106
Lucent Technologies — Proprietary This document contains proprietary information of Lucent Technologies and is not to be disclosed or used except in accordance with applicable agreements Copyright © 2000 Lucent Technologies Unpublished and Not for Publication All Rights Reserved Issue 3 March 2000 401-703-340 FLEXENT™ CDMA Microcell Site Preparation Guidelines

401-703-340Mo

Embed Size (px)

DESCRIPTION

modcell

Citation preview

Page 1: 401-703-340Mo

Issue 3March 2000

401-703-340

Lucent Technologies — Proprietary

This document contains proprietary information ofLucent Technologies and is not to be disclosed or used

except in accordance with applicable agreements

Copyright © 2000 Lucent TechnologiesUnpublished and Not for Publication

All Rights Reserved

FLEXENT™ CDMA Microcell

Site Preparation Guidelines

Page 2: 401-703-340Mo

Lucent Technologies — ProprietaryUse Pursuant to Company Instructions

This material is protected by the copyright and trade secret laws of the United States and other countries. It may not be reproduced, distributed or altered in any fashion by any entity, including other Lucent Technologies Business Units or Divisions, without the express written consent of the Customer Training and Information Products Organization.

For permission to reproduce or distribute please contact:

Product Development Manager 1-800-645-6759 (domestic); 1-317-322-6847 (international)

NoticeEvery effort was made to ensure that the information in this document was complete and accurate at the time of printing. However, information is subject to change.

TrademarksFLEXENT is a trademark of Lucent Technologies, Inc.PowerHouse is a trademark of Lucent Technologies, Inc.

Ordering InformationThe ordering number for this information product is 401-703-340. To order this document by phone, use one of the following numbers to contact the Lucent Technologies Customer Information Center.

Within the United States of America: 1-888-LUCENT8 (1-888-582-3688; Fax: 1-800-566-9568)

From Canada: +1-317-322-6619 (Fax +1-317-322-6359)

From Europe, the Middle East, and Africa: +1-317-322-6416 (Fax +1-317-322-6699)

From Asia, Central and South America, and the Caribbean and Pacific regions: +1-317-322-6411 (Fax +1-317-322-6699)

Support Telephone Numbers

Information Product Support NumberLucent Technologies provides a telephone number and contact person for you to report errors or to ask questions about the information in this document.

Technical Support Telephone NumberLucent Technologies provides a telephone number for technical assistance support from the Wireless Technical Support Center (WTSC). The support number is:

Developed by the Lucent Technologies Customer Training and Information Products Organization.

Rich Essick 1-336-727-3371(Fax 1-336-727-3132)

1-800-CALL-4NSC (1-800-225-4672)

Page 3: 401-703-340Mo

How Are We Doing?

Title

Iden

Luccan

1. P

2. P

oooooo

Ple

3. W

4. F

If w

Nam

Com

Add

Whe or F

: Flexent™ CDMA Microcell Site Preparation Guidelines

tification No. sue No ate

ent Technolo be of great v

lease rate th

lease check

Improve theImprove theImprove theInclude morAdd more eAdd more d

ase provide

hat did you

eel free to w

e may contac

e:

pany/Organ

ress:

n you have ax to: (336)-

Ease of Use

Clarity

Completeness

Accuracy

Organization

Appearance

Examples

Illustrations

Overall Satisfac

: Is401-703-340

gies welcomes your feedback on this Infoalue in helping us improve our IPs.

e effectiveness of this IP in the following

the ways you feel we could improve this

overview/introduction o Make it mo table of contents o Add more s organization o Add more te figures o Make it lesxamples o Add more/betail o Improve th

details for the suggested improvement.

like most about this IP?

rite any comments below or on an attach

t you concerning your comments, please

T

ization:

completed this form, please fold, tape and727-3132.

Excellent Good

tion

.: D3

rmation Product (IP

areas:

IP.

re concise/brieftep-by-step procedroubleshooting infos technicaletter quick referenc

e index

ed sheet.

complete the follow

elephone Number:

Date

return to address o

Fair

Poo

: March 2000

). Your comments

ures/tutorialsrmation

e aids

ing:

:

n back

r Not

Applicable

////////////////////////////////////

//////////////////

//////////////////

//////////////////

//////////////////

//////////////////

Page 4: 401-703-340Mo

BUSINESS REPLY MAILFIRST CLASS PERMIT NO. 1999 GREENSBORO, NC

POSTAGE WILL BE PAID BY ADDRESSEE

NO POSTAGENECESSARY

IF MAILEDIN THE

UNITED STATES

---------------------------------------------------------- Do Not Cut — Fold Here And Tape --------------------------------------------------------------------

DOCUMENTATION SERVICES2400 Reynolda RoadWinston-Salem, NC 27199-2029

Page 5: 401-703-340Mo

Contents

� About this Information Product ix

Reason for Reissue ix

Purpose ix

Scope x

Safety Labels xi

Related Documentation xii

Site Preparation Checklists xiii

Cell Site Configuration Sheets xiii

� Equipment Overview 1

Flexent™ CDMA Microcell 1

Primary Distribution Cabinet (Optional) 2

Network Interface Unit (Optional) 4

Power Backup Cabinet (Optional) 5

Metric Hardware 5

� Microcell Antenna Architecture and Configurations 6

Architecture 6

Configurations 6

� Environmental Requirements 9

Overview 9

Heat Dissipation 9

Minimum Clearances 9

Operational Outdoor Environmental Requirements 10

Operational Indoor Environmental Requirements 11

� Cell Site Equipment Installation Options 12

Mounting Requirements and Guidelines 12

Microcell Mounting Configurations 12

PDC Mounting Configurations 12

� Typical Mounting Configurations 13

Single-Sector Pole- Mounted Configuration 13

Two-Sector Integrated Antenna Pole-Mounted Configuration 14

Three-Sector Pole- Mounted Configuration 15

Pole Mounting Bracket Layout 16

Lucent Technologies — ProprietarySee notice on first page

Issue 3 March 2000 i

Page 6: 401-703-340Mo

Contents

Single-Sector Wall- Mounted Configuration 17

Three-Sector Wall- Mounted Configuration 19

Floor Stand Configuration 21

Floor Stand Anchor Hole Layout 22

� Outdoor Installation Physical Requirements 23

� Indoor Installation Physical Requirements 24

� Installation Equipment and Material Required for Site Preparation 25

� AC Power Requirements 26

General Requirements 26

AC Input Scenarios 26

AC Input Requirements 26

Main Circuit Breaker Requirement 27

� DC Power Requirements 28

General Requirements 28

DC Regulation and Operating Conditions 28

DC Cable Feeders 28

Lightning Surge Protection 29

Grounding of DC Return Conductors 29

� PDC and PBC Power Support Considerations 30

� Use of a PDC Equivalent 31

General 31

Power Requirements 31

PDC Equivalent Requirements 32

T1/E1 Lightning Protection 32

AC Lightning Protection 32

� No PDC Configuration 33

General 33

Surge and Lightning Protection 33

Metallic Conduits 34

Power Requirements 34

Power Cables 35

Connection of AC Power Cables in Microcell 36

Lucent Technologies — ProprietarySee notice on first page

ii Issue 3 March 2000

Page 7: 401-703-340Mo

Contents

Connection of DC Power Cables in Microcell 37

Microcell Input/Output Cables 38

� Use of a PBC Equivalent 41

General 41

PBC Equivalent Requirements for AC Power 41

PBC Equivalent Requirements for DC Power 41

� Grounding and Lightning Protection Bonding Requirements 42

General 42

Grounding Equipment 43

Grounding of Metal Pole 43

Wooden Pole Grounding Configuration 44

Metal Pole Grounding Configuration 45

Wall-Mounted Grounding Configuration 46

� Antenna Interface Requirements 47

General Requirements 47

� RF Antenna Requirements 48

Mounting Options 48

Integrated Antenna Restrictions for Cellular CDMA 48

Antenna Specifications 48

In-Building Antenna Considerations 49

� GPS Antenna Requirements 50

GPS Antenna Configuration 50

Antenna Ordering Information 51

Recommended Cable Types 51

Antenna Selection Based on Losses 52

GPS Antenna Installation 52

Verify GPS Installation and Line of Sight 52

� T1/E1 Facilities Requirements 53

T1/E1 Input Lines 53

T1/E1 Daisy-Chaining 53

Verify T1/E1 Facilities 54

Lucent Technologies — ProprietarySee notice on first page

Issue 3 March 2000 iii

Page 8: 401-703-340Mo

Contents

Appendix A Site Preparation Checklists� Overview A-1

Purpose A-1

Contents A-1

� SP-GEN Cell Site General Information A-3

� SP-1 Site Preparation General Checklist A-5

� SP-2 Site Preparation Power Source Checklist A-7

� SP-3 Site Preparation Grounding Checklist A-9

� SP-4 Site Preparation RF Antenna Checklist A-15

� SP-5 Site Preparation GPS Antenna Checklist A-17

� SP-6 Site Preparation Punchlist Sheet A-21

� SP-6A Site Preparation Punchlist Continuation Sheet A-23

Appendix B Cell Site Information

� Overview B-1

Purpose B-1

Contents B-1

� CSC-1 Cell Site Configuration Information B-3

Glossary

Lucent Technologies — ProprietarySee notice on first page

iv Issue 3 March 2000

Page 9: 401-703-340Mo

Figures

1. Flexent CDMA Microcell with Dimensions and Weight 12. Single and Multiple PDC with Dimensions and Weight 33. Single-Sector Flexent CDMA Microcell Configuration 74. Two-Sector Directional Antenna Flexent CDMA

Microcell Configuration 85. Three-Sector Directional Antenna Flexent CDMA

Microcell Configuration 86. Typical Single-Sector Pole-Mounted Configuration 137. Typical Two-Sector Integrated Antenna Pole-Mounted Configuration 148. Typical Three-Sector Pole-Mounted Configuration 159. Typical Pole Mounting Bracket Layout 1610. Typical Single-Sector Wall-Mounted Configuration 1711. Layout for Typical Single-Sector

Wall-Mounted Configuration 1812. Typical Three-Sector Wall-Mounted Configuration 1913. Layout for Typical Three-Sector

Wall-Mounted Configuration 2014. Fully Configured Floor Stand 2115. Floor Stand Anchor Hole Layout 2216. I/O Protection Module Cable Connections 3817. Typical Wooden Pole Installation Grounding Configuration4418. Typical Metal Pole Installation Grounding Configuration 4519. Typical Wall-Mounted Installation Grounding Configuration4620. GPS Antenna Serving Three Flexent CDMA Microcells 50

Lucent Technologies — ProprietarySee notice on first page

Issue 3 March 2000 v

Page 10: 401-703-340Mo

Figures

Lucent Technologies — ProprietarySee notice on first page

vi Issue 3 March 2000

Page 11: 401-703-340Mo

Tables

1. On-Line Power PBC Information 52. Flexent CDMA Microcell Configuration Options 63. Flexent CDMA Microcell and Ancillary Cabinet

Heat Dissipation 94. Minimum Clearances for Indoor Application 95. Outdoor Environmental Requirements 106. Indoor Environmental Requirements 117. AC Input Power Requirements 278. Flexent CDMA Microcell AC Power Requirements 319. Circuit Breakers for Microcell 3110. Protector Characteristics 3211. AC Surge Arrestor Electrical Characteristics 3312. Power Cable Information 3513. I/O Cable and Connector Information 3814. I/O Connector Pin Information 3915. GPS Antennas 5116. GPS Cable Characteristics 5117. Antenna Selection Data 52

Lucent Technologies — ProprietarySee notice on first page

Issue 3 March 2000 vii

Page 12: 401-703-340Mo

Tables

Lucent Technologies — ProprietarySee notice on first page

viii Issue 3 March 2000

Page 13: 401-703-340Mo

Lucent Technologies —See notice on fir

About this Information Product 0

Purpose 0 This document describes basic site requirements that can be used to plan a Flexent™ CDMA Microcell site. It also details the specific tasks that must be completed at the job site before the installation of a microcell can begin. For information on site requirements for the international version of this equipment, refer to FLEXENT™ CDMA Microcell Site Preparation Guidelines (International) (401-703-352).

