> Prysmian FP100® is the original fire resistant single core cable for use in metal conduits or trunking to achieve a highly robust fire resistant wiring system. It maintains circuit integrity during a fire both when tested in free air or in a metallic conduit. When burnt, it produces very low levels of smoke and virtually no (less than 0.5%) acidic gases, thus safeguarding human life and protecting equipment.
Through the use of a dual layer insulation system, FP100® offers fire resistance combined with abrasion and damage resistance, making it an excellent choice both for upgrading existing conduit based systems to current essential safety circuit standards or new installations.
Systems based upon standard pvc cables, even when protected by metal conduit, have been shown to fail within minutes in a fire. Therefore they are no longer permitted by BS5839-1 or BS5266-1 for fire alarm or emergency lighting systems, as they do not ensure prolonged operation in the event of a fire.
> Prysmian FP100® is Loss Prevention Certification Board (LPCB) listed as a fire resistant cable. The LPCB range approval is given on the basis of (i) satisfactory testing at an enhanced voltage of 600/1000V to BS6387 category CWZ when tested in steel conduit and the conduit is considered as the metallic layer required by BS6387, for those sizes capable of fitting within the test conduit, and (ii) satisfactory testing to IEC60331-21 at an enhanced temperature of 950°C for those sizes too large to fit in the test conduit.
Additional tests have demonstrated the ability of FP100® to achieve a 120 minute rating (PH120) to BS EN50200 and a 120 minute rating to BS8434-2 when tested in a steel conduit. These tests demonstrate the ability of FP100® to meet the fire resistance requirements necessary for use in "enhanced" installations in accordance with BS5839-1:2002 and "Cable systems with an inherently high resistance to attack by fire" in accordance with BS5266-1:2005.
Prysmian FP100® cables are manufactured under an ISO9001 Quality Management System certified by BASEC and LPCB.
> Prysmian FP100® may be considered as a low smoke conduit wire to BS7211 for the purposes of installation, and should be installed in accordance with BS7671/IEE Wiring Regulations, or any other appropriate national regulations. It is suitable for installation in surface mounted or embedded conduits and trunking, or other similar fixed protected installations. For surface systems, the use of a metallic conduit or trunking is recommended to ensure integrity of the system in the event of fire. For fully embedded systems protected by a non combustible layer, non metallic conduit or trunking may be used.
Temperature Range-25 to +90ºC≠
Bending Radiusup to 8mm diameter r=4D above 8mm diameter r=6D
Mechanical impactRequires protection
Fire PerformanceBSEN60332-1-2
FlexibilitySemi-flexible
Halogen FreeBSEN50267-2-1
Low Smoke EmissionsBSEN61034-2
Fire ResistantIEC 60331-21
BS6387 Category CWZ*EN50200 PH120*BS8434-2 120min*
*When tested in Steel Conduit
Certificate No 077c
* Sizes 1.5 - 10mm2 are rated at 450/750V.Installation methods for current rating “Enclosed in conduit on a wall or in trunking” in accordance with BS7671/IEE Wiring Regulations. Minimum recommended installation temperature -5°C.The tabulated ratings are based upon a 30°C ambient temperature at 90°C operating temperature.For other ambient temperatures or where several circuits are grouped together, the following rating factors should be applied.
> Essential safety circuits where the cable is protected by metal conduit or trunking.
> May be used for emergency lighting, fire alarm systems not requiring a twisted cable or other essential services.
CONDUCTOR
Plain annealed copper stranded (class 2)
conductor for flexibility.
PRIMARY INSULATIONMineral ceramic (Mica/Glass) fire resistant tape.
SECONDARY INSULATION90°C high performance cross linked mineral filled insulation.
o red o brown o black o yellow o orange
o grey o blue green/yellow
Other core colours available on request
Temperature rating factors
Rating factors for groupings
Nominal cross
sectional area
mm2
Approximate cable
weight
kg/km
Maximum conductorresistance
at 20°C
ohms/km
Current rating
DC or single phase AC
Amps
Current rating Three
phase AC
Amps
Volt drop DC
mV/A/m
Approximate overall
diameter
mm
Short circuit rating(1 sec)
Amps
Volt drop Single
phase AC
mV/A/m
Volt drop Three
phase AC
mV/A/m
Single Core
1 .5* 3.5 26 12.1 215 23 20 31 31 27
2.5* 4.1 38 7.41 360 31 28 19 19 16
4* 4.6 54 4.61 570 42 37 12 12 10
6* 5.2 75 3.08 860 54 48 7.9 7.9 6.8
10* 6.6 120 1.83 1425 75 66 4.7 4.7 4
16 7.7 180 1.15 2275 100 88 2.9 2.9 2.5
25 9.0 270 0.727 3375 133 117 1.85 1.9 1.65
35 10.0 360 0.524 5000 164 144 1.35 1.35 1.15
50 11.7 490 0.387 7150 198 175 0.99 1.05 0.9
70 13.2 680 0.268 10000 253 222 0.68 0.75 0.65
95 15.3 940 0.193 13575 306 269 0.49 0.58 0.5
120 16.8 1160 0.153 17150 354 312 0.39 0.48 0.42
150 18.7 1440 0.124 21450 393 342 0.32 0.43 0.37
185 20.8 1800 0.0991 26450 449 384 0.25 0.37 0.32
240 23.5 2350 0.0754 34325 528 450 0.19 0.33 0.29
300 27.3 3000 0.0601 42925 603 514 0.155 0.31 0.27
400 32.5 3970 0.0470 57225 683 584 0.120 0.29 0.25
500 36.0 4980 0.0366 71525 783 666 0.093 0.28 0.24
630 40.0 6340 0.0283 90125 900 764 0.072 0.27 0.23
Ambient Temperature°C 25 30 35 40 45 50 55 60
Rating factor 1.02 1.00 0.96 0.91 0.87 0.82 0.76 0.71
Number of circuits 2 3 4 5 6 7 8 9
Rating factor 0.80 0.70 0.65 0.60 0.57 0.54 0.52 0.50
Ref:FP1
00
/PY/0
8/0
7
UK Sales enquiriesTel: 0845 767 8345Fax: 023 8029 5465
UK Technical helplineTel: 0845 767 8345Fax: 023 8029 5002
Prysmian Cables & Systems LimitedChickenhall LaneEastleighHampshireSO50 6YUUnited Kingdom
For further information please see our dedicated FP website:www.fpcables.co.uk
www.prysmian.co.uk
Overseas Sales enquiriesTel: +44 23 8029 5481Fax: +44 23 8029 5465
Overseas Technical helplineTel: +44 23 8029 5481Fax: +44 23 8029 5002
Information hotlineTel: +44 (0) 23 8029 5029Fax: +44 (0) 23 8029 [email protected]
FP200 GOLD®
FIRE RESISTANT CABLES
FP200 GOLD® BS7629-1:2008
INSTALLATION
DATA CAPABILITY
APPROVALS
FP200 GOLD®
FIRE RESISTANT CABLES
> The original highly durable and dressable, easy to terminate and install fire resistant cable, using the unique InsuditeTM damage resistant insulation system. Approved for fire detection and fire alarm critical signal paths to BS5839-1:2002+A2:2008 and voice alarm systems to BS5839-8:2008 in ‘standard’ application areas, and emergency lighting systems to BS5266-1:2005.
The changes to cable test methods and requirements first introduced by BS5839-1:2002+A2:2008 “Fire detection and fire alarm systems for buildings - Part 1: Code of practice for system design, installation, commissioning and maintenance” mean that fire resistant cables must now be approved against new test requirements.
> In addition to approvals to BS7629-1 and BS6387 Category CWZ, FP200 Gold® has received BASEC and LPCB approval to BS5839-1:2002 for ‘standard’ applications. This includes approval to BS EN 50200 Class PH30 and the new integrated fire, shock and water test BS8434-1 for 30 minutes. FP200 Gold® is also approved to BS EN 50200 Class PH60 as required by BS5266-1:2005.
All Prysmian FP200Gold® cables are manufactured under an ISO 9001 Quality System certified by BASEC and LPCB.
> FP200 Gold® has excellent data/signal transmission characteristics making it ideal for voice alarm, addressable and networked systems.
> In accordance with BS5839-1 and BS5266-1 requirements, cables must be supported by a fixing that can withstand the same fire conditions as the cable. To meet this requirement the use of Prysmian AP LSOH® coated metal P-clips or the new FP FirefixTM rapid fixing system is recommended.
FP200Gold should be installed in accordance with BS7671/IEE Wiring Regulations and/or any other appropriate national regulations or codes. It is suitable for indoor and outdoor installation in suitably protected environments and particularly appropriate for surface wiring, direct burial in plaster, tray or other installations requiring a dressable product.
TemperatureRange
-20 to +70˚C
Bending RadiusFixed r=6D
Mechanical ImpactMedium
Fire PerformanceBS EN 60332-1-2BS EN 50266-2-4
FlexibiltyRigid
Halogen FreeBS EN 50267-2-1
Low Smoke EmissionsBS EN 61034-2
Fire ResistanceBS6387 Category CWZ
BS EN 50200 PH30 & PH603
BS EN 50200 Annex E
Certificate No 077fCertificate No 077k
CABLE CHARACTERISTICS
Two core
1.03 1/1.13 8.0 78 18.1 13 15 44 AP7 251/GL2520 UFPNF02
1.5 1/1.38 8.1 93 12.1 16.5 19.5 29 AP7 251/GL2520
2.5 1/1.78 9.5 140 7.4 23 27 18 AP9 251/GL2520 -
4.0 7/0.85 11.6 195 4.6 30 36 11 AP11 252/GL2520 -
Three core
1.03 1/1.13 8.2 88 18.1 13 15 44 AP7 251/GL2520 UFPNF02
1.5 1/1.38 8.4 116 12.1 16.5 19.5 29 AP8 251/GL2520 UFPNF04
2.5 1/1.78 10.4 180 7.4 23 27 18 AP10 252/GL2520 -
4.0 7/0.85 12.3 248 4.6 30 36 11 AP12 252 -
Four Core
1.03 1/1.13 8.5 107 18.1 13 15 44 AP8 251/GL2520 UFPNF04
1.5 1/1.38 10 143 12.1 16.5 19.5 29 AP9 251/GL2520 -
2.5 1/1.78 11.9 225 7.4 23 27 18 AP11 252/GL2520 -
4.0 7/0.85 13.5 310 4.6 30 36 11 AP13 254
1 Recommended clip spacing 300 mm horizontal and 400mm vertical. 2 Brass glands may be used as an alternative.3 BS5266-1:2005 clause 9.2.3 states a minimum cross-sectional area of conductor of 1.5mm2
FP200 Gold® is also available in multi-core versions (7,12 & 19 core) Minimum recommended installation temperature 0°C. Installation methods for current rating in accordance with BS7671/IEE Wiring Regulations. The tabulated ratings are based upon a 30°C ambient temperature and 70°C operating temperature. For other ambient temperatures or where cables are grouped together, appropriate rating factors should be applied.
KEY APPLICATIONS > Fire detection and fire alarm systems for buildings> Voice alarm systems> Emergency lighting> Other essential service circuits
CABLE DESCRIPTION
CONDUCTORPlain annealed copper solid (1.0 - 2.5 mm2) or stranded (4.0 mm2) circular conductor complying with BS EN 60228 class 1 or class 2.
INSULATIONHigh performance damage resistant InsuditeTM.British Standard Type EI5.
CORE IDENTIFICATION HARMONISED CORE IDENTIFICATION:o o brown-blue | o o o brown-black-greyo o o o blue-brown-black-grey
NON HARMONISED CORE IDENTIFICATION:o o red-black | o o o red-yellow-blueo o o o black-red-yellow-blue
Non harmonised colours to special order.
SCREEN/CPC Laminated aluminium tape screen bonded to sheath and in contact with full size tinned annealed copper circuit protective conductor which provides automatic screen earthing.
SHEATH Robust thermoplastic LSOH sheath; Colour - White or Red. Other colours to special order. For external exposure the use of a white sheath is recommended.
