 2-wire PCU Green/Yellow Ground
120/240 VAC,3-wire
PCU Black Line 1 In
120/240 VAC,3-wire
PCU Red Line 2 In
120/240 VAC,3-wire
PCU Green/Yellow Ground
120 VAC Heater Black Line In
120 VAC Heater White Neutral
120 VAC Heater Green/Yellow Ground
+24 VDC PCU Red Feed
+24 VDC PCU Black Return
Lucent Technologies — ProprietarySee notice on first page
Issue 3 March 2000 35
401-703-340
Connection of AC Power Cables in Microcell 12
The microcell AC power wires are pre-connected on the PCU and heaters (if used). They are coiled, tie-wrapped and tagged in the microcell junction box.
One set of black, white and green/yellow AC power wires is tagged “PCU”. If heaters are used in the microcell, a second set of black, white and green/yellow wires will be present and will be tagged “Heater”.
Perform the following steps to connect the customer-supplied AC power cables to the AC power wires in the microcell junction box.
Step Action
1 Strip the end of each AC cable to expose 13 mm (1/2 inch) of wire.
2 Connect the black AC cable labeled “PCU” to the black AC wire labeled “PCU - Line 1” in the junction box using a set screw connector. Tighten the screw on the set screw connector and screw the black insulator cap on the set screw.
3 If 120/240 VAC, 3-wire operation is used, connect the red AC cable labeled “PCU” to the white AC wire labeled “PCU-Line 2” in the junction box using a set screw connector. Tighten the screw on the set screw connector and screw the black insulator cap on the set screw.
4 If 120 VAC, 2-wire operation is used, connect the white AC cable labeled PCU to the white AC wire in the junction box using a set screw connector. Tighten the screw on the set screw connector and screw the black insulator cap on the set screw.
5 If heaters are used, connect each AC cable labeled “Heater” to the same color AC wire labeled “Heater” in the junction box using the set screw connector. Tighten the screw on the set screw connector and screw the black insulator cap on the set screw.
6 Connect the green cables to the ground lug in the junction box.
7 If the fan assembly is present, connect the three wires from it to the three fan assembly wires in the junction box.
Lucent Technologies — ProprietarySee notice on first page
36 Issue 3 March 2000
FLEXENT™ CDMA MicrocellSite Preparation Guidelines
Connection of DC Power Cables in Microcell 12
A #6 AWG connectorized pigtail is provided in the junction box of the microcell for +24 VDC applications.
Perform the following steps to connect the customer-supplied DC power cables to the pigtail, and the pigtail to the microcell PCU.
Step Action
1 Strip the end of each DC cable to expose 13 mm (1/2 inch) of wire.
2 Remove the insulating cap from the end of the #6 AWG pigtail and strip the end of each pigtail wire to expose 13 mm (1/2 inch) of wire.
3 Using an H-tap parallel connector kit, connect each DC cable to the same color wire of the pigtail and apply an insulating material over the connections.
4 Plug the connectorized end of the pigtail into the PCU DC connector.
Lucent Technologies — ProprietarySee notice on first page
Issue 3 March 2000 37
401-703-340
Microcell Input/Output Cables12
There are seven I/O cables that connect to the I/O protection module in the microcell. The I/O cables must be connectorized on the end that terminates in the microcell.
Table 14 shows I/O cable and connector information.
Table 14. I/O Cable and Connector Information
The I/O protection module is labeled with the connector reference designation of each cable as shown in Figure 16.
Figure 16. I/O Protection Module Cable Connections
Connector Reference Connector Type Function
J201 RJ-48C/(jack) Input, Primary T1/E1
J202 RJ-48C/(jack) Input, Secondary T1/E1
J203 RJ-45/(jack) Input, Maintenance Port
J204 RJ-11/(jack) Input, Voice
J205 DB-15/(jack) Input, Alarms
J207 RJ-45/(jack) Input, Peripheral Bus
J210 DB-9/(jack) Input, CDMA Test Port
Lucent Technologies — ProprietarySee notice on first page
38 Issue 3 March 2000
FLEXENT™ CDMA MicrocellSite Preparation Guidelines
Connectors must be wired on the microcell-end of the I/O cables as shown in Table 15.