Reason for Reissue 0 This document is being reissued to update outdoor environmental requirements for the Flexent™ CDMA Microcell and backup times for the Power Backup Cabinet (PBC).

Proprietaryst page

Issue 3 March 2000 ix

Page 14: 401-703-340Mo

401-703-340

Scope 0 This document provides the following information:

� An overview of microcell architecture and configuration

� Environmental and physical requirements for the cell site

� Cell site equipment installation options

� Typical mounting configurations

� Tools and equipment required for site preparation

� Outdoor installation physical requirements

� Indoor installation physical requirements

� Power requirements

� Grounding and lightning protection requirements

� Antenna interface requirements and information

� T1/E1 facility requirements

� Site preparation checklist

� Cell site configuration sheets

Lucent Technologies — ProprietarySee notice on first page

x Issue 3 March 2000

Page 15: 401-703-340Mo

About this Information Product

Safety Labels 0 Various safety labels and cautionary sttements appear on the equipment covered in this information product. Definition of three types of safety labels are as follows:

! DANGER:Indicates the presence of a hazard that will cause death or severe personal injury if the hazard is not avoided.

! WARNING:Indicates the presence of a hazard that will or can cause death or severe personal injury if the hazard is not avoided.

! CAUTION:Indicates the presence of a hazard that will or can cause minor personal injury or property damage if the hazard is not avoided.

Lucent Technologies — ProprietarySee notice on first page

Issue 3 March 2000 xi

Page 16: 401-703-340Mo

401-703-340

Related Documentation 0

Cell site planners and site preparation personnel must have the appropriate reference materials as outlined below: i

Document Number Title

NFPA 70 National Electric Code

NFPA 780 Standard for Installation of Lightning Protection Systems

NESC 1943-1990 National Electric Safety Code

UL 50 Underwriters Laboratories Publication #50

UL 1950 Underwriters Laboratories Publication #1950

UL 1778 Underwriters Laboratories Publication, Uninterruptible Power Supplies and Rectifying Equipment and Specialty Transformers

IEEE/ANSI C62.41 IEEE Recommended Practice on Surge Voltages in Low-voltage AC Power Circuits

Lucent Technologies 401-200-115

Grounding and Lightning Protection Guidelines for Lucent Technologies Network Wireless System Cell Sites

Lucent TechnologiesED-3R128-10

Flexent™ Microcell Cabinet Installation Requirements

Lucent Technologies401-703-341

Flexent™ CDMA Microcell Installation Manual

Lucent Technologies401-660-128

Base Station CDMA Reference Frequency Timing Generator and Antenna System Description, Operation, Installation and Maintenance

AT&T900-200-318

Outside Plant Engineering Handbook

CSA-CEC Canadian Standards Association, Part 1, 1998

BellcoreGR-63

Core Section 4.1.2 Environmental Requirements

Lucent Technologies — ProprietarySee notice on first page

xii Issue 3 March 2000

Page 17: 401-703-340Mo

About this Information Product

Site Preparation Checklists 0

It is highly recommended that the completion of all site preparation activities, as well as adherence to the guidelines, be verified prior to installing the microcell equipment and the associated ancillary hardware. Various checklists and a punchlist sheet have been provided in Appendix A of this document to aid customers and Lucent personnel during a cell site verification. The checklists can be used and should be completed during the Cell Site Method of Procedure (MOP) walk-through prior to equipment installation.

Utilization of the checklists will help to ensure a quality installation and provide a cell site history file for later reference during capacity growth, etc. The punchlist can be used to track the completion of any outstanding site preparation items, and aid in project managing installation resources.

Cell Site Configuration Sheets 0

Cell site configuration sheets have been provided in Appendix B of this document to aid the customer, Equipment Engineering and Wireless Project Management during the various stages of product deployment. The configuration sheets can be used to document the cell site equipment configuration, conditions and other pertinent information for reference during the product deployment, and later addition of microcells and ancillary equipment. The sheets should be completed during the equipment engineering phase. Reference to this information during the Cell Site MOP walk-through is often helpful in completing the site preparation checklists.

Lucent Technologies — ProprietarySee notice on first page

Issue 3 March 2000 xiii

Page 18: 401-703-340Mo

401-703-340

Lucent Technologies — ProprietarySee notice on first page

xiv Issue 3 March 2000

Page 19: 401-703-340Mo

FLEXENT™ CDMA MicrocellSite Preparation Guidelines

Equipment Overview 0

Flexent™ CDMA Microcell 0

The Flexent CDMA Microcell is a compact, self-contained unit, suitable for indoor and outdoor operation, that can be mounted on a pole, solid concrete wall or floor stand.

The CDMA Microcell implements the requirements for the air interface as found in IS-95A and IS-97A (cellular band), and ANSI J-STD-008 and J-STD-019 (PCS band).

Figure 1 shows the Flexent CDMA Microcell, along with its dimensions and weight.

Figure 1. Flexent™ CDMA Microcell with Dimensions and Weight

5 00 M M (1 9.55 IN )

930

MM

(3

6.56

IN)

2 80 M M (11 IN )

W E IG H T = 54 .5 4 K G (12 0 LB S .)

)

)

)

Lucent Technologies — ProprietarySee notice on first page

Issue 3 March 2000 1

Page 20: 401-703-340Mo

401-703-340

Primary Distribution Cabinet (Optional) 0

The Primary Distribution Cabinet (PDC) is an optional cabinet that provides a centralized point of demarcation for the various interfaces into and out of the microcell. It contains the components and interfaces necessary to properly connect customer-owned/maintained (and outside service provider-owned/maintained) equipment to the microcell cabinet.

There are two types of PDCs:

� Single PDC (supports one microcell)

� Multiple PDC (supports up to three microcells)

The following interfaces are provided by the PDC:

� AC utility power

� Peripheral bus

� T1/E1 facilities

� POTS line

� External alarm relay contacts

� Maintenance and test ports

� AC generator

� External power backup

To ensure surge protection operation, the PDC must be located within 14.5 meters (50 feet) of the microcell(s) it is serving.

For safety reasons, the PDC should be located within view of the microcell(s) it is serving. If the PDC is not in view of the microcell(s) it is serving, it must be equipped with a circuit breaker lock-out/tag-out feature.

If the PDC is located more than 2.9 meters (10 feet) from the microcell(s) it is serving, a customer-supplied duplex convenience outlet must be provided within 2.9 meters (10 feet) of the microcell.

If a Lucent Technologies PDC is not utilized, refer to page 31 of this document for PDC equivalent requirements.

Lucent Technologies — ProprietarySee notice on first page

2 Issue 3 March 2000

Page 21: 401-703-340Mo

FLEXENT™ CDMA MicrocellSite Preparation Guidelines

Figure 2 shows the Single PDC and Multiple PDC with dimensions and weights.

Figure 2. Single and Multiple PDC with Dimensions and Weight

440m m (17.17")

540m

m (

21.1

8")

2 4 0m m (9.3 6 ")

540m m (21 .17")

640

mm

(25

.18"

)

2 4 0m m (9.3 6 ")

SING LE PR IM ARYDISTR IB UTIO N C AB IN ET

M ULT IPL E PRIMA RYDISTR IB UTIO N C AB IN ET

(FRO NT V IE W ) (S IDE V IE W ) (FRO NT V IE W ) (S IDE V IE W )

SINGLE PDC WEIGHT = 12.27 KG (27 LBS) MULTIPLE PDC WEIGHT = 19.32 KG (42.5 LBS)

)

Lucent Technologies — ProprietarySee notice on first page

Issue 3 March 2000 3

Page 22: 401-703-340Mo

401-703-340

Network Interface Unit (Optional) 0

The Network Interface Unit (NIU) provides a central point for converting E1 coaxial signaling to balanced signaling required by the microcell. The conversion is from 75-ohm unbalanced to 120-ohm balanced cabling. The NIU also provides coaxial protection for two E1 transmit/receive circuits with expansion to four E1 circuits.

The NIU must be located within 6.1 meters (20 feet) of the PDC that it is serving. If a PDC is not used, the NIU must be located within 6.1 meters (20 feet) of the microcell that it is serving.

The dimensions of the NIU are 254 mm (height) x 254 mm (width) x 95 mm (depth) (10 inches x 10 inches x 3.75 inches).

Lucent Technologies — ProprietarySee notice on first page

4 Issue 3 March 2000

Page 23: 401-703-340Mo

FLEXENT™ CDMA MicrocellSite Preparation Guidelines

Power Backup Cabinet (Optional) 0

An optional internal battery is available for the Flexent CDMA Microcell that can provide backup power for ten seconds at full transmit power capability.

If the customer requires a longer power backup capability, Lucent Technologies recommends the use of a Power Backup Cabinet (PBC) from OnLine Power, Inc. The toll-free number for OnLine Power is 1-800-227-8899.

The PBC contains an Uninterruptible Power Supply (UPS) that conditions the utility power under normal operating conditions. If the power utility should fail, the PBC will maintain AC power to the microcell from its internal batteries via a converter. Table 1 provides information on the OnLine Power PBCs.

Table 1. OnLine Power PBC Information

Up to three PBCs can be mounted on a pole.

If another type of backup power cabinet will be used, the customer should refer to page 41 of this document.

Metric Hardware 1 All hardware associated with the Flexent CDMA Microcell is metric.

CabinetMicrocell

ConfigurationBackup Time

(Hours) Mounting

Height x Width x Depth Meters (Inches)

Weight kg

(lbs)

650-W UPS 1 microcell without heater

2.0 Pole, Pad .50 x .55 x .51(19.5 x 21.5 x 20)

154.5(340)

1.3-kW UPS

1 microcell without heater

4.0

Pole, Pad.50 x .55 x .51(19.5 x 21.5 x 20)

211.8(466)

1 microcell with heater

0.45

2 microcells without heater

1.6

3 microcells without heater

1.1

Lucent Technologies — ProprietarySee notice on first page

Issue 3 March 2000 5

Page 24: 401-703-340Mo

401-703-340

Microcell Antenna Architecture and Configurations 1

Architecture 1 The basic architecture of the Flexent CDMA Microcell provides one transmit path and two diversity receive paths for full duplex communication. The RF paths of the microcell can be configured in either simplex or duplex mode. In the simplex mode, each RF path requires an individual antenna. In the duplex mode, the transmit path and the first diversity receive path utilize a common antenna interface port. The second diversity receive path remains a simplex receive and utilizes an individual antenna interface port.