Nominal
cross
sectional
area
mm2
Conceptual
Construction
no./mm
Mean
overall
diameter
mm
Approximate
cable
weight
kg/km
Maximum
conductor
resistance
at 20°C
ohms/km
Current
rating DC or
single phase
AC
Enclosed
Amps
Current
rating DC or
single phase
AC
Clipped direct
Amps
Volt drop
DC or single
phase
AC
mV/A/m
1 LSOH®
fixing
clips
2 Nylon
LSOH®
gland
Recommended accessories
Colour - White or Red
FP FirefixTM
fixing
clips
Notes to table
FIRE RESISTANT CABLES 300/500V
Temperature ratings factor
Rating Factors for Groupings
Ambient Temperature°C 25 30 35 40 45 50
Rating factor 1.03 1.00 0.94 0.87 0.79 0.71
Number of circuits 2 3 4 5 6 7
Rating factor 0.80 0.70 0.65 0.60 0.57 0.54
UFPNF01*UFPNF02
* Single clip
UK Sales enquiries
Tel: 0845 767 8345
Fax: 023 8029 5465
UK Technical helpline
Tel: 023 8029 5222
Fax: 023 8029 5002
Prysmian Cables & Systems Limited
Chickenhall Lane
Eastleigh
Hampshire
SO50 6YU
United Kingdom
For further information please see
our dedicated FP website:
www.fpcables.co.uk
www.prysmian.co.uk
Overseas Sales enquiries
Tel: +44 23 8029 5481
Fax: +44 23 8029 5465
Overseas Technical helpline
Tel: +44 23 8029 5481
Fax: +44 23 8029 5002
Information hotline
Tel: +44 (0) 23 8029 5029
Fax: +44 (0) 23 8029 5437
Re
f:FP
20
0G
old
/06
/09
Mechanical Impact Medium
Temperature Range
-20 to +70°C
Fire ResistanceBS 6387 Category CWZ
BS EN 50200 PH30BS EN 50200 Annex E
Low Smoke EmissionsBS EN 61034-2
Halogen Free BS EN 50267-2-1
Flexibility Rigid
Fire Performance BS EN 60332-1-2BS EN 50266-2-4
Bending Radius Fixed r=6D
FP200 Gold® Multicore
BS7629-1:2008
>
>
>
>
FIRE RESISTANT CABLES
Plain annealed copper solid (1.0 - 1.5 mm2) or stranded
(2.5 mm2) circular conductor complying with BS EN 60228
class 1 or class 2.
High Performance damage resistant InsuditeTM.
British Standard Type EI5.
Laminated aluminium tape screen bonded to sheath and in contact with tinned annealed coppper 0.5mm2 drain wire which provides automatic screen earthing.
Conductor
Insulation
Screen
Core Identifi cation
Sheath Robust thermoplastic LSOH sheath
Colour - White or Red. Other colours to special order
For external exposure the use of a white sheath isrecommended.
>
Prysmian Cables & Systems Limited, Sales office, Chickenhall Lane, Eastleigh, Hants, SO50 6YU, UK
Commercial Enquiries, Tel 0845 767 8345, Fax: 023 8029 5465
www.fpcables.co.uk
Ref: FP200Gold_Multi/01/09
Certifi cate No 077aCertifi cate No 077b
7-12-19 cores white with printed number.
Key Applications > Fire detection and fi re alarm systems for buildings
Voice alarm systems
Emergency lighting
Other essential service circuits
1 Recommended clip spacing 300 mm and 400 mm vertical. 2 Brass gland may be used as an alernative.3 This size is not included in the latest (2008) edition of BS7629-1 and is therefore manufactured to BS7629-1:1997Installation methods for current rating in accordance with BS7671/IEE Wiring Regulations.Minimum recommended installation temperature 0°C.*The tabulated rating is as a two core and may be used where its number of cores carrying current does not exceed the square root of the total number of cores.
Notes to table
Temperature rating factors
Rating Factors for Grouping
Ambient Temperature °C 25 30 35 40 45 50 55 60
Rating factor 1.03 1.00 0.94 0.87 0.79 0.71 0.61 0.50
Prysmian FP200 Gold® Multicore Cable
Prysmian Cables & Systems Limited, Sales office, Chickenhall Lane, Eastleigh, Hants, SO50 6YU, UK
Commercial Enquiries, Tel 0845 767 8345, Fax: 023 8029 5465
www.fpcables.co.uk
Ref: FP200Gold_Multi/01/09
1.0 1/1.13 12.1 196 18.1 13* 15* 44 AP12 252
1.5 1/1.38 13.3 249 12.1 16.5* 19.5* 29 AP13 252
2.5 7/0.67 16.3 387 7.4 23* 27* 18 AP16 254
Nominal cross
sectional area
mm
Conceptual construction
no./mm
Mean overalldiameter
mm
Approximatecable weight
kg/km
Maximum conductorresistance at 20°C
ohms/km
Current rating DC or single phase AC Enclosed
Amps
Current rating
DC or single phase AC
Clipped direct Amps
Recommended accessories
2Nylon LSOH Gland
Volt drop DC or single phase AC
mV/A/m
Seven core
Twelve core
1.5 1/1.38 17.5 399 12.1 16.5 19.5* 29 AP18 254
2.5 7/0.67 21.7 637 7.4 23* 27* 18 AP22 255
Nineteen core
The tabulared ratings are based upon a 30°C ambient temperature and 70°C operating temperature.For other ambient temperatures or where cables are grouped toghether, the following rating factors should be applied.
1.5 1/1.38 20.5 588 12.1 16.5 19.5* 29 AP20 255
2.53 7/0.67 25.6 949 7.4 23* 27* 18 AP25 -
Number of circuits 2 3 4 5 6 7 8 9
Rating factor 0.80 0.70 0.65 0.60 0.57 0.54 0.52 0.50
1LSOH® Fixing Clips
Mechanical Impact Medium
Temperature Range
-25 to + 70°C
Fire ResistanceBS 6387 Catergory CWZ
BS EN 50200 PH30
Low Smoke EmissionsBS EN 61034-2
Halogen Free BS EN 50267-2-1
Flexibility Semi Flexible
Fire Performance BS EN 60332-1-2BS EN 50266-2-4
Bending Radius Fixed r=4D
FIRE RESISTANT CABLES
>
>
>
FP200 Flex
Plain annealed copper stranded circular conductor complying
with BS EN 60228 class 2
High performance damage resistant InsditeTM
o o brown-blueo o o brown-black-greyo o o o blue-brown-black-grey
Conductor
Insulation
Core Identification
Sheath Robust thermoplastic LSOH® sheath
Colour - White or Red. Other colours to special order
For external exposure the use of white sheath is recommended
>
Prysmian Cables & Systems Limited, Sales office, Chickenhall Lane, Eastleigh, Hants, SO50 6YU, UK
Commercial Enquiries, Tel 0845 767 8345, Fax: 023 8029 5465
www.fpcables.co.uk
Ref: FP200Flex/10/09
Key Applications Fire detection and fire alarm systems for buildings, voice alarm
systems, emergency lighting systems and other essential service
circuits. In addition to approvals to BS7629-1 from BASEC and
LPCB, FP 200 FlexTM has received LPCB approval against the fire
test requirement of BS6387 Category CWZ
>
Screen > Aluminium/Polyester tape screen in contact with full size
tinned annealed copper stranded circuit protective conductor
>
>
Certificate No 077a/03
BS7629-1
British Standard Type E15.
TM
1 Recommended clip spacing 300mm horizontal and 400mm vertical2 Brass glands may be used as an alternative
Minimum recommended installation temperature 0°CInstallation methods for current rating in accordance with BS7671/IEE Wiring Regulations.The tabulated ratings are based upon a 30°C ambient temperature and 70°C operating temperature.For other ambient temperatures or where cables are grouped togethor, the appropriate rating factors should be applied.
Notes to table
Temperature Rating Factors
Rating factors for Grouping
Prysmian FP200 FLEXTM Fire Resistant Cable
Prysmian Cables & Systems Limited, Sales office, Chickenhall Lane, Eastleigh, Hants, SO50 6YU, UK
Commercial Enquiries, Tel 0845 767 8345, Fax: 023 8029 5465
www.fpcables.co.uk
Ref: FP200Flex/10/09
Two Core
1.5 7/0.53 8.2 99 12.1 16.5 19.5 29 AP7 251/GL2520
2.5 7/0.67 9.6 145 7.4 23 27 18 AP9 251/GL2520
Three Core
1.5 7/0.53 8.7 120 12.1 16.5 19.5 29 AP8 251/GL2520
2.5 7/0.67 10.2 176 7.4 23 27 18 AP10 252/GL2520
Four Core
1.5 7/0.53 9.7 149 12.1 16.5 19.5 29 AP9 251/GL2520
2.5 7/0.67 11.4 218 7.4 23 27 18 AP11 252/GL2520
Nominal cross
sectional area
mm2
Conceptual construction
no./mm
Mean overall diameter
mm
Approximatecable weight
kg/km
Maximum conductor resistance at 20°C
ohms/km
Current rating
DC or single phase ACEnclosed
Amps
Current rating
DC or single phase AC
clipped directAmps
LSOH fixing clips 1
Recommended accessories
Nylon LSOH gland 2
Volt drop DC or single phase AC
mV/A/m
Ambient Temperature °C 25 30 35 40 45 50 55 60
Rating factor 1.03 1.00 0.94 0.87 0.79 0.71 0.61 0.50
Number of circuits 2 3 4 5 6 7 8 9
Rating factor 0.80 0.70 0.65 0.60 0.57 0.54 0.52 0.50
FP PLUS™
FIRE RESISTANT CABLES
New GenerationNow with enhanced
InsuditeTM insulation
FP PLUS™
‘ENHANCED’FIRE RESISTANT CABLES
CABLE CHARACTERISTICS
FP PLUS™ BS7629-1:2008
DATA CAPABILITY
INSTALLATION
APPROVALS In addition to approvals to BS7629-1 and BS6387 Category
CWZ, FP PLUSTM
has received BASEC and LPCB approval to
BS5839-1:2002 for enhanced applications. This includes approval
to BS EN 50200 Class PH120 and the new integrated fire, shock
and water test BS8434-2 for 120 minutes. All Prysmian FP PLUSTM
cables are manufactured under an ISO 9001 Quality System
certified by BASEC and LPCB.
FP PLUSTM
has excellent data/signal transmission characteristics
making it ideal for voice alarm, addressable and networked
systems.
In accordance with the new BS5839-1 and BS5266-1 requirements,
cables must be supported by a fixing that can withstand the same
fire conditions as the cable. To meet this requirement the use of
Prysmian AP LSOH® coated metal P-clips or the new FP FirefixTM rapid fixing system is recommended. FP PLUS
TM
should be installed
in accordance with BS7671/IEE Wiring Regulations and/or any
other appropriate national regulations or codes. It is suitable for
indoor and outdoor installation in suitably protected environments
and particularly appropriate for surface wiring, direct burial in
plaster, tray or other installations requiring a dressable product.
>
>
>
>
The new generation of FP PLUSTM
is a highly durable and dressable,
easy to terminate and install fire resistant cable, using an enhanced
variant of the unique InsuditeTM damage resistant insulation system.
It brings to the market for the first time an enhanced fire alarm
cable with the unmatched combination of rigidity and ease of
bending associated with the market leading FP200 Gold® cable.
New generation FP PLUSTM
sets previously unobtainable levels in
ease of installation for an enhanced cable whilst maintaining
full compliance with all the necessary test requirements.
Approved for fire detection and fire alarm critical signal paths to
BS5839-1:2002+A2:2008 and voice alarm systems to
BS5839-8:2008 in enhanced application areas and emergency
lighting systems to BS5266-1:2005.
Certificate No 077g/02
Mechanical Impact Medium
Fire ResistanceBS 6387 Category CWZBS EN 50200 PH120BS 8434-2 120 min
Low Smoke EmissionsBS EN 61034-2
Halogen Free BS EN 50267-2-1
Flexibility Rigid
Fire Performance BS EN 60332-1-2BS EN 50266-2-4
Bending Radius Fixed r=6D
Temperature Range
-20 to +70°C
FIRE RESISTANT CABLES 300/500V FP PLUS
KEY APPLICATIONS > Fire detection and fire alarm systems for buildings> Voice alarm systems> Emergency lighting> Other essential service circuits
CABLE DESCRIPTION
CONDUCTORPlain annealed copper solid circular conductor complying with BS EN 60228 class 1.
INSULATIONHigh performance damage resistant enhanced InsuditeTM.British Standard Type EI5.
CORE IDENTIFICATION HARMONISED CORE IDENTIFICATION:o o brown-blueo o o brown-black-greyo o o o blue-brown-black-grey SCREEN/CPC Laminated aluminium tape screen bonded to sheath and in contact with full size tinned annealed copper circuit protective conductor which provides automatic screen earthing.
SHEATH Robust thermoplastic enhanced LSOH sheath; Colour - White or Red. Other colours to special order. For external exposure the use of a white sheath is recommended.