Table 15. I/O Connector Pin Information
ConnectorConnector
TypePin Numbers
(Input or Output)FunctionalDescription
J201(Category 5
shieldedcable
required)
RJ-48C
5 (output) T1/E1 1TTIP
4 (output) T1/E1 1TRING
2 (input) T1/E1 1RTIP
1 (input) T1/E1 1RRING
J202(Category 5
shielded cable
required)
RJ-48C
5 (output) T1/E1 2TTIP
4 (output) T1/E1 2TRING
2 (input) T1/E1 2RTIP
1 (input) T1/E1 2RRING
J203 RJ-45
1 (output) METH TX(+)
2 (output) METH TX(-)
3 (input) METH RX(+)
6 (input) METH RX(-)
J204 RJ-114 (bi-directional) VTIP
3 (bi-directional) VRING
J205 DB-15
1 (input) ALARM1
3 (input) ALARM2
5 (input) ALARM3
7 (input) ALARM4
9 (input) ALARM5
11 (input) ALARM6
2, 4, 6, 8, 10, 12 FRM GND
J207 RJ-45
3 ARCNET(+)
5 (bi-directional) ARCNET(-)
4 (bi-directional) VTIP
Lucent Technologies — ProprietarySee notice on first page
Issue 3 March 2000 39
401-703-340
Table 15. I/O Connector Pin Information (Continued)
ConnectorConnector
TypePin Numbers
(Input or Output)FunctionalDescription
J210 DB-9
1(output) TFU RHO 10
2(output) 5 VD
3(output) TRU RHO EV
4(output) DEBUGON
5(output) TFU RHO 19
6(output) DGRD
7(output) DGRD
8(output) DGRD
9(output) DGRD
Lucent Technologies — ProprietarySee notice on first page
40 Issue 3 March 2000
FLEXENT™ CDMA MicrocellSite Preparation Guidelines
Use of a PBC Equivalent 15
General 15 Lucent Technologies recommends the use of a Power Backup Cabinet (PBC) from OnLine Power, Inc. If another manufacturer’s PBC equivalent is used, the following guidelines must be followed.
PBC Equivalent Requirements for AC Power 15
If another manufacturer’s PBC equivalent is used in an AC power scenario, it must meet the following minimum requirements.
� The enclosure used to house the power backup components must be rated a minimum of NEMA3R or UL50 type 3R.
� The PBC unit must deliver power values as specified in Table 8 on page 31.
� The operating temperature range of the cabinet must be from -40° to 52° C.
� The output voltage range must be from 85 to 130 volts at 120 VAC nominal, and 180 to 264 volts at 240 VAC nominal.
� The output frequency must be from 57 Hz to 63 Hz at 60 Hz nominal.
� The AC power surge protector must be protected in accordance with C62.41-1991 category C3. The cabinet must be approved by the appropriate safety agency for deployment.
� The cabinet must meet Class B emission requirements of 47CFR, part 15, subpart B.
� The cabinet must be connected ahead of the PDC or PDC equivalent when it is supporting one microcell with or without heaters, or three microcells without heaters.
� The customer must size the cable feeds between the AC source and the microcell to minimize voltage drops.
PBC Equivalent Requirements for DC Power 15
If another manufacturer’s PBC equivalent is used in a DC power scenario, the following requirements must be met.
� AC input is required to feed the charging device for the batteries.
� The DC output must be 24 VDC nominal at the terminals of the microcell.
� The customer must size the cable feeds between the DC source and the microcell to minimize voltage drops.
Lucent Technologies — ProprietarySee notice on first page
Issue 3 March 2000 41
401-703-340
Grounding and Lightning Protection Bonding Requirements 15
General 15 Flexent CDMA Microcell sites are susceptible to lightning surges due to their association with poles and antennas. Therefore, it is imperative that the cell site be properly grounded and that a low impedance path to earth be provided. The grounding conductors must be as straight and short as possible. No sharp bends or loops are permitted in grounding conductors.
Commercial AC power and T1/E1 facilities are particularly susceptible to lightning surges and must be properly protected. An appropriate surge protection device must be installed at the service entry point and be connected directly to the grounding electrode system.
The antenna cable shield must be bonded at the top and bottom of the vertical run, and also where it comes near the equipment. The metallic support for the antenna must also be bonded to the grounding system. In indoor applications, the antenna cable shield must also be bonded at the hatchplate before entering the building.
All metallic objects within 1.75 meters (6 feet) of the grounded equipment must be bonded to the grounding system.
All Flexent CDMA Microcell sites must be equipped with one or more grounding electrode systems (e.g., buried ring ground, copper clad rod, electrolytic rods, metallic water pipe, etc.). The cell site grounding, including all cabinets and antenna cable shields, must be bonded to the grounding electrode system. It is recommended that two separate, low impedance paths to earth be provided to bond together all grounding systems.
Buried ground conductors must be, as a minimum, #2 AWG bare, solid, tinned copper wire. Exterior ground conductors must be either solid bare tinned copper, or stranded, insulated (insulation to be sunlight-resistant) copper cable. The interior ground cable must be stranded copper with green insulation type THWN or equivalent.
All grounding system material (cable, connectors, buses, etc.) must be of high quality materials that resist deterioration and require little or no maintenance.
Exothermic weld is recommended for grounding connections where practical. All below grade connections must be exothermically welded. Compression type, two-hole (0.75” center) lugs or double crimp “C” taps are also acceptable. The contact area of metal to which connections are made must be prepared to bare bright finish, and coated with an anti-oxidation material before connections are made.
Lucent Technologies — ProprietarySee notice on first page
42 Issue 3 March 2000
FLEXENT™ CDMA MicrocellSite Preparation Guidelines
Refer to Grounding and Lightning Protection Guidelines, Lucent Technologies Network Wireless System Cell Sites (401-200-115) and FLEXENT Microcell Cabinet Installation Requirements (ED3R128-10) for detailed requirements related to grounding and lightning protection bonding.