Configurations 1 The configuration options of the Flexent CDMA Microcell are driven by the requirements of the application that it is intended to serve. A combination of microcells can be deployed to provide various cell site configurations.

Table 2 shows the configurations that are supported.

Table 2. Flexent™ CDMA Microcell Configuration Options

* Requires 1:3 GPS splitter.

Number of Sectors

Number of Carriers

Number of Microcells

GPS Antennas Cell Site RF Antennas

Simplex Duplex

1 1 1 1 3 2

2 1 2 1* or 2 6 4

3 1 3 1* or 3 9 6

Lucent Technologies — ProprietarySee notice on first page

6 Issue 3 March 2000

Page 25: 401-703-340Mo

FLEXENT™ CDMA MicrocellSite Preparation Guidelines

The microcell supports the following antenna configurations:

� 3 ports simplex: Tx, Rx0 and Rx1 for diversity

� 2 ports: Tx/Rx0 duplex and Rx1 for diversity

� Built-in antenna, duplexed Tx and Rx dual polarization diversity

� No diversity receive for in-building applications

� Simulcast control and traffic for rural highway applications. (Simulcast refers to the transmission and reception of the same RF information on separate physical antenna faces. The purpose is to direct the capacity of a single microcell to a very specific coverage area.)

The most basic application of the Flexent CDMA Microcell is for a single carrier with an omni-directional or directional antenna.

Figure 3 illustrates the single-sector single-carrier configuration.

Figure 3. Single-Sector Flexent CDMA Microcell Configuration

Lucent Technologies — ProprietarySee notice on first page

Issue 3 March 2000 7

Page 26: 401-703-340Mo

401-703-340

Multiple microcells with directional antennas can be collocated and controlled by a single Radio Cluster Server (RCS) to form a sectorized cell site. Figure 4 and Figure 5 illustrate examples of this.

Figure 4. Two-Sector Directional Antenna Flexent CDMA Microcell Configuration

Figure 5. Three-Sector Directional Antenna Flexent CDMA Microcell Configuration

Lucent Technologies — ProprietarySee notice on first page

8 Issue 3 March 2000

Page 27: 401-703-340Mo

FLEXENT™ CDMA MicrocellSite Preparation Guidelines

Environmental Requirements 2

Overview 2 This section outlines the environmental requirements related to the installation and operation of the Flexent CDMA Microcell, Primary Distribution Cabinet (PDC) and Power Backup Cabinet (PBC).

Heat Dissipation 2 Table 3 lists heat dissipation for various Flexent CDMA Microcells, PDCs and PBCs.

Table 3. Flexent CDMA Microcell and Ancillary Cabinet Heat Dissipation

Minimum Clearances3 Table 4 lists the minimum clearances for a microcell installation. These clearances must be maintained to ensure that proper ventilation and access are provided for the equipment.

Table 4. Minimum Clearances for Indoor Application

CabinetHeat Energy Dissipated

(Watts)

Flexent CDMA Microcell with heater 1,020 average1,400 maximum

Flexent CDMA Microcell without heater 400

Single PDC 0

Multiple PDC 0

OnLine Power 650-W UPS 300

OnLine Power 1.3-kW UPS 350

BetweenMinimum Clearance

mm (Inches)

Top cap of microcell and ceiling 152 (6)

Bottom of microcell and floor or any bottom obstruction 152 (6)

Rear of microcell plenum and rear wall 76 (3)

Left side of microcell (side with door latches) and left wall 102 (4)

Right side of microcell and right wall or any right side obstruction

456 (18)

Lucent Technologies — ProprietarySee notice on first page

Issue 3 March 2000 9

Page 28: 401-703-340Mo

401-703-340

Operational Outdoor Environmental Requirements 4

Table 5 lists the operational outdoor environmental requirements of this equipment.

Table 5. Operational Outdoor Environmental Requirements

Parameter Specification

Ambient Operating Temperature

-40 to +52° C with no wind-30 to +52° with 10 MPH maximum wind-20 to +52° with 20 MPH maximum wind-10 to +52° with 30 MPH maximum wind

Operating Relative Humidity

5 to 95% non-condensing (for door open repair activity)

Solar Loading 70 W/square foot

Operating Altitude -290 M to +3,048 M(-1,000 to 10,000 feet), referenced to sea

level

Rate of Temperature Change (Operating)

30° C/hour

Lucent Technologies — ProprietarySee notice on first page

10 Issue 3 March 2000

Page 29: 401-703-340Mo

FLEXENT™ CDMA MicrocellSite Preparation Guidelines

Operational Indoor Environmental Requirements 5

The indoor/closet environment must be controlled within the limitations specified in Bellcore GR-63-Core Section 4.1.2. If the microcell is located in a closet or enclosure, there must be a minimum of 100 CFM of fresh air flow for each microcell.

Table 6 lists the operational indoor environmental requirements of this equipment.

Table 6. Operational Indoor Environmental Requirements

Note: Short term is defined as not more than 96 consecutive hours and a total of not more than 15 days per year.

Parameter Specification

Ambient Operating Temperature

0 to +46° C

Ambient Short Term Temperature

-5 to +50° C

Ambient Operating Relative Humidity

5% to 85%

Ambient Short Term Relative Humidity

5% to 90% not to exceed 0.124 kg water /kg air

Lucent Technologies — ProprietarySee notice on first page

Issue 3 March 2000 11

Page 30: 401-703-340Mo

401-703-340

Cell Site Equipment Installation Options6

Mounting Requirements and Guidelines 6

The Flexent CDMA Microcell and its associated equipment can be installed in several different mounting configurations. It cannot be installed in a hazardous environment as defined by NEC Article 500. The customer is responsible for engineering and safety requirements for collocating the microcell and its associated equipment with other utilities. All installations must comply with NESC 1943-1990 and local codes. The top of the microcell must be a minimum of 610 mm (2 feet) from the lowest utility wire. See NESC 1943-1990 and refer to local codes for complete mounting restrictions.

Detailed mounting requirements and guidelines can be found in FLEXENT™ Microcell Cabinet Installation Requirements (ED3R128-10).

Microcell and PDC Mounting Configurations 6

The following Flexent CDMA Microcell and PDC mounting configurations are supported:

� Pole-Mounted (pole diameters from 203 mm to 432 mm (8” to 17”))

� Single microcell

� Two microcells, evenly spaced 180° apart

� Three microcells, evenly spaced 120° apart

� Wall-Mounted on a solid concrete wall

� Floor Stand-Mounted

NOTE:Various building materials and construction methods dictate that the Flexent CDMA Microcell and its ancillary cabinets be fastened to the wall with appropriate mounting hardware. It is the responsibility of the customer to provide any necessary support material and structures to ensure that the installation will be in compliance with Building Officials and Code Administrators (BOCA), Uniform Building Code (UBC) and all local codes.

PBC Mounting Configurations 6

The following PBC mounting configurations are supported:

� Pole-Mounted (pole diameters from 203 mm to 432 mm (8” to 17”))

� Up to three PBCs can be mounted on a pole

� Floor Stand-Mounted

Lucent Technologies — ProprietarySee notice on first page

12 Issue 3 March 2000

Page 31: 401-703-340Mo

FLEXENT™ CDMA MicrocellSite Preparation Guidelines

Typical Mounting Configurations 6

Single-Sector Pole- Mounted Configuration 6

Figure 6 shows a typical single-sector pole-mounted configuration.

Figure 6. Typical Single-Sector Pole-Mounted Configuration

G PS AN TE N N A

EN C LO SU R E BR AC KET

FLEXEN T M IC R O C ELL C ABIN ET

SIN G LE PR IM ARY D ISTR IBU TIO N C ABIN ET

FIN ISH G R AD E O R TO P O F FO U N D ATIO N

R F AN TEN N A

T

T

Lucent Technologies — ProprietarySee notice on first page

Issue 3 March 2000 13

Page 32: 401-703-340Mo

401-703-340

Two-Sector Integrated Antenna Pole-Mounted Configuration 6

Figure 7 shows a typical two-sector integrated antenna pole-mounted configuration with two PBCs.

Figure 7. Typical Two-Sector Integrated Antenna Pole-Mounted Configuration

MICROCELL #2

PBC #2

MULTIPLEPDC

MICROCELL #1

PBC #1

Lucent Technologies — ProprietarySee notice on first page

14 Issue 3 March 2000

Page 33: 401-703-340Mo

FLEXENT™ CDMA MicrocellSite Preparation Guidelines

Three-Sector Pole- Mounted Configuration 6

Figure 8 shows a typical three-sector pole-mounted configuration.

Figure 8. Typical Three-Sector Pole-Mounted Configuration

Lucent Technologies — ProprietarySee notice on first page

Issue 3 March 2000 15

Page 34: 401-703-340Mo

401-703-340

Pole Mounting Bracket Layout 6

Figure 9 shows a typical layout for single-sector mounting brackets. The same measurements also apply to a three-sector application.

Figure 9. Typical Pole Mounting Bracket Layout

M

Lucent Technologies — ProprietarySee notice on first page

16 Issue 3 March 2000

Page 35: 401-703-340Mo

FLEXENT™ CDMA MicrocellSite Preparation Guidelines

Single-Sector Wall- Mounted Configuration 6

Figure 10 shows a typical single-sector wall-mounted configuration.

Figure 10. Typical Single-Sector Wall-Mounted Configuration

Lucent Technologies — ProprietarySee notice on first page

Issue 3 March 2000 17

Page 36: 401-703-340Mo

401-703-340

Figure 11 shows a typical single-sector layout for mounting a microcell and PDC on the wall of a building.

Figure 11. Layout for Typical Single-Sector Wall-Mounted Configuration

497 mm(19.56”)

470 mm(18.5”)

1.5 M (5 FT)

OR

15 M (49 FT)MAX

SPRING NUT SEPARATION83 mm (3.25”) TYP

SPRING NUT SEPARATION268 mm (14.5”)

GUIDELINES FOR STRUTSTO SUPPORTSINGLE PDC

GUIDELINES TOSUPPORT STRUTSFOR MICROCELL

Lucent Technologies — ProprietarySee notice on first page

18 Issue 3 March 2000

Page 37: 401-703-340Mo

FLEXENT™ CDMA MicrocellSite Preparation Guidelines

Three-Sector Wall- Mounted Configuration 6

Figure 12 shows a typical three-sector wall-mounted configuration.

Figure 12. Typical Three-Sector Wall-Mounted Configuration

2

1

Lucent Technologies — ProprietarySee notice on first page

Issue 3 March 2000 19

Page 38: 401-703-340Mo

401-703-340

Figure 13 shows a typical three-sector layout for mounting microcells and a Multiple PDC on the wall of a building.

Figure 13. Layout for Typical Three-Sector Wall-Mounted Configuration

GUIDELINES TOSUPPORT STRUTSFOR MICROCELL

GUIDELINES TOSUPPORT STRUTSFOR MULTIPLE PDC

572 mm(22.5”)

497 mm(19.56”)

1.21M (4 FT)MIN

MAX15M (49 FT)

SPRING NUT SEPARATION83 MM (3.25”) TYP

OR

1.5 M (5 FT)

15 M (49 FT)MAX

SPRING NUT SEPARATION470 mm (18.5”)

Lucent Technologies — ProprietarySee notice on first page

20 Issue 3 March 2000

Page 39: 401-703-340Mo

FLEXENT™ CDMA MicrocellSite Preparation Guidelines

Floor Stand Configuration 6

Figure 14 shows a fully configured floor stand with three microcells, an MPDC and a PBC.