Nominal cross
sectional area
mm2
Conceptual Construction
no./mm
Mean overall
diameter
mm
Approximate cable
weight
kg/km
Maximum conductor resistance
at 20°C
ohms/km
Current rating DC or single phase
AC Enclosed
Amps
Current rating DC or single phase
AC Clipped direct
Amps
Volt drop DC or single
phase AC
mV/A/m
1 LSOH®
fixingclips
2 NylonLSOH®
gland
Recommended accessoriesColour - White or Red
FP FirefixTM
fixingclips
Two core
1.5 1/1.38 9.2 115 12.1 16.5 19.5 29 AP9 251/GL2520 UFPNF04
2.5 1/1.78 11.5 176 7.4 23 27 18 AP11 252/GL2520 -
1 Recommended clip spacing 300 mm horizontal and 400mm vertical. 2 Brass glands may be used as an alternative. Minimum recommended installation temperature 0°C.Installation methods for current rating in accordance with BS7671/IEE Wiring Regulations. The tabulated ratings are based upon a 30°C ambient temperature and 70°C operating temperature. For other ambient temperatures or where cables are grouped together, appropriate rating factors should be applied.
Notes to table
Temperature ratings factor
Rating Factors for Groupings
Ambient Temperature°C 25 30 35 40 45 50
Rating factor 1.03 1.00 0.94 0.87 0.79 0.71
Number of circuits 2 3 4 5 6 7
Rating factor 0.80 0.70 0.65 0.60 0.57 0.54
FP PlusTM‘Enhanced’Fire Resistant CablesLow Voltage (300/500 V)
BS7629-1:2008
> Plain annealed copper solid conductor complying with BS EN 60228
class 1.
> Cross-linked damage resistant insulation (Type EI5) over mineral
ceramic (mica/glass) tape.
Core Identifi cation
Insulation
Conductor
Prysmian Cables & Systems Limited, Sales Offi ce, Chickenhall Lane, Eastleigh, Hants, SO50 6YU, UK
Commercial Enquiries, Tel +44 (0) 8457 678 345, Fax: +44 (0) 23 8029 5465
www.prysmian.co.uk
> Robust thermoplastic LSOH® sheath
Colour - White or Red. Other colours to special order
For external exposure the use of a white sheath is recommended
Sheath
oo brown-blueooo brown-black-greyoooo blue-brown-black-grey
> Laminated copper tape screen bonded to sheath and in contact
with full size tinned annealed copper circuit protective
conductor which provides automatic screen earthing.
Ref: FPPlus/02/09
Screen
TemperatureRange
-20 to +70°C
Bending RadiusFixed r=6D
Mechanical ImpactMedium
Fire PerformanceBSEN60332-1-2BSEN50266-2-4
FlexibilityRigid
Halogen FreeBSEN50267-2-1
Low Smoke Emissions
BSEN61034-2
Fire ResistantBS6387 Category CWZ
BSEN50200 PH120BS8434-2 120 min
> Fire detection and fi re alarm systems for buildings. FP PLUSTM
is BASEC and LPCB approved in accordance with the requirements
of BS5839-1:2002+A2:2008 Clause 26.2 for enhanced fi re
resisting cables.
Key Applications
Certifi cate no 077g
Cable Details
Prysmian Cables & Systems Limited, Sales Offi ce, Chickenhall Lane, Eastleigh, Hants, SO50 6YU, UK
Commercial Enquiries, Tel +44 (0) 8457 678 345, Fax: +44 (0) 23 8029 5465
www.prysmian.co.uk
Ref:FPPlus/02/09
Nominalcross
sectionalarea
mm²
Conceptual construction
no./mm
Mean overall
diameter
mm
Approximate cable weight
kg/km
Maximum conductor resistance
at 20°C
ohms/km
Current ratingDC or single
phase AC Enclosed
Amps
Current rating DC or single phase
ACClipped direct
Amps
Volt drop DC or single
phase AC
mV/A/m
RecommendedAccessories
LSOH® fi xing clips 1
Nylon LSOH® gland 2
Two Core
1.0 1/1.13 8.5 110 18.1 13 15 44 AP8 251/GL2520
Three Core
1.0 1/1.13 9.0 125 18.1 13 15 44 AP9 251/GL2520
1.5 1/1.38 10.0 150 12.1 16.5 19.5 29 AP10 251/GL2520
Four Core
1.0 1/1.13 10.3 160 18.1 13 15 44 AP10 252/GL2520
1.5 1/1.38 11.0 190 12.1 16.5 19.5 29 AP11 252/GL2520
1 Recommended clip spacing 300mm horizontal and 400mm vertical 2 Brass glands may be used as an alternative
Minimum recommended installation temperature 0°C
Installation methods for current rating in accordance with BS7671/IEE Wiring Regulations
The tabulated ratings are based upon a 30°C ambient temperature and 70°C operating temperature.
For other ambient temperatures or where cables are grouped together, the appropriate rating factors should be applied.
FP PLUSTM Fire Resistant Cable
Temperature ratings factor
Correction factors for groupings
Ambient Temperature°C 25 30 35 40 45 50
Rating factor 1.03 1.00 0.94 0.87 0.79 0.71
Number of circuits 2 3 4 5 6 7
Rating factor 0.80 0.70 0.65 0.60 0.57 0.54
FP Plus Flex‘Enhanced’Fire Resistant CablesLow Voltage (300/500 V)
BS7629-1:2008
> Plain annealed copper solid (1.0 - 1.5mm²) or stranded (2.5 - 4.0mm²)
conductor complying with BS EN 60228 class 1 or class 2.
> Cross-linked damage resistant insulation (Type EI5) over mineral
ceramic (mica/glass) tape.
Core Identifi cation
Insulation
Conductor
Prysmian Cables & Systems Limited, Sales Offi ce, Chickenhall Lane, Eastleigh, Hants, SO50 6YU, UK
Commercial Enquiries, Tel +44 (0) 8457 678 345, Fax: +44 (0) 23 8029 5465
www.prysmian.co.uk
> Robust thermoplastic LSOH® sheath
> Colour - White or Red
> Other colours to special order
> For external exposure the use of a white sheath is recommended
Sheath
oo brown-blueooo brown-black-greyoooo blue-brown-black-grey
> Helically applied laminated copper tape screen in contact
with full size tinned annealed copper circuit protective conductor
which provides automatic screen earthing.
Ref: FPPlusFlex/01/09
Screen
TemperatureRange
-25 to +70°C
Bending RadiusFixed r=6D
Mechanical ImpactMedium
Fire PerformanceBSEN60332-1-2BSEN50266-2-4
FlexibilitySemi Flexible
Halogen FreeBSEN50267-2-1
Low Smoke Emissions
BSEN61034-2
Fire ResistantBS6387 Category CWZ
BSEN50200 PH120BS8434-2 120 min
> Fire detection and fi re alarm systems for buildings. FP PLUS Flex
is BASEC and LPCB approved in accordance with the requirements
of BS5839-1:2002+A2:2008 Clause 26.2 for enhanced fi re
resisting cables. Ideal for installations where a more fl exible cable
is required.
Key Applications
Certifi cate no 077h
Cable Details
Prysmian Cables & Systems Limited, Sales Offi ce, Chickenhall Lane, Eastleigh, Hants, SO50 6YU, UK
Commercial Enquiries, Tel +44 (0) 8457 678 345, Fax: +44 (0) 23 8029 5465
www.prysmian.co.uk
Ref:FPPlusFlex/01/09
Nominalcross
sectionalarea
mm²
Conceptual construction
no./mm
Mean overall
diameter
mm
Approximate cable weight
kg/km
Maximum conductor resistance
at 20°C
ohms/km
Current ratingDC or single
phase AC Enclosed
Amps
Current rating DC or single phase
ACClipped direct
Amps
Volt drop DC or single
phase AC
mV/A/m
RecommendedAccessories
LSOH® fi xing clips 1
Nylon LSOH® gland 2
Two Core
1.0 1/1.13 8.8 110 18.1 13 15 44 AP8 251/GL2520
1.5 1/1.38 9.4 130 12.1 16.5 19.5 29 AP9 251/GL2520
2.5 7/0.67 11.2 180 7.4 23 27 18 AP11 252/GL2520
4.0 7/0.85 12.6 240 4.6 30 36 11 AP12 252
Three Core
1.0 1/1.13 9.4 130 18.1 13 15 44 AP9 251/GL2520
1.5 1/1.38 10.0 155 12.1 16.5 19.5 29 AP10 252/GL2520
2.5 7/0.67 12.0 220 7.4 23 27 18 AP11 252
4.0 7/0.85 13.4 300 4.6 30 36 11 AP13 254
Four Core
1.0 1/1.13 10.4 160 18.1 13 15 44 AP10 252/GL2520
1.5 1/1.38 11.0 190 12.1 16.5 19.5 29 AP11 252/GL2520
2.5 7/0.67 13.3 280 7.4 23 27 18 AP13 254
4.0 7/0.85 15.0 390 4.6 30 36 11 AP15 254
1 Recommended clip spacing 300mm horizontal and 400mm vertical 2 Brass glands may be used as an alternative
Minimum recommended installation temperature 0°C
Installation methods for current rating in accordance with BS7671/IEE Wiring Regulations
The tabulated ratings are based upon a 30°C ambient temperature and 70°C operating temperature.
For other ambient temperatures or where cables are grouped together, the appropriate rating factors should be applied.
FP PLUS FLEX Fire Resistant Cable
Temperature ratings factor
Correction factors for groupings
Ambient Temperature°C 25 30 35 40 45 50
Rating factor 1.03 1.00 0.94 0.87 0.79 0.71
Number of circuits 2 3 4 5 6 7
Rating factor 0.80 0.70 0.65 0.60 0.57 0.54
UK Sales enquiriesTel: 0845 767 8345Fax: 023 8029 5465
UK Technical helplineTel: 023 8029 5222Fax: 023 8029 [email protected]
Prysmian Cables & Systems LimitedChickenhall LaneEastleighHampshireS050 6YUUnited Kingdom
For further information please see our dedicated FP website:www.fpcables.co.uk www.prysmian.co.uk
Overseas Sales enquiresTel: +44 23 5029 5481Fax: +44 23 8029 5465
Overseas Technical helplineTel: +44 23 8029 5481Fax: +44 23 8029 5111
Information hotlineTel: +44 (0) 23 8029 5029Fax: +44 (0) 23 8029 [email protected]
Ref:FP PLUS/03/11
FP Plus Flex‘Enhanced’Fire Resistant CablesLow Voltage (300/500 V)
BS7629-1:2008
> Plain annealed copper solid (1.0 - 1.5mm²) or stranded (2.5 - 4.0mm²)
conductor complying with BS EN 60228 class 1 or class 2.
> Cross-linked damage resistant insulation (Type EI5) over mineral
ceramic (mica/glass) tape.
Core Identifi cation
Insulation
Conductor
Prysmian Cables & Systems Limited, Sales Offi ce, Chickenhall Lane, Eastleigh, Hants, SO50 6YU, UK
Commercial Enquiries, Tel +44 (0) 8457 678 345, Fax: +44 (0) 23 8029 5465
www.prysmian.co.uk
> Robust thermoplastic LSOH® sheath
> Colour - White or Red
> Other colours to special order
> For external exposure the use of a white sheath is recommended
Sheath
oo brown-blueooo brown-black-greyoooo blue-brown-black-grey
> Helically applied laminated copper tape screen in contact
with full size tinned annealed copper circuit protective conductor
which provides automatic screen earthing.
Ref: FPPlusFlex/01/09
Screen
TemperatureRange
-25 to +70°C
Bending RadiusFixed r=6D
Mechanical ImpactMedium
Fire PerformanceBSEN60332-1-2BSEN50266-2-4
FlexibilitySemi Flexible
Halogen FreeBSEN50267-2-1
Low Smoke Emissions
BSEN61034-2
Fire ResistantBS6387 Category CWZ
BSEN50200 PH120BS8434-2 120 min
> Fire detection and fi re alarm systems for buildings. FP PLUS Flex
is BASEC and LPCB approved in accordance with the requirements
of BS5839-1:2002+A2:2008 Clause 26.2 for enhanced fi re
resisting cables. Ideal for installations where a more fl exible cable
is required.