! CAUTION:The equipment warranty can be voided if the guidelines detailed in the National Electric Code NFPA 70, The Standard for Installation of Lightning Protection System (NFPA 780, 1995 edition), Lucent Technologies 401-200-115 and Lucent Technologies Engineering Drawings referenced in this document are not followed.
Verification of the grounding requirements should be performed using checklists SP-3A and SP-3B found in Appendix A of this document.
Grounding Equipment 15
It is the customer’s responsibility to provide and install the following grounding equipment:
� RF and GPS coax cable shield grounding kits (per microcell)
� Grounding electrode system (for details, see 401-200-115)
� Coils of #2 AWG bare, solid tinned copper wire with sufficient length for connection of the main ground bus bar to the grounding electrode system (for details, see Figure 17, Figure 18 and Figure 19)
� Non-metallic cable clips (to secure #2 AWG bare, solid tinned copper wire to the pole or wall at 1.2 meter (48 inch) intervals)
It is recommended that during site preparation, the RF and GPS antenna cable shields be temporarily connected to the grounding electrode system through the #2 AWG bare, solid tinned copper wire mentioned above. During equipment installation, the temporary arrangement will be removed and the antenna cable shields will be connected to the grounding electrode system through the main ground bus bar.
Grounding of Metal Pole 15
If the pole on which the microcell is to be mounted is metallic, it may be used as a down conductor if approval is obtained from the manufacturer or owner of the pole.
The lowermost portion of the metallic pole must be bonded to the grounding electrode system using #2 AWG bare, solid tinned copper cable using exothermic welds.
Lucent Technologies — ProprietarySee notice on first page
Issue 3 March 2000 43
401-703-340
Wooden Pole Grounding Configuration 15
Figure 17 shows a typical grounding configuration for a wooden pole installation.
Figure 17. Typical Wooden Pole Installation Grounding Configuration
Lucent Technologies — ProprietarySee notice on first page
44 Issue 3 March 2000
FLEXENT™ CDMA MicrocellSite Preparation Guidelines
Metal Pole Grounding Configuration 15
Figure 18 shows a typical grounding configuration for a metal pole installation.
Figure 18. Typical Metal Pole Installation Grounding Configuration
THE M ETALLIC PO LE STRUCTUREMAY BE USED AS DOW N CONDUCTOR
AFTER APPROVAL OF MANUFACTURERAND/OR OW NER IS OBTAINED
METALLIC POLE
EXO THERMIC W ELD (W HERE APPLICABLE) W ITH APPROVAL OF OW NER AND/OR POLE ’S MANUFACTURER
#2 AWG BARE SOLID T INNED CO PPER W IRE
TOP OF FO UNDATION
152.4 M M (6”)
THE GREATER DEPTH OF 762 MM (30 ”) OR 152 .4 MM(6 ”) BELOW FROST LINE
15 .8 MM (5 /8 ’)X 2.44 M (8 ’) LONGCOPPER CLAD ROD SPACED 10 FT. MIN
#2 AWG BARE SOLID T INNED COPPER CABLE
GROUNDING ELECTRODE SYSTEM
EXO THERMIC W ELD (TYP.)
FINISH G RADE
Lucent Technologies — ProprietarySee notice on first page
Issue 3 March 2000 45
401-703-340
Wall-Mounted Grounding Configuration 18
Figure 19 shows a typical grounding configuration for a wall-mounted installation.
Figure 19. Typical Wall-Mounted Installation Grounding Configuration
3 M (1 0 ’) M IN .
# 2 A W G B A R E S O LID T IN N E D C O P P E R W IR E
F IN IS H G R A D E
G R E AT E R D E P T H O F 7 62 M M (3 0 ”)O R 1 5 2 .4 (6 ”) B E L O W F R O S T L IN E
B U IL D IN G W A L L F O R M O U N T IN GO F F L E X E N T M IC R O C E L L C A B IN E T
E X O T H E R M IC W E L D (T Y P.)
C O IL S U F F IC IE N T L E N G T H O F# 2 A W G B A R E S O LID T IN N E DC O P P E R W IR E F O R L AT E R C O N N E C T IO N T O T H E M A IN G R O U N D B U S B A R (T Y P.)
1 5 .8 M M (5 /8 ”) X 2 .4 4 M (8 ’)C O P P E R C L A D G R O U N D R O D (T Y P.))
Lucent Technologies — ProprietarySee notice on first page
46 Issue 3 March 2000
FLEXENT™ CDMA MicrocellSite Preparation Guidelines
Antenna Interface Requirements 19
General Requirements 19
All materials for outdoor antenna cables must be rated for outdoor use. All antenna connections must be waterproofed in accordance with the connector and cable manufacturer’s instructions. All cable runs must be appropriately supported in accordance with the connector and cable manufacturer’s instructions. All antenna jumper cables must be installed in accordance with Lucent Technologies engineering drawings.