Figure 14. Fully Configured Floor Stand

Lucent Technologies — ProprietarySee notice on first page

Issue 3 March 2000 21

Page 40: 401-703-340Mo

401-703-340

Floor Stand Anchor Hole Layout 6

Figure 15 shows the anchor hole layout for the floor stand.

Figure 15. Floor Stand Anchor Hole Layout

Lucent Technologies — ProprietarySee notice on first page

22 Issue 3 March 2000

Page 41: 401-703-340Mo

FLEXENT™ CDMA MicrocellSite Preparation Guidelines

Outdoor Installation Physical Requirements 6

For a typical outdoor cell site, the following requirements must be satisfied before installation of the Flexent CDMA Microcell and associated equipment can begin (see SP-1 through SP-5 in Appendix A).

� Adequate clearance provided around cabinets for service access and ventilation

� AC service installed

� DC power facilities installed (optional)

� External main circuit breaker and circuit breaker enclosure installed (always required in Canada, required in U.S. if PBC is utilized)

� T1/E1 facilities installed

� Grounding electrode system installed

� #2 AWG solid, bare, tinned copper ground wire bonded to grounding electrode system and coiled at bottom of pole or wall, or attached to pole or wall for temporary grounding of RF and GPS antenna cable shields

� RF and GPS antennas installed

� RF and GPS antenna runs installed (if required)

� RF and GPS antenna cable shields temporarily grounded

� Wall-mounted cabinet support structure installed (if required)

� Floor stand installed (if required)

� Concrete pad ready (if required for Power Backup Cabinet)

� Tower light power installed (if required)

� Tower light alarm installed (if required)

� Cell translations available

Lucent Technologies — ProprietarySee notice on first page

Issue 3 March 2000 23

Page 42: 401-703-340Mo

401-703-340

Indoor Installation Physical Requirements 6

For a typical indoor cell site, the following requirements must be satisfied before installation of the Flexent CDMA Microcell and associated equipment can begin (see SP-1 through SP-5 in Appendix A).

� Cable ducts installed

� All required room construction completed

� Cell site support structure installed

� HVAC and environmental control system installed

� Adequate clearance provided around cabinets for service access and ventilation

� AC service installed

� DC power facilities installed (optional)

� Power line surge protector installed

� External main circuit breaker and circuit breaker enclosure installed (always required in Canada, required in U.S. if PBC is utilized)

� T1/E1 facilities installed

� Grounding electrode system installed

� #2 AWG solid, bare, tinned copper ground wire bonded to grounding electrode system and coiled at wall, or attached to wall for temporary grounding of RF antenna cable shields

� RF and GPS antennas installed

� RF and GPS antenna runs installed (if required)

� RF and GPS antenna cable shields temporarily grounded

� Wall-mounted cabinet support structure installed (if required)

� Floor stand installed (if required)

� Tower light power installed (if required)

� Tower light alarm installed (if required)

� Cell translations available

Lucent Technologies — ProprietarySee notice on first page

24 Issue 3 March 2000

Page 43: 401-703-340Mo

FLEXENT™ CDMA MicrocellSite Preparation Guidelines

Installation Equipment and Material Required for Site Preparation 6

The equipment and materials required to install the Flexent CDMA Microcell mounting hardware and PDC are listed below.

� 32-tooth hack saw

� Insulation displacement tool

� Channel lock pliers

� Flat screwdriver

� Phillips screwdriver

� Open end wrenches (metric/standard)

� Ratchet set with extension (metric/standard)

� Two 16-foot ladders

� Gin boom

� Snatch block

� Rope

� Hoisting mechanism

� Four 1/4-inch anchor shackles (for lifting)

� Two 3-foot length chains for lifting (1/4-inch diameter welded link)

� Ground lug and C tap crimping tool

� Tape measure

� Chalk line

� Level

� Hammer

� Insulation stripping tool

� Drill

Lucent Technologies — ProprietarySee notice on first page

Issue 3 March 2000 25

Page 44: 401-703-340Mo

401-703-340

AC Power Requirements 6

GeneralRequirements 6

This section describes the AC power requirements for the Flexent CDMA Microcell and Primary Distribution Cabinet (PDC).

All AC wiring and over-current protection must be installed by a licensed electrician and must be provided in accordance with the National Electric Code (NFPA-70) and local electrical codes. An appropriate earth ground connection is required before commercial AC service can be connected.

It is the customer’s responsibility to make arrangements with the local power utility to install the necessary power service, power service entrance equipment and 1-inch PDC input conduit.

For indoor installations, the customer is responsible to provide a power line surge protector on the power input line.

See FLEXENT™ CDMA Microcell Installation Manual (401-703-341, Chapter 3) for detailed instructions on the installation of AC input cables.

AC Input Scenarios 6 The AC input cables can come to the PDC (or equivalent) from four sources:

� Power Backup Cabinet (PBC)

� Power company meter

� Power panel

� AC generator

AC Input Requirements 6

The PDC can have as input either 120/240 VAC, single phase, 60-Hz power or 120/208 VAC, single phase, 60-Hz power. If, however, the customer chooses to use a 120 VAC feed, Lucent Technologies must be consulted to evaluate the application on a case-by-case basis. The AC generator option and the Multiple PDC are not available when using a 120 VAC feed.

The 208/240 VAC input requirements for the PDC (or equivalent) are shown in Table 7.

Lucent Technologies — ProprietarySee notice on first page

26 Issue 3 March 2000

Page 45: 401-703-340Mo

FLEXENT™ CDMA MicrocellSite Preparation Guidelines

Table 7. AC Input Power Requirements

Main Circuit Breaker Requirement 7

If a PBC is utilized, the customer must provide an external main circuit breaker and circuit breaker enclosure located between the AC service meter and the PBC. The recommended equipment is a Square D main lug load center (part number QO2L70RB), and Square D circuit breaker (part number QO260). This is a type 3R weatherproof enclosure. Other manufacturers’ equivalent equipment is also acceptable.

In Canada, an external main circuit breaker and circuit breaker enclosure, as described above, are required for all applications. If a PBC is not utilized, the main circuit breaker and enclosure must be located between the AC service meter and the PDC.

Input Voltage 180 to 264 VAC, single phase, 3-wire, 60 Hz(208/240 VAC nominal)

Service 60 Amps

Wire 2 - 8 AWG copper only, 75°C temperature rating

Lucent Technologies — ProprietarySee notice on first page

Issue 3 March 2000 27

Page 46: 401-703-340Mo

401-703-340

DC Power Requirements 7

GeneralRequirements 7

The Flexent CDMA Microcell can be powered from a +24 VDC source. For this option, the microcell must be provided with an input voltage consistent with a standard +24 VDC battery plant. The maximum ripple and noise allowed on the +24 VDC input is 100 mVp-p from DC to 20 MHz, and 30 mVrms from DC to 20 MHz, measured at the output connector of the DC power source.

DC Regulation and Operating Conditions7

DC regulation and operating conditions are extremely important to ensure that the microcell is properly powered.

! CAUTION:In order to avoid damage to the microcell and ancillary equipment, a power plant should be carefully selected and the following operating conditions must be considered: regulation range, soft start, noise and ripple, transient load response, over-voltage shutdown and over-voltage surge protection.

DC Cable Feeders 7 The wire used for DC feeders must be rated for the environmental condition in which it is used.

DC wire feeders must be sized to limit the round-trip voltage drop between the power system output terminals and the microcell input terminals. The 24 VDC nominal must be present at the microcell terminals under normal conditions, and 20 VDC must be present at the microcell terminals under the most critical operating conditions. Therefore, the location and operating conditions of the DC power plant are extremely important to the operation of the microcell.

Lucent Technologies — ProprietarySee notice on first page

28 Issue 3 March 2000

Page 47: 401-703-340Mo

FLEXENT™ CDMA MicrocellSite Preparation Guidelines

Lightning Surge Protection 7

Lightning surge protection is required for outdoor configurations where the DC power source is located more than 7.6 meters (25 feet) from the microcell. Surge protectors must be provided and the DC feeders must be run in properly grounded metal conduit.

Lightning surge protection must be provided such that equipment shall not be degraded or damaged if the feeders are exposed to ten strikes of a surge of 500 V, 500 A 8 µsec/20 µsec pulse waveform.

If all of the cell site equipment and the DC power source are within the “zone of protection” of a higher metallic structure, surge protection on the DC feeders is not required. See Grounding and Lightning Protection Guidelines, Lucent Technologies Network Wireless System Cell Sites (401-200-115) to determine the “zone of protection”.

Grounding of DC Return Conductors 7

The DC return conductors must be bonded to the grounding electrode system at the output of the DC power source. Refer to Grounding and Lightning Protection Guidelines, Lucent Technologies Network Wireless System Cell Sites (401-200-115) for detailed grounding requirements.

Lucent Technologies — ProprietarySee notice on first page

Issue 3 March 2000 29

Page 48: 401-703-340Mo

401-703-340

PDC and PBC Power Support Considerations 7

7! CAUTION:

Caution must be taken when implementing PBC and PDC configurations.

� When the 650-W PBC is utilized to support one microcell, the heater circuit breaker (CB5) in the PDC must be in the OFF position and the heater wires must be permanently disconnected, since the 650-W PBC is designed to support one microcell without heaters.

� When the 1.3 kW PBC is utilized to support three microcells, the three heater circuit breakers (CB11, CB14, CB15) in the MPDC must be in the OFF position and the heater wires must be permanently disconnected, since the 1.3 kW PBC is designed to support three microcells without heaters.

Lucent Technologies — ProprietarySee notice on first page

30 Issue 3 March 2000

Page 49: 401-703-340Mo

FLEXENT™ CDMA MicrocellSite Preparation Guidelines

Use of a PDC Equivalent 7

General 7 The Lucent Technologies PDC is specifically designed as an interface to the Flexent CDMA Microcell. If another manufacturer’s PDC equivalent is used, the following guidelines must be followed.

Power Requirements 7 If another manufacturer’s PDC equivalent is used, it must provide power to the microcell in accordance with Table 8 over all input and output conditions including no load to full load, and low line to high line.

Table 8. Flexent™ CDMA Microcell AC Power Requirements

Table 10 lists the recommended circuit breakers for the microcell equipment.

Table 9. Circuit Breakers for Microcell

Voltage RangeFrequency

Range Nominal VoltageMaximum Current

85 - 130 VAC 57 - 63 Hz 120 VAC 16 A

180 - 264 VAC 57 - 63 Hz 240 VAC 8 A

20 - 30 VDC - 24 VDC 30 A

Type Voltage Equipment

RecommendedCircuitBreaker

AC 120 PCU 20 A

AC 120 Heaters 20 A

AC 240 PCU 20 A

DC 24 PCU 30 A

Lucent Technologies — ProprietarySee notice on first page

Issue 3 March 2000 31

Page 50: 401-703-340Mo

401-703-340

PDC Equivalent Requirements 9

If another manufacturer’s PDC equivalent is used, it must meet the following minimum requirements.