Key Applications
Certifi cate no 077h
Cable Details
Prysmian Cables & Systems Limited, Sales Offi ce, Chickenhall Lane, Eastleigh, Hants, SO50 6YU, UK
Commercial Enquiries, Tel +44 (0) 8457 678 345, Fax: +44 (0) 23 8029 5465
www.prysmian.co.uk
Ref:FPPlusFlex/01/09
Nominalcross
sectionalarea
mm²
Conceptual construction
no./mm
Mean overall
diameter
mm
Approximate cable weight
kg/km
Maximum conductor resistance
at 20°C
ohms/km
Current ratingDC or single
phase AC Enclosed
Amps
Current rating DC or single phase
ACClipped direct
Amps
Volt drop DC or single
phase AC
mV/A/m
RecommendedAccessories
LSOH® fi xing clips 1
Nylon LSOH® gland 2
Two Core
1.0 1/1.13 8.8 110 18.1 13 15 44 AP8 251/GL2520
1.5 1/1.38 9.4 130 12.1 16.5 19.5 29 AP9 251/GL2520
2.5 7/0.67 11.2 180 7.4 23 27 18 AP11 252/GL2520
4.0 7/0.85 12.6 240 4.6 30 36 11 AP12 252
Three Core
1.0 1/1.13 9.4 130 18.1 13 15 44 AP9 251/GL2520
1.5 1/1.38 10.0 155 12.1 16.5 19.5 29 AP10 252/GL2520
2.5 7/0.67 12.0 220 7.4 23 27 18 AP11 252
4.0 7/0.85 13.4 300 4.6 30 36 11 AP13 254
Four Core
1.0 1/1.13 10.4 160 18.1 13 15 44 AP10 252/GL2520
1.5 1/1.38 11.0 190 12.1 16.5 19.5 29 AP11 252/GL2520
2.5 7/0.67 13.3 280 7.4 23 27 18 AP13 254
4.0 7/0.85 15.0 390 4.6 30 36 11 AP15 254
1 Recommended clip spacing 300mm horizontal and 400mm vertical 2 Brass glands may be used as an alternative
Minimum recommended installation temperature 0°C
Installation methods for current rating in accordance with BS7671/IEE Wiring Regulations
The tabulated ratings are based upon a 30°C ambient temperature and 70°C operating temperature.
For other ambient temperatures or where cables are grouped together, the appropriate rating factors should be applied.
FP PLUS FLEX Fire Resistant Cable
Temperature ratings factor
Correction factors for groupings
Ambient Temperature°C 25 30 35 40 45 50
Rating factor 1.03 1.00 0.94 0.87 0.79 0.71
Number of circuits 2 3 4 5 6 7
Rating factor 0.80 0.70 0.65 0.60 0.57 0.54
> Prysmian FP400® is the original fire resistant armoured cable providing an easy to install and terminate, robust fire resistant wiring system. In addition to maintaining circuit integrity during a fire, FP400® produces very low levels of smoke and virtually no (less than 0.5%) acidic gases, thus safeguarding human life and protecting equipment.
FP400® handles like a standard armoured cable and can be installed just as easily. No special tools or accessories are needed for installation or termination of FP400®, which ensures that substantial installation cost savings, compared with MICC, can be achieved through its use.
FP400® is suitable for indoor or outdoor installation requiring a robust armoured cable, including direct burial, trough, fixed direct, tray or ladder.
Prysmian FP400® complies with BS7846 Category F2 which ensures that it complies with the requirements for "protected power circuits" given in the 2000 edition of Approved Document B Fire safety of The Building Regulations 2000.
> Prysmian FP400® is British Approvals Service for Cables (BASEC) approved to BS7846 Category F2. It is also Loss Prevention Certification Board (LPCB) listed as a fire resistant cable and approved to BS6387 Category CWZ, at an enhanced voltage of 600/1000V.
Witnessed ad-hoc tests have demonstrated the ability of FP400®
to achieve fire resistant properties in excess of those required by BS6387 Category CWZ and on the basis of these tests Prysmian FP400® has been approved for many projects where previously only MICC had been approved.
Additional tests have demonstrated the ability of FP400® to achieve a 60 minute rating (PH60) to BS EN50200 and a 30 minute rating to BS8434-1. These tests demonstrate that FP400®
also meets the requirements for use in "standard" installations in accordance with BS5839-1:2002 for fire detection and alarm systems, and "Cables with inherently high resistance to attack by fire" in accordance with BS5266-1:2005 for emergency lighting.
All Prysmian FP400®cables are manufactured under an ISO 9001 Quality System certified by BASEC and LPCB.
> Prysmian FP400® may be considered as a low smoke armoured cable to BS6724 for the purposes of installation and should be installed in accordance with BS7671/IEE Wiring Regulations or any other appropriate national regulations. Although standard armour cable fixings and glands may be used, it is important to ensure that, when the cable is required to maintain circuit integrity in a fire, any fixing used to support the cable can also withstand that fire. The use of the appropriate BICON® gland or cleat is recommended.
TemperatureRange
-25 to +90°C
Bending RadiusCircular conductor r=6DShaped conductor r=8D
Mechnical ImpactVery Good
Fire PerformanceBSEN60332-1-2BSEN50266-2-4
FlexibilityRigid
Halogen FreeBSEN50267-2-1
Low Smoke EmissionsBSEN61034-2
Fire ResistantBS6387Category
CWZ
Certificate No 077bCertificate No 517b
Ambient Temperature °C 25 30 35 40 45 50 55 60
Rating factor 1.02 1.00 0.96 0.91 0.87 0.82 0.76 0.71
> Essential safety circuits associated with fire detection, fire alarm, emergency lighting and particularly for power supplies to building equipment used in safety systems.
CONDUCTORPlain annealed copper stranded (class 2) conductor for ease of handling.
PRIMARY INSULATIONMineral ceramic (Mica/Glass) fire resistant tape
SECONDARY INSULATION90°C cross - linked insulation
HARMONISED CORE IDENTIFICATION:o o brown-blueo o o brown-black-greyo o o o blue-brown-black-grey7-48 cores white with printed numbers
NON HARMONISED CORE IDENTIFICATION:o o red-blacko o o red-yellow-blueo o o o black-red-yellow-blueNon harmonised colours to special order.
BEDDINGExtruded LSOH bedding compound.
ARMOURSingle layer of galvanised steel wires.
SHEATHRobust LSOH sheath. Colour - black.Other colours to special order
Minimum recommended installation temperature 0°C.Suitable for indoor and outdoor installations. For external exposure the use of a Black sheath is recommended.
Should be installed in accordance with BS7671/IEE Wiring Regulations or any other appropriate national regulations.
Suitable for direct burial, trough, tray, ladder or other installations requiring a robust armoured cable.
A minimum internal radius of bend of 6 x cable diameter is recommended during installations for cables having circular conductors and 8 x cable diameter for cables having shaped conductors.
No special accessories are required for the installationof FP400®.
Standard brass armoured cable glands and cast iron cleats may be used.
When the cable is required to maintain circuit integrity in a fire, it is important that any accessory used to support the cable can also withstand that fire. The use of the appropriate BICON® gland or cleat is recommended.
CURRENT RATINGSThe tabulated ratings are based upon a 30°C ambient temperature and a 90°C operating temperature.For other ambient temperatures or where cables are grouped together, the following rating factors should be applied.
Rating factors for Ambient temperatures
* Spaced by a clearance between adjacent surfaces of at least one cable diameter.Where the horizontal clearance between adjacent cables exceeds 2 cable diameters no correction factor need be appliedNote. Standard conditions of grouping as stated in BS7671 IEE Wiring Regs apply
Installation MethodNumber of circuits or multi-core cables
2 3 4 5 6 7 8 9
Single layer clipped to a non-metallic surface
Touching 0.85 0.79 0.75 0.73 0.72 0.72 0.71 0.70
Spaced* 0.94 0.90 0.90 0.90 0.90 0.90 0.90 0.90
Single layer multicore on a perforated metal cable tray,
vertical or horizontal
Touching 0.88 0.82 0.77 0.75 0.73 0.73 0.72 0.72
Spaced* 0.91 0.89 0.88 0.87 0.87 - - -
Rating factors for grouping of cables
Nominalcross
sectionalareamm2
Approximateoverall
diameter
mm
Approximatediameter
underarmour
mm
Nominaldiameterof armour
wiresmm
Approximatecable
weight
kg/km
Maximumconductorresistanceat 20°Cohms/km
Short Circuitrating (1 sec)of conductor
KA
Current ratingThree
phase AC Clipped direct
Amps
Current ratingThree
phase AC Free AirAmps
Volt dropThree
phase AC
mV/A/m
Three Core
1.5 13.4 8.8 0.9 340 12.1 0.20 23 25 27
2.5 14.8 10.2 0.9 430 7.41 0.35 31 33 16
4 16.1 11.5 0.9 510 4.61 0.57 42 44 10
6 17.4 12.8 0.9 620 3.08 086 53 56 6.8
10 20.3 14.8 1.25 930 1.83 1.4 73 78 4.0
16 22.8 17.1 1.25 1210 1.15 2.2 94 99 2.5
25 27.4 20.8 1.6 1800 0.727 3.6 124 131 1.65
35 29.2 22.4 1.6 2100 0.524 5.0 154 162 1.15
50 33.0 26.2 1.6 2600 0.387 7.1 187 197 0.87
70 37.0 30.0 1.6 3400 0.268 10.0 238 251 0.60
95 40.6 32.4 2.0 4500 0.193 13.6 289 304 0.45
120 43.8 35.4 2.0 5500 0.153 17.2 335 353 0.37
150 48.0 38.4 2.5 6900 0.124 21.4 386 406 0.30
185 52.0 42.2 2.5 8200 0.0991 26.5 441 463 0.26
240 57.1 46.9 2.5 10200 0.0754 34.3 520 546 0.21
300 63.0 52.6 2.5 12200 0.0601 42.9 599 628 0.185
400 69.5 58.7 2.5 15000 0.0470 57.2 673 728 0.165
Four Core
1.5 14.3 9.7 0.9 390 12.1 0.20 23 25 27
2.5 16.0 11.4 0.9 490 7.41 0.35 31 33 16
4 17.3 12.7 0.9 590 4.61 0.57 42 44 10
6 19.6 14.1 1.25 830 3.08 0.86 53 56 6.8
10 21.8 16.3 1.25 1040 1.83 1.4 73 78 4.0
16 24.6 18.9 1.25 1370 1.15 2.2 94 99 2.5
25 29.1 22.5 1.6 2100 0.727 3.6 124 131 1.65
35 32.2 25.4 1.6 2500 0.524 5.0 154 162 1.15
50 35.0 28.0 1.6 3200 0.387 7.1 187 197 0.87
70 40.2 32.0 2.0 4500 0.268 10.0 238 251 0.60
95 44.0 35.6 2.0 5600 0.193 13.6 289 304 0.45
120 48.4 38.8 2.5 7200 0.153 17.2 335 353 0.37
150 52.5 42.7 2.5 8500 0.124 21.4 386 406 0.30
185 57.1 46.9 2.5 10300 0.0991 26.5 441 463 0.26
240 62.7 52.3 2.5 12800 0.0754 34.3 520 546 0.21
300 69.6 58.8 2.5 15600 0.0601 42.9 599 628 0.185
400 78.0 65.3 3.15 20400 0.0470 57.2 673 728 0.165
Circular conductor 1.5 - 35mm2.
Shaped conductor 50mm2 and above.Installation methods for current rating in accordance with BS7671/IEE Wiring Regulations. The tabulated ratings are based upon a 30°C ambient temperature and 90°C operating temperature.