Grounding of the antenna cable outer shield must be performed in accordance with the ground kit manufacturer’s instructions and as outlined in Grounding and Lightning Protection Guidelines for Lucent Technologies Network Wireless System Cell Sites (400-200-115).
Lightning surge protection for antennas is provided on top of the Flexent CDMA Microcell.
RF antenna cable ends must be located as specified in the applicable Lucent Technologies engineering drawings. Failure to follow these drawings may result in problems during installation.
Verification of the antenna interface requirements can be performed using Checklist SP-4 found in Appendix A of this document.
Lucent Technologies — ProprietarySee notice on first page
Issue 3 March 2000 47
401-703-340
RF Antenna Requirements 19
Mounting Options 19 The Flexent CDMA Microcell is primarily intended for use with two RF antennas (one duplex Rx/Tx and one diversity Rx). These antennas may be mounted remotely and cabled to the microcell, or may be integrated within the front panel of the microcell.
In addition, other external antenna configurations are possible, such as:
� Connection to a distributed antenna system
� Connection to two antenna faces simultaneously
� Connections to antennas through an external filter enclosure
� No diversity receive for in-building applications
Integrated Antenna Restrictions for Cellular CDMA 19
When the RF antennas are integrated into the front panel of the microcell, they are mounted at cross angles to provide angular diversity instead of spatial diversity. However, FCC requirements for cellular band transmitters do not allow transmissions to be non-vertically polarized. Therefore the Cellular CDMA Microcell with integrated RF antennas will use simplex transmission, resulting in a total of three RF antennas. The transmit antenna will mount vertically while the two receive antennas are mounted at cross angles.
! CAUTION:The integrated antenna may expose individuals to radio frequency emissions which exceed FCC limits at distances closer than 1.2 meters (4 feet). Installation and maintenance personnel should refer to guidelines in training and user manuals to minimize exposure.
Antenna Specifications 19
All RF antennas must be 50 watts, with a minimum input and output return loss of 14 dB (VSWR less than 1.5:1) at the receive and transmit ports.
Lucent Technologies — ProprietarySee notice on first page
48 Issue 3 March 2000
FLEXENT™ CDMA MicrocellSite Preparation Guidelines
In-Building Antenna Considerations 19
There are often many rooms and hallways in any specific building. In order to achieve the best RF coverage in the building, the following items should be considered.
� Omni antennas are recommended for use in the middle of large conference rooms or auditoriums, and in the center of hallway intersections.
� High gain antennas that have 3-dB beamwidth less than, but close to, 180 degrees are recommended for use along the walls of large conference rooms or auditoriums, and at the ends of hallways.
� High gain antennas that have 3-dB beamwidth less than, but close to, 90 degrees are recommended to be used at a corner of a large conference room or auditorium.
� If several floors are to be covered by one antenna, it is recommended that an antenna with horizontal 3-dB beamwidth less than, but close to, 180 degrees be used. It should be noted that each concrete floor may provide another 10- to 15-dB wall loss to the free space propagation loss.
� Leaky coaxial radiators are recommended to provide RF coverage in elevator shafts or building connecting hallways.
Lucent Technologies — ProprietarySee notice on first page
Issue 3 March 2000 49
401-703-340
GPS Antenna Requirements 19
GPS Antenna Configuration 19
Each Flexent CDMA Microcell requires a GPS signal for synchronizing hand-offs with neighboring cell sites. The GPS antenna can be mounted directly on the microcell, or may be remotely located up to 145 meters (500 feet) from the microcell. GPS repeater amplifiers may be required for the remotely located antenna option. The 1/2-inch foam dielectric has a loss of 4.5-dB/100 feet at 1500 Hz.
When multiple microcells are collocated at a cell site, one GPS antenna can serve up to six microcells through the use of a 1:3 or 1:6 splitter. A 1.2-meter (4 feet) and 9.1-meter (30 feet) cable kit is available to connect the splitter to the microcell. Figure 20 shows three microcells sharing a single GPS antenna signal.
The GPS antenna requires +5 VDC and receives it from the first microcell that it is serving.
Figure 20 GPS Antenna Serving Three Flexent™ CDMA Microcells
Lucent Technologies — ProprietarySee notice on first page
50 Issue 3 March 2000
FLEXENT™ CDMA MicrocellSite Preparation Guidelines
Antenna Ordering Information 20
Table 16 lists the ordering information for the three types of GPS antennas.
Table 16 GPS Antennas
Recommended Cable Types 16
It is recommended that high-quality, low-loss cables be used for the GPS antenna connections. The cables should be outdoor (UV) as well as riser (fire-retardant) rated.
Table 17 lists the cable characteristics of two recommended cables.