� The enclosure used to house the interface components must be rated a minimum of NEMA3R or UL50 type 3R.

� T1/E1 and AC surge protection must be properly provided per the guidelines listed below.

� A GFCI duplex convenience outlet is recommended.

� A generator inlet connector for backup power to the microcell is recommended.

� T1/E1 connection to the microcell I/O module J201 port must be provided via an RJ45 connector.

T1/E1 Lightning Protection 9

Lightning protection for the T1/E1 input and six user alarms must be provided when the PDC equivalent and microcell are located outside the cone of protection. A building protector block is recommended with 5-pin plug-in protectors, with the characteristics listed in Table 10.

Table 10. Protector Characteristics

Characteristic Value

DC breakover voltage @ 100 V/second > 265 V @ 20 mA

Impulse breakover voltage @ 100 V/microsecond

265 - 400 V

Insulation resistance @ 100 VDC > 100 MegaOhms

DC holdover, impulse 52.5 VDC/265 mA135 VDC/200 mA

On state voltage @ 100 A < 10 V

Rated impulse discharge 10 x 1000 microseconds 200 A

Capacitance > 200 pF

Operational temperature range -40 to 65° C

Balanced voltage limiting < 5 V

Lucent Technologies — ProprietarySee notice on first page

32 Issue 3 March 2000

Page 51: 401-703-340Mo

FLEXENT™ CDMA MicrocellSite Preparation Guidelines

AC Lightning Protection 10

Surge protection must be provided on the AC line to prevent damage to the equipment as defined in IEEE/ANSI C62.41, “IEEE Recommended Practice on Surge Voltages in Low-voltage AC Power Circuits”.

Typical AC surge arrestor electrical characteristics are shown in Table 11.

Table 11. AC Surge Arrestor Electrical Characteristics

Characteristic Value

Voltage Rating (120 VAC L-N) Up to 120/240 VAC

Frequency 60 Hz

Maximum Surge Current 40,000 A/phase

Maximum Energy Dissipation 600 Joules

Protection Modes Line-to-LineLine-to-NeutralLine-to-GroundNeutral-to-Ground

Operating Temperature -40 to 52 C

Lucent Technologies — ProprietarySee notice on first page

Issue 3 March 2000 33

Page 52: 401-703-340Mo

401-703-340

No PDC Configuration 11

General 11 The Lucent Technologies PDC is specifically designed as an interface to the Flexent CDMA Microcell. If a PDC is not used, the following guidelines must be followed.

Surge and Lightning Protection 11

Surge and lightning protection must be provided for all cables entering the microcell. Refer to “T1/E1 Lightning Protection” on page 32 and “AC Lightning Protection” on page 33.

Metallic Conduits 11 All cables entering the microcell must be run in metallic conduit such as Lucent Technologies 1-inch liquid-tight flexible steel conduit with built-in continuous copper ground or equivalent. The conduit must be grounded at both ends using surfaces that are paint-free and conductive. Power cables and I/O cables must be run in separate conduits.

Power Requirements11 If a PDC is not used, power must be provided to the microcell in accordance with Table 8 over all input and output conditions including no load to full load, and low line to high line.

Recommended circuit breakers for the microcell equipment are listed in Table 9.

Lucent Technologies — ProprietarySee notice on first page

34 Issue 3 March 2000

Page 53: 401-703-340Mo

FLEXENT™ CDMA MicrocellSite Preparation Guidelines

Power Cables 11 The customer-supplied cables required for the microcell Power Converter Unit (PCU) vary depending on the power source that is used (120 VAC, 240 VAC or +24 VDC).

One set of AC or DC power cables must be provided for the microcell PCU. A second set of AC cables is required if the microcell is equipped with heaters.

Table 12 provides power cable information.

Table 12. Power Cable Information

Input Usage Wire Color Connection

120 VAC, 2-wire PCU Black Line In

120 VAC, 2-wire PCU White Neutral

120 VAC, 2-wire PCU Green/Yellow Ground

120/240 VAC,3-wire

PCU Black Line 1 In

120/240 VAC,3-wire

PCU Red Line 2 In

120/240 VAC,3-wire

PCU Green/Yellow Ground

120 VAC Heater Black Line In

120 VAC Heater White Neutral

120 VAC Heater Green/Yellow Ground

+24 VDC PCU Red Feed

+24 VDC PCU Black Return

Lucent Technologies — ProprietarySee notice on first page

Issue 3 March 2000 35

Page 54: 401-703-340Mo

401-703-340

Connection of AC Power Cables in Microcell 12

The microcell AC power wires are pre-connected on the PCU and heaters (if used). They are coiled, tie-wrapped and tagged in the microcell junction box.

One set of black, white and green/yellow AC power wires is tagged “PCU”. If heaters are used in the microcell, a second set of black, white and green/yellow wires will be present and will be tagged “Heater”.

Perform the following steps to connect the customer-supplied AC power cables to the AC power wires in the microcell junction box.

Step Action

1 Strip the end of each AC cable to expose 13 mm (1/2 inch) of wire.

2 Connect the black AC cable labeled “PCU” to the black AC wire labeled “PCU - Line 1” in the junction box using a set screw connector. Tighten the screw on the set screw connector and screw the black insulator cap on the set screw.

3 If 120/240 VAC, 3-wire operation is used, connect the red AC cable labeled “PCU” to the white AC wire labeled “PCU-Line 2” in the junction box using a set screw connector. Tighten the screw on the set screw connector and screw the black insulator cap on the set screw.

4 If 120 VAC, 2-wire operation is used, connect the white AC cable labeled PCU to the white AC wire in the junction box using a set screw connector. Tighten the screw on the set screw connector and screw the black insulator cap on the set screw.

5 If heaters are used, connect each AC cable labeled “Heater” to the same color AC wire labeled “Heater” in the junction box using the set screw connector. Tighten the screw on the set screw connector and screw the black insulator cap on the set screw.

6 Connect the green cables to the ground lug in the junction box.

7 If the fan assembly is present, connect the three wires from it to the three fan assembly wires in the junction box.

Lucent Technologies — ProprietarySee notice on first page

36 Issue 3 March 2000

Page 55: 401-703-340Mo

FLEXENT™ CDMA MicrocellSite Preparation Guidelines

Connection of DC Power Cables in Microcell 12

A #6 AWG connectorized pigtail is provided in the junction box of the microcell for +24 VDC applications.

Perform the following steps to connect the customer-supplied DC power cables to the pigtail, and the pigtail to the microcell PCU.

Step Action

1 Strip the end of each DC cable to expose 13 mm (1/2 inch) of wire.

2 Remove the insulating cap from the end of the #6 AWG pigtail and strip the end of each pigtail wire to expose 13 mm (1/2 inch) of wire.

3 Using an H-tap parallel connector kit, connect each DC cable to the same color wire of the pigtail and apply an insulating material over the connections.

4 Plug the connectorized end of the pigtail into the PCU DC connector.

Lucent Technologies — ProprietarySee notice on first page

Issue 3 March 2000 37

Page 56: 401-703-340Mo

401-703-340

Microcell Input/Output Cables12

There are seven I/O cables that connect to the I/O protection module in the microcell. The I/O cables must be connectorized on the end that terminates in the microcell.

Table 14 shows I/O cable and connector information.

Table 14. I/O Cable and Connector Information

The I/O protection module is labeled with the connector reference designation of each cable as shown in Figure 16.

Figure 16. I/O Protection Module Cable Connections

Connector Reference Connector Type Function

J201 RJ-48C/(jack) Input, Primary T1/E1

J202 RJ-48C/(jack) Input, Secondary T1/E1

J203 RJ-45/(jack) Input, Maintenance Port

J204 RJ-11/(jack) Input, Voice

J205 DB-15/(jack) Input, Alarms

J207 RJ-45/(jack) Input, Peripheral Bus

J210 DB-9/(jack) Input, CDMA Test Port

Lucent Technologies — ProprietarySee notice on first page

38 Issue 3 March 2000

Page 57: 401-703-340Mo

FLEXENT™ CDMA MicrocellSite Preparation Guidelines

Connectors must be wired on the microcell-end of the I/O cables as shown in Table 15.

Table 15. I/O Connector Pin Information

ConnectorConnector

TypePin Numbers

(Input or Output)FunctionalDescription

J201(Category 5

shieldedcable

required)

RJ-48C

5 (output) T1/E1 1TTIP

4 (output) T1/E1 1TRING

2 (input) T1/E1 1RTIP

1 (input) T1/E1 1RRING

J202(Category 5

shielded cable

required)

RJ-48C

5 (output) T1/E1 2TTIP

4 (output) T1/E1 2TRING

2 (input) T1/E1 2RTIP

1 (input) T1/E1 2RRING

J203 RJ-45

1 (output) METH TX(+)

2 (output) METH TX(-)

3 (input) METH RX(+)

6 (input) METH RX(-)

J204 RJ-114 (bi-directional) VTIP

3 (bi-directional) VRING

J205 DB-15

1 (input) ALARM1

3 (input) ALARM2

5 (input) ALARM3

7 (input) ALARM4

9 (input) ALARM5

11 (input) ALARM6

2, 4, 6, 8, 10, 12 FRM GND

J207 RJ-45

3 ARCNET(+)

5 (bi-directional) ARCNET(-)

4 (bi-directional) VTIP

Lucent Technologies — ProprietarySee notice on first page

Issue 3 March 2000 39

Page 58: 401-703-340Mo

401-703-340

Table 15. I/O Connector Pin Information (Continued)

ConnectorConnector

TypePin Numbers

(Input or Output)FunctionalDescription

J210 DB-9

1(output) TFU RHO 10

2(output) 5 VD

3(output) TRU RHO EV

4(output) DEBUGON

5(output) TFU RHO 19

6(output) DGRD

7(output) DGRD

8(output) DGRD

9(output) DGRD

Lucent Technologies — ProprietarySee notice on first page

40 Issue 3 March 2000

Page 59: 401-703-340Mo

FLEXENT™ CDMA MicrocellSite Preparation Guidelines

Use of a PBC Equivalent 15

General 15 Lucent Technologies recommends the use of a Power Backup Cabinet (PBC) from OnLine Power, Inc. If another manufacturer’s PBC equivalent is used, the following guidelines must be followed.

PBC Equivalent Requirements for AC Power 15

If another manufacturer’s PBC equivalent is used in an AC power scenario, it must meet the following minimum requirements.

� The enclosure used to house the power backup components must be rated a minimum of NEMA3R or UL50 type 3R.

� The PBC unit must deliver power values as specified in Table 8 on page 31.

� The operating temperature range of the cabinet must be from -40° to 52° C.

� The output voltage range must be from 85 to 130 volts at 120 VAC nominal, and 180 to 264 volts at 240 VAC nominal.

� The output frequency must be from 57 Hz to 63 Hz at 60 Hz nominal.

� The AC power surge protector must be protected in accordance with C62.41-1991 category C3. The cabinet must be approved by the appropriate safety agency for deployment.

� The cabinet must meet Class B emission requirements of 47CFR, part 15, subpart B.

� The cabinet must be connected ahead of the PDC or PDC equivalent when it is supporting one microcell with or without heaters, or three microcells without heaters.

� The customer must size the cable feeds between the AC source and the microcell to minimize voltage drops.