LOW VOLTAGE 600/1000V
Nominalcross
sectionalareamm2
Approximateoverall
diameter
mm
Approximatediameter
underarmour
mm
Nominaldiameterof armour
wiresmm
Approximatecable
weight
kg/km
Maximumconductorresistance
at 20°Cohms/km
Current ratingDC or Single
phase ACClipped direct
Amps
Current ratingDC or Single
phase ACFree Air Amps
Volt dropDC
mV/A/m
Volt dropSingle
phase AC
mV/A/m
Two Core
1.5 12.9 8.3 0.9 310 12.1 27 29 31 31
2.5 14.1 9.6 0.9 380 7.41 36 39 19 19
4 15.2 10.6 0.9 450 4.61 49 52 12 12
6 16.4 12.0 0.9 530 3.08 62 66 7.9 7.9
10 18.6 14.0 0.9 630 1.83 85 90 4.7 4.7
16 21.4 15.9 0.9 920 1.15 110 115 2.9 2.9
25 25.0 19.0 1.25 1200 0.727 146 152 1.85 1.9
35 28.0 21.0 1.6 1600 0.524 180 188 1.35 1.35
50 28.0 21.2 1.6 2000 0.387 219 228 0.98 1.00
70 31.0 24.0 1.6 2400 0.268 279 291 0.67 0.69
95 33.0 26.0 2.0 3300 0.193 338 354 0.49 0.52
120 37.0 29.0 2.0 3800 0.153 392 410 0.39 0.42
150 39.3 30.9 2.0 4400 0.124 451 472 0.31 0.35
185 44.2 34.4 2.5 5700 0.0991 515 539 0.25 0.29
240 48.0 38.0 2.5 7200 0.0754 607 636 0.195 0.24
300 54.0 44.0 2.5 8300 0.0601 698 732 0.155 0.21
400 59.0 49.0 2.5 10500 0.0470 787 847 0.120 0.19
Seven Core
1.5 16.4 11.8 0.9 500 12.1 27 * 29 * 31 31
2.5 18.3 13.7 0.9 640 7.41 36 * 39 * 19 19
4 20.8 15.3 1.25 910 4.61 49 * 52 * 12 12
Twelve Core
1.5 21.2 15.7 1.25 850 12.1 27 * 29 * 31 31
2.5 24.0 18.3 1.25 1090 7.41 36 * 39 * 19 19
4 27.3 20.9 1.6 1550 4.61 49 * 52 * 12 12
Nineteen Core
1.5 24.2 18.5 1.25 1120 12.1 27 * 29 * 31 31
2.5 28.6 22.0 1.6 1650 7.41 36 * 39 * 19 19
Twenty-seven Core
1.5 29.4 22.8 1.6 1650 12.1 27 * 29 * 31 31
2.5 33.4 26.6 1.6 2150 7.41 36 * 39 * 19 19
Thirty-seven Core
1.5 32.2 25.6 1.6 2000 12.1 27 * 29 * 31 31
2.5 36.7 29.9 1.6 2650 7.41 36 * 39 * 19 19
*The tabulated rating is as a two core cable and may be used where the number of cores carrying current does not exceed its square root of the total number of cores.
Ref:FP40
0/PY
/08
/07
UK Sales enquiriesTel: 0845 767 8345Fax: 023 8029 5465
UK Technical helpline Tel: 0845 767 8345Fax: 023 8029 5002
Prysmian Cables & Systems Limited Chickenhall LaneEastleighHampshireSO50 6YU United Kingdom
For further information please see our dedicated FP website: www.fpcables.co.uk
www.prysmian.co.uk
Overseas Sales enquiriesTel: +44 23 8029 5481Fax: +44 23 8029 5465
Overseas Technical helpline Tel: +44 23 8029 5481Fax: +44 23 8029 5002
Information hotlineTel: +44 (0) 23 8029 5029Fax: +44 (0) 23 8029 5437 [email protected]
FP600S
FIRE RESISTANT CABLES
Ultimate Protection for Electrical Emergency
Systems
Mechanical Impact Very Good
Temperature Range
-25 to +90°C
Fire ResistanceBS 7846 120 minBS 8491 120 min
Low Smoke EmissionsBS EN 61034-2
Halogen Free BS EN 50267-2-1
Flexibility Rigid
Flame PropagationBS EN 60332-1-2BS EN 60332-3-24
Bending Radius Fixed
Circular conductor r= 6DShaped conductor r= 8D
FIRE RESISTANT CABLES
Certificate No 077nCertificate No 517c/01
FP 600SBS 7846-F120
CABLE CHARACTERISTICS
FP600S is the ultimate fire resistant armoured power cable and it’s the right choice to power life safety or fire fighting systems in large and complex buildings.
BS 8519 – Category 1, 2 and 3
BS 7846 – F120, 120 mins fire, water jet & direct impact
BS 8491 – 120 mins fire, water jet & direct impact
BASEC – approved*
LPCB – approved*
London Underground – approved*
Afumex – Reduced flame propagation, low smoke and corrosive gas emission.
Designed, manufactured and tested by Prysmian in the UK to meet the demands of clients, engineers, regulators and installers.
FP600S is easy to install, requires no special tools and can be terminated, glanded and cleated like a standard armoured cable allowing significant savings compared with MICC.
>
>
>
>
>
>
>
* see www.fpcables.co.uk for certificates
4 21 15 1.25 800 4.61 0.57 42 44 10 370CG04 LSF25CW
6 23 17 1.25 950 3.08 0.86 53 56 6.8 370CG05 LSF25CW
10 24 19 1.25 1200 1.83 1.4 73 78 4.0 370CG05 LSF25CW
16 27 20 1.25 1600 1.15 2.2 94 99 2.5 370CG06 LSF25CW
25 32 24 1.6 2400 0.727 3.6 124 131 1.65 370CG07 LSF32CW
35 35 27 1.6 2800 0.524 5.0 154 162 1.15 370CG07 LSF40CW
50 36 29 1.6 3200 0.387 7.1 187 197 0.87 370CG08 LSF40CW
70 41 32 2.0 4500 0.268 10 238 251 0.64 370CG08 LSF50SCW
95 44 36 2.0 5700 0.193 13.6 289 304 0.45 370CG09 LSF50SCW
120 49 40 2.5 7300 0.153 17.2 335 353 0.37 370CG09 LSF50CW
150 55 44 2.5 8600 0.124 21.4 386 406 0.30 370CG10 LSF63CW
185 59 48 2.5 10500 0.0991 26.5 441 463 0.26 370CG11 LSF63CW
240 64 54 2.5 12900 0.0754 34.3 520 546 0.21 370CG12 LSF75CW
300 70 59 2.5 15500 0.0601 42.9 599 628 0.185 370CG13 LSF75CW
400 79 66 3.15 20100 0.0470 57.2 673 728 0.165 370CG14 CW85K
4 21 15 1.25 800 4.61 0.57 42 44 10 370CG04 LSF25CW
6 21 15 1.25 820 3.08 0.86 53 56 6.8 370CG04 LSF25CW
10 23 17 1.25 1050 1.83 1.4 73 78 4.0 370CG05 LSF25CW
16 24 19 1.25 1400 1.15 2.2 94 99 2.5 370CG06 LSF25CW
25 29 22 1.6 2000 0.727 3.6 124 131 1.65 370CG06 LSF32CW
35 31 24 1.6 2300 0.524 5.0 154 162 1.15 370CG07 LSF32CW
50 32 25 1.6 2800 0.387 7.1 187 197 0.87 370CG07 LSF40CW
70 36 29 1.6 3600 0.268 10 238 251 0.6 370CG08 LSF50SCW
95 40 32 2.0 4500 0.193 13.6 289 304 0.45 370CG08 LSF50SCW
120 43 35 2.0 5400 0.153 17.2 335 353 0.37 370CG08 LSF50SCW
150 48 39 2.5 6900 0.124 21.4 386 406 0.30 370CG09 LSF50CW
185 52 43 2.5 8200 0.0991 26.5 441 463 0.26 370CG09 LSF63CW
240 57 47 2.5 10100 0.0754 34.3 520 456 0.21 370CG09 LSF63CW
300 62 52 2.5 12200 0.0601 42.9 599 628 0.185 370CG11 LSF63CW
400 69 58 2.5 15000 0.0470 57.2 673 728 0.165 370CG12 LSF75CW
Nominal cross
sectional area
mm2
Approximateoverall
diameter
mm
Approximatediameterunderarmour
mm
Nominaldiameterof armour
wires
mm
Approximatecable weight
kg/km
Maximum conductor resistance at 20°C
ohms/km
Short circuit rating
(1sec) of conductor
kA
Current rating Three phase AC clipped
direct
AmpsClaw Cleat
Ref No.
Recommended accessoriesCurrent rating Three phase
AC Free air
Amps
Volt drop Three phase
AC
mV/A/m
Brass GlandRef No.
Three Core
Four Core
Circular conductor 4.0-35mm2
Shaped conductor 50mm2 and above
Installation methods for current rating in accordance with BS7671/IEE Wiring Regulations.
The tabulated ratings are based upon a 30°C ambient temperature and 90°C operating temperature.
For other ambient temperatures or where cables are grouped together, the following rating factors should be applied.
FP600S FIRE RESISTANT CABLES
FP600S
4 21 15 1.25 800 4.61 41 52 12 12 370CG04 LSF25CW
6 21 15 1.25 800 3.08 62 66 7.9 7.9 370CG04 LSF25CW
10 22 16 1.25 800 1.83 85 90 4.7 4.7 370CG04 LSF25CW
16 23 17 1.25 1000 1.15 110 115 2.9 2.9 370CG05 LSF25CW
25 26 20 1.25 1300 0.727 146 152 1.85 1.90 370CG06 LSF25CW
35 30 23 1.6 1800 0.524 180 188 1.35 1.35 370CG06 LSF32CW
50 31 24 1.6 2200 0.387 219 228 0.98 1.0 370CG06 LSF32CW
70 33 26 1.6 2600 0.268 279 291 0.67 0.69 370CG07 LSF32CW
95 35 27 2.0 3400 0.193 338 354 0.49 0.52 370CG07 LSF40CW
120 39 30 2.0 4100 0.153 392 410 0.39 0.42 370CG08 LSF50SCW
150 42 33 2.0 4700 0.124 451 472 0.31 0.35 370CG08 LSF50SCW
185 46 36 2.5 6100 0.0091 515 539 0.25 0.29 370CG09 LSF50CW
240 51 41 2.5 7500 0.0754 607 636 0.795 0.24 370CG09 LSF50CW
300 56 45 2.5 9000 0.0601 698 732 0.155 0.21 370CG10 LSF63CW
400 61 50 2.5 11000 0.0470 787 847 0.120 0.19 370CG11 LSF63CW
Nominal cross
sectional area
mm2
Approximateoverall
diameter
mm
Approximatediameterunderarmour
mm
Nominaldiameterof armour
wires
mm
Approximatecable weight
kg/km
Maximum conductor resistance at 20°C
ohms/km
Current Rating DC or single
phase AC Free Air
Amps
Current rating DC or single phase AC
clipped direct
AmpsClaw Cleat
Ref No.
Recommended accessoriesVoltage drop DC
mV/A/m
Volt drop single phase
AC
mV/A/m
Brass GlandRef No.
Two Core
FP600S
LOW VOLTAGE 600/1000V
KEY APPLICATIONS
Electrical supplies for fire fighting, life safety and property protection systems. Active fire safety systems part of a Fire Safety Engineering solution rely on an effective electrical supply remaining operational during a fire as described in BS8519:2010.
Greater emphasis is now being given to the integrity of electrical circuits which maintain the functional safe working conditions of such equipment and systems. FP600S is a new generation fire resistant power cable designed to meet the much more onerous fire survival requirement now considered appropriate for such applications.
Examples of circuits which are required to remain operational under such conditions include:
CABLE DESCRIPTION
CONDUCTORPlain annelaed copper stranded circular (4-35 mm²) or shaped (50-400 mm²) conductor complying with BS EN 60228 Class 2.
INSULATIONPrimary Insulation:Mineral ceramic (Mica/Glass) fire resistant tape
Secondary Insulation:90°C cross - linked insulation
Ambient Temperature °C 25 30 35 40 45 50 55 60
Correction Factor 1.02 1.0 0.96 0.91 0.87 0.82 0.76 0.71
Installation MethodNumber of circuits or multi-core cables
2 3 4 5 6 7 8 9
Single layer clipped to a non-metallic surface
Touching 0.85 0.79 0.75 0.73 0.72 0.72 0.71 0.70
Spaced* 0.94 0.90 0.90 0.90 0.90 0.90 0.90 0.90
Single layer multicore on a perforated metal cable tray,
vertical or horizontal
Touching 0.86 0.81 0.77 0.75 0.74 0.73 0.73 0.72
Spaced* 0.91 0.89 0.88 0.87 0.87 - - -
Correction factors for Ambient temperatures
Fire-fighting lift shafts>
>
Correction factors for grouping of cables
*Spaced by a clearance between adjacent surfaces of at least one cable diameter. Where the horizontal clearance between adjacent cables exceeds 2 cable diameters no correction factor need be applied. Note: Standard conditions of grouping as stated in BS791 (IEE Wiring Regs) apply.
FP600S
FP600S FIRE RESISTANT CABLES
CORE IDENTIFICATION
oo brown-blueooo brown-black-greyoooo blue-brown-black-grey
BEDDINGThermoplastic LSOH bedding compound
ARMOURSingle layer of galvanised steel wires
SHEATHRobust thermoplastic LSOH sheath. Colour - black.Other colours to speical order
INSTALLATION
Minimum recommended installation temperature 0°C.Suitable for indoor and outdoor installations. For externalexposure the use of a Black sheath is recommended.
Should be installed in accordance with BS7671/IEE WiringRegulations or any other appropriate national regulations.