Table 17 GPS Cable Characteristics
Code List Description
KS24019 112A 26 ± 3 dB gain GPS antenna
KS24019 116 40 ± 4 dB gain GPS antenna
KS24019 110A 50 ± 4 dB gain GPS antenna
KS 24019 115 Antenna mount
Manufacturer Cable P/N
Attenuation(dB/100 feet @
1.575 GHz)
DC Resistance (Ohms per 1000 feet)
Nominal Outer Diameter (inches)
Andrew FSJ4-RN-50B
4.8 1.82 0.53
Andrew LDF4-RN-50A
3.0 1.03 0.63
Lucent Technologies — ProprietarySee notice on first page
Issue 3 March 2000 51
401-703-340
Antenna Selection Based on Losses 17
The aggregate losses in cables, connectors, splitters and other hardware used to connect the GPS antenna to the microcell should be considered when selecting the GPS antenna.
Table 18 lists the aggregate losses and approximate allowable cable lengths for each type of antenna.
Table 18. Antenna Selection Data
GPS Antenna Installation 18
For detailed installation instructions for the GPS Antenna, refer to Base Station CDMA Reference Frequency Timing Generator and Antenna System Description, Operation, Installation and Maintenance (401-660-128).
Verify GPS Installation and Line of Sight 18
It is highly recommended that a Garmin 45XL (or equivalent) be used to verify the GPS antenna installation and line of sight prior to installing the Flexent CDMA Microcell.
Use Checklist SP-5 (Appendix A) to verify GPS antenna installation prior to beginning the microcell installation.
GPS Antenna KS24019
Nominal Antenna
Gain (dB)
TOTAL AllowableMinimum Loss (dB)
TOTAL Allowable Maximum Loss (dB)
Andrew Cable Type
ApproximateMinimum
Cable Length (feet)
Approximate Maximum
Cable Length (feet)
NominalCable
Length with 1:3 Splitter
(feet)
Worst Case Cable
Length with 1:3 Splitter (feet)
L112A 26 0.77 12 FSJ4 16 250 188 125
LDF4 25 400 300 200
L116 40 13.92 27.36 FSJ4 290 570 480 400
LDF4 470 1025 733 633
L110A 50 23.28 43.2 FSJ4 485 900 688 605
LDF4 765 1400 1100 966
Lucent Technologies — ProprietarySee notice on first page
52 Issue 3 March 2000
FLEXENT™ CDMA MicrocellSite Preparation Guidelines
T1/E1 Facilities Requirements 18
T1/E1 Input Lines 18 The Flexent CDMA Microcell communicates with the 5ESS DCS via a wideband channel called a packet pipe. A packet pipe carries packetized voice and data signals. The pipe consists of DS0 channels on a T1/E1 facility.
The Primary Distribution Cabinet (PDC) serves as the centralized connection point for interfacing all T1/E1 connections at the cell site. The Single PDC provides T1/E1 interface for one microcell and the Multiple PDC provides T1/E1 interfaces for up to three microcells.
For 75 ohm networks, the E1 facility terminates on the Network Interface Unit (NIU). The NIU provides a central point for converting E1 coaxial signaling to balanced signaling required by the microcell. The NIU also provides coaxial protection for two E1 transmit/receive circuits with expansion to four E1 circuits.
The NIU must be located within 6.1 meters (20 feet) of the PDC that it is serving. If an PDC is not used, the NIU must be located within 6.1 meters (20 feet) of the microcell that it is serving.
The Flexent CDMA Microcell accepts two T1 twisted wire pairs from the PDC (or equivalent). The T1 cable input lines should be in place prior to the start of the microcell or PDC installation.
The microcell utilizes one T1/E1 input pair if a dedicated T1/E1 facility is used, and a second facility connection is required for a daisy-chain application.
T1/E1 Daisy-Chaining 18
To make more efficient use of the digital facilities, customers may share a single DS1 facility over six microcells by daisy-chaining them together. The daisy-chaining of Flexent CDMA Microcells is done by running a full DS1 to the first microcell. The line interface unit within the first microcell receives the DS1, but also transmits it on to the next microcell in the chain.
Daisy-chaining can be used in applications where the microcells are closely located, such as a three-sector configuration, or where the microcells are used for in-building distribution and there are several cell sites located within the same building. The maximum distance between daisy-chained microcells without T1/E1 repeaters is 1735 meters (6000 feet).
Lucent Technologies — ProprietarySee notice on first page
Issue 3 March 2000 53
401-703-340
Verify T1/E1 Facilities18 Verification of the T1/E1 facilities can be performed using Checklist SP-1 found in Appendix A of this document.
Lucent Technologies — ProprietarySee notice on first page
54 Issue 3 March 2000
Lucent Technologies —See notice on fir
A
Site Preparation ChecklistsOverview
Purpose This section is for use by authorized personnel to verify completion of cell site preparation activities prior to installation of cell site equipment.
Contents Attached to this appendix are the following master sheets, from which copies should be made for each site preparation performed.