PBC Equivalent Requirements for DC Power 15

If another manufacturer’s PBC equivalent is used in a DC power scenario, the following requirements must be met.

� AC input is required to feed the charging device for the batteries.

� The DC output must be 24 VDC nominal at the terminals of the microcell.

� The customer must size the cable feeds between the DC source and the microcell to minimize voltage drops.

Lucent Technologies — ProprietarySee notice on first page

Issue 3 March 2000 41

Page 60: 401-703-340Mo

401-703-340

Grounding and Lightning Protection Bonding Requirements 15

General 15 Flexent CDMA Microcell sites are susceptible to lightning surges due to their association with poles and antennas. Therefore, it is imperative that the cell site be properly grounded and that a low impedance path to earth be provided. The grounding conductors must be as straight and short as possible. No sharp bends or loops are permitted in grounding conductors.

Commercial AC power and T1/E1 facilities are particularly susceptible to lightning surges and must be properly protected. An appropriate surge protection device must be installed at the service entry point and be connected directly to the grounding electrode system.

The antenna cable shield must be bonded at the top and bottom of the vertical run, and also where it comes near the equipment. The metallic support for the antenna must also be bonded to the grounding system. In indoor applications, the antenna cable shield must also be bonded at the hatchplate before entering the building.

All metallic objects within 1.75 meters (6 feet) of the grounded equipment must be bonded to the grounding system.

All Flexent CDMA Microcell sites must be equipped with one or more grounding electrode systems (e.g., buried ring ground, copper clad rod, electrolytic rods, metallic water pipe, etc.). The cell site grounding, including all cabinets and antenna cable shields, must be bonded to the grounding electrode system. It is recommended that two separate, low impedance paths to earth be provided to bond together all grounding systems.

Buried ground conductors must be, as a minimum, #2 AWG bare, solid, tinned copper wire. Exterior ground conductors must be either solid bare tinned copper, or stranded, insulated (insulation to be sunlight-resistant) copper cable. The interior ground cable must be stranded copper with green insulation type THWN or equivalent.

All grounding system material (cable, connectors, buses, etc.) must be of high quality materials that resist deterioration and require little or no maintenance.

Exothermic weld is recommended for grounding connections where practical. All below grade connections must be exothermically welded. Compression type, two-hole (0.75” center) lugs or double crimp “C” taps are also acceptable. The contact area of metal to which connections are made must be prepared to bare bright finish, and coated with an anti-oxidation material before connections are made.

Lucent Technologies — ProprietarySee notice on first page

42 Issue 3 March 2000

Page 61: 401-703-340Mo

FLEXENT™ CDMA MicrocellSite Preparation Guidelines

Refer to Grounding and Lightning Protection Guidelines, Lucent Technologies Network Wireless System Cell Sites (401-200-115) and FLEXENT Microcell Cabinet Installation Requirements (ED3R128-10) for detailed requirements related to grounding and lightning protection bonding.

! CAUTION:The equipment warranty can be voided if the guidelines detailed in the National Electric Code NFPA 70, The Standard for Installation of Lightning Protection System (NFPA 780, 1995 edition), Lucent Technologies 401-200-115 and Lucent Technologies Engineering Drawings referenced in this document are not followed.

Verification of the grounding requirements should be performed using checklists SP-3A and SP-3B found in Appendix A of this document.

Grounding Equipment 15

It is the customer’s responsibility to provide and install the following grounding equipment:

� RF and GPS coax cable shield grounding kits (per microcell)

� Grounding electrode system (for details, see 401-200-115)

� Coils of #2 AWG bare, solid tinned copper wire with sufficient length for connection of the main ground bus bar to the grounding electrode system (for details, see Figure 17, Figure 18 and Figure 19)

� Non-metallic cable clips (to secure #2 AWG bare, solid tinned copper wire to the pole or wall at 1.2 meter (48 inch) intervals)

It is recommended that during site preparation, the RF and GPS antenna cable shields be temporarily connected to the grounding electrode system through the #2 AWG bare, solid tinned copper wire mentioned above. During equipment installation, the temporary arrangement will be removed and the antenna cable shields will be connected to the grounding electrode system through the main ground bus bar.

Grounding of Metal Pole 15

If the pole on which the microcell is to be mounted is metallic, it may be used as a down conductor if approval is obtained from the manufacturer or owner of the pole.

The lowermost portion of the metallic pole must be bonded to the grounding electrode system using #2 AWG bare, solid tinned copper cable using exothermic welds.

Lucent Technologies — ProprietarySee notice on first page

Issue 3 March 2000 43

Page 62: 401-703-340Mo

401-703-340

Wooden Pole Grounding Configuration 15

Figure 17 shows a typical grounding configuration for a wooden pole installation.

Figure 17. Typical Wooden Pole Installation Grounding Configuration

Lucent Technologies — ProprietarySee notice on first page

44 Issue 3 March 2000

Page 63: 401-703-340Mo

FLEXENT™ CDMA MicrocellSite Preparation Guidelines

Metal Pole Grounding Configuration 15

Figure 18 shows a typical grounding configuration for a metal pole installation.

Figure 18. Typical Metal Pole Installation Grounding Configuration

THE M ETALLIC PO LE STRUCTUREMAY BE USED AS DOW N CONDUCTOR

AFTER APPROVAL OF MANUFACTURERAND/OR OW NER IS OBTAINED

METALLIC POLE

EXO THERMIC W ELD (W HERE APPLICABLE) W ITH APPROVAL OF OW NER AND/OR POLE ’S MANUFACTURER

#2 AWG BARE SOLID T INNED CO PPER W IRE

TOP OF FO UNDATION

152.4 M M (6”)

THE GREATER DEPTH OF 762 MM (30 ”) OR 152 .4 MM(6 ”) BELOW FROST LINE

15 .8 MM (5 /8 ’)X 2.44 M (8 ’) LONGCOPPER CLAD ROD SPACED 10 FT. MIN

#2 AWG BARE SOLID T INNED COPPER CABLE

GROUNDING ELECTRODE SYSTEM

EXO THERMIC W ELD (TYP.)

FINISH G RADE

Lucent Technologies — ProprietarySee notice on first page

Issue 3 March 2000 45

Page 64: 401-703-340Mo

401-703-340

Wall-Mounted Grounding Configuration 18

Figure 19 shows a typical grounding configuration for a wall-mounted installation.

Figure 19. Typical Wall-Mounted Installation Grounding Configuration

3 M (1 0 ’) M IN .

# 2 A W G B A R E S O LID T IN N E D C O P P E R W IR E

F IN IS H G R A D E

G R E AT E R D E P T H O F 7 62 M M (3 0 ”)O R 1 5 2 .4 (6 ”) B E L O W F R O S T L IN E

B U IL D IN G W A L L F O R M O U N T IN GO F F L E X E N T M IC R O C E L L C A B IN E T

E X O T H E R M IC W E L D (T Y P.)

C O IL S U F F IC IE N T L E N G T H O F# 2 A W G B A R E S O LID T IN N E DC O P P E R W IR E F O R L AT E R C O N N E C T IO N T O T H E M A IN G R O U N D B U S B A R (T Y P.)

1 5 .8 M M (5 /8 ”) X 2 .4 4 M (8 ’)C O P P E R C L A D G R O U N D R O D (T Y P.))

Lucent Technologies — ProprietarySee notice on first page

46 Issue 3 March 2000

Page 65: 401-703-340Mo

FLEXENT™ CDMA MicrocellSite Preparation Guidelines

Antenna Interface Requirements 19

General Requirements 19

All materials for outdoor antenna cables must be rated for outdoor use. All antenna connections must be waterproofed in accordance with the connector and cable manufacturer’s instructions. All cable runs must be appropriately supported in accordance with the connector and cable manufacturer’s instructions. All antenna jumper cables must be installed in accordance with Lucent Technologies engineering drawings.

Grounding of the antenna cable outer shield must be performed in accordance with the ground kit manufacturer’s instructions and as outlined in Grounding and Lightning Protection Guidelines for Lucent Technologies Network Wireless System Cell Sites (400-200-115).

Lightning surge protection for antennas is provided on top of the Flexent CDMA Microcell.

RF antenna cable ends must be located as specified in the applicable Lucent Technologies engineering drawings. Failure to follow these drawings may result in problems during installation.

Verification of the antenna interface requirements can be performed using Checklist SP-4 found in Appendix A of this document.

Lucent Technologies — ProprietarySee notice on first page

Issue 3 March 2000 47

Page 66: 401-703-340Mo

401-703-340

RF Antenna Requirements 19

Mounting Options 19 The Flexent CDMA Microcell is primarily intended for use with two RF antennas (one duplex Rx/Tx and one diversity Rx). These antennas may be mounted remotely and cabled to the microcell, or may be integrated within the front panel of the microcell.

In addition, other external antenna configurations are possible, such as:

� Connection to a distributed antenna system

� Connection to two antenna faces simultaneously

� Connections to antennas through an external filter enclosure

� No diversity receive for in-building applications

Integrated Antenna Restrictions for Cellular CDMA 19

When the RF antennas are integrated into the front panel of the microcell, they are mounted at cross angles to provide angular diversity instead of spatial diversity. However, FCC requirements for cellular band transmitters do not allow transmissions to be non-vertically polarized. Therefore the Cellular CDMA Microcell with integrated RF antennas will use simplex transmission, resulting in a total of three RF antennas. The transmit antenna will mount vertically while the two receive antennas are mounted at cross angles.

! CAUTION:The integrated antenna may expose individuals to radio frequency emissions which exceed FCC limits at distances closer than 1.2 meters (4 feet). Installation and maintenance personnel should refer to guidelines in training and user manuals to minimize exposure.

Antenna Specifications 19

All RF antennas must be 50 watts, with a minimum input and output return loss of 14 dB (VSWR less than 1.5:1) at the receive and transmit ports.

Lucent Technologies — ProprietarySee notice on first page

48 Issue 3 March 2000

Page 67: 401-703-340Mo

FLEXENT™ CDMA MicrocellSite Preparation Guidelines

In-Building Antenna Considerations 19

There are often many rooms and hallways in any specific building. In order to achieve the best RF coverage in the building, the following items should be considered.

� Omni antennas are recommended for use in the middle of large conference rooms or auditoriums, and in the center of hallway intersections.

� High gain antennas that have 3-dB beamwidth less than, but close to, 180 degrees are recommended for use along the walls of large conference rooms or auditoriums, and at the ends of hallways.

� High gain antennas that have 3-dB beamwidth less than, but close to, 90 degrees are recommended to be used at a corner of a large conference room or auditorium.

� If several floors are to be covered by one antenna, it is recommended that an antenna with horizontal 3-dB beamwidth less than, but close to, 180 degrees be used. It should be noted that each concrete floor may provide another 10- to 15-dB wall loss to the free space propagation loss.

� Leaky coaxial radiators are recommended to provide RF coverage in elevator shafts or building connecting hallways.

Lucent Technologies — ProprietarySee notice on first page

Issue 3 March 2000 49

Page 68: 401-703-340Mo

401-703-340

GPS Antenna Requirements 19

GPS Antenna Configuration 19

Each Flexent CDMA Microcell requires a GPS signal for synchronizing hand-offs with neighboring cell sites. The GPS antenna can be mounted directly on the microcell, or may be remotely located up to 145 meters (500 feet) from the microcell. GPS repeater amplifiers may be required for the remotely located antenna option. The 1/2-inch foam dielectric has a loss of 4.5-dB/100 feet at 1500 Hz.