Suitable for direct burial, trough, tray, ladder orother installations requiring a robust armoured cable.
BENDING RADIUS
A minimum internal radius of bend of 6 x cable diameteris recommended during installations for cables havingcircular conductors and 8 x cable diameter for cableshaving shaped conductors.
ACCESSORIESNo special accessories are required for the installationof FP600S.
Standard brass armoured cable glands and cast iron cleatsmay be used.
When the cable is required to maintain circuit integrityin a fire, it is important that any accessory used tosupport the cable can also withstand that fire. The use ofthe appropriate BICON® gland or cleat is recommended.
> Pressurization > Emergency lighting> Lift power suppliers
Fire suppression systems> Watermist> Sprinkler pumps > Hose reel
> Escape systems> Smoke and fire barriers > Smoke fans> Smoke curtains and sliding doors
BS8519 requires fire resistant power cable to meet category 1, 2 or 3 of BS8491, the integrated fire, shock and water jet test.
FP600S meets all three categories and achieves the highest 120 minute fire test rating.
Sales enquiriesTel: 0845 767 8345Fax: 023 8029 5465
UK Technical helplineTel: 0845 767 8345Fax: 023 8029 5002
Prysmian Cables & Systems LimitedChickenhall LaneEastleighHampshireS050 6YUUnited Kingdom
For further information please see our dedicated FP website:www.fpcables.co.uk www.prysmian.co.uk
Overseas Sales enquiresTel: +44 23 5029 5481Fax: +44 23 8029 5465
Overseas Technical helplineTel: +44 23 8029 5481Fax: +44 23 8029 5002
Information hotlineTel: +44 (0) 23 8029 5029Fax: +44 (0) 23 8029 [email protected]
Ref:FP600S/01/11
> Installation in surface mounted or embedded conduits, or similar closed
systems and for fi xed protected installation in or on lighting fi ttings and
inside appliances, switchgear and control gear particularly for situations
in which low emissions of smoke and acid gas is requred in case of
burning
> Green/Yellow for use as earth
LSOH Conduit Wire(HO7Z-R)
Key Applications
Ref: 6491B/06/09
LSOH Wiring CablesLow Voltage (450/750 V)
6491B
Cable Approvals Cable approved to BS7211
> Plain annealed copper stranded circular conductor complying with
BS EN 60228 Class 2
> 90°C LSOH insulation complying with BS EN 50363-5 Type El 5
Core Identifi cation
Insulation
Conductor
Prysmian Cables & Systems Limited, Sales Offi ce, Chickenhall Lane, Eastleigh, Hants, SO50 6YU, UK
Commercial Enquiries, Tel +44 (0) 8457 678 345, Fax: +44 (0) 23 8029 5465
www.prysmian.co.uk
TemperatureRange
-25 to +90°C
BendingRadius
Fixed r=6D
MechanicalImpactMedium
Fire PerformanceBS EN 60332-1-2
FlexibiltyRigid
o Redo Blacko Blueo Yellowo Browno Greyoooooooo Green/Yellow
Other core colours are available on request
Halogen freeBS EN 50267-2-2
Low smoke emissions
BS EN 61034-2
Cable Details
Ref: 6491B/06/09 Prysmian Cables & Systems Limited, Sales Offi ce, Chickenhall Lane, Eastleigh, Hants, SO50 6YU, UK
Commercial Enquiries, Tel +44 (0) 8457 678 345, Fax: +44 (0) 23 8029 5465
www.prysmian.co.uk
Nominalcross
sectionalarea
mm²
Conceptualconstruction
no/mm
Approx.overall
diameter
mm
Approx.cable
weight
kg
Maximumconductorresistance
at 20°C
ohms/km
Shortcircuitrating
90-160°C(1 sec)
kA
Shortcircuitrating 90-
250°C(1 sec)
kA
Currentrating DC or single phase AC enclosed
inconduit
ortrunking
Amps
CurrentratingThree
phase AC enclosed
inconduit
ortrunking
Amps
VoltagedropDC
mV/A/m
VoltagedropDC or singlephase
AC
mV/A/m
Voltagedropthreephase
AC
mV/A/m
1.5 7/0.53 3 21 12.1 0.15 0.22 22 19 31 31 27
2.5 7/0.67 3.6 32 7.41 0.25 0.36 30 26 19 19 16
4 7/0.85 4.2 47 4.61 0.4 0.6 40 35 12 12 10
6 7/1.04 4.7 66 3.08 0.6 0.9 51 45 7.9 7.9 6.8
10 7/1.35 6.1 114 1.83 1 1.4 71 63 4.7 4.7 4
16 7/1.70 7.2 171 1.15 1.6 2.3 95 85 2.9 2.9 2.5
25 7/2.14 8.4 250 0.727 2.5 3.6 126 111 1.85 1.9 1.65
35 comp.* 9.5 350 0.524 3.5 5 156 138 1.35 1.35 1.15
50 comp.* 11.3 470 0.387 5 7.2 189 168 0.99 1.05 0.9
70 comp.* 12.6 670 0.268 7 10 240 214 0.68 0.75 0.65
95 comp.* 14.7 930 0.193 9.5 13.6 290 259 0.49 0.58 0.5
120 comp.* 16.2 1160 0.153 12 17.2 336 299 0.39 0.48 0.42
150 comp.* 18.1 1430 0.124 15 21.5 375 328 0.32 0.43 0.37
185 comp.* 20.2 1790 0.0991 18.5 26.5 426 370 0.25 0.37 0.32
240 comp.* 22.9 2350 0.0754 24 34.3 500 433 0.19 0.33 0.29
300 comp.* 27 3030 0.0601 30 42.9 573 493 0.155 0.31 0.27
400 comp.* 32 4010 0.047 40 57.2 683 584 0.12 0.29 0.25
500 comp.* 35.5 5020 0.0366 50 71.6 783 666 0.093 0.28 0.24
630 comp.* 39.5 6440 0.0283 63 90.2 900 764 0.072 0.27 0.23
Ambient Temperature °C 25 30 35 40 45 50 55 60
Rating Factor 1.02 1.00 0.96 0.91 0.87 0.82 0.76 0.71
Temperature Rating Factors
Correction factors for Groupings
Number of circuits 2 3 4 5 6 7 8 9
Rating Factor 0.80 0.70 0.65 0.60 0.57 0.54 0.52 0.50
* Compressed stranded conducts
LSOH Conduit Wire(HO7Z-R)
kg/km
> Suitable for fi xed installation in dry or damp premises on walls, boards or
trays, in channels or embedded in plaster particularly for situations in
which low emission smoke and acid gas is required in case of burning
LSOH Flat Wiring Cables with Bare CPC
Key Applications
LSOH Wiring CablesLow Voltage (300/500 V)
6242B, 6243B
Cable Approvals Cable approved to BS7211
> Plain annealed copper solid (1.0 - 2.5mm²) or stranded (4.0 - 16.0mm²)
circular conductor complying with BS EN 60228 Class 1 or Class 2
> LSOH 90°C cross-linked insulation
Core Identifi cation
Insulation
Conductor
Prysmian Cables & Systems Limited, Sales Offi ce, Chickenhall Lane, Eastleigh, Hants, SO50 6YU, UK
Commercial Enquiries, Tel +44 (0) 8457 678 345, Fax: +44 (0) 23 8029 5465
www.prysmian.co.uk
TemperatureRange
-25 to +90°C
Bending RadiusFixed r=4D (minor
axis)
MechanicalImpactMedium
Fire PerformanceBS EN 60332-1-2
FlexibilityRigid
> LSOH Sheath complying with BS7655 Type LTS2
> Colour - white
o o o brown-CPC-blue
o o o o brown-black-CPC-grrey
Sheath
Ref:6242B/05/06
Low Smoke Emissions
BS EN 50268-2
Halogen FreeBS EN 50267-2-1
Cable Details
Prysmian Cables & Systems Limited, Sales Offi ce, Chickenhall Lane, Eastleigh, Hants, SO50 6YU, UK
Commercial Enquiries, Tel +44 (0) 8457 678 345, Fax: +44 (0) 23 8029 5465
www.prysmian.co.uk
Nominalcross
sectional area
phase/ CPC
mm²
Approx.overall
diameter
mm
Approximatecable
weight
kg/km
Maximumconductorresistance
at 20°C
Ohms/km
Short circuit
rating of conductor
(1 sec)
kA
Current rating Volt drop DC or single
phase AC
mV/A/m
Volt drop three
phase AC
mV/A/m
DC or Single
phase AC clipped direct
Amps
DC or Single
phase AC enclosed
in conduit or trunking
Amps
Three phase AC clipped direct
Amps
6242B Two core + CPC
1.0 / 1.0 4.5 x 8.2 70 18.1 0.14 19 17 - 46 -1.5 / 1.0 4.7 x 8.6 82 12.1 0.22 24 22 - 31 -2.5 / 1.5 5.3 x 9.9 115 7.41 0.36 33 30 - 19 -4.0 / 1.5 6.1 x 11.4 155 4.61 0.57 45 40 - 12 -6.0 / 2.5 6.8 x 13.1 216 3.8 0.85 58 51 - 7.9 -10.0 / 4.0 8.4 x 16.8 380 1.83 1.43 80 69 - 4.7 -16.0 / 6.0 9.6 x 19.5 560 1.15 2.28 107 91 - 2.9 -
6243B Three core + CPC1.0 / 1.0 4.5 x 10.7 94 18.1 0.14 19 17 17 46 401.5 / 1.0 4.7 x 11.4 112 12.1 0.22 24 22 22 31 272.5 / 1.5 5.3 x 12.8 152 7.41 0.36 33 30 30 19 16
Ambient Temperature°C 25 30 35 40 45 50 55 60Rating Factor 1.02 1.00 0.96 0.91 0.87 0.82 0.76 0.71
Temperature rating factors
Ref:6242B/05/06
Note: Where conductor operates at a temperature exceeding 70°C is shall be ascertained that the equipment connected to the conductor is suitable for the conductor operating temperature.
LSOH Flat Wiring Cables with Bare CPC
PRODUCT DATASHEET & APPLICATIONS GUIDE
KEY BENEFITS:
AFUMEX LSX
BS8436
LOW SMOKE ZERO HALOGEN SCREENED WIRING CABLES
TM
● BASEC approved for the full size range of BS8436 (1.0mm2 to 2.5mm2)
● Additionally tested for 600/1000 V rating by BASEC, certificate available uponrequest
● Suitable for use in thin walls and partitions as per clause 522.6 ofthe 17th Edition IEE Wiring Regulations (1.0mm2 to 2.5mm2)
● Independently assessed by ERA for nail penetration tests (1.0mm2 to 2.5mm2)
● Full 360° metal screen aids EMC compliance
● Low smoke emissions to BS EN 61034-2
● Acidic gas emission to BS EN 50267-2-1 (less than 0.5% acid gas)
● Reduced flame propagation to BS EN 60332-3-24
BASEC
APPROVED
AFUMEX LSX with EARTHSHIELD
Safety Screen Technology
AFUMEX Wiring Cables
TemperatureRange
-20 to +90°C
Bending RadiusCircular conductor r=6D
Mechanical ImpactMedium
Fire PerformanceBS EN 60332-1-2BS EN 60332-3-24
FlexibilityRigid
Halogen FreeBS EN 50267-2-1BS EN 50267-2-3
Low Smoke Emissions
BS EN 61034-2
Core Identification
Insulation
Conductor
Robust thermoplastic LSOH sheath. Colour - White.Other colours are available to special order
Sheath
oo brown-blueooo brown-black-greyoooo blue-brown-black-grey
Laminated aluminium tape screen bonded to sheath and in contact with full size tinned annealed copper circuit protective conductor for 2, 3 & 4 core cables
Screen
Nail PenetrationBS 8436
Afumex LSX
BS 8436
The AFUMEX LSX™ range was developed to address the specific needs of modern building services. For small power and lighting circuits, AFUMEX LSX™ has many applications, including cables installed in thin walls and partitions.
AFUMEX LSX™ is robust in design yet light in weight allowing it to be used in many instances where traditionally a bulky armoured cable would be installed, often with considerable cost savings. The dressable construction offers a combination of rigidity and ease of bending which keeps its shape during installation.