SP-GEN Cell Site General Information (1 page)
SP-1 Site Preparation General Checklist (1 page)
SP-2 Site Preparation Power Source Checklist (1 page)
SP-3 Site Preparation Grounding Checklist (3 pages)
SP-4 Site Preparation RF Antenna Checklist (1 page)
SP-5 Site Preparation GPS Antenna Checklist (2 pages)
SP-6 Site Preparation Punchlist Sheet (1 page)
SP-6A Punchlist Continuation Sheets (1 page)
Proprietaryst page
Issue 3 March 2000 A-1
Site Preparation Checklists
Lucent Technologies — ProprietarySee notice on first page
A-2 Issue 3 March 2000
Site Preparation Checklists
SP-GENCell Site General Information
Cell Site Name: MTA Name:
Cell Site Address: Cell Site #:
Cell Site AccessContact Name:
Contact Phone #and Pager #:
Lucent Technologies — ProprietarySee notice on first page
Issue 3 March 2000 A-3
Site Preparation Checklists
Lucent Technologies — ProprietarySee notice on first page
A-4 Issue 3 March 2000
Site Preparation Checklists
SP-1 Site Preparation General Checklist
Completed by:_____________________________ Date: _____________
Item# Description Yes No N/A Comment/Punchlist Issue #
1. Are all site permits complete? � � �
2. Has a Method of Procedure been developed and completed with the installation supervisor?
� � �
3. Are cell translations available? � � �
4. Has the installer cell site equipment parameter sheet been completed and reviewed with the installation supervisor?
� � �
5. Are the ECP/Switch and cell software generics compatible?
� � �
6. Is cell site T1/E1 demarcation point known?
� � �
7. Are T1/E1 facilities available and active? � � �
8. Is T1/E1 interface conduit in place at site?
� � �
9. Has all equipment been ordered and has delivery to site been scheduled?
� � �
10. Have all necessary arrangements been made for access to the site?
� � �
11. Have all necessary arrangements been made to get equipment onto the site?
� � �
Lucent Technologies — ProprietarySee notice on first page
Issue 3 March 2000 A-5
Site Preparation Checklists
Lucent Technologies — ProprietarySee notice on first page
A-6 Issue 3 March 2000
Site Preparation Checklists
SP-2 Site Preparation Power Source Checklist
Completed by:_____________________________ Date: _____________
Item # Description Yes No N/A Comment/Punchlist Issue #
1. Is AC service available? � � �
2. Have AC service and conduits been approved by local code?
� � �
3. Is AC service equipped with surge protection at service entry point?
� � �
4. Is AC power source nominal 208 or 240 VAC, single phase?
� � �
5. For indoor applications, has a Power Line Surge Protector been installed?
� � �
Lucent Technologies — ProprietarySee notice on first page
Issue 3 March 2000 A-7
Site Preparation Checklists
Lucent Technologies — ProprietarySee notice on first page
A-8 Issue 3 March 2000
Site Preparation Checklists
SP-3 Site Preparation Grounding Checklist
Item# Description Yes No N/A Comment/Punchlist Issue #
1 Is cell site resistance less than or equalto 10 ohms?
� � �
2. Have connections been provided to grounding electrode system?If yes, check all that apply:
� � �
�Via a buried ring ground and driven rod(s)
�Via a buried metallic & electrically continuous water pipe
�Via driven ground rod(s) and/or plate(s)
�Via electrolytic ground rod(s)
�Via grounded building steel
�Via grounded grid or radial
3. Is a lightning mast(s) or air terminal(s) provided and bonded?
� � �
4. Is antenna support structure(s) grounded?
� � �
5. Are antenna cable shields grounded at both ends?
� � �
6. If a tower is utilized and is greater than 200 feet high, are antenna cable shields grounded at mid-point and both ends?
� � �
7. Is antenna tower bonded to grounding electrode system?
� � �
8. Are guy wires bonded to grounding electrode system?
� � �
9. Is steel pole structure used as down conductor?
� � �
Lucent Technologies — ProprietarySee notice on first page
Issue 3 March 2000 A-9
Site Preparation Checklists
Lucent Technologies — ProprietarySee notice on first page
A-10 Issue 3 March 2000
Site Preparation Checklists
SP-3 Site Preparation Grounding Checklist (Continued)
Item# Description Yes No N/A Comment/Punchlist Issue #
10. Are all ground connections in compliance with Lucent requirements (exothermic weld, compression type with 2-hole lugs; properly secured; anti-oxidant used on contact surface area)?
� � �
11. Are grounding conductors routed as straight as possible with no loops or sharp bends?
� � �
12. Are metallic conduits bonded at both ends and 25-foot intervals?
� � �
13. Are all fence corner posts and gate posts properly grounded (including fence fabric and barbed wire, as applicable)?
� � �
14. Are all metallic objects within 6 feet bonded to the grounding electrode system?
� � �
15. Is AC power supply equipped with surge protection device and is the device properly connected to the grounding electrode system?
� � �
16. Is T1/E1 line equipped with surge protection device and is the device properly connected to the grounding electrode system?
� � �
17. Is tower light system (if installed) equipped with surge protection device and is the device properly connected to the grounding electrode system?