When multiple microcells are collocated at a cell site, one GPS antenna can serve up to six microcells through the use of a 1:3 or 1:6 splitter. A 1.2-meter (4 feet) and 9.1-meter (30 feet) cable kit is available to connect the splitter to the microcell. Figure 20 shows three microcells sharing a single GPS antenna signal.

The GPS antenna requires +5 VDC and receives it from the first microcell that it is serving.

Figure 20 GPS Antenna Serving Three Flexent™ CDMA Microcells

Lucent Technologies — ProprietarySee notice on first page

50 Issue 3 March 2000

Page 69: 401-703-340Mo

FLEXENT™ CDMA MicrocellSite Preparation Guidelines

Antenna Ordering Information 20

Table 16 lists the ordering information for the three types of GPS antennas.

Table 16 GPS Antennas

Recommended Cable Types 16

It is recommended that high-quality, low-loss cables be used for the GPS antenna connections. The cables should be outdoor (UV) as well as riser (fire-retardant) rated.

Table 17 lists the cable characteristics of two recommended cables.

Table 17 GPS Cable Characteristics

Code List Description

KS24019 112A 26 ± 3 dB gain GPS antenna

KS24019 116 40 ± 4 dB gain GPS antenna

KS24019 110A 50 ± 4 dB gain GPS antenna

KS 24019 115 Antenna mount

Manufacturer Cable P/N

Attenuation(dB/100 feet @

1.575 GHz)

DC Resistance (Ohms per 1000 feet)

Nominal Outer Diameter (inches)

Andrew FSJ4-RN-50B

4.8 1.82 0.53

Andrew LDF4-RN-50A

3.0 1.03 0.63

Lucent Technologies — ProprietarySee notice on first page

Issue 3 March 2000 51

Page 70: 401-703-340Mo

401-703-340

Antenna Selection Based on Losses 17

The aggregate losses in cables, connectors, splitters and other hardware used to connect the GPS antenna to the microcell should be considered when selecting the GPS antenna.

Table 18 lists the aggregate losses and approximate allowable cable lengths for each type of antenna.

Table 18. Antenna Selection Data

GPS Antenna Installation 18

For detailed installation instructions for the GPS Antenna, refer to Base Station CDMA Reference Frequency Timing Generator and Antenna System Description, Operation, Installation and Maintenance (401-660-128).

Verify GPS Installation and Line of Sight 18

It is highly recommended that a Garmin 45XL (or equivalent) be used to verify the GPS antenna installation and line of sight prior to installing the Flexent CDMA Microcell.

Use Checklist SP-5 (Appendix A) to verify GPS antenna installation prior to beginning the microcell installation.

GPS Antenna KS24019

Nominal Antenna

Gain (dB)

TOTAL AllowableMinimum Loss (dB)

TOTAL Allowable Maximum Loss (dB)

Andrew Cable Type

ApproximateMinimum

Cable Length (feet)

Approximate Maximum

Cable Length (feet)

NominalCable

Length with 1:3 Splitter

(feet)

Worst Case Cable

Length with 1:3 Splitter (feet)

L112A 26 0.77 12 FSJ4 16 250 188 125

LDF4 25 400 300 200

L116 40 13.92 27.36 FSJ4 290 570 480 400

LDF4 470 1025 733 633

L110A 50 23.28 43.2 FSJ4 485 900 688 605

LDF4 765 1400 1100 966

Lucent Technologies — ProprietarySee notice on first page

52 Issue 3 March 2000

Page 71: 401-703-340Mo

FLEXENT™ CDMA MicrocellSite Preparation Guidelines

T1/E1 Facilities Requirements 18

T1/E1 Input Lines 18 The Flexent CDMA Microcell communicates with the 5ESS DCS via a wideband channel called a packet pipe. A packet pipe carries packetized voice and data signals. The pipe consists of DS0 channels on a T1/E1 facility.

The Primary Distribution Cabinet (PDC) serves as the centralized connection point for interfacing all T1/E1 connections at the cell site. The Single PDC provides T1/E1 interface for one microcell and the Multiple PDC provides T1/E1 interfaces for up to three microcells.

For 75 ohm networks, the E1 facility terminates on the Network Interface Unit (NIU). The NIU provides a central point for converting E1 coaxial signaling to balanced signaling required by the microcell. The NIU also provides coaxial protection for two E1 transmit/receive circuits with expansion to four E1 circuits.

The NIU must be located within 6.1 meters (20 feet) of the PDC that it is serving. If an PDC is not used, the NIU must be located within 6.1 meters (20 feet) of the microcell that it is serving.

The Flexent CDMA Microcell accepts two T1 twisted wire pairs from the PDC (or equivalent). The T1 cable input lines should be in place prior to the start of the microcell or PDC installation.

The microcell utilizes one T1/E1 input pair if a dedicated T1/E1 facility is used, and a second facility connection is required for a daisy-chain application.

T1/E1 Daisy-Chaining 18

To make more efficient use of the digital facilities, customers may share a single DS1 facility over six microcells by daisy-chaining them together. The daisy-chaining of Flexent CDMA Microcells is done by running a full DS1 to the first microcell. The line interface unit within the first microcell receives the DS1, but also transmits it on to the next microcell in the chain.

Daisy-chaining can be used in applications where the microcells are closely located, such as a three-sector configuration, or where the microcells are used for in-building distribution and there are several cell sites located within the same building. The maximum distance between daisy-chained microcells without T1/E1 repeaters is 1735 meters (6000 feet).

Lucent Technologies — ProprietarySee notice on first page

Issue 3 March 2000 53

Page 72: 401-703-340Mo

401-703-340

Verify T1/E1 Facilities18 Verification of the T1/E1 facilities can be performed using Checklist SP-1 found in Appendix A of this document.

Lucent Technologies — ProprietarySee notice on first page

54 Issue 3 March 2000

Page 73: 401-703-340Mo

Lucent Technologies —See notice on fir

A

Site Preparation Checklists

Overview

Purpose This section is for use by authorized personnel to verify completion of cell site preparation activities prior to installation of cell site equipment.

Contents Attached to this appendix are the following master sheets, from which copies should be made for each site preparation performed.

SP-GEN Cell Site General Information (1 page)

SP-1 Site Preparation General Checklist (1 page)

SP-2 Site Preparation Power Source Checklist (1 page)

SP-3 Site Preparation Grounding Checklist (3 pages)

SP-4 Site Preparation RF Antenna Checklist (1 page)

SP-5 Site Preparation GPS Antenna Checklist (2 pages)

SP-6 Site Preparation Punchlist Sheet (1 page)

SP-6A Punchlist Continuation Sheets (1 page)

Proprietaryst page

Issue 3 March 2000 A-1

Page 74: 401-703-340Mo

Site Preparation Checklists

Lucent Technologies — ProprietarySee notice on first page

A-2 Issue 3 March 2000

Page 75: 401-703-340Mo

Site Preparation Checklists

SP-GENCell Site General Information

Cell Site Name: MTA Name:

Cell Site Address: Cell Site #:

Cell Site AccessContact Name:

Contact Phone #and Pager #:

Lucent Technologies — ProprietarySee notice on first page

Issue 3 March 2000 A-3

Page 76: 401-703-340Mo

Site Preparation Checklists

Lucent Technologies — ProprietarySee notice on first page

A-4 Issue 3 March 2000

Page 77: 401-703-340Mo

Site Preparation Checklists

SP-1 Site Preparation General Checklist

Completed by:_____________________________ Date: _____________

Item# Description Yes No N/A Comment/Punchlist Issue #

1. Are all site permits complete? � � �

2. Has a Method of Procedure been developed and completed with the installation supervisor?

� � �

3. Are cell translations available? � � �

4. Has the installer cell site equipment parameter sheet been completed and reviewed with the installation supervisor?

� � �

5. Are the ECP/Switch and cell software generics compatible?

� � �

6. Is cell site T1/E1 demarcation point known?

� � �

7. Are T1/E1 facilities available and active? � � �

8. Is T1/E1 interface conduit in place at site?

� � �

9. Has all equipment been ordered and has delivery to site been scheduled?

� � �

10. Have all necessary arrangements been made for access to the site?

� � �

11. Have all necessary arrangements been made to get equipment onto the site?

� � �

Lucent Technologies — ProprietarySee notice on first page

Issue 3 March 2000 A-5

Page 78: 401-703-340Mo

Site Preparation Checklists

Lucent Technologies — ProprietarySee notice on first page

A-6 Issue 3 March 2000

Page 79: 401-703-340Mo

Site Preparation Checklists

SP-2 Site Preparation Power Source Checklist

Completed by:_____________________________ Date: _____________

Item # Description Yes No N/A Comment/Punchlist Issue #

1. Is AC service available? � � �

2. Have AC service and conduits been approved by local code?

� � �

3. Is AC service equipped with surge protection at service entry point?

� � �

4. Is AC power source nominal 208 or 240 VAC, single phase?

� � �

5. For indoor applications, has a Power Line Surge Protector been installed?

� � �

Lucent Technologies — ProprietarySee notice on first page

Issue 3 March 2000 A-7

Page 80: 401-703-340Mo

Site Preparation Checklists

Lucent Technologies — ProprietarySee notice on first page

A-8 Issue 3 March 2000

Page 81: 401-703-340Mo

Site Preparation Checklists

SP-3 Site Preparation Grounding Checklist

Item# Description Yes No N/A Comment/Punchlist Issue #

1 Is cell site resistance less than or equalto 10 ohms?

� � �

2. Have connections been provided to grounding electrode system?If yes, check all that apply:

� � �

�Via a buried ring ground and driven rod(s)

�Via a buried metallic & electrically continuous water pipe

�Via driven ground rod(s) and/or plate(s)

�Via electrolytic ground rod(s)

�Via grounded building steel

�Via grounded grid or radial

3. Is a lightning mast(s) or air terminal(s) provided and bonded?

� � �

4. Is antenna support structure(s) grounded?

� � �

5. Are antenna cable shields grounded at both ends?

� � �

6. If a tower is utilized and is greater than 200 feet high, are antenna cable shields grounded at mid-point and both ends?

� � �

7. Is antenna tower bonded to grounding electrode system?

� � �

8. Are guy wires bonded to grounding electrode system?

� � �

9. Is steel pole structure used as down conductor?

� � �

Lucent Technologies — ProprietarySee notice on first page

Issue 3 March 2000 A-9

Page 82: 401-703-340Mo

Site Preparation Checklists

Lucent Technologies — ProprietarySee notice on first page

A-10 Issue 3 March 2000

Page 83: 401-703-340Mo

Site Preparation Checklists

SP-3 Site Preparation Grounding Checklist (Continued)

Item# Description Yes No N/A Comment/Punchlist Issue #

10. Are all ground connections in compliance with Lucent requirements (exothermic weld, compression type with 2-hole lugs; properly secured; anti-oxidant used on contact surface area)?