>
>
>
>
Plain annealed copper solid or stranded (class 1 or 2) conductor
90°C cross linked XLPE insulation complying with BS7655 Type GP8
> >
>
TM
Key Features Easy to strip, terminate and gland
Easy to install for surface clipped, tray and basket installations, giving reduced installation costs
A robust screen that meets the nail penetration test given in BS 8436*
70°C operating and 250°C short circuit temperature
Approvals
Specifications *AFUMEX LSX™ screened wiring cables comply with BS 8436 for 1.0mm2 to 2.5mm2 and are additionally tested for 600/1000 V rating
AFUMEX LSX™ screened wiring cables are rated at 600/1000 V. (4mm2 and 6mm2)
Cable Characteristics
complying with BS EN 60228
TM
BASEC Approved to BS 8436 (1.0mm2 to 2.5mm2)
Nail Penetration: ERA verified and tested
Additionally tested for 600/1000 V rating
All Prysmian cables are manufactured under our ISO 9001 Quality System certified by BASEC.
*
Full size CPC conductor on 2, 3 and 4 core cables
Provides excellent resistance to ignition and flame spread and produces very low levels of smoke and virtually no acidic gases when burnt, safeguarding human life and protecting equipment
Dressable - retains shape when installed
Cable Details
AFUMEX LSXTM Screened Wiring Cables
Installation methods for current rating in accordance with BS7671/IEE Wiring Regulations.
The tabulated ratings are based upon a 30°C ambient temperature and 70°C operating temperature. For other ambient temperatures or where cables are grouped together, the appropriate rating factors should be applied.
These cables when connected to suitably rated equipment are capable of being operated at a conductor temperature of 90°C. If current ratings etc are required please contact us.
Cables installed in floors, ceilings, thin walls and partitions When BS8436 cable is used to comply with BS7671:2008 clause 522.6.5 (ii), or 522.6.6 (i), or 522.6.8 (i), not only are the requirements of BS7671 on current rating, voltage drop, grouping etc. to be met but the recommendation of BS8436 for current rating and protective devices should also be followed.
Only Type B circuit breakers conforming to BS EN 60898 or Type B RCBOs conforming to BS EN 61009-12 should be used. They shall also have a maximum let-through energy (I²t) not greater than 42000 A²s for 1.0mm² and 1.5mm² cable and 60000 A²s for 2.5mm² cables.
For 1.0mm² cable the largest rated circuit breaker that shall be used is 16 amps, and may be lower depending on how the cable is used and installed.For 1.5mm² cable the largest rated circuit breaker that shall be used is 20 amps, and may be lower depending on how the cable is used and installed.For 2.5mm² cable the largest rated circuit breaker that shall be used is 32 amps, and may be lower depending on how the cable is used and installed.
Nominal cross
sectional area
mm²
Conceptual construction
no./mm
Approx overall
diameter
mm
Approx cable
weight
kg/km
Max conductor
resistance at 20°C
ohms/km
Current rating DC or single phase AC enclosed
Amps
Current rating, DC or single phase AC clipped
direct
Amps
Current rating, DC or single phase
AC perforated tray
Amps
Current rating, three
phase AC perforated
tray
Amps
Volt drop DC or single
phase AC
mV/A/m
Volt drop three
phase AC
mV/A/m
AFUMEX LSX BS8436Two Core
1.0 1/1.13 8.0 80 18.1 13 15 17 - 44 -
1.5 7/0.53 9.5 100 12.1 16.5 19.5 22 - 29 -
2.5 7/0.67 10.5 140 7.41 23 27 30 - 18 -
Three Core
1.0 1/1.13 8.5 105 18.1 13 15 17 14.5 44 38
1.5 7/0.53 9.5 120 12.1 16.5 19.5 22 18.5 29 25
2.5 7/0.67 10.5 170 7.41 23 27 30 25 18 15
Four Core
1.0 1/1.13 9.0 125 18.1 13 15 17 14.5 44 38
1.5 7/0.53 10.5 155 12.1 16.5 19.5 22 18.5 29 25
2.5 7/0.67 11.5 200 7.41 23 27 30 25 18 15
AFUMEX LSX Two Core
4.0 7/0.85 12.0 190 4.61 30 36 40 - 11 -
6.0 7/1.04 13.0 260 3.08 38 46 51 - 7.3 -
Three Core
4.0 7/0.85 12.5 230 4.61 30 36 40 34 11 9.5
6.0 7/1.04 13.5 300 3.08 38 46 51 43 7.3 6.4
Four Core
4.0 7/0.85 13.5 280 4.61 30 36 40 34 11 9.5
6.0 7/1.04 15.5 370 3.08 38 46 51 43 7.3 6.4
Ambient Temperature °C 25 30 35 40 45 50 55 60
Rating Factor 1.03 1.00 0.94 0.87 0.79 0.71 0.61 0.50
Number of circuits 2 3 4 5 6 7 8 9
Rating Factor 0.80 0.70 0.65 0.60 0.57 0.54 0.52 0.50
Temperature Rating Factors
Correction Factors for Groupings (Free Air Touching)
TM
TM
AFUMEX LSXTM Applications GuideScreened Wiring Cables
● Suitable for surface wiring, direct burial in plaster, tray or other installations
AFUMEX LSX™ wiring cables are designed for power and lighting applications where a screened low smoke halogen free cable is required such as:
● IEE Wiring Regulations compliant cable for installation in thin walls and partitions (clause 522.6 of 17th Edition) (1.0mm2 to 2.5mm2)
● Lightweight replacement for armoured cable in cases where high level mechanical protection is not needed
● Fully screened cable for EMC compliance and clean power supply
● Robust alternative to surface mounted flat wiring cable
● Reduced flame propagation, low smoke halogen free fire performance for public access buildings
Key Applications
Installations ● Minimum recommended installation temperature 0°C
● Automatic earthing of the screen is achieved by termination of circuit protective conductor
● Suitable for indoor and outdoor installations in suitably protected environments
● For external exposure white sheathed cable is recommended
● Should be installed in accordance with BS7671/IEE Wiring Regulations or other appropriate national regulations
Cables Installed in Thin Walls and Partitions
AFUMEX LSX™ contains an earthed metallic screen, which is in contact with a full size, un-insulated circuit protective conductor.
This provides an earth fault path for the fault current if the cable is penetrated by a nail (or similar), and when connected to a suitably selected protective device offers electrical protection by this connection of the circuit.
This performance has been independently verified by nail penetration tests carried out by ERA.
Installation note: AFUMEX LSX™ cable combined with a suitable protective device provides a means of compliance with clause 522-6 of BS 7671:2008. AFUMEX LSX™ cable meets the
Total Installed Costs of LSX™ vs SWA Cable
AFUMEX LSX™ is lightweight and compact in design, allowing cost savings to be made by the selection of smaller, lighter fixings, supports and cable tray or basket. AFUMEX LSX™ is also quick to install and easily stripped, significantly reducing the first and second fix termination times when compared with SWA cable (Steel Wire Armoured).
Simple NYLON/LSOH glands may be used.
Installation note: A neat finish can be quickly and easily achieved. AFUMEX LSX™ is ideal for clipping direct to the metal frame structure of a pre-fabricated fast track building.
Weight & Diameter Comparison Accessory SelectionCable size
SWA is heavier by %
LSXTM is smaller by %
LSOH Cable Gland Product
Code
AP Clip Code
2x1.0 - - 251 AP7W
2x1.5 135 17 251 AP9W
2x2.5 128 19 252 AP10W
2x4 100 17 252 AP11W
2x6 109 17 254 AP12W
3x1.0 - - 251 AP8W
3x1.5 115 16 251 AP9W
3x2.5 103 19 252 AP10W
3x4 80 19 252 AP12W
3x6 80 15 254 AP13W
4x1.0 - - 251 AP9W
4x1.5 100 15 252 AP10W
4x2.5 96 21 252 AP11W
4x4 73 21 254 AP13W
4x6 50 12 254 AP15W
AFUMEX LSX™ is lighter in weight and smaller in diameter than 1 kV armoured cables
requirements of BS8436 (1.0mm2 to 2.5mm2).
AFUMEX LSXTM Applications GuideScreened Wiring Cables
Small Power - Ring Main & Radial Circuits
Installation Note: XLPE 90°C rated conductor gives higher current ratings and improved design options.
Ring main or radial circuit designs utilising optimum circuit breaker range.
EMC and Clean Power Supply
AFUMEX LSX™ has a full 360° metal screen, aiding EMC compliance throughout the run of the cable. The full 360° metal screen makes AFUMEX LSX™ ideally suited for clean power supply use.
Installation note: AFUMEX LSX™ cables can be grouped with limited cross talk between cables.
Lighting - HPS, Tungsten & Fluorescent
HPS, tungsten and fluorescent lighting for office, retail and domestic applications.
Installation note: AFUMEX LSX™ can be easily refitted to accommodate merchandising floor area changes, making it suitable for HIGH CHURN environments.
Fixed Applications
Air conditioning, fans, compressors, heaters and hand dryers etc.
Installation note: All cables include an un-insulated CPC equal in size to the phase conductor and in contact with the full 360° aluminium screen, which provides automatic screen earthing.
LSOH® Standard
AFUMEX LSX™ offers a pronounced effect on safety and a dramatic reduction in risk.
Installation note: AFUMEX LSX™ is part of the most comprehensive range of Low Fire Hazard cables available and has reduced flame propagation properties and offers significant improvements over standard cables in the event of a fire, preventing the spread of flames from one area to another.
Public Access Buildings Other Applications
● Point of sales equipment ● Ring mains power ● Clean Rooms ● Compressor supplies● Stadium floodlights ● Fan motor supplies● Air conditioning ● Temporary wiring requirements● Ventilation systems ● Hospitals
Availability● AFUMEX LSX™ cables can be obtained from all reputable UK wholesalers or Prysmian agents. We also hold stocks at our factory for immediate dispatch.
● The standard colour for AFUMEX LSX™ is white. Other colours can be supplied, such as black or purple to meet specific needs. A minimum order quantity may apply.
● Cable is usually supplied in 100 metre lengths. Other lengths can be made to special order.