� � �
Lucent Technologies — ProprietarySee notice on first page
Issue 3 March 2000 A-11
Site Preparation Checklists
Lucent Technologies — ProprietarySee notice on first page
A-12 Issue 3 March 2000
Site Preparation Checklists
SP-3 Site Preparation Grounding Checklist (Continued)
Completed by:_____________________________ Date: _____________
Item# Description Yes No N/A Comment / Punchlist Issue #
18. Are antenna cable shields grounded prior to entering the building at the hatchplate?
� � �
19. Is surge protection installed on coaxial cable lines entering building?(not a requirement; good practice)
� � �
Lucent Technologies — ProprietarySee notice on first page
Issue 3 March 2000 A-13
Site Preparation Checklists
Lucent Technologies — ProprietarySee notice on first page
A-14 Issue 3 March 2000
Site Preparation Checklists
SP-4 Site Preparation RF Antenna Checklist
Item# Description Yes No N/A Comment/Punchlist Issue #
1. All antenna cable runs installed? � � �
2. All external cable connections weatherproofed?
� � �
3. All external insulated cables sunlight resistant?
� � �
4. Antenna cable run demarcation points in proper location?
� � �
5. Antenna cable runs marked and in proper sequence per applicable drawing?
� � �
6. Antenna and cable sweeps performed? � � �
7. Antennas properly installed and secured?
� � �
8. All antennas the proper type? � � �
9. Antennas at proper azimuth?(0, 120, or 240 degrees)
� � �
10. Antennas at proper height? � � �
Lucent Technologies — ProprietarySee notice on first page
Issue 3 March 2000 A-15
Site Preparation Checklists
Lucent Technologies — ProprietarySee notice on first page
A-16 Issue 3 March 2000
Site Preparation Checklists
SP-5 Site Preparation GPS Antenna Checklist
Item# Description Yes No N/A Comment / Punchlist Issue #
1. Antenna installed with base level within 2 degrees?
� � �
2. Antenna installed with less than 25% of the sky masked by obstruction?
� � �
3. GPS antenna located at least 1.22 meters (4 feet) vertically and horizontally from any transmitter
� � �
4. Aggregate cable loss, cable VSWR, total cable length, cable type, GPS antenna gain, KS-list and serial numbers recorded in the site installation records?
� � �
5. Proper gain antenna installed for the total aggregate cable loss and length?
� � �
6. Measured cable VSWR within its specified value?
� � �
7. GPS antenna cable properly grounded near antenna and at microcell (outdoor) or at hatchplate (indoor)?
� � �
8. Cable connections torqued to the appropriate value?
� � �
9. All external cable connections weatherproofed (except connector at antenna)?
� � �
10. All external cables UV rated? � � �
Lucent Technologies — ProprietarySee notice on first page
Issue 3 March 2000 A-17
Site Preparation Checklists
Lucent Technologies — ProprietarySee notice on first page
A-18 Issue 3 March 2000
Site Preparation Checklists
SP-5 Site Preparation GPS Antenna Checklist (Continued)
Completed by:_____________________________ Date: _____________
Item# Description Yes No N/A Comment/Punchlist Issue #
11. Antenna bracket, pipes and antenna properly secured?
� � �
12. GPS antenna location verified for line of sight using a Garmin 45XLS test unit or equivalent?
� � �
13. GPS antenna location free of external interference (i.e., radio stations,collocated equipment, etc.)?
� � �
Lucent Technologies — ProprietarySee notice on first page
Issue 3 March 2000 A-19
Site Preparation Checklists
Lucent Technologies — ProprietarySee notice on first page
A-20 Issue 3 March 2000
Site Preparation Checklists
SP-6Site Preparation Punchlist Sheet
Severity Column Definitions:
1. Equipment installation cannot occur until outage is rectified and will void warranty or potentially cause personal injury.
2. Equipment installation can occur but issue must be rectified prior to handoff to customer or service turn-up so that warranty is not voided.
3. Equipment installation, handoff to customer, or service turn-up can occur but not per Lucent recommendations.
Inspection Checklist Completion Sign-off
Check here if continuation sheet used �
Item# Comment/Description
Severity(1/2/3)
Corrective Action Required
(Y/N)Completed
(Date)
Lucent Technologies — ProprietarySee notice on first page
Issue 3 March 2000 A-21
Site Preparation Checklists
Inspector’s Name: Inspector’s Function:
Inspector’s Signature: Date:
Lucent Technologies — ProprietarySee notice on first page
A-22 Issue 3 March 2000
Site Preparation Checklists
SP-6ASite Preparation Punchlist Continuation Sheet
Item# Comment/Description
Severity(1/2/3)
CorrectiveAction Required
(y/n)Comp.Date
Lucent Technologies — ProprietarySee notice on first page
Issue 3 March 2000 A-23
Site Preparation Checklists
Lucent Technologies — ProprietarySee notice on first page
A-24 Issue 3 March 2000
Lucent Technologies —See notice on fir
B
Cell Site InformationOverview
Purpose This section is for use by Customer Project Management to document cell site configuration information.