� � �

11. Are grounding conductors routed as straight as possible with no loops or sharp bends?

� � �

12. Are metallic conduits bonded at both ends and 25-foot intervals?

� � �

13. Are all fence corner posts and gate posts properly grounded (including fence fabric and barbed wire, as applicable)?

� � �

14. Are all metallic objects within 6 feet bonded to the grounding electrode system?

� � �

15. Is AC power supply equipped with surge protection device and is the device properly connected to the grounding electrode system?

� � �

16. Is T1/E1 line equipped with surge protection device and is the device properly connected to the grounding electrode system?

� � �

17. Is tower light system (if installed) equipped with surge protection device and is the device properly connected to the grounding electrode system?

� � �

Lucent Technologies — ProprietarySee notice on first page

Issue 3 March 2000 A-11

Page 84: 401-703-340Mo

Site Preparation Checklists

Lucent Technologies — ProprietarySee notice on first page

A-12 Issue 3 March 2000

Page 85: 401-703-340Mo

Site Preparation Checklists

SP-3 Site Preparation Grounding Checklist (Continued)

Completed by:_____________________________ Date: _____________

Item# Description Yes No N/A Comment / Punchlist Issue #

18. Are antenna cable shields grounded prior to entering the building at the hatchplate?

� � �

19. Is surge protection installed on coaxial cable lines entering building?(not a requirement; good practice)

� � �

Lucent Technologies — ProprietarySee notice on first page

Issue 3 March 2000 A-13

Page 86: 401-703-340Mo

Site Preparation Checklists

Lucent Technologies — ProprietarySee notice on first page

A-14 Issue 3 March 2000

Page 87: 401-703-340Mo

Site Preparation Checklists

SP-4 Site Preparation RF Antenna Checklist

Item# Description Yes No N/A Comment/Punchlist Issue #

1. All antenna cable runs installed? � � �

2. All external cable connections weatherproofed?

� � �

3. All external insulated cables sunlight resistant?

� � �

4. Antenna cable run demarcation points in proper location?

� � �

5. Antenna cable runs marked and in proper sequence per applicable drawing?

� � �

6. Antenna and cable sweeps performed? � � �

7. Antennas properly installed and secured?

� � �

8. All antennas the proper type? � � �

9. Antennas at proper azimuth?(0, 120, or 240 degrees)

� � �

10. Antennas at proper height? � � �

Lucent Technologies — ProprietarySee notice on first page

Issue 3 March 2000 A-15

Page 88: 401-703-340Mo

Site Preparation Checklists

Lucent Technologies — ProprietarySee notice on first page

A-16 Issue 3 March 2000

Page 89: 401-703-340Mo

Site Preparation Checklists

SP-5 Site Preparation GPS Antenna Checklist

Item# Description Yes No N/A Comment / Punchlist Issue #

1. Antenna installed with base level within 2 degrees?

� � �

2. Antenna installed with less than 25% of the sky masked by obstruction?

� � �

3. GPS antenna located at least 1.22 meters (4 feet) vertically and horizontally from any transmitter

� � �

4. Aggregate cable loss, cable VSWR, total cable length, cable type, GPS antenna gain, KS-list and serial numbers recorded in the site installation records?

� � �

5. Proper gain antenna installed for the total aggregate cable loss and length?

� � �

6. Measured cable VSWR within its specified value?

� � �

7. GPS antenna cable properly grounded near antenna and at microcell (outdoor) or at hatchplate (indoor)?

� � �

8. Cable connections torqued to the appropriate value?

� � �

9. All external cable connections weatherproofed (except connector at antenna)?

� � �

10. All external cables UV rated? � � �

Lucent Technologies — ProprietarySee notice on first page

Issue 3 March 2000 A-17

Page 90: 401-703-340Mo

Site Preparation Checklists

Lucent Technologies — ProprietarySee notice on first page

A-18 Issue 3 March 2000

Page 91: 401-703-340Mo

Site Preparation Checklists

SP-5 Site Preparation GPS Antenna Checklist (Continued)

Completed by:_____________________________ Date: _____________

Item# Description Yes No N/A Comment/Punchlist Issue #

11. Antenna bracket, pipes and antenna properly secured?

� � �

12. GPS antenna location verified for line of sight using a Garmin 45XLS test unit or equivalent?

� � �

13. GPS antenna location free of external interference (i.e., radio stations,collocated equipment, etc.)?

� � �

Lucent Technologies — ProprietarySee notice on first page

Issue 3 March 2000 A-19

Page 92: 401-703-340Mo

Site Preparation Checklists

Lucent Technologies — ProprietarySee notice on first page

A-20 Issue 3 March 2000

Page 93: 401-703-340Mo

Site Preparation Checklists

SP-6Site Preparation Punchlist Sheet

Severity Column Definitions:

1. Equipment installation cannot occur until outage is rectified and will void warranty or potentially cause personal injury.

2. Equipment installation can occur but issue must be rectified prior to handoff to customer or service turn-up so that warranty is not voided.

3. Equipment installation, handoff to customer, or service turn-up can occur but not per Lucent recommendations.

Inspection Checklist Completion Sign-off

Check here if continuation sheet used �

Item# Comment/Description

Severity(1/2/3)

Corrective Action Required

(Y/N)Completed

(Date)

Lucent Technologies — ProprietarySee notice on first page

Issue 3 March 2000 A-21

Page 94: 401-703-340Mo

Site Preparation Checklists

Inspector’s Name: Inspector’s Function:

Inspector’s Signature: Date:

Lucent Technologies — ProprietarySee notice on first page

A-22 Issue 3 March 2000

Page 95: 401-703-340Mo

Site Preparation Checklists

SP-6ASite Preparation Punchlist Continuation Sheet

Item# Comment/Description

Severity(1/2/3)

CorrectiveAction Required

(y/n)Comp.Date

Lucent Technologies — ProprietarySee notice on first page

Issue 3 March 2000 A-23

Page 96: 401-703-340Mo

Site Preparation Checklists

Lucent Technologies — ProprietarySee notice on first page

A-24 Issue 3 March 2000

Page 97: 401-703-340Mo

Lucent Technologies —See notice on fir

B

Cell Site Information

Overview

Purpose This section is for use by Customer Project Management to document cell site configuration information.

Contents Attached to this appendix are the following master sheets, from which copies should be made for each site preparation performed.

CSC-1 Cell Site Configuration Information (5 pages)

Proprietaryst page

Issue 3 March 2000 B-1

Page 98: 401-703-340Mo

Cell Site Information

Lucent Technologies — ProprietarySee notice on first page

B-2 Issue 3 March 2000

Page 99: 401-703-340Mo

Cell Site Information

CSC-1Cell Site Configuration Information

Completed by:_____________________________ Date: _____________

Cell Site Name: MTA Name:

Cell Site Address: Cell Site #:

Cell Site Access Contact Name:

Contact Phone # & Pager #:

Documentation & DrawingInformation Referenced

Document or DrawingNumber

Issue #

Lucent Installation Engineering Drawing(s)

Site Preparation Document

Base Station Power & Alarm Requirements

Base Station GPS Document

Base Station Cabinet Installation Manual

Lightning Protection and Grounding Guidelines

Installation Type (Check all that apply)

� Indoor � ControlledEnvironment

� Pole

� Outdoor � UncontrolledEnvironment

� Rooftop

� Wall_______________

� Other (Specify)_______________

Lucent Technologies — ProprietarySee notice on first page

Issue 3 March 2000 B-3

Page 100: 401-703-340Mo

Cell Site Information

Lucent Technologies — ProprietarySee notice on first page

B-4 Issue 3 March 2000

Page 101: 401-703-340Mo

Cell Site Information

lexx

_

__

CSC-1Cell Site Configuration Information (continued)

Earthquake Zone Rating: � Zone 1 �Zone 2 �Zone 3 �Zone 4

Completed by:_____________________________ Date: _____________

Flexent CDMA Microcell Cell Site Equipment

Radio Cabinet /Serial Number

________________________

Number of Sectors:�Omni�1�2

� Simp� Duple

# of Carriers (1-6) _______

GPS AntennaKS/Model ____________

Total GPS CableLength (ft) _________

GPS Antenna Gain(dB)

_______

Antenna Type: � External

�Integrated

Antenna Jumper Cable Type:

�N-to-N

�N-to-DIN

Power Backup Cabinet(Type)

_________

AC Generator ? � Yes�No

Lucent Technologies — ProprietarySee notice on first page

Issue 3 March 2000 B-5

Page 102: 401-703-340Mo

Cell Site Information

Lucent Technologies — ProprietarySee notice on first page

B-6 Issue 3 March 2000

Page 103: 401-703-340Mo

Cell Site Information

)

CSC-1Cell Site Configuration Information (continued)

Completed by:_____________________________ Date: _____________

Cell Site Grounding � Yes

� No

If yes, select all that apply:

� Buried ring ground and driven rods

� Buried metallic and electrically continuous water pipe� Down conductors (Quantity:___)� Electrolytic ground rod(s) (Quantity:___� Driven ground rod(s) (Quantity:___) � Grounded building steel

� Ground grid

� Ground radial(s) (Quantity:___)

Collocated non-PCS equipment

� Yes

� No

Existing grounding system:

� Single Point� Integrated

Ground Bus � Yes

� No

If Yes, quantity:________________

Lucent Technologies — ProprietarySee notice on first page

Issue 3 March 2000 B-7

Page 104: 401-703-340Mo

Cell Site Information

Lucent Technologies — ProprietarySee notice on first page

B-8 Issue 3 March 2000

Page 105: 401-703-340Mo

Lucent Technologies —See notice on fir

Glossary

Overview

Purpose This section provides a list of acronyms and abbreviations used in this document.

Proprietaryst page

Issue 3 March 2000 GL-1

Page 106: 401-703-340Mo

Glossary

A Ampere(s) mVrms Millivolt Route Mean Square

AC Alternating Current NEC National Electric Code

ANSI American National Standards Institute NESC National Electric Safety Code

AWG American Wire Gauge NIU Network Interface Unit

BOCA Building Officials and Code Administrators OSP Outside Plant

C Celsius (or Centigrade) PBC Power Backup Cabinet

CDMA Code Division Multiple Access PCS Personal Communications Services

CFM Cubic feet per minute PCU Power Converter Unit

dB Decibel(s) PDC Primary Distribution Cabinet

DC Direct Current POTS Plain Old Telephone Service

DCS Digital Cellular Switch RCS Radio Cluster Server

ECP Executive Cellular Processor RF Radio Frequency

FCC Federal Communications Commission Rx Receive

GFCI Ground Fault Circuit Interrupter T1/E1 24-Channel Digital Carrier

GHz Gigahertz TFU Timing/Frequency Unit

GPS Global Positioning System Tx Transmit

HVAC Heating, Ventilation, Air Conditioning UBC Uniform Building Code

Hz Hertz UL Underwriters Laboratories

I/O Input/Output UPS Uninterruptible Power Supply

kG Kilogram(s) UV Ultraviolet

kW Kilowatt(s) VAC Volts Alternating Current

LNA Low Noise Amplifier VDC Volts Direct Current

MHz Megahertz VSWR Voltage Standing Wave Ratio

m Meter(s) W Watt(s)

mm Millimeter(s)

MOP Method of Procedure

mVp-p Millivolt Peak-to-Peak

Lucent Technologies — ProprietarySee notice on first page

GL-2 Issue 3 March 2000