A fire is bad enough, don’t make it worse
Minimise the risk with AFUMEX LSX™
Sales enquiriesTel: 0845 767 8345Fax: 023 8029 5465
UK Technical helplineTel: 023 8029 5222Fax: 023 8029 [email protected]
Prysmian Cables & Systems LimitedChickenhall LaneEastleighHampshireS050 6YUUnited Kingdom
www.prysmian.co.uk
Overseas Sales enquiresTel: +44 23 5029 5481Fax: +44 23 8029 5465
Overseas Technical helplineTel: +44 23 8029 5481Fax: +44 23 8029 5002
Information hotlineTel: +44 (0) 23 8029 5029Fax: +44 (0) 23 8029 [email protected]
Ref: AFU
MEXLSX/05/10
PiresafeTM FlexLSOH Flexible CablesLow Voltage (300/500 V)
> Plain annealed copper, flexible stranded circular conductor, complying
with BS EN 60228 Class 5
> LSOH insulation
Core Identification
Insulation
Conductor
Prysmian Cables & Systems Limited, Sales Office, Chickenhall Lane, Eastleigh, Hants, SO50 6YU, UK
Commercial Enquiries, Tel +44 (0) 8457 678 345, Fax: +44 (0) 23 8029 5465
www.prysmian.co.uk
> Flexible LSOH® sheath
> Colour - Normally white but other colours are available on request
Sheath
> Supply leads for medium duty domestic and office appliances, lighting
fittings and portable appliances . Used in a wide range of public access
buildings and industrial complexes where improved public safety and
environmental control are desirable
Ref: PiresafeFlex/11/09
Key Applications
oo blue-brownoo blue-brown-green/yellowooo brown-black-grey-green/yellow
TemperatureRange
-15 to +70°C
Bending RadiusFixed r=4D
Flexing r=6D
Mechanical ImpactMedium
Fire PerformanceBS EN 60332-1-2
FlexibilityFlexible
Halogen FreeBS EN 50267-2-1
Low smoke emissionsBS EN 61034-2
3182B, 3183B, 3184B
> Piresafe Flex is a flexible cable, which when burnt produces very low
quantities of smoke and virtually no acidic gases thus safeguarding
human life and protecting equipment
> All Prysmian cables are manufactured under an ISO 9001 Quality
System certified by BASEC
Key Features
oooo oooo
Prysmian Cables & Systems Limited, Sales Office, Chickenhall Lane, Eastleigh, Hants, SO50 6YU, UK
Commercial Enquiries, Tel +44 (0) 8457 678 345, Fax: +44 (0) 23 8029 5465
www.prysmian.co.uk
Cable Details
Nominalcross
sectionalarea
mm²
Conceptualconstruction
no./mm
Approximateconductordiameter
mm²
Nominaloverall
diameter
mm
Approximatecable
weight
kg/km
Minimumbendingradius
(Flexing)
mm
Maximumconductorresistance
at 20°C
ohms/km
Currentrating DC
orsingle
phase AC
Amps
Volt drop DCor single
phaseAC
mV/A/m
Currentrating threephase
AC
Amps
Volt dropthreephase
AC
mV/A/m
Two Core
0.75 24/0.20 1.14 6.2 59 40 26.0 6 62 - -
1.0 32/0.20 1.32 6.6 67 40 19.5 10 46 - -
1.5 30/0.25 1.6 7.6 90 45 13.3 16 32 - -
2.5 50/0.25 2.05 9.1 141 55 7.98 25 19 - -
Three Core
0.75 24/0.20 1.14 6.6 69 40 26.0 6 62 - -
1.0 32/0.20 1.32 7 80 45 19.5 10 46 - -
1.5 30/0.25 1.6 8.2 113 50 13.3 16 32 - -
2.5 50/0.25 2.05 9.8 176 60 7.98 25 19 - -
Four Core
0.75 24/0.20 1.14 7.0 83 45 26.0 6 62 6 54
1.0 32/0.20 1.32 7.8 101 50 19.5 10 46 10 40
1.5 30/0.25 1.6 9.2 141 55 13.3 16 32 16 27
2.5 50/0.25 2.05 10.8 214 80 7.98 25 19 20 16
Ambient Temperature °C 30 35 40 45 50 55
Rating factor 1.00 0.91 0.82 0.71 0.58 0.41
Temperature rating factors
PiresafeTM Flex
Ref: PiresafeFlex/11/09
> Installation in surface mounted or embedded conduits or similar closed
systems and for fi xed protected installation in or on lighting fi ttings and
inside appliances, switchgear and control gear
> Green/Yellow for use as earth
PVC Conduit Wire(H07V - U, H07V - R)
Key Applications
Ref: 6491X/04/06
Standard Wiring CablesLow Voltage (450/750 V)
6491X
Cable Approvals Cable approved to BS6004
TemperatureRange
-15 to +70°C
BendingRadius
Fixed r=6D
MechanicalImpactMedium
Fire PerformanceBS EN 60332-1-2
FlexibiltyRigid
> Plain annealed copper solid or stranded circular conductor complying with
BS EN 60228 Class 1 or Class 2
o Greyo Blacko Blueo Yellowo Browno o White
Green/Yellow
> PVC Insulation complying with BS EN 50363-3 Type Tl1
Core Identifi cation
Insulation
Conductor
Prysmian Cables & Systems Limited, Sales Offi ce, Chickenhall Lane, Eastleigh, Hants, SO50 6YU, UK
Commercial Enquiries, Tel +44 (0) 8457 678 345, Fax: +44 (0) 23 8029 5465
www.prysmian.co.uk
Cable Details
Ref: 6491X/04/06
Nominalcross
sectional area
mm²
Approximate overall
diameter
mm
Approximate cable weight
Kg/Km
Maximum conductor resistance at 20°C
Ohms/km
Short circuit rating (1 sec)
KA
Current rating DC or single phase AC enclosed
in conduit or
trunkingAmps
Current rating Three
phase AC enclosed
in conduit or
trunkingAmps
Voltage drop DC
mV/A/m
Voltage drop DCsingle phase
mV/A/m
Voltage drop three
phase AC
mV/A/m
H07V-U (Solid conductor)
1.5 3.0 21 12.1 0.17 17.5 15.5 29 29 25
2.5 3.6 32 7.41 0.28 24 21 18 18 15
H07V-R (Stranded conductor)
1.5 3.0 23 12.1 0.17 17.5 15.5 29 29 25
2.5 3.6 35 7.41 0.28 24 21 18 18 15
4 4.2 51 4.61 0.46 32 28 11 11 9.5
6 4.7 71 3.08 0.69 41 36 7.3 7.3 6.4
10 6.1 120 1.83 1.15 57 50 4.4 4.4 3.8
16 7.2 180 1.15 1.84 76 68 2.8 2.8 2.4
25 8.4 280 0.727 2.88 101 89 1.75 1.8 1.55
35 9.5 380 0.524 4.00 125 110 1.25 1.3 1.1
50 11.3 490 0.387 5.75 151 134 0.93 1.0 0.85
70 12.6 710 0.268 8.00 192 171 0.63 0.72 0.61
95 14.7 980 0.193 10.9 232 207 0.46 0.56 0.48
120 16.2 1210 0.153 13.8 269 239 0.36 0.47 0.41
150 18.1 1510 0.124 17.3 300 262 0.29 0.41 0.36
185 20.2 1900 0.0991 21.3 341 296 0.23 0.37 0.32
240 22.9 2490 0.0754 27.6 400 346 0.18 0.33 0.29
300 27.0 3050 0.0601 34.5 458 394 0.145 0.31 0.27
400 32.0 3900 0.047 41.1 546 467 0.105 0.29 0.25
Ambient Temperature °C 25 30 35 40 45 50 55 60 65
Rating Factor 1.03 1.00 0.94 0.87 0.79 0.71 0.61 0.50 0.35
Temperature Rating Factors
Number of Circuits 2 3 4 5 6 7 8 9 10 12 14 16 18 20
Rating Factor 0.80 0.70 0.65 0.60 0.57 0.54 0.52 0.50 0.48 0.45 0.43 0.41 0.39 0.38
Correction factors for Groupings
Prysmian Cables & Systems Limited, Sales Offi ce, Chickenhall Lane, Eastleigh, Hants, SO50 6YU, UK
Commercial Enquiries, Tel +44 (0) 8457 678 345, Fax: +44 (0) 23 8029 5465
www.prysmian.co.uk
PVC Conduit Wire(H07V - U, H07V - R)
> Fixed installation in dry or damp premises on walls, boards or trays, in
channels or embedded in plaster
PVC Flat Wiring Cables with Bare CPC
Key Applications
Standard Power CablesLow Voltage (300/500 V)
6241Y, 6242Y, 6243Y
Cable Approvals Cable approved to BS6004
> Plain annealed copper solid (1.0 - 2.5mm²) or stranded (4.0 - 16.0mm²)
circular conductor complying with BS EN 60228 Class 1 or Class 2
> PVC Insulation complying with BS EN 50363-3 Type Tl1
Core Identifi cation
Insulation
Conductor
Prysmian Cables & Systems Limited, Sales Offi ce, Chickenhall Lane, Eastleigh, Hants, SO50 6YU, UK
Commercial Enquiries, Tel +44 (0) 8457 678 345, Fax: +44 (0) 23 8029 5465
www.prysmian.co.uk
TemperatureRange
-15 to +70°C
Bending RadiusFixed r=4D(minor axis)
MechanicalImpactMedium
Fire PerformanceBS EN 60332-1-2
FlexibilityRigid
> PVC Sheath complying with BS7655 Type 6
> Colour - grey
o o o brown-CPC-blue
o o o o brown-black-CPC-grrey
Sheath
Ref:6242Y/05/06
Cable Details
Prysmian Cables & Systems Limited, Sales Offi ce, Chickenhall Lane, Eastleigh, Hants, SO50 6YU, UK
Commercial Enquiries, Tel +44 (0) 8457 678 345, Fax: +44 (0) 23 8029 5465
www.prysmian.co.uk
Nominalcross
sectional area/ CPC
mm²
Approx.overall
diameter
mm
Approximatecable
weight
kg/km
Maximumconductorresistance
at 20°C
Ohms/km
Short circuit
rating of conductor
(1 sec)
kA
Current rating Volt drop DC or single
phase AC
mV/A/m
Volt drop three
phase AC
mV/A/m
DC or Single
phase AC clipped direct
Amps
DC or Single phase AC enclosed
in conduit in an insulated
wallAmps
Three phase AC clipped direct
Amps
Single Core
1.0 / 1.0 4.5 x 5.6 41 18.1 0.12 16 11.5 13.5 44 381.5 / 1.0 4.7 x 5.8 49 12.1 0.17 20 14.5 17.5 29 25
Two Core1.0 / 1.0 4.5 x 8.2 68 18.1 0.12 16 11.5 - 44 -1.5 / 1.0 4.7 x 8.6 85 12.1 0.17 20 14.5 - 29 -2.5 / 1.5 5.3 x 9.9 124 7.41 0.28 27 20 - 18 -4.0 / 1.5 6.1 x 11.4 172 4.61 0.46 37 26 - 11 -6.0 / 2.5 6.8 x 13.1 238 3.08 0.69 47 32 - 7.3 -10 / 4.0 8.4 x 16.8 390 1.83 1.15 64 44 - 4.4 -16 / 6.0 9.6 x 19.5 575 1.15 1.84 85 57 - 2.8 -
Three Core1.0 / 1.0 4.5 x 10.7 95 18.1 0.12 16 11.5 13.5 44 381.5 / 1.0 4.7 x 11.7 115 12.1 0.17 20 14.5 17.5 29 252.5 / 1.5 5.3 x 12.8 170 7.41 0.28 27 20 24 18 154.0 / 1.5 6.4 x 16.0 155 4.61 0.46 37 26 32 11 9.56.0 / 2.5 7.0 x 18.1 340 3.08 0.69 47 32 41 7.3 6.410 / 4.0 8.3 x 22.5 550 1.83 1.15 64 44 57 4.4 3.816 / 6.0 9.5 x 26.3 790 1.15 1.84 85 57 76 2.8 2.4
Ambient Temperature°C 25 30 35 40 45 50 55 60Rating Factor 1.03 1.00 0.94 0.87 0.79 0.71 0.61 0.50
Temperature rating factors
Ref:6242Y/05/06
PVC Flat Wiring Cables with Bare CPC
> Fixed installation in dry or damp premises on walls, boards or trays, in
channels or embedded in plaster
PVC Insulated Sheathed Single Core
Key Applications
Standard Wiring CablesLow Voltage (300/500 V)
6181Y
Cable Approvals Cable approved to BS6004
> Plain annealed copper solid (1.0 - 2.5mm²) or stranded (4.0 - 35.0mm²)
circular conductor complying with BS EN 60228 Class 1 or Class 2
> PVC Insulation complying with BS EN 50363-3 Type Tl1
Core Identifi cation
Insulation
Conductor
Prysmian Cables & Systems Limited, Sales Offi ce, Chickenhall Lane, Eastleigh, Hants, SO50 6YU, UK
Commercial Enquiries, Tel +44 (0) 8457 678 345, Fax: +44 (0) 23 8029 5465
www.prysmian.co.uk
TemperatureRange
-15 to +70°C
Bending RadiusFixed r=4D
MechanicalImpactMedium
Fire PerformanceBS EN 60332-1-2
FlexibilityRigid
> PVC Sheath complying with BS7655 Type 6
> Normally grey but others available on request
o redo black o blueo brown
Sheath
Ref:6181Y/05/06
Cable Details
Prysmian Cables & Systems Limited, Sales Offi ce, Chickenhall Lane, Eastleigh, Hants, SO50 6YU, UK
Commercial Enquiries, Tel +44 (0) 8457 678 345, Fax: +44 (0) 23 8029 5465
www.prysmian.co.uk
Nominalcross
sectional area
mm²
Approx.overall
diameter
mm
Approximatecable
weight
kg/km
Maximumconductorresistance
at 20°C
Ohms/km
Short circuitrating(1 sec)
kA
Current Rating Volt drop DC or single
phase AC
mV/A/m
Volt drop three
phase AC
mV/A/m
DC or Single
phase AC enclosed
in conduit or trunking
Amps
DC or Single
phase AC clipped direct
Amps
Three phase AC clipped direct
Amps
1.0 4.2 28 18.1 0.12 13.5 15.5 14 44 381.5 4.6 36 12.1 0.17 17.5 20 18 29 252.5 5.3 50 7.41 0.28 24 27 25 18 154.0 6.1 75 4.61 0.46 32 37 33 11 9.56.0 6.7 98 3.08 0.69 41 47 43 7.3 6.410 8 155 1.83 1.15 57 65 59 4.4 3.816 9.5 232 1.15 1.84 76 87 79 2.8 2.425 11.3 338 0.727 2.88 101 114 104 1.75 1.635 12.3 442 0.524 4.00 125 141 129 1.25 1.1
Ambient Temperature °C 25 30 35 40 45 50 55 60Rating Factor 1.03 1.00 0.94 0.87 0.79 0.71 0.61 0.50
Temperature rating factors
Ref:6181Y/05/06
Number of Circuits 2 3 4 5 6 7 8 9Rating Factor 0.8 0.7 0.65 0.6 0.57 0.54 0.52 0.5
Correction Factors for Groupings
PVC Insulated Sheathed Single Core