Contents Attached to this appendix are the following master sheets, from which copies should be made for each site preparation performed.
CSC-1 Cell Site Configuration Information (5 pages)
Proprietaryst page
Issue 3 March 2000 B-1
Cell Site Information
Lucent Technologies — ProprietarySee notice on first page
B-2 Issue 3 March 2000
Cell Site Information
CSC-1Cell Site Configuration Information
Completed by:_____________________________ Date: _____________
Cell Site Name: MTA Name:
Cell Site Address: Cell Site #:
Cell Site Access Contact Name:
Contact Phone # & Pager #:
Documentation & DrawingInformation Referenced
Document or DrawingNumber
Issue #
Lucent Installation Engineering Drawing(s)
Site Preparation Document
Base Station Power & Alarm Requirements
Base Station GPS Document
Base Station Cabinet Installation Manual
Lightning Protection and Grounding Guidelines
Installation Type (Check all that apply)
� Indoor � ControlledEnvironment
� Pole
� Outdoor � UncontrolledEnvironment
� Rooftop
� Wall_______________
� Other (Specify)_______________
Lucent Technologies — ProprietarySee notice on first page
Issue 3 March 2000 B-3
Cell Site Information
Lucent Technologies — ProprietarySee notice on first page
B-4 Issue 3 March 2000
Cell Site Information
lexx
_
__
CSC-1Cell Site Configuration Information (continued)
Earthquake Zone Rating: � Zone 1 �Zone 2 �Zone 3 �Zone 4
Completed by:_____________________________ Date: _____________
Flexent CDMA Microcell Cell Site Equipment
Radio Cabinet /Serial Number
________________________
Number of Sectors:�Omni�1�2
� Simp� Duple
# of Carriers (1-6) _______
GPS AntennaKS/Model ____________
Total GPS CableLength (ft) _________
GPS Antenna Gain(dB)
_______
Antenna Type: � External
�Integrated
Antenna Jumper Cable Type:
�N-to-N
�N-to-DIN
Power Backup Cabinet(Type)
_________
AC Generator ? � Yes�No
Lucent Technologies — ProprietarySee notice on first page
Issue 3 March 2000 B-5
Cell Site Information
Lucent Technologies — ProprietarySee notice on first page
B-6 Issue 3 March 2000
Cell Site Information
)
CSC-1Cell Site Configuration Information (continued)
Completed by:_____________________________ Date: _____________
Cell Site Grounding � Yes
� No
If yes, select all that apply:
� Buried ring ground and driven rods
� Buried metallic and electrically continuous water pipe� Down conductors (Quantity:___)� Electrolytic ground rod(s) (Quantity:___� Driven ground rod(s) (Quantity:___) � Grounded building steel
� Ground grid
� Ground radial(s) (Quantity:___)
Collocated non-PCS equipment
� Yes
� No
Existing grounding system:
� Single Point� Integrated
Ground Bus � Yes
� No
If Yes, quantity:________________
Lucent Technologies — ProprietarySee notice on first page
Issue 3 March 2000 B-7
Cell Site Information
Lucent Technologies — ProprietarySee notice on first page
B-8 Issue 3 March 2000
Lucent Technologies —See notice on fir
Glossary
Overview
Purpose This section provides a list of acronyms and abbreviations used in this document.
Proprietaryst page
Issue 3 March 2000 GL-1
Glossary
A Ampere(s) mVrms Millivolt Route Mean Square
AC Alternating Current NEC National Electric Code
ANSI American National Standards Institute NESC National Electric Safety Code
AWG American Wire Gauge NIU Network Interface Unit
BOCA Building Officials and Code Administrators OSP Outside Plant
C Celsius (or Centigrade) PBC Power Backup Cabinet
CDMA Code Division Multiple Access PCS Personal Communications Services
CFM Cubic feet per minute PCU Power Converter Unit
dB Decibel(s) PDC Primary Distribution Cabinet
DC Direct Current POTS Plain Old Telephone Service
DCS Digital Cellular Switch RCS Radio Cluster Server
ECP Executive Cellular Processor RF Radio Frequency
FCC Federal Communications Commission Rx Receive
GFCI Ground Fault Circuit Interrupter T1/E1 24-Channel Digital Carrier
GHz Gigahertz TFU Timing/Frequency Unit
GPS Global Positioning System Tx Transmit
HVAC Heating, Ventilation, Air Conditioning UBC Uniform Building Code
Hz Hertz UL Underwriters Laboratories
I/O Input/Output UPS Uninterruptible Power Supply
kG Kilogram(s) UV Ultraviolet
kW Kilowatt(s) VAC Volts Alternating Current
LNA Low Noise Amplifier VDC Volts Direct Current
MHz Megahertz VSWR Voltage Standing Wave Ratio
m Meter(s) W Watt(s)
mm Millimeter(s)
MOP Method of Procedure
mVp-p Millivolt Peak-to-Peak
Lucent Technologies — ProprietarySee notice on first page
GL-2 Issue 3 March 2000